FORM NO. G11-448 REV. 9
Supersedes Form No. G11-448 Rev. 8
GAS FURNACES
RGPH- SERIES
Models with Input Rates from
50,000 to 150,000 BTU/HR
[13 to 44 kW]
(U.S. & Canadian Models)
CRITERION
®
II
80.0%–81.7% A.F.U.E.
✝
UPFLOW/
HORIZONTAL
GAS FURNACES
II line of upflow/horizontal gas furThe Rheem ® Criterion ® naces are designed for utility rooms, closets, alcoves, or attics. Because of the Criterion’s low-profile 34 inch
[864 mm] height, the upflow model can also be used to satisfy most applications that traditionally call for a horizontal furnace.
The design is certified by CSA.
■
Features
Patented Heat Exchanger, constructed of both stainless and aluminized steel for the maximum in corrosion resistance.
■
■
■
■
■
■
■
■
Low profile “34 inch” design is lighter and easier to handle, and leaves room for optional equipment.
Convertible from upflow to horizontal left or right without field conversion.
Left or right side gas and electric inlet connections with quick, simple change.
Direct spark ignition models utilize remote sense and feature an integrated board with humidifier and electronic air cleaner hookups.
Insulated blower compartment helps to reduce jacket loss and noise.
Pre-paint galvanized steel cabinet.
Molded permanent filter.
Grab-holes in doors to aid in easy door removal and replacement.
A variety of cooling coils and plenums designed to use with
Rheem Criterion II gas furnaces are available as optional accessories.
These furnaces can be installed in an upflow position or laid on either side in a horizontal position. No field converting required.
✝A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with Department of
Energy test procedures.
RHEEM CRITERION II 80%
UPFLOW/HORIZONTAL GAS FURNACE
Heat Exchanger Draft Inducer Motor
In-Shot Burners
Direct Spark Ignitor with Remote Sense
Integrated
Furnace
Control
2
STANDARD EQUIPMENT
Completely assembled and wired; induced draft blower; pressure switch; redundant main gas control; blower compartment door safety switch; solid state time on/time off blower control; limit control; manual shut-off valve, pressure regulator for natural and L.P. (propane) gas; transformer; direct drive multi-speed blower motor. Furnaces are equipped with cooling/heating relay and transformer (40VA) ready for air conditioning applications. (Please note: a thermostat is not included as standard equipment.) Flame sensor diagnostics;
on-board twinning options; fused transformer (secondary), 3rd speed fan option for continuous fan; common heat/cool terminal.
OPTIONAL EQUIPMENT
Side filter frame assembly. Return air cabinet for all sizes. (See Page 6)
NOTE: Furnace is not listed for use with fuels other than natural or L.P.
(propane) gas.
Rheem Manufacturing Company
Molded
Permanent Filter
The complete terms of limited and other warranties are available at our sales office, or through local installer.
All models can be converted by a qualified Rheem distributor or local service dealer to use L.P. (propane) gas without changing burners. Factory approved kits must be used to convert from natural to L.P. (propane) gas and may be ordered as optional accessories from a Rheem parts distributor.
For L.P. (propane) operation, refer to Conversion Kit Index Form.
WARNING
THIS FURNACE IS NOT APPROVED
OR RECOMMENDED
FOR USE IN MOBILE HOMES
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE
FROM YOUR RETAILER.
PHYSICAL DATA AND SPECIFICATIONS
U.S. AND CANADA MODELS (UPFLOW/HORIZONTAL)
MODEL NUMBERS
RGPH- SERIES
05EAUER
05NAUER
07EAUER
07NAUER
07EAMGR
07NAMGR
10EAMER
10NAMER
10EBRJR
10NBRJR
12EARJR
12NARJR
Input-BTU/Hr [kW] ➁
Heating Capacity BTU/Hr [kW] ➀
High Altitude Input [kW]*
High Altitude Output
Capacity [kW]*
Heat Ext. Static Pressure [kPa]
Blower (D x W) [mm]
Motor H.P.–Speeds–
PSC Type [W]
Motor Full Load Amps
Heating Speed
Cooling Speed
Cooling CFM @ .5" [kPa] E.S.P.
(Nominal) [L/s]
Rated E.S.P. (In. W.C.) [kPa]
Temperature Rise Range °F
[°C]
Max. Outlet Air Temp. °F
[°C]
Standard Filter–In.
[mm]
Approx. Shipping Weight (Lbs.)
[kg]
Return Air Cabinets
(Opt.) RXGR-
Filter Size [mm]
50,000 [15]
41,000 [12]
45,000 [13]
36,500 [11]
.10 [.025]
11 x 6
[279 x 152]
1 /
2
-4-PSC
[373]
6.8
MED-LOW
HIGH
1200
[566]
.50 [.12]
25-55
[13.9-30.6]
155
[68.3]
15 3 /
4 x 25
[400 x 635]
85
[39]
C14B
(2) 12 x 16
[305 x 406]
81.4%
75,000 [22]
60,000 [18]
67,500 [20]
53,500 [16]
.12 [.029]
11 x 6
[279 x 152]
1 /
2
-4-PSC
[373]
7.1
MED-HIGH
HIGH
1200
[566]
.50 [.12]
40-70
[22.2-38.9]
165
[73.8]
15 3 /
4 x 25
[400 x 635]
105
[48]
C17B
(2) 12 x 16
[305 x 406]
80.6%
75,000 [22]
60,000 [18]
67,500 [20]
54,000 [16]
.12 [.029]
11 x 7
[279 x 178]
3 /
4
-4-PSC
[559]
9.5
MED-LOW
MED-HIGH
1600
[755]
.50 [.12]
25-55
[13.9-30.6]
155
[68.3]
15 3 /
4 x 25
[400 x 635]
105
[48]
C17B
(2) 12 x 16
[305 x 406]
80.5%
100,000 [29]
80,000 [23.4]
90,000 [26]
72,000 [21]
.15 [.037]
11 x 7
[279 x 178]
1 /
2
-4-PSC
[373]
7.1
MED-HIGH
HIGH
1200
[566]
.50 [.12]
50-80
[27.8-44.4]
190
[87.7]
15 3 /
4 x 25
[400 x 635]
115
[52]
C17B
(2) 12 x 16
[305 x 406]
80.0%
100,000 [29]
81,000 [23.7]
90,000 [26]
72,500 [21]
.15 [.037]
11 x 10
[279 x 254]
3 /
4
-4-PSC
[559]
9.5
MED-LOW
MED-HIGH
2000
[944]
.50 [.12]
40-70
[22.2-38.9]
170
[76.6]
19 1 /
4 x 25
[489 x 635]
120
[54]
C21B
(2) 20 x 16
[508 x 406]
80.0%
125,000 [37]
99,000 [29]
112,500 [33]
89,000 [26.1]
.20 [.05]
11 x 10
[279 x 254]
3 /
4
-4-PSC
[559]
9.5
MED-LOW
MED-HIGH
2000
[944]
.50 [.12]
35-65
[19.4-36.1]
180
[82.2]
22 3 /
4 x 25
[578 x 635]
140
[63]
C24B
(2) 24 x 16
[610 x 406]
80.0% AFUE–Electric Ignition Models ➀
California Seasonal Efficiency–
Electric Ignition/No x
Models
74.9/75.4
74.9/75.4
74.7/75.3
75.4/75.4
73.9/74.5
74.2/74.2
NOTES: All models are 115V, 60HZ, 1Ø. Gas connection size for all models is 1 /
2
" [12.7 mm] N.P.T.
➀ In accordance with D.O.E. test procedures.
➁ See Conversion Kit Index Form No. 92-21519-52 for U.S. models and Form No. 92-21519-53 for Canadian models for high altitude derate.
* Data references Canadian Models only.
15EARJR
15NARJR
150,000 [44]
119,000 [35]
135,000 [39.6]
107,500 [31.5]
.20 [.05]
11 x 10
[279 x 254]
3 /
4
-4-PSC
[559]
9.5
MED-LOW
MED-HIGH
2000
[944]
.50 [.12]
50-80
[27.8-44.4]
190
[87.7]
22 3 /
4 x 25
[578 x 635]
150
[68]
C24B
(2) 24 x 16
[610 x 406]
80.0%
74.7/74.7
MODEL IDENTIFICATION—UPFLOW MODELS
R G P H
Rheem Gas Upflow/ Design
Furnace Horizontal Series
— 07E A U E R
Electric
Ignition
05E
07E
10E
12E
15E
Heating Input Designation
NOx
Model
Input
BTU/HR
05N
07N
10N
12N
15N
50,000 [15 kW]
75,000 [22 kW]
100,000 [29 kW]
125,000 [37 kW]
150,000 [44 kW]
Variations
A = Std.
Cabinet
B = Wide
Cabinet
Blower
Designation
U = 11 x 6
[279 x 152 mm]
M = 11 x 7
[279 x 178 mm]
R = 11 x 10
[279 x 254 mm]
Heating & Cooling
Designation
S = 500-1200 CFM
[236-566 L/s]
E = 1100-1330 CFM
[519-628 L/s]
G = 1450-1750 CFM
[684-826 L/s]
J = 1800-2075 CFM
[850-979 L/s]
Fuel Type
R = Natural Gas,
U.S. and
Canadian
Standard
Furnace
[ ] Designates Metric Conversions
Rheem Manufacturing Company 3
UPFLOW DIMENSIONS
TABLE 1. DIMENSIONS AND CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES) [mm]
MODEL
RGPH-
05
07
10 (A)
10 (B)
12
15
14 [356]
17 1 /
2
[445]
17 1 /
2
[445]
21 [533]
24
24
1
1
/
/
2
2
A
[622]
[622]
23
23
11
11
/
/
B
12 27 /
32
[326]
16 11 /
32
[415]
16 11 /
32
[415]
19 27 /
32
[504]
32
32
[593]
[593]
C D E
10 3 /
8
[263] ➀ 11 1 /
2
[292]
12 1 /
8
[308] ➀ 15 [381]
12 1 /
8
[308] ➀ 15 [381]
13 7 /
8
[352] ➀ 18 1 /
2
[470]
15 5 /
8
[397] ➀ 22 [559]
15 5 /
8
[397] ➀ 22 [559]
LEFT
SIDE
0
0
0
0
0
0
RIGHT
SIDE
4 [102] ➁
3 [76] ➁
3 [76] ➁
0
0
0
REDUCED CLEARANCES (IN.) [mm]
BACK
0
0
0
0
0
0
TOP FRONT VENT
1 [25] 3 [76] 6 [152] ➂
1 [25] 3 [76] 6 [152] ➂
1 [25] 3 [76] 6 [152] ➂
1 [25] 3 [76] 6 [152] ➂
1 [25] 3 [76] 6 [152] ➂
1 [25] 3 [76] 6 [152] ➂
SHIP. WGTS.
(LBS.) [kg]
85 [38.6]
105 [47.6]
115 [52.2]
120 [54.4]
140 [63.5]
150
NOTES: ➀ May require a 3" [76 mm] to 4" [102 mm] or 3" [76 mm] to 5" [127 mm] adapter.
➁ May be 0" [0 mm] with type B vent.
➂ May be 1" [25 mm] with type B vent.
Furnaces must be vented in accordance with ANSI Z21.47-1993 • CAN/CGA-2.3-M93 venting table guidelines and in accordance with local codes.
[68]
[ ] Designates Metric Conversions
4 Rheem Manufacturing Company
HORIZONTAL DIMENSIONS
WA R N I N G
THIS FURNACE IS NOT APPROVED
OR RECOMMENDED FOR INSTALLATION
ON ITS BACK, WITH ACCESS DOORS
FACING UPWARDS.
TABLE 1. DIMENSIONS AND CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES) [mm]
RIGHT
SIDE
4 [102] ➁
3 [76] ➁
3 [76] ➁
0
0
0
REDUCED CLEARANCES (IN.) [mm]
MODEL
RGPH-
05
07
10 (A)
10 (B)
12
15
14
17
17
21
24
24
1
1
1
1
/
/
/
/
2
2
2
2
A
[356]
[445]
[445]
[533]
[622]
[622]
12
16
16
19
23
23
27
11
11
27
11
11
/
/
/
/
/
/
B
32
32
32
32
32
32
[326]
[415]
[415]
[504]
[593]
[593]
10
12
12
13
15
15
3
1
1
7
5
5
/
/
/
/
/
/
8
8
8
8
8
8
C
[263]
[308]
[308]
[352]
[397]
[397]
D
➀
➀
➀
➀
➀
➀
11
15
15
18
22
22
1
1
/
/
2
2
E
[292]
[381]
[381]
[470]
[559]
[559]
LEFT
SIDE
0
0
0
0
0
0
BACK
0
0
0
0
0
0
TOP FRONT VENT
1 [25] 3 [76] 6 [152] ➂
1 [25] 3 [76] 6 [152] ➂
1 [25] 3 [76] 6 [152] ➂
1 [25] 3 [76] 6 [152] ➂
1 [25] 3 [76] 6 [152] ➂
1 [25] 3 [76] 6 [152] ➂
NOTES: ➀ May require a 3" [76 mm] to 4" [102 mm] or 3" [76 mm] to 5" [127 mm] adapter.
➁ May be 0" [0 mm] with type B vent.
➂ May be 1" [25 mm] with type B vent.
Furnaces must be vented in accordance with ANSI Z21.47-1993 • CAN/CGA-2.3-M93 venting table guidelines and in accordance with local codes.
SHIP. WGTS.
(LBS.) [kg]
85 [38.6]
105 [47.6]
115 [52.2]
120 [54.4]
140 [63.5]
150 [68]
[ ] Designates Metric Conversions
Rheem Manufacturing Company 5
ACCESSORIES—UPFLOW
PLENUM DATA FOR “A” COILS
Plenum adapters are required in some instances for use on upflow applications when plenum and furnace size do not match.
FURNACE
WIDTH
IN. [mm]
14 [356]
14 [356]
17 1 /
2
[445]
17 1 /
2
[445]
17 1 /
2
[445]
17 1 /
2
[445]
21 [533]
21 [533]
21 [533]
24 1 /
2
[622]
24 1 /
2
[622]
PLENUM
WIDTH
IN. [mm]
16 1 /
4
[413]
20 1 /
4
[514]
16 1 /
4
[413]
20 1 /
4
[514]
21 5 /
8
[549]
25 1 /
4
[641]
25 1 /
4
[641]
22 1 /
4
[565]
21 5 /
8
[549]
25 1 /
4
[641]
21 5 /
8
[549]
PLENUM ADAPTER
UPFLOW
RXAA-C171
RXAA-C172
RXAA-C185
RXAA-C173
RXAA-C187
RXAA-C174
RXAA-C175
RXAA-C176
RXAA-C188
RXAA-C177
RXAA-C187
COIL
PLENUM
RXAL-B16BU
RXAL-B20BU
RXAL-B16BU
RXAL-B20BU
RXAL-B21BU
RXAL-B25BU
RXAL-B25BU
RXAL-B22BU
RXAL-B21BU
RXAL-B25BU
RXAL-B21BU
Note: See Form Number C11-206 for MultiFlex coil data.
OPTION CODE FOR HIGH ALTITUDE: US-277
Canada-298
(U.S. Models—Kit packaged with furnace.
Requires field installation.)
EXTERNAL BOTTOM FILTER RACK: RXGF-CB
FILTER RACK FILTER SIZES† INCHES [mm]
MODEL
RGPH-
RXGF-CA
(SIDE)
05, 07, 10*A
10*BRJ
12, 15
15 3 /
4 x 25
[400 x 635]
15 3 /
4 x 25
[400 x 635]
15 3 /
4 x 25
[400 x 635]
† Filter racks are shipped without filters.
Filters shipped with furnace may be used or a suitable 1" [25.4 mm] filter.
*Designates “E” or “N”.
RXPF-F01 and F02
FOSSIL FUEL KITS are for use with Rheem Heat Pumps and Criterion II warm air furnaces. The RXPF-F02 meets TVA requirements.
ACCESSORY RETURN
AIR CABINETS
Return Air Cabinets may be installed on rear or either side application except RXGR-C24B
(side application must be on side opposite gas and electrical connections).
THE RXGR-C24B MAY ONLY BE INSTALLED
ON REAR AND LEFT SIDES.
RETURN AIR CABINETS
RXGR-C14B
RXGR-C17B
RXGR-C21B
RXGR-C24B
A
IN. [mm]
B
IN. [mm]
FILTER SIZE
IN. [mm]
14 [356] 12 27 /
32
[326] (2) 12 x 16 [305 x 406]
17 1 /
2
[445] 16 11 /
32
[415] (2) 12 x 16 [305 x 406]
21 [533] 19 27 /
32
[504] (2) 20 x 16 [508 x 406]
24 1 /
2
[622] 23 11 /
32
[593] (2) 24 x 16 [610 x 406]
WARNING: IMPORTANT NOTICE
A SOLID METAL BASE PLATE (SEE TABLE) MUST BE IN PLACE WHEN THE FURNACE
IS INSTALLED WITH SIDE OR REAR AIR RETURN DUCTS. FAILURE TO INSTALL A
BASE PLATE COULD CAUSE PRODUCTS OF COMBUSTION TO BE CIRCULATED INTO
THE LIVING SPACE AND CREATE POTENTIALLY HAZARDOUS CONDITIONS. SOLID
BOTTOM IS AVAILABLE FACTORY INSTALLED WITH OPTION CODE 263.
FURNACE
WIDTH
IN. [mm]
SOLID BOTTOM
KIT NO.
BASE
PLATE NO.
BASE
PLATE SIZE
IN. [mm]
14 [356]
17 1 /
2
[445]
21 [533]
24 1 /
2
[622]
RXGB-D14
RXGB-D17
RXGB-D21
RXGB-D24
AE-61874-01
AE-61874-02
AE-61874-03
AE-61874-04
11 5 /
8 x 23 9 /
16
[295 x 598]
15 1 /
8 x 23 9 /
16
[384 x 598]
18 5 /
8 x 23 9 /
16
[473 x 598]
25 5 /
8 x 23 9 /
16
[651 x 598]
[ ] Designates Metric Conversions
6 Rheem Manufacturing Company
BLOWER PERFORMANCE DATA—UPFLOW/HORIZONTAL MODELS
MODEL
NUMBER
RGPH-
SERIES
BLOWER
SIZE
[mm]
MOTOR
H.P.
[W]
BLOWER
SPEED
05EAUE
05NAUER
07EAUER
07NAUER
07EAMGR
07NAMGR
*
10EAMER
10NAMR
10EBRJR
10NBRJR
12EARJR
12NARJR
15EARJR
15NARJR
11 x 6
[279 x 152]
11 x 6
[279 x 152]
11 x 7
[279 x 178]
*
11 x 7
[279 x 178]
11 x 10
[279 x 254]
11 x 10
[279 x 254]
11 x 10
[279 x 254]
1/2
[373]
1/2
[373]
3/4
[559]
*
1/2
[373]
3/4
[559]
3/4
[559]
3/4
[559]
LOW
MED-LO
MED-HI
HIGH
LOW
MED-LO
MED-HI
HIGH
LOW
MED-LO
MED-HI
HIGH
LOW
MED-LO
MED-HI
HIGH
LOW
MED-LO
MED-HI
HIGH
MED-HI
HIGH
LOW
MED-LO
MED-HI
HIGH
NOTES: * *Not to be used as a heating speed.
Data compiled with factory filters installed.
.1 [.02]
675 [319]
950 [448]
1115 [526]
1270 [599]
1110 [524]
1265 [597]
1245 [588]
1555 [734]
1810 [854]
2050 [967]
925 [437]*
1050 [496]
1220 [576]
1410 [665]
1295 [611]
1645 [776]
2045 [965]
2320 [1095]
1280 [604]
1645 [776]
2050 [967]
2365 [1116]
1270 [599]
1620 [765]
2010 [949]
2340 [1104]
CFM [L/s] AIR DELIVERY
EXTERNAL STATIC PRESSURE INCHES [kPa] WATER COLUMN
.2 [.05]
655 [309]
930 [439]
1090 [514]
1250 [590]
1090 [514]
1240 [585]
1220 [576]
1515 [715]
1755 [828]
1985 [937]
890 [420]*
1040 [491]
1195 [564]
1380 [651]
1275 [602]
1615 [762]
2000 [944]
2260 [1067]
1275 [602]
1635 [772]
2015 [951]
2310 [1090]
1250 [590]
1595 [753]
1985 [937]
2275 [1074]
.3 [.07]
635 [300]
905 [427]
1070 [505]
1225 [578]
1070 [505]
1210 [571]
1195 [564]
1475 [696]
1705 [805]
1915 [904]
865 [408]*
1030 [486]
1160 [547]
1345 [635]
1250 [590]
1580 [746]
1955 [923]
2200 [1038]
1265 [597]
1615 [762]
1960 [925]
2250 [1062]
1220 [576]
1570 [741]
1960 [925]
2215 [1045]
.4 [.10]
610 [288]
880 [415]
1040 [491]
1200 [566]
1040 [491]
1175 [555]
1165 [550]
1435 [677]
1645 [776]
1845 [871]
835 [394]*
990 [467]
1140 [538]
1300 [614]
1225 [578]
1550 [732]
1905 [899]
2130 [1005]
1245 [588]
1590 [750]
1935 [913]
2185 [1031]
1195 [564]
1545 [729]
1915 [904]
2145 [1012]
.5 [.12]
585 [276]
860 [406]
1015 [479]
1165 [550]
1010 [477]
1140 [538]
1135 [536]
1395 [658]
1585 [748]
1785 [842]
810 [382]*
960 [453]
1105 [522]
1255 [592]
1195 [564]
1510 [713]
1845 [871]
2060 [972]
1215 [573]
1560 [736]
1885 [890]
2115 [998]
1165 [550]
1515 [715]
1850 [873]
2080 [982]
.6 [.15]
555 [262]
830 [392]
985 [465]
1130 [533]
975 [460]
1100 [519]
1105 [522]
1350 [637]
1530 [722]
1715 [809]
775 [366]*
920 [434]
1065 [503]
1205 [569]
1165 [550]
1465 [691]
1785 [842]
1985 [937]
1185 [559]
1520 [717]
1835 [866]
2035 [960]
1135 [536]
1480 [698]
1800 [850]
2010 [949]
.7 [.17]
520 [245]
800 [378]
945 [446]
1085 [512]
935 [441]
1055 [498]
1065 [503]
1300 [614]
1470 [694]
1655 [781]
745 [352]*
890 [420]
1020 [481]
1150 [543]
1135 [536]
1425 [673]
1720 [812]
1910 [901]
1145 [540]
1470 [694]
1775 [838]
1950 [920]
1105 [522]
1440 [680]
1730 [816]
1940 [916]
[ ] Designates Metric Conversions
GENERAL TERMS OF LIMITED WARRANTY
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy.
Gas Heat Exchanger Limited Warranty .......Twenty (20) Years
*Any Other Part..............................................Five (5) Years
*This five year limited warranty is applicable only to single-phase products installed in residential applications on or after January 1, 2001.
Rheem Manufacturing Company 7
Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and
Local codes, regulations, and practices.
RHEEM
AIR CONDITIONING
DIVISION
5600 Old Greenwood Road, Fort Smith, Arkansas 72908
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”
PRINTED IN U.S.A.
9-01 DC FORM NO. G11-448 REV. 9
Supersedes Form No. G11-448 Rev. 8