User manual VK-2C
POWER SUPPLY
RELAY CONTACTS
10. SPECIFICATIONS
Nominal voltage
230 VAC / 50-60 Hz
Maximum voltage
250 V
Nominal current
60 mA
Fuse
100 mA / 250 V
Maximum current
3 A
11. FUSE REPLACEMENT
1. Disconnect completely the unit.
2. Open the unit removing screws of the back cover.
3. Take out the electronic circuit of its box.
4. Replace the fuse from the vertical socket near of the transformer.
12. QUICK GUIDE
Parameters modification
a. To find the parameter to be changed, press repeatedly button. b. To enter to modify the parameter press button. c. To change the value press and buttons. d. To save the value press button twice.
Basic configuration
1. Make the necessary connections.
2. Adjust the zero with cabin empty: find parameter in the menu, press
button and then press button twice. Wait till the countdown expires.
Zero adjustment is required before load adjustment.
3. Adjust of weight with car loaded: find parameter in the menu, press button, change the value according to the load introduced inside the car and then press twice. Wait till the countdown expires.
4. Choose the alarms levels with its associated relays in the
and
parameter:
parameters and the state of
∙ AL-C: From this level, the elevator is considered at full load.
∙ AL-S: From this level, the elevator is considered overloaded.
Dinacell Electrónica, S.L. - www.dinacell.com
C/ El torno, 8 - 28522 Rivas Vaciamadrid - Madrid (SPAIN)
19-6073-00
14/03/2013
12