CENTRAL AIR CONDITIONERS
FREE MATCH Ċ MULTI VRF
SERVICE MANUAL
T1/R410A/50Hz
(GC201106 -ĉ)
http://splitoff.ru/tehn-doc.html
,
,
,
.
CONTENTS
PRODUCT ..................................................................................................................... 2
1 MODELS LIST ............................................................................................................................ 2
1.1 Outdoor Unit .......................................................................................................................................................2
1.2 Indoor Unit...........................................................................................................................................................2
2 NOMENCLATURE ..................................................................................................................... 4
2.1 Nomenclature of Outdoor Unit ..........................................................................................................................4
2.2 Nomenclature of indoor unit ..............................................................................................................................4
3 FUNCTION ................................................................................................................................... 5
4 PRODUCT DATA ....................................................................................................................... 6
4.1 Product data of outdoor......................................................................................................................................6
4.2 Product data of indoor ........................................................................................................................................7
4.3 Working Temperature Range...........................................................................................................................12
5 PIPING DIAGRAM ................................................................................................................... 13
CONTROL ................................................................................................................... 15
1 OPERATION FLOWCHART ................................................................................................... 15
1.1 Cooling/Dehumidfying Operation ...................................................................................................................16
1.2 Heating Operation.............................................................................................................................................17
2 MAIN LOGIC ............................................................................................................................. 18
2.1 Control Function of Outdoor Unit...................................................................................................................18
2.2 Protection Function ..........................................................................................................................................19
2.3 other function.....................................................................................................................................................20
2.4 Control Function of Indoor Unit......................................................................................................................20
3 REMOTE CONTROLLER ....................................................................................................... 23
3.1 Wired Remote Controller ................................................................................................................................23
3.2 Wireless Remote Controller..............................................................................................................................28
INSTALLATION ......................................................................................................... 33
1 PRECAUTIONS FOR INSTALLATION ................................................................................ 33
1.1 Precautions for Installation ..............................................................................................................................33
1.2 Key Points of Installation .................................................................................................................................34
2 FLOW CHART OF INSTALLATION...................................................................................... 35
3 OUTDOOR UNIT INSTALLATION........................................................................................ 36
3.1 Before Installation .............................................................................................................................................36
3.2 Installation Site..................................................................................................................................................36
3.3 Caution for Installation.....................................................................................................................................36
3.4 Dimension Data ................................................................................................................................................36
3.5 Installation Clearance Data..............................................................................................................................37
4 INDOOR UNIT INSTALLATION ............................................................................................ 38
4.1 Installation of Duct Type...................................................................................................................................38
: http://splitoff.ru/tehn-doc.html
4.2 Installation of Cassette Type.............................................................................................................................41
4.3 Installation of Floor Ceiling Type ....................................................................................................................47
5 REFRIGERATION PIPING WORK ....................................................................................... 50
5.1 Connection between Indoor and Outdoor Units.............................................................................................50
5.2 Refrigerant Charging and Trial Running ......................................................................................................52
6 ELECTRIC WIRING WORK................................................................................................... 55
6.1 Wiring Principle ................................................................................................................................................55
6.2 Electric Wiring Design ......................................................................................................................................55
6SHFL¿FDWLRQRI3RZHU6XSSO\:LUHDQG$LU6ZLWFK ......................................................................................57
MAINTENANCE......................................................................................................... 59
1 TROUBLE TABLE..................................................................................................................... 59
1.1 Please check the following items before contact the maintenance serviceman............................................59
7KHFRQGLWLRQVOLVWHGEHORZDUHQRWFODVVL¿HGLQWRHUURUV ..............................................................................59
1.3 Error description ...............................................................................................................................................60
2 FLOW CHART OF TROUBLESHOOTING .......................................................................... 64
3 WIRING DIADRAM.................................................................................................................. 69
3.1 Outdoor unit ......................................................................................................................................................69
3.2 Indoor unit .........................................................................................................................................................70
4 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS ................................ 72
4.1 Outdoor Unit......................................................................................................................................................72
4.2 Indoor Unit.........................................................................................................................................................74
5 EXPLODED VIEWS AND PART LIST ................................................................................... 81
5.1 Outdoor Unit .....................................................................................................................................................81
5.2 Indoor Unit.........................................................................................................................................................85
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
PRODUCT
1
: http://splitoff.ru/tehn-doc.html
QSPEVDU
Free Match
Service Manual
PRODUCT
1 MODELS LIST
1.1 Outdoor Unit
Capacity
Units
Series
Model
Product Code
Cooling
(kW)
Heating
(kW)
GWHD(36)NK3AO
CN860W0011
9.789
11
Free
Match
Outdoor
Unit
GWHD(42)NK3AO
CN860W0020
11.6
Ref.
Power
Supply
R410A
220~ 240V
-1Ph-50Hz
Ref.
Power
Supply
R410A
220~ 240V
-1Ph-50Hz
Ref.
Power
Supply
R410A
220~ 240V
-1Ph-50Hz
R410A
220~ 240V
-1Ph-50Hz
Appearance
13
1.2 Indoor Unit
1.2.1 Duct type
Capacity
Units
Series
Free
Match
Duct Type
Indoor
Unit
Model
Product Code
Cooling
(kW)
Heating
(kW)
GFH(09)EA-K3DNA1A/I
CN210N0010
2.5
2.80
GFH(12)EA-K3DNA1A/I
CN210N0020
3.5
3.85
GFH(18)EA-K3DNA1A/I
CN210N0030
5.0
5.50
GFH(21)EA-K3DNA1A/I
CN210N0040
6.0
6.60
GFH(24)EA-K3DNA1A/I
CN210N0050
7.1
8.00
Appearance
1.2.2 Cassette type
Units
Series
Free
Match
Cassette
Type
Indoor
Unit
Capacity
Model
Product Code
Cooling
(kW)
Heating
(kW)
GKH(12)BA-K3DNA1A/I
CN510N0010
3.5
3.85
GKH(18)BA-K3DNA1A/I
CN510N0020
5.0
5.50
GKH(24)BA-K3DNA1A/I
CN510N0030
7.1
8.00
GKH(12)BA-K3DNA2A/I
CN510N0040
3.5
4.0
GKH(18)BA-K3DNA2A/I
QSPEVDU
CN510N0050
4.5
5.0
2
: http://splitoff.ru/tehn-doc.html
Appearance
Free Match
Service Manual
1.2.3 Floor ceiling type
Units
Series
Free
Match
Floor/
Ceiling
Type
Indoor
Unit
Capacity
Model
Product Code
Cooling
(kW)
Heating
(kW)
GTH(09)BA-K3DNA1A/I
CN610N0010
2.5
2.80
GTH(12)BA-K3DNA1A/I
CN610N0020
3.5
3.85
GTH(18)BA-K3DNA1A/I
CN610N0030
5.0
5.50
GTH(24)BA-K3DNA1A/I
CN610N0040
7.1
8.00
Ref.
Power
Supply
R410A
220~ 240V
-1Ph-50Hz
Appearance
3
: http://splitoff.ru/tehn-doc.html
QSPEVDU
Free Match
Service Manual
2 NOMENCLATURE
2.1 Nomenclature of Outdoor Unit
GW
Ƒ
Ƒ
Ƒ
Ƒ
Ƒ
Ƒ
Ƒ
O
1
2
3
4
5
6
7
8
9
NO.
Description
Options
1
GW
Free-Match Code
2
Cooling Function
C: Cooling Only
H: Heat pump
3
Compressor Frequency
D:DC inverter rotor type
4
Cooling Capacity
36 represents 36000Btu/h
1kW=3.412KBtu
5
Climate Type
T1
6
Power Supply
M:380-415V-3Ph-50Hz;
K:220-240V-1Ph-50Hz
7
Refrigerant
R410A
8
Design No.
A :First generation
9
O
Outdoor Unit Code
O:Outdoor
I:Indoor
2.2 Nomenclature of indoor unit
QSPEVDU
G
Ƒ
Ƒ
Ƒ
Ƒ
1
2
3
4
5
-
Ƒ
Ƒ
Ƒ
Ƒ
Ƒ
Ƒ
6
7
8
9
10
11
NO.
Description
1
G
2
Product Type
3
Cooling Function
C: Cooling Only
H: Heat pump
4
Cooling Capacity
12 represents 12000Btu/h
1kW=3.412KBtu
5
Series
6
Power Supply
7
Refrigerant
8
Compressor Frequency
9
Climate Type
10
Panel Code
1 Alphabet +1 Numeral
11
Design No.
A :First generation
12
I
Indoor Unit Code
O:Outdoor
I:Indoor
/
I
12
Options
GREE
F:Duct type
K:Cassette type
T:Floor ceiling type
Alphabets: Series code + Shell code
M:380-415V-3Ph-50Hz;
K:220-240V-1Ph-50Hz
R410A
D:DC inverter rotor type
T1
4
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
3 FUNCTION
Function
For Comfortable
Air Conditioning
Duct type
Cassette type
Floor ceiling type
Fan operation Mode
Ɣ
Ɣ
Ɣ
Auto Swing Controller
-
Ɣ
Ɣ
Timer Selector
Ɣ
Ɣ
Ɣ
Auto Mode Operation
Ɣ
Ɣ
Ɣ
Cool Mode Operation
Ɣ
Ɣ
Ɣ
Heat Mode Operation
Ɣ
Ɣ
Ɣ
Dry Mode Operation
Ɣ
Ɣ
Ɣ
Fan Mode Operation
Ɣ
Ɣ
Ɣ
Sleep mode setting
Ɣ
Ɣ
Ɣ
Drain Pump
Ɣ
Ɣ
-
Wired Controller
Ɣ
Ɣ
Ɣ
Wiredless Remote Controller
Ɣ
Ɣ
Ɣ
For Flexible Control
Ɣ+DYH)XQFWLRQV
- :No Functions
5
: http://splitoff.ru/tehn-doc.html
QSPEVDU
Free Match
Service Manual
4 PRODUCT DATA
4.1 Product data of outdoor
Heat pump
GWHD(36)NK3AO
GWHD(42)NK3AO
Product Code
CN860W0011
CN860W0020
Model
Cooling
kW
9.789
11.6
Heating
kW
11
13
Capacity adjustment range
%
23% ~ 150%
19%~ 150%
EER
kW/kW
3.23
3.23
COP
kW/kW
3.65
3.67
Power supply
V-Ph-Hz
220~240-1-50
220~240-1-50
R410A
R410A
3.6
4.8
Brand
MITSUBISHI
MITSUBISHI
Type
DC inverter rotor type
DC inverter rotor type
Quantity
1
1
IP×4
IP×4
6*3
6*3
Flare Connection
Flare Connection
dB(A)
54
54
Capacity
Type
Refrigerant
Charge volume
Compressor
kg
Moisture protection
Wiring connection
mm2
Area*quantity
Connecting pipe
Connection method
Sound pressure level
Outline dimension
W×D×H
mm
950×412×840
1015×440×1103
Package dimension
W×D×H
mm
1100×450×905
1155×490×1220
Net weight
kg
73
102
Gross weight
kg
78
112
Maximum drive IDU NO.
unit
4
5
Max. equivalent connection pipe length
m
70
80
20'GP
52
22
40' GP
108
48
40' HQ
108
48
Loading quantity
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27ć DB,
1 9 ć WB. Outdoor Temperature is 35 ć DB.The rated heating capacity data is measured under the following work
condition: Indoor Temperature is 20ć DB. Outdoor Temperature is 7ć DB, 6ć WB.
b. The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.
QSPEVDU
6
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
4.2 Product data of indoor
4.2.1 Duct Type
Heat pump
GFH(09)EA-K3DNA1A/I
GFH(12)EA-K3DNA1A/I
GFH(18)EA-K3DNA1A/I
Product Code
CN210N0010
CN210N0020
CN210N0030
Model
Cooling
kW
2.5
3.5
5.0
Heating
kW
2.80
3.85
5.50
Power supply
V-Ph-Hz
220 ~ 240-1- 50
220 ~ 240-1- 50
220 ~ 240-1- 50
Motor power input
kW
0.075
0.065
0.08
m3/h
450
550
700
CFM
265
324
412
dB(A)
37/31
39/32
40/33
Output
kW
0.041
0.036
0.044
Running
current
A
0.406
0.348
0.428
Gas
inch
ƎĭPP
ƎĭPP
ƎĭPP
Liquid
inch
ƎĭPP
ƎĭPP
ƎĭPP
Flare Connection
Flare Connection
Flare Connection
Capacity
$LUÀRZYROXPH
Sound pressure level(H/L)
Fan motor
Connecting pipe
Connection method
External dia.
mm
ĭ
ĭ
ĭ
Thickness
mm
1.5
1.5
1.5
Outline
dimension
W×D×H
mm
700×615×200
700×615×200
900×615×200
Package
dimension
W×D×H
mm
893×743×305
893×743×305
1123×743×305
Net Weight
kg
22
23
27
Gross weight
kg
27
29
36
20'GP
108
108
90
40' GP
234
234
180
40' HQ
234
234
180
Drain pipe
Loading quantity
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27ć DB,
1 9 ć WB. Outdoor Temperature is 35 ć DB.The rated heating capacity data is measured under the following work
condition: Indoor Temperature is 20ć DB. Outdoor Temperature is 7ć DB, 6ć WB.
b. The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.
7
: http://splitoff.ru/tehn-doc.html
QSPEVDU
Free Match
Service Manual
Heat pump
GFH(21)EA-K3DNA1A/I
GFH(24)EA-K3DNA1A/I
Product Code
CN210N0040
CN210N0050
Model
Cooling
kW
6.0
7.1
Heating
kW
6.60
8.00
Power supply
V-Ph-Hz
220~240-1-50
220~240-1-50
Motor power input
kW
0.11
0.11
m3/h
1000
1000
CFM
589
589
dB(A)
42/34
42/34
Output
kW
0.061
0.061
Running current
A
0.588
0.588
Gas
inch
ƎĭPP
ƎĭPP
Liquid
inch
ƎĭPP
ƎĭPP
Flare Connection
Flare Connection
Capacity
$LUÀRZYROXPH
Sound pressure level(H/L)
Fan motor
Connecting pipe
Connection method
External dia.
mm
ĭ
ĭ
Thickness
mm
1.5
1.5
Outline dimension
W×D×H
mm
1100×615×200
1100×615×200
Package dimension
W×D×H
mm
1323×743×305
1323×743×305
Net Weight
kg
31
31
Gross weight
kg
41
41
20'GP
72
72
40' GP
162
162
40' HQ
162
162
Drain pipe
Loading quantity
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27ć DB,
1 9 ć WB. Outdoor Temperature is 35 ć DB.The rated heating capacity data is measured under the following work
condition: Indoor Temperature is 20ć DB. Outdoor Temperature is 7ć DB, 6ć WB.
b. The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.
QSPEVDU
8
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
4.2.2 Cassette type
Heat pump
GKH(12)BA-K3DNA1A/I
GKH(18)BA-K3DNA1A/I
GKH(24)BA-K3DNA1A/I
Product Code
CN510N0010
CN510N0020
CN510N0030
Model
Cooling
kW
3.5
5
7.1
Heating
kW
3.85
5.50
8.00
Power supply
V-Ph-Hz
220~240-1-50
220~240-1-50
220~240-1-50
Motor power input
kW
0.07
0.07
0.1
m3/h
680
680
1180
CFM
400
400
694
dB(A)
37/33
37/33
39/35
Output
kW
0.0385
0.0385
0.055
Running current
A
0.374
0.374
0.535
Gas
inch
Ǝĭ9.52mm)
ƎĭPP
ƎĭPP
Liquid
inch
ƎĭPP
ƎĭPP
ƎĭPP
Flare Connection
Flare Connection
Flare Connection
Capacity
$LUÀRZYROXPH
Sound pressure level(H/L)
Fan motor
Connecting
pipe
Connection method
External dia.
mm
ĭ
ĭ
ĭ
Thickness
mm
3
3
3
Body(W×D×H)
mm
840×840×190
840×840×190
840×840×240
Panel(W×D×H)
mm
950×950×60
950×950×60
950×950×60
Body(W×D×H)
mm
963×963×273
963×963×273
963×963×325
Panel(W×D×H)
mm
1043×1028×130
1043×1028×130
1043×1028×130
Body
kg
25
25
30
Panel
kg
6.5
6.5
6.5
Body
kg
33
33
38
Panel
kg
10
10
10
20'GP
72
48
40
40' GP
128
128
108
40' HQ
144
144
128
Drain pipe
Outline
Dimension
Package
Dimension
Net Weight
Gross Weight
Loading quantity
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27ć DB,
1 9 ć WB. Outdoor Temperature is 35 ć DB.The rated heating capacity data is measured under the following work
condition: Indoor Temperature is 20ć DB. Outdoor Temperature is 7ć DB, 6ć WB.
b. The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.
9
: http://splitoff.ru/tehn-doc.html
QSPEVDU
Free Match
Service Manual
Heat pump
GKH(12)BA-K3DNA2A/I
GKH(18)BA-K3DNA2A/I
Product Code
CN510N0040
CN510N0050
Model
Cooling
kW
3.5
4.5
Heating
kW
4.0
5.0
Power supply
V-Ph-Hz
220~240-1-50
220~240-1-50
Motor power input
kW
0.05
0.05
m3/h
600
600
CFM
353
353
dB(A)
46
46
Output
kW
0.011
0.011
Running current
A
0.25
0.25
Gas
inch
Ǝĭ9.52mm)
ƎĭPP
Liquid
inch
ƎĭPP
ƎĭPP
Flare Connection
Flare Connection
Capacity
$LUÀRZYROXPH
Sound pressure level(H/L)
Fan motor
Connecting pipe
Connection method
External dia.
mm
ĭ
ĭ
Thickness
mm
3
3
Body(W×D×H)
mm
570×570×230
570×570×230
Panel(W×D×H)
mm
650×650×50
650×650×50
Body(W×D×H)
mm
851×731×325
851×731×325
Panel(W×D×H)
mm
733×673×117
733×673×117
Body
kg
18
18
Panel
kg
6.5
6.5
Body
kg
23
23
Panel
kg
10
10
20'GP
102
102
40' GP
209
209
40' HQ
246
246
Drain pipe
Outline Dimension
Package
Dimension
Net Weight
Gross Weight
Loading quantity
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27ć DB,
1 9 ć WB. Outdoor Temperature is 35 ć DB.The rated heating capacity data is measured under the following work
condition: Indoor Temperature is 20ć DB. Outdoor Temperature is 7ć DB, 6ć WB.
b. The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.
QSPEVDU
10
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
4.2.3 Floor ceiling type
Heat pump
GTH(09)BA-K3DNA1A/I
GTH(12)BA-K3DNA1A/I
Product Code
CN610N0010
CN610N0020
Model
Cooling
kW
2.5
3.5
Heating
kW
2.8
3.85
Power supply
V-Ph-Hz
220~240-1-50
220~240-1-50
Motor power input
kW
0.055
0.055
m3/h
650
650
CFM
383
383
dB(A)
40/36
40/36
Output
kW
0.3
0.3
Running current
A
0.297
0.297
Gas
inch
ƎĭPP
ƎĭPP
Liquid
inch
ƎĭPP
ƎĭPP
Flare Connection
Flare Connection
Capacity
$LUÀRZYROXPH
Sound pressure level(H/L)
Fan motor
Connecting pipe
Connection method
External dia.
mm
ĭ
ĭ
Thickness
mm
1.75
1.75
Outline dimension
W×D×H
mm
1220×700×225
1220×700×225
Package dimension
W×D×H
mm
1343×823×315
1343×823×315
Net Weight
kg
40
40
Gross weight
kg
50
50
20'GP
48
48
40' GP
96
96
40' HQ
96
96
Drain pipe
Loading quantity
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27ć DB,
1 9 ć WB. Outdoor Temperature is 35 ć DB.The rated heating capacity data is measured under the following work
condition: Indoor Temperature is 20ć DB. Outdoor Temperature is 7ć DB, 6ć WB.
b. The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.
11
: http://splitoff.ru/tehn-doc.html
QSPEVDU
Free Match
Service Manual
Heat pump
GTH(18)BA-K3DNA1A/I
GTH(24)BA-K3DNA1A/I
Product Code
CN610N0030
CN610N0040
Model
Cooling
kW
5
7.1
Heating
kW
5.5
8.0
Power supply
V-Ph-Hz
220~240-1-50
220~240-1-50
Motor power input
kW
0.11
0.11
3
m /h
950
1250
CFM
559
736
dB(A)
45/40
48/40
Output
kW
0.061
0.061
Running current
A
0.588
0.588
Gas
inch
ƎĭPP
ƎĭPP
Liquid
inch
ƎĭPP
ƎĭPP
Flare Connection
Flare Connection
Capacity
$LUÀRZYROXPH
Sound pressure level(H/L)
Fan motor
Connecting pipe
Connection method
External dia.
mm
ĭ
ĭ
Thickness
mm
1.75
1.75
Outline dimension
W×D×H
mm
122×700×225
1220×700×225
Package dimension
W×D×H
mm
1343×823×315
1343×823×315
Net Weight
kg
40
45
Gross weight
kg
50
54
20'GP
48
48
40' GP
96
96
40' HQ
96
96
Drain pipe
Loading quantity
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27ć DB,
1 9 ć WB. Outdoor Temperature is 35 ć DB.The rated heating capacity data is measured under the following work
condition: Indoor Temperature is 20ć DB. Outdoor Temperature is 7ć DB, 6ć WB.
b. The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.
4.3 Working Temperature Range
Indoor side state
Outdoor side stae
Dry bulb temp. ć
Wet bulb temp. ć
Dry bulb temp. ć
Wet bulb temp. ć
Rated Cooling
27
19
35
24
Max. cooling
32
23
48
26
Min. cooling
21
15
18
—
Rated Heating
20
15
7
6
Max. heating
27
—
24
18
Min. heating
20
15
ˉ 15
ˉ 16
Notes˖
a. The heating/cooling capacity and noise listed below are all measured before the shipment.
b. All parameters listed below are measured under the standard working conditions. If there is any change, the
parameters marked on the nameplate always prevail.
c. The heating capacity of the indoor unit just involves that of the heat pump but apart from that of the auxiliary
electric heater.
QSPEVDU
12
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
5 PIPING DIAGRAM
Schematic Diagram of Free Match Series Inverter Heat Pump Multi VRF System
M
Schematic Diagram of Free Match Series Inverter Heat Pump Multi VRF System
The outdoor and indoor units start to work once the power is switched on. During the cooling operation, the low
temperature, low pressure refrigerant gas from the heat exchanger of each indoor unit gets together and then is taken into
the compressor to be compressed into high temperature, high pressure gas, which will soon go to the heat exchanger of
the outdoor unit to exchange heat with the outdoor air and then is turned into refrigerant liquid. After passing through the
throttling device, the temperature and pressure of the refrigerant liquid will further decrease and then go the main valve.
After that, it will be divided and go to the heat exchanger of each indoor unit to exchange heat with the air which needs
to be conditioned. Consequently, the refrigerant liquid become low temperature, low pressure refrigerant gas again. Such
a refrigeration cycle goes round and round to achieve the desired refrigeration purpose. During the heating operation, the
four-way valve is involved to make the refrigeration cycle run reversely. The refrigerant radiates heat in the heat exchanger
of the indoor unit (so do the electric heating devices) and absorb heat in the heat exchanger of the outdoor unit for a heat
pump heating cycle so as to achieve the desired heating purpose.
13
: http://splitoff.ru/tehn-doc.html
QSPEVDU
Free Match
Service Manual
INSTALLATION
32
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
INSTALLATION
1 PRECAUTIONS FOR INSTALLATION
1.1 Precautions for Installation
Before installation, please ensure if the installing site, power ratings, possible operating range (pipe distance, height
difference between indoor and outdoor unit, power voltage) and installing space are correct and suitable. The outdoor unit
is general to all models according to its power.
ƹ To ensure correct installation, please make sure to read the Safety Considerations thoroughly before starting the
installation works.
WARNING and
CAUTION. Those that might cause
ƹ The considerations stated below are classified into
GHDWKRUVHYHUHLQMXU\LQFDVHRIZURQJLQVWDOODWLRQDUHLGHQWL¿HGLQ WARNING. However, those that are stated in
CAUTION may also cause severe accidents sometimes. Therefore, both of them relate to important safety considerations
and must be strictly followed..
ƹ $IWHUFRPSOHWLQJWKHLQVWDOODWLRQDQGWHVWUXQDQGFRQ¿UPLQJWKDWDOODUHQRUPDOSOHDVHLQWURGXFHWRWKHFOLHQW
on how to use and repair the machine according to the Operating Instructions. Besides, please deliver the considerations
herein to the clients together with the Operating Instructions, and ask them to keep properly.
WARNING!
ƹ The installation shall be performed by the vendor or professional dealer from which you buy the machine. If you
LQVWDOOE\\RXUVHOIDQ\LPSURSHULQVWDOODWLRQPLJKWFDXVHZDWHUOHDNDJHHOHFWULFVKRFNRU¿UHDFFLGHQW
ƹ The installation shall be done correctly according to installation instructions. Improper installation may cause
ZDWHUOHDNDJHHOHFWULFVKRFNRU¿UH
ƹ To install a large air-conditioning system in a small room, please make sure to take measures to prevent that the
refrigerant will not exceed the limit concentration in case of leakage. For the measures to prevent the refrigerant from
exceeding the limit concentration, please consult your dealer. If no proper measures, it might cause human suffocation in
case of refrigerant leakage.
ƹ Please install at a position that is strong enough to support the weight of machine. If the installing position is of
low strength, the machine may drop down and thus cause human injury.
ƹ Please carry out installation in accordance with the rules for preventing the typhoon or earthquake. The machine
may tip over if the installation does not comply with the requirements.
ƹ The electrical cabling shall be carried out by qualified electricians in accordance with the Safety Code for
Electrical Equipment, relevant local rules and the installation instructions. Make sure to use the special-purpose circuit. If
WKHSRZHUFLUFXLWFDSDFLW\LVORZRUWKHFRQVWUXFWLRQLVLPSURSHULWPLJKWFDXVHHOHFWULFVKRFNRU¿UHDFFLGHQWV
ƹ Please use suitable cables and connect them securely. Please fix the terminal joints securely. The terminal
FRQQHFWLRQVKDOOQRWEHDIIHFWHGGXHWRDQ\H[WHUQDOIRUFHDSSOLHGRQWRWKHFDEOH,PSURSHUFRQQHFWLRQDQG¿[LQJPD\
FDXVHKHDWLQJDQG¿UHDFFLGHQWV
ƹ Keep the cables in correct shape and prevent them from protruding upward. Please protect them securely with
UHSDLUERDUG,PSURSHULQVWDOODWLRQPD\FDXVHKHDWLQJDQG¿UHDFFLGHQWV
ƹ When erecting or relocating the air conditioner, do not let any air enter into cooling circulation system except the
VSHFL¿HGUHIULJHUDQW,IDQ\DLULVPL[HGDEQRUPDOKLJKSUHVVXUHZLOORFFXULQWKHFRROLQJFLUFXODWLRQV\VWHPWKXVFDXVLQJ
crack or human injury accidents.
ƹ During installation, please always use the attached parts or designated parts. Failure to use the designated parts
PD\FDXVHZDWHUOHDNDJHHOHFWULFVKRFN¿UHRUUHIULJHUDQWOHDNDJH
CAUTION:
ƹ Please earth securely. Do not connect the earth wires to gas pipe, water pipe, lightning rod or telephone line.
Improper earthling might cause electric shock.
ƹ Leakage circuit breaker must be installed at some place. No installation of leakage circuit breaker might cause
electric shock.
ƹ 'RQRWLQVWDOODWDSODFHZKHUHLQÀDPPDEOHJDVPLJKWOHDN*DVOHDNDJHDQGGHVSRWDURXQGWKHPDFKLQHPLJKW
FDXVH¿UHDFFLGHQWV
ƹ To ensure correct drainage of water, the drainage pipe shall be installed according to the installation instructions.
Also the heat insulation shall be provided to avoid condensing. Improper installation of the pipe might result in water
leakage and lead to possible wetting of the articles in the room.
33
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
1.2 Key Points of Installation
Installation Procedures
Description and Acceptance Criteria
Material Selection and Equipment Inspection
7KHPDWHULDOVVSHFL¿HGRQWKHHQJLQHHULQJGUDZLQJVKDOOEHSXUFKDVHGDVVSHFL¿HGHJFRSSHU
tube, thermal insulation tube, PVC pipe, power cables, air switch, etc).
7KHPDWHULDOVQRWVSHFL¿HGRQWKHHQJLQHHULQJGUDZLQJVKDOOEHSXUFKDVHGDFFRUGLQJWRWKH
actual quantity of works (e.g. hanger frame, cable duct, etc).
Check if the outdoor unit, indoor unit, communication wires and accessories are complete.
Connection
Communication
wire
Address
dial code
Remote Control
Installation
of indoor unit
The power cables shall be separated from communication wires at a least distance of 10cm.
To avoid breaking the communication wires, please do not use strong force.
For multiple units, please mark them properly.
Switch on indoor and outdoor unit, and ensure there is no display of “Communication Wire
Error E6”.
Each indoor unit under the same system has a unique address dial code.
The wired controller and its corresponding indoor unit have the same address dial code.
Select the remote control mode.
The centralized controller and communication module shall be installed free from the source
of interference.
7KHSRZHUFDEOHPXVWPHHWWKHVSHFL¿FDWLRQV
7KHLQGRRUXQLWVXQGHUWKHVDPHV\VWHPPXVWEHDUUDQJHGXQGHUXQL¿HGSRZHUVXSSO\
Power cord
Installation
7KH39&SLSHVPXVWPHHWWKHVSHFL¿FDWLRQV
$VSHFL¿FJUDGLHQWPXVWEHSURYLGHGDORQJWKHZDWHUÀRZGLUHFWLRQ
Carry out water detection after installation.
Carry out thermal insulation to the drainage pipe only after the water detection is accepted.
Thermal
insulation
7KHWKHUPDOLQVXODWLRQWXEHPXVWPHHWWKHVSHFL¿FDWLRQV
Seal between the thermal insulation pipes to avoid air entry.
Drainage Pipe
Installation of Air Duct (when with
high static pressure duct-type unit)
Welding
Installation
of connection
pipes
Purge and make leakage
detection under pressure
Thermal insulation
Design the length of air duct according to static pressure;
The air inlet shall be optimally designed to avoid too small size
7KHFRSSHUWXEHPXVWPHHWWKHVSHFL¿FDWLRQV
Ensure it is dry and clean inside the tube.
Make sure to charge nitrogen as required for protection when welding the tubes.
Please keep to the welding process and ensure the system free of leakage.
$GGDGXDOZD\¿OWHURQOLTXLGSLSHVLGH
For multiple systems, please mark them properly.
Carry out leakage detection under pressure after welding.
Purge the system clean.
Keep the pressure for 24 hours
Except for the influence by temperature, it is deemed acceptable if pressure drop is within
0.02MPa. (With the temperature change by 1ć , the pressure will change by approx. 0.01MPa)
7KHWKHUPDOLQVXODWLRQWXEHPXVWPHHWWKHVSHFL¿FDWLRQV
Seal between the thermal insulation pipes to avoid air entry.
Installation of outdoor unit
Select the installing position correctly.
Build the foundation according to the anchor bolt position and the dimension of outdoor unit
Build the damping device properly.
Avoid sharp knock when handling the outdoor unit. The inclination angle shall not be higher
than 15°.
Connection of indoor unit and outdoor unit
Tighten the nuts.
Provide proper protection to the outdoor connection pipe, communication wires and power
supply.
Leakage detection under pressure
Keep the pressure for 24 hours. Except for the influence by temperature, it is deemed
acceptable if pressure drop is within 0.02MPa. (With the temperature change by 1 ć , the
pressure will change by approx. 0.01MPa).
Vacuuming
Add refrigerant
Establish vacuum simultaneously in the gas pipe and liquid pipe;
The vacuuming time shall be long enough.
Put still for 1 hour after vacuuming. It is deemed acceptable if the pressure will not rise.
$GGUHIULJHUDQWDFFRUGLQJWRWKHYROXPHDVVSHFL¿HGRQWKHHQJLQHHULQJGUDZLQJ
Open the valve of outdoor unit
Commissioning of complete unit
Remarks:
a. Described above are general working procedures. The procedures might vary with the site conditions.
b. For detailed installation rules, please see the description in each chapter.
34
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
2 FLOW CHART OF INSTALLATION
Design Kicking-off
Material selection
Inspection of site installation position
Installation of indoor unit
Installation of
remote control
Connection of
power cables and
communication wires
Installation of connection pipes
Installation of
drainage pipes
Installation of outdoor unit
Purge and make leakage
detection under pressure
Connection of power cables
Thermal
insulation
Connection of indoor unit and outdoor unit
Connection of indoor unit and outdoor unit
Leakage detection
under pressure
Test run of indoor unit
meanwhile vacuum the system
through the gas and liquid valves
Air flow and noise
level inspection
Add refrigerant
Open the valve
Commissioning
of complete unit
As-built Drawing
Delivery of the Operating Instructions
35
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
3 OUTDOOR UNIT INSTALLATION
3.1 Before Installation
ƹ Check if there is any damage to the unit when receive and unpack the unit, and check if the compressor runs
reversely, if the grease oil and refrigerant leak, and if all parts are completely prepared. If there is any damage on the
surface or the inner side, please inform the shipping company or the equipment manufacturer in the written form promptly.
ƹ Check if the model, specs and quantity of the unit are consistent with the contact after receive the unit.
3.2 Installation Site
ƹ The unit may be installed on balcony, roof, special platform or any other position easy to install and able to
support the weight.
ƹ Select the place with good ventilation, where the exhaust is smooth and will not be circulated. Meanwhile, the
exhaust from the unit shall not affect the neighbors.
ƹ 7KHDLUGLVFKDUJHGIURPWKHXQLWZLOOQRWÀRZEDFNDQGWKHUHVKDOOEHDGHTXDWHVHUYLFHVSDFHDURXQGWKHPDFKLQH
ƹ Around the unit there shall be no strong heat source or exhaust port of other equipment, nor any strong hot steam
RULQÀDPPDEOHJDV
ƹ When several units are to be installed, adequate suction space shall be ensured to avoid short-circuit circulation.
ƹ Install at a place that will not be affected by rainstorm in winter.
ƹ Install at a place where there is no obstruction close to the air inlet or outlet.
ƹ Around the machine body, drainage channel shall be provided for discharge of cold or warm water.
ƹ The indoor connection pipe is easy to connect outdoors.
ƹ The indoor and outdoor units shall be installed to minimize the length and bends of refrigerant pipe.
ƹ Install close to power socket for easy connection of the cables.
ƹ Open space required around the unit.
ƹ Fasten the machine onto the supporting legs and base with M12 screw combination.
3.3 Caution for Installation
The following rules should be followed when the installation location is being considered so as to let the unit run
well enough.
ƹ The discharged air from the outdoor unit won’t return back and enough space should be left for maintenance
around the unit.
ƹ The installation location should be in good condition so that the unit is able to take in and discharge enough air.
Besides, make sure there is no obstacle at the air inlet/outlet of the unit. If there is, remove it.
ƹ The unit must be installed where it is secure enough to support the weight of the unit and capable of reducing to
some extent noise and vibration to make sure they do not bother your neighbors.
ƹ The designated lifting hole must be used for lifting the unit and protect the unit carefully during lifting to prevent
damaging the mental sheet which would result in rusting in future.
ƹ The unit should be installed where there is as little as direct sunlight.
ƹ The unit must be installed where the rain water and defrosting water can be drained.
ƹ The unit must be installed where the unit won’t be covered by the snow and won’t be affected by rubbish and oil
fog.
ƹ Rubber or spring shock absorbers should be used during the installation of the outdoor unit to meet the noise and
vibration requirements.
ƹ The installation dimensions should meet the requirement covered in this manual and the outdoor unit must be
¿[HGVHFXUHO\
ƹ The installation should be carried out by the professionally skilled personnel.
3.4 Dimension Data
7KHIROORZLQJ¿JXUHLVDSSOLFDEOHWRWKH2XWGRRUXQLWVRI : GWHD(36)NK3AO
36
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
350
840
412
110 76
340
378
1022
950
192
96
572
7KHIROORZLQJ¿JXUHLVDSSOLFDEOHWRWKH2XWGRRUXQLWVRI : GWHD(42)NK3AO
450
191
99
631
362
121 76
440
401
1103
1087
1015
3.5 Installation Clearance Data
Installation Space Requirements of the Outdoor Unit: GWHD(36)NK3AOǃGWHD(42)NK3AO
˚
˚
˚
˚
˚
˚
˚
37
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
4 INDOOR UNIT INSTALLATION
4.1 Installation of Duct Type
4.1.1 Before Installation
Check if there is any damage to the indoor unit, and the wireless controller and other part and components are
prepared completely.
4.1.2 Installation Site
Ɣ7KHVHOHFWLRQRIWKHLQVWDOODWLRQSODFHRIWKHDLUFRQGLWLRQHUXQLW
The installation must accord with the national and local safe criterion.
Since the quality of installation would affect the operation directly, user should contact the seller
and have the conditioner installed and tested by the professional install personnel according to the install
instruction instead of install by himself/herself.
2QO\FRQQHFWWKHSRZHUDIWHUDOOWKHLQVWDOODWLRQZRUNVDUH¿QLVKHG
Ɣ7KHVHOHFWLRQRIWKHLQVWDOODWLRQSODFHRIWKHLQGRRUXQLW
ƹ Prevent direct sun burn.
ƹ Make sure that the top steeve, ceiling, and the structure of the construction etc. is strong enough to bear the weight
of the unit.
ƹ The drainage pipe is easy to drain.
ƹ 7KHDLUÀRZLVQRWEORFNHGDWWKHRXWOHWDQGLQWDNHYHQWV
ƹ The connecting pipe indoor and outdoor can by lead to outside conveniently.
ƹ7KHXQLWFDQQRWEHLQVWDOOHGLQWKHSODFHZKHUHVWRUHGWKHÀDPPDELOLW\HDV\H[SORGHGWKLQJRUWKHSODFHZKHUH
ZRXOGKDYHOHDNDJHRIÀDPPDELOLW\DQGH[SORGHGJDV
ƹ The unit cannot be installed in the place where has the corrupt gas and serious dust, saline fog, lampblack and
huge humidity.
Note:
The air conditioner unit installed in the following place may have malfunction, if the malfunction cannot prevent,
please contact the Nominated Repair Center Of Gree Electric Appliances, Inc. Of Zhuhai.
a. The place with greasy all around;
b. The seashore place with salinity and alkali;
c. The place with vulcanized gas( such as vulcanized hot spring);
d. The place with high frequency equipment ( such as wireless equipment, electric welding machine and medical
treatment equipment);
e. The place with special environment.
4.1.3 Caution for Installation
ƹ Ensure the hanger is strong enough to withstand the weight of the unit.
ƹ The drainage of the drain pipe is easy.
ƹ No obstacle is in the inlet/outlet and the air circulation is in good condition.
ƹ Ensure the installation space is left for the access to maintenance.
ƹ,WVKRXOGEHIDUDZD\IURPZKHUHWKHUHLVKHDWVRXUFHOHDNDJHRILQÀDPPDEOHH[SORVLYHVXEVWDQFHVRUVPRJ
ƹ It is the ceiling type unit (concealed in the ceiling).
ƹ The power cords and connection lines of the indoor and outdoor units must be at least 1m away from the TV set
or radio to avoid the image interference and noise ( even if 1m is kept, the noise may be produced due to the strong electric
wave).
4.1.4 Dimension Data
NoteWKHXQLWLQWKHIROORZLQJV¿JXUHVLVPPXQOHVVRWKHUZLVHVSHFL¿HG
Applicable to GFH(09)EA-K3DNA1A/I,GFH(12)EA-K3DNA1A/I,GFH(18)EA-K3DNA1A/I, GFH(21)EAK3DNA1A/I, GFH(24)EA-K3DNA1A/I:
38
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
Table Outline Dimensions:
Item
Model
GFH(09)EA-K3DNA1A/I
A
B
C
D
E
F
G
H
I
J
742
491
662
620
700
615
782
156
200
635
942
491
862
820
900
615
982
156
200
635
1142
491
1062
1020
1100
615
1182
156
200
635
GFH(12)EA-K3DNA1A/I
GFH(18)EA-K3DNA1A/I
GFH(21)EA-K3DNA1A/I
GFH(24)EA-K3DNA1A/I
4.1.5 Installation Clearance Data
Nut with washer
Spring pad
˚500
˚250
a. Installation of the Indoor Unit
Insert the M10 expansion bolt into the hole, and then knock the nail into the bolt. Refer to the Outline Dimension
Drawings of the Indoor Unit for the distance between holes and see Fig.3 for the installation of the expansion bolt.
Install the hanger on the indoor unit:
39
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
Hanger bolt
Air conditioning unit
Anchor
Install the indoor unit on the ceiling:
CUATION:
a. Prior to the installation, please make a good preparation for all piping (refrigerant pipe, drain pipe) and wiring
(wires of the wired controller, wires between the indoor and outdoor unit) of the indoor unit to make the further installation
much easier.
b. ,IWKHUHLVDQRSHQLQJLQWKHFHLOLQJLWLVEHWWHUWRUHLQIRUFHLWWRNHHSLWÀDWDQGSUHYHQWLWYLEUDWLQJ&RQVXOWWKH
user and builder for more details.
c. ,IWKHVWUHQJWKRIWKHFHLOLQJLVQRWVWURQJHQRXJKDEHDPPDGHRIDQJOHLURQFDQEHXVHGDQGWKHQ¿[WKHXQLWRQ
it.
d. If the indoor unit is not installed in the air conditioning area, please use sponge around the unit to prevent
condensing. The thickness of the sponge depends on the actual installation environment.
4.1.6 Horizontality Check of the Indoor Unit
After the installation of the indoor unit, its horizontality must be checked to make sure the unit keep horizontal fore
and aft and keep an inclination of 5° toward the drain pipe right and left.
Fig.6
4.1.7 Installation of the Air Supply Duct
a. Installation of the Rectangular Air Supply Duct
40
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
Table
No.
Name
No.
Name
1
Hanger
5
Filter Screen
2
Return Air Duct
6
Main Air Supply Duct
3
Canvas Duct
7
Air Supply Outlet
4
Return Air Inlet
8
Plenum Box
b. Installation of the Round Air Supply Duct
1
2
3
4
5
6
7
8
9
Table
No.
Name
No.
Name
1
Hanger
6
Transition Duct
2
Return Air Duct
7
Air Supply Duct
3
Canvas Duct
8
Diffuser
4
Return Air Louver
9
Diffuser Joint
5
Air Supply Outlet
c. Installation Steps of the Round Air Supply Duct
3UHLQVWDOOWKHRXWOHWRIWKHURXQGGXFWRQWKHWUDQVLWLRQGXFWDQGWKHQ¿[LWE\WKHVHOIWDSSLQJVFUHZ
3ODFHWKHWUDQVLWLRQGXFWWRWKHDLURXWOHWRIWKHXQLWDQG¿[LWZLWKULYHW
3) Connect the outlet to the duct and then tighten them with tape. Other installation details are not covered herein.
CUATION:
a. The maximum length of the duct means the maximum length of the air supply duct plus the maximum length of
the return air duct.
b. For the unit with the auxiliary electric heating function, if the round duct is to be adopted, then the straight length
of the transition duct can not be less than 200mm.
c. The duct is either rectangular or round and connected with the air inlet/outlet of the indoor unit. Among all air
supply outlets, at least one should be kept open. As for the round duct, it needs a transition duct of which the size should
PDWFKZLWKWKHDLUVXSSO\RXWOHWRIWKHXQLW$IWHUWKH¿WWLQJRIWKHWUDQVLWLRQGXFWLWLVWKHWXUQRIWKHURXQGGXFWZKLFKLV
better to be kept 10 meters far away from the corresponding diffuser. The standard accessories supplied by GREE is the
WUDQVLWLRQGXFWPPORQJDQGURXQGDLURXWOHWijKRZHYHUWKRVHRIRWKHUVSHFL¿FDWLRQVFDQEHSXUFKDVHG
4.2 Installation of Cassette Type
4.2.1 Before Installation
Check if there is any damage to the indoor unit, and the wireless controller and other part and components are
prepared completely.
4.2.2 Installation Site
Select install location of the indoor unit
a. 2EVWUXFWVKRXOGSXWDZD\IURPWKHLQWDNHRURXWOHWYHQWRIWKHLQGRRUXQLWVRWKDWWKHDLUÀRZFDQEHEORZQWKRXJK
all the room.
b. Make sure that the installation had accord with the requirement of the schematic diagram of installation spaces.
c. Select the place where can stand 4 times of the weight of the indoor unit and would not increase the operating
noise and oscillate.
d. The horizontally of the installation place should be guaranteed.
e. Select the place where easy drain condensated coagulated water, and easy connect with outdoor unit.
41
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
f. Make sure that there are enough space for care and maintenance. Make sure that the weight between the indoor
unit and ground is above 1800mm.
g. When installing the steeve bolt, check if the install place can stand the weight 4 times of the unit’s. If not,
UHLQIRUFHEHIRUHLQVWDOODWLRQ5HIHUWRWKHLQVWDOOFDUGERDUGDQG¿QGZKHUHVKRXOGEHUHLQIRUFHG
Note!
There will be lots of lampblack and dust stick on the acentric, heat exchanger and water pump in dining room and
kitchen, which would reduce the capacity of heat exchanger, lead water leakage and abnormal operation of the water pump.
The following treatment should be taken under this circumstance:
a. Ensure that the smoke trap above cooker has enough capacity to obviate lampblack to prevent the indraft of the
lampblack by the air conditioner.
b. Keep the air conditioner far from the kitchen so that the lampblack would not be indraft by the air conditioner.
ƾ Important notice:
ƹ To guarantee the good performance, the unit must be installed by professional personnel according with this
instruction.
ƹ Please contact the local Gree special nominated repair department before installation. Any malfunction caused
by the unit that is installed by the department that is not special nominated by GREE would not deal with on time by the
inconvenience of the business contact.
4.2.3 Dimension Data
780( Gaps between hoisting screw rods)
840( Indoor unit)
890*(Ceiling opening)
950( Decorated surface boards )
Dimension of ceiling opening and location of the hoisting screw (M10)
Refrigerant pipe
Hoisting screw (X4)
680(Gaps between hoisting screw rods)
840( Indoor unit )
890(Ceiling opening )
950(Decorated surface boards )
A
Install dimension of mode
GKH(12)BA-K3DNA1A/I\;GKH(18)BA-K3DNA1A/I; GKH(24)BA-K3DNA1A/I
42
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
650
570
400
570 604 650
Install dimension of mode GKH(12)BA-K3DNA2A/I;GKH(18)BA-K3DNA2A/I
ƹ The drilling of holes in the ceiling must be done by the professional personnel.
(160)
Installation stands for main body of the unit
Ceiling
Above 20
Notes: The dimension for the ceiling openings with * marks can be as large as 910mm. But the overlapping sections
of the ceiling and the decorated surface boards should be maintained at no less than 20mm.
2.2.4 Installation Clearance Data
GKH(12)BA-K3DNA1A/I\;GKH(18)BA-K3DNA1A/I; GKH(24)BA-K3DNA1A/I
H
˚
Wall
surface
Wall
surface
Wall
surface
ı
ı
ı
Model
GKH(12)BA-K3DNA1A/I
GKH(18)BA-K3DNA1A/I
GKH(24)BA-K3DNA1A/I
unit:mm
H
260
Ground
surface
43
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
GKH(12)BA-K3DNA2A/I;GKH(18)BA-K3DNA2A/I
H
˚
Wall
surface
Wall
surface
Wall
surface
ı
ı
ı
unit:mm
Model
H
GKH(12)BA-K3DNA2A/I
GKH(18)BA-K3DNA2A/I
260
Ground
surface
ƾ Main body of hoisting air conditioner
a. The primary step for install the indoor unit.
ƹ When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper and lower of the
KRLVWLQJVWDQGWR¿[LW7KHXVHRIJDVNHWDQFKRUERDUGFDQSUHYHQWJDVNHWEUHDNRII
b. Use install cardboard
ƹ Please refer to the install cardboard about the dimension of ceiling opening.
ƹ The central mark of the ceiling opening is marked on the install cardboard.
ƹ,QVWDOOWKHLQVWDOOFDUGERDUGRQWKHXQLWE\EROWSLHFHDQG¿[WKHDQJOe of the drainage pipe at the outlet vent by
bolt.
c. Adjust the unit to the suitable install place.
d. Check if the unit is horizontal.
ƹ Inner drainage pump and bobber switch are included in the indoor unit, check if 4 angle of every unit are
KRUL]RQWDOE\ZDWHUOHYHU,IWKHXQLWLVVODQWWRZDUGWKHRSSRVLWHRIWKHFRDJXODWHZDWHUÀRZWKHUHPD\EHPDOIXQFWLRQRI
the bobber switch and lead water drop.)
e. Backout the gasket anchor board used to prevent gasket break off and tighten the nut on it.
f. Backout the install cardboard.
Note!
ƔPlease do tighten the nuts and bolts to prevent air conditioner break off.
ƾ Connection of the refrigerant pipe
ƹ When connect the pipe to the unit or backout it from the unit, please do use both spanner and torque wrench.
44
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
ƹ:KHQFRQQHFWVPHDUERWKLQVLGHDQGRXWVLGHRIWKHÀDUHQXWZLWKIUHH]HPRWRURLOVFUHZLWE\KDQGDQGWKHQ
tighten it with spanner.
ƹ Refer to form 1 to check if the wrench had been tightened (too tight would mangle the nut and lead leakage).
ƹ Examine the connection pipe to see if it had gas leakage, then take the treatment of heat insulation, as shown in
WKH¿J
ƹ Only use median sponge to entwine the wiring interface of the gas pipe and heat preservation sheath of the gas
collection tube.
Smear freeze motoroil
here
Median sponge (attachment)
(entwine the wiring interface
with seal mat)
Thread fasten(x4)
Torque wrench
Heat preservation
sheath of liquid inlet
tube (attachment) (for
liquid tube)
Spanner
Wiring interface
Flare nut
Gas collection tube
Liquid inlet tube
Heat preservation
sheath of gas collection
tube (attachment)(for
gas tube)
Form 1: The tightening torque needed for tightening nut
Diameter˄Inch˅
Surface thickness˄mm˅
Tightening torque (N·m)
ij’’
ı 0.5
15-30 (N·m)
ij’’
ı 0.71
30-40 (N·m)
ij’’
ı1
45-50 (N··m)
ij’’
ı1
60-65 (N·m)
ij’’
ı1
70-75 (N··m)
ƾ Drainage hose
a. Install the drain hose
ƹ The diameter of the drain hose should be equal or bigger than the connection pipe’s. ( The diameter of polythene
pipe: Outer diameter 25mm Surface thickness ı 1.5mm)
ƹ Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of air bubble.
ƹ If drain hose cannot has enough drooping gradient, drain raising pipe should be added.
ƹ To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m.
ƹ Use the drain hose and clamp attached. Insert the drain hose to the drain vent, and then
tighten the clamp.
ƹ Entwine the big sponge on the clamp of drain hose to insulate heat.
ƹ Heat insulation should be done to indoor drain hose.
45
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
Sponge(attachment)
Clamp(attachment)
Clamp
Sponge (gray)
Drain hose
Below 4mm
Drain stepup pipe note
ƹ The install height of the drain raising pipe should less than 280mm.
ƹ The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond 300mm.
Instruction
ƹ The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t has to endure
the unnecessary outside force.
ƹ Please install the drain hose according to the following process if several drain hoses join together.
b. Check the smoothness of drain after installation.
ƹ Check the drain state by immitting 600cc water slowly from the outlet vent or test hole.
ƹ Check the drain in the state of refrigerating after installation of the electric circuit.
46
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
4.3 Installation of Floor Ceiling Type
4.3.1 Before Installation
Check if there is any damage to the indoor unit, and the wireless controller and other part and components are
prepared completely.
4.3.2 Installation Site
Selection of Installation Location for Air Conditioner Unit
The installation of air conditioner unit must be in accordance with national and local safety codes.
Installation quality will directly affect the normal use of air conditioner unit. The user is prohibited
from installation by himself. Please contact your dealer after buying this machine. Professional
installation workers will provide installation and test services according to installation manual.
Do not connect to power until all installation work is completed.
Selection of Installation Location
ƹ Such a place where cool air can be distributed throughout the room.
ƹ Such a place where is condensation water is easily drained out.
ƹ Such a place that can handle the weight of indoor unit.
ƹ Such a place, which has easy access for maintenance.
ƹ Such a place where is permitting easy connection with the outdoor unit.
ƹ Such a place where is 1m or more away from other electric appliances such as television, audio device, etc.
ƹ $YRLGDORFDWLRQZKHUHWKHUHLVKHDWVRXUFHKLJKKXPLGLW\RULQÀDPPDEOHJDV
ƹ Do not use the unit in the immediate surroundings of a laundry, a bath, a shower or a swimming pool.
ƹ Be sure that the installation conforms to the installation dimension diagram.
4.3.3 Dimension Data
H
When installing the indoor unit, you can refer the paper pattern for installation, and make sure that the drainage side
PXVWEHPPORZHUWKDQWKHRWKHUVLGHLQRUGHUWRGUDLQWKHFRQGHQVDWLRQZDWHUÀXHQWO\
Unit:mm
A
B
D
C
Model
A
B
H
C
D
1220
225
700
1158
280
GTH(09)BA-K3DNA1A/I
GTH(12)BA-K3DNA1A/I
GTH(18)BA-K3DNA1A/I
GTH(24)BA-K3DNA1A/I
4.3.4 Installation Clearance Data
a. Space dimension for installation of the unit
The space around the unit is adequate for ventilation .
47
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
b. Important Notice
ƹ The unit must be installed by the professional personnel according to this install instruction to ensure the well use.
Please contact the local Gree special nominated repair department before installation. Any malfunction caused
by the unit that is installed by the department that is not special nominated by Gree would not deal with on time by the
inconvenience of the business contact.
ƹ It should be done by professional personnel when the air conditioner unit is moved to other place.
c. There are 2 styles of installation
ˆ Ceiling type
ˆ Floor type
1) Each type is similar to the other as follows:
Determine the mounting position on ceiling or wall by using paper pattern to indicate indoor frame. Mark the pattern
and pull out the paper pattern. (Refer to ķ )
ķĸ
2) Remove the return grill, the side panel and the hanger bracket from the indoor unit as per procedure bellow.
ƹ 3UHVVWKH¿[LQJNQRERIWKHDLULQWDNHJULOOVWKHJULOOHVZLOOEHRSHQHGZLGHUDQGWKHQSXOOWKHPRXWIURPWKH
indoor.
ƹ 5HPRYHWKHVLGHSDQHO¿[LQJVFUHZDQGSXOOWRWKHIURQWGLUHFWLRQDUURZGLUHFWLRQWRUHPRYH6LGHSDQHO¿[LQJ
screw (Refer to ĸ ).
ƹ /RRVHQWZRKDQJHUEUDFNHWVHWWLQJEROWV0RQHDWKVLGHIRUOHVVWKDQPP5HPRYHWZRKDQJHUEUDFNHW¿[LQJ
bolts (M6) on the rear side. Detach the hanger bracker by pulling it backward (Refer to ĺ ).
3) Set the suspension bolt. (Use W3/8 or M10 size suspension bolts)
Adjust the distance from the unit to the ceiling slab beforehand (Refer to Ĺ )
4) Fix the hanger bracket to the suspension bolt.
Warning ʽ
ƹ Make sure that extended suspension bolt from the ceiling stays inside the arrowed position. Readjust the hanger
48
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
bracket when it is outside the arrowed position. (Refer to Ļ )
ƹ Suspension bolt stays inside the cap of indoor unit. Never remove the cap.
5) Lift the unit and slide forward unit the dent. (Refer to ļ )
6) Screw tightly both hanger bracket-setting bolts (M8). (Refer to ĺ )
6FUHZWLJKWO\ERWKKDQJHUEUDFNHW¿[LQJEROWV0WRSUHYHQWWKHPRYHPHQWRIWKHLQGRRUXQLW5HIHUWR ĺ )
8) Adjust the height so that rear side of the drainpipe slightly inclines to improve drainage.
Caution ʽ
ƹ Adjust the height by turning the nut with a spanner.
ƹ Insert the spanner from the hanger bracket opening. (Refer to Ľ )
In case of hanging
It is possible to install using inward facing hanger brackets by not removing the brackets from the indoor unit. (Refer
to ľ )
%HVXUHWRXVHRQO\WKHVSHFL¿HGDFFHVVRULHVDQGSDUWVIRULQVWDOODWLRQZRUN
Celling
Hanger bracket
40 or less
Hanger bracket
setting bolt(M8)
Suspension bolt
Hanger bracket
fixing bolt(M6)
Hanger bracket
Ĺ
Celling slab
ĺ
BOLT POSITION
INWARD
Hanger bracket
Ļ
Ľ
ļ
ľ
49
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
5 REFRIGERATION PIPING WORK
5.1 Connection between Indoor and Outdoor Units
a. Wiring of the Power Cord
CUATION ʽ
A breaker must be installed, capable of cutting off the power supply for the whole system.
1) Open the side plate.
2) Let the power cord go through the rubber ring.
3) Connect the power card to the terminals “L”, “N” and also the earthing bolt, and then connect the wiring terminals
“N(1),2,3” of the indoor unit to those of the outdoor unit correspondingly.
4) Fix the power cord with wire clips.
b. Capacity Level and Capacity Code of the Indoor and Outdoor Units
Indoor Unit
Capacity Level
Capacity Code
09
25
12
35
18
50
21
60
24
71
36
100
42
120
Outdoor Unit
ƹ2QHRXWGRRUXQLWLVFDSDEOHRIGULYLQJ¿YHDWPD[LPXPDQGWZRDWPLQLPXPLQGRRUXQLWV
ƹTotal capacity of the indoor units can be among 50%-150% of that of the outdoor unit.
1) The outdoor unit with capacity level 36 can drive up to four sets of indoor units, while the outdoor unit 42 can
GULYHXSWR¿YH
2) The sum of the capacity codes of the indoor units should be among 50%-150% of that of the outdoor unit.
c. Allowable Length and Height Fall of the Refrigerant Pipe
Allowable Length
Refrigerant Pipe
36
42
36
42
Total Length(m)
70
80
L1+L2+L3+ L4
L1+L2+L3+ L4+ L5
Max. Length for Single Unit(m)
20
25
LX
Outdoor unit and indoor unit
15
15
H1
Indoor unit and indoor unit
7.5
7.5
H2
Max. installation
altitude
Dimension of the Refrigerant Pipe of the Indoor Unit
unit:mm
Capacity Level of the Indoor Unit
Gas Pipe
Liquid Pipe
09,12
ij
ij
18
ij
ij
21,24
ij
ij
d. Piping between the Indoor and Outdoor Units
1) Refer to Fig.6 for the moments of torque for tightening screws.
/HWWKHÀDUHHQGRIWKHFRSSHUSLSHSRLQWDWWKHVFUHZDQGWKHQWLJKWHQWKHVFUHZE\KDQG
3) After that, tighten the screw by the torque wrench unit it clatters.
50
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
Pipe
Flare Nut
Pipe
Torque Wrench
Ordinary
4) The bending degree of the pipe can not be too small; otherwise it will crack. And please use a pipe bender to bend
the pipe.
5) Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape.
Moments of Torque for Tightening Screws
Diameter
Wall Thickness˄mm˅
Moment of Torque
ijPP
ı 0.5
15-30(N·m)
ijPP
ı 0.71
30-40(N·m)
ijPP
ı1
45-50(N·m)
ijPP
ı1
60-65(N·m)
CUATION ʽ
a. During the connection of the indoor unit and the refrigerant pipe, never pull any joints of the indoor unit by force;
otherwise the capillary pipe or other pipe may crack, which then would result in leakage.
b. The refrigerant pipe should be supported by brackets, that is, don’t let the unit withstand the weight of it.
CUATION ʽ
For the GMV multi VRF system, each pipe should be labeled to tell which system it belongs to avoid mistaken
inaccurate piping.
e. Installation of the Protection Layer of the Refrigerant Pipe
1) The refrigerant pipe should be insulated by the insulating material and plastic tape in order to prevent condensing
and leaking.
2) The joints of the indoor unit should be wrapped with the insulating material and no gas is allowed on the joint of
the indoor unit.
No gap
CUATION ʽ
After the pipe is protected well enough, never bend it to form a small angle; otherwise it would crack or break
f. Wrapping the pipe with tape:
1) Bundle the refrigerant pipe and electric wire together with tape, and separate them from the drain pipe to prevent
WKHFRQGHQVDWHZDWHURYHUÀRZLQJ
2) Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where it enters the wall. During the
wrapping, the later circle should cover half of the former one.
3) Fix the wrapped pipe on the wall with clamps.
CUATION ʽ
a. Do not wrap the pipe too tightly; otherwise the insulation effect would be weakened. Additionally, make sure the
drain hose is separated from the pipe
b. $IWHUWKDW¿OOWKHKROHRQWKHZDOOZLWKVHDOLQJPDWHULDOWRSUHYHQWZLQGDQGUDLQFRPLQJLQWRWKHURRP
51
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
5.2 Refrigerant Charging and Trial Running
a. Refrigerant Charging
1) The refrigerant has been charged into the outdoor unit before shipment, while additional refrigerant still need be
FKDUJHGLQWRWKHUHIULJHUDQWSLSHGXULQJWKH¿HOGLQVWDOODWLRQ
2) Check if the liquid valve and the gas valve of the outdoor unit are closed fully.
$VVKRZQLQWKHIROORZLQJ¿JXUHH[SHOWKHJDVLQVLGHWKHLQGRRUXQLWDQGUHIULJHUDQWSLSHRXWE\WKHYDFXXP
pump.
Manometer
Manometer
“HI” knob
“LO” knob
Vacuum pump
Hose
Gas Valve
4) When the compress is not running, charge the R410A refrigerant into the refrigerant pipe from the liquid valve of
the outdoor unit (do not do it from the gas valve)
b. Calculation of the Additional Refrigerant Charge
1) Refrigerant Charge in the Outdoor Unit before Shipment
Model
GWHD(36)NK3AO
GWHD(42NK3AO
Refrigerant Charge (kg)
3.6
4.8
Notes˖
a. The refrigerant charge mentioned in the table above is not included those charged additionally in the indoor unit
and the refrigerant pipe.
b. The amount of the additional refrigerant charge is dependent on the diameter and length of the liquid refrigerant
pipe which is decided by the actual yield installation requirement.
c. Record the additional refrigerant charge for future maintenance.
2) Calculation of the Additional Refrigerant Charge
If the total refrigerant pipe length (liquid pipe) is smaller than that listed in the table below, no additional refrigerant
will be charged.
Model
Total Liquid Pipe Lenght (a+b+c+d+e)
GWHD(36)NK3AO
İ 40m
GWHD(42)NK3AO
İ 50m
$GGLWLRQDO5HIULJHUDQW&KDUJH ™([WUD/LTXLG3LSH/HQJWKîJP(liquid pipe 1/4''
Note: if the total refrigerant pipe length is larger than that listed in the table above, the additional refrigerant for the
extra length of the pipe needs to be charged as per 22g/m.
3) Example : GWHD (42) NK3AO
e
d
c
b
a
Indoor Unit
52
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
Serial No.
Model
Indoor Unit Ļ
Ducted Type GFH(09)EA-K3DNA1A/I
Indoor Unit ĺ
Ducted Type GFH(09)EA-K3DNA1A/I
Indoor Unit Ĺ
Ducted Type GFH(09)EA-K3DNA1A/I
Indoor Unit ĸ
Ducted Type GFH(09)EA-K3DNA1A/I
Indoor Unit ķ
Ducted Type GFH(18)EA-K3DNA1A/I
Liquid Refrigerant Pipe
Serial No.
e
d
c
b
a
Diameter
ij
ij
ij
ij
ij
Length
20m
20m
15m
5m
5m
The total length of each liquid refrigerant pipe is: e+d+c+b+a=20+20+15+5+5=65m. Thus, the minimum additional
refrigerant charge=(65-50)×0.022=0.33kg (Note: no additional refrigerant is needed for the liquid pipe within 50m).
4) Additional Refrigerant Charge Record
Indoor Unit
No.
Indoor Unit Model
Additional Refrigerant Charge(kg)
1
2
……
N
Total
Refrigerant Pipe
Diameter
Total Length(m)
Additional Refrigerant Charge(kg)
ĭ
ĭ
ĭ
ĭ
Total
c. Items to be checked after the Installation
Items to be Checked
Possible Errors
Has each part and component the of unit
installed securely?
The unit may fall off, vibrate or generate noise.
Has the gas leakage test been taken?
The cooling (heating) capacity may be poor.
,VWKHWKHUPDOLQVXODWLRQVXI¿FLHQW"
Dews and water drops may be generated.
Does the drainage go well?
Dews and water drops may be generated.
Is the actual power voltage in line with
the value marked on the nameplate?
The unit may break down or some
components may be burnt out.
Are the wiring and the piping correct?
The unit may break down or some
components may be burnt out.
Has the unit been earthed reliably?
There may be a danger of electric shock.
Does the wire meet the regulated requirement?
The unit may break down or the
component may be burnt out.
Is there any obstacle at the air inlet/outlet
of the indoor/outdoor unit?
The cooling (heating) capacity may be poor
Have the length of the refrigerant pipe and
the refrigerant charge been recorded?
It may be hard to know the exact refrigerant charge.
Check Results
53
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
d. Trial Running
1) Check before the Trial Running
ƹ Check if the appearance of the unit and the piping system are damaged during the transportation.
ƹ Check if the wiring terminals of the electronic component are secure.
ƹ Check if the rotation direction of the fan motor is right.
ƹ Check if all valves in the system are fully opened.
2) Trial Running
ƹ The trial running should be carried out by the professionally skilled personnel on the premise that all items listed
above are in normal conditions.
ƹ Let the unit energized and switch the wired controller or the remoter controller to “ON”.
ƹ The fan motor and compressor of the outdoor unit will run automatically in one minute.
ƹ If there is some unusual sound after the compressor is started, turn off the unit for an immediate check.
54
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
6 ELECTRIC WIRING WORK
6.1 Wiring Principle
6.1.1 Itemized Description of Cautions.
The electrical installation must be done by professional electricians.
The electrical installation must be done in accordance with applicable technical codes and other rules.
WARNING!
Please make sure to install earth leakage circuit breaker. Earth leakage circuit breaker must be installed to prevent
HOHFWULFVKRFNRU¿UH
CAUTIONS!
7KHDLUFRQGLWLRQHUPXVWEHVHFXUHO\HDUWKHG,QFRUUHFWHDUWKLQJPD\FDXVHHOHFWULFVKRFNRU¿UH
ƹ All the electric installations must be carried out by specialist technicians in accordance with the local laws, rules
and these instructions.
ƹ The indoor unit and outdoor unit shall use different power supplies. The indoor units under the same system must
EHSRZHUHGE\DXQL¿HGSRZHUVRXUFH$OOWKHLQGRRUXQLWVFDQRQO\EHFRQWUROOHGE\RQHPDVWHUSRZHUVZLWFK5DWHG
supply voltage and special circuit for air conditioner must be used.
ƹ The earthing shall be secure. The earthing wire shall be connected to the special earthing device on the
construction. The installation must be done by specialist technicians. Never connect the earth lead to the gas pipe, water
pipe, lightening rod or telephone earth wire.
ƹ To avoid electric shock or any accident due to mal-operation, the air switch and shock-resistant earth leakage
circuit breaker that can cut off the power supply of the complete system must be installed. The air switch shall have both
the magnetic tripping and thermal tripping functions to ensure protection against the short circuit and overload. Electric
shock or fire might be caused if no installation of earth leakage circuit breaker. Do not switch on the power before
completion of the electrical work. Make sure to cut off the power supply before repair.
ƹ Under no condition could use the capacitor to improve the power factor.
ƹ Please use cable conduit for power cords.
ƹ Do not lay the electronic control cables (remote control and signal line) outside the machine with other cables;
otherwise the machine might become malfunctioned or failed due to electrical noise.
ƹ 7KHSRZHUFRUGPXVWEHDOZD\VFRQQHFWHGWRWKHSRZHUFRUGWHUPLQDOERDUGDQG¿[HGE\XVLQJWKHORFNFRQQHFWRU
LQFOXGHGZLWKWKHPDFKLQH0HDQZKLOHSUHYHQWWKHPIURPFRQWDFWLQJWKH¿WWLQJSLSH7KHGLDPHWHURISRZHUFRUGVVKDOOEH
ODUJHHQRXJK6HHEHORZIRUWKHGHWDLOHGVSHFL¿FDWLRQV7KHGDPDJHGSRZHUFRUGVDQGFRQQHFWLRQOLQHVPXVWEHUHSODFHG
ZLWKWKHGHVLJQDWHGFDEOHV:KHQFRQQHFWLQJWKHFDEOHSOHDVHFRQ¿UPWKDWDOOWKHHOHFWULFDOFRPSRQHQWVLQVLGHWKHHOHFWULF
box shall have no coupling or terminal loosened. (Improper installation of electric box cover may lead to potential water
leakage, which will cause the unit abnormal or short circuit).
ƹ Earth lead must be connected before connecting the power cord. An earth lead longer than the power cord shall be
provided.
ƹ For site wiring, please refer to the circuit diagram attached on the machine body.
6.1.2 Earthing Requirements
7KHDLUFRQGLWLRQHULVFODVVL¿HGLQWRWKH&ODVV,DSSOLDQFHVVRLWVHDUWKLQJPXVWEHUHOLDEOH
7KH\HOORZJUHHQOLQHRIWKHDLUFRQGLWLRQHULVWKHHDUWKOLQHDQGFDQQRWEHXVHGIRURWKHUSXUSRVHFXWRIIRU¿[HG
by the self-tapping screw; otherwise it would cause the hazard of electric shock.
3) The reliable earth terminal should be provided and the earth wire can not be connected to any of the following
places.
ķ Running water pipe;
ĸ Coal gas pipe;
Ĺ Sewage pipe;
ĺ Other places where the professional personnel think unreliable
6.2 Electric Wiring Design
Caution: The power of every indoor unit should be connected in outdoor unit.
a. Open surface panel.
b. Remove the electrical box cover.
c. Route the power connection cord from the back of the indoor unit and pull it toward the front through the wiring
hole upward.
d. Connect the wiring (communication) through the piping hole of the chassis and the bottom of the appliance
upward, then connect the brown wire to the Terminal board “3”;black wire(the communication wire) to the Terminal
board“2”;blue wire to the Terminal board“N(1)”,and connect the earthing wire to the screw terminal on the electric box.
55
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
Clamp them with the corresponding wire clamp packed in the chassis;
e. Reassemble the electrical box cover.
f. Recover the surface panel.
g. The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper
tube.
GWHD(36)NK3AO
POWER
INDOOR UNITA
INDOOR UNITB
INDOOR UNITC
INDOOR UNITD
N L
1
OUTDOOR UNIT
GWHD(42)NK3AO
INDOOR UNIT D
XT5
INDOOR UNIT C
XT4
INDOOR UNIT B
XT3
INDOOR UNIT A
XT2
OUTDOOR UNIT
INDOOR UNIT E
XT6
L
POWER
N
XT1
Caution ʽ
a. The incorrect of wiring connecting would lead malfunction of some of the electric elements.
b. 0DNHVXUHWKDWWKHOHDGEHWZHHQWKHFRQQHFWHQGDQGWKHFODPSHQGKDVVRPHQHHGVSDFHDIWHUWKHZLUHLV¿[HG
c. The appliance shall be installed in accordance with national wiring regulations.
Noise Precautions
56
: http://splitoff.ru/tehn-doc.html
Free Match
Service Manual
1) The air conditioning unit should be installed where ventilation is in good condition, otherwise the working
capability of the unit would be reduced or working noise would be increased.
2) The air conditioning unit should be installed on the base frame which is stable and secure uncouth to withstand
the weight of the unit; otherwise it would incur vibration and noise.
3) During the installation, a consideration should be taken that the produced hot air or noise should not affect
neighbors and surroundings.
4) Do not stack obstacles near the air outlet of the outdoor unit; otherwise it would reduce the working capability of
the unit or increase the working noise.
5) In the event of the occurrence of abnormal noise, please contact the sales agent as soon as possible.
Accessories for Installation
Refer to the packing list for the accessories of the indoor and outdoor units respectively.
6SHFL¿FDWLRQRI3RZHU6XSSO\:LUHDQG$LU6ZLWFK
1) The installation must be done in accordance with the national wiring regulations.
2) Only the power cord with the rated voltage and exclusive circuit for the air conditioning can be used.
3) Do not pull the power cord by force.
4) The electric installation should be carried out by the professional personnel as instructed by the local laws,
regulations and also this manual.
5) The diameter of the power cord should be large enough and once it is damaged it must be replaced by the
dedicated one.
6) The earthing should be reliable and the earth wire should be connected to the dedicated device of the building by
the professional personnel. Besides, the air switch coupled with the leakage current protection switch must be equipped,
which is of enough capacity and of both magnetic and thermal tripping functions in case of the short circuit and overload.
Models
Power Supply
Capacity of the Air Switch
Recommended Cord
˄pieces× sectional area˅
GWHD(36)NK3AO
220-240V~ 50Hz
32A
6mm2×3
GWHD(42)NK3AO
220-240V~ 50Hz
32A
6mm2×3
57
: http://splitoff.ru/tehn-doc.html