ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE. Revolv VMA1-75N
Add to My manuals56 Pages
Revolv VMA1-75N is a gas fired high efficiency furnace designed for down flow & direct vent (sealed combustion) applications. It is suitable for installation in manufactured homes, modular homes/buildings, and site constructed residential (single story dwellings). This furnace provides reliable heating with adjustable BTU input rate, burner adjustment, and temperature rise settings. It comes with a condensate drain line and trap assembly for efficient moisture removal. Its compact design and flexible venting options make it a versatile choice for various heating needs.
advertisement
All installations and services must be performed by qualified service personnel.
VMA1-75
ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE
COOLING UNIT HTG Speed Recommended CLG Speed
24,000
30,000
36,000
MED-LOW
MED-LOW
MED-LOW
MED-LOW
MED-HIGH
HIGH
Speed Tap \
Static
Pressure
Low
ML
MH
High
Speed Tap \
Static
Pressure
Low
ML
MH
High
Speed Tap \
Static
Low
ML
MH
High
Furnace Airflow (CFM) vs. External Static pressure (in. WC.)
0.1
817
1019
1257
1470
0.2
797
995
1210
0.3
773
959
1174
0.4
730
918
1125
0.5
668
869
1076
0.6
620
821
1024
0.7
555
760
959
1420 1366 1312 1259 1196
Temperature Rise vs. External Static Pressure (in. WC.)
1127
0.1
81
65
52
45
0.2
83
66
55
46
0.3
85
69
56
48
0.4
90
72
59
50
0.5
90
76
61
52
0.6
106
80
64
55
0.7
119
87
69
59
Blower Motor Current Draw (Amps) vs. External Static pressure (in. WC.)
3.1
3.9
4.8
5.7
0.2
3.0
3.8
4.6
5.5
0.3
2.9
3.6
4.4
5.4
0.4
2.8
3.5
4.2
5.2
0.5
2.7
3.3
4.1
5.1
0.6
2.6
3.2
4.0
5.0
0.7
2.5
3.1
3.8
4.8
Speed Tap \
Static
Pressure
Low
ML
MH
High
0.1
312
400
513
624
Blower Motor Watts vs. External Static pressure (in. WC.)
0.2
303
390
490
605
0.3
298
381
478
591
0.4
291
366
462
573
=
Recommended operation range
0.5
280
354
447
556
0.6
273
342
432
542
0.7
264
330
413
522
31
All installations and services must be performed by qualified service personnel.
: TURN OFF THE ELECTRICAL POWER to the furnace
before attempting to change blower speed wiring.
The furnace is factory wired to the ignition control with standard heating and cooling speeds. When changing motor speeds, simply switch the needed speed to either the heating or cooling terminal as applicable on the module to obtain the desired CFM. The unused speeds should then be reconnected to the module in the “park” positions. (Refer to figure 15)
Refer to section II for blower speed and air flow performance for A/C installation.
5. FIELD WIRING AND REPLACING WIRING
Field wiring between the furnace and devices not attached to the furnace shall conform with the temperature limitation for Type T 35 C wire. If any of the original factory supplied furnace wiring is replaced or a separate device other than the thermostat is wired internal to the unit 105
°C thermoplastic or equivalent wire must be used.
32
All installations and services must be performed by qualified service personnel.
V. STARTING THE UNIT
A. SEQUENCE OF OPERATIONS
AT ANY TIME THE
GAS VALVE IS
NOT ENERGIZED
START
CONTINUOUS SAFE OPERATION CHECK
IF FLAME SIMULATION CONDITION
PRESENT OR ROLL-OUT SWITCH OPENS, SYSTEM
ENERGIZES INDUCER FAN FOR 15 SECONDS AND CIRCULATOR BLOWER AT
HEATING SPEED UNTIL SITUATION CORRECTION
THERMOSTAT CALLS FOR
HEAT, CONTACTS CLOSE
CONTROL BOARD ENERGIZED,
INDUCER ENERGIZED
PRESSURE SWITCH SENSES
ADEQUATE DIFFERENTIAL PRESSURE,
CONTACTS CLOSE
POWER INTERRUPTION
SYSTEM SHUTS OFF,
RESTARTS WHEN POWER
IS RESTORED.
START
TRIAL
FOR
IGNITION
POWER IS APPLIED TO
THE SILICON NITRIDE
IGNITOR. IGNITOR
WARM-UP IS 20 SECONDS.
AFTER IGNITOR WARM-UP,
THE GAS VALVE IS
ENERGIZED TO OPEN
FLAME MUST BE DETECTED
WITHIN 4 SECONDS IF
FLAME IS DETECTED, THE
DELAY-TO-FAN-ON TIME
BEGINS (45 SECONDS)
IF FLAME IS NOT DETECTED, THE
GAS VALVE IS DE-ENERGIZED,
THE IGNITOR IS TURNED OFF AND
THE CONTROL BOARD CONTROL GOES
INTO "RETRY" SEQUENCE.
33
All installations and services must be performed by qualified service personnel.
MAIN
BURNER
OPERATION
AFTER DELAY-TO-FAN-ON
PERIOD ENDS, CIRCULATING
AIR FAN IS ENERGIZED AT
HEATING SPEED. THE (OPTIONAL)
ELECTRONIC AIR CLEANER
AND HUMIDIFIER ARE
ENERGIZED.
THE RETRY SEQUENCE
PROVIDES A 60 SECOND
WAIT BEFORE IGNITION
RETRY. RETRY IS
ATTEMPTED WITH AN
ADDITIONAL 10 SECONDS
OF IGNITOR WARM-UP
TIME.
CALL
FOR
HEAT
SATISFIED
END
OF CYCLE
WHEN THERMOSTAT IS
SATISFIED, CONTACTS
OPEN AND THE GAS
VALVE IS DE-ENERGIZED.
AFTER PROOF OF FLAME
LOSS, INDUCER STARTS 5 SECOND
POST SURGE AND (OPTIONAL)
HUMIDIFIER ARE
DE-ENERGIZED. THE DELAY-
TO-FAN-OFF PERIOD
BEGINS (120 SECONDS)
IF IGNITION ATTEMPT IS
UNSUCCESSFUL, ONE MORE
RETRY WILL BE MADE
BEFORE THE CONTROL BOARD
GOES INTO SYSTEM LOCKOUT.
IF FLAME IS DETECTED,
THEN LOST, THE CONTROL BOARD
WILL REPEAT THE INITIAL IGNITION
SEQUENCE FOR A TOTAL OF SIX
RECYCLES. AFTER SIX UNSUCCESSFUL
RECYCLE ATTEMPTS, THE CONTROL
WILL GO INTO SYSTEM LOCKOUT.
AFTER THE DELAY-TO-
FAN-OFF PERIOD ENDS,
THE CIRCULATING AIR
FAN AND (OPTIONAL)
ELECTRONIC AIR CLEANER
ARE DE-ENERGIZED.
IF SYSTEM IS IN LOCKOUT, THE
MODULE WILL RESET ITSELF AFTER
60 MINUNTES OR MAY BE MANUALLY RESET BY
INTERRUPTING THE POWER TO THE
FURNACE AT THE DISCONNECT OR INTERRUPTING
THE CALL FOR HEAT AT THE THERMOSTAT.
IF THIS DOES NOT RESTART THE SYSTEM,
REFER TO THE TROUBLESHOOTING
SECTION OF THIS MANUAL.
34
All installations and services must be performed by qualified service personnel.
B. INITIAL START UP:
This furnace does not have a pilot. It is equipped with a hot surface igniter which automatically lights the burner. Do not attempt to light the burner by hand. Check the following items before the initial start-up.
1. Check all wiring for loose connections and proper hook up.
2. Leak test gas piping connections.
3. Check all tubing to the pressure switch and drains to make sure they are connected firmly at all their connection points.
4. Check flue pipe, combustion air inlet and all pvc connections for tightness and to make sure there is no blockage.
5. Make sure air filter is in place.
6. Make sure the outside vent and air intakes are installed according to instructions and that they are free from blockage.
7. Make sure that the drain trap is properly connected to the furnace and to the drain system.
OPERATING INSTRUCTIONS:
: Turn off power to furnace before it is placed into service. The gas piping system must have been leak tested by a qualified heating contractor in accordance with State, Local and National Codes including the National Fuel Gas Code NFPA 54/ANSI-Z233.1 (Latest Edition).
: It may be necessary to purge the air out of the gas line for initial start-up of the furnace after installation. This should be done by a qualified heating contractor. If excessive gas escapes when purging the gas supply at the union, allow the area to ventilate for at least 15 minutes before attempting to start the furnace. LP gas is especially dangerous because the specific gravity of LP gas allows it to accumulate at floor level at a dangerous concentration.
: Heat exchanger oil will burn off on initial firing creating an unpleasant odor. To prevent this odor from occurring more than once, it is suggested that:
1. A window(s) be opened.
2. The thermostat set at highest setting.
3. The furnace remain running as noted above for 15 minutes or until odor
has dissipated.
35
All installations and services must be performed by qualified service personnel.
C. ADJUSTMENT OF BTU INPUT RATE:
The orifice for this furnace was sized: 1) for natural gas having a heating value of
1025 BTU per cubic foot and a specific gravity of .65, or 2) for liquefied propane gas with a heating value of 2500 BTU per cubic foot and a specific gravity of
1.55. The information plate inside the furnace vestibule will specify which gas your furnace is orificed for. If the furnace is installed at an altitude that is more than 2,000 feet above sea level, it is mandatory that the input to the burner be reduced 4.0% for every 1,000 feet that it is above sea level. If the furnace is installed at an elevation of 5,000 feet, its input must be reduced 20.0%. Example: a furnace rated at 75,000 BTU at sea level must be reduced to a firing rate of
60,000 (75,000 x .80 = 60,000) at an elevation of 5,000 feet. If the furnace is installed at an elevation of 2,000 feet or less, no reduction in input is required.
Your gas supplier or Style Crest will supply you with the correct orifice sizing information.
To check the input of your natural gas furnace, allow the unit to operate for 10 to
15 minutes and proceed as follows:
1. Call your gas supplier and ask for the BTU content (heating value) of one cubic foot of the gas, supplied to the installation area. An alternate approach is to assume a value of 1025 BTU/Cu Ft which is the national average.
2. With all other gas appliances turned off and using a stopwatch, clock the time required for the (small) dial on the gas meter to make one full revolution. The meter dial will state the cubic feet of flow for one revolution usually one, two or five.
FORMULA: BTU/Cu Ft x Number of Cu Ft x 3600 Seconds = Input BTU/hr
Seconds for one revolution
EXAMPLE: 1025 BTU/Cu Ft x 2 Cu Ft x 3600 = 73,505 BTU Input
100.40 Seconds
Check the model number of the furnace, the input rate, the type of gas, and the manifold pressure on the rating label located in the burner vestibule. If using the above example, the furnace is a VMA1-75N model and the input rate is 73,505 BTU/hr. The input rate would be acceptable because it was within + 2% of the listed input of 75,000.
3. Make sure that the gas supply pressure to the furnace is within the allowable range of 5.5" to 14" WC pressure on natural gas and 11.0" to
14.0" WC on propane gas. The pressure to the furnace must be checked while the furnace burner and any other gas appliances on the same supply system are operating, using the 1/8 in. NPT manifold pressure tap.
36
All installations and services must be performed by qualified service personnel.
GAS PRESSURE CHART FOR VMA* MODEL FURNACES
SUPPLY PRESSURE MANIFOLD PRESSURE
NAT
MAX 14” WC
MIN 4.5” WC
3.5 + .3” WC
PROPANE
MAX 14” WC
MIN 11” WC
10.0” + .3” WC
TABLE 3
This gas furnace is equipped with a fixed orifice sized for the manifold pressure shown on the rating label. The input can only be increased, or decreased, by adjusting the manifold pressure. Remove the 1/8" threaded pipe plug located on the gas manifold.
Use a U tube manometer or recently calibrated pressure gage to measure the pressure. To adjust the pressure, remove the screw cap from the regulator on the gas valve and using the adjustment screw. Decrease the pressure by turning the screw counterclockwise or increase it by turning the screw clockwise.
: ADJUSTMENTS TO THE LISTED PRESSURE MUST NOT
EXCEED 0.3" WC. A 0.3" WC adjustment will increase or decrease the input approximately 4.0%.
Replace screw (cap) when adjustment is complete.
The correct input can be assumed if the furnace manifold pressure is the same as that shown on the rating label if a gas meter is not available for natural gas or the unit is installed on an unmetered propane gas supply.
Shut off the gas supply to the furnace. Remove the pressure gage and reinstall the pipe plug using a thread compound resistant to the action of LP gases.
If the rated input cannot be obtained with the present orifice at the correct pressure, your local gas supplier may assist in sizing the proper orifice.
Style Crest will gladly assist in sizing the orifice if you provide them with the heating value in BTU per cubic foot and the specific gravity of the fuel gas.
D. BURNER ADJUSTMENT
This unit is designed to not require any burner adjustment. The flames should be checked by looking through the sight glass located on the burner box. Burner
37
All installations and services must be performed by qualified service personnel.
flames should be clear, blue and almost transparent in color. (see Figure 16).
NOTE: It is not unusual to have orangish flames visible in the tube for LP gas.
Figure 16.
:
The VMA furnace models are direct vent design and do not require an air shutter adjustment (air shutters are not used) for proper flame characteristics. Burner box access cover must always be secured
with all screws in place and tightened before operating furnace.
E. SETTING TEMPERATURE RISE
All VMA Models are designed and wired at the factory for a heating blower speed that should result in an approximate temperature rise of 60
°F. The blower motors are wired on med-low speed for heating mode. The temperature rise through the furnace may vary depending on the duct system, elevation, heating value, etc. for each installation. A lower temperature rise will result in a higher efficiency.
Temperature rise = supply air temperature - return air temperature.
After 10 to 15 minutes of continuous operation, the temperature rise through the furnace must fall within a range of 40
°F to 70°F. If the outlet or supply duct temperature is too high, you should check to make sure that your return air filter is clean, your return air openings are free from obstruction, your outlet registers are properly adjusted and clear and your supply and return air ducts are open.
The circulating air blower is not moving enough air if the supply air temperature is still too high. Before proceeding further, turn off the power supply to the furnace and remove the front door of the unit.
The speed of the blower must be increased by changing the speed tap from the motor (see figure 15). This is accomplished by locating the control panel attached to the blower housing and switching the blue (med. low) blower lead, which should be connected to the “Heat” terminal on the White-Rodgers 50A65-143
38
All installations and services must be performed by qualified service personnel.
control, with one of the higher speed blower leads attached to a terminal marked
“Park”. Be sure to attach any unused blower leads to a terminal marked “Park”.
Replace the blower door and turn on the power supply.
F. FURNACE CHECKOUT PROCEDURE
Before any system of gas piping is finally put into service, it shall be carefully tested to assure that it is gas tight as indicated in the Fuel Piping Section of this
Furnace Manual.
NOTICE: All controls on the unit should be checked for proper functioning prior to the qualified service personnel leaving the job site. Specifically the following should be checked:
With furnace in normal heating operation, check to make certain blower will start and stop automatically under control of integrated fan control.
1. Check safety limit control as follows: a. Shut off incoming power. b. Block return air opening or disconnect blower motor leads. c. Restore power to furnace. d. Set thermostat above room temperature calling for heat. e. When temperatures are reached in furnace at limit control setting with
blower out of operation, burner should shut off. f. Shut off electrical power.
IMPORTANT: Remove blockage or reconnect blower motor and restore power.
2. Make certain thermostat will automatically start and stop furnace.
3. Block the flue pipe outlet gradually with a flat piece of metal, until the pressure switch functions shutting off the main burners. IMPORTANT: Remove flue outlet blockage when done.
4. Block the PVC pipe inlet gradually with a flat piece of metal until pressure switch functions shutting off the main burners. IMPORTANT: Remove air inlet blockage when done.
5. Remove the blower compartment access door with the furnace operating. The door interrupt switch is in the 120 volt circuit and will shut down the entire system. Replace the blower door and the furnace start-up cycle will begin.
39
All installations and services must be performed by qualified service personnel.
VI. INSTALLER'S INSTRUCTIONS TO USER:
After completing the installation, the installer shall inform and/or demonstrate to the homeowner:
1. The location of all the instructions in the furnace and that the instructions must be kept along with instructions for any accessories in the plastic pouch.
2. The location and use of the manual gas shut off valve and furnace electrical disconnect switch. Instruct user to always shut off gas before shutting off electric power.
3. The sequence of operation of the furnace.
4. The correct operation and maintenance of the appliance as outlined in this manual.
5. That failure to maintain and operate this furnace in accordance with these instructions could result in hazardous conditions, bodily injury, property damage and may void the limited warranty on the furnace.
6. Review with and encourage the user to read the label reproductions and all warnings and instructions in this manual.
7. Recommend that the user have a qualified heating contractor inspect the furnace at the start of each heating season. Inform the user of the frequency of inspection required for each component.
8. Should the furnace not operate after installation – note diagnostic code through view port prior to removing door.
VII. DEALER MAINTENANCE
The following maintenance procedures should be performed at the beginning of each heating season by a qualified heating contractor. Correct any
deficiencies at once.
: Personal injury or property damage could result from repair or service of this furnace by anyone other than a qualified heating contractor.
: To avoid injury from moving parts, shut off the power to the furnace before removing blower compartment door.
:
Label wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous operation.
40
All installations and services must be performed by qualified service personnel.
A. ELECTRICAL:
1. Check diagnostic code through view port prior to removing access door.
2. Check all wiring for loose connections and any signs of damage or unusual wear.
3. Check for correct voltage at the furnace when operating.
4. Check amp-draw on blower motor and inducer motor to assure they are not
exceeding name plate amp rating.
5. Check for correct operation and proper settings (if manually adjustable) of all controls.
Shut off gas and disconnect power before continuing.
B. GENERAL INSPECTION
1. VENT PIPE COMBUSTION AIR INTAKE
a. Remove the vent and check the vent for signs of carbon build-up and for signs of blockage. b. The entire length of vent and combustion air inlet pipe and their terminations should be inspected for restrictions, loose or loosely sealed joints, carbon build-up. Also inspect the outside vent and combustion air terminals and ensure that they are clear and unobstructed.
2. CONDENSATE LINE/TRAP ASSEMBLY
The condensate line must be inspected to make sure it is not blocked. All of the lines should be flushed with water to remove any build-up of sediment.
3. BURNERS
If it appears that material is accumulating in the burner box, the burner box cover can be removed and the box and burners can be vacuumed. (NOTE: The igniter
& flame sensor must be removed before removing the assembly.) If necessary, the burners assembly can be removed by taking out the two screws/one on each bracket on the bottom of the box on VMA’s or on top of the box and removing the burner drawer assembly. Assembly must be pulled & tilted away from the blower compartment in order to remove from box. If necessary, the individual tubes can be cleaned out using compressed air to blow out the individual tubes. Care must be taken not to damage the igniter.
4. INDUCER BLOWER ASSEMBLY
Inspect the pressure switch and drain tubing connections and inspect the blower/assembly for warpage, deterioration and carbon or other build-up. If necessary, clean the accessible portions of the housing and blower with a damp cloth. Vacuum to remove any lint or dust from the motor assembly.
41
All installations and services must be performed by qualified service personnel.
5. GASKETS/SEALING MATERIALS
Inspect all visible gaskets for signs of degradation or liquid seepage, especially any seals which were removed as part of the inspection. Replace any suspect gaskets.
C. HEAT EXCHANGER
Inspect for corrosion, pitting, warpage, deterioration, carbon build-up and loose gaskets in the flue pipe, burner box and accessible areas of the heat exchanger.
1. CLEANING THE COIL AIR SIDE
a. Remove the blower from the blower compartment. In order to remove the blower, it will first be necessary to disconnect the furnace from the outside power supply and disconnect the blower wire harness from the furnace at the blower pan quick connect. b. Clean the coil with a vacuum cleaner by going through the blower pan opening being careful not to bend or damage any of the fins. c. Once all components are cleaned, they must be re-installed to their factory produced state. Any seals or joints in the flue system which have been removed or loosened must be reconnected and sealed if necessary. Do this in accordance with the installation instructions.
:
The inducer motor mounting plate gasket and the collector box
gasket must be replaced.
D. HOUSE AIR BLOWER
Check and clean the blower wheel, housing and compartment with a vacuum.
Check the motor name plate and follow the motor manufacturers instructions for lubrication, if required.
IMPORTANT: Some motors are permanently lubricated and should not be
oiled. See motor name plate for specific instructions.
E. RETURN AIR FILTER
The Return Air Filter(s): Provided with this unit is a permanent type filter. This filter(s) should be inspected and when dirty, cleaned or replaced, if necessary to assure proper furnace operation. Follow the cleaning, removal and replacement procedure below.
42
All installations and services must be performed by qualified service personnel.
FILTER MAINTENANCE PROCEDURE
The filter is located inside front door of the VMA. Remove filter retaining rod and remove dirty filter. Clean the filter by vacuuming, rinsing with tap water, hosing or dipping in an ordinary detergent solution. After cleaning, replace the completely dry filter and retain with retaining rod. If the filter has a mesh, the mesh side of the filter must be towards the furnace.
FILTER REPLACEMENT
Should the filter require replacement, replace with like size and type filter as originally supplied with furnace.
IMPORTANT: Remind homeowner of importance of monthly filter inspections during the heating season to ensure efficient and trouble-free operation of their furnace.
VIII. TROUBLESHOOTING
NOTICE: BEFORE TROUBLESHOOTING, FAMILIARIZE YOURSELF WITH THE
START UP AND CHECKOUT PROCEDURE.
ALL INSTALLATION AND SERVICES MUST BE PERFORMED BY QUALIFIED
HEATING CONTRACTORS.
To assist you in troubleshooting this furnace, it is equipped with an integrated ignition control with diagnostics. These diagnostics evaluate what control system has experienced a failure and will activate a flashing light on the control in different sequences to help pinpoint the failure which has occurred.
Note – check diagnostic code through view port prior to removing access door.
DIAGNOSTIC FEATURES
The 50A65 control used on this furnace continuously monitors its operation and the operation of the system. If a failure occurs, the LED light on the control will flash a code. If the failure is internal to the control, the light will stay on continuously.
In this case, the entire control should be replaced, as the control is not fieldrepairable.
If the sensed failure is in the system (external to the control), the LED will flash in the following flash-pause sequences to indicate failure status (each flash will last approximately 0.25 seconds, and each pause will last approximately 2 seconds).
1 flash, then pause
2 flashes, then pause system locked pressure switch stuck closed
43
All installations and services must be performed by qualified service personnel.
3 flashes, then pause
4 flashes, then pause
6 flashes, then pause
7 flashes, then pause
8 flashes, then pause pressure switch stuck open open high limit switch
115 volt AC power reversed low flame sense signal check ignitor or improper grounding
Continuous flashing
(no pause)
Flame has been sensed when no flame should be present
(no call for heat)
The LED will also flash once at power-up.
: Power must be disconnected before servicing.
44
All installations and services must be performed by qualified service personnel.
TROUBLESHOOTING GUIDE
THE SYSTEM IS STARTED BY SETTING THE THERMOSTAT TO CALL FOR
HEAT. THE FOLLOWING SHOULD HELP ESTABLISH THE TYPE OF
MALFUNCTION OR DEVIATION FROM THE NORMAL OPERATION.
TO USE THIS DIAGRAM, YOU JUST NEED TO FOLLOW THE INSTRUCTIONS IN THE BOXES.
NOTE: CHECK DIAGNOSTIC CODE THROUGH VIEW PORT PRIOR TO REMOVING ACCESS DOOR.
TURN THERMOSTAT TO CALL FOR HEAT
DOES THERMOSTAT MAKE CONTACT?
Yes
Yes
No
No
IS ROOM
TEMPERATURE
ABOVE 90 DEGREES F?
No
IS ROOM TEMPERATURE
BELOW THERMOSTAT
SETTING?
TURN T'STAT
SETTING ABOVE
ROOM TEMP.
Yes
Yes
COOL THE THERMOSTAT
IS THE TRANSFORMER
SUPPLYING 24 VOLTS
TO THE THERMOSTAT?
No
ARE WIRES CONNECTED
PROPERLY?
Yes
REPLACE
THERMOSTAT
Yes
IS INTERNAL DAMAGE
PRESENT ON THE
TRANSFORMER?
No
No CORRECT WIRE
CONNECTIONS
CHECK INPUT
POWER, DOOR
INTERLOCK,
SERVICE SWITCH
AND FUSES.
Yes
REPLACE TRANSFORMER
IS THE INDUCER
BLOWER OPERATING?
Yes
No
IS THERE 24 VOLTS
ACROSS "TH" & "TR"
AT THE INTEGRATED
CONTROL MODEL?
Yes
No CHECK FOR
CONTINUITY
& PROPER
CONNECTIONS
45
All installations and services must be performed by qualified service personnel.
Yes
Yes
IS THERE LINE VOLTAGE
ACROSS INDUCER POWER
TERMINALS "IND" & "IND N"
AT THE INTEGRATED CONTROL?
Yes
CHECK WIRING TO INDUCER
AND IF OK, REPLACE
INDUCER ASSEMBLY.
No CHECK THE INTEGRATED
CONTROL DIAGNOSTIC LED
LAMP. RESET BY INTERRUPTING
POWER TO CONTROL FOR MORE
THAN ONE SECOND. IF LED STAYS
ON CONTINUOUSLY, REPLACE
INTEGRATED CONTROL.
DOES THE HOT
SURFACE
IGNITOR ENERGIZE
AND GLOW?
Yes
No IS THERE VOLTAGE PRESENT
AT THE HOT SURFACE
IGNITOR TERMINALS
"IGN" & "IGN N" AT THE
INTEGRATED CONTROL?
Yes
CHECK WIRING TO
HOT SURFACE IGNITOR
AND IF OK, REPLACE
HOT SURFACE IGNITOR ASSEMBLY.
No
CHECK THE INTEGRATED CONTROL
DIAGNOSTIC LED LAMP. RESET BY
INTERRUPTING POWER TO CONTROL
FOR MORE THAN ONE SECOND. IF
LED STAYS ON CONTINUOUSLY,
REPLACE INTEGRATED CONTROL.
AFTER HOT SURFACE
IGNITOR WARM-UP,
DOES GAS VALVE OPEN?
No
CHECK ACROSS "MV"
TERMINALS ON INTEGRATED
CONTROL FOR 24 VOLTS DURING
THE 4 SECOND FLAME PROVING
PERIOD AFTER IGNITOR WARM-UP.
IS THERE 24VOLTS?
Yes
Yes
CHECK WIRING TO GAS
VALVE AND IF OK,
REPLACE GAS VALVE.
No
SAME AS ABOVE.
46
All installations and services must be performed by qualified service personnel.
Yes
AFTER GAS VALVE
OPENS, DO THE
BURNERS IGNITE?
No CHECK FOR PROPER
MANIFOLD PRESSURE.
Yes
Yes
ADJUST TO 3.5" FOR NATURAL GAS
IS IGNITOR
POSITIONED CORRECTLY?
No
OR 10.0" WC FOR LP GAS
REPOSITION TO
CORRECT LOCATION.
DO BURNERS STAY
LIT PAST PROOF
OF FLAME CHECK?
Yes
DOES THE INTEGRATED CONTROL
ENERGIZE THE
CIRCULATING AIR BLOWER
AFTER THE 45 SECOND
TIME DELAY.
No
CHECK ACROSS THE
CIRCULATING AIR
BLOWER TERMINALS
"CIR N" & "HEAT"
FOR PROPER VOLTAGE.
No
REPLACE THE
INTEGRATED CONTROL.
Yes
DOES THE CIRCULATING
AIR FAN COME ON
WHEN ENERGIZED?
Yes
No
DOES BLOWER
SPIN FREELY?
Yes
IS CAPACITOR
WORKING PROPERLY
No
CONFIRM IF
EITHER BLOWER WHEEL
IS RUBBING AGAINST
HOUSING OR MOTOR
SHAFT IS SPINNING
FREELY AND REPAIR
OR REPLACE AS NECESSARY.
Yes
REPLACE MOTOR
No
REPLACE CAPACITOR
47
All installations and services must be performed by qualified service personnel.
Yes
DOES SYSTEM RUN UNTIL
THERMOSTAT IS SATISFIED?
Yes
DOES BURNER SHUT OFF
WHEN THERMOSTAT IS
SATISFIED?
Yes
DOES THE CIRCULATING
AIR BLOWER TURN OFF
AFTER THERMOSTAT IS
SATISFIED WITHIN
120 SECONDS?
No
IS LED LIGHT
ON INTEGRATED
CONTROL FLASHING?
Yes
No
No
CHECK FOR SHORT IN WIRE TO
THERMOSTAT AND CORRECT
IF NECESSARY.
CHECK ALL
WIRING FOR
LOOSE CONNECTIONS.
Yes
48
All installations and services must be performed by qualified service personnel.
Yes Yes
TROUBLESHOOTING COMPLETE.
IF LED LIGHT FLASHES:
1 FLASH, THEN PAUSE SYSTEM LOCKOUT
2 FLASHES, THEN PAUSE PRESSURE SWITCH STUCK CLOSED
3 FLASHES, THEN PAUSE PRESSURE SWITCH STUCK OPEN
4 FLASHES, THEN PAUSE OPEN LIMIT SWITCH OR ROLLOUT SWITCH
6 FLASHES, THEN PAUSE 115 VOLT AC POWER REVERSED
7 FLASHES, THEN PAUSE LOW FLAME SENSE SIGNAL
8 FLASHES, THEN PAUSE CHECK IGNITOR OR IMPROPER GROUNDING
CONTINUOUS FLASHING FLAME HAS BEEN SENSED WHEN
(NO PAUSE) NO FLAME SHOULD BE PRESENT
(NO CALL FOR HEAT)
CHECK COMPLETE SYSTEM OUT.
THE LED WILL ALSO FLASH ONCE AT POWER-UP.
LED LIGHT STAYS ON CONTINUOUSLY,
COMPLETE FAILURE - REPLACE
INTEGRATED CONTROL.
49
All installations and services must be performed by qualified service personnel.
APPENDIX – A REPLACEMENT PARTS
50
All installations and services must be performed by qualified service personnel.
51
All installations and services must be performed by qualified service personnel.
APPENDIX – B WIRING DIAGRAM
52
All installations and services must be performed by qualified service personnel.
53
advertisement
Key Features
- High efficiency condensing design for energy savings
- Suitable for installation in various types of homes
- Adjustable BTU input rate for customized heating output
- Precise burner adjustment for optimal combustion
- Adjustable temperature rise for tailored comfort levels
- Integrated condensate drain line and trap assembly
- Direct venting through sidewall or roof for flexible installation options
Related manuals
Frequently Answers and Questions
What type of gas is this furnace compatible with?
What is the recommended external static pressure range for the duct system?
How often should the furnace be serviced?
advertisement
Table of contents
- 2 FOR YOUR SAFETY
- 2 WHAT TO DO IF YOU SMELL GAS
- 3 NATIONAL FUEL GAS CODE NATIONAL FIRE PROTECTION ASSOCIATION
- 9 II. FURNACE SPECIFICATIONS - VMA SERIES
- 10 III. GENERAL INSTRUCTIONS AND CLEARANCES – READ BEFORE START OF INSTALLATION
- 12 A. FURNACE LOCATION
- 15 B. BASE INSTALLATION
- 16 C. ALCOVE INSTALLATION
- 18 E. FUEL PIPING
- 19 F. GENERAL VENTING REQUIREMENTS
- 19 1. The vent/air intake terminations outlined in this manual must be used.
- 20 Table 2
- 22 H. Direct Venting Through a Sidewall
- 26 I. Installation Of Outside Exhaust / Intake Terminations
- 27 J. CONNECTING THE FURNACE TO ROOF VENT / AIR TERMINATIONS
- 27 Dual 2” vent/air termination kit VAOPS7484
- 31 If the heat anticipator is set too high, the furnace may delay activation of a heating cycle for too long. If the heat anticipator is set too low, the furnace may cycle too frequently. Either condition may not provide optimal comfort to the homeowner.
- 36 V. STARTING THE UNIT
- 36 A. SEQUENCE OF OPERATIONS
- 40 TABLE 3
- 40 D. BURNER ADJUSTMENT
- 41 E. SETTING TEMPERATURE RISE
- 42 F. FURNACE CHECKOUT PROCEDURE
- 45 E. RETURN AIR FILTER
- 52 APPENDIX – A REPLACEMENT PARTS
- 53 APPENDIX – B WIRING DIAGRAM
- 33 ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE
- 33 HTG Speed
- 33 Recommended CLG Speed
- 34 ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE
- 34 HTG Speed
- 34 Recommended CLG Speed