Carel heaterSteam is a humidifier that provides precise control of relative humidity levels through steam injection. With advanced features like autotest retry, high-temperature tolerance, and various alarm functions, it ensures reliable operation and prevents potential issues. It finds applications in various industries, including textile, printing, and food processing, where humidity control is crucial. Its user-friendly interface and comprehensive alarm system make it easy to operate and maintain.
advertisement
9
9 alarm alarm dehum.
30% 50% 75% 100% reset
1 2 3 4
Fig. 15.a
x1000
Fig. 15.b
PRG reset
SEL
15. ALARMS AND TROUBLESHOOTING
15.1 Alarm summary table
When an alarm is activated a message identifying the alarm is displayed on the control module.
In the case of potentially dangerous alarms, the control module automatically shuts the humidifi er down.
For some alarm events (see Table 15.a), the signalling of the alarm is accompanied by the activation of an alarm relay, as described in: Other auxiliary contacts.
If the cause of the alarm is no longer valid, the humidifi er and alarm relay output can be reset automatically or manually, according to the type of problem, while the message displayed is deactivated manually by pressing the reset-PRG button.
If no longer active, the alarm status continues to be indicated until the reset-PRG button is pressed.
5
5
Still active alarms can not be reset.
In the type C control module the presence of an alarm is indicated by the lighting up of LED 9 and a combination of the LEDs 5 (Fig. 15.a); in the event of more than one alarm, these are indicated in sequence, at 2 second intervals.
In the type H or T control module, if not in programming phase, in the presence of an alarm LED 9 (see fi g. 15.b) begins fl ashing, while the display 5 indicates the alphanumeric alarm code.
The message is displayed cyclically, for a duration of two seconds, alternating with the measurement normally displayed (if the measurement normally displayed corresponds to a disconnected probe, the measurement is not displayed; this will automatically return to the display if the probe is reconnected).
In the event of more than one alarm, the display indicates all the corresponding codes in sequence, at two second intervals.
The alarm Ec cannot be reset.
In the event of the alarm CL (regular maintenance required), the alarm can be reset only by resetting the hour counter; see Resetting the hour counter.
The alarm E1 may appear in two distinct cases:
1. Malfunction when reading from the parameter memory (typically on start-up)
The default parameters are temporarily recalled, without being saved in the parameter memory (the parameters can be accessed and the correct values restored).
In any case the default parameter recall procedure is recommended; see Recalling the default parameters.
2. Malfunction when writing to the parameter memory (typically on pressing the PRG button)
Any modifi cations made will be cancelled; the parameters can be accessed, the values modifi ed and save operation repeated.
Table 15.a lists the alarm indications, the causes, the conditions and the possible solutions.
The remote terminal column indicates the alarm message that appears on the LCD display of the CAREL
Humivisor remote control panel, if one is connected to the humidifi er.
H and T controller
code displayed
C controller alarm alarm non previsto
30% 50% 75% 100%
1 2 3 4
30% 50% 75% 100%
1 2 3 4
CAREL
Humivisor remote terminal cause
E202 •activation of safety
thermostat
• Klixon activation
•the thp output is open
solution ( once having tried the suggestion, if the problem persists, contact the CAREL service department)
- check the earth current of the heaters, and if replace necessary.
- manually reset the Klixon
- problem dependent mainly on operation without water;
- turn the machine off and, once it has cooled down, reactivate the thermostat on the cylinder cover
after having cleaned the cylinder and the level control, checking the effi ciency of the components;
- check that the electrical and water connections are in order and that the machine is supplied correctly;
- it may be necessary to replace the PTC sensors if installed
E204 contradiction of the fl oat - check the correct supply of water to the cylinder;
- turn the machine off and clean: the cylinder, the level control and the fi ll electrovalve
action
see procedure
“AR”
E205 high conductivity of the supply water reset not available active if Et remain in order at least a minute.
manual
auto available alarm relay only if EE appears during
AR active - turn the machine off and clean the water conductivity measuring electrodes;
- if the problem persists, change the source of the supply water or install a suitable treatment system (demineralisation, even partial);
- the problem will not be resolved by softening the supply water
total shutdown
58 heaterSteam +030222011 - r el. 2.2 - 24.01.2011
H and T controller
C controller alarm alarm alarm alarm
code displayed
not featured
not featured
not featured
not featured
30% 50% 75% 100%
30%
1
30%
1
30%
1
30%
50% 75%
2
50% 75%
2
50% 75%
2
3
3
3
100%
4
100%
4
100%
4
100%
CAREL
Humivisor remote terminal
E211
E213
E214
E215
E231 cause
autotest failed;
probable problems
in: supply water, level
control or electrovalve
• electrical power not
available; on machine
start-up no steam is
produced or the water is not pre-heated
•fl oat locked in high level position.
no water
formation of foam in the cylinder during boiling
high water conductivity
pre-alarm
E221 high ambient humidity
(high temperature in T control)
E222 low ambient humidity
low temperature in T control)
E224 high outlet humidity
E201 internal memory error
solution ( once having tried the suggestion, if the problem persists, contact the CAREL service department)
- ensure that the machine is supplied with water;
- turn the machine off and clean the level control and the fi ll valve
with the machine off and disconnected from mains power supply, check that there are no defective of malfunctioning electrical connections
- check that the supply pipe from the water supply to the humidifi er and the internal pipe is not blocked or choked and that the pressure is suffi cient (1-8 bar);
- check the operation of the fi ll electrovalve;
- check that the steam supply does not have to work
against excessive back-pressure, preventing the fl ow of water into the cylinder due to gravity;
- check that the steam supply pipe is not choked or that there are no pockets of condensation
- the formation of foam is usually due to the presence of surfactants in the water (lubricants, solvents, detergents, water treatment or softening agents) or an excessive concentration of dissolved salts. Drain the water supply line;
- clean the cylinder
- check the conductivity of the supply water;
- if necessary, install a suitable water treatment system;
- the problem will not be resolved by softening the supply water
check the operation of the probe and the limit set by parameter P2
check the operation of the probe and the limit set by parameter P3
check the operation of the outlet probe
contact the CAREL service department
action reset alarm relay see procedure
“AR” see procedure
“AR”
manual
manual
humidifi er disabled after waiting 10 min the alarm is automatically reset and a new fi ll cycle is attempted signal only manual or automatic (if after waiting
10 min the water supply returns)
manual active only on the second
EP or after EE during
AR active only on the second
EP or after EE during
AR active not active
humidifi er disabled signal only signal only signal only
humidifi er disabled
auto available
auto available
auto available
auto available reprogram
CAREL not active active active active active
50% 75%
4 alarm
not featured
1 2 3
not featured
not featured
not featured
not featured
not featured alarm
30% 50% 75% 100%
1 2 3 4
30% 50% 75% 100%
1 2 3 4
E212
E230
user parameter error
hour counter error
with the machine off check that there are no defective or malfunctioning electrical connections
reset the hour counter (see Resetting the hour counter)
E220
E223 outlet probe not connected (if featured)
E225 NTC probe for measuring the water temperature not connected (if featured)
E232
E216
E233
room probe not connected
regular maintenance
signal no drain pre-alarm or fi lter blocked boiler full of water with no humidifi cation demand pre-alarm
check the connection of the probe and the setting of parameter A0 for ON/OFF confi guration (see Reading and programming the parameters)
check the connection of the probe or the setting of parameter A0 (see Reading and programming the parameters)
- check the pre-heating operation and the setting of
parameters b1, b2, b3 (see Reading and programming the parameters);
- check the connections to the terminal block on the cylinder cover
stop the machine and carry out a complete maintenance routine on the humidifi er, resetting the hour counter (see
Resetting the hour counter)
- check the drain valve/pump;
- check if the pipes or the manifold are blocked;
- check if the level sensor is faulty or the pipes are blocked;
- the fi lter inside the boiler may be clogged.
- check if the fi ll valve is leaking;
- check if the high level sensor is dirty.
humidifi er disabled hour counter saving disabled
humidifi er disabled reprogram parameters manual hour counter reset
auto available
humidifi er disabled pre heating disabled signal only
see procedure
“AR” signal only
auto available
auto available
manual
manual
auto available active not active active active active not active active on the second
“Ed” not active alarm
Table 15.a
heaterSteam +030222011 - r el. 2.2 - 24.01.2011
59
Step Description Drain status
1 Stop producOff tion.
Open contactor
2 Drain by time On
3
4
Wait for level to stabilise
Fill water
Off
Off
5 Wait for level to stabilise
Off
6 Drain On
7 Wait for level to stabilise
Off
Fill status Contactor status
Off Off 3 sec
Off
Off
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
15.2 Autotest Retry procedure (Fault tolerance)
AUTOTEST RETRY (“AR”)
Duration Condition that can stop “AR”
No
Display
If at the end of a set time the fl oat is below to the minimum reed, the procedure goes to step 3, otherwise it drains again and then goes to step 3
3 sec
High level sensor active
High level sensor active
Ends when the fl oat reaches the control reed
10 sec
Contradiction of the levels
High level sensor active
The fi ll time exceeds a maximum limit
Contradiction of the levels
High level sensor
EE
EE
EE
EE
Ends when the fl oat reaches the control reed Contradiction of the levels EE
1 sec
High level sensor active
The drain time exceeds a maximum limit
Contradiction of the levels
High level sensor active
EE
Tab. 15.b
NOTE:
- During the Autotest Retry procedure the display shows the code “AR” alternating with the alarm code that triggered the procedure.
- If the PRG button is pressed during the Autotest Retry procedure, the procedure is stopped and normal humidifi er operation resumes.
15.3 Troubleshooting
Problem
The control does not turn on
The humidifi er does not start
Cause
1. no electrical power supply;
2. external switch in position 0 (open);
3. control connectors poorly installed;
4. fuses blown;
5. transformer malfunction.
1. remote ON/OFF contact open (relay/terminals 7I - 8I);
2. the external regulator/humidistat or probe has not been connected correctly;
3. probe/humidistat malfunction;
4. parameters not set correctly;
5. safety thermostat activated;
6. fan circuit breaker activated (H or T control);
The humidifi er fi lls with water
without producing steam
1. steam outlet back-pressure too high;
2. leaking fl ow regulator in the water fi ll electrovalve (with leaks in the water circuit);
3. level control malfunction;
4. cylinder inlet fi lter blocked;
5. lime in the fi ll tank;
6. drain electrovalve malfunction;
Line circuit breaker is activated 1. the line circuit breaker is rated too low;
The humidifi er wets the duct
The humidifi er wets the fl oor below
2. resistors short-circuited
1. the distributor is not installed correctly;
2. the system is rated too high;
3. the humidifi er is active when the duct fan is off;
1. the humidifi er pipe is blocked;
2. the water supply or overfi ll circuit has leaks;
3. the condensate drain pipe does not drain the water back to the fi ll tank;
4. the steam outlet pipe is not properly attached to the cylinder;
Solution
1. check the protection devices upstream of the humidifi er and the mains power supply;
2. close the switch: position I;
3. check that the connector are properly installed on the terminal block;
4. check the state of fuses F1/F2;
5. check that the secondary of the transformer has an output of 24 Vac.
1. close ON/OFF contacts (relay/terminals 7I - 8I);
2. check the external connection;
3. check the external signal;
4. reprogram the parameters correctly;
5. reset the thermostat after having eliminated the cause of the problem;
6. reset the circuit breaker after having eliminated the cause of the problem;
1. check that the steam outlet pipe is not bent or choked;
2. replace the fi ll electrovalve;
3. clean the level control or replace if necessary;
4. clean the fi lter;
5. clean the fi ll tank;
6. check for the presence of 24Vac at the drain electrovalve; clean the drain electrovalve;
1. check that the circuit breaker is rated for a current of at least 1.5 times the rated current of the humidifi er;
2. check, by measuring, the value of the resistors and replace them if necessary
1. check that the steam distributor has been installed correctly;
2. diminish the steam production set on the control;
3. check the connection of the device (fl ow switch or differential pressure switch) linked to the humidifi er for ventilation in the duct (terminals
7I - 8I)
1. clean the pipe in the bottom tank;
2. check the entire water circuit;
3. check the correct positioning of the condensate drain pipe in the fi ll tank;
4. check the fastening of the pipe clamp on the steam outlet pipe;
Table 15.c
60 heaterSteam +030222011 - r el. 2.2 - 24.01.2011
number of heating elements steam connection (
mm)( inch) supply pressure limits (Pa) supply water connection temperature limits (°C)(°fH) pressure limits (MPa) hardness limits (°fH) instant fl ow rate (l/min) (gpm) drain water connection (
mm)( inch) typical temperature (°C)(°fH) instant fl ow rate (l/min)(gpm) environmental conditions ambient operating temperature (°C) ambient operating humidity (% rH) storage temperature (°C) (°fH) storage humidity (% rH) index of protection control type voltage / auxiliary frequency (V / Hz) maximum auxiliary power (VA) probe inputs (general characteristics)
16. HUMIDIFIER TECHNICAL SPECIFICATIONS
model
UR002 UR004 UR006 UR010 UR020 UR027 UR040 UR060
1 1 3 3 6 6 6 9 power to active probes (general characteristics) alarm relay and dehumidifi cation outputs
(general characteristics) remote enabling input (general characteristics) serial communication
30/1.18
0…1500
40/1.57
40 /1.57
2000
G3/4”M
1T40/33.8T104
0.1 to 0.8 (1 to 8 bar)
40
0,6/0.13
0,6/0.13
1,2/0.26
1,2/0.26
4/0.88
4/0.88
4/0.88
10/2.2
5/1.32
40/1.57
100 / 212
22,5/5.94
1T40/33.8T104
10 to 60
-10T70/14T158
5 to 95
IP20
2x40/1.57
URC-URH-URS
24 / 50/60
30 selectable input signal: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 Vdc, 0 to 20 mA,
4 to 20 mA input impedance: 60 k
with signals: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 Vdc
50
with signals: 0 to 20 mA, 4 to 20 mA
24 Vdc (24 Vac rectifi ed), Imax= 250 mA
12 Vdc 5%, Imax= 50 mA
250 V 8 A (2 A)
type of micro-switching action 1C free contact; max. resistance max. 50
; Vmax=24 Vdc; Imax=5 mA two-lead RS485
Table 16.a
heaterSteam +030222011 - r el. 2.2 - 24.01.2011
61
17. SPARE PARTS
Exploded of the cylinder 6-10kg/h ( 13.2-22 lbs/h )
n.
description
1 PTC probe wire terminals
2 NTC Probe
3 Wire terminal bracket
4 NTC well
5 Power connection protection cover
6 Cylinder cover
8 Cylinder gasket
11 Cylinder cover locking clamp
7 PTC probe
9 Heating elements: with antiadherent fi lm without antiadherent fi lm 208V
230V
400V
460V
575V
10 Heating element centring spring 13C453A048
12 Cylinder
13 Filter, ring nut and pipe union
Gasket kit
208V
230V
400V
460V
575V
Spare Parts Code
UR006 – 1 ~ * UR006 – 3~** UR010 – 3~**
URKTB00000
URKNTC0000
URK0000022
URKNTCCAS1
URKCOPC00M
URKH00A347
URKH00A320
URKH00R347
URKH00R320
URKG100000
URKBR00000
URKPTCS000
URKH00A347
URKH00A320
URKH00A320
URKH00A344
URKH00A341
URKH00R347
URKH00R320
URKH00R320
URKH00R344
URKH00P341
----
URKB100000
UEKF000000
URKG00000M
URKH00A346
URKH00A322
URKH00A322
URKH00A347
URKH00A342
URKH00R346
URKH00R322
URKH00R322
URKH00R347
URKH00R342
Tab. 17.a
Fig. 17.a
62 heaterSteam +030222011 - r el. 2.2 - 24.01.2011
Exploded of the cylinder 2-4 kg/h ( 4.4 - 8.8 lbs/h)
n.
description
1 NTC probe
2 NTC well
3 PTC probe wire terminals
4 Terminal fastening bracket
5 Power connection protection cover
6 Cylinder cover
8 Cylinder gasket
10 Cylinder cover locking clamp
7 PTC probe
9 Heating elements: with antiadherent fi lm without antiadherent fi lm
208V
230V
208V
230V
11 cylinder
12 fi lter, ring nut and pipe union
13
Gasket kit
Spare Parts Code
UR002
URKNTC0000
UR004
URKNTCCAS2
URKTB00000
URK0000022
URKCOPC00S
URKG100000
URKBR00000
URKPTCS000
URKH00A348
URKH00A348
URKH00R348
URKH00R348
URKH00A349
URKH00A349
URKH00P349
URKH00P349
URKB040000
UEKF000000
URKG00000M
Tab.le17.b
heaterSteam +030222011 - r el. 2.2 - 24.01.2011
63
Fig. 17.b
Exploded of the cylinder 20-27-40-60 kg/h 44.1-59.5-88.1-132.3 lbs/h )
Spare Parts Code
UR020 n.
description
1 Heating element protection
2 PTC probe
UR027 UR040
----
URKPTCL000
3 PTC probe wire terminals
4 Cylinder cover
5 Anti-foaming system
6 Heating element assembly
7 Cylinder gasket
8 Heating element with antiadherent fi lm 208V
230V
400V without antiadherent fi lm
460V
575V
208V
230V
400V
460V
575V
9 Heating element centring spring
10 Cylinder
11 NTC probe
12 Use fi lter
13 Use fl ange
14 Pump fastening braket
15 Drain pump
Gasket kit
UR060
URKTB00000 URKTB00000 URKTB00000 URKTB00000
URKCOP4000 URKCOP4000 URKCOP4000 URKCOP6000
---
URKG400000
6 x
URKH00A382
URKFS00000
--
URKG400000
--
URKG400000
6 x
URKH00A383
6 x
--
URKG600000
9 x
URKH00A381
URKH00A381
URKH00A382
URKH00A382 URKH00A387 URKH00A387
URKH00A390
URKH00A389
URKH00A386
URKH00A385
URKH00R382
URKH00R381
URKH00R381
URKH00A381
URKH00A380
URKH00R383
URKH00R382
URKH00R382
URKH00A390
URKH00A389
URKH00R387
URKH00R386
URKH00R385
URKH00R381
URKH00R380
URKB270000
URKH00R390
URKH00R389
----
URKB400000
URKNTC0000
URKF0000XL
URKFLAN000
URKFLAN000
KITPSR0000
URKG0000XL
URKH00R387
URKH00R390
URKH00R389
URKB600000
URKG000XXL
Table17.c
Fig. 17.c
64 heaterSteam +030222011 - r el. 2.2 - 24.01.2011
17.a Maintenance of the other plumbing components
IMPORTANT WARNINGS: do not use detergents or solvents to clean the plastic components. To remove the deposits use a 20% acetic acid solution, then rinse thoroughly with water.
Water parts ur 2-10kg/h ( 4.4 - 22 lbs/h) n.
description
1
2 tank
Supply pipe
3
4
Fill electrovalve
Level control:
4a sensor cap
4b o-ring
4c sensor fl oating
6
7
8
4d sensor pipe
4e control board
5 Drain electrovalve
A/D manifold (fi ll - drain)
Drain pipe
Overfl ow pipe
Spare part codes
UR002 to UR004 UR006 to UR010
URKT00000S
UEKVASC000
URKT00000M
KITVC00006
URKSL00004
KITVC0012
URKDRAIN00
URKT00000S
URKDRAIN00
URKT00000M
Table 17.d
Fig. 17.d
Water parts ur 20-27-40-60 kg/h
( 44.1-59.5-88.1-132.3 lbs/h )
Spare part codes n.
description
1
2
3
Overfl ow pipe
Drain column
Supply pipe
4 Level control:
4a Sensor cap
4b o-ring
4c sensor fl oating
4d sensor pipe
4e control board
5 Drain pump
6 Fill electrovalve
7 Drain tank
UR020
URKT0000XL
--
UR027 UR040
URKDC00000
URKT0000XL URKT000XXL
URKSL00004
KITPSR0000
KITVC00040
---
UR060
URKT000XXL
KITVC00100
--
Table 17.e
• Fill electrovalve (Fig. 17.d, part. no. 3 - Fig. 17.e, part. no. 6)
After having disconnected the cables and the pipe, remove the electrovalve and check the state of the inlet fi lter, cleaning it if necessary using water and a soft brush.
• Supply and drain manifold (Fig. 17.d, part. no. 6)
Check that there are no solid residues at the cylinder coupling; remove any impurities.
Check that the O-ring is not damaged or cracked; replace it if necessary.
• Drain electrovalve / drain pump (Fig. 17.d, part. no. 5 – Fig. 17.e, part. no.5)
Disconnect the power cables, remove the bobbin and remove the valve block after having unscrewed the two fastening screws from the manifold; remove any impurities and rinse; as regards the pump it is suffi cient to screw the clamping screw and remove possible impurities;
• Fill tank (Fig. 17.d, part. no. 1)
Check that there are no blockages or solid particles and that the conductivity measuring electrodes are clean, remove any impurities and rinse.
• Supply, fi ll, overfi ll pipe (Fig. 17.a, part. no.2-8 – Fig. 17.e, part. no. 3-1)
Check that they are free and do not contain any impurities; remove any impurities and rinse.
• Level control (Fig. 17.d, part. no.4 – Fig. 17.e, part. no. 4)
The level control must be released from the partition wall of the cabinet. Disconnect the connector from the terminals of the electronic board, take off the connection pipes. Release the spacers and the board, then take off the caps. Check that the o-rings are not damaged or cracked; replace them if necessary.
Check the cleanliness and free sliding of the two fl oat switches.
Clean all the components and reassemble and replace the device.
heaterSteam +030222011 - r el. 2.2 - 24.01.2011
65
Fig. 17.e
Carefully check that the connection pipes are properly fi tted and that they are not blocked or choked at any point.
IMPORTANT WARNING: after having replaced or checked the plumbing components, check that the connections have been carried out correctly, with their corresponding seals. Re-start the machine and run through a number of fi ll and drain cycles (from 2 to 4), at the end of which, applying the safety procedure, check for any water leaks.
17.2 Replacing the components
17.2.1 Non-stick fi lm
If requested as an option, the internal wall of the cylinder is lined with a non-stick fi lm to avoid lime being deposited on the internal walls of the cylinder. To clean or replace the fi lm, remove the cylinder following the procedure described in Maintenance of the cylinder-cylinder and then:
• slowly remove the fi lm towards the mouth of the cylinder, without forcing it to avoid damage;
• open the fi lm after having released the click-on couplings;
• clean the fi lm with water and a plastic spatula if necessary; replace the fi lm if damaged;
• wind the fi lm around itself, reinserting the click-on couplings, and place it into the cylinder after the latter has been carefully cleaned and freed from deposits.
17.2.2 Elements
To replace the elements remove the cylinder following the procedure described in Maintenance of the cylinder-cylinder and loosen the fastening nuts from the threaded spigots of the elements.
Before reassembling the elements, check the state of the gaskets and replace them if necessary.
17.2.3 PTC overtemperature sensor
The PTC sensors (one for each heating element) do not require regular maintenance; they should only be replaced if the safety thermostat is activated due to operation without water: in fact, the intervention of just one PTC will cause the control module to shut-down operation.
To replace the sensors, remove the cylinder following the procedure described in Maintenance of the cylinder-cylinder and then:
• disconnect the PTC sensor terminals (see Fig.: 7.p.a to 7.p.n);
• remove the electrical elements corresponding to the sensors being replaced;
• unscrew the PTC sensor (fi g. 17.a, part. no. 7 or Fig. 17.b part. no. 7 or Fig. 17.c part. no. 2) using a spanner on the hexagonal spigot, accessible from the under side of the cover;
• reassemble a new PTC sensor, replacing the o-ring and screwing it tight; reconnect the terminals;
• reposition the electric heating elements, making sure the PTC sensor enters into the corresponding sheath in the aluminium casting.
17.2.4 NTC temperature sensor (version with type H or T control module only)
As for the PTC sensors, the NTC sensor controlling the water temperature does not require regular maintenance.
To replace this sensor, remove the cylinder following the procedure described in Maintenance of the cylinder-cylinder and then:
• disconnect the terminals of the NTC sensor (see Fig.: 7.p.a to 7.p.n);
• remove the sensor from the well housed in the measuring sheath (fi g. 17.a part. no. 2, or Fig. 17.b part. no. 1, or Fig. 17.d part. no. 11);
• reposition and connect the new sensor in the place of the old one.
66 heaterSteam +030222011 - r el. 2.2 - 24.01.2011
17.2.5 Fuses (uxiliary circuit)
These measure 10.3 x 38mm and are housed in the fuse cartridge; to check the state of the fuses, check their continuity using a tester.
Use the types of fuses indicated in table 17.e.
fuses 1 and 2 transformer power supply
fuses 3 pump protection (on humidifi ers from 20 to 60kg/h) (44.1 to
132.3 lbs/h)
Fuse 4 transformer secondary
models
UR002 UR004 UR006 - 1~* UR006 -3~** UR010 UR020 UR027 UR040 UR060
All fast blow and capacity 1 A, GL, 10,3x38 contained in fuse carrier on Omega rail
1 A GL , 10,3x38 FAST
2,5 A,T 5x20 in pottery
Table 17.f
*: single-phase **: three-phase
17.2.6 Load protection fuses (humidifi ers UR027 at 208-230 V, UR060 at 460 V)
Dimension of the fuses 27x60 mm rapid, housed in fuse carrier bases that can be selected. Check their continuity using a tester.
fuses F5, F6, F7 fuses F8, F9, F10
UR027
40 A, GG
40 A, GG
UR060
35 A, GG
50 A, GG
Table 17.g
17.2.7 Solid state relays (version with type H or T control module only)
The solid-state relays (one in the single-phase unit, two in the three-phase unit) can malfunction in one of two ways: by short-circuit or burn-out. The respective consequences for the supply of power are: continuous conduction or permanent opening.
In the event of malfunctioning, check the conduction of the relay using a tester.
For the replacement of the solid-state relay:
• turn the humidifi er off;
• open the disconnection switch in the power line (safety procedure);
• disconnect the power and auxiliary cables from the solid-state relay terminal block;
• remove the relay from the electrical panel by using a screwdriver to lower the fastening lever to the omega guide;
• replace the new relay on the omega guide and reconnect the wires as before.
17.2.8 Cooling fan and circuit breaker (version with type H or T control module only)
The SSR relays are cooled by a fan placed in the upper part, on the right side of the machine for the
20-60kg/h (44-132.2lbr/h) models, or placed on the base of the humidifi er for the models up to 10kg/h
(22lbr/h).
With insuffi cient ventilation the temperature of the electrical panel may rise excessively until, reaching
65°C, power to the solid-state relays is cut by a special Klixon (heat sensor, used in this application as circuit breaker - hereafter: circuit breaker), with manual reset (indicated by S2 in the wiring diagram) and without an activation signal. In this case, check:
• Whether the thermoprotective placed in the din rail near to the SSR relays has been working, or placed in front of the baffl e pressing the reset button (see Fig. 17.f);
• that the fan power board, fi tted in front of the baffl e, is powered (input terminals: 24 Vac) and in turn powers the fan (output terminals: 24 Vdc), (only for models up to).
If the fan is faulty:
- in the models up to 10 Kg/h (22 lbs/h):
• remove the baffl e, after having unscrewed the two side nuts for fastening to the partition of the appliance;
In case of malfunction, the thermoprotective can be replaced unscrewing the fastening screws;
- in the 20-27-40-60 Kg/h
( 44.1-59.5-88.1-132.3 lbs/h )
models:
• unscrew the 4 fastening screws placed on the right side of the structural work and extract the fan from the inside of the panel.
In case of malfunction, the thermoprotective can be replaced removing the polycarbonate transparent protection of the solid state relays and unscrewing the fastening screws.
Key:
1
2
3
4
Klixon (thermoprotective - where fi tted) solid state relay (SSR) (where fi tted) fan (where fi tted) heatsink
1
2
3
1
3
4
2
Fig. 17.f
heaterSteam +030222011 - r el. 2.2 - 24.01.2011
67
17.3 Spare parts
Models UR002 UR004 UR006 - 1~* UR006 - 3~** UR010 UR020 UR027 UR040 UR060
plumbing
humidifi er gasket kit
Cylinder gasket kit
cylinder cover kit boiler cover locking bracket
cylinder fi lter kit
URKG00000M URKG00000M URKG00000M URKG00000M URKG00000M
URKG100000 URKG100000 URKG100000 URKG100000 URKG100000
URKG0000XL
URKG400000
URKG0000XL
URKG400000
URKG0000XL URKG000XXL
URKG400000 URKG600000
URKCOPC00S URKCOPC00S URKCOPC00M URKCOPC00M URKCOPC00M URKCOP4000 URKCOP4000 URKCOP4000 URKCOP6000
URKBR00000 URKBR00000 URKBR00000 URKBR00000 URKBR00000
UEKF000000 UEKF000000 UEKF000000 UEKF000000 UEKF000000 URKF0000XL
URKFLAN000
URKF0000XL
URKFLAN000
URKF0000XL
URKFLAN000
URKF0000XL
URKFLAN000
Tefl on-coated heating elements
208 V
230 V
400 V
460 V
575 V
non-Tefl on heating elements
208 V
230 V
400 V
460 V
575 V
cylinder fastening strap
steel cylinder
fi ll tank
drain electrovalve kit
drain pump kit
drain pipe kit
fi ll valve
internal pipe kit level control with sensor
non-stick fi lm
external terminal covering
URKH00A348
URKH00A348
URKH00A349
URKH00A349
URKH00R348
URKH00R348
URKH00R349
URKH00R349
URKH00R347
URKH00R320
URKH00R347
URKH00R320
URKH00R320
URKH00R346
URKH00R322
URKH00R322
URKH00R344
URKH00R341
URKH00P347
URKH00R342
URKBLOCK00 URKBLOCK00 URKBLOCK00 URKBLOCK00 URKBLOCK00
URKB040000 URKB040000 URKB100000 URKB100000 URKB100000
UEKVASC000 UEKVASC000 UEKVASC000 UEKVASC000 UEKVASC000
URKDRAIN00 URKDRAIN00 URKDRAIN00 URKDRAIN00 URKDRAIN00
KITVC00006
URKT00000S
KITVC00006
URKT00000S
URKSL00004 URKSL00004
URKBAG0400 URKBAG0400
URKTI04000 URKTI04000
URKH00A347
URKH00A320
URKH00A347
URKH00A320
URKH00A320
URKH00A344
URKH00A341
URKH00A346
URKH00A322
URKH00A322
URKH00A347
URKH00A342
KITVC00012 KITVC00012 KITVC00012
URKT00000M URKT00000M URKT00000M
URKSL00004
URKBAG1000
URKTI10000
URKSL00004
URKBAG1000
URKTI10000
URKSL00004
URKBAG1000
URKTI10000
URKH00A382 URKH00A383
URKH00A381 URKH00A382
URKH00A381 URKH00A382
URKH00A386 URKH00A381
URKH00A387
URKH00A390
URKH00A387
URKH00A390
URKH00A385 URKH00A380 URKH00A389 URKH00A389
URKH00R382
URKH00R381
URKH00R381
URKH00R386
URKH00R385
---
URKB270000
---
--
KITPSR0000
URKT0000XL
KITVC00040
URKT0000XL
URKSL00004
---
URKTI27000
URKH00R383
URKH00R382
URKH00R382
URKH00R381
URKH00R380
--
URKB270000
--
--
KITPSR0000
URKT0000XL
KITVC00040
URKT0000XL
URKSL00004
--
URKTI27000
URKH00R387 URKH00R387
URKH00R390 URKH00R390
URKH00R389 URKH00R389
---
URKB400000 URKB600000
--
--
KITPSR0000
URKT000XXL
--
--
KITPSR0000
URKT000XXL
KITVC00040
URKT000XXL
URKSL00004
--
URKTI40000
KITVC00100
URKT000XXL
URKSL00004
--
URKTI60000
electrical parts contactor
voltage 208 V
230 V
400 V
460 V
575 V
URKCONT100 URKCONT100 URKCONT100 URKCONT100 URKCONT100 URKCONT400 URKCONT400
URKCONT300
URKCONT100 URKCONT100 URKCONT200 URKCONT200 URKCONT200 URKCONT300
URKCONT100 URKCONT100 URKCONT200 URKCONT200 URKCONT400 URKCONT300
URKCONT100 URKCONT100 URKCONT200 URKCONT200 URKCONT200 URKCONT300
URKCONT500 URKCONT500 URKCONT500 URKCONT500 Auxiliary contact
power supply transformer
voltage
fuse carrier
voltage
230 - 400 V URKTR10000 URKTR10000 URKTR10000 URKTR10000 URKTR10000 URKTR40000 URKTR40000 URKTR40000 URKTR40000
208 - 208 - URKTR20000 URKTR20000 URKTR20000 URKTR20000 URKTR20000 URKTR30000 URKTR30000 URKTR30000 URKTR30000
460 - 575 V
460 V
208-230 V
URKFH10000 URKFH10000 URKFH10000 URKFH10000 URKFH10000 URKFH20000 URKFH20000
URKFH30000
URKFH20000 URKFH20000
URKFH30000
fuses
F1, F2
F3
208-230 V
400V
460-575 V
400V
208-230-
460-575 V
URKFUSE100 URKFUSE100 URKFUSE100 URKFUSE100
URKFUSE300
URKFUSE100
URKFUSE100
URKFUSE300
URKFUSE100
URKFUSE200
URKFUSE300
URKFUSE100
URKFUSE300
URKFUSE400
URKFUSE200
URKFUSE300
URKFUSE100
URKFUSE300
URKFUSE400
URKFUSE300 URKFUSE300
URKFUSE100 URKFUSE100
URKFUSE300 URKFUSE300
URKFUSE400 URKFUSE400
F4
F5, F6, F7, F8, F9, F10
F5, F6, F7
F8, F9, F10 from 40 A
(208-230V) from 35 A
(460V ) from 50 A
(460V)
URKFUSE500 URKFUSE500 URKFUSE500
URKFUSE700
URKFUSE500
URKFUSE600
URKFUSE800 fan
Motor protector
URKFANS000 URKFANS000 URKFANS000 URKFANS000 URKFANS000 URKFANL000
THP00A0000 THP00A0000 THP00A0000 THP00A0000 THP00A0000
URKNTCCAS2 URKNTCCAS2 URKNTCCAS1 URKNTCCAS1 URKNTCCAS1
THP00A0000
URKKL00000
URKFANL000
THP00A0000
URKKL00000
URKFANL000 URKFANL000
THP00A0000 THP00A0000
URKKL00000 URKKL00000
socket for pre-heater probe
electronic parts
version C control module
version H control module
version T control module
main control board
fl at connection cable fan and SSR motorprotector
URI0000000
59C460A003
URKKL10000
URI000000i
59C460A003
URKKL10000
URCxxvppri (for further information see the CAREL instruction sheet code +050003700)
URHxxvppri (for further information see the CAREL instruction sheet code +050003700)
URSxxvppri (for further information see the CAREL instruction sheet code +050003700)
URI000000i URI000000i URI000000i URI000000i URI000000i
59C460A003
URKKL10000
59C460A003
URKKL10000
59C460A003
URKKL10000
59C486A003
URKKL10000
59C486A003
URKKL10000
URI000000i
59C486A003
URKKL10000
URI000000i
59C486A003
URKKL10000 boiler motorprotector
fan circuit breaker
fan control board
solid state relay
6132702AXX
URKCFAN000
6132702AXX
URKCFAN000
6132702AXX
URKCFAN000
6132702AXX
URKCFAN000
6132702AXX
URKCFAN000
URKKL00000
6132702AXX
URKKL00000
6132702AXX
URKKL00000 URKKL00000
6132702AXX 6132702AXX
208 V
230 V
400 V
460 V
URKSSR1000
URKSSR1000
URKSSR1000
URKSSR1000
URKSSR1000
URKSSR1000
URKSSR1000
URKSSR1000
URKSSR2000
URKSSR2000
URKSSR1000
URKSSR1000
URKSSR1000
URKSSR1000
URKSSR2000
URKSSR1000
URKSSR1000
URKSSR1000
URKSSR3000
URKSSR3000
URKSSR3000
URKSSR3000
URKSSR3000
URKSSR3000
URKSSR3000
URKSSR3000
URKSSR3000
URKSSR3000
URKSSR3000
URKSSR3000
575 V URKSSR1000 URKSSR1000 URKSSR3000 URKSSR3000 URKSSR3000 URKSSR3000
PTC probe ( res. without antiadherent fi lm) URKPTCS000 URKPTCS000 URKPTCS000 URKPTCS000 URKPTCS000 URKPTCL000 URKPTCL000 URKPTCL000 URKPTCL000
NTC probe ( res. with antiadherent fi lm) URKNTC0000 URKNTC0000 URKNTC0000 URKNTC0000 URKNTC0000 URKNTC0000 URKNTC0000 URKNTC0000 URKNTC0000
Table 17.h
*: single-phase **: three-phase
68
17.4 Disposal of the parts of the humidifi er
The humidifi er is made up of metallic and plastic parts, refer to Figs. 2.a e 14.b. All these parts must be disposed of according to the local standards regarding product waste disposal.
heaterSteam +030222011 - r el. 2.2 - 24.01.2011