95-8616


Add to my manuals
34 Pages

advertisement

95-8616 | Manualzz

Instructions

Electrochemical Gas Detector

GT3000 Series

Includes Transmitter (GTX) and Sensor Module (GTS)

11.1 Rev: 8/15 95-8616

Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Gts sensor Module . . . . . . . . . . . . . . . . . . . . . . 1

GtX transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . 2 real time clock . . . . . . . . . . . . . . . . . . . . . . . . . . 2

History/event Logs . . . . . . . . . . . . . . . . . . . . . . . . 2

HArt communication . . . . . . . . . . . . . . . . . . . . . 3

Magnetic switch . . . . . . . . . . . . . . . . . . . . . . . . . . 3

LeDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 specificAtions . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 cALiBrAtion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Gt3000 calibration . . . . . . . . . . . . . . . . . . . . . . 12 calibration procedure . . . . . . . . . . . . . . . . . . . . . 13

MAintenAnce . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 routine inspection . . . . . . . . . . . . . . . . . . . . . . . 14 sensor Module replacement . . . . . . . . . . . . . . . 14

DeVice repAir AnD return . . . . . . . . . . . . . . . 15 iMportAnt sAfety notes . . . . . . . . . . . . . . . . . . 5 orDerinG inforMAtion . . . . . . . . . . . . . . . . . . 15

Gts Gas sensors . . . . . . . . . . . . . . . . . . . . . . . 15 calibration Kits for Gas sensors . . . . . . . . . . . . 15 parts & Accessories . . . . . . . . . . . . . . . . . . . . . . 15 instALLAtion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 identification of Vapor(s) to be Detected . . . . . . . 6 identification of Detector Mounting Locations . . . 6

Device Mounting orientation . . . . . . . . . . . . . . . . 6

Detector installation . . . . . . . . . . . . . . . . . . . . . . . 7 sensor termination Box . . . . . . . . . . . . . . . . . . . . 7 wirinG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 power supply requirements . . . . . . . . . . . . . . . . 7 wiring cable requirements . . . . . . . . . . . . . . . . . 7 intrinsic safety Barriers . . . . . . . . . . . . . . . . . . . . 8

Guidelines for intrinsic safety wiring . . . . . . . . . . 8 wiring procedure . . . . . . . . . . . . . . . . . . . . . . . . . 8

AppenDiX A — fM ApproVAL Description . . . . . 18

AppenDiX B — csA certificAtion Description . 20

AppenDiX c — AteX ApproVAL Description . . . 21

AppenDiX D — iecex ApproVAL Description . . 22

AppenDiX e — otHer ApproVALs . . . . . . . . . . . . . 23

AppenDiX f — DecLArAtion of conforMity . . 24

AppenDiX G — sensor coMpArison / cross sensitiVity . . . . . . . . . . . . 25

AppenDiX H — HArt coMMunicAtion . . . . . . . . . 27

AppenDiX i — controL DrAwinGs . . . . . . . . . . . . 29

INSTRUCTIONS

Electrochemical Gas Detector

GT3000 Series

Includes Transmitter (GTX)

and Sensor Module (GTS)

Sensor

Module

(GTS)

Transmitter

(GTX)

Detector (GT3000)

Important

Be sure to read and understand the entire instruction manual before installing or operating the gas detection system. This product is intended to provide early warning of the presence of a toxic or explosive gas mixture, or of oxygen depletion. Proper device installation, operation, and maintenance are required to ensure safe and effective operation. If this equipment is used in a manner not specified in this manual, safety protection may be impaired.

that are able to monitor a linear 4-20 mA dc signal. All alarm functions are provided by the monitoring device.

The GT3000 is designed and approved as a stand alone unit for use in hazardous locations. It is suitable for outdoor applications that require IP66 rating and uses a hydrophobic filter that is easily replaced without opening the device or use of tools. The GT3000 is furnished as either explosion-proof or intrinsically safe.

The GT3000 supports local one-person calibration with the use of a magnet and on-board LED.

Description

The GT3000 Electrochemical Gas Detector is an intelligent stand-alone industrial gas detector, designed to provide continuous monitoring of the atmosphere for hazardous gas leaks or oxygen depletion. It is fully performance tested and approved by Factory Mutual.

Refer to Appendix F for individual gas specifications.

GTS SENSOR MODUlE

The GTS’s electrochemical sensor cell uses capillary diffusion barrier technology for monitoring gas concentrations in ambient air.

The GT3000 Gas Detector consists of a replaceable sensor module (Model GTS) connected to a transmitter module (Model GTX). A single transmitter is compatible with all GTS sensor modules. A variety of electrochemical sensor models are available in various concentration ranges.

The GT3000 is a 2-wire device that generates a 4-20 mA output signal with HART communication that is proportional to the concentration of the target gas.

live Maintenance

The hot swappable GTS sensor module is intrinsically safe and allows live maintenance while under power, without de-classifying the hazardous area. When the sensor is removed, the transmitter generates a fault output. If a new sensor of the same type and range is installed, the fault self-clears. However, if the type or range of the new sensor module does not match the old, the transmitter generates a fault until a successful calibration or acceptance of the new sensor type is completed. For additional information regarding Live

Maintenance, refer to “Sensor Module Replacement” in the Maintenance section of this manual.

The GT3000 is compatible with FlexVu

®

Model UD10 and

UD20 Universal Display Units, as well as other devices

11.1

©

Detector Electronics Corporation 2015

Rev: 8/15 95-8616

Automatic Sensor Module Recognition

The transmitter provides automatic gas sensor recognition, allowing the operator to access the following information via HART, or a UD10 or UD20

Universal display:

• Date of manufacture of the sensor module

• Sensor module serial number

• Gas type

• Measurement range

HISTORY/EvENT lOGS

Both the transmitter and sensor are able to store 256 history logs, which are saved in non-volatile memory and retained through power cycles. A UD10/UD20

Universal Display Unit, a HART communication device, or AMS software is required to view the history logs.

The sensor module is factory programmed for the gas type and measurement range. When the sensor module powers up, the transmitter reads and acknowledges the gas type and measurement range.

GTX TRANSMITTER

The transmitter output is a linear 4-20 mA dc signal with HART communication that directly corresponds to

0-100% full scale.

A 3.8 mA output indicates sensor calibration in progress

(17.3 mA for O

2

sensor). The GT3000 comes with one of two pre-programmed fault output levels: 2.45 mA or

3.5 mA.

Priority of output signals from highest to lowest is:

Sensor logging Capability

The sensor module logs the following operating parameters in non-volatile memory:

• Running Hours

- The sensor module maintains the total operating hours, and cannot be reset.

• Min/Max Temperature

- The sensor module maintains the minimum and maximum temperatures with a date and time stamp.

• Calibration

- The sensor module logs the calibration history with a date and time stamp, along with the success or cause of failure codes. See Table 1. The zero and span values (AD converter values recorded at the time of calibration) are also saved. This allows the logs to follow the sensor module when it is calibrated separately from the transmitter. (Calibration data is available via a UD10/UD20, a HART communication device, or AMS software.)

The sensor module gets the current time and date from the transmitter and provides calibration log information to the transmitter. See Figure 1.

1

2

3

Calibration

(In progress)

Fault

Gas Level

Transmitter Wiring

The GTX transmitter is a two-wire loop powered device that uses a three-wire cable (power, signal, and earth ground) for connecting to a controller or monitoring device. The use of shielded cable is required.

REAl TIME ClOCk (RTC)

The GTX transmitter has a real time clock with battery back-up, that is used for time stamping the event logs.

The time and date are set and read using a UD10/

UD20 Universal Display Unit, a HART communication device, or AMS software. The time stamp on the logs will not be correct if the RTC in the transmitter is not set correctly.

Table 1—Calibration Status Codes

8

9

10

11

5

6

7

Number

0

1

2

3

4

Definition

EMPTY LOG

NOT USED

NOT USED

ZERO CAL

SPAN CAL

ABORT CAL

FAILED CAL

NOT USED

NOT USED

INIT CAL LOG

NOT USED

CLR CAL FAULTS

11.1

2

95-8616

Transmitter updates sensor module time / date

GT3000

Gas Detector

Transmitter

RTC

Event Logs

HART Interface

Transmitter reads calibration logs from sensor

Sensor Module

Calibration Logs

GREEN LED (ON)

YELLOW LED (OFF)

Figure 1—GT3000 Logging

A2450

Transmitter logging Capability

The transmitter logs the following events with a time and date stamp:

• Power-up

• Sensor change

• All Faults.

Figure 3— Location of LEDs on GT3000 Gas Detector

MAGNETIC SWITCH

The GT3000 is furnished with an internal magnetic reed switch as part of the user interface. The magnetic switch allows the user to initiate calibration by momentarily placing a magnet against the housing at the designated location. See Figure 2.

HART COMMUNICATION

The transmitter supports HART communication on the

4-20 mA loop. This allows for configuration capability and provides device status information, calibration, and diagnostics capabilities. The GT3000 is compatible with HART interface devices such as a HART handheld communicator, the Det-Tronics UD10 or UD20 Display

Unit, or an AMS system. (See Appendix G for HART menu structure.)

lEDs

The GT3000 has one green and one yellow LED

(See Figure 3). The LEDs are used to signal normal, calibration, and fault conditions. See Table 2.

NoTe

The GT3000 does not have alarm setpoints and, therefore, does not have a red LeD.

MAGNETIC

SWITCH

11.1

B2443

Figure 2—Location of Magnetic Switch on GT3000 Detector

3

Table 2—LEDs and Analog Output

During Various Operating Conditions

Function Green lED Yellow lED

Analog

4-20 Signal

Output

3.5***

Warm-up

*

Single Flash

Normal

Operation

Steady On

Fault

Condition

Calibration

No Power

Off

Off

Off

On

Off

On

See Table 5

Off

4-20

3.5***

3.8

**

0

*

Warm-up time can last up to 150 seconds.

**

O

2

sensor generates 17.3 mA during calibration.

***2.45 for TYPE OUTPUT "29", reference GTX Model Matrix .

95-8616

specifications

6.2

(15.8)

SENSOR AND TRANSMITTER

AVAILABLE SENSORS—

Refer to Appendix F.

CROSS SENSITIVITY—

See Appendix F for Cross Sensitivity information.

CALIBRATION—

Sensors are calibrated at the factory. Gas type and range are read by the transmitter. Field calibration is initiated at the detector, at the UD10/UD20 Universal

Display Unit, or by some other HART interface device.

OPERATING VOLTAGE—

24 volts dc nominal. (12 Vdc minimum, 30 Vdc maximum).

Maximum ripple is 2 volts peak-to-peak.

If using the HART function, the installation must comply with the HART power standard.

POWER CONSUMPTION—

0.8 watt maximum @ 30 Vdc.

CURRENT OUTPUT—

• 4-20 mA (Normal operating mode).

• 3.8 mA indicates calibrate mode.

• 3.5 mA or less indicates a fault condition (2.45 mA option available).

MAXIMUM LOOP RESISTANCE—

300 ohms at 18 Vdc, 600 ohms at 24 Vdc.

WIRING—

The transmitter has flying leads, 20” long, 600V insulation.

Colors: Red = V+

Black = V–

Green = earth ground

Gauge: 22 AWG (red and black)

16 AWG (green).

WARM-UP—

Warm-up time can last up to 150 seconds.

OPERATING TEMPERATURE—

See Appendix F.

STORAGE TEMPERATURE—

Transmitter: –55°C to +75°C (–67°F to +167°F)

Sensor: 0°C to +20°C (+32°F to +68°F).

Ideal: +4°C to +10°C (+39°F to +50°F).

HUMIDITY RANGE—

15 to 90% RH.

2.5

(6.4)

5.6

(14.3)

B2397

Figure 4—Dimensions of GT3000 Gas Detector in Inches (CM)

PRESSURE RANGE—

Atmospheric ±10%.

INGRESS PROTECTION—

IP66.

ELECTRO-MAGNETIC COMPATIBILITY—

EMC Directive 2004/108/EC

EN55011 (Emissions)

EN50270 (Immunity).

THREAD OPTIONS—

3/4" NPT or M25.

ENCLOSURE MATERIAL—

GTX Transmitter: 316 Stainless Steel

GTS Sensor Module: PPA (30% carbon filled).

DIMENSIONS—

See Figure 4.

WARRANTY—(For the GTX and GTS)

12 months from date of installation or 18 months from date of shipment, whichever occurs first.

CERTIFICATIONS—

®

For complete approval details, refer to the appropriate

Appendix:

Appendix A - FM

Appendix B - CSA

Appendix C - ATEX

Appendix D - IECEx

Appendix E - Other Approvals

11.1

4

95-8616

important safety notes

CaUtIon

The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Be certain that all wiring complies with the NeC as well as all local codes. If in doubt, consult the authority having jurisdiction before wiring the system. Installation must be done by a properly trained person.

CaUtIon

This product has been tested and approved for use in hazardous areas. However, it must be properly installed and used only under the conditions specified within this manual and the specific approval certificates. Any device modification, improper installation, or use in a faulty or incomplete configuration will render warranty and product certifications invalid.

CaUtIon

The GT3000 contains no field repairable components. User performed service is limited to replacement of the gas sensor module.

CaUtIon

Hazardous location temperature limits exceed the product operational temperature limits. If the sensor is exposed to temperatures beyond the operational temperature limits listed in Appendix

F, then the sensor module (GTS) should be replaced or a response test, as described in the GT3000 Safety Manual (95-8685), shall be performed.

LIabILItIes

The manufacturer’s warranty for this product is void, and all liability for proper function of the detector is irrevocably transferred to the owner or operator in the event that the device is serviced or repaired by personnel not employed or authorized by Detector electronics Corporation, or if the device is used in a manner not conforming to its intended use.

CaUtIon

observe precautions for handling electrostatic sensitive devices.

NoTe

The sensor housing is made of Polyphthalamide

(PPA), 30% carbon filled (Material Manufacturer

RTP). Questions regarding chemical resistance should be addressed to:

www.det-tronics.com

US toll free 800-468-3244 or 952-941-5665

11.1

5

95-8616

installation

The gas detector can be installed either in a stand-alone configuration as a loop powered device, or it can be connected to a UD10/UD20 Universal Display Unit.

housing.

NoTe

The gas detector housing must be electrically connected to earth ground. A dedicated earth ground wire is provided on the transmitter for connection to earth ground or to a grounded

The most effective number and placement of detectors varies depending on the conditions on site. The individual designing the installation must often rely on experience and common sense to determine the detector quantity and best locations to adequately protect the area. Note that it is typically advantageous to locate detectors where they are accessible for maintenance. Locations near excessive heat or vibration sources should be avoided if possible.

Final suitability of possible gas detector locations should be verified by a site survey. If any questions arise regarding installation, please contact the factory.

The detector must always be installed per local installation code.

Before installing the gas detector, define the following application details:

DEvICE MOUNTING ORIENTATION

The gas detector must be mounted in a vertical position only, with the sensor pointing down (See Figure 5).

IDENTIFICATION OF vApOR(S) TO bE DETECTED

It is necessary to always identify the vapor(s) of interest at the job site. In addition, the fire hazard properties of the vapor, such as vapor density, flashpoint, and vapor pressure should be identified and used to assist in selecting the optimum detector mounting location within the area.

Important

The sensor should be oriented with the LeDs facing forward so they are easily visible to personnel within the area. To ensure correct orientation (the LeDs are not visible when power is off), position the GND lug on the left hand side and the calibration notch to the front. Note that the

LeDs are located directly above the calibration notch.

IDENTIFICATION OF DETECTOR MOUNTING lOCATIONS

Identification of the most likely leak sources and leak accumulation areas is typically the first step in identifying the best detector mounting locations. In addition, identification of air current/wind patterns within the protected area is useful in predicting gas leak dispersion behavior. This information should be used to identify optimum sensor installation points.

If the vapor of interest is lighter than air, place the sensor above the potential gas leak. Place the sensor close to the floor for gases that are heavier than air. Note that air currents may cause a gas that is slightly heavier than air to rise under some conditions. Heated gases may also exhibit the same phenomenon.

GND LUG

GREEN LED

CALIBRATION NOTCH

B2436

Figure 5—Correct Mounting Orientation for the GT3000

11.1

6

95-8616

DETECTOR INSTAllATION

3/4" NpT Models

3/4" NPT models have Tapered Threads and no Lock

Nut. Install the sensor as follows:

1. Screw the detector into the appropriate entry on the termination box. Ensure a minimum of 5 fully engaged threads. Use of teflon tape on NPT threads is recommended to prevent thread damage.

2. When the detector gets tight, note the position of the

LEDs, GND lug and calibration notch and adjust the detector as required so that the LEDs will be easily visible.

SENSOR TERMINATION bOX

A Det-Tronics sensor termination box (Model STB) is required for installing the sensor in a stand alone configuration, or for installing the GT3000 remotely from the UD10/UD20 Universal Display Unit.

When installing the GT3000 remotely from a UD10/

UD20, two-conductor shielded cable is required to prevent possible nuisance EMI/RFI. The maximum cable length between the GT3000 and the UD10/UD20 is 2000 ft.

WirinG

M25 Models

M25 models have Straight Threads and a Lock Nut.

Install the detector as follows:

1. Screw the detector lock nut as far back as it will go, then screw the detector into the appropriate entry on the termination box. Ensure a minimum of 7 fully engaged threads.

2. With the detector in the desired position (LEDs visible as shown in Figure 5), tighten the lock nut against the termination box to hold the detector securely in place.

3. Tighten the set screws (minimum of two) to prevent movement of the lock nut. See Figure 6.

pOWER SUpplY REqUIREMENTS

Calculate the total gas detection system power consumption rate in watts from cold start-up. Select a power supply with adequate capability for the calculated load. Ensure that the selected power supply provides sufficient regulated and filtered output power for the entire system. If a back-up power system is required, a float-type battery charging system is recommended. If an existing source of power is being utilized, verify that system requirements are met.

NoTe

The power supply must also meet the noise requirements for HART systems.

WIRING CAblE REqUIREMENTS

Always use proper cabling type and diameter for input power as well as output signal wiring. 22 to 14 AWG shielded stranded copper wire is recommended.

Always install a properly sized, master power fuse or breaker on the system power circuit.

Set Screws

Figure 6—Location of Lock Nut and Set Screws

(Metric Models Only)

NoTe

The use of shielded cable in conduit or shielded armored cable is highly recommended. In applications where the wiring is installed in conduit, dedicated conduit is recommended.

Avoid low frequency, high voltage, and non-signaling conductors to prevent nuisance eMI problems.

CaUtIon

The use of proper conduit installation techniques, breathers, glands, and seals is required to prevent water ingress and/or maintain the explosion-proof rating.

11.1

7

95-8616

INTRINSIC SAFETY bARRIERS

When the GT3000 is used in an intrinsically safe installation, care must be taken when selecting an I.S. barrier to ensure proper function of the device. The

GT3000 has been tested with the types of barriers listed in Tables 3 and 4.

GUIDElINES FOR INTRINSIC SAFETY WIRING

Intrinsically safe systems must be installed in accordance with the approved control drawings for the field equipment and the intrinsic safety barriers.

Capacitance and inductance of interconnecting wiring must always be included in wiring calculations.

Table 3 lists zener barriers. The third column gives the range of input voltage to the barrier. The upper limit is set by the barrier. The lower limit is limited by voltage drops in the 4-20 mA loop with a maximum of 10 Ohms of resistance in each leg of the loop.

Table 4 lists isolating barriers that provide a wider range of input power supply voltages and are less dependent on voltage drops in the loop. Input voltage to the barrier is specified by the barrier manufacturer.

Shielded twisted pair cables with at least 18 AWG conductors are recommended to ensure circuit performance.

The intrinsically safe conductors must be separated from all other wiring by placing them in separate conduits or raceways, or by an airspace of at least 2 inches (50 mm). When located within an enclosure, the conductors can be separated by a grounded metal or insulated partition. Wires must be tied down to prevent loosening and/or shorting.

For additional information regarding proper IS installation, refer to the Control Drawings in Appendix

H of this manual.

Intrinsically safe wiring must be identified. Raceways, cable trays, open wiring, and terminal boxes must be labeled as Intrinsically Safe. Intrinsically safe wiring may be light blue in color when no other conductors colored light blue are used.

Table 3—Acceptable Intrinsic Safety Barriers for use with GT3000 – Zener Barriers

Manufacturer

Turck

MTL

Pepperl & Fuchs

p/N

MZB87PX

MTL7787P+

Z787.h

Wiring enclosures should be located as close as possible to the hazardous area to minimize cable runs and reduce total capacitance of the wiring.

A high quality intrinsic safety ground is required. Some general rules for grounding intrinsically safe systems are:

• The maximum impedance of the grounding conductor between the barrier ground terminal and the main ground point must be less than 1 ohm.

• The grounding conductor must be a minimum of 12

AWG.

• Redundant grounding conductors are recommended to facilitate testing of the ground connection.

• The grounding conductor should be insulated and protected from the possibility of mechanical damage.

Table 4—Acceptable Intrinsic Safety Barriers for use with GT3000 – Isolating Barriers

Manufacturer

Turck

MTL

Pepperl & Fuchs

Stahl

p/N

IM33-11Ex-Hi

5541

KCD2-STC-Ex1

9160/13-10-11

WIRING pROCEDURE

Wire the transmitter as shown in Figures 7 through 12.

CaUtIon

If ripple on the main power source causes interference with the HART function, the use of an isolated power source (Figure 12) is recommended for best HART performance.

11.1

8

95-8616

SENSOR TERMINATION BOX

GREEN

RED

BLA

CK

BLACK

RED

BLACK

+

SEE NOTES 2 & 3

24 VDC

SEE NOTE 1

A2502

GT3000

GAS DETECTOR

NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE

END ONLY.

NOTE 2 250 OHM RESISTOR REQUIRED FOR HART

MENU ACCESS.

NOTE 3 EXTERNAL HART COMMUNICATION DEVICES

CAN BE CONNECTED ACROSS THE 250 OHM

RESISTOR OR ACROSS THE GT3000.

NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

Figure 7—GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Explosion-Proof)

11.1

HAZARDOUS LOCATION

SENSOR TERMINATION BOX

GREEN

RED

BLA

CK

BLACK

RED

BLACK

NON-HAZARDOUS LOCATION

SEE NOTES 2 & 3

+

24 VDC

SEE NOTE 1

A2530

GT3000

GAS DETECTOR

NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE

END ONLY.

NOTE 2 250 OHM RESISTOR REQUIRED FOR HART

MENU ACCESS.

NOTE 3 EXTERNAL HART COMMUNICATION DEVICES

CAN BE CONNECTED ACROSS THE 250 OHM

RESISTOR OR ACROSS THE GT3000.

NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

Figure 8— GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Intrinsically Safe)

9

95-8616

RED

BLACK

GREEN

UD20 DISPLAY UNIT

+

J2-6

J2-5

POWER

LOOP

SHIELD J2-4

J2-3

+

J2-2

SEE NOTE 1

J2-1 SHIELD

SENSOR

LOOP

J2

GT3000

GAS DETECTOR

NOTE 1 CONNECT THE GREEN DETECTOR LEAD TO THE

CHASSIS GROUND LUG ON THE INSIDE BOTTOM

OF THE UD20 DISPLAY UNIT ENCLOSURE.

NOTE 2 250 OHM RESISTOR REQUIRED FOR HART

MENU ACCESS.

NOTE 3 EXTERNAL HART COMMUNICATION DEVICES CAN BE

CONNECTED ACROSS THE 250 OHM RESISTOR,

ACROSS J2-5 AND J2-6, OR ACROSS J2-2 AND J2-3.

NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

NOTE 5 GROUND THE SHIELD AT THE POWER SOURCE

END ONLY.

Figure 9—GT3000 Wired Directly to UD20 Display Unit (Explosion-Proof)

+

SEE NOTES 2 & 3

24 VDC

SEE NOTE 5

B2478

11.1

SENSOR TERMINATION BOX

GREEN

RED

BLA

CK

BLACK

UD20 DISPLAY UNIT

+

J2-6

J2-5

POWER

LOOP

SEE NOTE 1

SHIELD J2-4

J2-3

+

RED

BLACK

J2-2

J2-1

SHIELD

SENSOR

LOOP

J2

SEE NOTES 2 & 3

GT3000

GAS DETECTOR

NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE

END ONLY.

NOTE 2 250 OHM RESISTOR REQUIRED FOR HART

MENU ACCESS.

NOTE 3 EXTERNAL HART COMMUNICATION DEVICES CAN BE

CONNECTED ACROSS THE 250 OHM RESISTOR,

ACROSS J2-5 AND J2-6, OR ACROSS J2-2 AND J2-3.

NOTE 4 JUNCTION BOXES MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

Figure 10—GT3000 with Sensor Termination Box Wired to UD20 Display Unit (Explosion-Proof)

10

+

24 VDC

SEE NOTE 1

D2408

95-8616

NON-HAZARDOUS LOCATION HAZARDOUS LOCATION

PLC 4-20 mA INPUT CARD

INPUT

4-20 mA

250

OHMS

MINIMUM

24 VDC

+

Notes: Resistor may be external if voltage input card is used.

Sinking resistance at PLC must be 250 ohms minimum for HART communication.

C2453

BLACK

RED

UD10

DISPLAY UNIT

Sensor Connector

J3

Output Loop

Connector

P1-3

4-20 mA +

P1-2

4-20 mA –

P1-1

P1

SHIELD

J2

J2-3

COM

J2-2

RS485 A

J2-1 RS485 B

MODBUS

Connector

P12

Power Supply Connector

P2

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J4

J4-1

J4-2

J4-3

J4-4

J4-5

GT3000

GREEN

SEE NOTE 1

GAS DETECTOR

NOTE 1 CONNECT THE GREEN DETECTOR LEAD

TO THE CHASSIS GROUND LUG ON THE

INSIDE BOTTOM OF THE DISPLAY UNIT

ENCLOSURE.

NOTE 2 JUNCTION BOXES MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

Figure 11—GT3000 Wired Directly to the UD10 Display Unit / UD10 Wired to PLC with 4-20 mA Non-Isolated Sourcing Output

11.1

INPUT

4-20 mA

250

OHMS

MINIMUM

24 VDC

+

NON-HAZARDOUS LOCATION

PLC 4-20 mA INPUT CARD

Notes: Resistor may be external if voltage input card is used.

Sinking resistance at PLC must be 250 ohms minimum for HART communication.

C2479

HAZARDOUS LOCATION

BLACK

RED

UD10

DISPLAY UNIT

GREEN

Sensor Connector

J3

Output Loop

Connector

P1-3 4-20 mA +

P1-2

4-20 mA –

SHIELD

P1-1

P1

J2

J2-3

COM

J2-2 RS485 A

J2-1

RS485 B

MODBUS

Connector

P12

Power Supply Connector

P2

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

J4-8

J4-9

J4-10

J4-11

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-12

J4

24 VDC

+

GT3000

SEE NOTE 1

GAS DETECTOR

NOTE 1 CONNECT THE GREEN DETECTOR

LEAD TO THE CHASSIS GROUND

LUG ON THE INSIDE BOTTOM OF

THE DISPLAY UNIT ENCLOSURE.

NOTE 2 JUNCTION BOXES MUST BE

ELECTRICALLY CONNECTED

TO EARTH GROUND.

Figure 12—GT3000 Wired Directly to the UD10 Display Unit / UD10 Wired to PLC with 4-20 mA Isolated Sourcing Output

11

95-8616

calibration

GT3000 CAlIbRATION

The GT3000 supports one person calibration, which can be initiated locally using a calibration magnet, or remotely with a command from the HART interface.

The calibration process is automatic, with the exception of gas delivery. LEDs on the transmitter guide the operator when to apply and remove the calibration gas

See Table 5.

NoTe

The HART interface allows the operator to adjust the calibration gas concentration within the range of 30 to 90% full scale. The default value for all gas sensors except oxygen is 50% full scale. oxygen sensors use a default value of 20.9%.

The calibration process proceeds automatically after initiation. Onboard LEDs signal the operator when to apply the calibration gas and inform of the progress.

The calibration can be aborted by activating the magnetic switch or with a command from the HART communication device in lieu of applying the calibration gas.

If the calibration process takes longer than 10 minutes, the detector will time-out and signal a calibration fault.

If the calibration sequence is aborted or not completed successfully, the detector reverts back to the previous calibration values and signals a calibration fault. The calibration fault can be cleared by activating the magnetic switch for one second or by performing a successful calibration.

All GT3000 gas detectors require a two-point calibration — zero and span. The calibration process can be initiated using the magnetic switch or through a

HART interface, such as the UD10/UD20. All sensors, including oxygen, should be in clean air (20.9% oxygen) when the calibration sequence is initiated.

The calibration process can fail for the following causes:

• Zero is out of range

• Span is out of range

• Time-Out.

Table 5— LEDs During Calibration

Calibration Step

Waiting for Zero

Yellow lED

Steady

The time and date of calibration events are logged in non-volatile memory along with the calibration outcome.

Possible calibration scenarios include the following:

• Successful Calibration

• Aborted Calibration

• Failed Calibration and the Cause

Waiting for Gas

Waiting for Span

Blinking

Blinking

The Sensor Module stores calibration data in non-volatile memory to allow the sensor to be calibrated off-site and installed in the field without the need for re-calibration.

Remove Cal Gas Off

11.1

12

95-8616

CAlIbRATION pROCEDURE

NoTe

When attaching or removing the calibration cup, push or pull the cup with a slight

clockwise twist.

Turning counterclockwise can cause the filter assembly on the GT3000 to loosen. If the filter assembly is inadvertently loosened, tighten it by hand (no tools required).

NoTe

The calibration procedure must be completed within a ten minute period. If the calibration is not completed, a calibration fault will be generated and the transmitter will continue to use the previous calibration data.

Toxic and Hydrogen Sensors

1. Clean air must be present at the GT3000 sensor module prior to initiating calibration. The use of bottled air is recommended.

NoTe

To ensure reliable detection performance, calibration should be performed at regularly scheduled intervals. Various factors affect the time interval between periodic calibrations

(typically 30, 60, or 90 day intervals, depending on the ambient conditions).

Calibration of ammonia sensor is recommended any time the sensor has been exposed to 90 ppm ammonia.

NoTe

2. Initiate calibration by momentarily holding the calibration magnet against the designated location on the sensor module (see Figure 13) until the green LED turns off and the yellow LED turns on steady (approximately one second). Remove the magnet when the green LED turns off. The detector immediately begins taking zero readings.

Calibration can also be initiated via HART interface

(see Appendix G) or the UD10 (see manual number

95-8618).

Oxygen Sensor

1. Using the magnet, activate the magnetic calibration switch on the GT3000. The green LED turns off and the yellow LED turns on steady.

3. When the zero calibration is complete, the yellow

LED changes from steady to blinking. Apply the calibration gas to the sensor.

2. The device automatically performs the zero calibration.

3. When the yellow LED on the GT3000 flashes, the device automatically performs the span calculation.

If using bottled 20.9% oxygen, apply immediately.

4. When the yellow LED turns off, remove the calibration gas. The gas level at the sensor gradually returns to zero. The green LED turns on steady to indicate that the device has returned to normal operation, using the new calibration data.

4. After successful calibration, the yellow LED turns off and the green LED turns on steady to indicate that the device has returned to normal operation, using the new calibration data. Remove calibration gas (if used).

LED

PLACE MAGNET HERE

TO ACTIVATE INTERNAL

MAGNETIC SWITCH

B2452

Figure 13—Location of Magnetic Switch on GT3000 Detector

11.1

13

95-8616

maintenance

NoTe

Refer to the GT3000 Safety Manual (number

95-8685) for specific requirements and recommendations applicable to the proper installation, operation, and maintenance of all

SIL-Certified GT3000 gas detectors.

ROUTINE INSpECTION

The gas inlet to the sensor should be inspected periodically, or during scheduled maintenance, to ensure that external obstructions such as plastic bags, litter, heavy oil and tar, paint, mud, snow, or other materials do not block the flow of gas to the sensor, thereby impairing the performance of the device.

To replace a dirty or damaged filter, simply grasp the filter assembly and twist counterclockwise to remove.

Screw the new filter in place on the sensor module. Do not overtighten. See Figure 14.

To ensure reliable protection, it is important to check and calibrate the detection system on a regularly scheduled basis. The frequency of these checks is determined by the requirements of the particular installation – typically

30, 60, or 90 day intervals, depending on the ambient conditions.

SENSOR MODUlE REplACEMENT

(live Maintenance)

The hot swappable, intrinsically safe sensor module can be replaced in the field without removing power or de-classifying the hazardous area.

To replace the sensor module, locate the three captive screws on the front of the module as shown in Figure

15. Loosen these screws and remove the old sensor module. Install the new sensor module onto the transmitter, and tighten the screws. To ensure proper moisture ingress protection and grounding of the plastic nosepiece, tighten the screws to 70-100 oz-in (0.5-0.7

N-m).

Important

Always exercise caution when working in combustible gas areas. Follow replacement instructions explicitly.

NoTe

Removing the sensor module with power applied will result in a fault condition until a new sensor module of the same type is installed. When replacing an oxygen sensor, this action will result in an alarm condition as the decreasing 4-20 mA signal passes through the alarm range. Inhibit response devices to prevent unwanted actuation.

NoTe oxygen (o

2

) electrochemical sensors contain lead (Pb). observe all local waste management requirements when disposing of exhausted o

2 electrochemical sensors.

NoTe electrochemical sensors are highly sensitive to antiseptic wipes and/or cleaning products that contain alcohol and antibacterial/antiviral agents.

Antiseptic products should be removed from areas where sensors are stored, handled, or used. If antiseptic products are being used on workers' hands, sufficient time should be allowed for the alcohol to evaporate before handling sensors.

TURN FILTER COUNTERCLOCKWISE

TO REMOVE. NO TOOLS REQUIRED.

A2481

Figure 14—GT3000 with Replaceable Filter Removed

11.1

14

LOOSEN CAPTIVE PHILLIPS

SCREWS (3) TO REMOVE

SENSOR MODULE.

B2451

Figure 15—Location of Screws for Sensor Module Replacement

95-8616

DeVice repair anD retUrn

Prior to returning devices, contact the nearest local

Detector Electronics office so that a Return Material

Identification (RMI) number can be assigned. A

written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure

.

Pack the unit properly. Always use sufficient packing material. Where applicable, use an antistatic bag as protection from electrostatic discharge.

NoTe

Inadequate packaging that ultimately causes damage to the returned device during shipment will result in a service charge to repair the damage incurred during shipment.

Return all equipment transportation prepaid to the factory in Minneapolis.

NoTe

It is highly recommended that a complete spare be kept on hand for field replacement to ensure continuous protection.

orDerinG information

Sensor module (GTS) and transmitter (GTX) must be ordered separately. Refer to the Transmitter and Sensor

Model Matrix on next page for ordering details.

GTS GAS SENSORS

Gas Concentration

Hydrogen Sulfide (H

Hydrogen Sulfide (H

2

2

S)

S)

Hydrogen Sulfide (H

2

S)

Oxygen (O

2

)*

Carbon Monoxide (CO)

Carbon Monoxide (CO)

0-20 ppm

0-50 ppm

0-100 ppm

0-25% V/V

0-100 ppm

0-500 ppm

Ammonia (NH

3

)

Sulfur Dioxide (SO

2

)

Sulfur Dioxide (SO

2

)

Chlorine (Cl

2

)

Hydrogen (H

2

)

Nitrogen Dioxide (NO

2

)

0-100, or 0-500 ppm

0-20 ppm

0-100 ppm

0-10 ppm

0-1000 ppm

0-20 ppm

*Oxygen detector for O

2

depletion (< 21% V/V) only.

CAlIbRATION kITS FOR GAS SENSORS part Number Gas / Concentration

010274-001 H

2

S / 10 ppm

010274-002 H

010274-003 H

010274-008 H

2

2

2

S / 25 ppm

S / 50 ppm

010274-009 O

2

/ 500 ppm

/ 20.9%

010274-010

010274-011

010274-005

010274-006

010274-016

CO / 50 ppm

CO / 250 ppm

NH

010274-004 Cl

2

3

NH

3

010274-013 SO

2

010274-014 SO

2

NO

2

/ 50 ppm

/ 250 ppm

/ 10 ppm

/ 50 ppm

/ 5 ppm

/ 10 ppm

Replacement gas cylinders for all calibration kits are available.

pARTS & ACCESSORIES part Number

009700-001

009737-001

107427-059

101678-007

162552-001

009640-001

012509-001

012509-002

010780-003

010783-001

012513-XXX*

012514-XXX*

Description

Magnetic Tool

Calibration Cup

Calibration Cup O-ring

3 Foot Tubing

Regulator, 1 LPM

Replacement Filter

Q312 Sample Draw without Fittings

Q312 Sample Draw with Fittings

GT3000 Remote Calibration Adaptor

GT3000 Remote Calibration Filter

Q912 Duct Mount Enclosure, M25

Q912 Duct Mount Enclosure, 3/4"

*Refer to the Product Catalog for a list of options.

ASSISTANCE

For assistance in ordering a system to meet the needs of a specific application, contact:

Detector Electronics Corporation

6901 West 110th Street

Minneapolis, Minnesota 55438 USA

Operator: (952) 941-5665 or (800) 765-FIRE

Customer Service: (952) 946-6491

Fax: (952) 829-8750

Web site: www.det-tronics.com

E-mail: [email protected]

11.1

15

95-8616

GTS Sensor Model Matrix

MODEl

GTS

DESCRIpTION

Gas Sensor Module

TYpE GAS / RANGE

H2S

H2S+

Hydrogen Sulfide

20p

0 - 20 PPM

50p

0 - 50 PPM

100p

0 - 100 PPM

Hydrogen Sulfide

Cl2

NH3

H2

O2

CO

SO2+

NO2

20p

50p

100p

Chlorine

10p

Ammonia

100p

500p

0 - 20 PPM

0 - 50 PPM

0 - 100 PPM

0 - 10 PPM

100p

500p

Sulfur Dioxide

0 - 100 PPM

0 - 500 PPM

Hydrogen

1000p

0 - 1000 PPM

Oxygen

25v

Carbon Monoxide

0 - 25 % by Vol

0 - 100 PPM

0 - 500 PPM

20p

100p

0 - 20 PPM

0 - 100 PPM

Nitrogen Dioxide

20p

0 - 20 PPM

TYpE

D

R

S

T

W b

C

APPROVAL

*

INMETRO (Brazil)

CSA

DNV

Russia

SIL

SIL/FM/CSA/ATEX/CE/IECEx

FM/CSA/ATEX/CE/IECEx

*

Type Approval can use one or more letters to designate the Approvals on the product.

11.1

16

95-8616

GTX Transmitter Model Matrix

MODEl DESCRIpTION

GTX

Gas Transmitter

TYpE MATERIAl

S

Stainless Steel (316)

TYpE THREAD SIZE

N

M

3/4" NPT

Metric M25

TYpE

26

29

OUTpUTS

4-20 mA, HART (3.5 mA FAULT)

4-20 mA, HART (2.45 mA FAULT)

TYpE b

R

W

AppROvAlS

INMETRO (Brazil)

Russia

FM/CSA/ATEX/CE/IECEx

TYpE

4

5

ClASSIFICATION (Division/Zone)

Intrinsically Safe

Explosion-Proof

Note: Approvals Type W and B are SIL 2 Capable when used with an H

2

S or O

2

GTS sensor module.

11.1

17

95-8616

appenDix a

FM AppROvAl DESCRIpTION

The following items, functions and options describe the FM approval.

AppROvAl

Electrochemical Gas Detector, GT3000 Series.

Explosion Proof Model

Class I, Div. 1, Groups A, B, C, & D (T4).

Class I, Div. 2, Groups A, B, C, & D (T4).

Class I, Zone 1, AEx d mb [ia Ga] IIC T4.

IP66.

Conduit seal not required.

Acidic atmospheres excluded.

NoTe

The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of installation to provide protection for the flying leads.

Intrinsically Safe Model

IS Class I, Div. 1, Groups A, B, C, & D (T4).

Class I, Zone 0, AEx ia IIC (T4).

IP66.

NoTe

In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an approved I.S. barrier.

For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.

Performance verified per ANSI/ISA 92.00.01, FM6340/41 and EN50104.

11.1

18

95-8616

part Number

010274-001

010274-002

010274-003

010274-008

010274-009

010274-010

010274-011

010274-005

010274-006

010274-013

010274-014

010274-004

010274-016

009700-001

009737-001

107427-059

101678-007

162552-001

009640-001

AppROvED ACCESSORIES

Description

Gas Calibration Kit, 10 ppm H

2

S

Gas Calibration Kit, 25 ppm H

2

S

Gas Calibration Kit, 50 ppm H

2

S

Gas Calibration Kit, 500 ppm H

2

Gas Calibration Kit, 20.9% O

2

Gas Calibration Kit, 50 ppm CO

Gas Calibration Kit, 250 ppm CO

Gas Calibration Kit, 50 ppm NH

3

Gas Calibration Kit, 250 ppm NH

3

Gas Calibration Kit, 10 ppm SO

2

Gas Calibration Kit, 50 ppm SO

2

Gas Calibration Kit, 5 ppm Cl

2

Gas Calibration Kit, 10 ppm NO

2

Magnetic Tool

Calibration Cup

Calibration Cup O-ring

3 Foot Tubing

Regulator, 1 LPM

Replaceable Filter

11.1

19

95-8616

appenDix b

CSA CERTIFICATION DESCRIpTION

The following items, functions and options describe the CSA approval.

AppROvAl

Electrochemical Gas Detector, GT3000 Series.

Explosion Proof Model

Class I, Div. 1, Groups A, B, C, & D (T4).

Class I, Div. 2, Groups A, B, C, & D (T4).

Class I, Zone 1, AEx d mb [ia Ga] IIC T4.

IP66.

Conduit seal not required.

Acidic atmospheres excluded.

NoTe

The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of installation to provide protection for the flying leads.

Intrinsically Safe Model

Class I, Div. 1 & 2, Groups A, B, C, & D (T4).

IP66.

NoTe

In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an approved I.S. barrier.

For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.

11.1

20

95-8616

appenDix c

ATEX AppROvAl DESCRIpTION

The following items, functions and options describe the ATEX approval.

AppROvAl

Electrochemical Gas Detector, GT3000 Series.

Explosion Proof Model

®

II 2(1)G.

Ex d mb [ia Ga] IIC T4 Gb IP66.

FM10ATEX0009X.

NoTe

The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of installation to provide protection for the flying leads.

Intrinsically Safe Model

®

II 1 G Ex ia IIC T4 Ga IP66.

FM08ATEX0045X.

NoTe

In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an approved I.S. barrier.

For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.

11.1

21

95-8616

appenDix D

IECEx AppROvAl DESCRIpTION

The following items, functions and options describe the IECEx approval.

AppROvAl

Electrochemical Gas Detector, GT3000 Series.

Explosion Proof Model

Ex d mb [ia Ga] IIC T4 Gb IP66.

IECEx FMG 10.0003X.

NoTe

The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of installation to provide protection for the flying leads.

Intrinsically Safe Model

Ex ia IIC T4 Ga IP66.

IECEx FMG 08.0005X.

NoTe

In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an approved I.S. barrier.

For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.

11.1

22

95-8616

appenDix e

OTHER AppROvAlS

The following items, functions and options describe various other approvals applicable to the GT3000.

SIl AppROvAl

IEC 61508

Certified SIL 2 Capable.

SIL Certification includes H

2

S and O

2

GTS models only. For specific information regarding SIL models, refer to the

GT3000 Safety Reference Manual, form 95-8685.

INMETRO (bRAZIl)

Explosion Proof Model

UL-BR 15.0752X

Ex d mb [ia Ga] IIC T4 Gb IP66

Tamb –40°C to +50°C (H

2

S)

Tamb –20°C to +50°C (other)

NoTe

The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of installation to provide protection for the flying leads.

NoTe

Consideration must be given to overall Gas System Performance Requirements.

Intrinsically Safe Model

UL-BR 15.0404X

Ex ia IIC T4 Ga IP66

Tamb –40°C to +50°C

NoTe

In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an approved I.S. barrier.

For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.

DNv

Type Approval Certificate No. A-12358.

MED

Certificate No. MED-B-6708.

RUSSIA / kAZAkHSTAN / INDIA

Contact Det-Tronics for details.

11.1

23

95-8616

appenDix f

DEClARATION OF CONFORMITY

11.1

For a copy of the original document, please contact the factory.

24

95-8616

appenDix G

SENSOR COMpARISON/CROSS SENSITIvITY

Electrochemical Gas Sensors

Gas Range

Response

Time

1

Accuracy of

Reading

(Whichever is Greater)

Operating

Temperature Range

Zero Drift

Hydrogen Sulfide

(H

2

(H

(H

(H

(H

(H

2

2

2

2

2

S)

Hydrogen Sulfide

S)

Hydrogen Sulfide

S)

Hydrogen Sulfide+

S+)

Hydrogen Sulfide+

S+)

Hydrogen Sulfide+

S+)

Ammonia (NH

Ammonia (NH

Oxygen (O

2

)

3

3

)

)

Carbon

Monoxide (CO)

Carbon

Monoxide (CO)

Sulfur Dioxide+

(SO

2

+)

Sulfur Dioxide+

(SO

2

+)

Chlorine

(Cl

2

)

Hydrogen

(H

2

)

Nitrogen Dioxide

(NO

2

)

0-20 PPM

0-50 PPM

0-100 PPM

0-20 PPM

0-50 PPM

0-100 PPM

0-100 PPM

0-500 PPM

0-25% V/V

0-100 PPM

0-500 PPM

0-20 PPM

0-100 PPM

0-10 PPM

0-1,000 PPM

0-20 PPM

2

2

3

T20 = ≤7 Sec

T50 = ≤10 Sec.

T90 = ≤16 Sec.

T20 = ≤4 Sec

T50 = ≤7 Sec.

T90 = ≤16 Sec.

T20 = ≤5 Sec

T50 = ≤8 Sec.

T90 = ≤21 Sec.

T20 = ≤10 Sec

T50 = ≤13 Sec.

T90 = ≤23 Sec.

T20 = ≤6 Sec

T50 = ≤9 Sec.

T90 = ≤15 Sec.

T20 = ≤6 Sec

T50 = ≤8 Sec.

T90 = ≤15 Sec.

T50 = 24 Sec.

T90 = 65 Sec.

T50 = 30 Sec.

T90 = 120 Sec.

T20 = 7 Sec.

T90 = 30 Sec.

T50 = 15 Sec.

T90 = 40 Sec.

T50 = 12 Sec.

T90 = 25 Sec.

T50 = 12 Sec.

T90 = 30 Sec.

T50 = 15 Sec.

T90 = 35 Sec.

T50 = ≤14 Sec.

T90 = ≤34 Sec.

T50 = 8 Sec.

T90 = 60 Sec.

T50 = 7 Sec.

T90 = 31 Sec.

±2 ppm or

±10% of Reading

±2 ppm or

±10% of Reading

±2 ppm or

±10% of Reading

±2 ppm or

±10% of Reading

±2 ppm or

±10% of Reading

±2 ppm or

±10% of Reading

±4 ppm or

±10% of Reading

±4 ppm or

±10% of Reading

< 0.5% V/V

±5 ppm or

±10% of Reading

±5 ppm or

±10% of Reading

±0.6 ppm or

±10% of Reading

±0.6 ppm or

±10% of Reading

±0.6 ppm or

±10% of Reading

±50 ppm or

±10% of Reading

±2 ppm or

±10% of Reading

–40°C to +50°C

–40°C to +50°C

–40°C to +50°C

–40°C to +55°C

–40°C to +55°C

–40°C to +55°C

–20°C to +40°C

–20°C to +40°C

–20°C to +50°C

–20°C to +50°C

–20°C to +50°C

–40°C to +55°C

–40°C to +55°C

–20°C to +50°C

–20°C to +40°C

–20°C to +40°C

± 1 ppm/Mo.

± 1 ppm/Mo.

± 2 ppm/Mo.

± 1 ppm/Mo.

± 1 ppm/Mo.

± 2 ppm/Mo.

± 2 ppm/Mo.

± 10 ppm/Mo.

< 2 %/Mo.

± 2 ppm/Mo.

± 9 ppm/Mo.

± 0.4 ppm/Mo.

± 0.4 ppm/Mo.

< 0.2 ppm/Mo.

± 20 ppm/Mo.

± 0.1 ppm/Mo.

1

Time to reach percentage of final reading when gas concentration equal to full scale is applied to sensor.

2

Background concentrations of ammonia may shorten lifetime of sensor.

3

Sensor approved for oxygen depletion (< 21% V/V) only.

4

Factory Mutual Performance Approved.

performance

Approved Standard

ISA 92.00.01

ISA 92.00.01

ISA 92.00.01

ISA 92.00.01

ISA 92.00.01

ISA 92.00.01

FM6340

4

Det-Tronics Verified

(CSA Exd)

BS EN 50104

ISA 92.00.01

ISA 92.00.01

Det-Tronics Verified

(CSA Exd)

Det-Tronics Verified

(CSA Exd)

FM6340

4

4

4

Det-Tronics Verified

(CSA Exd)

Det-Tronics Verified

(CSA Exd)

4

4

4

4

4

4

4

11.1

25

95-8616

Typical Cross Sensitivity of H

2

S Sensor (0-20 ppm / 0-50 ppm / 0-100 ppm)

Gas

Carbon monoxide

Sulfur dioxide

Nitric oxide

Hydrogen

Ammonia

Nitrogen dioxide

Methanol

Concentration

300 ppm

5 ppm

35 ppm

10000 ppm

50 ppm

5 ppm

200 ppm

Reading

H

2

S

≤ 2 ppm

~ 1 ppm

H

2

S+

≤ 2 ppm

~ 0 ppm

< 0.7 ppm

≤ 10 ppm

~ 0 ppm

~ –1 ppm

~ 0 ppm

~ 0 ppm

~ 0 ppm

~ 0 ppm

Typical Cross Sensitivity of NH

3

Sensor (0-100 ppm)

Gas

Alcohols

Carbon dioxide

Carbon monoxide

Hydrocarbons

Hydrogen

Hydrogen sulfide

Concentration

1000 ppm

5000 ppm

100 ppm

% Range

10000 ppm

20 ppm

1

Short time gas exposure in minute range.

Reading

0 ppm

0 ppm

0 ppm

0 ppm

0 ppm

~ 2 ppm

1

Typical Cross Sensitivity of NH

3

Sensor (0-500 ppm)

Gas

Alcohols

Carbon monoxide

Chlorine

Nitrogen dioxide

Sulfur dioxide

Hydrogen

Hydrogen sulfide

Concentration

1000 ppm

100 ppm

5 ppm

10 ppm

20 ppm

3000 ppm

20 ppm

Reading

0 ppm

0 ppm

0 ppm

0 ppm

–40 ppm

0 ppm

2 ppm

Typical Cross Sensitivity of CO Sensor (0-100 ppm / 0-500 ppm)

Gas

Hydrogen sulfide

Sulfur dioxide

Nitric oxide

Chlorine

Hydrogen

Nitrogen dioxide

Concentration

15 ppm

5 ppm

35 ppm

1 ppm

100 ppm

5 ppm

Reading

CO

~ 45 ppm

~ 2.5 ppm

~ 10 ppm

–1 ppm

< 40 ppm

~ –3 ppm

Typical Cross Sensitivity of SO

2

Sensor (0-20 ppm / 0-100 ppm)

Gas

Carbon monoxide

Nitric oxide

Nitrogen dioxide

Hydrogen Sulfide

Chlorine

Ammonia

Hydrogen

Hydrogen Cyanide

Acetylene

Ethene

Concentration

300 ppm

50 ppm

6 ppm

25 ppm

5 ppm

20 ppm

400 ppm

10 ppm

10 ppm

50 ppm

Reading

< 1 ppm

0-5 ppm

< –10 ppm

< 0.1 ppm

< –2 ppm

0 ppm

< 1 ppm

< 5 ppm

< 30 ppm

< 45 ppm

Typical Cross Sensitivity of Cl

2

Sensor (0-10 ppm)

Gas

Carbon monoxide

Hydrogen sulfide

Sulfur dioxide

Nitric oxide

Concentration

300 ppm

15 ppm

5 ppm

35 ppm

Reading

0 ppm

~ –7.5 ppm

0 ppm

0 ppm

Typical Cross Sensitivity of NO

2

Sensor (0-20 ppm)

Gas

Alcohols

Carbon dioxide

Chlorine

Nitric oxide

Sulfur dioxide

Hydrogen

Concentration

1000 ppm

5000 ppm

1 ppm

100 ppm

20 ppm

3000 ppm

Reading

0 ppm

0 ppm

≤ 1 ppm

0.4 ppm

5 ppm

0 ppm

For details on other interfering gases, please contact Detector Electronics Corp.

11.1

26

95-8616

appenDix H

HART COMMUNICATION

Hart menU strUctUre

This section displays the menu tree for the GT3000. The menu tree shows the primary commands and options available when using menu selections of a HART handheld communicator.

11.1

27

95-8616

11.1

28

95-8616

appenDix i

INTRINSIC SAFETY CONTROl DRAWING — FM

009803-001 Rev. D

11.1

29

95-8616

INTRINSIC SAFETY CONTROl DRAWING — CSA

009803-002 Rev. b

11.1

30

95-8616

EXplOSION pROOF CONTROl DRAWING — FM

012555-001 Rev. A

11.1

31

95-8616

95-8616

FlexSonic TM Acoustic

Leak Detector

X3301 Multispectrum

IR Flame Detector

PointWatch Eclipse ® IR

Combustible Gas Detector

FlexVu ® Universal Display with GT3000 Toxic Gas Detector

Eagle Quantum Premier ®

Safety System

Corporate Office

6901 West 110 th Street

Minneapolis, MN 55438 USA

www.det-tronics.com

Phone: 952.946.6491

Toll-free: 800.765.3473

Fax: 952.829.8750

[email protected]

All trademarks are the property of their respective owners.

© 2015 Detector Electronics Corporation. All rights reserved.

Det-Tronics manufacturing system is certified to ISO 9001— the world’s most recognized quality management standard.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement