P36D-1 Zero Clearance

Direct Vent Gas Fireplace

MODELS: P36D-NG1 Natural Gas P36D-LP1 Propane

Owners & Installation Manual

WARNING:

If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.

FOR YOUR SAFETY

Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.

FOR YOUR SAFETY

What to do if you smell gas:

Do not try to light any appliance

Do not touch any electrical switch: do not use any phone in your building.

Immediately call your gas supplier from a neighbour's phone. Follow the gas

Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.

If you cannot reach your gas supplier, call the fi re department.

Tested by:

918-522b

Installer: Please complete the details on the back cover

and leave this manual with the homeowner.

Homeowner: Please keep these instructions for future reference.

FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4

05/04/11

To the New Owner:

Congratulations!

You are the owner of a state-of-the-art Gas Fireplace by REGENCY

®

FIREPLACE PROD-

UCTS The P36D-1 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The model P36D-1 has been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your REGENCY

®

Fireplace.

2

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE

This REGENCY

®

product has been tested and listed by Warnock Hersey to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88a-2007/

CSA 2.33a-2007 and GAS-FIRED APPLIANCES FOR USE AT HIGH ATLITUDES CAN/CGA 2.17-M91.

This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities

ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.

This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current

National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA B149 Gas Installation

Code and the current Canadian Electrical Code CSA C22.1 in Canada.

This FPI Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the unit.

This FPI Mobile/Manufactured Home listed appliance comes equipped with a dedicated #8 ground lug to which an 18 gauge copper wire from the steel chassis ground must be attached.

This appliance may only be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes.

This appliance is only use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.

3

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

TABLE OF CONTENTS

SAFETY LABEL

Copy of Safety Decal for P36D-1 ..................................6

REQUIREMENTS

MA Code - CO Detector.................................................7

Unit Dimensions ............................................................8

Hampton Faceplate Dimensions ...................................8

Before You Start ............................................................9

Important Message .....................................................10

General Safety Information..........................................10

Installation Checklist ...................................................10

Locating Your

Gas Fireplace .............................................................. 11

Manufactured Mobile Home Additional Requirements 11

Heatwave Duct System (Optional) ............................. 11

Heat Release kit (Optional) ........................................ 11

Clearances ..................................................................12

Regency

®

Clearances ..........................................13

Tripoli Arch Door Clearances ...............................13

Hampton

®

Clearances .........................................13

Regency ® Combustible Mantel Clearances ................14

Hampton ® Combustible Mantel Clearances ...............16

Regency ® Mantel Leg Clearances ...............................17

Hampton ® Trim

Mantel Leg Clearances................................................17

Framing And Finishing .................................................18

tripoli Arch Door Framing Note ....................................19

Unit Assembly Prior To Installation ..............................20

Top Standoff Assembly ........................................20

Top Facing Support &

Side Nailing Strips ...............................................20

Venting Introduction .....................................................20

Exterior Vent Termination Locations ............................21

Venting.........................................................................22

Direct Vent System (Flex) ..................................22

4” x 6-5/8” Rigid Pipe Cross Reference Chart .............23

Rigid Pipe Venting Systems .................................25

Venting Arrangements

Horizontal Termination .................................................26

Venting Arrangements Vertical Termination .................27

Horizontal Venting with Two (2) 90 o Elbows ................29

Horizontal Venting with Three (3) 90 o Elbows .............29

Vertical Venting with Two (2) 90 o Elbows .....................30

Vertical Venting with Three (3) 90 o Elbows ..................30

Vertical Termination With Co-linear Flex System .........31

Venting Arrangement - Vertical Terminations ..............32

Unit installation with Horizontal termination .................33

Unit installation with Vertical Termination ....................34

Direct Vent System (Flex)

Installation Procedures ................................................35

P36D-NG1 System Data ............................................36

P36D-LP1 System Data .............................................36

High Elevation .............................................................36

Gas Line Installation ....................................................36

Pilot Adjustment ...........................................................36

Gas Pipe Pressure Testing ..........................................36

S.I.T. Valve Description ................................................36

Conversion from NG to LP ..........................................37

Optional Brick Panels ..................................................40

Log Set Installation ......................................................42

Standard Flush Door ...................................................45

Remote Control (Optional)...........................................46

Wall Switch (Optional) .................................................46

Wall Thermostat (Optional) .........................................46

Wiring Diagrams .........................................................47

Optional Fan Installation ..............................................49

Optional Fan Removal .................................................49

4

NOTE:

All installation instructions apply to

Regency

®

& Hampton

®

Series unless otherwise specifi ed.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

OPERATING INSTRUCTIONS

Operating Instructions .................................................50

Shutdown Procedure ...................................................50

First Fire ......................................................................50

Lighting Procedure ......................................................50

Aeration Adjustment ....................................................50

Normal Operating Sounds Of Gas Appliances ............50

Copy of the Lighting Plate Instructions ........................51

MAINTENANCE

Maintenance Instructions.............................................51

General Vent Maintenance ..........................................52

Gold or Brass...............................................................52

Louvers & Trim ............................................................52

Log Replacement ........................................................52

Thermopile/Thermocouple...........................................52

Glass Gasket ...............................................................52

Door Glass...................................................................52

Flush Glass Replacement ....................................52

Bay Glass Replacement ......................................52

Removing Valve ...........................................................53

Installing Valve .............................................................53

Flush Trim ....................................................................54

Flush Louvers ..............................................................54

Bay Door......................................................................55

Bay Trim ......................................................................55

Bay Louvers.................................................................55

Full Screen door Installation .....................................56

Tripoli screen door .......................................................58

Hampton ® Cast Faceplate ...........................................61

Hampton ® Cast Grills ...................................................62

TABLE OF CONTENTS

PARTS LIST

Main Assembly ............................................................63

Burner Assembly & Log Set.........................................64

Regency

®

Bay Front Assembly ....................................65

Regency

®

Flush Front Assembly .................................66

Hampton

®

Cast

Faceplate & Grill Assembly..........................................67

WARRANTY

The Warranty: Limited Lifetime ...................................71

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

SAFETY LABEL

This is a copy of the label that accompanies each P36D-1 Zero Clearance Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. The safety label is located on the front inside base of the unit, visible when the bottom louver is open.

NOTE: FPI units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.

COPY OF SAFETY DECAL FOR P36D-1

Duplicate S/N

306

Listed:

VENTED GAS FIREPLACE HEATER / FOYER AU GAZ À ÉVACUATION

CANADA and U.S.A.

Tested to:

CGA-2-17-M91, ANSI Z21.88a-2007 / CSA 2.33a-2007

WN# 16462

MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE

.

DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE

306

Serial No./ No de serie

NATURAL GAS:

L

Model P36D-NG1

Minimum supply pressure

Manifold pressure high

5"

3.8"

Manifold pressure low

Orifice size

Minimum input

Maximum input

Altitude

1.1"

# 37

WC(1.25 kPa)

WC(0.95 kPa)

WC(0.27 kPa)

DMS

15,500 Btu/h (4.54 kW)

30,000 Btu/h (8.79 kW)

0-4500 ft/pi(0-1372 m)

APPAREIL FONCTIONNANT AU NATURAL GAZ

CONCU POUR ETRE POELE: Modéle P36D-NG1

Pression d'allimentation minimum

Grandeur de l'injecteur

Calorifique minimum selon

Calorifique l'altitude maximum selon

B

Minimum Clearances to Combustibles /

Degagement Minimum De Materiaux Combustibles

Ceiling

32"

0" Clearance to combustibles from:

Top, sides, bottom and rear of unit

A

B

Mantel Clearances from Top:

(A) Min. 7" (177mm)

Side Wall Clearance from Side Facing

B) 6" with Flush or Bay Front

B) 8" with Barcelona Trim

PROPANE:

L

Minimum input

Maximum input

Altitude

Model P36D-LP1

Minimum supply pressure

Manifold pressure high

Manifold pressure low

Orifice size

12"

11"

2.9"

# 52

WC(3.00 kPa)

WC(2.74 kPa)

WC(0.72 kPa)

DMS

15,000 Btu/h (3.96 kW)

30,000 Btu/h (7.91 kW)

0-4500 ft/pi(0-1372 m)

APPAREIL FONCTIONNANT AU GAZ PROPANE

CONCU POUR ETRE POELE: Modéle P36D-LP1

Pression d'allimentation minimum

Grandeur de l'injecteur

Calorifique minimum selon

Calorifique l'altitude maximum selon

The "Bay Louvers" MUST be used with the Bay Glass option

DOOR SEAL: Please check that the door is properly sealed

(

See Instruction Manual for detailed instructions)

Alcove approved for

Bay & Flush Louvers.

Alcove Clearances:

Max. Depth 36" (914mm)

Min. Width 48" (1219mm),

Min. Height 72" (1229mm)

Minimum Vent Clearances:

Horizontal Top

Horizontal Side

2-1/2" (64mm)

1-1/2" (38mm)

Horizontal Bottom 1-1/2" (38mm)

This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1.

This appliance must be installed in accordance with the Standard CAN/CSA Z240 MH, Mobile Housing, in Canada, or with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United

States, or when such a standard is not applicable, ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations Standard or ANSI A119.2 ou NFPA 501C Standard for Recreational Vehicles

This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured (mobile) home where not prohibited by local codes. See owner's manual for details.

Fan (Part # 432-917) Optional Bay Window (Part #510-930) Option: HeatWave Kit # 946-556

Installer l'appareil selon les codes ou règlements locaux, ou, en l'absence de tels règlements, selon les codes d'installation ANSI Z223.1, National Fuel Gas Code ou CSA-B149.1 en vigueur.

Installer l'appareil selon la norme CAN/CSA-Z240, Série MM, Maison mobiles ou CAN/CSA-Z240 VC, Véhicules de camping, ou la norme 24 CFR Part 3280, Manufactured Home Construction and Safety Standard. Si ces normes ne sont pas pertinentes, utilisez la norme ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations Standard, ou ANSI A119.2 ou NFPA 501C Standard for Recreational Vehicles.

Cet appareil doit être utilize uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil peut être installé dans une maison préfabriquée ou mobile (É.-U. seulement) installée à demeure si les règlements locaux le permettent. Voir la notice de l'utilisateur pour plus de renseignements. Cet appareil ne peut pas être utilisé avec d'autres gaz sauf si une trousse de conversion certifiée est fournie.

This vented gas fireplace heater is not for use with air filters.

For use with glass doors certified with the appliance only

Ne pas utiliser de filtre à air avec ce foyer au gaz à évacuation.

Pour utilisation uniquement avec les portes en verre certifiées avec l'appareil

Made in Canada/

Fabrique au Canada

Electrical supply / Électrique 115VAC, 1.13 A, 60Hz.

FPI Fireplace Products International Ltd.Delta, BC, Canada

VENTED GAS FIREPLACE HEATER -NOT FOR USE WITH SOLID FUELS.

FOYER AU GAZ À ÉVACUATION NE PAS UTILISER AVEC DU COMBUSTIBLE SOLIDE.

918-500a

6

For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth of

Massachusetts.

For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.

For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.

The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

REQUIREMENTS

MA Code - CO Detector

(for the State of Massachusetts only)

5.08:

Modifications to NFPA-54, Chapter 10

(2) Revise 10.8.3 by adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight

(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size,

"GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS".

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR

5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1. Detailed instructions for the installation of the venting system design or the venting system components; and

2. A complete parts list for the venting system design or venting system.

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a

Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies

"special venting systems", the following requirements shall be satisfied by the manufacturer:

1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and

2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

7

INSTALLATION

UNIT DIMENSIONS

33"(838mm)

36" (914mm)

36"(914mm)

17-1/8"(435mm)

HAMPTON FACEPLATE DIMENSIONS

43-1/4” (1099mm)

1-1/4” (32mm)

8

32-1/4” (819mm)

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

BEFORE YOU START

Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI

Standards to make you aware of the following:

INSTALLATION AND REPAIR SHOULD

B E D O N E B Y A N AU T H O R I Z E D

SERVICE PERSON. THE APPLIANCE

SHOULD BE INSPECTED BEFORE

USE AND AT LEAST ANNUALLY BY A

PROFESSIONAL SERVICE PERSON.

MORE FREQUENT CLEANING MAY

BE REQUIRED DUE TO EXCESSIVE

LINT FROM CARPETING, BEDDING

MATERIAL, ETC. IT IS IMPERATIVE THAT

CONTROL COMPARTMENTS, BURNERS

AND CIRCULATING AIR PASSAGEWAYS

OF THE APPLIANCE BE KEPT CLEAN.

YOUNG CHILDREN SHOULD BE CARE-

FULLY SUPERVISED WHEN THEY ARE

IN THE SAME AREA AS THE APPLI-

ANCE. TODDLERS, YOUNG CHILDREN

AND OTHERS MAY BE SUSCEPTIBLE

TO ACCIDENTAL CONTACT BURNS. A

PHYSICAL BARRIERS IS RECOMMEND-

ED IF THERE ARE AT RISK INDIVIDUAL

IN THE HOUSE. TO RESTRICT ACCESS

TO A FIREPLACE OR STOVE, INSTALL

AN ADJUSTABLE SAFETY GATE TO

KEEP TODDLERS, YOUNG CHILDREN

AND OTHER AT RISK INDIVIDUALS OUT

OF THE ROOM AND AWAY FROM HOT

SURFACES.

CLOTHING OR OTHER FLAMMABLE

MATERIAL SHOULD NOT BE PLACED

ON OR NEAR THE APPLIANCE.

DUE TO HIGH TEMPERATURES, THE

APPLIANCE SHOULD BE LOCATED

OUT OF TRAFFIC AND AWAY FROM

FURNITURE AND DRAPERIES.

WARNING: FAILURE TO INSTALL THIS

APPLIANCE CORRECTLY WILL VOID

YOUR WARRANTY AND MAY CAUSE A

SERIOUS HOUSE FIRE.

CHILDREN AND ADULTS SHOULD BE

ALERTED TO THE HAZARDS OF HIGH

SURFACE TEMPERATURES, ESPE-

CIALLY THE FIREPLACE GLASS, AND

SHOULD STAY AWAY TO AVOID BURNS

OR CLOTHING IGNITION.

INSTALLATION

9

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

IMPORTANT MESSAGE

SAVE THESE

INSTRUCTIONS

to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.

The P36D-NG1 or P36D-LP1 Direct Vent Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fi replace is installed in compliance with manufacturer's instructions and all applicable codes.

13)

Do not slam shut or strike the glass door.

14)

Under no circumstances should any solid fuels

(wood, paper, cardboard, coal, etc.) be used in this appliance.

15)

The appliance area must be kept clear and free of combustible materials, (gases and other fl ammable vapours and liquids).

Emissions from burning wood or gas could contain chemicals known to the State of

California to cause cancer, birth defects or other reproductive harm.

GENERAL SAFETY

INFORMATION

1)

The appliance installation must conform with local codes or, in the absence of local codes, with the current Canadian or National Gas Codes,

CAN1-B149 or ANSI Z223.1 Installation Codes.

INSTALLATION

CHECKLIST

1)

Locate appliance a) Room location (Refer to "Locating Your Gas fi replace" section) b) Clearances to Combustibles (Refer to

"Clearances" section) c) Mantle Clearances (Refer to "Combustible

Mantel Clearances" section) d) Framing & Finishing Requirements (Refer to "Framing & Finishing" section) e) Venting Requirements (Refer to "Venting" section)

2)

Assemble Top Standoffs and Top Facing

Support and Side Nailing Strips (Refer to "Unit

Assembly Prior to Installation" Section). NOTE:

Must be done before installing unit into place.

3)

Install vent (Refer to "Venting" sections).

2)

The appliance when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Canadian Electrical Code.

3)

See general construction and assembly instructions. The appliance and vent should be enclosed.

4)

This appliance must be connected to the specifi ed vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fi tted as per Venting instructions.

5)

Inspect the venting system annually for blockage and any signs of deterioration.

6)

Venting terminals shall not be recessed into a wall or siding.

7)

Any safety glass removed for servicing must be replaced prior to operating the appliance.

8)

To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fi replace.

9)

Wear gloves and safety glasses for protection while doing required maintenance.

10)

Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.

11)

Under no circumstances should this appliance be modifi ed. Parts that have to be removed for servicing should be replaced prior to operating this appliance.

12)

Installation and any repairs to this appliance should be done by a qualifi ed service person.

A professional service person should be called

4)

Make gas and electrical connections. Test the pilot. Must be as per diagram (Refer to "Pilot

Adjustment " section).

Convert to propane if desired (Refer to "Gas

Line Installation" and "Conversion Kit from NG to LPG" sections).

5)

Install standard and optional features. Refer to the following sections: a. Optional Brick Panels b. Log Set Installation c. Standard Flush Door

Regency

®

Flush or Bay Fronts

Hampton ® Cast Faceplate f. Remote Control (Optional) g. Wall Switch (Optional) h. Wall Thermostat (Optional) i. Optional Fan Installation

6)

Final

10

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

This includes:

1)

Clocking the appliance to ensure the correct fi ring rate (rate noted on label 30,000 Btu/h) after burning appliance for 15 minutes.

2)

If required, adjusting the primary air to ensure that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.

CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.

LOCATING YOUR

GAS FIREPLACE

1)

When selecting a location for your fi replace, ensure that the clearances outlined on this page are met.

2)

P r o v i d e a d e q u a t e c l e a r a n c e s f o r servicing.

3)

The appliance must be installed on a fl at, solid, continuous surface (e.g. wood, metal, concrete). This may be the fl oor, or raised up on a platform to enhance its visual impact.

If the appliance is going to be installed on carpeting, combustible linoleum tile or other combustible material other than wood fl ooring, the appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.

4)

The P36D-1 Direct Vent Gas Fireplace can be installed in a recessed position or framed out into the room as in A, B, C, D.

See Diagram 1.

Diagram 1

INSTALLATION

MANUFACTURED

MOBILE HOME

ADDITIONAL

REQUIREMENTS

1)

Ensure that structural members are not cut or weakened during installation.

2)

Ensure proper grounding using the #8 ground lug provided. See "Wiring Diagram" section.

A)

Flat on Wall

B)

Flat on Wall Corner

C)

Recessed into Wall/Alcove

D)

Corner

HEATWAVE

DUCT SYSTEM

(OPTIONAL)

#946-556

5)

This appliance is Listed for bedroom installations when used with a Listed Millivolt

Thermostat. Some areas may have further requirements, check local codes before installation.

The

HeatWave

Air Duct Kit increases the effectiveness of your fi replace by dispersing warm air from the fi replace to remote locations in the same room or other rooms in your home.

6)

The P36D-1 Direct Vent Gas Fireplace is approved for alcove installations, which meet the clearances listed on the next page.

Up to two kits may be installed on the fi replace.

Please Note:

Only 1 HeatWave kit may be operated at one time. This includes the internal blower option as well.

7)

We recommend that you plan your installation on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have a qualifi ed inspector, dealer, or installer review your plans before installation.

Note: For vent terminations see "Exterior

Vent Termination Location" section.

HEAT RELEASE KIT

(OPTIONAL)

#946-570

The Heat Release Kit expels warm air from the fi replace to the outside of the building, allowing the fi replace to be operated with less heat entering the room. The kit may be used on either the left or right side.

11

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fi replace and vent system be installed only in accordance with these instructions.

Clearance to Combustibles from:

Back

(0mm)

Side

(0mm)

Floor

(0mm)

NOTE: The minimum fl oor clearance must be maintained from the top surface of the carpeting, tile, etc.

Minimum Clearance from Top of Unit to:

Ceiling

32" (1016mm)

Side Wall Clearances:

Bay or Flush Front

6"*

Hampton Cast Faceplate

Full Screen Doors

6"* (152mm)

* Measured from Surround or Front. See Regency ® Clearances section for dimensions.

Horizontal Vent Clearances:

Top

(51mm)

Side

(38mm)

Bottom

(38mm)

Vertical Vent Clearances

1-1/4"

Alcove Clearances**:

Max.

(914mm)

Min.

Min.

(1829mm)

WARNING: Fire hazard is an extreme risk if these clearances are not adhered to.

Heat Release Kit

The

HeatWave

Duct Kit and the Heat

Release Kit have different clearance and framing requirements, check the

HeatWave

and Heat Release manual for details.

12

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

REGENCY

®

CLEARANCES

INSTALLATION

Clearances for Bay Front, Flush Front

& Full Screen Doors

TRIPOLI ARCH DOOR CLEARANCES

HAMPTON

®

CLEARANCES

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

13

INSTALLATION

REGENCY

®

COMBUSTIBLE MANTEL CLEARANCES

Because of the extreme heat this fi replace emits, the mantel clearances are critical.

Combustible mantel clearances from top of unit are shown in Diagrams 1 & 2.

Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board.

10

8

6

4

16

14

12

2

0

Mantel Clearances with

12 10 8 6 4

2

14"

12" Mantel

7 1/2" Mantel

3 1/2"

Mantel

10"

7"

Drywall

16

14

12

10

8

6

4

2

0

30-1/2" to floor

Top of

Unit

12

Mantel Clearances

10

with Bay Option

8 6 4

2

0

13" to floor

12" Mantel

30-1/2"

7 3/4“ Mantel

10"

3 1/2"

Mantel

Top of

Unit

7"

Drywall

Side View

Side View

Diagram 1

Diagram 2

These drawings are to scale at 1:6 (one inch = 6 inches)

Mantel can be installed anywhere in shaded area or higher using the above scale.

Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.

14

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

REGENCY

®

SERIES COMBUSTIBLE MANTEL CLEARANCES

Because of the extreme heat this fi replace emits, the mantel clearances are critical.

Combustible mantel clearances from top of unit are shown in the diagram below.

Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board.

These drawings are to scale at 1:6 (one inch = 6 inches)

Mantel can be installed anywhere in shaded area or higher using the above scale.

Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

15

INSTALLATION

HAMPTON

®

COMBUSTIBLE MANTEL CLEARANCES

Because of the extreme heat this fi replace emits, the mantel clearances are critical.

Combustible mantel clearances from top of unit are shown in the diagram below.

Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board.

Mantel Clearances with

16

These drawings are to scale at 1:6 (one inch = 6 inches)

Mantel can be installed anywhere in shaded area or higher using the above scale.

Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

REGENCY

®

MANTEL LEG CLEARANCES

Combustible mantel leg clearances as per diagram:

INSTALLATION

Maximum 1-1/2" projection at 2" minimum clearance.

HAMPTON

®

TRIM

MANTEL LEG CLEARANCES

Combustible mantel leg clearances as per diagram:

P36D

Fireplace

Hampton ® Cast Faceplate Width: 43-1/4"

Hampton

Cast Faceplate

Measure from edge of Faceplate.

Maximum 1-1/2" projection at 2" minimum clearance.

2"

5"

Allowable mantel leg projection.

6" Min.

17

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

FRAMING AND FINISHING

1)

Determine the total thickness of facing material (e.g. drywall plus ceramic tiles) to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.

NOTE: See next page for important

Barcelona™ Series framing note.

A

Framing Dimensions

B C D

36-1/4" 37-1/4" 17-3/8" 46-1/2"*

921mm 946mm 441mm 1181mm*

* 'D' is Minimum height to combustible materials including the Minimum 2-1/2" (64mm) Top clearance to the Horizontal Vent.

Note: 40-1/2" (1029mm) is the minimum height for both fl ex termination or

Simpson Dura-Vent venting.

Note: The unit does not have to be completely enclosed in a chase. The clearance on top of the unit is 0" to the standoffs so combustible building materials can be laid directly on top of the standoffs.

You must maintain clearance from the vent to combustible materials for fl ex, see Vent Clearances.

3)

For exterior walls, insulate the enclosure to the same degree as the rest of the house, apply vapour barrier and drywall, as per local installation codes.

(Do not insulate the fi replace itself.)

5)

Use steel studs for framing where the

1-1/2" (38mm) clearance from the vent to combustible material cannot be maintained, e.g. front top header.

Install Side Nailing Strips, Top Facing

Support, and Top Standoffs before unit is slipped into position. See "Unit Assembly

Prior to Installation" section for assembly details.

4)

The top of the unit must not be closer than

32" (813mm) to the ceiling.

2)

Frame in the enclosure for the unit with framing material. The framed opening is

37-1/4" high x 36-1/4" wide x 17-3/8" deep

(946mm high x 921mm wide x 441mm deep).

18

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

TRIPOLI ARCH DOOR FRAMING NOTE

When installing the optional Tripoli Arch Door, a non-combustible material 12" (305mm) above the unit and 6" (153mm) on each side must be used. See diagram 2.

For complete framing dimensions - see page 57 in this manual.

The Tripoli Arch Door also

requires steel stud framing

above and on each side of the unit, see diagram 2.

Diagram 2

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

19

INSTALLATION

UNIT ASSEMBLY

PRIOR TO

INSTALLATION

The Top Facing Support, the Side Nailing Strips and the 2 Top Standoffs must be correctly positioned and attached to the top before unit is slipped into position.

Top Standoff Assembly

Top Facing Support &

Side Nailing Strips

Determine the total thickness of facing material

(e.g. drywall plus ceramic tiles) to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2"

(13mm) to 1-1/4" (32mm) thick.

The Top Facing Support can be mounted in 3 different positions depending on the thickness of the facing material.

The top standoffs are shipped in a fl at position and must be folded into shape and attached.

"C" Screw Position:

For a facing material depth of 1-1/4" (32mm), the top facing support must be reversed.

1) Remove the standoffs from the fi replace top.

2) Take each standoff and bend into the correct shape. Bend up at the bend lines until the screw holes in the standoff and the prepunched screw holes on the fi replace top line up.

Screw

Position

A

B

C

*

Facing Material

Depth

1/2" / 13mm

7/8" / 22mm

1-1/4" / 32mm

2)

Fold out the two nailing strips on each side.

3) Attach the standoff securely to the top with

2 screws per standoff (on opposite corners).

*

For "C" screw position the top facing support is reversed.

1)

Mount Top Facing Support using the 3 supplied screws into the three pre-punched screw holes on the top front of the unit. Use hole positions A, B, or C depending on your facing depth.

Side

Nailing Strips

VENTING

INTRODUCTION

The P36D-1 uses the "balanced fl ue" technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.

Note: These flue pipes must not be connected to any other appliance.

The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance.

Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.

20

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

EXTERIOR VENT TERMINATION LOCATIONS

INSTALLATION

Minimum Clearance Requirements

Canada

1

USA

2

A

B

C

D

Clearance above grade, veranda, porch, deck, or balcony

Clearance to window or door that may be opened

Clearance to permanently closed window

Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm)

from the center line of the terminal (check with the local code)

12"(30cm)

12"(30cm)

*

1 8 "(46cm)

12"(30cm)

9" (23cm)

*

1 8 "(46cm)

E

F

G

H

J

K

L

Clearance to unventilated soffi t

Clearance to outside corner: with

AstroCap

Termination Cap.

Clearance to outside corner: with all other approved Termination Caps.

Clearance to inside corner: with

AstroCap

Termination Cap

Clearance to inside corner: with all other approved Termination Caps.

Clearance to each side of center line extended above meter/regulator assembly

Clearance to service regulator vent outlet

Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance

Clearance to a mechanical air supply inlet

#3' (91cm) above if within 10' (3m) horizontally.

15"(3 8 cm)

6"(15cm)

14"(36cm)

6"(15cm)

12"(30cm)

36"(90cm) a

36"(90cm)

12"(30cm)

72"(1.

8 m)

15"(3 8 cm)

6"(15cm)

14"(36cm)

6"(15cm)

12"(30cm)

*

*

9" (23cm)

36"(90cm)

M

Clearance above paved sidewalk or a paved driveway located on public property 8 4"(2.1m)

*

N

Clearance under veranda, porch, deck, or balcony 12"(30cm)

*

1

In accordance with current CSA B149.1,

Natural Gas and Propane Installation Code

2

In accordance with the current

ANSI Z223.1/NFPA 54, National Fuel Gas Code

A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.

* Clearance in accordance with local installation codes and the requirements of the gas supplier

3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly b

3 feet (91cm) above - if within 10 feet (3m) horizontally b

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

21

INSTALLATION

VENTING

DIRECT VENT SYSTEM (FLEX)

HORIZONTAL TERMINATIONS ONLY

These venting systems, in combination with the P36D-1 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by

Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in the "Exterior Vent

Termination Locations" section.

FPI Direct Vent (Flex) System Termination Kit (Part # 946-515) includes all the parts needed to install the P36 with a maximum run of 4 feet.

7)

8)

9)

1)

2)

3)

4)

5)

6)

6-7/8" dia. fl exible liner (4 ft. length)

4" dia. fl exible liner (4 ft. length) spring spacers (4) thimble (2)

AstroCap

termination cap (1) screws (12) tube of Mill Pac (1) plated screws (8) screws #8 x 1-1/2" Drill Point, Stainless

Steel (4)

If longer runs are needed, the FPI Direct

Vent system (Flex) # 946-516 includes all the parts needed to install the P36 with a maximum 10' run.

1)

2)

3)

4)

5)

6)

7)

8)

9)

6-7/8" dia. fl exible liner (10 ft. length)

4" dia. fl exible liner (10 ft. length) spring spacers (7) thimble (2)

AstroCap

termination cap (1) screws (12) tube of Mill Pac (1) plated screws (8)

screws #8 x 1-1/2" Drill Point, Stainless

Steel (4)

Notes:

1) Liner sections should be continuous without any joints or seams.

2) Only Flex pipe purchased from FPI may be used for Flex installations.

3) If you are installing the P36 into a FPI Cabinet Mantel Kit, use the minimum horizontal vent height (centre-line of 40-1/2"). Remember to include the mantel base (3" in height) in your calculations and to maintain the 2" clearance to the underside of the mantel top.

22

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART

Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.

Description

6” Pipe Length-Galvanized

6” Pipe Length-Black

7” Pipe Length-Galvanized

7” Pipe Length-Black

9” Pipe Length-Galvanized

9” Pipe Length-Black

12” Pipe Length-Galvanized

12” Pipe Length-Black

1 8 ” Pipe Length-Galvanized

1 8 ” Pipe Length-Black

24” Pipe Length-Galvanized

24” Pipe Length-Black

36” Pipe Length-Galvanized

36” Pipe Length-Black

4 8 ” Pipe Length-Galvanized

4 8 ” Pipe Length-Black

60” Pipe Length-Galvanized

60” Pipe Length-Black

Adjustable Length 3”-10”-Galvanized

Adjustable Length 3”-10”-Black

Adjustable Length 7”-Galvanized

Adjustable Length 7”-Black

Extension Pipe 8 -1/2”-Galvanized

Extension Pipe 8 -1/2”-Black

Adjustable Length 12”-Galvanized

Adjustable Length 12”-Black

Extension Pipe 16”-Galvanized

Extension Pipe 16”-Black

45

º

Elbow-Galvanized

45

º

Elbow-Black

45

º

Elbow Swivel-Galvanized

45

º

Elbow Swivel-Black

90

º

Elbow-Galvanized

90

º

Elbow-Black

90

º

Elbow, Swivel-Galvanized

90

º

Elbow, Swivel-Black

90

º

Starter Elbow, Swivel-Galvanized

Adaptor*

Ceiling Support

Cathedral Support Box

Wall Support/Band

Offset Support

Wall Thimble-Black

Wall Thimble Support/Ceiling Support

Firestop Spacer

Trim Plate-Black

Simpson

Direct Vent Pro

®

46DVA-06

46DVA-06B

N/A

N/A

46DVA-09

46DVA-09B

46DVA-12

46DVA-12B

46DVA-1 8

46DVA-1 8 B

46DVA-24

46DVA-24B

46DVA-36

46DVA-36B

46DVA-4 8

46DVA-4 8 B

46DVA-60

46DVA-60B

N/A

N/A

N/A

N/A

46DVA-0 8 A

46DVA-0 8 AB

N/A

N/A

46DVA-16A

46DVA-16AB

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

46DVA-E45

46DVA-E45B

See 46DVA-E45

See 46DVA-E45B

46DVA-E90

46DVA-E90B

See 46DVA-E90

See 46DVA-E90B

N/A

N/A

4DT-EL45

4DT-EL45B

N/A

N/A

4DT-EL90S

4DT-EL90SB

N/A

N/A

N/A

N/A

N/A

46DVA-CS

46DVA-WS

46DVA-ES (N/A - FPI)

46DVA-WT

46DVA-DC

46DVA-FS

N/A

4DT-CS

4DT-CSS

4DT-WS/B

4DT-OS

4DT-WT

N/A

4DT-FS

4DT-TP

Selkirk

Direct Temp™

4DT-6

4DT-6B

N/A

N/A

4DT-9

4DT-9B

4DT-12

4DT-12B

4DT-1 8

4DT-1 8 B

4DT-24

4DT-24B

4DT-36

4DT-36B

4DT-4 8

4DT-4 8 B

4DT-60

4DT-60B

4D12B

4D1 8

4D1 8 B

4D24

4D24B

4D36

4D36B

4D4 8

4D4 8 B

N/A

N/A

American Metal

Products®

Amerivent Direct

N/A

N/A

4D7

4D7B

N/A

N/A

4D12

Metal-Fab™

Sure Seal

4D12B

4D1 8

4D1 8 B

4D24

4D24B

4D36

4D36B

4D4 8

4D4 8 B

N/A

N/A

4D6

4D6B

N/A

N/A

N/A

N/A

4D12

N/A

N/A

4D7A

4D7AB

N/A

N/A

4D12A

4D12A

N/A

N/A

4D45L

4DT-EL45B

N/A

N/A

4DT-EL90S

4DT-EL90SB

N/A

N/A

N/A

N/A

4DFSP

4DRSB

4DWS

N/A

4DWT

N/A

4DFSP

4DFPB

4 DSP

4DRS

4DWS

N/A

4DWT

N/A

4DFS

4DCP

N/A

N/A

4D45L

4D45LB

N/A

N/A

4D90L

4D90LB

4D90A

4D90L

N/A

N/A

N/A

N/A

4DAL

4DALB

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

TC-4DLT

TC-4DLTB

N/A

N/A

N/A

N/A

TE-4DE45

TE-4DE45B

N/A

N/A

TE-4DE90

TE-4DE90B

N/A

N/A

N/A

N/A

TE-4DE45

TE-4DE45B

N/A

N/A

TE-4DE90

TE-4DE90B

N/A

N/A

ICC Excel

Direct

TC-4DL6

TC-4DL6B

N/A

N/A

N/A

N/A

TC-4DL1

TC-4DL1B

TC-4DL1 8

TC-4DL1 8 B

TC-4DL2

TC-4DL2B

TC-4DL3

TC-4DL3B

TC-4DL4

TC-4DL4B

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

SV4LA12

SV4LBA12

N/A

N/A

SV4SD

SV4CSB

SV4BM

SV4SU

SV4RSM

SV4PF

SV4BF

SV4LA

N/A

N/A

SV4E45

SV4EB45

N/A

SV4EBR90-1

SV4E90-1

SV4EB90-1

N/A

N/A

Security

Secure- Vent®

SV4L6

SV4LB6

N/A

N/A

N/A

N/A

SV4L12

SV4LB12

SV4LA

SV4LA

SV4L24

SV4LB24

SV4L36

SV4LB36

SV4L4 8

SV4LB4 8

N/A

N/A

23

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

24

Description

Simpson

Direct Vent Pro

®

Attic Insulation Shield 12” 46DVA-IS

N/A@ FPI

N/A

Attic Insulation Shield - Cold Climates 36” N/A N/A

Selkirk

Direct Temp™

American Metal

Products®

Amerivent Direct

4DAIS12

4DAIS12

N/A

N/A

Metal-Fab™

Sure Seal

Security

Secure- Vent®

SV4RSA

N/A

Basic Horizontal Termination Kit (A)

Horizontal Termination Kit (B)

Vertical Termination Kit

High Wind Vertical Cap

High Wind Horizontal Cap

Horizontal Square Termination Cap

Vertical Termination Cap

Storm Collar

Adjustable Flashing 0/12-6/12

Adjustable Flashing 6/12-12/12

Vinyl Siding Standoff

Vinyl Siding Shield Plate

Disc.

46DVA-KHA

(Changed Components)

Disc.

4DT-HKA

4DT-HKB

4DT-VKC

46DVA-VCH

46DVA-HC

See 46DVA-HC

46DVA-VC

46DVA-0 8 A

46DVA-F6

46DVA-FLA

46DVA-VSS

N/A

N/A

N/A

4DT-HHC

4DT-HVC

4DT-SC

4DT-ST14

4DT-ST36

4DT-VS

4DT-VSP

4DHTK2

4DHTK1

4DHTK

N/A

N/A

4DHC

4DVC

4DSC

4D12S

4D36S

N/A

N/A

4DHTKA

4DHTKB

4DHTK

N/A

N/A

4DHT

4DVT

4DSC

4DST14

4DST36

4DVS

N/A

SV-SHK

SV-HK

SV-FK

N/A

N/A

SV4CHC-1

SV4CGV-1

SV4FC

SV4STC14

SV4STC36

SV4VS

SV4VS

ICC Excel

Direct

N/A

TM-4AS

N/A

N/A

N/A

TM-4VT

TM-4DHT

TM-4HT

TM-4VT

TM-SC

TF-4FA

TF-4FB

TM-VSS

N/A

Snorkel Termination 14”

Snorkel Termination 36”

46DVA-SNKL

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

TM-4ST14

TM-4ST36

Restrictor Disk

Extended Vertical Termination Cap

Chimney Conversion Kit A (USA only)

Chimney Conversion Kit B (USA only)

Chimney Conversion Kit C (USA only)

Chimney Conversion Kit Masonry

(USA only)

Wall Firestop

Colinear Flex Connectors

N/A

N/A

46DVA-KCA

46DVA-KCB

46DVA-KCC

46DVA-KMC

46DVA-WFS

46DVA-ADF

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

TM-4DS

N/A

TM-4CA6

TM-4CA7

TM-4CA 8

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

TM-4TR

N/A

FPI

946-506/P

510-994

640-530/P

946-605

Vent Guard (Optional) for AstroCap

Rigid Pipe Adaptor (Must use with all rigid piping)

Riser Vent Terminal

Starter Collar Increaser 4” x 6-5/ 8 ” to 5” x 8 ”

946-205

946-20 8 /P

946-523/P

946-206

Vinyl Siding Shield for Riser Vent Terminal

Vent Guard (Optional) for Riser Vent Terminal

AstroCap Horizontal Cap

Vinyl Siding Standoff for AstroCap

Note:

When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).

Offset Pipe Selection:

Use this table to determine offset pipe lengths.

Pipe Length

(L)

4” x 6-5/ 8 ” Venting

Run (X) Rise (Y)

0” (0mm)

6” (152mm)

9” (229mm)

4-7/

8

8 ” (124mm)

” (203mm)

10-1/ 8 ” (257mm)

13-7/

16-1/2” (419mm)

1 8 -5/

8

8

” (340mm)

” (473mm)

12” (305mm)

24” (610mm)

36” (914mm)

4 8 ” (1219mm)

12-1/4” (311mm)

20-5/ 8 ” (524mm)

29” (737mm)

37-7/16” (951mm)

20-3/4” (527mm)

29-1/ 8 ” (740mm)

37-1/2” (953mm)

45-15/16” (1167mm)

For specifi c instructions on venting components - visit the manufacturers website listed below.

Simpson Direct Vent Pro: www.duravent.com

Selkirk Direct-Temp: www.selkirkcorp.com

American Metal Products: www.americanmetalproducts.com

Metal-Fab Sure Seal: www.mtlfab.com

Security Secure Vent: www.securitychimneys.com

Industrial Chimney Company: www.icc-rsf.com

Note:

Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination.

Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.

Regency Fireplace Products . 69 88 Venture St. . Delta, BC . Canada . V4G 1H4 . 604-946-5155 . www.regency-fi re.com

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

RIGID PIPE VENTING SYSTEMS

Horizontal or Vertical Terminations

The minimum components required for a basic horizontal termination are:

1 90 o

Elbow

1 Length of pipe to suit wall thickness

Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap.

For siding other than vinyl furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal must not be recessed into siding. Measure the wall thickness including furring strips.

If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2 inches.

Flat Wall Installation

Wall Thickness (inches) Vent Length Required (inches)

4" - 5-1/2"

7" - 8-1/2"

6"

9"

10" - 11-1/2"

9" - 14-1/2"

15" - 23-1/2"

4-1/4" - 5-3/4"

12"

11" - 14-5/8" Adj. Pipe

17" - 24" Adj. Pipe

Corner Installation

Wall Thickness (inches)

3-1/4" - 6-3/4"

Vent Length Required (inches)

11" - 14-5/8" Adj. Pipe

7-3/4" - 16-1/4"

7-1/4" - 8-3/4"

17" - 24" Adj. Pipe

6" + 12"

9" + 9"

6" + 9"

Vertical

Termination

Cap

Storm Collar

Flashing

Ceiling Firestop

Pipe Length

Alternate

Horizontal

Termination

Caps

Vinyl Siding

Standoff (Optional)

Horizontal

Termination

Cap

Wall Thimble o

90 Elbow

Adj.Pipe Length

11" - 14-5/8"

24" Pipe

Length

Rigid Pipe Adaptor

WARNING:

Do not combine venting components from different venting systems.

However use of the AstroCap TM and FPI Riser is acceptable with all systems.

This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with

DuraVent Direct Vent, Selkirk Direct-Temp, Ameri

Vent Direct venting and Security Secure Vent systems. Use of these systems with the Rigid

Pipe Adaptor is deemed acceptable and does not affect the Intertek WHI listing of components.

The FPI AstroCap TM and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent ® Direct Vent ,

American Metal Products, Security Secure Vent

®

, AmeriVent Direct Vent. AstroCap

TM

is the proprietary trademark of FPI Fireplace Products International

Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.

25

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

VENTING ARRANGEMENTS

HORIZONTAL TERMINATION

RIGID PIPE AND FPI DIRECT VENT SYSTEM (FLEX)

(Propane & Natural Gas)

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90 o elbow (two 45 o elbows equal one 90 o elbow).

Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe venting systems.

26

All Rigid Pipe Systems

4" inner diameter

6-5/8" outer diameter

FPI Flex Vent

4" inner diameter

6-7/8" inner diameter

A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.

Note: FPI Direct Vent Flex System Part #'s

946-515 and 946-516 are only approved for horizontal terminations.

• Maintain clearances to combustibles.

• Horizontal vent must be supported every 3 feet.

• Firestops are required at each fl oor level and whenever passing through a wall.

NOTE: If you are installing the P36D-1 into an FPI cabinet Mantel Kit, use the minimum horizontal vent height

(centre-line of 40-1/2"). Remember to include the mantel base (3" in height) in your calculations and to maintain the 2" clearance from the top with rigid or fl ex pipe systems to the underside of the mantel top.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

VENTING ARRANGEMENTS

VERTICAL TERMINATION

RIGID PIPE SYSTEM

(Propane & Natural Gas)

The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90 o elbow, with

rigid pipe

vent systems for Propane and Natural Gas.

• Vent must be supported at offsets.

• Firestops are required at each fl oor level and whenever passing through a wall.

• Maintain clearances to combustibles.

Note: Must use optional rigid pipe adaptor when using rigid vent systems (Part # 510-994).

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

27

INSTALLATION

The P36D-1 is approved for a 40 ft. straight vertical, with

rigid pipe

vent systems for Propane and Natural

Gas, as per the diagram 1.

The shaded area in the diagram 1 shows all allowable combinations of straight vertical and offset to vertical terminations with

rigid pipe

vent systems for Propane and Natural Gas. Maximum two 45 o elbows allowed.

• Vent must be supported at offsets

• Firestops are required at each fl oor level and whenever passing through a wall.

• Maintain clearances to combustibles.

28

Diagram 1

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

HORIZONTAL VENTING WITH TWO (2) 90

O

ELBOWS

INSTALLATION

H1

H

One 90 o

elbow = Two 45 o

elbows.

Option V

A)

H + H1

0' Min. 2' Max.

W i t h t h e s e o p t i o n s , maximum total pipe length is 30 feet with minimum B) 1' Min. 3' Max.

C) 2' Min. 4' Max.

of 6 feet total vertical and maximum 8 feet total

D) 3' Min. 5' Max.

E) 4' Min. 6' Max.

horizontal.

Please note minimum 1

F) 5' Min. 7' Max.

foot between 90 o elbows

G) 6' Min. 8' Max.

is required.

Lengths do not include elbow indicated.

HORIZONTAL VENTING WITH THREE (3) 90

O

ELBOWS

V

One 90 o elbow = Two 45 o elbows.

Option V H V + V1 H + H1

A) 0' Min. 1' Max. 1' Min. 2' Max.

B) 1' Min. 2' Max. 3' Min. 3' Max.

C) 2' Min. 2' Max. 5' Min. 4' Max.

D) 3' Min. 2' Max. 7' Min. 5' Max.

E) 4' Min. 3 Max. 9' Min. 6' Max.

F) 5' Min. 4' Max. 10' Min. 7' Max.

G) 6' Min. 5' Max. 11' Min. 8' Max.

H) 7' Min. 6' Max. 12' Min. 9' Max.

Lengths do not include elbow indicated.

With these options, max. total pipe length is 30 feet with min. of

12 feet total vertical and max. 9 feet total horizontal.

Please note min. 1 foot between 90 o elbows is required.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

29

INSTALLATION

VERTICAL VENTING WITH TWO (2) 90

O

ELBOWS

V1

One 90 o elbow = Two 45 o elbows.

Option V H V + V1

A) 0' Min. 2' Max. 1' Min.

B) 1' Min. 4' Max. 3' Min.

C) 2' Min. 5' Max. 4' Min.

D) 3' Min. 6' Max. 5' Min.

E) 4' Min. 7' Max. 6' Min.

F) 5' Min. 8' Max. 7' Min.

With these options, max. total pipe length is 30 feet with min. of 7 feet total vertical and max.

8 feet total horizontal.

Please note min. 1 foot between 90 o

elbows is required.

Lengths do not include elbow indicated.

VERTICAL VENTING WITH THREE (3) 90

O

ELBOWS

H

V

V1

One 90 o

elbow = Two 45 o

elbows.

Option V H + H1 V + V1

A)

B)

C)

0' Min. 2' Max. 2' Min.

1' Min. 2' Max. 3' Min.

2' Min. 3' Max. 4' Min.

D) 3' Min. 4' Max. 6' Min.

E) 4' Min. 5' Max. 7' Min.

F) 5' Min. 6' Max. 8' Min.

G) 6' Min. 7' Max. 9' Min.

H) 7' Min. 8' Max. 10' Min.

With these options, max. total pipe length is 30 feet with min. of 10 feet total vertical and max. 8 feet total horizontal.

Please note min. 1 foot between 90 o elbows is required.

Lengths do not include elbow indicated.

30

H1

H

V

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

THE APPLIANCE MUST NOT BE

CONNECTED TO A CHIMNEY FLUE

SERVING A SEPARATE SOLID FUEL

BURNING APPLIANCE.

VERTICAL TERMINATION

WITH CO-LINEAR FLEX SYSTEM

Masonry chimneys may take various contours which the fl exible liner will accommodate. However,

keep the fl exible liner as straight as possible

, avoid unnecessary bending.

The Air Intake pipe must be attached to the inlet air collar of the termination cap.

This appliance is designed to be attached to two 3" (76mm) co-linear aluminium fl ex running the full length of the chimney. See the Venting

Arrangements on next page for minimum and maximum heights.

Required Parts:

Part # Description

946-529 Co-linear DV Vertical

948-305 3" Flex - 35 ft.

946-563 Co-Axial to Co-Linear Adapter Kit which contains the following:

Co-linear Flex Adapter

Co-linear DV

Vertical Termination

Cap # 946-529

A maximum of two certified joiner kits may be used per length.

#948-305 (35 ft)

Flex Liner

Exhaust

Flue

FPI Cabinet and/or Flat Wall Mantles may be used in these applications ensuring that clearances to combustibles are maintained.

Outer

Pipe with Kit#

946-563

Pipe Length

Rigid Pipe Adapter

# 510-994

90 Degree

Elbow

Inner Pipe

Adapter with Kit#

946-563

Air Intake

Co-Linear

Flex

Adapter with Kit#

946-563

31

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

VENTING ARRANGEMENT - VERTICAL TERMINATIONS

CO-LINEAR FLEX SYSTEM

INTO MASONRY FIREPLACES

FOR BOTH RESIDENTIAL & MANUFACTURED HOMES

30

32

Horizontal Distance (Feet)

The shaded area in the diagrams show the allowable vertical terminations.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

UNIT INSTALLATION WITH

HORIZONTAL TERMINATION

b)

Horizontal runs of vent must be supported every three feet. Wall straps are available for this purpose.

Install the vent system according to the manufacturer's instructions included with the components.

1)

Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit and the electrical (junction block is on the left side) on the left.

2)

Direct Vent pipe and fi ttings are designed with special twist-lock connections to connect the venting system to the appliance fl ue outlet. A twist-lock appliance adaptor is an available option that must be used in conjunction with the Simpson Dura-Vent Direct Vent system.

3)

Put a bead of silicone inside the outer section of the adapter and a bead of Mill Pac on the inner collar. Slip the adapter over the existing inner and outer fl ue collar and fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier). Level the fi replace and fasten it to the framing using nails or screws through the nailing strips.

5)

Mark the wall for a 10" x 10" square hole. The center of the square hole should line up with the centerline of the horizontal pipe. Cut and frame the 10 inch square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material, i.e. masonry block or concrete, a 7"(178mm) dia. (7-1/2"(191mm) dia. for fl ex) hole is acceptable.

Note: With

D u r a - Ve n t , the minimum h e i g h t i s achieved by i n s t a l l i n g a 90 o elbow d i r e c t l y t o the rigid pipe adaptor.

Diagram 2

Notes:

a)

The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fi re.

Note: Riser Vent is only for use in above grade terminations.

Diagram 3a

*Diagrams 3 & 4: As specifi ed in CGA B149

Installation Code. Local codes or regulations may require different clearances.

Below Grade Installation

If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the Snorkel Termination. Refer to Diagram 4. Do not attempt to enclose the

Snorkel within the wall, or any other type of enclosure.

4)

Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.

Notes:

a) Twist-lock procedure: Four indentations, located on the female ends of pipes and fi ttings, are designed to slide straight onto the male ends of adjacent pipes and fi ttings, by orienting the four pipe indentations so they match and slide in to the four entry slots on the male ends, Diagram 1. Push the pipe sections completely together, then twist-lock one section clockwise approximately one-quarter turn, until the two sections are fully locked. The female locking lugs will not be visible from the outside, on the Black Pipe or fi ttings. They may be located by examining the inside of the female ends.

NOTE:

Diagram 1

For best results and optimum performance with each approved venting system, it is highly recommended to apply

“Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. Silicone (red RTV) is optional.

b)

The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For

External Vent Terminal Locations, see

Exterior Vent Termination Location.

c) Snorkel Terminations:

For installations requiring a vertical rise on the exterior of the building, 14inch and 36-inch tall

Snorkel Terminations are available, as well as the standard Riser

Vent. Follow the same installation procedures as used for standard

Horizont a l Te r mination.

N E V E R install the s n o r k e l u p s i d e down.

Diagram 3

Diagram 4

NOTE: For Snorkel terminations in ABOVE grade installations, follow national or local code requirements.

6) The arrow on the vent cap should be pointing up.

Insure that the 1-1/2" clearances to combustible materials are maintained (Diagram 4). Install the termination cap.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

33

INSTALLATION

34

UNIT INSTALLATION WITH

VERTICAL TERMINATION

4)

Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed.

1)

Maintain the 1-1/4" clearances

(air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfaces. Do not pack air spaces with insulation.

Check for the maximum vertical rise of the venting system and the maximum horizontal offset limitations.

The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

Diagram 5

Note: If installing termination on a siding

7) covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.

Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall

Thimble over the vent pipe.

8)

Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. It is important that the vent pipe extends into the vent cap suffi cient distance so as to result in a minimum pipe overlap of 1-1/4 inches. Secure the connection between the vent pipe and the vent cap by attaching the two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the strips to the pipe section. See Diagram 6.

2)

Set the gas appliance in its desired location. Drop a plumb bob down from the ceiling to the position of the appliance fl ue exit, and mark the location

Diagram 1

where the vent will penetrate the ceiling. Drill a small hole at his point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters or other framing will obstruct the venting system.

You may wish to relocate the appliance or to offset, as shown in Diagram 2 to avoid cutting load bearing members.

Diagram 2

NOTE: For best results and optimum performance with each approved venting system, it is highly recommended to apply

“Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. Silicone (red RTV) is optional.

5)

Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2. The hole should be of suffi cient size to meet the minimum requirements for clearance to combustibles of 1-1/2". Slip the fl ashing under the shingles (shingles should overlap half the fl ashing) as per Diagram 4.

Diagram 4: The upper half of the fl ashing is installed under the roofi ng material and not nailed down until the chimney is installed.

This allows for small adjustments.

6)

Continue to assemble pipe lengths.

Note: If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet, to avoid excessive stress on the elbows, and possible separation.

Wall straps are available for this purpose (Diagram 2).

Galvanized pipe is desirable above the roofl ine due to its higher corrosion resistance. Continue to add pipe sections through the fl ashing until the height of the vent cap meets the minimum height requirements specifi ed in Diagram 5 or local codes. Note that for steep roof pitches,

Diagram 5

Diagram 6

9)

Install wall thimble in the center of the 10" square and attach with wood screws

(Diagram 7).

Diagram 7

3)

A Firestop spacer must be installed in the fl oor or ceiling of every level. To install the

Firestop spacer in a fl at ceiling or wall, cut a 10 inch square hole. Frame the hole as shown in Diagram 3 and install the fi restop.

Diagram 3

Roof Pitch Minimum Vent Height

Feet Meters fl at to 7/12 over 7/12 to 8/12

2

2

0.61

0.61

over 8/12 to 9/12 over 9/12 to 10/12 over 10/12 to 11/12 over 11/12 to 12/12

2

2.5

3.25

4

0.61

0.76

0.99

1.22

over 12/12 to 14/12 over 14/12 to 16/12 over 16/12 to 18/12 over 18/12 to 20/12 over 20/12 to 21/12

5

6

7

7.5

8

1.52

1.83

2.13

2.29

2.44

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

the vertical height must be increased. A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem.

7)

Ensure vent is vertical and secure the base of the fl ashing to the roof with roofi ng rails, slide storm collar over the pipe section and seal with a mastic.

N o t e : To m a k e t h e i n s t a l l a t i o n more aesthetically p l e a s i n g , w e recommend framing out a square to mount the terminal to.

4)

Separate the 2 halves of the wall thimble and securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls.

The liners must slip over the collars a minimum of 1-3/8".

8)

Install the vertical termination cap by twistlocking it.

the vent passes through must be enclosed.

Note: If installing termination on a siding covered wall, furring strips must be used to ensure that the termination is not recessed into the siding.

Offset Chart

2)

Level fi replace and fasten it to the framing using nails or screws through the nailing strips.

5)

Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with proper down slope for draining water.

Fasten the cap to the outer wall with the 4 supplied screws.

6)

Pull the centre 4"(100mm) liner and outer

6-7/8"(175mm) liner out enough to slip over the fl ue collars of the fi replace. (You may wish to cut the liner shorter to make it more workable.) Do not bend liner more than

90 o

.

3)

Assemble the vent assembly by applying

Mill Pac to the 4"(100mm) inner collar of the termination and slipping the 4"(100mm) liner over it at least 1-3/8" (35mm). Fasten with the 3 screws (drilling pilot holes will make this easier). Apply Mill Pac or high temperature silicone to the 6-7/8"(175mm) fl ex pipe and slip it over the 6-7/8" outer collar of the vent terminal at least 1-3/8"(35mm) and fasten with the 3 screws.

7)

8)

Apply Mill Pac over the fi replace inner collar and slip the 4"(100mm) liner down over it and attach with 3 supplied screws.

Do the same with the 6-7/8"(175mm) liner.

NOTE: Horizontal sections must be supported at intervals not exceeding

3 feet (0.9 meter). (Flame picture and performance will be affected by sags in the liner).

9)

Apply a bead of silicone between the thimble and termination and around the outer edge of the terminal at the wall in order to keep the water out.

IMPORTANT: Do not locate termination hood where excessive snow or ice buildup may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

DIRECT VENT

SYSTEM (FLEX)

INSTALLATION

PROCEDURES

1)

Locate the unit in the framing, rough in the gas (preferably on the right side of the unit) and the electrical (Junction block is on the left side) on the left. Locate the centerline of the termination and mark wall accordingly.

Cut a 10"(254mm) hole in the wall (inside dimension).

Note: A 1-1/2"(38mm) clearance around the liner must be maintained except that only a 1" (25mm) clearance is needed at the termination end. We recommend framing a 10"(254mm) x 10"(254mm) (inside dimensions) hole to give structural rigidity for mounting the termination.

35

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

36

P36D-NG1 SYSTEM DATA

always best to consult with your local authorities and the CAN/CGA B149 installation code.

PILOT ADJUSTMENT

The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.

For 0 to 4500 feet altitude

Burner Inlet Orifi ce Sizes:

#37

Max. Input Rating

3 0 , 0 0 0

Min. Input Rating

15,500 Btu/h

For USA installations follow local codes and/ or the current National Fuel Gas Code, ANSI

Z223.1.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

Supply Pressure

min.5.0"

Manifold Pressure

(High)

3.8"+/-

Electrical

: 120 V A.C. System.

Circulation Fan

: variable speed 130 CFM.

Log Set

: Ceramic fi bre, 7 per set.

Vent System:

Simpson Dura-Vent Direct

Vent System or FPI Direct

Vent System (Flex)

When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.

Important: Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open fl ame for leak testing.

1)

Make sure the valve is in the "OFF" position.

2)

Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a

3)

Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.

4)

Light the pilot and turn the valve to "ON" position.

P36D-LP1 SYSTEM DATA

Conversion Kit # 514-969

For 0 to 4500 feet altitude

Burner Inlet Orifi ce Sizes:

#52

Max. Input Rating

30,000 Btu/h

Min. Input Rating

15,000 Btu/h

Supply Pressure

min.12.0"

Periodically check the pilot fl ames. Correct fl ame pattern has three strong blue fl ames:

1 fl owing around the thermopile, 1 around the thermocouple and 1 fl owing across the burner (it does not have to be touching the burner).

contact your FPI dealer for further instructions.

5)

The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.

6)

When fi nished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver.

Note: Screw should be snug, but do not over tighten.

Manifold Pressure

(High)

11"+/- 0.2" w.c.

Electrical

: 120 V A.C. System.

Circulation Fan

: variable speed 130 CFM.

Log Set

: Ceramic fi bre, 7 per set.

Vent System:

Vent System

Simpson Dura-Vent Direct

HIGH ELEVATION

This unit is approved in Canada for altitude 0 to 4500 ft. (CAN1 2.17-M91) with the orifi ce supplied.

S.I.T. VALVE

DESCRIPTION

Incorrect fl ame pattern will have small, probably yellow fl ames, not coming into proper contact with the rear burner or thermopile or thermocouple.

1)

Gas on/off knob

2)

Manual high/low adjustment

3)

Pilot

4)

Thermocouple Connection -

option

5)

Outlet Pressure Tap

6)

Inlet Tap

7)

Pilot

8)

Main Gas Outlet

9)

Alternative Connection

Point

GAS LINE

INSTALLATION

The gas line can be brought through either the right or the left side of the appliance. The gas valve is situated on the right hand side of the unit and the gas inlet is on the right hand side of the valve.

GAS PIPE PRESSURE

TESTING

Note: If the gas line is being installed from the left side, be sure to leave room to accommodate servicing of the fan.

The gas line connection may be made of rigid pipe, copper pipe or an approved fl ex connector.

(If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.

(3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

CONVERSION KIT# 514-969 FROM NG TO LP

for P36D-1 / P36-4 / U32-4 / U37-1 using SIT 820 NOVA Gas Valve

THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER

IF IN DOUBT DO NOT DO THIS CONVERSION !!

Each Kit contains one LPG

Conversion Kit and one DC

Sparker Kit.

Conversion Kit Contains:

Qty. Part # Description

1 904-390 Burner Orifi ce #52

For P36D-1 / P36-4 Only:

5)

Remove the 2 screws holding the Burner

Assembly to the fi rebox base. Push the

Burner Assembly to the left and lift out.

6)

Pull off the pilot cap to expose the pilot orifi ce.

1 910-903

904-781

904-782

(Pilot ce)

DC Sparker Kit Contains:

Qty. Part # Description

1 820-475

1 820-476

1 904-153

Bracket DC Sparker

Bracket DC Sparker

Washer #8 External Star

2 904-531

1 904-543

2 904-553

1 910-073

1 910-074

Bushing Split Plastic

Screw 8-32 x 3/4 Pan

Head

Screw #8 x 1/2 Type "B",

Spark Generator Battery

Holder

Spark Generator Switch

Energizer En91

Wire Fan To Power Cord

Ground 30 in.

Velcro Hook, Black

Velcro Hook, Black

Remove the 2 screws, push Burner Assembly to the left and lift out.

For U32-5 Only:

5a)

Remove the grate by removing the screws on each side of the grate.

Remove the 2 screws holding the grate in position.

5b)

Remove the Burner Tray by removing the screws on each side of the tray.

Push the tray to the left and lift up.

7)

Unscrew the pilot orifi ce with the allen key; then replace with the LPG pilot orifi ce and the pilot cap, provided in the kit.

8)

Remove burner orifi ce with a 1/2" wrench. Use another wrench to hold on to the elbow behind the orifi ce. Discard orifi ce.

Installation of LPG

Conversion Kit:

1) Shut off the gas supply.

2)

Remove the louvers (and bay door if it is installed).

3)

Open the fl ush door and remove the door.

4)

Remove the logs and embers (if already installed).

Remove the 2 screws, push Burner Tray to the left, and lift off.

IMPORTANT

Before re-installation of the burner (once the LP conversion is complete), the air defl ector must be installed. See step 18a.

Burner Orifi ce

37

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

9)

Reinstall new burner orifi ce LPG stamped #52 and tighten.

10)

Turn control knob to the “OFF” position.

16)

Verify that if the conversion is from

NG to LPG, the screw must be reassembled with the red o-ring visible

(Fig. 5).

LPG Configuration

Red o-ring visible

11)

Remove black protection cap by hand from the hi-low knob

(Fig.1).

Fig.5

Fig. 1

17)

Re-assemble the black protection cap (Fig. 6).

12)

Insert a 5/32” or 4mm

Allen wrench into the hexagonal key-way of the screw (Fig.

2), rotate it counterclockwise until it is free and extract it.

Fig.2

13)

Check that the screw is clean and if necessary remove dirt.

14)

Flip the screw (Fig. 3).

Installation of the DC Sparker:

21)

Locate the Piezo Ignitor situated at the side of valve.

Piezo

Ignitor

22)

Remove the Piezo Ignitor by unscrewing the nut at the back of the mounting bracket.

Ignitor

Wire

Fig. 6

18)

Reverse steps 6 - 1.

Piezo

Ignitor

For U32-5 Only:

18a)

Install the air defl ector to the back wall of the fi rebox using 2 screws.

23)

Disconnect the ignitor wire from the

Piezo Ignitor and connect it to the DC

Sparker.

DC

Sparker

Fig.3

Ignitor

Wire

15)

Using the Allen wrench as shown in Fig.4, rotate the screw clockwise until snug, do not overtighten.

Fig.4

Air Defl ector

WARNING!

Also check that the pilot and main burner injectors are appropriate for the gas type.

WARNING!

Do not over tighten the screw.

Recommended to grip the wrench by the short side.

19)

Attach the label "This unit has been converted to LPG" near or on top of the serial # decal.

20)

Replace yellow "NG" label with red

"LPG" label.

24)

Connect the DC spark generator wires to the SIT Valve with the screw, which is provided in the kit.

38

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

25)

Locate the ground lug.

For P36D-1 / P36-4 Only:

25a)

By the receptical box, left of the unit.

INSTALLATION

28)

Install the 1/2" bushing to the heat shield.

32)

Mount the heat shield to the DC Sparker.

Secure into place with the velcro, which is provided in the kit.

For U32-5 Only:

25b)

Located on the left side of the unit.

29)

Plug the DC spark generator wires to the

DC Sparker.

33)

Find a location which is not too hot and is easy to reach for changing the battery.

Note: It should be kept away from the chain.

Chain

26)

Connect one end of the supplied green ground wire to the lug with the nut and washer from the kit.

Ground wire from kit

30)

Connect the ground wire to the DC Sparker mounting bracket.

34)

Tie up the loose wires with the wire clip.

27)

Run the other end of the ground wire and DC spark generator wires through the bushing on the heat shield.

Heat Shield

31)

Install the supplied battery into the DC

Sparker Box by opening the battery compartment.

Battery

Compartment

35)

Check for gas leaks.

36)

Check inlet and outlet pressures.

37)

Check operation of fl ame control.

38)

Check for proper fl ame appearance and glow on logs.

NOTE: The battery in the DC Sparker

Box will need to be replaced an-

nually.

39

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

OPTIONAL

BRICK PANELS

1)

Undo the bottom 2 door latches and open and remove glass door.

Remove logs.

4)

Install the 2 brick retaining clips, one on each side.

Note: The logs must not be in the unit.

2)

Insert the back brick panel fi rst by carefully slipping it between the back wall of the fi rebox and the rear log bracket.

3)

Put the side panels in next. Slide them in from the front and push them fl at up against the wall. Be very careful not to scratch them on the fi rebox hardware.

Note:

If the bottom brick panel must be removed: Remove the Rear

Log Stand, then remove the Burner Tray.

40

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

Read the instructions below carefully and refer to the diagrams. If logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot operation.

3)

Place the Log 02-75 on the rear log support pins with the fl at side to the back.

The gas log kit (Part #780-930) contains the following pieces:

02-75

a) 02-75 Rear Log b) 02-55 Middle Left Log c) 02-50 Front Left Log d) 02-53 Center Left Log e) 02-51 Front Bottom Log f) 02-54 Center Right Log g) 02-52 Middle Right Log h) 902-156 Embers j) 946-669 Platinum Embers

(supplied with packaged manual)

NOTE: If you will be installing the optional Brick Panels

(P36D & P90 only), install the Brick Panels prior to installing the logs.

Model shown has P36D and P90 burner/grate with brick panel option.

4)

Place Log 02-51 on the front right side of the burner. Push the back of the log against the 2 brackets with the notch on the bottom right side of the log fi tting into the right side of the grate.

02-75

02-75

02-51

02-51

02-54

02-53

02-55

Bracket

Bracket

Notch

02-50

02-52

The "02" reference numbers (i.e. 02-75) are molded into the rear of each log.

1)

Carefully remove the logs from the box and unwrap them.

The logs are fragile, handle with care -

do not force into position.

2)

Sprinkle the vermiculite over base brick panel.

02-51

Notch

41

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

42

INSTALLATION

LOG SET INSTALLATION

5)

Position Log 02-53 across the cutouts in Logs 02-75 and

02-51 with the notch on the left side of the log fi tting into the 2nd grate tab.

02-53

02-75

02-51

5th Grate Tab

7)

Place the bottom left front edge of Log 02-55 against the rear bracket on the burner tray and rest the log on the cutout on Log 02-53.

Cutouts

2nd Grate Tab

02-51

02-53

02-75

02-55

02-53

6)

Position Log 02-54 across the cutouts in Logs 02-51 and

02-53. The notch in the bottom right end fi tting against the

5th grate tab.

Rear Bracket

Cutouts

02-54

02-51

02-53

5th Grate Tab

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

8)

Place Log 02-52 between Logs 02-51 and 02-75 and on the indentation on Log 02-54. The bottom right end sits behind the rear grate tab.

9)

Sit Log 02-50 on the front left side of the burner. Push the back of the log against the 2 front brackets with the notch on the bottom of the log fi tting into the fi rst grate tab.

02-50

02-53

02-52

02-51

02-54

Log Indentation

02-52

02-54

Rear

Grate Tab

Photo shows rear grate tab.

Log 02-51 was removed to show the positioning of Log 02-52.

Notch

Front Brackets

02-50

02-55

02-53

43

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

10)

Place the embers on the front of the burner tray in the places shown on the photos below.

Separate platinum embers and place on the front burner on and around the embers. Avoid stacking platinum embers.

Platinum embers may be placed over burner ports.

02-51

Place embers in these 3 locations on the burner tray.

02-54

Do not block the burner ports in this area adjacent to the Log 02-54

IMPORTANT

When placing Embers, do not block burner ports as this can cause an incorrect fl ame pattern, carbon deposits and delayed ignition.

11)

Test fi re to ensure proper light off (make sure fl ame fl ows smoothly from one end of burner to the other). If there is any fl ame hesitation, check that area for any blockage of the burner ports.

02-50

02-75

02-55

02-53

02-52

02-51

02-54

44

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

STANDARD FLUSH DOOR

The standard fl ush door

comes with a black frame. To install the frame, simply hook the top door fl ange onto the top of the unit and swing the door towards the unit, see diagram 1.

Be careful that the glass gasket does not roll up; there must be a gap between the gasket and the door lip to ensure that the door sits securely on the unit, see Diagram 2.

Diagram 1

Diagram 2

Use the hook to pull the spring out until you can put the hook into the slot on the bottom door bracket. Repeat for 2nd spring. See diagram 3.

Diagram 3

To remove the fl ush door, reverse the above steps.

45

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

REMOTE CONTROL

(OPTIONAL)

Use the FPI Remote Control Kit approved for this unit. Use of other systems may void your warranty.

WALL SWITCH

(OPTIONAL)

1)

Run the wire through the right or left side inlet opening. Be careful not to damage wire.

WALL THERMOSTAT

(OPTIONAL)

A wall thermostat may be installed if desired, connect the wires as per the wiring diagram.

Use the table below to determine the maximum wire length.

The remote control kit comes with a hand held transmitter, a receiver and a wall mounting plate.

Note: We recommend a maximum of 15' of wire but if you wish to go with a longer run, use the Thermostat Wire

Table.

Note: Preferable if the thermostat is installed on an interior wall.

1)

Choose a convenient location on the wall to install the receiver and the receptacle box (protection from extreme heat is very important). Run wires from the fi replace to that location. Use the Thermostat Wire Table.

2)

Connect the two wires to the gas valve. See diagram below.

2)

Connect the wire to the wall switch and install into the receptacle box.

FPI offers an optional programmable thermostat but any 250-750 millivolt rated non-anticipator type thermostat that is CSA, ULC or UL approved may be used.

CAUTION

Do not connect millivolt wall switch wire to a 120V wire.

CAUTION

Do not connect millivolt wall thermostat wires to a 120V wire.

CAUTION

Do not connect millivolt remote control wires to a

120V wire.

3)

Install 3 AAA alkaline batteries in transmitter and 4 AA alkaline batteries in the receiver.

Install the receiver and its cover in the wall.

Switch the remote receiver to "remote" mode. The remote control is now ready for operation.

Thermostat Wire Table

Recommended Maximum Lead Length

(Two-Wire) When Using Wall

Thermostat (CP-2 System)

Wire Size Max. Length

14 GA.

16 GA.

18 GA.

20 GA.

22 GA.

50 Ft.

32 Ft.

20 Ft.

12 Ft.

9 Ft.

46

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

This heater does not require a 120V A.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/ thermostat will continue to operate. However, a 120V A.C. power supply is needed for the fan/blower operation.

WIRING DIAGRAMS

(Do not cut the ground terminal off under any circumstances.)

NOTE: Even if the fan is not purchased with the unit, it is still a good idea to bring power to the receptacle box

(provided with the unit) in case the fan is installed at a later date.

For

NATURAL GAS

Units and Units

NOT

Equipped with DC Spark Boxes

Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

47

INSTALLATION

For

PROPANE

Units and Units Equipped with DC Spark Boxes*

*For installation of the DC Spark Box refer to the LP Conversion instructions in this manual.

48

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

OPTIONAL FAN

INSTALLATION

120 Volt AC power is needed for the fan switch and blower. The fan can be hard wired if desired.

The receptacle box should be installed on the left hand side of the unit by a qualifi ed electrician. The neutral (wider) slot of the polarized receptacle should be at the top.

6)

Slide the thermodisc/cover assembly into the bracket clip on the underside of the fi rebox. Check that no wire will touch the hot surfaces. Diagram 2.

11)

Attach the two control boxes to the bottom louver and tighten the 2 screws on the left side and 1 screw on the right side.

Unit must be grounded at all times. Do not cut the ground terminal off under any circumstances.

Secure left side with 2 screws.

1) Shut the power off.

2)

Remove the standard fl ush door and the optional bay door, if installed. Open the bottom louver door.

3)

4)

Loosen the 2 screws holding the Burner

ON/OFF switch and bracket to the bottom louver and lift the assembly out.

Turn the fan base on its side (with the base facing towards you) and then slide the fan in towards the rear of the unit. Turn the fan upright and slip it over the two mounting studs. Take care not to damage the insulation on the fan base.

do not rub against the valve tubing.

Diagram 1.

Ensure that the fan blades

7)

Diagram 2

Attach the Fan control box to the Burner

ON/OFF control box.

Secure right side with one screw.

12)

Secure the fan wires and power cord by attaching one of the adhesive backed wire holder clips (Part #910-199) onto the stove base. Use the second clip to bundle up the wires approximately 4" from the control box.

Ensure that there is no interference with the wires when the louver is closed and that no wire will touch the hot metal surfaces or sharp edges.

Use the clip & hook on the side of the control boxes to join them together.

8)

Secure the two boxes together with one screw.

13)

Plug the fan power cord into the rear end of the receptacle box to provide the maximum clearance from the louvers.

OPTIONAL FAN REMOVAL

1) Shut the power off.

2)

Reverse the above instructions.

Secure the 2 boxes together with one screw.

9)

Position the control box assembly on the bottom louver and mark the position of the slot on the right side bracket.

Note: The bearings are lubricated for life. Do not lubricate them. Make sure you vacuum the fan area on a regular basis.

IMPORTANT:

These fans collect a lot of dust from within your home. Ensure you maintain these fan motors on a regular basis by vacuuming out the fan blades and housing using a soft brush nozzle.

Diagram 1

5)

Connect fan ground cable to ground lug.

Refer to wiring diagram.

Hold control box assembly in place and mark the position of the right side slot

10)

Remove the control box assembly and push the hold-down clip onto the louver. Bend the tab until it is at 90 o

to the louver.

49

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

OPERATING INSTRUCTIONS

OPERATING

INSTRUCTIONS

1)

Read and understand these instructions before operating this appliance.

2)

Check to see that all wiring is correct and enclosed to prevent possible shock.

3)

Check to ensure there are no gas leaks.

4)

Make sure the glass in the door frame is properly positioned. Never operate the appliance with the glass removed.

5)

Verify that the venting and cap are unobstructed.

6)

Ensure that the brick panels are installed.

3)

Turn gas control knob counterclockwise so indicator points to the "PILOT" position.

Depress the gas control knob fully. Depress the igniter button several times until the pilot lights. After approximately one minute, release the gas control knob. The pilot fl ame should continue to burn. If the pilot does not remain lit, repeat operation allowing a longer period before releasing gas control knob.

During the fi rst few fi res, a white fi lm may develop on the glass front as part of the curing process. The glass should be cleaned or the fi lm will bake on and become very diffi cult to remove. Use a non-abrasive cleaner and NEVER clean the glass while it is hot.

4)

When the pilot stays lit, turn the gas knob further counterclockwise to the "ON" position.

5)

Use the wall switch, thermostat or remote control to turn on the unit.

6)

Rotate fl ame height regulator to adjust the fl ame height higher or lower.

AERATION

ADJUSTMENT

The air shutter can be adjusted by moving the adjusting wire up or down. The wire is accessed through the bottom louver opening. Open the air shutter for a blue fl ame or close for a yellower fl ame. The burner aeration is factory set but may need adjusting due to either the local gas supply or altitude.

Minimum Air Shutter Opening:

7)

Verify log placement. If the pilot cannot be seen when lighting the unit, the logs have been incorrectly positioned.

8)

The unit should never be turned off, and on again without a minimum of a 60 second wait.

SHUTDOWN

PROCEDURE

1)

Use the wall switch, thermostat or remote control to turn off the main burner.

CAUTION: Carbon will be produced if air shutter is closed too much.

2)

Turn the main gas control clockwise to the

"OFF" position to turn off the pilot.

3)

Turn off all electric power to appliance if service is to be performed.

Note: Any damage due to carboning resulting from improperly setting the aeration controls is NOT covered under warranty.

FIRST FIRE

Note: Aeration Adjustment should only be performed by an authorized FPI

Installer at the time of installation or service.

LIGHTING

PROCEDURE

The fi rst fi re in your fi replace is part of the paint curing process. To ensure that the paint is properly cured, it is recommended that you burn your fi replace for at least four (4) hours the fi rst time before you use it with the fan on.

IMPORTANT

To ignite or reignite the pilot, you must fi rst release the tension springs below the door.

When fi rst operated, the unit will release an odour caused by the curing of the paint, the burning off of any oils remaining from manufacturing.

Smoke detectors in the house may go off at this time. Open a few windows to ventilate the room for a couple of hours.

Only when the pilot holds, without pressure being applied to the control knob, reapply the tension springs to the door. The unit

must not

be operated with the tension springs unattached.

The glass panel may require cleaning after the unit has cooled down.

DO NOT ATTEMPT

TO CLEAN THE GLASS WHILE IT

IS HOT.

NOTE: For all propane units and units equipped with electric spark boxes, see "Copy of Lighting Plate Instructions" section for more details.

IMPORTANT Gas on/off knob cannot be turned from "PILOT" to "OFF" unless it is partially depressed.

Note: When the glass is cold and the appliance is lit, it may cause condensation and fog the glass.

This condensation is normal and will disappear in a few minutes as the glass heats up.

Adjustment Wire: Push to close or pull to open aeration cap.

Closed - Tall yellow

Open - Short Blue

NORMAL OPERATING

SOUNDS OF GAS

APPLIANCES

1)

Turn burner OFF using "ON/OFF" switch.

2)

Turn gas control knob so indicator points to "OFF" position and allow 5 minutes for any gas in the combustion chamber to escape.

DO NOT BURN THE APPLIANCE

WITHOUT THE GLASS FRONT IN

PLACE.

It is possible that you will hear some sounds from your gas appliance. This is perfectly normal due to the fact that there are various gauges and types of steel used within your appliance.

Listed below are some examples. All are

normal operating sounds

and should not be considered as defects in your appliance.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

COPY OF THE LIGHTING PLATE INSTRUCTIONS

OFF a

Blower:

FPI gas appliances use high tech blowers to push heated air farther into the room. It is not unusual for the fan to make a "whirring" sound when ON. This sound will increase or decrease in volume depending on the speed setting of your fan speed control.

Burner Tray:

The burner tray is positioned directly under the burner tube(s) and logs and is made of a different gauge material from the rest of the fi rebox and body. Therefore, the varying thicknesses of steel will expand and contract at slightly different rates which can cause "ticking" and "cracking" sounds. You should also be aware that as there are temperature changes within the unit these sounds will likely re-occur. Again, this is normal for steel fi reboxes.

Blower Thermodisc:

When this thermally activated switch turns ON it will create a small "clicking" sound. This is the switch contacts closing and is normal.

Pilot Flame:

While the pilot fl ame is on it can make a very slight "whisper" sound.

Gas Control Valve:

As the gas control valve turns ON and OFF, a dull clicking sound may be audible, this is normal operation of a gas regulator or valve.

Unit Body/Firebox:

Different types and thicknesses of steel will expand and contract at different rates resulting in some "cracking" and "ticking" sounds will be heard throughout the cycling process.

MAINTENANCE

INSTRUCTIONS

1)

Always turn off the gas valve before cleaning.

For relighting, refer to lighting instructions.

Keep the burner and control compartment clean by brushing and vacuuming at least once a year. When cleaning the logs, use a soft clean paint brush as the logs are fragile and easily damaged.

2)

Clean appliance and door with a damp cloth (never when unit is hot). Never use an abrasive cleaner. The glass should be cleaned with a gas fi replace glass cleaner.

The glass should be cleaned when it starts looking cloudy.

3)

The heater is fi nished in a heat resistant paint and should only be refi nished with heat resistant paint. FPI uses StoveBright

Paint - Metallic Black #6309.

4)

Make a periodic check of burner for proper position and condition. Visually check the fl ame of the burner periodically, making sure the fl ames are steady; not lifting or fl oating.

If there is a problem, call a qualifi ed service person.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

MAINTENANCE

52

5)

The appliance and venting system must be inspected before use, and at least annually, by a qualifi ed fi eld service person, to ensure that the fl ow of combustion and ventilation air is not obstructed.

Note: Never operate the appliance without the glass properly secured in place.

6)

Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace nay part of the control system and any gas control which has been under water.

7)

Verify operation after servicing.

GENERAL VENT

MAINTENANCE

Conduct an inspection of the venting system semi-annually. Recommended areas to inspect as follows:

2)

Remove the Cap, and shine a fl ashlight down the Vent. Remove any bird nests, or other foreign material.

LOG REPLACEMENT

1)

Check the Venting System for corrosion in areas that are exposed to the elements.

These will appear as rust spots or streaks, and in extreme cases, holes.

These components should be replaced immediately.

3)

Disconnect thermocouple by loosening nut from the valve with a 9mm wrench.

Disconnect thermopile by loosening 2 screws marked TP on the valve.

DOOR GLASS

The unit should never be used with broken logs.

Turn off the gas valve and allow the unit to cool before opening door and carefully remove the logs. (The pilot light generates enough heat to burn someone.) If for any reason a log should need replacement, you must use the proper replacement log. The position of these logs must be as shown in the diagrams under Log

Installation.

Your FPI fireplace is supplied with high temperature, 5 mm Neoceram ceramic glass that will withstand the highest heat that your unit will produce. If your glass requires cleaning, we recommend using an approved glass cleaner available at all authorized dealers. Do not use abrasive materials. Do not clean the glass when hot.

Note: Improper positioning of logs may create carbon build-up and will severely alter the unit's performance w h i c h i s n o t c o v e r e d u n d e r warranty.

In the event that you break your glass by impact, purchase your replacement from an authorized

FPI dealer only, and follow our step-by-step instructions for replacement.

THERMOPILE/

THERMOCOUPLE

1)

Open the bottom louvers.

WARNING: Do not operate the appliance with the glass panels removed, cracked or broken.

Replacement of the glass panels should be done by a licensed or qualifi ed service person.

Caution: Wear gloves when removing damaged or broken glass.

2)

Loosen the thermocouple or thermopile with a 7/16" wrench.

FLUSH GLASS REPLACEMENT

4)

Drop the thermocouple or thermopile down from the bracket and pull it out of the unit.

Remove the fl ush door front. Remove the 4 glass clips from each corner. Slide in the new replacement glass. Push the 4 glass clips back onto the frame.

The glass must have gasketing around it.

3)

Check for evidences of excessive condensation, such as water droplets forming in the inner liner, and subsequently dripping out the joints, Continuous condensation can cause corrosion of caps, pipe, and fi ttings.

It may be caused by having excessive lateral runs, too many elbows, and exterior portions of the system being exposed to cold weather.

5)

Reinstall the new ones in reverse order.

GLASS GASKET

If the glass gasket requires replacement use

5/8" fl at glass gasket for the Bay Front (Part

# 936-243) and a tadpole glass gasket for the

Flush Front (Part # 936-155).

4)

Inspect joints, to verify that no pipe sections or fi ttings have been disturbed, and consequently loosened. Also check mechanical supports such as Wall Straps, or plumbers' tape for rigidity.

GOLD or BRASS

LOUVERS & TRIM

The 24 carat gold-plated or brass fi nish on the louvers and trim requires little maintenance, and need only be cleaned with a damp cloth. DO

NOT use abrasive materials or chemical cleaners, as they may harm the fi nish and void the warranty.

Clean any fi ngerprints off before turning the unit on. If the top louvers start to discolour, check the door gasket seal and replace if necessary.

BAY GLASS REPLACEMENT

1)

Remove the door from the unit and place on a soft surface to prevent scratching.

2)

Remove the nuts holding the glass clips in place and remove.

3)

Replace the glass.

The glass must have gasketing around it.

4)

Reverse the previous steps, replace the glass clips and fasten with the nuts but do not over tighten, as this can break the glass.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

MAINTENANCE

5)

Replace door on the stove and check the seal.

7)

Lift out the bottom brick panel.

16)

Remove the 4 Phillips head screws from the sides of the valve bracket and remove valve.

Hint: If you are using black pipe, ensure that there is a union by the valve, otherwise removal will be almost impossible.

INSTALLING VALVE

1)

REMOVING VALVE

Shut off the gas supply.

2)

Remove the louvers (and bay door if it is on).

8)

Disconnect the inlet gas line. See diagram

2.

1)

Attach the valve to the valve bracket with the 4 (m5x8 metric) screws provided.

9)

Disconnect the 2 TP wires and the 2 TH wires from the valve.

2)

Reconnect the "gas out" fl are fi tting with an

11/16" wrench.

3)

Reconnect the "gas out" fl are nut with a

10)

Remove the 10 Phillips head screws securing the valve tray assembly in place and then lift the entire assembly out.

4)

Install piezo ignitor push button assembly and reconnect wire.

3)

Open fl ush door and remove the door.

5)

Reconnect the quick drop out thermocouple nut with a 9mm wrench.

4)

Remove the logs.

5)

Remove the burner/grate assembly by removing the two Phillips head screws and then lift the burner assembly out.

6)

Reconnect the pilot tube nut with a 7/16" wrench.

7

)

Scrape off the old gasket from the fl oor of the fi rebox and from the valve tray assembly.

screws

Valve Tray Assembly

8)

Install a new gasket and reinstall the valve tray assembly.

Note: Failure to install a new gasket may severely affect the appliance performance.

9)

Reinstall the 10 hold down screws.

10)

Hook up the 2 TP and 2 TH wires to the appropriate connections on the valve.

11)

Reinstall the bottom brick panel and the front log stand.

12)

Install Burner/grate assembly

Diagram 1: Remove the left and right screws and then lift out the burner/grate assembly.

6)

Remove the rear log stand by removing the

2 screws.

screws

Rear Log Stand

11)

Undo the pilot tube from the valve with a

13)

Hook up the gas line and check for gas leaks with a soap and water solution or a

14)

gas leak detector. (Do not use open fl ame for leak testing.)

Fire up the unit temporarily

12)

Undo the quick drop out thermocouple nut on the valve with a 9mm (metric) wrench.

15)

Check the manifold pressure.

13)

Remove the Piezo igniter wire and push button assembly.

16)

Reinstall the logs and brick panels as needed.

17)

Close the door and replace the louvers.

14)

Undo the "gas out" fl are nut with a 13/16" wrench.

18)

Fire up the unit again and check for proper fl ame appearance and glow on logs.

15)

Undo the "gas out" fl are fi tting with an 11/16" wrench.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

53

REGENCY

®

OPTIONS

FLUSH TRIM

Attach the round magnets to the back of the top trim piece and to the bottom trim piece, then attach trim to the top and bottom of Flush door.

FLUSH LOUVERS

1)

Install the top louver by sliding the two bracket clips into the brackets located underneath the top of the fi rebox.

2)

The bottom louver has a hinge that is attached (2 screws per hinge) to the lip on bottom of the unit.

3)

Open the bottom louver. Pull the Burner

ON/OFF control box from inside the bottom of the fi replace and position the slots in the bracket over the 2 screws on the left side of the bottom louver. Push down to lock into place. Tighten the screws.

N o t e : To p a n d bottom louvers are different.

Screws on louver bracket

Burner ON/OFF control box

Burner ON/

OFF control box attached to bottom fl ush louver.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

REGENCY

®

OPTIONS

BAY DOOR

The Bay louvers MUST be used with the Bay glass option.

The optional Bay door is an overlay on the fl ush front.

The standard fl ush door and glass must remain on the unit.

BAY TRIM

Attach supplied magnets each to the back of the top and bottom trim pieces, and attach trim to the top and bottom of Bay door.

2)

Install bottom louver by sliding the two bracket clips into the brackets located underneath the bay door. Secure with 1 screw into each Bottom Louver Mounting

Bracket as per diagram below. Use the bottom hole in the bracket.

1)

Slide the Bay Defl ector into the 2 Bay

Defl ector brackets in the top of the unit.

2)

Hook the top of the bay door over the fl ush door fl ange and swing the bottom against the bottom fl ange of the fl ush door.

3)

Secure to the fl ush door bottom bracket with

2 screws provided.

3)

Slide the valve extension knobs onto the valve knobs. Match the correct ext. knob with the valve knob.

Note: If any maintenance etc. must be done in the fi rebox, fi rst remove the

Bay louvers and door.

BAY LOUVERS

1)

Install top louver by sliding the two bracket clips into the brackets located on top of the bay door. See below. The fi tted louver leaves a small gap between faceplate bottom and louver top.

4)

Open the bottom louver. Pull the Burner

ON/OFF control box from inside the bottom of the fi replace and position the slots in the bracket over the 2 screws on the left side of the bottom louver. Push down to lock into place. Tighten the screws.

Burner ON/OFF control box

Screws on louver bracket

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

REGENCY

®

OPTIONS

FULL SCREEN DOOR INSTALLATION

1)

Before beginning the installation, remove the Screen Doors from the

Full Screen Door Frame by fully opening the doors and lifting up off of the hinges. See important note in step 7.

2) Full Screen Door Frame Installation a)

Before attaching the Full Screen Door Frame to the unit, loosen the left and right side #8 Philips Head Screws located on the inside top of the outer frame of the appliance. Also remove the center screw.

Loosen the #8 Philips Head Screw on the inner side of each hinge bracket as shown below.

Cut-Out

Oblong Hole

Cut-Out

Top

Flange

Inside Top of Outer

Frame

Backside of Full

Screen Door

Frame Shown

Bottom

Flange

Cut-Outs

Hinge

Bracket

Inner Hinge

Bracket Screw

b)

Slide the cut-outs in the Top and Bottom Flange of the Full Screen

Door Frame under the screw heads which were loosened in step

2a. Once the Frame is in place, tighten the screws to secure. Also re-secure the top center screw through the oblong hole.

NOTE:

Should the fi nished wall protrude beyond the face of the unit, you can accommodate up to 1/2" depth.

Simply push in the Full Screen Door Frame until it aligns against the fi nished wall. Secure Top Flange of Full Screen Door Frame as described in step 2.

For the Bottom Flange of the Full Screen Door Frame, push the bottom of the Frame until it aligns with the wall. Use the inner cut-outs to secure the base of the Frame using the 2 x Hex Head Drill Point

Screws provided.

Bottom

Flange

Inner

Cut-Outs

Backside of Full Screen

Door Frame Shown

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

3)

Install the hinges to the hinge brackets on the left and right side of the bottom of the outer frame, secure using 2 x #8 Philips Head Screws per hinge.

REGENCY

®

OPTIONS

6)

Slide the Top Grill into the louver brackets located on the inside top of the fi rebox. Push in place.

Top Grill

4)

Place the Bottom Grill near hinge. Flip the hinge over the Bottom Grill and secure with 3 x #8 Phillips Head Screws per side.

Hinge Location

7)

Install the Left and Right Side Screen Doors in the fully open position by placing over top of the hinges on the Full Screen Door Frame.

NOTE:

Failure to install the doors in the fully open position could result in paint damage to the surface of the door.

Bottom Grill

Hinge

5)

Mount the Burner ON/OFF Control Box to the left side of the Bottom

Grill using 2 x #8 - 1/4" Philips Head Screws.

Left Side of Bottom

Grill

8)

Close screen doors.

Screen Door

Burner ON/OFF

Control Box

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

REGENCY

®

OPTIONS

TRIPOLI SCREEN DOOR

When installing the optional Tripoli Screen Door Series, a non-combustible material 12" (305mm) above the unit and 6" (153mm) on each side must be used (see Diagram 1).

The Tripoli Screen Door Series

also requires steel stud framing

above and on each side of the unit (refer to Diagram 1).

Diagram 1

Option #1:

Fireplace with 1-1/2" (38mm) Facing Material

Option #2:

Fireplace with 1" (25mm) Facing Material

1

2

INSTALLATION NOTE:

The hearth material must be brought past the Tripoli frame all the way to the unit face, so there will be no gap between the face and the actual fi replace.

FRAMING DIMENSIONS

OPTIONS

A

36-1/4”

(921mm)

36-1/4”

(921mm)

B

36-1/4”

(921mm)

36-1/4”

(921mm)

P36

C

14-1/4”

(362mm)

13-3/4”

(349mm)

D

46”*

(1168mm)

46”

(1168mm)

A

36-1/4”

(921mm)

36-1/4”

(921mm)

B

36-1/4”

(921mm)

36-1/4”

(921mm)

P36D

C

18-5/8”

(473mm)

18-1/8”

(460mm)

D

46”*

(1168mm)

46”

(1168mm)

* 'D' is Minimum height to combustible materials including the Minimum 2" (51mm) Top clearance to the Horizontal Vent.

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

REGENCY

®

OPTIONS

Note:

The facing material has to go on after the unit is set.

1)

Remove Glass Door. Refer to P36 Manual.

2)

Remove 2 screws and bracket as indicated (refer to Diagram 2).

4)

Place bracket under the Flange. Secure with 2 screws as indicated in Diagram 4.

Remove both screws

Remove bracket

Diagram 2

3)

Install On/Off switch (refer to Diagram 3).

Diagram 3

Diagram 4

5)

Loosen the 3 x #8 Phillips Head Screws located on the inside top of the outer frame of the appliance (refer to Diagram 5).

On/Off Switch

Control

Mounting

Bracket

3 x #8 Phillips

Diagram 5

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

REGENCY

®

OPTIONS

6) Install Top Support Frame

Slide in the Top Support Frame using the slots as a guide. Secure and re-tighten the screws to the unit.

8) Attach Top and Side Support Frame

a) Ensure the Side Supports are aligned with the correspond hole on the Top Support Frame, then secure with 1 screw. b) Repeat step on the other side.

Cut-Outs

View of backside of Top Support Frame.

Note:

The Nailing Strips can be adjusted, depending on the fac material (as indicated in Diagram 7).

7) Side Support Frame

a) Mount Side Support Frame to unit as shown in Diagram 6, then secure with 2 screws on each side.

b) Repeat step on the other side.

1/2” Facing

Material

1” Facing

Material

Diagram 7

9) Optional

Install Optional 3-Panel Arch Door. (Refer to Install 3-Panel A

Door Instruction Sheet).

10) Change in Logo

Replace existing logo with Regency logo.

Diagram 6

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

HAMPTON

®

OPTIONS

HAMPTON

®

CAST FACEPLATE

1)

Remove top louver and grill.

2)

Open bottom louver and grill.

3)

Install the left side faceplate by pushing in at the side of the fi rebox and line up with top and bottom holes on side. Secure with screws, tighten loosely.

5)

Slide top piece of faceplate into side faceplates by fi tting mounting plates into brackets.

(Back View)

Secure bottom of faceplate with screw.

Secure top of faceplate with screw.

Top piece

Faceplate

Mounting

Plate

Side piece

Faceplate

Bracket on back of side faceplate.

6)

Push in both side faceplate pieces and completely tighten screws.

7)

Re-install top louver and grill.

8)

Close bottom louver and grill.

4)

Repeat step 3 for the right side faceplate.

NOTE: Do not push in side faceplates all the way, allow for room to place the top faceplate.

HAMPTON

®

OPTIONS

HAMPTON

®

CAST GRILLS

1)

Remove the 3 faceplate mounting phillips head screws from the inside top of fi rebox, and discard if necessary.

5)

Install hinge to bracket then secure with screw.

Hinge

Bracket

2)

Place top grill in brackets located inside top of fi rebox as shown.

6)

Place something underneath bottom grill to prevent scratching.

7)

Line up hinge holes in bottom grill holes.

8)

Place screws half way in -- do not secure completely.

Bracket inside top of fi rebox.

Bracket

Top Grill

3)

Remove hinge brackets on bottom left and right side of fi rebox by removing 2 screws and discard brackets only.

9)

Place bracket over screws then push to the side against faceplate to lock in place as per diagram.

Bracket

Hinge bracket.

Left side shown.

4)

Install new hinge brackets using the same 2 screws removed in step 3.

10)

Tighten screws. (Screws will easily be tightened if using a stubby screwdriver.)

Black Metallic Grills Only:

Mount grill stopper to bottom of fi rebox securing with one screw.

Grill

Stopper

New hinge bracket.

Left side shown.

11)

Adjust ball plunger if necessary.

PARTS LIST

MAIN ASSEMBLY

Part # Description Part # Description

2) 510-026 Hinge Bracket - Left/Right

3) 948-045 Chain

4) 948-115 Spring

6)

7)

9)

430-129

910-429

910-430

Receptacle Box Mount

Box - Receptacle

Cover - Receptacle

31) *

32) *

33) *

34) *

35) *

Brick Panel - Back

Brick Panel - Left

Brick Panel - Right

Brick Panel - Bottom

20) 510-033 Top Nailing Strip

22) 780-010 Baffl e Plate 432-967 Burner ON/OFF Switch Assy

38) 910-241 Switch-Burner ON/OFF(3-way)

24) 780-013 Standoff - Side/Back

27) * Outer Flue Collar

28) *

29) *

30) *

Inner Flue Collar Assy

Flue Mounting Plate

Gasket for Flue Collar

89

93

94

93

432-917 Fan & Speed Control Assy

(120 Volts) Optional

432-966 Fan Switch Assy (120 Volts)

Optional

50

29

92

30

91

96

95

99

100

102

22

28

30

23

27

97

98

90

23

20

Part # Description

43) 910-813 Power Cord (120 Volts)

46) 910-330 Fan Speed Control Switch

47) 904-586 Knob - Speed Control

48) 910-199 Wire Holder Clip

ON/OFF)

910-845 Wire Harness - Plug In Fan

50) 510-994 Optional Rigid Pipe Adaptor

946-556 Optional Heat Wave Duct Kit

91) 946-002 Round to Oval Adaptor

94) 946-517/P Fan Assembly - HeatWave

Option

95) 946-006 Grill Plate - White

96) 946-005/01 Wall Adaptor Plate - White

97) 910-417 Knob - White

98) 910-366 Switch Cover Plate - White

99) 910-412 Fan Speed Controller

100) 910-367 Box - Plastic Switch

Receptacle

101) 690-022 Cover Plate - Outer Box Side

102) 946-010 Flexible Air Duct

946-011 Insulation 6" dia. x 24"

946-570 Heat Release Duct Kit

(Optional)

105) 910-165 Fan (120 Volts)

106) 946-000 Flexible Air Release Duct

514-969 Conversion Kit - NG to LP

*Not available as a replacement part.

24

DOORS & LOUVERS PLEASE

REFER SEPARATE SECTION

10

6

7

31

8

9

1

35

2

4

3

2

101

106

24

34

105

32

BRICK PANEL SET

33

42

38

ON-OFF

SWITCH

ASSEMBLY

43

47

48

46

FAN SWITCH ASSEMBLY

49

HEAT RELEASE DUCT KIT

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

63

PARTS LIST

Part #

52) 910-190

53) 780-021

54) 910-421

55) 910-422

BURNER ASSEMBLY & LOG SET

Description

Piezo Ignitor & Nut

Gasket - Valve Access Plate NG/LP

Pilot ON/OFF 3" Extension Knob

Flame HI/LOW 3" Extension Knob

780-574/P Valve Assy - Natural Gas

780-576/P Valve Assy - Propane

56) * Valve Tray - NG/LP

57) 910-478 Valve - S.I.T. - Natural Gas / Propane

58) *

65) *

Valve Bracket

Pilot Bracket

66) 910-038

910-039

67) *

Pilot Assy - S.I.T. - 3 Flame NG

Pilot Assy - S.I.T. - 3 Flame LP

Pilot Holder

68) W840470

904-240

Pilot Assembly Gasket

Orifi ce #37 - Natural Gas

904-390 Orifi ce #52 - Propane

936-170 Orifi ce Gasket

69) *

75) *

76) *

79) 791-535

82) 511-030

83) 780-028

84) *

85) 780-930

Firebox Base

Defl ector - Left

Defl ector - Right

Burner Assy - NG/LP

Burner Grate Assy

Rear Log Support Bracket

Defl ector

Log Set

*Not available as a replacement part.

64

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

REGENCY

®

BAY FRONT ASSEMBLY

Part # Description

780-931 Bay Front Complete

112) * Bay Front Trim - Top/Bottom

780-934 Bay Front Trim (Set) - Gold

113) *

114) *

Part # Description

510-988 Bay Louvers - Black

510-993 Bay Louvers - Steel/Black

510-990 Bay Louvers - Gold/Black

510-992 Bay Louvers - Brass/Black

115) *

116) *

117) 904-196 Magnet (1" round)

119) 780-025 Bay Door Baffl e

120) * Glass Retainer Bracket

160) 948-216 Regency ® Logo Plate

*Not available as a replacement part.

PARTS LIST

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

65

PARTS LIST

Part # Description

REGENCY

®

FLUSH FRONT ASSEMBLY

Part # Description

136) 936-155 Glass Gasket (Tadpole)

904-691 U-Clip

510-920 Flush Louvers (Set)-Gold/Blk

510-921 Flush Louvers (Set)-Brass/Blk

510-922 Flush Louvers (Set)-Black

510-923 Flush Louvers (Set)-Steel/Black

138) *

139) *

510-934 Flush Glass Trim (Set) - Brass

510-947 Flush Glass Trim (Set) - Steel

152) *

904-196 Magnet

510-932 Flush Glass Trim (Set) - Gold

150) *

904-196 Magnet

510-986 Finishing Trim (Set) - Black

157) *

158) * Finishing Trim Top

159) *

161) 948-216 Regency

®

Logo Plate

*Not available as a replacement part.

66

150

152

138

148

158

146

139

132

161

157

159

136

135

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

HAMPTON

®

CAST

FACEPLATE & GRILL ASSEMBLY

Part # Description

513-971** Cast Faceplate (Set)

201) *

202) *

203) *

Cast Faceplate - Right

Cast Faceplate - Top

Cast Faceplate - Left

513-981** Cast Grills (Set)

204) *

205) *

Top Grill

Bottom Grill

*Not available as a replacement part.

** Last digit of part number represents colour:

1=Black Metallic, 5=Enamel Brown

PARTS LIST

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

67

NOTES

68

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

NOTES

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

69

NOTES

70

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

WARRANTY

Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of a

Excalibur Product. This warranty is not transferable.

The Warranty:

Limited Lifetime

The combustion chamber, heat exchanger, burner tubes/pans, logs, brick panels and gold plating (against defective manufacture only) are covered under the Limited Lifetime

Warranty for fi ve (5) years for parts and subsidized labour* and parts only thereafter.

Glass is covered for lifetime against thermal breakage only, parts and subsidized labour* for fi ve (5) years and parts only thereafter from date of purchase.

External casting, surrounds and grills are covered against cracks and warps resulting from manufacturer defects, parts and subsidized labour* for three (3) years from the date of purchase and parts only thereafter.

Special Finishes - One year on brushed nickel and antique copper full screens and doors. You can expect some changes in color as the product "ages" with constant heating and cooling. FPI warranties the product for any manufacturing defects on the original product. However, the manufacturers warranty does not cover changing colors and marks, ie. fi nger prints, etc applied after the purchase of the product. Damage from the use of abrasive cleaners is not covered by warranty.

Electrical and mechanical components such as blowers, switches, wiring, thermodiscs, FPI remote controls, spill switches, thermopiles, thermocouples, pilot assembly components, and gas valves are covered for two years parts and one year subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are considered repairs and continue as if new with appliance. ie. twelve (12) months from original purchase date of appliance with a minimum of three (3) months coverage from date of replacement.

FPI venting components are covered parts and subsidized labour* for three (3) years from date of purchase.

Simpson Dura-Vent venting components (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.

Repair/replacement parts purchased by the consumer from FPI after the original coverage has expired on the unit will carry a 90 day warranty, valid with a receipt only. Any item shown to be defective will be repaired or replaced at our discretion. No labor coverage is included with these parts.

Conditions:

Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI's option, through an accredited distributor or agent provided that the defective part be returned to the distributor or agent

Transportation Prepaid,

if requested.

Porcelain/Enamel - Absolute perfection is either guaranteed nor commercially possible. Any chips must be reported and inspected by an authorized dealer within three days of installation. Reported damage after this time will be subject to rejection.

It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for manufacturer defect.

The authorized selling dealer is responsible for all in-fi eld service work carried out on your Regency product. FPI will not be liable for results or costs of workmanship from unauthorized service persons or dealers.

At all times FPI reserves the right to inspect product in the fi eld which is claimed to be defective.

All claims must be submitted to FPI by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer name, purchase date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.

Exclusions:

This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim.

At no time will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufactured. ie. as products evolve, fi eld modifi cations or upgrades will not be performed.

FPI will not be liable for travel costs for service work.

Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.

Embers, rockwool, gaskets, door handles and paint are not covered under the terms of this warranty policy.

Any unit which shows signs of neglect or misuse is not covered under the terms of this warranty policy.

The warranty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, negligence or accident, spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by mechanical systems such as furnaces, fans, clothes dryer, etc.

Freight damage to stoves and replacement parts is not covered by warranty and is subject to a claim against the freight carrier by the dealer.

FPI will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.

Performance problems due to operator error will not be covered by this warranty policy.

Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from FPI, may nullify your warranty on this product.

Any alteration to the unit which causes sooting or carboning that results in damage to the interior / exterior facia is not the responsibility of FPI.

* Subsidy according to job scale as predetermined by FPI.

71

Regency

®

P36D-1 Zero Clearance Direct Vent Gas Fireplace

Register your Regency

®

warranty online www.regency-fi re.com

Reasons to register your product online today!

• View and modify a list of all your registered products.

• Request automatic email notifi cation of new product updates.

• Stay informed about the current promotions, events, and special offers on related products.

Installer: Please complete the following information

Dealer Name & Address: ______________________________________________

___________________________________________________________________

Installer: ___________________________________________________________

Phone #: ___________________________________________________________

Date Installed: ______________________________________________________

Serial No.: __________________________________________________________

Hampton, Panorama, AstroCap,Tripoli, HeatWave and Heat Release are trademarks of FPI

Fireplace Products International Ltd.

© Copyright 2011 FPI Fireplace Products International Ltd. All rights reserved.