advertisement
Sigma CP-A
Conventional Fire Control Panel
(KA11020M2, KA11040M2, KA11080M2)
Man-1138 Issue 05 January 2013
Intelligent Security & Fire Ltd
Contents
1. Introduction ......................................................................................................................... 4
2. Safety .................................................................................................................................. 4
4. Technical specification ........................................................................................................... 5
5. Control panel fascia............................................................................................................... 7
6. Connecting to the circuit board .............................................................................................. 8
7. Software revision number ...................................................................................................... 8
8. Detection zone wiring ............................................................................................................ 9
9. Priority/Non-priority alarm settings ......................................................................................... 9
10. Standard Sounder circuit wiring ......................................................................................... 10
11. Connection to remote control terminals .............................................................................. 10
12. Aux 24V DC supply ............................................................................................................ 11
13. Connection to relay contacts .............................................................................................. 11
14. Connection to Repeater panels ........................................................................................... 11
15. Connection to Ancillary boards ........................................................................................... 12
16. Connection to 8 way Sounder boards ................................................................................. 12
17. Panel operation ................................................................................................................. 13
17.1 Normal condition ..................................................................................................................... 13
17.2 Fire condition (sounders set to priority alarm) ............................................................................ 13
17.3 Fire condition (sounders set to non-priority alarm) ...................................................................... 13
17.4 Silence/sound alarms ............................................................................................................... 13
17.5 Reset ...................................................................................................................................... 13
17.6 Zone fault ............................................................................................................................... 13
17.7 Sounder fault .......................................................................................................................... 13
17.8 Power fault ............................................................................................................................. 13
17.9 System fault ............................................................................................................................ 13
17.10 Lamp test .............................................................................................................................. 13
17.11 Disablements ......................................................................................................................... 13
Intelligent Security & Fire Ltd
17.11.3 Activate delays ........................................................................................................................................ 14
17.11.4 Disable fault contact ............................................................................................................ 14
17.12 Test mode ............................................................................................................................. 14
18. Configuration options ................................................................................................................. 14
19. Watchdog reset switch ...................................................................................................... 17
20. Processor reset switch ....................................................................................................... 17
21. Internal indications – troubleshooting ................................................................................. 17
21.1 Mains fail ................................................................................................................................ 17
21.2 Batt fail ................................................................................................................................... 17
Man-1138_Sigma_CPA_Alarmsense_5 Page 2 of 22
21.3 CPU fault ................................................................................................................................ 17
21.4 Aux 24V fault .......................................................................................................................... 18
21.5 Batt low .................................................................................................................................. 18
21.6 Earth fault ............................................................................................................................... 18
21.7 Sys fuse fault .......................................................................................................................... 18
21.8 S1 fault and S2 fault ................................................................................................................ 18
21.9 Comms fault ............................................................................................................................ 18
22. Power supply .................................................................................................................... 19
23. Maintenance ..................................................................................................................... 20
24. Zone designation label ....................................................................................................... 20
25. Record of Configuration ..................................................................................................... 21
Intelligent Security & Fire Ltd
Man-1138_Sigma_CPA_Alarmsense_5 Page 3 of 22
1. Introduction
The Sigma CP Alarmsense range consists of a series of conventional fire alarm control panels that comply with European standards EN54-2 and EN54-4, Fire Detection and Fire Alarm systems - Control and Indicating Equipment.
The range consists of 2, 4 and 8 zone control panels.
The Apollo Alarmsense system allows compatible smoke and heat detectors, call points, sounders, sounder/ beacons and alarm relays to be connected to a single pair of wires rather than having two pairs of wires, one for detection devices and one for sounders and relays.
Wiring sounders to the detection circuits eliminates the need to install separate sounder circuit cables and also offers the ability to provide zoned or two stage sounder operation.
The Alarmsense priority/non-priority sounder scheme makes the Alarmsense system ideal for protection of Houses of
Multiple Occupation. With appropriate settings on the sounder and sounder beacon devices it is possible to configure the system such that when an alarm is detected, only the sounder local to the activated detector is operated to alert occupants in that vicinity subject to a configurable alarm verification period. This functionality allows full compliance with
BS5839-6.
All control panels have an integral, mains powered battery charger and power supply.
In addition to the requirements of EN54-2 the control panel has the following facilities:
………….
Test condition
with requirements.
to allow the automatic resetting of zones in alarm for testing purposes. EN54-2 Section 10 option
………….
Delay of the actioning
of fire alarm devices (sounders) so that an alarm may be verified before a premises is evacuated. EN54-2 Section 7.11 option with requirements.
………….
Fire alarm devices
to enable an audible warning to be sounded throughout a premises upon the detection of a fire condition or the operation of a manual call point. EN54-2 Section 7.8 option with requirements.
Also in addition to the requirements of EN54-2, all control panels have voltage free relay contacts for fire and local fire which operate upon fire condition. These are to be used for local control and signalling.
2. Safety
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work act 1974 to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used.
An article is not regarded as properly used if it is used ‘without regard to any relevant information or advice’ relating to its use made available by the supplier.
This product should be installed, commissioned and maintained by trained service personnel in accordance with the following:
(i)
(ii)
(iii)
(iv)
IEE regulations for electrical equipment in buildings
Codes of practice
Statutory requirements
Any instructions specifically advised by the manufacturer
According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that you make any appropriate information about this product available to anyone concerned with its use.
This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction. As such it
Intelligent Security & Fire Ltd simultaneously shall be incorporated in the fixed wiring.
Switch disconnect devices such as MK Sentry 63A or similar are suitable for this.
Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe.
This control panel is designed for indoor use only and at temperatures between -5
0 a maximum relative humidity of 95%.
C (+/- 3) and +40
0
C (+/- 2) and with
The IP rating for the enclosure is IP30.
Operation outside of these limits may render the equipment unsafe.
Man-1138_Sigma_CPA_Alarmsense_5 Page 4 of 22
3. Mounting
The control panel should be mounted on a dry, flat surface, at eye height to the display and in a level position such that the enclosure is not distorted.
Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all three mounting positions.
It should be positioned in an accessible position as agreed with the end user.
Suitable fixings should be used at all fixing points such that the control panel is securely mounted and is not liable to move once fixed.
The control panel should not be mounted in another enclosure or near sources of excessive heat.
Cables should be connected using suitable cable glands fitted to the knockouts provided. If additional cable entry points are required, all swarf and debris caused by drilling of additional cable entries must be cleared before power is applied to the panel.
4. Technical specification
Table 1 - Electrical specifications
Mains supply
Mains supply fuse
230V AC +10% - 15% (100 Watts maximum)
1.6Amp (F1.6A L250V)
Replace only with similar type
Power supply rating
Maximum ripple current
Output voltage
Imax a
3 Amps total including battery charge
28V +/ 2V
1.5 Volts
18.5 to 29V DC +/- 2%
400 milliamps
Imax b 2.3 Amps
Imin 0.065A
Battery type (Yuasa NP)
See table 2 for capacities
Battery charge voltage
Two 12 Volt sealed lead acid (7Ah maximum)
27.6VDC nominal (temperature compensated)
See table 3
Battery charge current
Battery lead fuse
Battery high impedance warning (Rimax)
Low battery voltage indication
Low battery shut off voltage
Maximum current draw from batteries
R0V output
Dedicated sounder outputs
Zonal sounder outputs
Alarm verification delay
0.7A maximum
20mm, 3.15A glass
1.35 ohms max
21V +/- 2%
18.5V +/- 2%
3 Amps
Fused at with electronic fuse
24V Fused at 500mA with electronic fuse
24V rated at 200mA with electronic fuse
30, 60 or 120 seconds
Replace only with the same type
With main power source off
1.6 Amp total load over all circuits
1.6 Amp total load over all circuits
Configuarble
Fault relay contact rating
Zone quiescent current
30VDC 1A Amp maximum for each
Fire relay contact rating
Local fire relay contact rating
30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Intelligent Security & Fire Ltd
30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Maximum ratings not to be exceeded
4mA maximum
0.5mm
2
to 2.5mm
2 solid or stranded wire
See table 4 for detector types
Terminal capacity
Number of detectors per zone
Number of sounders per common sounder circuit
Detection circuit end of line
Sounder circuit end of line
No. of detection circuits
SIL, AL, FLT, RST inputs
Cabling
Up to 20
Dependent on type and current consumption
See table 6 for sounder types
3K3 5% ½ Watt resistor
10K 5% ¼ Watt resistor
(see table 2 for number of zones for each model)
Supplied in terminals
Supplied in terminals
Dependent on model
Switched -ve, max resistance 100 Ohms
FP200 or equivalent (maximum capacitance 1uF maximum inductance 1 millihenry)
Metal cable glands must be used
Man-1138_Sigma_CPA_Alarmsense_5 Page 5 of 22
Table 2 - Standby battery capacity required for fully loaded system
Panel model 24 hours standby
48 hours standby
72 hours standby
KA11020 (2 Zones) 3Ah
KA11040 (4 Zones) 3.3Ah
KA11080 (8 Zones) 3.75Ah
4.6Ah 6.2Ah
Table 3 - Battery charge voltage versus temperature
Temperature
0
C
0
10
Battery charge voltage
29.2
28.56
20
30
40
27.99
27.55
27.13
Standby current
0.065
Table 4 - Compatible detectors
Manufactur er
Maximum Number per zone
55000-190 HEAT
(A1R)
Apollo
20
20
20
Table 5 - Compatible detector bases and call points
Max panel alarm current
0.10A
45681-244
55000-894
AlarmSense mounting base Apollo
AlarmSense manual call point
Apollo
Table 6 - Compatible AlarmSense sounder bases and relay
Model Type Manufac turer
Maximum number per zone
45681-510 AlarmSense 20
45681-509
55000-017
AlarmSense Sounder Beacon base
Alarmsense Open Area Sounder
Apollo 20
Apollo 10
55000-018
Beacon
Alarmsense Open Area sounder Apollo 10
55000-035
55000-835
45681-294
Alarmsense Open Area Beacon
AlarmSense Alarm Relay
Sounder base cap white
Apollo
Apollo
Apollo
10
20
N/A
45681-295 Sounder base cap red Apollo N/A
Intelligent Security & Fire Ltd
Table 7 - Compatible sounders for the two common sounder circuits
Model Type
BANSHEE ELECTRONIC
WAFER ELECTRONIC
FIRECRYER RANGE ELECTRONIC VOICE
KOBELL MOTORISED
ASKARI ELECTRONIC
ROSHNI ELECTRONIC
SQUASHNI ELECTRONIC
SYMPHONI ELECTRONIC
ELECTRONIC BELL ELECTRONIC
CFB BELLS
B6 AND B8 BELLS
MOTORISED
SOLENOID
VIMPEX
VIMPEX
VIMPEX
VIMPEX
FULLEON
FULLEON
FULLEON
Standard polarised type only
Standard polarised type only
Standard polarised type only
Man-1138_Sigma_CPA_Alarmsense_5 Page 6 of 22
5. Control panel fascia
In addition to the mandatory controls and indications required by the EN54-2 standard, two, seven segment, LED displays and MODE, SELECT and ENTER buttons are provided to allow easy entry and storage of codes to configure the control panel to suit the requirements of the installation.
Removing the fascia
Before the fascia can be removed it will be necessary to unplug the three way terminal block on the left hand side of the
PCB.
The fascia of the control panel is held in place by countersunk screws. Undo the two screws and lift the fascia gently away from the box towards you.
With the fascia removed there is much more room inside the panel for making off and dressing cables.
When cabling work is complete the fascia can be re-fitted with the two countersunk screws and the red, green/yellow and black wires re-connected to the three way terminal block.
It is most important that the polarity of the red and black wires is observed as wrong connection of these will damage the control panel.
Fire Alarm Control
Model: KA11080M2
Intelligent Security & Fire Ltd
Man-1138_Sigma_CPA_Alarmsense_5 Page 7 of 22
6. Connecting to the circuit board
All connections for field wiring are to a single row of terminals along the top of the circuit board.
The connections for the power cables are to a pluggable terminal block, which may be pulled off of the board to remove the plate/PCB assembly. Remove this pluggable terminal only with mains power off.
Shielded fire alarm cable such as FP200 and metal cable glands must be used for all connections to the panel.
The resistance of any core of any cable must not exceed 25 ohms. The shield of the cable must be bonded securely to the enclosure via a metal gland.
Wiring should enter the enclosure at the top of the panel using the knockouts provided and be formed tidily to the appropriate terminals leaving only enough wire to ensure that there is no strain on the PCB.
Terminals are capable of accepting wires of up to 2.5mm
2
.
Terminal designations
Wiring must not go across the front of the circuit board plate or between the plate and the circuit board.
If cable entries need to be in positions other than at the knockouts provided, wiring must be fed behind and well away from the surface of the circuit board.
The space at the bottom of the enclosure is largely occupied by the standby batteries, so this must be borne in mind when considering cable entries.
CORRECT
INCORRECT INCORRECT
7. Software revision number
C 7
D 4
IC 10
X1
C6
C 27
C 5 C 4
VDR4
F 2
RL3
D 35
C 68
+
D 3
C 75
R 13
D 34
+
C 67
C 3 C 2 C 1
RL 2
VDR3
C 97 C 93
D 2
D 33
C 74
R 7
+
C 66
J 1
C 41
C 23 C 22 C 21 C 20 C127 C128 C 35 C 36 C 33 C 34 C 60 C 61
D 1
C 73
R 1
D 32
C 65
+
R 129
TR 24
R 87
D 16
R 104
D 15
R 85
R 86
D 14
R 130
D 13
R 131
R 132
D 23
R 133
D 22
R 78
R 135
R 134
D 30
VDR1
F 10
D 12
IC 2
IC 1
TR 25
+
TR9 D 11
C 24
D 9
+
TR 28
R 126
C 82
D 10
IC 4
IC 5
C 25
+
Z 14
F 11
FB21
TR47
TR 23
X2
C 106 C 107
+
FB20
C 51 TR 19
Z 11
New features may be added to fire control panels from time to time and when this is done the operating software of the unit is updated. The software revision can be located on the main processor by removing the plate holding the PCB from the enclosure and turning it over. The software version will have a number such as “SigXX.hex” and it is this number, which will determine
REG1
VR1
C 56
Intelligent Security & Fire Ltd
L 1 which features the panel has installed and its compatibility with Sigma CP ancillary board, sounders boards, repeaters etc.
SW2 T 3
SW4
SW1
LED17 LED35
D 1008 ISSUE 06
LED4
SERIAL NUMBER
+
R 75
R 76
TH1
PANEL SOFTWARE VERSION LABEL
Man-1138_Sigma_CPA_Alarmsense_5 Page 8 of 22
8. Detection zone wiring
The detection zones provide a nominal 12V DC to power conventional Alarmsense detectors and call points as listed in the compatibility tables on page 6.
Note:
Only Alarmsense detection devices and call points are compatible.
Kentec K14060 LCMU end of line monitoring devices are not compatible with Alarmsense panels.
To activate Alarmsense sounders connected to the zone wiring, the voltage is raised to 24V DC.
The wiring is monitored for open and short circuit fault conditions by removing the 3K3 end of line monitoring resistors that are supplied fitted to the control panels’ terminals and placing them across the last device that is wired to the zone circuit.
Detection zone circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuits to work correctly.
Alarmsense sounders must also be wired across the detection zone.
Alarmsense sounder and sounder beacon bases can be set as priority or non-priority via switch 1 on the DIL switch in the base unit. When a sounder or sounder beacon base is set to non-priority, activation of a detector connected to the base will not cause the panel to enter the alarm condition and will only activate the sounder to which the detector is connected. After the configured alarm verification delay (30 seconds, 60 seconds or 120 seconds) the panel will reset the activated detector. If smoke is no longer present the system will revert to normal quiescent condition. If smoke is still present and the detector activates again a fire condition will be indicated at the control panel and all sounders will operate.
This functionality is particularly well suited to residential buildings such as Houses of Multiple Occupation because the alarm is restricted to the local area before it is verified thus minimising disruption due to false alarms. This allows compliance with the requirements of BS5839 part 6.
Man-1138_Sigma_CPA_Alarmsense_5 Page 9 of 22
10. Standard Sounder circuit wiring
In addition to the ability to operate Alarmsense sounder and sounder beacons from the detection circuit, the control panel also has two standard sounder outputs which provide 24V DC upon any alarm. All sounders connected to these outputs must be of the polarised type. If non-polarised sounders are used, the control panel will permanently show a fault condition. See table 7 for a list of compatible sounder types.
Sounder circuits are monitored for open and short circuit faults by placing the 10K end of line monitoring resistor that is supplied fitted to the terminals in the control panel across the last sounder device on the circuit.
Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuit to work correctly.
A maximum of 1.6 Amps is available for powering sounders including those connected to the detection zones with a maximum load of 0.41 Amps on any one of the standard sounder circuits described here.
The sounder circuits are protected by 500 milliamp fuses.
POLARISED
SOUNDER
+
IN
+
OUT
_ _
IN OUT
POLARISED
SOUNDER
+
IN
+
OUT
_ _
IN OUT
10K end of line resistor
11. Connection to remote control terminals
Some functions of the control panel can be controlled externally from the panel if required. Operation of these inputs
must be restricted by an access level 2 control as defined in EN54-2 These are abbreviated at the terminals block
as follows: a) Remote 0 V supply - ROV b) Silence Alarm – SIL c) Sound Alarm – AL d) Fault – FLT e) Reset – RST
To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open switch or contact and via a resistance of no greater than 100 ohms.
Intelligent Security & Fire Ltd
Man-1138_Sigma_CPA_Alarmsense_5 Page 10 of 22
12. Aux 24V DC supply
An auxiliary 24V DC supply is provided to enable local signalling or control of ancillary systems such as door release controllers.
The terminals for the Aux 24V supply are labelled Aux 24V and ROV. The ROV terminal is the negative terminal and is the same terminal that should be used to switch the remote control terminals.
It is possible to make the ROV terminal pulsing so that by connecting it to the AL terminal via a remote, volt free contact, it can be used to pulse the dedicated sounder circuits in response to a signal from another system for example to give an alert. See programming code 24.
The supply is fitted with an electronic self resetting fuse to protect the control panel’s 24V supply in the event of a wiring fault.
Any standing load on the Aux 24V supply must be taken into account when calculating battery standby times as standby time will be significantly affected by even modest standing loads. It is recommended that the Aux24V output is not used to power standing loads and not used to supply loads of greater than 300 milliamps
Where the Aux 24V supply is used to power electromechanical devices such as relays or door retainers it is imperative that a suppression diode is fitted across the coil of the electromechanical device to prevent the generation of high voltage transients back to the control panels power supply.
The Aux 24V DC Supply is not suitable for powering Sigma CP sounder boards, a separate power supply should be used for these.
13. Connection to relay contacts
Volt free changeover relay contacts are provided for local control and signalling if required. These contacts are rated for switching signalling circuits only and the maximum ratings listed in table 1 on page 5 should not be exceeded under any circumstances.
Fault relay
The fault relay is normally energised and will de-energise upon any fault condition including total loss of power.
Local fire relay
The local fire relay will energise upon activation of a fire condition on any of the zones or pressing of the sound alarm button on the front panel. The relay will remain activated until the alarm is silenced or the panel is reset. This relay will not operate upon activation of the remote AL input or when a fire condition is triggered on a zone that is in test mode.
Fire relay
The fire relay will energise upon activation of a fire condition on any of the zones. The relay will remain activated until the control panel is reset. This relay will
NOT
operate upon activation of the remote AL input. Individual zones can be configured not to operate the Fire relay by setting configuration options E1 to E8.
14. Connection to Repeater panels
Repeater panels connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel
PCB. Up to 7 repeaters may be connected and each repeater has terminals for the incoming cables and outgoing cables.
All except the last ancillary board, sounder board or repeater panel connected to the cable must have the jumper links J2 removed.
Set the repeater address using the DIP switch (SW7); ensure no two repeaters share the same address.
Apply power to main panel first and then all repeater panels. Turn on the Enable Control keyswitch and set the Write
Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a few seconds and the
Turn the write enable switch off, then on again and then press the ENTER button to accept each repeater that has been switch on the main panel.
Intelligent Security & Fire Ltd found. When all repeaters have been added, set the main panel Write Enable switch to off. Press the Watchdog reset
All repeaters are now configured and the main control panel will report a fault if any repeaters that have been accepted become faulty or go off line.
For full details of commissioning procedures for repeaters see the Sigma CP Repeater Operation and maintenance manual.
Man-1138_Sigma_CPA_Alarmsense_5 Page 11 of 22
15. Connection to Ancillary boards
Ancillary boards connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel
PCB. Up to 7 Ancillary boards may be connected and each board has terminals for the incoming cables and outgoing cables. All except the last ancillary board, sounder board or repeater panel connected to the cable must have the jumper links J2 removed.
Set the ancillary board address using the DIP switch (SW7); ensure no two ancillary boards share the same address.
Apply power to main panel first and then all ancillary boards. Turn on the Enable Control keyswitch and set the Write
Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a few seconds and the main panel will show the addresses of the ancillary boards that were found on the display for instance 01 indicates that an ancillary board at address 1 has been found.
Turn the write enable switch off, then on again and then press the ENTER button to accept each ancillary board that has been found. When all ancillary boards have been added, set the main panel Write Enable switch to off. Press the
Watchdog reset switch on the main panel.
All ancillary boards are now configured and the main control panel will report a fault if any ancillary boards that have been accepted become faulty or go off line.
For full details of commissioning procedures for ancillary boards see the Sigma CP Ancillary board Operation and maintenance manual.
16. Connection to 8 way Sounder boards
Sounder boards connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel
PCB. Up to 7 Sounder boards may be connected and each board has terminals for the incoming cables and outgoing cables. All except the last Ancillary board, Sounder board or Repeater connected to the cable must have the jumper links
J2 removed. Sounder boards must be powered from a separate power supply which is suitably rated to supply the full sounder load that is connected. This can be up to 4 Amps if all circuits are fully loaded.
Set the sounder board address using the DIP switch (SW7); ensure no two sounder boards share the same address.
Apply power to main panel first and then all sounder boards. Turn on the Enable Control keyswitch and set the Write
Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a few seconds and the main panel will show the addresses of the sounder boards that were found on the display for instance b1 indicates that a sounder board at address 1 has been found.
Turn the write enable switch off, then on again and then press the ENTER button to accept each sounder board that has been found. When all sounder boards have been added, set the main panel Write Enable switch to off. Press the
Watchdog reset switch on the main panel.
All sounder boards are now configured and the main control panel will report a fault if any sounder boards that have been accepted become faulty or go off line.
For full details of commissioning procedures for Sounder boards see the Sigma CP Sounder board Operation and maintenance manual.
Intelligent Security & Fire Ltd
Man-1138_Sigma_CPA_Alarmsense_5 Page 12 of 22
17. Panel operation
17.1 Normal condition
Under normal conditions, control panels will have only the green,
17.2 Fire condition (sounders set to priority alarm)
Power On
LED lit.
Upon receipt of a fire condition by activation of a detector or call point, the zonal
Fire
Common Fire
indicator will light and the
indicators will flash at around 2Hz. The zonal indicators can be used to differentiate call point and detector activation by setting configuration option 28. If option 28 is set, and a call point is operated, the zonal indicator will flash and if a detector is operated it will illuminate continuously.
The internal fire and local fire relays will also operate and signal any systems to which they are connected.
Any sounders connected to the detection zones or standard sounder circuits will operate in common, zonal or 2-stage mode as selected by configuration options 10 to 12 (see table 8).
17.3 Fire condition (sounders set to non-priority alarm)
Upon receipt of a fire condition by activation of a detector, the sounder or sounder beacon to which the detector is connected will sound. After two minutes, the control panel will reset the detector. If the detector is successfully reset the panel will revert to the Normal condition. If the detector re-enters the alarm state, sounders and relays connected to the detection zones will operate in common, zoned or two stage alarm mode depending on the setting of configuration options 10 to 12 (see table 8), the internal fire and local fire relays will operate and the two standard 24V sounder outputs will operate.
17.4 Silence/sound alarms
The
Silence/Sound alarm
be inserted.
button can only be operated at access level two which means that the
Enable Control
To silence the sounders, insert the Enable Control key and press the Silence/Sound alarm button.
key must
When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state.
Pressing the again.
Silence/Sound alarm
whilst the control panel is in this silenced condition, will cause the sounders to operate
The sounders can be toggled on and off with the
Silence/Sound alarm
button as required.
17.5 Reset
To reset the panel, insert the Enable key then press the Reset button.
17.6 Zone fault
Removal of a detector from its base or a fault on any of the zone wiring will cause the
Fault
LED and
Zone Fault
LEDs to light indicating the zone in which the fault has occurred. All devices that are connected beyond the point where a detector is removed from its base will continue to operate.
17.7 Sounder fault
A fault on the wiring to detection zones and sounder circuits will cause the indicating a fault on the wiring to the sounder circuits.
Fault
and
Sounder Fault
LEDs to light
17.8 Power fault
Failure of the mains power, disconnection of the standby battery or high impedance in the charging circuit will cause the
Fault
and
Power Fault
LEDs to light indicating an abnormality in the power supply to the control panel.
17.9 System fault
Intelligent Security & Fire Ltd
The
System Fault
LED will light if the configuration memory has not been set or has become corrupt.
17.10 Lamp test
All LED indicators can be tested at any time by pressing the be inserted to test the indicators.
The buzzer can be silenced at any time by pressing the inserted to silence the buzzer.
Lamp Test
button. The
Enable Control
key does not need to
Buzzer Silence
button. The enable key does not need to be
17.11 Disablements
It is possible to disable parts of the system. This may be required if there are works going on in a building which may cause the fire alarm system to operate in error.
17.11.1 Disable zones
To disable zones, the
Enable Control
key should be inserted and the mode button pressed until “d” appears in the first of the two seven segment LED displays. The
Select
button should then be pressed to select the number of the zone which
Man-1138_Sigma_CPA_Alarmsense_5 Page 13 of 22
is to be disabled in the second of the two seven segment displays. Once the desired zone is displayed, the enter button should be pressed to confirm the disablement.
The
Disable
LED will light and the
Zone Fault
LED will light for each disabled zone.
When is a zone is disabled, all detectors, call points and sounders in the zone will be disabled.
A disabled zone is shown on the seven segment display as ‘dx.’ (where x is the zone number from 1-8). If the ‘x’ is flashing, it means that there are activated devices in that zone and re-enabling it will put the control panel into the fire condition.
The panel should be Reset before enabling any zone with a flashing “dx.” Indication.
Note: The flashing “dx” indicator will only appear on panels produced after January 2013.
17.11.2 Disable sounders
To disable sounder outputs, press the mode button to select “db” on the seven segment display. Pressing enter will disable all sounders and cause the
Disable
and
Sounder Fault
LEDs to light.
17.11.3 Activate delays
To activate delays on zones as set in configuration options 31 to 48, press the mode button until Ad appears on the seven segment LED display. When the enter button is pressed any zones that are set as delayed will have their alarm outputs delayed by the time set in configuration options 00 to 09.
17.11.4 Disable fault contact
The fault relay can be disabled by selecting configuration option 22.
17.12 Test mode
Fire alarm systems must be tested regularly to ensure that they are functioning correctly. The Sigma CP range of panels enable the system to be tested single handed by using a test mode. When in test mode, activation of a fire alarm will be automatically reset after a few seconds to eliminate the need to return to the control panel to reset after every activation.
Test mode is entered in a similar way to disablements. With the
“t” appears in the first of the seven segment displays. Then press the appears. Pressing the in test mode.
Enter
button will cause the
Test
and
Enable Control
Zone Fault
key inserted, press the
Mode
button until
Select
button until the required zone number
LEDs to illuminate indicating the zones which are
Disablements and zone tests are cleared by repeating the sequence that is used to select them, i.e. the "db" function
(for example) toggles between sounders disabled and sounders enabled.
18. Configuration options
The panel range has many configuration options which can be set at the time of commissioning to suit the requirements of the installation. These options are normally set once and will rarely need to change. The configuration options are only available at access level 3. To get to access level 3, CAREFULLY slide the Write Enable switch (located behind the aperture in the panel plate) to the right position using a small screwdriver or similar. When the panel is at access level 3, the buzzer will “pip” three times every few seconds as an indication that it is at this access level.
Intelligent Security & Fire Ltd
Configuration options are simple to enter using the codes in table 8 below. When the control panel is at access level 3, the sub-text of the
Mode
and
Select
buttons is used to enter a number using tens (+10) and units (+1).
When the required code number is displayed, pressing the enter button will cause the dot on the units, seven segment display to flash. This indicates that a configuration option has been set.
To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 to A8, C1 to
C8 and E1 to E8 and those with a flashing dot indicate which options have been set.
Man-1138_Sigma_CPA_Alarmsense_5 Page 14 of 22
ZONE 1 - ALARM
FROM DETECTOR
DELAYED
DOT
FLASHING
ZONE 1 - ALARM
FROM DETECTOR
NOT DELAYED
NO DOT
Table 8 – Configuration codes
COD
E
FUNCTION COMMENTS
L0 NON-PRIORITY ALARM CONFORMATION TIME
30S
Sets time before detector resets and checks if smoke still present at detector.
L1 NON-PRIORITY ALARM CONFORMATION TIME
60S
L2 NON-PRIORITY ALARM CONFORMATION TIME
120S
01
02
03
SOUNDER DELAY TIME = 1 MINUTE
SOUNDER DELAY TIME = 2 MINUTES
SOUNDER DELAY TIME = 3 MINUTES
04 SOUNDER DELAY TIME = 4 MINUTES
05 SOUNDER DELAY TIME = 5 MINUTES
06 SOUNDER DELAY TIME = 6 MINUTES
07 SOUNDER DELAY TIME = 7 MINUTES
Sets the time delay before sounders operate in combination with configuration codes 31 to 48 and access level 2 function AD.
08 SOUNDER DELAY TIME = 8 MINUTES
09 SOUNDER DELAY TIME = 9 MINUTES
10 COMMON ALARM MODE (default)
11 TWO-STAGE ALARM MODE
12 ZONED ALARM MODE
21* DISABLE FIRE BUZZER
22* DISABLE FAULT OUTPUT
All sounders operate upon any fire condition
Continuous sounders in activated zone, pulsing elsewhere
Only sounders connected to zone in alarm operate
Buzzer will not operate on fire condition
Fault relay will not operate except upon total power failure
23 DISABLE EARTH FAULT MONITORING Connection of fire alarm wiring to earth will not announce a fault
24
Intelligent Security & Fire Ltd
26 DISABLE FIRE OUTPUT Fire relay will not operate upon any alarm
27 REMOVE AUX 24 UPON PANEL RESET
28 INDICATE CALL POINT ACTIVATION
29 DO NOT RE-SOUND ALARMS FROM ANOTHER
ZONE
31 ZONE 1 ALARM FROM DETECTOR DELAYED
32 ZONE 2 ALARM FROM DETECTOR DELAYED
33 ZONE 3 ALARM FROM DETECTOR DELAYED
34 ZONE 4 ALARM FROM DETECTOR DELAYED
35 ZONE 5 ALARM FROM DETECTOR DELAYED
24V supply switches off for about 5 seconds when panel is reset
Activation of an AlarmSense call point is indicated by a flashing zone indicator and “Pu” on the 7 segment display.
Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display.
Silenced sounders will not re-sound upon further zone activations
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by detector only.
Note: Access level 2 function Ad must be set for this to take effect.
Man-1138_Sigma_CPA_Alarmsense_5 Page 15 of 22
36 ZONE 6 ALARM FROM DETECTOR DELAYED
37 ZONE 7 ALARM FROM DETECTOR DELAYED
38 ZONE 8 ALARM FROM DETECTOR DELAYED
41 ZONE 1 ALARM FROM CALL POINT DELAYED
42 ZONE 2 ALARM FROM CALL POINT DELAYED
43 ZONE 3 ALARM FROM CALL POINT DELAYED
44 ZONE 4 ALARM FROM CALL POINT DELAYED
45 ZONE 5 ALARM FROM CALL POINT DELAYED
46 ZONE 6 ALARM FROM CALL POINT DELAYED
47 ZONE 7 ALARM FROM CALL POINT DELAYED
48 ZONE 8 ALARM FROM CALL POINT DELAYED
51 COINCIDENCE ZONE 1
52 COINCIDENCE ZONE 2
53 COINCIDENCE ZONE 3
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by call point only.
Note access level 2 function Ad must be set for this to take effect.
Zone contributes to ancillary board coincidence O/P. Any number of zones can be selected to contribute.
54 COINCIDENCE ZONE 4
55 COINCIDENCE ZONE 5
56 COINCIDENCE ZONE 6
57 COINCIDENCE ZONE 7
58 COINCIDENCE ZONE 8
61
62
FULL ALARM MODE ZONE 1
FULL ALARM MODE ZONE 2
71* ZONE 1 SHORT CIRCUIT INDICATES ALARM
72* ZONE 2 SHORT CIRCUIT INDICATES ALARM
73* ZONE 3 SHORT CIRCUIT INDICATES ALARM
74* ZONE 4 SHORT CIRCUIT INDICATES ALARM
When this option is set, any detector activating on the zone will put the panel into alarm. I.e. Non-priority setting on sounder or sounder beacon bases will be ignored.
63 FULL ALARM MODE ZONE 3
64 FULL ALARM MODE ZONE 4
65 FULL ALARM MODE ZONE 5
66 FULL ALARM MODE ZONE 6
67 FULL ALARM MODE ZONE 7
68 FULL ALARM MODE ZONE 8
COD
E
FUNCTION COMMENTS
Changes the trigger threshold of the zone so that the control panel can be used on older systems that had no short circuit monitoring. (Not for use if Alarmsense devices are connected to the zone)
75* ZONE 5 SHORT CIRCUIT INDICATES ALARM
76* ZONE 6 SHORT CIRCUIT INDICATES ALARM
77* ZONE 7 SHORT CIRCUIT INDICATES ALARM
78* ZONE 8 SHORT CIRCUIT INDICATES ALARM
81* ZONE 1 NON-LATCHING Renders the zone self-resetting so that it can be used to receive signals from
82* ZONE 2 NON-LATCHING
83* ZONE 3 NON-LATCHING
84* ZONE 4 NON-LATCHING
85* ZONE 5 NON-LATCHING
86* ZONE 6 NON-LATCHING
87*
88*
Intelligent Security & Fire Ltd other systems and will reset when the input is removed.
Note: It can take up to 20 seconds for zone to reset itself when sounders are operating.
(Not for use if Alarmsense devices are connected to the zone)
91 ZONE 1 DOES NOT SOUND ALARMS
92 ZONE 2 DOES NOT SOUND ALARMS
Prevents the zone from operating any sounders whether connected the two common sounder outputs or to detection zones.
93 ZONE 3 DOES NOT SOUND ALARMS
94 ZONE 4 DOES NOT SOUND ALARMS
95 ZONE 5 DOES NOT SOUND ALARMS
96 ZONE 6 DOES NOT SOUND ALARMS
97 ZONE 7 DOES NOT SOUND ALARMS
98 ZONE 8 DOES NOT SOUND ALARMS
A1* ZONE 1 ANY ALARM DELAYED
A2* ZONE 2 ANY ALARM DELAYED
A3* ZONE 3 ANY ALARM DELAYED
A4* ZONE 4 ANY ALARM DELAYED
A5* ZONE 5 ANY ALARM DELAYED
Zone needs to be triggered for 30 seconds continuously before an alarm is generated.
(Detectors fitted to Alarmsense non-priority sounders are not delayed)
Man-1138_Sigma_CPA_Alarmsense_5 Page 16 of 22
A6* ZONE 6 ANY ALARM DELAYED
A7* ZONE 7 ANY ALARM DELAYED
A8* ZONE 8 ANY ALARM DELAYED
C1 ZONE 1 SOUNDERS INHIBITED
C2 ZONE 2 SOUNDERS INHIBITED
C3 ZONE 3 SOUNDERS INHIBITED
C4 ZONE 4 SOUNDERS INHIBITED
C5 ZONE 5 SOUNDERS INHIBITED
C6 ZONE 6 SOUNDERS INHIBITED
C7 ZONE 7 SOUNDERS INHIBITED
C8 ZONE 8 SOUNDERS INHIBITED
E1* ZONE 1 WILL NOT OPERTATE FIRE RELAY
E2* ZONE 2 WILL NOT OPERTATE FIRE RELAY
E3* ZONE 3 WILL NOT OPERTATE FIRE RELAY
Enables individual zones to be configured not to operate zonal sounders.
E4* ZONE 4 WILL NOT OPERTATE FIRE RELAY
E5* ZONE 5 WILL NOT OPERTATE FIRE RELAY
E6* ZONE 6 WILL NOT OPERTATE FIRE RELAY
E7* ZONE 7 WILL NOT OPERTATE FIRE RELAY
E8* ZONE 8 WILL NOT OPERTATE FIRE RELAY
Enables individual zones to be selected to not operate the fire relay. This is sometimes combined with the nonlatching function to prevent ring around on interconnected panels.
NOTE: Setting the options marked with asterisks does not comply with EN54-2
Once the required configuration options have been set, the Write enable switch must be returned to its normal position to the right. The General fault indicator will remain lit if the Write enable switch is not turned off.
19. Watchdog reset switch
If for any reason the microprocessor in the control panel fails to carry out its operation correctly it will attempt to restart itself. This process is called a “watchdog” and the control panel must record and indicate these events.
If a watchdog event occurs, the control panel will show the FAULT and SYSTEM FAULT LEDs on the front panel, the CPU fault LED inside the panel.
This fault can only be cleared by pressing the WATCHDOG RESET button on the PCB inside the control panel. The control panel buzzer cannot be silenced and will continue to sound until the watchdog activation is reset.
20. Processor reset switch
Once started, the microprocessor controlling the panel should continue to run continuously without interruption. If the microprocessor fails to run correctly it can be reset by pressing the PROCESSOR RESET button on the PCB inside the control panel.
This should not normally be necessary but should be done as a matter of course if the system is behaving abnormally.
The system should resume normal operation within a couple of seconds of pressing the processor reset button.
21. Internal indications – troubleshooting
To assist in identifying fault conditions, which are not detailed on the front of the control panel, a number of internal indicators are visible with the front cover removed as follows:
21.1 Mains fail
If there is not a power cut, check the panels mains fuse.
21.2 Batt fail
Intelligent Security & Fire Ltd
Indicates that the standby battery has become disconnected or that the charging circuit of the control panel has a high resistance or has failed. Check that both batteries are connected and linked together. Test battery. Disconnect battery and ensure that 28 Volts can be measured on battery charger leads.
21.3 CPU fault
Indicates that the central processor unit has failed to correctly execute code and has been re-started by the system watchdog. The watchdog reset switch must be pressed to clear the CPU fault condition.
Press watchdog reset. If system does not return to normal then the panel is probably damaged and needs the circuit board replacing. (See maintenance section).
Man-1138_Sigma_CPA_Alarmsense_5 Page 17 of 22
21.4 Aux 24V fault
The Aux 24V and R0V terminals provide a 500 milliamp, 24V DC power supply for power fire alarm ancillary equipment.
This LED indicates that fuse protecting the R0V output has operated and the rating of this output has been exceeded.
The fuse is a self resetting type and the supply will resume when the fault condition is removed.
21.5 Batt low
Illuminates when the system is running on batteries and the battery voltage is lower than 21V +/-2% (the minimum battery voltage).
21.6 Earth fault
Indicates that part of the system wiring is connected to earth. Remove all system wiring and re-connect cables one at a time until the earth fault returns. This will indicate which cable the earth fault is present on.
21.7 Sys fuse fault
Indicates that the total power rating of the power supply has been exceeded and that the system fuse has come into operation. Remove and review all loads and re-connect one at a time until over rated circuit trips fuse to identify troublesome circuit.
21.8 S1 fault and S2 fault
Indicates a short or open circuit on the standard 24V DC sounder outputs. Remove wiring and refit end of line resistors.
Check sounder circuit wiring.
21.9 Comms fault
Indicates that communication has been lost with a repeater panel or Ancillary board. Check for comms fault at all repeaters and ancillary boards to identify the source of the problem.
Intelligent Security & Fire Ltd
Man-1138_Sigma_CPA_Alarmsense_5 Page 18 of 22
22. Power supply
The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply, which connects to the fused terminal block labelled “230V”.
The fused terminal block contains a 20mm, F1.6A L250V fuse which should only be replaced with a similar type.
The output voltage of the power supply is 28V DC +/- 2V and the total current rating including a maximum 0.7A for battery charging is 3 Amps. Fuse F12 mounted on the circuit board is a self-resetting electronic fuse rated at 4 Amps.
The incoming mains cable should be routed well away from other lower voltage wiring by a distance of at least 50mm.
Mains wiring should include an earth conductor, which is securely bonded to the building earth and should enter the enclosure as close as possible to the mains terminal block. Mains wires should be kept very short inside the enclosure and secured together close to the mains terminal block with a cable tie.
The control panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity (see table 2 for battery size required for each model).
The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps.
Battery leads are supplied wired to the PCB along with a link to connect the two batteries in series. The PCB is fitted with a 20mm, 3.15A T1 glass fuse (F13) in the battery charging circuit, which must only be replaced with one of the same type.
It is most important that the polarity of the batteries is carefully observed when connecting.
When the batteries are discharged to a level at which a low battery indication is given, the BATT FAIL indicator will also be lit.
Wrongly connected batteries could cause damage to the control panel.
MAINS
TERMINAL
KEEP MAINS WIRES AS SHORT AS POSSIBLE
AND SECURE ALL THREE WIRES CLOSE TO
THE TERMINAL BLOCK WITH A CABLE TIE
L
N
E
N
L
+
RED BATTERY
LEAD TO +
TERMINAL
+
GREY LINK
-
BLACK BATTERY
LEAD TO -
TERMINAL
Intelligent Security & Fire Ltd
Man-1138_Sigma_CPA_Alarmsense_5 Page 19 of 22
23. Maintenance
The control panels do not require any specific maintenance but should the control panel become dirty it can be wiped over with a damp cloth and should then be dried with a dry, lint free cloth. Detergents or solvents should not be used to clean the panel and care must be taken that water does not enter the enclosure.
The control panel contains sealed lead acid batteries to provide standby power in the event of a mains failure. The batteries have a life expectancy of around 4 years. The control panel monitors the condition of the batteries and will announce a fault if the battery impedance becomes too high.
It is recommended that these batteries be tested in accordance with the battery manufacturer’s recommendations annually to determine their suitability for continued standby applications.
Routine testing of the fire alarm system in accordance with BS5839: Part 1: 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately.
Should the control panel become faulty the complete electronic assembly can be replaced.
To do this, any configured options should be noted then both mains and battery power should be removed before the work is started.
The field wiring should be carefully labelled and removed from the terminals.
The PCB can now be taken out of the panel by removing the 2 M4 screws holding the plate in position.
Fitting the new PCB is the reverse of the procedure for removing the board.
24. Zone designation label
The control panels are supplied with a zone designation label onto which zone designations can be written.
This enables each zone to be given a text description allowing easier identification of any zones showing an alarm, fault or disablement condition.
Intelligent Security & Fire Ltd
Man-1138_Sigma_CPA_Alarmsense_5 Page 20 of 22
25. Record of Configuration
06
07
08
09
10
02
03
04
05
11
L0
L1
L2
00
01
Use the table below to record the configuration codes that have been set on the control panel for future reference. Place a tick in the grey band for any configuration options that are set.
It is recommended that a copy of this table is left with the control panel under the supervision of the person responsible for the fire detection system.
CODE FUNCTION TICK IF THIS
OPTION IS
SET
NON-PRIORITY ALARM CONFORMATION TIME 30S
NON-PRIORITY ALARM CONFORMATION TIME 60S
NON-PRIORITY ALARM CONFORMATION TIME 120S
SOUNDER DELAY TIME = 30 SECONDS
SOUNDER DELAY TIME = 1 MINUTE
SOUNDER DELAY TIME = 2 MINUTES
SOUNDER DELAY TIME = 3 MINUTES
SOUNDER DELAY TIME = 4 MINUTES
SOUNDER DELAY TIME = 5 MINUTES
SOUNDER DELAY TIME = 6 MINUTES
SOUNDER DELAY TIME = 7 MINUTES
SOUNDER DELAY TIME = 8 MINUTES
SOUNDER DELAY TIME = 9 MINUTES
COMMON ALARM MODE (default)
TWO-STAGE ALARM MODE
21* DISABLE FIRE BUZZER
54
55
56
57
51
52
53
44
45
46
47
48
41
42
43
35
36
37
38
31
32
33
34
23
24
26
27
28
29
63
64
65
66
67
58
61
62
68
DISABLE EARTH FAULT MONITORING
PULSED REMOTE CONTROL OUTPUT
DISABLE FIRE OUTPUT
REMOVE AUX 24 UPON PANEL RESET
INDICATE CALL POINT ACTIVATION
DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE
ZONE 1 ALARM FROM DETECTOR DELAYED
ZONE 2 ALARM FROM DETECTOR DELAYED
ZONE 3 ALARM FROM DETECTOR DELAYED
ZONE 4 ALARM FROM DETECTOR DELAYED
ZONE 5 ALARM FROM DETECTOR DELAYED
ZONE 6 ALARM FROM DETECTOR DELAYED
ZONE 7 ALARM FROM DETECTOR DELAYED
ZONE 8 ALARM FROM DETECTOR DELAYED
ZONE 1 ALARM FROM CALL POINT DELAYED
ZONE 2 ALARM FROM CALL POINT DELAYED
ZONE 3 ALARM FROM CALL POINT DELAYED
ZONE 4 ALARM FROM CALL POINT DELAYED
ZONE 5 ALARM FROM CALL POINT DELAYED
ZONE 6 ALARM FROM CALL POINT DELAYED
ZONE 7 ALARM FROM CALL POINT DELAYED
ZONE 8 ALARM FROM CALL POINT DELAYED
COINCIDENCE ZONE 1
COINCIDENCE ZONE 2
Intelligent Security & Fire Ltd
COINCIDENCE ZONE 3
COINCIDENCE ZONE 4
COINCIDENCE ZONE 5
COINCIDENCE ZONE 6
COINCIDENCE ZONE 7
COINCIDENCE ZONE 8
FULL ALARM MODE ZONE 1
FULL ALARM MODE ZONE 2
FULL ALARM MODE ZONE 3
FULL ALARM MODE ZONE 4
FULL ALARM MODE ZONE 5
FULL ALARM MODE ZONE 6
FULL ALARM MODE ZONE 7
FULL ALARM MODE ZONE 8
Man-1138_Sigma_CPA_Alarmsense_5 Page 21 of 22
CODE FUNCTION
95
96
97
98
A1*
A2*
A3*
A4*
86*
87*
88*
91
92
93
94
71*
72*
73*
74*
75*
76*
77*
78*
81*
82*
83*
84*
85*
C5
C6
C7
C8
E1*
E2*
E3*
A5*
A6*
A7*
A8*
C1
C2
C3
C4
E4*
E5*
E6*
E7*
ZONE 1 SHORT CIRCUIT INDICATES ALARM
ZONE 2 SHORT CIRCUIT INDICATES ALARM
ZONE 3 SHORT CIRCUIT INDICATES ALARM
ZONE 4 SHORT CIRCUIT INDICATES ALARM
ZONE 5 SHORT CIRCUIT INDICATES ALARM
ZONE 6 SHORT CIRCUIT INDICATES ALARM
ZONE 7 SHORT CIRCUIT INDICATES ALARM
ZONE 8 SHORT CIRCUIT INDICATES ALARM
ZONE 1 NON-LATCHING
ZONE 2 NON-LATCHING
ZONE 3 NON-LATCHING
ZONE 4 NON-LATCHING
ZONE 5 NON-LATCHING
ZONE 6 NON-LATCHING
ZONE 7 NON-LATCHING
ZONE 8 NON-LATCHING
ZONE 1 DOES NOT SOUND ALARMS
ZONE 2 DOES NOT SOUND ALARMS
ZONE 3 DOES NOT SOUND ALARMS
ZONE 4 DOES NOT SOUND ALARMS
ZONE 5 DOES NOT SOUND ALARMS
ZONE 6 DOES NOT SOUND ALARMS
ZONE 7 DOES NOT SOUND ALARMS
ZONE 8 DOES NOT SOUND ALARMS
ZONE 1 ANY ALARM DELAYED
ZONE 2 ANY ALARM DELAYED
ZONE 3 ANY ALARM DELAYED
ZONE 4 ANY ALARM DELAYED
ZONE 5 ANY ALARM DELAYED
ZONE 6 ANY ALARM DELAYED
ZONE 7 ANY ALARM DELAYED
ZONE 8 ANY ALARM DELAYED
ZONE 1 SOUNDERS INHIBITED
ZONE 2 SOUNDERS INHIBITED
ZONE 3 SOUNDERS INHIBITED
ZONE 4 SOUNDERS INHIBITED
ZONE 5 SOUNDERS INHIBITED
ZONE 6 SOUNDERS INHIBITED
ZONE 7 SOUNDERS INHIBITED
ZONE 8 SOUNDERS INHIBITED
ZONE 1 WILL NOT OPERATE FIRE RELAY
ZONE 2 WILL NOT OPERATE FIRE RELAY
ZONE 3 WILL NOT OPERATE FIRE RELAY
ZONE 4 WILL NOT OPERATE FIRE RELAY
ZONE 5 WILL NOT OPERATE FIRE RELAY
ZONE 6 WILL NOT OPERATE FIRE RELAY
ZONE 7 WILL NOT OPERATE FIRE RELAY
E8* ZONE 8 WILL NOT OPERATE FIRE RELAY
Intelligent Security & Fire Ltd
TICK IF THIS
OPTION IS
SET
Man-1138_Sigma_CPA_Alarmsense_5 Page 22 of 22
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 13 17.1 Normal condition
- 13 17.2 Fire condition (sounders set to priority alarm)
- 13 17.3 Fire condition (sounders set to non-priority alarm)
- 13 17.4 Silence/sound alarms
- 13 17.5 Reset
- 13 17.6 Zone fault
- 13 17.7 Sounder fault
- 13 17.8 Power fault
- 13 17.9 System fault
- 13 17.10 Lamp test
- 13 17.11 Disablements
- 14 17.11.3 Activate delays
- 14 17.11.4 Disable fault contact
- 14 17.12 Test mode
- 14 18. Configuration options
- 17 21.1 Mains fail
- 17 21.2 Batt fail
- 17 21.3 CPU fault
- 18 21.4 Aux 24V fault
- 18 21.5 Batt low
- 18 21.6 Earth fault
- 18 21.7 Sys fuse fault
- 18 21.8 S1 fault and S2 fault
- 18 21.9 Comms fault