advertisement
Instructions
Electrochemical Gas Detector
GT3000 Series
Includes Transmitter (GTX) and Sensor Module (GTS)
11.1 Rev: 8/15 95-8616
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Gts sensor Module . . . . . . . . . . . . . . . . . . . . . . 1
GtX transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . 2 real time clock . . . . . . . . . . . . . . . . . . . . . . . . . . 2
History/event Logs . . . . . . . . . . . . . . . . . . . . . . . . 2
HArt communication . . . . . . . . . . . . . . . . . . . . . 3
Magnetic switch . . . . . . . . . . . . . . . . . . . . . . . . . . 3
LeDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 specificAtions . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 cALiBrAtion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Gt3000 calibration . . . . . . . . . . . . . . . . . . . . . . 12 calibration procedure . . . . . . . . . . . . . . . . . . . . . 13
MAintenAnce . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 routine inspection . . . . . . . . . . . . . . . . . . . . . . . 14 sensor Module replacement . . . . . . . . . . . . . . . 14
DeVice repAir AnD return . . . . . . . . . . . . . . . 15 iMportAnt sAfety notes . . . . . . . . . . . . . . . . . . 5 orDerinG inforMAtion . . . . . . . . . . . . . . . . . . 15
Gts Gas sensors . . . . . . . . . . . . . . . . . . . . . . . 15 calibration Kits for Gas sensors . . . . . . . . . . . . 15 parts & Accessories . . . . . . . . . . . . . . . . . . . . . . 15 instALLAtion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 identification of Vapor(s) to be Detected . . . . . . . 6 identification of Detector Mounting Locations . . . 6
Device Mounting orientation . . . . . . . . . . . . . . . . 6
Detector installation . . . . . . . . . . . . . . . . . . . . . . . 7 sensor termination Box . . . . . . . . . . . . . . . . . . . . 7 wirinG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 power supply requirements . . . . . . . . . . . . . . . . 7 wiring cable requirements . . . . . . . . . . . . . . . . . 7 intrinsic safety Barriers . . . . . . . . . . . . . . . . . . . . 8
Guidelines for intrinsic safety wiring . . . . . . . . . . 8 wiring procedure . . . . . . . . . . . . . . . . . . . . . . . . . 8
AppenDiX A — fM ApproVAL Description . . . . . 18
AppenDiX B — csA certificAtion Description . 20
AppenDiX c — AteX ApproVAL Description . . . 21
AppenDiX D — iecex ApproVAL Description . . 22
AppenDiX e — otHer ApproVALs . . . . . . . . . . . . . 23
AppenDiX f — DecLArAtion of conforMity . . 24
AppenDiX G — sensor coMpArison / cross sensitiVity . . . . . . . . . . . . 25
AppenDiX H — HArt coMMunicAtion . . . . . . . . . 27
AppenDiX i — controL DrAwinGs . . . . . . . . . . . . 29
INSTRUCTIONS
Electrochemical Gas Detector
GT3000 Series
Includes Transmitter (GTX)
and Sensor Module (GTS)
Sensor
Module
(GTS)
Transmitter
(GTX)
Detector (GT3000)
Important
Be sure to read and understand the entire instruction manual before installing or operating the gas detection system. This product is intended to provide early warning of the presence of a toxic or explosive gas mixture, or of oxygen depletion. Proper device installation, operation, and maintenance are required to ensure safe and effective operation. If this equipment is used in a manner not specified in this manual, safety protection may be impaired.
that are able to monitor a linear 4-20 mA dc signal. All alarm functions are provided by the monitoring device.
The GT3000 is designed and approved as a stand alone unit for use in hazardous locations. It is suitable for outdoor applications that require IP66 rating and uses a hydrophobic filter that is easily replaced without opening the device or use of tools. The GT3000 is furnished as either explosion-proof or intrinsically safe.
The GT3000 supports local one-person calibration with the use of a magnet and on-board LED.
Description
The GT3000 Electrochemical Gas Detector is an intelligent stand-alone industrial gas detector, designed to provide continuous monitoring of the atmosphere for hazardous gas leaks or oxygen depletion. It is fully performance tested and approved by Factory Mutual.
Refer to Appendix F for individual gas specifications.
GTS SENSOR MODUlE
The GTS’s electrochemical sensor cell uses capillary diffusion barrier technology for monitoring gas concentrations in ambient air.
The GT3000 Gas Detector consists of a replaceable sensor module (Model GTS) connected to a transmitter module (Model GTX). A single transmitter is compatible with all GTS sensor modules. A variety of electrochemical sensor models are available in various concentration ranges.
The GT3000 is a 2-wire device that generates a 4-20 mA output signal with HART communication that is proportional to the concentration of the target gas.
live Maintenance
The hot swappable GTS sensor module is intrinsically safe and allows live maintenance while under power, without de-classifying the hazardous area. When the sensor is removed, the transmitter generates a fault output. If a new sensor of the same type and range is installed, the fault self-clears. However, if the type or range of the new sensor module does not match the old, the transmitter generates a fault until a successful calibration or acceptance of the new sensor type is completed. For additional information regarding Live
Maintenance, refer to “Sensor Module Replacement” in the Maintenance section of this manual.
The GT3000 is compatible with FlexVu
®
Model UD10 and
UD20 Universal Display Units, as well as other devices
11.1
©
Detector Electronics Corporation 2015
Rev: 8/15 95-8616
Automatic Sensor Module Recognition
The transmitter provides automatic gas sensor recognition, allowing the operator to access the following information via HART, or a UD10 or UD20
Universal display:
• Date of manufacture of the sensor module
• Sensor module serial number
• Gas type
• Measurement range
HISTORY/EvENT lOGS
Both the transmitter and sensor are able to store 256 history logs, which are saved in non-volatile memory and retained through power cycles. A UD10/UD20
Universal Display Unit, a HART communication device, or AMS software is required to view the history logs.
The sensor module is factory programmed for the gas type and measurement range. When the sensor module powers up, the transmitter reads and acknowledges the gas type and measurement range.
GTX TRANSMITTER
The transmitter output is a linear 4-20 mA dc signal with HART communication that directly corresponds to
0-100% full scale.
A 3.8 mA output indicates sensor calibration in progress
(17.3 mA for O
2
sensor). The GT3000 comes with one of two pre-programmed fault output levels: 2.45 mA or
3.5 mA.
Priority of output signals from highest to lowest is:
Sensor logging Capability
The sensor module logs the following operating parameters in non-volatile memory:
• Running Hours
- The sensor module maintains the total operating hours, and cannot be reset.
• Min/Max Temperature
- The sensor module maintains the minimum and maximum temperatures with a date and time stamp.
• Calibration
- The sensor module logs the calibration history with a date and time stamp, along with the success or cause of failure codes. See Table 1. The zero and span values (AD converter values recorded at the time of calibration) are also saved. This allows the logs to follow the sensor module when it is calibrated separately from the transmitter. (Calibration data is available via a UD10/UD20, a HART communication device, or AMS software.)
The sensor module gets the current time and date from the transmitter and provides calibration log information to the transmitter. See Figure 1.
1
2
3
Calibration
(In progress)
Fault
Gas Level
Transmitter Wiring
The GTX transmitter is a two-wire loop powered device that uses a three-wire cable (power, signal, and earth ground) for connecting to a controller or monitoring device. The use of shielded cable is required.
REAl TIME ClOCk (RTC)
The GTX transmitter has a real time clock with battery back-up, that is used for time stamping the event logs.
The time and date are set and read using a UD10/
UD20 Universal Display Unit, a HART communication device, or AMS software. The time stamp on the logs will not be correct if the RTC in the transmitter is not set correctly.
Table 1—Calibration Status Codes
8
9
10
11
5
6
7
Number
0
1
2
3
4
Definition
EMPTY LOG
NOT USED
NOT USED
ZERO CAL
SPAN CAL
ABORT CAL
FAILED CAL
NOT USED
NOT USED
INIT CAL LOG
NOT USED
CLR CAL FAULTS
11.1
2
95-8616
Transmitter updates sensor module time / date
GT3000
Gas Detector
Transmitter
RTC
Event Logs
HART Interface
Transmitter reads calibration logs from sensor
Sensor Module
Calibration Logs
GREEN LED (ON)
YELLOW LED (OFF)
Figure 1—GT3000 Logging
A2450
Transmitter logging Capability
The transmitter logs the following events with a time and date stamp:
• Power-up
• Sensor change
• All Faults.
Figure 3— Location of LEDs on GT3000 Gas Detector
MAGNETIC SWITCH
The GT3000 is furnished with an internal magnetic reed switch as part of the user interface. The magnetic switch allows the user to initiate calibration by momentarily placing a magnet against the housing at the designated location. See Figure 2.
HART COMMUNICATION
The transmitter supports HART communication on the
4-20 mA loop. This allows for configuration capability and provides device status information, calibration, and diagnostics capabilities. The GT3000 is compatible with HART interface devices such as a HART handheld communicator, the Det-Tronics UD10 or UD20 Display
Unit, or an AMS system. (See Appendix G for HART menu structure.)
lEDs
The GT3000 has one green and one yellow LED
(See Figure 3). The LEDs are used to signal normal, calibration, and fault conditions. See Table 2.
NoTe
The GT3000 does not have alarm setpoints and, therefore, does not have a red LeD.
MAGNETIC
SWITCH
11.1
B2443
Figure 2—Location of Magnetic Switch on GT3000 Detector
3
Table 2—LEDs and Analog Output
During Various Operating Conditions
Function Green lED Yellow lED
Analog
4-20 Signal
Output
3.5***
Warm-up
*
Single Flash
Normal
Operation
Steady On
Fault
Condition
Calibration
No Power
Off
Off
Off
On
Off
On
See Table 5
Off
4-20
3.5***
3.8
**
0
*
Warm-up time can last up to 150 seconds.
**
O
2
sensor generates 17.3 mA during calibration.
***2.45 for TYPE OUTPUT "29", reference GTX Model Matrix .
95-8616
specifications
6.2
(15.8)
SENSOR AND TRANSMITTER
AVAILABLE SENSORS—
Refer to Appendix F.
CROSS SENSITIVITY—
See Appendix F for Cross Sensitivity information.
CALIBRATION—
Sensors are calibrated at the factory. Gas type and range are read by the transmitter. Field calibration is initiated at the detector, at the UD10/UD20 Universal
Display Unit, or by some other HART interface device.
OPERATING VOLTAGE—
24 volts dc nominal. (12 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
If using the HART function, the installation must comply with the HART power standard.
POWER CONSUMPTION—
0.8 watt maximum @ 30 Vdc.
CURRENT OUTPUT—
• 4-20 mA (Normal operating mode).
• 3.8 mA indicates calibrate mode.
• 3.5 mA or less indicates a fault condition (2.45 mA option available).
MAXIMUM LOOP RESISTANCE—
300 ohms at 18 Vdc, 600 ohms at 24 Vdc.
WIRING—
The transmitter has flying leads, 20” long, 600V insulation.
Colors: Red = V+
Black = V–
Green = earth ground
Gauge: 22 AWG (red and black)
16 AWG (green).
WARM-UP—
Warm-up time can last up to 150 seconds.
OPERATING TEMPERATURE—
See Appendix F.
STORAGE TEMPERATURE—
Transmitter: –55°C to +75°C (–67°F to +167°F)
Sensor: 0°C to +20°C (+32°F to +68°F).
Ideal: +4°C to +10°C (+39°F to +50°F).
HUMIDITY RANGE—
15 to 90% RH.
2.5
(6.4)
5.6
(14.3)
B2397
Figure 4—Dimensions of GT3000 Gas Detector in Inches (CM)
PRESSURE RANGE—
Atmospheric ±10%.
INGRESS PROTECTION—
IP66.
ELECTRO-MAGNETIC COMPATIBILITY—
EMC Directive 2004/108/EC
EN55011 (Emissions)
EN50270 (Immunity).
THREAD OPTIONS—
3/4" NPT or M25.
ENCLOSURE MATERIAL—
GTX Transmitter: 316 Stainless Steel
GTS Sensor Module: PPA (30% carbon filled).
DIMENSIONS—
See Figure 4.
WARRANTY—(For the GTX and GTS)
12 months from date of installation or 18 months from date of shipment, whichever occurs first.
CERTIFICATIONS—
®
For complete approval details, refer to the appropriate
Appendix:
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
Appendix E - Other Approvals
11.1
4
95-8616
important safety notes
CaUtIon
The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Be certain that all wiring complies with the NeC as well as all local codes. If in doubt, consult the authority having jurisdiction before wiring the system. Installation must be done by a properly trained person.
CaUtIon
This product has been tested and approved for use in hazardous areas. However, it must be properly installed and used only under the conditions specified within this manual and the specific approval certificates. Any device modification, improper installation, or use in a faulty or incomplete configuration will render warranty and product certifications invalid.
CaUtIon
The GT3000 contains no field repairable components. User performed service is limited to replacement of the gas sensor module.
CaUtIon
Hazardous location temperature limits exceed the product operational temperature limits. If the sensor is exposed to temperatures beyond the operational temperature limits listed in Appendix
F, then the sensor module (GTS) should be replaced or a response test, as described in the GT3000 Safety Manual (95-8685), shall be performed.
LIabILItIes
The manufacturer’s warranty for this product is void, and all liability for proper function of the detector is irrevocably transferred to the owner or operator in the event that the device is serviced or repaired by personnel not employed or authorized by Detector electronics Corporation, or if the device is used in a manner not conforming to its intended use.
CaUtIon
observe precautions for handling electrostatic sensitive devices.
NoTe
The sensor housing is made of Polyphthalamide
(PPA), 30% carbon filled (Material Manufacturer
RTP). Questions regarding chemical resistance should be addressed to:
www.det-tronics.com
US toll free 800-468-3244 or 952-941-5665
11.1
5
95-8616
installation
The gas detector can be installed either in a stand-alone configuration as a loop powered device, or it can be connected to a UD10/UD20 Universal Display Unit.
housing.
NoTe
The gas detector housing must be electrically connected to earth ground. A dedicated earth ground wire is provided on the transmitter for connection to earth ground or to a grounded
The most effective number and placement of detectors varies depending on the conditions on site. The individual designing the installation must often rely on experience and common sense to determine the detector quantity and best locations to adequately protect the area. Note that it is typically advantageous to locate detectors where they are accessible for maintenance. Locations near excessive heat or vibration sources should be avoided if possible.
Final suitability of possible gas detector locations should be verified by a site survey. If any questions arise regarding installation, please contact the factory.
The detector must always be installed per local installation code.
Before installing the gas detector, define the following application details:
DEvICE MOUNTING ORIENTATION
The gas detector must be mounted in a vertical position only, with the sensor pointing down (See Figure 5).
IDENTIFICATION OF vApOR(S) TO bE DETECTED
It is necessary to always identify the vapor(s) of interest at the job site. In addition, the fire hazard properties of the vapor, such as vapor density, flashpoint, and vapor pressure should be identified and used to assist in selecting the optimum detector mounting location within the area.
Important
The sensor should be oriented with the LeDs facing forward so they are easily visible to personnel within the area. To ensure correct orientation (the LeDs are not visible when power is off), position the GND lug on the left hand side and the calibration notch to the front. Note that the
LeDs are located directly above the calibration notch.
IDENTIFICATION OF DETECTOR MOUNTING lOCATIONS
Identification of the most likely leak sources and leak accumulation areas is typically the first step in identifying the best detector mounting locations. In addition, identification of air current/wind patterns within the protected area is useful in predicting gas leak dispersion behavior. This information should be used to identify optimum sensor installation points.
If the vapor of interest is lighter than air, place the sensor above the potential gas leak. Place the sensor close to the floor for gases that are heavier than air. Note that air currents may cause a gas that is slightly heavier than air to rise under some conditions. Heated gases may also exhibit the same phenomenon.
GND LUG
GREEN LED
CALIBRATION NOTCH
B2436
Figure 5—Correct Mounting Orientation for the GT3000
11.1
6
95-8616
DETECTOR INSTAllATION
3/4" NpT Models
3/4" NPT models have Tapered Threads and no Lock
Nut. Install the sensor as follows:
1. Screw the detector into the appropriate entry on the termination box. Ensure a minimum of 5 fully engaged threads. Use of teflon tape on NPT threads is recommended to prevent thread damage.
2. When the detector gets tight, note the position of the
LEDs, GND lug and calibration notch and adjust the detector as required so that the LEDs will be easily visible.
SENSOR TERMINATION bOX
A Det-Tronics sensor termination box (Model STB) is required for installing the sensor in a stand alone configuration, or for installing the GT3000 remotely from the UD10/UD20 Universal Display Unit.
When installing the GT3000 remotely from a UD10/
UD20, two-conductor shielded cable is required to prevent possible nuisance EMI/RFI. The maximum cable length between the GT3000 and the UD10/UD20 is 2000 ft.
WirinG
M25 Models
M25 models have Straight Threads and a Lock Nut.
Install the detector as follows:
1. Screw the detector lock nut as far back as it will go, then screw the detector into the appropriate entry on the termination box. Ensure a minimum of 7 fully engaged threads.
2. With the detector in the desired position (LEDs visible as shown in Figure 5), tighten the lock nut against the termination box to hold the detector securely in place.
3. Tighten the set screws (minimum of two) to prevent movement of the lock nut. See Figure 6.
pOWER SUpplY REqUIREMENTS
Calculate the total gas detection system power consumption rate in watts from cold start-up. Select a power supply with adequate capability for the calculated load. Ensure that the selected power supply provides sufficient regulated and filtered output power for the entire system. If a back-up power system is required, a float-type battery charging system is recommended. If an existing source of power is being utilized, verify that system requirements are met.
NoTe
The power supply must also meet the noise requirements for HART systems.
WIRING CAblE REqUIREMENTS
Always use proper cabling type and diameter for input power as well as output signal wiring. 22 to 14 AWG shielded stranded copper wire is recommended.
Always install a properly sized, master power fuse or breaker on the system power circuit.
Set Screws
Figure 6—Location of Lock Nut and Set Screws
(Metric Models Only)
NoTe
The use of shielded cable in conduit or shielded armored cable is highly recommended. In applications where the wiring is installed in conduit, dedicated conduit is recommended.
Avoid low frequency, high voltage, and non-signaling conductors to prevent nuisance eMI problems.
CaUtIon
The use of proper conduit installation techniques, breathers, glands, and seals is required to prevent water ingress and/or maintain the explosion-proof rating.
11.1
7
95-8616
INTRINSIC SAFETY bARRIERS
When the GT3000 is used in an intrinsically safe installation, care must be taken when selecting an I.S. barrier to ensure proper function of the device. The
GT3000 has been tested with the types of barriers listed in Tables 3 and 4.
GUIDElINES FOR INTRINSIC SAFETY WIRING
Intrinsically safe systems must be installed in accordance with the approved control drawings for the field equipment and the intrinsic safety barriers.
Capacitance and inductance of interconnecting wiring must always be included in wiring calculations.
Table 3 lists zener barriers. The third column gives the range of input voltage to the barrier. The upper limit is set by the barrier. The lower limit is limited by voltage drops in the 4-20 mA loop with a maximum of 10 Ohms of resistance in each leg of the loop.
Table 4 lists isolating barriers that provide a wider range of input power supply voltages and are less dependent on voltage drops in the loop. Input voltage to the barrier is specified by the barrier manufacturer.
Shielded twisted pair cables with at least 18 AWG conductors are recommended to ensure circuit performance.
The intrinsically safe conductors must be separated from all other wiring by placing them in separate conduits or raceways, or by an airspace of at least 2 inches (50 mm). When located within an enclosure, the conductors can be separated by a grounded metal or insulated partition. Wires must be tied down to prevent loosening and/or shorting.
For additional information regarding proper IS installation, refer to the Control Drawings in Appendix
H of this manual.
Intrinsically safe wiring must be identified. Raceways, cable trays, open wiring, and terminal boxes must be labeled as Intrinsically Safe. Intrinsically safe wiring may be light blue in color when no other conductors colored light blue are used.
Table 3—Acceptable Intrinsic Safety Barriers for use with GT3000 – Zener Barriers
Manufacturer
Turck
MTL
Pepperl & Fuchs
p/N
MZB87PX
MTL7787P+
Z787.h
Wiring enclosures should be located as close as possible to the hazardous area to minimize cable runs and reduce total capacitance of the wiring.
A high quality intrinsic safety ground is required. Some general rules for grounding intrinsically safe systems are:
• The maximum impedance of the grounding conductor between the barrier ground terminal and the main ground point must be less than 1 ohm.
• The grounding conductor must be a minimum of 12
AWG.
• Redundant grounding conductors are recommended to facilitate testing of the ground connection.
• The grounding conductor should be insulated and protected from the possibility of mechanical damage.
Table 4—Acceptable Intrinsic Safety Barriers for use with GT3000 – Isolating Barriers
Manufacturer
Turck
MTL
Pepperl & Fuchs
Stahl
p/N
IM33-11Ex-Hi
5541
KCD2-STC-Ex1
9160/13-10-11
WIRING pROCEDURE
Wire the transmitter as shown in Figures 7 through 12.
CaUtIon
If ripple on the main power source causes interference with the HART function, the use of an isolated power source (Figure 12) is recommended for best HART performance.
11.1
8
95-8616
SENSOR TERMINATION BOX
GREEN
RED
BLA
CK
BLACK
RED
BLACK
+
SEE NOTES 2 & 3
–
24 VDC
SEE NOTE 1
A2502
GT3000
GAS DETECTOR
NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE
END ONLY.
NOTE 2 250 OHM RESISTOR REQUIRED FOR HART
MENU ACCESS.
NOTE 3 EXTERNAL HART COMMUNICATION DEVICES
CAN BE CONNECTED ACROSS THE 250 OHM
RESISTOR OR ACROSS THE GT3000.
NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
Figure 7—GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Explosion-Proof)
11.1
HAZARDOUS LOCATION
SENSOR TERMINATION BOX
GREEN
RED
BLA
CK
BLACK
RED
BLACK
NON-HAZARDOUS LOCATION
SEE NOTES 2 & 3
+
–
24 VDC
SEE NOTE 1
A2530
GT3000
GAS DETECTOR
NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE
END ONLY.
NOTE 2 250 OHM RESISTOR REQUIRED FOR HART
MENU ACCESS.
NOTE 3 EXTERNAL HART COMMUNICATION DEVICES
CAN BE CONNECTED ACROSS THE 250 OHM
RESISTOR OR ACROSS THE GT3000.
NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
Figure 8— GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Intrinsically Safe)
9
95-8616
RED
BLACK
GREEN
UD20 DISPLAY UNIT
+
J2-6
–
J2-5
POWER
LOOP
SHIELD J2-4
J2-3
+
J2-2
–
SEE NOTE 1
J2-1 SHIELD
SENSOR
LOOP
J2
GT3000
GAS DETECTOR
NOTE 1 CONNECT THE GREEN DETECTOR LEAD TO THE
CHASSIS GROUND LUG ON THE INSIDE BOTTOM
OF THE UD20 DISPLAY UNIT ENCLOSURE.
NOTE 2 250 OHM RESISTOR REQUIRED FOR HART
MENU ACCESS.
NOTE 3 EXTERNAL HART COMMUNICATION DEVICES CAN BE
CONNECTED ACROSS THE 250 OHM RESISTOR,
ACROSS J2-5 AND J2-6, OR ACROSS J2-2 AND J2-3.
NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
NOTE 5 GROUND THE SHIELD AT THE POWER SOURCE
END ONLY.
Figure 9—GT3000 Wired Directly to UD20 Display Unit (Explosion-Proof)
+
SEE NOTES 2 & 3
–
24 VDC
SEE NOTE 5
B2478
11.1
SENSOR TERMINATION BOX
GREEN
RED
BLA
CK
BLACK
UD20 DISPLAY UNIT
+
J2-6
–
J2-5
POWER
LOOP
SEE NOTE 1
SHIELD J2-4
J2-3
+
RED
BLACK
J2-2
–
J2-1
SHIELD
SENSOR
LOOP
J2
SEE NOTES 2 & 3
GT3000
GAS DETECTOR
NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE
END ONLY.
NOTE 2 250 OHM RESISTOR REQUIRED FOR HART
MENU ACCESS.
NOTE 3 EXTERNAL HART COMMUNICATION DEVICES CAN BE
CONNECTED ACROSS THE 250 OHM RESISTOR,
ACROSS J2-5 AND J2-6, OR ACROSS J2-2 AND J2-3.
NOTE 4 JUNCTION BOXES MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
Figure 10—GT3000 with Sensor Termination Box Wired to UD20 Display Unit (Explosion-Proof)
10
+
–
24 VDC
SEE NOTE 1
D2408
95-8616
NON-HAZARDOUS LOCATION HAZARDOUS LOCATION
PLC 4-20 mA INPUT CARD
INPUT
4-20 mA
250
OHMS
MINIMUM
24 VDC
–
+
Notes: Resistor may be external if voltage input card is used.
Sinking resistance at PLC must be 250 ohms minimum for HART communication.
C2453
BLACK
RED
UD10
DISPLAY UNIT
Sensor Connector
J3
Output Loop
Connector
P1-3
4-20 mA +
P1-2
4-20 mA –
P1-1
P1
SHIELD
J2
J2-3
COM
J2-2
RS485 A
J2-1 RS485 B
MODBUS
Connector
P12
Power Supply Connector
P2
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
J4-6
J4-7
J4-8
J4-9
J4-10
J4-11
J4-12
J4
J4-1
J4-2
J4-3
J4-4
J4-5
GT3000
GREEN
SEE NOTE 1
GAS DETECTOR
NOTE 1 CONNECT THE GREEN DETECTOR LEAD
TO THE CHASSIS GROUND LUG ON THE
INSIDE BOTTOM OF THE DISPLAY UNIT
ENCLOSURE.
NOTE 2 JUNCTION BOXES MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
Figure 11—GT3000 Wired Directly to the UD10 Display Unit / UD10 Wired to PLC with 4-20 mA Non-Isolated Sourcing Output
11.1
INPUT
4-20 mA
250
OHMS
MINIMUM
24 VDC
–
+
NON-HAZARDOUS LOCATION
PLC 4-20 mA INPUT CARD
Notes: Resistor may be external if voltage input card is used.
Sinking resistance at PLC must be 250 ohms minimum for HART communication.
C2479
HAZARDOUS LOCATION
BLACK
RED
UD10
DISPLAY UNIT
GREEN
Sensor Connector
J3
Output Loop
Connector
P1-3 4-20 mA +
P1-2
4-20 mA –
SHIELD
P1-1
P1
J2
J2-3
COM
J2-2 RS485 A
J2-1
RS485 B
MODBUS
Connector
P12
Power Supply Connector
P2
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
J4-8
J4-9
J4-10
J4-11
J4-1
J4-2
J4-3
J4-4
J4-5
J4-6
J4-7
J4-12
J4
24 VDC
–
+
GT3000
SEE NOTE 1
GAS DETECTOR
NOTE 1 CONNECT THE GREEN DETECTOR
LEAD TO THE CHASSIS GROUND
LUG ON THE INSIDE BOTTOM OF
THE DISPLAY UNIT ENCLOSURE.
NOTE 2 JUNCTION BOXES MUST BE
ELECTRICALLY CONNECTED
TO EARTH GROUND.
Figure 12—GT3000 Wired Directly to the UD10 Display Unit / UD10 Wired to PLC with 4-20 mA Isolated Sourcing Output
11
95-8616
calibration
GT3000 CAlIbRATION
The GT3000 supports one person calibration, which can be initiated locally using a calibration magnet, or remotely with a command from the HART interface.
The calibration process is automatic, with the exception of gas delivery. LEDs on the transmitter guide the operator when to apply and remove the calibration gas
See Table 5.
NoTe
The HART interface allows the operator to adjust the calibration gas concentration within the range of 30 to 90% full scale. The default value for all gas sensors except oxygen is 50% full scale. oxygen sensors use a default value of 20.9%.
The calibration process proceeds automatically after initiation. Onboard LEDs signal the operator when to apply the calibration gas and inform of the progress.
The calibration can be aborted by activating the magnetic switch or with a command from the HART communication device in lieu of applying the calibration gas.
If the calibration process takes longer than 10 minutes, the detector will time-out and signal a calibration fault.
If the calibration sequence is aborted or not completed successfully, the detector reverts back to the previous calibration values and signals a calibration fault. The calibration fault can be cleared by activating the magnetic switch for one second or by performing a successful calibration.
All GT3000 gas detectors require a two-point calibration — zero and span. The calibration process can be initiated using the magnetic switch or through a
HART interface, such as the UD10/UD20. All sensors, including oxygen, should be in clean air (20.9% oxygen) when the calibration sequence is initiated.
The calibration process can fail for the following causes:
• Zero is out of range
• Span is out of range
• Time-Out.
Table 5— LEDs During Calibration
Calibration Step
Waiting for Zero
Yellow lED
Steady
The time and date of calibration events are logged in non-volatile memory along with the calibration outcome.
Possible calibration scenarios include the following:
• Successful Calibration
• Aborted Calibration
• Failed Calibration and the Cause
Waiting for Gas
Waiting for Span
Blinking
Blinking
The Sensor Module stores calibration data in non-volatile memory to allow the sensor to be calibrated off-site and installed in the field without the need for re-calibration.
Remove Cal Gas Off
11.1
12
95-8616
CAlIbRATION pROCEDURE
NoTe
When attaching or removing the calibration cup, push or pull the cup with a slight
clockwise twist.
Turning counterclockwise can cause the filter assembly on the GT3000 to loosen. If the filter assembly is inadvertently loosened, tighten it by hand (no tools required).
NoTe
The calibration procedure must be completed within a ten minute period. If the calibration is not completed, a calibration fault will be generated and the transmitter will continue to use the previous calibration data.
Toxic and Hydrogen Sensors
1. Clean air must be present at the GT3000 sensor module prior to initiating calibration. The use of bottled air is recommended.
NoTe
To ensure reliable detection performance, calibration should be performed at regularly scheduled intervals. Various factors affect the time interval between periodic calibrations
(typically 30, 60, or 90 day intervals, depending on the ambient conditions).
Calibration of ammonia sensor is recommended any time the sensor has been exposed to 90 ppm ammonia.
NoTe
2. Initiate calibration by momentarily holding the calibration magnet against the designated location on the sensor module (see Figure 13) until the green LED turns off and the yellow LED turns on steady (approximately one second). Remove the magnet when the green LED turns off. The detector immediately begins taking zero readings.
Calibration can also be initiated via HART interface
(see Appendix G) or the UD10 (see manual number
95-8618).
Oxygen Sensor
1. Using the magnet, activate the magnetic calibration switch on the GT3000. The green LED turns off and the yellow LED turns on steady.
3. When the zero calibration is complete, the yellow
LED changes from steady to blinking. Apply the calibration gas to the sensor.
2. The device automatically performs the zero calibration.
3. When the yellow LED on the GT3000 flashes, the device automatically performs the span calculation.
If using bottled 20.9% oxygen, apply immediately.
4. When the yellow LED turns off, remove the calibration gas. The gas level at the sensor gradually returns to zero. The green LED turns on steady to indicate that the device has returned to normal operation, using the new calibration data.
4. After successful calibration, the yellow LED turns off and the green LED turns on steady to indicate that the device has returned to normal operation, using the new calibration data. Remove calibration gas (if used).
LED
PLACE MAGNET HERE
TO ACTIVATE INTERNAL
MAGNETIC SWITCH
B2452
Figure 13—Location of Magnetic Switch on GT3000 Detector
11.1
13
95-8616
maintenance
NoTe
Refer to the GT3000 Safety Manual (number
95-8685) for specific requirements and recommendations applicable to the proper installation, operation, and maintenance of all
SIL-Certified GT3000 gas detectors.
ROUTINE INSpECTION
The gas inlet to the sensor should be inspected periodically, or during scheduled maintenance, to ensure that external obstructions such as plastic bags, litter, heavy oil and tar, paint, mud, snow, or other materials do not block the flow of gas to the sensor, thereby impairing the performance of the device.
To replace a dirty or damaged filter, simply grasp the filter assembly and twist counterclockwise to remove.
Screw the new filter in place on the sensor module. Do not overtighten. See Figure 14.
To ensure reliable protection, it is important to check and calibrate the detection system on a regularly scheduled basis. The frequency of these checks is determined by the requirements of the particular installation – typically
30, 60, or 90 day intervals, depending on the ambient conditions.
SENSOR MODUlE REplACEMENT
(live Maintenance)
The hot swappable, intrinsically safe sensor module can be replaced in the field without removing power or de-classifying the hazardous area.
To replace the sensor module, locate the three captive screws on the front of the module as shown in Figure
15. Loosen these screws and remove the old sensor module. Install the new sensor module onto the transmitter, and tighten the screws. To ensure proper moisture ingress protection and grounding of the plastic nosepiece, tighten the screws to 70-100 oz-in (0.5-0.7
N-m).
Important
Always exercise caution when working in combustible gas areas. Follow replacement instructions explicitly.
NoTe
Removing the sensor module with power applied will result in a fault condition until a new sensor module of the same type is installed. When replacing an oxygen sensor, this action will result in an alarm condition as the decreasing 4-20 mA signal passes through the alarm range. Inhibit response devices to prevent unwanted actuation.
NoTe oxygen (o
2
) electrochemical sensors contain lead (Pb). observe all local waste management requirements when disposing of exhausted o
2 electrochemical sensors.
NoTe electrochemical sensors are highly sensitive to antiseptic wipes and/or cleaning products that contain alcohol and antibacterial/antiviral agents.
Antiseptic products should be removed from areas where sensors are stored, handled, or used. If antiseptic products are being used on workers' hands, sufficient time should be allowed for the alcohol to evaporate before handling sensors.
TURN FILTER COUNTERCLOCKWISE
TO REMOVE. NO TOOLS REQUIRED.
A2481
Figure 14—GT3000 with Replaceable Filter Removed
11.1
14
LOOSEN CAPTIVE PHILLIPS
SCREWS (3) TO REMOVE
SENSOR MODULE.
B2451
Figure 15—Location of Screws for Sensor Module Replacement
95-8616
DeVice repair anD retUrn
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A
written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure
.
Pack the unit properly. Always use sufficient packing material. Where applicable, use an antistatic bag as protection from electrostatic discharge.
NoTe
Inadequate packaging that ultimately causes damage to the returned device during shipment will result in a service charge to repair the damage incurred during shipment.
Return all equipment transportation prepaid to the factory in Minneapolis.
NoTe
It is highly recommended that a complete spare be kept on hand for field replacement to ensure continuous protection.
orDerinG information
Sensor module (GTS) and transmitter (GTX) must be ordered separately. Refer to the Transmitter and Sensor
Model Matrix on next page for ordering details.
GTS GAS SENSORS
Gas Concentration
Hydrogen Sulfide (H
Hydrogen Sulfide (H
2
2
S)
S)
Hydrogen Sulfide (H
2
S)
Oxygen (O
2
)*
Carbon Monoxide (CO)
Carbon Monoxide (CO)
0-20 ppm
0-50 ppm
0-100 ppm
0-25% V/V
0-100 ppm
0-500 ppm
Ammonia (NH
3
)
Sulfur Dioxide (SO
2
)
Sulfur Dioxide (SO
2
)
Chlorine (Cl
2
)
Hydrogen (H
2
)
Nitrogen Dioxide (NO
2
)
0-100, or 0-500 ppm
0-20 ppm
0-100 ppm
0-10 ppm
0-1000 ppm
0-20 ppm
*Oxygen detector for O
2
depletion (< 21% V/V) only.
CAlIbRATION kITS FOR GAS SENSORS part Number Gas / Concentration
010274-001 H
2
S / 10 ppm
010274-002 H
010274-003 H
010274-008 H
2
2
2
S / 25 ppm
S / 50 ppm
010274-009 O
2
/ 500 ppm
/ 20.9%
010274-010
010274-011
010274-005
010274-006
010274-016
CO / 50 ppm
CO / 250 ppm
NH
010274-004 Cl
2
3
NH
3
010274-013 SO
2
010274-014 SO
2
NO
2
/ 50 ppm
/ 250 ppm
/ 10 ppm
/ 50 ppm
/ 5 ppm
/ 10 ppm
Replacement gas cylinders for all calibration kits are available.
pARTS & ACCESSORIES part Number
009700-001
009737-001
107427-059
101678-007
162552-001
009640-001
012509-001
012509-002
010780-003
010783-001
012513-XXX*
012514-XXX*
Description
Magnetic Tool
Calibration Cup
Calibration Cup O-ring
3 Foot Tubing
Regulator, 1 LPM
Replacement Filter
Q312 Sample Draw without Fittings
Q312 Sample Draw with Fittings
GT3000 Remote Calibration Adaptor
GT3000 Remote Calibration Filter
Q912 Duct Mount Enclosure, M25
Q912 Duct Mount Enclosure, 3/4"
*Refer to the Product Catalog for a list of options.
ASSISTANCE
For assistance in ordering a system to meet the needs of a specific application, contact:
Detector Electronics Corporation
6901 West 110th Street
Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491
Fax: (952) 829-8750
Web site: www.det-tronics.com
E-mail: [email protected]
11.1
15
95-8616
GTS Sensor Model Matrix
MODEl
GTS
DESCRIpTION
Gas Sensor Module
TYpE GAS / RANGE
H2S
H2S+
Hydrogen Sulfide
20p
0 - 20 PPM
50p
0 - 50 PPM
100p
0 - 100 PPM
Hydrogen Sulfide
Cl2
NH3
H2
O2
CO
SO2+
NO2
20p
50p
100p
Chlorine
10p
Ammonia
100p
500p
0 - 20 PPM
0 - 50 PPM
0 - 100 PPM
0 - 10 PPM
100p
500p
Sulfur Dioxide
0 - 100 PPM
0 - 500 PPM
Hydrogen
1000p
0 - 1000 PPM
Oxygen
25v
Carbon Monoxide
0 - 25 % by Vol
0 - 100 PPM
0 - 500 PPM
20p
100p
0 - 20 PPM
0 - 100 PPM
Nitrogen Dioxide
20p
0 - 20 PPM
TYpE
D
R
S
T
W b
C
APPROVAL
*
INMETRO (Brazil)
CSA
DNV
Russia
SIL
SIL/FM/CSA/ATEX/CE/IECEx
FM/CSA/ATEX/CE/IECEx
*
Type Approval can use one or more letters to designate the Approvals on the product.
11.1
16
95-8616
GTX Transmitter Model Matrix
MODEl DESCRIpTION
GTX
Gas Transmitter
TYpE MATERIAl
S
Stainless Steel (316)
TYpE THREAD SIZE
N
M
3/4" NPT
Metric M25
TYpE
26
29
OUTpUTS
4-20 mA, HART (3.5 mA FAULT)
4-20 mA, HART (2.45 mA FAULT)
TYpE b
R
W
AppROvAlS
INMETRO (Brazil)
Russia
FM/CSA/ATEX/CE/IECEx
TYpE
4
5
ClASSIFICATION (Division/Zone)
Intrinsically Safe
Explosion-Proof
Note: Approvals Type W and B are SIL 2 Capable when used with an H
2
S or O
2
GTS sensor module.
11.1
17
95-8616
appenDix a
FM AppROvAl DESCRIpTION
The following items, functions and options describe the FM approval.
AppROvAl
Electrochemical Gas Detector, GT3000 Series.
Explosion Proof Model
Class I, Div. 1, Groups A, B, C, & D (T4).
Class I, Div. 2, Groups A, B, C, & D (T4).
Class I, Zone 1, AEx d mb [ia Ga] IIC T4.
IP66.
Conduit seal not required.
Acidic atmospheres excluded.
NoTe
The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of installation to provide protection for the flying leads.
Intrinsically Safe Model
IS Class I, Div. 1, Groups A, B, C, & D (T4).
Class I, Zone 0, AEx ia IIC (T4).
IP66.
NoTe
In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an approved I.S. barrier.
For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.
Performance verified per ANSI/ISA 92.00.01, FM6340/41 and EN50104.
11.1
18
95-8616
part Number
010274-001
010274-002
010274-003
010274-008
010274-009
010274-010
010274-011
010274-005
010274-006
010274-013
010274-014
010274-004
010274-016
009700-001
009737-001
107427-059
101678-007
162552-001
009640-001
AppROvED ACCESSORIES
Description
Gas Calibration Kit, 10 ppm H
2
S
Gas Calibration Kit, 25 ppm H
2
S
Gas Calibration Kit, 50 ppm H
2
S
Gas Calibration Kit, 500 ppm H
2
Gas Calibration Kit, 20.9% O
2
Gas Calibration Kit, 50 ppm CO
Gas Calibration Kit, 250 ppm CO
Gas Calibration Kit, 50 ppm NH
3
Gas Calibration Kit, 250 ppm NH
3
Gas Calibration Kit, 10 ppm SO
2
Gas Calibration Kit, 50 ppm SO
2
Gas Calibration Kit, 5 ppm Cl
2
Gas Calibration Kit, 10 ppm NO
2
Magnetic Tool
Calibration Cup
Calibration Cup O-ring
3 Foot Tubing
Regulator, 1 LPM
Replaceable Filter
11.1
19
95-8616
appenDix b
CSA CERTIFICATION DESCRIpTION
The following items, functions and options describe the CSA approval.
AppROvAl
Electrochemical Gas Detector, GT3000 Series.
Explosion Proof Model
Class I, Div. 1, Groups A, B, C, & D (T4).
Class I, Div. 2, Groups A, B, C, & D (T4).
Class I, Zone 1, AEx d mb [ia Ga] IIC T4.
IP66.
Conduit seal not required.
Acidic atmospheres excluded.
NoTe
The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of installation to provide protection for the flying leads.
Intrinsically Safe Model
Class I, Div. 1 & 2, Groups A, B, C, & D (T4).
IP66.
NoTe
In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an approved I.S. barrier.
For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.
11.1
20
95-8616
appenDix c
ATEX AppROvAl DESCRIpTION
The following items, functions and options describe the ATEX approval.
AppROvAl
Electrochemical Gas Detector, GT3000 Series.
Explosion Proof Model
®
II 2(1)G.
Ex d mb [ia Ga] IIC T4 Gb IP66.
FM10ATEX0009X.
NoTe
The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of installation to provide protection for the flying leads.
Intrinsically Safe Model
®
II 1 G Ex ia IIC T4 Ga IP66.
FM08ATEX0045X.
NoTe
In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an approved I.S. barrier.
For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.
11.1
21
95-8616
appenDix D
IECEx AppROvAl DESCRIpTION
The following items, functions and options describe the IECEx approval.
AppROvAl
Electrochemical Gas Detector, GT3000 Series.
Explosion Proof Model
Ex d mb [ia Ga] IIC T4 Gb IP66.
IECEx FMG 10.0003X.
NoTe
The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of installation to provide protection for the flying leads.
Intrinsically Safe Model
Ex ia IIC T4 Ga IP66.
IECEx FMG 08.0005X.
NoTe
In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an approved I.S. barrier.
For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.
11.1
22
95-8616
appenDix e
OTHER AppROvAlS
The following items, functions and options describe various other approvals applicable to the GT3000.
SIl AppROvAl
IEC 61508
Certified SIL 2 Capable.
SIL Certification includes H
2
S and O
2
GTS models only. For specific information regarding SIL models, refer to the
GT3000 Safety Reference Manual, form 95-8685.
INMETRO (bRAZIl)
Explosion Proof Model
UL-BR 15.0752X
Ex d mb [ia Ga] IIC T4 Gb IP66
Tamb –40°C to +50°C (H
2
S)
Tamb –20°C to +50°C (other)
NoTe
The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of installation to provide protection for the flying leads.
NoTe
Consideration must be given to overall Gas System Performance Requirements.
Intrinsically Safe Model
UL-BR 15.0404X
Ex ia IIC T4 Ga IP66
Tamb –40°C to +50°C
NoTe
In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an approved I.S. barrier.
For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.
DNv
Type Approval Certificate No. A-12358.
MED
Certificate No. MED-B-6708.
RUSSIA / kAZAkHSTAN / INDIA
Contact Det-Tronics for details.
11.1
23
95-8616
appenDix f
DEClARATION OF CONFORMITY
11.1
For a copy of the original document, please contact the factory.
24
95-8616
appenDix G
SENSOR COMpARISON/CROSS SENSITIvITY
Electrochemical Gas Sensors
Gas Range
Response
Time
1
Accuracy of
Reading
(Whichever is Greater)
Operating
Temperature Range
Zero Drift
Hydrogen Sulfide
(H
2
(H
(H
(H
(H
(H
2
2
2
2
2
S)
Hydrogen Sulfide
S)
Hydrogen Sulfide
S)
Hydrogen Sulfide+
S+)
Hydrogen Sulfide+
S+)
Hydrogen Sulfide+
S+)
Ammonia (NH
Ammonia (NH
Oxygen (O
2
)
3
3
)
)
Carbon
Monoxide (CO)
Carbon
Monoxide (CO)
Sulfur Dioxide+
(SO
2
+)
Sulfur Dioxide+
(SO
2
+)
Chlorine
(Cl
2
)
Hydrogen
(H
2
)
Nitrogen Dioxide
(NO
2
)
0-20 PPM
0-50 PPM
0-100 PPM
0-20 PPM
0-50 PPM
0-100 PPM
0-100 PPM
0-500 PPM
0-25% V/V
0-100 PPM
0-500 PPM
0-20 PPM
0-100 PPM
0-10 PPM
0-1,000 PPM
0-20 PPM
2
2
3
T20 = ≤7 Sec
T50 = ≤10 Sec.
T90 = ≤16 Sec.
T20 = ≤4 Sec
T50 = ≤7 Sec.
T90 = ≤16 Sec.
T20 = ≤5 Sec
T50 = ≤8 Sec.
T90 = ≤21 Sec.
T20 = ≤10 Sec
T50 = ≤13 Sec.
T90 = ≤23 Sec.
T20 = ≤6 Sec
T50 = ≤9 Sec.
T90 = ≤15 Sec.
T20 = ≤6 Sec
T50 = ≤8 Sec.
T90 = ≤15 Sec.
T50 = 24 Sec.
T90 = 65 Sec.
T50 = 30 Sec.
T90 = 120 Sec.
T20 = 7 Sec.
T90 = 30 Sec.
T50 = 15 Sec.
T90 = 40 Sec.
T50 = 12 Sec.
T90 = 25 Sec.
T50 = 12 Sec.
T90 = 30 Sec.
T50 = 15 Sec.
T90 = 35 Sec.
T50 = ≤14 Sec.
T90 = ≤34 Sec.
T50 = 8 Sec.
T90 = 60 Sec.
T50 = 7 Sec.
T90 = 31 Sec.
±2 ppm or
±10% of Reading
±2 ppm or
±10% of Reading
±2 ppm or
±10% of Reading
±2 ppm or
±10% of Reading
±2 ppm or
±10% of Reading
±2 ppm or
±10% of Reading
±4 ppm or
±10% of Reading
±4 ppm or
±10% of Reading
< 0.5% V/V
±5 ppm or
±10% of Reading
±5 ppm or
±10% of Reading
±0.6 ppm or
±10% of Reading
±0.6 ppm or
±10% of Reading
±0.6 ppm or
±10% of Reading
±50 ppm or
±10% of Reading
±2 ppm or
±10% of Reading
–40°C to +50°C
–40°C to +50°C
–40°C to +50°C
–40°C to +55°C
–40°C to +55°C
–40°C to +55°C
–20°C to +40°C
–20°C to +40°C
–20°C to +50°C
–20°C to +50°C
–20°C to +50°C
–40°C to +55°C
–40°C to +55°C
–20°C to +50°C
–20°C to +40°C
–20°C to +40°C
± 1 ppm/Mo.
± 1 ppm/Mo.
± 2 ppm/Mo.
± 1 ppm/Mo.
± 1 ppm/Mo.
± 2 ppm/Mo.
± 2 ppm/Mo.
± 10 ppm/Mo.
< 2 %/Mo.
± 2 ppm/Mo.
± 9 ppm/Mo.
± 0.4 ppm/Mo.
± 0.4 ppm/Mo.
< 0.2 ppm/Mo.
± 20 ppm/Mo.
± 0.1 ppm/Mo.
1
Time to reach percentage of final reading when gas concentration equal to full scale is applied to sensor.
2
Background concentrations of ammonia may shorten lifetime of sensor.
3
Sensor approved for oxygen depletion (< 21% V/V) only.
4
Factory Mutual Performance Approved.
performance
Approved Standard
ISA 92.00.01
ISA 92.00.01
ISA 92.00.01
ISA 92.00.01
ISA 92.00.01
ISA 92.00.01
FM6340
4
Det-Tronics Verified
(CSA Exd)
BS EN 50104
ISA 92.00.01
ISA 92.00.01
Det-Tronics Verified
(CSA Exd)
Det-Tronics Verified
(CSA Exd)
FM6340
4
4
4
Det-Tronics Verified
(CSA Exd)
Det-Tronics Verified
(CSA Exd)
4
4
4
4
4
4
4
11.1
25
95-8616
Typical Cross Sensitivity of H
2
S Sensor (0-20 ppm / 0-50 ppm / 0-100 ppm)
Gas
Carbon monoxide
Sulfur dioxide
Nitric oxide
Hydrogen
Ammonia
Nitrogen dioxide
Methanol
Concentration
300 ppm
5 ppm
35 ppm
10000 ppm
50 ppm
5 ppm
200 ppm
Reading
H
2
S
≤ 2 ppm
~ 1 ppm
H
2
S+
≤ 2 ppm
~ 0 ppm
< 0.7 ppm
≤ 10 ppm
~ 0 ppm
~ –1 ppm
~ 0 ppm
~ 0 ppm
~ 0 ppm
~ 0 ppm
Typical Cross Sensitivity of NH
3
Sensor (0-100 ppm)
Gas
Alcohols
Carbon dioxide
Carbon monoxide
Hydrocarbons
Hydrogen
Hydrogen sulfide
Concentration
1000 ppm
5000 ppm
100 ppm
% Range
10000 ppm
20 ppm
1
Short time gas exposure in minute range.
Reading
0 ppm
0 ppm
0 ppm
0 ppm
0 ppm
~ 2 ppm
1
Typical Cross Sensitivity of NH
3
Sensor (0-500 ppm)
Gas
Alcohols
Carbon monoxide
Chlorine
Nitrogen dioxide
Sulfur dioxide
Hydrogen
Hydrogen sulfide
Concentration
1000 ppm
100 ppm
5 ppm
10 ppm
20 ppm
3000 ppm
20 ppm
Reading
0 ppm
0 ppm
0 ppm
0 ppm
–40 ppm
0 ppm
2 ppm
Typical Cross Sensitivity of CO Sensor (0-100 ppm / 0-500 ppm)
Gas
Hydrogen sulfide
Sulfur dioxide
Nitric oxide
Chlorine
Hydrogen
Nitrogen dioxide
Concentration
15 ppm
5 ppm
35 ppm
1 ppm
100 ppm
5 ppm
Reading
CO
~ 45 ppm
~ 2.5 ppm
~ 10 ppm
–1 ppm
< 40 ppm
~ –3 ppm
Typical Cross Sensitivity of SO
2
Sensor (0-20 ppm / 0-100 ppm)
Gas
Carbon monoxide
Nitric oxide
Nitrogen dioxide
Hydrogen Sulfide
Chlorine
Ammonia
Hydrogen
Hydrogen Cyanide
Acetylene
Ethene
Concentration
300 ppm
50 ppm
6 ppm
25 ppm
5 ppm
20 ppm
400 ppm
10 ppm
10 ppm
50 ppm
Reading
< 1 ppm
0-5 ppm
< –10 ppm
< 0.1 ppm
< –2 ppm
0 ppm
< 1 ppm
< 5 ppm
< 30 ppm
< 45 ppm
Typical Cross Sensitivity of Cl
2
Sensor (0-10 ppm)
Gas
Carbon monoxide
Hydrogen sulfide
Sulfur dioxide
Nitric oxide
Concentration
300 ppm
15 ppm
5 ppm
35 ppm
Reading
0 ppm
~ –7.5 ppm
0 ppm
0 ppm
Typical Cross Sensitivity of NO
2
Sensor (0-20 ppm)
Gas
Alcohols
Carbon dioxide
Chlorine
Nitric oxide
Sulfur dioxide
Hydrogen
Concentration
1000 ppm
5000 ppm
1 ppm
100 ppm
20 ppm
3000 ppm
Reading
0 ppm
0 ppm
≤ 1 ppm
0.4 ppm
5 ppm
0 ppm
For details on other interfering gases, please contact Detector Electronics Corp.
11.1
26
95-8616
appenDix H
HART COMMUNICATION
Hart menU strUctUre
This section displays the menu tree for the GT3000. The menu tree shows the primary commands and options available when using menu selections of a HART handheld communicator.
11.1
27
95-8616
11.1
28
95-8616
appenDix i
INTRINSIC SAFETY CONTROl DRAWING — FM
009803-001 Rev. D
11.1
29
95-8616
INTRINSIC SAFETY CONTROl DRAWING — CSA
009803-002 Rev. b
11.1
30
95-8616
EXplOSION pROOF CONTROl DRAWING — FM
012555-001 Rev. A
11.1
31
95-8616
95-8616
FlexSonic TM Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
PointWatch Eclipse ® IR
Combustible Gas Detector
FlexVu ® Universal Display with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
Corporate Office
6901 West 110 th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
All trademarks are the property of their respective owners.
© 2015 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001— the world’s most recognized quality management standard.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement