Below you will find brief information for HB Mini Controller. This controller integrates seamlessly with 24 VAC thermostats, supports single or multi-stage setups, and includes an auto-staging feature. It monitors equipment safeties, logs data, and locks out the equipment upon multiple failures.
Advertisement
Advertisement
FACTORY CONTROLS SYSTEM HB Mini - Controller Technical Guide Table Of Contents Controller Overview ........................................................................................................................ 3 General ...................................................................................................................................................................................... 3 Inputs ......................................................................................................................................................................................... 3 Outputs ...................................................................................................................................................................................... 3 Controller Sequence Of Operation ................................................................................................. 4 Fan Mode ................................................................................................................................................................................... Heating Mode ............................................................................................................................................................................ Cooling Mode ............................................................................................................................................................................ Lockout Modes ......................................................................................................................................................................... 4 4 4 4 Controller Installation & Wiring ...................................................................................................... 5 Controller Mounting ................................................................................................................................................................. 5 Important Wiring Considerations ............................................................................................................................................ 5 Programming With The HB Service Tool ...................................................................................... 11 Entering Passcodes ................................................................................................................................................................ 11 General Procedures ................................................................................................................................................................ 11 Module Selection Screens .................................................................................................................................................. 11 HB Mini Controller Status & Setpoints ................................................................................................................................. 12 Main Status Screens .......................................................................................................................................................... 12 Fan Module Status Screens .............................................................................................................................................. 13 Cooling Module Status Screens ........................................................................................................................................ 13 Cooling Module Setpoint Screens ..................................................................................................................................... 14 Heating Module Status Screens ........................................................................................................................................ 15 Heating Module Setpoint Screens ..................................................................................................................................... 16 Alarm Module Status Screens ........................................................................................................................................... 16 HVAC Test Module Screens .............................................................................................................................................. 17 Troubleshooting ............................................................................................................................ 19 Using LEDs To Verify Operation ............................................................................................................................................ 19 HB Mini Controller Fault Condition Operation ................................................................................................................... 19 Appendix ........................................................................................................................................ 20 Notes: ............................................................................................................................................ 22 WattMaster Controls Inc. 8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: [email protected] Visit our web site at www.wattmaster.com Form: AA-HBM-TGD-01A Copyright 2005 WattMaster Controls, Inc. AAON® is a registered trademark of AAON, Inc., Tulsa, OK. WattMaster Controls, Inc. assumes no responsibility for errors, or omissions. This document is subject to change without notice. Technical Guide Controller Overview General Outputs The HB Mini Controller is designed to work with a normal 24 VAC Thermostat. Single or Multi-stage Thermostats can be used. When a Single Stage Thermostat is used, an auto-staging feature is built-in for Multi-stage HB units. Supply Fan High Speed Relay Supply Fan Low Speed Relay Cool-1 Relay Cool-2 Relay Heat-1 Relay Heat-2 Relay Heat-3 Relay C1, C2: Clogged Filter Switch 24 VAC Output Terminals The HB Mini Controller also monitors equipment safeties, logs information and locks out the equipment in the event of multiple failures. Terminal block style connections are provided for field wiring of the Thermostat. All other inputs and outputs are connected via a wiring harness on the HB unit. A list of all available inputs and outputs follows. Inputs G, Y1, Y2, W1, W2, W3 Outdoor Air Temperature Sensor Heat Safety Monitor (monitors main and auxiliary limit thermostats) High Pressure Switch Low Pressure Switch Clogged Filter Switch Figure 1: HB Mini Controller Dimensions HB Mini Controller 3 Technical Guide Controller Sequence Of Operation Fan Mode The HB Mini Controller controls the 2 Speed Supply Fan . On a call for "G" the Supply Fan runs at Low Speed. Minimum on and off times are maintained in the event of a short cycled call for "G". Heating Mode On a call for "W1" the Supply Fan runs at High Speed (maintained during the Heating mode) and Heat Stage 1 is energized. On a call for "W2", Heat Stage 2 is energized after the stage up delay. If "W2" is called without "W1", Heat Stage 1 is energized and then Heat Stage 2 is energized after the Auto Stage Up Delay period. On a call for "W3", Heat stage 3 is energized after the Stage Up delay. If "W3" is called without "W1" or "W2", Heat Stages 1, 2 and 3 will energize based on Auto Stage Up Delays. Cooling Mode Speed and Cool Stage 2 is energized after the Stage Up Delay. If "Y2" is called without "Y1", Cool stage 1 is energized and then Cool stage 2 is energized after the Auto Stage Up Delay. Lockout Modes Heating Mode is locked out if the HSM (Heat Safety Monitor) trips 3 times during a call for Heating. To reset the lockout condition, either remove the call for Heating or cycle power to the HB Mini Controller. Heating Mode is also locked out if the Outdoor Air Temperature is above the OAT Heat Lockout setpoint temperature. Cooling Mode is locked out if the LPS (Low Pressure Switch) trips 3 times during a call for Cooling. To reset the lockout condition, either remove the call for Cooling, or cycle power to the HB Mini Controller. Cooling Mode is also locked out if the Outdoor Air Temperature is below the OAT Cool Lockout setpoint temperature or if the OAT Sensor is bad or missing. If the HB Mini Controller is configured for 1 stage of Cooling, on a call for "Y1" the Supply Fan runs at High speed and Cool Stage 1 will energize. If the HB Mini Controller is configured for 2 stages of Cooling, on a call for "Y1" the Supply Fan runs at Low Speed and Cool Stage 1 is energized. On a call for "Y2" the Supply Fan runs at High 4 HB Mini Controller Technical Guide Controller Installation & Wiring Controller Mounting 2. It is important to mount the controller in a location that is free from extreme high or low temperatures, moisture, dust and dirt. Be careful not to damage the electronic components when mounting the controller. The HB Mini Controller mounts in the HB unit control panel using the 4 plastic standoffs located on the HB control enclosure mounting base. All wiring is to be in accordance with local and national electrical codes and specifications. Minimum wire size for 24 VAC thermostat wiring should be 22 gauge. Minimum wire size for all sensors should be 24 gauge. Be sure that all wiring connections are properly inserted and tightened into the terminal blocks. Do not allow wire strands to stick out and touch adjoining terminals which could potentially cause a short circuit. Be sure all modular wiring harness connectors are seated firmly in their respective modular connectors on the HB Mini circuit board. 3. 4. 5. Important Wiring Considerations 6. Please carefully read and apply the following information when wiring the HB Mini Controller. 1. All 24 VAC wiring must be connected so that all ground wires remain common. Failure to follow this procedure can result in damage to the controller and connected devices. PIN11 - 24 VAC ECONO SECTION PIN12 - RAB PIN13 - CO2 PIN14 - GND PIN10 - COM_23 PIN9 - ECONO POS PIN11 - COM_23 PIN2 - GND PIN6 - GND PIN5 - OAT PIN9 - HT_MON PIN8 - HEAT_3 PIN12 - GND PIN7 - HEAT_2 PIN1 - HEAT_1 P9 PIN1 - SW_24VAC HEAT SECTION PIN6 - COM_1 PIN8 - CFS P1 PIN7 - 24 VAC PIN10 - GND PIN5 - HEAT_1 PIN2 - 24 VAC PIN4 - GND PIN3 - 24 VAC PIN3 - SPARE IN PIN4 - 24 VAC HEAT SECTION ECONO SECTION P3 P9 V3 V1 P1 HIGH SPEED SERIAL COMMUNICATIONS CONNECTOR P3 HSS K4 LD3 SERIAL # C20 C38 R30 R58 R61 C46 P-BUS DRV C40 R42 R44 D11 R49 R52 C22 R54 R55 D14 R59 X1 R4 C23 R51 R53 D13 C24 R75 R72 R73 R74 P-BUS P-BUS R60 C28 R62 R64 D15 C30 C27 U4 R41 VR1 R43 C18 C39 R32 R36 D9 C14 R45 R47 D12 C25 U6 C13 C17 R37 R38 D10 C19 U1 P6 MADE IN THE USA R35 C15 RN1 HSS DRV LD2 R24 R26 R28 D8 R C G Y1 Y2 W1 W2 W3 C1 C2 Q7 LD1 HB MINI YS102032 REV 1 C41 R63 R65 D16 P11 Q3 Q2 Q5 Q4 PERIPHERAL BUS CONNECTOR D3 D2 D17 D4 K5 D22 L1 TB3 HIGH SPEED SERIAL COMMUNICATIONS CONNECTOR C5 R1 R2 R3 D5 C12 (GND) R8 R11 R13 C37 U5 C1 See Thermostat Wiring Diagrams For Complete Wiring Connection Details D19 Q9 D20 R12 R10 R71 R27 R34 R40 D21 Q8 SW1 P8 K2 C3 (R) FROM THERMOSTAT (C) FROM THERMOSTAT (G) FROM THERMOSTAT (Y1) FROM THERMOSTAT (Y2) FROM THERMOSTAT (W1) FROM THERMOSTAT (W2) FROM THERMOSTAT (W3) FROM THERMOSTAT (C1) CLOGGED FILTER SWITCH 24 VAC OUTPUT (C2) CLOGGED FILTER SWITCH 24 VAC OUTPUT HSS HSS HSS P8 P11 C29 V10 R66 R67 C32 C31 D23 V8 V7 VR2 P4 GND 24VAC GND 24VAC PIN2 - 24 VAC V9 V5 R68 R69 P10 C33 COOLING SECTION PIN1 - GND P10 PIN9 - LPS PIN10 - HPS PIN8 - COOL_1 PIN11 - LO_SPD P4 PIN12 - FAN PIN7 - COOL_2 PIN6 - COND PIN1 - GND PIN5 - GND PIN2 - VFD PIN4 - LL_TMP PIN3 - GND COOLING SECTION Figure 2: HB Mini Controller Wiring HB Mini Controller 5 Technical Guide Controller Installation & Wiring Single Stage T-stat Wiring For HB Units Unit With 1 Stage Cooling & 1 Stage Heating Single-Stage Thermostat (24VAC) 1-Cool / 1-Heat W1 Y1 G C RC RH HB Mini Controller Terminal Block R (GND) C G Y1 Y2 W1 W2 W3 Clogged Filter Indicator (Outputs 24VAC) 24VAC C1 GND C2 TB3 V10 R69 GND 24VAC P10 Figure 3: Single Stage T-stat Wiring For HB Unit With 1 Stage Cooling & 1 Stage Heating 6 HB Mini Controller Technical Guide Single Stage T-stat Wiring For HB Units Unit With 2 1 Stage Cooling & 2 1 Stage Heating Single-Stage Thermostat (24VAC) 1-Cool / 1-Heat W1 Y1 G C RC RH HB Mini Controller Terminal Block R (GND) C G Y1 Y2 W1 W2 W3 24VAC Clogged Filter Indicator (Outputs 24VAC) GND C1 C2 TB3 V10 R69 GND 24VAC P10 Figure 4: Single Stage T-stat Wiring For HB Units With 2 Stage Cooling & 2 Stage Heating HB Mini Controller 7 Technical Guide Controller Installation & Wiring Single Stage T-stat Wiring For HB Units Unit With 2 1 Stage Cooling & 3 1 Stage Heating Single-Stage Thermostat (24VAC) 1-Cool / 1-Heat W1 Y1 G C RC RH HB Mini Controller Terminal Block R (GND) C G Y1 Y2 W1 W2 W3 Clogged Filter Indicator (Outputs 24VAC) 24VAC C1 GND C2 TB3 V10 R69 GND 24VAC P10 Figure 5: Single Stage T-stat Wiring For HB Units With 2 Stage Cooling & 3 Stage Heating 8 HB Mini Controller Technical Guide Multi-Stage Single StageT-stat T-statWiring WiringFor ForHB HBUnits Unit With 2 1 Stage Cooling & 2 1 Stage Heating Multi-Stage Thermostat (24VAC) 2-Cool / 2-Heat W2 W1 Y2 Y1 G C RC RH HB Mini Controller Terminal Block R (GND) C G Y1 Y2 W1 W2 W3 Clogged Filter Indicator (Outputs 24VAC) 24VAC C1 GND C2 TB3 V10 R69 GND 24VAC P10 Figure 6: Multi Stage T-stat Wiring For HB Units With 2 Stage Cooling & 2 Stage Heating HB Mini Controller 9 Technical Guide Controller Installation & Wiring Multi-Stage Single StageT-stat T-statWiring WiringFor ForHB HBUnits Unit With 2 1 Stage Cooling & 3 1 Stage Heating Multi-Stage Thermostat (24VAC) 2-Cool / 3-Heat W3 W2 W1 Y2 Y1 G C RC RH HB Mini Controller Terminal Block R (GND) C G Y1 Y2 W1 W2 W3 Clogged Filter Indicator (Outputs 24VAC) 24VAC C1 GND C2 TB3 V10 R69 GND 24VAC P10 Figure 7: Multi Stage T-stat Wiring For HB Units With 2 Stage Cooling & 3 Stage Heating 10 HB Mini Controller Technical Guide Programming With The HB Service Tool Entering Passcodes The HB Service Tool is used to program setpoints and view the status of the HB Mini Controller. It is connected to the HB Mini Controller by means of a modular cable. The cable is connected between the HB Service Tool and the HB Mini Controller board. The HB Service Tool doesn’t require batteries or a separate power source as all power to operate the HB Service Tool is provided through this cable. The HB Mini Controller must be powered in order for the HB Service Tool to function. The passcode entry screen uses a four digit alpha passcode. Position the cursor under the first letter field. To select the desired letter, use the ADJUST ARROWS. The UP arrow increases through the alphabet and the DOWN arrow decreases. When the desired letter appears, press the RIGHT ARROW key to advance to the next letter field. Once all four letter fields spell the desired passcode, press the ENTER key. Available passcodes are: Device Address 064 “OPER” = The Operator is at level 1 for Status and Setpoints “CONT” = The Contractor is at level 2 for Status, Setpoints and Force Modes Again, if no passcode is entered, the default level is 0 and only allows viewing of the status screens. General Procedures When the HB Service Tool is initially powered up, this screen will be displayed. Press ENTER to proceed to the next screen. Version: X.XX Date: XX/XX/XX When the HB Service Tool is initially powered up, the program version and the current time and date will be displayed. After the initial power up, this screen only appears when the HB power is removed and then reapplied. Press ENTER and the HB Service Tool will check all current parameters. When it has finished this checking procedure, press ENTER and the main HB programming screen will be displayed. If you want to change setpoints you will need to enter a passcode at this time. If you only want to view status, a passcode is not required and you can proceed to view status directly by pressing the ENTER key. If you want to change the Passcode, hold down on the UP and DOWN SELECT ARROWS simultaneously and the following screen will be displayed. Enter your passcode as described in the previous section and proceed by pressing the MENU key. The following screen will be displayed. Device Address: 064 Line #2 displays the default address for the HB Mini Controller. Press the ENTER key. The following screen will be displayed. Device Name HBMini Line #2 displays the controller name or program name. Press the ENTER key to advance. Enter Code AAAA Module Selection Screens After pressing ENTER in the previous step, the first available programming module screen appears. All of the HB Mini Controller Status and Setpoint Screens are grouped in specific modules designated by a specific function name. Main Status Fan Status Using the select arrows, scroll to select the desired module on line #1 and press the ENTER key. The other available module screens are listed below in order that they would appear as you scroll down. HB Mini Controller 11 Technical Guide Programming With The HB Service Tool OAT Cool Lockout Cooling Module Heating Module Alarms HVAC Test OAT Cool Lockout NO Line #2 displays “YES” if the Outdoor Air Temperature is below the Cooling Lockout Temperature Setpoint. OAT Temperature OAT Factory Options Factory Options should not be accessed without contacting AAON® or WattMaster. XXX F Line #2 displays the current Outdoor Air Temperature. Alarms Warning: The Factory Options settings should only be accessed when authorized by AAON® or WattMaster Technical Support personnel. Serious damage to the controller and/or HVAC unit could result from improper use of these settings. HB Mini Controller Status & Setpoints The Status and Setpoint screens for the various modules are accessed by selecting a specific module and pressing the ENTER key. Alarms NO Line #2 displays “YES” if an alarm is active. To identify the active alarm(s), press the ESC key, select the Alarm Module and scroll through the available alarms using the up and down SELECT arrow keys. Program Date Program Date XX/XX/XX Main Status Screens The Main Status Screen is accessed by selecting the Main Status Module and pressing the ENTER key. This screen, as its name indicates, allows the user to view the Main Status screens for the HB Mini Controller. After the ENTER key is pressed, the following screen will be displayed. Line #2 displays the Month/Day/Year that the HB Mini Controller software was created. Program Time HVAC Mode Program Time XX:XX:XX HVAC Mode Idle Line #2 displays one of the following HVAC Modes: • Idle • Venting • Cooling • Fault • Heating Press the down SELECT arrow key or up SELECT arrow key to move forward or backward through the Main Status screens as desired. Line #2 displays the time, in 24-hour (military) format that the HB Mini Controller software was created . Program Version Program Version X.XX Line #2 displays the HB Mini Controller software version number. . OAT Heat Lockout OAT Heat Lockout NO Line #2 displays “YES” if the Outdoor Air Temperature is above the Heating Lockout Temperature Setpoint. 12 HB Mini Controller Technical Guide Reset Counts Cooling Stage 1 Energized Reset Count XXXX Y1-Active NO Line #2 displays the total number of times the HB Mini Controller has been reset or has had its power cycled. Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Controller terminal “Y1”. Fan Module Status Screens Cooling Stage 2 Energized The Fan Module Status Screens are accessed by navigating to the Fan Module and pressing the ENTER key. Y2-Active NO Fan Terminal Active G-Active NO Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Controller terminal “Y2”. Fan Status Line #2 displays “YES” if there is a 24 VAC signal connected to the “G” Fan terminal on the HB Mini Controller. Fan Status Fan Off High Speed Fan Relay High Fan Relay OFF Line #2 displays the current Supply Fan Status. If the Supply Fan is on, line #2 displays either “Fan Low Speed” or “Fan High Speed”. Cooling Relay #1 Line #2 displays “ON” if the High Speed Fan Relay is active. Cool 1 Relay OFF Low Speed Fan Relay Low Fan Relay OFF Line #2 displays “ON” if the Low Speed Fan Relay is active. Cooling Module Status Screens The Cooling Module Status Screens are accessed by navigating to the Cooling Module screen and pressing the ENTER key. The following screen will then appear. Line #2 displays “ON” if Cooling Relay #1 is active. Cooling Relay #2 Cool 2 Relay OFF Line #2 displays “ON” if Cooling Relay #2 is active. Status Setpoints Select “Status” by pressing the ENTER key. Press the up or down SELECT arrow key to move forward or backward through the Cooling Module Status screens. HB Mini Controller Low Pressure Switch LPS OPEN Line #2 displays the current status of the Low Pressure Switch. It will only display “CLOSED” when Cooling Relay #1 relay is active and the Low Pressure Switch is operating correctly. 13 Technical Guide Programming With The HB Service Tool High Pressure Switch HPS OPEN Cooling Minimum On Time Cool Min On XXX Sec Line #2 displays the current status of the High Pressure Switch. It will only display “CLOSED” when Cooling Relay #1 relay is active and the High Pressure Switch is operating correctly. Adjust the desired Cooling Minimum On Time and then press the ENTER key. Cooling Module Setpoint Screens Cooling Stage Up Delay The Cooling Module Setpoints Screens are accessed by navigating to the Cooling Module screen and then pressing the ENTER key. The following screen will then appear. Status Setpoints Cool Stage Up XXX Sec Adjust the desired Cooling Stage Up Delay time and then press the ENTER key. Cooling Stage Down Delay Press the down SELECT arrow key until “Setpoints” is on the top line of the screen and then press the ENTER key. Press the down SELECT arrow key or up SELECT arrow key to move forward or backward through the Cooling Module Setpoint screens. Please see the Appendix section in the back of this manual for Tables listing the minimum, maximum and default setpoints for all of the setpoint screens. Cooling Stages Quantity Cool Stages X Adjust the quantity of Cooling Stages or Steps of Cooling and then press the ENTER key. Outdoor Air Temperature Cooling Lockout OAT Cool Lockout XXX F Adjust the Outdoor Air Temperature Cooling Lockout and then press the ENTER key. Cooling Minimum Off Time Cool Min Off XXX Sec Adjust the desired Cooling Minimum Off Time and then press the ENTER key. 14 Cool Stage Down XXX Sec Adjust the desired Cooling Stage Down Delay time and then press the ENTER key. Low Pressure Switch Delay LPS Delay XXX Sec The Low Pressure Switch Delay time is a factory setting and should not be changed unless authorized to do so by WattMaster or AAON® Technical Support. Low Pressure Switch Safety Delay LPS Safety XX Sec The Low Pressure Switch Safety Delay time is a factory setting and should not be changed unless authorized to do so by WattMaster or AAON® Technical Support. LPS Maximum Trips LPS Max trips XX The Low Pressure Switch Max Trips is a factory setting and should not be changed unless authorized to do so by WattMaster or AAON® Technical Support. HB Mini Controller Technical Guide Cooling Fan Off Delay Heating Stage 3 Energized Cool Fan Off Dly XXX Sec The Cooling Fan Off Delay is a factory setting and should not be changed unless authorized to do so by WattMaster or AAON® Technical Support. W3-Active NO Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Controller terminal “W3”. Fan Status Auto Stage Up Time Fan Status Fan Off Auto Stage Up XXX Sec The Auto Stage Up Time can be adjusted on this screen when you are using a single-stage thermostat with a multi-stage HB unit. Line #2 displays the current Supply Fan Status. If the Supply Fan is on, line #2 displays either “Fan Low Speed” or “Fan High Speed”. Heating Relay #1 Heating Module Status Screens Heat 1 Relay OFF The Heating Module Status Screens are accessed by navigating to the Heating Module screen and pressing the ENTER key. The following screen will then appear. Line #2 displays “ON” if Heating Relay #1 is active. Status Setpoints Heating Relay #2 Heat 2 Relay OFF Select “Status” by pressing the ENTER key. Press the up or down SELECT arrow key to move forward or backward through the Heating Module Status screens. Line #2 displays “ON” if Heating Relay #2 is active. Heating Stage 1 Energized W1-Active NO Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Controller terminal “W1”. Heating Stage 2 Energized W2-Active NO Heating Relay #3 Heat 3 Relay OFF Line #2 displays “ON” if Heating Relay #3 is active. Heat Safety Monitor HSM CLOSED Line #2 displays “OPEN” anytime the Heat Safety Monitor is open. Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Controller terminal “W2”. HB Mini Controller 15 Technical Guide Programming With The HB Service Tool Heating Module Setpoint Screens The Heating Module Setpoints Screens are accessed by navigating to the Heating Module and then pressing the ENTER key. The following screen will then appear. Status Setpoints Heating Stage Up Delay Heat Stage Up XXX Sec Adjust the desired Heating Stage Up Delay time and then press the ENTER key. Heating Stage Down Delay Press the down SELECT arrow key until “Setpoints” is on the top line of the screen and then press the ENTER key. Press the down SELECT arrow key or up SELECT arrow key to move forward or backward through the Heating Module Setpoint screens. Please see the Appendix section in the back of this manual for Tables listing the minimum, maximum and default setpoints for all of the setpoint screens. Heating Stages Quantity Heat Stages X Adjust the quantity of Heating Stages and then press the ENTER key. Heat Stage Down XXX Sec Adjust the desired Heating Stage Down Delay time and then press the ENTER key. Heat Safety Monitor Maximum Trips HSM Max Trips X The Heating Safety Maximum Trips is a factory setting and should not be changed unless authorized to do so by WattMaster or AAON® Technical Support. Outdoor Air Temperature Heating Lockout OAT Heat Lockout XXX F Adjust the Outdoor Air Temperature Heating Lockout and then press the ENTER key. Heating Fan Off Delay Heat Fan Off Dly XXX Sec The Heating Fan Off Delay is a factory setting and should not be changed unless authorized to do so by WattMaster or AAON® Technical Support. Heating Minimum Off Time Heat Min Off XXX Sec Adjust the desired Heating Minimum Off Time and then press the ENTER key. Auto Stage Up Time Auto Stage Up XXX Sec The Auto Stage Up Time can be adjusted on this screen when you are using a single-stage thermostat with a multi-stage HB unit. Heating Minimum On Time Heat Min On XXX Sec Alarm Module Status Screens The Alarm Module Status Screens are accessed by navigating to the Alarm Module and pressing the ENTER key. Setpoints are not available for the Alarm Module. After pressing ENTER the following screen will appear. Adjust the desired Heating Minimum On Time and then press the ENTER key. 16 HB Mini Controller Technical Guide HSM Lockout Clogged Filter HSM Lockout NO Line #2 displays “YES” when the Heat Safety Monitor has tripped more than the HSM Max Trips setpoint. HPS Fault Clogged Filter NO Line #2 displays “YES” if there is a 24 VAC signal on the Clogged Filter Input. HVAC Test Module Screens HPS Fault NO Line #2 displays “YES” when the High Pressure Switch is open and a Cooling Relay is active. The HVAC Test Module screens are accessed by navigating to the HVAC Test Module screen and pressing the ENTER key. After pressing ENTER the following screen will then appear. Force Time Limit Force Time Limit XXX Min LPS Lockout LPS Lockout NO Adjust the desired time needed for forcing the HB Mini Controller into an HVAC Test Mode and then press the ENTER key. Force Relays Line #2 displays “YES” when the Low Pressure Switch has tripped more than the LPS Max Trips setpoint. Force Relays NO Bad OAT Sensor Bad OAT NO Line #2 displays “YES” when the Outdoor Air Temperature Sensor is bad or missing. Select “YES” to enable Relay Force Mode and then press the ENTER key. High Speed Fan Relay Force HSpd Fan Relay OFF OAT Cooling Lockout OAT Cool Lockout NO Select “YES” to activate the High Speed Supply Fan Relay and then press the ENTER key. Low Speed Fan Relay Force Line #2 displays “YES” if the Outdoor Air Temperature is below the Cooling Lockout Temperature setpoint. LSpd Fan Relay OFF OAT Heating Lockout OAT Heat Lockout NO Select “YES” to activate the Low Speed Supply Fan Relay and then press the ENTER key. Line #2 displays “YES” if the Outdoor Air Temperature is above the Heating Lockout Temperature setpoint. HB Mini Controller 17 Technical Guide Programming With The HB Service Tool Cooling Relay #1 Force Cool 1 Relay OFF Heating Relay #2 Force Heat 2 Relay OFF Select “YES” to activate Cooling Relay #1 and then press the ENTER key. Select “YES” to activate Heating Relay #2 and then press the ENTER key. Cooling Relay #2 Force Heating Relay #3 Force Cool 2 Relay OFF Select “YES” to activate Cooling Relay #2 and then press the ENTER key. Heat 3 Relay OFF Select “YES” to activate Heating Relay #3 and then press the ENTER key. Heating Relay #1 Force Heat 1 Relay OFF Select “YES” to activate Heating Relay #1 and then press the ENTER key. 18 HB Mini Controller Technical Guide Troubleshooting Using LEDs To Verify Operation The HB Mini Controller is equipped with LEDs that can be used as very powerful troubleshooting tools. The HB Mini Controller circuit board has three different colored LEDs. See Figure 8 for the various LED locations. The Red LED is used to indicate fault conditions. The Yellow LED indicates the mode of operation the HB Mini Controller is currently operating in. The Green LED indicates the power and communications status of the HB Mini Controller. HB Mini Controller Fault Condition Operation If the Red LED indicates you have a Bad Outdoor Air Temperature Sensor, heating mode will operate but Cooling Mode will be disabled until the sensor problem is fixed. Yellow LED LED Blinks 1 Mode Indication Description Vent Mode (Fan Only) 2 Heating Mode 3 Cooling Mode MHGRV RESET ECONO POS RAB LD1 - Red LED Table 2: Yellow LED Blink Codes GND TB2 Green LED LED Blinks 1 Power/Communications Description Power Indicator (No Communications) LD3 LD3 - Green LED LD2 LD1 LD2 - Yellow LED 2 HSS Communications TB1 SAT Table 3: Green LED Blink Codes GND HB Controller Board Figure 8: HB Board LED Locations One LED blink is defined as a 1 second LED on period immediately followed by a 1 second LED off period. After each series of blinks is completed the LED will power off for 3 seconds and then repeat the series of blinks. The various blink codes and their meanings are defined in the tables that follow. Red LED LED Blinks 1 Fault Condition Description Heat Safety Lockout 2 High Pressure Fault 3 Low Pressure Lockout 5 Bad Outdoor Air Temperature Sensor 7 Clogged Filter Switch Notes: 1.) When no fault exists the red LED will be off. 2.) Heat Safety Lockout (1 blink) is the highest priority. Clogged Filter Switch (7 blinks) is the lowest priority. Table 1: Red LED Blink Codes HB Mini Controller 19 Technical Guide Appendix The HB Mini Controller has many setpoints that are user adjustable. This adjustability allows the installer complete control of all major unit operating characteristics during the setup and commissioning phase of the HB unit installation. It also allows a service technician the ability to change setpoints to monitor and record unit operation to determine if the unit is functioning as specified. The tables that follow show the available setpoints for each classification or control group provided on the HB Mini Controller. Cooling Control Setpoints Description Min. Default Cooling Stages 1 2 Minimum Off Time 180 Sec 180 Sec Minimum On Time 300 Sec 300 Sec Staging Up Delay Interval 180 Sec 180 Sec Staging Down Delay Interval 60 Sec 60 Sec Low Pressure Delay Period 5 Sec 30 Sec Low Pressure Safety 5 Sec 5 Sec Low Pressure Max. Trip Point 1 3 Fan Off Delay Period 1 Sec 45 Sec Auto Staging Up Delay 180 Sec 600 Sec Temperature Description Cooling Lockout Temperature Heating Lockout Temperature Control Setpoints Min. Default 32° F 40° F Max. 80° F 40° F 120° F 80° F Table 6: Temperature Control Setpoints Max. 2 900 Sec 900 Sec 900 Sec 900 Sec 60 Sec 30 Sec 5 120 Sec 900 Sec Miscellaneous Control Setpoints Description Min. Default Max. Force Mode Timer 1 Min 60 Min 240 Min Table 7: Miscellaneous Control Setpoints Table 4: Cooling Control Setpoints Heating Control Setpoints Description Min. Default Heating Stages 1 3 Minimum Off Time 60 Sec 60 Sec Minimum On Time 120 Sec 120 Sec Staging Up Delay Interval 180 Sec 180 Sec Staging Down Delay Interval 60 Sec 60 Sec Heat Safety Maximum Count 1 3 Fan Off Delay Period 1 Sec 120 Sec Auto Stage Up Delay 180 Sec 600 Sec Max. 3 900 Sec 900 Sec 900 Sec 900 Sec 5 180 Sec 900 Sec Table 5: Heating Control Setpoints 20 HB Mini Controller Technical Guide Temperature – Resistance – Voltage For Type III 10 K Ohm Thermistor Sensors Temp Resistance Temp Resistance (Ohms) Voltage @ Input (VDC) (ºF) -10 -5 0 5 10 15 20 25 30 35 40 45 50 52 54 56 58 Temp Resistance (Ohms) Voltage @ Input (VDC) (ºF) (Ohms) Voltage @ Input (VDC) (ºF) 93333 80531 69822 60552 52500 45902 40147 35165 30805 27140 23874 21094 18655 17799 16956 16164 15385 2.98 2.94 2.89 2.83 2.77 2.71 2.64 2.57 2.49 2.41 2.33 2.24 2.15 2.11 2.08 2.04 2.00 60 62 64 66 68 69 70 71 72 73 74 75 76 78 80 82 84 14681 14014 13382 12758 12191 11906 11652 11379 11136 10878 10625 10398 10158 9711 9302 8893 8514 1.96 1.93 1.89 1.85 1.81 1.79 1.78 1.76 1.74 1.72 1.70 1.68 1.66 1.63 1.59 1.55 1.52 86 88 90 95 100 105 110 115 120 125 130 135 140 145 150 8153 7805 7472 6716 6047 5453 4923 4449 4030 3656 3317 3015 2743 2502 2288 1.48 1.45 1.41 1.33 1.24 1.16 1.09 1.02 0.95 0.88 0.82 0.76 0.71 0.66 0.61 Thermistor Sensor Testing Instructions 1.) Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered). 2.) Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-”(minus) lead on GND terminal and the “+”(plus) lead on the sensor input terminal being investigated. If the voltage is above 3.3 VDC, then the sensor or wiring is “open.” If the voltage is less than 0.05 VDC, the sensor or wiring is shorted. Table 8: Temperature Sensor - Voltage & Resistance for Type III Sensors HB Mini Controller 21 Technical Guide Notes: 22 HB Mini Controller Technical Guide HB Mini Controller 23 Form: AA-HBM-TGD-01A All rights reserved AAON, Inc. Printed in the USA WattMaster Controls Inc. • 8500 NW River Park Drive Phone (816) 505-1100 www.wattmaster.com • November 2005 Copyright 2005 Parkville, Mo. • 64152 Fax (816) 505-1101 2425 So. Yukon Ave • Tulsa, OK 74107-2728 Ph: (918) 583-2266 • Fax: (918) 583-6094 AAON® Part No. R38860 ">
Download
Advertisement
Key features
24 VAC thermostat integration
Single/multi-stage thermostat support
Auto-staging feature
Equipment safety monitoring
Fault condition lockout modes
2-speed fan control
Frequently asked questions
It utilizes a built-in auto-staging feature.
It monitors the Heat Safety Monitor, High Pressure Switch, and Low Pressure Switch.
Heating mode is locked out and reset by removing the call for heating or cycling power to the controller.
Cooling Mode locks out if the Low Pressure Switch trips too many times, if the Outdoor Air Temperature is too low, or if the OAT Sensor malfunctions.