(20) VAR8-ACU operation guide

Add to My manuals
138 Pages

advertisement

(20) VAR8-ACU operation guide | Manualzz

VAR8-ACU and Variants - Operation, Commissioning, Fault Finding, and Maintenance Guide

26 Manual Restoration of Default Settings

It is possible to restore all default settings, including the access code, by setting DIP-switches to a special power-up condition.

DIP Switch

26.1 Restoring Access Code

1. Power down the unit by disconnecting the 24 V DC power supply.

2. Set DIP Switch-3 to ON.

3. Power on with the above settings selected to clear the access code in the non-volatile memory and restore the default settings of ‘0999’.

This will only take a couple of seconds. The VAR8-ACU display indicates when this process is complete.

4. Power off and restore the settings for normal operation.

26.2 Restoring All Defaults

1. Power down the unit by disconnecting the 24 V DC power supply.

2. Set DIP Switch-4 to ON.

3. Power on with the above setting selected to clear the whole configuration in the non-volatile memory and restore the default settings as shown below.

This will only take a couple of seconds. The VAR8-ACU display indicates when this process is complete.

4. Power off and restore the settings for normal operation.

Issue: 02 complete, approved

Page 130 of 138

VAR8-ACU and Variants - Operation, Commissioning, Fault Finding, and Maintenance Guide

Access code

Setting

Report over-temperature

Maximum temperature

Default Value

0999

No

70 °C

Input Type

Input Gain

Input Surv

Input Surv Sensitivity

EQ

Unused

Inputs 1, 3, and 4 = Network Channel

−20 dB

Off

−40

0 dB All bands, HPF=Off

Fades 00

Chime Type Off

Chime Level

Output Gains

−12 dB

0 dB

Name

Output Level

Surveillance Mode

Level

Override Gain

DVA Modes

Busy Indication

Fault Contacts

As input number

0 dB

Continuous ‘On’

−9 dB

−30 dB

DVA Full

On

Not-config

Issue: 02 complete, approved

Page 131 of 138