Cummins 2 Megawatt Diesel Generator specifications!

Add to My manuals
4 Pages

advertisement

Cummins 2 Megawatt Diesel Generator specifications! | Manualzz

Diesel generator set

QSK60 series engine

EPA emissions

1600 kW - 2000 kW 60 Hz

Description

Cummins Power Generation commercial generator sets are fully integrated power generation systems providing optimum performance, reliability and versatility for stationary and prime power applications.

This generator set is designed in facilities certified to ISO9001 and manufactured in facilities certified to ISO9001 or ISO9002.

The Prototype Test Support (PTS) program verifies the performance integrity of the generator set design. Cummins Power

Generation products bearing the PTS symbol meet the prototype test requirements of NFPA

110 for Level 1 systems.

All low voltage models are CSA certified to product class 4215-01.

The generator set is available Listed to UL

2200, Stationary Engine Generator

Assemblies. The PowerCommand control is

Listed to UL 508 - Category NITW7 for U.S. and Canadian usage. Circuit breaker assemblies are UL 489 Listed for 100% continuous operation and also UL 869A Listed

Service Equipment.

U.S. EPA

Engine certified to U.S. EPA Nonroad Source

Emissions Standards, 40 CFR 89, Tier 2.

Model

DQKAA

DQKAB

Standby rating

60 Hz kW (kVA)

50 Hz kW (kVA)

Prime rating

60 Hz kW (kVA)

50 Hz kW (kVA)

1750 (2188) 1600

2000 (2500)

Features

Cummins ® heavy-duty engine - Rugged 4-cycle, industrial diesel delivers reliable power, low emissions and fast response to load changes.

Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads and fault clearing short-circuit capability.

Permanent magnet generator (PMG) - Offers enhanced motor starting and fault clearing short-circuit capability.

Control system - The PowerCommand

®

electronic control is standard equipment and provides total genset system integration including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display,

AmpSentry™ protection, output metering, auto-shutdown at fault detection and NFPA 110 Level 1 compliance.

Cooling system - Standard integral set-mounted radiator system, designed and tested for rated ambient temperatures, simplifies facility design requirements for rejected heat.

NFPA - The genset accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems.

Warranty and service - Backed by a comprehensive warranty and worldwide distributor network.

Continuous rating

60 Hz kW (kVA)

50 Hz kW (kVA)

Data sheets

60 Hz 50 Hz

D-3335

D-3336

©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry and “Our energy working for you.” are trademarks of

Cummins Power Generation. Other company, product or service names may be trademarks or service marks of others.

S-1514d (2/08)

Generator set specifications

Governor regulation class

Voltage regulation, no load to full load

Random voltage variation

Frequency regulation

Random frequency variation

Radio frequency emissions compliance

Engine specifications

Design

Bore

Stroke

Displacement

Cylinder block

Battery capacity

Battery charging alternator

Starting voltage

Fuel system

Fuel filter

Air cleaner type

Lube oil filter type(s)

Standard cooling system

Alternator specifications

Design

ISO8528 Part 1 Class G3

± 0.5%

± 0.5%

Isochronous

± 0.25%

IEC 801.2 through IEC 801.5; MIL STD 461C, Part 9

4 cycle, V-block, turbocharged and low temperature air aftercooled

158.8 mm (6.25 in)

190.0 mm (7.48 in)

60.2 litres (3673 in 3 )

Cast iron, 60°V 16 cylinder

2200 amps minimum at ambient temperature of -18 °C to 0 °C

(0 °F to 32 °F)

40 amps

24 volt, negative ground

Cummins modular common rail

Dual element, 10 micron filtration, spin-on fuel filters with 15 micron water separator

Dry replaceable element oil filters

Four spin-on, combination full flow filter and bypass filters

High ambient radiator

Rotor

Insulation system

Brushless, 4 pole, revolving field

Single bearing, flexible disc

Class H on low and medium voltage, Class F on high voltage

Exciter type

Phase rotation

Alternator cooling

AC waveform total harmonic distortion

Telephone influence factor (TIF)

Telephone harmonic factor (THF)

Available voltages

60 Hz line-neutral/line-line

• 219/380

• 254/440

• 277/480

• 347/600

• 2400/4160

• 7200/12470

* Note: Consult factory for other voltages.

• 7620/13200

• 7970/13800

PMG (permanent magnet generator)

A (U), B (V), C (W)

Direct drive centrifugal blower fan

< 5% no load to full linear load, < 3% for any single harmonic

< 50 per NEMA MG1-22.43

< 3

50 Hz line-neutral/line-line

• 220/380

• 230/400

• 240/415

• 254/440

• 1905/3300

• 3640/6300

Generator set options and accessories

Engine

… 208/240/480 V coolant heater for ambient above 4.5

°C

(40

°F)

… 208/240/480 V coolant heater for ambient below 4.5

°C

(40

°F)

Control panel

… 120/240 V, 100 W control anti-condensation space heater

… Paralleling configurations

… Remote fault signal package

… Run relay package

Alternator

… 80 °C rise alternator

… 105

… 125

°C rise alternator

°C rise alternator

… 120/240 V, 300 W anticondensation heater

… Temperature sensor - RTDs,

2/phase

… Temperature sensor – alternator bearing RTD

… Differential current transformers

Exhaust system

… Industrial grade exhaust silencer

… Residential grade exhaust silencer

… Critical grade exhaust silencer

Cooling system

… Remote radiator cooling

Generator set

… AC entrance box

… Batteries

* Note: Some options may not be available on all models - consult factory for availability.

• 3810/6600

• 6350/11000

… Battery rack w/hold-down - floor standing

… Circuit breaker - set mounted

… Disconnect switch - set mounted

… PowerCommand Network

… Remote annunciator panel

… Spring isolators

… 2 year warranty

… 5 year warranty

… 10 year major components

Our energy working for you.™ www.cumminspower.com

©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry and “Our energy working for you.” are trademarks of

Cummins Power Generation. Other company, product or service names may be trademarks or service marks of others.

S-1514d (2/08)

Control system

Operator panel features

Analog AC metering panel - Provides color-coded display of generator set output voltage, current, frequency, power factor and kW. All phases of voltage and current are simultaneously displayed. Easy to see output status from a distance.

Graphical data display - Allows operator to view all engine and alternator data; perform operator adjustments for speed, voltage and time delays; view fault history; and set up and adjust the generator set (set up requires password access). A portion of the display is allocated to display system status including alarm and shutdown conditions. Display is controlled by sealed membrane switches. Up to 9 lines of data can be displayed with approximately 26 characters per line.

LED status lamps - The status lamps indicate remote start command (green), not in auto (red-flashing), warning

(amber) and shutdown (red).

Mode selector switch - Off/manual/auto and run/stop switches allow remote automatic starting or manual starting from the operator panel. Panel includes an LED lamp to indicate manual mode operation.

Exerciser switch - Automated exercise function in the control allows an operator to initiate an exercise period and have it automatically completed by the control.

Fault reset switch - Allows the operator to reset the control after a warning or shutdown condition. LED lamp with switch indicates that a fault is present on the system.

Panel lamps and switch - Operator panel can be illuminated by a series of high-intensity LED lamps controlled by a membrane switch on the panel. Panel lamps include a time delay to automatically switch off after a preset time period.

Emergency stop switch - Provides positive and immediate shutdown of the generator set on operation.

Construction - Operator panel is a sealed design with membrane switches for most functions. Mechanical switches are oil-tight design. Plug interfaces are provided to the generator set control system. Display panel labeling is configurable for language.

Standard control functions

• Integrated Isochronous governing and fuel control system.

• Integrated 3-phase sensing voltage regulation system with automatic single and three phase fault regulation.

• Integrated AC protective functions include over/under voltage, short-circuit, overcurrent (warning and shutdown) and overload.

• Integrated engine management system including configurable cycle-cranking functions and configurable start sequence.

• Comprehensive warning and shutdown protection including customer configurable warning and shutdown conditions.

• Comprehensive data displays including 3-phase AC voltage, current, power factor, kW and kVA; engine oil pressure, coolant temperature, DC volts and other service functions; operating history (load and fault conditions) and system setup information.

Options

… Integrated digital paralleling controls including options for semi-automatic and automatic (isolated bus) applications.

… LonMark compliant network interface.

… Control anti-condensation heater.

… Key-type mode select switch.

… Relay outputs for genset running, common warning and common shutdown.

… Exhaust temperature alarm.

… Alternator temperature alarm(s).

… Centinel™ lube oil burn system.

… Power transfer control function to allow generator set to control remote power circuit breakers for open, fast closed or soft (ramping) power transfer from a utility source to the genset (2 minute maximum fail-todisconnect timer).

Our energy working for you.™ www.cumminspower.com

©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry and “Our energy working for you.” are trademarks of

Cummins Power Generation. Other company, product or service names may be trademarks or service marks of others.

S-1514d (2/08)

Ratings definitions

Emergency standby power (ESP):

Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS

5514.

Limited-time running power (LTP):

Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528.

Prime power (PRP):

Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN

6271 and BS 5514.

Base load (continuous) power (COP):

Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous

Power (COP) in accordance with ISO 8528, ISO 3046, AS

2789, DIN 6271 and BS 5514.

This outline drawing is for reference only. See respective model data sheet for specific model outline drawing number.

Do not use for installation design

Model

DQKAA

DQKAB

Dim “A” mm (in.)

6175 (243)

6175 (243)

Dim “B” mm (in.)

2534 (100)

2534 (100)

Dim “C” mm (in.)

3043 (120)

3043 (120)

Set Weight* dry kg (lbs)

15231 (33569)

17382 (38309)

* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.

Cummins Power Generation

1400 73 rd Avenue N.E.

Minneapolis, MN 55432 USA

Telephone: 763 574 5000

Fax: 763 574 5298

Set Weight* wet kg (lbs)

15396 (33932)

17908 (39470)

Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system except through an approved device or after building main switch is open.

Our energy working for you.™ www.cumminspower.com

©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry and “Our energy working for you.” are trademarks of

Cummins Power Generation. Other company, product or service names may be trademarks or service marks of others.

S-1514d (2/08)