6-6 Continuity Check (400Ω range fixed)

 ※ The  continuity  check  mode  is  enabled  by  pressing  the  mode  selector  switch  on  resistance  range.  "    "  is  indicated  on  the  display to show the instrument in the continuity check mode. The  buzzer beeps, if the resistance under test is 20.0Ω or less.

   DANGER

●Never use the instrument on an energized circuit.

● Do  not  make  measurement  with  the  battery  compartment  cover  removed.

● Keep  your  fingers  and  hands  behind  the  protective  fingerguard  during measurement.

 ①Set the function selector switch to the "  Ω" position.

 ② Slide the terminal cover to the left to disclose the V/Ω and COM  terminals. Plug the red test lead into the V/Ω terminal and the  black test lead into the COM terminal.

 ③ With  the  tip  of  the  test  leads  shorted  together,  press  the  Zero 

Adjust/Reset button to offset the resistance of the test leads.

 ④ Press  the  mode  selector  button  once  to  enter  from  the  normal  mode  to  the  continuity  check  mode.  "    "  should  be  indicated  on the display.

 ⑤ Connect the tip of the test leads to the circuit under test. If the  resistance is 20.0Ω or less, the buzzer beeps.

6-7 Frequency Measurement

 ● On  ACA  or  ACV  range,  the  frequency  of  the  current  or  voltage  under test can be counted and shown on the display.

 ● In  the  frequency  measurement  mode,  "Hz"  is  indicated  on  the  display.

 ● Trigger threshold is approx. 10V for AC voltage and approx. 40A  for AC current. 