450W Single Output Power Supply
Features:
Universal AC input / Full range
Built in active PFC function, PF > 0.90
+5V / 0.3A auxiliary output
150% Peak load Capability
Constant current limit
Power OK signal
Remote ON / OFF, Remote sense function
Protection: OVP, OLP, OTP, SCP, Fan failure
3 years warranty
AK-450
series
Output
Input
MODEL
DC Voltage Range
Rated Current
Current Range
Rated Power
Ripple & Noise (Max.)
Voltage Adj. Range
Voltage Tolerance
Line Regulation
Load Regulation
Setup, Rise Time
Hold Up Time (Typ.)
Voltage Range
Frequency Range
Power Factor (Typ.)
Efficiency (Typ.)
AC Current (Typ.)
Inrush Current (Typ.)
Leakage Current
Over Load
AK-450-12 AK-450-24 AK-450-30 AK-450-36 AK-450-48
Note.2
Note.3
12V
37.5A
0 ~ 37.5A
450W
24V
19A
0 ~ 19.0A
456W
30V
15A
0 ~ 15.0A
450W
<1% (mVp-p), according to the rated Output Voltage
±10% Typical adjustment by potentiometer
±1.0%
±0.5%
±0.5%
36V
12.7A
0 ~ 12.7A
457W
48V
9.5A
0 ~ 9.5A
456W
Note.4
800ms, 60ms at full load
16ms / 230VAC at full load
90 ~ 264VAC, 127 ~ 370VDC
47 ~ 63Hz
0.98 / 230VAC, 0.99 / 115VAC at full load
89% 91% 91% 92%
4.5A / 115VAC, 2.2A / 230VAC
27A / 115VAC, 54A / 230VAC
< 1.0mA / 240VAC
Hiccup mode: when the rated output power is within 105 ~ 150% for more than 3secs.
Constant current limit: > 150% rated power / short circuit
93%
Auto-recovery: If O/P drop to 40% of the rated output voltage, PSU will shut down and auto-recover
5times (If fault condition remains after 5times recovery, PSU will shut down. User must re-power on to recover)
Protection
Over Voltage
Over Temperature
14.4 ~ 15.6V
28.8 ~ 31.2V
36.0 ~ 39.0V
43.2 ~ 46.8V
Protection type: Latch-style (Recovery after reset AC power ON or inhibit)
57.8 ~ 62.4V
By detecting primary and secondary heat sink.
Protection type: Shut down o/p voltage (Auto recovers automatically after temperature goes down)
Function
Environment
Auxiliary Power
Remote ON / OFF Control
Power OK Signal
Working Temp.
Working Humidity
Storage Temp. & Humidity
Temp. Coefficient
Vibration
External switch or NPN Transistor to turn ON / OFF
Open drain signal low when PSU turns on, Max. sink current: 20mA, Max. drain voltage: 40V.
-20 ~ +70°C (Refer to output load de-rating curve)
20 ~ 90% RH non-condensing
-40 ~ +85°C, 10 ~ 95% RH
±0.02% / °C (0 ~ 50°C)
10 ~ 500Hz, 5G 10min. / 1cycle, period for 60min. each along X, Y, Z axes Compliance to
IEC 68-2-6, IEC 68-2-64
Safety & EMC
Others
Note
Note.5
Safety Standards
Withstand Voltage
Isolation Resistance
EMI Conduction & Radiation
Harmonic Current
Note.6
EMS Immunity
MTBF
Cooling
Dimension (WxHxD)
Packing
Certified UL 60950-1; EN 60950-1
I/P-O/P: 3KVAC (4242VDC), I/P-FG: 1.5KVAC (2121VDC), O/P-FG: 0.5KVAC (707VDC), 1min
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
Certified EN 55022
Certified EN 61000-3-2; EN 61000-3-3
Certified EN 55024; IEC 61000-4-2, 3, 4, 5, 6, 8, 11
74.71K HRS Certified MIL-HDBK-217F
105x41x199 mm / 4.134x1.614x7.835 inch
1.1kg; 18pcs / 20.1kg / 1.02CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uF & 47uF parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. De-rating may apply in low input voltage. Please check the de-rating curve for more details.
5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still
meets EMC directives.
6. Conduct this test without enclosure.
REV. B3
13/03/13
1
Mechanical Specification:
450W Single Output Power Supply AK-450
series
Unit:mm[inch]
Airf low direction
4-M4 L=5mm
AC Input & DC Output
Pin No. Assignment
Pin No.
1
2
3
4,5
6,7
Assignment
AC/L
AC/N
FG
-V
+V
Control pin number assignment (CN2): JST S8B-PHDSS or equivalent
Pin No.
1
2
3
4
Assignment
AUX
GND
P-OK
EN-
Pin No.
5
7
8
Assignment
GND
EN+
VS+
VS-
Mating Housing
PHDR-08VS
Terminal
SPHD-002T-P05
Function Description of CN2:
Pin No.
7
8
5
6
3
4
1
2
Function
AUX
GND
P.OK
EN-
GND
EN+
VS+
VS-
Description
+5V / 0.3A auxiliary power
Ground
Power OK
Remote ON/OFF (–)
Ground
Remote ON/OFF (+)
Remote voltage sense (+)
Remote voltage sense (–)
8-M4 L=5mm
REV. B3
13/03/13
2
450W Single Output Power Supply AK-450
series
De-rating Curve:
Load V.S Temp.
100
80
60
40
20
-20 0 10 20 30 40 50
Ambient Temperature (°C)
60 70
Load V.S I/P Voltage
100
90
80
70
60
50
40
90
100 110 120
Input Voltage (Vac)
Ta=25°C
264
Peak Loading:
I-peak
I
I-normal
0
T-normal
T-peak
T
T-
PEAK
represents the period during which the output current is at 110% to 150% of nominal (shown as I-
PEAK
). Curve B shows the relationship between the percentage of peak current (I-
PEAK
) and the allowable duration (T-
PEAK
).
If the peak current is taken for longer that the allowed duration indicated by curve B, the output current will drop to a constant limited current of 105% of nominal, then.
The unit between peak currents (T-
NORMAL
) is dependant up on the output current drawn between the peaks (I-
NORMAL
) and curve A shows the relationship between the two.
The higher the percentage of normal current (I-
NORMAL
) is of the nominal current, the longer the interval (T-
NORMAL
) before the next peak current can be drawn.
T-normal (sec.)
24
20
16
12
8
4
0
10 20 30 40 50 60 70 80 90 % I-normal
T-peak (sec.)
24
20
16
12
8
4
0
110 115 120 125 130 135 140 145 150 % I-peak
CURVE A CURVE B
REV. B3
13/03/13
3
1. Power OK Signal and Auxiliary output
450W Single Output Power Supply AK-450
series
DC / DC
5V / 0.3A
* Place an additional capacitor to have a better
performance of auxiliary power operation.
* The grounding of "AUX" power should be
connected to "GND" port. If " V-" is connected
as Grounding, make sure to short the GND
and V- ports.
* 470μF
10V
AUX.
LOAD
2. Remote ON/OFF Control
(A)
2KΩ
AUX
EN+
SW
5V
EN-
GND sw
OFF
ON
Power ON
Power OFF
(A) Using internal 5V auxiliary source
(B)
AUX
2K Ω
EN+
5V
ENTr
GND
L / H
GND
Tr
L
H
Power ON
Power OFF
(B) ON / OFF Control by NPN transistor
5V
2K Ω
AUX
EN+
EN-
5V
SW
GND sw
OFF
ON
Power ON
Power OFF
(C) Using external voltage source
3. Remote Sense
2
GND
CN2
AUX
1
ENP-OK
EN+
VS-
GND
VS+
8 7
+V -V
R Load
REV. B3
13/03/13
4