Amana SS 5 is a versatile, energy-efficient air handler designed for both cooling and heating applications. Compatible with R-410A refrigerant and featuring a variable-speed ECM blower motor, it delivers consistent airflow and humidity control. The ComfortNet™ Communicating System integration allows for precise temperature management and remote access. It includes a built-in coil with horizontal, vertical, and downflow drain pans, enhancing drainage efficiency.
advertisement
AVPTC
M
ulTi
-P
osiTion
, V
AriAble
-s
Peed
A
ir
H
Andler
1½
To
5 T
ons
Standard Features
• Compatible with the ComfortNet™ Communicating
System family of products
• R-410A refrigerant-compatible
• Factory-installed thermal expansion valves for cooling and heat pump applications
• Variable-speed ECM blower motor
• All-aluminum evaporator coil
• Provides constant CFM over a wide range of static pressure conditions independent of duct system; provides low CFM for efficient fan-only operation
• In non-communicating mode, up to 12 field-selectable airflow settings can be adjusted to optimize the system’s CFM for each individual mode of operation
• Auto configuration of the airflow and tonnage in communicating mode
• CFM indicator
• Maximum four low-voltage wires required for operation in communicating mode
• Improved humidity control and comfort
• Compatible with heat pumps and variable-capacity cooling applications
• Built-in coil has horizontal, vertical, and downflow drain pans with secondary drain connections
• Complies with the Factory-sealed Air Handling Credit with or without field-installed filter kits as listed in the 2001
Florida Building Code, Chapter 13, Section 610.2.A.2.1
• AHRI Certified; ETL Listed
Cabinet Features
• Fully insulated, painted steel cabinet with attractive
Architectural Gray finish
• Compact, versatile upflow, downflow, or horizontal multiposition installations
• Built-in filter rack for 1” filter (filter not included)
• Low-voltage cabinet connections; control circuit is arranged to permit staging
• Power supply on top; low-voltage entry on top or side
• Factory-sealed to achieve 2% or less leakage rate with or without field-installed filter kits at 1.0” water gauge external duct static pressure
SS-AAVPTC
* Complete warranty details available from your local dealer or at www.amana-hac.com.
To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Québec.
www.amana-hac.com
Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P., Houston, Texas.
5/11
Supersedes 2/11
P roduCT
s
PeCifiCATions n
oMenClATure
A
1
Brand
A Single-‐piece
Air Handler
R
S
V
D
E
Unit Applica3on
C Ceiling Mount PSC Motor
Downflow PSC Motor
MulI-‐PosiIon Variable-‐Speed Motor
MulI-‐PosiIon PSC Motor
MulI-‐PosiIon EEM Motor
MulI-‐PosiIon Variable-‐Speed Motor
W Wall Mount PSC Motor
P
N
Cabinet Finish
U Unpainted
Painted
Uncased
Expansion Device
F Flowrater
T Expansion Valve
V
2
P
3
T
4
C
5
3642
6,7,8,9
1
10
4
11
AA
12,13
Engineering *
Major/ Minor Revisions
* Not used for inventory management
Refrigerant Compatability
4 = R-‐410A
Electrical
1 208/240 V, 1 Phase, 60 Hz
Nominal Capacity Range @ 13 SEER
Mul3-‐Posi3on & Downflow Applica3ons
1830 1½-‐2½ Tons
3137 2-‐3 Tons
4260 3-‐5 Tons
Communica3ons
C ComfortNet™ CompaIble
P roduCT
s
PeCifiCATions
SS-AAVPTC www.amana-hac.com 3
P roduCT
s
PeCifiCATions s
PeCifiCATions
Nominal Ratings
Cooling (BTU/h)
CFM (High/ Low)
Blower
Diameter
Width
Coil Drain Connection FPT
Service Valve
Liquid
Suction
Electrical Data
Voltage
Electric Heat Capacity (kW)
Min Circuit Ampacity
Max. Overcurrent Device (amps)
Minimum VAC
Maximum VAC
Blower Motor
FLA
HP
Ship Weight (lbs)
AVPTC
183014
18,000-30,000
1,200/ 600
9½"
8"
¾"
⅜"
¾"
208/240
3, 5, 8, 10
4.9/4.9
15/15
197
253
3.9
½
127
AVPTC
313714
30,000-36-000
1,200/ 600
10⅝"
10⅝"
¾"
⅜"
⅞"
208/240
3, 5, 6, 8,10, 15
6.5/6.5
15/15
197
253
5.2
¾
178
AVPTC
426014
42,000-60,000
1,800/ 1,200
10⅝"
10⅝"
¾"
⅜"
⅞"
208/240
3,5,6,8,10,15,20,21
8.6/8.6
15/15
197
253
6.9
1
197
P roduCT
s
PeCifiCATions
SS-AAVPTC www.amana-hac.com 3
P roduCT
s
PeCifiCATions d
iMensions
Model
AVPTC183014
AVPTC313714
AVPTC426014
A
46¾”
53¼”
53¼”
B
22”
24”
24”
C
17½”
20”
20”
D
19½”
22”
22”
E
10”
12”
12”
F G H I
14½” 11 15 /
16
” 17⅛” 17 15 /
16
”
J
2”
14½” 11 15 /
16
” 19⅝” 19 15 /
16
” 1 13 /
16
”
14½” 11 15 /
16
” 19⅝” 19 15 /
16
” 1 13 /
16
”
P roduCT
s
PeCifiCATions
SS-AAVPTC www.amana-hac.com 5
P roduCT
s
PeCifiCATions
P roduCT
s
PeCifiCATions
A
irflow
d
ATA
Electric Heat Airflow
Htr kW
3
5
6
8
10
15
20
21
9
ON
ON
ON
ON
OFF
OFF
OFF
OFF
10
ON
ON
OFF
OFF
ON
ON
OFF
OFF
11
ON
OFF
ON
OFF
ON
OFF
ON
OFF
AVPTC
183014*
630
730
840
1080
1270
NR
NR
NR
AVPTC
313714*
610
710
840
1060
1260
1470
NR
NR
AVPTC
426014*
600
680
790
990
1190
1390
1580
1580
Note: Airflow data shown applies to the emergency heat mode (electric heat only) in either legacy mode operation or fully communicating mode operation.
Model
AVPTC183014*
AVPTC313714*
AVPTC426014*
Cooling / Heat Pump Airflow
Tap
A
B
C
A
B
C
D
A
B
C
D
Low-Stage
Cool
420
560
700
410
560
700
830
810
940
1050
1210
High-Stage
Cool
630
840
1040
610
830
1040
1240
1210
1410
1560
1800
Notes
• Airflow data shown applies to legacy mode operation only. For a fully communicating system, see the outdoor unit’s installation instructions for cooling and heat pump airflow data. See ComfortNet™ System —
Airflow Consideration section for details.
• Airflow blink codes are approximations a=of actual airflow.
d
iPswiTCH
s
eTTings
Speed Selection Dipswitches
Tap
C
D
A
B
Cool
Switches
1 2
Switches
3
Adjust
4
Profile
Switches
5 6
Off Off Off Off Off Off
On Off On Off On Off
Off On Off On Off On
On On On On On On
Profiles
A
B
C
D
Pre-Run
-----
-----
-----
30 sec / 50%
Short-Run
-----
30 sec / 50%
7.5 min / 82%
7.5 min / 82%
OFF Delay
60 sec / 100%
60 sec / 100%
60 sec / 100%
30 sec / 50%
To set airflow:
1. Select appropriate model from Cooling/Heat Pump Airflow Table. Based on desired Airflow for your application select corresponding tap (A,B,C or D). Set dip switches 1 & 2 to the appropriate ON/OFF positions.
2. Select appropriate Airflow adjustment factor for application (0%. +10%, -10%). Set dip switches 3 & 4 to the appropriate ON/OFF positions.
3. If installed with Heater Kit: Using Electric Heat Airflow Table, set dip switches 9, 10 and 11 to the appropriate ON/OFF positions based on Heater kit installed. If installed without Heater Kit: Ensure dip switches 9, 10 and 11 are set to a valid heater kit selection. Example: The only valid heater kits for
AVPTC183014* applications are 3, 5, 6, 8 and 10 kW. Failure to do so will result in a Heater Kit error code.
To set Comfort mode: Select desired Comfort Mode profile (see profiles above). Set switches 5 and 6 to the appropriate ON/OFF positions.
SS-AAVPTC www.amana-hac.com 5
P roduCT
s
PeCifiCATions
AVPTC w
iring
d
iAgrAM
1
2
3
4
K G
BIAS
BIAS
TERM
CONNECTOR
CUIT MOTOR 4 CIR
COOL
ADJUST
DELAY
DEHUM
UNUSED
ELEC
HEAT
AF
NS IO CT NE ON
NS TIO NEC ON T C STA MO HER V T 24
T C TA OS RM HE V T 24
1
4
3
2
P roduCT
s
PeCifiCATions
Wiring is subject to change. Always refer to the wiring diagram or the unit for the most up-to-date wiring.
⚠
W
arning
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
SS-AAVPTC www.amana-hac.com 7
P roduCT
s
PeCifiCATions
P roduCT
s
PeCifiCATions
A
CCessories
H eAT
K iT
s eleCTion
Models
HKR-03*
HKR-05*/-05C*
HKR-06*
HKR-08*/-08C*
HKR-10*/-10C*
HKR-15C*
HKR-20C*
HKR-21C*
AVPTC
183014A*
X
X
X
X
X¹
AVPTC
313714*
X
X
X
X
X
X²
AVPTC
426014A*
X
X
X
X
X
X
X³
X³
* Revision level that may or may not be designated
C Circuit breaker option
Notes:
When 8kW and 10kW heat kits are used with an AVPTC1830 and AVPTC3137, matched with
2- ton outdoor unit, see Note 1 below.
¹ Set Heater Kit dip switches 9, 10 and 11 to 6kW setting (9-ON, 10-OFF,11-ON) to obtain
840 CFM.
² This heater kit can only be used for ‘1000 CFM or higher’ applications.
³ This heater kit can only be used for ‘1200 CFM or higher’ applications.
d rAin
P
An
i nsulATion
K iTs
Downflow Applications
1830
Model
3137-4260
Insulation Kit
DPI36-42/20
DPI48-61/20
Note: Each kit contains enough material to modify 20 coils
Horizontal Applications
1830
Model
3137-4260
Insulation Kit
DPIH36-42
DPIH48-61
Note: Each kit contains enough material to modify 20 coils s ingle
P oinT
K iT
**
Model HKR-15C HKR-20C HKR-21C
SPW-01 X X X
** Must be installed along with any of the above compatible heat kits. This kit will fit any AVPTC air handler as long as a compatible heat kit is installed in the unit.
f ilTers
Model
N/A
1830
3137
4260
Filter #
FIL 18-32
FIL-36-42
FIL 48-61
FIL 48-61
Qty
Required
1
1
1
1
SS-AAVPTC www.amana-hac.com 7
P roduCT
s
PeCifiCATions n
oTes
P roduCT
s
PeCifiCATions
Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P. All rights reserved. Our continuing commitment to quality products may mean a change in specifications without notice. © 2011 • Goodman Company, L.P. • Houston, Texas • Printed in the USA.
SS-AAVPTC www.amana-hac.com PB
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement