Tripp Lite SMART5000TEL3U Specification


Add to my manuals
5 Pages

advertisement

Tripp Lite SMART5000TEL3U Specification | Manualzz

Tripp Lite

1111 West 35th Street

Chicago, IL 60609 USA

Telephone: +(773) 869 1234

E-mail: [email protected]

Model #: SMART5000TEL3U

SmartPro 5kVA Line Interactive Sine Wave UPS, SNMPWEBCARD option, 3U Rack/Tower, USB, Serial, EPO,

208V

Highlights

5kVA / 5000VA line interactive 3U rack/tower UPS; Sine wave output

208V nominal output during inputs of 174-282V; Supports 600VA 120V output

USB, Serial, EPO & optional SNMP/Web card monitoring options

97% line-mode efficiency; Hot-swappable internal batteries

NEMA L6-30P input; 2 NEMA 5-15R, 2 L6-20R & 1 L6-30R outlets

Description

Tripp Lite's SMART5000TEL3U intelligent, line interactive UPS protects server, networking and telecommunications equipment from blackouts, voltage fluctuations and surges in a compact rackmount housing. Completely self-contained UPS system occupies only 3 rack spaces (3U) in a standard 19 inch rack, making this model one of the smallest 5kVA UPS systems available. Included accessories support mounting 4 post rack enclosures. Large capacity 5000 VA/3750 watt UPS system accepts raw AC input, adjusting output to regulated 208V levels. One pair of 120V outlets support up to 600VA monitors and other low voltage accessories. Includes slot for internal SNMP/web card, plus 2 DB9 and 2 USB enhanced monitoring ports for unattended shutdown, remote control and monitoring of UPS system and power data. Five outlets (two L6-20R, one

L6-30R and two 5-15R) allow the connection of high current 20 and 30 amp 208V connectors and up to two 120V devices (max 600VA at 120V).

Package Includes

SMART5000TEL3U UPS System

PowerAlert Software and cabling

Mounting hardware

Instruction manual

Features

Large 5000VA/3750-watt output capacity accommodates solitary large loads or multiple low-power loads

High power density 5kVA power module occupies only 3 rack spaces (3U)

16 minutes half-load runtime (with a continuous load 2500VA; much longer runtime available at smaller loads)

Line-interactive voltage regulation corrects severe brownouts and overvoltages without using battery power

High voltage output supports 208V server, internetworking and telecom applications

Pair of 120V outlets supports up to 600VA for standard 120V monitors, voicemail and other low-power networking devices

Five total outlets (two L6-20R, one L6-30R and two 5-15R)

Diagnostic LEDs provide visual indication of 17 separate performance conditions

Included PowerAlert Software provides e-mail or pager notification of power problems and simultaneous automatic unattended shutdown of multiple servers

4 built-in communications ports (2 USB/2 DB9) for remote monitoring and unattended shutdown

Slot for SNMP/web card (part#: SNMPWEBCARD) and environmental sensor (part#: ENVIROSENSE) for remote communications in large

IP environments

Emergency Power Off (EPO) interface for emergency shutoff in large facilities

Hot-swappable/user-replaceable batteries allow on-site battery replacement through the front panel without powering off connected equipment or removing the UPS from the rack

UPS ships fully assembled and ready for installation; no time-consuming user battery connections required

Specifications

OUTPUT

Output Volt Amp Capacity

(VA)

Output kVA capacity (kVA)

Output Watt Capacity

(watts)

Output kW capacity

Output power factor

Nominal Output Voltage(s)

Supported

Nominal Voltage details

Frequency compatibility

Output voltage regulation

(line mode)

Output voltage regulation

(Battery mode)

Built-in UPS output receptacles

Output receptacle details

Output circuit breaker

5000

5

3750

3.8

0.8

120V; 208V

120V output is limited to 600VA / 450 watts (maximum)

60 Hz

208 & 120V (-6%, +20%)

+/- 5%

2 5-15R outlet(s); 2 L6-20R outlet(s); 1 L6-30R outlet(s)

Output AC waveform (AC mode)

Output AC waveform

(battery mode)

INPUT

Rated input current (at maximum load)

Nominal Input Voltage(s)

Supported

UPS input connection type

UPS Input cord length (ft.)

UPS Input cord length (m)

Recommended Electrical

Service

Phase

BATTERY

Full load runtime (minutes)

Half load runtime (minutes)

DC system voltage (VDC)

120V 5-15R outlets are limited to 600VA / 450 watts (maximum)

20A double pole breaker supports L6-20R outlets, 5A breaker supports 5-15R outlets, L6-30R outlet is unbreakered

Sine wave

Pure Sine wave

24A

208V AC

L6-30P

10

3

30A 208V

Single-Phase

8.5 min. (3750w)

20 min. (1875w)

48

Battery recharge rate

(included batteries)

Replacement battery cartridge (internal UPS battery replacement)

Battery Access

Battery replacement description

VOLTAGE REGULATION

Voltage regulation description

Less than 4 hours from 10% to 90%

RBC94-3U (quantity 3)

Front panel battery access door

Hot-swappable, user replaceable batteries

Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 167 to 260

Overvoltage correction

Undervoltage correction

LEDS ALARMS & SWITCHES

LED Indicators

Alarms

Alarm cancel operation

Input voltages between 228V and 260V are reduced by 12%

Input voltages between 167V and 194V are boosted by 12%

5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status

Audible alarm indicates power-failure, overload and low-battery conditions

Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status

Switches

SURGE / NOISE SUPPRESSION

2 Switches control off/on power status and alarm-cancel/self-test operation

UPS AC suppression joule rating

1020

UPS AC suppression response time

Instantaneous

Yes EMI / RFI AC noise suppression

PHYSICAL

Installation form factors supported with included accessories

Installation form factors supported with optional accessories

4 post 19 inch rackmount

2 post rackmount (2POSTRMKITWM); Tower (2-9USTAND)

Rackmount

5.25 x 17.5 x 25

Primary form factor

UPS / Power Module dimensions in primary form factor (height x width x depth / inches)

UPS / Power Module dimensions in primary form factor (height x width x depth / cm)

Rack Height

Secondary form factor

UPS / Power Module weight

(lbs)

13.3 x 44.4 x 63.5

3U

Tower (requires

143.3

2-9USTAND )

UPS / Power Module weight

(kg)

UPS Shipping dimensions

(height x width x depth / inches)

UPS Shipping dimensions

(height x width x depth / cm)

Shipping weight (lbs)

Shipping weight (kg)

65.1

11.2 x 23 x 31.5

28.6 x 58.4 x 80

181.9

82.6

Cooling method

UPS housing material

ENVIRONMENTAL

Operating Temperature

Range

Fan

Steel

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

AC mode BTU / hr. (full load)

COMMUNICATIONS

Communications interface

Network monitoring port description

PowerAlert software

Communications cable

WatchDog compatibility

LINE / BATTERY TRANSFER

Transfer time

0 to 95%, non-condensing

366

USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface

Supports detailed monitoring of UPS and site power conditions

Included

USB and DB9 cabling included

Supports Watchdog application, OS and hard-reboot restart options for remote applications

7 milliseconds (AC to Battery), 1 millisecond (Battery to AC)

167 Low voltage transfer to battery power (setpoint)

High voltage transfer to battery power (setpoint)

SPECIAL FEATURES

Grounding lug

Cold Start (startup in battery mode during a power failure)

High availability UPS features

Green & high efficiency features

CERTIFICATIONS

UPS Certifications

WARRANTY

260

Back panel grounding lug

Cold-start operation supported

Hot swappable batteries

Greater than 95% efficiency - GREEN UPS

Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category A (EMI)

Product Warranty Period

(Worldwide)

Connected Equipment

Insurance (U.S., Canada &

Puerto Rico)

2-year warranty, 3 year with registration . Note: registration is required for 3-year warranty.

$250,000 Ultimate Lifetime Insurance

Related Items

Optional Products

Related Model

SNMPWEBCARD

ENVIROSENSE

U022-010

DTEL2

DCATV

DNET1

WEXT5-5000TEL

2-9USTAND

MODBUSCARD

2POSTRMKITHD

Description

For remote monitoring and control via SNMP, Web, or Telnet.

Monitors temperature, humidity and contact-closure inputs. (Requires SNMPWEBCARD or switched PDU.)

10-ft. USB2.0 A/B Gold Device Cable

(A Male to B Male)

Network Surge Suppressor - Essential protection for data and communication lines

Network Surge Suppressor - Essential protection for TV/VCR coaxial lines

Network Surge Suppressor - Essential protection for data and communication lines

5-Year Extended Warranty - For SMART5000TEL3U only

Enables Tower Placement of Rackmount UPS Systems

For remote monitoring and control via MODBUS protocol

Enables 2-Post Rackmount Installation of 3U and Larger UPS, Transformer and Battery

Pack Components

More information, including related products, owner's manuals, and additional technical specifications, can be found online at www.tripplite.com/en/products/model.cfm?txtModelID=3035 .

Copyright © 2013 Tripp Lite. All rights reserved. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos may differ slightly from final products.

Qty.

1

1

1

1

1

1

1

1

1

1

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Line-Interactive
  • 5 kVA 3750 W
  • Waveform: Sine
  • 5 AC outlet(s)
  • Rackmount/Tower Black