Diesel generator set
QSK60 series engine
EPA emissions
1600 kW - 2000 kW 60 Hz
Description
Cummins Power Generation commercial generator sets are fully integrated power generation systems providing optimum performance, reliability and versatility for stationary and prime power applications.
This generator set is designed in facilities certified to ISO9001 and manufactured in facilities certified to ISO9001 or ISO9002.
The Prototype Test Support (PTS) program verifies the performance integrity of the generator set design. Cummins Power
Generation products bearing the PTS symbol meet the prototype test requirements of NFPA
110 for Level 1 systems.
All low voltage models are CSA certified to product class 4215-01.
The generator set is available Listed to UL
2200, Stationary Engine Generator
Assemblies. The PowerCommand control is
Listed to UL 508 - Category NITW7 for U.S. and Canadian usage. Circuit breaker assemblies are UL 489 Listed for 100% continuous operation and also UL 869A Listed
Service Equipment.
U.S. EPA
Engine certified to U.S. EPA Nonroad Source
Emissions Standards, 40 CFR 89, Tier 2.
Model
DQKAA
DQKAB
Standby rating
60 Hz kW (kVA)
50 Hz kW (kVA)
Prime rating
60 Hz kW (kVA)
50 Hz kW (kVA)
1750 (2188) 1600
2000 (2500)
Features
Cummins ® heavy-duty engine - Rugged 4-cycle, industrial diesel delivers reliable power, low emissions and fast response to load changes.
Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads and fault clearing short-circuit capability.
Permanent magnet generator (PMG) - Offers enhanced motor starting and fault clearing short-circuit capability.
Control system - The PowerCommand
®
electronic control is standard equipment and provides total genset system integration including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display,
AmpSentry™ protection, output metering, auto-shutdown at fault detection and NFPA 110 Level 1 compliance.
Cooling system - Standard integral set-mounted radiator system, designed and tested for rated ambient temperatures, simplifies facility design requirements for rejected heat.
NFPA - The genset accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems.
Warranty and service - Backed by a comprehensive warranty and worldwide distributor network.
Continuous rating
60 Hz kW (kVA)
50 Hz kW (kVA)
Data sheets
60 Hz 50 Hz
D-3335
D-3336
©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry and “Our energy working for you.” are trademarks of
Cummins Power Generation. Other company, product or service names may be trademarks or service marks of others.
S-1514d (2/08)
Generator set specifications
Governor regulation class
Voltage regulation, no load to full load
Random voltage variation
Frequency regulation
Random frequency variation
Radio frequency emissions compliance
Engine specifications
Design
Bore
Stroke
Displacement
Cylinder block
Battery capacity
Battery charging alternator
Starting voltage
Fuel system
Fuel filter
Air cleaner type
Lube oil filter type(s)
Standard cooling system
Alternator specifications
Design
ISO8528 Part 1 Class G3
± 0.5%
± 0.5%
Isochronous
± 0.25%
IEC 801.2 through IEC 801.5; MIL STD 461C, Part 9
4 cycle, V-block, turbocharged and low temperature air aftercooled
158.8 mm (6.25 in)
190.0 mm (7.48 in)
60.2 litres (3673 in 3 )
Cast iron, 60°V 16 cylinder
2200 amps minimum at ambient temperature of -18 °C to 0 °C
(0 °F to 32 °F)
40 amps
24 volt, negative ground
Cummins modular common rail
Dual element, 10 micron filtration, spin-on fuel filters with 15 micron water separator
Dry replaceable element oil filters
Four spin-on, combination full flow filter and bypass filters
High ambient radiator
Rotor
Insulation system
Brushless, 4 pole, revolving field
Single bearing, flexible disc
Class H on low and medium voltage, Class F on high voltage
Exciter type
Phase rotation
Alternator cooling
AC waveform total harmonic distortion
Telephone influence factor (TIF)
Telephone harmonic factor (THF)
Available voltages
60 Hz line-neutral/line-line
• 219/380
• 254/440
• 277/480
• 347/600
• 2400/4160
• 7200/12470
* Note: Consult factory for other voltages.
• 7620/13200
• 7970/13800
PMG (permanent magnet generator)
A (U), B (V), C (W)
Direct drive centrifugal blower fan
< 5% no load to full linear load, < 3% for any single harmonic
< 50 per NEMA MG1-22.43
< 3
50 Hz line-neutral/line-line
• 220/380
• 230/400
• 240/415
• 254/440
• 1905/3300
• 3640/6300
Generator set options and accessories
Engine
208/240/480 V coolant heater for ambient above 4.5
°C
(40
°F)
208/240/480 V coolant heater for ambient below 4.5
°C
(40
°F)
Control panel
120/240 V, 100 W control anti-condensation space heater
Paralleling configurations
Remote fault signal package
Run relay package
Alternator
80 °C rise alternator
105
125
°C rise alternator
°C rise alternator
120/240 V, 300 W anticondensation heater
Temperature sensor - RTDs,
2/phase
Temperature sensor – alternator bearing RTD
Differential current transformers
Exhaust system
Industrial grade exhaust silencer
Residential grade exhaust silencer
Critical grade exhaust silencer
Cooling system
Remote radiator cooling
Generator set
AC entrance box
Batteries
* Note: Some options may not be available on all models - consult factory for availability.
• 3810/6600
• 6350/11000
Battery rack w/hold-down - floor standing
Circuit breaker - set mounted
Disconnect switch - set mounted
PowerCommand Network
Remote annunciator panel
Spring isolators
2 year warranty
5 year warranty
10 year major components
Our energy working for you.™ www.cumminspower.com
©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry and “Our energy working for you.” are trademarks of
Cummins Power Generation. Other company, product or service names may be trademarks or service marks of others.
S-1514d (2/08)
Control system
Operator panel features
Analog AC metering panel - Provides color-coded display of generator set output voltage, current, frequency, power factor and kW. All phases of voltage and current are simultaneously displayed. Easy to see output status from a distance.
Graphical data display - Allows operator to view all engine and alternator data; perform operator adjustments for speed, voltage and time delays; view fault history; and set up and adjust the generator set (set up requires password access). A portion of the display is allocated to display system status including alarm and shutdown conditions. Display is controlled by sealed membrane switches. Up to 9 lines of data can be displayed with approximately 26 characters per line.
LED status lamps - The status lamps indicate remote start command (green), not in auto (red-flashing), warning
(amber) and shutdown (red).
Mode selector switch - Off/manual/auto and run/stop switches allow remote automatic starting or manual starting from the operator panel. Panel includes an LED lamp to indicate manual mode operation.
Exerciser switch - Automated exercise function in the control allows an operator to initiate an exercise period and have it automatically completed by the control.
Fault reset switch - Allows the operator to reset the control after a warning or shutdown condition. LED lamp with switch indicates that a fault is present on the system.
Panel lamps and switch - Operator panel can be illuminated by a series of high-intensity LED lamps controlled by a membrane switch on the panel. Panel lamps include a time delay to automatically switch off after a preset time period.
Emergency stop switch - Provides positive and immediate shutdown of the generator set on operation.
Construction - Operator panel is a sealed design with membrane switches for most functions. Mechanical switches are oil-tight design. Plug interfaces are provided to the generator set control system. Display panel labeling is configurable for language.
Standard control functions
• Integrated Isochronous governing and fuel control system.
• Integrated 3-phase sensing voltage regulation system with automatic single and three phase fault regulation.
• Integrated AC protective functions include over/under voltage, short-circuit, overcurrent (warning and shutdown) and overload.
• Integrated engine management system including configurable cycle-cranking functions and configurable start sequence.
• Comprehensive warning and shutdown protection including customer configurable warning and shutdown conditions.
• Comprehensive data displays including 3-phase AC voltage, current, power factor, kW and kVA; engine oil pressure, coolant temperature, DC volts and other service functions; operating history (load and fault conditions) and system setup information.
Options
Integrated digital paralleling controls including options for semi-automatic and automatic (isolated bus) applications.
LonMark compliant network interface.
Control anti-condensation heater.
Key-type mode select switch.
Relay outputs for genset running, common warning and common shutdown.
Exhaust temperature alarm.
Alternator temperature alarm(s).
Centinel™ lube oil burn system.
Power transfer control function to allow generator set to control remote power circuit breakers for open, fast closed or soft (ramping) power transfer from a utility source to the genset (2 minute maximum fail-todisconnect timer).
Our energy working for you.™ www.cumminspower.com
©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry and “Our energy working for you.” are trademarks of
Cummins Power Generation. Other company, product or service names may be trademarks or service marks of others.
S-1514d (2/08)
Ratings definitions
Emergency standby power (ESP):
Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS
5514.
Limited-time running power (LTP):
Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528.
Prime power (PRP):
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN
6271 and BS 5514.
Base load (continuous) power (COP):
Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous
Power (COP) in accordance with ISO 8528, ISO 3046, AS
2789, DIN 6271 and BS 5514.
This outline drawing is for reference only. See respective model data sheet for specific model outline drawing number.
Do not use for installation design
Model
DQKAA
DQKAB
Dim “A” mm (in.)
6175 (243)
6175 (243)
Dim “B” mm (in.)
2534 (100)
2534 (100)
Dim “C” mm (in.)
3043 (120)
3043 (120)
Set Weight* dry kg (lbs)
15231 (33569)
17382 (38309)
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.
Cummins Power Generation
1400 73 rd Avenue N.E.
Minneapolis, MN 55432 USA
Telephone: 763 574 5000
Fax: 763 574 5298
Set Weight* wet kg (lbs)
15396 (33932)
17908 (39470)
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system except through an approved device or after building main switch is open.
Our energy working for you.™ www.cumminspower.com
©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry and “Our energy working for you.” are trademarks of