3.3 Description of Local Display (and Web Interface) Menus Line Items

The following are descriptions of the editable parameters presented in the local display menus. Parameter descriptions can also be used for the WEB Interface menus. Note that the names in the WEB Interface menus may be longer since the WEB Interface allows more characters to be displayed then the local (LCD) display.

3.3.1 Settings Menu

Alarm Setting

Alarm Severity Menu

Menu Navigation: Main Menu / Settings / Alarm Setting / Alm Severity

Note: For WEB Interface, menu item is found under Configuration / Signal Information Modification

/ select “Alarm Signal” in “Signal Type” drop-down box.

"Alarm Severity" Parameter Settings:

Use the menus to assign an Alarm Severity Level (none, minor, major, critical) to each possible alarm.

Alarm Relay Menu

Menu Navigation: Main Menu / Settings / Alarm Setting / Alarm Relay

Note: For WEB Interface, menu item is found under Configuration / Alarm Relays.

"Alarm Relay" Parameter Settings:

Use the menus to assign an alarm relay (for connection of external alarm circuits) to each possible alarm.

Alarm Param Menu

Menu Navigation: Main Menu / Settings / Alarm Setting / Alarm Param

Note: For WEB Interface;

“Block Alarm” menu item is found under Device Information / Power

System / Settings Tab

, “Clr Alarm Hist” menu item is found under Maintenance / Clear Data, and

“Alarm Voice” menu item is not available.

"Alarm Param" Parameter Settings:

Alarm Voice: Programs the audible alarm feature.

Off: Disables the audible alarm.

On: When a new alarm occurs, the audible alarm sounds.

Press any key to silence the audible alarm.

3 minutes / 10 minutes / 1 hour / 4 hours: When a new alarm occurs, the audible alarm sounds. The audible alarm automatically silences after the selected time period.

Block Alarm

Normal: Alarms are processed normally.

Blocked: Forces the alarm relays in the "off" state and blocks alarms from changing the relay state.

Clr Alm Hist: The only selection for "Clr Alm Hist" is Yes. Once Yes is selected and confirmed, the alarm history log is cleared.

92 Chapter 3. Local Display Menus

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Advanced control of rectifiers and converters
  • Comprehensive monitoring of system components and generation of system alarms
  • Acquisition and logging of operating data
  • Intelligent power matching for energy optimization
  • Power split feature for flexible system design
  • Diesel management feature for efficient generator operation
  • PLC (Programmable Logic Controller) function for custom control logic
  • Supervisory Module (SM Modules) monitoring for enhanced system visibility
  • Hybrid control function for seamless integration of multiple power sources
  • Maximum current limit function for protection against overloads

Related manuals

Frequently Answers and Questions

What are the main functions of Emerson M820B?
Emerson M820B's main functions include rectifier control, converter control, system monitoring and alarms, data acquisition and logging, battery management, intelligent power matching, power split feature, diesel management, PLC function, supervisory module monitoring, and hybrid control function.
How does the Emerson M820B help optimize energy usage?
The Emerson M820B's intelligent power matching feature optimizes energy usage by automatically adjusting the power output of the rectifiers and converters based on the load demand.
Can I monitor the Emerson M820B remotely?
Yes, the Emerson M820B can be monitored remotely using the web interface.

advertisement

Table of contents