- No category
advertisement
HCTL-1100 Series
General Purpose Motion Control ICs
Data Sheet
Description
The HCTL-1100 series is a high performance, general purpose motion control IC, fabricated in Avago CMOS technology. It frees the host processor for other tasks by performing all the time-intensive functions of digital motion control. The programmability of all control parameters provides maximum flexibility and quick design of control systems with a minimum number of components. In addition to the HCTL-1100, the complete control system consists of a host processor to specify commands, an amplifier, and a motor with an incremental encoder (such as the HP HEDS-5XXX,
-6XXX, -9XXX series). No analog compensation or velocity feedback is necessary.
Features
• Low power CMOS
• PDIP and PLCC versions available
• Enhanced version of the HCTL-1000
• DC, DC brushless, and step motor control
• Position and velocity control
• Programmable digital filter and commutator
• 8-Bit parallel, and PWM motor command ports
• TTL compatible
• SYNC pin for coordinating multiple HCTL-1100 ICs
• 100 kHz to 2 MHz operation
• Encoder input port
Pinouts
ESD WARNING: NORMAL HANDLING PRECAUTIONS SHOULD BE TAKEN TO AVOID STATIC DISCHARGE.
Applications
Typical applications for the
HCTL-1100 include printers, medical instruments, material handling machines, and industrial automation.
Note: Avago Technologies
encoders are not recommended for use in safety critical applications. Eg. ABS braking systems, power steering, life support systems and critical care medical equipment. Please contact sales representative if more clarification is needed.
HCTL-1100 vs. HCTL-1000
The HCTL-1100 is designed to replace the HCTL-1000. Some differences exist, and some enhancements have been added.
System Block Diagram
Comparison of HCTL-1100 and HCTL-1000
Description HCTL-1100 HCTL-1000
Max. Supply Current
Max. Power Dissipation
30 mA
165 mW
180 mA
950 mW
Max. Tri-State Output
Leakage Current
Operating Frequency
Operating Temperature
Range -20
°
C to +85
°
C 0
°
C to 70
°
C
Storage Temperature Range -55
°
C to +125
°
C - 40
°
C to +125
°
C
Synchronize 2 or More ICs Yes –
Preset Actual Position
Registers
Read Flag Register
Limit and Stop Pins
150 nA 10
µ
A
100 kHz-2 MHz 1 MHz-2 MHz
Yes
Yes
Must be pulled up to V
DD
if not used.
–
–
Can be left floating if not used.
Hard Reset
PLCC Package Available
Required
Yes
Recommended
–
2
Package Dimensions
4.83
0.190
1.27
0.050
±
0.15
0.006
Theory of Operation
The HCTL-1100 is a general purpose motor controller which provides position and velocity control for DC, DC brushless and stepper motors. The internal block diagram of the HCTL-1100 is shown in Figure 1. The HCTL-
1100 receives its input commands from a host processor and position feedback from an incremental encoder with quadrature output. An 8-bit bi-directional multiplexed address/data bus interfaces the HCTL-1100 to the host processor. The encoder
0-15
°
13.72
0.540
13.72
0.540
±
0.25
0.010
feedback is decoded into quadrature counts and a 24-bit counter keeps track of position.
The HCTL-1100 executes any one of four control algorithms selected by the user. The four control modes are:
• Position Control
• Proportional Velocity Control
• Trapezoidal Profile Control for point to point moves
• Integral Velocity Control with continuous velocity profiling using linear acceleration
The resident Position Profile
Generator calculates the necessary profiles for Trapezoidal Profile Control and Integral Velocity
Control. The HCTL-1100 compares the desired position (or velocity) to the actual position (or velocity) to compute compensated motor commands using a programmable digital filter D(z). The motor command is externally available at the Motor Command port as an 8-bit byte and at the
PWM port as a Pulse Width
Modulated (PWM) signal.
The HCTL-1100 has the capability of providing electronic commutation for DC brushless and stepper motors. Using the encoder position information, the motor phases are enabled in the correct sequence. The commutator is fully programmable to encompass most motor/encoder combinations. In addition, phase overlap and phase advance can be programmed to improve torque ripple and high speed performance. The HCTL-1100 contains a number of flags including two externally available flags, Profile and Initialization, which allow the user to see or check the status of the controller. It also has two emergency inputs, Limit and Stop, which allow operation of the
HCTL-1100 to be interrupted under emergency conditions.
The HCTL-1100 controller is a digitally sampled data system.
While information from the host processor is accepted asynchronously with respect to the control functions, the motor command is computed on a discrete sample time basis. The sample timer is programmable.
3
Figure 1. Internal Block Diagram.
4
Figure 2. Operating Mode Flowchart.
Electrical Specifications
Absolute Maximum Ratings
Operating Temperature, T
A ...................................................................
Storage Temperature, T
S ......................................................................
-20
°
C to 85
°
C
-55
°
C to 125
°
C
Supply Voltage, V
DD ......................................................................................
-0.3 V to 7 V
Input Voltage, V
IN .........................................................................
-0.3 V to V
DD
Maximum Operating Clock Frequency, f
CLK ...............................................
+0.3 V
2 MHz
DC Electrical Characteristics
V
DD
= 5 V
±
5%; T
A
= -20
°
C to +85
°
C
Parameter
Supply Voltage
Supply Current
Input Leakage Current
Input Pull-Up Current
SYNC PIN
Tristate Output Leakage
Current
Symbol Min.
V
DD
I
DD
I
IN
4.75
I
I
PU
OZ
Input Low Voltage
Input High Voltage
Output Low Voltage
Output High Voltage
Power Dissipation
Input Capacitance
Output Capacitance
V
IL
V
IH
V
OL
V
OH
P
D
C
IN
C
OUT
-0.3
2.0
-0.3
2.4
Typ.
5.00
15
10
- 40
10
75
100
0.8
V
DD
0.4
V
DD
165
20
Max.
Units
5.25
V
30
100 mA nA
Test Conditions
V
IN
= 0.00 and 5.25 V
±
150
-150
µ
A nA
V
IN
= 0.00 V
Sync, LIMIT, STOP pin #35 (PDIP)
V
OUT
= -0.3 to 5.25 V pin #38 (PLCC)
V mW pF pF
V
V
V
I
I
OL
OH
= 2.2 mA
= -200
µ
A
5
AC Electrical Characteristics
V
DD
= 5 V
±
5%; T
A
= -20
°
C to +85
°
C; Units = nsec
ID
# Signal
1 Clock Period (clk)
2 Pulse Width, Clock High
3 Pulse Width, Clock Low
4 Clock Rise and Fall Time
5 Input Pulse Width Reset
6 Input Pulse Width Stop, Limit
7
8
9
Input Pulse Width Index, Index
Input Pulse Width CHA, CHB
Delay CHA to CHB Transition
Clock Frequency
2 MHz 1 MHz
Formula*
Symbol Min.
Max.
Min.
Max.
Min.
t
CPER t
CPWH t
CPWL t
CR t
IRST t
IP
500
230
200
2500
600
50
1000
300
200
5000
1100
50
200 t t t
IX
IAB
AB
1600
1600
600
3100
3100
1100
5 clk
1 clk
+ 100 ns
3 clk
+ 100 ns
3 clk
+ 100 ns
1 clk
+ 100 ns
Max.
50
10 Input Rise/Fall Time CHA, CHB,
Index t
IABR
450 900 900 (clk
< 1 MHz)
11 Input Rise/Fall Time Reset, ALE,
CS, OE, Stop, Limit
12 Input Pulse Width ALE, CS
13 Delay Time, ALE Fall to CS Fall
14 Delay Time, ALE Rise to CS Rise
15 Address Setup Time Before
ALE Fall
16 Address Setup Time Before CS
Fall
17 Write Data Setup Time Before
CS Rise
18 Address/Data Hold Time
19 Setup Time, R/W Before CS Rise
20 Hold Time, R/W After CS Rise
21 Delay Time, Write Cycle, CS
Rise to ALE Fall
22 Delay Time, Read/Write, CS
Rise to CS Fall
23 Write Cycle, ALE Fall to ALE
Fall For Next Write t t t t t t t t t t t t
IR
IPW
AC
CA
ASR1
ASR
DSR t
H
WCS
WH
CSAL
CSCS
WC
80
50
50
20
20
20
20
20
20
1700
1500
1830
50
80
50
50
20
20
20
20
20
20
3400
3000
3530
50
80
50
50
20
20
20
20
20
20
3.4 clk
3 clk
3.7 clk
50
6
AC Electrical Characteristics (continued).
ID
# Signal
24 Delay Time, CS Rise to OE Fall
Clock Frequency
2 MHz 1 MHz
Formula*
Symbol Min.
Max.
Min.
Max.
Min.
t
CSOE
1700 3200 3 clk
+ 200 ns
Max.
25 Delay Time, OE Fall to Data
Bus Valid
26 Delay Time, CS Rise to Data
Bus Valid t
OEDB
100 100 100 t
CSDB
1800 3300 3 clk
+ 300 ns
100 27 Input Pulse Width OE
28 Hold Time, Data Held After
OE Rise
29 Delay Time, Read Cycle, CS
Rise to ALE Fall t t
IPWOE
DOEH
100
20
100
20 20 t
CSALR
1820 3320 3 clk
+ 320 ns
30 Read Cycle, ALE Fall to ALE
Fall For Next Read t
RC
1950 3450 3 clk
+ 450 ns
31 Output Pulse Width, PROF,
INIT, Pulse, Sign, PHA-PHD,
MC Port
32 Output Rise/Fall Time, PROF,
INIT, Pulse, Sign, PHA-PHD,
MC Port
33 Delay Time, Clock Rise to
Output Rise
34 Delay Time, CS Rising to MC
Port Valid
35 Hold Time, ALE High After
CS Rise
36 Pulse Width, ALE High
37 Pulse Width, SYNC Low t t t t
OF
OR
EP
CSMC t
ALH t
ALPWH t
SYNC
500
20
20
100
100
9000
150
300
1600
1000
20
20
100
100
18000
150
300
3200
1 clk
20
20
100
100
18 clk
*General formula for determining AC characteristics for other clock frequencies (clk), between 100 kHz and 2 MHz.
150
300
3.2 clk
7
HCTL-1100 I/O Timing Diagrams
Input logic level values are the TTL Logic levels V
IL
= 0.8 V and V
IH
= 2.0 V. Output logic levels are V
OL
= 0.4 V and V
OH
= 2.4 V.
8
HCTL-1100 I/O Timing Diagrams
There are three different timing configurations which can be used to give the user flexibility to interface the
HCTL-1100 to most microprocessors. See the I/O interface section for more details.
9
HCTL-1100 I/O Timing Diagrams
10
HCTL-1100 I/O Timing Diagrams
11
Pin Descriptions and Functions
Input/Output Pins
Symbol
Pin Number
PDIP PLCC Description
AD0/DB0-
AD5/DB5
2-7 3-8 Address/Data Bus – Lower 6 bits of 8-bit I/O port which are multiplexed between address and data.
DB6, DB7 8, 9 9, 10 Data bus – Upper 2 bits of 8-bit I/O port used for data only.
Input Signals
Symbol
Pin Number
PDIP PLCC Description
CHA/CHB 31, 30 34, 33 Channel A, B – Input pins for position feedback from an incremental shaft encoder. Two channels, A and B, 90 degrees out of phase are required.
Index 33 36 Index Pulse – Input from the reference or index pulse of an incremental encoder. Used only in conjunction with the Commutator. Either a low or high true signal can be used with the Index pin. See Timing
Diagrams and Encoder Interface section for more detail.
R/W
ALE
37
38
41
42
Read/Write – Determines direction of data exchange for the I/O port.
Address Latch Enable – Enables lower 6 bits of external data bus into internal address latch.
CS 39 43
OE
Limit
Stop
40
14
15
44
15
16
Chip Select – Performs I/O operation dependent on status of R/W line.
For a Write, the external bus data is written into the internal addressed location. For Read, data is read from an internal location into an internal output latch.
Output Enable – Enables the data in the internal output latch onto the external data bus to complete a Read operation.
Limit Switch – An internal flag which when externally set, triggers an unconditional branch to the Initialization/Idle mode before the next control sample is executed. Motor Command is set to zero. Status of the Limit flag is monitored in the Status register.
Stop Flag – An internal flag that is externally set. When flag is set during Integral Velocity Control mode, the Motor Command is decelerated to a stop.
Reset
ExtClk
V
DD
GND
SYNC
NC
36
34
40
37
Reset – A hard reset of internal circuitry and a branch to Reset mode.
External Clock
11, 35 12, 38 Voltage Supply – Both V
DD
pins must be connected to a 5.0 volt supply.
10, 32 1, 11, Circuit Ground
23, 35
1 2 Used to synchronize multiple HCTL-1100 sample timers.
– 17, 39 Not connected. These pins should be left floating.
12
Output Pins
Symbol
Pin Number
PDIP PLCC Description
MC0-MC7 18-25 20-22, Motor Command Port – 8-bit output port which contains the digital
24-28 motor command adjusted for easy bipolar DAC interfacing. MC7 is the most significant bit (MSB).
Pulse 16 18 Pulse – Pulse width modulated signal whose duty cycle is proportional to the Motor Command magnitude. The frequency of the signal is
External Clock/100 and pulse width is resolved into 100 external clocks.
Sign 17 19 Sign – Gives the sign/direction of the pulse signal.
PHA-PHD 26-29 29-32 Phase A, B, C, D – Phase Enable outputs of the Commutator.
Prof 12 13
Init 13 14
Profile Flag – Status flag which indicates that the controller is executing a profiled position move in the Trapezoidal Profile Control mode.
Initialization/Idle Flag – Status flag which indicates that the controller is in the Initialization/Idle mode.
Pin Functionality
SYNC Pin
The SYNC pin is used to synchronize two or more ICs. It is only valid in the INIT/IDLE mode
(see Operating the HCTL-1100).
When this pin is pulled low, the internal sample timer is cleared and held to zero. When the level on the pin is returned to high, the internal sample timer instantly starts counting down from the programmed value.
Connecting all SYNC pins together in the system and pulsing the SYNC signal from the host processor will synchronize all controllers.
Limit Pin
This emergency-flag input is used to disable the control modes of the HCTL-1100. A low level on this input pin causes the internal
Limit flag to be set. If this pin is
NOT used, it must be pulled up to
V
DD
. If it is not connected, the pin could float low, and possibly trigger a false emergency condition.
The Limit flag, when set in any control mode, causes the HCTL-
1100 to go into the Initialization/
Idle mode, clearing the Motor
Command and causing an immediate motor shutdown. When the
Limit flag is set, none of the three control mode flags (F0, F3, or
F5) are cleared as the HCTL-1100 enters the Initialization/Idle mode.
The user should be aware that these flags are still set before commanding the HCTL-1100 to re-enter one of the four control modes from Initialization/Idle mode.
In general, the user should clear all control mode flags after the limit pin has been pulled low, then proceed.
Stop Pin
The Stop flag affects the HCTL-
1100 only in the Integral Velocity
Mode.
When a low level is present on this emergency-flag input, the internal stop flag is set. If this pin is NOT used, it must be pulled up to V
DD
. If it is not connected, the pin could float low, and possibly trigger a false emergency condition.
When the STOP flag is set, the system will come to a decelerated stop and stay in this mode with a command velocity of zero until the Stop flag is cleared and a new command velocity is specified.
Notes on Limit and Stop Flags
Stop and Limit flags are set by a low level input at their respective pins. The flags can only be cleared when the input to the corresponding pin goes high, signifying that the emergency condition has been corrected,
AND a write to the Status register
(R07H) is executed. That is, after the emergency pin has been set and cleared, the flag also must be cleared by writing to R07H. Any word that is written to R07H after the emergency pin is set and cleared will clear the emergency flag. The lower four bits of that word will also reconfigure the
Status register.
13
Encoder Input Pins (CHA, CHB,
INDEX)
The HCTL-1100 accepts TTL compatible outputs from 2 and 3 channel incremental encoders such as the HEDS-5XXX, 6XXX, and 9XXX series encoders.
Channels A and B are internally decoded into quadrature counts which increment or decrement the 24-bit position counter. For example, a 500-count encoder is decoded into 2000 quadrature counts per revolution. The position counter will be incremented when Channel B leads
Channel A. The Index channel is used only for the Commutator and its function is to serve as a reference point for the internal
Ring Counter.
The HCTL-1100 employs an internal 3-bit state delay filter to remove any noise spikes from the encoder inputs to the HCTL-1100.
This 3-bit state delay filter requires the encoder inputs to remain stable for three consecutive clock rising edges for an encoder pulse to be considered valid by the HCTL-1100’s actual position counter (i.e., an encoder pulse must remain at a logic level high or low for three consecutive clock rising edges for the HCTL-
1100’s actual position counter to be incremented or decremented.)
The designer should therefore generally avoid creating the encoder pulses of less than 3 clock cycles.
The index signal of an encoder is used in conjunction with the
Commutator. It resets the internal ring counter which keeps track of the rotor position so that no cumulative errors are generated.
The Index pin of the HCTL-1100 also has a 3-bit filter on its input.
The Index pin is active low and
level transition sensitive
. It detects a valid high-to-low transition and qualifies the low input level through the 3-bit filter.
At this point, the Index signal is internally detected by the commutator logic. This type of configuraiton allows an Index or
Index signal to be used to generate the reference mark for commutator operation as long as the AC specifications for the
Index signal are met.
Motor Command Port (MC0-MC7)
The 8-bit Motor Command port consists of register R08H whose data goes directly to external pins
MC0-MC7. MC7 is the most significant bit. R08H can be read and written to, however, it should be written to only during the
Initialization/Idle mode. During any of the four Control modes, the controller writes the motor command into R08H.
This topic is further discussed in the “Register Section” under
“Motor Command Register
R08H”.
Pulse Width Modulation (PWM)
Output Port (Pulse, Sign)
The PWM port consists of the
Pulse and Sign pins. The PWM port outputs the motor command as a pulse width modulated signal with the correct polarity. This topic is further discussed in the
“Register Section” under “PWM
Motor Command Register R09H”.
Trapezoid Profile Pin (Prof)
The Trapezoid Profile Pin is internally connected to software flag bit 4 in the Status Register.
This flag is also represented by bit
0 in the Flag Register (R00H).
See the “Register Section” for more information. Both the Pin and the Flag indicate the status of a trapezoid profile move. When the HCTL-1100 begins a trapezoid move, this flag is set by the controller (a high level appears on the pin), indicating the move is in progress. When the
HCTL-1100 finishes the move, this flag is cleared by the controller.
Note that the instant the flag is cleared may not be the same instant the motor stops. The flag indicates the completion of the command profile, not the actual profile. If the motor is stalled during the move, or cannot physically keep up with the move, the flag will be cleared before the move is finished.
INIT/IDLE Pin (INIT)
This pin indicates that the HCTL-
1100 is in the INIT/IDLE mode, waiting to begin control. This pin is internally connected to the software flag bit 5 in the Status
Register R07H. This flag is also represented by bit 1 in the Flag
Register (R00H) (See the
“Register Section” for more information).
Commutator Pins (PHA-PHD)
These pins are connected only when using the commutator of the
HCTL-1100 to drive a brushless motor or step motor. The four pins can be programmed to energize each winding on a multiphase motor.
14
Operation of the HCTL-1100
Registers
The HCTL-1100 operation is controlled by a bank of 64 8-bit registers, 35 of which are user accessible. These registers contain command and configuration information necessary to properly run the controller chip.
The 35 user-accessible registers are listed in Tables 1 and 2. The register number is also the address. A functional block diagram of the HCTL-1100 which shows the role of the useraccessible registers is also included in Figure 3. The other 29 registers are used by the internal
CPU as scratch registers and should not be accessed by the user.
Figure 3. Register Block Diagram.
15
Table 1. Register Reference By Mode
Hex
Register
Dec.
Function
General Control
R00H
R05H
R07H
R0FH
R12H
R13H
R14H
R15H
R16H
R17H
R00D
R05D
R07D
R15D
R18D
R19D
R20D
R21D
R22D
R23D
Flag Register
Program Counter
Status Register
Sample Timer
Read Actual Position MSB
Read Actual Position
Read Actual Position LSB
Preset Actual Position MSB
Preset Actual Position
Preset Actual Position LSB
Output Registers
R07H
R08H
R09H
R07D
R08D
R09D
Filter Registers
R20H
R21H
R22H
R32D
R33D
R34D
Sign Reversal Inhibit
8 bit Motor Command
PWM Motor Command
Filter Zero, A
Filter Pole, B
Gain, K
Commutator Registers
R07H
R18H
R19H
R1AH
R1BH
R1CH
R1FH
R07D
R24D
R25D
R26D
R27D
R28D
R31D
Status Register
Commutator Ring
Velocity Timer
X
Y Phase Overlap
Offset
Max. Phase Advance
Position Control Mode
R00H
R12H
R13H
R14H
R0CH
R0DH
R0EH
R00D
R18D
R19D
R20D
R12D
R13D
R14D
Flag Register
Read Actual Position MSB
Read Actual Position
Read Actual Position LSB
Command Position MSB
Command Position
Command Position LSB
Data Type
[1]
scalar scalar
2’s Complement
2’s Complement
2’s Complement
2’s Complement
2’s Complement
2’s Complement
-
2’s Complement+80H
2’s Complement scalar scalar scalar
scalar
[6,7] scalar scalar
[6,7] scalar
[6,7]
2’s Complement
[7] scalar
[6,7]
-
2’s Complement
2’s Complement
2’s Complement
2’s Complement
2’s Complement
2’s Complement
User
Access
r/w r/w r/w r/w
[2] r/w w r/w r/w r/w r/w r/w r/w r/w
[2] r/w r
[4] r
[4]
/w
[5] r
[4] w
[8] w
[8] w
[8] r/w
[2] r/w r/w r/w r
[4] r
[4]
/w
[5] r
[4] r/w
[3] r/w
[3] r/w
[3]
16
Table 1. (continued).
Hex
Register
R00H
R12H
R13H
R14H
R23H
R24H
R34H
R35H
Dec.
R00D
R18D
R19D
R20D
R35D
R36D
R52D
R53D
Function
Trapezoid Profile Control Mode
R00H
R07H
R12H
R13H
R14H
R29H
R2AH
R2BH
R26H
R27H
R28H
R00D
R07D
R18D
R19D
R20D
R41D
R42D
R43D
R38D
R39D
R40D
Flag Register
Status Register
Read Actual Position MSB
Read Actual Position
Read Actual Position LSB
Final Position LSB
Final Position
Final Position MSB
Acceleration LSB
Acceleration MSB
Maximum Velocity
Integral Velocity Mode
R00H
R12H
R13H
R14H
R26H
R27H
R3CH
R00D
R18D
R19D
R20D
R38D
R39D
R60D
Flag Register
Read Actual Position MSB
Read Actual Position
Read Actual Position LSB
Acceleration LSB
Acceleration MSB
Command Velocity
Proportional Velocity Mode
Flag Register
Read Actual Position MSB
Read Actual Position
Read Actual Position LSB
Command Velocity LSB
Command Velocity MSB
Actual Velocity LSB
Actual Velocity MSB
-
-
-
-
Data Type
2’s Complement
2’s Complement
2’s Complement
2’s Complement
2’s Complement
2’s Complement scalar scalar
[6] scalar
[6]
2’s Complement
2’s Complement
2’s Complement scalar scalar
[6]
2’s Complement
2’s Complement
2’s Complement
2’s Complement
2’s Complement
2’s Complement
2’s Complement
2’s Complement
User
Access
r/w r/w r r
[4] r
[4]
[4] r/w r/w r/w r/w r/w r/w r/w r
[4]
[2]
/w
[5] r
[4]
/w
[5] r
[4] r/w r/w r/w r r r/w r
[4] r
[4]
/w
[5] r
[4] r/w r/w
Notes:
1. Consult appropriate section for data format and use.
2. Upper 4 bits are read only.
3. Writing to R0EH (LSB) latches all 24 bits.
4. Reading R14H (LSB) latches data in R12H and R13H.
5. Writing to R13H clears Actual Position Counter to zero.
6. The scalar data is limited to positive numbers (00H to 7FH).
7. The commutator registers (R18H, R1CH, R1FH) have further limits which are discussed in the Commutator section of this data sheet.
8. Writing to R17H (R23D) latches all 24 bits (only in INIT/IDLE mode).
17
Table 2. Register Reference Table by Register Number
Register
Hex
R00H
R05H
R07H
R08H
R09H
R0CH
R0DH
R0EH
R0FH
R12H
R13H
R14H
R15H
R16H
R17H
R18H
R19H
R1AH
R1BH
R1CH
R1FH
R20H
R21H
R22H
R23H
R24H
R26H
R27H
R28H
R29H
R2AH
R2BH
R34H
R35H
R3CH
Dec.
R00D
R05D
R07D
R08D
R09D
R12D
R13D
R14D
R15D
R18D
R19D
R20D
R21D
R22D
R23D
R24D
R25D
R26D
R27D
R28D
R31D
R32D
R33D
R34D
R35D
R36D
R38D
R39D
R40D
R41D
R42D
R43D
R52D
R53D
R60D
Function
Flag Register
Program Counter
Status Register
8 bit Motor Command Port
PWM Motor Command Port
Command Position (MSB)
Command Position
Command Position (LSB)
Sample Timer
Read Actual Position (MSB)
Read Actual Position
Read Actual Position (LSB)
Preset Actual Position (MSB)
Preset Actual Position
Preset Actual Position (LSB)
Commutator Ring
Commutator Velocity Timer
X
Y Phase Overlap
Offset
Maximum Phase Advance
Filter Zero, A
Filter Pole, B
Gain, K
Command Velocity (LSB)
Command Velocity (MSB)
Acceleration (LSB)
Acceleration (MSB)
Maximum Velocity
Final Position (LSB)
Final Position
Final Position (MSB)
Actual Velocity (LSB)
Actual Velocity (MSB)
Command Velocity
Mode Used
All
All
All
All
All
All except Proportional
Velocity
All except Proportional
Velocity
All except Proportional
All
Velocity
All
All
All
INIT/IDLE
INIT/IDLE
INIT/IDLE
All
All
All
All
All
All
All except Proportional
Velocity
All except Proportional
Velocity
All
Proportional Velocity
Proportional Velocity
Integral Velocity and
Trapezoidal Profile
Integral Velocity and
Trapezoidal Profile
Trapezoidal Profile
Trapezoidal Profile
Trapezoidal Profile
Trapezoidal Profile
Proportional Velocity
Proportional Velocity
Integral Velocity
Data Type
– scalar
–
2’s complement
+ 80H
2’s complement
2’s complement
2’s complement
2’s complement scalar
2’s complement
2’s complement
2’s complement
2’s complement
2’s complement
2’s complement scalar scalar scalar scalar scalar scalar scalar scalar scalar scalar scalar
[6,7]
[6]
[6]
2’s complement
[6,7]
2’s complement
2’s complement
[6]
[6]
2’s complement
2’s complement
2’s complement
2’s complement
2’s complement
2’s complement
[7]
User
Access
r/w w r/w r/w r/w r/w r/w r/w
[2] w r/w r/w r/w r/w r/w r/w r [4] r [4] /w [5] r [4] w [8] w [8] w [8] r/w r/w r/w r/w r/w r/w r/w r/w r/w r/w r/w r r r/w
[3]
[3]
[3]
Notes:
1. Consult appropriate section for data format and use.
2. Upper 4 bits are read only.
3. Writing to R0EH (LSB) latches all 24 bits.
4. Reading R14H (LSB) latches data in R12H and R13H.
5. Writing to R13H clears Actual Position Counter to zero.
6. The scalar data is limited to positive numbers (00H to 7FH).
7. The commutator registers (R18H, R1CH, R1FH) have further limits which are discussed in the Commutator section of this data sheet.
8. Writing to R17H (R23D) latches all 24 bits (only in INIT/IDLE mode).
18
Register Descriptions – General
Control, Output, Filter, and
Commutator
Flag Register (R00H)
The Flag register contains flags
F0 through F5. This register is a read/write register. Each flag is set and cleared by writing an 8-bit data word to R00H. When writing to R00H, the upper four bits are ignored by the HCTL-1100, bits
0,1,2 specify the flag address, and bit 3 specifies whether to set
(bit=1) or clear (bit=0) the addressed flag.
Flag Descriptions
F0–Trapezoidal Profile Flag – set
by the user to execute Trapezoidal Profile Control. The flag is reset by the controller when the move is completed. The status of
F0 can be monitored at the Profile pin and in Status register R07H bit 4.
F1–Initialization/Idle Flag – set/
cleared by the HCTL-1100 to indicate execution of the
Initialization/Idle mode. The status of F1 can be monitored at the Initialization/Idle pin and in bit 5 of the Status register
(R07H). The user should not attempt to set or clear F1.
F2–Unipolar Flag – set/cleared by
the user to specify Bipolar (clear) or Unipolar (set) mode for the
Motor Command port.
F3–Proportional Velocity Control
Flag – set by the user to specify
Proportional Velocity control.
F4–Hold Commutator flag – set/
cleared by the user or automatically by the Align mode.
When set, this flag inhibits the internal commutator counters to allow open loop stepping of a motor by using the commutator.
(See “Offset register” description in the “Commutator section.”)
F5–Integral Velocity Control – set
by the user to specify Integral
Velocity Control. Also set and cleared by the HCTL-1100 during execution of the Trapezoidal
Profile mode. This is transparent to the user except when the Limit flag is set (see “Emergency Flags” section).
Writing to the Flag Register
When writing to the flag register, only the lower four bits are used.
Bit 3 indicates whether to set or clear a certain flag, and bits
0,1,and 2 indicate the desired flag. The following table shows the bit map of the Flag register:
Bit Number
7-4
3
2
1
0
Function
Don’t Care
1 = set
0 = clear
AD2
AD1
AD0
The following table outlines the possible writes to the Flag
Register:
Flag
F0
F1
F2
F3
F4
F5
SET
08H
-
0AH
0BH
0CH
0DH
CLEAR
Reading the Flag Register
00H
-
02H
03H
04H
05H
Reading register R00H returns the status of the flags in bits 0 to
5. For example, if bit 0 is set
(logic 1), then flag F0 is set. If bit
4 is set, then flag F4 is set. If bits
0 and 5 are set, then both flags F0 and F5 are set.
The following table outlines the
Flag Register Read:
Bit
Number
2
1
0
8-6
5
4
3
Flag
(1 = set)
(0 = clear)
Don’t Care
F5
F4
F3
F2
F1
F0
Notes:
1. A soft reset (writing 00H to R05H) will not reset the flags in the flag register. A hard reset (RESET pin low) is required to reset all the flags. The flags can also be reset by writing the proper word to the Flag register as explained above.
2. While in Trapezoid Profile Mode, Flag
F0 will be set, and Flag F5 may be set.
F5 is used for internal purposes. Both flags will be cleared at the end of the profile.
Program Counter Register (R05H)
The Program Counter, which is a write-only register, executes the preprogrammed functions of the controller. The program counter is used along with the control flags F0, F3, and F5 in the Flag register (R00H) to change control modes. The user can write any of the following four commands to the Program Counter.
Value
written to R05H
00H
01H
02H
03H
Action
Software Reset
Enter Init/Idle Mode
Enter Align Mode
(only from INIT/
IDLE Mode)
Enter Control Mode
(only from INIT/
IDLE Mode)
These Commands are discussed in more detail in the “Operating
Modes” section.
19
Status Register (R07H)
The Status register indicates the status of the HCTL-1100. Each bit decodes into one signal. All 8 bits are user readable and are decoded as shown below. Only the lower 4 bits can be written to by the user to configure the HCTL-1100. To set or clear any of the lower 4 bits, the user writes an 8-bit word to R07H. The upper 4 bits are ignored. Each of the lower 4 bits directly sets/clears the corresponding bit of the Status register as shown below. For example, writing XXXX0101 to R07H sets the PWM Sign Reversal Inhibit, sets the Commutator Phase
Configuration to “3 Phase,” and sets the Commutator Count
Configuration to “full.”
Motor Command Register (R08H)
The 8-bit Motor Command Port consists of register R08H. The register is connected to external pins MC0-MC7. MC7 is the most significant bit. R08H can be read and written to; however, it should be written to only in the
Initialization/Idle mode. During any of the four control modes, the
HCTL-1100 writes values to register R08H.
The Motor Command Port operates in two modes, bipolar and unipolar, when under control of internal software. Bipolar mode allows the full range of values in
R08H (-128D to +127D). The data written to the Motor
Command Port by the control algorithms is the internally
Table 3. Status Register
Status Bit Function
0
1
2
3
4
5
6
7
PWM Sign Reversal Inhibit
0 = off
1 = on
Commutator Phase Configuration
0 = 3 phase
1 = 4 phase
Commutator Count Configuration
0 = quadrature
1 = full
Should always be set to 0
Trapezoidal Profile Flag F0
1 = in Profile Control
Initialization/Idle Flag F1
1 = in Initialization/Idle Mode
Stop Flag
0 = set (Stop triggered)
1 = cleared (no Stop)
Limit Flag
0 = set (Limit triggered)
1 = cleared (no Limit) computed 2’s-complement motor command with an 80H offset added. This allows direct interfacing to a DAC. Connecting the
Motor Command Port to a DAC,
Bipolar mode allows the full voltage swing (positive and negative).
Unipolar mode functions such that with the same DAC circuit, the motor command output is restricted to positive values
(80H to FFH) when in a control mode. Unipolar mode is used with multi-phase motors when the commutator controls the direction of movement. (If needed, the Sign pin could be used to indicate direction). In Unipolar mode, the user can still write a negative value to R08H in INIT/IDLE mode.
Unipolar mode or Bipolar mode is programmed by setting or clearing flag F2 in the Flag
Register R00H.
Internally, the HCTL-1100 operates on data of 24, 16 and 8bit lengths to produce the
8-bit motor command, available externally. Many times the computed motor command will be greater than 8 bits. At this point, the motor command is saturated by the controller. The saturated value output by the controller is not the full scale value 00H
(00D), or FFH (255D). The saturated value is adjusted to 0FH
(15D) (negative saturation) and
F0H (240D) (positive saturation).
Saturation levels for the Motor
Command port are in Figure 4.
20
PWM Motor Command Register
(R09H)
The PWM port outputs the motor command as a pulse width modulated signal with the correct sign of polarity. The PWM port consists of the Pulse and Sign pins and R09H.
The PWM signal at the Pulse pin has a frequency of External
Clock/100 and the duty cycle is resolved into the 100 clocks. (For example, a 2 MHz clock gives a
20 KHz PWM frequency.)
The Sign pin gives the polarity of the command. Low output on Sign pin is positive polarity.
The 2’s-complement contents of
R09H determine the duty cycle and polarity of the PWM command. For example, D8H
(–40D) gives a 40% duty cycle signal at the Pulse pin and forces the Sign pin high. Data outside the 64H (+100D) to 9CH
(–100D) linear range gives 100% duty cycle. R09H can be read and written to. However, the user should only write to R09H when the controller is in the Initialization/Idle mode.
Figure 5 shows the PWM output versus the internal motor command.
21
Figure 4. Motor Command Port Output.
When any Control mode is being executed, the unadjusted internal
2’s-complement motor command is written to R09H. Because of the hardware limit on the linear range
(64H to 9CH,
±
100D), the PWM port saturates sooner than the 8bit Motor Command port (00H to
FFH, +127D to –128D). When the internal motor command saturates above 8 bits, the PWM port is saturated to the full
±
100% duty cycle level. Figure 5 shows the actual values inside the
PWM port. Note that the Unipolar flag, F2, does not affect the PWM port.
For commutation of brushless motors with the PWM port, only use the Pulse pin from the PWM port as the commutator already contains sign information. (See
Figure 9.)
The PWM port has an option that can be used with H-bridge type amplifiers. The option is Sign
Reversal Inhibit, which inhibits the Pulse output for one PWM period after a sign polarity reversal. This allows one pair of transistors to turn off before others are turned on and thereby avoids a short across the power supply. Bit 0 in the Status register
(R07H) controls the Sign Reversal
22
Figure 5. PWM Port Output.
Figure 6. Sign Reversal Inhibit.
Inhibit option. Figure 6 shows the output of the PWM port when Bit
0 is set.
Actual Position Registers
Read, Clear: R12H,R13H,R14H
Preset : R15H,R16H,R17H
The Actual Position Register is accessed by two sets of registers in the HCTL-1100. When reading the Actual Position from the
HCTL-1100, the host processor will read Registers R12H(MSB),
R13H, and R14H(LSB). When presetting the Actual Position
Register, the processor will write to Registers R15H(MSB), R16H, and R17H(LSB).
When reading the Actual Position registers, the order should be
R14H, R13H, R12H. These registers are latched, such that, when reading Register R14H, all three bytes will be latched so that count data does not change while reading three separate bytes.
When presetting the Actual
Position Register, write to R15H and R16H first. When R17H is written to, all three bytes are simultaneously loaded into the
Actual Position Register.
Note that presetting the Actual
Position Registers is only allowed while the HCTL-1100 is in INIT/
IDLE mode.
The Actual Position Registers can be simultaneously cleared at any time by writing any value to
R13H.
Digital Filter Registers
Zero (A) R20H
Pole (B) R21H
Gain (K) R22H
All control modes use some part of the programmable digital filter
D(z) to compensate for closed loop system stability. The compensation D(z) has the form:
A
K
z – –––
256
D(z) = –––––––––––
B
4
z + –––
256
[1] where: z = the digital domain operator
K = digital filter gain (R22H)
A = digital filter zero (R20H)
B = digital filter pole (R21H)
The compensation is a first-order lead filter which in combination with the Sample Timer T (R0FH) affects the dynamic step response and stability of the control system. The Sample Timer, T, determines the rate at which the control algorithm gets executed.
All parameters, A, B, K, and T, are
8-bit scalars that can be changed by the user any time.
As shown in equations [2] and
[3], the digital filter uses previously sampled data to calculate D(z). This old internally sampled data is cleared when the
Initialization/Idle mode is executed.
In Position Control, Integral
Velocity Control, and Trapezoidal
Profile Control the digital filter is implemented in the time domain as shown below:
MC n
= (K/4)(X n
) –
[(A/256)(K/4)(X n–1
) +
(B/256)(MC n-1
)] [2] where: n = current sample time n-1 = previous sample time
MC n
= Motor Command Output at n
MC n-1
= Motor Command
Output at n-1
X n
= (Command Position –
Actual Position) at n
X n-1
= (Command Position –
Actual Position) at n-1
In Proportional Velocity control the digital compensation filter is implemented in the time domain as:
[3] MC n
= (K/4)(Y n
) where:
Y n
= (Command Velocity –
Actual Velocity) at n
For more information on system sampling times, bandwidth, and stability, please consult Avago
Application Note 1032, Design of
the HCTL-1000’s Digital Filter
Parameters by the Combination
Method
.
23
Sample Timer Register (R0FH)
The contents of this register set the sampling period of the HCTL-
1100. The sampling period is: t = 16(T+1)(1/frequency of the external clock) [4] where:
T = contents of register R0FH
The Sample Timer has a limit on the minimum allowable sample time depending on the control mode being executed. The limits are given in Table 4 below.
The minimum value limits are to make sure the internal programs have enough time to complete proper execution.
The maximum value of T (R0FH) is FFH (255D). With a 2 MHz clock, the sample time can vary from 64
µ sec to 2048
µ sec. With a 1 MHz clock, the sample time can vary from 128
µ sec to 4096
µ sec.
Digital closed-loop systems with slow sampling times have lower stability and a lower bandwidth than similar systems with faster sampling times. To keep the system stability and bandwidth as high as possible the HCTL-1100 should typically be programmed with the fastest sampling time possible. This rule of thumb must be balanced by the needs of the velocity range to be controlled.
Velocities are specified to the
HCTL-1100 in terms of quadrature encoder counts per sample time. The faster the sampling time, the higher the slowest possible speed.
Hardware Description
The Sample Timer consists of a buffer and a decrement counter.
Each time the counter reaches
00H, the Sampler Timer Value T
(value written to R0FH) is loaded from the buffer into the counter, which immediately begins to decrement from T.
Writing to the Sample Timer
Register
Data written to R0FH will be latched into the internal buffer and used by the counter after it completes the present sample time cycle by decrementing to
00H. The next sample time will use the newly written data.
Reading the Sample Timer Register
Reading R0FH gives the values directly from the decrementing counter. Therefore, the data read from R0FH will have a value anywhere between T and 00H, depending where in the sample time cycle the counter is.
Table 4.
Control Mode
Position Control
Proportional Velocity Control
Trapezoidal Profile Control
Integral Velocity Control
R0FH Contents
Minimum Limit
07H(07D)
07H(07D)
0FH(15D)
0FH(15D)
Example –
1. On reset, the value of the timer is pre-set to 40H.
2. Reading R0FH shows
3EH . . . 2BH . . . 08H . . .
3CH . . .
Synchronizing Multiple Axes
Synchronizing multiple axes with
HCTL-1100s can be achieved by using the SYNC pin as explained in the Pin Discussion section.
Some users may not only want to synchronize several HCTL-1100s but also follow custom profiles for each axis. To do this, the user may need to write a new command position or command velocity during each sample time for the duration of the profile. In this case, data written to the
HCTL-1100 has to be coordinated with the Sample Timer. This is so that only one command position or velocity is received during any one sample period, and that it is written at the proper time within a sample period.
At the beginning of each sample period, the HCTL-1100 is performing calculations and executions. New command positions and velocities should not be written to the HCTL-1100 during this time. If they are, the calculations may be thrown off and cause unpredictable control.
The user can read the Sample
Timer Register to avoid writing too early during a sample period.
Since the Sample Timer Register continuously counts down from its programmed value, the user can check if enough time has passed in the sample period to insure the completion of the internal calculations. The length of time needed by the HCTL-1100
24
to do its calculations is given by the Minimum Limits of R0FH
(Sample Timer Register) as shown in Table 4. For Position Control
Mode, the user should wait for the
Sample Timer to count down 07H from its programmed value before writing the next command position or velocity. If the programmed sample timer value is 39H, wait until the Sample
Timer Register reads 32H.
Writing between 32H and 00H will make the command information available for the next sample period.
Commutator
Status Register
Commutator Ring
X Register
Y Phase Overlap
Offset
Max. Phase Advance
Velocity Timer
(R07H)
(R18H)
(R1AH)
(R1BH)
(R1CH)
(R1FH)
(R19H)
The commutator is a digital state machine that is configured by the user to properly select the phase sequence for electronic commutation of multiphase motors. The Commutator is designed to work with 2, 3, and 4phase motors of various winding configurations and with various encoder counts. Along with providing the correct phase enable sequence, the Commutator provides programmable phase overlap, phase advance, and phase offset.
Phase overlap is used for better torque ripple control. It can also be used to generate unique state sequences which can be further decoded externally to drive more complex amplifiers and motors.
Phase advance allows the user to compensate for the frequency characteristics of the motor/ amplifier combination. By advancing the phase enable command (in position), the delay in reaction of the motor/amplifier combination can be offset and higher performance can be achieved.
Phase offset is used to adjust the alignment of the commutator output with the motor torque curves. By correctly aligning the
HCTL-1100’s commutator output with the motor’s torque curves, maximum motor output torque can be achieved.
The inputs to the Commutator are the three encoder signals,
Channel A, Channel B, and Index, and the configuration data stored in registers.
The Commutator uses both channels and the index pulse of an incremental encoder. The index pulse of the encoder must be physically aligned to a known torque curve location because it is used as the reference point of the rotor position with respect to the
Commutator phase enables.
The index pulse should be permanently aligned during motor encoder assembly to the last motor phase. This is done by energizing the last phase of the motor during assembly and permanently attaching the encoder codewheel to the motor shaft such that the index pulse is active as shown in Figures 7 and 8. Fine tuning of alignment for commutation purposes is done electronically by the Offset register (R1CH) once the complete control system is set up.
Figure 7. Index Pulse Alignment to Motor Torque Curves.
25
Each time an index pulse occurs, the internal commutator ring counter is reset to 0. The ring counter keeps track of the current position of the rotor based on the encoder feedback. When the ring counter is reset to 0, the
Commutator is reset to its origin
(last phase going low, Phase A going high) as shown in
Figure 10.
The output of the Commutator is available as PHA, PHB, PHC, and
PHD. The HCTL-1100’s commutator acts as the electrical equivalent of the mechanical brushes in a motor. Therefore, the outputs of the commutator provide only proper phase sequencing for bidirectional operation. The magnitude information is provided to the motor via the Motor Command and PWM ports. The outputs of the commutator must be combined with the outputs of one of the motor ports to provide proper
DC brushless and stepper motor control. Figure 9 shows an example of circuitry which uses the outputs of the commutator with the Pulse output of the PWM port to control a DC brushless or
Figure 8. Codewheel Index Pulse Alignment.
Figure 9. PWM Interface to Brushless DC Motors.
26
Figure 10. Commutator Configuration.
stepper motor. A similar procedure could be used to combine the commutator outputs PHA-
PHD with a linear amplifier interface output (Figure 16) to create a linear amplifier system.
The Commutator is programmed by the data in the following registers. Figure 10 shows an example of the relationship between all the parameters.
Status Register (R07H)
Bit #1- 0 = 3-phase configuration, PHA, PHB, and
PHC are active outputs.
1 = 4-phase configuration, PHA – PHD are active outputs.
Bit #2- 0 = Rotor position measured in quadrature counts
(4x decoding).
1 = Rotor position measured in full counts (1 count = 1 codewheel bar and space.)
Bit #2 only affects the commutator’s counting method. This includes the Ring register
(R18H), the X and Y registers
(R1AH & R1BH), the Offset register (R1CH), the Velocity
Timer register (R19H), and the
Maximum Advance register
(R1FH).
Quadrature counts (4x decoding) are always used by the HCTL-
1100 as a basis for position, velocity, and acceleration control.
Ring Register (R18H)
The Ring register is defined as 1 electrical cycle of the commutator which corresponds to 1 torque cycle of the motor. The Ring register is scalar and determines the length of the commutation cycle measured in full or quadrature counts as set by bit #2 in the
Status register (R07H). The value of the ring must be limited to the range of 0 to 7FH.
X Register (R1AH)
This register contains scalar data which sets the interval during which only one phase is active.
Y Register (R1BH)
This register contains scalar data which set the interval during which two sequential phases are both active. Y is phase overlap. X and Y must be specified such that:
X + Y = Ring/(# of phases) [5]
These three parameters define the basic electrical commutation cycle.
Offset Register (R1CH)
The Offset register contains two’s-complement data which determines the relative start of the commutation cycle with respect to the index pulse. Since the index pulse must be physically referenced to the rotor, offset performs fine alignment between the electrical and mechanical torque cycles.
The Hold Commutator flag (F4) in the Status register (R07H) is used to decouple the internal commutator counters from the encoder input. Flag (F4) can be used in conjunction with the
Offset register to allow the user to advance the commutator phases open loop. This technique may be used to create a custom commutator alignment procedure. For example, in Figure 10, case 1, for a three-phase motor where the ring = 9, X = 3, and Y = 0, the phases can be made to advance open loop by setting the Hold
Commutator flag (F4) in the Flag register (R07H). When the values
0, 1, or 2 are written to the Offset register, phase A will be enabled.
When the values 3, 4 or 5 are written to the Offset register, phase B will be enabled. And, when the values 6, 7, or 8 are written to the Offset register, phase C will be enabled. No values larger than the value programmed into the Ring register should be programmed into the Offset register.
Phase Advance Registers (R19H,
R1FH)
The Velocity Timer register and
Maximum Advance register linearly increment the phase advance according to the measured speed for rotation up to a set maximum.
The Velocity Timer register
(R19H) contains scalar data which determines the amount of phase advance at a given velocity.
The phase advance is interpreted in the units set for the Ring counter by bit #2 in R07H. The velocity is measured in revolutions per second.
Advance = N f v
∆ t [6] where:
∆
16 (R19H + 1) t = –––––––––––– [7]
f external clk
N f
= full encoder counts/ revolution.
v = velocity (revolutions/ second)
The Maximum Advance register
(R1FH) contains scalar data which sets the upper limit for phase advance regardless of rotor speed.
Figure 11 shows the relationship between the Phase Advance registers. Note: If the phase advance feature is not used, set both R19H and R1FH to 0.
27
Commutator Constraints and Use
When choosing a three-channel encoder to use with a DC brushless or stepper motor, the user should keep in mind that the number of quadrature encoder counts (4x the number of slots in the encoder’s codewheel) must be an integer multiple (1x, 2x, 3x,
4x, 5x, etc.) of the number of pole pairs in the DC brushless motor or steps in a stepper motor. To take full advantage of the commutator’s overlap feature, the number of quadrature counts should be at least 3 times the number of pole pairs in the DC brushless motor or steps in the stepper motor. For example, a
1.8
°
, (200 step/revolution) stepper motor should employ at least a 150 slot codewheel = 600 quadrature counts/revolution = 3 x 200 steps/revolution).
There are several numerical constraints the user should be aware of to use the Commutator.
The parameters of Ring, X, Y, and
Max Advance must be positive numbers (00H to 7FH).
Additionally, the following equation must be satisfied:
(-128D) 80H
≤
3/2 Ring
+ Offset
±
Max Advance
≤
7FH (127D) [8]
In order to utilize the greatest flexibility of the Commutator, it must be realized that the
Commutator works on a circular ring counter principle, whose range is defined by the Ring register (R18H). This means that for a ring of 96 counts and a needed offset of 10 counts, numerically the Offset register can be programmed as 0AH
(10D) or AAH (-86D), the latter satisfying Equation 8.
If bit #2 in the Status register is set to allow the commutator to count in full counts, a higher resolution codewheel may be chosen for precise motor control without violating the commutator constraints equation (Equation 8).
Example: Suppose you want to commutate a 3-phase 15 deg/step
Variable Reluctance Motor attached to a 192 count encoder.
1. Select 3-phase and quadrature mode for commutator by writing 0 to R07H.
2. With a 3-phase 15 degree/step
Variable Reluctance motor the torque cycle repeats every 45 degrees or 8 times/revolution.
3. Ring register
(4)(192) counts/revolution
= ––––––––––––––––––––––
8/revolution
= 96 quadrature counts
= 1 commutation cycle
4. By measuring the motor torque curve in both directions, it is determined that an offset of 3 mechanical degrees, and a phase overlap of 2 mechanical degrees is needed.
Offset = 3
°
(4) (192)
––––––––
360
°
≅
6 quadrature counts
Figure 11. Phase Advance vs. Motor Velocity.
28
To create the 3 mechanical degree offset, the Offset register (R1CH) could be programmed with either A6H
(-90D) or 06H (+06D).
However, because 06H (+06D) would violate the commutator constraints Equation 8, A6H
(-90D) is used.
(2
°
) (4) (192)
Y = overlap = ––––––––––
≅
4
360
°
X + Y = 96/3
Therefore, X = 28
Y = 4
For the purposes of this example, the Velocity Timer and Maximum
Advance are set to 0.
Operation Flowchart
The HCTL-1100 executes any one of three setup routines or four control modes selected by the user. The three setup routines include:
– Reset
– Initialization/Idle
– Align.
The four control modes available to the user include:
– Position Control
– Proportional Velocity Control
– Trapezoidal Profile Control
– Integral Velocity Control
The HCTL-1100 switches from one mode to another as a result of one of the following three mechanisms:
1. The user writes to the Program
Counter.
2. The user sets/clears flags F0,
F3, or F5 by writing to the Flag register (R00H).
3. The controller switches automatically when certain initial conditions are provided by the user.
Figure 12. Operation Flowchart.
This section describes the function of each setup routine and control mode and the initial conditions which must be provided by the user to switch from one mode to another. Figure 12 shows a flowchart of the setup routines and control modes, and shows the commands required to switch from one mode to another.
29
Setup Modes
Hard Reset
Executed by:
-Pulling the RESET pin low
(required at power up)
When a hard reset is executed
(RESET pin goes low), the following conditions occur:
– All output signal pins are held low except Sign, Data bus, and
Motor Command.
– All flags (F0 to F5) are cleared.
– The Pulse pin of the PWM port is set low while the Reset pin is held low. After the Reset pin is released (goes high) the Pulse pin goes high for one cycle of the external clock driving the
HCTL-1100. The Pulse pin then returns to a low output.
– The Motor Command port
(R08H) is preset to 80H
(128D).
– The Commutator logic is cleared.
– The I/O control logic is cleared.
– A soft reset is automatically executed.
Soft Reset
Executed by:
- Writing 00H to R05H, or
- Automatically called after a
hard reset
When a soft reset is executed, the following conditions occur:
– The digital filter parameters are preset to
A (R20H) = E5H (229D)
B (R21H) = K (R22H) = 40H
(64D)
– The Sample Timer (R0FH) is preset to 40H (64D).
– The Status register (R07H) is cleared.
– The Actual Position Counters
(R12H, R13H, R14H) are cleared to 0.
From Reset mode, the HCTL-1100 goes automatically to
Initialization/Idle mode.
Initialization/Idle
Executed by:
- Writing 01H to R05H, or
- Automatically executed after a hard reset, soft reset, or
- Limit pin goes low.
The Initialization/Idle mode is entered either automatically from
Reset, by writing 01H to the
Program Counter (R05H) under any conditions, or pulling the
Limit pin low.
In the Initialization/Idle mode, the following occur:
– The Initialization/Idle flag (F1) is set.
– The PWM port R09H is set to
00H (zero command).
– The Motor Command port
(R08H) is set to 80H (128D)
(zero command).
– Previously sampled data stored in the digital filter is cleared.
It is at this point that the user should pre-program all the necessary registers needed to execute the desired control mode.
The HCTL-1100 stays in this mode (idling) until a new mode command is given.
Align
Executed by:
- Writing 02H to R05H
Before attempting to enter the
Align mode, the user should clear all control mode flags and set both the Command Position registers (R0CH, R0DH, and
R0EH) and the Actual Position registers (R12H, R13H, and
R14H) to zero. After the Align mode has been executed, the
HCTL-1100 will automatically enter the Position Control mode and go to position zero. By following this procedure, the largest movement in the Align mode will be one torque cycle of the motor.
The Align mode assumes: the encoder index pulse has been physically aligned to the last motor phase during encoder/ motor assembly, the Commutator parameters have been correctly preprogrammed (see the section called Commutator for details), and a hard reset has been executed while the motor is stationary.
The Align mode first disables the
Commutator and with open loop control enables the first phase
(PHA) and then the last phase
(PHC or PHD) to orient the motor on the last phase torque detent.
Each phase is energized for 2048 system sampling periods (t). For proper operation, the motor must come to a complete stop during the last phase enable. At this point the Commutator is enabled and commutation is closed loop.
The Align mode is executed only when using the commutator feature of the HCTL-1100. This mode automatically aligns multiphase motors to the HCTL-
1100’s internal Commutator.
The Align mode can be entered only from the Initialization/Idle mode by writing 02H to the
Program Counter register (R05H).
The HCTL-1100 then automatically switches from the Align mode to Position Control mode.
Control Modes
Control flags F0, F3, and F5 in the Flag register (R00H) determine which control mode is executed. Only one control flag can be set at a time. After one of
30
these control flags is set, the control modes are entered either automatically from Align or from the Initialization/Idle mode by writing 03H to the Program
Counter (R05H).
Position Control Mode
Flags: F0 Cleared
F3 Cleared
F5 Cleared
Registers Used:
Register Function
R00H R00D Flag Register
R12H R18D Read Actual
Position MSB
R13H R19D Read Actual
Position
R14H R20D Read Actual
Position LSB
R0CH R12D Command
Position MSB
R0DH R13D Command
Position
R0EH R14D Command
Position LSB
Position Control performs pointto-point position moves with no velocity profiling. The user specifies a 24-bit position command, which the controller compares to the 24-bit actual position. The position error is calculated, the full digital lead compensation is applied and the motor command is output.
The controller will remain position-locked at a destination until a new position command is given.
The actual and command position data is 24-bit two’s-complement data stored in six 8-bit registers.
Position is measured in encoder quadrature counts.
The command position resides in
R0CH (MSB), R0DH, R0EH
(LSB). Writing to R0EH latches all 24 bits at once for the control algorithm. Therefore, the command position is written in the sequence R0CH, R0DH and
R0EH. The command registers can be read in any desired order.
The actual position resides in
R12H (MSB), R13H, and R14H
(LSB). Reading R14H latches the upper two bytes into an internal buffer. Therefore, Actual Position registers are read in the order of
R14H, R13H, and R12H for correct instantaneous position data.
The largest position move possible in Position Control mode is
7FFFFFH (8,388,607D) quadrature encoder counts.
Proportional Velocity Mode
Flags: F0 Cleared
F3 Set
F5 Cleared
Registers Used:
Register Function
R00H R00D Flag Register
R23H R35D Command
Velocity LSB
R24H R36D Command
Velocity MSB
R34H R52D Actual Velocity
LSB
R35H R53D Actual Velocity
MSB
Proportional Velocity Control performs control of motor speed using only the gain factor, K, for compensation. The dynamic pole and zero lead compensation are not used. (See the “Digital Filter” section of this data sheet.)
Example Code to Program Position Moves
{ Begin }
Hard Reset { HCTL-1100 goes into INIT/IDLE Mode }
Initialize Filter, Timer, Command Position Registers
Write 03H to Register R05H
{ HCTL-1100 is now in Position Mode }
Write Desired Command Position to Command Position Registers
{ Controller Moves to new position }
Continue writing in new Command Positions
{ end }
31
The command and actual velocity are 16-bit two’s-complement words.
The command velocity resides in registers R24H (MSB) and R23H
(LSB). These registers are unlatched which means that the command velocity will change to a new velocity as soon as the value in either R23H or R24H is changed. The registers can be read or written to in any order.
R24H R23H
IIII IIII IIII FFFF
COMMAND VELOCITY FORMAT
The units of velocity are quadrature counts/sample time. To convert from rpm to quadrature counts/sample time, use the formula shown below:
Vq = (Vr)(N)(t)(0.01667/rpm-sec) [9]
Where:
Vq = velocity in quadrature counts/sample time
Vr = velocity in rpm
N = 4 times the number of slots in the codewheel (i.e., quadrature counts).
t = The HCTL-1100 sample time in seconds. (See the section on the HCTL-1100’s Sample Timer register).
Because the Command Velocity registers (R24H and R23H) are internally interpreted by the
HCTL-1100 as 12 bits of integer and 4 bits of fraction, the host processor must multiply the desired command velocity (in quadrature counts/sample time) by 16 before programming it into the HCTL-1100’s Command
Velocity registers.
The actual velocity is computed only in this algorithm and stored in scratch registers R35H (MSB) and R34H (LSB). There is no fractional component in the actual velocity registers and they can be read in any order.
The controller tracks the command velocity continuously until new mode command is given. The system behavior after a new velocity command is governed only by the system dynamics until a steady state velocity is reached.
Integral Velocity Mode
Flags: F0 Cleared
F3 Cleared
F5 Set to begin move
Registers Used:
Register Function
R00H R00D Flag Register
R26H R38D Acceleration LSB
R27H R39D Acceleration MSB
R3CH R60D Command
Velocity
Integral Velocity Control performs continuous velocity profiling which is specified by a command velocity and command acceleration. Figure 13 shows the capability of this control algorithm.
The user can change velocity and acceleration any time to continuously profile velocity in time.
Once the specified velocity is reached, the HCTL-1100 will maintain that velocity until a new command is specified. Changes between actual velocities occur at the presently specified linear acceleration.
The command velocity is an 8-bit two’s-complement word stored in
R3CH. The units of velocity are quadrature counts/sample time.
Example Code for Programming Proportional Velocity Mode
{ Begin }
Hard Reset { HCTL-1100 goes into INIT/IDLE Mode }
Initialize Filter, Timer, Command Position Registers
Write 03H to Register R05H
{ HCTL-1100 is now in Position Mode }
Write Desired Command Velocity (if needed)
Set Flag F3 {Proportional Velocity Move Begins}
{ System ramps to Command Velocity }
{end}
Continue writing new Command Velocities
32
The conversion from rpm to quadrature counts/sample time is shown in equation 9. The
Command Velocity register
(R3CH) contains only integer data and has no fractional component.
While the overall range of the velocity command is 8 bits, two’scomplement, the difference between any two sequential commands cannot be greater than
7 bits in magnitude (i.e., 127 decimal). For example, when the
HCTL-1100 is executing a command velocity of 40H
(+64D), the next velocity command must fall in the range of
7FH (+127D), the maximum command range, C1H (-63D), the largest allowed difference.
The command acceleration is a
16-bit scalar word stored in R27H and R26H. The upper byte
(R27H) is the integer part and the lower byte (R26H) is the fractional part provided for resolution. The integer part has a range of 00H to 7FH. The contents of R26H are internally divided by 256 to produce the fractional resolution.
Ar = Acceleration in rpm/sec
N = 4 times the number of slots in the codewheel (i.e., quadrature counts) t = The HCTL-1100 sample time in seconds. (See the section on the HCTL-1100’s Sample Timer register).
Because the Command Acceleration registers (R27H and R26H) are internally interpreted by the
HCTL-1100 as 8 bits of integer and 8 bits of fraction, the host processor must multiply the desired command acceleration (in quadrature counts/[sample time]
2
) by 256 before programming it into the HCTL-1100’s Command
Acceleration registers.
Internally, the controller performs velocity profiling through position control.
Each sample time, the internal profile generator uses the information which the user has programmed into the Command
Velocity register (R3CH) and the
Command Acceleration registers
(R27H and R26H) to determine the value which will be automatically loaded into the Command
Position registers (R0CH, R0DH, and R0EH). After the new command position has been generated, the difference between the value in the Actual Position registers (R12-R13H, and R14H) and the new value in the
Command Position registers is calculated as the new position error. This new position error is used by the full digital compensation filter to compute a new motor command output by this sample time. The register block in Figure
3 further shows how the internal profile generator works in
Integral Velocity mode. In control theory terms, integral compensation has been added and therefore, this system has zero steadystate error.
Although Integral Velocity Control mode has the advantage over
Proportional Velocity mode of zero steady state velocity error, its disadvantage is that the closed
R27H R26H
0IIIIIII FFFFFFFF/256
Command Acceleration Format
The units of acceleration are quadrature counts/sample time squared.
To convert from rpm/sec to quadrature counts/[sample time]
2
, use the formula shown below:
Aq = (Ar)(N)(t
2
)(0.01667/rpmsec) [10]
Where:
Aq = Acceleration in quadrature counts/[sample time]
2
Figure 13. Integral Velocity Modes.
33
loop stability is more difficult to achieve. In Integral Velocity
Control mode the system is actually a position control system and therefore the complete dynamic compensation D(z) is used.
If the external Stop flag F6 is set during this mode signalling an emergency situation, the controller automatically decelerates to zero velocity at the presently specified acceleration factor and stays in this condition until the flag is cleared. The user then can specify new velocity profiling data.
Trapezoid Profile Mode
Flags: F0 Set to begin move
F3 Cleared
F5 Cleared
Registers Used:
Register Function
R00H R00D Flag Register
R07H R07D Status Register
R12H R18D Read Actual
Position MSB
R13H R19D Read Actual
Position
R14H R20D Read Actual
Position LSB
R29H R41D Final Position
LSB
R2AH R42D Final Position
R2BH R43D Final Position
MSB
R26H R38D Acceleration LSB
R27H R39D Acceleration MSB
R28H R40D Maximum
Velocity
Trapezoid Profile Control performs point-to-point position moves and profiles the velocity trajectory to a trapezoid or triangle. The user specifies only the desired final position, acceleration and maximum velocity. The controller computes the necessary profile to conform to the command data. If maximum velocity is reached before the distance halfway point, the profile will be trapezoidal, otherwise the profile will be triangular. Figure 14 shows the possible trajectories with Trapezoidal Profile Control.
The command data for
Trapezoidal Profile Control mode consists of a final position, a command acceleration, and a maximum velocity. The 24-bit,
Example Code for Programming Integral Velocity Mode
(Begin)
Hard Reset {HCTL-1100 goes into INIT/IDLE Mode}
Initialize Filter, Timer, Command Position Registers
Write 03H to Register R05H
{HCTL-1100 is now in Position Mode}
Write Desired Acceleration (if needed)
Write Desired Maximum Velocity (if needed)
Set Flag F5 {Integral Velocity Move Begins}
{System ramps to Maximum Velocity}
Continue writing new Accelerations and Velocities
{ end }
34
Figure 14. Trapezoidal Profile Mode.
two’s-complement final position is written to registers R2BH, (MSB),
R2AH, and R29H (LSB). The 16bit command acceleration resides in registers R27H (MSB) and
R26H (LSB). The command acceleration has the same integer and fraction format as discussed in the Integral Velocity Control mode section. The 7-bit maximum velocity is a scalar value with the range of 00H to 7FH (0D to
127D). The maximum velocity has the units of quadrature counts per sample time, and resides in register R28H. The command data registers may be read or written to in any order.
The internal profile generator produces a position profile using the present Command Position
(R0CH-R0EH) as the starting point and the Final Position
(R2BH-R29H) as the end point.
Once the desired data is entered, the user sets flag F0 in the Flag register (R00H) to commence motion (if the HCTL-1100 is already in Position Control mode).
When the profile generator sends the last position command to the
Command Position registers to complete the trapezoidal move, the controller clears flag F0. The
HCTL-1100 then automatically goes to Position Control mode with the final position of the trapezoidal move as the command position.
When the HCTL-1100 clears flag
F0 it does NOT indicate that the motor and encoder are at the final position NOR that the motor and encoder have stopped. The flag indicates that the command profile has finished. The motor and encoder’s true position can only be determined by reading the
Actual Position registers. The only way to determine if the motor and encoder have stopped is to read the Actual Position registers at successive intervals.
The status of the Profile flag can be monitored both in the Status register (R07) and at the external
Profile pin at any time. While the
Profile flag is high NO new command data should be sent to the controller.
Each sample time, the internal profile generator uses the information which the user has programmed into the Maximum
Velocity register (R28H), the
Command Acceleration registers
(R27H and R26H), and the Final
Position registers (R2BH, R2AH, and R29H) to determine the value which will be automatically loaded into the Command Position registers (R0EH, R0DH, and
R0CH). After the new command position has been generated, the difference between the value in the Actual Position registers
(R12H, R13H, and R14H) and the new value in the Command
Position registers is calculated as the new position error. This new position error is used by the full digital compensation filter to compute a new motor command output for the sample time. (The register block diagram in Figure 3 further shows how the internal profile generator works in
Trapezoidal Profile mode.)
35
Example Code for Programming Trapezoid Moves
{ Begin }
Hard Reset { HCTL-1100 goes into INIT/IDLE Mode }
Inititalize Filter, Timer, Command Position Registers
Write 03H to Register R05H
{ HCTL-1100 is now in Position Mode }
{ Profile #1}
Write Desired Acceleration
Write Desired Maximum Velocity
Write Final Position
Set Flag F0 {Trapezoid Move Begins, PROF pin goes high}
Poll PROF pin until it goes low (Move is complete)
{ Profile #2}
Write Desired Acceleration
Write Desired Maximum Velocity
Write Final Position
Set Flag F0 {Trapezoid Move Begins, PROF pin goes high}
Poll PROF pin until it goes low (Move is complete)
.
.
{ Repeat }
.
.
{ end }
Applications of the HCTL-1100
Interfacing the HCTL-1100 to Host
Processors
The HCTL-1100 looks to the host microprocessor like a bank of 8bit registers to which the host processor can read and write (i.e., the host processor treats the
HCTL-1100 like RAM). The data in these registers controls the operation of the HCTL-1100. The host processor communicates to the HCTL-1100 over a bidirectional multiplexed 8-bit data bus. The four I/O control lines. ALE, CS, OE, and R/W execute the data transfers (see
Figure 15).
36
There are three different timing configurations which can be used to give the user greater flexibility to interface the HCTL-1100 to most microprocessors (see
Timing diagrams). They are differentiated from one another by the arrangement of the ALE signal with respect to the CS signal. The three timing configurations are listed below.
1. ALE, CS non-overlapped
2. ALE, CS overlapped
3. ALE within CS
Any I/O operation starts by asserting the ALE signal which starts sampling the external bus into an internal address latch.
Rising ALE or falling CS during
ALE stops the sampling into the address latch.
CS low after rising ALE samples the external bus into the data latch. Rising CS stops the sampling into the data latch, and starts the internal synchronous process.
In the case of a write, the data in the data latch is written into the addressed location. In the case of a read, the addressed location is written into an internal output latch. OE low enables the internal output latch onto the external bus. The OE signal and the internal output latch allow the I/O port to be flexible and avoid bus conflicts during read operations.
It is important that the host microprocessor does not attempt to perform too many I/O operations in a single sample time of the HCTL-1100. Each
I/O operation interrupts the execution of the HCTL-1100’s internal code for 1 clock cycle.
Although extra clock cycles have been allotted in each sample time for I/O operations, the number of extra cycles is reduced as the value programmed into the
Sample Timer register (R0FH) is reduced.
Table 5 shows the maximum number of I/O operations allowed under the given conditions.
The number of external clock cycles available for I/O operations in any of the four control modes can be increased by increasing the value in the Sample Timer register (R0FH).
For every unit increase in the
Sample Timer register (R0FH) above the minimums shown in
Table 5 the user may perform 16 additional I/O operations per sample time.
Interfacing the HCTL-1100 to
Amplifiers and Motors
The Motor Command port is the ideal interface to an 8-bit DAC, configured for bipolar output. The
Sample Timer
Register Value
07H (07D)
OFH (15D) data written to the 8-bit Motor
Command port by the control algorithms is the internally computed 2’s-complement motor command with an 80H offset added. This allows direct interfacing to a DAC. Figure 16 shows a typical DAC interface to the HCTL-1100. An inexpensive
DAC, such as MC1408 or equivalent, has its digital inputs directly connected to the Motor
Command port. The DAC produces an output current which is converted to a voltage by an operational amplifier. R
O
and R
G control the analog offset and gain.
The circuit is easily adjusted for
+5 V to –5 V operation by first writing 80H to R08H and adjusting R
O
for 0 V output. Then
FFH is written to R08H and R
G adjusted until the output is 5 V.
is
Note that 00H in R08H corresponds to –5 V out.
Figure 17 shows an example of how to interface the HCTL-1100 to an H-bridge amplifier. An Hbridge amplifier allows bipolar motor operation with a unipolar power supply.
Table 5. Maximum Number of I/O Allowed
Operating Mode
Position Control or
Prop. Vel. Control
Position Control or
Prop. Vel. Control
Trapezoidal Prof.
or Integral
Vel. Control
Maximum Number of I/O Operations
Allowed per Sample
5
133
6
37
Figure 15. I/O Port Block Diagram.
2.5 K
(LSB) MC
0
MC
1
MC
2
HCTL-1000
MC
3
MC
4
MC
5
MC
6
(MSB) MC
7
21
22
23
24
25
18
19
20
7
6
9
8
5
12
11
10
A
6
A
5
A
4
15
A
V ref+
8
(LSB)
A
7
MC1408
2
GND
V
CC
V ref+
A
3
A
2
A
1
(MSB)
COMP
16
V
EE
3
I
O
13
14
4
2.5 K
75 pf
–12 V
Figure 16. Linear Amplifier Interface.
+5 V +5 V
R
O
5 K
R
L
5 K
2
3
X–
LF356
X+
6
V
OUT
UDN2954W
A
K
K
RC V
CC
PH OE
A
1 2 3 4 5 6 7 8 9 10 11 12
30 K
+V
MOTOR
+5 V
10 µF
SIGN
PULSE
DC MOTOR
Figure 17. H-Bridge Amplifier Interface.
38
Additional Information From Avago
Technologies
Application notes and Application briefs regarding the HCTL-1100 are from the Avago Technologies
Motion Control Factory. Please contact your local Avago sales representative for more information.
- M003 - Z80 Interface to the
HCTL-1100
- M005 - Sample Timer and
Digital Filter
- M009 - List of Board Level
Vendors Using HCTL-1100
- M010 - HCTL-1100 Trouble
Shooting Guide
- M012 - Commutator Port in the
HCTL-1100
- M015 - Interfacing the HCTL-
1100 to the 8051
- M016 - 8051/HCTL-1100 Stand
Alone Controller with RS232
Port
- M018 - The Effects of High-
Frequency Noise on the HCTL-
1100
- M021 - Interfacing the HCTL-
1100 to 68HC11.
- M024 - Using the HCTL-1100 with DC Brush Motors.
- M025 - Using the HCTL-1100 with DC Brushless Motors.
- M026 - Using the HCTL-1100 with Stepper Motors.
Ordering Information
HCTL-1100: 40 Pin DIP Package
HCTL-1100#PLC: 44 Pin PLCC
Package
39
For product information and a complete list of distributors, please go to our website:
www.avagotech.com
Avago, Avago Technologies, and the A logo are trademarks of Avago Technologies Limited in the United States and other countries.
Data subject to change. Copyright © 2006 Avago Technologies Limited. All rights reserved. Obsoletes 5988-4215EN
5988-5896EN June 7, 2006
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement