CBECC-Res USER MANUAL FOR CALIFORNIA BUILDING

Add to my manuals
153 Pages

advertisement

CBECC-Res USER MANUAL FOR CALIFORNIA BUILDING | Manualzz

CBECC User Manual

Mechanical Systems

Table 8-3: Cooling Equipment

Descriptor

Ductless Split Air

Conditioner

Evaporative Direct

Evaporative

Indirect/Direct

Evaporative Indirect

Cooling Equipment Reference

Split air conditioning outdoor unit that uses refrigerant to transport cooling to at least one terminal in each habitable space in the dwelling unit. These include small ductless mini-split and multiple-split air conditioners. Distribution is non-ducted.

[Efficiency metric: EER]

Direct evaporative cooling systems. Assume minimum efficiency air conditioner.

The default distribution system is ducts in attic. [Efficiency metric: SEER]

Indirect-direct evaporative cooling systems. Assume energy efficiency ratio of 13

EER. Requires air flow and media saturation effectiveness from the Energy

Commission appliance directory. Distribution is ducted or non-ducted. [Efficiency metric: EER]

Indirect cooling systems. The default distribution system is duct in attic; evaporative cooler duct insulation requirements are the same as those for air conditioner ducts.

Assume energy efficiency ratio of 13 EER. Requires air flow and media saturation effectiveness from the Energy Commission directory. [Efficiency metric: EER]

EvapCondenser

Large Package Air

Conditioner

No Cooling

Systems rated at or above 65,000 Btu/hr (cooling capacity). Distribution is ducted.

[Efficiency metric: EER]

When the proposed building is not cooled or when cooling is optional (to be installed at some future date). Both the standard design and proposed design use the same default system. Distribution is ducted (either the same system as heating

or default ducts in attic). (See also section 8.3.2). [Efficiency metric: SEER]

Package Air Conditioner Central packaged air conditioning systems less than 65,000 Btu/hr cooling capacity.

Distribution is ducted. [Efficiency metric: SEER and EER]

Room Air Conditioner

Evaporatively-cooled condenser. The default distribution system is duct in attic; evaporatively cooled condenser duct insulation requirements are the same as those for air conditioner ducts. Requires refrigerant charge testing, EER verification, and compliance with RA4.3.2. [Efficiency metric: EERa and EERb ]

Split Air Conditioner

A factory encased air conditioner that is designed as a unit for mounting in a window, through a wall, or as a console. Distribution is non-ducted. [Efficiency metric: EER]

Split air conditioning systems. Distribution is ducted. [Efficiency metric: SEER and

EER]

8.3.1 Cooling System Data

8.3.1.1 Name

User-defined name for the cooling system.

8.3.1.2 Type

Cooling system type (see Table 8-3).

8-15

CBECC User Manual

Figure 8-11: Cooling System Data

Mechanical Systems

8.3.1.3 SEER

Cooling equipment Seasonal Energy Efficiency Ratio (SEER). For equipment tested only with an

EER, enter the EER as the SEER. When a value higher than 13 SEER for “Compliance 2014” is modeled, it triggers a HERS Verification of High SEER. With “Compliance 2015” the minimum efficiency requirement of the Appliance Efficiency Standards changes to 14 SEER, and only when an

SEER higher than 14 is modeled is a HERS Verification of High SEER triggered. Efficiency information can be obtained from the Energy Commission’s appliance directories

(http://www.appliances.energy.ca.gov/AdvancedSearch.aspx) or from the Air-Conditioning,

Heating, and Refrigeration Institute (AHRI) Certified Products Directory http://www.ahridirectory.org.

8.3.1.4 EER

Cooling equipment Energy Efficiency Ratio (EER). CBECC has default values for the EER based on the SEER value modeled. Two conditions will result in a HERS verified EER. (a) An EER higher than the default of 11.3 for “Compliance 2014” or higher than 11.7 for “Compliance 2015”, and (b) checking the box “

Use this EER in compliance analysis.” Because the EER depends on the specific combination of coil and condenser model numbers, other than default EER ratings can be obtained from AHRI directory http://www.ahridirectory.org.

8.3.1.5 CFM per Ton

The mandatory requirement for cooling airflow is 350 CFM/ton for ducted cooling systems (also assumed for dwellings with no cooling), or 150 CFM/ton for Zonal Single Speed systems. Users may model a higher airflow. All systems other than no cooling require HERS verified system airflow using diagnostic testing procedures from

Reference Appendices

, Residential Appendix RA3.

8.3.1.6 AC Charge

Verified refrigerant charge. Select not verified, verified, or Charge Indicator Display (CID). There is no mandatory requirement for verified refrigerant charge, however, the standard design in climate zones 2 and 8-15 includes proper refrigerant charge in the standard design for most equipment types

(see Standards Section 150.1(c)8.).

8-16

CBECC User Manual

Mechanical Systems

Charge Indicator Display

System Airflow

Air-handling Unit Fan

Efficacy

EER

SEER

Table 8-4: Air Conditioning Measures Requiring HERS Verification

Measure

Refrigerant Charge

Description

Air-cooled air conditioners and air-source heat pumps must be diagnostically tested to verify that the system has the correct refrigerant charge.

A Charge Indicator Display (CID), alternative to refrigerant charge testing.

Ducted systems require a verified system airflow greater than or equal to

350 CFM/ton (mandatory requirement) or another specified value.

To verify that fan efficacy is less than or equal to 0.58 Watts/CFM (a mandatory requirement) or other specified criterion.

Credit for higher than minimum EER by installation of specific air conditioner or heat pump models.

Credit for higher than minimum SEER.

8.3.1.7 Refrigerant Type

Default R410A assumed for all refrigerant containing equipment.

8.3.1.8 Multi-Speed Compressor

Use this field to indicate if the system is a zonally controlled multi-speed compressor. An exception for single speed compressors would leave this box unchecked and specify 150 CFM/ton (see Section

8.3.1.5).

8.3.2 No Cooling

When no cooling system is installed in a dwelling, create a cooling system using the system type

NoCooling (see Figure 8-12).

The software sets the default cooling system to a ducted split system air conditioner that exactly meets Package A for the efficiency, airflow, and refrigerant charge for both the proposed and standard design. The duct system should be the same as the heating system ducts (if any), or a system equivalent to Package A (NOTE: the software will model the appropriate conditions).

The fan system can be set to none.

8-17

CBECC User Manual

Figure 8-12: No Cooling System

Mechanical Systems

 

8.3.3 Evaporatively Cooled Condensing

This   type   of   air   conditioning   is   suited   for   hot   dry   climates.

  The   efficiencies   are   reported   as   multiple  

EER   values   at   different   conditions.

  More   information   can   be   obtained   from   the   2013   Residential  

Manual,   Section   4.7.9

  and   a   full   list   of   compliance   requirements   is   included   in   the   2013   Residential  

Appendices,   Residential   Appendix   RA4.3.2.

  Requires   HERS   verification   of   EER,   refrigerant   charge,   and   duct   leakage   testing.

 

An   example   file   (1StoryExample16EvapCond.ribd)   is   included   in   the   projects   folder.

 

8.3.3.1 EERa

EER   at   95 ° F   dry   bulb   and   75 ° F   wet   bulb,   obtained   from   AHRI   Certified   Products   Directory   http://www.ahridirectory.org.

 

8.3.3.2 EERb

EER   at   82

°

F   dry   bulb   and   65

°

F   wet   bulb.

  This   value   must   be   tested   and   published   by   the   manufacturer   according   to   AHRI   guidelines.

 

Until   the   manufacturers   of   non ‐ typical   cooling   technologies   pursue   an   exceptional   method,   the  

Energy   Commission   has   determined   that   there   is   not   enough   data   about   how   these   systems   perform   in   achieving   comfort   conditions   to   simulate   their   efficiency.

  Model   the   proposed   system,   however,   the   systems   will   be   modeled   as   equivalent   to   the   standard   design,   meaning   there   is   no   credit   and   no  

8-18

CBECC User Manual

Mechanical Systems

penalty. Non-ducted systems are modeled with the distribution system defined as a “distribution system without ducts”.

8.3.5 Evaporative Cooling

[Not yet Implemented] Specify one of three types of evaporative cooling: (1) direct evaporative cooler, the most commonly available system type, (2) indirect, or (3) indirect-direct. Product specifications and other modeling details are found in the Energy Commission appliance directory for evaporative cooling. The default system type is evaporative direct, which is assigned an efficiency of 13 SEER (or the minimum appliance efficiency standard for split system cooling). For indirect or indirect-direct, select the appropriate type, based on the Energy Commission appliance directory as well as the air flow and media saturation effectiveness or cooling effectiveness from the

Energy Commission appliance directory, and specify 13 EER (if required input 13 SEER as well).

Direct evaporative coolers are assumed to be equivalent to a minimum split system air conditioner.

The evaporative cooling modeling methodology addresses two performance issues: (1) rising indoor relative humidity during periods with extended cooler operation, and (2) evaporative cooler capacity limitations. Since modeling of indoor air moisture levels is beyond the capability of simulation models, a simplified algorithm is used to prohibit evaporative cooler operation during load hours when operation is expected to contribute to uncomfortable indoor conditions. The algorithm disallows cooler operation when outdoor wet bulb temperatures are 70°F, or above. As for the capacity limitations, since evaporative coolers are 100 percent outdoor air systems, their capacity is limited by the outdoor wet bulb temperature. Each hour with calculated cooling load, the algorithm will verify that the cooling capacity is greater than the calculated house cooling load.

8.4 Distribution System Data

Model the distribution system (ducts) associated with the HVAC system within a given zone. When modeled as one system, assume the worst case conditions.

When modeling a multi-story building, the computer model already assumes that some ductwork is between floors and inside the conditioned space.

Figure 8-13: Distribution System Data

8-19

CBECC User Manual

Mechanical Systems

8.4.1.1 Name

User-defined name.

8.4.1.2 Type

Indicate the type of duct system, location, or no ducts (see Table 8-5).

Table 8-6 summarizes the duct conditions that require HERS verification, including sealed and tested

ducts, which are a mandatory requirement.

Proposed HVAC systems with ducts in the crawl space or a basement must have supply registers within two feet of the floor and show the appropriate locations for the ducts. Ducts in crawl space and basement can be verified by the local enforcement agency (no HERS verification or duct design).

8.4.1.3 Use all distribution system defaults

By checking this option, the detailed information about the supply and return ducts is completed based on other building inputs, including climate zone. NOTE: If you change the climate zone to one with a different Package A duct insulation value, the program will change to match Package A, which may not match the plans.

Figure 8-14: Duct Leakage

8.4.1.4 Duct Leakage

Select sealed and tested. To specify a target leakage number, select Low Leakage Air Handler (see

Figure 8-14). HERS verification is required for this mandatory measure.

8.4.1.5 Duct Insulation R-value

Specify the R-value of HVAC system ducts. The mandatory minimum R-value allowed is 6. Valid options are 0, 2.1, 4.2, 6.0, 8.0, 10.0 and 12.0.

8-20

CBECC User Manual

Mechanical Systems

Table 8-5: Distribution Type

Descriptor

Ducts located in attic

Ducts located within the conditioned space (except 12 lineal feet)

Ducts located entirely in conditioned space

Distribution Type and Location

Ducts located overhead in the attic space (and default condition for no cooling).

Ducts located in a crawl space Ducts located in crawl space.

Ducts located in a garage Ducts located in garage space.

Less than 12 linear feet of duct is outside of the conditioned space.

Distribution system without ducts

HVAC equipment and all HVAC ducts (supply and return), furnace cabinet and plenums, located within the conditioned floor space. Location of ducts in conditioned space eliminates conduction losses but does not change losses due to leakage.

Leakage from either ducts that are not tested for leakage or from sealed ducts is modeled as leakage to outside the conditioned space.

Air distribution systems without ducts such as window air conditioners, wall furnaces, floor furnaces, radiant electric panels or combined hydronic heating equipment.

Ducts located in exposed locations outdoors. Ducts located in outdoor locations

Verified low-leakage ducts entirely in conditioned space

Ducts located in multiple places

Verified Low Leakage Ducts in Conditioned Space - defined as duct systems for which air leakage to outside conditions is equal to or less than 25 CFM when measured in accordance with

Reference Appendices

, Residential Appendix RA3.1.

Allows a different location for supply and return ducts.

8.4.1.6 Has Bypass Duct

If the system meets zonal control criteria, indicate if the system has or does not have a bypass duct.

When specifying that there is no bypass duct, this credit requires HERS rater verification with

Reference Appendices

, Residential Appendix RA3.1.4.6.

8.4.1.7 Supply Ducts

If Section 8.4.1.3 is unchecked so that credit may be obtained for a verified duct design/reduced

surface area (see

Reference Appendices

, Residential Appendix RA3.1), enter the supply duct details for area, diameter and location. The supply duct begins at the exit from the furnace or air handler cabinet.

The supply duct surface area for crawl space and basement applies only to buildings or zones with all supply ducts installed in the crawl space or basement. If the supply duct is installed in locations other than crawl space or basement, the default supply duct location is “Other.” Do not include the surface area of supply ducts completely inside conditioned space, or ducts in floor cavities or vertical chases when surrounded by conditioned space with draft stops.

8-21

CBECC User Manual

Mechanical Systems

The surface area of each supply duct system segment is calculated based on its inside dimensions and length. The total supply surface area in each unconditioned location (attic, attic with radiant barrier, crawl space, basement, other) is the sum of the area of all duct segments in that location.

Table 8-6: Summary of Verified Air Distribution Systems

Measure

Duct Sealing

Supply Duct Location, Reduced

Surface Area and R-value

Low Leakage Ducts in

Conditioned Space

Low Leakage Air-handling Units

Return Duct Design

Air Filter Device Design

Bypass Duct Condition

Description

Mandatory measures require that space conditioning ducts be sealed. Field verification and diagnostic testing is required.

Compliance credit for improved supply duct location, reduced surface area and R-value. Field verification that duct system was installed according to the duct design, including location, size and length of ducts, duct insulation R-value and installation of buried ducts. For buried ducts, this measure also requires improved construction quality or QII and duct sealing.

When space conditioning ducts are located entirely in directly conditioned space, this is verified by diagnostic testing. Compliance credit can be taken for verified duct systems with low air leakage to the outside. Field Verification for ducts in conditioned space and duct sealing are required (

Reference Appendices

, Residential

Appendix RA3.1.4.3.8).

Compliance credit can be taken for installation of a factory sealed air handling unit tested by the manufacturer and certified to the

Commission to have met the requirements for a Low Leakage Air-

Handling Unit achieved. Field verification of the air handler’s model number is required. Duct sealing is required.

Verification to confirm that the return duct design conforms to the criteria given in Table 150.0-C or Table 150.0-D. as an alternative to meeting 0.58 W/CFM fan efficacy of Section 150.0(m)12.

Verification to confirm that the air filter devices conform to the requirements given in Section 150.0(m)12.

Verification to determine if system is zonally controlled, and confirm that bypass ducts condition modeled matches installation.

8.4.1.8 Return Ducts

Return duct surface area is not a compliance variable. If Section 8.4.1.3 is unchecked in order to take

credit for a verified duct design, enter the return duct details for area, diameter and location. The calculations assume that the return duct is located entirely in the attic, unless (a) the return duct is located entirely in the basement, in which case the calculation shall assume basement conditions for the return duct efficiency calculation, or (b) the return duct is located entirely in conditioned space and the system meets the requirements for

Verified Low Leakage Ducts in Conditioned Space

, in which case the return duct is assumed to be in conditioned space.

8.4.2 Low Leakage Air Handlers

Credit can be taken for installation of a factory sealed air handling unit tested by the manufacturer and certified to the Energy Commission to meet the requirements for a Low Leakage Air-Handler.

Field verification of the air handler’s model number is required.

8-22

CBECC User Manual

Mechanical Systems

A Low Leakage Air Handler is reported on the compliance report and field verified in accordance with the procedures specified in

Reference Appendices

, Residential Appendix RA3.1.4.3.9.

8.4.3 Verified Low Leakage Ducts in Conditioned Space

For ducted systems the user may specify that all ducts are entirely in conditioned space and the software will model the duct system with no leakage and no conduction losses.

Systems that have all ducts entirely in conditioned space are reported on the compliance documents and this is verified by measurements showing duct leakage to outside conditions is equal to or less than 25 CFM when measured in accordance with

Reference Appendices

, Residential Appendix RA3.

8.4.4 Buried Ducts

Ducts partly or completely buried under blown attic insulation also meeting the requirements for verified quality insulation installation, verified duct design and duct leakage testing may take credit for increased effective duct insulation using the HERS verified credit for buried ducts. Additional details regarding the duct design and the inspection process can be found in

Reference Appendices

,

Residential Appendix RA3.1.4 and the

Residential Compliance Manual

Section 4.4.3.

The duct design shall identify the segments of the duct that meet the requirements for buried ducts on the ceiling (“buried ducts”) and ducts that are enclosed in a lowered ceiling and completely covered by ceiling insulation (“deeply buried ducts”), and these are input separately from supply and return ducts that are not buried. Buried ducts shall have a minimum of R-4.2 duct insulation prior to being buried. The ceiling must be level with at least 6 inches of space between the outer jacket of the installed duct and the roof sheathing above.

8.4.4.1 Buried Ducts

Select the check box for buried ducts (see Figure 8-15) and enter the return duct length (in feet) for

the portion of duct runs directly on or within 3.5 inches of the ceiling gypsum board and surrounded with blown attic insulation of R-30 or greater. Determine the appropriate effective R-value as shown

in Table 8-7 (assume the worst case where multiple conditions exist).

8.4.4.2 Deeply Buried Ducts

Select the check box for deeply buried ducts (see Figure 8-15) and enter the return duct length (in

feet) for ducts installed in lowered areas of ceiling and covered by at least 3.5 inches of insulation above the top of the duct insulation jacket. Model R-25 duct R-value for fiberglass ceiling insulation or R-31 duct R-value for cellulose ceiling insulation.

8-23

CBECC User Manual

Mechanical Systems

Figure 8-15: Buried Ducts

R-43

R-49

R-60

R-30

R-38

Attic Insulation

R-30

R-38

R-40

R-40

R-43

R-49

R-60

Table 8-7: Buried Duct Effective R-values

Nominal Round Duct Diameter

4'' 5'' 6'' 7'' 8''

Effective Duct Insulation R-value for Blown Fiberglass Insulation

R-13 R-13 R-13 R-9 R-9

R-25

R-25

R-25

R-25

R-25

R-25

R-13

R-25

R-13

R-13

R-25

R-25

R-25

R-25

R-25

R-25

R-25

R-25

R-25

R-25

R-25

R-25

R-25

R-25

R-25

Effective Duct Insulation R-value for Blown Cellulose Insulation

R-9 R-4.2 R-4.2 R-4.2 R-4.2

R-15 R-15 R-9 R-9 R-4.2

R-15

R-15

R-31

R-31

R-15

R-15

R-31

R-31

R-15

R-15

R-15

R-31

R-9

R-15

R-15

R-31

R-9

R-9

R-15

R-31

10''

R-4.2

R-4.2

R-4.2

R-4.2

R-9

R-15

R-4.2

R-9

R-13

R-13

R-25

R-25

12''

R-4.2

R-9

R-9

R-9

R-13

R-25

R-4.2

R-4.2

R-4.2

R-4.2

R-9

R-15

R-9

R-13

R-25

R-4.2

R-4.2

14''

R-4.2

R-4.2

R-9

R-4.2

R-4.2

R-4.2

R-9

R-4.2

R-9

R-13

R-4.2

R-4.2

16''

R-4.2

R-4.2

R-4.2

R-4.2

R-4.2

R-4.2

R-9

8.5 HVAC Fan System

The HVAC fan system moves air for the air conditioning and heating systems.

8-24

CBECC User Manual

Figure 8-16: HVAC Fan

Mechanical Systems

8.5.1.1 Name

User-defined name.

8.5.1.2 Type

Default single speed furnace fan.

8.5.1.3 Watts/CFM Cooling

The mandatory requirement in Section 150.0(m)13 is for an air-handling unit fan efficacy less than or equal to 0.58 Watts/CFM as verified by a HERS rater. The alternative to HERS verification of 0.58

Watts/CFM is HERS verification of a return duct design that conforms to the specification given in

Table 150.0-C or D. However, if a value less than 0.58 Watts/CFM is modeled for compliance credit, the fan efficacy value must be verified and the alternative is not allowed.

If no cooling system is installed, this value is assumed to be 0.58 W/CFM.

8.6 Indoor Air Quality (IAQ) Fan Data

Figure 8-17: IAQ Fan Data

8-25

CBECC User Manual

Mechanical Systems

Mechanical ventilation is required to meet minimum indoor air quality (IAQ) requirements of

ASHRAE Standard 62.2 (see

Residential Compliance Manual

, Section 4.6). The IAQ system requires

HERS verification meeting

Reference Appendices

, Residential Appendix RA3.3.

The simplest IAQ fan system is an exhaust fan, such as a bathroom fan that meets the criteria in

ASHRAE Standard 62.2 for air delivery and low noise, and that operates continuously. More advanced IAQ fan systems have a supply or both supply and exhaust fans. In most cases, the energy impact of this mandatory requirement is neutral. The only system for which credit can accrue is a central fan integrated system with HERS verified W/CFM of less than 0.58.

8.6.1.1 Name

User-defined name (must be the same name as specified in Section 4.6).

8.6.1.2 IAQ CFM

Enter the size of fan being installed to meet the minimum CFM required to meet the mandatory

ventilation requirements (found under Building in Section 4.4).

8.6.1.3 W/CFM IAQ Vent

The default value is 0.25 W/CFM. The standard design is set to the same value as proposed up to 1.2

W/CFM).

8.6.1.4 IAQ Fan Type

Select exhaust, supply, or balanced (both exhaust and supply).

8.6.1.5 IAQ Recovery Effectiveness

When the fan type is balanced, enter the IAQ Recovery Effectiveness.

8.7 Cooling Ventilation Fans

Ventilation cooling systems bring in outside air to cool the house when this can reduce cooling loads and save cooling energy. Whole house fans involve window operation and attic venting. Central fan integrated systems use the HVAC duct system to distribute ventilation air. Ventilation cooling systems that exhaust air through the attic require a minimum of 1 ft

2

of free attic ventilation area per

1000 CFM of rated capacity for relief (see Section 150.1(c)12 of the Standards).

CBECC-Res can model system types shown in Table 4-2. If a “default prescriptive whole house fan” was specified in Section 4.7, there is no need to provide details about the fan. For central fan

integrated (CFI) night ventilation, first make sure that the Cool Vent tab at the project level is set to

CFI (see Section 4.7.1.1). For a fixed speed fan, set the HVAC system type to “Other Heating and

Cooling System” or for a variable speed fan, set the HVAC system type to “Variable Outdoor Air

Ventilation Central Heat/Cool System (see Section 8.1.1.2). Fixed Flow for the Cooling Vent drop-

down menu. It is also necessary that the Cool Vent tab at the project level be set to CFI (see Section

4.7.1.1).

8-26

CBECC User Manual

Figure 8-18: Cooling Ventilation

Mechanical Systems

8.7.1.1 Name

User defined name, which must also be specified in Section 4.7.

8.7.1.2 Use all fan system defaults

Sets the default minimum to 2 CFM/ft

2

.

8.7.1.3 Cooling Vent CFM

If system default is not checked, enter the actual CFM of the proposed ventilation fan.

8.7.1.4 W/CFM Cooling Vent

Enter the Watts/CFM of the proposed system.

8-27

CBECC User Manual

Domestic Hot Water

Chapter 9. Domestic Hot Water (DHW)

The water heating system is defined at the zone level (see Section 5.5.1.11), while the details of the

systems are contained under the mechanical tab. The information in this chapter is from the point of view of the mechanical tab.

9.1 Efficiency Information

Water heaters are required to be certified to the Energy Commission and the applicable efficiency values needed for modeling are found in the on-line certified appliance directory

(http://www.appliances.energy.ca.gov/). From this site, an

advanced search

yields the most useful information, which can be exported to a spreadsheet format for sorting and searching.

Alternatively, data may be found in the Air-Conditioning, Heating and Refrigeration Institute

(http://www.ahridirectory.org/ahridirectory). The AHRI directory does not contain the standby loss for large water heaters, which is a required input.

The federal minimum energy factor used to establish the standard design changes for small water heaters effective April 16, 2015.

Type Volume Current Effective April 16, 2015

Gas-fired storage < 55 gallons

> 55 gallons

Electric storage < 55 gallons

> 55 gallons

0.97-(0.00132 x Volume) 0.960-(0.0003 x Volume)

2.057-(0.00113 x Volume)

For a 50-gallon water heater, the change is from 0.575 to 0.60 Energy Factor for gas and 0.904 to 0.945

Energy Factor for electric.

0.67-(0.0019 x Volume) 0.675-(0.0015 x volume)

0.8012-(0.00078 x Volume)

9.2 Water Heater Types

Tank types are based on the Appliance Efficiency Regulations definitions:

• Small storage has an input of less than or equal to 75,000 Btu gas/propane, less than or equal to 105,000 Btu/hr oil, less than or equal to 12 kW electric, or less than or equal to 24 amps heat pump.

Small tankless has an input of less than or equal to 200,000 Btu per gas/propane, 210,000 Btu per hour or less oil-fired, or 12 kW or less electric. A tankless water heater is a water heater with an input rating of at least 4,000 Btu per hour per gallon of stored water.

9-1

CBECC User Manual

Domestic Hot Water

Large   storage   has   an   input   greater   than   75,000   Btu/hr   gas   or   propane,   greater   than   105,000  

Btu/hr   oil ‐ fired,   or   greater   than   12   kW   electric.

  Rated   with   thermal   efficiency   and   standby   loss.

 

Large   tankless   has   an   input   of   greater   than   200,000   Btu   per   hour   gas/propane,   greater   than  

210,000   Btu   per   hour   oil ‐ fired,   or   greater   than   12   kW   electric.

  Tankless   water   heater   is   a   water   heater   with   an   input   rating   of   at   least   4,000   Btu   per   hour   per   gallon   of   stored   water.

  

Boiler   is   a   space   heater   supplying   steam   or   hot   water   for   space   heating.

  

  Indirect   is   a   water   heater   consisting   of   a   storage   tank   with   no   heating   elements   or   combustion   devices,   connected   via   piping   and   recirculating   pump   to   a   heat   source   consisting   of   a   boiler.

 

9.3.1 Single Family Distribution Type

Distribution   types  

(Figure   9 ‐ 1)

  range   from   standard   (distribution   system   multiplier   1.0)   to   recirculating   with   no   control   (distribution   system   multiplier   7.0)   as   options   with   no   HERS   verification   requirement.

  Some   systems   are   allow   for   a   higher   credit   if   the   system   will   be   verified   by   a   HERS   rater.

  See

  Table   9 ‐ 1  

for   a   comparison   of   the   multiplier   (lower   number   equals   more   efficient   system).

  More   information   about   distribution   types   can   be   found   in  

Residential   Compliance   Manual

,  

Section   5.3

  and  

Reference   Appendices

,   Residential   Appendix   RA3.6.

 

Figure 9-1: Single Family Distribution Systems

9-2

 

 

CBECC User Manual

Domestic Hot Water

Table 9-1: Water Heater Distribution System Multipliers

Distribution System

NO HERS INSPECTION REQUIRED

Standard

Pipe Insulation, All Lines

Parallel Piping

Recirculation, Non-demand Control (no control, runs 24 hrs/day)

Recirculation, Manual Demand Control Push Button

Recirculation, Demand Control Occupancy/Motion

OPTIONAL CASES: HERS INSPECTION REQUIRED

Pipe Insulation, All Lines

Parallel Piping

Compact Design

Point of Use

Recirculation, Demand Control Push Button

Recirculation, Demand Control Occupancy/Motion

Non-Compliant Installation Distribution Multiplier

Distribution System

Multiplier

1.00

0.90

1.05

9.00

1.60

2.40

0.80

0.95

0.70

0.30

1.45

2.20

1.20

9.3.2 Multi-Family Distribution Type

When using central water heating in a multi-family building, the options for distribution systems are

shown in Figure 9-2. More information about distribution types can be found in

Residential

Compliance Manual

, Section 5.3 and

Reference Appendices

, Residential Appendix RA3.6.

9-3

CBECC User Manual

Figure 9-2: Multi-Family Distribution Systems

Domestic Hot Water

9.4 Water Heating System Data

Under the Mechanical Tab, the water heating system details are defined (see Figure 9-2).

9.4.1.1 System Name

User defined name. This is the same name that was provided under the Zone Data tab (see Section

5.5.1.11).

9.4.1.2 Distribution type

Drop-down menu with options based on the building and water heater type being specified. See

Section 9.3 and Table 9-1. For installation and compliance requirements see

Residential Compliance

Manual

Chapter 5 and

Reference Appendices

, Residential Appendix RA3.6 and 4.4.

9.4.1.3 Multi-Family Hot Water Distribution Type

Drop-down menu with options for the level of control on the recirculating system serving the

dwelling unit, based on the building and water heater type being specified. See Section 9.3.2 and

Figure 9-2. An input for the recirculation loops is also required (see Figure 9-3).

9.4.1.4 Recirculation Pump Power (bhp)

Multi-family recirculation pump power (brakehorse power). Typical value less than 1.00.

9.4.1.5 Efficiency (fraction)

Multi-family recirculation motor efficiency (fraction). Typical value less than 1.00. See

Table 9-2

for

default efficiencies.

9-4

CBECC User Manual

Domestic Hot Water

Table 9-2: Default Recirculating Pump Motor Efficiency

Nameplate or Brake

Horsepower

0.050 (1/20)

0.083 (1/12)

0.125 (1/8)

0.167 (1/6)

Standard Fan Motor

Efficiency

0.40

0.49

0.55

0.60

0.250 (1/4)

0.333 (1/3)

0.64

0.66

0.500 (1/2) 0.70

0.750 (3/4) 0.72

Source: Reference Appendices, Nonresidential Appendix NA3

9.4.1.6 Water Heater(s)

The name of the water heater (which holds more information about the water heater, see Section

5.5.1.11).

9.4.1.7 Count

The number of water heaters named in the adjacent field that are in the system. Include different water heaters or different water heater efficiencies on a different line.

Figure 9-3: Recirculation Loops

9.5 Solar Water Heating Data

When a water heating system has a solar system to provide part of the water heating, the Solar

Fraction (SF) is determined using an F-chart program, OG-100 or OG-300 calculation method (see www.gosolarcalifornia.org). The calculation methods require varying levels of detail about the solar system and the site of the installation. Calculations use published efficiency data for the solar water heating system.

9-5

CBECC User Manual

Figure 9-4: Solar Water Heating Data, Annual

Domestic Hot Water

Figure 9-5: Solar Water Heating Data, Monthly

9.5.1.1 Solar Fraction Type

Select annual or monthly, based on the appropriate calculation method for the system type. See www.gosolarcalifornia.org.

9.5.1.2 Solar Fraction

Enter one annual solar fraction (see Figure 9-4) or 12 monthly solar fractions (see Figure 9-5), as

calculated for the system type.

9.6 Water Heater Data

The specifications of the water heater accessed in Figure 9-3 are contained in the water heater data as

shown in Figure 9-6. The fields will vary based on the tank type.

9-6

CBECC User Manual

Figure 9-6: Water Heater Data Small Storage

Domestic Hot Water

Figure 9-7: Large Storage Water Heater Data

9.6.1.1 Name

User-defined name that is specified in the water heating system data for the field water heater (see

Section 9.4.1.6).

9.6.1.2 Heater Element Type

Choose electric resistance, natural gas, propane, heat pump, or oil.

9.6.1.3 Tank Type

Choose boiler, indirect, large instantaneous, large storage, small instantaneous, small storage, or

unfired tank. Most instantaneous water heaters are small, based on the rated input (see Section 9.2

Water Heater Types).

9-7

CBECC User Manual

Domestic Hot Water

9.6.1.4 Efficiency

Certified efficiency from one of the sources listed in Section 9.1. Based on the tank type, the efficiency

is energy factor for small storage, small instantaneous, and small heat pump water heaters. For large storage, large instantaneous, large heat pump, or boilers the efficiency is thermal efficiency, recovery efficiency, or AFUE. Indirect water heater efficiency is based on the type of device being used to heat the water. Value entered as a decimal, such as 0.60 or 0.80.

9.6.1.5 Standby Loss or Pilot Energy

Required input for large storage water heaters and mini tanks. For large storage, a standby loss of 3% is entered as 0.03. For mini tanks, enter the standby loss Watts. Find the standby loss by conducting an advanced search in the Energy Commission’s appliance efficiency database of water heating

equipment (see Section 9.1).

Some large storage water heaters are not required to report standby loss. This value can be calculated using equations from the 2012 Appliance Efficiency Regulations, Tables F2 and F3, as follows:

Standby loss Btu/hr = (rated input / 800) + (110 x (volume x 0.5)

Convert to Standby Loss Percent as:

Standby loss Btu/hr / (8.25 x Volume x 70)

There is no source for pilot energy. Leave this value as 0.

9.6.1.6 Tank Volume

Enter the tank volume (in gallons). The rated input rather than the tank volume is used to determine

if a tank type is large or small (see Section 9.2)

9.6.1.7 Exterior R-value

For indirect and unfired tanks.

9.6.1.8 Input Rating

The input rating (consistent with the tank type) from one of the listed sources in Section 9.1.

9.6.1.9 Ambient Conditions

For an indirect water heater, specify whether it is installed in unconditioned or conditioned space.

9.6.1.10 Recovery Efficiency

If the equipment is part of a hydronic system, enter the recovery efficiency, thermal efficiency or

AFUE for appropriate water heating type. The value comes from one of the listed sources in Section

9.1 and is entered as a percent (e.g., 78, 80).

9-8

CBECC User Manual

Domestic Hot Water

9.7 Hydronic and Combined Hydronic

A combined hydronic system uses a device typically used for water heating for both space heating and water heating. If there is a device that is only providing water heating, this is a separate hydronic system.

9.8 Ground Source Heat Pump and Air to Water Heat Pump

The water heating portion of a ground source heat pump or air to water heat pump is modeled by

first defining the HVAC system, as described in Section 8.2.3 and checking the box “System Heats

DHW” or domestic hot water.

The inputs for the water heating equipment data are:

9.8.1.1 Tank Volume

Enter the tank volume (in gallons).

9.8.1.2 Insulation R-value

R-value of external tank insulation.

9.8.1.3 Ambient Conditions

Specify whether it is installed in unconditioned or conditioned space.

The final step is to connect the HVAC system to the DHW system. In this example, an HVAC system named Ground Source HP was specified and can be selected to serve as the water heating system for

the zone. Once this connection is made, the mechanical tab will look like Figure 9-9 (in order to

refresh the screen, click on the envelope tab and then the mechanical tab).

Figure 9-8: Water Heater from an HVAC System

9-9

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Table of contents