Simplex 4002 Installation And Operating Instructions Manual

Add to my manuals
48 Pages

advertisement

Simplex 4002 Installation And Operating Instructions Manual | Manualzz

Simplex

I

4002 Fire Alarm

l

Installation and Operating

Instructions

0 1994 Simplex Xme Recorder Co.

All specifications and other informatlon shown were current as of p&kation, and are s&+xt to change without notce.

Technical Manuals Online! - http://www.tech-man.com

FA4-21-151 (574-009)

Ed 3 94

WARRANTY

Contact your local

Simplex Time Recorder Co. branch office listed in the

Yellow Pages for Warranty

Registration & Information.

Technical Manuals Online! - http://www.tech-man.com

TABLE OF CONTENTS

PAGE

SECTION 1

System Operation Description ..........................................................................................................................

Pushbuttons

..................................................................................................................................................

Toggle Switches ............................................................................................................................................

Indicators .......................................................................................................................................................

Panei Displavs

Normal Condition ...........................................................................................................................................

Trouble Condition ........................................................................................................

Alarm Condition ........................................

..................................

.....................................................................................................

6

6

6

Operating 4002 Optional Equipment ................................................................................................................

6

Control Panel Operating instructions

Alarm Conditions ...........................................................................................................................................

Trouble Conditions ........................................................................................................................................

Sprinkler Activation

........................................................................................................................................

7

7

8

System Test Procedures

Battery Test .................................................................................................................................................... 9

3

4

4

4

Walk TestTM ...................................................................................................................................................

LED and Trouble Buzzer Test .....................................................................................................................

Manual Evacuation Test (Drill) .......... ..........................................................................................................

Graphic Representation Of Audible Zone Codes ...........................................................................................

What To Do In Case Of Trouble .....................................................................................................................

System Troubleshooting Chart ....................................................................................................................

1:

10

11

12

12

SECTION 2

Installation

Introduction ..................................................................................................................................................

General Notes .............................................................................................................................................

General Requirements For Fire Alarm Wiring ...............................................................................................

16

16

Installation Checklist ...................................................................................................................................

Back Box Installation

............................................................................................................ ..........................

17

18

19

Plastic Pipe, Raceway, Cable ....................................................................................................................

System Wiring Specifications

.........................................................................................................................

19

19

Initiating Device Wiring ...............................................................................................................................

Notification Appliance Wiring.. .....................................................................................................................

Control Circuits .................................................................................................

::

.......................................... 20

Incoming Power ..........................................................................................................................................

21

Earth Detection (Ground) ............................................................................................................................ 21

Mounting and Wiring Peripheral Devices .......................................................................................................

21

Style 6 ......................................................................................................................................................... 21

Style D .........................................................................................................................................................

Checking System Wiring .................................................................................................................................

22

22

Style B Initiating Device.. ............................................................................................................................. 22

Style D Initiating Device ..............................................................................................................................

Sprinkler Tamper Switch Circuit ...................................................................................................................

.22

22

Style Y Notification Appliance.. ....................................................................................................................

Style Z Notification Appliance ......................................................................................................................

Re-Mounting Electronic Components in Back Box ..........................................................................................

Terminations Of System Wiring ........................................................................................................................

Initiating Device Circuit .................................................................................................................................

22

23

23

24

24

Control Relay Circuit .

Annunciator Output Circuit ...........................................................................................................................

City Relay ......................................................................................................................................................

Special Zone Inputs ......................................................................................................................................

Connect Power to System ............................................................................................................................

2120 Connection ...........................................................................................................................................

SCU/RCU Wiring ............................................................................

..............................................................

Fan Control Module ......................................................................................................................................

24

24

24

24

25

25

25

Walk T~s:‘~ is protected by U.S. Patent NO. 4.725818.

Technical Manuals Online! - http://www.tech-man.com

Setting DIP Switches, SWl, SW2 And SW3 ...................................................................................................

Definitions Of System Functions ...... ............................................................................................................

Normal Operation ..........................................................................................................................................

Alarm Verification ..........................................................................................................................................

Coded input On Zone 1 ...............................................................................................................................

Waterflow On Zone 7 ...................................................................................................................................

Sprinkler Supervision On Zone 8 ...................................... ...........................................................................

Signal Cutoff After 10 Minutes .....................................................................................................................

Signal Silence Inhibit ....................................................................................................................................

2120 Connection Present In System ...........................................................................................................

Walk TestTM Mode.. .........................................................................................................................................

Manual Evacuation Switch Enabled/Disabled ..............................................................................................

Signal Coding ................................................................................................................................................

Selective Signal Circuit Operation ................ ................................................................................................

ESP Program Mode ......................................................................................................................................

Walk TestTM.. .......................................................................................................................................................

Re-Mounting Retainer and Door ........... ...........................................................................................................

Customer Information ......... ..............................................................................................................................

Glossary of 4002 Fire Alarm System Terms ...................................................................................................

APPENDIX A - Expanded Simplex Programming Option .................................................................................

Selective Signal Circuit Operation ....................................................................................................................

Selective Relay Control Operation ...................................................................................................................

Selective Fan/Damper Control Relay Operation ..............................................................................................

Selective Door Holder Relay Control ...............................................................................................................

Selective Bypass Control Switch Operation .....................................................................................................

Selective Switch Operation ...............................................................................................................................

Multiple Tamper Zones .....................................................................................................................................

Stage l/Stage 2 Operation or Pre-Signal Operation .......................................................................................

Cross Zoning .....................................................................................................................................................

Timing Functions ...............................................................................................................................................

Master Code .....................................................................................................................................................

Non-Alarm Monitor Point Operation .................................................................................................................

Non-Latching Monitor Point Operation .............................................................................................................

Pie20 Signal Operation .....................................................................................................................................

AC Power Fail (Control) ...................................................................................................................................

2120 Non-Default Operation .............................................................................................................................

RCU Switch Non-Default Operation .................................................................................................................

SCU Point Matrix (Zone Grouping) ..................................................................................................................

Elevator Recall with Alternate Floor .................................................................................................................

System Reset (Special Operation) ...................................................................................................................

Point Sensing ....................................................................................................................................................

PNIS Zone Coding ............................................................................................................................................

APPENDIX B - Fan Control Module

Features .._..___._._..........._.._............................................ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .._............................................. 36

Panel Connections . . . .._..._................................................................................................................................ 36

Field Connections.. .

35

35

35

35

34

34

34

35

35

34

34

34

34

34

34

34

33

33

33

33

34

34

34

28

28

29

29

29

29

29

30

30

31

31

31

32

25

27

27

27

28

28

Switch SW2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....................... 37

Switch SW3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ............... 38

DIP Switch SW4.... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............. 38

DIP Switch SW3 on CPU Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .._.................................................... 38

Interconnection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .._.................................................................... 39

Wire Length Chart in Feet . . . . . . . . . . . . . . . . . . .._... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

APPENDIX C - Battery Testing Information . . . . . . . . . . . . . . . . . . . . . .._..................._........._................................................. 41

Technical Manuals Online! - http://www.tech-man.com

SECTION 1

Figure 1 - 4002 Fire Alarm System

SYSTEM OPERATION DESCRIPTION

The 4002 is a battery-backed, U.L. listed, power-limited, electrically-supervised fire alarm system that, depending on its size, can operate up to six notification appliance (signal) circuits and monitor up to 32 zones of initiating device circuits. In addition, a 4002 can automatically control equipment such as fire doors, smoke dampers, fans and elevators during a fire condition.

The 4002 provides audible and visual indications during trouble or alarm (fire) conditions. Should either of the above occur, the system sounds the applicable notification device(s) and flashes the applicable LED (one of the yellow LEDs for trouble, one of the red LEDs for alarm). The indications continue until someone appropriately acknowledges the condition (presses the TROUBLE SILENCE or the ALARM SILENCE push button). l

Acknowledging the condition silences the notification device(s), causes the flashing LED to illuminate steadily and, in the case of an alarm, illuminates the ALARM SILENCED LED.

Note 1: If, following a trouble or alarm acknowledgement, another circuit or zone goes into trouble or alarm, the applicable LED flashes and, in the

case

of an alarm, the alarm notification device(s) resound.

Note 2: Once in alarm, the system remains in alarm until (1) the device that initiated the alarm is restored to normal and (2) the panel is reset.

The user interface with the system consists of controls and indicators which are mounted in the control panel. The purposes of these controls and indicators are as follows, and are shown on Figure 2.

3

Technical Manuals Online! - http://www.tech-man.com

4002 CONTROL PANEL

OPERATOR SWITCHES AND INDICATORS a. PUSH BUTTONS

1. SYSTEM RESET - Used to reset the system following an alarm condition.

2. ALARM SILENCE - Used to stop alarm signal operation during an alarm condition.

3. TROUBLE SILENCE - Used to stop the panel trouble signal from sounding during trouble conditions.

4. MANUAL EVAC - Causes the alarm signals to operate. (Does not activate control relays or city disconnect). This pushbutton must be held in for 3 seconds to activate indicating appliances. b. TOGGLE SWITCHES

1. CITY BYPASS - In the “UP” position, prevents the system from reporting an alarm condition to the municipal fire department and causes both the “system trouble” and “city trouble” LEDs along with the trouble signal to activate.

2. AUX 1 BYPASS - A. The UP position, prevents alarm relay #l from energizing during an alarm condition and causes the “SYSTEM TROUBLE” LED and trouble signal to activate.

B. Becomes inoperative if jumper JW12 is removed. The Aux 1 relay will operate like the piezo during a trouble condition. The “System Trouble” LED will illuminate when a trouble condition exists. Outputs of Aux 1 relay are silenced with the

Trouble Silence push button.

3. AUX 2 BYPASS - The “UP” position, prevents alarm relay #2 from energizing during an alarm condition and causes the “system trouble” LED and the trouble signal to activate. c. INDICATORS (amber LED’s)

1. SYSTEM TROUBLE - Used to indicate abnormal conditions in the system.

2. SIGNAL 1 TROUBLE - Indicates a wiring fault (open or short) or a defective device in signal circuit #l .

3. SIGNAL 2 TROUBLE - Indicates a wiring fault (open or short) or a defective device in signal circuit ##2.

4. CITY TROUBLE - Indicates either the “Cii Bypass” toggle switch in the bypass position or a wiring fault

(open) between the panel and the municipal fire reporting system.

5. ANNUN TROUBLE - Indicates a problem within the annunciator or a wiring fault (open) between the panel and the annunciator.

6. POWER TROUBLE - Indicates either total or partial loss of AC power (brown out conditions) or battery is disconnected.

7. GROUND TROUBLE - Indicates a ground fault in the system.

8. POWER ON - indicates AC power is applied to system. This is a green LED.

9. ALARM SILENCED- Indicates Alarm Evacuation Signals have been silenced.

10. ZONE - From 8 to 32 red “ALARM” LEDs and an equal number of amber “TROUBLE” LEDs. l

Each “ZONE ALARM” LED indicates an alarm condition (fire) in its zone; each “ZONE TROUBLE” LED indicates a trouble in its zone.

ANNUNCIATOR TROUBLE ZONE 1 ALARM

POWER TROUB\E

I I

ZgNE 2 ALARM

SYSTEM TROUBLE ,:

SIGNAL 1 TROUBLE 3 :

SIGNAL 2 TROUBLE i

ClTY TROUBLE

-4

:

GROUND TROUBLE

I

I

I I

\

ZONE 3 ALARM

ZdNE 4 ALARM

POWER ON

,ZONE 1 TROUBLE

ZONE 2 TROUBLE

*ZONE 3 TROUBLE

ZONE 4 TROUBLE

AUX 1 BYPASS

\

ZONE 5 ALARM

CITY BYPASS

ZONE 6 ALARM

/

SYSTEM RESET

ALARM SILENCE

TROUBLE SILENCE

MANUAL EVACUATION

A”X 2 BypAss ALARM’SILENCED

ZONE 8 ALARM

\

ZONE 7 ALARM

Figure 2 - 4002 Operator Switches And Indicators

Technical Manuals Online! - http://www.tech-man.com

ZONE 5 TROUBLE

ZONE 6 TROUBLE

ZONE 7 TROUBLE

ZONE 8 TROUBLE

4002 PANEL DISPLAYS

NORMAL, TROUBLE AND ALARM CONDITIONS l

Normal Condition

- Green “POWER ON” LED on.

- All other panel indicators off.

0 Trouble Condition

- System Trouble buzzer sounds continually.

- One or more amber “TROUBLE” LEDs on.

0 Alarm Condition (Non-ESP)

- All signals sound.

- AUX and city relays activate.

- One or more “ALARM” LEDs flash.

- System trouble buzzer sounds at a march time cadence (120 pulses per minute).

Note: The following Software functions will affect the ALARM SILENCE operation. a.

Selective coded station input

- Indicating appliances cannot be silenced when zone 1 is in alarm. The indicating appliances will be silenced automatically when coding is complete. The flashing zone LED will change to a steady state when the code is completed. b.

Waterflow Sprinkler On

Zone 7 - Indicating appliances cannot be silenced if water is flowing in the sprinkler system. c.

Alarm Silence inhibit

- Programmed for 1, 3, or 5 minutes. d.

Signal

Cutoff - After 10 minutes of continuous operation, signals silence autom&aiiy. l

Signals can be manually silenced at any time.

OPERATING 4002 OPTIONAL EQUIPMENT l

ESP Programming Option (See Appendix A)

- System programmed to meet customer requirements.

- Provides 23 additional functions. l

Fan Control Module (See Appendix B)

- Provides hand/OFF/automatic (HOA) operations for climate and smoke control.

Technical Manuals Online! - http://www.tech-man.com

4002 FIRE ALARM SYSTEM OPERATING INSTRUCTIONS

FOLLOWING AN ALARM/TROUBLE CONDITION

YOUR SAFETY AN0 THE SAFETY OF THOSE AROUND YOU

ALWAYS COMES FIRST! g a fire depend upon lee01 practices. Be sure

HOW TO OPERATE THE PANEL DURING AN ALARM SITUATION: l l Identify the zone in alarm via the control panel indicators. Follow Local Procedure to investigate that zone to determine the cause of the alarm. (Pull station activated, smoke detector activated etc.)

After all occupants are evacuated, unlock and open the panel door. l To silence signals, press the alarm silence push button.

- Audible signals are silenced, alarm silenced LED illuminates, and any red zone indicator that was flashing comes on steady. If another alarm is reported from another zone, the alarm signals sound again, the alarm silenced LED turns OFF, and the red indicator representing the zone in alarm flashes until the audible signals are again silenced.

HOW TO RESET THE FIRE ALARM SYSTEM FOLLOWING AN ALARM CONDITION: l When the alarm situation has been cleared, restore or replace all affect& alarm-initiating devices (pull stations and detectors) in accordance with the instructions provided with each device. l Press and hold the SYSTEM RESET switch until LEDs illuminate (see Note below).

- The trouble buzzer sounds for 2 seconds and LEDs illuminate for approximately 5 seconds.

WHAT TO DO IN CASE OF TROUBLE: l Notify appropriate personnel.

NAME ADDRESS

PHONE

NUMBER l l

Unlock and open panel door.

If tone device is sounding, press the trouble silence push button. l

Refer to the 4002 Customer Instructions manual for additional instructions or call a local Simplex Branch Office for assistance.

Note: The following options affect the system as follows: l Waterflow/Sprinkler - you cannot silence an alarm or reset the system if water is flowing in the sprinkler system. l Coded Input On Zone 1 -the signals cannot be silenced while a code is being transmitted. l

ESP (Expanded Simplex Programming) l Silence Inhibit - you cannot silence an alarm or reset the system until the specified time period has elapsed.

0 Custom Project Specific Software Programming

THESE INSTRUCTIONS ARE INTENDED TO BE FRAMED AND MOUNTED ADJACENT TO THE

CONTROL PANEL FOR READY REFERENCE.

__--- -_------------- ------

Refer to the Customer’s Instructions for a detailed description of system operation.

4

7

Technical Manuals Online! - http://www.tech-man.com

HOW TO OPERATE THE PANEL 4002 CONTROL

PANEL DURING AND AFTER SPRINKLER

SYSTEM ACTIVATION

The panel, when programmed in software for this function, indicates one or more sprinkler water

flow

devices connected to zone 7 are in alarm by:

a. Flashing zone 7 red “ALARM” LED. b. Sounding the “sprinkler alarm” (general alarm signals) and designated signal circuit 2. c. Piezo sounds “FAST MARCH TIME” signal.

Note: The designated sprinkler alarm signal(s) on signal circuit #2 cannot be silenced while the sprinkler system is active.

Actions to take:

a. Investigate the cause of the sprinkler system alarm. It could be a fire. lf NO FIRE or WHEN THE FIRE IS OUT, continue. b. Turn off the water supply valve for the sprinkler system. c. Zone 8 “ALARM” LED flashes. d. Press the “ALARM SILENCE” push button to silence signals.

- “ALARM SILENCED” LED illuminates

- The general alarm signals and piezo are silenced.

- Zone 7 red “ALARM” LED goes on steady.

- Zone 8 red “ALARM” LED goes on steady until someone turns the sprinkler system water supply valve back on, then it will automatically go off. e. Restore or replace sprinkler heads in accordance with the instructions provided with the devices. f. Recharge the sprinkler system in accordance with the directions provided with the sprinkler system.

- During the recharging period, zone 7 “ALARM” LED glows steady. g. When the sprinkler system is fully charged, press the “SYSTEM RESET” push button.

- .The “ALARM” LEDs go off.

Note: Until the sprinkler system is fully charged, waterflow may be detected by the panel and the fire alarm system may go into alarm again. You may have to repeat this procedure several times while recharging the sprinkler system.

4002 FIRE ALARM SYSTEM

TEST PROCEDURE

Note: This procedure should be followed when the system is installed during periodic tests required by code.

Check with local codes to determine how frequently your system should be tested. Inform appropriate personnel that you wili be testing the fire alarm system. Then unlock and open the panel door. Remove the panel retainer plate (two “squeeze clips” hold it in place).

BATTERY TEST a. Check battery power as follows:

1. Remove AC power from panel by disconnecting the main power feed.

2. Silence the trouble signals by pressing the “TROUBLE SILENCE” push button.

3. Wait five minutes.

4. Activates the “MANUAL EVAC” switch. Ailow the system to sound for 2 minutes.

5. Using a meter, read across the pins of P5 (found on the bottom-left of the CPU board [see Figure 4, page

151). l Voltage must exceed 20VDC (if less than 20VDC, call your local Simplex Branch office).

6. Apply AC power to the panel.

Note: See Appendix C for additional battery testing information.

WALK TEST”‘.’

PROGRAM SWJTCHES

#a. Put the panel in its

Walk

Test” mode as follows:

1. (See Figure 3) Transfer program DIP switch

SW2-1 to OFF. l

For location of SW2, see Figure 4 (page 15). c

2. Press the SYSTEM RESET push button. The panel’s LEDs will all light (except POWER and

GROUND TROUBLE) then the panel will indicate SYSTEM TROUBLE and CITY

TROUBLE. The city circuit is disabled during the walk test.

Figure 3 - DIP Switch SW2 Position 1

3. Activate each of the system’s alarm initiating devices (pull stations, smoke detectors, heat detectors etc.). o The signals will sound a “zone identification” code following the activation of any alarm initiating device

(See CODE CHART ON PAGE 11).

0 After the code, the system resets itself in approximately 5 seconds,

Note: Smoke detector and rate-of-rise heat detectors may require more than five seconds to clear, and hence may cause the system to reissue the previous code.

9

Technical Manuals Online! - http://www.tech-man.com

4. Test for electrical supervision of wiring to each device as follows:

1. Disconnect a wire from each device (in the case of a smoke detector, remote it from its base).

2. Reconnect the wire or reinstall the smoke detector head. l

The signals should sound for four seconds each time a wire is disconnected or a smoke detector head is removed.

Note: Failure of the signals to sound indicates an improperly wired zone circuit, signal circuit or smoke detector base.

IMPORTANT: Upon completing the system Walk TestTM:

l

Return DIP switch SW2-1 to its ON position. l

Install the panel frontplate. l

Press the SYSTEM RESET push button. l

Notify appropriate personnel that the test has been completed.

LED AND TROUBLE BUZZER TEST

Press the SYSTEM RESET push button for approximately two seconds. l

The trouble buzzer will sound for approximately 2 seconds. l

Except for the “POWER TROUBLE,” “GROUND TROUBLE,” and those for signal circuits 3 and above, all panel

LEDs must light for about 5 seconds.

MANUAL EVACUATION TEST (DRILL) a. Perform “Manual Evacuation Test” as follows:

1. Inform appropriate personnel that you will be testing the fire alarm system.

2. Unlock and open the fire alarm panel door.

3. Press and hold the “MANUAL EVAC” push button IN for 3 seconds.

The notification appliances will sound to alert personnel within the building. The notification appliance will continue to sound until silenced by pressing the “ALARM SILENCE” or the “SYSTEM RESET” push button.

Note: Manual evacuation tests do not activate the auxiliary relays or the municipal fire department city connections. l

Should a valid alarm initiation occur during a manual evacuation test, the auxiliary relays and the city circuit connections activate.

10

Technical Manuals Online! - http://www.tech-man.com

GRAPHIC REPRESENTATION OF AUDIBLE ZONE CODES a. If “simple

coding”

is programmed in your system to identify the zone where a fire condition exists, a zone code repeats on the alarm signals until the alarm is silenced. b. If a Walk TesP is being performed, a zone code sounds once on the alarm signals before the panel automatically resets itself. c. Each long dash (-) represents a half-second-long signal pulse. d. Each short dash (-) represents a quarter-second-long signal pulse.

Zone

No.

8=

9=

10 =

11 =

12 =

13 =

14 =

15 =

16 =

17 =

18 = l=

2=

3=

4=

5=

6=

7=

19 =

20 =

21 =

22 =

23 =

24 =

25 =

26 =

27 =

28 =

29 =

30 =

31 =

32 =

Zone Identification Code

-

-

-

-

-----

_-----

_------

_-------

---

----

-

--

-

-

_----s-v-

-

-

_

_

--

--

_-

--

--

--

--

--

--

--

---

---

---

----

-----

---e-e

-A-----

--

---

-

--

-_--A---

___------

--

-

--

---

----

-----

--e-w-

_--A---

--------

---------

--

-

--

11

Technical Manuals Online! - http://www.tech-man.com

Description

1 long

2 long

3 long

4 long

5 long

6 long

7 long

8 long

9 long

1 long, pause, 2 short

1 long, pause, 1 long

1 long, pause, 2 long

1 long, pause, 3 long

1 long, pause, 4 long

1 long, pause, 5 long

1 long, pause, 6 long

1 long, pause, 7 long

1 long, pause, 8 long

1 long, pause, 9 long

2 long, pause, 2 short

2 long, pause, 1 long

2 long, pause, 2 long

2 long, pause, 3 long

2 long, pause, 4 long

2 long, pause, 5 long

2 long, pause, 6 long

2 long, pause, 7 long

2 long, pause, 8 long

2 long, pause, 9 long

3 long, pause, 2 short

3 long, pause, 1 long

3 long, pause, 2 long

WHAT TO DO IN CASE OF TROUBLE a. Notify appropriate personnel that the system is in trouble. b. Unlock and open the panel door. Then press the TROUBLE SILENCE push button. c. Check to see what the panel’s symptoms are. Then perform the action which applies to those symptoms as described in the SYSTEM TROUBLESHOOTING CHART. See Figure 4 (page 15) for location of components identified on the troubleshooting chart. The troubleshooting chart is located on pages 12 through 14.

SYSTEM TROUBLESHOOTING CHART

IMPORTANT

Corrective actions which follow asterisks should be performed only by a Simplex technician or a qualified electrician.

Symptom

C 1. Zone “ALARM* LED is on, and system cannot be reset

Probable Cause l

Pull station activated l

Smoke detector alarm indicator on steady l

Duct smoke detector alarm indicator on steady l

Heat detector activated

Corrective Action

Restore pull station.

Reset or replace smoke detector.

Reset or replace duct detector.

Restore or replace heat detector. l

Waterflow device activated l

Zone circuit shorted

Restore waterflow device.

* Clear shorted line condition.

(The E.O.L. resistors 3.3K ohms should be read between the zone terminals.)

# 2. Both “SYSTEM TROUBLE” and one or more “ZONE” Trouble LEDs are on. l

Alarm initiating device (smoke det, pull station) removed from zone

0 Open connection in zone wiring

# 3. “POWER ON” LED is off

Replace alarm initiating device. l

Defective module in tire alarm panel l

Fire alarm 120VAC circuit breaker tripped l

Fuse F2 in panel open

* Repair the open line condition.

(The E.O.L. resistor’s 3.3K ohms should be read between the zone terminals.)

Call Simplex

Reset breaker.

Replace fuse F2 (8 Amp) (see page 15, Figure 4).

* Check power distribution in building. l

Low AC voltage or “brownout” condition (brown-out voltage is

102 VAC or less)

12

Technical Manuals Online! - http://www.tech-man.com

1 Probable Cause 1 Corrective Action

. A remote annunciator’s RESET or SILENCE switch not in the normal postion l

Transformer connection P4 not l

Open card supervisory loop l

Battery fuse F3 open nections are not

# 8. Both “SYSTEM TROUBLE” and one or more “SIGNAL” Trouble LEDs are on from circuit (bell, horn, AN uni

0 Open connection on signal circuit l

Electrical short in signal circuit

Restore to normal position.

Connect the transformer cable rconnecting harnesses

Replace F3 (8 amp) fuse.

- Repair the open line condition.

(The E.O.L. resistor’s 1 OK ohms should be read between the signal

- Repair the short circuit condition.

(The E.O.L. resistor’s 10K ohms should be read between the signal

EM TROUBLE” and CITY

TROUBLE LEDs are on

. CITY BYPASSswitch not in its normal position l

Configuration jumpers incorrectly set l

Open in city circuit field wiring

# 8. Both “SYSTEM TROUBLE” and

“GROUND TROUBLE” LEDs are on

# 9. Both “SYSTEM TROUBLE” and

“ANNUN TROUBLE” LED’s are on

Set jumper correctly.

- Repair the open line condition. l

One or more conductors are shorted to ground

Burned out LED in annunciator

* Remove field wiring from connector: one pair at a time until ground fault clears.

* Depress SYSTEM RESET to check annunciator LEDs.

* Repair open line condition. l

Open connection between panel and annunciator l

Serial annunciator not installed in system l

DIP switch SW3 settings incorrect

Set SW3 to all closed positions. l l

0 DIP switch SW1 1 settings incorrect

Defective annunciator

Defective module in fire alarm panel

Set SW3 to indicate correct number of senal annunciators in system.

Set SW1 1 to indicate correct number of supervised annunciators. See Wire

Diagrams.

Call Simplex

Call Simplex

13

Technical Manuals Online! - http://www.tech-man.com

l

Zone circuit incorrectly wired l

Defective module in fire alarm panel

* Correct wiring fault in zone circuit. l

N.O. or N.C. wiring incorrect s Defective fuse(s) Replace Fuse F4 or F5 (3 amps).

#12. “SYSTEM TROUBLE” and several

“Zone trouble” LEDs are flashing

#13. “SYSTEM TROUBLE” and “Signal 2

Trouble” LEDs are flashing and the l

Defective 24 volt power supply l

Fuse F9 defective l

Defective notification appliance l

Fuse F6 defective Replace fuse F6 (3 amps).

NEED HELP?

CALL YOUR LOCAL SIMPLEX BRANCH OFFICE, WHICH IS LISTED IN THE YELLOW PAGES, FOR ALL

MALFUNCTIONS NOT LISTED IN THE ABOVE TROUBLESHOOTING CHART, OR IF YOU WOULD LIKE A

QUALIFIED SIMPLEX TECHNICIAN TO ASSIST YOU WITH INSTALLATION, TESTING, AND

TROUBLESHOOTING THE SYSTEM.

4002 MAIN C.P.U.

COMPONENT LOCATIONS

DIP Switch, SW1 1

Annunciator

Supervision

Fuse Fl, 3 Amp

Annunciator

Voltage ( + 24VDC)

,DIP Switch, SW3

Serial Annunciator

Program Switch

DIP Switch, S W2

Program Switch

DIP Switch, SW7

Program Switch

Fuse F2 8 Amp

Main Power

Fuse F9,3 Amp

+ ‘“/““”

, Fuse F5,3 Amp

Aux 1 Rela ‘Y

-Fuse F4,3 Amp

AUX 2 Rel; ay

Conmctor P4-

Transformer Cable

I

Connector P5

Battery Cable

Pins + and -

Fuse W, 3 Amp

Signal Circuit 1

\

Fuse F6,3 Amp

Signal Circuit 2

Figure 4 - Component Locations

15

Technical Manuals Online! - http://www.tech-man.com

SECTION 2

__ ..-...-------.-. ._ _--- _... .-

CAUTION

!

I

/

NEVER REMOVE OR REPLACE CABLES OR WIRES WITH POWER APPLIED TO THE SYSTEM

To power down the system:

1. Disconnect either of the battery’s terminals.

2 Turn off system power at the AC breaker.

!---------_-_-.-- ..--- --

To power up the system:

1. Turn on system power at the AC breaker.

2 Apply battery power.

1

1

I

I

INSTALLATION INSTRUCTIONS

INTRODUCTION

This section provides both information and instructions on the 4002 fire alarm system wiring. It is important that you read this section and utilize the 4002 field wiring diagrams 841-669 and 841-687 which accompany the control panel to install your fire alarm system. l

To help you in the installation of this and other Simplex fire alarm systems, the following publication has been made available for general reference: How to Wire a Building for a Fire Alarm System (Simplex Publication

No. FA2-91-001).

General Notes a. When running wires to the control panel, identify and tag all wires appropriately: 120 VAC or 220/240 VAC power; signal circuit 1; zone 1, zone 5 etc.; and identify all “+” and ‘I-” wires by color code or numerical sequence. b. The panel’s terminal strips are labeled with a terminal strip number (TBl, TB2, etc.), and each terminal is designated by a terminal number (1, 2, 3, etc.). Therefore, TBl-1 is terminal 1 on terminal strip 1, TB3-2 is terminal 2 on terminal strip 3, etc. In addition, each terminal is identified by an abbreviation of the circuit function to be connected. For example, zone 1 = ZNl +, ZNl -, signal circuit 2 = S2B + , S2B - ; annunciator output from zone 5 = ANN 5 - . c. Use the color code shown in Figure 5 to determine E.O.L. resistor values. E.O.L. resistors are provided as part of the System Support Material when shipped. A 1,000 ohm (1 k, 1 W) resistor is provided for the city relay termination, and should be installed when city connections are not required. Terminate all unused zone circuits with 3.3k ohm resistors. Terminate all unused signal circuits with 10K ohm resistors. k-

Zqne Circuit E.O.L. Resistor

3,300 ohm (3.3k, 1 W)

Signal Circuit E.O.L. Resistor

10,000 ohm (lOk, l/2 W)

Figure 5 - E.O.L. Resistors d. All wiring should be done in accordance with local codes and the National Electrical Code, Article 760. e. Remember: A neatly wired panel helps assure accurate inspection of terminal connections and simplifies troubleshooting.

16

Technical Manuals Online! - http://www.tech-man.com

INSTALLATION CHECKLIST

4 o This section provides a systematic 10 step method for installing a 4002 fire alarm system. e Use the field wiring diagram

#Ml-669

and 841-687as reference. l

Upon comp!etion of a step, check the appropriate box. l

Detailed instructions for each installation step can be referenced on the pages noted. l

Common hand tools and a volt/ohm meter are required to perform this installation.

STEP # q 1. cl 3.

0 4. cl 5. cl 6.

Cl 7.

Cl

8.

Cl 9. q

10.

ACTION REQUIRED

Mount Control Panel Back Box (Less internal electronic subassemblies)

Install System Wiring throughout building for zone, signal, control and input power circuits (including system ground connection). Tag each wire at the control panel location. install all peripheral devices (stations, detectors, horns, bells, etc.) and end-of-line resistors.

Check all system .wiring with a volt/ohm meter for shorts, opens, grounds or extraneous voltages.

Re-mount electronic sub-assemblies in the control panel back box.

Re-make all factory harness connections.

Terminate all system wiring at the specified terminal locations.

Program basic system functions via DIP switch SW1 and SW2.

Perform a complete system test of all device using “walk-test” mode.

Mount retainer panel and door on cabinet. Connect door ground wire to box.

Instruct owner’s representative on system operation.

FOR DETAIL,

REFER TO

PAGE NUMBER

18

19

21

24

25

31

31

31

22

23

17

Technical Manuals Online! - http://www.tech-man.com

STEP #l

BACK BOX INSTALLATION

4002 Back Boxes may be shipped with or without their electronic components, and come in three different sizes.

The procedures listed below should be used when installing a back box with electronic components. Details for mounting a back box without electronic components are shipped with the empty back boxes.

A. Systems With Electronic Components

1. Carefully open the shipping container.

2.

Inventory the contents of the shipping container to ensure complete shipment of the required materials. (See packing list.)

3.

Remove the panel door box from the shipping container.

4.

Remove the back box from the shipping container and lay the unit on a flat surface.

5.

Remove the retainer (internal door) by squeezing and pulling the two black plastic tabs located on the upper center of the retainer. Lift the retainer from the back box.

Note: For semi-fiush mounting, the back box must be extended 1 l/2 inches from the finished wall.

Page 23 of this manual contains details for remounting the electronic components into the back box.

‘TYPE 4002-2202

OPTIONAL

SEMI-FLUSH 1”

TRIM BAND

6.

Carefully mark one end of each interconnection cable.

7.

Remove

one end

of all interconnection from the electronic assemblies. cables

8.

Loosen the screws holding the small upper and lower rack sets and remove them from the back box (none in #2 units). Loosen the screws holding the large rack set that contains the CPU module

(located on the left side of the back box) and remove the large rack set from back box. The electronic assemblies and one end of the cables and wiring harness should remain mounted to these rack sets.

SEMI-FLU% MOUNT

(LEFT-SIDE ONLY) - HINGE -

SURFACE MOUNT

IRIGHT SIDE)

NOTE: USE TOP SMALL KNOCKOUTS FOR SEMI-FLUSH

MOUNTING AND LEFT HAND HINGE ONLY.

Note: The use of a grounded wrist strap is recommended rack sets. when removing/replacing the

9. Store the electronic assemblies in the shipping container.

10. Place the retainer in the shipping container.

11. Place the panel door box in the shipping container.

Figure 6 - Back Box Mounting Instructions

PRODUCT

IDENTIFICATION

NUMBER

DESCRIPTION

SIZE WEIGHT

. HEIGHT

W)

12. Store the shipping container in a safe, clean, and dry location until the back box installation and the system field wiring is completed, and you are ready to reassemble the control panel as instructed on page 23.

NOTE: WEIGHT IS IN POUNDS, AND DOES NOT INCLUDE

BATTERIES.

13.

Mount the back box as shown in Figure 6.

Technical Manuals Online! - http://www.tech-man.com

$

,

STEP #2

GENERAL REQUIREMENTS FOR FIRE ALARM WIRING

Note: These wiring specifications are subject to local codes, and are not intended to circumvent any required codes, jaws, or regulations. e Only copper conductors may be used.

0 Al! wiring, except ground connection wiring, must be free from shorts and have a minimum resistance of one megohm to ground. o Metallic conduit, metallic raceway, plastic pipe, plastic raceway or approved fire alarm cable may be used.

Note: When using metallic conduit, and the continuity of the conduit is not maintained, a 12 AWG drain wire

(ground) must be connected between the break in the conduit installation. o Only fire alarm system wiring may be run in the same conduit, raceway or multiconductor cable. l

Each peripheral device (pull station, detector, horn, bell, etc.) must have its own enclosure (back box, outlet box, etc.) per instructions provided with each device. l

All wiring shall be terminated with U.L. listed devices (wire nuts, pressure connectors, etc.). Wiring terminated with only electrical tape is not permitted. All splicing (free ends of conductors) shall be covered with an insulation equivalent to that of the conductors.

REQUIREMENTS WHEN USING PLASTIC PIPE, PLASTIC RACEWAY, OR APPROVED FIRE ALARM CABLE l

When a system wire is adjacent and parallel to other building wire runs, a minimum of 6 in. shall be maintained between the different wire runs. l

When a system wire is to cross over other building wires, the system wires shall cross at a 90” angle and have a minimum of 6 in. separation. l

All fire alarm cables entering an electrical box must be provided with a connector that provides strain relief and protection for the cable. l

All fire alarm cables shall be separated by at least 3 ft. from every heat-radiating recessed fixture (for example, a high-hat fixture). Furthermore, cables shall not be installed in direct contact with lay-in fixture ballasts. l

Where fire alarm cables are exposed to the weather, the cables shall be shielded or run in metallic raceway with approved weatherproof or rain-tight fittings.

SYSTEM WIRING SPECIFICATIONS

hifiafing Device Wiring

(Zone Circuits) Use Field Wiring Diagrams #841-687 and 841-669.

Devices connected: Pull Stations, Heat Detectors, Smoke Detector, etc.

Wiring: - Up to 32 circuits with either two wires (for Style B operation) or four wires (for Style D operation) per circuit. Each Style B, 2 wire circuit terminates with a 3.3K ohm E.O.L. resistor at the last device.

Zone wire resistance must not exceed 50 ohms, and its total wire length must not exceed 5,000 ft. Style:

B or 2,500 ft. Style D.

19

Technical Manuals Online! - http://www.tech-man.com

STEP #I2 cont.

Notification Appliance Wiring

(Signal Circuits) Use Field Wiring Diagrams #841-687 and 841-669.

Examples: Horns, bells, visual units, etc.

The chart below should be used to determine the wire lengths in a 2-wire parallel DC signal circuit.

Note 1: Calculate the total current for all devices to be powered by a circuit. This is accomplished by adding current requirements for each device on a circuit. Then use the “TOTAL CURRENT IN CIRCUIT” column to determine wire length.

Note 2: Current draw of typical indicating appliances are:

Lamp - .075 A

Bell-.llOA

Horn - ,035 A

Visual Devices - .070 A

NOTE 3.

Line distance was determined based on

.11 A per device and the devices spaced at equal distances.

(For circuits where all devices are located at end of the circuit, contact your local Simplex

Field Office)

NOTE 4.

Wiring distance is l/2 distance for Style 0,

4-wire notification appliance circuits.

TOTAL CURRENT

O.llA

0.22A

0.33A

0.44AA95-

0.55A

0.66A

0.77A

0.88A

0.99A l.lOA

1.21A

1.32A

1.43A

1.54A

1.65A

1.76A

1.87A

1.98A

DISTANCE TO LAST DEVICE

FROM THE PANEL IN FEET

18 AWG 16AWG 14 AWG

2349-

1566-

1198 -1904-

783 -1245

681 -1083

602

526

479

438-

400

374

335

314-

293-

281

266

253

3735-

2494 -3960

1518-

595

534

500

466

448

423

403

-1722

958 -1524

836 -1330

761

697-

636-

5940

3029

241 5

1980

1211

1108

1012

945

849

795

472

7l?

673

641

CONTROL CIRCUITS l

AUXlLIARY ALARM RELA

YS (Activate on system alarm) Use Field Wiring Diagrams #841-687 and 841-669.

Devices controlled: Lights, fans, door release, dampers, etc.

Contacts: Form C dry contacts rated 2 amps @ 30 VDC/30 VAC or 0.5 amps @ 120 VAC resistive.’

Wiring: From 14 to 18 AWG wire may be used.

0 TROUBLE RELAY

(Not Silenceable - Activates on system trouble) Use Field Wiring Diagrams #841-687 and

841-669.

Devices controlled: Trouble horns, bells, lights, etc.

Contacts: Form C dry contacts rated 2 amps @ 30 VDC/30 VAC or 0.5 amps @ 120 VAC resistive.*

Wiring: From 14 to to 18 AWG wire may be used. l

TROUBLE RELAY

(Silenceable - Activates on system trouble) Use Field Wiring Diagrams #841-687 and 841-

669. Change AUX 1 alarm relay from alarm to trouble by removing Jumper JW12. When this jumper is removed, the trouble silence push button disconnects the relay.

CAUTION

Use of external power may void power limited U.L. Listing on that circuit.

20

Technical Manuals Online! - http://www.tech-man.com

l incoming Power (See W.D. #841-669, [sheet 22 for 120 VAC; sheets 36,37 and 38 for 220/240 VAC]

Source: Dedicated fire alarm power circuit with a 10 amp fused disconnect or as required by local codes.

Wiring: Use two 14 AWG wires or 14 AWG cable. l

Earth Detection

(Ground) (See W.D. #841-669)

Source: Connection must be made to an approved dedicated earth ground per NEC Article 250 (NFPA 70).

IMPORTANT

Terminate ground wire on green ground lug screw inside fire control back box.

STEP #3

MOUNTING AND WIRING PERIPHERAL DEVICES

(Refer to Wiring Diagrams 841-687 and

Instructions Provided with Each Device.) l

Style B

install all peripheral devices (detectors, horns, pull stations, etc.) and connect them to the appropriate wires.

Connect a 3.3K ohm end-of-line resistor (EOLR) across the terminals of the last device in the initiating device circuits and mark the device accordingly (see Figure 7). Connect a lOk-ohm EOLR across the terminals of the last device in the notification appliance circuits and mark the device accordingly (see Figure 8).

Note: (X) = Zone Circuit #

(Y) = Signal Circuit #

I DEVICE

CIRCUIT

PANEL

! L-M-k4

NOllFlCAllON

APPLIANCE

ClFlCUlT

Style B Initiating Device Circuit - Style Y Notification Appliance Circuit

Figure 7 Figure 8

AT THE LAST

NOTlFlCATlON

APPLIANCE,

CONNECT A 10K

EOLR, l/2 WA-IT

21

Technical Manuals Online! - http://www.tech-man.com

l

Style D

Same as class B, except both ends of every circuit terminate at the panel (see Figure 9 for typical initiating de- vice circuit and Figure 10 for typical notification appliance circuit).

ZN(X)A + IN

ZN(X) + OUT

I

1

I

PANEL 1

ZW) - OUT

ZN(X)A - IN

I

1

I

I

S(Y)A + IN

S(Y)B +OUT

I

PANEL

S(Y)B - OUT

S(Y)A - IN

I

I

I

)

I

Style D Initiating Device Circuit - Style Z Notification Appliance Circuit

Figure 9 Figure 10

STEP #4

CHECKING SYSTEM WIRING l

At the control panel, use a volt/ohm meter to check each wiring circuit. Use the green grounding lug in the control panel for all measurements to station ground. Each measurement has a tolerance of + or - 10%. l

Each circuit must test free of grounds and extraneous voltages. l

Each of the following circuit types must have the following resistance readings.

Meter Reading Circuit Type

Style B Initiating Device (Zone) Circuit

From zone + to zone - (each zone)

From zone + to station ground

From zone - to station ground

Style D Initiating Device (Zone) Circuit,

From zone + to zone - (each zone)

From zone + to station ground

From zone - to station ground

From zone + OUT to + IN

From -OUT to - IN

Sprinkler Tamper Switch Circuit (zone 8)

From + to station ground

From - to station ground

From + to - across circuit

3.3K ohms

Infinity

Infinity

Infinity

Infinity

Infinity less than 50 ohms

Less than 50 ohms

Infinity

Infinity

560

ohms

Style Y Notification Appliance Circuit (each signal circuit)

From + to station ground

From - to station ground

Resistance across circuits

In one direction

In opposite direction

22

Technical Manuals Online! - http://www.tech-man.com

Infinity

Infinity

1 OK ohms

Less than 200 ohms

Style Z Notification Appliance Circuit (each signal circuit)

From + to station ground

From - to station ground

From + OUT to + IN

From -OUT to - IN

Resistance across circuits

In one direction

In opposite direction

Infinity

Infinity

Less than 50 ohms

Less than 50 ohms

Infinity

Less than 200 ohms

STEP #5

RE-MOUNTING ELECTRONIC COMPONENTS IN BACK BOX

Note: Care must be taken to avoid contact and potential static damage to the printed circuit boards during the following procedures. A grounding wrist strap is recommended. l

Make sure system ground wire is attached to the green lug screw in the back box.

Re-mount the transformer first. l

Re-mount electronic sub-assemblies complete with rails using screws provided in the same relative box position as they were shipped from the factory (see F.W. diagrams 641-669). l

Connect ALL cables and wiring harness in original locations as shipped from the factory and previously marked during back box installation.

23

Technical Manuals Online! - http://www.tech-man.com

STEP #I6

TERMINATIONS OF SYSTEM WIRING

AT THE 4002 CONTROL PANEL

Note: Terminate all system wiring as specified in the Field Wiring Diagrams (641-669). Refer to sheets and figures listed below.

SHEET # FIG. # a. Initiating device (zone) circuits l

Style B l

With zone disconnect/suppressor board

61 7

10

N/A

N/A l l l l

Style D with 4-wire detectors.

With zone disconnect/suppressor board.

2 unit, Class B suppression.

4 and 6 unit, Class B suppression. b. Notification appliance (signal) circuits l l

Style Y

Style Z c. Control relay circuits l l l l

From AUX and TBL relay contacts

(on CPU board).

From AUX relay contacts

(on AUX relay board).

From relay contacts (on relay boards).

10 Amp relay module. d. Annunciator output circuits l

LED annunciators (with remote trouble, acknowledge or reset). l l

LED annunciators (w/o remote trouble, acknowledge or reset).

Incandescent lamp annunciators. l l l

A Auxiliary

B Auxiliary

D Auxiliary e. City circuit l

Connections, programming, Reverse polarity,

Local energy, Shunt, Form C. f. Special zone inputs l

Coded input on zone 1. l l

Waterflow switch on zone 7.

Sprinkler tamper switch on zone 8. g. Connect Power to system l

AC Power. l l

System Batteries.

4 unit Expansion Power Supply. l l l

6 unit Expansion Power Supply.

To silence signals press the TROUBLE and SYSTEM

RESET push buttons.

Use the harnesses provided with the system.

81 9

11/12

24

25

13115

14

16

16

17

26

18 i8

19

32

33

34

20

21

21

21

22

22

29

30

N/A

N/A

N/A

N/A

14

15

19

8

9

9

20

21

N/A

N/A

16

17

18

N/A

11

11

12

N/A

N/A

N/A

24

Technical Manuals Online! - http://www.tech-man.com

h. 2120 Connections l

Transponder.

. interface Module (set DIP switch SW1 -8 OFF)

23

28

N/A

N/A i. SCUIRCU Wiring (See Note 3) 27 NiA j. Fan Control Module (See Note 3) 31 N/A

Notes: 1. Wire devices according to Field Wiring Diagrams 841-687.

2. If the system continues to display trouble, follow the troubleshooting procedures on page 12.

3. DIP Switch SW3 on the CPU module must be set in accordance with Table 2 on page 26. A wire length chart is found on page 40.

STEP #7

SETTING PROGRAM DIP SWITCH SWl, SW2, AND SW3

DIP Switch, SW1 and SW2 are used to select a variety of functions which are required for alarm operations. The locations of these switches are shown on Figure 4, page 15, or Field Wiring Diagrams 841-669, sheet 2.

Information on all basic programmable functions can be found on pages 25 through 30.

The installer must select the alarm operations/functions required for each system installation. Use a pointed, non- metallic object for selecting switches. See Figure 11 below for details of DIP Switches SW1 and SW2. l

Press SYSTEM RESET after making changes to SW1 and SW2 settings.

Use the information in Table 1, on next page, (also shown on sheet #2 of wiring diagrams) to determine exact

DIP Switch settings required for this installation.

DIP switch SW3 is used for supervisory modules connected to the serial annunciator port on the CPU module

(TB4 COM and REC). Use the information in Table 2, on next page, to determine required settings for this installation.

Note: When shipped, the system contains NO special programmed functions and normal operation is general alarm.

SW14 SHOWN-

IN “OFF”

POSITION

Figure 11 - DIP Switches, SW1 and SW2

Normal Operation: The following represents normal system operation when DIP Switch, SW1 and SW2 are set to the ON position. a. The activation of any alarm initiating device on any zone immediately causes all signals throughout the system to operate continuously. b. Pressing the “ALARM SILENCE” push button immediately stops all signal operations. c. All push buttons and switches in the fire alarm panel are enabled.

25

Technical Manuals Online! - http://www.tech-man.com

STEP #7 cont.

PROGRAMMING BASIC SYSTEM FUNCTIONS

VIA DIP SWITCH PACKAGES SW1 AND SW2

TABLE 1

DIP Switch SW1

SWl-1 = Alarm Verification

On.....Normal operation

Off.. . ..Alarm Verification

SW1 -2 = Coded Input (Zone 1)

On.....Normal operation

Off.....Coded input on Zone 1 (cut JWll)

SW13 = Waterflew

On.....Normal operation

Off.....Waterflow on Zone 7 (signal 2 not silencable)

SWl-4 = Sprinkler Supervision (Tamper)

On.....Normal operation

Qff.....Sprinkler supervision on Zone 8

SW1 -5 = Time Limit Cut Off

On.....Normal operation

Off.....Signal Cutout after 10 minutes

SW1 -6

On

Off

On

Off

SW1 -7 = Silence Inhibit

On.....Normal operation

On.....One minute signal silence inhibit

Off.....Three minutes signal silence inhibit

Off.....Five minutes signal silence inhibit

SWl-8 = 2120 Connection

On.....Normal operation

Off.....21 20 connection is present in system

DIP Switch SW2

SW2-1 = Svstem Test

On.....Normal operation

SW2-2 = Manual Evacuation

On.....MANUAL EVAC switch enabled

Off.....MANUAL EVAC switch disabled

SW2-3

On

Off

On

Off

On off

On

Off

SW2-4

On

On

Off off

On

On

Off

Off

SW26 = Sional Codinq

On.....Normal operation

On.....March time

On.....Slow march time

On.....Temporal coding

Off.....Simple coding

Off.....California code (one minute)

Off.....Califomia code, three minutes

Off.....Califomia code, (five minutes)

SW2-6

On

Off

On

Off

SW2-7 = Selective Signallinq

On.....Normal operation

On.....March time on signal circuit 1 until reset

Off.....Signal circuit 1 on steady until reset

Off.....Signal circuits 1 and 2 on steady until reset

SW2-8 = Expanded Simplex Proarammina IESP)

On.....Normal operation

Off.....ESP program mode

SElTlNG DIP SWITCH SW3 FOR SERIAL PORT SUPERVISION

TABLE 2

DIP SWITCH SW3

Number of Mcdules tn System

.Swdch

Number

SW3-1

SW3-2

SW3-3

SW3-4

0 I 2 3

4

5 6 7 8 9 10 11 12 13 14 15

ON OFF ON

ON ON

OFF ON OFF ON OFF ON CFF ON OFF ON

OFF OFF ON ON OFF OFF ON ON 1 OFF OFF ON

ON ON ON ON [ OFF OFF OFF 1 OFF ON [ON 1 ON ON

OFF ON OFF

ON 1 OFF , OFF

OFF OFF 1 OFF 1 OFF

ON ON ON ON 1 ON ON

ON 1 ON OFF 1 OFF 1 OFF OFF OFF OFF 1 OFF (OFF

STEP #7 cont.

I

*

= 3

SUPERVISED

(SW31

ADDRESS ON COMM LINE.

FAN

CONTROL

Notes:

1. Normal

Operation

in the ON position.

- Indicates that a special function is NOT selected and DIP Switches, SW1 and SW2 are

2. For a complete description of each system function, see pages 27 through 30.

3. The “SYSTEM RESET” switch must be pressed after DIP switches are set.

4. See page 15 for location of DIP Switches SW1 , SW2 and SW3.

BASIC DEFINITIONS OF DIP SWlTCH SELECTABLE SYSTEM FUNCTIONS l

Norma/ Operation:

The following represents normal system operation and all DIP switches are set to the ON position. a. The activation of any alarm initiating device on any zone immediately causes all signals throughout the system to operate continuously. b. Pressing the ALARM SILENCE push button immediately stops all signal operation. c. All push buttons and toggle switches on the panel’s front are enabled. l

Alarm Verification (DIP Switch SW&7 OFF)

The alarm verification feature is used to reduce unwanted alarms in smoke detectors. It allows smoke detectors to be verified while residing in the same zone with heat detectors and manual stations that are riot verified.

Operation is as follows: a. If a smoke detector senses an alarm, the 4002 will start a 30 second timer and ignore the alarm. b. At the end of the 30 second timer, if no other zones or contact devices have alarmed, the zone is reset for

5 seconds. c. After power is restored to the detectors, the 4002 begins a 120 second confirmation period. If, during this time, the detector re-alarms‘(or another detector alarms), the signals are sounded and alarm functions occur as programmed.

27

Technical Manuals Online! - http://www.tech-man.com

STEP #7 cont. d. If no alarms occur during the 120 second confirmation period, the 4002 returns automatically to the normal mode.

/Vote: If, any time during the alarm cycle, an alarm is sensed from another zone or contact device (heat detector or manual station), the 4002 alarms immediately. l

Coded Input on Zone 1 (DIP Switch SWl-2 OFF and JW77 Cut)

The coded input operation is used for either coded stations or coded systems. When selected, this feature allows the 4002 to connect to devices that input a specific code for their location. These devices must be wired to zone 1. The coded input feature bypasses the normal latch circuit on zone 1 and allows the signals to foilow the input code. All other alarm functions remain the same (e.g., auxiliary relays and city circuit operation). The coded input signal takes priority over other signals while the code device is pulsing. The 4002 will turn priority over to the other alarm functions after 30 seconds of silence from the coded input device. l

Waterflow on Zone 7 (DIP Switch SWl-3 OFF)

Zone 7 may be used for connecting to the waterflow contacts on a sprinkler system. When selected, zone 7 will monitor normally-open waterflow contacts for closure to indicate an alarm. Notification appliance circuit 2 will turn on and cannot be silenced as long as the waterflow contacts are closed. When the flow contacts are restored to normal, notification appliance circuit 2 can then be silenced by the system reset push button. l

Sprinkler Tamm?r Switch Su,pervision on Zone 8 (DIP Switch SWl-4 OFF)

By setting DIP Switch SWl-4 to off, Zone 8 may be used for monitoring the position of sprinkler gate valves. It can be connected to normally-closed sprinkler-tamper contacts. The 4002 allows up to five normally-closed con- tacts, and the circuit is supervised for opens and shorts. When a contact opens, the following sequence occurs.

1. Zone 8 Alarm LED flashes.

2. The Auxiliary Trouble Relay and Piezo activates until silenced.

3. Activating the ALARM SILENCE push button silences the trouble circuit.

4. Restoring the valve to the normal position causes the zone LED to extinguish.

Notes:

1. The 4002 can be reset while a supervisory circuit is still open (not normal). If the circuit is still open when reset, the sequence will again start at step 1 above.

2. ESP must be provided if operation of an Auxiliary Alarm Relay from Zone 8 is required. l

Sianal Cutoff Time Limit After 10 Minutes (DIP Switch SW14 OFF)

The signal cutoff feature provides an automatic signal silence function. When an alarm occurs, the signals will sound for 10 minutes and then be silenced.

Note. If the signal silence inhibit feature (see below) is selected in conjunction with this option, the signals will automatically silence 10 minutes after the conclusion of the signal silence inhibit time.

STEP #7 cont. l

Sianal Silence Inhibit (DIP Switches S WI-6 and S WI-7 OFF)

The signal silence inhibit feature prevents the operator from silencing the signals until the inhibit duration expires.

Available inhibit durations are:

No delay (normal operation)

1 Minute delay

3 Minutes delay

5 Minutes delay l

2120 Connection is Present in System (DIP Switch SWl-6 OFF)

An option that, when selected, allows the Control Panel to communicate with a Simplex 2120 Multiplex System via the 2120 Communication Module. l

Walk Testnvr Mode (DIP Switch SW2-7 OF9

When selected, the following occurs: a. The system Trouble LED illuminates. b. The city alam relay is bypassed. c. The auxiliary alarm relays are bypassed.

Note: The auxiliary relays connected to the annunciator outputs still follow the zone alarm LEDs. d. The system is ready for a Walk TestTM (see page 9)

IMPORTAM: The system DOES NOT provide fire protection when in the Walk TestTM mode. l

MANUAL EVAC Switch Enabled or Disabled (DIP Switch SW2-2)

The “manual evacuation” switch is standard on all systems.

When enabled, (SW2-2 ON) activating the switch will turn on all indicating appliance circuits while leaving the auxiliary alarm relays and city circuit in their normal position. The manual evacuation signal is terminated by pressing either the signal silence or system reset switch.

When disabled, (SW2-2 OFF) the switch has no effect on the system whatsoever.

8 Signal Coding (DIP Switches S W2-3, S W2-4 and S W2-5)

The signal coding option uses three DIP switch positions to allow 8 different selections. Only one code selection can be used. This feature is common to the operation of all indicating appliances in the system. The coding choices are: a.

Normal operation

- When selected, the signals will sound continuously. b. March

time

- When selected, the signals will sound a march time code of

120

beats a minute.

c. Slow march time

-When selected, the signals will sound a march time code of 20 beats a minute.

29

Technical Manuals Online! - http://www.tech-man.com

STEP #7 cont. d.

Temporal code

- When selected, the signals will repeat a code pattern ccnsisting of 0.5 set on, 0.5 set off,

0.5 set on, 0.5 set off. 0.5 set on, 2.5 set off. e.

Simple coding-When

selected, the signals will sound a code that represents the area in alarm. f.

California code (one minute)

- When selected, the signals will sound a special code used in L.A. county for one minute and then stop.

g. Caiifomia code (three minutes)

- When selected, the signals will sound the above code for three minutes and then stop. h.

California code

(five

minutes)

- When selected, the signals will sound the above code for five minutes and then stop. l

Selective Signal Circuit Operation (DIP Switches SW-6 and S W2-7)

The selective signal circuit feature provides one of four operating modes for notification appliance circuits 1 and 2 as follows: a.

Normal operation

- Both signal circuit 1 and signal circuit 2 silence when the alarm silence switch is activated. b.

March time on signal circuit I until reset -

Causes notification appliance circuit 1 to code a march time signal while the other notification appliance circuits follow the coding selection DIP switch settings. Notification appliance circuit 1 remains on until the system is reset whife all other appliance circuits can be silenced by the alarm silence switch. This mode of operation can be used to flash incandescent lamps after the audible signals have been reset.

c. Signal circuit 7 on steady until reset -

Causes notification appliance circuit 1 to operate continuously while appliances in other circuits follow the coding selection DIP switch settings. Notification appliance circuit 1 remains on until the system is reset while all other appliance circuits can be silenced by the alarm silence switch.

This mode of operation can be used to flash strobe lamps after the audible signals have been silenced. d.

Signal zones 1 and 2 on steady until reset

- Same as the above, except that it also applies to signal circuit 2. l

ESP Program Mode (DIP Switch S W2-8)

The ESP program mode allows qualified Simplex personnel to custom-program the system by entering ESP

(Expanded Simplex Programming) equations into system memory.

IMPORTANT

DIP switch SW2-8 must

Programming procedures).

never

be lett in its OFF (Program) position (except when performing ESP l

When DIP switch SW2-8 is in its On (Normal) position, the panel functions as a fire control unit - a device which provides fire protection: when DIP switch SW2-8 is in its Off (Program) position the panel functions as a program entry device - a device which provides

no

fire protection.

STEP ##8

WALK TEST’-’

Perform a complete Walk Test TM to ensure proper system operations. These procedures are located on page 9 in this manual.

STEP #9

RE-MOUNTING RETAINER AND DOOR a. Mount the lock bracket to the back box. b. Insert the lip located on the lower portion of the retainer (interior door) over the lip at the bOttOM of the back box. c. Squeeze the two black plastic locking tabs at the top of the retainer, then insert them into the two slots at the top of the back box. This will secure the retainer to the back box. d. Place the door on the two back box hinges. The door should open freely to allow access to operator controls.

1 IMPORTANT 1

: e. Ground the door by attaching the green ground wire and the ground screw lugs to both the door and the back box.

STEP 10.

CUSTOMER INFORMATION

Provide the owner with a complete system orientation to include operating instructions. These procedures start on page 3 in this manual. Leave all documentation with the customer including electrical drawings of the system and 4002 Field Wiring Diagrams.

31

Technical Manuals Online! - http://www.tech-man.com

GLOSSARY OF 4002 FIRE ALARM SYSTEM TERMS

A/arm Verification Option:

A field-programmed option tha? causes the CPU to verify (double-check) all atarM initiations originated by SMOke detectors before sounding the signals.

Annunciator;

A reMotely-located, electrically-powered display, separate from the control panel, containing LEDs or lamps to indicate the status of the fire aiarm system.

Auxiliary (AUX) Relays:

Control relays that normally energize during alarm conditions, and that are used to either apply power to or remove power from other equipment during an alarm condition. An auxiliary relay can also be programmed for activation during a trouble condition rather than an alarm condition.

City Remote

Station Connection Circuit:

Circuitry contained on the CPU board, which allows the 4002 fire alarm system to be tied either indirectly (via leased telephone lines) or directly (via a shunt or local energy master box) to a municipal fire station.

C/ass A Cireuitr

An initiating device (Style D) or notification appliance circuit (Style Z) within which all components remain fully functional even though a single open or ground exists in the circuit.

C/ass

8

Circuit:

An initiating device (Style B) or notification appliance circuit (Style Y) within which some or all components May be disabled when a single open or ground exists in the circuit.

CPU

(Centrat Processing Unit):

That portion of the fire alarm panel which processes alarm and trouble information received from throughout the system, and acts on that information in an approprlate Manner.

CPU Board:

A Panel-Mounted Module consisting of (among other things) the CPU itself, eight zone [circuit]

Monitors, two signal [circuit] Monitors and two AUX relays.

End-of-Line (E.O.L.)

Resistor: A resistor installed at the electrically farthermost point in a signal or zone circuit.

Fan Control Module:

A panel-mounted Module that consists of manual switches which allow fan or damper control circuits to be turned on, turned off, or operated automatically.

Fire Alarm Control Pane/:

The portion of the fire alarm system which provides the power and contains the circuitry needed for system operation.

Notification Appliance (Signal) Circuit:

A circuit consisting of one or More notification appliances.

Notification Appliance (Signahg

Device): A device which produces an audible and/or visual signal in response to a fire condition. l

Horn, bell, chime, flashing light, etc.

hifiating

Device: A Manual or automatic device which, when activated, initiates an alarm. l

Pull station, heat or smoke detector, waterflow switch, etc.

Initiating Device (Zone) Circuit:

A circuit consisting of one or more initiating devices.

Local Energy Master

Box: A municipal fire department connection box, Mounted external to the panel, that uses electrical energy from the fire alarm panel to energize its (the master box’s) electromagnetic tripping mechanism.

Power Supply Module:

That portion of the fire alarm panel which provides the power needed to operate all panel modules, as well as that needed to operate all electrically-powered initiating devices and all notification appliances.

Shunt Master Box:

A municipal fire department connection box, mounted external to the panel, that uses electrical energy from the municipal fire alarm system to energize its (the master box’s) electromagnetic tripping mechanism.

Signal Module:

A panel-Mounted Module which supervises two notification appliance (signal) circuits.

Silence lnhibif Option:

A field-programmed option which, when entered, prevents all alarm-notification appliances from being silenced, and the system from being reset, until the delay’s duration expires.

Supervision:

The continuous electrical checking of fire alarm circuits and components for troubles (opens and, in some cases, shorts). l

For example, 4002 signal circuits are supervised for both opens and shorts, while 4002 zone circuits are supervised for opens only (a zone circuit short causes an alarm condition).

Zone Module:

A panel-mounted Module containing the circuitry needed to supervise either four or eight zone circuits for both trouble and alarm conditions.

APPENDIX A

ESP Programming Option

NOrMally the 4002 is used as a general alarm system. Activation of any monitor point will energize all signal circuits, relays (to include the city relay), and the piezo. A number of DIP switch selectable functions may also be used to enhance the general alarm operation.

When more sophisticated project specific operations are required, Expanded Simplex Programming (ESP) Option must be installed. This option allows the operation of the system to be tailored to meet your specific requirements and perform up to 23 additional special operations. These special operations are defined by the user and may be modified at any time by qualified SIMPLEX personnel. ESP programs are defined for each desired operation, then programmed at the local SIMPLEX branch office. SIMPLEX personnel must install the ESP option, then test each ESP programmed operation.

Once programmed, the system will handle its ESP controlled inputs and outputs differently, while the rest of the system will operate general alarm. SIMPLEX personnel will demonstrate the operation and provide detailed instructions on each ESP programmed function. These tailored instructions are not included in any reference manual and must be used as required. a. Selective Signal Circuit Operation

One or more selected monitor point inputs will act upon one or more signal output circuits,

Selective signal operations may be used for various applications.

Three specific selective signal operations are as follows:

1. Selective signals by floor - Evacuation signals sound on the floor of the alarm initiation; other signals may sound on other floors.

2. Selective signals by zone - Evacuation signals sound in the zone or area of the alarm initiation; other signals may sound on other areas.

3. Floor above and floor below - Evacuation signals sound on the floor of the alarm initiation, and on the floor above and the floor below the floor of the alarm initiation; other signals may sound on other floors. b. Selective Relay Control Operation

One or more selected monitor point inputs will act upon one or more general purpose output relay control circuits. c. Selective Fan/Damper Control Relay Operation

One or more selected monitor point inputs will act upon one or more relay circuits which control fan/damper circuits.

33

Technical Manuals Online! - http://www.tech-man.com

d. Selective Door Holder Reiay Control

One or more selected monitor point inputs will act upon one or more relay circuits which control door holder circuits. e. Selective Bypass Control Switch Operation

One or more selected inputs (monitor or control) will selectively bypass control circuits. f. Selective Switch Operation

One or more selected switch inputs will selectively control output circuits. g. Multiple Tamper Zones

One or rhore selected monitor point inputs (connected to sprinkler gate valves, N/O or N/C) which activate specific tamper signals. h. Stage l/Stage 2 Operation or Presignal Operation

Stage l/Stage 2 - Zone activation alerts in-house personnel and starts a delay timer. If the timer is not reset before the delay expires, evacuation signals sound automatically.

Presignal - Zone activation alerts in-house personnel. A second (manual) action is required before evacuation signals sound. i. Cross Zoning

A method of operation by which two or more monitor points must be activated before an output action can occur. j. Timing Functions

One or more selected monitor point inputs may cause a selected output to activate fur a predetermined time period or after a time period elapses. k. Master Code

One or more selected monitor point inputs will cause a selected coded pulse pattern to be outputted to selected control outputs. (Usually the notification appliance circuits or city circuit).

I. Non-Alarm Monitor Point Operation

A method of removing one or more selected monitor points from the 4002 general alarm program. The monitor point alarm LED will flash when activated, but no control outputs will occur unless specified in an

E.S.P. equation.

M. Non-latching Monitor Point OperatiOn

A method of allowing one or more selected monitor point to “track” a peripheral device contact closing or opening. l

Only non-alarm contacts should be non-latching. n. Piezo Signal Operation

The ability to control the Piezo selectively using any function statement in E.S.P. o. AC Power Fail (Control)

The ability to control any output during an AC power loss or brownout condition at the 4002 panel.

p. 2120 Non-Default Operation

The 2120 communicator Module has a standard operation consisting of:

1. Zone alarm and trouble reporting to the 2120 CPU.

2. The ability for the 2120 to initiate 4002 system reset, alarm silence, trouble silence and manual evacuation.

Should an operation other than the default program be required, an ESP equation must be written and the data base may have to be changed. q. RCU Switch Non-Default Operation

The 4602 Serial Annunciator RCU switches have a standard default operation consisting of:

1. System Reset

2. Alarm Silence

3. Trouble Silence

4. Manual evacuation

Should an operation other than the default program be required, an ESP equation must be written and the data base must be changed. r. SCU Point Matrix (Zone Grouping)

A method by which zones may be grouped in ESP Memory points and assigned to a specified 4602 Serial

Annunciator LED. s. Elevator Recall w/Alternate Floor

A method that alters the recall of the elevator to ground level during an alarm situation. If the alarm is initiated from ground level the elevator may be recalled to an alternate floor. t. System Reset (Special Operation)

A Method of changing the state of an output circuit when the system is reset. u. Point Sensing

A method of changing an initiating device circuit (zones) to detect inputs other than normally open contact devices. (i.e., current limited and normally closed devices). v. PNIS Zone Coding

A specified pulsed signal is sounded by the indicating appliances to audibly indicate where the alarm was initiated. ESP Data Base and ESP Equations are used to define the type of codes and their use.

35

Technical Manuals Online! - http://www.tech-man.com

APPENDIX B

FAN CONTROL MODULE (Figures 12 and 13)

A. Features

A 4002 system may include up to four fan control

MOdUieS, each of which consists of two fan control circuits.

Each fan control Module includes: l l l l l l l

Two 3-position Maintained toggle switches (SW2 and SW3).

Two DIP switch packages (SW1 and SW4).

Two P connectors (Pl and P2).

Two red LEDs (fan OFF).

Two green LEDs (fan ON).

Two yellow LEDs (fan circuit TBL).

One terminal block (TBl).

SW2

Yebl&ED sw3.

6. Panel Connections

Pl = 24VDC input power (2-wire harness) from any of the following:

Yellow LED”

(TBL)

P6 on CPU Module

P2 of another fan control Module

P3 of a signal expansion module

P2 on a 2120 interface MOdUle

Pl’ r‘s1

P2 = 24VDC output power

Figure 12

TBl-1 = REC (from TB4-20 [REC] on the CPU [or from TBl-1 on another fan control Module]).

TBl-2 = COM (from TB4-21 [COM] on the CPU [or from TBl-2 on another fan control Module]).

C. Field Connections

hen LED

(Fan ON)

Red LED

:Fan OFF)

&s! LED

[Fan OFF)

-P2

TBl-3 = ON1 (OV out to pick fan 1 ON relay).

TBl-4 = OFF1 (OV out to pick fan 1 OFF relay).

TBl-5 = ON2 (OV out to pick fan 2 ON relay).

TBl-6 = OFF2 (OV out to pick fan 2 OFF relay).

TBl-7 z TK 1 (+24 [feedback] from 1 st fan circuit via vane, sail or pressure differential switch in 1 st air duct).

TBl-8 = TK2 (+24 [feedback] from 2nd fan circuit via vane, sail or pressure differential switch in 2nd air duct).

D. Switches

DIP

Switch SW1

Switches SWl-1 and SWl-2 (Control the red and green LEDs.)

SWl-1 OFF = Green LED lit when +24 present on TBl-8.

Red LED lit when +24 absent from TBl-8.

SWl-1 ON = Green LED lit when SW2 in ON position.

Red LED ON when SW2 in OFF position.

SW1 -2 OFF = Green LED lit when +24 present on TBl-7.

Red LED lit when +24 absent from TBl-7.

SW1 -2 ON = Green LED lit when SW3 in ON position.

Red LED lit when SW3 in OFF position.

Switches SWl-3 and SW1-4 (Functions depend on whether or not the 4002 has ESP.)

If the panel

lacks

ESP, the module responds to the issuance of any alarm message as follows:

SWl-3

ON

ON

OFF

OFF

SW1 -4

ON

OFF

ON

OFF

= Leaves fans in their current state.

= Turns both fan circuits OFF.

= Turns both fan circuits ON.

= Turns fan circuit 1 ON, turns fan circuit 2 OFF.

If the panel has ESP, switches SW1 -3 and SW1 -4 identify the fans under the module’s control as follows:

SW1 -3 SW1 -4

ON

ON

OFF

OFF

ON

OFF

ON

OFF

=

=

Module controls fans 1 and 2.

Module controls fans 3 and 4.

= Module controls fans 5 and 6.

= Module controls fans 7 and 8.

Note: ESP allows the CPU to turn individual fans ON or OFF, depending on which of the system’s zones is in alarm.

Switches SWl-5 thru SW1-8 (Set the fan control module’s address.)

SW1 -5

ON

ON oi

ON

---

+ urr

OFF j ON

I h

OFF 1 OFF / 3

I

ON

OFF ON I ON 4

I

ON

I

1

ON 1 OFF 1 ON 1 OFF / 5

I

Layout,

Switch SW1

I

OFF ON

Switch SW2 (Position determines the presence or absence of OV on terminals TBl-3 and TBl-4)

Up position = Applies OV to TBl-3 (ONl), energizing fan control relay Kl .

Center position = Presence or absence of OV determined by the fan control module’s microprocessor.

Down position = Applies OV to TBl-4 (OFFl), energizing fan control relay K2.

Note: Relays Kl and K2 must mount within 3 ft. of 1st fan motor.

37

Technical Manuals Online! - http://www.tech-man.com

Switch SW3

(Position determines the presence or absence of OV on terminals TBl-5 and TBl-6)

Up position = Applies OV to TBl -5 (ON2), energizing fan control relay K3.

Center position = Presence or absence of OV determined by the fan control module’s microprocessor.

Down position = Applies OV to TBl-6 (OFF2), energizing fan control relay K4.

Note:

Relays K3 and K4 must mount within 3 ft. of 2nd fan motor.

DIP Switch SW4

(Allows for supervision of a fan control relay’s wiring during the relay’s de-energized state.)

SW4-1 = OFF to supervise wiring to ON1 fan control relay.

ON if circuit lacks ON1 fan control relay (or if supervision not wanted).

SW4-2 = OFF to supervise wiring to OFF1 fan control relay.

ON if circuit lacks OFF1 fan control relay (or if supervision not wanted).

SW4-3 = OFF to supervise wiring to ON2 fan control relay.

ON-if circuit lacks ON2 fan control relay (or if supervision not wanted).

Layout,

Switch SW4

OFF l-FN

2cn

3l sw4-4 = OFF to supervise wiring to OFF2 fan control relay.

ON if circuit lacks OFF2 fan control relay (or if supervision not wanted).

4m

Note:

If an SW4 switch is turned OFF, the appropriate TBL (yellow) LED on the fan control module illuminates - and the 4002 panel indicates trouble - when an open exists in the fan control relay circuit.

E. DIP Switch SW3 on the CPU Module (Figure 4 - page 15)

Set the switches on switch package SW3 as shown below sw3-1

SW3-2 sw3-3 sw3-4

Number of devices (SCUs/RCUs, fan control units, etc.) in system

3 4 5 6 7 8 9 10 11 12 ,131

ON /OFF/ON IOFFION

ON /ON /OFF/OFF\ON

IOFFION (OFFION

/ON ~OFF(OFF/ON

IOFF~ON /OFFION

ION JoFF/OFF(ON

/OFF/ON IOFF

(ON /OFFjCFFj

ON /ON ION ON

OFF I OFF / OFF OFF ON ON ON ON OFF OFF OFF OFF

I

ON / ON ON ON ON ON / ON

ON

OFF OFF OFF OFF OFF OFF OFF / OFF

Number of Serial

Devices = 3

I

0

Address on Comm Line

I

1

I I

I

1

2

4200

Panel

SW3 cl

---/-%EC

-COM-

- A

RCU

F.

Interconnection Diagram

O 1 I-

NOTE 2,3

FACTORY-

WIRED

I

--I

A

\ \

‘FEEDBACK

CKT

1

,

L

I

I

AIR DUCT mm------ -l

I

1

NOTES:

1. FAN CONTROL RELAYS MUST MOUNT WITHIN 3 FT. OF FAN. r

2. CONNECTIONS TO THE COILS OF Kl AND K2 FAN CONTROL 1

-------

RELAYS SHOW THE WIRING REQUIRED FOR ON/OFF FAN &;.,foL

CONTROL, WITH A STATUS CONTACT (VANE,

SAIL OR I

PRESSURE DlFFERENTlAL SWITCH) THAT CLOSES WHEN THE L

----------

FAN RUNS. ACTUAL SYSTEMS MAY NOT REQUIRE ALL OF

THESE FEATURES, WIRE ONLY AS REQUIRED.

OFF cl

3. ALL WIRING IS SUPERVISED, EXCEPT ME WIRE THAT

CONNECTS THE STATUS CONTACT TO TERMINAL TKl (TBl-7).

-

1

;

I f

I

4. THE MODULE CONTAINS TWO IDENTlCAL FAN CONTROL

OUTPUTS. WlRE ON2,OFF2, AND TK2 TO OPERATE THE SAME

AS THE CIRCUIT SHOWN.

5. ELECTRICAL RATINGS:

ONl, OFF1 , ON2,OFF2

TKl, TK2

ANN+

= 150 mA @ 24 VDC

= 24 VDC @ 0.1 mA

= 1.2 Amps @ 24 VDC

6. FAN CONTROL RELAYS Kl AND K2 MUST BE 24VDC THAT

OPERATE BETWEEN O-1 50 mA.

7. ALL CONDUCTORS MUST TEST FREE OF GROUNDS. f

Figure 13

J

Ll L2 L3 N

G. Wire Length Chart

in Feet

(for a-Wire Fan Control Relay Circuits)

I

0.050

0.075

0.100

0.150

0.200

0.300

0.400

0.500

0.600

0.700

0.800

0.900

1.000

1.100

1.200

Total

Current . in Amps

Wire Size

#12 i #I4 / #16 ; #18

I

10,000 i 10,000 j 6,716 / 4,225

10,000 j 6,923 ! 4,477 i 2,816

8,437 ! 5,192 / 3,358 : 2,112

5,625 ! 3,461 ; 2,238 i 1,408

4,218 / 2,596 j 1,679 : 1,056

2,812 ! 1,730 ! 1,119 j 704

2,109 / 1,298 i 839 j 528

1,687 i 1,038 ; 671 1 422

1.406 ( 865 \ 559

i

352

11205 i

1,054 /

741 j 479 j 301

649 1 419 j 264

937 / 576 i 373 / 234

843 /

766

519 / 335 j 211 i 471 I 305 I 192

703 1 432

i

279 i 176

Figure 14

JTERY TESTING INFORMATION neral information sealed lead-acid batteries in fire alarm service should be tested annually.

Replace all sealed lead-acid batteries that have been in service for four or more years.

It is recommended that a battery tester made specifically for checking sealed lead-acid batteries be used.

Such a tester is available under Service Part No. 553-602. battery tester is unavailable, the “voltage response test” described below can be used to detect batteries with y low capacity or shorted ceils.

DORTANT: A defective battery charger circuit can cause battery failure. Check the condition of the battery charger when either a battery tester or a voltage response test reveals weakened batteries. sting

Connect a digital voltmeter across the battery.

Connect the appropriate sized resistor(s) (see Chart 1 ) across the battery’s terminals for the listed test time.

Record the end voltage reading.

Treat the battery as described in Chart 2.

CHART 1

VOLTAGE AMP HR 1 TESTTIME

12 5.2 a.0 50 380-008 (2 in parallel) 2 Seconds

12 6.2 6.0 50 380-031 1 2 Seconds

I

12 I a I 4.5 / 50 / 380-031 (adi to 4.5 Ohm) 1 2 Seconds

I

12 I 10 I 4.0 I 50 / 380-031 (adi to 4 Ohm) 1 2 Seconds

I

12 I ia

I

2.0

I

100 I 380-031 (3 in parallel) / 2 Seconds

I

12 I 20

I

1.5

I

100 I 382-090 (2 in parallel) 1 2 Seconds

12 33 / 1.0 150 382-090 (3 in parallel) 1 2 Seconds

6’

12

50

110

(

RESISTOR ’ ,,,,ATTs

(OHMS)

.

1 .o

150

150

PART NUMBER

AND DESCRIPTION

382-090 (3 in parallel)

382-090 (3 in parallel)

4 Seconds

4 Seconds

* Test 2 batteries in series for 12V l l l

CAUTION * l l

Resistors will get hot during test!

3

Use 12AWG wire for battery-to-resistor hookup.

41

Technical Manuals Online! - http://www.tech-man.com

CHART 2

IF END VOLTAGE READING OF BAlTERY IS:

11

.av

or more

11.7v to ll.OV

10.9 or less

l

Retest battery after charging.

INSTRUCTIONS

Put in Service

Charge Battery

l

Discard Battery

Note 1:

Discard if battery has been in service for four or more years (dispose of properly).

Note

2: Dispose of properly.

42

Technical Manuals Online! - http://www.tech-man.com

Technical Manuals Online! - http://www.tech-man.com

Technical Manuals Online! - http://www.tech-man.com

Technical Manuals Online! - http://www.tech-man.com

Ed394

BSimplex

Simplex Time Recorder Co., l

Simplex Plaza l

Gardner, Massachusetts 01441-0001 U.S.A.

FA4-21-151

(574-009) 1

Technical Manuals Online! - http://www.tech-man.com

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • 4002 is designed to be easy to use, with simple controls and clear indicators.
  • It can be used in a variety of applications, from small businesses to large commercial buildings.
  • The 4002 is reliable and durable, with a long history of proven performance.

Related manuals

Frequently Answers and Questions

What are the different types of alarm conditions that the 4002 can handle?
The 4002 can handle a variety of alarm conditions, including fire, burglary, and medical emergencies.
What are the different types of trouble conditions that the 4002 can handle?
The 4002 can handle a variety of trouble conditions, including power failures, system malfunctions, and device failures.
How do I test the 4002's battery?
To test the 4002's battery, simply press the "Battery Test" button on the control panel.
Download PDF

advertisement