Specifications. Honeywell TRIPLEAQUASTAT L8151A, L8151A


Add to my manuals
6 Pages

advertisement

Specifications. Honeywell TRIPLEAQUASTAT L8151A, L8151A | Manualzz

L8151A

SPECIFICATIONS • INSTALLATION • ORDERING INFORMATION

IMPORTANT: The specifications given in this publication do not include normal manufacturing tolerances.

Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

MODEL: L8151A Triple Aquastat ® Relay for remote bulb control of hydronic heating systems that include domestic hot water.

ELECTRICAL RATINGS:

Power Supply: 120 Vac, 60 Hz; 220 Vac, 50 Hz and

240 Vac, 60 Hz operation.

Contact Ratings (A): See Table 1.

Full Load

TABLE 1—CONTACT RATINGS.

Locked Rotor

120 Vac

7.4

44.4

240 Vac

3.7

22.2

MAXIMUM POWER CONSUMPTION: 8W at 120 Vac,

60 Hz.

Specification

MAXIMUM AMBIENT TEMPERATURE: 150 °F (66°C) at case. 265 °F (130°C) at sensing element.

PRESSURE RATING: 200 psi (1380 kPa) on outside of immersion well.

THERMOSTAT HEAT ANTICIPATOR SETTING: 0.2A.

LOW LIMIT (Fig. 2):

Function: Maintains water temperature at setting during thermostat off periods.

Setting: 110 °F to 220°F adjustable (43°C to 104°C).

Differential: 10 °F to 25°F adjustable (6°C to 14°C).

HIGH LIMIT (Fig. 2):

Function: Opens burner circuit if water temperature reaches high limit setting.

Setting: 130 °F to 240°F adjustable (54°C to 116°C).

Differential: 10 °F fixed (6°C).

MOUNTING MEANS: Mounting lugs on back of case.

DIMENSIONS: See Fig. 1.

SENSING ELEMENT: 3/8 x 2-7/8 in. (10 x 73 mm).

CAPILLARY LENGTH: 36 in. (914 mm), armored capillary.

UNDERWRITERS LABORATORIES INC. LISTED: File

No. MP466, Guide No. MBPR2.

Installation

WHEN INSTALLING THIS PRODUCT...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3. Installer must be a trained, experienced service technician.

4. After installation is complete, check out product operation as provided in these instructions.

WARNING

CAN CAUSE PROPERTY DAMAGE,

SEVERE INJURY OR DEATH.

Product is for use only in a system with a pressure relief valve.

Ordering Information

When purchasing replacement and modernization products from your TRADELINE ® wholesaler or distributor, refer to the Tradeline ®

Catalog or price sheets for complete ordering number, or specify—

1. Order number.

2. Accessories, if desired.

3. Order additional system components and system accessories separately.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1. Your local Home and Building Control Sales Office (please check the white pages of your phone directory).

2. Home and Building Control Customer Logistics

Honeywell Inc., 1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and

Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,

Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

60-2553—3 2

CAUTION

• Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.

• Avoid making sharp bends or kinks in the capillary. Bends should be no less than 1 in. (25 mm).

IMPORTANT: Terminals on these Aquastat ® Relays are approved for copper wire only.

L8151A

INSTALLATION

IMMERSION WELL MOUNTING

NOTE: Immersion well must be ordered separately. For a list of available wells, refer to form 68-0040, Wells and

Fittings for Temperature Controllers.

The boiler manufacturer generally provides a tapping for the immersion well. This tapping should be located at a point where typical water temperature can be measured.

The immersion well must never be located close to a hot or cold water inlet or a steam coil, or where the pressure exceeds 200 psi (1380 kPa).

If the system is filled, drain to a point below the selected installation location.

Fig. 1—Approximate L8151 dimensions in in.

(mm).

1/8

(3)

Fig 2— Internal view of L8151.

1-1/2

(38)

1-7/16

(37)

2-3/16

(56)

GROUNDING SCREW

VOLTAGE BARRIER

TRANSFORMER

FOR THERMOSTAT

CIRCUIT

13/64 X 21/64 (4)

CAPILLARY

30 IN. (762)

4-1/2

(114)

6-1/8

(156)

DIFFERENTIAL

SETTING

CIRCULATOR

RELAY

LOW LIMIT SETTING

4-5/16 (110)

4-23/32 (120)

1-1/4

(32)

1-1/4

(32)

HIGH LIMIT SETTING M8893

KNOCKOUT

FOR 1/2 IN.

CONDUIT (5)

13/16

(21)

2-3/6

(56)

3-5/16

(84)

M8892

MOUNTING THE CASE

Mount the case in a convenient location near the boiler.

Remember that the shielded capillary must reach from the case to the immersion well. This maximum ambient temperature of the selected location must not exceed 150 °F

(66 °C) at the case, 265°F (130°C) at the sensing element.

1. Screw the well into the boiler, tank, or pipe tapping.

2. Insert the bulb into the well, pushing tubing until bulb bottoms in well. Avoid making sharp bends or kinks in the capillary. Bends should be no sharper than 1 in. (25 mm) radius.

3. Attach the retainer clamp to end of well spud. Loosen draw nut and spread jaws of clamp with screwdriver if necessary, Fig. 3.

3 60-2553—3

L8151A

INSTALLATION

Fig. 3—Remote bulb installation.

JAWS

SPREAD JAWS

TO FIT OVER

RIDGE ON SPUD

OF WELL

SCREWDRIVER

INSERT— MOUNTING CLAMP

DRAW

NUT

B

MOUNTING

CLAMP SPUD

BULB

WELL

TUBING

A

M8777

4. With part no.121371AA Retainer Clamp attached to well spud (be sure jaws of clamp hook over ridge at end of spud, as shown at points A), adjust tubing to fit through retainer clamp groove, as shown at point B.

5. Tighten draw nut so that retainer clamp is firmly attached to well spud and tubing is held securely in place. Be careful not to damage the capillary.

6. Carefully coil the excess capillary at the bottom of the

Aquastat ® case.

WIRING

CAUTION

• Disconnect power supply before wiring to avoid electrical shock or equipment damage.

• Be sure the terminal connections are inside an enclosure that meets local codes.

IMPORTANT: Terminals on the L8151A Aquastat ® Relay are approved for use only with copper wire. The terminals allow wraparound wiring only.

1. Strip 7/16 in. of insulation from the wire end.

2. Wrap the wire at least three fourths of the distance around the screws as shown.

3. Use a standard flat-headed screwdriver to tighten the

M8843 screw until the wire is snugly in contact with the screw and contact plate.

4. Tighten the screw an additional one-half turn.

NOTE: Do not use a push-type ratchet screwdriver.

All wiring must comply with local electrical codes and ordinances. The limits given in the Specifications section must not be exceeded when applying this control. Use manufacturer instructions when wiring controlled equipment or refer to typical hookups in Fig. 4 through 6.

When the B1 terminal on the device being replaced is

1/4 in. tab terminal, use the existing wiring harness terminals to install the replacement device. When the B1 terminal on the device being replaced is a screw terminal, insert the provided tab terminal to screw terminal adapter on the

1/4 in. tab terminal of the replacment device. After the adapter is installed, the existing wraparound wire end can be reused to make an electrical connection to the B1 terminal.

NOTE: Do not use a push type ratchet screwdriver.

1. Strip 7/16 in. of insulation from the wire end.

2. Wrap the wire at least three-fourths of the distance around the screw as shown.

3. Using a standard, flat-headed screwdriver, tighten the screw until the wire is snugly in contact with the screw and contact plate.

4. Tighten the screw an additional one-half turn.

Fig. 4—Typical hookup for L8151A in a single zone system.

LOW VOLTAGE

THERMOSTAT

T

THERM.

T

C1

CIRC.

C2

1

LINE

2

ZC

ZR

B1

BURNER

B2

3

X

X

1

L1

(HOT)

L2

G 2

X

X

X

X

2

1

OR

OIL BURNER

RELAY

LINE TERMINAL

LINE VOLTAGE

GAS VALVE

LINE VOLTAGE

CIRCULATOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND

OVERLOAD PROTECTION AS REQUIRED.

2 CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.

USE GROUNDING SCREW PROVIDED.

3 B1 IS 1/4 IN. TAB TERMINAL.

M8886

60-2553—3 4