T20.0.4X.6C-03

Transmitter for

from version V3.2

Operating Manual

temperature

GTMU - MP

Content

1 INTENDED USE

2 GENERAL ADVICE

3 SAFETY INSTRUCTIONS

4 DISPOSAL NOTES

5 ASSIGNMENT OF ELBOW-TYPE PLUG (DEPENDING ON TYPE)

6 GENERAL INSTALLATION INSTRUCTIONS:

7 DESIGN TYPES, DIMENSION

8 DISPLAY FUNCTIONS

8.1

M

EASURING DISPLAY

8.2

M IN /M AX V ALUE M EMORY

9 ERROR AND SYSTEM MESSAGES

10 CONFIGURATION OF THE DEVICE

11 NOTES TO THE CALIBRATION SERVICES

12 SPECIFICATION

4

5

6

6

3

4

4

4

3

3

2

2

2

2

WEEE-Reg.-Nr.: DE93889386

GREISINGER

electronic GmbH

D - 93128 Regenstauf, Hans-Sachs-Straße 26

+49 (0) 9402 / 9383-0

+49 (0) 9402 / 9383-33  [email protected]

T20.0.4X.6C-03 Operating Manual GTMU - MP

_____________________________________________________ page 2 of 6

_____________________________________________________________________________

1 Intended use

The device measures the temperature of air or non corrosive / non ionizing gases.

The safety instructions (see chapter 3) have to be observed.

The device must not be used for purposes and under conditions for that the device had not been designed.

The device must carefully dealt with and has to be used according to the specifications (do not throw, knock, etc.). It has to be protected against dirt.

Do not expose the sensor to aggressive gases (like ammonia) for longer time.

Avoid condensation, as after drying there may remain residues, which may affect the precision negatively.

In dusty environment additional protection has to be applied (special protection caps).

2 General advice

Read through this document attentively and make yourself familiar to the operation of the device before you use it. Keep this document in a ready-to-hand way in order to be able to look up in the case of doubt .

3 Safety instructions

This device has been designed and tested in accordance to the safety regulations for electronic devices.

However, its trouble-free operation and reliability cannot be guaranteed unless the standard safety measures and special safety advises given in this manual will be adhered to when using it.

1. Trouble-free operation and reliability of the device can only be guaranteed if it is not subjected to any other climatic conditions than those stated under “Specification”.

Transporting the device from a cold to a warm environment condensation may result in a failure of the function. In such a case make sure the device temperature has adjusted to the ambient temperature before trying a new start-up.

2. General instructions and safety regulations for electric, light and heavy current plants, including domestic safety regulations (e.g. VDE), have to be observed.

3. If device is to be connected to other devices (e.g. via PC) the circuitry has to be designed most carefully.

Internal connection in third party devices (e.g. connection GND and earth) may result in not-permissible voltages impairing or destroying the device or another device connected.

4. Whenever there may be a risk whatsoever involved in running it, the device has to be switched off immediately and to be marked accordingly to avoid re-starting. Operator safety may be a risk if:

- there is visible damage to the device

- the device is not working as specified

- the device has been stored under unsuitable conditions for a longer time

In case of doubt, please return device to manufacturer for repair or maintenance.

5. Warning: Do not use this product as safety or emergency stop device or in any other application where failure of the product could result in personal injury or material damage.

Failure to comply with these instructions could result in death or serious injury and material damage.

4 Disposal notes

This device must not be disposed as “residual waste”.

To dispose this device, please send it directly to us (adequately stamped).

We will dispose it appropriately and environmentally friendly.

T20.0.4X.6C-03 Operating Manual GTMU - MP

_____________________________________________________ page 3 of 6

_____________________________________________________________________________

5 Assignment of elbow-type plug (depending on type)

4-20mA (2-wire connection) voltage (3-wire connection) voltage (4-wire connection)

1 = supply voltage +Uv

2 = GND / signal

1 = signal +

3 = supply voltage +Uv

(4) = supply voltage -Uv

signal -

1 = signal +

2 = signal -

3 = supply voltage +Uv

(4) = supply voltage –Uv

The type “current-” or “voltage output” is set by works and cannot be changed.

6 General installation instructions:

To mount the connection cable (2-, 3-, or 4-wire depending on type of device) the elbow-type plug screw has to be loosened and the coupling insert has to be removed by means of a screw driver at the position indicated (arrow).

Pull out connection cable through PG gland and connect to the loose coupling insert as described in the wiring diagram. Replace loose coupling insert onto the pins at the transducer housing and turn cover cap with PG gland in the direction desired till it snaps on (4 different starting positions at 90° intervals). Re-tighten the screw at the angle plug.

7 Design types, dimension

design-type 1 design-type 2 design-type 3 design-type 4

T20.0.4X.6C-03

8 Display Functions

Operating Manual GTMU - MP

_____________________________________________________ page 4 of 6

_____________________________________________________________________________

8.1 Measuring display

During normal operation the temperature in [°C] or [°F] is displayed.

SET

1 2 3

°C

8.2 Min/Max Value Memory watch Min values (Lo): press ▼ shortly once watch Max values (Hi): press ▲ shortly once restore current values: press ▼ or ▲ once again clear Min-values: clear Max-values: press ▼ for 2 seconds press ▲ for 2 seconds display changes between „Lo„ and Min values display changes between „Hi„ and Max values current values are displayed

Min values are cleared. Display shows shortly „CLr„.

Max values are cleared. Display shows shortly „CLr„.

After 10 seconds the currently measured values will be displayed again.

9 Error and system messages

Display Description

Err.1

Err.2

Err.7

Err.9

Er.11

Measuring range exceeded

Measuring value below measuring range

System fault

Sensor error

Calculation not possible

8.8.8.8 Segment test

Possible fault cause Remedy

Wrong signal

Temperatures above the measuring range are not allowed.

Wrong signal

Error in device

Temperatures below the measuring range are not allowed.

Disconnect from supply and reconnect.

If error remains: return to manufacturer

Sensor or cable defective

Check sensors, cable and connections, damages visible?

Calculation variable missing or invalid

Check temperature

The transducer performs a display test for 2 seconds after power up. After that it will change to the display of the measuring.

T20.0.4X.6C-03 Operating Manual GTMU - MP

_____________________________________________________ page 5 of 6

_____________________________________________________________________________

10 Configuration of the device

Follow these instructions to configure the functions of the device:

Press SET until the first parameter

UNIT

appears in the display

If a parameter should be changed, press or,

The device changed to the setting – edit with or

Confirm the value with SET

Jump to the next parameter with SET.

ATTENTION!

Parameter

SET value

▼ and ▲ information

If the jumper is removed from the shown contacts, the configuration is inaccessible, values are protected.

Never connect other contacts!

UNIT

VT

VT

Unit of temperature displays factory setting: °C

°C Temperatures in °Celsius

°F Temperatures in °Fahrenheit

Display at zero output of humidity display value (output scaling)

xxx.0 … +xxx.0

Entry of display value at which the temperature output should deliver

4 mA (or 0V) (factory setting: 0.0)

Display at maximum output for humidity display value (output scaling)

-

xxx.0 … +xxx.0

Entry of display value at which the temperature output should deliver

20 mA (or 1 V / 10 V) (factory setting: 100.0)

Offset correction of humidity measuring *) oFF

-5.

0 … +5.0 deactivated (factory setting)

Selectable from -5.0 to +5.0 % rel. humidity

Scale correction of humidity measuring *) oFF deactivated (factory setting)

-15.

00 … +15.00

Selectable from -15.00 to +15.00 % scale correction

Pressing SET again stores the settings, the instruments restarts (segment test)

Please note: If there is no key pressed within the menu mode within 2 minutes, the configuration will be cancelled, the entered settings are lost!

*) if higher values are needed, please check sensor, if necessary return to manufacturer for inspection.

Calculation: corrected value = (measured value – Offset) * (1+Scale/100)

T20.0.4X.6C-03 Operating Manual GTMU - MP

_____________________________________________________ page 6 of 6

_____________________________________________________________________________

11 Notes to the calibration services

Calibration certificates - DKD-certificates - other certificates:

If device should be certificated for its accuracy, it is the best solution to return it with the referring sensors to the manufacturer. (please state desired test values, e.g. 25°C)

12 Specification

Measuring range

Accuracy

Display

Add. Output signal

Media

Sensor

Meas. frequency

Adjusting

Min-/Max-value memory

Output signals

Scaling

Connection

For option AV01, AV10

Auxiliary energy:

(supply voltage, each output)

Perm. impedance

Permissible load

Display

Operating elements

Ambient conditions

Nom. temperature

Operating temperature

Relative humidity

Storage temperature

Housing

Dimensions

Mounting

Mounting distance

Electrical connection

EMC

50.0 ... 400.0 °C or -58.0 ... 752.0 °F

(at nom. temperature 25°C)

±0.4% of meas. value. ±0.2°C

± 0.2% FS

Non corrosive gasses

Pt1000

1 per second

Digital offset and scale adjustment for humidity and temperature

Min and max measured values are stored refer to type plate, both freely scalable by entering display values for 4mA (resp. 0V) and 20mA (resp.

1V/10V) output

4 - 20 mA (2-wire)

0 - 1 (10) V (3-wire)

4 - 20 mA: Uv = 12 - 30 V DC

0-1V: Uv = 12 - 30 V DC, max. 10mA

0-10V: Uv = 18 - 30 V DC, max. 10mA

4 - 20 mA: RA(Ohm) < ( (Uv - 12V) / 0,02A )

example: for Uv = 18V: RA < (18V - 12V) / 0.02A => RA < 300 Ohm

0 - 1 (10) V: RL(Ohm) > 3000 Ohm approx. 10 mm high, 4-digit LCD-display

3 keys

25°C

Electronics: -25 ... 70 °C

Please consider that the allowable range of the housing and electronics must not be exceeded, especially when using the probe at higher temperatures!

Electronics: 0 ... 95 %RH (not condensing)

-25 ... 70 °C

ABS (IP65, except sensor head)

82 x 80 x 55 mm (without elbow-type plug and sensor tube) for Option “Kabel”: Sensor head Ø14mm*68mm, 1m teflon cable, high humidity sensor

Holes for wall mounting (in housing - accessible after cover has been removed).

50 x 70 mm, max. shaft diameter of mounting screws is 4 mm

Elbow-type plug conforming to DIN 43650 (IP65), max. wire cross section: 1.5 mm², wire/cable diameter from 4.5 to 7 mm

The device corresponds to the essential protection ratings established in the

Regulations of the Council for the Approximation of Legislation for the member countries regarding electromagnetic compatibility (2004/108/EG).