REQ 71-125 B Technical Data


Add to my manuals
36 Pages

advertisement

REQ 71-125 B Technical Data | Manualzz

technical data

REQ-B8V3B_REQ-B8W1B

Pair Application

Split

Sky Air

Split - Sky Air

Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.

ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.

Daikin Europe N.V. is approved by LRQA for its

Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin units comply with the European regulations that guarantee the safety of the product.

“The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin

Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V.

explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe

N.V..”

Daikin Europe N.V. participates in the Eurovent

Certification Programme for Air Conditioners

(AC), Liquid Chilling Packages (LCP) and Fan Coil units (FC); the certified data of certified models are listed in the Eurovent Directory.

Naamloze Vennootschap

Zandvoordestraat 300

B-8400 Ostend, Belgium www.daikin.eu

BTW: BE 0412 120 336

RPR Oostende

EEDEN0 7

technical data

REQ-B8V3B_REQ-B8W1B

Pair Application

Split

Sky Air

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

TABLE OF CONTENTS

REQ-B8V3B_REQ-B8W1B

1

2

5

6

3

4

7

8

9

10

11

12

Features

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Specifications

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Nominal Capacity and Nominal Input

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Technical Specifications

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Electrical Specifications

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Electrical data

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Safety device settings

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Options

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Capacity tables

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Cooling capacity tables

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Heating capacity tables

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Dimensional drawing & centre of gravity

. . . . . . . . . . . . . . . . . . . . . . . 23

Dimensional drawing

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Centre of gravity

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Piping diagram

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Wiring diagram

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Wiring diagram

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

External connection diagram

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Sound data

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Sound pressure spectrum

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Sound power spectrum

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Installation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Installation method

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Service space

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Operation range

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

• Split Sky Air • Outdoor Units 4

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

1 Features

Q E y n R _ U k B 3 S V a 8 o o 0 B 1 d 4 Q p u E R R S O • Outdoor units for pair application

• Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.

• Outdoor units are fitted with a scroll compressor, renowned for low noise and high energy efficiency.

• The piping connections can be accessed from underneath, front, side or rear.

• The sevice valves are hidden inside the casing.

• A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions

1

1

5 • Split Sky Air • Outdoor Units

2

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

Specifications

2-1 NOMINAL CAPACITY AND NOMINAL INPUT

For combination indoor units + outdoor units

Nominal

Capacity

For combination indoor units + outdoor units

Indoor Units

Cooling

Heating

Nominal input Cooling

Heating

EER

COP

Energy

Labeling

Directive

Nominal

Capacity

Standard

Standard

Standard

Standard

Cooling

Heating

Cooling

Heating kW kW kW kW

Annual energy consumption kWh

Indoor Units

Cooling

Heating

Standard

Standard kW kW

Nominal input Cooling

Heating

For combination indoor units + outdoor units

EER

COP

Energy

Labeling

Directive

Nominal

Capacity

Standard

Standard

Cooling

Heating

Cooling

Heating kW kW

Annual energy consumption kWh

Indoor Units

Cooling

Heating

Standard

Standard kW kW

Nominal input Cooling

Heating

For combination indoor units + outdoor units

EER

COP

Energy

Labeling

Directive

Nominal

Capacity

Standard

Standard

Cooling

Heating

Cooling

Heating kW kW

Annual energy consumption kWh

Indoor Units

Cooling

Heating

Standard

Standard kW kW

Nominal input Cooling

Heating

For combination indoor units + outdoor units

EER

COP

Energy

Labeling

Directive

Standard

Standard

Cooling

Heating

Cooling

Heating kW kW

Annual energy consumption kWh

REQ71B8V3B

FDEQ71B8V3B

D

1350

1360

FBQ71B8V3B

7.1

8

2.79

2.49

2.54

3.21

E

C

1395

FHQ71BVV1B

7.1

8

2.7

2.85

2.63

2.81

1395

FCQ71C7VEB

7.1

8

2.79

2.49

2.54

3.21

E

C

2.54

3.21

E

C

7.1

8

2.79

2.49

2-2 TECHNICAL SPECIFICATIONS

Casing

Dimensions

Colour

Material

Unit

Packing

Height

Width

Depth

Height

Width

Depth

Weight Unit

Packed Unit mm mm kg kg mm mm mm mm

REQ71B8V3B

980

420

83

87

770

900

320

900

REQ71B8W1B

FDEQ71B8V3B

REQ100B8V3B

FDEQ100B8V3B

REQ100B8W1B

FDEQ100B8V3B

REQ125B8W1B

FDEQ125B8V3B

1330

FBQ71B8V3B

7.1

8

2.68

2.49

2.65

3.21

D

C

1340

FHQ71BVV1B

7.1

8

2.65

2.8

2.68

2.86

1340

FCQ71C7VEB

7.1

8

2.66

2.80

2.67

2.86

D

C

2.65

3.21

D

C

7.1

8

2.68

2.49

D

1325

9.8

11.2

3.98

3.99

2.46

2.81

E

D

1990

FCQ100C7VEB

10

11.2

3.83

3.75

2.61

2.99

D

1915

FBQ100B8V3B

10

11.2

3.79

3.91

2.64

2.86

D

D

1895

FHQ100BVV1B

9.8

11.2

3.75

4.13

2.61

2.71

D

E

1875

980

420

83

87

770

900

320

900

REQ71B8W1B REQ100B8V3B

Daikin White

Painted galvanized steel plate

1170

900

320

1300

980

420

102

107

REQ100B8W1B

1170

900

320

1300

980

420

100

105

1780

FBQ100B8V3B

10

11.2

3.6

3.87

2.78

2.89

D

D

1800

FHQ100BVV1B

9.8

11.2

3.68

4.01

2.66

2.79

2.49

2.83

E

D

9.8

11.2

3.94

3.96

1970

FCQ100C7VEB

10

11.2

3.56

3.66

2.81

3.06

C

D

E

1840

2.68

3.23

D

C

12.5

14.5

4.67

4.52

2335

FCQ125C7VEB

12.5

14.6

4.66

5.06

2.68

2.89

D

1170

900

320

1300

980

420

108

113

2330

FBQ125B8V3B

12.2

14.5

4.67

4.52

2.61

3.21

D

C

2335

FHQ125BVV1B

12.2

14.5

4.51

5.16

2.71

2.81

D

2255

REQ125B8W1B

• Split Sky Air • Outdoor Units

1

2

6

2

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

Specifications

1

2

2-2 TECHNICAL SPECIFICATIONS

Heat

Exchanger

Fan

Motor

Fan

Motor

Fan

Compressor

Operation

Range

Sound Level

(nominal)

Dimensions

Cooling

Length

Nr of Rows

Fin Pitch

Nr of Passes mm mm

Face Area m²

Nr of Stages

Tube type

Fin

Type

Discharge direction

Type

Treatment

Quantity

Air Flow Rate

(nominal at

230V)

Motor

Cooling

Heating

Quantity

Model

Position

Steps Speed

(nominal)

Motor Output

Position

Steps Speed

(nominal)

Motor

Quantity

Motor

Output

Model

Type

Motor

Output

Crankcase

Heater m³/min m³/min

W

W

W

W

Heating

Cooling

Min

Max

Min

Max

Sound

Power

Sound

Pressure

°CDB

°CDB

°CWB

°CWB dBA dBA

Refrigerant Type

Charge

Control

Nr of Circuits

Refrigerant Oil Type

Charged Volume l kg

REQ71B8V3B

857

2

2.00

6

0.641

34

1

48.0

43.0

1

3

65

1

JT90G-P4V1N@S

2200

33

10.0

46.0

-10

15

65.0

53.0

2.5

1

1.5

REQ71B8W1B

857

2

2.00

6

0.641

34

1

48.0

43.0

REQ100B8V3B

857

2

2.00

10

0.980

52

Hi-XSS cooling tube

Non-symmetric waffle louvre

Anti-corrosion treatment (PE)

Direct Drive Propeller

Horizontal

1

55.0

50.0

REQ100B8W1B

857

2

2.00

10

0.980

52

1

55.0

50.0

1 1

P47L11S

1

3

65

3

90

3

90

1

JT90G-YE

2200

1

JT125G-P4V1@S

Hermetically sealed scroll compressor

3000

1

JT125G-YE

3000

33 33 33

10.0

46.0

-10

15

65.0

53.0

10.0

46.0

-10

15

70.0

57.0

10.0

46.0

-10

15

70.0

57.0

2.5

1

1.5

R-410A

3.6

Expansion valve (electronic type)

1

Daphne FVC68D

1.5

3.6

1

1.5

REQ125B8W1B

857

2

2.00

10

0.980

52

2

89.0

80.0

1

Lower

3

85

Upper

3

65

1

JT160G-YE

3750

33

10.0

46.0

-10

15

70.0

57.0

3.6

1

1.5

7 • Split Sky Air • Outdoor Units

2

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

Specifications

2-2 TECHNICAL SPECIFICATIONS

Piping connections

Liquid (OD)

Gas mm mm

Drain Quantity

Type

Diameter

(OD) mm

Piping Length Minimum m

Maximum m

Installation height difference

Equivalent m

Chargeless m

Maximum m

Max. internunit level difference

Heat Insulation m

Defrost Method

Defrost Control

Capacity Control Method

Safety Devices

Quantity

Type

Diameter

(OD)

Quantity

Type

Diameter

(OD)

Standard

Accessories

Item

Quantity

Item

Quantity

Notes

REQ71B8V3B

1

9.52

1

15.9

3

26

5

50

70

7.5

30.0

REQ71B8W1B

1

9.52

1

15.9

3

26

5

50

70

7.5

30.0

REQ100B8V3B

1

Flare connection

9.52

1

Flare connection

15.9

3

Hole

26

5

50

70

7.5

30.0

REQ100B8W1B

1

9.52

1

15.9

3

26

5

50

70

7.5

30.0

0.5

0.5

0.5

0.5

0.5

Both liquid and gas pipes

Reversed cycle

Sensor for outdoor heat exchanger temperature

None

Reverse phase protector

PC board fuse

Overcurrent relay (compressor)

Low pressure switch

High pressure switch

Fan motor thermal protector

Declaration of conformity

1 1 1 1 1

1 1

Installation manual

1 1 1

Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound level drawings of this chapter.

The sound power level is an absolute value indicating the power which a sound source generates.

Sound values are measured in a semi-anechoic room.

In case of drain piping for outdoor unit, drain piping kit (option) is needed.

Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.

Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m

REQ125B8W1B

1

9.52

1

15.9

3

26

5

50

70

7.5

30.0

2-3 ELECTRICAL SPECIFICATIONS

Power Supply Name

Phase

Current

Wiring connections

Frequency

Voltage

Voltage range Minimum V

Maximum V

Recomended fuses

For Power

Supply

Quantity

Remark

Hz

V

A

For connection with indoor

Power Supply Intake

Quantity

Remark

REQ71B8V3B

V3

1

50

230

32

1

3 wires (earth wire included)

1

REQ71B8W1B REQ100B8V3B REQ100B8W1B

W1

3N

50

400

V3

1

50

230

W1

3N

50

400

16

1

-10%

+10%

40

1

5 wires (earth wire included)

1

3 wires (earth wire included)

1

4 wires (earth wire included)

5 wires (earth wire included)

1

Outdoor unit only

16

1

REQ125B8W1B

W1

3N

50

400

20

1

5 wires (earth wire included)

1

• Split Sky Air • Outdoor Units

1

2

8

1

3

3

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

Electrical data

Indoor unit

Unit combination

Outdoor unit

FCQ71B

FCQ71C

REQ71B8V3B

REQ71B8V3B

FHQ71

FBQ71

FDEQ71

FCQ71B

REQ71B8V3B

REQ71B8V3B

REQ71B8V3B

REQ71B8W1B

FCQ71C

FHQ71

FBQ71

FDEQ71

REQ71B8W1B

REQ71B8W1B

REQ71B8W1B

REQ71B8W1B

SYMBOLS

MCA : Min. Circuit Amps

TOCA : Total Over Current Amps

MFA

LRA

: Max. Fuse Amps (see note 7)

: Locked Rotor Amps

RLA

OFM

IFM

FLA kW

: Rated Load Amps

: Outdoor Fan Motor

: Indoor Fan Motor

: Full Load Amps

: Rated motor output

Hz-Volts

50-230

50-230

50-230

50-230

50-230

50-400

50-400

50-400

50-400

50-400

Power supply

Voltage range

Max. 50Hz-253V

Min. 50Hz-207V

Max. 50Hz-440V

Min. 50Hz-360V

8.1

6.8

7.1

7.5

17.4

15.4

7.3

MCA TOCA

16.6

23.3

16.4

16.8

23.1

23.2

23.5

23.5

11.3

11.1

11.2

11.5

11.5

MFA

32

32

32

32

32

16

16

16

16

16

41.1

41.1

41.1

41.1

75.5

75.5

75.5

41.1

Compressor

LRA RLA

75.5

75.5

12.2

12.2

12.5

12.7

11.1

4.8

5.3

4.2

4.8

5.0

0.065

0.065

0.065

0.065

0.065

0.065

0.065

0.065

kW

OFM

FLA

0.065

0.065

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.065

0.062

0.125

0.125

0.062

0.125

0.125

0.045

kW

IFM

FLA

0.045

0.065

0.7

0.5

0.6

0.9

0.9

0.7

0.9

0.9

0.5

0.6

3TW26599-9A

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. TOCA means the total value of each OC set

3. Voltage range

Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits

4. Maximum allowable voltage unbalance between phases is 2%.

5. MCA/MFA

MCA = 1.25 x RLA + all FLA, MFA = < 2.25 x RLA + all FLA (next lower standard fuse rating Min. 16A)

6. Select wire size based on the larger value of MCA or TOCA

7. Instead of fuse, use circuit breaker

8. For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select

’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button.

Finally, click on the document title of your choice.

9 • Split Sky Air • Outdoor Units

3

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

Electrical data

Indoor unit

Unit combination

Outdoor unit

FCQ100B

FCQ100C

REQ100B8V3B

REQ100B8V3B

FHQ100

FBQ100

FDEQ100

FCQ100B

REQ100B8V3B

REQ100B8V3B

REQ100B8V3B

REQ100B8W1B

FCQ100C

FHQ100

FBQ100

FDEQ100

REQ100B8W1B

REQ100B8W1B

REQ100B8W1B

REQ100B8W1B

Hz-Volts

50-230

50-230

50-230

50-230

50-230

50-400

50-400

50-400

50-400

50-400

SYMBOLS

MCA : Min. Circuit Amps

TOCA : Total Over Current Amps

MFA

LRA

: Max. Fuse Amps (see note 7)

: Locked Rotor Amps

RLA

OFM

IFM

FLA kW

: Rated Load Amps

: Outdoor Fan Motor

: Indoor Fan Motor

: Full Load Amps

: Rated motor output

Power supply

Voltage range

Max. 50Hz-253V

Min. 50Hz-207V

Max. 50Hz-440V

Min. 50Hz-360V

8.9

9.6

8.9

9.4

23.2

24.2

9.2

MCA TOCA

23.8

34.8

23.5

25.3

34.5

34.5

34.8

34.8

11.8

11.5

11.5

11.8

11.8

MFA

40

40

40

40

40

16

16

16

16

16

48.2

48.2

48.2

48.2

98.5

98.5

98.5

48.2

Compressor

LRA RLA

98.5

98.5

17.6

17.6

19.0

17.1

17.9

4.8

5.3

4.2

4.8

5.0

0.090

0.090

0.090

0.090

0.090

0.090

0.090

0.090

kW

OFM

FLA

0.090

0.090

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.120

0.130

0.135

0.135

0.130

0.135

0.135

0.090

kW

IFM

FLA

0.090

0.120

1.0

0.7

0.7

1.0

1.0

1.0

1.0

1.0

0.7

0.7

3TW26619-9A

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. TOCA means the total value of each OC set

3. Voltage range

Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits

4. Maximum allowable voltage unbalance between phases is 2%.

5. MCA/MFA

MCA = 1.25 x RLA + all FLA, MFA = < 2.25 x RLA + all FLA (next lower standard fuse rating Min. 16A)

6. Select wire size based on the larger value of MCA or TOCA

7. Instead of fuse, use circuit breaker

8. For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select

’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button.

Finally, click on the document title of your choice.

1

3

• Split Sky Air • Outdoor Units 10

1

3

3

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

Electrical data

Indoor unit

Unit combination

Outdoor unit

FCQ125B REQ125B8V3B

FCQ125C REQ125B8V3B

FHQ125

FBQ125

FDEQ125

REQ125B8V3B

REQ125B8V3B

REQ125B8V3B

SYMBOLS

MCA : Min. Circuit Amps

TOCA : Total Over Current Amps

MFA : Max. Fuse Amps (see note 7)

LRA

RLA

OFM

: Locked Rotor Amps

: Rated Load Amps

: Outdoor Fan Motor

IFM

FLA kW

: Indoor Fan Motor

: Full Load Amps

: Rated motor output

Hz-Volts

50-400

50-400

50-400

50-400

50-400

Power supply

Voltage range

Max. 50Hz-400V

Min. 50Hz-360V

MCA TOCA

12.4

15.3

MFA

20

12.4

12.3

12.2

12.6

15.3

15.0

15.7

15.7

20

20

20

20

Compressor

LRA RLA

63 8.1

63

63

63

63

8.1

8.2

7.6

7.9

0.065

+0.085

0.065

+0.085

0.065

+0.085

kW

OFM

FLA

0.065

+0.085

0.065

+0.085

0.6+0.7

0.6+0.7

kW

0.09

0.12

IFM

FLA

1.0

1.0

0.6+0.7

0.6+0.7

0.6+0.7

0.13

0.225

0.225

0.7

1.4

1.4

3TW26639-9A

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. TOCA means the total value of each OC set

3. Voltage range

Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits

4. Maximum allowable voltage unbalance between phases is 2%.

5. MCA/MFA

MCA = 1.25 x RLA + all FLA, MFA = < 2.25 x RLA + all FLA (next lower standard fuse rating Min. 16A)

6. Select wire size based on the larger value of MCA or TOCA

7. Instead of fuse, use circuit breaker

8. For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select

’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button.

Finally, click on the document title of your choice.

11 • Split Sky Air • Outdoor Units

4

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

Safety device settings

REQ71 ∼ 125B

Safety device

Fan motor thermal protector

HPS

LPS

Max discharge temperature

Overcurrent relay

Model

REQ71BV3

REQ71BW1

REQ100BV3

REQ100BW1

Off 135 ±5°C

On 95 ±15°C

Off 4,15

On 3.2

+0

- 0,10

Mpa

+0,15

- 0,15

Mpa

Off -0.03

+0,02

- 0,02

Mpa

On 0.05

+0,03

- 0,03

Mpa

By thermistor and software control

By overcurrent sensor and software control

REQ125BW1

4TW26321-2B

• Split Sky Air • Outdoor Units

1

4

12

5 Options

REQ71 ∼125B

Name of option

Central drain plug

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

REQ71B

Kit name

REQ100B

KKPJ5F180

REQ125B

4TW26599-1

1

5

13 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

6 Capacity tables

6 - 1 Cooling capacity tables

FHQ71-125B + REQ71-100BV3

REQ71-125BW1

Cooling capacity table

Outdoor

Indoor

EWB EDB

(°C) (°C) TC

20

SHC PI TC

25

SHC PI TC

32

SHC

Outdoor temp. (°CDB)

PI TC

35

SHC PI TC

40

SHC PI TC

46

SHC PI

SYMBOLS

AFR: Air flow rate

BF: Bypass factor

EWB: Entering wet bulb temp.

EDB: Entering dry bulb temp.

DB*: Dry bulb temp.

TC: Total cooling/heating capacity

SHC: Sensible heating capacity

PI: Power input

(comp.+indoor+outdoor fan motor)

Caution:

TC and SHC are shown by kW

V3: 230 V [50 Hz]

W1: 400 V [50 Hz]

(m 3 /min)

(°CWB)

(°CDB)

(°CDB)

(kW)

(kW)

(kW)

NOTES

1. Ratings shown are net capacities.

Influence of fan motor heat is included.

2.

Shows nominal capacities

3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb

SHC* = 0.29 x 60 x AFR (m 3 /min.) x (1 −BF) x (DB*−EDB)/860

Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible.

Do not extrapolate.

5. Capacities are based on following conditions:

Corresponding refrigerant piping length

Level difference

6. Air flow rate and BF are tabulated below.

: 7.5 m

: 0 m

Model

71

100

125

AFR

BF

AFR

BF

AFR

BF

FHQ

17

0.1

24

0.14

30

0.13

7. Add the following corrections to power input of each model.

Model

71

100

125

Supply

V3

W1

V3

W1

W1

FHQ

0.05

0

0.07

0

0

3TW26592-3

1

6

• Split Sky Air • Outdoor Units 14

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

6 Capacity tables

6 - 1 Cooling capacity tables

Cooling capacity table

FCQ71-125C7VEB+ REQ71-100B8V3B

REQ71-125B8W1B

Outdoor

Indoor

EWB EDB

(°C) (°C) TC

20

SHC PI TC

25

SHC PI TC

32

SHC

Outdoor temperature (°CDB)

PI TC

35

SHC PI TC

40

SHC PI TC

46

SHC PI

1

6

SYMBOLS

AFR: Air flow rate

BF: Bypass factor

EWB: Entering wet bulb temp.

EDB: Entering dry bulb temp.

(m 3 /min)

(°CWB)

(°CDB)

DB*:

TC:

Dry bulb temp.

Total capacity

SHC: Sensible heating capacity

PI:

(°CDB)

(kW)

(kW)

Power input (Comp. + indoor + outdoor fan motor). (kW)

Caution

TC and SHC are shown by kW

V3: 230V (50Hz)

W1: 400V (50Hz)

1

2

3

4

5

6

7

3D057263

NOTES

Ratings shown are net capacities which include a deduction for indoor fan motor heat

Shows nominal capacities

SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb

= 0.29 x 60 x AFR [m 3 /min.] x (1-BF) x (DB*-EDB)/860

Add SHC* to SHC if SHC > TC, then TC equal SHC

Direct interpolation is permissible.

Do not extrapolate.

Capacities are based on following conditions:

Corresponding refrigerant piping length:

Level difference:

5 m

0 m

Air flow rate (AFR) and Bypass factor (BF) are taburated below.

Model

71

100

125

AFR

BF

AFR

BF

AFR

BF

FBQ

15.5

0.19

23.5

0.16

27.5

0.19

Add the following corrections to power input of each model.

Model

71

100

125

Supply

V3

W1

V3

W1

W1

FBQ

0.06

0

0.27

0

0

15 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

6 Capacity tables

6 - 1 Cooling capacity tables

FBQ71-125B + REQ71-100BV3

REQ71-125BW1

Cooling capacity table

Outdoor

Indoor

EWB EDB

(°C) (°C) TC

20

SHC PI TC

25

SHC PI TC

32

SHC

Outdoor temp. (°CDB)

PI TC

35

SHC PI TC

40

SHC PI TC

46

SHC PI

SYMBOLS

AFR: Air flow rate

BF: Bypass factor

EWB: Entering wet bulb temp.

EDB: Entering dry bulb temp.

DB*: Dry bulb temp.

TC: Total cooling/heating capacity

SHC: Sensible heating capacity

PI: Power input

(comp.+indoor+outdoor fan motor)

Caution:

TC and SHC are shown by kW

V3: 230 V [50 Hz]

W1: 400 V [50 Hz]

(m 3 /min)

(°CWB)

(°CDB)

(°CDB)

(kW)

(kW)

(kW)

NOTES

1. Ratings shown are net capacities.

Influence of fan motor heat is included.

2.

Shows nominal capacities

3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb

SHC* = 0.29 x 60 x AFR (m 3 /min.) x (1 −BF) x (DB*−EDB)/860

Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible.

Do not extrapolate.

5. Capacities are based on following conditions:

Corresponding refrigerant piping length

Level difference

6. Air flow rate and BF are tabulated below.

: 7.5 m

: 0 m

Model

71

100

125

AFR

BF

AFR

BF

AFR

BF

FBQ

19

0.11

27

0.2

35

0.14

7. Add the following corrections to power input of each model.

Model

71

100

125

Supply

V3

W1

V3

W1

W1

FBQ

0.11

0

0.19

0

0

3TW26592-2

1

6

• Split Sky Air • Outdoor Units 16

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

6 Capacity tables

6 - 1 Cooling capacity tables

FDEQ71-125B + REQ71-100BV3

REQ71-125BW1

Cooling capacity table

Outdoor

Indoor

EWB EDB

(°C) (°C) TC

20

SHC PI TC

25

SHC PI TC

32

SHC

Outdoor temp. (°CDB)

PI TC

35

SHC PI TC

40

SHC PI TC

46

SHC PI

1

6

SYMBOLS

AFR:

BF:

Air flow rate

Bypass factor

EWB: Entering wet bulb temp.

EDB:

DB*:

Entering dry bulb temp.

Dry bulb temp.

TC: Total cooling/heating capacity

SHC: Sensible heating capacity

PI: Power input

(comp.+indoor+outdoor fan motor)

Caution:

TC and SHC are shown by kW

V3: 230 V [50 Hz]

W1: 400 V [50 Hz]

(m 3 /min)

(°CWB)

(°CDB)

(°CDB)

(kW)

(kW)

(kW)

NOTES

1. Ratings shown are net capacities.

Influence of fan motor heat is included.

2.

Shows nominal capacities

3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb

SHC* = 0.29 x 60 x AFR (m 3 /min.) x (1 −BF) x (DB*−EDB)/860

Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible.

Do not extrapolate.

5. Capacities are based on following conditions:

Corresponding refrigerant piping length

Level difference

6. Air flow rate and BF are tabulated below.

: 7.5 m

: 0 m

Model

71

100

125

AFR

BF

AFR

BF

AFR

BF

FDEQ

19

0.11

27

0.2

35

0.14

7. Add the following corrections to power input of each model.

Model

71

100

125

Supply

V3

W1

V3

W1

W1

FDEQ

0.11

0

0.04

0

0

3TW26592-4

17 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

6 Capacity tables

6 - 2 Heating capacity tables

FHQ71-125B + REQ71-100BV3

REQ71-125BW1

Heating capacity table

Outdoor

Indoor

EDB

(°C) TC

-10

PI TC

-5

PI TC

0 outdoor temperature (°CWB)

PI TC

6

PI TC

10

PI TC

15

PI

SYMBOLS

AFR: Air flow rate

EDB: Entering dry bulb temp.

WB: Wet bulb temperature

TC:

PI:

Total cooling/heating capacity

Power input

(comp.+indoor+outdoor fan motor)

Caution:

TC is shown by kW

V3: 230 V [50 Hz]

W1: 400 V [50 Hz]

3TW26592-7

(m 3 /min)

(°CDB)

(°CWB)

(kW)

(kW)

NOTES

1. Ratings shown are net capacities.

Influence of fan motor heat is included.

2.

Shows nominal capacities

3. Capacities are based on following conditions:

* outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB

* Corresponding refrigerant piping length

Level difference

4. Direct interpolation is permissible.

: 7.5 m

: 0 m

Do not extrapolate.

5. Air flow rate and BF are tabulated below.

Model

71

100

125

AFR

BF

AFR

BF

AFR

BF

FHQ

17

0.1

24

0.14

30

0.13

6. Add the following corrections to power input of each model.

Model

71

100

125

Supply

V3

W1

V3

W1

W1

FHQ

0.05

0

0.12

0

0

1

6

• Split Sky Air • Outdoor Units 18

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

6 Capacity tables

6 - 2 Heating capacity tables

Heating capacity table

FCQ71-125C7VEB+ REQ71-100B8V3B

REQ71-125B8W1B

Outdoor

Indoor

EDB

(°C) TC

-10

PI TC

-5

PI TC

0

Outdoor temperature (°CDB)

PI TC

6

PI TC

10

PI TC

15

PI

1

6

SYMBOLS

AFR:

WB: Wet bulb temperature

EDB: Entering dry bulb temp.

TC: Total capacity

PI:

Air flow rate (m 3 /min)

(°CWB)

(°CDB)

(kW)

Power input (Comp. + indoor + outdoor fan motor). (kW)

Caution

TC and SHC are shown by kW

V3: 230V (50Hz)

W1: 400V (50Hz)

1

2

3

4

5

6

3D057264

NOTES

Ratings shown are net capacities which include a deduction for indoor fan motor heat

Shows nominal capacities

Capacities are based on following conditions: outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB

Corresponding refrigerant piping length:

Level difference:

5 m

0 m

Direct interpolation is permissible.

Do not extrapolate.

Air flow rate (AFR) and Bypass factor (BF) are taburated below.

Model

71

100

125

AFR

BF

AFR

BF

AFR

BF

FBQ

16.0

0.19

23.5

0.16

27.5

0.19

Add the following corrections to power input of each model.

Model

71

100

125

Supply

V3

W1

V3

W1

W1

FBQ

0.05

0

0.09

0

0

19 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

6 Capacity tables

6 - 2 Heating capacity tables

FBQ71-125B + REQ71-100BV3

REQ71-125BW1

Heating capacity table

Outdoor

Indoor

EDB

(°C) TC

-10

PI TC

-5

PI TC

0 outdoor temperature (°CWB)

PI TC

6

PI TC

10

PI TC

15

PI

SYMBOLS

AFR: Air flow rate

EDB: Entering dry bulb temp.

WB: Wet bulb temperature

TC:

PI:

Total cooling/heating capacity

Power input

(comp.+indoor+outdoor fan motor)

Caution:

TC is shown by kW

V3: 230 V [50 Hz]

W1: 400 V [50 Hz]

3TW26592-6

(m 3 /min)

(°CDB)

(°CWB)

(kW)

(kW)

NOTES

1. Ratings shown are net capacities.

Influence of fan motor heat is included.

2.

Shows nominal capacities

3. Capacities are based on following conditions:

* outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB

* Corresponding refrigerant piping length

Level difference

4. Direct interpolation is permissible.

: 7.5 m

: 0 m

Do not extrapolate.

5. Air flow rate and BF are tabulated below.

Model

71

100

125

AFR

BF

AFR

BF

AFR

BF

FBQ

19

0.11

27

0.2

35

0.14

6. Add the following corrections to power input of each model.

Model

71

100

125

Supply

V3

W1

V3

W1

W1

FBQ

0

0

0.04

0

0

1

6

• Split Sky Air • Outdoor Units 20

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

6 Capacity tables

6 - 2 Heating capacity tables

FDEQ71-125B + REQ71-100BV3

REQ71-125BW1

Heating capacity table

Outdoor

Indoor

EDB

(°C) TC

-10

PI TC

-5

PI TC

0 outdoor temperature (°CWB)

6

PI TC PI TC

10

PI TC

15

PI

1

6

AFR:

EDB:

WB:

TC:

PI:

SYMBOLS

Air flow rate

Entering dry bulb temp.

Wet bulb temperature

Total cooling/heating capacity

Power input

(comp.+indoor+outdoor fan motor)

Caution:

TC is shown by kW

V3: 230 V [50 Hz]

W1: 400 V [50 Hz]

3TW26592-8

(m 3 /min)

(°CDB)

(°CWB)

(kW)

(kW)

NOTES

1. Ratings shown are net capacities.

Influence of fan motor heat is included.

2.

Shows nominal capacities

3. Capacities are based on following conditions:

* outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB

* Corresponding refrigerant piping length

Level difference

4. Direct interpolation is permissible.

: 7.5 m

: 0 m

Do not extrapolate.

5. Air flow rate and BF are tabulated below.

Model

71

100

125

AFR

BF

AFR

BF

AFR

BF

FDEQ

19

0.11

27

0.2

35

0.14

6. Add the following corrections to power input of each model.

Model

71

100

125

Supply

V3

W1

V3

W1

W1

FDEQ

0

0

0.04

0

0

21 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

6 Capacity tables

6 - 2 Heating capacity tables

RR/RQ/REQ71 ∼ 125B

Capacity in function of field piping length for non-inverter

Capacity (%)

Cooling

Heating

Field piping length (m)

3TW26322-15

• Split Sky Air • Outdoor Units

1

6

22

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

7 Dimensional drawing & centre of gravity

7 - 1 Dimensional drawing

REQ71B

Hole for anchor bolt

4-M12

1 Gas pipe connection J15.9 flare

2 Liquid pipe connection - J9.5 flare

3 Service port (in the unit)

4 Grounding terminal M5 (in switch box)

5 Refrigerant piping intake

6 Power supply wiring intake (knock hole J34)

7 Control wiring intake (knock hole J27)

8 Drain outlet unit (mm)

1

7

REQ100B

Hole for anchor bolt

4-M12

23 • Split Sky Air • Outdoor Units

1 Gas pipe connection J15.9 flare

2 Liquid pipe connection - J9.5 flare

3 Service port (in the unit)

4 Grounding terminal M5 (in switch box)

5 Refrigerant piping intake

6 Power supply wiring intake (knock hole J34)

7 Control wiring intake (knock hole J27)

8 Drain outlet

3TW26324-1 unit (mm)

3TW26344-1

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

7 Dimensional drawing & centre of gravity

7 - 1 Dimensional drawing

REQ125B

Hole for anchor bolt

4-M12

1 Gas pipe connection J15.9 flare

2 Liquid pipe connection - J9.5 flare

3 Service port (in the unit)

4 Grounding terminal M5 (in switch box)

5 Refrigerant piping intake

6 Power supply wiring intake (knock hole J34)

7 Control wiring intake (knock hole J27)

8 Drain outlet unit (mm)

3TW26364-1

1

7

24 • Split Sky Air • Outdoor Units

1

7

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

7 Dimensional drawing & centre of gravity

7 - 2 Centre of gravity

REQ71B

REQ71B

Model A

267

3TW26329-5C

REQ100B

REQ100B

Model A

390

3TW26349-5C

25 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

7 Dimensional drawing & centre of gravity

7 - 2 Centre of gravity

REQ125B

REQ125B

Model A

390

3TW26369-5C

1

7

26 • Split Sky Air • Outdoor Units

8

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

Piping diagram

REQ71 ∼125B (Pair)

Solenoid valve

Electronic expansion valve

One way valve One way valve

Filter

Filter

One way valve One way valve

Strainer

Service port 5/16 ″

Receiver

Heat exchanger

Capillary tube

4-way valve

One way valve

Filter Low pressure switch

High pressure switch

Muffler

Field piping J9.5 C122OT-O

Filter

Field piping J15.9 C122OT-O

Compressor

Indoor unit

Stop valve

(with service port 1/4 ″ flare)

Outdoor unit

O

Check valve

L

Flare connection

M

Screw connection

N

Flange connection

Z

Pinched pipe

P

Spinned pipe

Heat exchanger

Heating

Cooling

Service port 5/16 ″

3TW26325-1

1

8

27 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

9 Wiring diagram

9 - 1 Wiring diagram

REQ71-100BV3

Power supply

1 ∼50Hz

230V

Indoor

A1P

BS1

C1R

C3R

DS1

E1HC

F1U

HAP

Printed circuit board

Push button (forced defrost-pump down)

Capacitor (M1F)

Capacitor (M1C)

DIP switch

Crankcase heater

Fuse (T6.3/250V)

Light emitting diode (service monitor green)

K1M

K1R

K2R

K3R

Magnetic contactor (M1C)

Magnetic relay (K1M)

Magnetic relay (Y2S)

Magnetic relay (E1HC)

K4R Magnetic relay (Y1S)

K5R,K6R,K7R Magnetic relay (M1F)

M1C

M1F

Motor compressor

Motor fan

PC

Q1DI

Q1M

R1T

R2T

R3T

RC

S1PH

Power circuit

Earth leakage breaker (30mA)

Thermo switch (M1F)

Thermistor (air)

Thermistor (coil)

Thermistor (discharge pipe)

Signal receiver circuit

Pressure switch (high)

S1LP

SD

T1A

TC

Pressure switch (low)

Safety devices input

Current transformer

Signal transmission circuit

X1M,X2M Terminal strip

Y1E Expansion valve (electronic type)

Y1S

Y2S

CT

4-way valve

Solenoid valve

Current transformer

Switch box

(Outdoor)

Note:

Confirm the method of setting the DIP switch (DS1) by service manual when the unit is shipped by factory all switches are set to be off.

Position of compressor terminal

Wire entrance

ON

OFF g Field wiring

D : Terminal

F : Connector b

L

: Protective earth (screw)

: Live

N : Neutral

: Terminal

Colours

BLK: Black/ BLU: Blue/ WHT: White/

RED: Red/ ORG: Orange/ YLW:Yellow

Outdoor

2TW26326-1B

REQ71-100BW1

Switch box

(Outdoor)

Indoor

Outdoor

Power supply

3N ∼50Hz

400V

Note:

Confirm the method of setting the DIP switch (DS1) by service manual when the unit is shipped by factory all switches are set to be off.

g Field wiring

D : Terminal

F : Connector b

L

: Protective earth (screw)

: Live

N : Neutral

: Terminal

Colours

BLK: Black/ BLU: Blue/ WHT: White/

RED: Red/ ORG: Orange/ YLW:Yellow

Position of compressor terminal

Wire entrance

A1P

BS1

C1

Printed circuit board

Push button (forced defrost-pump down)

Capacitor (M1F)

DS1

E1HC

DIP switch

Crankcase heater

F1U, F2U Fuse (T6.3/250V)

HAP Light emitting diode (service monitor green)

K1M

K1R

Magnetic contactor (M1C)

Magnetic relay (K1M)

K2R

K3R

K4R

Magnetic relay (Y2S)

Magnetic relay (E1HC)

Magnetic relay (Y1S)

K5R,K6R,K7R Magnetic relay (M1F)

M1C Motor compressor

M1F

PC

Motor fan

Power circuit

Q1DI

Q1M

Earth leakage breaker (30mA)

Thermo switch (M1F)

Q1RP

R1T

R2T

R3T

RC

S1HP

S1LP

SD

T1A

Phase reverse circuit

Thermistor (air)

Thermistor (coil)

Thermistor (discharge pipe)

Signal receiver circuit

Pressure switch (high)

Pressure switch (low)

Safety devices input

Current transformer

TC Signal transmission circuit

X1M,X2M Terminal strip

Y1E Expansion valve (electronic type)

Y1S

Y2S

CT

4-way valve

Solenoid valve

Current transformer

ON

OFF

2TW26336-1B

1

9

• Split Sky Air • Outdoor Units 28

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

9 Wiring diagram

9 - 1 Wiring diagram

REQ125BW1

Switch box

(Outdoor)

Indoor

Power supply

3N ∼50Hz

400V

Note:

Confirm the method of setting the DIP switch (DS1) by service manual when the unit is shipped by factory all switches are set to be off.

g Field wiring

D : Terminal

F b

L

: Connector

: Protective earth (screw)

: Live

N : Neutral

: Terminal

Colours

BLK: Black/ BLU: Blue/ WHT: White/

RED: Red/ ORG: Orange/ YLW:Yellow

Position of compressor terminal

Wire entrance

A1P

BS1

C1

C2

DS1

E1HC

Printed circuit board

Push button (forced defrost-pump down)

Capacitor (M1F)

Capacitor (M2F)

DIP switch

Crankcase heater

F1U, F2U Fuse (T6.3/250V)

HAP Light emitting diode (service monitor green)

K1M Magnetic contactor (M1C)

K1R

K2R

K3R

K4R

Magnetic relay (K1M)

Magnetic relay (Y2S)

Magnetic relay (E1HC)

Magnetic relay (Y1S)

K5R,K6R,K7R Magnetic relay (M1F)

K8R,K9R,K10R Magnetic relay (M2F)

M1C Motor compressor

M1F, M2F Motor fan

PC Power circuit

Q1D

Q1M

Q2M

Q1RP

R1T

R2T

R3T

RC

S1PH

Earth leakage breaker (30mA)

Thermo switch (M1F)

Thermo switch (M2F)

Phase reverse circuit

Thermistor (air)

Thermistor (coil)

Thermistor (discharge pipe)

Signal receiver circuit

Pressure switch (high)

S1LP

SD

T1A

TC

Pressure switch (low)

Safety devices input

Current transformer

Signal transmission circuit

X1M,X2M Terminal strip

Y1E Expansion valve (electronic type)

Y1S

Y2S

CT

4-way valve

Solenoid valve

Current transformer

ON

OFF

Outdoor

2TW26366-1B

1

9

29 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

9 Wiring diagram

9 - 2 External connection diagram

REQ71 ∼125B

Field wire

Symbol explication

I = Pair

II = Twin

III = Triple

M = Master

S = Slave

1 = Earth leak detector

2 = Fuse

3 = Remote control

4TW26329-7

1

9

30 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

10 Sound data

10 - 1 Sound pressure spectrum

REQ71B - Cooling REQ71B - Heating

3TW26597-1

NOTES

Octave band center frequency (Hz)

1 Data is valid at free field condition

2 Data is valid at nominal operation condition

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)

4 Reference acoustic pressure 0dB = 20μPa

5 Curve for REQ71B in cooling mode

Measuring location

(discharge side)

REQ100B - Cooling

3TW26597-2

NOTES

Octave band center frequency (Hz)

1 Data is valid at free field condition

2 Data is valid at nominal operation condition

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)

4 Reference acoustic pressure 0dB = 20μPa

5 Curve for REQ71B in heating mode

Measuring location

(discharge side)

REQ100B - Heating

1

10

31

3TW26617-1

NOTES

Octave band center frequency (Hz)

1 Data is valid at free field condition

2 Data is valid at nominal operation condition

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)

4 Reference acoustic pressure 0dB = 20μPa

5 Curve for REQ100B in cooling mode

Measuring location

(discharge side)

• Split Sky Air • Outdoor Units

3TW26617-2

NOTES

Octave band center frequency (Hz)

1 Data is valid at free field condition

2 Data is valid at nominal operation condition

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)

4 Reference acoustic pressure 0dB = 20μPa

5 Curve for REQ100B in heating mode

Measuring location

(discharge side)

REQ125B - Cooling

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

10 Sound data

10 - 1 Sound pressure spectrum

REQ125B - Heating

3TW26637-1

NOTES

Octave band center frequency (Hz)

1 Data is valid at free field condition

2 Data is valid at nominal operation condition

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)

4 Reference acoustic pressure 0dB = 20μPa

5 Curve for REQ125B in cooling mode

Measuring location

(discharge side)

3TW26637-2

NOTES

Octave band center frequency (Hz)

1 Data is valid at free field condition

2 Data is valid at nominal operation condition

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)

4 Reference acoustic pressure 0dB = 20μPa

5 Curve for REQ125B in heating mode

Measuring location

(discharge side)

1

10

32 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

10 Sound data

10 - 2 Sound power spectrum

REQ71B - Cooling REQ100B - Cooling

3TW26597-3

NOTES

Octave band center frequency (Hz)

1 Data is valid at free field condition

2 Data is valid at nominal operation condition

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)

4 Reference acoustic pressure 0dB = 20μPa

5 Curve for REQ71B in cooling mode

REQ125B - Cooling

3TW26617-3

NOTES

Octave band center frequency (Hz)

1 Data is valid at free field condition

2 Data is valid at nominal operation condition

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)

4 Reference acoustic pressure 0dB = 20μPa

5 Curve for REQ100B in cooling mode

1

10

33

3TW26637-3

NOTES

Octave band center frequency (Hz)

1 Data is valid at free field condition

2 Data is valid at nominal operation condition

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)

4 Reference acoustic pressure 0dB = 20μPa

5 Curve for REQ125B in cooling mode

• Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

11 Installation

11 - 1 Installation method

REQ71 ∼ 125B

Oil trap

Indoor unit

Oil trap

Outdoor unit

Gas piping

Liquid piping

NOTE:

Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases of deterioration of oil return, it well be necessary to provide a trap at an appropriate place in the riser gas piping.

A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.

4TW25149-8

1

11

• Split Sky Air • Outdoor Units 34

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

11 Installation

11 - 2 Service space

REQ71 ∼ 125B

A. Non stacked installation

B. Stacked installation

1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet

Legend

Suction side obstacle

Discharge side obstacle

Left side obstacle

Right side obstacle

Top side obstacle

Obstacle is present

In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.

In these cases, only 2 units can be installed.

This situation is not allowed.

Figures between ( ) indicate the dimensions only for the

100-125 class models.

1

11

Do not stack more than one unit.

About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.

Get the portion A sealed so that air from the outlet does not bypass.

C. Multiple-row installation

1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row

Relation of dimensions of H, A, and L are shown in the table below.

L ≤ H

H < L

L

0 < L ≤ 1/2 H

A

150 (250)

1/2 H < L 200 (300)

Installation impossible

3TW25149-4A

35 • Split Sky Air • Outdoor Units

• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B

12 Operation range

REQ71 ∼125B

Cooling

REQ71BV3

REQ71BW1

Model name

REQ100BV3

REQ100BW1

Heating

REQ125BW1

Indoor temp. (°CWB)

Notes:

- Depending on operation and installation conditions, the indoor unit can change over to freeze-up operation (indoor de-icing).

- To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install the outdoor unit in a location not exposed to wind.

Indoor temperature (°CDB)

3TW26593-1

1

12

36 • Split Sky Air • Outdoor Units

advertisement