UNIPOWER X75 COMPACT INTEGRATED DC power system OPERATING MANUAL
Publicitate
Publicitate
OPERATING MANUAL
X75 COMPACT INTEGRATED
DC POWER SYSTEM
Manual No. X75M-5
08/12 X75-Man
WWW.UNIPOWERTELECOM.COM
© 2012 UNIPOWER Corp.
All Rights Reserved
UNIPOWER Telecom, Division of UNIPOWER LLC
NORTH AMERICA • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • Tel: +1 954-346-2442 • Fax: +1 954-340-7901 • [email protected]
EUROPE • Parkland Business Centre, Chartwell Road, Lancing BN15 8UE, ENGLAND • Tel: +44(0)1903 768200 • Fax: +44(0)1903 764540 • [email protected]
X75 SERIES
INSTALLATION & OPERATING MANUAL
CONTENTS
5.0
6.0
7.0
8.0
1.0
2.0
3.0
4.0
INTRODUCTION _________________________________________________________ 4
FEATURES AND OPTIONS ________________________________________________ 5
SAFETY WARNINGS ______________________________________________________ 5
WARRANTY (Summary) ____________________________________________________ 6
UNPACKING AND INSPECTION ____________________________________________ 6
GENERAL SPECIFICATIONS ______________________________________________ 7
FRONT PANEL DESCRIPTION _____________________________________________ 9
REAR PANEL DESCRIPTION _____________________________________________ 10
9.0
10.0
LED INDICATORS _______________________________________________________ 13
MAKING CONNECTIONS TO THE X75____________________________________ 14
11.0
INSTALLATION _______________________________________________________ 17
12.0
USING THE CONTROLLER WEB BROWSER INTERFACE __________________ 20
Appendix 1 - SNMP MIB Information _____________________________________________ 39
Appendix 2 - Revision History _____________________________________________________ 43
Datasheet _____________________________________________________________________ 44
Manual No. X75M-5
2
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
FIGURES
Figure 1 - X75 Compact Integrated DC Power System – base unit with front bezel removed ____ 4
Figure 2 - Front Panel with Bezel Removed __________________________________________ 9
Figure 3a - Rear Panel – Base Unit ________________________________________________ 10
Figure 3b - Rear Panel – Expansion Unit ___________________________________________ 10
Figure 4 - LED Indicators – viewed with front bezel in place ____________________________ 13
Figure 5 – Battery Temp. Probe & Alarm Relay Connector Pin-Out ______________________ 15
Figure 6 - Ethernet Connector Pin-Out _____________________________________________ 15
Figure 7 – Auxiliary Connector Pin-Out ____________________________________________ 16
Figure 8 - Controller Status WEB Page (typical) ______________________________________ 21
Figure 9 - Rectifier Status WEB Page (typical) _______________________________________ 22
Figure 10 - Rectifier I²C Addressing _______________________________________________ 22
Figure 11 - Controller Factory Calibration WEB Page (typical) _________________________ 24
Figure 12 - Controller Site Installation WEB Page (typical) _____________________________ 25
Figure 13 - Alarm Configuration WEB Page (typical) _________________________________ 28
Figure 14 - Controller Network Settings (typical) _____________________________________ 31
Figure 15 - Controller Alarm Log WEB Page (typical) _________________________________ 34
Figure 16 - Controller Control Panel WEB Page (typical) ______________________________ 35
Figure 17 - Controller System Settings WEB Page (typical) _____________________________ 36
Figure 18 - SNMP Configuration WEB Page (typical) _________________________________ 37
Figure 4 - Controller Help WEB Page (typical) _______________________________________ 38
Figure 5 - About UNIPOWER Telecom WEB Page (typical) ____________________________ 38
Manual No. X75M-5
3
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
COMPACT INTEGRATED DC POWER SYSTEM
X75 SERIES
INTRODUCTION 1.0
Gravitas X75 is an ultra-compact, integrated DC power system. The base system is a 1RU shelf holding up to three hot-swap rectifier modules. This system produces up to 1950 watts output at -54.4, +27.2 or +13.6VDC.
It can also be operated as a 2+1 redundant system with up to 1300 watts output. The expanded system consists of a base shelf plus an expander shelf with a 2RU total height. This system holds up to six rectifier modules with up to 3900 watts output; it can be operated as a 5+1 redundant system with up to 3250 watts output. Each rectifier module is cooled by a fan that operates at a speed which is a function of load and temperature.
There are up to five circuit-breaker protected DC outputs or up to 10 GMT fuse protected outputs on the base system. A battery string breaker and a low-voltage battery disconnect are standard features. The expander shelf comes with a ribbon cable and connectors to link the signals between the two units at their rear panels.
It also comes with bus bar links to parallel the rectifier output bus bars.
The base and expander shelves can also be operated as a battery backup, single feed power system (without load circuit breakers or fuses).
The remote access controller has LED visual indicators and Form C relay alarms. It is programmed by means of a remote PC web page display with communication by Ethernet LAN. Temperature compensated rectifier output is provided by means of an accessory TC probe. The X75 can be quickly installed by a qualified technician.
Figure 1 - X75 Compact Integrated DC Power System – base unit with front bezel removed
Manual No. X75M-5
4
08/12 X75-man
2.0
FEATURES AND OPTIONS
Standard Features 2.1
1RU High Base System
1RU High Expander Shelf
Remote Control & Monitoring via TPC/IP Ethernet LAN
Fully Integrated System
Up to 72A at -54.4VDC
Up to 75A at +27.2VDC or +13.6VDC
Wide Range AC Input
Up to 10 DC Load Circuts
Circuit Breakers or GMT Fuses
Quick and Easy Installation
Universal 19/23-Inch Mounting Brackets
X75 SERIES
INSTALLATION & OPERATING MANUAL
2.2
Options & Accessories
Additional Temperature Probe for External Temperature Measurement (‘T’ Option)
SNMP reporting and Error Trapping (‘S’ Option)
Various AC Line cords
3.0
SAFETY WARNINGS
3.1
The X75 Compact DC Power System operates at voltages that could potentially be hazardous. Furthermore, inadvertent short circuiting of the system battery and/or rectifier by misconnection or other error could be harmful. This product should be handled, tested and installed only by qualified technical persons who are trained in the use of power systems and are well aware of the hazards involved.
3.2
When operating the X75 the chassis ground terminal must be connected to the system frame ground or other proper safety ground for the protection of personnel.
3.3
3.4
All connections to the X75 should be carefully checked for errors before applying power to it.
This equipment is intended only for installation in a “RESTRICTED ACCESS
LOCATION”.
Manual No. X75M-5
5
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
4.0
WARRANTY (Summary)
All products of UNIPOWER Telecom, a division of UNIPOWER LLC, are warranted for two (2) years from date of shipment against defects in material and workmanship. This warranty does not extend to products which have been opened, altered or repaired by persons other than persons authorized by the manufacturer or to products which become defective due to acts of God, negligence or the failure of customer to fully follow instructions with respect to installation, application or maintenance.
For a complete text of UNIPOWER’s warranty conditions please request a copy from your local Sales Office.
5.0
UNPACKING AND INSPECTION
5.1
This X75 compact DC power system was carefully tested, inspected and packaged for shipment from our factory. Upon receipt the unit should be carefully unpacked and inspected for any damage in shipment.
5.2
If there is evidence of damage,
do not attempt to install the unit
. The freight carrier should be notified immediately and a claim for the cost of the X75 should be filed with the carrier for direct reimbursement. Be sure to include the model and serial number of the damaged unit in all correspondence with the freight carrier. Also save the shipping carton and packing material as evidence of damage for the freight carrier’s inspection.
5.3
5.4
UNIPOWER Telecom will cooperate fully in case of any shipping damage investigation.
Always save the packing materials for later use in shipping the unit. Never ship the controller without proper packing.
Manual No. X75M-5
6
08/12 X75-man
6.0
X75 SERIES
INSTALLATION & OPERATING MANUAL
GENERAL SPECIFICATIONS
6.1
Inputs
85-264VAC Phase
Each rectifier position is supplied via an individual IEC60320 C14
Supply Current:
Battery Input:
A 3-phase supply may be connected provided that the voltage presented to each individual rectifier position does not exceed
264VAC.
Maximum 9A per Inlet Socket
Direct connection to DC output bus via protection breaker.
Digital alarm inputs:
*Volts free contacts are internally pulled up to 5V with reference to rectifier negative sense, these lines should not be tied to anything other than volts free contacts or floating opto-coupler outputs.
Temperature probes:
Volts free contact input*
Sensor with output current proportional to temperature.
6.2
Outputs
Breaker Distribution: Up to 5 circuits, maximum 30A per circuit.
Fuse Distribution: Up to 10 circuits, maximum 12A per circuit.
DC 72A.
Alarm Relay Contacts: Form C, 1A max at 30VDC.
6.3
Protection
Supply Input:
Output Distribution:
Bulk DC Bus:
Each rectifier is individual fused internally.
Magnetic Breaker.
According to installed circuit breakers or fuses.
Rectifier Current Limiting / Battery Breaker.
Manual No. X75M-5
7
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
6.4
Safety
The X75 is compliant with UL60950-1, EN60950-1, CSA22.2-60950-1 and all other derivatives of the core IEC60950-1 standard when installed correctly within a restricted access environment.
The X75 is CE marked to indicate conformance to the European Union’s Low Voltage and EMC
Directive.
6.5
EMC
The X75 complies with the following Norms when correctly installed.
Conducted Emissions: EN55022, level A
Radiated Emissions: EN55022, level A
ESD:
Radiated Immunity:
EN61000-4-2, level 4, criterion A - 8kV contact, 15kV air.
EN61000-4-3, level 3, criterion A - 10V/m.
Surges (power ports): EN61000-4-5, level 1, criterion A - 500V
6.6
Environmental
Operating Temperature Range: -20°C to 50°C
Storage Temperature Range: -40°C to + 85°C
Humidity: 0% to 95% Non-Condensing
6.7
Physical Specification
Dimensions: 1.72H (43.7) x 17.2W(437) x 14.47D(368)
Rack Width: 19 or 23 Inches (Mounting brackets are dual purpose).
Manual No. X75M-5
8
08/12 X75-man
7.0
FRONT PANEL DESCRIPTION
X75 SERIES
INSTALLATION & OPERATING MANUAL
7 LED INDICATORS
STATUS & ALARM
HOT-SWAP RECTIFIER MODULES
DC DISTRIBUTION
1-5 CIRCUIT BREAKERS
OR
10-WAY GMT FUSE BLOCK
(breaker option shown)
Figure 2 - Front Panel with Bezel Removed
7.1
7.2
7.3
From left to right there are 3 rectifier slots. Each slot can accept one rectifier from the Sigma
Series rated up to 650W output power. Only identical model rectifiers of appropriate output voltage may be installed at the same time. For example, a nominal -48V system may contain between 1 and 3 model RSG48/10-Z OR between 1 and 3 model RSG48/12-Z but not a mixture of the two types.
To the right of the rectifiers are 7 LED indicators which display various status and alarm conditions. These are described in more detail in section 9.
On the right hand side of the unit is the DC distribution section which may contain between 1 and 5 circuit breakers OR a 10-way GMT fuse block.
Manual No. X75M-5
9
08/12 X75-man
8.0
REAR PANEL DESCRIPTION
BATTERY
BREAKER
X75 SERIES
INSTALLATION & OPERATING MANUAL
BUS BARS
VB -V +V
J3
ETHERNET
J2
AUX. INPUTS
DC LOAD TERMINALS AC INPUTS
IEC60320 C14 X 3
RS232
CONSOLE
J4
RELAY ALARMS
TEMP. COMP.
J1
EXPANSION
INTERFACE
Figure 3a - Rear Panel – Base Unit
-V +V
BUS BARS
Figure 3b - Rear Panel – Expansion Unit
J1
EXPANSION
INTERFACE
AC INPUTS
IEC60320 C14 X 3
8.1
8.2
8.3
On the left hand side of the Base Unit, viewed from the rear, is a bank of screw terminal blocks for the DC load connections.
When the Circuit Breaker option has been specified two connections are provided for Load and Return for each breaker position.
When the GMT Fuse option has been specified one connection is provided for Load and
Return for each fuse position.
To the right of the Load connection terminals is the Battery Breaker. This is a magnetic circuit breaker rated at 100A. This circuit breaker provides two functions.
8.2.1
In the first instance it enables the user to disconnect the batteries from the system for maintenance, replacement or other purposed.
8.2.2
The second function is to protect the batteries against excessive charge or discharge currents.
To the right and below the battery breaker there is a 9-way D sub connector marked RS232.
This connector provides a ‘console’ only function to UNIPOWER Telecom service personnel and should not be connected to for any other purpose.
Manual No. X75M-5
10
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
8.4
8.5
8.6
In the centre of the unit are three bus bar terminals.
8.4.1
To the left side is the VB or BAT terminal. This is connected to the ‘hot’ or ‘feed’ side of the battery.
8.4.2
In the middle is the –V or –VO terminal. This is the ‘negative’ output of the rectifier bus.
8.4.3
To the right side is the +V or +VO terminal. This is the ‘positive’ output of the rectifier bus.
8.4.4
Battery connection for -48VDC systems is as follows:
+Ve battery terminal connects to the +V terminal.
–Ve battery terminal connects to the VB terminal.
Note that in -48VDC systems the +V terminal is internally connected to chassis ground.
8.4.5
Batter connection for +24VDC and +12VDC systems is as follows:
+Ve battery terminal connects to the VB terminal.
-Ve battery terminal connects to the –V terminal.
Note that in +24VDC and +12VDC systems the -V terminal is internally connected to chassis ground.
8.4.6
When the system is required to provide a bulk feed output without using the internal distribution the +V and –V terminals are used to provide this feed to the load.
8.4.7
When an expansion shelf is used to increase the overall capacity of the system the
+V and –V terminals of the expansion unit should be bussed together with the +V and –V terminals of the system unit respectively using the supplied link bars.
Immediately to the right of the bus bar terminals is a bank of 15 Spring Clamp Terminals designated J4. These terminals provide connections for the battery temperature compensation probe and the relay alarm outputs. They are described in detail in section 10.
Next to J4 is a 25-way Sub-miniature D-Type connector, designated J1, which is used to connect various signal and control lines between a base unit and an expansion shelf.
Expansion shelves are supplied with a short cable to link the J1 connectors between the base unit and the expansion shelf.
Manual No. X75M-5
11
08/12 X75-man
8.7
8.8
8.9
X75 SERIES
INSTALLATION & OPERATING MANUAL
Above J1 is a 4-way Phoenix connector type MCO.5/4-G-2.5.
This connector, designated J2, provides terminations for the auxiliary digital alarm input and the optional external temperature probe. The pinout for this connector is described in section
10.
To the left of J2 is the Ethernet TCP/IP connector (J3). This connection uses a standard RJ45
Network connector. It is used to connect either to a Local Area Network or directly to a PC with network connection, the latter using a standard cross-over cable.
The primary means of setting up the X75 unit is via it’s built-in WEB server, which is accessed using a WEB browser via this Ethernet TCP/IP connection.
At the right hand side of the base unit and also the expansion shelf are three IEC60320 C14 inlets. These provide individual AC input feeds to each of the 3 rectifier slots.
The X75 employs UNIPOWER Telecom Sigma Series rectifiers which operate from a
Universal 85-264VAC 50-60Hz single phase supply. The system is designed so that various single and 3-phase supply connections can be made. For example, in the U.S. it might be desirable to connect each rectifier between two 120VAC phases; in which case each rectifier is operating at 208VAC.
IMPORTANT NOTE: DO NOT CONNECT THE UNIT SUCH THAT MORE THAN 264VAC
WILL BE PRESENT BETWEEN THE LIVE AND NEUTRAL TERMINALS OF ANY ONE
INLET SOCKET. SUCH CONNECTION MAY BE HAZARDOUS, WILL DAMAGE THE UNIT
AND INVALIDATE THE WARRANTY.
Manual No. X75M-5
12
08/12 X75-man
9.0
LED INDICATORS
X75 SERIES
INSTALLATION & OPERATING MANUAL
Figure 4 - LED Indicators – viewed with front bezel in place
During normal operation there will be one green LEDs displayed as shown in figure 4 above.
The LED indicators provide visual indication of both status and alarm conditions as described below:
CTR – GREEN
– Indicates that the unit has power and is functioning normally.
MAJA – RED
– Indicates a ‘Major’ (Immediate Response) alarm condition.
MINA – RED
– Indicates a ‘Minor’ (Scheduled response) alarm condition.
ACFA – RED
– Indicates an AC supply failure.
RFA – RED
– Indicates a Rectifier module failure.
OTA – RED
– Indicates that one or more of the monitored temperatures is too high.
OVA – RED
– Indicated that the system Bus Voltage is too high.
Manual No. X75M-5
13
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
10.0
MAKING CONNECTIONS TO THE X75
10.1
DC Load Connections
The DC load distribution connections at the rear left of the unit are clearly marked as follows:
10.1.1
Circuit breaker option.
For each load circuit there are two terminals marked V1, V2, V3, V4 and V5 respectively for the DC ‘feed’ and two marked RTN for the DC ‘return’.
10.1.2
GMT Fuse option.
For each load circuit there is one terminal marked V1 through to V10 respectively for the DC ‘feed’ and one marked RTN for the DC ‘return’.
Note that in the case of -48VDC system the ‘feed’ terminals are at a negative potential with respect to the ‘return’ terminals. In the case of +24VDC and +12VDC systems the ‘feed’ terminals are at a positive potential with respect to the ‘return’ terminals.
When connecting to the DC load terminals it is important to ensure that the cables used are adequately sized to carry the expected load current for the circuit in question.
The maximum current rating for the individual load terminals is 32A, but where long cable runs to the load are to expected care should be taken to avoid unacceptable cable voltage drop; this is most likely occur at currents in excess of 20A if only a single feed and return cable are employed. It is recommended that for circuits where a 20A or greater breaker is fitted pairs of feed and return cables are installed.
10.2
Alarm Relay and Battery Temperature Probe Connections – J4
Connection to the Form-C alarm relay outputs is made through a 15-way spring clamp terminal connector. There are a total of 4 relay outputs with Normally Open, Normally
Closed and Common Contacts available for connection. The individual relays contact sets are fully isolated and may be floated from GROUND by up to 100V. Maximum contact current and voltage are 1A and 30V (DC or AC) respectively.
The alarm relays are designated K1 to K4. K1 and K2 are pre-programmed for MAJOR and
MINOR alarm conditions by default. K3 and K4 are not programmed for any alarm function.
The function of each alarm may be programmed using the
Alarm Configuration
WEB page described later in section 12.
Manual No. X75M-5
14
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
Connection of the supplied battery temperature probe, if required, is made using terminals 1 and 3 of this same spring clamp terminal connector.
1
J4 CONNECTIONS
BATT. TEMP. PROBE -
7
8
9
10
3
4
5
6
11
12
13
14
15
BATT. TEMP. PROBE +
K1 - MAJ ALARM – N/C
K1 - MAJ ALARM – COM
K1 - MAJ ALARM – N/O
K2 - MIN ALARM – N/C
K2 - MIN ALARM – COM
K2 - MIN ALARM – N/O
K3 – FREE ALARM – N/C
K3 – FREE ALARM – COM
K3 – FREE ALARM – N/O
K4 – FREE ALARM – N/C
K4 – FREE ALARM – COM
K4 – FREE ALARM – N/O
Note that terminal 1 is to the left when viewed from the rear of the system.
Figure 5 – Battery Temp. Probe & Alarm Relay Connector Pin-Out
10.3
Ethernet Connection – J3
The X75 is connected to a TCP/IP LAN (Local Area Network) or directly to a PC using connector J3. This is a standard RJ45 network connector allowing connection of any generally available Ethernet cable. Note that if the X75 is to be connected directly to a PC rather than a LAN then a cross-over Ethernet cable will be required.
J3 CONNECTIONS
Pin Function
Figure 6 - Ethernet Connector Pin-Out
Manual No. X75M-5
15
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
10.4
Auxiliary Connections – J2
Auxiliary connector J2 provides connections for an external temperature probe which can be supplied optionally with the system and for a single volt free contact closure input.
NOTE: Any sensor, such as a switch or relay, that is connected to the digital input MUST be galvanically isolated.
This connector is a Phoenix Contact part type MCO.5/4-G-2.5.
The optional temperature probe is identical to the battery temperate probe that is supplied as standard, so there is no risk of mixing the two up on receipt.
J2 CONNECTIONS
Pin Function
1
2
Contact Closure Input
3
4
Ext. Temp. Probe +
Ext. Temp. Probe -
Note that pin 1 is to the right when viewed from the rear of the system
Figure 7 – Auxiliary Connector Pin-Out
10.5
Expansion shelf connector – J1
This connector is used to jumper the necessary signal and control functions for the rectifiers that are installed in an optional expansion shelf back to the base unit. The functions and pin-out are not described in detail as these are internal to the general operation of the unit.
Manual No. X75M-5
16
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
11.0
INSTALLATION
The X75 can be mounted in either 19” or 23” racks by using the supplied brackets. Mount it from the front of the rack using the correct offsets to align with existing rack-mounted equipment. Once mounted in the rack the following connections must be made with the unit switched off.
CAUTION: Re-read the Safety Warnings and Precautions in Section 3. All power should be OFF for the input and output loads before making connections. Connection of the X75 chassis to frame ground should be made first. If the X75 has been turned on before installation connections, it should be turned off and given a 5-minute waiting period for all internal energy storage capacitors to be discharged.
11.1
Input AC Power Connection
A 3-wire AC power line should be connected to the input IEC connectors but not plugged into the AC power source. The line, neutral and ground connections should be carefully observed when making the AC connections. The AC line cord should be sized to safely carry
15 amperes AC each, minimum.
11.2
Checking Outputs
Turn all output circuit breakers to the OFF position and/or remove all fuses from the GMT fuse-holder. With no loads connected and without the battery connected, plug in or connect the AC input cords one at a time to the AC power source. Be sure to use the correct AC voltage for the rectifier inputs. Using a volt meter measure the DC voltage reading across the
–VO and +VO bus bars at the rear of the unit. The voltage should be approximately 54.4,
27.2, or 13.6VDC (depending on model), which is the factory setting. One by one, turn each output circuit breaker to the ON position and/or insert a GMT fuse and measure the DC voltage across the corresponding output terminals. The voltage should again read approximately 54.4, 27.2, or 13.6 volts. After each output is measured, turn OFF that circuit breaker and/or remove the GMT fuse and turn ON and/or insert a fuse in the next one. After measuring the last circuit, turn off that breaker and/or remove the GMT fuse and make sure that all output breakers are in the OFF position and/or all fuses are removed. Next, unplug or disconnect the AC input power source. Before touching any terminals wait 5 minutes for the internal storage capacitors to discharge.
11.3
Controller Section Operation and Settings
At this point, before the final installation connections, read section 12 covering Controller setup. Next, make any required signal connections, controller adjustments, temperature compensation adjustment and alarm enabling settings.
WARNING: Remember to take precautions each time the system is turned on and also when connecting or disconnecting the battery. Remember that the battery presents an energy hazard at its terminals. Also remember to allow 5 minutes for internal capacitors to discharge after disconnecting the AC input power and the battery.
Manual No. X75M-5
17
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
11.4
Connection to Loads
With input AC power unplugged, the battery disconnected and no other power sources connected to the loads, make sure that all load circuit breakers are set to the OFF position and/or all GMT fuses are removed. Connect load wires to each set of output terminals, one at a time. Note that the front panel breaker and fuse numbers directly correspond to the output terminal numbers. Be sure to connect the polarities correctly.
11.5
Connection to Battery
WARNING: Improper polarity of the battery connection may damage the power system. Take precautions when installing the battery and note that the battery cables are “hot” (live) and present an energy hazard.
With AC input unplugged, remove the three rectifier modules from the system chassis. Make sure all load circuit breakers are in the OFF position and/or all GMT fuses removed. Set the battery circuit breaker to the OFF position. Carefully connect the battery cables to the DIN-
Rail battery terminals shown in Figure 2 while observing the correct polarity.
Note that until AC power is applied to the system the controller will not activate the LVD contactor.
11.6
System Turn-On
Perform the following operations:
1.
Set the battery and all load circuit breakers to the OFF position.
For systems with GMT fuse distribution remove all fuses if already installed.
2.
Plug in the rectifier modules.
3.
Connect the AC power cables to the AC source.
4.
Check that the green LED on the front panel has lit. After approximately 20 seconds for initialization the MAJA LED at least will light. The RFA LED may also light, dependent on the number of rectifiers installed at the time.
5.
Set the battery circuit breaker to the ON position. Then set the load breakers to the
ON position and/or insert the GMT fuses.
After approximately 5 seconds the status of various alarm LEDs will change, dependent on the number of rectifiers installed.
Using the WEB browser interface described in section 12 it is now possible to check overall system status for correct operation.
Manual No. X75M-5
18
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
In particular, it is important to ensure that the load current reading does not exceed the maximum capacity of the installed rectifiers or, where N+1 operation is required, the maximum capacity of one less than the total number of rectifiers installed. Note also, that the system should have been sized so that a proportion of the available rectifier capacity is allocated for battery charging. Where N+1 redundant operation is used the additional ‘spare’ rectifier will normally provide this current.
IMPORTANT NOTES: a) It is not possible to start the system by connecting the batteries alone. b) During the 30 seconds initialization period the system bus voltage will be at the factory preset level of the rectifiers. Nominally 54.4V, 27.2V or 13.6V depending on system voltage. After this period the internal controller will lower the output voltage by approximately 15% in order to limit current flowing to the batteries. During a following period of approximately 30 minutes the controller will ramp the system voltage up to the correct float voltage as determined by the temperature compensation algorithm.
Manual No. X75M-5
19
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.0
USING THE CONTROLLER WEB BROWSER INTERFACE
The X75 is provided with a built-in WEB server which can be accessed through the TCP/IP Ethernet port using a WEB browser.
The WEB server employs Java Applets to continually scan system parameters and update the WEB page data. These same Applets return programming data to the X75 when set-up changes need to be made.
The WEB server communicates with the browser using HTTP on IP Port 80 and the Java Applets on IP Port
8888. If any firewall or proxies are configured on the LAN that the X75 is connected to it is important to ensure that these ports are open, otherwise the X75 will not respond.
Note also that a genuine Java engine must be installed on the browser PC. The latest version can be downloaded and installed for free from
www.java.com
.
The X75 has various network programming capabilities which allow it to be connected to almost any configuration of IP network.
The default network settings that the X75 is shipped with are:
IP Address
Subnet Mask
– 192.168.0.200
– 255.255.255.0
All pages served by the X75 built-in WEB server consist of two frames; a ‘navigation’ frame on the left hand side and an ‘information/programming’ frame which occupies the majority of the browser window.
The buttons in the ‘navigation’ frame can be used at all times to jump between the various pages. Clicking on the UNIPOWER Telecom logo at the top will navigate directly to the UNIPOWER Telecom WEB site www.unipowertelecom.com
.
Each of the blocks of information in the ‘information/programming’ frame is a Java applet. In some cases these applets simply collect information from the X75 and presents it on-screen, in other cases the applets contain data entry fields for uploading programming information to the unit.
Note that a PC screen resolution of 1024 x 768 or higher is recommended to avoid excessive amounts of page scrolling.
The following sections describe the various WEB pages that can be viewed with the browser and give details of programming parameters that may be entered and sent to the unit.
IMPORTANT NOTE: The screenshots shown throughout this section are ‘typical’ examples. The exact data content will differ dependent on the system voltage and whether alterations from the default settings have been made. Settings can be returned to the factory defaults at any time by clicking on the
‘DEFAULT’ then ‘UPLOAD’ buttons on the relevant setup page. This action requires the level 1 password.
Manual No. X75M-5
20
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.1
Controller Status
When the X75 is first accessed using a WEB browser the
Controller Status
page shown below is downloaded.
Figure 8 - Controller Status WEB Page (typical)
This page presents two blocks of information. The top block displays a number of system status parameters by mimicking a block of LEDs. 7 of these functions, described earlier, are displayed on the front panel of the system unit.
The bottom block of information shows the following ‘live’ data:
Bus Voltage
Battery Current
Rectifier Current
Load Current
Battery Temperature
External Temperature
Controller Temperature
No. of Rectifiers Installed (includes all rectifiers that are present regardless of status)
If the battery or external temperature probes are not connected a reading of 25ºC will be displayed by default.
Manual No. X75M-5
21
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.2
Rectifier Status
The
Rectifier Status
page presents detailed information about an individual rectifier module. Two types of data are included; ‘live’ status information and ‘static’ inventory information. In addition the controller returns the I²C address as confirmation that the unit has responded.
Figure 9 - Rectifier Status WEB Page (typical)
In order to obtain status information about a particular rectifier module it is necessary first to dial in the required rectifier address according to the table below and then click on the SELECT button to confirm the request.
RECTIFIER I²C ADDRESSING
Rectifier
Position
Base
System
Expander
Shelf
Address Address
Left 0
Center 1
4
5
Right 2 6
Figure 10 - Rectifier I²C Addressing
A few seconds after the SELECT button has been pressed the X75 will respond and the status and inventory information will be updated as follows:
‘Live’ data is presented in the form of 8 coloured indicator blocks to the left. A green block indicates a ‘good’ condition and a red block indicates a ‘bad’ condition. In addition the unit’s internal temperature is presented on the right.
Manual No. X75M-5
22
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
Note that Sigma Series rectifiers include a single fan only and that two of the status indicator blocks will always be greyed out.
‘Inventory’ data, presented on the right below the temperature measurement includes, among other items, rectifier model number Serial Number and Revision Number.
12.2.1
Rectifier Inhibit (Shutdown)
The X75 includes a facility that enables the user to manually inhibit or shutdown individual rectifiers. This may be desirable when a particular rectifier is to be removed from the system for maintenance, although all UNIPOWER rectifiers are Hot-Swap, or for some other reason.
To inhibit a rectifier first dial in the I²C address of the required unit and the click on
SHUTDOWN.
To restart a rectifier that has been inhibited dial in the I²C address of the required unit and the click on RUN.
Note that any rectifiers which have been inhibited will remain in this state until they are either restarted using the above method or the AC power is recycled.
Manual No. X75M-5
23
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.3
Controller Factory Calibration
The primary purpose of the
Controller Factory Calibration
page is to allow UNIPOWER Telecom to setup a range of necessary calibration values to ensure correct operation.
When this page is requested and the Java applet has loaded a dialog requesting the Level 2 Passcode is presented. Once the passcode has been entered click ENTER and the page will then be updated with current values after a few seconds.
Figure 11 - Controller Factory Calibration WEB Page (typical)
NOTE: It should not normally be necessary for changes to be made to this page.
Manual No. X75M-5
24
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.4
Controller Site Installation
The
Controller Site Installation
page provides the system integrator or installer facilities for setting up the main system parameters.
Figure 12 - Controller Site Installation WEB Page (typical)
To retrieve the currently programmed settings from the X75 click on REFRESH. After a few seconds the values will be displayed.
To reprogram to the factory default settings click on DEFAULT. After a few seconds the default values will be displayed.
To setup this page for a new configuration type in or select each new entry required and click on
ENTER to confirm that entry. Once all required entries have been made click on UPLOAD. To confirm the new settings have been programmed into the X75 click on REFRESH. Check the entries after a few seconds to make sure they are still as required.
Each setting that can be made on this page is described below in detail:
SITE DETAILS
Site Name
– Optional setting which may be used to identify the location of the unit.
Serial Number
– Displays the unit serial number. (Cannot be changed.)
Manual No. X75M-5
25
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
SYSTEM VOLTAGES
System
– Dial in the Nominal system voltage; 12V, 24V or 48V.
Float – Enter the float voltage in accordance with the specifications of the batteries that are being employed with the system.
Equalize – Enter the equalization voltage in accordance with the specifications of the batteries that are being employed with the system.
Equ Time – Enter the desired time that the system should remain in equalize mode in accordance with the specifications of the batteries that are being employed with the system.
SYSTEM SHUNTS
Rect Shunt Amps – This is the 50mV Full-Scale rating for the internal shunt that is used to measure the total rectifier current. THIS SETTING SHOULD NOT BE CHANGED.
Load Shunt Amps – This is the 50mV Full-Scale rating for the shunt that is used to measure the total load current. THIS SETTING SHOULD NOT BE CHANGED.
LVD SETTINGS
LVD1 Off – Enter the voltage at which the LVD1 contactor will open during a battery discharge.
The factory default setting is that recommended for most sealed lead acid batteries.
LVD1 On – Enter the voltage at which the LVD1 contactor will re-connect once the rectifiers are running. The factory default setting is that recommended for most sealed lead acid batteries.
LVD2 Off & LVD2 On – These settings are not required for the X75.
TEMPERATURE COMPENSATION
Temp Comp (mV/°C/Cell) – Enter the temperature compensation slope value in accordance with the specifications of the batteries that are being employed with the system.
Number Of Cells – Enter the total number of battery cells.
Max Temp (°C) – Enter the maximum temperature at which temperature compensation may be applied. Above this temperature the X75 will cease to apply further compensation to the float voltage.
Min Temp (°C) – Enter the minimum temperature at which temperature compensation may be applied. Below this temperature the X75 will cease to apply further compensation to the float voltage.
Manual No. X75M-5
26
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
VOLTAGE ALARMS
OVA – Enter the voltage above which the Over-Voltage Alarm will be triggered.
UVA – Enter the voltage below which the Under-Voltage Alarm will be triggered.
EVA – Enter the voltage below which the End-Voltage Alarm will be triggered.
TEMPERATURE ALARMS
Battery OT – Enter the temperature at which the battery Over-Temperature alarm will be triggered.
External OT – Enter the temperature at which the external Over-Temperature alarm will be triggered.
Controller OT – Enter the temperature at which the controller’s internal Over-Temperature alarm will be triggered. THIS SETTING SHOULD NOT NORMALLY BE CHANGED.
DC WALK-IN
ON (Default) – Causes the controller to slowly ramp up the DC rectifier voltage when AC is applied.
The voltage will rise from approximately 45V (for 48V systems), 22V (for 24V systems) and 11V
(for 12V systems) up to the float voltage. The ramp-up time is several minutes and cannot be adjusted. The purpose of this feature is to avoid initially large battery charging currents.
OFF – Causes the controller to program all rectifiers to the float voltage almost immediately after AC is applied. Battery charging current will only be limited by the current limit of the rectifiers.”
AC MONITOR
This facility is not available in the X75 and is not accessible.
RECTIFIER CONFIGURATION
Rectifier Type – This selects the type of rectifier installed in the system from the drop-down list.
In the X75 this is factory preset to RPCM/P and SHOULD NOT BE CHANGED.
Minimum Rectifiers – Enter the minimum number of rectifiers that is required to provide sufficient current to the load and to simultaneously re-charge the batteries from a fully discharged state in the desired time according to the specification of the batteries being employed with the system.
CURRENT LIMIT
Select the appropriate button for ENABLE or DISABLE as required.
Battery Charge Limit – When enabled enter the maximum desired battery charge current.
Using this setting the X75 will intelligently control the rectifier float voltage such that the battery charge current never exceeds the set value.
Manual No. X75M-5
27
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.5
Alarm Configuration
The
Alarm Configuration
page presents a matrix of tick boxes which are used to programme how certain system conditions affect the actions of the alarm relays and front panel LEDs. It is also used to define the ‘good’ condition (polarity) of the auxiliary digital input. The screen shot below shows the factory default settings.
Figure 13 - Alarm Configuration WEB Page (typical)
12.5.1
Alarm Matrix Programming
K1 MAJ – An item ticked in this column will enable the MAJOR alarm relay when active. Any item that is considered to represent a condition which should be acted upon immediately should be ticked.
K2 MIN – An item checked in this column will enable the MINOR alarm relay when active. Any item that is considered to represent a condition that can wait for action at a later time should be ticked.
K3 & K4 – A ticked item in any of these columns will activate the relevant auxiliary alarm relay.
Note that K5 – K8 are not installed in the X75 system.
Manual No. X75M-5
28
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
MAJ LED – An item ticked in this column will enable the MAJOR alarm LED when active.
MIN LED – An item ticked in this column will enable the MINOR alarm LED when active.
ACF LED – An item ticked in the column will activate the ACF LED when the condition occurs.
RFA LED – An item ticked in the column will activate the RFA LED when the condition occurs.
OTA LED – An item ticked in the column will activate the OTA LED when the condition occurs.
OVA LED – An item ticked in the column will activate the OVA LED when the condition occurs.
Note: The following LEDs are not fitted on the X75 but the function will show a valid condition on the controller status WEB page.
UVA LED – An item ticked in the column will activate the UVA LED when the condition occurs.
EVA LED – An item ticked in the column will activate the EVA LED when the condition occurs.
LVD LED – An item ticked in the column will activate the LVD LED when the condition occurs.
FUSE LED – An item ticked in the column will activate the FUSE LED when the condition occurs.
CHKB LED – An item ticked in the column will activate the CHKB LED when the condition occurs.
COM LED – An item ticked in the column will activate the COM LED when the condition occurs.
FLT LED – An item ticked in the column will activate the FLT LED when the condition occurs.
EQU LED – An item ticked in the column will activate the EQU LED when the condition occurs.
BTST LED – An item ticked in the column will activate the BTST LED when the condition occurs.
Manual No. X75M-5
29
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
EMAIL – When the email reporting feature is activated ticking an item in this column results in an email message being sent immediately.
12.5.2
Aux. Input Polarities
By selecting the NO or NC radio buttons for the AUX 3 input the ‘good’ condition can be set to either Normally Open or Normally Closed respectively.
NOTE THAT THE LVD AND FUSE SETTINGS ARE PRESET AND SHOULD
NOT BE CHANGED.
AUX 4 to AUX 8 are not fitted on the X75 system.
Once the required alarm and input polarity settings have been selected it is necessary to click on the
UPLOAD button to store the new settings in the unit’s memory. To confirm that the new settings have been received and programmed click on the REFRESH button and wait a few seconds for the unit to respond. If no changes are apparent then the unit has been successfully reprogrammed.
To return the unit to the factory default settings click on the DEFAULT button.
Manual No. X75M-5
30
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.6
Comms
Clicking on the
Comms
button loads to
Controller Network Settings
page. This page is used to setup the Ethernet and E-Mail communications settings.
Figure 14 - Controller Network Settings (typical)
12.6.1
Ethernet Settings
12.6.1.1
IP Address
This setting defines the IP Address for the controller.
The default factory setting of 192.168.0.200 is a designated ‘private’ IP Address commonly used in IP based local area networks behind proxies, NAT routers or network bridges.
To enter a new IP address use the up/down arrows to dial in the required numbers or type them directly into the boxes as required. It is important to press the ENTER key on completion.
Manual No. X75M-5
31
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.6.1.2
Subnet Mask
This setting defines the Subnet Mask associated with the above IP Address.
The default factory setting is 255.255.255.0.
To alter the Subnet mask use the up/down arrows to dial in the required numbers or type them directly into the boxes as required. It is important to press the ENTER key on completion.
12.6.1.3
Default Gateway
This setting defines the Network Gateway to which the controller will route all IP traffic that is destined for any location outside the LAN to which it is connected.
This setting would normally be the address for the Proxy, NAT Router or Bridge that routes network traffic to the Internet or other WAN segments.
The default factory setting is 0.0.0.0, i.e. all traffic is retained within the LAN environment.
To alter the Default Gateway use the up/down arrows to dial in the required numbers or type them directly into the boxes as required. It is important to press the ENTER key on completion.
12.6.2
E-Mail Settings
12.6.2.1
Mail Host
This setting is the IP Address of the E-Mail Server that will route SMTP messages sent by the controller.
To set this address use the up/down arrows to dial in the required numbers or type them directly into the boxes as required. It is important to press the ENTER key on completion.
12.6.2.2
Mail Service
Select the ETHERNET radio button to switch on the E-Mail alarm facility, select the
DISABLE radio button to switch it off.
Manual No. X75M-5
32
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.6.2.3
E-Mail 1, 2 & 3
The X75 is able to send alarm messages to up to three unique email addresses.
Type in the desired address in the E-Mail 1 box using the normal name@domain format and press the ENTER key to confirm.
Repeat as required for E-Mail 2 and E-Mail 3.
12.6.2.4
Controller E-Mail
The X75 requires an email address of its own to send email alarm messages. Note, however, that it is unable to receive messages sent to this address.
Type in the desired address in the Controller E-Mail box using the normal name@domain format and press the ENTER key to confirm.
Once all desired Ethernet and E-Mail settings have been entered click on the UPLOAD button to programme them into the controller. To confirm successful programming on these setting click on the REFRESH button, wait a few seconds for the unit to respond and then ensure that the desired settings are returned by the unit.
CAUTION:
Once a new IP Address has been uploaded it will be necessary to redirect the browser to this new address in order to access the WEB pages.
Manual No. X75M-5
33
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.7
Alarm Log
The
Alarm Log
page can be used to view a history of alarm and other conditions that have occurred.
When this page is first loaded the alarm log window will be empty.
To load the current log file click on REFRESH. After a few seconds the log data will be loaded.
To clear the log click on the CLEAR button, the refresh the page click on the REFRESH button.
Figure 15 - Controller Alarm Log WEB Page (typical)
Manual No. X75M-5
34
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.8
Control
The
Controller Control Panel
page is used to remotely switch the system between FLOAT and
EQUALIZE modes. This page displays various system status functions enabling the operator to monitor these system parameters from a remote location.
To set the system to equalize mode click on the EQUALIZE button. After a few seconds the unit will respond by switching off the FLT LED indicator and switching on the EQU LED indicator.
To return the system to float mode, click on the FLOAT button. The unit will respond by returning the FLT and EQU LED indicators to their normal state.
Note that if the unit is not returned to float mode manually it will be returned automatically after the pre-programmed time has elapsed.
Figure 16 - Controller Control Panel WEB Page (typical)
Manual No. X75M-5
35
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.9
System
The Controller System Settings page enables a user to alter the controller’s real-time clock date and time settings. New date and time settings can be entered manually or automatically synchronised with a ‘host’ system.
Figure 17 - Controller System Settings WEB Page (typical)
12.9.1
Manual Setting
To enter a new date and/or time manually either use the up/down buttons to dial in the desired settings or type them directly into the required boxes. Press the ENTER key in each case to confirm.
Once the desired settings have been enter click on the SET button to upload them.
12.9.2
Automatic Setting
To synchronise the date and time with the computer being used to access the controller click on the SYNC button to load the new settings from the computer and then click on the SET button to upload them.
To update this page with the controller’s current date and time click on the GET button.
Manual No. X75M-5
36
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.10
SNMP
(Option)
The SNMP Configuration page is used to setup the controller’s SNMP System Information, Alarm
Trap and Agent Information parameters. It also allows the SNMP feature to be activated.
When the SNMP option has not been purchased it is not possible to enter any parameters on this page.
Figure 18 - SNMP Configuration WEB Page (typical)
Note: It is assumed that customers wishing to employ the SNMP features of the X75 will be familiar with the necessary set-up procedure for this page.
As with all other WEB pages described in this manual it is necessary to click on UPLOAD to programme the desired settings and to click on REFRESH to review them.
Clicking on ACTIVATE will have no effect unless the SNMP feature has been purchased and installed in the unit.
The X75 MIB, detailed in Appendix 3 of this manual is available for download from the
UNIPOWER Telecom WEB site: www.unipowertelecom.com
Manual No. X75M-5
37
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
12.11
Help
The Controller Help Page provides a few quick reminder notes. For more detailed help the user is referred to this manual.
Figure 4 - Controller Help WEB Page (typical)
12.12
About
The About UNIPOWER Telecom page provides contact information in case additional technical or other support is required.
Figure 5 - About UNIPOWER Telecom WEB Page (typical)
Manual No. X75M-5
38
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
Appendix 1 – SNMP MIB Information.
The SNMP feature provides status read-out and alarm trapping only. All parameters described in this appendix are therefore read-only.
Refer to the appropriate sections earlier in the main body of this manual for system set-up.
Parameters for UNIPOWER X75 Remote Access Controller MIB
1.
Voltages
Bus Voltage -
Description: Live data giving actual voltage of system bus.
2.
Currents
Battery Current -
Live data giving actual current drawn from or into battery string(s).
Rectifier Current -
Live data giving actual current drawn from rectifier power supply system.
Load Current -
Live data giving actual current delivered to the load.
3.
Temperatures
Battery Temperature -
Live data giving actual temperature of battery string.
External Temperature -
Live data giving actual temperature of external sensor.
Controller Temperature -
Live data giving actual temperature within the controller enclosure.
4.
Rectifier Info
Number of Rectifiers -
Live data giving number of rectifiers detected by the controller.
Manual No. X75M-5
39
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
5.
Auxiliary Inputs
These are all part of one status flag held within the controller.
Digital Input 1 (Low Voltage Disconnect State)
Digital Input 2 (Fuse/Breaker State)
Digital Input 3
Digital Input 4
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
6.
Alarms
These are all part of one alarm status flag held within the controller.
ACFAIL -
Indicates an AC Failure detected by the power supply rectifiers or an external sensor.
MAJOR -
Indicates that a major alarm condition requiring immediate attention has been detected by the controller.
MINOR -
Indicates that a minor alarm condition requiring attention at the next scheduled maintenance has been detected by the controller.
SINGLE RECTIFIER FAILURE (SRFA) -
The controller has detected that a single rectifier has failed
MULTI RECTIFIER FAILURE (MRFA) -
The controller has detected that multiple rectifiers have failed.
OVER TEMPERATURE ALARM (OTA) -
The controller has detected an over temperature condition on battery/external/controller temperature sensor.
OVER VOLTAGE ALARM (OVA) -
The controller has detected an over voltage condition on the bus.
UNDER VOLTAGE ALARM (UVA) -
The controller has detected an under voltage condition on the bus.
END VOLTAGE ALARM (EVA) -
The controller has detected an End Voltage condition, i.e. the batteries are near end of discharge.
LOW VOLTAGE DISCONNECT ALARM (LVD) -
The controller has detected that one of the LVDs is open.
FUSE ALARM -
The controller has detected that a fuse or breaker is open.
Manual No. X75M-5
40
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
CHECK BATTERY (CHKBAT) -
The controller has detected a fault with the battery string(s) either temperature or current related.
COMMUNICATION FAULT (COMM) -
The controller has detected a problem with the internal I²C bus.
7.
Settings
OVER VOLTAGE ALARM SETTING -
Setting for over voltage alarm.
UNDER VOLTAGE ALARM SETTING -
Setting for under voltage alarm.
END VOLTAGE ALARM SETTING -
Setting for end voltage alarm.
LVD1OFF SETTING -
Setting for voltage at the point where LVD1 will be shut off.
LVD1ON SETTING -
Setting for voltage at the point where LVD1 will be turned on.
LVD2OFF SETTING -
Setting for voltage at the point where LVD2 will be shut off.
LVD2ON SETTING -
Setting for voltage at the point where LVD2 will be turned on.
FLOAT VOLTAGE -
Voltage setting for the bus in float mode (modified by temp. compensation).
EQUALIZE VOLTAGE -
Voltage setting for the bus in equalization mode.
NOMINAL SYSTEM VOLTAGE -
The nominal system voltage (12, 24 or 48).
CONTROLLER OVER TEMPERATURE ALARM -
The controller temperature, in degrees Celsius, above which an over temperature alarm will activate.
BATTERY OVER TEMPERATURE ALARM -
The battery temperature, in degrees Celsius, above which an over temperature alarm will activate.
EXTERNAL OVER TEMPERATURE ALARM -
The external temperature, in degrees Celsius, above which an over temperature alarm will activate.
TEMPERATURE COMPENSATION SLOPE -
The parameter applied, in millivolts/°C/cell, to the float voltage to achieve temperature compensation.
TEMPERATURE COMPENSATION MAX TEMPERATURE -
The temperature above which no further temperature compensation will be applied.
TEMPERATURE COMPENSATION MIN TEMPERATURE -
The temperature below which no further temperature compensation will be applied.
Manual No. X75M-5
41
08/12 X75-man
X75 SERIES
INSTALLATION & OPERATING MANUAL
8.
Identification
SITE NAME -
Holds the name of the site/system.
SERIAL NUMBER -
Holds the serial number of the site/system.
9.
SNMP Traps
The X75 will issue a trap if any of the alarm conditions mentioned above are activated.
A trap will also be issued when an alarm condition is cleared.
To obtain a copy of the latest X75 MIB download it from: http://www.unipowerco.com/operating-manuals or contact one of our sales offices.
Manual No. X75M-5
42
08/12 X75-man
Appendix 2 - REVISION HISTORY
Rev.
#
Date Detail
X75 SERIES
INSTALLATION & OPERATING MANUAL
Page
2
3
4
12/06/06 Correction to Input Supply Current specification.
Section 6.4 – Wording altered for clarification.
Section 10.4 – Wording altered for clarification, table corrected.
Section 11.4 – Wording altered for clarification.
Figure 11 – Screen grab changed to reflect standard X75 setup.
Figure 13 – Screen grab changed to reflect standard X75 setup.
05/14/07 Figure 3a – J2 & J4 designation corrected.
Figure 13 – Screen grab changed to correct rectifier thermal & fan alarm setups.
URL to MIB files changed.
07/26/07 Figure 3a – Bus Bar designations corrected.
Section 8.4 – Wording altered to clarify connection arrangements.
Section 11.6 – Wording altered to clarify start-up sequence.
Section 12 – Note added relating to content of screen images and
‘typical’ added to titles for all screenshot Figures.
Add DC Walk-in.
Update WEB address.
18
23
27
7
8
16
10
11
18
20-38
10
27
41
21
22
24
25
28
34-38
27
42
Manual No. X75M-5
43
08/12 X75-man
1RU HIGH 48V, 24V and 12V
INTEGRATED DC POWER SYSTEMS
GRAVITAS X75 BASE SYSTEM
LVD2006/95/EC
KEY FEATURES
1RU High Base System
1RU High Expander Shelf
Remote Monitoring & Control
Fully Integrated System
Hot-Swap Rectifier Modules
Up to 72A at -54.4VDC
Up to 75A at +27.2VDC
Up to 75A at +13.6VDC
Wide Range AC Input
Up to 10 DC Load Circuits
Quick and Easy Installation
SAFETY STANDARDS
UL60950-1
CSA22.2 No. 60950-1
EN60950-1
TWO-YEAR WARRANTY
DESCRIPTION
Gravitas X75 is an ultra-compact, integrated DC power system.
The base system is a 1RU shelf holding up to three hot-swap rectifier modules. This system produces up to 1958 watts output at -54.4, +27.2 or +13.6VDC. It can also be operated as a 2+1 redundant system with up to 1305 watts output. The expanded system consists of a base shelf plus an expander shelf with a 2RU total height. This system holds up to six rectifier modules with up to 3916 watts output; it can be operated as a 5+1 redundant system with up to 3264 watts output. Each rectifier module is cooled by a fan that operates at a speed which is a function of load and temperature.
There are up to five circuit-breaker protected DC outputs or up to 10 GMT fuse protected outputs on the base system. A battery string breaker and a low-voltage battery disconnect are standard features. The expander shelf comes with a ribbon cable and connectors to link the signals between the two units at their rear panels. It also comes with bus bar links to parallel the rectifier output bus bars.
The system can also be operated as a battery backup, single feed power system (without load circuit breakers or fuses).
The remote access controller monitors the system parameters and has alarms for system failures. There are six red LED alarms which indicate a failure: Major Alarm, Minor Alarm, Rectifier
Alarm, AC Input Alarm, Overtemperature Alarm and Overvoltage
Alarm. A green LED indicates that the controller is operating. Four
Form C relay outputs give alarms: Major Alarm, Minor Alarm,
Rectifier Alarm and AC Input Alarm. The controller is programmed by means of a remote PC webpage display. Communication is by Ethernet LAN with an SNMP (Simple Network Management
Protocol) alarm option. It also has provision for temperature compensated charging of an external battery using a supplied
TC probe.
www.unipowerco.com
GRAVITAS X75 SUMMARY FEATURES
-48, +24, or +12VDC Rectifiers
Hot-Swap Rectifiers Modules
Power Factor Corrected
Class B EMI Input Filter
Base and Expander Shelves
N+1 Redundant Operation
Up to 10 DC Load Circuits
Circuit Breakers or GMT Fuses
Battery String Breaker
LV Battery Disconnect
Remote Monitoring & Control
Quick, Easy Installation
19 or 23-Inch Rack Mounting
SNMP Alarm Option
SYSTEM
CAPABILITY
System Voltage
System Max. Current
System Current, N+1 Redundant
No. of Rectifiers, Max.
Battery String Breaker
Low Voltage Disconnect
Total No. DC Loads, Max.
Option A - miniature breakers
Option B - GMT fuses
Controller Features
Alarm Outputs
External Digital Inputs
Temp. Compensation
Communications
Ethernet TCP/IP
SNMP
Shelf Height
Mounting Width, Inches
GRAVITAS X75 CAPABILITY GUIDE
SYSTEM CAPABILITY
X75-48
BASE
SYSTEM
-54.4VDC
36.0A
24.0A
3
EXPANDED
SYSTEM
-54.4VDC
72.0A
60.0A
6
X75-24
BASE
SYSTEM
+27.2VDC
55.2A
36.8A
3
EXPANDED
SYSTEM
+27.2VDC
75.0A
73.5A
5
Standard
Standard
10
1-30A x 5
0.5A-12A x 10
4
1
Standard
BASE
SYSTEM
+13.6VDC
75.0A
66.0A
3
X75-12
EXPANDED
SYSTEM
NOT
AVAILABLE
Standard
Optional
1RU, Base Shelf and Expansion Shelf
19 or 23 (universal reversible mounting brackets)
Notes:
1. The expander shelf allows up to 3 additional rectifier modules to be connected to the rectifier bus for additional power capability.
The rectifiers are paralleled to the system bus via bus bars and expansion interface connections.
2. For applications not requiring battery support consult UNIPOWER sales office about using Front-End power modules instead of rectifier modules.
MODULE
MODEL NO.
RSJ48/12-Z
RSG48/10-Z
RSF48/7-Z
RSG24/18-Z
RSF24/13-Z
RSG12/33-Z
RSF12/22-Z
RECTIFIER MODULES vs. SYSTEM CAPACITIES
OUTPUT
VDC
-54.4VDC
-54.4VDC
-54.4VDC
+27.2VDC
+27.2VDC
+13.6VDC
+13.6VDC
OUTPUT
AMPS
12.0
10.1
7.4
18.4
12.9
33.0
22.1
NO. SYST.
MODULES
MAX. SYST.
AMPS
NO. N+1
MODULES
N+1 SYST.
AMPS
BASE EXP. BASE EXP. BASE EXP. BASE EXP.
3
3
3
3
3
3
3
6
6
6
5
5
36.0
30.3
22.2
55.2
38.7
75.0
66.3
72.0
60.6
44.4
75.0
75.0
2+1
2+1
2+1
2+1
2+1
2+1
2+1
5+1
5+1
5+1
4+1
4+1
24.0
20.2
14.8
36.8
25.8
66.0
44.2
60.0
50.5
37.0
73.6
51.6
DIV. OF UNIPOWER LLC • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • Tel: 954-346-2442 • Fax: 954-340-7901 • [email protected]
UN POWER EUROPE • Parkland Business Centre, Chartwell Road, Lancing, BN15 8UE, ENGLAND • Tel: +44(0)1903 768200 • Fax: +44(0)1903 764540 • sales-europe@unipowerco com
RECTIFIER MODULE SPECIFICATIONS
INPUT
Voltage Range _________________________ 85-264VAC
Power Factor ________________________________ 0.99
Total Harmonic Distortion, Max. __________________ 5%
Frequency ______________________________ 47-63Hz
Inrush Current Limiting ____________________ 30A Peak
EMI Filter, Conducted _______ FCC20780 pt. 15J Curve B
________________________________EN55022 Curve B
Input Current, max.
RSJ _____________ _____ 3.2A/230VAC, 6.2A/120VAC
RSG_____________ _____ 2.7A/230VAC, 5.2A/120VAC
RSF_____________ _____ 2.0A/230VAC, 3.8A/120VAC
Input Immunity, Conducted
Fast Transients, Line-Line _ ±2kV (EN61000-4-4 Level 3)
Surges, Line-Line _______ ±2kV (EN61000-4-5 Level 3)
Surges, Line-Ground _____ ±4kV (EN61000-4-5 Level 4)
Total Regulation, Max. _________________________ 2%
Holdup Time _____________________________ 10msec.
Overvoltage Protection, 48V Nominal _____________ 58V
24V Nominal _____________ 29V
12V Nominal ___________ 14.5V
Filtering: Wideband Noise, 20Mhz BW, P-P _______ 1.0%
Voice Band Noise ________________________ <32dBrnC
Current Limit ____________________105% Rated Current
Efficiency ________________________________ 85-90%
SAFETY STANDARDS
UL 60950-1, CSA22.2-60950-1, EN60950-1
STATUS INDICATOR
DC Good _____________________________ Green LED
OUTPUT
Current & Voltage _________________________ see table
Voltage Adjustment Range, 48V Nominal _____45-58VDC
24V Nominal _____22-29VDC
12V Nominal ___ 11-14.5VDC
ENVIRONMENTAL
Operating Temp. Range _______________ -20
0
C to +70
0
C
Output Current Derating _________ 2.5%/
0
C, 50
0
C to 70
0
C
Storage Temp. Range ________________-40
0
C to + 85
0
C
Humidity _______________ 0% to 95%, Non-Condensing
ESD _________Bellcore GR-1089-Core and EN61000-4-2
Cooling ______________________________ Internal Fan
X75 BASE SYSTEM REAR VIEW
ES75 EXPANDER REAR VIEW
DIV. OF UN POWER LLC • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • Tel: 954-346-2442 • Fax: 954-340-7901 • sales-northamerica@unipowerco com
UN POWER EUROPE • Parkland Business Centre, Chartwell Road, Lancing, BN15 8UE, ENGLAND • Tel: +44(0)1903 768200 • Fax: +44(0)1903 764540 • [email protected]
CONFIGURATION GUIDE
1.
Determine the capacity of the system desired, taking into account future expansion, then check the type of rectifier required and fill in the initial quantity to be ordered including spares. This will determine the system unit base number.
BASE SYSTEM
OUTPUT, MAX.
BASE SYSTEM
OUTPUT, N+1
RECTIFIER MODULES
CHECK TYPE REQ.
q
RSJ48/12-Z
q
RSG48/10-Z
q
RSF48/7-Z
q
RSG24/18-Z
q
RSF24/13-Z
q
RSG12/33-Z
q
RSF12/22-Z
NO. MODULES
REQUIRED
_______
_______
_______
SYSTEM UNIT
BASE NUMBER
X75-48
X75-24
X75-12
2.
If the required capacity initially or in the future exceeds the capability of the base system check against the same rectifier type as above and fill in the number of additional rectifiers required. This defines that an expansion unit needs to be ordered.
TOTAL SYSTEM
OUTPUT, MAX.
TOTAL SYSTEM
OUTPUT, N+1
RECTIFIER MODULES
CHECK TYPE REQ.
q
RSJ48/12-Z
q
RSG48/10-Z
q
RGF48/7-Z
q
RSG24/18-Z
q
RSF24/13-Z
NO. MODULES
REQUIRED
_______
_______
EXPANSION
UNIT NUMBER
X75-ES
3.
Check either option A or option B for DC distribution. For option A fill in the rating and code for each breaker to be installed.
For option B fill in the number of fuses for each value required including spares.
DC DISTRIBUTION
q
OPTION A:
Up to 5 Breakers Total, maximum 30A each.
1. Breaker ___ A, code ___ 3. Breaker ___ A, code ___ 5. Breaker ___ A, code ___
2. Breaker ___ A, code ___ 4. Breaker ___ A, code ___
Enter rating & code above:
1A(F), 2.5A(G), 5A(H), 10A(I), 15A(J), 20A(K), 25A(L) & 30A(M), Not required(X).
q
OPTION B:
Up to 10 GMT Fuses Total. Enter the number required below.
NO.
REQ’D
NO.
REQ’D
AMPS
0.5A
0.75
1
1.33
2
BUSSMAN NO.
GMT - 1/2
GMT - 3/4
GMT - 1
GMT - 1 1/3
GMT - 2
COLOR
Red
Brown
Gray
White
Orange
AMPS
10
12
0
3
5
BUSSMAN NO.
GMT - 3
GMT - 5
GMT - 10
GMT - 12
GMT - Dummy
COLOR
Blue
Green
Red-White
Green-Yel
Orange
4.
Check any options/accessories required and fill in the number of line cords if checked.
OPTIONS & ACCESSORIES
q
Additional Temperature Probe (One supplied as standard)
q
SNMP - Simple Network Management Protocol
AC Line Cords:
6ft. (1.8m) with IEC60320 C-13 connector, one per rectifier position in use.
q
125VAC with NEMA OR q
250VAC with NEMA OR q
250VAC unterminated
6-15 plug. 3x14AWG 6-15 plug. 3x14AWG 3 x 18AWG
Qty. _____ Pt. No. 364-1412-0000 Qty. _____ Pt. No. 364-1414-0000 Qty. _____ No. 364-1421-0000
5.
Send the completed form to the relevant UNIPOWER sales office and we will issue a configuration Model Number which will use the following format.
l l l
System unit Option A:
System unit Option B:
Expansion unit:
X75-vv-A-bbbbb-ST
X75-vv-B-ST
X75-ES
(voltage independent, no options available)
Key: vv = system voltage.
b = breaker code, five characters total.
S = SNMP option fitted. (add as suffix)
T = additional Temp. probe. (add as suffix)
NOTE: Fuses, rectifiers, accessories and the expansion unit are supplied as separate items from the main system unit and will be detailed separetely in quotations, proposals and Sales Order documentation.
x75-ds-revF-0712.indd