LPB and BSB plants

Web server OZW672... V4.0

Commissioning instructions

OZW672.01

OZW672.04

OZW672.16

CE1C5712en

28.08.2012

Building Technologies

Siemens Switzerland Ltd

Infrastructure & Cities Sector

Building Technologies Division

Gubelstrasse 22

CH-6301 Zug

Tel. +41 41-724 24 24 www.siemens.com/sbt

2 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

© 2010-2012 Siemens Switzerland Ltd

Subject to change

CE1C5712en

28.08.2012

Table of contents

1

1.1

1.2

Overview ..................................................................................................7

Introduction ...............................................................................................7

Display and operating elements................................................................8

1.3

Web operation...........................................................................................9

1.3.1

User levels ..............................................................................................10

1.4

Symbols, notations, abbreviations .......................................................... 11

1.4.1

Symbols .................................................................................................. 11

1.4.2

Notations .................................................................................................12

1.4.3

Abbreviations ..........................................................................................12

2

2.1

Commissioning .....................................................................................13

Prerequisites ...........................................................................................13

2.2

Getting started.........................................................................................14

2.2.1

Turn on web server .................................................................................14

2.2.2

Log into web server.................................................................................15

2.3

Administer user accounts........................................................................16

2.4

Create device web pages .......................................................................18

2.5

Web server settings ................................................................................22

2.5.1

Operating page settings "Time of day/date" ...........................................22

2.5.2

Operating page settings "Settings" .........................................................23

2.5.3

Operating page settings "Message recipient".........................................30

2.6

Commission network components ..........................................................32

2.6.1

Operator station on a local area network (LAN) .....................................32

2.6.2

Router .....................................................................................................33

2.7

Functional check .....................................................................................34

2.8

Additional settings...................................................................................36

2.9

Final steps...............................................................................................37

2.9.1

Check faults ............................................................................................37

2.9.2

Final steps on web server .......................................................................37

2.10

Supply state ............................................................................................38

2.11

Update software ......................................................................................38

3

3.1

Operate using a web browser..............................................................39

Overview .................................................................................................39

3.2

Operate the plant ....................................................................................41

3.2.1

Bus device operation ..............................................................................41

3.2.2

Operate web server ................................................................................41

3.2.3

Web server diagnostics...........................................................................44

3.3

Faults ......................................................................................................47

3.3.1

Overview .................................................................................................47

3.3.2

Web server fault ......................................................................................47

3.4

3.5

File transfer .............................................................................................48

Operation with ACS790...........................................................................51

Siemens

Building Technologies

Web server OZW672... V4.0

Table of contents

3 / 116

CE1C5712en

28.08.2012

4

4.1

4.2

4.3

4.4

4.5

4.6

Visualize plants .....................................................................................53

Overview .................................................................................................53

Example of a plant web page..................................................................54

Plant web page features .........................................................................55

Toolbar.....................................................................................................56

Import web-capable plant diagrams........................................................57

Create own plant web pages...................................................................59

5

"Energy indicator" function .................................................................63

5.1

Introduction..............................................................................................63

5.1.1

Function description ................................................................................63

5.1.2

LPB/BSB bus topology............................................................................64

5.1.3

LPB/BSB devices ....................................................................................65

5.1.4

Navigation and device web pages ..........................................................65

5.2

"Energy indicator" function levels............................................................66

5.2.1

"Plant" level .............................................................................................66

5.2.2

"Partial plants" level.................................................................................67

5.2.3

"Data points" level ...................................................................................68

5.2.4

Number of "Monitored data points" .........................................................69

5.2.5

"Energy indicator" visibility ......................................................................70

5.2.6

Summary display "Energy indicator" for a plant......................................71

5.3

"Energy indicator" commissioning function .............................................72

5.3.1

Commissioning notes..............................................................................72

5.3.2

Start "Energy indicator" function..............................................................72

5.3.3

Estimated processing time ......................................................................73

5.3.4

Deactivating "Data point monitoring".......................................................73

5.3.5

Activating "Data point monitoring"...........................................................75

5.4

Dialog boxes, data points, and "Green limits" .........................................77

5.4.1

General dialog boxes ..............................................................................77

5.4.2

Dialog boxes with numeric data points....................................................78

5.4.3

Dialog boxes with enumeration data points ............................................79

5.4.4

User groups "Service" and "End user" ....................................................79

5.5

E-mail with "Energy indicator" for the plant.............................................80

5.5.1

E-mail receiver configuration...................................................................80

5.5.2

Mail inbox ................................................................................................81

5.5.3

E-mail contents........................................................................................82

5.6

Exceptions...............................................................................................83

6

Communications ...................................................................................85

6.1

Remote operation....................................................................................85

6.1.1

Local area network (LAN) .......................................................................85

6.1.2

Remote operation via the Internet...........................................................89

6.2

Messages via e-mail ...............................................................................93

7

7.1

Appendix ................................................................................................99

General notes..........................................................................................99

7.2

Diagnostics..............................................................................................99

7.2.1

Web server fault codes ...........................................................................99

7.2.2

Windows commander............................................................................100

4 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Table of contents

CE1C5712en

28.08.2012

7.3

Communications ...................................................................................101

7.3.1

Internet protocol ....................................................................................101

7.3.2

Free e-mail account providers ..............................................................101

7.3.3

Install RNDIS driver...............................................................................102

7.3.4

Alternative network configuration..........................................................103

7.3.5

Siemens routers....................................................................................105

7.4

Glossary of Ethernet and Internet terms...............................................106

Index .............................................................................................................. 113

Siemens

Building Technologies

Web server OZW672... V4.0

Table of contents

5 / 116

CE1C5712en

28.08.2012

6 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Table of contents

CE1C5712en

28.08.2012

Type summary

Document contents

Focus on web browser operation

Important notes

Safety /

Product liability

Intended use

Disposal

1 Overview

1.1 Introduction

Product number

OZW672.01

OZW672.04

OZW672.16

Max. number of monitored devices

1 LPB or 1 BSB device

4 LPBs or 1 BSB device(s)

16 LPBs or 1 BSB device(s)

The document describes commissioning and operating the web server OZW672.

In this edition of "Web server OZW672, V4.0", the new "Energy indicator" function

is described in Section 5. Sections 2 and 6 contain supplementary information on

the DHCP client.

The ACS790 PC software can also be used to commission and operate the web server OZW672. To simplify reading, this document focuses on commissioning and operating via web browser.

This symbol draws your attention to special safety notes and warnings.

Ignoring this type of note may result in device damage and personal injury.

• Devices may only be used in building technical plants and for the described applications only. Comply with all local regulation (installation, etc.).

• Disconnect the power and immediately replace a defective or obviously damaged device.

• Do not open the device. Failure to comply will invalidate any warranty claims.

• The technical data are provided solely for use with Siemens bus devices. The user ensures the functionality of operation when using third-party devices not expressly mentioned here. Siemens assumes no responsibility for service and warranty under these circumstances.

Trouble-free and safe product operation presupposes transport, storage, mounting, installation, and commissioning as intended as well as careful operation.

Dispose of the device as electronic waste in compliance with European directive

2002/96/EEC (WEEE) and not as municipal waste. Observe all corresponding national, legal regulations, and dispose of the device via appropriate channels.

Comply with all locally applicable laws and regulations.

Siemens

Building Technologies

Web server OZW672... V4.0

Overview

7 / 116

CE1C5712en

28.08.2012

1.2 Display and operating elements

Overview

Pos

1

Name

On LED, Operation and

"Energy indicator"

6

7

8

2 A

3 B

LPB/BSB LED

No function

4

Fault LED

5 (LED) No function

Remote button

Service button

Message suppression switch

9

No function

LED displays

1 (red/ green/orange)

2 LPB/BSB A

(green)

• Dark

• Steady red

• Flashing red

• Steady green

No power.

Web server starts operating system.

Web server starts application.

Web server operational, "Energy indicator" = "Green leaf".

• Steady orange

Web server operational, "Energy indicator" = "Orange leaf".

• Dark

• Lit

• Flashing

No bus power.

LPB/BSB operational.

Communication on LPB/BSB.

3 (LED) B

4 Faults (red)

• Dark

• Lit

No fault (normal operating state).

Fault exists.

5 (LED)

Operating buttons

6 Remote

7 Service

Button combinations

8

9

and

Switch

Message inhibition

(DIP switches)

• Long (> 6 s)

• Long (> 6 s)

Sends system report to fault e-mail recipients

(not to "Energy indicator" recipients)

See "Button combinations".

• Long (> 6 s)

Simultaneously press and restores default factory settings.

Note : All configuration data and settings are reset. The device list, uploaded files, and all unsent messages are deleted. History data is not deleted.

• Position "On" Messages cannot be sent.

• Position "Off" Message sending allowed.

No

8 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Overview

CE1C5712en

28.08.2012

Use the web browser to operate the web server. The main window is sub-divided into various display areas.

1 Primary navigation

2 Secondary

navigation

3 Command sequence

4 User

5 Plant state

fault

6 Plant state

Energy indicator

7 Plant name

8 Display

9 Logo area

The following main functions are selected via primary navigation:

Home

Energy indicator

Faults

File transfer

Menu-based plant and device operation.

Display and operate "Energy indicator" data points.

Display system faults.

Download of event history, upload of documents, logos and system definitions.

Device web pages Create device list and operating pages.

Device operation (via home) queries devices and their operating pages via secondary navigation (menu tree).

The path displays the workflow starting at the main menu to the open operating page. Simply click at any point on the path to return to that location.

This field shows the currently logged-in user. Clicking [Logout] ends the current session. The session remains active until logout.

The "Plant state fault" field is displayed permanently:

• Green field: No fault

• Red field: Plant fault

Click the "Plant state fault" field to display all faults in the plant.

The "Plant state Energy indicator" field is displayed permanently:

• Green leaf: All "Energy indicator" data points are always within their "green limits", i.e. "within the green/allowed range".

• Orange leaf: One or multiple "Energy indicator" data points are outside their "green limits"

Clicking the "Plant state Energy indicator" field opens the "Energy indicator" function.

Displays plant name as entered.

The display range displays content corresponding to the selected function via primary and secondary navigation.

Shows Logo 1 and Logo 2.

Siemens

Building Technologies

Web server OZW672... V4.0

Overview

9 / 116

CE1C5712en

28.08.2012

End user

1.3.1 User levels

Display and operation depend on the access level of the logged in user:

• Operate end user data.

• Fault overview

• Administer own user account.

Service • Operate service and end user data.

• Fault overview

• Documents, Message history, Logos, and System definitions.

• Administer own user account.

Administrator • Operate service and end user data.

• Fault overview

• Documents, Message history, Logos and System definitions.

• Administer all user accounts.

• Create device websites.

10 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Overview

CE1C5712en

28.08.2012

Symbols

1.4 Symbols, notations, abbreviations

1.4.1 Symbols

Symbol Meaning

Data point at the service level.

Data point at the end user level.

Read/write data point; the setting value can be changed.

Read-only data point; the value cannot be changed.

Link to entry field.

Delete object.

Checkbox.

Selection box.

Calendar.

Arrows to incrementally adjust values.

Adjustment tab.

/

Arrow to display sort order.

Up.

File upload (to web server).

File download (from web server).

Safety note, intended to protect against misuse.

Always observe/follow.

Note; important information.

Network connection.

Link to device.

User.

Message history.

System definitions

Logos.

,

Switch over displays: Full view, partial view

/

Fault indication: Green field = no fault; red field = fault (alarm)

"Green leaf"

"Orange leaf"

"Grey leaf"

Siemens

Building Technologies

Web server OZW672... V4.0

Overview

11 / 116

CE1C5712en

28.08.2012

Command sequences

IP address, domains

Buttons

Abbreviations

1.4.2 Notations

Menu command sequences are printed as follows:

• Web server: Home > 0.5 OZW672... > Settings > Time of day/date

• PC: Start > Settings > Network connections > Local Area Connection

OZW672... stands for: OZW672.01 or

OZW672.16

Entry in the web browser address line:

• IP address:

• Domains:

Buttons are written as follows: [ Add ]

1.4.3 Abbreviations

Auto MDI-X

DHCP

DynDNS

HTTP

HTTPS

Auto Medium Dependent Interface - Crossed

Dynamic Host Configuration Protocol

Dynamic Domain Name System

Hyper Text Transfer Protocol

Hyper Text Transfer Protocol Secure

LPB

BSB

Local Process Bus

Boiler System Bus

RNDIS

SMTP

Remote Network Driver Interface Specification

Simple Mail Transfer Protocol

TCP

TLS

UPnP

USB

Transmission Control Protocol

Transport Layer Security

Universal Plug and Play

Universal Serial Bus

Web API Web Application Programming Interface

Further explanations on abbreviations and terms are available in the appendix.

12 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Overview

CE1C5712en

28.08.2012

Prerequisites

Notes

2 Commissioning

This section describes how to commission the web server.

2.1 Prerequisites

The following conditions must be met to commission the web server:

• The web server is mounted and wired (see Installation instructions, G5711).

• The connected bus device is commissioned.

• The bus device has a valid address and is operational.

• The bus device works trouble free; the fault LED is not lit.

• The bus power supply to the bus device is turned on.

• Recommended by clock time supplier: The LPB bus device is clock slave with remote setting.

• Connecting a SmartPhone App to a web server makes sense only after the web server is fully commissioned.

• IP address USB: 192.168.250.1

(cannot be changed)

IP address Ethernet: As per the address assigned by the router.

Without router: 192.168.2.10

(default state,

see Section 6.1.1)

• Commissioning with a PC/laptop and a web browser via the USB interface.

The RNDIS driver must be installed to connect via USB.

• The RNDIS driver is automatically installed when connecting via USB if the

PC/laptop is connected to the Internet (as long as the Microsoft online update is enabled). You can manually install the RNDIS driver when there is no

connection to the Internet (see Section 7.3.3).

• The RNDIS driver is supplied on the web server at http://<IP-Adresse>/drivers/.

• To navigate, always start with primary navigation, then use the secondary navigation to select the desired menu item.

• Return: Click "Upward" or navigate via the path or primary navigation.

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

13 / 116

CE1C5712en

28.08.2012

Turn on web server

2.2.1 Turn on web server

Connect the web server to the power supply and connect it to the PC:

1. Connect power supply to turn on power on web server. The web server is operational, when the green LED is lit.

2. Check additional displays:

• LED A

Green light if LPB/BSB bus power supply is available. Check the LPB/BSB bus wiring and setting for the bus power supply on the bus device if no bus power supply is available.

• LED

Dark if no fault is pending. You can resolve pending faults later (see

Section 2.9).

3. Plug the supplied USB cable into the web server and the PC and start up the

PC. The PX recognizes the web server as a USB device. Otherwise, the

RNDIS is still not installed.

Note

4. The RNDIS driver is installed automatically if the PC is connected to the Internet and no RNDIS driver is installed. The installation wizard will guide you through installation.

You can also manually set up the RNDIS driver (see Section 7.3.3).

14 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

Log on

2.2.2 Log into web server

A PC with USB interface and web browser is used to commission the web server.

1. Start web browser.

2. In the address line, enter the USB IP address ( 192.168.250.1

).

3. First time Login

• User name Administrator

• Password Password

4. Click [ Login ] to finish.

5. After logging on the first time, the dialog box is displayed to define a new password.

Important note

A new password must be defined the first time you log in (you can also change the language).

• You cannot exit the dialog box if you do not define a new password (i.e. not equal to "Password") and the following note is displayed:

• The following message is displayed if you fail to fill out all required fields:

• Capitalization must be observed when entering the password.

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

15 / 116

CE1C5712en

28.08.2012

Administer user accounts

Note

Use the "User accounts" menu to change the administrator password at delivery and set up additional user accounts.

The user account settings equally apply to access via Smartphone app and other applications via Web API.

Change administrator data

Procedure:

1. Click red pencil symbol

.

The "Change user" dialog box opens.

Add a new user

2. Change administrator data:

- Password

- Repeat Password

- Description (optional)

- Email address (optional)

- Language: English

3. Click [ OK ] to finish.

Procedure:

1. Click [ Add ]

The "Add user" dialog box is displayed.

2. Enter / select user data:

- User name

- Password

- Repeat password

- Description (optional)

- E-mail address (optional)

- Language: English

- User group

3. Close with [ OK ]

16 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

Change user data

Procedure:

1. Click red pencil symbol for the corresponding user.

The "Change user" dialog box opens.

Delete user account

Notes

2. Change user data:

- User name

- Password

- Repeat password

- Description (optional)

- E-mail address (optional)

- Language: English

3. User group.Close with [ OK ]

Procedure:

1. Click red garbage can for the corresponding user.

The "User accounts" dialog box is displayed.

2. Click [ Yes ] for "User to be deleted?".

• The administrator account cannot be deleted. The name "Administrator" and user group "Administrator" cannot be changed. You may, however, add user accounts with administrator rights.

• You can only add new users and delete existing ones on the "Administrator" user level.

• Changing other user accounts is reserved to the "Administrator" user level.

• A secure password is comprised of lowercase and uppercase letters, numbers and special characters, is at least 20 characters long, and does not include a name or words from dictionaries.

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

17 / 116

CE1C5712en

28.08.2012

Create device websites

Note

2.4 Create device web pages

You must first add associated devices and device websites before you can operate the web server and the bus device. To this via the "Device web pages" menu.

Device web pages can only be created on the "Administrator" user level.

Notes

Add device

Note

Linked devices are listed in a table with the following information:

• Device name

• Device address Device type

• Serial number

• State

• Generated on

• Click the column header to sort the table.

• Per default, the devices are sorted in ascending device address order.

• The web server itself is already in the device list.

• Only added bus devices are monitored.

• Only generated bus devices can be operated.

• Changes to settings of the connected bus device may require that the device web pages be recreated or updated to apply changes from web operation.

• You must delete and re-add a bus device after you update the bus device software, or replace the bus device.

You can only add a device on the "Administrator" user level.

The workflow below shows how to add a bus device and create the associated device web page(s):

1. Click [ Add ]

2. Enter the bus address:

LPB: Segment number and Device number.

3. BSB: Device number (default: 1=basic device).

4. You can add just one BSB device to the device list.

5. Click [ OK ] to confirm.

The web server searches for a device with the entered bus address. It is displayed in the device list if found.

18 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

6. The added device can be named by clicking the red pencil symbol for the corresponding device . A maximum of 20 characters are available.

7. Select the devices whose web pages you want to create.

8. Click [ Generate ]

Device web pages are generated.

Process takes a few minutes

until Process finished is displayed.

In the device list, the web server and the bus device display state

"Generated".

Delete device

Note

10. The device websites are now available under Home.

You can only delete a bus device on the "Administrator" user level.

Procedure:

1. Select the bus device you want to remove from the device list .

2. Click [ Delete ]

3. Click [ Yes ] to confirm.

The web server removes the device from the device list. until Process finished is displayed.

5. Click [ OK ] confirm.

The device is removed from the device list.

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

19 / 116

CE1C5712en

28.08.2012

Create device web pages

Note

You must create device web pages for the following cases:

• After you add a device (see "Add device").

• Changes to settings of the connected bus device may require that the device web pages be recreated to apply changes from web operation.

• For changes to be applied, you must recreate the device web pages after

you update the system definition (see Section 3.4, part "Upload system

definitions").

Device web pages can only be created on the "Administrator" user level.

Procedure

1. Select the devices whose web pages you want to newly create.

2. Click [ Generate ]

Device web pages are generated.

Process takes a few minutes

until Process finished is displayed.

4. Close with [ OK ]

In the device list, the web server and the bus device display state

"Generated".

20 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

Update device websites

Notes

When you change one of the following texts, the status at the web server changes from "Generated" to "Not updated":

• Message receiver 1…4

• Fault input 1…2

• Text for: No fault

• Text for: Fault

You can change the following texts without influencing device status:

• Name (web server).

• Bus device name.

You must update the device web pages of the web server to apply all text changes to the menu.

• You can update device web pages on user levels "Administrator" and "Service".

• Click [ Update ] on the Service and [ Generate ] on the Administrator level to start updating (see "Create device web pages").

The following update procedure applies to the Service level:

1. Select the web server

.

2. Click [ Update ]

The device web pages are updated.

Process takes a few minutes

The device list for the web server display state "Generated".

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

21 / 116

CE1C5712en

28.08.2012

Notes

Time of day/date

Backup battery

2.5 Web server settings

The "Home" menu is used to set the web server. The web server and then the corresponding operating page are selected in secondary navigation.

• The settings depend on the user level.

• This section does not describe read-only data points.

2.5.1 Operating page settings "Time of day/date"

Path: Home > 0.5 OZW672… > Time of day/date

The clock has a backup battery for at least 72 hours. The clock continues to run after power failure for the duration of the backup battery.

Both date and time are reset in case of an extended interruption.

• The time is corrected automatically if the time is synchronized to the master

clock on the LPB/BSB bus (see Section 2.5.2, LPB / BSB).

• Otherwise, both date and time must be newly set.

Data point Explanation, example

Time of day/date

Default val: 00:00 1.1.2005

Setting val: Time of day/date

Set the current time and date.

Weekday is calculated automatically.

22 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

Language

Time of day/date

Note

2.5.2 Operating page settings "Settings"

Path: Home > 0.5 OZW672… > Settings > Web server

Data point

Language

Default val: English

Setting val: See example

Explanation, example

Web server language.

The language set is applied to web server fault text messages, message history, messages and system reports.

Access code for PC Software ACS790.

Code

Default val: 01

Setting val: max. 20 char.

Reset admin password *

Default val: No

Setting val: Yes

If you do not know the administrator password for the web server, setting value "Yes" again provides access to the web server via the administrator password "Password" ("Password"

= Factory setting for administrator password).

Setting value "Yes" is a temporary state, i.e. the setting value automatically goes to "No" after ca. 2 seconds.

*

*

* with PC software ACS790 only.

Path: Home > 0.5 OZW672… > Settings > Time of day/date

Changeover to daylight saving time and back is automatic. The dates are set internationally and can be changed if the international standard is changed.

Data point Explanation, example

Summer time start

Default val.: 25. March

Setting val.: 01.01...31.12.

Date for changeover to daylight saving time: On the first Sunday from this point, one hour is ad-

— ded to current time (standard time), i.e. time is adjusted forward one hour.

Date for changeover to standard time: On the Winter time start

Default val.: 25. October

Setting val.: 01.01...31.12.

first Sunday from this point, one hour is deducted from current time (daylight saving time), i.e. time is adjusted backward one hour.

Disable the function by setting both start of daylight saving and standard time to the same date.

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

23 / 116

CE1C5712en

28.08.2012

LPB / BSB

Ethernet

Notes

Path: Home > 0.5 OZW672… > Settings > Communication > LPB / BSB

Data point Explanation, example

Device number*

Default val: 5

Setting val: 5...8

Clock time source*

Default val: Autonomous

Setting val: Autonomous,

Slave with remote setting,

Slave without rem setting,

Master

Set the Device number. The device number

(segment and device number) must be unique within the same LPB bus system.

The setting is meaningless on the BSB: The

BSB device address of the web server is canned (50).

Autonomous: Time/date is created from the

Quartz of the web server. No synchronization with bus devices.

Slave with remote setting: Web server receives time/date from master. The master supplies both date and time on the web server and is then sent to all bus devices.

Slave without rem setting: Web server receives time/date from master. The web server date/time setting is not sent to the master. The master resets date/time.

Master: Time/date is created from the Quartz of the web server. The web server supplies both date and time to all bus devices.

Recommended: Configure web server as master and bus device as slave with or without remote setting.

* This setting affects the LPB only.

The Device number and time supplier are automatically specified on BSB.

Path: Home > 0.5 OZW672… > Settings > Communication > Ethernet

• Enter these settings if you intend to operate the web server on a local area network (LAN) or via the Internet.

• For more information on different network topologies, see Section 6.

Data point

Explanation, example

DHCP client

Default val: On

Setting val: Off, On

IP address

Default val: 192.168.2.10

Setting val: IP address

Subnet mask

Default val: 255.255.255.0

Setting val: IP address

Default gateway

Default val: 192.168.2.1

Setting val: IP address

Service automatically getting the web server's

IP network configuration automatically from

the router; see Section 6.1.1.

Web server IP address. Does not require setting if "DHCP client = On".

The IP subnet mask sets the size of the subnet. Does not require setting if "DHCP client = On".

The standard gateway represents the interface between the local and public network. You typically enter the IP address for the router here. Does not require setting if "DHCP client

= On".

24 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

UPnP localization

Preferred DNS server

Default val: 192.168.2.1

Setting val: IP address

The DNS server (domain name system) on the

Internet connects a globally valid name to a domain with an IP address (e.g. domain www.siemens.com

with IP address

146.254.191.150

).

The setting corresponds to the IP address for the next router or DNS server that recognizes for its part a queried name (domain) or another DNS server.

The setting is typically identical to the setting for the standard Gateway. Required to send emails. Does not require setting if "DHCP client

= On".

Alternate DNS server

Default val: (blank)

Setting val: IP address

UPnP localization

Default val: Ethernet

Setting val: ---, Ethernet, USB

The alternative DNS server is only defined for redundant systems. Settings are typically empty. Does not require setting if "DHCP client

= On".

The web server registers its presence in the network via the Universal Plug and Play

(UPnP) service.

Web server registers its existence via Ethernet, when

• "UPnP localization" = "Ethernet" is set and

• The connection between PC/laptop and the web server is active via Ethernet.

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

25 / 116

CE1C5712en

28.08.2012

E-mail

Notes

USB

UPnP localization

Path: Home > 0.5 OZW672… > > Settings > Communication > E-mail

• Enter these settings if the web server is to send an e-mail for a fault.

• Additional information on email settings is available in Section 6.2.

• Automatically negotiate the securest connection:

TLS mode is selected automatically if the device sending the email and the email provider supports it.

Data point Explanation, example

Address mail server

Default val:

smtp.example.com

Setting val:

Max. 46 characters

Port number mail server

Default val: 25

Setting val: 1…65535

The provider supplies the IP address or mail server domain name. Often referred to as the outgoing mail server or SMTP server instead of mail server.

Port number 25 is default for the mail server

(and does not normally require change).

E-mail address sender

Default val:

[email protected]

Setting value:

Max. 46 characters

Authentification mail server

Default val: No

Setting val: No/Yes

User name

Default val: (Blank)

Setting val: Max. 46 char.

The setting corresponds to the e-mail address of the web server.

The email address is displayed in the "From" field of each email.

Select Yes for mail server access with authentication.

In this case, user name and password (data points below) are required.

User name and password help authenticate each e-mail via the mail server.

Password

Default val: (Blank)

Setting val: Max. 46 char.

Signature line 1..10

Default val: (Blank)

Setting val: Max. 46 char.

Password and user name help authenticate each email via the mail server.

Signature lines are transmitted with the e-mail.

It identifies the sender, e.g. the plant's Internet address.

Path: Home > 0.5 OZW672… > Settings > Communication > USB

Data point Explanation, example

UPnP localization

Default val: USB

Setting val: ---, Ethernet, USB

The web server registers its presence in the network via the Universal Plug and Play

(UPnP) service.

Web server registers its existence in the USB network, when

• "UPnP localization" = "USB" is set and

• The connection between PC/laptop and the web server is active via USB.

26 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

Message receiver 1…4

Note

System report

Note

Path: Home > 0.5 OZW672… > Settings > Message receiver > Message receiver

1…4

The settings are made if the web server sends messages via e-mail.

Data point Explanation, example

Message receiver 1…4

Default val: (Blank)

Setting val: Max. 20 char.

Receiver type

Default val: ---

Setting val: ---, E-mail

Fault priority

Default val: All

Setting val: All,

Only urgent ones

Customizable text for message recipient. The designation is displayed in the menu and transmitted as part of the message.

Notes:

• Note Section 2.4 "Update device web pages".

• Delete the entry to reset to default text.

The following recipient types are available:

---: No messages to this recipient.

E-mail: Message recipient configured for email messages via Ethernet.

Setting value "Only urgent ones" serves as a filter when sending system reports and fault status messages.

— E-mail address

Default val: messagereceiver@

For E-mail recipient types:

Setting value is recipient email address.

example.com

Setting val: Max. 46 characters

Path: Home > 0.5 OZW672… > Settings > System report

Enter these settings if the web server is to regularly send an e-mail for a fault.

Data point Explanation, example

Signal time

Default val: 06:00 hh:mm

Setting val: 00:00...23:59

(Resol. 00:01).

Message cycle

Default val: 1 d (day)

Setting val: 0...255 d

(Resolution: 1 d)

The setting value corresponds to the time of day when a system report is sent (time can be defined).

Priority

Default val: Urgent

Setting val: Urgent / urgent

The setting value corresponds to the interval

(in days) at which a system report is sent.

The first system report is delivered after completion of the first message cycle and then as per the message cycle. The system report is disabled when the message cycle =0.

Filter when sending the system reports.

The setting "Urgent" sends the system report to all active message recipients. The setting

Not urgent exempts all message recipients subscribing to "Only urgent ones".

Waiting time to next system report. Next report

Default val: 0 d (day)

Setting val: 0...255 d

(Resolution: 1 d)

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

27 / 116

CE1C5712en

28.08.2012

Fault input 1...2

Note

Faults

28 / 116

Siemens

Building Technologies

Path: Home > 0.5 OZW672… > Settings > Inputs > Fault input 1…2

Digital inputs D1, D2 help connect potential-free status contacts. They work as fault inputs.

The following settings show how to configure fault inputs.

Select "Settings > Faults > Local > Fault input 1…2" to define behavior during faults.

Data point Explanation, example

Fault input 1…2*

Default val: (Blank)

Setting val: Max. 20 char.

Customizable text for fault input. The designation is displayed in the menu and transmitted as part of the message.

Identical to data point in "Settings > Faults >

Local > Fault input 1…2".

Normal position specifies the contact position deemed "No fault".

— Normal position

Default val: Open

Setting val: Open,

Closed

Text for: Logic 0*

Default val: 0

Setting val: Max. 20 characters

Logic 0: No fault.

Customizable text for fault input status, e.g.

Water pressure normal.

Text for: Logic 1*

Default val: 1

Setting val: Max. 20 char.

Logic 1: Fault.

Customizable text for fault input status, e.g.

Water pressure too low.

* Notes:

• Note Section 2.4, "Update device web pages".

• Delete the entry to reset to default text.

Path: Home > 0.5 OZW672… > Settings > Faults

The following settings specify behavior in case of faults.

Select "Settings > Inputs > Fault input 1…2" to configure the fault inputs.

Data point Explanation, example

Message triggering

Default val.: Coming

Setting val: Coming,

Coming and going

Fault input 1..2*

Default val.: (Blank)

Setting val: Max. 20 char.

Coming: A message is triggered when a fault is received (start of fault).

Coming and going: A corresponding message is triggered at start and end of fault. A web server fault displays the LED .

Customizable text for fault input. The designation is displayed in the menu and transmitted as part of the message.

Identical to data point in "Settings > Inputs >

Fault input 1…2".

Fault status message delay mm:ss

Default val.: 00:05.

Setting val: 00:00…59:55

00:05)

The Fault status message delay acts as a filter for short-term fault events. The time the web server must wait until a fault becomes active is set here.

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

Note

Texts

Fault priority

Default val.: Urgent

Setting val: Urgent urgent

Filter when sending a fault.

The setting Urgent sends the fault to all active message recipients. The setting Not urgent exempts all message recipients subscribing to

"Only urgent ones".

Text for: No fault*

Default val: [Fault input x] Fault.

Setting val: Max. 20 char.

Customizable text for the message for an outgoing fault at the fault input; e.g. Water pressure ok.

Text for: Fault*

Default val: [Fault input x] Fault

Setting val: Max. 20 char.

The designation is transmitted in messages.

Customizable text for the message for an incoming fault at the fault input; e.g. Fill in water.

The designation is transmitted in messages.

* Notes:

• Note Section 2.4, "Update device web pages".

• Delete the entry to reset to default text.

"System" faults refer to bus device faults received via LPB/BSB bus.

Path: Home > 0.5 OZW672... > Settings > Texts

Data point Explanation, example

Name User definable text for the plant displayed by

Default val: OZW672.01 web server and transmitted in the message.

OZW672.04

OZW672.16

Setting val: max. 20 characters regenerate web server device web page.

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

29 / 116

CE1C5712en

28.08.2012

Message receiver

Notes

Send messages

2.5.3 Operating page settings "Message recipient"

You can define time periods for each message recipient when messages can be sent.

• The following settings are optional if you want to limit the time periods when messages can be sent (default: no time limit).

• General: Messages outside sending periods are resubmitted if they are still pending during the sending period.

Path: Home > 0.5 OZW672… > Message receiver > Message receiver 1…4 >

Send messages

You can define time periods per weekday or special day when messages can be sent to the message recipients.

Special days are defined via Holidays/special days.

Data point Explanation, example

Monday...Sunday, Max 3 sending periods can be defined when

Special day web servers can send messages for each

Default val: Monday weekday and special day(s). The previous day's status is transferred to the current day.

Setting val: Monday...Sunday,

The default settings is to always send messages.

00:00…24:00

Notes

• Check to enable switching points.

• You can copy the switching times for a day of the week by clicking [ Copy ] one day to a selection of other days .

• Click [ Check ] to check the data before it is saved.

30 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

Holidays/special days

Notes

Path: Home > 0.5 OZW672… Message receiver > Message receiver 1…4 >

Holidays/special days

No messages are sent during vacation/holidays. For special days, sending periods are defined via "Send messages".

• General: Messages outside sending periods are resent during the next send period.

• If a special day occurs during a holiday/vacation, the day is a special day.

• Holidays/special days can be set as recurring days each year.

Data point Explanation, example

Entry 1...16

Default val: ---

Each recipient has a yearly calendar to enter holidays and special days.

Setting val: Beginning

End

Holiday or special day can be selected as

Reason

Annually Beginning and End of the periods can be indicated with date and time. Selecting Annually repeats the periods each year.

Notes

• Select checkbox to select active entries.

• Select "Annually" to set annually recurring switching times.

• Click [ Check ] to check the data before it is saved.

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

31 / 116

CE1C5712en

28.08.2012

Commissioning

2.6 Commission network components

The web server can be operated from a PC with web browser on a local area network (LAN) or via the Internet.

The illustration shows a typical application with operation via Internet and home network. The configuration data for the devices (IP address, Subnet mask, Default gateway und Preferred DNS server) are examples and show the various relationships (dotted lines).

2.6.1 Operator station on a local area network (LAN)

Operator station

Note

32 / 116

Siemens

Building Technologies

The operator station requires the following settings, if the web server is operated from a PC with web browser on a local area network (LAN):

• IP address

• Subnet mask

The addresses in the illustration are examples must be adapted to router

addressing. See Section 6.1.1 for more details.

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

2.6.2 Router

Router

Notes

The router settings below are required, when

• Accessing the web server from outside the local area network.

• A message is send via email for a fault.

Remote access (e.g. DSL router with Internet connection) must already set up.

A static IP address or DynDNS-capable controller with DynDNS account is prerequisite for operation via Internet.

Settings:

• NAT/PAT: Translate private parties on public IP addresses and ports.

• DynDNS: The dynamic IP address for the connection must be published if no fixed public IP address is available.

Settings depend on network type and application. The different variants are

described in Section 6.1.2.

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

33 / 116

CE1C5712en

28.08.2012

Test condition

LAN

Internet

Test message receiver

Note

Cause: Cause of error and problem solution

Connections must be tested if all settings were made to the web server as well as to system devices.

A PC on the local network is used to test operations via LAN. The log in dialog box must be displayed after entering the local IP address for the web server

(see Section 2.2.2).

We recommend using mobile participants with Internet access (Smart phone, mobile phone) to test operation over the Internet. The login dialog box must be

displayed after entering the public IP address or plant domain (see Section 3).

Do the test if the web server is to send a message or system report via e-mail for a fault.

The test is also carried out if message suppression is switched on.

Path: Home > 0.5 OZW672… > Settings > Message receiver

Data point Explanation, example

Test message receiver

Default val: ---

Setting val: Message receiver

1..4

System report sent

Display values: ---, Yes, No

Select a message receiver to test the connection to the receiver.

The display changes from "

---

" to "Yes" after a few seconds. Message sent successfully.

Cause

Display values:

---, Network cable, DNS setting,

Address mail server, Port number mail server, E-mail address receiver, Authentication mail server. See the following table.

Message inhibition

Display values: Yes, No

No: Message receiver not reached.

"Cause" displays the results of "System report sent".

For "Yes" the cause is "---"

For "No" the cause is displayed.

The first fault is displayed for multiple faults.

Shows the message suppression switch

setting (8) (see Section 1.2).

A specific cause can originate in different sources. The problem must be solved accordingly.

Cause Cause of error Solution

--- No ---

Netzwork cable No network cable or no active network connected.

Connect cable or active network. LEDs must be lit at Ethernet connection.

DNS setting DNS server could not be reached or no guaranteed network connection.

Check Setting DNS server, Default gateway, or network connection.

Table continued on next page

34 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

Cause

Address mail server

Cause of error

Address mail server not discovered by DNS server.

Port number mail server Mail server refuses connection or does not answer.

E-mail address receiver Invalid E-mail address.

Authentication mail server

Mail server refuses connection.

Inconsistent Mail server response. "Authentication mail server" contains different errors.

Encrypted mail server

(i.e. with TLS = Transport

Layer Security) may not be supported.

Solution

Check Address mail server, Default gateway, or network connection.

Check Port number mail server.

A company proxy server may block Internet connection.

Check E-mail address.

Check "Authentication mail server = Yes" and user name and

Password.

An invalid "E-mail address sender" can also result in this error.

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

35 / 116

CE1C5712en

28.08.2012

Hide devices

Note

You can determine whether a device in the device list can be operated under

"Home".

You can only hide devices on the "Administrator" user level.

Procedure:

1. Device web pages In primary navigation, select.

2. Select the device

you want to hide.

3. Click [ Hide ]

Delete history

Note

Path: Home > 0.5 OZW672… > Settings > Faults

We recommend deleting the history after you have completed commissioning.

Data point Explanation, example

Delete history

Default val: No

Setting val: Yes

Delete history of all events and messages.

Note : Setting value Yes is a temporary state, i.e. the value automatically returns to No after ca. 2 seconds.

36 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

Fault indication

Note

No fault

2.9.1 Check faults

The fault indicator displays the plant state.

No faults may be pending after commissioning. Additional information on faults

is available in Section 3.3.

The fault indicator remains green as long as no fault is pending.

Fault

The fault indicator changes to red for faults.

The most severe plant faults are displayed:

• Device name

• Fault text

Final tasks

Note

Siemens

Building Technologies

2.9.2 Final steps on web server

The final function checks are conducted on the web server, the cover is mounted and the LEDs checked.

On display and operating elements, see Section 1.2.

Procedure:

1. Unplug USB cable.

2. Switch off message suppression:

– Remove the cover

– Message suppression switch (8) must be on "Off"

.

3. Mount terminal cover.

4. Press Remote (6) button for more than 6 seconds.

– The web server sends a system report to the defined message receivers.

– Fault LED (4) displays (flashing) error in establishing communications.

5. On LED must be green.

6. Fault LED must be dark.

Web server OZW672... V4.0

Commissioning

37 / 116

CE1C5712en

28.08.2012

Restore default state

Notes

System data update

Note

Firmware update

Logo update

2.10 Supply state

The web server can be reset to factory default settings. This is probably a good idea when using the web server for another plant.

Procedure:

1. Simultaneously press buttons Remote (6) and Service (7) for more than 6 seconds.

LED On turns off. The web server restarts.

2. Wait until the web server is operational (LED On is green).

When restoring default state:

• All settings are reset to default (also applies to LPB/BSB device address and Ethernet IP address).

• The device list is deleted.

• Uploaded files are deleted.

• Unsent messages are deleted.

• History data is not deleted (must be deleted manually; see Section 2.8).

2.11 Update software

We differentiate between the following:

• System definition updates to integrate device descriptions of new devices in the web server.

• Firmware updates to update the web server to the latest firmware version. Firmware updates may also contain new device descriptions (system definitions).

The web server supports a number of bus devices and differentiates them via device descriptions. A text catalog with various languages contains all web server texts and device descriptions. The system data can be updated on site to add device descriptions for new devices or new languages retroactively.

A system definition update is a simply operational step via web browser that can.

See Section 3.4, part "Upload system definitions" for information on uploading.

Local operatings on web server required to update firmware so that remote update is not possible. Procedures are communicated for any firmware update accordingly.

The logos can be customized. See Section 3.4, part "Upload logos" for information

on uploading.

38 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Commissioning

CE1C5712en

28.08.2012

Overview

3 Operate using a web browser

This section describes web server and bus device operation via a web browser.

3.1 Overview

The plant is operated via PC, Smartphone or mobile phone with compatible web browsers via USB interface, LAN/Ethernet or Internet.

Connection

Login

Note

Enter the IP address for the interface (USB, Ethernet) or the plant’s domain name in the web browser’s address line.

The login follows:

• User name

• Password

You can automate the process by adding the login information to the web browser’s address line.

Format: <IP address>/main.app?user=<User name>&pwd=<myPassword>

Example: 10.169.9.121/main.app?user=Administrator&pwd=myPassword

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

39 / 116

CE1C5712en

28.08.2012

"Deep link"

Example

Note

You can create and save a deep link to go to a sub-page without navigating. The easiest way to do this is to copy the URL for the desired subpage and replace the browsers session ID with user name and password.

Original URL:

http://192.168.250.1/main.app?SessionId=f9d53187-2868-4a6b-8b20-

9eca4e859a4d&section=popcard&id=637&idtype=4

Available as "Deep Link": http://192.168.250.1/main.app?user=Administrator&pwd=myPassword&section

=popcard&id=637&idtype=4

The current, valid login information must be included for syntax "user=<user name>&pwd=<myPassword>".

Deep links can be rendered invalid by generating an associated bus device.

40 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

CE1C5712en

28.08.2012

Operate the plant

Devices ready for operation are displayed via "Home".

Bus device operation

Example for operating page

3.2.1 Bus device operation

Select the device in the left menu pane to operate the bus. Web server displays the top level of the menu tree. From here, you can go to all operating pages and data points.

Path: Home > 0.1 RVS61.843/109 > Heating circuit 1

Operate web server

3.2.2 Operate web server

Left-click in the menu to select web server operation. Web server displays the top level of the menu tree. From here, you can go to all operating pages and data points.

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

41 / 116

CE1C5712en

28.08.2012

Switch views

Only the following parts of the user interface are displayed to operate the web server from a smaller screen or to hide navigation:

• Plant state

• Plant name

• Display

The double arrow in the upper left-hand corner switches the view.

Full screen

Partial screen

Note In partial view, navigation to other plant web pages must be implemented using user-defined links. You can return to the full view at any time for navigation.

42 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

CE1C5712en

28.08.2012

Time of day/date

Note

Message receiver

Send messages

Path: Home > 0.5 OZW672… > Time of day/date

You can set "Time of day/date" during operation. The clock time master overwrites the time if the web server clock slave does not have remote adjustment (See

Section 2.5.1).

Data point Explanation, example

Time of day/date

Default val: 00:00 1.1.2005

Setting val: Time of day/date

Set the current time and date.

Weekday is calculated automatically.

You can define the times and days for sending messages for each message receiver.

Path: Home > 0.5 OZW672… > Message receiver > Message receiver 1…4 >

Send messages

Data point Explanation, example

Monday...Sunday, Max 3 sending periods can be defined

Special day

Default val: Monday

00:00 On …

Special

00:00 On … when web servers can send messages for each weekday and special day(s). The previous day's status is transferred to the current day.

Setting val: Monday...Sunday, day messages.

00:00…24:00

Off / On

The default settings is to always send

Notes

• Select the checkbox to enable active switching points.

• Click [ Copy ] to copy the switching times for any weekday to a number of other days .

• Click [ Check ] to check the data before it is saved.

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

43 / 116

CE1C5712en

28.08.2012

Holidays/special days

Path: Home > 0.5 OZW672… > Message receiver > Message receiver 1…4 >

Holidays/special days

Data point Explanation, example

Entry 1...16

Default val: ---

Setting val: Beginning

Each recipient has a yearly calendar to enter holidays and special days.

End

Reason

Annually

Beginning and End of the periods can be indicated with date and time. Selecting Annually repeats the periods each year.

Notes

Diagnostics

Device information

Web server

• Select checkbox to select active entries.

• Select "Annually" to set repetitive switching points.

• Click [ Check ] to check the data before it is saved.

3.2.3 Web server diagnostics

The following information is required to identify product version and settings. Infor-

mation on faults is available in Section 3.2.2.

Device information helps identify the web server.

Path: Home > 0.5 OZW672… > Device information

Data point Explanation, example

Plant name

Web server type

Production number

Software version

Build

Hardware version

Field bus module 1

Software version

Message inhibition

Web server or plant name.

Web server product number (ASN).

Device number from production.

Software version of the web server.

Revision status for the software.

Web server hardware version.

Field bus module 1 type.

Field bus module 1 software version.

Shows the setting of the message suppression switch (8).

44 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

CE1C5712en

28.08.2012

LPB / BSB

The following information displays the current settings and states on the LPB / BSB bus.

Path: Home > 0.5 OZW672… > Device information > LPB / BSB

Data point Explanation, example

Connected bus

Segment number

Device number

Clock time source

The web server autonomously identifies the bus system connected. Possible values ---, LPB,

BSB.

Part of the LPB device address.

Part of the LPB device address.

Autonomous: Time/date is created from the

Quartz of the web server. No synchronization with bus devices.

Slave with remote setting: Web server receives time/date from master. The master supplies both date and time on the web server and is then sent to all bus devices.

Slave without rem setting: Web server receives time/date from master. The web server date/time setting is not sent to the master.

The master resets date/time.

Master: Time/date is created from the Quartz of the web server. The web server supplies both date and time to all bus devices.

Last change

Recommended: Configure the web server as

Master and the bus device as slave with or without remote setting.

Number of devices max Maximum possible number of devices monitored

Number of devices by the web server on the LPB/BSB bus.

Actual number of devices monitored by the web current server on the LPB/BSB bus.

Time of last change to device list.

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

45 / 116

CE1C5712en

28.08.2012

Ethernet

You can consult the following information as needed to analyze problems on the

Ethernet. It displays the current settings for the subnet.

Path: Home > 0.5 OZW672… > Device information > Ethernet

Data point Explanation, example

IP address

Subnet mask

Alternate DNS server

Physical address

IP address of the web server. The IP address for the web server on the Ethernet ex works is:

192.168.2.10

The Subnet mask sets the size of the subnet.

A value of 255 masks the partial network; a value of 0 masks the device portion of the IP addresses on the subnet. Devices must have the same partial network to communicate directly.

The factory setting for the web server subnet mask 255.255.255.0.

The Default gateway connects the subnetwork Default gateway for the web server to additional networks, e.g. the Internet. The router typically is the default gateway.

Preferred DNS server Preferred DNS server Required to send e-mails.

The router typically is the DNS server for the web server.

An alternative DNS server is only defined for redundant systems and is typically empty.

The physical address is a unique identification for the Ethernet interface.

46 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

CE1C5712en

28.08.2012

Fault overview

3.3 Faults

3.3.1 Overview

The "Faults" function displays the most severe fault on a device in the device list. It is available to all user levels. The following information helps identify the fault:

• Fault

• Device name

• Fault information (date, time, fault code).

• Fault text

• Device address

• Device type

Note

Faults current local

Note

System faults

Note

Click to go to the corresponding device's web operation.

3.3.2 Web server faults

You can display detailed information on all faults via the "Home" menu.

Displays all web server faults.

Path: Home > 0.5 OZW672… > Faults current > Local

Data point Explanation, example

Fault 1…10 Displays for each fault:

• Fault information (date, time, fault code).

• Fault text

Overview of all web server faults included in Section 7.1.

The most severe faults are displayed for each device on the bus.

Path: Home > 0.5 OZW672... > Faults current > System > Fault 1…n

Data point Explanation, example

Fault 1..n Displayed under "Fault 1..n":

Device name, Fault information, Fault text,

Device address, Device type.

Faults for bus devices are listed in the documentation for the corresponding devices.

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

47 / 116

CE1C5712en

28.08.2012

"File transfer" helps to

• Upload documents to the web server.

• Download message history as Excel or text file.

• Upload logos.

• Upload system definitions.

Documentation

Upload

Procedure:

1. Select File transfer in primary navigation.

2. Click [ Add ]

Notes

Message history download

3. Select the desired file.

4. Click [ Upload ] to finish.

• Make sure there is enough memory for uploading.

• The Administrator and Service levels allow for uploading documents.

Procedure:

1. Select Message history from secondary navigation.

2. Click next to the desired document

(messages.txt: Text file, messages.xls: Excel file).

The "File download" dialog box opens.

Notes

48 / 116

Siemens

Building Technologies

3. Open the file with the application or save it to any location.

• Message history export is available to administrator and service user levels.

• The message history remains intact when resetting the web server to default.

Web server OZW672... V4.0

Operate using a web browser

CE1C5712en

28.08.2012

History data

The message history includes the last 500 events on faults, fault messages, and system reports. It contains the following information:

• Plant information:

– Plant name

– Phone number plant

• Information per entry:

– Event

– Plant section, i.e. device name (LPB/BSB address)

– Date of occurrence

– Time of occurrence

– Fault code+text

– Transmission date

– Transmission time

– Message receiver

– Cause

Upload logos

Siemens

Building Technologies

Procedure:

1. Select Logos from secondary navigation.

2. Save existing logo(s) as needed (see below).

3. Click .

4. Select the desired file.

Adhere to maximum dimensions (see Notes).

5.

Click [ Upload ]

6. Delete the browser cache

(Internet Explorer: Ctrl+F5, Firefox: Ctrl+R).

Save logos:

1. Click "Logo 1" or "Logo 2". The browser window opens with the logo.

2. Right-click the log and save to the desired location via "Save Image As".

Web server OZW672... V4.0

Operate using a web browser

49 / 116

CE1C5712en

28.08.2012

Notes

Upload system definitions

• Log file transfer is available to administrator and service user levels.

• Allowed file formats: PNG, GIF, JPG, BMP.

• The left logo (Logo 1) has max. 625 x 54 pixels.

• The right logo (Logo 2) has max. 200 x 54 pixels.

• The original logos are restored when resetting the web server to default.

Procedure:

1. System definitions Select from secondary navigation.

2. Click [ Update ]

Notes

System definitions

Note

3. Select the desired file.

4. Click [ Upload ] to finish.

5. Restart web server with power-down, power-up.

6. You must recreate the devices following a system definition upload.

• System definition file transfer is available to administrator and service user levels.

• Uploading and installing make take more than 5 minutes.

System definitions comprise:

• Device descriptions.

• Text catalogs in each user language.

• Units catalog.

The device web pages use the uploaded system definitions to properly display devices and menus.

You must generate all device web pages following successful uploading. This applies the new system definitions.

The system definitions must be compatible with the web server's software version.

If incompatible, an associated message is displayed and the old system definitions remain as is.

Make sure there is at least 60 MB free memory on the web server when uploading.

If not, check the contents via File transfer > Documents.

50 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

CE1C5712en

28.08.2012

The following functions are available with ACS790:

• Commissioning with device search.

• Popcard.

• Plant diagrams:

For standard applications for the LPB/BSB controller, web-capable plant diagrams may be exported from ACS790 and import them to the web server.

• Parameterization:

Read and write parameter sets.

• Commissioning protocol.

• Offline trend.

For more details, see data sheet N5649.

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

51 / 116

CE1C5712en

28.08.2012

Empty page

52 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Operate using a web browser

CE1C5712en

28.08.2012

Import plant diagrams

Create own plant web pages

Web page elements

Edit/view mode

Note

4.1 Overview

Web server OZW672... visualizes technical equipment in buildings via plant web pages. The plant is operated and monitored via one or more generated plant web page(s).

Web-capable plant diagrams may be exported from ACS790.

You can freely design plant web pages.

As a hybrid form, you can also modify and extend imported plant diagrams.

Plant web pages are designed with the following web page elements:

• Background image.

• Data point elements.

• Text elements.

• Link elements.

• Partial pictures.

Data point elements are used to operate and monitor read and write values for devices connected via the bus and the web server.

Plant web pages are generated online in the web browser.

The web page designer with administrator rights also switches the plant web pages to edit mode.

Other users can query and operate the last saved visualization during the transition phase.

Plant web pages return to view mode once the changes are saved. The new state is now available online at this point.

The switch from an LPB to a BSB bus system and vice versa is not recommended since this renders the defined plant web pages unusable.

Siemens Web server OZW672... V4.0

53 / 116

CE1C5712en

28.08.2012

4.2 Example of a plant web page



Please observe…!

Background image

Data point element

Text element

Link element

All surfaces, symbols and the diagram.

Two data point elements: Room temperature nominal and reduced setpoint.

Explanation text.

Link to Internet.

Integrated web cam image.

Partial picture

element

The example above is an extension to a web-capable plant diagram downloaded from HIT.

The extension consists of additional, explanatory text (3), a link to the Internet (4) and an integrated web cam image (5), that is updated periodically (e.g. every minute).

54 / 116

Siemens Web server OZW672... V4.0 CE1C5712en

28.08.2012

Background image

Position in secondary navigation

Front side /

Background

Show/Hide

Delete

Changes to controller configuration

Key variables

4.3 Plant web page features

A plant web page has an expandable area that can be used to place web page elements. The display area has a minimum size of 800 px (width) and 580px

(height).

The minimum display area is filled with a transparent background image if no background image is explicitly selected.

• The display area can be expanded to any size by adding a larger background image.

• The following types are accepted: png, jpg, gif and bmp; we do not recommend using bmp due to the file size.

Multiple plant web pages are listed from top to bottom in the secondary navigation per their "Position". The plant web page is built and displayed at "Position"=1 when going to a home or device node. The "Position" can be set in secondary navigation via "New > Properties > Position" and for existing plant web site via "Properties >

Position".

The following applies to levels within a plant web page:

• The background picture is located in the background.

• The group of partial pictures are in front.

• The group with all remaining elements are in front.

• More recently added elements are on top of previously added elements within the group of partial pictures and remaining elements.

Please note the following for the last statement:

• If an element is deleted as part of editing and another element added, the new element jumps to the level of the deleted one. This level is not always the top level.

• You must add a new element as part of new editing to ensure that the new elements are placed at the top (finish with OK and re-click edit).

Plant web pages are hidden for a hidden device with appended plant web pages.

The associated plant web pages are displayed again if the device is re-generated

and displayed (see Note in Section 2.8).

Appended plant web pages are irretrievably deleted once a device is deleted. The same is true when you reset the web server.

Any change to the controller configuration creates differences between the controller and the mapping on the web server. This impacts plant web pages as well where data point elements access the controller via the web server map. You must run

"Generate" each time you change the controller configuration (See Section 2.4 for

workflow).

Any number of plant web pages per web server are possible.

• The web server has 180 MB in memory.

• You should pay special attention to image file size to save memory;

(current available memory is available at "File transfer > Documents")

• A maximum of 100 elements may be added on a plant webpage from one web page element type (e.g. a maximum of 100 data point elements).

Siemens Web server OZW672... V4.0

55 / 116

CE1C5712en

28.08.2012

Note

View mode, no web page available

View mode, web page available

Edit

User levels

4.4 Toolbar

The menus described below are only displayed and operable on the "Administrator" user level.

The following toolbar is displayed at home and on the device nodes, if no plant web pages is generated:

Menu

New

Import

Description

Create new plant web page.

Import archived plant web page.

Plant web pages are archived and imported as .tar files.

The toolbar is as follows for an existing plant web page:

Menu

Properties

Description

Properties dialog for the plant web page. Enter the same as for

"New".

Furthermore, "Replace datapoint addresses" address data points with the same names on another bus device.

New

Import

Edit

Copy

Export

Create another plant web page.

Import archived plant web page.

Switch to edit.

Copy selected plant web page to another device node.

Export selected plant web page as .tar archive.

Delete Deleted selected plant web page.

Click Edit to switch the plant web page to edit mode. The toolbar is as follows:

Menu

Datapoint

Text

Description

Embed data point element to web page.

A data point element consists of two fields:

• Data point value for a device connected via the bus or the web server.

• Data point text.

Add free text (single line) to plant web page. The text is entered in the field "Displayed name".

Link Hyperlink to other plant web pages, to a document or an external web page.

Partial picture Add additional picture to plant web page. "Link external" integrates periodically updated, external images (e.g. web cams).

Only an administrator may generate and change visualization. User levels have the same rights for operation and monitoring.

56 / 116

Siemens Web server OZW672... V4.0 CE1C5712en

28.08.2012

Prerequisites

Export plant diagram from ACS790

4.5 Import web-capable plant diagrams

• The drafter is logged on to the web server as an administrator.

• Web server is connected with the bus with one or more bus devices.

• The devices web page for the bus device is generated per Section 2.4.

The web server menu tree and data point information for the controller is now available.

Procedure on ACS790:

• Select bus device.

• Copy standard diagram and re-add to the same bus device (standard diagram cannot be exported). The copied icon is light blue.

• Rename diagram.

• Export diagram using the "Export to…" function.

In the data type dialog field, select *.tar and save.

Import plant diagram to web server

Workflow on web server:

1. Start at the home node in secondary navigation for the desired bus.

The import dialog ("file name (*.tar)") is displayed.

3. "Search..." to go to the .tar file saved on the computer.

Import information is displayed while the file is being read; the property dialog box now opens.

6. Check replacement function with "Replace datapoint addresses".

7. From the dropdown list box, select the bus address for the connected controller.

Siemens

8. Click [ OK ] to start.

The plant diagram is finished.

Web server OZW672... V4.0

57 / 116

CE1C5712en

28.08.2012

Result

Note

The bus device or plant can now be operated and monitored via the web-based plant diagram. The default display is as follows:

• Operating values (e.g. operating mode Auto, Comfort, etc.) is displayed in red.

The cursor changes to a hand symbol when you move it over the display. Click to open the applicable settings dialog box.

• Set points are displayed in orange; actual values in white.

For reasons of compatibility and regardless of the user level, individual data points for the bus device may not be mapped to the plant diagram.

• The data point text "Data point not found" is displayed.

• Three question marks "???" are displayed as the data point value.

See Section 4.6 for any post editing.

58 / 116

Siemens Web server OZW672... V4.0 CE1C5712en

28.08.2012

Prerequisites

Create plant web page

4.6 Create own plant web pages

You can generate complete plant web pages yourself. As an option, you can chan-

ge and extend any imported plant diagrams (See Section 4.5) as needed.

This section presents the steps required to generate and design a customized plant web page.

• The drafter is logged on to the web server as an administrator.

• Web server is connected with one or more bus devices.

• The devices web page for the web server and the bus devices is generated

per Section 2.4. The web server menu tree and data point information is now

available.

The following describes how to create a plant web page and add a background image.

1. Go to home nodes or to a device node.

The properties dialog box is displayed.

3. In the Displayed name field, enter the name for the plant web page

(is displayed later in the navigation area for the web server).

4. Click the red pencil in the Background picture field.

The add dialog box is displayed.

5. Search to go to the desired background picture.

The file name for the selected picture is displayed in the background picture field.

Add data point element

The plant web page is now saved with the background picture.

The following describes how to add a data point element to a newly created plant web page.

The plant web page switches to edit.

The data point dialog box is displayed.

3. Click the red pencil in the Datapoint address field.

The data point address dialog box is displayed.

4. Go to the data point via device, menu text(s).

The entire data point path is entered in the data point address field.

6. Set the X/Y position for the data point field in the display area.

7. Modify formats such as text field size for "Datapoint - value" and "Datapoint - text" as needed.

8. Click Apply to check the results of the change in formatting as a preview to the plant web page.

9. If satisfied, click OK to finish.

10. Click OK to change to view.

The data point value was read and is displayed.

Siemens Web server OZW672... V4.0

59 / 116

CE1C5712en

28.08.2012

Notes

Notes

Add text element

Notes

Add link element

• Double-click the data point element in edit to reopen the settings dialog box for an already created data point element. The data point element can also be deleted in the settings dialog box.

This note applies as well to other web page elements.

• As an alternative to setting the X/Y position in the data point dialog box, you can also position data point elements using drag and drop in edit mode. The element can no longer be moved after switching to view mode.

This note applies as well to other web page elements.

• The X/Y position in the data point dialog box is anchored to the text in the data point value field and its alignment. In conjunction with the alignment functions, the data point field moves to the right for left align and to the left for right align

(see the following graphic).

This note refers as well to text and link elements accordingly.

Alignment

Left Data point text

x

Data point value

x

Center Data point text Data point value

x

Right Data point text Data point value

• The "x" displays the changed position of the anchor.

• The alignment of all the data point texts is left aligned.

The following describes how to add informational text to a plant web page.

The plant web page switches to edit.

The text dialog box is displayed.

3. Enter the desired text in the Displayed name field.

4. Set the X/Y position for the text field in the display area.

5. Format as needed.

6. Click Apply to check the results of formatting in a preview.

7. If satisfied, click OK to finish.

8. Click OK to change to view.

Text elements are single lines.

Only a limited number of fonts are available for texts:

• Small 10pt

• Normal 12pt

• Large 16pt

• XL

24pt

The following describes how to add two lines to the plant web page:

• To another plant web page.

• To an external web page.

The link to a document is not displayed, but works accordingly.

60 / 116

Siemens Web server OZW672... V4.0 CE1C5712en

28.08.2012

Link to another plant web page

Tip

Notes

Links to an external web page

The plant web page switches to edit.

The link dialog box is displayed.

3. Enter the desired text for display in the Displayed name field.

4. Select Link to in the "Plant diagram" field.

5. Click the red pencil in the same field.

The plant diagram dialog box is displayed with all plant diagrams available on the web server.

6. Select the desired plant diagram.

Enter the path for the plant diagram in the "Link to" field.

7. Set the X/Y position for the link field in the display area.

8. Format the link as needed.

9. Click Apply to check the results of formatting in a preview.

10. If satisfied, click OK to finish.

11. Click OK to change to view.

The link is enabled immediately in the view mode: Click to open the corresponding plant web page.

We recommend adding a link on the target web page to return to the previous page.

• Links are broken after importing a plant web page to another web server and must be restored per the instructions above.

• The links to other plant web pages are also broken after a firmware update for web pages exported in advance and then imported and must be restored per instructions above.

The plant web page switches to edit.

The link dialog box is displayed.

3. Enter the desired text for display in the Displayed name field.

4. Select external link in the Link to field.

5. Click the red pencil in the same field.

The link external dialog box is displayed.

6. Enter the desired URL.

7. Check the correctness of the entry: The Internet page is opened.

9. Enter the URL in the "Link to" field.

10. Format the link as needed.

11. Click Apply to check the results of formatting in a preview.

12. If satisfied, click OK to finish.

13. Click OK to change to view.

The link is enabled immediately in the view mode: Click to open the corresponding web page.

Siemens Web server OZW672... V4.0

61 / 116

CE1C5712en

28.08.2012

Add partial picture

Static partial picture

The following describes how to add two partial pictures to the plant web page:

• A static picture downloaded to the web server.

• A link to an external picture on a server, e.g. continuously updated images from a webcam.

The plant web page switches to edit.

2. Click Partial picture.

The partial picture dialog box is displayed.

3. Select "Picture source" in File field.

4. Click the red pencil in the same field.

The add dialog box is displayed.

6. Go to desired image file.

Dynamic partial picture

Enter the file name for the selected image in the Field Source field.

9. Edit Position and Scaling.

10. Click Apply to check the results of formatting in a preview.

11. If satisfied, click OK to finish.

12. Click OK to change to view.

The plant web page switches to edit.

2. Click Partial picture.

The partial picture dialog box is displayed.

3. Select "Picture source" in Link external field.

4. Opens the web cam image on the Internet.

6. Select properties for webcam image.

7. Highlight the address (URL) of the webcam image and copy to clip board.

8. Click the red pencil in the Source Picture field.

The link external dialog box is displayed.

9. Add the URL for the webcam image.

10. Check the correctness of the entry: The webcam image is opened.

12. Edit Position and Scaling.

13. Click Apply to check the results of formatting in a preview.

14. If satisfied, click OK to finish.

15. Click OK to change to view.

62 / 116

Siemens Web server OZW672... V4.0 CE1C5712en

28.08.2012

"Energy indicator" function

Monitored data points and their "Green limits"

Notes

Tree leaf as

"Energy indicator"

Green leaf

Orange leaf

Grey leaf

No tree leaf

Standard EN 15232

5 "Energy indicator" function

5.1 Introduction

5.1.1 Function description

Function "Energy indicator" is available on the OZW672… web server from V4.0.

The web server uses the "Energy indicator" function to read selected data point values from the LPB and BSB bus devices and to compare the values to energyrelated limit values, or so-called "Green limits".

The data points are also monitored for adherence to the "Green limits". As a result, the "Energy indicator" is displayed in the form of a tree leaf.

The monitored data points and their "Green limits" depend on the device type. The following applies e.g. to a controller:

Monitored data points "Green limits" (technical energy limit values)

Comfort setpoint

Reduced setpoint

>21 °C

>15 °C

Setpoint readjustment >± 1.0 K ( ± readjustment has 2 "Green limits")

Operating mode Automatic, Reduced, Protection  "Green leaf"

Comfort / Continuous  "Orange leaf"

The "Green limits" are used only together with the "Energy indicator" function. They do not represent process or safety limit values which trigger e.g. fault messages or turn off the plant in the event of limit violations.

Users also are allowed to change data point values (setpoints). E-mail messages from the system then remind the user that a value or values were changed.

"Green leaf"  Green tree leaf, leaf pointing up.

• The "Green leaf" symbol indicates that a data point value has not exceeded its "Green limit", i.e. the value is within a "green" range in terms of energy consumption.

"Orange leaf"  Orange tree leaf, leaf pointing down.

• The "Orange leaf" symbol indicates that a data point value has exceeded its "Green limit", i.e. the value is outside a "green" range in terms of energy consumption.

"Gray leaf"  Gray tree leaf, horizontal leaf.

• The "Grey leaf" symbol indicates that a data point value is not current, e.g. transmission of a data point value is incomplete, or there is no data communication with the bus.

• The data point is not monitored via the "Energy indicator" function.

The "Energy indicator" function is based on standard EN 15232 "Energy efficiency in buildings".

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

63 / 116

CE1C5712en

28.08.2012

Example: Web page

"Energy indicator"

Web page with "Energy indicator" function; example with data points from "Heat circuit 1" and open dialog box to set data point value "Room temperature Comfort setpoint HC1" and its "Green limit".

5.1.2 LPB/BSB bus topology

The OZW672.01 web server can monitor 1 bus device via the "Energy indicator" function. The OZW672.04 web server can monitor up to 4, and OZW672.16 up to

16 bus devices via the "Energy indicator" function.

Note

64 / 116

Siemens

Building Technologies

A maximum processing time of ca. 40 minutes results for the max. quantity of

"Energy indicator" data points.

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

Device description

Navigation

Primary navigation

5.1.3 LPB/BSB devices

The following devices from the Sigmagyr/Albatros product range can be connected to each OZW672… web server via LPB/BSB.

• Heating controllers RVL4.., RVP3..

• District heating controller RVD2..

• Heating controllers RVA.., RVS.., RVC..

• Boiler management units LMU.., LMS..

The "Energy indicator" data points and "Green limits" have predefined in the

"Device description" with device-specific default values. The default values can be changed with a few notable exceptions.

Neither number nor selection of the "Energy indicator" data points and "Green limits" that exist in the "Device description" can be changed.

5.1.4 Navigation and device web pages

Go to the "Energy indicator" function as follows:

• Via primary navigation, main function "Energy indicator".

• Click the "Plant state Energy indicator" pane

(top right field pane tree leaf in the screenshot below).

On the web page, you can select the "Energy indicator" function from the primary navigation next to "Home".

Secondary navigation

Device web pages state "Generated"

In secondary navigation, both partial plants and/or devices are displayed sorted by device address in ascending order.

State "Generated" in column "State" in "Device web pages" is a precondition for

displaying the devices using the "Energy indicator" function (see Section 2.4).

Note

Siemens

Building Technologies

The "Device web pages" (see screenshot) pane can be opened with "Service" and

"Administrator" access rights.

Web server OZW672... V4.0

"Energy indicator" function

65 / 116

CE1C5712en

28.08.2012

Level designations

Enter the

"Plant" level

5.2 "Energy indicator" function levels

The contents of the "Energy indicator" function are distributed across 2 or 3 levels depending on the functionality of the respective device.

• Simple devices have 2 levels:

1. "Plant"

2. "Data points"

• Complex devices have 3 levels:

3. "Plant"

4. "Partial plants"

5. "Data points"

5.2.1 "Plant" level

Enter the "Plant" level as follows:

• Click the "Energy indicator" function (primary navigation) or

• Click the "Plant state Energy indicator" pane.

The "Plant" level shows all devices of a plant subject to the "Energy indicator" function.

"Energy indicator"

for a plant

"Energy indicator"

for devices

Next lower level

Table columns

Energy indicator

66 / 116

Siemens

Building Technologies

The "Energy indicator" of the plant is displayed as a summary display in the

"Plant state Energy indicator" pane. See Section 5.2.6 for information on the

summary display.

The "Energy indicator" for devices is displayed at the "Plant" level in the "Energy indicator" column for each device.

Clicking the name of a device in secondary navigation or in the "Device name" column opens the next lower level for that device.

"Energy indicator" (tree leaf) for each actively monitored device.

This column also contains:

• Checkboxes to activate/deactivate monitoring of the "Energy indicator" data points for the selected device.

• Summary checkbox (green/red) to activate/deactivate monitoring for all data points of the plant.

The summary checkbox is available only for access level "Administrator"; see

Section 5.3.4.

When a checkbox is cleared (deactivated), message "Monitoring off, green limits

reset to default values! Really to be continued?" is displayed; see Section 5.3.4.

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

Device name, device type

Device address

Device type

Monitored data points

Note

"Partial plants" level

The device name is displayed if defined (prior to creating the "Device list"), otherwise the device type.

The devices are sorted by device address in ascending order.

Network address (area.line.deviceaddress)

Device type (technical device designation)

Indication of the number of actively monitored data points (x) for possible number

of data points to be monitored (y) for each device; see Section 5.2.4.

Clicking the column title

• Device name

• Device address

• Device type sorts the column contents in the table in ascending or descending order.

5.2.2 "Partial plants" level

The "Partial plants" level shows the partial plants of functionally complex devices

(see partial plants below for RVS.. Heating controller).

Next lower level

Next higher level

Table columns

Energy indicator

Partial plant name

Monitored data points

Clicking the name of a partial plant in secondary navigation or in the "Partial plant name" column opens the next lower level for that partial plant.

Clicking (in secondary navigation) opens the next higher level.

"Energy indicator" (tree leaf) for each actively monitored partial plant.

This column also contains the checkboxes to activate/deactivate "Energy indicator" monitoring of the data points for the selected partial plant (deactivate without confirmation message).

Name of the partial plant (taken over by device).

Indication of the number of actively monitored data points (x) for possible number

of data points to be monitored (y) for each partial plant; see Section 5.2.4.

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

67 / 116

CE1C5712en

28.08.2012

Notes

"Data points" level

When level "Partial plants" is selected, they are sorted by "Device description".

Users cannot change the sort order.

In functionally complex devices with many data points, they are assigned to the partial plants. The data points of the partial plants (per partial plant) are displayed at the "Data point" level; see below.

The "Partial plants" level is not available in functionally simple devices with few data points.

5.2.3 "Data points" level

The "Data points" level shows the data points to be monitored (see the data points for partial plant "Heat circuit 1" below).

Next higher level

Table columns

Energy indicator

Data point

Value

Symbol (red pen)

Green limit(s)

Note

Clicking (in secondary navigation) opens the next higher level.

"Energy indicator" (tree leaf) for each actively monitored data point.

This column also contains the checkboxes to activate/deactivate "Energy indicator" monitoring of the selected data point (deactivate without confirmation message).

Name of the data point.

Value of the data point (dependent on data point type with unit, e.g. °C).

Clicking the red pen symbol opens the dialog box for the selected data point;

see Section 5.4.

Value of the set "Green limit" (dependent on data point type and unit).

Enumeration values for "Green leaf" are displayed for "Green limits" with enumeration values such as "Automatic", "Comfort".

Invisible values are replaced by dots "…" if not all enumeration values can be displayed. The dialog box (click red pen symbol ) shows all enumeration values.

When level "Data points" is selected, they are sorted by "Device Description". Users cannot change the sort order.

68 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

Column "Monitored data points"

"Plant" level

5.2.4 Number of "Monitored data points"

The "Monitored data points" column shows the number of actively monitored data points (x) compared to the number of data points (y) that could be monitored.

"x of y" is displayed for each device and partial plant in the corresponding row.

The sum of all devices and partial plants is displayed in the bottom row.

"Partial plants" level

"x of y" is displayed for each partial plant in the corresponding row and the sum of all partial plants is displayed in the bottom row.

Note

Level "Data points" does not have indication "x of y".

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

69 / 116

CE1C5712en

28.08.2012

Configuration of visibility

5.2.5 "Energy indicator" visibility

Visibility of the "Energy indicator" symbol is configured at the "Administrator" access level and "Service" in the web server.

Path: OZW672… > Settings > Energy indicator > Energy indicator on the web

(very bottom of web page)

Notes

"Energy indicator" remains active even if "Energy indicator on the web = Not visible" is selected.

Configuration "Energy indicator on the web" (Visible/Not visible) also applies to user groups "Service" and "End user".

70 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

Summary display

LED on web server

Summary display

"Plant" web page

5.2.6 Summary display "Energy indicator" for a plant

The "Energy indicator" of the plant OR-links the "Energy indicators" of all devices across all levels. It is displayed as a summary:

• LED on the web server (see figure in Section 1.2).

• Web page "Plant" in the "Plant state Energy indicator" pane.

The following colors of LED on the web server front mean:

• LED is lit green

"Energy indicator" of the plant = "Green leaf".

• LED is lit orange

"Energy indicator" of the plant = "Orange leaf".

• "Green leaf"

All actively monitored data points of the plant are within limits, i.e. no "Green limits" are violated.

• "Orange leaf"

At least one monitored data point is outside its "Green limit". The number of data points outside their "Green limit" is displayed in addition to the tree leaf.

The summary display "Orange leaf" with "2 Green limit(s) crossed" is displayed (in the previous example) because two "Green limits" were exceeded in "Heat circuit

2" (see next screenshot).

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

71 / 116

CE1C5712en

28.08.2012

Prerequisites

Device web pages

5.3 "Energy indicator" commissioning function

5.3.1 Commissioning notes

Prerequisites for commissioning the "Energy indicator" function:

• Login with "Administrator" access right.

• Generating the devices in the web server. This generates the "Energy indicator" data points for each device.

• Devices on the Device web pages must have state "Generated".

Start "Energy indicator" function

Notes

Temporary status

5.3.2 Start "Energy indicator" function

The "Energy indicator" function in the OZW672… web server is started automatically if the above prerequisites are fulfilled.

The devices must contain at least one "Energy indicator" data point to be displayed as part of the "Energy indicator" function.

The "Energy indicator" database only exists on the web server. And the web server itself has no data points subject to the "Energy indicator" function.

"---" is temporarily displayed for a data point's status in the "Value" column until the data point value is read and processed via the bus.

Updates on the web page

Note

A maximum of 4 "Energy indicators" per second are updated on a web page. The actual number depends on effective bus load. In the event of concurrent user access, bandwidth is distributed across all users.

Device data point values are not transmitted if there is no bus supply or if the

LPB/BSB bus is interrupted.

No comparison to "Green limits" then takes place and column "Value" contains "---" while column "Energy indicator" displays a "Grey leaf".

72 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

Estimated processing time

5.3.3 Estimated processing time

After starting the "Energy indicator" function, the "Plant" web page contains the following:

• Summary display "Energy indicator"; see Section 5.2.6.

• Number of monitored data points; see Section 5.2.4.

• "Estimated processing time"; see below.

The "Estimated processing time" is displayed in hours and minutes.

Processing time at base load

Updated display for

"Energy indicator"

Note

Deactivation

When monitoring is active, the web server first reads each data point from the bus devices and then compares the values to its "Green limit".

Processing time at base load per data point is 12 seconds (longer if the bus carries a heavy load).

Thus, updating the "Energy indicator" (leaf color) display may take up to 40 minutes. Therefore:

• "Green leaf" (start-up mode)

The "Green leaf" display does not necessarily reflect the current plant state prior to completion of the "Estimated processing time".

• The updated display of "Energy indicator" can be postponed by max. the "Estimated processing time".

Note the restriction from the "updated "Energy indicator" display" also when navigating to other web pages.

5.3.4 Deactivating "Data point monitoring"

Monitoring "Energy indicator" data points is activated automatically following device list creation.

Thus, data point monitoring can only be deactivated as a first step.

• Deactivation for "Data point monitoring" requires "Administrator" access rights.

The checkbox in the "Energy indicator" column allows for deactivating monitoring of one or multiple data points e.g. for operational reasons.

Data point monitoring active (default following commissioning)

Data point monitoring deactivated

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

73 / 116

CE1C5712en

28.08.2012

"Plant" level

Selecting the checkbox deactivates the data points for the selected device (can be reactivated).

Selecting the summary checkbox (green/red, bottom row) deactivates the data points for the plant (can be reactivated)).

Note

"Partial plants" level

"Data points" level

Confirmation message for "Monitoring off"

A confirmation message is displayed when data point monitoring for a device or plant is deactivated; see below.

Selecting the checkbox deactivates the data points for the selected partial plant

(can be reactivated)).

No confirmation message is displayed when data point monitoring for a partial plant is deactivated.

Selecting the checkbox deactivates the selected data point (can be reactivated)).

No confirmation message is displayed when data point monitoring is deactivated.

A confirmation message is displayed when data point monitoring for a device or plant is deactivated:

Green limits to default values!

Note

Clicking [ Yes ] for message "Really to be continued?" to deactivate monitoring also resets "Green limits" (changed by the user) to their default values. Therefore:

"Monitoring off" deactivates monitoring while, at the same time, setting the "Green limits" to the default values of device list creation.

Contrary to the "Green limits", deactivation does not reset changed data point values to default values. Therefore:

Following "Monitoring off" and reactivation, "Energy indicator" data points may no longer be within the green limits, as the "Green limits" reset to default values have different dependencies.

74 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

Activation

"Plant" level

"Partial plants" level

Example

5.3.5 Activating "Data point monitoring"

Monitoring "Energy indicator" data points is activated automatically following device list creation.

Data point monitoring can thus be activated only following deactivation; see

Section 5.3.4.

• Activation for "Data point monitoring" requires "Administrator" access rights.

The checkbox in the "Energy indicator" column allows for activating monitoring of one or multiple data points e.g. following temporary deactivation.

Data point monitoring deactivated (by user)

Data point monitoring activated

Selecting the checkbox activates the data points for the selected device.

Selecting the summary checkbox (green/red, bottom row) activates the data points for the plant.

Selecting the checkbox activates the data points for the selected partial plant.

Monitoring is deactivated for partial plant " Cooling circuit 1". As a result, all data points are deactivated.

"Cooling circuit 1" is deactivated. Data points "Cooling circuit 1" are deactivated.

"Monitored data points" 0 of 2.

Selecting the checkbox for partial plant "Cooling circuit 1" activates it. As a result, all data points at the "Data points" level are also activated.

"Cooling circuit 1" is reactivated. All data points of "Cooling circuit 1" are reactivated.

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

75 / 116

CE1C5712en

28.08.2012

"Data points" level

Example

Note

Selecting the checkbox activates the selected data point.

Starting point: All data points of partial plant "Cooling circuit 1" are deactivated.

Activating just one data point also activates the partial plant.

A data point (Release cooling circuit 1) of partial plant "Cooling circuit 1" is activated.

Partial plant "Cooling circuit 1" is automatically activated.

Note that "Monitoring activated" at the "Partial plants" level does not mean that

all subordinate data points are activated and monitored also. This also applies to "Monitoring activated" at the "Plant level".

76 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

Open a dialog box

Dialog box

5.4 Dialog boxes, data points, and "Green limits"

5.4.1 General dialog boxes

Clicking the red pen symbol opens the dialog box for the selected data point.

This allows you to either change the data point value and/or the "Green limit".

Room temperature Comfort setpoint HC1

Contents

Value

Data point value

Setting range

Bars

The dialog box contains the following information:

• Name (data point)

• Value (data point)

• "Energy indicator" as:

"Green leaf" Green tree leaf or

"Orange leaf" Orange tree leaf

• "Green limit(s)"

• Setting range 16.0 °C to 35.0 °C for data point and "Green limit(s)"

The set data point value is displayed in the field above the setting range. There are 3 ways to change the data point value:

• Change the data point value in the entry field.

• Move the data point slider to the right or left.

• Arrows

to adjust the value step by step.

The data point slider is green for as along as the data point value is within the green setting range (up to and including "Green limit"). If the data point value is moved to the orange range, the slider turns orange.

The setting range for the data point value and its "Green limit" corresponds to the green/orange bar limited by value indications to the right and left of the bar.

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

77 / 116

CE1C5712en

28.08.2012

Green limit(s)

Notes

Note

Room temperature

Comfort setpoint HC1

Each data point monitored with the "Energy indicator" function has its own "Green limit". There are 3 ways to change the "Green limit":

• Change the value for the "Green limit(s)" in the entry field.

• Move the "Green limit(s)" slider to the right or left.

• Arrows

to adjust the value step by step.

The "Green limit" slider is always "green/orange". If the slider is moved to the setting range limit value, the bar color disappears in the direction of the movement.

The default values defined for data point and "Green limit(s)" in the "Device description" are displayed in the corresponding entry field.

After values are changed (by the user), default values can be regenerated only by deactivating "Data point monitoring" (with summary checkbox).

5.4.2 Dialog boxes with numeric data points

In numeric data points such as "Room temperature Comfort setpoint HC1", the

"Green limits" may depend on neighboring values. Therefore:

To achieve the desired setting range, the data points (heating circuit and cooling circuit setpoints) and their "Green limits" must be set in relation to the neighboring value.

Dependency of neighboring values always depends on the data point values (setpoints), not the "Green limits".

Note

Room temp Comfort setpoint cooling circuit 1

Set the heating setpoint by 1 K lower (or max. the same) as the "Green limit" to display the "Energy indicator" = "Green leaf".

Note

78 / 116

Siemens

Building Technologies

Set the cooling setpoint by 1 K higher (or max. the same) as the "Green limit" to display the "Energy indicator" = "Green leaf".

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

Room temp setpoint readjustment HC2

In the "Room temp readjustment setpoint HC2" dialog box, the data point value corresponds to the adjustment range, symmetrical to the zero-point axis. This requires 2 "Green limits".

Operating mode heat circuit 1

5.4.3 Dialog boxes with enumeration data points

A dialog box with enumeration values, at least one "Green limit" for a value to be monitored needs to be set.

Note

The enumeration values are predefined as per the data point type. The "Green limit(s)" are set by clicking the selection boxes.

5.4.4 User groups "Service" and "End user"

The dialog boxes for the "Energy indicator" data points can be opened also in the

"Service" and "End user" user groups.

The entry fields of values that can not be set are grayed, i.e. they are unavailable for editing. Other than that, the dialog boxes are the same as for the "Administrator" user group.

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

79 / 116

CE1C5712en

28.08.2012

E-mail receiver configuration

5.5 E-mail with "Energy indicator" for the plant

5.5.1 E-mail receiver configuration

Either no E-mail (no transmit time = Default) or one or two e-mails (Transmit time 1 and/or Transmit time 2) can be sent with the plant's "Energy indicator".

E-mail receivers 1 and 2 can be configured with "Administrator" and "Service" access rights on the web server.

Path: OZW672… > Settings > Energy indicator

Notes

Test receiver

E-mail receivers 1 and 2 are configured individually (separate settings).

If Transmit time 1 and/or 2 are configured, the "Energy indicator" of the plant is sent as an e-mail only if at least one monitored data point exceeds its "Green limit".

Configuration of e-mail receivers 1 and 2 for the "Energy indicator" of the plant is not related to the e-mail receivers of fault messages (device failure etc.).

One e-mail each can be sent for test purposes to E-mail receiver 1 and 2.

• The test is triggered manually via data point "Test receiver = Trigger".

• Reception is confirmed in data point "Energy indicator transmitted = Yes".

• Data point "Reason" contains feedback on whether the e-mail was sent or which setting must be checked in the event of an error.

80 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

"Energy indicator transmitted" and "Reason"

Note

Fault message e-mail

Reset fault message

Note

The values of the data points "Energy indicator transmitted" and "Reason" are displayed after testing until:

• Another test is triggered manually.

• The next transmitted e-mail is transmitted as per Transmit time 1 and/or 2.

• The device supply is switched on and off.

Data point Function

Test receiver [ ---, trigger]

"Energy indicator transmitted" [ ---, Yes, No]

Reason [ ---, DNS setting, mail server address, mail server port number, e-mail address recipient, mail server authentication, network cable]

Manual triggering for test purposes does not trigger a fault message.

If an e-mail with "Energy indicator" of the plant is not transmitted without error, a fault message is triggered for the corresponding e-mail recipient.

The fault message is reset if:

• The next transmitted e-mail is transmitted as per Transmit time 1 and/or 2.

• Manually triggered "Test receiver" is successful.

The diagnostic options are identical to those of other e-mail recipients.

5.5.2 Mail inbox

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

81 / 116

CE1C5712en

28.08.2012

E-mail Energy indicator contents

Reference field

Examples

Message field

Example

E-mail

"Energy indicator"

5.5.3 E-mail contents

The contents of the e-mails comprises (see screenshot below):

• E-mail format Text only (see message field below).

• E-mail sender

As per the settings (e.g. [email protected]).

• E-mail recipient As per the settings (e.g. first [email protected]).

The Reference field comprises the following information:

• Plant name:

OZW type or user-defined name (see examples).

• Energy indicator Fixed text (e.g. "Energy indicator" translated into the language selected in the web server.

OZW672.16: Energy indicator

Landmatt 1: Energy indicator

The actual message is written in the language selected in the web server.

2 of 117 monitored data points have crossed their Green limits.

10 lines follow this text where each line may contain a free text regardless of the language selected in the web server. (Signature line 1...10, with max. 49 characters per line).

82 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

Regenerate bus devices

Bus devices

Hide

5.6 Exceptions

The following applies to the "Energy indicator" function when regenerating bus devices:

• Existing data points and their "Green limits" as well as the set status for "Data point monitoring activated/deactivate" remain as is.

• Data points no longer available and their "Green limits" are deleted from the

"Energy indicator" database.

• New data points and their "Green limits" are taken over into the "Energy indicator" database and data point monitoring is activated.

Hiding bus devices is the same as deactivating monitoring. Thus, "Energy indicators" are not calculated and displayed.

Generate again

Change configuration

Replace

Delete

Special cases

Bus device failure

Missing bus supply

System data update

Firmware update

Bus devices are shown again via "Generate".

Complete changes to the configuration via "Generate".

Complete bus device replacements via "Generate".

When deleting bus devices from the device list, the "Energy indicator" data is deleted also.

In the event of bus device failure, e.g. no communication via LPB/BSB bus, the

"Grey leaf" is displayed. The "Estimated processing time" does not change.

If there is no bus supply, the data point values of the bus devices cannot be read and a "Grey leaf" is displayed. The "Estimated processing time" does not change.

Complete system data updates for all bus devices via "Generate". "Generate" does not lead to data loss.

In the event of a firmware update, the entire configuration is lost, i.e. parameter set and data for the "Energy indicator" function.

Read and write of the parameter set via ACS790 allow for retaining the configuration of the OZW672 (device list and "Device Descriptions").

Changed data of the "Energy indicator" function are lost. The "Energy indicator" function starts with the data point values and "Green limits" similar to creating a device list in the web server.

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

83 / 116

CE1C5712en

28.08.2012

Empty page

84 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

"Energy indicator" function

CE1C5712en

28.08.2012

6 Communications

The web server can be operated from a PC with web browser on a local area network (LAN) or via the Internet. The following settings also apply to access via

Smartphone and other apps via Web API.

Local area network

(with router)

6.1.1 Local area network (LAN)

The PC and web server must be on the same IP subnet to communicate. You must first determine the subnet as well as the IP addresses.

Siemens

Building Technologies

A router normally serves as the DHCP server if installed on a local area net- work (e.g. DSL router for Internet access). As such, it automatically assigns

IP addresses to all participants that are DHCP clients.

If a PC is connected to the router via Ethernet, an IP address, subnet mask, standard gateway and DNS server are assigned automatically.

When delivered, the web server already contains an enabled DHCP client; as a result, users do not need to enter Ethernet settings.

The connection is checked every 3 minutes. It is recommended to assign the

IP address of the web server in the router according to its MAC address.

If the router with DHCP server is not available, the web server uses the default

IP address 192.168.2.10

.

Web server OZW672... V4.0

Communications

85 / 116

CE1C5712en

28.08.2012

For manual settings, use the PC to determine the required data.

Procedure:

2. Select "Support" tab.

3. Click [ Details… ]

Notes

86 / 116

Siemens

Building Technologies

In the example, the PC is assigned the IP address 192.168.2.199

and subnet mask 255.255.255.0

. The default gateway and DNS server have

IP address 192.168.2.1

.

You can use the data to set the web server:

• IP address: Unused address on the subnet. For example

192.168.2.10

is still available if the PC uses 192.168.2.199

and the router uses 192.168.2.1

.

• Subnet mask:

• Default gateway:

• Preferred DNS server:

192.168.2.1

• Alternate DNS server (empty).

• In the example, the subnet has an address of

192.168.2.x

. Devices must have the same subnet address to communicate directly (i.e. without a router).

• The web server is delivered as preconfigured DHCP client with automatic reception of the network configuration.

The web server's IP address can be set manually as an option.

• We recommend using IP addresses from the private range in the home network

(see Section 7.3.1).

Web server OZW672... V4.0

Communications

CE1C5712en

28.08.2012

Local area network without router

IP addresses and subnet masks must be entered manually if a local area network is installed with PC and web server, but without a router.

On the PC, set as follows:

2. Select the "General" tab.

3. Click [ Properties ]

Siemens

Building Technologies

4. Select "Internet Protocol (TCP/IP)".

5. Click [ Properties ]

6. Select "Use the following IP address".

Continued on next page.

Web server OZW672... V4.0

Communications

87 / 116

CE1C5712en

28.08.2012

7. Enter the IP address and subnet mask.

Notes

8. Click [ OK ]

In the example, the PC is assigned IP address 192.168.2.199

and subnet mask

255.255.255.0

You can now set the web server:

• IP address: An unused address in subnet, e.g.

192.168.2.10

255.255.255.0

• Default gateway(empty).

• Preferred DNS server(empty).

• Alternate DNS server(empty).

• In the example, the subnet has an address of

192.168.2.x

. Devices must have the same subnet address to communicate directly (i.e. without a router).

• The default gateway and DNS server settings have no meaning for LANs without router, provided no e-mail is sent within the home network.

• We recommend using IP addresses from the private range in the home network

(see Section 7.3.1).

88 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Communications

CE1C5712en

28.08.2012

Internet connection

Notes

Local area network

(LAN)

6.1.2 Remote operation via the Internet

The appropriate connection is required (e.g. DSL router) for remote operation via

Internet. Setting up Internet access is not described here.

• The example here were created using the Siemens Gigaset SX763 router (see

Section 7.3.5). Workflow, terms and functionality may differ when using other

products.

• The router must support NAT/PAT, DynDNS and DHCP as an option.

• The web server supports HTTPS (Hyper Text Transfer Protocol Secure).

Web operating pages are transmitted secured and encrypted.

IP address, subnet mask and DHCP are set up under Local Network in addition to other settings:

• The IP address router is fixed.

• The subnet mask defines the size of the subnet.

• The router assigns the DHCP clients (e.g. the PC on the local area network) an IP address from a selecting setting range ("First issued IP address" through

"Last issued IP address") if set as DHCP server.

• The "Default gateway" is typically the router's IP address as well.

• The "Lease time" defines how long a client maintains the IP address received from the DHCP server (the DHCP server regularly renews the client IP addresses).

Siemens

Building Technologies

In the example, the router has a set IP address of 192.168.2.1

and receives subnet mask 255.255.255.0

. As a DHCP server, it renews the IP addresses of the DHCP clients every 30 (in the above example) minutes. DHCP clients are assigned addresses from a range of 192.168.2.100

through 192.168.2.199

. The router is the gateway between LAN and Internet.

Web server OZW672... V4.0

Communications

89 / 116

CE1C5712en

28.08.2012

Firewall

We recommend enabling the firewall to protect the local area network:

• Firewall: On.

Address Translation

(NAT)

Activate NAT to ensure that the web server can be reached via the Internet.

• NAT: On.

90 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Communications

CE1C5712en

28.08.2012

Port Forwarding (PAT)

Notes

• Port Forwarding is used to determine which local IP addresses/ports the router translates to which public IP addresses/ports.

• Web operating pages are preset on the web server via Port 80 (HTTP) or port

443 (HTTPS). As a result, queries from the Internet must be translated using the public IP address/port to the private IP address/port 80 or 443 for the web server.

• When using PC software ACS790 for remote operation, you must also change

Port 21 (FTP) and Port 50005 (ACS private) from the public to a private IP address.

• The port IP address is appended to the web browser address line:

<IP address>:<Port>, e.g. 122.104.2.10:80.

• The web browser always uses port 80 unless another port is entered. As a result, the information in the address line for the web browser is always:

<IP address>:80 and <IP address>, or 122.104.2.10:80 and 122.104.2.10

.

• Ports not equal to 80 are considered more robust against hackers.

• We recommend using Port Forward Ports from the private range.

In the example, queries from the Internet to the public IP address (Internet connection)/Port 80 is forwarded to the local IP address 192.168.2.10

(web server) /

Port 80.

Siemens

Building Technologies

Web server OZW672... V4.0

Communications

91 / 116

CE1C5712en

28.08.2012

DynDNS

Dynamic IP address

Registration

Report dynamic address

The web server can communicate directly with the fixed IP address or domain if a fixed IP address or domain (e.g. www.myname.com

) is available for the Internet connection.

For dynamic IP addresses, the Internet provides free-of-charge DynDNS services that connect user-defined domain names to dynamic IP addresses. The router must support DynDNS to use this function.

To use the DynDNS service, a new account must be set up at the respective provider.

The router must inform the service of changes to the dynamic IP address for the web server to communicate via the DynDNS service setup. Set up the router

DynDNS as follows:

• Dynamic DNS: On

• Service provider: Service provider.

• Domain name

Domain = Host name (own name).

• User name:

User name for the DynDNS account (e.g. MyUserAccount).

• Password:

Password for DynDNS account.

Encrypted connection (HTTPS)

Note

Principal workflow

Note

HTTPS encryption via port 443 is also supported. The required certificate is not accredited. The self-signed certificate from Siemens is valid for 20 years and is installed on the web server. The certificate must be installed on the web browser for encrypted communications.

One own certificate must be installed for each web server.

The web browser security warning is displayed the first time you connect via the https address. The page continues to load contrary to the web browser recommendation.

The certificate must now be installed: A context-sensitive installation routine is available depending on web browser used.

The warning "Certificate error" remains for individual web browsers even after the certificate is successfully installed. Transmission is nevertheless secure.

92 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Communications

CE1C5712en

28.08.2012

E-mail

6.2 Messages via e-mail

SMTP is used to send fault messages and system reports via email. The mail server (SMTP server, out-going mail server) must be known to the web server to send e-mails to the receivers.

Example mail

The following applies to send e-mails via the Internet:

• An e-mail account is available and set up.

• Internet access is set up for the web server (see Section 6.1.2).

• The settings for "E-mail", "Message receiver 1…4", "System report"

(see Section 2.5.2).

Siemens

Building Technologies

Web server OZW672... V4.0

Communications

93 / 116

CE1C5712en

28.08.2012

Messages

Web server fault

The message content is based on pending faults. The following provides and overview of the outline of various e-mail messages. As follows:

• The path for user settings starts each time with:

Home > 0.5 OZW672... > Settings > …

• Set components of the e-mail are in italics.

• User settings are in bold

Data point, information Example of an e-mail

From:

[email protected]

…> Communication > E-mail: E-mail address sender

To:

[email protected]

Subj:

Message central unit:

…> Message receiver > Message receiver 1…4: E-mail address

Message type:

Demo HCS,

No bus power supply

…> Texts: Name,

Fault text

Device:

Demo HCS (0.5) …> Texts: Name (Device address).

Message: No bus power supply.

Fault text

Fault number: 81.

Fault priority: Urgent.

Fault code

Fault priority

Occurred at: 15.09.2009 at 08:44 Occurred at

myhome.dyndns.info

…> Communication > E-mail: Signature line 1…10

Fault bus device

Example of an e-mail

myhome.dyndns.info

Data point, information

From:

[email protected]

To:

[email protected]

Subj:

Message central unit:

…> Communication > E-mail: E-mail address sender

…> Message receiver > Message receiver 1…4: E-mail address

Message type:

Demo HCS,

Outside temperature sensor

Device:

RVS61.843/109 (0,1) sen.

Fault number: 10.

Fault priority: Urgent.

Message: Outside temperature

…> Texts: Name,

Fault text

…> Texts: Name bus device (Device address).

Fault text

Fault code

Fault priority

Occurred at: 15.09.2009 at 08:44 Occurred at

…> Communication > E-mail: Signature line 1…10

94 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Communications

CE1C5712en

28.08.2012

Fault inputs 1...2

Example of an e-mail

From:

[email protected]

To:

Subj:

Message central unit:

Demo HCS,

Overpressue /

Pressure normal

Device:

Pressure sensor

(Fault input 1) (0.5)

Message:

[email protected]

Data point, information

…> Communication > E-mail: E-mail address sender

…> Message receiver > Message receiver 1…4: E-mail address

Message type:

…> Texts: Name,

…> Faults > Local > Fault input 1…2:

Text for: Fault / Text for: No fault

…> Faults > Local > Fault input 1…2: Fault input 1…2

(fault input 1...2) (device address).

…> Faults > Local > Fault input 1…2:

Overpressure /

Pressure normal

Fault number: 171 / 00

Text for: Fault / Text for: No fault

Fault code

Fault priority:

Not urgent.

…> Faults > Local > Fault input 1…2: Fault priority

Occurred at: 15.09.2009 at 08:44 Occurred at

myhome.dyndns.info

…> Communication > E-mail: Signature line 1...10

Fault eliminated

Example of an e-mail Data point, information

From:

[email protected]

…> Communication > E-mail: E-mail address sender

To:

[email protected]

Subj:

Message central unit:

…> Message receiver > Message receiver 1…4: E-mail address

Message type:

Demo HCS,

No fault

…> Texts: Name,

Fault text

Device:

Demo HCS (0.5)

Message: No fault.

Fault number: 00.

Fault priority: Urgent.

…> Texts: Name / Name bus device (Device address).

Fault text

Fault code

Fault priority

Occurred at: 15.09.2009 at 08:44 Occurred at

myhome.dyndns.info

…> Communication > E-mail: Signature line 1...10

Siemens

Building Technologies

Web server OZW672... V4.0

Communications

95 / 116

CE1C5712en

28.08.2012

System report with fault

Example of an e-mail Data point, information

From:

[email protected]

To:

[email protected]

Subj:

Message central unit:

Demo HCS, N. OK

Status: N. OK

Fault 1:

Device: Demo HCS (0.5)

…> Communication > E-mail: E-mail address sender

…> Message receiver > Message receiver 1…4: E-mail address

Message type:

…> Texts: Name, status

Status

Fault 1:

…> Texts: Name (Device address),

Message:

No bus power supply, 81.

Fault text, fault code

Occurred at: 15.09.2009 at 08:44 Occurred at

myhome.dyndns.info

…> Communication > E-mail: Signature line 1...10

System report without fault

Example of an e-mail

From:

[email protected]

To:

[email protected]

Subj:

System report central unit:

Demo HCS, OK.

Status: OK.

myhome.dyndns.info

Data point, information

…> Communication > E-mail: E-mail address sender

…> Message receiver > Message receiver 1…4: E-mail address

Message type:

…> Texts: Name, status

Status

…> Communication > E-mail: Signature line 1...10

96 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Communications

CE1C5712en

28.08.2012

MS Outlook

You can provide the required information as follows for an e-mail account under

MS Outlook:

2. Go Tools / E-mail accounts… .

3.

View or change existing e-mail accounts.

4. Click [ Next ]

5. Select desired account.

6. Click [ Change ]

The e-mail account dialog box is displayed with the data on the e-mail account.

7. Click [ More Settings ]

Displays authentication (if required).

Notes

8. Click [ Cancel ] to exit the account settings.

• A list of providers that send e-mails at no charge is available in Section 7.3.2.

• The web server supports HTTPS (Hyper Text Transfer Protocol Secure). E-mails are transmitted unsecured and unencrypted.

• Web server supports SSL (Secure Sockets Layer, network protocol for the secure transfer of data) and TLS (Transport Layer Security, encryption protocol for data transmissions over the Internet; a further development of SSL).

• "Authentication mail server = Yes" checks unsecured, unencrypted information in the data items "User name" and "Password" from the mail server for each e-mail transmission.

• The mail server can also be installed on the local area network.

Siemens

Building Technologies

Web server OZW672... V4.0

Communications

97 / 116

CE1C5712en

28.08.2012

Empty page

98 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Communications

CE1C5712en

28.08.2012

Text entry

Note

Fault codes

7 Appendix

Names of data points and message text, e.g. of faults, cannot contain special characters or umlauts. Valid characters:

• a…z and A…Z

• 0…9

• ! „ $ % & ‚ ( ) * + ` - . / : ; < = > ? "Space

When sent, invalid characters will be converted to "?" (question marks).

7.2 Diagnostics

7.2.1 Web server fault codes

Fault code Web server fault

General

Communications

81

95

No bus power supply

1)

Invalid time of day (Web server time not or incorrectly entered).

100

142

>1 clock time master

Device failure (Bus)

2)

171

172

438

[Fault input 1] fault

[Fault input 2] fault

Incorrect bus connected

439

448

449

Bus module not identified

Message receiver 1 not reached

3)

Message receiver 2 not reached

3)

Message receiver 3 not reached

3)

450

451 Message receiver 4 not reached

3)

System configuration errors

82 >1 identical device address (Devices have same address).

1) Device failure monitoring (Bus) is stopped if the bus has no power.

2) Created by the web server for the device failed.

Device failure (Bus) as a result, device failure (bus) is assigned to "System faults",

whereas all other faults generated by the web server are assigned as "Local faults".

3) Possible causes of recipient type e-mail: Erroneous Ethernet or e-mail settings.

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

99 / 116

CE1C5712en

28.08.2012

Windows Commander

7.2.2 Windows commander

You can use the Windows commander to check availability of IP addresses, domains or servers:

1. Open Windows commander: Start > Run.

2. Enter "cmd" in the pane.

3. Click [ OK ]

4. Enter the desired command in the command line C:\>:

Command Result, application

ping <IP address> or

<domain>

Response times to the query: Checks whether an IP address can be reached in the network.

Tracet <IP address> or

<domain>.

Progress of the IP address implementation to the goal:

Check whether DNS and mail servers can be reached. nslookup <IP address> or <domain>

Translates an IP address to the domain name and vice versa: Look up domain names.

100 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

CE1C5712en

28.08.2012

7.3 Communications

7.3.1 Internet protocol

Private networks

Ports

Public

Private

The following IP addresses are reserved for private networks:

• Class A: 10.0.0.0–10.255.255.255.

• Class B: 172.16.0.0–172.31.255.255.

• Class C: 192.168.0.0–192.168.255.255 (typical for home networks).

There are predefined public ports and ranges for private ports:

HTTP 80 HTTPS

FTP 21 SMTP

Range 49152 to 65535

7.3.2 Free e-mail account providers

Note

You can use free-of-charge e-mail accounts to send e-mails. Note that some ISPs work with encryption or can be accessed and used only via the web server's DSL connection.

The following list is not conclusive, ISPs are subject to change.

Free e-mail account providers

Address mail server Port mail server Authentification Restriction

blueVARIA.de mail.bluevaria.de 25 Yes

GMX

Google Mail

Hotmail smtp.gmail.com 587 Yes

TLS required smtp.live.com 587 Yes TLS required

WEB.DE

Yahoo! Mail

Online service provider

smtp.web.de 25 Yes smtp.mail.yahoo.com 25 Yes

Alice DSL

AOL

AOL

Arcor

CompuServe

Freenet

T-Online

Note smtp.alice-dsl.net 25 Yes smtp.de.aol.com 587 Yes smtp.aim.com 587 Yes mail.arcor.de 25 Yes smtp.compuserve.de 25 mx.freenet.de 25

Yes

Yes smtpmail.t-online.de 25 Yes

Additional information on free e-mail providers:

• http://www.patshaping.de/hilfen_ta/pop3_smtp.htm

• http://www.iopus.com/guides/bestpopsmtp.htm

Siemens is not responsible for third-party page contents.

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

101 / 116

CE1C5712en

28.08.2012

RNDIS driver

Note

Automatic installation

7.3.3 Install RNDIS driver

The PC requires a USB RNDIS driver for the connection between the PC and the web server.

Windows hardware recognition recognizes the web server when the USB cable is plugged into the USB cable. You can start the Add Hardware Wizard if no RNDIS driver is installed.

The driver is installed in the background using an Internet connection. You can install the driver manually without an Internet connection.

The operating system must be equipped with the latest updates.

Procedure:

1. Select "Search for and install the hardware automatically (Recommended)".

2. Click [ Next > ]

The software is installed.

3. Confirm hardware installation:

Click [ Continue installation ]

4. Wait until installation is complete and click [ Finish ]

Result The RNDIS driver is now installed.

The PC can communicate with the web server via USB.

102 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

CE1C5712en

28.08.2012

Manual installation

The RNDIS driver is supplied on the web server at http://<IP address>/drivers/

can be accessed via Ethernet connection (see Section 2.6.1).

Result

Note

Alternative configuration

The driver Siemens_RNDIS_Driver_x64.msi is installed on a 64-bit operating system; on a 32-bit operating system Siemens_RNDIS_Driver_x86.msi. The installation file for the driver can be executed directly on the PC. Following the steps for the installation wizard.

The RNDIS driver is now installed.

The PC can communicate with the web server via USB.

The RNDIS driver is installed as part of the ACS790 Siemens software installation.

7.3.4 Alternative network configuration

We recommend setting up IP settings for commissioning as an alternative configuration if a PC, connected to a network, is temporarily used to commission the web server and the local area network.

On the PC, set as follows:

1.

Select Start > Control Panel > Network Connections > Local Area Connection

2. Select the "General" tab.

3. Click [ Properties ]

Continued on next page.

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

103 / 116

CE1C5712en

28.08.2012

4. Select "Internet Protocol (TCP/IP)".

5. Click [ Properties ]

6. Select "Alternate Configuration" tab.

7. Enter IP address, subnet mark and operational standard gateway as well as DNS server.

Result The PC assumes the configuration with these settings as soon as it is no longer integrated in the standard network.

104 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

CE1C5712en

28.08.2012

7.3.5 Siemens routers

We recommend the following router from Siemens to connect to an internal network with DSL connection:

We recommend the Gigaset SX763 WLAN dsl by Siemens. This router supports all requirements for trouble-free operation of web server.

Performance features

Technical data

Protocols / Service

DoS attack

Denial of Service

• 1 connection for analog, leased line network.

• 2 internal connections for analog devices (phone, fax, answering machines).

• Integrated phone system for up to 6 extensions (analog, LAN, WLAN).

• 4 Ethernet ports to network PC or other LAN.

• WLAN (IEEE 802.11b/g) with variable reduction of WLAN transmission.

• 6 VoIP accounts can be configured.

• USB 2.0 host connection for printer or external storage media.

• Ready for connection to home entertainment services.

• Remote management.

• Integrated SIP proxy.

• Security and firewall functionality.

• Easy installation and setup.

TCP/IP, UDP, DHCP server/client, HTTP/ HTTPS, DNS, RIPv1/v2, Telnet, UPnP,

IGMP, NTP, port forwarding, DynDNS, preconfigured gateways, backup, NAT,

URL/port filter, DoS blocking, packet inspection, firewall, WPA2, WPA, 64/128-bit

WEP encryption, SSID broadcast can be deactivated, Mac filter.

High-speed WLAN gateway for triple play services: Supports Internet, home entertainment, leased line and VoIP.

When buying routers, make sure they can defend against DoS attacks

(function is available on most commercially available routers).

A DoS attack is a special type of hacker attack on computers and networks with connection to the Internet.

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

105 / 116

CE1C5712en

28.08.2012

7.4 Glossary of Ethernet and Internet terms

ADSL

Upstream and downstream channel transport data at different rates, i.e. asymmetrically via a two-wire line (DLS, copper phone line) on a broadband network.

Very little data is sent upstream, i.e. to the server, when surfing. The requested data, however, are sent at high speed downstream to the requesting computer.

You can call or e.g. send faxes while transmitting data.

The Internet Service Provider ISP provides the ADSL connection. You need a DSL modem for this type of connection.

See ADSL

Asymmetrical Digital

Subscriber Line

Bit rate

Broadcast

Client

Default gateway

Denial of Service

DHCP

The bit rate describes the transmission speed or rate in bits per second (bps).

Data sent out to all participants on the network.

A client is a network device unable to execute certain services and thus requests those services from the server. The server provides the service and sends a reply.

Gateway that is selected when one IP address is outside its own subnet and therefore the standard gateway is unknown.

See DoS attack

The new Dynamic Host Configuration Protocol allows for dynamic allocation of a network configuration to clients (PC, web server) via a server (router).

Digital Subscriber Line

see DSL

DNS

The DNS allows for assigning IP addresses to names (that are easier to remember than 32-bit IP addresses). A DNS server must manage this information for each LAN with Internet connection. When you select an Internet page, the web browser accesses the IP address of that site assigned by the DNS server to open a connection.

On the Internet, domain names are assigned to IP addresses as per a hierarchical system. A local PC only knows the address of the local DNS server. This server, in turn, knows the addresses of all PCs on the local network as well as that of the higher DNS servers that, in turn, know the addresses of the next higher DNS servers.

The domain name is the web server designation on the Internet. The DNS server

Domain name

assigns an IP address to the domain name.

Domain Name System

See DNS

DoS attack

A DoS attack (denial of service) is a special type of hacker attack on computers and networks connected to the Internet. The DoS attack aims at disabling computers and networks to prevent network resources from being provided and services from being executed.

106 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

CE1C5712en

28.08.2012

DSL

DSL router

Dynamic DNS

Dynamic Host

Configuration Protocol

Dynamic IP address

DynDNS

Ethernet

Firewall

Gateway

HTTP proxy

HTTPS

Hub

DSL is a type of data transmission allowing for 1.5 Mbps access to the Internet on standard copper phone lines. The Internet Service Provider ISP provides the DSL connection. You need a DSL modem for this type of connection.

The DSL router has several functions. It connects the Ethernet network (LAN) and the internal network devices to the Internet. The router then requests the IP addresses for the internal network devices from the DNS server. Port forwarding (NAT,

PAT) is also configured in the router. In addition, service "DynDNS", which automatically is updated after a change of the DynDNS server, is activated in the router.

See DynDNS

See DHCP

A dynamic IP address is assigned automatically via DHCP to a network device.

As a result, the IP address for a network device differs every time the device logs in or at periodic intervals.

The ISP assigns dynamic IP addresses to network devices that are not online continuously, i.e. integrated in the network. Dynamic IP addresses are reassigned to other devices, as the number of addresses is limited. Web server (permanently online) does not use a dynamic IP address.

The DNS server assigns domain names and IP addresses. Dynamic DNS

(DynDNS) is needed for dynamic IP addressing. It allows deployment of a network device with dynamic IP address on the Internet.

DynDNS ensures that a service is always available on the Internet under the same domain name regardless of the current IP address.

A domain name can be registered with a DynDNS service.

Ethernet is a network technology for local networks (LAN). Ethernet operates at a transmission rate of 10 or 100 Mbps and has a maximum range of 100 meters between two network components.

A firewall protects networks against unauthorized access from the outside.

Firewalls are hardware and/or software measures designed to control data exchange between the private network to be protected and an unsecured network

(e.g. the Internet).

A gateway is a device connecting networks of different architecture (addressing, protocols, interfaces, etc.). Although not entirely correct, the term often is used interchangeably with router.

A proxy is a server used by network devices for Internet traffic. All requests are sent via the proxy server.

The web server supports HTTPS (Hyper Text Transfer Protocol Secure).

A hub in a star-topology network connects various network devices by receiving all data from one device and forwarding it to other devices.

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

107 / 116

CE1C5712en

28.08.2012

Hyper Text Transfer

Protocol Secure

Internet

Internet Protocol

Internet Service

Provider

IP

IP address

IP address pool

LAN

Local Area Network

MAC address

Mbps

Media Access Control

See HTTPS

The Internet is a data network with millions of members. A number of protocols are used to exchange data, summarized under the term TCP/IP.

All devices connected to the Internet can be identified via IP address. The DNS server assigns domain names to IP addresses.

See IP

See ISP

The IP protocol is a TCP/IP protocol. It is responsible for addressing devices on a network based on IP addresses and transmitting data packages from sender to recipient. The IP protocol determines the order and network connection used to send data packages (routing).

The transmission control protocol TCP reassembles the data packages in the right order at the recipient.

The IP address is a unique address of a network device on the network based on

TCP/IP protocols. The IP address consists of four sections, separated by a dot

( 192.168.1.1

).

The IP address comprises the network number and the computer number

(number of the network device). Depending on the subnet mask, one, two or three portions form the network or computer number.

IP addresses can be assigned automatically or manually. On the Internet, domain names are used rather than IP addresses. The DNS server assigns domain names to IP addresses.

IP address pool defined at the router (IP address range) the DHCP server can be used to assign dynamic IP addresses.

A local network (size: large building, building sites) is a number of interconnected network devices. In LANs, data is exchanged and resources are used jointly. A

LAN can be connected to other networks such as WAN or Internet.

See LAN

The MAC address allows for worldwide identification of a network adapter (network card). It consist of hexadecimal numbers, grouped in six portions at 2x4 bit each, thus 48 bit, e.g. 00-55-96-5D-00-2C. The MAC address is assigned by the network adapter manufacturer and cannot be changed.

Million bits per second indicates the transmission rate in a network.

See MAC address

108 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

CE1C5712en

28.08.2012

NAT

Network

NAT is a method to translate IP addresses (private IP addresses) in a network into one or several public IP addresses on the Internet. NAT allows us to use several network devices in a LAN together with a public IP address of a router for Internet access.

The network devices of the local network are masked by the IP address (router) registered on the Internet. Thanks to this security function, NAT often is used as a part of a network's firewall. Web server is accessible from a public network thanks to the correct NAT table definition; see also port forwarding.

A network (LAN, WAN) is a linked group of devices connected via various lines or radio sharing common resources such as data or peripheral devices.

Network adapter

Network Address

Translation

Network configuration

PAT

Plant room

Hardware to connect network components to a local area network (LAN).

Connection can be wired or wireless.

See NAT

All settings an IP-based device requires to work on a network: IP address, subnet mask, standard gateway, preferred DNS server, and alternate DNS server.

PAT or NPAT (Network and Port Address Translation) translates all private network addresses into one public (dynamic) IP address. In this process, port numbers are exchanged in addition to addresses when there is a connection. As a result, an entire private network only requires one single registered public IP address.

The ISP provides the connection to the Internet via DSL or cable TV (at a fee).

Point-to-Point Protocol

See PPP

Port

Ports are used to exchange data between different applications on a network. The port number addresses the application within a network device. The combination of IP address and port number serves as a unique identification of the recipient or the sender of the data package with the network.

Internet service applications work with set port numbers (HTTP 80, FTP 21).

See http://www.iana.org/assignments/port-numbers for registered port numbers.

Port and Address

Translation

Port Forwarding

Port numbers 0 to 49151 are set and reserved, port numbers 49152 to 65535 are dynamic (and therefore available).

See PAT

With port forwarding, the router forwards data packages from the Internet, destined for a particular port, to the port of the responsible network device. As a result, serv-

PPP

PPP over Ethernet

ers (web server) integrated in a LAN, can be reached from the Internet (without a need for a public IP address). Port Forwarding is achieved by the correct NAT /

PAT definition in the router.

Protocol for dial-up connection of a computer to the ISP.

See PPPoE

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

109 / 116

CE1C5712en

28.08.2012

PPPoE

Private IP address

Protocol

Provider

Public IP address

Router

Secure Sockets Layer

Server

Simple Mail Transfer

Protocol

SMTP

SSL

Standard gateway

Protocol used to connect to the Internet via ADSL or DSL.

The private IP address (local IP address) is the address of a network device on a local network (LAN). The provider assigns this address at will. DSL routers have a public IP address for the WAN and a private IP address for the LAN. The following

IP ranges are recommended for private IP addresses:

10.0.0.0…10.255.255.255  Class A.

172.16.0.0…172.31.255.255  Class B.

192.168.0.0…192.168.255.255  Class C.

The first IP address xxx.xxx.xxx.0 and the last IP address xxx.xxx.xxx.255 in a network segment cannot be used, as xxx.xxx.xxx.0 is reserved for the network and xxx.xxx.xxx.255 for broadcasting.

A protocol describes the type of communication on a network. It contains rules on opening, managing, and closing a connection, on data formats, time sequences, and possible error correction. Different protocols are needed to allow two applications at different levels to communicate with each other, e.g. TCP/IP protocols on the Internet.

Provider of telecommunications services. Also referred to as network provider or network operator.

The public IP address is the worldwide valid (global) address of a network device on the Internet. The ISP assigns these addresses. A network device with public IP address is a device establishing a connection between local network LAN and the

Internet.

DSL routers have a private IP address for the LAN and a public IP address for the

WAN (Internet).

A router forwards data packages from a local network LAN to a higher network while selecting the fastest route. A router allows for connecting different networks with different network topologies. For example, the router connects a local network to the Internet.

See SSL

A server accepts requests from clients, processes them and responds to the clients. Network servers, data servers, web servers also assume services for other network devices.

See SMTP

The SMTP protocol is a TCP/IP protocol. It controls e-mail traffic on the Internet.

The ISP provides the SMTP server (mail server).

Outdated form for TLS; see TLS.

A standard gateway (see also DSL router) is also referred to as a network address used by clients to send their packages if the target address is outside the immediate network.

110 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

CE1C5712en

28.08.2012

Static IP address

Subnet

Subnet mask

Switch

TCP

TCP/IP

TLS

Transmission Control

Protocol

Transport Layer

Security

UDP

Network devices, and servers in particular, integrated permanently in a network, have static IP addresses. Clients often have a dynamic IP address.

Web server (integrated permanently in a network) has a static IP address and can thus be reached easily by clients.

A subnet subdivides a network into smaller network segments.

A subnet mask masks the IP address, i.e. it determines which parts of the IP address form the network number and which parts the computer number (e.g. server).

Subnet mask 255.255.255.0 means that the first three sections of the IP address determine the network number, and the fourth section is used for the computer number. In this case, the first three IP address sections are identical for all network devices. Example:

Subnet mask 255.255.255.0 masks IP addresses: 192.168.1.1…192.168.1.254.

Please note: Do not use the first IP address 192.168.1.0 and last IP address

192.168.1.255.

A switch, similar to a hub, is a connecting element to connect various network segments or network devices. Contrary to the hub, a switch is an intelligent device used to route packages only to the subnet or network device for which a package is destined.

The TCP protocol is a TCP/IP protocol. TCP is responsible for transporting data between two communication partners (applications). TCP is a secured transmission protocol, i.e. a connection is established, monitored and disconnected to data transmission.

TCP is a so-called connection-oriented protocol. The transmission control protocol

TCP reassembles the data packages, sent by the Internet protocol IP via different network connections, in the right order at the recipient.

Family of protocols used as the basis for the Internet. TCP/IP for the basis for any number of internet services such as HTTP (Web), FTP (file transfer) and

SMTP (mail).

TLS (Transport Layer Security, for [outdated]: SSL Secure Sockets Layer) a hybrid encryption protocol to transmit data over the Internet. TLS 1.0, 1.1 and

1.2 are standardized developments of SSL 3.0 (TLS 1.0 is now used for SSL 3.1).

In other words, SSL is being further developed under the name TLS.

The web server always uses TLS for e-mails to the extent supported by the e-mail provider supports.

See TCP

See TLS

UDP is a TCP/IP protocol to control data traffic between two communication partners (application). UDP, in contrast to TCP, is an unsecured protocol. UCP is a socalled connection-less protocol. Data packets are broadcast. The recipient is responsible for receiving data. The sender does not receive notification if the data packages were received.

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

111 / 116

CE1C5712en

28.08.2012

Uniform Resource

Locator

See URL

Universal Plug and Play

See UPnP

UPnP

UPnP technology was designed for home and office networks. Devices supporting

UPnP automatically configure their network settings as soon as connected to a

URL

network. In addition, they automatically provide, depending on class, own services or use services of other devices on the network.

A URL refers to an information source, e.g. http://www.siemens.com. The URL is a uniform web address that is used to determine the network protocol used (e.g. http) or the location of the resource on the network.

User Datagram Protocol See UDP

WAN

The wide area network WAN has a spatial dimension of ca. 50 km. A WAN can comprise a number of several LANs. If an ISP operates a WAN, private LAN users receive access to the Internet.

Wide Area Network

Wireless LAN

WLAN

See WAN

See WLAN

Wireless LANs allow network devices to communicate via radio. The WALN can be added as an extension to a wired LAN, or it can be the basis of a new network.

112 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Appendix

CE1C5712en

28.08.2012

Index

A

Abbreviations ........................................................ 12

Activate Energy indicator function ........................ 75

Address Translation (NAT).................................... 90

Administer user accounts ..................................... 16

Alternative network configuration ....................... 103

B

Bus device operation ............................................ 41

C

Commissioning

Create device list............................................... 18

Final steps ......................................................... 37

Functional check ............................................... 34

LAN ................................................................... 32

Log into web server........................................... 15

Message recipient ............................................. 30

Network components ........................................ 32

Prep web server ................................................ 14

Prerequisites ..................................................... 13

Router settings .................................................. 33

Settings ............................................................. 23

Communication

Email ................................................................. 93

LAN ................................................................... 85

Remote control.................................................. 85

Create own plant web pages ................................ 59

D

Deactivate Energy indicator function

Confirmation message ...................................... 74

Data point monitoring ........................................ 73

Green limits to default values............................ 74

Monitoring off..................................................... 74

Summary checkbox........................................... 74

Device Description................................................ 65

Device information ................................................ 44

Ethernet............................................................. 46

LPB / BSB ......................................................... 45

Dialog box Energy indicator

Data point value ................................................ 77

Enumeration data points ................................... 79

General.............................................................. 77

Green limit(s)..................................................... 78

Numeric data points .......................................... 78

Setting range..................................................... 77

Display and operating elements ............................. 8

DynDNS................................................................ 92

E

E-mail Energy indicator

Configure E-mail receiver ..................................80

Contents.............................................................82

Energy indicator of plant ....................................80

Mailbox...............................................................81

Energy indicator

Green leaf ..........................................................63

Grey leaf ............................................................63

Orange leaf ........................................................63

Summary display ...............................................71

Temporary status ...............................................72

Visibility ..............................................................70

Energy indicator function, Data point monitoring ..75

F

Fault codes............................................................99

Faults current local ................................................47

Faults, Message triggering ....................................28

Firewall ..................................................................90

Function Energy indicator

Commissioning ..................................................72

Estimated processing time.................................73

Monitored data points and green limit(s) ...........63

Number of monitored data points ......................69

User groups service and end user.....................79

G

Glossary ..............................................................106

H

HIT.........................................................................57

I

Install RNDIS driver, Automatically......................102

Invalid characters ..................................................99

L

Levels Energy indicator function

Data points.........................................................68

Partial plants ......................................................67

Plant...................................................................66

M

Message recipient

Holidays/special days ..................................31, 44

Monday...Sunday, special day .....................30, 43

Siemens

Building Technologies

Web server OZW672... V4.0

Index

113 / 116

CE1C5712en

28.08.2012

O

Operate the plant .................................................. 41

Operate&monitor................................................... 53

Operation

Faults................................................................. 47

File transfer ....................................................... 48

Overview ........................................................... 39

P

Plant diagrams ...................................................... 57

Plant state Energy indicator

Green leaf.......................................................... 71

Orange leaf........................................................ 71

Summary display............................................... 71

Plant web page (example) .................................... 54

Plant web pages ................................................... 53

Port Forwarding (PAT) .......................................... 91

Primary navigation .................................................. 9

R

Remote operation via the Internet ........................ 89

S

Secondary navigation ............................................. 9

Settings

Email

Email address sender .................................... 26

Mail server address ....................................... 26

Mail server port number................................. 26

Ethernet

IP address...................................................... 24

Subnet mask .................................................. 24

Fault input 1…2 ................................................. 28

LPB / BSB, Clock time supplier......................... 24

Message recipients 1 to 4 ................................. 27

Time/Date .......................................................... 22

Daylight saving time ...................................... 23

Time zone...................................................... 23

Web server, Language...................................... 23

Standard applications ........................................... 57

Start Function Energy indicator ............................ 72

Summary checkbox Energy indicator................... 74

Summary display Energy indicator....................... 71

Supply state.......................................................... 38

Symbols.................................................................11

System faults ........................................................ 47

System report ....................................................... 27

T

Terms.................................................................. 106

Text entry .............................................................. 99

Time/date.............................................................. 22

Tree leaf as Energy indicator................................ 63

U

UPnP localization ................................................. 26

User levels............................................................ 10

V

Valid characters .................................................... 99

Visibility Energy indicator...................................... 70

Visualize ............................................................... 53

W

Web operation, user interface ................................ 9

Web page

Energy indicator function .................................. 64

Energy indicator update.................................... 72

Web server diagnostics ........................................ 44

Web server faults.................................................. 47

Web server operation ........................................... 41

114 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

Index

CE1C5712en

28.08.2012

Siemens

Building Technologies

Web server OZW672... V4.0

115 / 116

CE1C5712en

28.08.2012

Siemens Switzerland Ltd

Infrastructure & Cities Sector

Building Technologies Division

Gubelstrasse 22

CH-6301 Zug

Tel. +41 41-724 24 24 www.siemens.com/sbt

116 / 116

Siemens

Building Technologies

Web server OZW672... V4.0

© 2010-2012 Siemens Switzerland Ltd

Subject to change

CE1C5712en

28.08.2012

advertisement

Key Features

  • Control and monitor your building automation system from anywhere in the world
  • Intuitive web interface makes it easy to access and manage all of your devices
  • Energy indicator function can help you to reduce your energy consumption
  • Advanced features and ease of use make it the perfect solution for managing your building automation system

Related manuals

Frequently Answers and Questions

How do I get started with the OZW672?
To get started with the OZW672, you will need to turn on the web server and log into the web interface.
How do I create a device web page?
To create a device web page, you will need to go to the "Create device web pages" section of the web interface.
How do I commission network components?
To commission network components, you will need to go to the "Commission network components" section of the web interface.