DSC PC1555 v2.1 Security System Program Sheet
إعلان
إعلان
P R O G R A M M I N G W O R K S H E E T S
Keypad Programming
[000] Keypad Enrollment
(Section 2.5 “Keypad Enrollment”)
NOTE: This must be done at each keypad requiring programming.
[0] Slot [Valid entries are 11-18; ie. enter [11] for slot 1, [12] for slot 2, etc.]
[1] Function Key 1 Assignment (Valid entries are 00-17)
[2] Function Key 2 Assignment (Valid entries are 00-17)
[3] Function Key 3 Assignment (Valid entries are 00-17)
[4] Function Key 4 Assignment (Valid entries are 00-17)
[5] Function Key 5 Assignment (Valid entries are 00-17)
Function Key Options:
00
Null Key
03 Stay Arm
04 Away Arm
05 [ ✱ ][9] No-Entry Arm
06 [ ✱ ][4] Chime On / Off
07 [ ✱ ][6][——][4] System Test
08 [ ✱ ][1] Bypass Mode
09 [ ✱ ][2] Trouble Display
10 [ ✱ ][3] Alarm Memory
11 [ ✱ ][5] User Programming
12 [ ✱ ][6] User Functions
13 Command Output #1 [
✱
][7][1]
14 Command Output #2 [
✱
][7][2]
16 [
✱
][0] Quick Exit
17 [ ✱ ][1] Reactivate Stay/Away’s
LED Defaults
LCD Defaults
KEYPAD 1
KEYPAD 2
KEYPAD 3
KEYPAD 4
KEYPAD 5
KEYPAD 6
KEYPAD 7
KEYPAD 8
Slot (Address)
11
18
I________I________I
I________I________I
I________I________I
I________I________I
I________I________I
I________I________I
I________I________I
I________I________I
Function
Key 1
03
03
I________I
I________I
I________I
I________I
I________I
I________I
I________I
I________I
Function
Key 2
04
04
I________I
I________I
I________I
I________I
I________I
I________I
I________I
I________I
Function
Key 3
06
06
I________I
I________I
I________I
I________I
I________I
I________I
I________I
I________I
Function
Key 4
14
14
I________I
I________I
I________I
I________I
I________I
I________I
I________I
I________I
Function
Key 5
16
16
I________I
I________I
I________I
I________I
I________I
I________I
I________I
I________I
29
P R O G R A M M I N G W O R K S H E E T S
Basic Programming
Zone Definitions
00
Null Zone (Not Used)
09
24 Hour Supervisory (LINKS)
18
24 Hour Sprinkler
01
Delay 1
10
24 Hour Supervisory Buzzer
19
24 Hour Water
02
Delay 2
11
24 Hour Burglary
20
24 Hour Freeze
03
Instant
12
24 Hour Holdup
21
24 Hour Latching Tamper
04
Interior
13
24 Hour Gas
22
Momentary Keyswitch Arm
05
Interior, Stay/Away
14
24 Hour Heat
23
Maintained Keyswitch Arm
06
Delay, Stay/Away
15
24 Hour Medical
24
LINKS Answer
07
Delayed 24 Hour Fire (Hardwired)
16
24 Hour Panic
87
Delay 24 Hour Fire (Wireless)
08
Standard 24 Hour Fire (Hardwired)
17
24 Hour Emergency
88
Standard 24 Hour Fire (Wireless)
If 24-hour Buzzer zones are used, keypads must be installed
[001] Zone 1-8 Definitions
(Section 5.2 “Zone Programming”)
Default Default
01
I_______I_______I
Zone 1 04
I_______I_______I
Zone 5
03
I_______I_______I
Zone 2 04
I_______I_______I
Zone 6
03
I_______I_______I
Zone 3 00
I_______I_______I
Zone 7
03
I_______I_______I
Zone 4 00
I_______I_______I
Zone 8
Keypad zones are assigned in Section [020]. Zone Attributes are assigned in Sections [101] - [108].
Zone assignment is in section [202].
[005] System Times
Default [001-255]
030
I_______I_______I_______I
Entry Delay 1 (in seconds)
(Section 5.18 “Entry/Exit Delay Options”)
045
I_______I_______I_______I
Entry Delay 2 (in seconds)
(Section 5.18 “Entry/Exit Delay Options”)
120
I_______I_______I_______I
Exit Delay (in seconds)
(Section 5.18 “Entry/Exit Delay Options”)
004
I_______I_______I_______I
Bell Cut-off (in minutes)
(Section 5.13 “Siren”)
[006] Installer’s Code
(Section 4.1 “Installer Programming”)
Default
1555
I_______I_______I_______I_______I
Version 2.3 use 5555
[007] Master Code
(Section 5.1 “Programming Security Codes”)
Default
1234
I_______I_______I_______I_______I
[008] Maintenance Code
(Section 5.1 “Programming Security Codes”)
Default
AAAA
I_______I_______I_______I_______I
30
P R O G R A M M I N G W O R K S H E E T S
[009] PGM Output Programming (PGM 1 and 2)
(Section 5.11 “PGM Output Options”)
Programmable Output Options
01
Burglary and Fire Bell Output
02
For future use
03
Sensor Reset
04
2-wire Smoke Support (PGM2 only)
05
System Armed Status
06
Ready To Arm
07
Keypad Buzzer Follow Mode
08
Courtesy Pulse
09
System Trouble Output (with Trouble options)
10
Latched System Event [Strobe (with Event options)]
11
System Tamper (all sources: zones, kpd, modules)
12
TLM and Alarm
13
Kissoff Output
14
Ground Start Pulse
15
Remote Operation (DLS-1 Support)
16
LINKS 1000 Support (PGM1 only)
17
Away Armed Status
18
Stay Armed Status
19
Command Output #1 ([✱] [7] [1])
20
Command Output #2 ([✱] [7] [2])
21
For future use
22
For future use
23
Silent 24 Hour (PGM2 Only)
24
Audible 24 Hour (PGM2 Only)
Output types [03], [04] and [20] cannot be used together on the same system.
Default
19
I_______I_______I
PGM 1
10
I_______I_______I
PGM 2
Program PGM Option Attributes in sections [141] & [142].
[012] Keypad Lockout Options
(Section 5.21 “Keypad Lockout Options”)
If Keypad Lockout is active, the panel cannot be disarmed with a keyswitch.
Default
000
000
I_______I_______I_______I
I_______I_______I_______I
Number of Invalid Codes Before Lockout (001-255 codes)
Lockout Duration (001-255 minutes)
[013] First System Option Code
Default
OFF
OFF
ON
Option
I________I
I________I
I________I
1
2
3*
ON
Normally Closed Loops
Double End-of-Line Resistors
OFF
End-of-Line Resistors
Single End-of-Line Resistors
Section
2.8
2.8
Panel shows all troubles when armed Panel shows only Fire troubles when armed 3.4
OFF
OFF
I________I
I________I
4
5
Tampers/Faults do not show as open
Zone 1 is Fast Loop Response
Tampers/Faults show as open
Zone 1 is Standard Loop Response
5.8
5.24
ON
ON
OFF
I________I
I________I
I________I
6
7
8
Audible Exit Fault Enabled Audible Exit Fault Disabled
Event Buffer Follows Swinger Shutdown Event Buffer Logs Events Past shutdown
Temporal Three Fire Signal Enabled
*
Option 3 must be OFF if LCD keypads older than v2.0 are used.
Standard Pulsed Fire Signal
5.18
5.20
5.13
[014] Second System Option Code
Default Option ON
OFF
OFF
I________I
I________I
1
2
Arm / Disarm Bell Squawk enabled
Bell Squawk During Auto Arm
OFF
OFF
OFF
ON
OFF
OFF
I________I
I________I
I________I
I________I
I________I
I________I
3
4
5
6
7
8
Bell Squawk On Exit Delay
Bell Squawk On Entry Delay
Bell Squawk On Trouble
Audible Exit with Urgency
Exit Delay Termination Enabled
Fire Bell is Continuous
OFF
Arm / Disarm Bell Squawk disabled
No Bell Squawk During Auto Arm
No Bell Squawk On Exit Delay
No Bell Squawk On Entry Delay
No Bell Squawk On Trouble
Silent Exit Delay
Exit Delay Termination Disabled
Fire Bell follows Bell Cut-off
Section
5.17
5.18
5.18
5.18
3.4
5.18
5.18
5.13
31
P R O G R A M M I N G W O R K S H E E T S
[015] Third System Option Code
Default Option ON
ON
OFF
I________I
I________I
1
2
Fire Keys Enabled
Panic Keys Audible (Bell / Beeps)
OFF
ON*
OFF
OFF
ON
OFF
I________I
I________I
I________I
I________I
I________I
I________I
3
4
5
6
7
8
Quick Exit Enabled
Quick Arming Enabled
Code Required For Bypassing
Master Code Not Changeable
TLM Enabled
TLM Audible (Bell) When Armed
* When using a PC5132 version 2.1 or older with WLS909 Wireless Keys, option [4] must be ON for the arm button to work.
[016] Fourth System Option Code
Default
ON
OFF
OFF
OFF
I________I
I________I
I________I
I________I
Option
1
2
3
4
ON
AC Trouble Displayed
Trouble Light Flashes if AC Fails
Blank Keypad When Not Used
OFF
AC Trouble Not Displayed
Trouble Light Does Not Follow AC Status
Keypad Active Always
Code Required to Remove Kypd Blanking No Code Required
ON
OFF
OFF
I________I
I________I
I________I
5
6
7
Keypad Backlighting is enabled
Power Save Mode enabled
Keypad Backlighting is disabled
Power Save Mode disabled
Section
3.4
3.4
5.22
5.22
5.23
5.22
Bypass Status Displayed While Armed Bypass Status Not Displayed While Armed 5.17
OFF
I________I
8
Keypad Tampers enabled Keypad Tampers disabled 5.25
[020] Keypad Zone Assignments
(Section 2.12 “Keypad Zones”)
OFF
Fire Keys Disabled
Panic Keys Silent
Quick Exit Disabled
Section
5.16
5.16
3.4
Quick Arming Dis. / Function keys Req. Code3.4
No Code Required 3.4
Master Code Changeable
TLM Disabled
TLM Trouble Beeps When Armed
5.1
5.12
5.12
Only one keypad may be assigned to any given zone.
00
00
00
00
00
Default
00
00
00
I________I_______I
I________I_______I
I________I_______I
I________I_______I
I________I_______I
I________I_______I
I________I_______I
I________I_______I
Keypad (Slot 1) Zone
Keypad (Slot 2) Zone
Keypad (Slot 3) Zone
Keypad (Slot 4) Zone
Keypad (Slot 5) Zone
Keypad (Slot 6) Zone
Keypad (Slot 7) Zone
Keypad (Slot 8) Zone
Valid entries are zones 01-08
Valid entries are zones 01-08
Valid entries are zones 01-08
Valid entries are zones 01-08
Valid entries are zones 01-08
Valid entries are zones 01-08
Valid entries are zones 01-08
Valid entries are zones 01-08
32
P R O G R A M M I N G W O R K S H E E T S
Advanced System Programming
Zone Attributes
(Section 5.3 “Zone Attributes”)
Zone Attribute Defaults (Y = Option ON; N = Option OFF):
Attribute:
ON
OFF
Zone Type:
00
Null Zone
01
Delay 1
02
Delay 2
03
Instant
04
Interior
05
Int. Stay/Away
06
Dly. Stay/Away
07
Dly. 24hr Fire (Hardw.)
08
Stand. 24hr Fire (Hardw.)
09
24hr Superv.
10
24hr Superv. Buzzer
11
24hr Burglary
12
24hr Holdup
13
24hr Gas
14
24hr Heat
15
24hr Medical
16
24hr Panic
17
24hr Emergency
18
24hr Sprinkler
19
24hr Water
20
24hr Freeze
21
24hr Latching Tamper
22
Momentary Keyswitch
23
Maintained Keyswitch
24
LINKS Answer
87
Dly. 24hr Fire (Wireless)
88
Stand. 24hr Fire (Wireless)
1
Audible
Silent
Y
Y
Y
Y
Y
N
N
Y
Y
N
Y
Y
Y
Y
Y
Y
N
N
Y
Y
Y
Y
N
Y
N
Y
Y
2
Steady
Pulsed
3
Chime
No
Y
Y
Y
Y
Y
N
N
Y
Y
N
Y
Y
N
N
Y
N
Y
Y
Y
Y
Y
N
N
Y
Y
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
Y
Y
Y
N
N
N
N
N
N
N
N
Section Zone # Zone
Type*
[101]
1
( )
[102]
[103]
[104]
2
3
4
( )
( )
( )
1
I________I
I________I
I________I
I________I
2
I________|
I________|
I________|
I________|
3
I________|
I________|
I________|
I________|
[105]
[106]
5
6
( )
( )
I________I
I________I
I________|
I________|
I________|
I________|
[107]
7
( ) I________I I________| I________|
[108]
8
( ) I________I I________|
*Record here based on programming in section [001]
I________|
6
Swing
No
N
N
N
N
N
N
N
N
N
N
Y
Y
N
N
N
N
Y
Y
Y
Y
N
N
N
N
N
N
N
6
5
Force
No
N
N
N
N
N
Y
Y
N
N
Y
Y
Y
N
N
Y
N
N
N
N
N
N
N
N
N
N
N
N
5
4
Bypass
No
N
N
N
N
N
N
N
N
N
N
Y
Y
N
N
N
N
Y
Y
Y
Y
N
N
N
Y
Y
N
N
4
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________|
I________I
I________I
I________I
I________I
I________I
I________I
I________I
I________I
7
Tx. Delay
No
8
Wireless Zn.
No
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
7
Y
Y
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
8
33
P R O G R A M M I N G W O R K S H E E T S
PGM Output Attributes
(Section 5.11 “PGM Output Options”)
Program only the following attributes for the PGM Options listed. All others will be ignored. PGM Options are programmed in section [009].
PGM Attribute Defaults (Y = Attribute ON; N = Attribute OFF):
Attribute:
ON
OFF
1
Output enabled
Output disabled
2
—
—
3
True Output
Inverted
PGM Option
[01]
Burg. / Fire Bell
[03]
Sensor Reset
[04]
2-Wire Smk
[05]
Armed Status
[06]
Ready To Arm
[07]
Kypd Bzz Follow
[08]
Courtesy Pulse
[11]
System Tamper
[12]
TLM and Alarm
[13]
Kiss-off
[14]
Gnd Strt Pulse
[15]
Remote Op.
[16]
LINKS 1000 Sup.
[17]
Away Armed Status
[18]
Stay Armed Status
[19]
Comm. Output #1
[20]
Comm. Output #2
[23]
Silent 24 Hr
[24]
Audible 24 Hr
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
4
5 sec. pulse
On / Off
Y
Y
5
Code Req.
No Code Req.
N
N
Y
N
Attribute:
PGM Option
ON
OFF
[09]
System Trouble
1
Serv. req.
Disabled
Y
2
AC Fail
Disabled
Y
3
TLM Fault
Disabled
Y
4
FTC
Disabled
Y
5
Zone Fault
Disabled
Y
6
Zone Tmp.
Disabled
Y
7
Zn. Low Bat.
Disabled
Y
8
Loss of Clock
Disabled
Y
ON
OFF
[10]
Latched Sys. Event
Burg. Evnt.
Disabled
Y
Fire Evnt.
Disabled
Y
Panic Evnt.
Disabled
Y
Med. Evnt.
Disabled
Y
Supv. Evnt.
Disabled
Y
Priority Evnt.
Disabled
Y
Holdup Evnt.
Disabled
Y
—
—
Section PGM Output
# Type*
[141]
1
( )
1
I________I
2
I________|
3
I________|
[142]
2
( ) I________I I________|
*Record here based on programming in section [009]
I________|
4
I________|
I________|
5
I________|
I________|
6
I________|
I________|
7
I________|
I________|
8
I________I
I________I
[160] Maximum Dialing Attempts to Each Phone Number
(Section 5.5 “Communicator Dialing”)
Default: 008
I_______I_______I_______I
Valid entries are 001-255 attempts (Do not enter 000)
[161] Post Dial Wait for Handshake (All Formats)
(Section 5.5 “Communicator Dialing”)
Default: 040
I_______I_______I_______I
Valid entries are 001-255 seconds
34
P R O G R A M M I N G W O R K S H E E T S
[202] Zone Assignments
(Section 5.2 “Zone Programming”)
Program Zone Definitions in section [001] and Zone Attributes in sections [101] - [108].
Program Keypad Zone Assignments in section [020].
Any zones not used on the system should be disabled in this section. Disabled wireless zones should have a blank serial number (ie. [000000]).
ON
ON
ON
ON
ON
Default
ON
ON
ON
I________I
I________I
I________I
I________I
I________I
I________I
I________I
I________I
Option ON
1
Zone 1 is enabled
2
3
6
7
4
5
8
Zone 2 is enabled
Zone 3 is enabled
Zone 4 is enabled
Zone 5 is enabled
Zone 6 is enabled
Zone 7 is enabled
Zone 8 is enabled
OFF
Zone 1 is disabled
Zone 2 is disabled
Zone 3 is disabled
Zone 4 is disabled
Zone 5 is disabled
Zone 6 is disabled
Zone 7 is disabled
Zone 8 is disabled
Communicator Programming
NOTE: For sections [301] to [353], the content of every section by default is [F].
[301] First Telephone Number (32 Digits)
(Section 5.7 “Communicator – Phone Numbers”)
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[302] Second Telephone Number (32 Digits)
(Section 5.7 “Communicator – Phone Numbers”)
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[303] Third Telephone Number (32 Digits)
(Section 5.7 “Communicator – Phone Numbers”)
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[310] First/Third Telephone Number Account Code
(Section 5.6“Communicator – Account Numbers”)
I_______I_______I_______I_______I
[311] Second Telephone Number Account Code
(Section 5.6 “Communicator – Account Numbers”)
I_______I_______I_______I_______I
[320] Alarm Reporting Codes, Zones 1-8
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Zone 1
Zone 2
Zone 3
Zone 4
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
[324] Alarm Restoral Reporting Codes, Zones 1-8
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Zone 1
Zone 2
Zone 3
Zone 4
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
[328] Miscellaneous Alarm Reporting Codes
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
Duress Alarm
Opening After Alarm
Recent Closing
I_______I_______I
I_______I_______I
I_______I_______I
Zone 5
Zone 6
Zone 7
Zone 8
Zone 5
Zone 6
Zone 7
Zone 8
Zone Expander Supervisory Alarm
Zone Expander Supervisory Restoral
Cross Zone Police Code Alarm
35
P R O G R A M M I N G W O R K S H E E T S
[329] Priority Alarm and Restoral
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Keypad Fire Alarm
Keypad Auxiliary Alarm
Keypad Panic Alarm
PGM2 Alarm
[330] Tamper Reporting Codes, Zones 1-8
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Zone 1
Zone 2
Zone 3
Zone 4
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
[334] Tamper Restoral Reporting Codes, Zones 1-8
(Section 5.8 “Communicator – Reporting Codes”)
Keypad Fire Restoral
Keypad Auxiliary Restoral
Keypad Panic Restoral
PGM2 Restoral
Zone 5
Zone 6
Zone 7
Zone 8
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Zone 1
Zone 2
Zone 3
Zone 4
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
[338] Miscellaneous Tamper Reporting Codes
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
General System Tamper
General System Tamper Rest.
Keypad Lockout
Zone 5
Zone 6
Zone 7
Zone 8
[339] Closing (Arming) Reporting Codes, Access Codes 1-8
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 1
Code 2
Code 3
Code 4
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 5
Code 6
Code 7
Code 8
[340] Closing (Arming) Reporting Codes, Access Codes 9-16
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 9
Code 10
Code 11
Code 12
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 13
Code 14
Code 15
Code 16
[341] Closing (Arming) Reporting Codes, Access Codes 17-24
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 17
Code 18
Code 19
Code 20
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 21
Code 22
Code 23
Code 24
[342] Closing (Arming) Reporting Codes, Access Codes 25-32
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 25
Code 26
Code 27
Code 28
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 29
Code 30
Code 31
Code 32
36
P R O G R A M M I N G W O R K S H E E T S
[343] Miscellaneous Closing (Arming) Reporting Codes
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Closing by Duress Code 33
Closing by Duress Code 34
Closing by System Code 40
Closing by System Code 41
I_______I_______I
I_______I_______I
I_______I_______I
Closing by System Code 42
Partial Closing
Special Closing
[344] Opening (Disarming) Reporting Codes, Access Codes 1-8
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 1
Code 2
Code 3
Code 4
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 5
Code 6
Code 7
Code 8
[345] Opening (Disarming) Reporting Codes, Access Codes 9-16
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 9
Code 10
Code 11
Code 12
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 13
Code 14
Code 15
Code 16
[346] Opening (Disarming) Reporting Codes, Access Codes 17-24
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 17
Code 18
Code 19
Code 20
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 21
Code 22
Code 23
Code 24
[347] Opening (Disarming) Reporting Codes, Access Codes 25-32
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 25
Code 26
Code 27
Code 28
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Code 29
Code 30
Code 31
Code 32
[348] Miscellaneous Opening (Disarming) Reporting Codes
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Opening by Duress Code 33
Opening by Duress Code 34
Opening by System Code 40
Opening by System Code 41
I_______I_______I
I_______I_______I
I_______I_______I
Opening by System Code 42
Auto Arm Cancellation
Special Opening
[349] Maintenance Alarm Reporting Codes
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Battery Trouble Alarm
AC Failure Trouble Alarm
Bell Circuit Trouble Alarm
Fire Trouble Alarm
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
[350] Maintenance Restoral Reporting Codes
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Battery Trouble Restoral
AC Failure Trouble Restoral
Bell Circuit Trouble Restoral
Fire Trouble Restoral
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Auxiliary Power Supply Trouble Alarm
TLM Trouble Code (via LINKS)
General System Trouble
General System Supervisory
Auxiliary Power Supply Trouble Restoral
TLM Restoral
General System Trouble Restore
General System Supervisory Restore
37
P R O G R A M M I N G W O R K S H E E T S
[351] Miscellaneous Maintenance Reporting Codes
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
I_______I_______I
Phone Number 1 Failure to Communicate Restore
Phone Number 2 Failure to Communicate Restore
Event Buffer is 75% Full Since Last Upload
DLS Lead IN
DLS Lead OUT
General Zone Trouble Alarm
General Zone Trouble Restore
Delinquency Code
[352] Test Transmission Reporting Codes
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
Periodic Test Transmission
System Test
I_______I_______I
LINKS 1000 Test Transmission Code*
I_______I_______I
*The LINKS Test Transmission Code must be programmed as “00” for the LINKS Test Transmission to be disabled.
[353] Wireless Maintenance Reporting Codes
(Section 5.8 “Communicator – Reporting Codes”)
I_______I_______I
General Zone Low Battery Alarm
I_______I_______I
General Zone Low Battery Restore
[360] Communicator Format Options
(Section 5.9 “Communicator – Reporting Formats”)
The Third telephone number follows the format of the First telephone number.
Default
02
I_______I_______I
1st Phone Number
02
I_______I_______I
2nd Phone Number
01 20 BPS, 1400 HZ handshake
02 20 BPS, 2300 HZ handshake
03 DTMF CONTACT ID
04 SIA FSK
[361] Alarm/Restore Communicator Call Directions
(Section 5.5 “Communicator – Dialing”)
Default
ON
OFF
OFF
OFF
OFF
I_______I
I_______I
I_______I
I_______I
I_______I
Option ON
1
2
3
4
5-8
1st Telephone Number
2nd Telephone Number
1st Telephone Number (via LINKS)
2nd Telephone Number (via LINKS)
For Future Use
[363] Tamper/Restore Communicator Call Directions
(Section 5.5 “Communicator – Dialing”)
Default
ON
OFF
OFF
OFF
OFF
I________I
I________I
I________I
I________I
I________I
Option ON
1
2
3
4
5-8
1st Telephone Number
2nd Telephone Number
1st Telephone Number (via LINKS)
2nd Telephone Number (via LINKS)
For Future Use
[365] Opening/Closing Communicator Call Directions
(Section 5.5 “Communicator – Dialing”)
Default
ON
OFF
OFF
OFF
OFF
I________I
I________I
I________I
I________I
I________I
Option ON
1
2
3
4
5-8
1st Telephone Number
2nd Telephone Number
1st Telephone Number (via LINKS)
2nd Telephone Number (via LINKS)
For Future Use
OFF
Disabled
Disabled
Disabled
Disabled
OFF
Disabled
Disabled
Disabled
Disabled
OFF
Disabled
Disabled
Disabled
Disabled
05 Pager
38
P R O G R A M M I N G W O R K S H E E T S
[367] System Maintenance Alarm/Restore Communicator Call Directions
(Section 5.5 “Communicator – Dialing”)
Default
ON
OFF
OFF
OFF
OFF
I________I
I________I
I________I
I________I
I________I
Option ON
1
2
3
4
5-8
1st Telephone Number
2nd Telephone Number
1st Telephone Number (via LINKS)
2nd Telephone Number (via LINKS)
For Future Use
OFF
Disabled
Disabled
Disabled
Disabled
[368] System Test Transmissions Communicator Call Directions
(Section 5.5 “Communicator – Dialing”)
Default
ON
OFF
OFF
OFF
OFF
I________I
I________I
I________I
I________I
I________I
Option ON
1
2
3
4
5-8
1st Telephone Number
2nd Telephone Number
1st Telephone Number (via LINKS)
2nd Telephone Number (via LINKS)
For Future Use
OFF
Disabled
Disabled
Disabled
Disabled
The LINKS1000 backup call directions will only back up their respective telephone numbers.
[370] Communication Variables
Default
003
I_______I_______I_______I
Swinger Shutdown (Alarms and Rest)
003
I_______I_______I_______I
Swinger Shutdown (Tampers and Rest)
003
I_______I_______I_______I
Swinger Shutdown (Maint and Rest)
000
I_______I_______I_______I
Transmission Delay
030
I_______I_______I_______I
AC Failure Communication Delay
003
I_______I_______I_______I
TLM Trouble Delay
030
I_______I_______I_______I
Test Transmission Cycle (land line)
030
I_______I_______I_______I
Test Transmission Cycle (LINKS)
007
I_______I_______I_______I
Zone Low Battery Transmission Delay
030
I_______I_______I_______I
Delinquency Transmission Cycle
*Depends on programming in section [380], option [8].
(001-014 Transmissions, 000=disabled)
(001-014 Transmissions, 000=disabled)
(001-014 Transmissions, 000=disabled)
(001-255 seconds)
(001-255 minutes)
(001-255 days)
(001-255 days)
(000-255 days)
(001-255 days / hours)*
NOTE: To disable the AC failure communications delay, program [000].
Section
5.19
5.19
5.19
5.15
5.8
(No. of checks required - valid entries 003 - 255) 5.12
5.14
5.14
5.8
5.8
[371] Test Transmission Time of Day
(Section 5.14 “Test Transmission”)
Default
9999
I_______I_______I_______I_______I
(Valid entries are 0000-2359, 9999 to disable)
[380] First Communicator Option Code
Default
ON
OFF
OFF
ON
I_______I
I_______I
I_______I
I_______I
Option
1
2
3
4
ON
Communications Enabled
Restorals on Bell Time-out
Pulse Dialing
OFF
Communications Disabled
Restorals Follow Zones
DTMF Dialing
Switch to Pulse Dialing on 5th Attempt DTMF Dial For All Attempts
OFF
OFF
I_______I
I_______I
5
6
3rd Phone Number enabled
Alternate Dial (1st and 3rd)
3rd Phone Number disabled
Call 1st Number, Backup to 3rd
OFF
OFF
I_______I
I_______I
7
8
Call LINKS as well as Land Line LINKS is Backup of Land Line(s)
Delinquency Follows Zone Activity (hours)Delinquency Follows Arming (days)
Section
5.5
5.8
5.5
5.5
5.7
5.7
5.26
5.8
39
P R O G R A M M I N G W O R K S H E E T S
[381] Second Communicator Option Code
Default
OFF
I_______I
Option
1
ON OFF Section
Open After Alarm Kypd Ringback enabled Open After Alrm Kypd Ringback disabled 5.17
OFF
OFF
I_______I
I_______I
2
3
Open After Alarm Bell Ringback enabled Open After Alrm Bell Ringback disabled
SIA Sends Programmed Rep. Codes SIA Sends Automatic Rep. Codes
5.17
5.9
OFF
OFF
I_______I
I_______I
4
5-8
Closing Confirmation Enabled
For Future Use
Closing Confirmation Disabled
—
5.17
[390] LINKS Preamble (First Telephone Number)
(Section 5.26 “LINKS 1000 Cellular Communicator”)
Default
FFFF
I_______I_______I_______I_______I
(Program all unused digits with Hex F)
[391] LINKS Preamble (Second Telephone Number)
(Section 5.26 “LINKS 1000 Cellular Communicator”)
Default
FFFF
I_______I_______I_______I_______I
(Program all unused digits with Hex F)
[392] LINKS Preamble (Third Telephone Number)
(Section 5.26 “LINKS 1000 Cellular Communicator”)
Default
FFFF
I_______I_______I_______I_______I
(Program all unused digits with Hex F)
[393] LINKS Special Function Preamble (All Telephone Numbers)
(Section 5.26 “LINKS 1000 Cellular Communicator”)
Default
FFFFFF
I_______I_______I_______I_______I_______I_______I
• Enter [✱] [2] [✱] (HEX B) to dial [✱]
• Enter [✱] [3] [✱] (HEX C) to dial [#]
(Program all unused digits with Hex F)
Downloading Options
[401] First Downloading Option Code
(Section 5.10 “Downloading”)
Default
OFF
ON
OFF
OFF
OFF
I_______I
I_______I
I_______I
I_______I
I_______I
Option ON
1
2
3
4
5-8
Answering machine/double call enabled Answering machine/double call disabled
User Can Enable DLS Window
Call-Back Enabled
User-initiated call-up enabled
For Future Use
OFF
User Cannot Enable DLS Window
Call-Back Disabled
User-initiated call-up disabled
[402] Downloading Computer’s Telephone Number (32 Digits)
(Section 5.10 “Downloading”)
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[403] Downloading Access Code
(Section 5.10 “Downloading”)
Default: 1555
Default: 1555
I_______I_______I_______I_______I
[404] Panel Identification Code
(Section 5.10 “Downloading”)
I_______I_______I_______I_______I
Enter 4 HEX digits
Enter 4 HEX digits
[405] Answering Machine Double-call Timer
(Section 5.10 “Downloading”)
Default: 060
I_______I_______I_______I
(Valid entries are 001-255 seconds)
40
P R O G R A M M I N G W O R K S H E E T S
[406] Number of Rings to Answer On
(Section 5.10 “Downloading”)
Default: 000
I_______I_______I_______I
(Valid entries are 000-255 rings)
[490] LINKS Preamble (Downloading Telephone Number)
(Section 5.10 “Downloading”)
Default: FFFF
I_______I_______I_______I_______I
(Program all unused digits with Hex F)
[499] [Installer’s Code] [499] Initiate PC-Link (Local Downloading)
(Section 5.10 “Downloading”)
Module Programming
[801] PC5400 Printer Module Programming
Please refer to your PC5400 Installation Manual for installation and programming instructions.
[803] LINKS2X50 Long Range Radio Interface Programming
Please refer to your LINKS2X50 Installation Manual for installation and programming instructions.
[804] PC5132 Wireless Expansion Programming
Please refer to your PC5132 Installation Manual for programming locations and instructions.
Special Installer Functions
[901] Installer Walk Test Mode Enable / Disable
(Section 5.30 “Walk Test [Installer]”)
[902] Module Supervision Reset
(Section 2.7 “Removing Modules”)
[903] Module Supervision Field
(Section 2.6 “Supervision”)
[904] Wireless Module Placement Test
For more information, please refer to your PC5132 Installation Manual
• Select the module / transmitter (Zones 01-8).
• Press [#] to Cancel.
Placement
Good
Led Keypad
Light 1 ON Steady
Fair
Bad
Light 2 ON Steady
Light 3 ON Steady
[990] Installer Lockout Enable
(Section 5.29 “Installer Lockout”)
LCD Keypad
“GOOD”
“FAIR”
“BAD”
[991] Installer Lockout Disable
(Section 5.29 “Installer Lockout”)
[993] Restore LINKS2X50 Factory Default Programming
(Section 5.28 “Resetting Factory Defaults”)
[996] Restore PC5132 Factory Default Programming
(Section 5.28 “Resetting Factory Defaults”)
[997] Restore PC5400 Factory Default Programming
(Section 5.28 “Resetting Factory Defaults”)
[999] Restore PC1555 Factory Default Programming
(Section 5.28 “Resetting Factory Defaults”)
Bell / Buzzer
1 Beep / Squawk
2 Beeps / Squawks
3 Beeps / Squawks
41
Contact ID
A P P E N D I X A
The Partition ID Codes must be 4 digits. All reporting codes must be 2 digits.
The following is a list of Contact ID reporting codes. The first digit (in parentheses) will automatically be sent by the control. The last two digits are programmed to indicate specific information about the signal.
For example, if zone 1 is an entry/exit point, the alarm reporting code could be programmed as [34]. The central station would receive the following:
*BURG - ENTRY/EXIT - 1
In the above example, the “1” indicates which zone went into alarm.
When using 2-wire smoke and Contact ID, the zone number will be identified as 99.
Event Codes (as per ADEMCO):
Medical Alarms
(1)AA Medical
(1)A1 Pendant Transmitter
(1)A2 Fail to Report In
Fire Alarms
(1) 1A Fire Alarm
(1)11 Smoke
(1)12 Combustion
(1)13 Water Flow
(1)14 Heat
(1)15 Pull Station
(1)16 Duct
(1)17 Flame
(1)18 Near Alarm
Panic Alarms
(1)2A Panic
(1)21 Duress
(1)22 Silent
(1)23 Audible
Burglar Alarms
(1)3A Burglary
(1)31 Perimeter
(1)32 Interior
(1)33 24 Hour
(1)34 Entry / Exit
(1)35 Day / Night
(1)36 Outdoor
(1)37 Tamper
(1)38 Near Alarm
General Alarms
(1)4A General Alarm
(1)43 Exp. module failure
(1)44 Sensor tamper
(1)45 Module Tamper
(1)4A Cross Zone Police Code
24 Hour Non-Burglary
(1)5A 24 Hour non-Burg
(1)51 Gas detected
(1)52 Refrigeration
(1)53 Loss of Heat
(1)54 Water Leakage
(1)55 Foil Break
(1)56 Day Trouble
(1)57 Low bottled Gas level
(1)58 High Temp
(1)59 Low Temp
(1)61 Loss of Air Flow
Fire Supervisory
(2)AA 24 Hour non-Burg
(2)A1 Low Water Pressure
(2)A2 Low CO2
(2)A3 Gate Valve Sensor
(2)A4 Low water level
(2)A5 Pump activated
(2)A6 Pump failure
System Troubles
(3)AA System Trouble
(3)A1 AC Loss
(3)A2 Low System Battery
(3)A3 RAM checksum bad
*
(3)A4 ROM checksum bad
*
(3)A5 System Reset
*
(3)A6 Panel prog. changed
*
(3)A7 Self-test failure
(3)A8 System Shutdown
(3)A9 Battery Test Failure
(3)1A Ground Fault
Sounder / Relay Troubles
(3)2A Sounder / Relay
(3)21 Bell 1
(3)22 Bell 2
(3)23 Alarm Relay
(3)24 Trouble Relay
(3)25 Reversing
System Peripheral Troubles
(3)3A System Peripheral
(3)31 Polling Loop Open
(3)32 Polling Loop Short
(3)33 Exp. Module Failure
(3)34 Repeater Failure
(3)35 Local Printer Paper Out
(3)36 Local Printer Failure
Communication Troubles
(3)5A Communication
(3)51 Telco 1 Fault
(3)52 Telco 2 Fault
(3)53 Lng-Rnge Rad. xmttr. fault
(3)54 Fail to Communicate
(3)55 Loss of radio super.
(3)56 Loss of central polling
Protection Loop Troubles
(3)7A Protection Loop
(3)71 Protection Loop open
(3)72 Protection Loop short
(3)73 Fire Trouble
Sensor Troubles
(3)8A Sensor Trouble
(3)81 Loss of super. RF
(3)82 Loss of super. RPM
(3)83 Sensor Tamper
(3)84 RF xmitter low batter
Open / Close
(4)AA Open / Close
(4)A1 O / C by User
(4)A2 Group O / C
(4)A3 Automatic O / C
(4)A4 Late to O / C
(4)A5 Deferred O / C
(4)A6 Cancel
(4)A7 Remote Arm / Disarm
(4)A8 Quick Arm
(4)A9 Keyswitch O / C
Remote Access
(4)11 Callback request made
*
(4)12 Successful Download access
*
(4)13 Unsuccessful access
*
(4)14 System Shutdown
(4)15 Dialer Shutdown
Access Control
(4)21 Access denied
(4)22 Access report by user
Miscellaneous
(4)56 Partial close
(4)59 Recent close
System Disables
(5)AA-(5)1A
Sounder / Relay Disables
(5)2A Sounder / Relay disable
(5)21 Bell 1 disable
(5)22 Bell 2 disable
(5)23 Alarm relay disable
(5)24 Trouble relay disable
(5)25 Reversing relay disable
System Peripheral Disables
(5)3A-54A
Communication Disables
(5)51 Dialer disabled
(5)52 Radio xmitter disabled
Bypasses
(5)7A Zone bypass
(5)71 Fire bypass
(5)72 24 Hour zone bypass
(5)73 Burg bypass
(5)74 Group bypass
Test / Misc.
(6)A1 Manual Trigger Test
*
(6)A2 Periodic Test report
*
(6)A3 Periodic RF xmission
*
(6)A4 Fire test
*
(6)A5 Status report to follow
*
(6)A6 Listen-in to follow
(6)A7 Walk test mode
(6)23 Event buffer 90% full
*
Restore not applicable
42
SIA Format
A P P E N D I X B
SIA Format
Level 2 (Hardcoded)
The SIA communication format used in this product follows the level 2 specifications of the SIA Digital Communication Standard -
January 1996. This format will send the Account Code along with its data transmission. The transmission would look similar to the following at the receiver:
N Ri01 BA 01
N = New Event
Ri01 = Partition / Area Identifier
BA = Burglary Alarm
01 = Zone 1
PC1555 Reporting Codes SIA Identifiers &
Auto-Reporting Code
Delay Zone Alarm /Restore ....................................... BA-XX / BH-XX *
Instant Zone Alarm / Restore ..................................... BA-XX / BH-XX *
Interior Zone Alarm / Restore ..................................... BA-XX / BH-XX *
Delay S.A. Zone Alarm /Restore .............................. BA-XX / BH-XX *
Interior S.A. Zone Alarm / Restore ............................ BA-XX / BH-XX *
24 Hr Burg Zone Alarm / Restore .............................. BA-XX / BH-XX *
Standard Fire Zone Alarm / Restore .......................... FA-XX / FH-XX *
Delayed Fire Zone Alarm / Restore ............................ FA-XX / FH-XX *
24 Hr Supervisory Buzzer Zone Alarm / Restore ..... UA-XX/ UH-XX *
24 Hr Supervisory Zone Alarm / Restore ................. UA-XX / UH-XX *
24 Hr Medical Zone Alarm / Restore ....................... MA-XX / MH-XX *
24 Hr Panic Zone Alarm / Restore ............................ PA-XX / PH-XX *
24 Hr Holdup Zone Alarm / Restore ......................... HA-XX / HH-XX *
24 Hr Gas Zone Alarm / Restore .............................. GA-XX / GH-XX *
24 Hr Heat Zone Alarm / Restore .............................. KA-XX / KH-XX *
24 Hr Emergency Zone Alarm / Restore .................. QA-XX / QH-XX *
24 Hr Sprinkler Zone Alarm / Restore ....................... SA-XX / SH-XX *
24 Hr Water Zone Alarm / Restore .......................... WA-XX / WH-XX *
24 Hr Freeze Zone Alarm / Restore .......................... ZA-XX / ZH-XX *
24 Hr Latching Tamper Alarm / Restore ................... BA-XX / BH-XX *
Duress Alarm .......................................................................... HA-00
Opening After Alarm ............................................................... OR-00
Recent Closing ........................................................................ CR-00
Zone Expander Supervisory Alarm / Restore ............. UA-00/UH-00
Keypad Fire Alarm / Restore ...................................... FA-00 / FH-00
Keypad Auxiliary Alarm / Restore ............................ MA-00 / MH-00
Keypad Panic Alarm /Restore ................................... PA-00 / PH-00
2-wire Smoke Alarm / Restore .................................... FA-99 / FH-99
Audible/Silent 24 Hr .................................................. UA-99 / UH-99
PC1555 Reporting Codes SIA Identifiers &
Auto-Reporting Code
Zone Tamper (1-8) .................................................................... TA-XX *
Zone Tamper Restorals (1-8) ................................................... TR-XX *
General System Tamper / Restore ............................... TA-00 / TR-00
Keypad Lockout ........................................................................ JA-00
Closing By Access Codes 1-32, 33, 34, 40-42 ...................... CL-XX
◆
Partial Closing .......................................................................... CG-XX
▼
Special Closing (DLS, Keys, Maint, Quick) ............................. CL-00
Opening By Access Codes 1-32, 33, 34, 40-42 .................... OP-XX
◆
Auto-Arm Cancellation .............................................................. CE-00
Special Opening (DLS, Keys, Maint) ...................................... OP-00
Battery Trouble Alarm / Restore .................................... YT-00 / YR-00
AC Failure Trouble Alarm / Restore .............................. AT-00 / AR-00
Bell Circuit Trouble Alarm / Restore .............................. UT-99 / UJ-99
Fire Trouble Alarm / Restore ........................................... FT-00 / FJ-00
Auxiliary Power Supply Trouble Alarm / Restore ........ YP-00 / YQ-00
TLM Trouble Code (via LINKS) ................................................ LT-00
General System Trouble / Restore ................................ YX-00 / YZ-00
General System Supervisory / Restore ......................... ET-00 / ER-00
TLM Restoral ............................................................................. LR-00
FTC Restoral ............................................................................. YK-00
Event Buffer 75% Full Since Last Upload ................................ JL-00
DLS Lead In .............................................................................. RB-00
DLS Lead Out (Successful) ...................................................... RS-00
Periodic Test Transmission ...................................................... RP-00
System Test ............................................................................... RX-00
LINKS1000 Test Transmission Code ....................................... TX-00
General Transmitter Low Battery / Restore .................. XT-00 / XR-00
General Zone Trouble / Restore .................................... UT-00 / UJ-00
Cross Zone Police Code .......................................................... BV-00
Delinquency Code ................................................................... CD-00
* Zone Number is Identified
◆ User Number is Identified
▼ Each Zone Number is Identified (using UB-XX)
NOTE
: Activity Delinquency will transmit the identifier for
Closing Delinquency (CD-00).
43
Programming LCD Keypads
A P P E N D I X C
If you have an LCD5500Z Keypad, additional programming is required for proper operation. The following is a description of the available programming options and their accompanying programming sections:
How to Enter LCD Programming
Follow the programming procedure as outlined in Section 4 by pressing [
✱
] [8] [Installer’s Code]. Press the [
✱
] key. Enter the two digit
Section number to be programmed.
Programmable Labels – Sections [01] - [08], [33], [34], [40], [44], [51], [52]
Zone labels and other LCD display identifiers can be customized to make operation of the system easier for the end user. The following procedure should be used for creating all LCD labels:
• Enter Installer’s Programming. Enter the Number corresponding to the label to be programmed.
• Use the arrow keys (<>) to move the underline bar underneath the letter to be changed.
• Press the number key [1] to [9] corresponding to the letter you require. The first time you press the number the first letter will appear.
Pressing the number key again will display the next letter. Refer to the following chart:
[1] - A, B, C, 1 [2] - D, E, F, 2
[6] - P, Q, R, 6 [7] - S, T, U, 7
[3] - G, H, I, 3
[8] - V, W, X, 8
[4] - J, K, L, 4
[9] - Y, Z, 9,0
[5] - M, N, O, 5
[0] - Space
• When the required letter or number is displayed use the arrow keys (<>) to scroll to the next letter.
• When you are finished programming the Zone Label, press the [ ✱ ] key, scroll to “Save,” then press [ ✱ ].
• Continue from Step 2 until all labels are programmed.
[01] to [08] Zone Labels (14 Characters)
Default: “Zone 1”
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
Default: “Zone 2”
Default: “Zone 3”
Default: “Zone 4”
Default: “Zone 5”
Default: “Zone 6”
Default: “Zone 7”
Default: “Zone 8”
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[33] Fire Alarm Label (14 Characters)
Default: “Fire Zone”
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[34] System Label (14 Characters)
Default: “System”
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[40] to [44] [
✱
] [7] [1-2] Command Output Option Labels (14 Characters)
[40] Default: “Command O/P 1”
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[44] Default: “Command O/P 2”
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[51] Fail to Arm Event Message
Default: “System Has Failed to Arm”
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[52] Alarm When Armed Event Message
Default: “Alarm Occurred While Armed < >”
I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[60] First User Display Mask
Default Option
ON
ON
I_______I
I_______I
1
2
ON
ON
I_______I
I_______I
3
4
ON
ON
ON
ON
I_______I
I_______I
I_______I
I_______I
5
6
7
8
ON
Hold [P]anic Keys prompt ON
Zone Bypassing prompt ON
Troubles prompt ON
Alarm Memory prompt ON
Door Chime Control prompt ON
Access Codes prompt ON
User Functions prompt ON
Output Control prompt ON
OFF
Hold [P]anic Keys prompt OFF
Zone Bypass prompt OFF
Troubles prompt OFF
Alarm Memory prompt OFF
Door Chime Control prompt OFF
Access Codes prompt OFF
User Functions prompt OFF
Output Control prompt OFF
44
P R O G R A M M M I N G L C D K E Y P A D S
[61] Second User Display Mask
Default Option ON
OFF
ON
ON
ON
OFF
ON
OFF
I_______I
I_______I
I_______I
I_______I
I_______I
I_______I
I_______I
1
2
3
4
5
6
7-8
Installer Programming prompt ON
Stay Arm prompt ON
Quick Arm prompt ON
Interior Arm prompt ON
Quick Exit prompt ON
View Event Buffer prompt ON
For Future Use
OFF
Installer Programming prompt OFF
Stay Arm prompt OFF
Quick Arm prompt OFF
Interior Arm prompt OFF
Quick Exit prompt OFF
View Event Buffer prompt OFF
[62] Third User Display Mask
Default
ON
I_______I
Option
1
ON
ON
ON
ON
ON
ON
ON
I_______I
I_______I
I_______I
I_______I
I_______I
I_______I
I_______I
2
3
4
5
6
7
8
ON
System Test prompt ON
Time and Date prompt ON
Auto-Arm Control prompt ON
Auto-Arm Time prompt ON
Download Enable prompt ON
Bright Control prompt ON
Contrast Control prompt ON
Buzzer Control prompt ON
[63] Downloaded LCD Message Duration
OFF
System Test prompt OFF
Time and Date prompt OFF
Auto-Arm Days prompt OFF
Auto-Arm Time prompt OFF
Download Enable prompt OFF
Bright Control prompt OFF
Contrast Control prompt OFF
Buzzer Control prompt OFF
Default: 003
I______I______I______I
(Valid entries are 000-255, 000=Unlimited Message Display. This number represents the number of times the Downloaded message is cleared by pressing any key while the message is up after timeout)
[64] Key Options
Default
ON
ON
ON
I_______I
I_______I
I_______I
Option
1
2
3
[65] Fourth User Display Mask
Default Option
ON
OFF
OFF
ON
I_______I
I_______I
I_______I
I_______I
1
2
3
4
ON
OFF
OFF
I_______I
I_______I
I_______I
5
6
7
[66] Keypad Options
Default Option
ON
ON
I_______I
I_______I
1
2
OFF
ON
OFF
I_______I
I_______I
I_______I
3
4
5-8
[97] View Software Version
ON
[F]ire Keys enabled
[A]uxiliary Keys enabled
[P]anic Keys enabled
ON
User Initiated Call-up Prompt ON
For Future Use
For Future Use
Command Output #1 prompt ON
Command Output #2 prompt ON
For Future Use
For Future Use
ON
Local Clock Display Enabled
Local Clock Displays 24 Hour time
Auto Alarm Memory Scroll Enabled
For Future Use
OFF
[F]ire Keys disabled
[A]uxiliary Keys disabled
[P]anic Keys disabled
OFF
User Initiated Call-up Prompt OFF
Command Output #1 prompt OFF
Command Output #2 prompt OFF
OFF
Display Access Code when Programming Display ‘X’ when Programming
Local Clock Display Disabled
Local Clock Displays AM/PM
Auto Alarm Memory Scroll Disabled
[98] Initiate Global Label Broadcast
All LCD programming is done per keypad. If more than one LCD keypad are present on the system, and the PC5400 receives labels, labels programmed at one keypad can be broadcast to all other LCD keypads. Perform the following procedure in order to broadcast labels:
Step 1 - Program one LCD keypad completely.
Step 2 - Make sure all LCD keypads are connected to the Keybus.
Step 3 - Enter Installer’s Programming, then enter Section [98] at the keypad that was programmed. The keypad will now broadcast all the information programmed to all the other LCD keypads on the system.
Step 4 - When the keypad is finished press the [#] key to exit.
[99] Reset LCD EEPROM to Factory Defaults
ASCII Characters
032 035 038 041 044 047 060 063 094 124 127 228 231
238
241 246 253
033
034
036 039
042 045 058 061
064 095
040 043 046 059 062 093
125
176 234 239
244 248
254
126 225 230 236 240 249 255