wm14


Add to my manuals
7 Pages

advertisement

wm14 | Manualzz
Energy Management
Power Analyzer
Type WM14-DIN “Basic Version”
• Optional dual pulse output
• Alarms (visual only) VLN, An
• Optional galvanically insulated measuring inputs
• Class 1 (active energy)
• Class 2 (reactive energy)
• Accuracy ±0.5 F.S. (current/voltage)
• Power analyzer
• Display of instantaneous variables: 3x3 digit
• Display of energies: 8+1 digit
• System variables and phase measurements: W, Wdmd,
var, VA, VAdmd, PF, V, A, An, Admd, Hz
• Amax, Admd max, Wdmd max indication
• Energy measurements: kWh and kvarh
• Hour counter (5+2 DGT)
• TRMS meas. of distorted sine waves (voltages/currents)
• Power supply: 24V, 48V, 115V, 230V, 50-60Hz; 18 to 60VDC
• Protection degree (front): IP40
• Front dimensions: 107.8x90mm
• Optional RS422/485 serial port
Product Description
How to order
3-phase power analyzer with
built-in programming keypad. Particularly recommended for displaying the
main electrical variables.
Housing for DIN-rail mount-
Model
Range code
System
Power supply
Option
ing, (front) protection degree
IP40, and optional RS485
serial port or dual pulse output. Parameters programmable by means of
CptBSoft.
How to order
Range codes
System
Power supply
AV5:
3:
A:
1-2-3-phase,
balanced/unbalanced
load,with or without
neutral
B:
C:
D:
3:
Input specifications
Rated inputs
Current “X-S options”
Current “SG-PG options”
Voltage
Accuracy (display, RS485)
(@25°C ±5°C, R.H. ≤60%)
Current
Neutral current
Phase-phase voltage
Phase-neutral voltage
Active and Apparent power,
Reactive power
CptBSoft
CptBSoft (compatible only with S or SG options): software
to program the working parameters of the power analyzer
and to read the energy and the instantaneous variables.
Type Selection
380/660VL-L/5(6)AAC
VL-N: 185 V to 460 V
VL-L: 320 V to 800 V
AV6: 120/208VL-L/5(6)AAC
VL-N: 45 V to 145 V
VL-L: 78 V to 250 V
Phase current: 0.03A to 6A
Neutral current: 0.09 to 6A
WM14-DIN AV5 3 D PGX
3 (non insulated each other)
3 (insulated each other)
4
with CT=1 and VT=1 AV5:
1150W-VA-var, FS:230VLN,
400VLL; AV6: 285W-VA-var,
FS:57VLN, 100VLL
0.25 to 6A: ±(0.5% FS +1DGT)
0.03A to 0.25A: ±(0.5%FS+7DGT)
0.25 to 6A: ±(1.5% FS +1DGT)
0.09A to 0.25A: ±(0.5%FS+7DGT)
±(1.5% FS +1 DGT)
±(0.5% FS + 1 DGT)
0.25 to 6A: ±(1% FS +1DGT);
0.03A to 0.25A: ±(1% FS+5DGT)
0.25 to 6A: ±(2% FS +1DGT);
0.03A to 0.25A: ±(2% FS+5DGT)
Specifications are subject to change without notice
24VAC
-15+10%, 50-60Hz
48VAC
-15+10%, 50-60Hz
115VAC
-15+10%, 50-60Hz
230VAC
-15+10%, 50-60Hz
18 to 60VDC (not
available in case of
SG or PG options)
Active energy “X-S option”
Reactive energy “X-S option”
Active energy “SG-PG opt.”
Reactive energy “SG-PG opt.”
Frequency
Additional errors
Humidity
Temperature drift
Sampling rate
Display refresh time
Display
Type
Read-out for instant. var.
Read-out for energies
Read-out for hour counter
WM14-DINPDS070905
Options
X:
S:
SG:
PG:
None
RS485 port
RS485+galvanic insulated measurig inputs
Dual pulse output +
galvanically insulated
measuring inputs.
Class 2 (start up “I”: 30mA)
Class 3 (start up “I”: 30mA)
Class 1 (start up “I”: 30mA)
Class 2 (start up “I”: 30mA)
±0.1Hz (48 to 62Hz)
≤0.3% FS, 60% to 90% RH
≤ 200ppm/°C
1400 samples/s @ 50Hz
1700 samples/s @ 60Hz
700ms
LED, 9mm
3x3 DGT
3+3+3 DGT (Max indication:
999 999 99.9)
1+3+3 DGT (Max. indication:
9 999 9.99)
1
WM14-DIN
Input specifications (cont.)
Measurements
Coupling type
Crest factor
Input impedance
380/660VL-L (AV5)
120/208VL-L (AV6)
Current
Current, voltage, power,
power factor, frequency,
energy, TRMS measurement
of distorted waves.
Direct
< 3, max 10A peak
(X-S options)
1 MΩ ±5%
453 KΩ ±5%
≤ 0.02Ω
Input impedance
380/660VL-L (AV5)
120/208VL-L (AV6)
Current
Frequency
Overload protection
Continuos voltage/current
For 500ms: voltge/current
(PG-SG options)
1 MΩ ±1%
1 MΩ ±1%
≤ 0.02Ω
48 to 62 Hz
1.2 F.S.
2 Un/36A
RS485 Serial Port Specifications
RS422/RS485 (on request)
Type
Connections
Addresses
Protocol
Multidrop
bidirectional (static and
dynamic variables)
2 or 4 wires, max. distance
1200m, termination directly
on the instrument
1 to 255, key-pad selectable
MODBUS/JBUS
Data (bidirectional)
Dynamic (reading only)
Static (writing only)
Data format
Baud-rate
System, phase variables and
energies
All configuration parameters
1 bit di start , 8 data bit,
no parity, 1 stop bit
9600 bit/s
CptBSoft software: parameter programming and reading data
CptBSoft
Multi language software to
program the working
parameters of the power
analyzer and to read the
energies and the
instantaneous variables.
The program runs under
Windows 95/98/98SE/2000/
NT/XP.
Working mode
Data access
Two different working
modes can be selected:
- management of a local
RS485 network;
- management of
communication from a single
instrument to PC (RS232);
By means of RS485
serial port.
Dual pulse output
Digital outputs (on request)
Pulse outputs
Number of outputs
Number of pulses
Output type
2
2 (one for kWh one for kvarh)
From 0.01 to 999 in
compliance with the
following formula:
[Psys max (kW or
kvar)*pulses (pulses/kWh
or kvarh)] <14400
Relay
min current: 0.05A@250VAC/30VDC
max current: 5A@250VAC/30VDC
Pulse duration
Insulation
Electrical life: min 2*105 cycles
Mechanical life: 5*106 cycles
≥100ms <120ms (ON)
≥100ms (OFF)
According to EN622053-31
By means of relays,
4000 VRMS outputs to
measuring inputs,
4000 VRMS output to
supply input.
Insulation between the two
outputs: 1000VRMS
Specifications are subject to change without notice
WM14-DINPDS070905
WM14-DIN
Software functions
Password
1st level
2nd level
System selection
Transformer ratio
CT
VT
Filter
Operating range
Filtering coefficient
Filter action
Displaying
3-phase system with neutral
Numeric code of max. 3
digits; 2 protection levels
of the programming data
Password “0”, no
protection
Password from 1 to 999,
all data are protected
3-phase with/without n, unbal.
3-phase balanced
3-phase ARON, unbalanced
2-phase
Single phase
1 to 999
1.0 to 99.9
0 to 100% of the input
display scale
1 to 16
Measurements, alarms,
serial out. (fundamental var: V,
A, W and their derived ones).
Up to 3 variables per page
Page 1: V L1, V L2, V L3
Page 2: V L12, V L23, V L31
Page 3: A L1, A L2, A L3
Page 4: A L1 dmd, A L2 dmd,
A L3 dmd
Alarms
Reset
Page 5: An, An Alarm
Page 6: W L1, W L2, W L3
Page 7: PF L1, PF L2, PF L3
Page 8: var L1, var L2, var L3
Page 9: VA L1, VA L2, VA L3
Page 10: VA ∑, W ∑, var ∑
Page 11: VA dmd, W dmd, Hz
Page 12: W dmd max (*)
Page 13: Wh (*)
Page 14: varh (*)
Page 15: VL-L ∑, PF ∑,
VLN Alarm
Page 16: A max (*)
Page 17: A dmd max (*)
Page 18: hour counter (*)
(*) = These variables are
stored in EEPROM when the
instrument is switched off
Programmable, for the VL∑ and
An (neutral current).
Note: the alarm is only visual,
by means of LED on the front
of the instrument.
Independent
alarm (VL∑, An)
max: A dmd, W dmd
all energies (Wh, varh) and
hour counter
Power Supply Specifications
Auxiliary power supply
230VAC
-15 +10%, 50-60Hz
115VAC
-15 +10%, 50-60Hz
48VAC
-15 +10%, 50-60Hz
Power consumption
24VAC
-15 +10%, 50-60Hz
18 to 60VDC
AC: 4.5 VA
DC: 4W
General Specifications
Operating
temperature
Storage
temperature
Installation category
Insulation (for 1 minute)
0° to +50°C (32 to 122°F)
(RH < 90% non condensing)
-10° to +60°C (14 to 140°F)
(RH < 90% non condensing)
Cat. III (IEC 60664, EN60664)
4000VAC, 500VDC
between mesuring
inputs and power supply.
500VAC/DC between
Specifications are subject to change without notice
Dielectric strength
EMC
Emissions
WM14-DINPDS070905
mesuring inputs and RS485.
4000VAC, 500VDC between
power supply and RS485
4000 VAC (for 1 min)
EN50084-1 (class A)
residential environment,
commerce and light industry
3
WM14-DIN
General Specifications (cont.)
EMC (cont.)
Immunity
Pulse voltage (1.2/50µs)
Safety standards
Approvals
Connections 5(6) A
Max cable cross sect. area
EN61000-6-2 (class A)
industrial environment.
EN61000-4-5
IEC60664, EN60664
CE, (cURus, CSA only “X”
and “S” options)
Screw-type
2.5 mm2
Housing
Dimensions (WxHxD)
Material
Mounting
Protection degree
Weight
107.8 x 90 x 64.5 mm
ABS
self-extinguishing: UL 94 V-0
DIN-rail
Front: IP40 (standard)
Connections: IP20
Approx. 400 g (pack. incl.)
Display pages
Display variables in 3-phase systems (in a 3-phase system with neutral)
No
1st variable
2nd variable
3rd variable
1
V L1
V L2
V L3
2
V L12
V L23
V L31
3
4
A L1
A L1 dmd
A L2
A L2 dmd
A L3
A L3 dmd
5
An
AL.n
6
W L1
W L2
W L3
7
8
PF L1
var L1
PF L2
var L2
PF L3
var L3
9
10
11
VA L1
VA system
VA dmd
(system)
VA L3
var system
Hz
(system)
12
13
Wh (MSD)
VA L2
W system
W dmd
(system)
W dmd MAX
Wh
14
varh (MSD)
varh
varh (LSD)
15
V LL system
AL.U
PF system
16
17
18
A MAX
A dmd max
h
Wh (LSD)
Note
Decimal point blinking on the right
of the display
dmd = demand (integration time
selectable from 1 to 30 minutes)
AL.n if neutral current alarm is
active
Decimal point blinking on the right
of the display if generated power
Decimal point blinking on the right
of the display if generated power
dmd = demand (integration time
selectable from 1 to 30 minutes)
Maximum sys power demand
The total indication is given in
max 3 groups of 3 digits.
The total indication is given in
max 3 groups of 3 digits.
AL.U= is activated only if one of
VLN is not within the set limits.
max. current among the three phases
max. dmd current among the three phases
hour counter
MSD: most significant digit
LSD: least significant digit
1) Example of kWh visualization:
This example is showing 15 933 453.7 kWh
4
2) Example of kvarh visualization:
This example is showing 3 553 944.9 kvarh
Specifications are subject to change without notice
WM14-DINPDS070905
WM14-DIN
Waveform of the signals that can be measured
Figure B
Sine wave, indented
Fundamental content
10...100%
Harmonic content
0...90%
Frequency spectrum: 3rd to 16th harmonic
Additional error: <1% FS
Figure A
Sine wave, undistorted
Fundamental content
100%
Harmonic content
0%
Arms =
1.1107 | A |
Figure C
Sine wave, distorted
Fundamental content
70...90%
Harmonic content
10...30%
Frequency spectrum: 3rd to 16th harmonic
Additional error: <0.5% FS
Accuracy
kWh, accuracy (RDG) depending on the current
PF=1
PF=L0.5
or C0.8
Error
+2.5%
+2%
+1.5%
+1%
Class 2
+1%
+1.5%
+2%
+2.5%
PF=L0.5
or C0.8
+1.5%
Class 2
0.10A
(0.02In)
0.25A
(0.05In)
0.25A
(0.05In)
0.5A
(0.1In)
Error
+4%
+3%
+2.5%
+2%
Class 3
0%
Class 2
- 1%
+2%
+2.5%
Class 3
-1.5%
+3%
+4%
+ 1%
Class 1
0%
PF=1
kvarh, accuracy (RDG) depending on the current
5A (In)
6A (Imax)
sinϕ=1
5A (In)
6A (Imax)
sinϕ=0.5
Class 2 accuracy limits (Active energy)
5(6A) Start-up current: 30mA
0.1A
(0.02In)
0.25A
(0.05In)
0.25A
(0.05In)
0.5A
(0.1In)
5A (In)
6A (Imax)
5A (In)
6A (Imax)
Class 3 accuracy limits (Reactive energy)
5(6A) Start-up current: 30mA
: this graph is only referred to instrument models with the “SG or PG” option.
: this graph is only referred to instrument models with the “X or S” option.
Used calculation formulas
Phase variables
Instantaneous effective voltage
Instantaneous apparent power
3-phase active power
Instantaneous reactive power
3-phase apparent power
System variables
Equivalent 3-phase voltage
3-phase power factor
Instantaneous power factor
Instantaneous effective current
3-phase reactive power
Instantaneous active power
Neutral current
Specifications are subject to change without notice
WM14-DINPDS070905
An = AL1 + AL2 + AL3
5
WM14-DIN
Used calculation formulas (cont.)
Energy metering
Where:
i = considered phase (L1, L2 or L3)
P = active power
Q = reactive power
t1, t2 = starting and ending time points of consumption recording
n = time unit
∆t = time interval between two successive power consumptions
n1, n2 = starting and ending discrete time points of consumption recording
Wiring diagrams
CT connection
2-phase connection
ARON and VT connection
3CT and 3VT connection
Fig. 4
Fig. 3
Fig. 2
Fig. 1
Fig. 5
3-phase load balanced connection
Fig. 6
1-phase connection
NOTE: Only for “PG” and “SG” options: the current measuring inputs are galvanically insulated
and therefore they can be connected to ground singly.
NOTE: For all models except for “PG” or “SG” the current inputs can be connected to the lines
ONLY by means of current transformers. The direct connection is not allowed.
6
Specifications are subject to change without notice
WM14-DINPDS070905
WM14-DIN
RS485 port connections
[c]
10
10
GND
T
11
T
11
RS485 RS232
RX+
12
RX+
12
TX+
RX-
13
RX-
13
TX-
TX+
14
TX+
14
RX+
TX-
15
TX-
15
RX-
[b]
[a]
PC
4-wire
connection
[c]
10
10
GND
T
11
T
11
RS485 RS232
RX+
12
RX+
12
TX+
RX-
13
RX-
13
TX-
TX+
14
TX+
14
RX+
TX-
15
TX-
15
RX-
GND
Fig. 8
GND
Pulse 2
GND
Pulse 1
[b]
[a]
Dual pulse output connections
21
GND
PC
2-wire
connection
N
+
L
-
12
6 13
7
43
14
8 15
9
Fig. 7: a-Last instrument; b-1...n Instrument
c-RS485/232 serial converter
Front Panel Description
1. Key-pad
To program the configuration parameters and the display of
the variables.
S
Key to enter programming and confirm selections;
1
▲
▲
2
Keys to:
- programme values;
- select functions;
- display measuring pages.
2. Display
LED-type with alphanumeric indications to:
- display configuration parameters;
- display all the measured variables.
45mm
44mm
90mm
Dimensions and Panel Cut-out
108,5mm
32,2mm
107,8mm
Specifications are subject to change without notice
50,1mm
64,5mm
WM14-DINPDS070905
7

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement