Sample Unit

Generator Ratings* @ 1800 RPM

Voltage Ph Hz

120/240 1 60

120/208 3 60

120/240 3 60

277/480 3 60

Standby Output

kW (kVA)

150 (150)

150 (188)

150 (188)

150 (188)

Standard Generator Set Features

Prime Output kW (kVA)

135 (135)

135 (169)

135 (169)

135 (169)

Standby Max Amp

Output

625

520

451

226

Optional Equipment

Number of

Wires

12

12

12

12

· Perkins Diesel Engine Model 1106D-E66TAG3 Tier 3

· AC, Single bearing direct coupled alternator with class

‘H’ insulation, sized for 130°C temperature rise.

· Engine and alternator mounted on vibration isolators.

· Radiator sized for 120°F ambient clearance

· High coolant temp., low oil pressure safety shutdowns.

· Dry type air cleaner.

· 12-VDC starter, engine mounted battery charging alternator, battery cables and rack along with grounding strap.

· Microprocessor based control panel w/ metering, alarms,

shut down, under / over frequency & voltage protection.

· Weather protective enclosure constructed of marine grade aluminum 0.125 thickness, SS hardware

White powder coat paint finish on both sides

Sound insulation resistant to high temperatures,

fuel and oil. Hinged, removable keyed alike doors.

Residential rated interior mounted exhaust silencer

Vertical radiator and exhaust discharge

Oil & coolant drain lines with brass ball check valves

· Mainline circuit breaker.

· Digital or analog control panels.

· Automatic transfer switch

· Starting battery

· Automatic battery chargers 6 or 10 amps

· Thermostat controlled jacket water heater

· Low coolant level switch

· Single wall tanks

· UL 142 fuel tanks

· Day tanks

· Water separator fuel filter

· Space heater

· Permanent Magnet Generator (PMG) with voltage

regulator upgrade

· Generator drip covers

· 17 Light remote annunciator panel

· 120V Receptacle for battery charger and / or coolant

heater.

· D.O.T trailers, single or dual axle with brakes.

· Enviro - friendly custom color options.

*Stand by ratings are applicable for the duration of any power outage. No overload is available at these ratings. Prime ratings are continuous per BS 5514, DIN 6271,

ISO3046 & IEC 34-1. Overload capacity on prime-power ratings is 10% for one hour in each twelve hours of operation. All single phase ratings are based on a 1.0 power factor, three (3) phase ratings based on a 0.8 power factor. Ratings are established based on 85°F ( 29°C ) and an elevation of 1,000 feet ( 305 meters ).

Please consult your Stateline representative for information concerning derates for temperature, altitude & humidity.

Model: Perkins 1106D-E66TAG3 Tier 3

Max power: 220 bhp / 164 kWm @ 1800 rpm

Cubic capacity: 402.8 in³ / 6.6 L

Bore & stroke: 4.13” x 5” (105mm x 127mm)

Turbocharged, air to air charge cooled, 6 cylinder in line

direct injected, governor type-electronic ± 0.4%

Frequency regulation: Isochronous, steady-state ± 0.25%

Flywheel to SAE J620 size 11.5 / housing SAE 3

Fluids: Oil cap. total system - 17.4 quarts ( 16.5 liters )

Coolant cap. w/ radiator - 5.5 gallons ( 21 liters )

Engine Specifications

Fuel Consumption US gallon ( liters ) / hr @ 1800 rpm

50% load - 6.08 ( 23 )

75% load - 8.45 ( 32 )

100% load - 10.5 ( 40 )

General: Oil filter-Spin-on type glow plugs

Electrical system: 12v starter, 100amp alternator DC output

Minimum recommended battery size: 1190 CCA

Fuel type: BS 2869: Part 2 1998 Class A2 or BS EN590 or JP8

Alternator Specifications

Marathon Electric: Type brushless, 4pole rotating field

Voltage regulation: + / - 1%, volts/hertz, electronic, EMI filtered

Class insulation: ‘H’ to NEMA MG-1-1.66

Rated temperature: Standby 130 C° rise / 40 C° ambient

Coupling: SAE adapter, flexible disc, direct.

Load acceptance: One step, 100% per NFPA 110

Features: Self ventilated drip-proof construction. Superior voltage

waveform achieved by a 2/3 pitch and skewed rotor.

Vacuum-impregnated windings with fungus-resistant epoxy for

dependability and long-life. Compliance with NEMA, IEEE and ANSI

standards for temp. rise. Sustained short-circuit capability enabling

down-line circuit breakers to trip without collapsing the generator field.

No load to full-load regulation of +/- 2%.

DGC2020

Microprocessor based, navigation key with large LCD display event recording transfer switch control SAE J1939 CANBUS communication multilingual capability suitable for rental application.

Remote communication capability (optional)

Control Panel Specifications

·

Operational features

Alternator protection: under / over voltage,

under / over frequency.

·

Engine protection: Low oil pressure, high

coolant temperature, over speed & over

crank, sender unit failure, fuel leak / fuel

sender failure, battery charger failure.

·

All protections are programmable as alarms or pre-alarms.

·

Operating power: Nominal 12-24 Vdc

consumption 14.2W run mode

•Metering (ample range): Volts, current, Hz

watts, VA, Pf oil pressure, coolant

temperature, rpm, DC volts, fuel level,

engine running time.

• Engine vontrol with timers

• External remote start input (on or off load)

• 16 programmable contact inputs.

• 7 Contact outputs

Agency Approvals: UL 508 R CSA C22.2 No 14 NFPA 110

CE Compliance: EC LVD-73/23/EEC EN 61000-6-4:2001 EMC EN 50178:1997 EMC- 89/336/EEC EN 610000 6-2:2001 EMC Immunity

One complete set Owners / Operators, Engine, Alternator and Accessory manual

Dimensional and Mounting Specifications

inches (mm): 131.50 ( 3340 ) L x 44 ( 1118 ) W x 67 ( 1702 )H (Enclosure only)

Estimated Dry Weight lb. (kg): 3820 (1732) Less Fuel Tank

Note: The above dimensions and weights would change if a sub-base fuel tank was added. An electrical stub area is positioned at the rear of the sub-base fuel tanks. Spacing from rear access cover to the tank is approximately 9 inches (228.6 mm).

Specifications subject to change without notice

15749 Lyons Valley Rd.

Jamul CA 91935 www.HardyDiesel.com

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement