Sigma CP-A Conventional Fire Control Panel Manual


Add to my manuals
22 Pages

advertisement

Sigma CP-A Conventional Fire Control Panel Manual | Manualzz

Sigma CP-A

Conventional Fire Control Panel

(KA11020M2, KA11040M2, KA11080M2)

Man-1138 Issue 05 January 2013

Intelligent Security & Fire Ltd

Contents

1. Introduction ......................................................................................................................... 4 

2. Safety .................................................................................................................................. 4 

4. Technical specification ........................................................................................................... 5 

5. Control panel fascia............................................................................................................... 7 

6. Connecting to the circuit board .............................................................................................. 8 

7. Software revision number ...................................................................................................... 8 

8. Detection zone wiring ............................................................................................................ 9 

9. Priority/Non-priority alarm settings ......................................................................................... 9 

10. Standard Sounder circuit wiring ......................................................................................... 10 

11. Connection to remote control terminals .............................................................................. 10 

12. Aux 24V DC supply ............................................................................................................ 11 

13. Connection to relay contacts .............................................................................................. 11 

14. Connection to Repeater panels ........................................................................................... 11 

15. Connection to Ancillary boards ........................................................................................... 12 

16. Connection to 8 way Sounder boards ................................................................................. 12 

17. Panel operation ................................................................................................................. 13 

17.1 Normal condition ..................................................................................................................... 13

 

17.2 Fire condition (sounders set to priority alarm) ............................................................................ 13

 

17.3 Fire condition (sounders set to non-priority alarm) ...................................................................... 13

 

17.4 Silence/sound alarms ............................................................................................................... 13

 

17.5 Reset ...................................................................................................................................... 13

 

17.6 Zone fault ............................................................................................................................... 13

 

17.7 Sounder fault .......................................................................................................................... 13

 

17.8 Power fault ............................................................................................................................. 13

 

17.9 System fault ............................................................................................................................ 13

 

17.10 Lamp test .............................................................................................................................. 13

 

17.11 Disablements ......................................................................................................................... 13

 

Intelligent Security & Fire Ltd

17.11.3 Activate delays ........................................................................................................................................ 14

 

 

 

17.11.4 Disable fault contact ............................................................................................................ 14

 

17.12 Test mode ............................................................................................................................. 14

 

18. Configuration options ................................................................................................................. 14

 

19. Watchdog reset switch ...................................................................................................... 17 

20. Processor reset switch ....................................................................................................... 17 

21. Internal indications – troubleshooting ................................................................................. 17 

21.1 Mains fail ................................................................................................................................ 17

 

21.2 Batt fail ................................................................................................................................... 17

 

Man-1138_Sigma_CPA_Alarmsense_5 Page 2 of 22

21.3 CPU fault ................................................................................................................................ 17

 

21.4 Aux 24V fault .......................................................................................................................... 18

 

21.5 Batt low .................................................................................................................................. 18

 

21.6 Earth fault ............................................................................................................................... 18

 

21.7 Sys fuse fault .......................................................................................................................... 18

 

21.8 S1 fault and S2 fault ................................................................................................................ 18

 

21.9 Comms fault ............................................................................................................................ 18

 

22. Power supply .................................................................................................................... 19 

23. Maintenance ..................................................................................................................... 20 

24. Zone designation label ....................................................................................................... 20 

25. Record of Configuration ..................................................................................................... 21 

Intelligent Security & Fire Ltd

Man-1138_Sigma_CPA_Alarmsense_5 Page 3 of 22

1. Introduction

The Sigma CP Alarmsense range consists of a series of conventional fire alarm control panels that comply with European standards EN54-2 and EN54-4, Fire Detection and Fire Alarm systems - Control and Indicating Equipment.

The range consists of 2, 4 and 8 zone control panels.

The Apollo Alarmsense system allows compatible smoke and heat detectors, call points, sounders, sounder/ beacons and alarm relays to be connected to a single pair of wires rather than having two pairs of wires, one for detection devices and one for sounders and relays.

Wiring sounders to the detection circuits eliminates the need to install separate sounder circuit cables and also offers the ability to provide zoned or two stage sounder operation.

The Alarmsense priority/non-priority sounder scheme makes the Alarmsense system ideal for protection of Houses of

Multiple Occupation. With appropriate settings on the sounder and sounder beacon devices it is possible to configure the system such that when an alarm is detected, only the sounder local to the activated detector is operated to alert occupants in that vicinity subject to a configurable alarm verification period. This functionality allows full compliance with

BS5839-6.

All control panels have an integral, mains powered battery charger and power supply.

In addition to the requirements of EN54-2 the control panel has the following facilities:

………….

Test condition

with requirements.

to allow the automatic resetting of zones in alarm for testing purposes. EN54-2 Section 10 option

………….

Delay of the actioning

of fire alarm devices (sounders) so that an alarm may be verified before a premises is evacuated. EN54-2 Section 7.11 option with requirements.

………….

Fire alarm devices

to enable an audible warning to be sounded throughout a premises upon the detection of a fire condition or the operation of a manual call point. EN54-2 Section 7.8 option with requirements.

Also in addition to the requirements of EN54-2, all control panels have voltage free relay contacts for fire and local fire which operate upon fire condition. These are to be used for local control and signalling.

2. Safety

Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work act 1974 to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used.

An article is not regarded as properly used if it is used ‘without regard to any relevant information or advice’ relating to its use made available by the supplier.

This product should be installed, commissioned and maintained by trained service personnel in accordance with the following:

(i)

(ii)

(iii)

(iv)

IEE regulations for electrical equipment in buildings

Codes of practice

Statutory requirements

Any instructions specifically advised by the manufacturer

According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that you make any appropriate information about this product available to anyone concerned with its use.

This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction. As such it

Intelligent Security & Fire Ltd simultaneously shall be incorporated in the fixed wiring.

Switch disconnect devices such as MK Sentry 63A or similar are suitable for this.

Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe.

This control panel is designed for indoor use only and at temperatures between -5

0 a maximum relative humidity of 95%.

C (+/- 3) and +40

0

C (+/- 2) and with

The IP rating for the enclosure is IP30.

Operation outside of these limits may render the equipment unsafe.

Man-1138_Sigma_CPA_Alarmsense_5 Page 4 of 22

3. Mounting

The control panel should be mounted on a dry, flat surface, at eye height to the display and in a level position such that the enclosure is not distorted.

Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all three mounting positions.

It should be positioned in an accessible position as agreed with the end user.

Suitable fixings should be used at all fixing points such that the control panel is securely mounted and is not liable to move once fixed.

The control panel should not be mounted in another enclosure or near sources of excessive heat.

Cables should be connected using suitable cable glands fitted to the knockouts provided. If additional cable entry points are required, all swarf and debris caused by drilling of additional cable entries must be cleared before power is applied to the panel.

4. Technical specification

Table 1 - Electrical specifications

Mains supply

Mains supply fuse

230V AC +10% - 15% (100 Watts maximum)

1.6Amp (F1.6A L250V)

Replace only with similar type

Power supply rating

Maximum ripple current

Output voltage

Imax a

3 Amps total including battery charge

28V +/ 2V

1.5 Volts

18.5 to 29V DC +/- 2%

400 milliamps

Imax b 2.3 Amps

Imin 0.065A

Battery type (Yuasa NP)

See table 2 for capacities

Battery charge voltage

Two 12 Volt sealed lead acid (7Ah maximum)

27.6VDC nominal (temperature compensated)

See table 3

Battery charge current

Battery lead fuse

Battery high impedance warning (Rimax)

Low battery voltage indication

Low battery shut off voltage

Maximum current draw from batteries

R0V output

Dedicated sounder outputs

Zonal sounder outputs

Alarm verification delay

0.7A maximum

20mm, 3.15A glass

1.35 ohms max

21V +/- 2%

18.5V +/- 2%

3 Amps

Fused at with electronic fuse

24V Fused at 500mA with electronic fuse

24V rated at 200mA with electronic fuse

30, 60 or 120 seconds

Replace only with the same type

With main power source off

1.6 Amp total load over all circuits

1.6 Amp total load over all circuits

Configuarble

Fault relay contact rating

Zone quiescent current

30VDC 1A Amp maximum for each

Fire relay contact rating

Local fire relay contact rating

30VDC 1A Amp maximum for each

Maximum ratings not to be exceeded

Intelligent Security & Fire Ltd

30VDC 1A Amp maximum for each

Maximum ratings not to be exceeded

Maximum ratings not to be exceeded

4mA maximum

0.5mm

2

to 2.5mm

2 solid or stranded wire

See table 4 for detector types

Terminal capacity

Number of detectors per zone

Number of sounders per common sounder circuit

Detection circuit end of line

Sounder circuit end of line

No. of detection circuits

SIL, AL, FLT, RST inputs

Cabling

Up to 20

Dependent on type and current consumption

See table 6 for sounder types

3K3 5% ½ Watt resistor

10K 5% ¼ Watt resistor

(see table 2 for number of zones for each model)

Supplied in terminals

Supplied in terminals

Dependent on model

Switched -ve, max resistance 100 Ohms

FP200 or equivalent (maximum capacitance 1uF maximum inductance 1 millihenry)

Metal cable glands must be used

Man-1138_Sigma_CPA_Alarmsense_5 Page 5 of 22

Table 2 - Standby battery capacity required for fully loaded system

Panel model 24 hours standby

48 hours standby

72 hours standby

KA11020 (2 Zones) 3Ah

KA11040 (4 Zones) 3.3Ah

KA11080 (8 Zones) 3.75Ah

4.6Ah 6.2Ah

Table 3 - Battery charge voltage versus temperature

Temperature

0

C

0

10

Battery charge voltage

29.2

28.56

20

30

40

27.99

27.55

27.13

Standby current

0.065

Table 4 - Compatible detectors

Manufactur er

Maximum Number per zone

55000-190 HEAT

(A1R)

Apollo

20

20

20

Table 5 - Compatible detector bases and call points

Max panel alarm current

0.10A

45681-244

55000-894

AlarmSense mounting base Apollo

AlarmSense manual call point

Apollo

Table 6 - Compatible AlarmSense sounder bases and relay

Model Type Manufac turer

Maximum number per zone

45681-510 AlarmSense 20

45681-509

55000-017

AlarmSense Sounder Beacon base

Alarmsense Open Area Sounder

Apollo 20

Apollo 10

55000-018

Beacon

Alarmsense Open Area sounder Apollo 10

55000-035

55000-835

45681-294

Alarmsense Open Area Beacon

AlarmSense Alarm Relay

Sounder base cap white

Apollo

Apollo

Apollo

10

20

N/A

45681-295 Sounder base cap red Apollo N/A

Intelligent Security & Fire Ltd

Table 7 - Compatible sounders for the two common sounder circuits

Model Type

BANSHEE ELECTRONIC

WAFER ELECTRONIC

FIRECRYER RANGE ELECTRONIC VOICE

KOBELL MOTORISED

ASKARI ELECTRONIC

ROSHNI ELECTRONIC

SQUASHNI ELECTRONIC

SYMPHONI ELECTRONIC

ELECTRONIC BELL ELECTRONIC

CFB BELLS

B6 AND B8 BELLS

MOTORISED

SOLENOID

VIMPEX

VIMPEX

VIMPEX

VIMPEX

FULLEON

FULLEON

FULLEON

Standard polarised type only

Standard polarised type only

Standard polarised type only

Man-1138_Sigma_CPA_Alarmsense_5 Page 6 of 22

5. Control panel fascia

In addition to the mandatory controls and indications required by the EN54-2 standard, two, seven segment, LED displays and MODE, SELECT and ENTER buttons are provided to allow easy entry and storage of codes to configure the control panel to suit the requirements of the installation.

Removing the fascia

Before the fascia can be removed it will be necessary to unplug the three way terminal block on the left hand side of the

PCB.

The fascia of the control panel is held in place by countersunk screws. Undo the two screws and lift the fascia gently away from the box towards you.

With the fascia removed there is much more room inside the panel for making off and dressing cables.

When cabling work is complete the fascia can be re-fitted with the two countersunk screws and the red, green/yellow and black wires re-connected to the three way terminal block.

It is most important that the polarity of the red and black wires is observed as wrong connection of these will damage the control panel.

Fire Alarm Control

Model: KA11080M2

Intelligent Security & Fire Ltd

Man-1138_Sigma_CPA_Alarmsense_5 Page 7 of 22

6. Connecting to the circuit board

All connections for field wiring are to a single row of terminals along the top of the circuit board.

The connections for the power cables are to a pluggable terminal block, which may be pulled off of the board to remove the plate/PCB assembly. Remove this pluggable terminal only with mains power off.

Shielded fire alarm cable such as FP200 and metal cable glands must be used for all connections to the panel.

The resistance of any core of any cable must not exceed 25 ohms. The shield of the cable must be bonded securely to the enclosure via a metal gland.

Wiring should enter the enclosure at the top of the panel using the knockouts provided and be formed tidily to the appropriate terminals leaving only enough wire to ensure that there is no strain on the PCB.

Terminals are capable of accepting wires of up to 2.5mm

2

.

Terminal designations

Wiring must not go across the front of the circuit board plate or between the plate and the circuit board.

If cable entries need to be in positions other than at the knockouts provided, wiring must be fed behind and well away from the surface of the circuit board.

The space at the bottom of the enclosure is largely occupied by the standby batteries, so this must be borne in mind when considering cable entries.

CORRECT

INCORRECT INCORRECT

7. Software revision number

C 7

D 4

IC 10

X1

C6

C 27

C 5 C 4

VDR4

F 2

RL3

D 35

C 68

+

D 3

C 75

R 13

D 34

+

C 67

C 3 C 2 C 1

RL 2

VDR3

C 97 C 93

D 2

D 33

C 74

R 7

+

C 66

J 1

C 41

C 23 C 22 C 21 C 20 C127 C128 C 35 C 36 C 33 C 34 C 60 C 61

D 1

C 73

R 1

D 32

C 65

+

R 129

TR 24

R 87

D 16

R 104

D 15

R 85

R 86

D 14

R 130

D 13

R 131

R 132

D 23

R 133

D 22

R 78

R 135

R 134

D 30

VDR1

F 10

D 12

IC 2

IC 1

TR 25

+

TR9 D 11

C 24

D 9

+

TR 28

R 126

C 82

D 10

IC 4

IC 5

C 25

+

Z 14

F 11

FB21

TR47

TR 23

X2

C 106 C 107

+

FB20

C 51 TR 19

Z 11

New features may be added to fire control panels from time to time and when this is done the operating software of the unit is updated. The software revision can be located on the main processor by removing the plate holding the PCB from the enclosure and turning it over. The software version will have a number such as “SigXX.hex” and it is this number, which will determine

REG1

VR1

C 56

Intelligent Security & Fire Ltd

L 1 which features the panel has installed and its compatibility with Sigma CP ancillary board, sounders boards, repeaters etc.

SW2 T 3

SW4

SW1

LED17 LED35

D 1008 ISSUE 06

LED4

SERIAL NUMBER

+

R 75

R 76

TH1

PANEL SOFTWARE VERSION LABEL

Man-1138_Sigma_CPA_Alarmsense_5 Page 8 of 22

8. Detection zone wiring

The detection zones provide a nominal 12V DC to power conventional Alarmsense detectors and call points as listed in the compatibility tables on page 6.

Note:

Only Alarmsense detection devices and call points are compatible.

Kentec K14060 LCMU end of line monitoring devices are not compatible with Alarmsense panels.

To activate Alarmsense sounders connected to the zone wiring, the voltage is raised to 24V DC.

The wiring is monitored for open and short circuit fault conditions by removing the 3K3 end of line monitoring resistors that are supplied fitted to the control panels’ terminals and placing them across the last device that is wired to the zone circuit.

Detection zone circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuits to work correctly.

Alarmsense sounders must also be wired across the detection zone.

Alarmsense sounder and sounder beacon bases can be set as priority or non-priority via switch 1 on the DIL switch in the base unit. When a sounder or sounder beacon base is set to non-priority, activation of a detector connected to the base will not cause the panel to enter the alarm condition and will only activate the sounder to which the detector is connected. After the configured alarm verification delay (30 seconds, 60 seconds or 120 seconds) the panel will reset the activated detector. If smoke is no longer present the system will revert to normal quiescent condition. If smoke is still present and the detector activates again a fire condition will be indicated at the control panel and all sounders will operate.

This functionality is particularly well suited to residential buildings such as Houses of Multiple Occupation because the alarm is restricted to the local area before it is verified thus minimising disruption due to false alarms. This allows compliance with the requirements of BS5839 part 6.

Man-1138_Sigma_CPA_Alarmsense_5 Page 9 of 22

10. Standard Sounder circuit wiring

In addition to the ability to operate Alarmsense sounder and sounder beacons from the detection circuit, the control panel also has two standard sounder outputs which provide 24V DC upon any alarm. All sounders connected to these outputs must be of the polarised type. If non-polarised sounders are used, the control panel will permanently show a fault condition. See table 7 for a list of compatible sounder types.

Sounder circuits are monitored for open and short circuit faults by placing the 10K end of line monitoring resistor that is supplied fitted to the terminals in the control panel across the last sounder device on the circuit.

Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuit to work correctly.

A maximum of 1.6 Amps is available for powering sounders including those connected to the detection zones with a maximum load of 0.41 Amps on any one of the standard sounder circuits described here.

The sounder circuits are protected by 500 milliamp fuses.

POLARISED

SOUNDER

+

IN

+

OUT

_ _

IN OUT

POLARISED

SOUNDER

+

IN

+

OUT

_ _

IN OUT

10K end of line resistor

11. Connection to remote control terminals

Some functions of the control panel can be controlled externally from the panel if required. Operation of these inputs

must be restricted by an access level 2 control as defined in EN54-2 These are abbreviated at the terminals block

as follows: a) Remote 0 V supply - ROV b) Silence Alarm – SIL c) Sound Alarm – AL d) Fault – FLT e) Reset – RST

To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open switch or contact and via a resistance of no greater than 100 ohms.

Intelligent Security & Fire Ltd

Man-1138_Sigma_CPA_Alarmsense_5 Page 10 of 22

12. Aux 24V DC supply

An auxiliary 24V DC supply is provided to enable local signalling or control of ancillary systems such as door release controllers.

The terminals for the Aux 24V supply are labelled Aux 24V and ROV. The ROV terminal is the negative terminal and is the same terminal that should be used to switch the remote control terminals.

It is possible to make the ROV terminal pulsing so that by connecting it to the AL terminal via a remote, volt free contact, it can be used to pulse the dedicated sounder circuits in response to a signal from another system for example to give an alert. See programming code 24.

The supply is fitted with an electronic self resetting fuse to protect the control panel’s 24V supply in the event of a wiring fault.

Any standing load on the Aux 24V supply must be taken into account when calculating battery standby times as standby time will be significantly affected by even modest standing loads. It is recommended that the Aux24V output is not used to power standing loads and not used to supply loads of greater than 300 milliamps

Where the Aux 24V supply is used to power electromechanical devices such as relays or door retainers it is imperative that a suppression diode is fitted across the coil of the electromechanical device to prevent the generation of high voltage transients back to the control panels power supply.

The Aux 24V DC Supply is not suitable for powering Sigma CP sounder boards, a separate power supply should be used for these.

13. Connection to relay contacts

Volt free changeover relay contacts are provided for local control and signalling if required. These contacts are rated for switching signalling circuits only and the maximum ratings listed in table 1 on page 5 should not be exceeded under any circumstances.

Fault relay

The fault relay is normally energised and will de-energise upon any fault condition including total loss of power.

Local fire relay

The local fire relay will energise upon activation of a fire condition on any of the zones or pressing of the sound alarm button on the front panel. The relay will remain activated until the alarm is silenced or the panel is reset. This relay will not operate upon activation of the remote AL input or when a fire condition is triggered on a zone that is in test mode.

Fire relay

The fire relay will energise upon activation of a fire condition on any of the zones. The relay will remain activated until the control panel is reset. This relay will

NOT

operate upon activation of the remote AL input. Individual zones can be configured not to operate the Fire relay by setting configuration options E1 to E8.

14. Connection to Repeater panels

Repeater panels connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel

PCB. Up to 7 repeaters may be connected and each repeater has terminals for the incoming cables and outgoing cables.

All except the last ancillary board, sounder board or repeater panel connected to the cable must have the jumper links J2 removed.

Set the repeater address using the DIP switch (SW7); ensure no two repeaters share the same address.

Apply power to main panel first and then all repeater panels. Turn on the Enable Control keyswitch and set the Write

Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a few seconds and the

Turn the write enable switch off, then on again and then press the ENTER button to accept each repeater that has been switch on the main panel.

Intelligent Security & Fire Ltd found. When all repeaters have been added, set the main panel Write Enable switch to off. Press the Watchdog reset

All repeaters are now configured and the main control panel will report a fault if any repeaters that have been accepted become faulty or go off line.

For full details of commissioning procedures for repeaters see the Sigma CP Repeater Operation and maintenance manual.

Man-1138_Sigma_CPA_Alarmsense_5 Page 11 of 22

15. Connection to Ancillary boards

Ancillary boards connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel

PCB. Up to 7 Ancillary boards may be connected and each board has terminals for the incoming cables and outgoing cables. All except the last ancillary board, sounder board or repeater panel connected to the cable must have the jumper links J2 removed.

Set the ancillary board address using the DIP switch (SW7); ensure no two ancillary boards share the same address.

Apply power to main panel first and then all ancillary boards. Turn on the Enable Control keyswitch and set the Write

Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a few seconds and the main panel will show the addresses of the ancillary boards that were found on the display for instance 01 indicates that an ancillary board at address 1 has been found.

Turn the write enable switch off, then on again and then press the ENTER button to accept each ancillary board that has been found. When all ancillary boards have been added, set the main panel Write Enable switch to off. Press the

Watchdog reset switch on the main panel.

All ancillary boards are now configured and the main control panel will report a fault if any ancillary boards that have been accepted become faulty or go off line.

For full details of commissioning procedures for ancillary boards see the Sigma CP Ancillary board Operation and maintenance manual.

16. Connection to 8 way Sounder boards

Sounder boards connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel

PCB. Up to 7 Sounder boards may be connected and each board has terminals for the incoming cables and outgoing cables. All except the last Ancillary board, Sounder board or Repeater connected to the cable must have the jumper links

J2 removed. Sounder boards must be powered from a separate power supply which is suitably rated to supply the full sounder load that is connected. This can be up to 4 Amps if all circuits are fully loaded.

Set the sounder board address using the DIP switch (SW7); ensure no two sounder boards share the same address.

Apply power to main panel first and then all sounder boards. Turn on the Enable Control keyswitch and set the Write

Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a few seconds and the main panel will show the addresses of the sounder boards that were found on the display for instance b1 indicates that a sounder board at address 1 has been found.

Turn the write enable switch off, then on again and then press the ENTER button to accept each sounder board that has been found. When all sounder boards have been added, set the main panel Write Enable switch to off. Press the

Watchdog reset switch on the main panel.

All sounder boards are now configured and the main control panel will report a fault if any sounder boards that have been accepted become faulty or go off line.

For full details of commissioning procedures for Sounder boards see the Sigma CP Sounder board Operation and maintenance manual.

Intelligent Security & Fire Ltd

Man-1138_Sigma_CPA_Alarmsense_5 Page 12 of 22

17. Panel operation

17.1 Normal condition

Under normal conditions, control panels will have only the green,

17.2 Fire condition (sounders set to priority alarm)

Power On

LED lit.

Upon receipt of a fire condition by activation of a detector or call point, the zonal

Fire

Common Fire

indicator will light and the

indicators will flash at around 2Hz. The zonal indicators can be used to differentiate call point and detector activation by setting configuration option 28. If option 28 is set, and a call point is operated, the zonal indicator will flash and if a detector is operated it will illuminate continuously.

The internal fire and local fire relays will also operate and signal any systems to which they are connected.

Any sounders connected to the detection zones or standard sounder circuits will operate in common, zonal or 2-stage mode as selected by configuration options 10 to 12 (see table 8).

17.3 Fire condition (sounders set to non-priority alarm)

Upon receipt of a fire condition by activation of a detector, the sounder or sounder beacon to which the detector is connected will sound. After two minutes, the control panel will reset the detector. If the detector is successfully reset the panel will revert to the Normal condition. If the detector re-enters the alarm state, sounders and relays connected to the detection zones will operate in common, zoned or two stage alarm mode depending on the setting of configuration options 10 to 12 (see table 8), the internal fire and local fire relays will operate and the two standard 24V sounder outputs will operate.

17.4 Silence/sound alarms

The

Silence/Sound alarm

be inserted.

button can only be operated at access level two which means that the

Enable Control

To silence the sounders, insert the Enable Control key and press the Silence/Sound alarm button.

key must

When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state.

Pressing the again.

Silence/Sound alarm

whilst the control panel is in this silenced condition, will cause the sounders to operate

The sounders can be toggled on and off with the

Silence/Sound alarm

button as required.

17.5 Reset

To reset the panel, insert the Enable key then press the Reset button.

17.6 Zone fault

Removal of a detector from its base or a fault on any of the zone wiring will cause the

Fault

LED and

Zone Fault

LEDs to light indicating the zone in which the fault has occurred. All devices that are connected beyond the point where a detector is removed from its base will continue to operate.

17.7 Sounder fault

A fault on the wiring to detection zones and sounder circuits will cause the indicating a fault on the wiring to the sounder circuits.

Fault

and

Sounder Fault

LEDs to light

17.8 Power fault

Failure of the mains power, disconnection of the standby battery or high impedance in the charging circuit will cause the

Fault

and

Power Fault

LEDs to light indicating an abnormality in the power supply to the control panel.

17.9 System fault

Intelligent Security & Fire Ltd

The

System Fault

LED will light if the configuration memory has not been set or has become corrupt.

17.10 Lamp test

All LED indicators can be tested at any time by pressing the be inserted to test the indicators.

The buzzer can be silenced at any time by pressing the inserted to silence the buzzer.

Lamp Test

button. The

Enable Control

key does not need to

Buzzer Silence

button. The enable key does not need to be

17.11 Disablements

It is possible to disable parts of the system. This may be required if there are works going on in a building which may cause the fire alarm system to operate in error.

17.11.1 Disable zones

To disable zones, the

Enable Control

key should be inserted and the mode button pressed until “d” appears in the first of the two seven segment LED displays. The

Select

button should then be pressed to select the number of the zone which

Man-1138_Sigma_CPA_Alarmsense_5 Page 13 of 22

is to be disabled in the second of the two seven segment displays. Once the desired zone is displayed, the enter button should be pressed to confirm the disablement.

The

Disable

LED will light and the

Zone Fault

LED will light for each disabled zone.

When is a zone is disabled, all detectors, call points and sounders in the zone will be disabled.

A disabled zone is shown on the seven segment display as ‘dx.’ (where x is the zone number from 1-8). If the ‘x’ is flashing, it means that there are activated devices in that zone and re-enabling it will put the control panel into the fire condition.

The panel should be Reset before enabling any zone with a flashing “dx.” Indication.

Note: The flashing “dx” indicator will only appear on panels produced after January 2013.

17.11.2 Disable sounders

To disable sounder outputs, press the mode button to select “db” on the seven segment display. Pressing enter will disable all sounders and cause the

Disable

and

Sounder Fault

LEDs to light.

17.11.3 Activate delays

To activate delays on zones as set in configuration options 31 to 48, press the mode button until Ad appears on the seven segment LED display. When the enter button is pressed any zones that are set as delayed will have their alarm outputs delayed by the time set in configuration options 00 to 09.

17.11.4 Disable fault contact

The fault relay can be disabled by selecting configuration option 22.

17.12 Test mode

Fire alarm systems must be tested regularly to ensure that they are functioning correctly. The Sigma CP range of panels enable the system to be tested single handed by using a test mode. When in test mode, activation of a fire alarm will be automatically reset after a few seconds to eliminate the need to return to the control panel to reset after every activation.

Test mode is entered in a similar way to disablements. With the

“t” appears in the first of the seven segment displays. Then press the appears. Pressing the in test mode.

Enter

button will cause the

Test

and

Enable Control

Zone Fault

key inserted, press the

Mode

button until

Select

button until the required zone number

LEDs to illuminate indicating the zones which are

Disablements and zone tests are cleared by repeating the sequence that is used to select them, i.e. the "db" function

(for example) toggles between sounders disabled and sounders enabled.

18. Configuration options

The panel range has many configuration options which can be set at the time of commissioning to suit the requirements of the installation. These options are normally set once and will rarely need to change. The configuration options are only available at access level 3. To get to access level 3, CAREFULLY slide the Write Enable switch (located behind the aperture in the panel plate) to the right position using a small screwdriver or similar. When the panel is at access level 3, the buzzer will “pip” three times every few seconds as an indication that it is at this access level.

Intelligent Security & Fire Ltd

Configuration options are simple to enter using the codes in table 8 below. When the control panel is at access level 3, the sub-text of the

Mode

and

Select

buttons is used to enter a number using tens (+10) and units (+1).

When the required code number is displayed, pressing the enter button will cause the dot on the units, seven segment display to flash. This indicates that a configuration option has been set.

To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 to A8, C1 to

C8 and E1 to E8 and those with a flashing dot indicate which options have been set.

Man-1138_Sigma_CPA_Alarmsense_5 Page 14 of 22

ZONE 1 - ALARM

FROM DETECTOR

DELAYED

DOT

FLASHING

ZONE 1 - ALARM

FROM DETECTOR

NOT DELAYED

NO DOT

Table 8 – Configuration codes

COD

E

FUNCTION COMMENTS

L0 NON-PRIORITY ALARM CONFORMATION TIME

30S

Sets time before detector resets and checks if smoke still present at detector.

L1 NON-PRIORITY ALARM CONFORMATION TIME

60S

L2 NON-PRIORITY ALARM CONFORMATION TIME

120S

01

02

03

SOUNDER DELAY TIME = 1 MINUTE

SOUNDER DELAY TIME = 2 MINUTES

SOUNDER DELAY TIME = 3 MINUTES

04 SOUNDER DELAY TIME = 4 MINUTES

05 SOUNDER DELAY TIME = 5 MINUTES

06 SOUNDER DELAY TIME = 6 MINUTES

07 SOUNDER DELAY TIME = 7 MINUTES

Sets the time delay before sounders operate in combination with configuration codes 31 to 48 and access level 2 function AD.

08 SOUNDER DELAY TIME = 8 MINUTES

09 SOUNDER DELAY TIME = 9 MINUTES

10 COMMON ALARM MODE (default)

11 TWO-STAGE ALARM MODE

12 ZONED ALARM MODE

21* DISABLE FIRE BUZZER

22* DISABLE FAULT OUTPUT

All sounders operate upon any fire condition

Continuous sounders in activated zone, pulsing elsewhere

Only sounders connected to zone in alarm operate

Buzzer will not operate on fire condition

Fault relay will not operate except upon total power failure

23 DISABLE EARTH FAULT MONITORING Connection of fire alarm wiring to earth will not announce a fault

24

Intelligent Security & Fire Ltd

26 DISABLE FIRE OUTPUT Fire relay will not operate upon any alarm

27 REMOVE AUX 24 UPON PANEL RESET

28 INDICATE CALL POINT ACTIVATION

29 DO NOT RE-SOUND ALARMS FROM ANOTHER

ZONE

31 ZONE 1 ALARM FROM DETECTOR DELAYED

32 ZONE 2 ALARM FROM DETECTOR DELAYED

33 ZONE 3 ALARM FROM DETECTOR DELAYED

34 ZONE 4 ALARM FROM DETECTOR DELAYED

35 ZONE 5 ALARM FROM DETECTOR DELAYED

24V supply switches off for about 5 seconds when panel is reset

Activation of an AlarmSense call point is indicated by a flashing zone indicator and “Pu” on the 7 segment display.

Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display.

Silenced sounders will not re-sound upon further zone activations

Sounder outputs will be delayed by time set at options

0-9 when selected zone(s) triggered by detector only.

Note: Access level 2 function Ad must be set for this to take effect.

Man-1138_Sigma_CPA_Alarmsense_5 Page 15 of 22

36 ZONE 6 ALARM FROM DETECTOR DELAYED

37 ZONE 7 ALARM FROM DETECTOR DELAYED

38 ZONE 8 ALARM FROM DETECTOR DELAYED

41 ZONE 1 ALARM FROM CALL POINT DELAYED

42 ZONE 2 ALARM FROM CALL POINT DELAYED

43 ZONE 3 ALARM FROM CALL POINT DELAYED

44 ZONE 4 ALARM FROM CALL POINT DELAYED

45 ZONE 5 ALARM FROM CALL POINT DELAYED

46 ZONE 6 ALARM FROM CALL POINT DELAYED

47 ZONE 7 ALARM FROM CALL POINT DELAYED

48 ZONE 8 ALARM FROM CALL POINT DELAYED

51 COINCIDENCE ZONE 1

52 COINCIDENCE ZONE 2

53 COINCIDENCE ZONE 3

Sounder outputs will be delayed by time set at options

0-9 when selected zone(s) triggered by call point only.

Note access level 2 function Ad must be set for this to take effect.

Zone contributes to ancillary board coincidence O/P. Any number of zones can be selected to contribute.

54 COINCIDENCE ZONE 4

55 COINCIDENCE ZONE 5

56 COINCIDENCE ZONE 6

57 COINCIDENCE ZONE 7

58 COINCIDENCE ZONE 8

61

62

FULL ALARM MODE ZONE 1

FULL ALARM MODE ZONE 2

71* ZONE 1 SHORT CIRCUIT INDICATES ALARM

72* ZONE 2 SHORT CIRCUIT INDICATES ALARM

73* ZONE 3 SHORT CIRCUIT INDICATES ALARM

74* ZONE 4 SHORT CIRCUIT INDICATES ALARM

When this option is set, any detector activating on the zone will put the panel into alarm. I.e. Non-priority setting on sounder or sounder beacon bases will be ignored.

63 FULL ALARM MODE ZONE 3

64 FULL ALARM MODE ZONE 4

65 FULL ALARM MODE ZONE 5

66 FULL ALARM MODE ZONE 6

67 FULL ALARM MODE ZONE 7

68 FULL ALARM MODE ZONE 8

COD

E

FUNCTION COMMENTS

Changes the trigger threshold of the zone so that the control panel can be used on older systems that had no short circuit monitoring. (Not for use if Alarmsense devices are connected to the zone)

75* ZONE 5 SHORT CIRCUIT INDICATES ALARM

76* ZONE 6 SHORT CIRCUIT INDICATES ALARM

77* ZONE 7 SHORT CIRCUIT INDICATES ALARM

78* ZONE 8 SHORT CIRCUIT INDICATES ALARM

81* ZONE 1 NON-LATCHING Renders the zone self-resetting so that it can be used to receive signals from

82* ZONE 2 NON-LATCHING

83* ZONE 3 NON-LATCHING

84* ZONE 4 NON-LATCHING

85* ZONE 5 NON-LATCHING

86* ZONE 6 NON-LATCHING

87*

88*

Intelligent Security & Fire Ltd other systems and will reset when the input is removed.

Note: It can take up to 20 seconds for zone to reset itself when sounders are operating.

(Not for use if Alarmsense devices are connected to the zone)

91 ZONE 1 DOES NOT SOUND ALARMS

92 ZONE 2 DOES NOT SOUND ALARMS

Prevents the zone from operating any sounders whether connected the two common sounder outputs or to detection zones.

93 ZONE 3 DOES NOT SOUND ALARMS

94 ZONE 4 DOES NOT SOUND ALARMS

95 ZONE 5 DOES NOT SOUND ALARMS

96 ZONE 6 DOES NOT SOUND ALARMS

97 ZONE 7 DOES NOT SOUND ALARMS

98 ZONE 8 DOES NOT SOUND ALARMS

A1* ZONE 1 ANY ALARM DELAYED

A2* ZONE 2 ANY ALARM DELAYED

A3* ZONE 3 ANY ALARM DELAYED

A4* ZONE 4 ANY ALARM DELAYED

A5* ZONE 5 ANY ALARM DELAYED

Zone needs to be triggered for 30 seconds continuously before an alarm is generated.

(Detectors fitted to Alarmsense non-priority sounders are not delayed)

Man-1138_Sigma_CPA_Alarmsense_5 Page 16 of 22

A6* ZONE 6 ANY ALARM DELAYED

A7* ZONE 7 ANY ALARM DELAYED

A8* ZONE 8 ANY ALARM DELAYED

C1 ZONE 1 SOUNDERS INHIBITED

C2 ZONE 2 SOUNDERS INHIBITED

C3 ZONE 3 SOUNDERS INHIBITED

C4 ZONE 4 SOUNDERS INHIBITED

C5 ZONE 5 SOUNDERS INHIBITED

C6 ZONE 6 SOUNDERS INHIBITED

C7 ZONE 7 SOUNDERS INHIBITED

C8 ZONE 8 SOUNDERS INHIBITED

E1* ZONE 1 WILL NOT OPERTATE FIRE RELAY

E2* ZONE 2 WILL NOT OPERTATE FIRE RELAY

E3* ZONE 3 WILL NOT OPERTATE FIRE RELAY

Enables individual zones to be configured not to operate zonal sounders.

E4* ZONE 4 WILL NOT OPERTATE FIRE RELAY

E5* ZONE 5 WILL NOT OPERTATE FIRE RELAY

E6* ZONE 6 WILL NOT OPERTATE FIRE RELAY

E7* ZONE 7 WILL NOT OPERTATE FIRE RELAY

E8* ZONE 8 WILL NOT OPERTATE FIRE RELAY

Enables individual zones to be selected to not operate the fire relay. This is sometimes combined with the nonlatching function to prevent ring around on interconnected panels.

NOTE: Setting the options marked with asterisks does not comply with EN54-2

Once the required configuration options have been set, the Write enable switch must be returned to its normal position to the right. The General fault indicator will remain lit if the Write enable switch is not turned off.

19. Watchdog reset switch

If for any reason the microprocessor in the control panel fails to carry out its operation correctly it will attempt to restart itself. This process is called a “watchdog” and the control panel must record and indicate these events.

If a watchdog event occurs, the control panel will show the FAULT and SYSTEM FAULT LEDs on the front panel, the CPU fault LED inside the panel.

This fault can only be cleared by pressing the WATCHDOG RESET button on the PCB inside the control panel. The control panel buzzer cannot be silenced and will continue to sound until the watchdog activation is reset.

20. Processor reset switch

Once started, the microprocessor controlling the panel should continue to run continuously without interruption. If the microprocessor fails to run correctly it can be reset by pressing the PROCESSOR RESET button on the PCB inside the control panel.

This should not normally be necessary but should be done as a matter of course if the system is behaving abnormally.

The system should resume normal operation within a couple of seconds of pressing the processor reset button.

21. Internal indications – troubleshooting

To assist in identifying fault conditions, which are not detailed on the front of the control panel, a number of internal indicators are visible with the front cover removed as follows:

21.1 Mains fail

If there is not a power cut, check the panels mains fuse.

21.2 Batt fail

Intelligent Security & Fire Ltd

Indicates that the standby battery has become disconnected or that the charging circuit of the control panel has a high resistance or has failed. Check that both batteries are connected and linked together. Test battery. Disconnect battery and ensure that 28 Volts can be measured on battery charger leads.

21.3 CPU fault

Indicates that the central processor unit has failed to correctly execute code and has been re-started by the system watchdog. The watchdog reset switch must be pressed to clear the CPU fault condition.

Press watchdog reset. If system does not return to normal then the panel is probably damaged and needs the circuit board replacing. (See maintenance section).

Man-1138_Sigma_CPA_Alarmsense_5 Page 17 of 22

21.4 Aux 24V fault

The Aux 24V and R0V terminals provide a 500 milliamp, 24V DC power supply for power fire alarm ancillary equipment.

This LED indicates that fuse protecting the R0V output has operated and the rating of this output has been exceeded.

The fuse is a self resetting type and the supply will resume when the fault condition is removed.

21.5 Batt low

Illuminates when the system is running on batteries and the battery voltage is lower than 21V +/-2% (the minimum battery voltage).

21.6 Earth fault

Indicates that part of the system wiring is connected to earth. Remove all system wiring and re-connect cables one at a time until the earth fault returns. This will indicate which cable the earth fault is present on.

21.7 Sys fuse fault

Indicates that the total power rating of the power supply has been exceeded and that the system fuse has come into operation. Remove and review all loads and re-connect one at a time until over rated circuit trips fuse to identify troublesome circuit.

21.8 S1 fault and S2 fault

Indicates a short or open circuit on the standard 24V DC sounder outputs. Remove wiring and refit end of line resistors.

Check sounder circuit wiring.

21.9 Comms fault

Indicates that communication has been lost with a repeater panel or Ancillary board. Check for comms fault at all repeaters and ancillary boards to identify the source of the problem.

Intelligent Security & Fire Ltd

Man-1138_Sigma_CPA_Alarmsense_5 Page 18 of 22

22. Power supply

The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply, which connects to the fused terminal block labelled “230V”.

The fused terminal block contains a 20mm, F1.6A L250V fuse which should only be replaced with a similar type.

The output voltage of the power supply is 28V DC +/- 2V and the total current rating including a maximum 0.7A for battery charging is 3 Amps. Fuse F12 mounted on the circuit board is a self-resetting electronic fuse rated at 4 Amps.

The incoming mains cable should be routed well away from other lower voltage wiring by a distance of at least 50mm.

Mains wiring should include an earth conductor, which is securely bonded to the building earth and should enter the enclosure as close as possible to the mains terminal block. Mains wires should be kept very short inside the enclosure and secured together close to the mains terminal block with a cable tie.

The control panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity (see table 2 for battery size required for each model).

The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps.

Battery leads are supplied wired to the PCB along with a link to connect the two batteries in series. The PCB is fitted with a 20mm, 3.15A T1 glass fuse (F13) in the battery charging circuit, which must only be replaced with one of the same type.

It is most important that the polarity of the batteries is carefully observed when connecting.

When the batteries are discharged to a level at which a low battery indication is given, the BATT FAIL indicator will also be lit.

Wrongly connected batteries could cause damage to the control panel.

MAINS

TERMINAL

KEEP MAINS WIRES AS SHORT AS POSSIBLE

AND SECURE ALL THREE WIRES CLOSE TO

THE TERMINAL BLOCK WITH A CABLE TIE

L

N

E

N

L

+

RED BATTERY

LEAD TO +

TERMINAL

+

GREY LINK

-

BLACK BATTERY

LEAD TO -

TERMINAL

Intelligent Security & Fire Ltd

Man-1138_Sigma_CPA_Alarmsense_5 Page 19 of 22

23. Maintenance

The control panels do not require any specific maintenance but should the control panel become dirty it can be wiped over with a damp cloth and should then be dried with a dry, lint free cloth. Detergents or solvents should not be used to clean the panel and care must be taken that water does not enter the enclosure.

The control panel contains sealed lead acid batteries to provide standby power in the event of a mains failure. The batteries have a life expectancy of around 4 years. The control panel monitors the condition of the batteries and will announce a fault if the battery impedance becomes too high.

It is recommended that these batteries be tested in accordance with the battery manufacturer’s recommendations annually to determine their suitability for continued standby applications.

Routine testing of the fire alarm system in accordance with BS5839: Part 1: 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately.

Should the control panel become faulty the complete electronic assembly can be replaced.

To do this, any configured options should be noted then both mains and battery power should be removed before the work is started.

The field wiring should be carefully labelled and removed from the terminals.

The PCB can now be taken out of the panel by removing the 2 M4 screws holding the plate in position.

Fitting the new PCB is the reverse of the procedure for removing the board.

24. Zone designation label

The control panels are supplied with a zone designation label onto which zone designations can be written.

This enables each zone to be given a text description allowing easier identification of any zones showing an alarm, fault or disablement condition.

Intelligent Security & Fire Ltd

Man-1138_Sigma_CPA_Alarmsense_5 Page 20 of 22

25. Record of Configuration

06

07

08

09

10

02

03

04

05

11

L0

L1

L2

00

01

Use the table below to record the configuration codes that have been set on the control panel for future reference. Place a tick in the grey band for any configuration options that are set.

It is recommended that a copy of this table is left with the control panel under the supervision of the person responsible for the fire detection system.

CODE FUNCTION TICK IF THIS

OPTION IS

SET

NON-PRIORITY ALARM CONFORMATION TIME 30S

NON-PRIORITY ALARM CONFORMATION TIME 60S

NON-PRIORITY ALARM CONFORMATION TIME 120S

SOUNDER DELAY TIME = 30 SECONDS

SOUNDER DELAY TIME = 1 MINUTE

SOUNDER DELAY TIME = 2 MINUTES

SOUNDER DELAY TIME = 3 MINUTES

SOUNDER DELAY TIME = 4 MINUTES

SOUNDER DELAY TIME = 5 MINUTES

SOUNDER DELAY TIME = 6 MINUTES

SOUNDER DELAY TIME = 7 MINUTES

SOUNDER DELAY TIME = 8 MINUTES

SOUNDER DELAY TIME = 9 MINUTES

COMMON ALARM MODE (default)

TWO-STAGE ALARM MODE

21* DISABLE FIRE BUZZER

54

55

56

57

51

52

53

44

45

46

47

48

41

42

43

35

36

37

38

31

32

33

34

23

24

26

27

28

29

63

64

65

66

67

58

61

62

68

DISABLE EARTH FAULT MONITORING

PULSED REMOTE CONTROL OUTPUT

DISABLE FIRE OUTPUT

REMOVE AUX 24 UPON PANEL RESET

INDICATE CALL POINT ACTIVATION

DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE

ZONE 1 ALARM FROM DETECTOR DELAYED

ZONE 2 ALARM FROM DETECTOR DELAYED

ZONE 3 ALARM FROM DETECTOR DELAYED

ZONE 4 ALARM FROM DETECTOR DELAYED

ZONE 5 ALARM FROM DETECTOR DELAYED

ZONE 6 ALARM FROM DETECTOR DELAYED

ZONE 7 ALARM FROM DETECTOR DELAYED

ZONE 8 ALARM FROM DETECTOR DELAYED

ZONE 1 ALARM FROM CALL POINT DELAYED

ZONE 2 ALARM FROM CALL POINT DELAYED

ZONE 3 ALARM FROM CALL POINT DELAYED

ZONE 4 ALARM FROM CALL POINT DELAYED

ZONE 5 ALARM FROM CALL POINT DELAYED

ZONE 6 ALARM FROM CALL POINT DELAYED

ZONE 7 ALARM FROM CALL POINT DELAYED

ZONE 8 ALARM FROM CALL POINT DELAYED

COINCIDENCE ZONE 1

COINCIDENCE ZONE 2

Intelligent Security & Fire Ltd

COINCIDENCE ZONE 3

COINCIDENCE ZONE 4

COINCIDENCE ZONE 5

COINCIDENCE ZONE 6

COINCIDENCE ZONE 7

COINCIDENCE ZONE 8

FULL ALARM MODE ZONE 1

FULL ALARM MODE ZONE 2

FULL ALARM MODE ZONE 3

FULL ALARM MODE ZONE 4

FULL ALARM MODE ZONE 5

FULL ALARM MODE ZONE 6

FULL ALARM MODE ZONE 7

FULL ALARM MODE ZONE 8

Man-1138_Sigma_CPA_Alarmsense_5 Page 21 of 22

CODE FUNCTION

95

96

97

98

A1*

A2*

A3*

A4*

86*

87*

88*

91

92

93

94

71*

72*

73*

74*

75*

76*

77*

78*

81*

82*

83*

84*

85*

C5

C6

C7

C8

E1*

E2*

E3*

A5*

A6*

A7*

A8*

C1

C2

C3

C4

E4*

E5*

E6*

E7*

ZONE 1 SHORT CIRCUIT INDICATES ALARM

ZONE 2 SHORT CIRCUIT INDICATES ALARM

ZONE 3 SHORT CIRCUIT INDICATES ALARM

ZONE 4 SHORT CIRCUIT INDICATES ALARM

ZONE 5 SHORT CIRCUIT INDICATES ALARM

ZONE 6 SHORT CIRCUIT INDICATES ALARM

ZONE 7 SHORT CIRCUIT INDICATES ALARM

ZONE 8 SHORT CIRCUIT INDICATES ALARM

ZONE 1 NON-LATCHING

ZONE 2 NON-LATCHING

ZONE 3 NON-LATCHING

ZONE 4 NON-LATCHING

ZONE 5 NON-LATCHING

ZONE 6 NON-LATCHING

ZONE 7 NON-LATCHING

ZONE 8 NON-LATCHING

ZONE 1 DOES NOT SOUND ALARMS

ZONE 2 DOES NOT SOUND ALARMS

ZONE 3 DOES NOT SOUND ALARMS

ZONE 4 DOES NOT SOUND ALARMS

ZONE 5 DOES NOT SOUND ALARMS

ZONE 6 DOES NOT SOUND ALARMS

ZONE 7 DOES NOT SOUND ALARMS

ZONE 8 DOES NOT SOUND ALARMS

ZONE 1 ANY ALARM DELAYED

ZONE 2 ANY ALARM DELAYED

ZONE 3 ANY ALARM DELAYED

ZONE 4 ANY ALARM DELAYED

ZONE 5 ANY ALARM DELAYED

ZONE 6 ANY ALARM DELAYED

ZONE 7 ANY ALARM DELAYED

ZONE 8 ANY ALARM DELAYED

ZONE 1 SOUNDERS INHIBITED

ZONE 2 SOUNDERS INHIBITED

ZONE 3 SOUNDERS INHIBITED

ZONE 4 SOUNDERS INHIBITED

ZONE 5 SOUNDERS INHIBITED

ZONE 6 SOUNDERS INHIBITED

ZONE 7 SOUNDERS INHIBITED

ZONE 8 SOUNDERS INHIBITED

ZONE 1 WILL NOT OPERATE FIRE RELAY

ZONE 2 WILL NOT OPERATE FIRE RELAY

ZONE 3 WILL NOT OPERATE FIRE RELAY

ZONE 4 WILL NOT OPERATE FIRE RELAY

ZONE 5 WILL NOT OPERATE FIRE RELAY

ZONE 6 WILL NOT OPERATE FIRE RELAY

ZONE 7 WILL NOT OPERATE FIRE RELAY

E8* ZONE 8 WILL NOT OPERATE FIRE RELAY

Intelligent Security & Fire Ltd

TICK IF THIS

OPTION IS

SET

Man-1138_Sigma_CPA_Alarmsense_5 Page 22 of 22

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals