Troubleshooting - FR. Bosch Greenstar 131

Add to My manuals
80 Pages

advertisement

Troubleshooting - FR. Bosch Greenstar 131 | Manualzz

TROUBLESHOOTING - FR110

9 TROUBLESHOOTING - FR110

BUS device faults are indicated.

If the controller shows Fault 12, the cylinder temperature is so high that the cylinder High Limit

Thermal Cut-out has tripped.

B Reset the High Limit Thermal Cut-out.

9.1

TROUBLESHOOTING USING THE DISPLAY

The current fault is indicated on the controller:

9 12 h 15

1

6

3

18

2

B Identify the BUS device affected by the current fault.

The fault can only be rectified on the BUS device from which the fault originates.

4

3 24 h

21

8716115748-10.1Wo

3

4

Fig. 17 Fault display

1

2

Fault number

BUS device which detected the fault and reported it to the controller

Description of fault

Code or additional information about fault

Information displayed

(Æ items 1, 3 and 4 in Fig. 17 )

Text

Fault 01

BUS communication fault

Fault 02

Internal fault

Fault 02

Internal fault

Some parameters reset to factory settings due to EEPROM problem

Fault 02

Internal fault

FR110 can no longer control the CH system

Fault 03

Room temp sensor faulty

Code Cause

200 Boiler no longer reporting.

Remedy

Check BUS device, BUS connection and repair circuit break if necessary.

Identify and replace incorrect 201 Incorrect BUS subscriber connected.

BUS device.

40 Incorrect module type detected.

Replace IPM.

100 ISM not responding.

Check BUS connection and repair circuit break if necessary.

205 Some parameters reset to default. Check parameter settings and

255 FR 110 can no longer control the heating system.

readjust them as necessary.

Identify faulty controller and replace.

Identify faulty controller and replace.

20

21

There is a circuit break on the room temperature sensor built into the FR 110.

There is a short circuit on the room temperature sensor built into the FR 110.

Identify faulty controller and replace.

Tab. 32

8 716 115 748 (2009/09) 63

TROUBLESHOOTING - FR110

Information displayed

(Æ items 1, 3 and 4 in Fig. 17 )

Text

Fault 11

System configuration: new BUS device

New ISM detected. Power up all ISMs simultaneously and start automatic system configuration.

Fault 12

System configuration: BUS device missing

ISM1 not detected. Check connection.

Fault 13

System configuration: BUS device changed or replaced

Check system configuration for DHW or start automatic system configuration.

Fault 13

System configuration: BUS device changed or replaced

Check system configuration for heating circuit x and connections on IPM for heating circuit x.

Fault 14

System configuration: incompatible

BUS device

DHW controlled by boiler. IPM control of DHW has no effect.

Fault 14

System configuration: incompatible

BUS device

IPM for cylinder must be set to identification 3 or higher.

Fault 19

Unable to save parameter settings

Code Cause

131

132

New ISM detected.

Remedy

Power up all ISMs simultaneously and start automatic system configuration.

170

171

HLC has tripped or is faulty.

Check HLC.

Check solar parameter T2

ISM1 no longer detected despite

Is thermal disinfection active?

Check connection.

having been configured.

157 BUS device changed or replaced.

Check system configuration for hot water system or start automatic system configuration.

159 BUS device changed or replaced.

Check system configuration for heating circuit x.

117 Incompatible BUS device:

118

119

Incompatible BUS device:

Identify incompatible BUS device and remove from the system.

Set IPM for cylinder to coding 3 or higher.

Fault 33

Temperature sensors incorrectly connected

Fault 40

Temperature sensor T1 on collector group 1 faulty

Fault 41

Temperature sensor T2 at bottom of solar cylinder faulty

Tab. 32

202

22

101

BUS device is configured but not available at present.

A temperature sensor is connected to the IUM.

Short circuit on the sensor lead

(T

1

).

102 Break in the sensor lead (T

1

).

103 Short circuit on the sensor lead

(T

2

).

104 Break in the sensor lead (T

2

).

Check system layout, check system configuration, modify if necessary and set parameter again.

Remove the temperature sensor and insert a coding plug if necessary.

Check temperature sensor (T

1

) and replace if necessary.

Check temperature sensor (T and replace if necessary.

2

)

64 8 716 115 748 (2009/09)

TROUBLESHOOTING - FR110

Information displayed

(Æ items 1, 3 and 4 in Fig. 17 )

Text

Fault 50

Solar pump jammed or air in system

Fault 51

Incorrect temperature sensor type connected

Fault 52

Temperature sensors reversed

Fault 53

Temperature sensor fitted in wrong location

Fault 54

Temperature for thermal disinfection not reached in solar cylinder

Fault 55

Solar system not yet commissioned

Fault 56

At least one pump/valve in manual mode

Code Cause

121 Solar pump (SP) sticking due to physical blockage.

Air in solar thermal system.

122 Collector temperature sensor type used as cylinder temperature sensor (T

2

).

123 Cylinder temperature sensor type used as collector temperature sensor (T

1

)

132 Temperature sensor type PTC

1000 used as cylinder temperature sensor (T

2

).

133 Temperature sensor type PTC

1000 used as collector temperature sensor (T

1

).

124 Temperature sensors (T

1

and T

2

) reversed.

Remedy

Unscrew and remove the slotted screw on the pump head and use a screwdriver to release the pump shaft. Do NOT strike the pump shaft with the screwdriver.

Bleed solar system and top up with heat transfer fluid if necessary.

Use correct type of temperature sensor. Æ Technical data in ISM installation instructions.

125 Collector temperature sensor (T

145 fitted on collector array inlet.

Maximum temperature for solar cylinder too low.

Delivery rate of disinfection pump

(PE) too low.

Thermal disinfection cancelled manually before the required temperature was reached in the solar cylinder.

146 Solar system is not yet in operation.

1

)

Check the temperature sensors and swap the connections if necessary.

Fit collector temperature sensor

(T

1

) close to collector array outlet.

Set higher maximum temperature for solar cylinder.

Æ Limiting cylinder temperature.

Set higher pump speed on disinfection pump (PE) or, if possible, open flow restrictor more.

This is not a fault. Message is shown only for 5 minutes.

147 Pump (SP) in manual mode.

Fill, bleed and prepare the solar thermal system for commissioning according to its documentation. Then start up the solar system.

Reset parameters for pump or valve to “Auto”.

Tab. 32

8 716 115 748 (2009/09) 65

TROUBLESHOOTING - FR110

Information displayed

(Æ items 1, 3 and 4 in Fig. 17 )

Text

Fault 59

Mass flow rate in solar system too high/ low.

Code Cause

201 Mass flow rate in solar system for collector group 1 is too high.

202 Mass flow rate in solar system for collector group 1 is too low.

Remedy

Set mass flow in solar system correctly (e.g. increase/ decrease pump speed) and if necessary open or close flow restrictor more on solar station.

Guide figure: 20 - 40 kg/m 2 of collector area per hour.

Check setting for collector area, type and climate zone on Solar optimisation menu.

Tab. 32

66 8 716 115 748 (2009/09)

advertisement

Related manuals

advertisement

Table of contents