ARJAY ENGINEERING EC-Gold Dual User manual

Add to My manuals
26 Pages

advertisement

ARJAY ENGINEERING EC-Gold Dual User manual | Manualzz

EC-Gold Dual

Gas Concentration Transmitter

User Manual

Technical Support

Continental North America Toll Free 1-(800) 387-9487

Ph: +1 (905) 829-2418 Fx: +1 (905) 829-4701

A Product of Arjay Engineering Ltd.

Oakville, Ontario, Canada www.ArjayEng.com www.EnmetGasDetection.com

ECGOLDDUALUM12.doc Rev: 1.2

Model: EC-GOLD Dual

TABLE OF CONTENTS

1.0

  INSTRUMENT OVERVIEW .............................................................................. 3  

1.1

  Features ................................................................................................ 3  

1.2

  Description ............................................................................................ 3  

1.3

  Specifications ........................................................................................ 6  

2.0

  INSTALLATION ................................................................................................. 7  

2.1

  Mechanical Installation .......................................................................... 7  

2.2

  Electrical Installation .............................................................................. 8  

3.0

  STARTUP AND CONFIGURATION .................................................................. 11  

3.1

  Notes On The User Interface ................................................................ 11  

3.2

  Startup ................................................................................................... 12  

3.3

  Menu Configuration ............................................................................... 12  

3.3.1

  Normal Operating Menu Flow Chart ......................................... 13  

3.3.2

  Sensors Setup Menu Flow Chart ............................................. 14  

4.0

  CALIBRATION .................................................................................................. 15  

4.1

  Calibration Notes ................................................................................... 15  

4.2

  Calibration Procedures (Full Feature Mode) ......................................... 15  

4.3 Calibration Procedures (Standard Feature Mode)................................. 18  

4.3.1

  CALIBRATION NOTES ......................................................................... 18 

4.3.2

  SINGLE POINT CALIBRATION ............................................... 18  

5.0

  PUSH TO TEST FEATURE .............................................................................. 19  

6.0

  TROUBLESHOOTING ...................................................................................... 20  

7.0

  CONTROLLER SETTINGS SHEET .................................................................. 21  

- 2 -

Model: EC-GOLD Dual

ECGOLDDUALUM12.doc Rev: 1.2

1.0 INSTRUMENT OVERVIEW

1.1 Features

 Gas monitor for a large variety of gas types.

 Can monitor up to 4 different sensor inputs at one time

Port 1: on board CO (Carbon Monoxide) Electrochemical

Port 2: on board electrochemical for NO2 (Nitrogen Dioxide), CL2 (Chlorine),

H2S (Hydrogen Sulfide), NH3 (Ammonia) and others.

Port 3: integral or remote MOS broad range toxic and combustibles

Port 4: remote 4-20 mA input transmitters

 Carbon Monoxide sensor has expected life of

5 years min. (3 year guarantee)

 Other sensors have expected life of 2 years (1 year guarantee)

 Output may be user selectable for analog (4-20mA / 2-10V) or Arjay’s Discrete Voltage

Output (DVO).

 Convenient pushbutton calibration.

 User selectable for Single or Dual Point calibration

 High/High, High, Low, and optional System Fault Indication in place of High/High alarm

 User selectable High and Low Alarm levels

 Modbus protocol via RS-485 for access by Arjay/Enmet Central Access Panel or compatible system

 Can be used as a stand alone gas detector or can be used with other EC-Gold sensors for interfacing with an Arjay Central control panel or customer system

 User specified custom features might be added by contacting Arjay Engineering Ltd.

1.2 Description

The EC-Gold Dual can be used a Stand Alone gas detector with relays and outputs available to communicate with remote devices such as alarms, fans and building automation systems.

The standard model provides 3 relays, a 4-20 mA output and an RS-485 interface. The full feature model provides the addition of an LCD display of concentration, buzzer with silence, and keypad interface.

The 4-20 mA output will represent the peak value determined from all sensor inputs based on the percentage concentration of their range. For example, assume the detector has a CO sensor calibrated for 0-200 ppm and an NO2 sensor with a calibrated range of 0-20 ppm. If the

CO sensor reads a 20ppm and the NO2 sensor reads 10ppm, the 4-20 mA output will be 12 mA. This will represent that the NO2 is at 50% of its range while the CO is only at 10% of its range. An analog output cannot be averaged among sensors. This would provide outputs not representative of actual conditions and could result in unsafe conditions.

The relays are common to all sensors and are set to ppm or % LEL values specific and proper for each sensor type.

The LCD display will provide a real time reading of the ppm or % LEL concentrations of all sensors.

The EC-Gold Dual can be used with multiple sensors connected to any Arjay/Enmet Control panel. The following are examples of typical methods of installing the EC-Gold Dual.

Figure 1.0: The EC-Gold Dual can be a Stand Alone detector to interface with fans or alarms using the relays or analog outputs.

Figure 1.1: EC-Gold Dual can be combined with other EC-Gold Dual or EC-Gold sensors to the

ISA 66 RLU panel using the cost effective Arjay/Enment DVO signal. Ideal for multi-zone installations where a central control panel is desirable.

- 3 -

Model: EC-GOLD Dual

ECGOLDDUALUM12.doc Rev: 1.2

Figure 1.2: EC-Gold Dual can be combined with other EC-Gold Dual or EC-Gold sensors to the

ISA Gas Alert Max panel using the cost effective Arjay/Enment DVO signal. Ideal for single or multi-zone installations where the control panel is desirable at each fan location or in central location.

Figure 1.3: EC-Gold Dual can be combined with other EC-Gold Dual or EC-Gold sensors to the

PG-2000 panel using the RS-485 communication to address each sensor. Ideal for applications that require more complex zone control or analog outputs for VFD fan control.

Dual 3/4" & 1/2"

Knock-Outs for rear entry cabling.

CO 0

CO 0

NO

C

NC

NO

C

NC

NO

C

NC

3

4

5

1

2

6

7

8

9

Buzzer has built-in ACk.

EC

Sensor

MOS Sensor Remote XMTR

CANADA LTD.

LCD www.arjayeng.com

EC 2

MENU

EC 1

SELECT

WITHOUT COVER

EC-Gold Dual Stand Alone Application

Figure 1.0

FRONT COVER

- 4 -

Model: EC-GOLD Dual

BUZZER

Zone 1

Relays

ECGOLDDUALUM12.doc Rev: 1.2

Zone 5

Relays

3 Wire Discrete Voltage Output shielded connection

ZONE 1

ZONE 2

ZONE 5

CANADA LTD.

LCD www.arjayeng.com

EC 2

MENU

EC 1

SELECT

EC-Gold Dual

EC-Gold Dual RLU Application

Figure 1.1

3 Wire Discrete Voltage Output shielded connection

To other sensors

EC-Gold

To other sensors

Relays

R1

R2

R3

R4

STATUS

CAL

1

4

2

5

3

6

SETUP

7

.

0

8 9

ENTER www.arjayeng.com

PG-2000 Scanner

CANADA LTD.

LCD www.arjayeng.com

EC 2

MENU

EC 1

SELECT

EC-Gold

EC-Gold Dual

EC-Gold Dual Gas Alert Application

Figure 1.2

24 VDC 2 Wires

2 Wires RS-485 Network

To other sensors

Up to 128 Transmitters on the Network

4-20 mA Output

Up to 80

Sensors

4-20 mA Output

CANADA LTD.

LCD www.arjayeng.com

EC 2

MENU

EC 1

SELECT

EC-Gold Dual

EC-Gold Dual PG-2000 Network Application

Figure 1.3

- 5 -

EC-Gold

Model: EC-GOLD Dual

1.3 Specifications

ECGOLDDUALUM12.doc Rev: 1.2

OPERATION

The EC-Gold Dual is a multi-sensor gas detector. A variety of gases may be sensed when fitted with the appropriate sensors.

PUSH-TEST FEATURE On demand using the Push to Test pushbutton.

LCD DISPLAY/KEYPAD 2 x 8 LCD display showing ppm concentrations and calibration menus

USER INTERFACE

Calibration and setup Keypad, LCD, pushbutton, and LED status lights.

Push-Test Pushbutton.

Network RS-485 modbus protocol. Used either with the ARJAY/ENMET

CAP unit or via third party, modbus compatible systems.

INPUTS

Port 1 (EC1):

Port 2 (EC2):

Port 3:

on board CO (Carbon Monoxide) Electrochemical

on board electrochemical for NO2 (Nitrogen Dioxide), CL2

(Chlorine), H2S (Hydrogen Sulfide), NH3 (Ammonia) and others.

integral or remote MOS broad range toxic/combustibles and catalytic combustibles

remote 4-20 mA input transmitters Port 4:

OUTPUTS mA output

DC Voltage output

PERFORMANCE

When configured for Analog output: 4-20mA into 700 ohms max.

When configured for Voltage output: 2-10V proportional to calibrated range. mA / Voltage output 0.1% resolution – non-isolated.

RLU DV output When configured for RLU Discrete Voltage Output mode:

Alarms

0V = No Alarm, 1.8V = Low Alarm, 2.8V = High Alarm, 10V =

Sensor Fault. (Sensor Fault only detected with CO sensor).

3 alarms (High/High, High, Low) and Optional System Fault May be factory selected

Alarm Indication High (Red), Low (Yellow), and a 2 color LED for Sensor Fault (Red) and No Alarms (Green). The 2 color LED is also used to flash calibration errors (Red for ~2 seconds after an unsuccessful calibration).

Accuracy ±2% of Full Scale Range (the accuracy is limited by the sensors – the electronic accuracy is better than 1%.

POWER

12VDC - 24VDC @ 200mA max OR 24VAC INPUT (See JP1

Jumper in Fig 2.1)

Require extra current if use external transmitter

MECHANICAL SPECIFICATIONS

Enclosure

Dimensions

Nema 1 wall mount

9.61” [244mm] H x 6.25” [159mm] W x 2” [50mm] D

Weight

ENVIRONMENTAL SPECIFICATIONS

Operating Temp.

Relative Humidity

-20°C to +55°C

90% max. with no condensation.

- 6 -

Model: EC-GOLD Dual

2.0 INSTALLATION

2.1 Mechanical Installation

ECGOLDDUALUM12.doc

(2) Dual 3/4" & 1/2"

Knock-Outs for top entry cabling.

5.66"

5.16"

Dual 3/4" & 1/2"

Knock-Outs for rear entry cabling.

CO 0

CO 0

NO

C

NC

NO

C

NC

NO

C

NC

1

2

3

4

5

6

7

8

9

B u z r

Buzzer has built-in ACk.

V+ Sig

MOS Sensor Remote XMTR

EC

Sensor

Mounting Holes

(4 Places)

Without Cover

Dual 3/4" & 1/2"

Knock-Outs for external sensor.

6.25"

With Cover

CANADA LTD.

LCD www.arjayeng.com

EC 2

MENU

EC 1

SELECT

Rev: 1.2

Figure 2.0

Locate the EC-Gold Dual on a vertical surface away from drafts, open doors or windows, condensation or dripping moisture.

The vertical placement (above the floor) depends on the gas being monitored. For CO, the unit should be located within the breathing zone: about 4 - 5 feet above the finished floor*. For other gases, refer to an Arjay Engineering representative.

* Check local building codes (i.e. Ontario Building code requires mounting 2’11” to 3’11”).

- 7 -

ECGOLDDUALUM12.doc Rev: 1.2

Model: EC-GOLD Dual

EC-Gold Dual Stand Alone Electrical Installationion

Out

!

Use good installation practice!

Do not run High Voltage cables in the same conduit as signal wires.

RS-485 Network 24VAC/DC Input

JP1

Jumper In for DC Power

For Network applications, the 2 wires

RS-485 network connects to the

PG-2000 Scanner or Central Access

Panel.

CO 0

CO 0

For RLU Loop (alarm only) applications, the output is configured for Loop output and connects to the corresponding Zone connection on the ISA-66 RLU board.

NC

NO

C

NC

NO

C

NC

NO

C

6

7

8

3

4

5

9

1

2

Buzzer has built-in ACk.

EC

Sensor

MOS Sensor Remote XMTR

Figure 2.1

- 8 -

Model: EC-GOLD Dual

R1

R2

R3

R4

STATUS

ECGOLDDUALUM12.doc

EC-Gold Dual and PG-2000 or Central Access Panel

Electrical Installationion

4 Wires + Shielded

(Shielded connected at this point only)

GND

24VAC/VDC

D-

D+

RS-485

(2 Wires)

Communication

Wire

CO 0

CO 0

CAL

1 2

4 5

3

6

SETUP

7 8

.

0

9

ENTER www.arjayeng.com

NC

NO

C

NC

NO

C

NC

NO

C 5

6

3

4

1

2

7

8

9

EC

Sensor

Buzzer has built-in ACk.

MOS Sensor Remote XMTR

Figure 2.2

EC-Gold Dual and ISA 66 RLU

Electrical Installationion

Rev: 1.2

CO 0

CO 0

NC

NO

C

NC

NO

C

NC

NO

C 5

6

3

4

1

2

7

8

9

B u z z e r

Buzzer has built-in ACk.

V+ Si

MOS Sensor Remote XMTR

EC

Sensor

For clarity only Zone 5 is shown connected.

sensors pr zone: Typically around 20 depending on wires sizes and lengths.

SGND connection (on ISA-66 RLU) NOT made to EC-Gold Dual.

24V

PGND

VSIG

SGND

N/C

CO 0

CO 0

To other

Zones

NO

C

NC

NO

C

NC

NO

C

NC

1

2

3

4

5

6

7

8

9

EC

Sensor

Buzzer has built-in ACk.

MOS Sensor Remote XMTR

Figure 2.3

CO 0

CO 0

NC

NO

C

NC

NO

C

NC

NO

C

1

2

3

4

5

6

7

8

9

B u z z e r

Buzzer has built-in ACk.

V+ Si

MOS Sensor Remote XMTR

EC

Sensor

- 9 -

Model: EC-GOLD Dual

Gas Alert

ECGOLDDUALUM12.doc Rev: 1.2

EC-Gold Dual and Gas Alert

Electrical Installationion

The Gas Alert only accommodates a single zone.

Sensors per zone: Typically around 20 depending on wires sizes and lengths.

SGND connection ( on Gas Alert) NOT made to ED-Gold Dual.

24V

PGND

VSIG

SGND

N/C

CO 0

CO 0

CO 0

CO 0

NO

C

NC

NO

C

NC

NO

C

NC

1

2

3

4

5

6

7

8

9

Buzzer has built-in ACk.

EC

Sensor

NO

C

NC

NO

C

NC

NO

C

NC

1

2

3

4

5

6

7

8

9

B u z z e r

Buzzer has built-in ACk.

EC

Sensor

MOS Sensor Remote XMTR

V+ Sig

MOS Sensor Remote XMTR

Figure 2.4

All user connections are via mating plug/receptacle connectors to make installation and service easier.

CAUTION:

THE UNIT HOUSES SENSITIVE ELECTRONIC COMPONENTS AND SHOULD BE HANDLED

WITH CARE. IF PUNCHING OR DRILLING THROUGH THE ENCLOSURE WALLS IS

NECESSARY MAKE SURE THAT THE INTERNAL ELECTRONIC MODULES ARE SHIELDED

FROM DEBRIS ESPECIALLY METAL PARTICLES.

PLEASE MAKE SURE THAT THE CONNECTIONS HAVE THE POLARITY AS INDICATED OR

THE CONTROLLER MAY BE DAMAGED.

USE GOOD INSTALLATION PRACTICE! DO NOT RUN HIGH VOLTAGE CABLE IN THE

SAME CONDUIT AS SIGNAL WIRES.

- 10 -

Model: EC-GOLD Dual

ECGOLDDUALUM12.doc

3.0 STARTUP AND CONFIGURATION

User Interface Overview

With Cover

Rev: 1.2

CO 0

CO 0

CANADA LTD.

LCD www.arjayeng.com

NO

C

NC

NO

C

NC

NO

C

NC

6

7

8

9

3

4

5

1

2

Buzzer has built-in ACk.

EC

Sensor

EC 2

MENU

EC 1

SELECT

MOS Sensor Remote XMTR

Calibration

Pushbutton

Push To Test only available when used with CO sensor

Push To Test

Pushbutton

LED

LED 1

LED 2

LED 3

LED 4

Status Color

Green

Red

Yellow

Red

Red

Meaning

Instrument ok, no faults.

Will remain green for Low, Hi and Hi/Hi alarm

Instrument failure / Sensor Fault condition

Low Alarm

High Alarm

Hi/Hi Alarm, Buzzer on

Calibration

Pushbutton

Push To Test

Pushbutton

Figure 3.0

3.1 Notes On The User Interface

The EC-Gold Dual can monitor up to 4 different Sensor inputs at one time.

Port 1: on board CO (carbon monoxide) sensor

Port 2: on board electrochemical sensor

Port 3: remote MOS sensor

Port 4: remote 4-20 mA Input Transmitter

The standard model provides 3 relays, a 4-20mA output and an RS-485 interface. The full feature model provides the addition of an LCD display of concentration, buzzer with silence and keypad interface.

The EC-Gold Dual may be configured and calibrated using the following methods:

1. Using the calibration pushbuttons (basic model without keypad). The pushbutton is accessible without removing the front cover.

- 11 -

Model: EC-GOLD Dual

ECGOLDDUALUM12.doc Rev: 1.2

2. Using the keypad and display (full feature model). The user follows the menus on the display.

3. Using Arjay’s optional 2000-CAL hand held calibrator. The calibrator communicates with the EC-Gold Dual via the RS-485 connection using the modbus protocol. The calibrator’s LCD and keypad offer a more convenient method of setting up and calibrating the EC-Gold Dual unit.

3.2 Startup

Power up the unit. The status LED should be green. The High and Low alarm LED’s should go off in less than a minute.

The unit is normally pre-configured and calibrated at the factory so field setup is not required on startup.

To re-calibrate, see section 4.0 Calibration.

To re-enter or modify settings, follow the procedures described below. Only the full feature model interface procedure is described here.

After powering up the unit and under normal operating conditions, the LCD displays the Normal

Operating Menu. See the next page for detail Menu configuration>

The Default Password: 2000

Alrm Del – Alarm and Buzzer Delay (Setup Alarm Delay On and Off Time in second; setup

Buzzer Delay On time in second)

K1 – Relay 1 Alarm Delay On/Off time

K2 – Relay 2 Alarm Delay On/Off time

K3 – Relay 3 Alarm Delay On/Off time

Buzzer – Delay On time

Sel Snsr – Select Sensor

A1 – Relay 1 Alarm Setting Value (normally, Low alarm value)

A2 – Relay 2 Alarm Setting Value (normally, High alarm value)

A3 – Relay 3 Alarm Setting Value (normally, Hi/Hi alarm value)

- 12 -

Model: EC-GOLD Dual

3.3.1 Normal Operating Menu Flow Chart

ECGOLDDUALUM12.doc Rev: 1.2

13

Model: EC-GOLD Dual

3.3.2 Sensors Setup Menu Flow Chart

ECGOLDDUALUM12.doc Rev: 1.2

14

Model: EC-GOLD Dual

4.0 CALIBRATION

ECGOLDDUALUM12.doc Rev: 1.2

The instrument was calibrated and tested prior to leaving the factory. Therefore, it is possible to use the instrument directly out of the box. Under normal conditions, recalibration is recommended once every 6 months. For a two point calibration, the first point is typically Zero

(clear air); the second point (also called span) is a determined gas concentration value.

If the preset EC-Gold Dual calibration span value is known and you have the same calibration gas concentration, the entire calibration procedure can be completed without removing the front cover.

4.2 Calibration Procedures (Full Feature Mode with LCD / KEYPAD)

Calibration

CANADA LTD.

LCD www.arjayeng.com

EC 2

MENU

EC 1

SELECT

EC2

EC1

Calibration Ports

Flowrate Regulator preset for 0.5 Lpm Male, Quick Disconnect tube insertedinto EC-Gold

Dual Calibration Ports

(EC1 & EC2)

Flow On/Off Knob 6 feet of 5/16" O.D. x 3/16" I.D.

flexible, clear tubing.

Cal Gas Canister

Figure 4.0

1. Under normal operating conditions, the LCD displays the following (depending on sensors order):

CO 0

NO2 0

2. Follow the Manu Flow Chart, until the following screen display:

#1: CO

Zero

15

Model: EC-GOLD Dual

ECGOLDDUALUM12.doc Rev: 1.2

3. Zero Calibration only needs to be done when installing a new sensor. Press <MENU> key to bypass Zero Calibration, and go to step 6 to start second point calibration. If a

Zero Calibration is required, follow the steps 4-5.

4. Press <SELECT> key, the LCD display:

Z xx mv xx

5. Make sure the ambient air around the sensor is clean ie. it has no traces of the gas being monitored. In applications where the ambient air is not guaranteed to be clean, use a compressed air calibration canister and apply the air to the sensor hole (EC1). For the Zero point, the mv values should be less then 100 mv. If the mv value is changing within 5 mv for a minimum of 10 seconds, the instrument will automatically accept the

Zero calibration. Or press <SELECT> key and finish the first point (Zero) calibration.

6. The LCD now displays the following and the instrument is ready for the second point calibration.

#1: CO

2nd Pt.

7. Press <SELECT> key to start the second point calibration, and the LCD displays the following. Press <SELECT> key to move the cursor and accept the second point calibration. If want to change gas concentration value, press <SELECT> key to move the cursor to proper position and press <MENU> key to increase up to the right value. Press

<SELECT> key to accept the gas concentration value.

S stands for second point

#1: CO

S 200

8. After selecting gas concentration value, the LCD displays the following and the instrument is ready for the second calibration:

S xxx mv xxx

9. Apply the Gas in the sensor hole (EC1). EC1 is for Carbon Monoxide; EC2 is for other types of gas, such as NO2. Start gassing the sensor by opening the valve on the canister. The flow rate is set to 0.5 Lpm (or ~1 SCFH (Standard Cubic Foot per Hour).

Wait about 90 seconds. After this, if the mv value is changing within 5 mv for a minimum of 10 seconds, the instrument will automatically accept the second point. Or press

<SELECT> key to manually accept the second point. If the calibration was successful, the LCD displays the following. Otherwise, the LCD displays the calibration error message.

#1: CO

Cal OK

10. The “Cal OK” or “Error Message” only displays a couple of seconds, then the LCD displays the following alarm 1 setting value:

#1: CO

A1

35

11. Press <MENU> key to bypass the Alarm value setting menu, until the following Sensor

Selection Menu shows up:

16

Model: EC-GOLD Dual

Sel Snsr

#1: CO

ECGOLDDUALUM12.doc Rev: 1.2

12. Press <

> or <> key to select the #2 Sensor or Exit. If choose the #2 Sensor, the LCD displays the following:

Sel Snsr

#2: NO2

13. Press <SELECT> Key to the second sensor calibration menu. If the sensor is mA input sensor, then go to step 14

#2 NO2

Zero

The calibration procedure for second sensor is the same as the first sensor except for applying gas to sensor hole (EC2). Follow the steps 3-12, then press <MENU> key to go to the normal working display.

14. If the sensor is mA input sensor, the calibration of the sensor is done at the remote sensor (see Remote Sensor Manual). The mA scale is normally factory set, but may be changed if change needed. Press <SELECT> to change mA settings or press <MENU> key to bypass the calibration and go back to the Sensor Selection Menu.

#2 CO mA Scale

15. Press <SELECT> key to set 4 mA, and the LCD displays the following. Press

<SELECT> key to move the cursor and accept the value. Normally, set 4 mA equals 0 ppm. To change the value, press <SELECT> key to move the cursor to proper position and press <MENU> key to increase up to the right value. Press <SELECT> key to accept the setting value.

#2 CO

4= 0

16. Press <SELECT> key to set 20 mA, and the LCD displays the following. Press

<SELECT> key to move the cursor and accept the value. 20 mA is normally set for maximum range of remote XMTR. To change the value, press <SELECT> key to move the cursor to proper position and press <MENU> key to increase up to the right value.

Press <SELECT> key to accept the setting value.

#2 CO

20= 200

17. Then the display goes to the Alarm setting Menu. Press <MENU> key to bypass the calibration and go back to the Sensor Selection Menu. Repeat Step 12 to Step 16 if calibrate more sensors.

18. Go back to the normal operating Menu by following the Normal Operating Menu Flow

Chart

THIS COMPLETES THE CALIBRATION PROCEDURE FOR

FULL FEATURE CONTROLLER

17

Model: EC-GOLD Dual

ECGOLDDUALUM12.doc Rev: 1.2

4.3 Calibration Procedures (Standard Feature Mode Without LCD / KEYPAD)

The EC-Gold Dual may be calibrated using a Single Point calibration procedure, by using calibration push button.

The Calibration pushbutton may be accessed using a screwdriver or other fine tool – See Figure 4.1 for the location of the access hole.

A full Dual Point calibration is always performed at the factory and involves zeroing the sensor in clean air, then calibrating at a preset gas concentration. The Single Point calibration is typically used in the field since it is more convenient. Also, it does not require clean air as one of the calibration points, since clean air cannot be guaranteed in all installations. A Single Point calibration assumes the unit has

already been zeroed. This is always true for new units from the factory.

Figure 4.1

4.3.2 SINGLE POINT CALIBRATION

The calibration gas concentration value must be known. The unit comes factory set for Single

Point Calibration and 100 ppm CO or 10 ppm NO2. If either setting is in doubt, then see section

7, controller setting sheet.

1. Determine what Calibration gas concentration the EC-Gold Dual is expecting. This value is listed on the packing slip and may be recorded in the back of the user manual in the CONTROLLER SETTINGS sheet for future reference.

18

Model: EC-GOLD Dual

ECGOLDDUALUM12.doc Rev: 1.2

2. The gas sensor is mounted directly behind the Calibration Port in the middle of the front plate of the EC-Gold Dual housing [See Fig. 4.1]. Insert the Quick Disconnect tube into the EC-Gold’s Dual Calibration Port.

3. Start gassing the sensor by opening the valve on the canister. The flow rate is preset to 0.5 Lpm (or ~1 SCFH (Standard Cubic Foot per Hour). Wait about 90 seconds.

4. Press and hold the calibration pushbutton (via the access hole – see Fig. 4.1) until the

Status LED glows orange acknowledging the calibration request. Release the pushbutton.

5. If the Status LED remains green after the Calibration pushbutton is released,

then the Calibration has been successfully completed. If the calibration was successful, the Status LED remains green. If there was a calibration error such as not enough change for the gas concentration used, then the Status LED shows red for about 2-3 seconds before reverting back to green.

THIS COMPLETES THE CALIBRATION PROCEDURE

FOR STANDARD FEATURE CONTROLLER

5.0 PUSH TO TEST FEATURE

The Push to Test feature allows the customer to verifty if the controller is receiving a LOW, HIGH, HIGH

HIGH and Total span alarm signals and that ventilation fans, audio alarms etc are working.

Press the Push to Test pushbutton to activate this feature. See Figure 3.0 for the pushbutton location.

When the button is pressed and released, the Status LED starts blinking green on and off every 2 seconds to indicate a test is underway. This feature forces the sensor to Low alarm plus 1ppm.

Press Button again to force High alarm plus 1ppm. Press Button again to force HIGH HIGH alarm (HIGH

HIGH alarm plus 1ppm). Press Button again to force span value alarm. Press Button again to get out of

Push to Test feature. If Push to Test feature is left ON, it will time out after 30 minutes.

19

Model: EC-GOLD Dual

ECGOLDDUALUM12.doc

6.0 TROUBLESHOOTING

ERROR DESCRIPTION

1. No Output and all lights off

2. 4-20mA output does not track the gas concentration.

3. In Discrete Voltage Output mode, the

ISA-66RLU or Gas Alert connected to the EC-Gold always shows Sensor Fault

Rev: 1.2

WHAT TO DO

 Check the power to the unit. The voltage should be 24VAC/DC at the power connector with the positive and negative connected as shown on the connector label.

 Make sure JP1 is in place for DC voltage

 If the Power checks out, call Arjay

Service.

 Make sure that the EC-Gold Dual output mode is set to Analog mode and not to Discrete Voltage Output mode. See Controller Settings Sheet section for details.

 Make sure the maximum range of the remote XMTR is the same as the 2 nd calibration point. Ex. 20mA=200ppm

CO

 Calibration may be required. See the calibration section for details.

 Call Arjay/Enmet Service for Help if none of the above fixes the problem.

 Make sure that the EC-Gold DUAL output mode is set to Discrete

Voltage Output mode and not to

Analog.

20

Model: EC-GOLD Dual

ECGOLDDUALUM12.doc

7.0 CONTROLLER SETTINGS SHEET

Checked by

Model Number

Serial Number

Hardware Rev.

Software Rev.

Rev: 1.2

The factory settings column below lists the typical default settings. The user may change these values at any time. If changed, please fill in the USER SETTING column for future reference.

PARAMETER DESCRIPTION

FACTORY

SETTING

OUTPUT MODE

There are2 main output modes :

Analog(4-20 mA) and DVO (discrete Voltage

Output)

BUZZER TYPE

Enable or disable the buzzer

LOW ALARM DELAY

TO ON

LOW ALARM DELAY

TO OFF

HIGH ALARM DELAY

TO ON

HIGH ALARM DELAY

TO OFF

Hi/Hi ALARM DELAY

To ON

Hi/Hi ALARM DELAY

To OFF

USER

SETTING

The minimum time in seconds a Low Alarm must exist before the corresponding relay and indicator are activated.

The minimum time in seconds the Ec-Gold Dual must be out of Low Alarm before the Low Alarm relay and indicator are de-activated

The minimum time in seconds a High Alarm must exist before the High Alarm relay and indicator are activated.

The minimum time in seconds the Ec-Gold Dual must be out of High Alarm before the High Alarm relay and indicator are de-activated.

The minimum time in seconds a Low Alarm must exist before the corresponding relay and indicator are activated.

The minimum time in seconds the Ec-Gold Dual must be out of Low Alarm before the Low Alarm relay and indicator are de-activated

Type or Port.

SENSOR #1

Sensor serial number

Gas name

Low alarm value

High alarm value

Hi/Hi alarm value

Span Value

21

Model: EC-GOLD Dual

ECGOLDDUALUM12.doc Rev: 1.2

PARAMETER DESCRIPTION

FACTORY

SETTING

SENSOR #1

USER

SETTING

First Cal point

Enter ppm and corresponding mV e.g. 0ppm= 150mV

Second Cal point

Enter ppm and corresponding mV e.g. 100ppm=400mV

Type or Port.

SENSOR #2

Sensor serial number

Gas name

Low alarm value

High alarm value

Hi/Hi alarm value

SENSOR #3

SENSOR #4

Span Value

First Cal point

Enter ppm and corresponding mV e.g. 0ppm= 150mV

Second Cal point

Enter ppm and corresponding mV e.g. 100ppm=400mV

Type or Port.

Sensor serial number

Gas name

Low alarm value

High alarm value

Hi/Hi alarm value

Span Value

First Cal point

Enter ppm and corresponding mV e.g. 0ppm= 150mV

Second Cal point

Enter ppm and corresponding mV e.g. 100ppm=400mV

Type or Port.

Sensor serial number

Gas name

Low alarm value

High alarm value

Hi/Hi alarm value

Span Value

First Cal point

Enter ppm and corresponding mV e.g. 0ppm= 150mV

Second Cal point

Enter ppm and corresponding mV e.g. 100ppm=400mV

22

MAINTENANCE AND CALIBRATION

Your ARJAY / ENMET gas detector is the state of the art in gas detection, but like any other part of your ventilation system, it requires periodic maintenance and calibration.

There are various sensor technologies that may be used in your Arjay gas monitor; including solid state MOS, Electrochemical, Infrared and Pellister Pair (Hot wire). These have a normal operating life of 3 to 5 years under ambient conditions. You should consider a preventive maintenance schedule whereby you test your system on a periodic basis to ensure its proper calibration and operation.

For solid state (MOS) sensors, we recommend calibration every 3 to 4 months for a typical garage application. For Electrochemical sensors, we recommend calibration every 6 months for a typical garage application. Pellister Pair we recommend every 3 to 4 months and Infrared we recommend every 6 months. For applications that are more sensitive, or where internal policies exist, a higher frequency of calibration may be required. This is a simple procedure which will indicate any problems with your system. A test and calibration kit may be purchased from

ARJAY ENGINEERING for this purpose. Parts are also readily available from our facility.

MAINTENANCE CONTRACT

Alternatively you may wish to consider a Maintenance Contract with ARJAY ENGINEERING whereby one of our service technicians comes to your site and checks out the unit for proper calibration and operation on a regularly scheduled basis. This is done on a flat per annum fee.

All parts are extra. Typical target gases are included, however, exotic or specialty gases may have a surcharge. If you wish us to quote a Maintenance Contract fill in the section below and return to our office.

COMPANY:

ADDRESS:

CONTACT PERSON:

PHONE: FAX:

EMAIL:

MODEL AND SERIAL

NO. OF GAS DETECTOR:

Fax to address below or e-mail to [email protected]

ARJAY ENGINEERING LTD

2851 Brighton Rd

Oakville, Ontario, Canada L6H 6C9

Telephone: +1 (905)-829-2418

Telefax: +1 (905)-829-4701

N. America Toll: (800)-387-9487

Internet: www.arjayEng.com

E-Mail: [email protected]

ARJAY ENGINEERING LTD.

GUARANTEE

We hereby guarantee this instrument to be free from defects in workmanship and materials, and if found defective in workmanship or materials, upon being returned to our factory, prepaid, within one year from date of purchase, it will be repaired or replaced at factory without charge. However, if upon being returned and after inspection, there is evidence that the instrument has been subjected to tampering, careless handling, improper or faulty application or installation, the above guarantee shall not be applicable, and we shall have the right in any such case to make a charge to cover the cost of repairs, servicing and transportation expense. The undersigned assumes and shall have no liability for consequential damages resulting from the use or misuse of the instrument.

The foregoing guarantee is in lieu of all other guarantees or warranties, expressed or implied, and all other obligations or liabilities, contractual or otherwise, either to the original purchaser of said instrument, or to any other person whomever.

BY: ARJAY ENGINEERING LTD.

For service, call ARJAY Engineering Ltd. directly: Canada (905) 829-2418

North American Toll Free: 1-800-387-9487

Fax: (905) 829-4701

Internet:

E-mail: www.arjayeng.com

[email protected]

ARJAY ENGINEERING LTD

2851 Brighton Rd

Oakville, Ontario, Canada L6H 6C9

Telephone: +1 (905)-829-2418

Telefax: +1 (905)-829-4701

N. America Toll: (800)-387-9487

Internet: www.arjayEng.com

E-Mail: [email protected]