User's manual | Daikin BRC7EB519 User`s manual

Add to my manuals
16 Pages

advertisement

User's manual | Daikin BRC7EB519 User`s manual | Manualzz

Warning

Ask a qualified installer or contractor to install this product. Do not try to install the product by yourself.

Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.

2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install

the outdoor unit close to the sea shore, contact your local distributor.

AIR CONDITIONING SYSTEM

COOLING ONLY [50Hz]

PCSHK1010C

Specifications, designs and other content appearing in this brochure are current as of July 2013 but subject to change without notice.

All rights reserved 07/13 SS

HFC R-410A Line Up for Stores and Offices.

CEILING MOUNTED

CASSETTE TYPE

WALL MOUNTED TYPE

CEILING SUSPENDED TYPE

1

P r o d u c t L i n e u p

71 Series

CEILING MOUNTED

CASSETTE TYPE

Round Flow

Indoor unit

Outdoor unit

CEILING SUSPENDED TYPE

FCQ71LUV1

RR71MV1 / Y1

100

FCQ100LUV1

RR100MY1

125 140

FCQ125LUV1

RR125MY1

FCQ140LUV1

RR140MY1

Page 3

Page 7

WALL MOUNTED TYPE

Indoor unit

Outdoor unit

FHQ71BVV1B

RR71MV1 / Y1

FHQ100BVV1B

RR100MY1

NEW

FHQ125BVV1B

RR125MY1

Page 9

Indoor unit

Outdoor unit

FAQ71BVV1B

RR71MV1 / Y1

FAQ100CVEA

RR100MY1

DUCT CONNECTION

MIDDLE/HIGH STATIC

PRESSURE TYPE

Indoor unit

Outdoor unit

FBQ71DV1

RR71MV1 / Y1

FBQ100DV1

RR100MY1

FBQ125DV1

RR125MY1

FBQ140DV1

RR140MY1

Page 11

Page 13

RR71MV1

RR71MY1

RR100MY1 RR125MY1

O U T D O O R U N I T

RR140MY1

DUCT CONNECTION MIDDLE/HIGH STATIC

PRESSURE TYPE

OUTDOOR UNIT

2

CEILING MOUNTED CASSETTE TYPE

Round Flow

FCQ71LU/100LU/125LU/140LU

Option

Accessory required for indoor unit

Wired LCD remote controller

BRC1C61

Wireless LCD remote controller

A signal receiver must be added to the indoor unit.

BRC7F633F

Signal receiver unit

(Installed type)

Wireless remote controller and signal receiver unit are sold as a set.

Wired LCD remote controller with weekly schedule timer

Navigation Remote

Controller

(Wired Remote Controller)

Features

Comfort Remote controller Cleanliness Work & Servicing

BRC1D61 BRC1E62

Control features Options Others

3

• • • • •

*1

*2

* 1 Applicable when wired remote controller is used

* 2 Applicable when BRC1E62 is used

* 3 Applicable when BRC1D61 or BRC1E62 is used

* 4 Applicable when BRC1C61 is used

* 5 For the outdoor units

*2 *3 *2 *4

• • •

*5

• • • • • • • • • • • • • • •

*5

Avoids uneven temperature and discomfort caused by drafts.

Comfort enhanced by Round Flow!

360° airflow

With uniform temperature distribution

Air movement is gentle with Round Flow

Enhanced Comfort

Airflow distribution

Creates uniform comfort throughout the space

360° airflow can maintain comfort even if air discharge speed is lower.

Greater comfort

Improved energy saving

If you raise the set temperature by 1 to

1.5°C,and velocity is decreased by 25%, you still obtain the same feeling temperature and comfort.

Adapts easily to the installation space.

Because air flows out from corner outlets, comfort spreads more widely.

Typical flow patterns There are a total of 23 flow patterns.

All-round flow 3-way flow

L-shaped

2-way flow

Opposite

2-way flow

(E.g., installed in middle of ceiling)

4-way flow also possible.

(E.g., installed near a wall)

(E.g., installed in a corner)

(E.g., installed in a long room)

Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to close each unused outlet.

Operation sound increases when using 2-way or 3-way flow.

Grime prevention and bactericidal coating: Make cleaning easier.

External panels are treated with a coating that repels dirt.

Treated surface

Untreated surface

To prevent dirt sticking to the external panels, they have been coated with a surface treatment.

Resists soiling

Grimy surface

• Condition after exposure to the smoke of 600 cigarettes in 1 m 3 enclosed space.

Silver ion anti-bacterial drain pan

Mould-proof drain pan includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.

Non-flocking flaps

Condensation does not easily form on and dirt does not cling to non-flocking flaps.

It is easy to clean.

Filter has anti-mould and bactericidal treatment

Prevents mould and microorganisms growing out of the dust and moisture that adheres to the filters.

4

CEILING MOUNTED CASSETTE TYPE

Round Flow

Fine square panels

Panel size is same for all models, FCQ71-140LU.

It is easy to maintain a neat appearance when multiple units are installed.

950 mm

950 mm

Same for all models

Compact body and quiet operation

dB(A)

Indoor unit

71LU

100LU

125LU

140LU

High

35

43

44

44

Low

28

32

34

36

Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

Optimal comfort and convenience assured by air discharge modes

Note: Air direction is set to the standard position when the unit is shipped from the factory.

The position can be changed from the remote controller.

Air direction

Desired situation

Standard setting

Standard position to prevent draft.

Setting to prevent soiling of ceiling *

Recommended for shops with light coloured ceilings that must be kept spotless.

Auto-swing

Auto-swing between

15° and 60°

Auto-swing between

25° and 60°

5-levels air direction setting

Settable to 5 different levels between 15° and 60°

Settable to 5 different levels between 25° and 60°

Auto air direction control

The air direction is set automatically to the memorised position of the previous air direction.

*Closing of the corner discharge outlets is recommended.

Suitable for high ceilings

Even in spaces with high ceilings, a comfortable airflow is carried down to the floor level.

Criteria for ceiling height and number of air discharge outlets

(Ceiling height is reference value)

Ceiling height

Standard

High ceiling

High ceiling

All round flow

2.7 m

3.0 m

3.5 m

Number of air discharge outlets used

71LU 100LU–140LU

4-way flow

3.1 m

3.4 m

4.0 m

3-way flow

3.0 m

3.3 m

3.5 m

2-way flow

3.5 m

3.8 m

-

All round flow

3.2 m

3.6 m

4.2 m

4-way flow

3.4 m

3.9 m

4.5 m

3-way flow

3.6 m

4.0 m

4.2 m

Note: Factory settings are for standard ceiling height and all-round flow.

High ceiling settings (1) and (2) are set with the remote controller by field setting.

2-way flow

4.2 m

4.2 m

-

Two selectable temperature-sensors

Both indoor unit and wired remote controller (option

(BRC1D61,BRC1E62)

) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature must be set during commissioning by the technicians.

*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.

**Wireless remote controller does not have a temperature-sensor.

Switchable fan speed: High/Low

High setting provides maximum reach while low setting minimises drafts.

5

On/Off timer

Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.

Quick and easy to install

Just 256 mm high. Installable in tight ceiling spaces

(71LU)

256 mm * 1

266 mm * 2

*1 298 mm high with 100LU–140LU

*2 308 mm high with 100LU–140LU

Easy height adjustment

Each corner of the unit has an Adjuster Pocket that lets you easily adjust the unit's suspended height.

Note: If the wireless remote control option is installed, a light receptor unit is housed in one of the adjuster pockets.

All models can be installed without using lifter because of the light weight.

Installable in any direction

Since the orientation of the intake grill can be adjusted after installing, the direction of the intake grill lines can be unified when multiple units are installed.

Drain pump is equipped as standard accessory with 850 mm lift.

850 mm

175 mm

Transparent drain socket

Because the drain socket is transparent, after the drain piping has been installed, it is easy to check if the drain come out through the socket.

Connection to a centralised control system is available without option

Easier to maintain

The condition of the drain pan and drain water can be checked by removing the drain plug and intake grille.

Drain plug

Just open the intake grille!

With ultra-long-life filters (option), maintenance is not required in normal shops or offices for up to four years.

Options required for specific operating environments

Ultra-long-life filter

Even in smoky environments where the air conditioning is on most of the time, the ultra long-life filter only has to be changed once a year.

Smoky atmosphere: annual filter change

*For dust concentration of 0.3 mg/m 3 (Requires separately sold Air Cleaner.)

1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year

Ordinary store or office: filter change every 4 years

*For dust concentration of 0.15 mg/m 3

4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 4 years

High-efficiency filter

Available in two types: 65% and 90% colorimetry.

Fresh air intake kit

Using this kit, a duct can be fitted to increase the intake of outdoor air.

Outside

Note: *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.

**Outside Air fan interlocked with air conditioning unit is necessary.

Optional PCB(KRP1C63)is required for interlocking.

***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating sound and may also influence temperature sending.

Panel spacer

Use when only minimal space is available between drop ceilings and ceiling slabs.

40 mm

Panel spacer

Note: Some ceiling constructions may hinder installation.

Contact your Daikin Dealer before installing your unit.

Sealing material of air discharge outlet

Sealing material block air discharge openings not used in

2-way or 3-way blow.

Branch duct (direct-connection round duct)

A round duct can be attached without the need for a chamber.

A flanged port for direct connection of a round duct is provided. An existing branch duct chamber can also be fitted

(square slit hole).

The units can be installed in the following different ways.

Chamber type Chamber type

(without T-joint pipe and fan) (with T-joint pipe and without fan)

KDDP55B160 KDDP55B160K

Flexible duct

(procured locally)

T-joint pipe

(procured locally)

Flexible duct

T-joint pipe

Direct installation type

KDDP55X160

Suction chamber

Connection chamber

Intake duct

(procured locally)

(duct length: 4 m max.)

Note: Use of options will increase operating sound.

Suction chamber

Connection chamber

Intake duct

(procured locally)

(duct length: 4 m max.)

Duct flange

(with insulation

material)

Intake duct

(procured locally)

6

CEILING SUSPENDED TYPE

Quiet and compact system.

FHQ71BV / 100BV / 125BV

Option

Accessory required for indoor unit

Wired LCD remote controller

BRC1C61

Wireless LCD remote controller

A signal receiver must be added to the indoor unit.

BRC7EA66

Signal receiver unit (Installed type)

Wireless remote controller and signal receiver unit are sold as a set.

Wired LCD remote controller with weekly schedule timer

Navigation Remote

Controller

(Wired Remote Controller)

Features

Comfort

BRC1D61

Remote controller Cleanliness Work & Servicing

BRC1E62

Control features Others

7

• • •

*1 *2

*3

* 1 Installable on max. 3.5 m high ceiling

* 2 Applicable when wired remote controller is used

* 3 Applicable when BRC1E62 is used

* 4 Applicable when BRC1D61 or BRC1E62 is used

* 5 Applicable when BRC1C61 is used

* 6 Option

* 7 For the outdoor units

*3 *4 *3 *5

*6 *7

• • • • • • • • • •

*7

Diffuses comfortable air throughout the room

Auto-swing (up&down) brings comfort to the room.

Wide air discharge openings produce a spreading 100° airflow

Air is blown up to 50° in the downward direction.

Quiet operation

Sound operation has been reduced on the exposed ceiling suspended type unit.

dB(A)

Indoor unit High Low

71BV

100BV

39

42

44

35

37

39 125BV

Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

Uses quiet stream fan and other quiet technologies.

50°

100°

Installable on ceilings 3.5 m high

Two selectable temperature-sensors

Both indoor unit and wired remote controller (option

(BRC1D61,BRC1E62)

) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature requires initial setting by the installer.

*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.

**Wireless remote controller does not have a temperature-sensor.

Switchable fan speed: High/Low

Programme "Dry"

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Turbulent flow

is reduced

Straightening plate

Quiet stream fan

Easier to maintain

Long-life filter lasts about half year * maintenance not required

* For dust concentration of 0.15 mg/m 3

Two time settings (2500 hrs and 1250 hrs) are available to match the installation environment. Maintenance time warning is displayed on the remote controller (filter sign).

Non-flocking flap

Condensation does not easily form on and dirt does not cling to non-flocking flap.

It is easy to clean.

Non-flocking flap

Easy-clean, flat surfaces

It is easy to wipe dirt off the flat side and lower surfaces of the unit.

Installation flexibility for freedom of design

Uniform height and depth. Compact design for small-capacity models to meet tighter dimensional constraints.

Indoor unit

Height

Width

Depth

71BV

1,160

(mm)

100BV 125BV

195

1,400

680

1,590

For all maintenance tasks, access is from bottom surface.

Flexible installation

The unit fits more snugly into tight spaces.

30 mm

or more

30 mm

or more

*Water used in the test-run can now be drained from the air discharge opening rather than from the side as was formerly the case.

Drain pump kit (option) can be easily incorporated

Drain pipe connection can be done inside the unit. refrigerant and drain pipe outlets are at the same opening.

600 mm

Drain pump kit

(built inside main unit)

All wiring and internal servicing can be done from under the unit

Pipes more easily rigged, too

Plastic panels are used to conceal piping holes. Holes can be easily punched out without requiring special tools.

Oil resistant grille

Oil-resistant plastic is used for the air suction grille.

This satisfies durability in restaurants and other similar environments.

Note: Intended for use in salons, dining rooms, and ordinary sales floors, this specification is not suitable for kitchens or other harsh environments.

8

WALL MOUNTED TYPE

Compact design and easy installation

F A Q 7 1 B V / 1 0 0 C

FAQ71BV

NEW FAQ100C

Features

Comfort

Option

Accessory required for indoor unit

Wired LCD remote controller

BRC1C61

Wireless LCD remote controller

A signal receiver must be added to the indoor unit.

71BV

100C

BRC7EA619

BRC7EB519

71BV

100C

Signal receiver unit (Installed type)

Wireless remote controller and signal receiver unit are sold as a set.

Wired LCD remote controller with weekly schedule timer

Navigation Remote

Controller

(Wired Remote Controller)

BRC1D61

Remote controller Cleanliness Work & Servicing

BRC1E62

Control features Others

9

*1 *2 *3

• •

*4

* 1 FAQ71: 2 step, FAQ100: 3 step

* 2 FAQ100 only

* 3 Applicable when BRC1E62 is used

* 4 Applicable when wired remote controller is used

*3 *3 *5 *3 *6

*7 *8

* 5 Applicable when BRC1D61 or BRC1E62 is used

* 6 Applicable when BRC1C61 is used

* 7 Option

* 8 For the outdoor units

• • • • • • • • • •

*8

340 mm

Compact &

Sophisticated design

FAQ100

9 kg lighter

FAQ100BV FAQ100C

Height 360 mm 340 mm

Width 1,570 mm 1,200 mm

Depth 200 mm 240 mm

1,200mm

370mm shorter Weight 26 kg 17 kg

Flaps are closed when not operating

Comfortable

Auto swing (up and down) and wide-angle louvers

(left and right by hand) facilitate even room temperature

Wide-angle louvers

(by hand)

Soft material louver bends airflow over a wider area

An air discharge modes ensure comfortable air distribution across the entire room

Auto-swing 5-level air direction setting Auto-air direction control

Auto-swing from 10 to 70

10°

70°

10°

Gettable to 5 different levels between 10 to 70

70°

10°

The air direction is set automatically to the memorised position of the previous air direction.

(Initial setting is 10 for cooling .)

Comfort even on the far side of the room

To carry air to the far side of long rooms, extra-high airflow adds 10% more fan speed the "high" setting.

Air discharge strength is selected from the remote controller.

Easy installing and servicing

6-direction piping offers greater installation flexibility.

Left pipe

Back-left pipe

Bottom-left pipe

Right pipe

Bottom-right pipe

Back-right pipe

Maintenance possible from the front of the unit

All maintenance tasks can be carried out via front access. During service work, attachment and detachment of parts is easier.

Drain pump kit is available as option.

Installs onto side of unit.

Height of drain up

Refrigerant piping

1,000 mm

Drain pump kit

Drain pump kit can be installed on either left and right side of the air conditioner.

Indoor unit

Connection to a centralised control system is available without option

Easy cleaning

Removable and washable grille

Two selectable temperature-sensors

Switchable fan speed: High/Middle/Low

(FAQ100)

: High/Low

(FAQ71)

Auto airflow rate (FAQ100 only when BRC1E62 is used)

Programme "Dry"

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Flat panel, easy to wipe dust off

(FAQ100)

Non-flocking flaps

Condensation does not easily form on and dirt does not cling to non-flocking flaps.

It is easy to clean.

10

DUCT CONNECTION MIDDLE HIGH STATIC PRESSURE TYPE

FBQ71D/100D/125D/140D

Option

Accessory required for indoor unit

Wired LCD remote controller

BRC1C61

Wireless LCD remote controller

A signal receiver must be added to the indoor unit.

BRC4C64

Signal receiver unit

(Separate type)

Wireless remote controller and signal receiver unit are sold as a set.

Wired LCD remote controller with weekly schedule timer

Navigation Remote

Controller

(Wired Remote Controller)

Features

Comfort Remote controller Cleanliness Work & Servicing

BRC1D61 BRC1E62

Control features Option Others

11

• •

*1

*2 *2 *3

* 1 Applicable when wired remote controller is used

* 2 Applicable when BRC1E62 is used

* 3 Applicable when BRC1D61 or BRC1E62 is used

* 4 Applicable when BRC1C61 is used

* 5 Option

* 6 For the outdoor units

*2 *4 *5

• •

*6 *5

• • • • • • • • • • •

*6

Increased freedom of design thanks to variable control over external static pressure

Comfort airflow achieved in accordance with conditions such as duct length.

Using a DC fan motor, the external static pressure can be controlled within a range of 50 Pa to 200 Pa.

Freely control external static pressure

50 Pa 200 Pa

Set to low static pressure when ducts are short.

Set to high static pressure for advanced needs such as when using dampers and long ducts.

Reduced installation time

Use remote controller to adjust airflow

When testing standard integrated ceiling units that employ duct work, much time used to be required to adjust airflow to the right level. Thanks to the ability provided by Daikin to automatically perform this troublesome adjustment using a remote controller, this step is now quick and easy. (Adjust by H tap .)

1. Adjust to approximately ±10% of the rated H tap airflow.

2. Once actual operation has begun, adjustment of the rated airflow is not possible.

Connection to a centralised control system is available without option

Quiet operation

High

Low

71D

37

32

100D

38

33

300

125D

40

36 dB(A)

140D

40

36

Thin, lightweight indoor unit makes delivery and installation easy.

With a height of only 300 mm, installation is possible even in buildings with narrow ceiling spaces.

300 mm

Easy maintenance

Maintenance is easy because the drain pan can be removed.

Clean

Silver ion anti-bacterial drain pan

Mould-proof drain pan includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.

Indoor unit

Height

(mm)

Width

(mm)

Depth

(mm)

Machine Weidth

(kg)

71D

1,000

36

100D 125D

300

1,400

700

46

140D

Drain pump is equipped as standard accessory with 700 mm lift.

700 mm

Comfortable

Two selectable temperature-sensors

Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.

This feature requires initial setting by the installer.

*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.

**Wireless remote controller does not have a temperature-sensor.

Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)

When air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicated ventilation grilles should be installed on the partitioning wall or under the door between the rooms.

Partitioning wall

Ventilates air through the partitioning wall.

(See right)

Door-installed ventilation grille

Ventilation grille

Wall-installed ventilation grille

Ventilation grille

Under-door cutout

Under-door cutout

Note: The under-door cutout method should be used only when there is a small volume of airflow.

12

OUTDOOR UNIT

OUTDOOR UNIT

13

RR71MV1

RR71MY1 RR100MY1 RR125MY1 RR140MY1

Easy installation and maintenance

Pre charged for up to 30 metres

If refrigerant piping length does not exceed

30 m, there is no need for on-site gas charging.

70 m piping length

4-direction piping offers greater layout freedom

The outer panel for the piping connection part of the front, right side and backside can be removed and is easier for post-installation piping work.

Allowed refrigerant pipe length and

level difference

Pre charged 1

ALL model

30 m

Max. length

70 m

(Equivalent length 90m)

Max. level difference

30 m

Note: 1 Additional refrigerant charging is required if

the refrigerant pipe is longer than the length.

Separation available

Easy centralised installation with the module oriented design

Depth of 71-140M are standardised as 320 mm. Horizontal continuous mounting is available.

Facilitates pump down

(Refrigerant recovery function)

A pump-down switch is provided to make it easier to collect refrigerant if the unit is to be moved or layout modified.

*Pump-down function is available for pre-charged refrigerant amount.

Suction

320 mm

Discharge

71M 100M 125M 140M

900 mm 900 mm 900 mm 900 mm

Compact

Slim-design and low-profile compact outdoor units

Compactly designed outdoor unit with interior layout organised for the smooth flow of air.

40

30

20

10

0

-10

-20

Operation range

Suited for year-round cooling applications

Cooling is efficient even in winter when indoor temperatures are higher than those outside, such as in underground public spaces or offices with many computers.

Wide operation range

(Applies to RR71-125M)

50

46

˚C

DB

Outdoor temp

(˚CDB)

Safety

Cooling

-15

˚C

DB

Reinforcing wire fittings

(option) are available

Fittings can be mounted on the four locations, right/ left on front and back side of the outdoor unit.

Durability

Heat exchange fins provided with anti-corrosion treatment

Construction

Non-treated fin

PE fin

Aluminium

Hydrophilic film

Aluminium

Corrosion resistant acrylic resin

Example of installation service space for outdoor unit

For RR71MV1, RR71-140MY1

The values represent the case for the RR71-140 type. The values in ( ) are for RR71 type. (The unit values is mm. )

1 When there is an obstruction on the inlet side

1) When the overhead space is open

1. For single unit installation

When there is an obstruction only on the inlet side

100(50) or more

When there are obstructions on both sides

2 When there is an obstruction on the outlet side

1) When the overhead space is open

1. For single unit installation

2. For multiple units installation

(more than two units)

500 or more

2. For multiple units installation

(more than two units)

When there are obstructions on both sides

1000 or more

100 or more

100 or more

200 or more

100 or more

300(200) or more

2) When there is an obstruction

in the overhead space

1. For single unit installation

When there is an obstruction on the inlet side

An obstruction in the overhead space

500 or less

100 or more

When there are obstructions on the inlet side and both sides

An obstruction in the overhead space

150 or more

500 or less

150 or more

150 or more

2. For multiple units installation (more than two units)

When there are obstructions on the inlet side and both sides

500 or less

An obstruction in the overhead space

1000 or more

2) When there is an obstruction

in the overhead space

1. For single unit installation

An obstruction in the overhead space

2. For multiple units installation

(more than two units)

An obstruction in the overhead space

1000 or more

3 When there are obstructions on both the inlet and outlet sides

(When the obstruction on the outlet side is higher than the

unit itself)

1) When the overhead space is open

(There is no limit to the height of the obstruction on the

outlet side.)

1. For single unit installation

L H

2. For multiple units installation

(more than two units)

1000 or more

500 or less

500 or more

500 or less

500 or more

100(50)

or more

200 or more

300(200) or more

L H

Note : As for other patterns of installation, please refer to Installation manual or Engineering Data Book.

1000 or more

300(200)

or more

14

Wired LCD remote controller

LCD REMOTE CONTROLLER

Necessary optional accessory

15

Easy-to-read LCD remote controller allows various system control configurations and can control multiple indoor units.

Remote controller options are shown on the page introducing each indoor unit model.

NEW

Navigation Remote Controller

(Wired Remote Controller BRC1E62)

This simple, modern designed remote controller with fresh white colour matches your interior design. Operation is much easier and smoother, just follow the indications on the navigation remote controller.

Wired LCD remote controller

Easy to read because of large LCD screen.

The rubber switch and the oil-resistant plastic casing are adopted for durability.

Only 17 mm thick. Can be installed either recessed or exposed.

Wired remote controller has built-in temperature-sensor

(Applies to wired remote controllers

(BRC1C61,BRC1D61,BRC1E62)

)

Enables temperature sensing closer to target area for improved comfort. (When using remote control from another room, temperature-sensor in indoor unit's air inlet must be selected.)

BRC1C61

Dot matrix display

A combination of fine dots enables various icons.

Large text display is easy to see.

Clear Display

Energy saving

NEW Setpoint auto reset

- Even if the set temperature is changed, it returns to the preset temperature after apreset period of time.

- Period selectable from 30min/60min/90min/120min.

Restaurant sample

Restaurant opened

Temperature is set to 27ºC

27 °C

Full tables at lunchtime

Then is lowered to 24ºC for crowded room

24 °C

After 30 minutes*

Automatically returns to preset temperature (27ºC)

Returns to

27 °C automatically

Backlight display

NEW Setpoint range set

- Saves energy by limiting the min. and max. set temperature.

- Avoids excessive heating or cooling.

- This function is convenient when the remote controller is installed at a place where any number of people may operate it.

Wired LCD remote controller with weekly schedule timer

Remote control is equipped with weekly timer function.

24-hour clock function.

Programming function for each day of week.

Scheduling possible of start/stop and temperature limit (5 settings/day).

BRC1D61

LCD wireless remote controller

Light receptor mounted type

The wireless remote controller is supplied in a set with a signal receiver.

Shape of signal receiver unit differs according to the indoor unit.

Wireless remote controller

BRC7F633F

Signal receiver unit

(For ceiling mounted

cassette type)

Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of the ceiling mounted cassette type.

Facilitates maintenance and repair

All initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted cassette type can be remotely set without having to use stepladder access for manual setting.

Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically).

Remote controller is equipped with model name and failure display functions. This facilitates service in the unlikely event of a malfunction.

(Applies to wired remote controller

(BRC1E62)

)

SkyAir shares common control with

Heat Reclaim Ventilator and the other Daikin air-conditioning units, thus simplifying interlocking operations.

Easily adaptable to large-scale, high-function, centralised remote control systems.

Installing and connecting control wiring between

SkyAir and other Daikin air-conditioning equipment is easy.

*Please refer to page 17 for more details.

*Setting possible for after 30, 60, 90, and 120

minutes. Off timer (programmed)

- Turns off the air conditioner after a preset period of time.

- Period can be preset from 30 to 180 minutes in10-minute increments.

Indoor units applicable for the remote controller

Signal receiver unit is contained inside decoration panel or indoor unit

CEILING MOUNTED CASSETTE TYPE

CEILING SUSPENDED TYPE

WALL MOUNTED TYPE 71BV

100C

DUCT CONNECTION MIDDLE HIGH STATIC PRESSURE TYPE

BRC7F633F

BRC7EA66

BRC7EA619

BRC7EB519

BRC4C64

Convenience

Weekly schedule

NEW

- 5 actions per day can be scheduled for each day

of the week.

- The holiday function will disable schedule timer

for the days that have been set as holiday.

- 3 independent schedules can be set.

(e.g. summer, winter, mid-season)

Multilingual display

Display is available in 11 languages.

(English, German, French, Spanish,

Italian, Portuguese, Greek, Dutch,

Russian, Turkish, and Polish).

LCD panel shows operating status in letters, numbers, and motion.

Airflow / swing display

Preset temperature / operation mode display

Programming time display

Self-diagnosis function

Displays auto-swing operating status and setting position of air discharge angle.

Displays preset room temperature and operating status (fan, dry, cool).

Operation start and stop time can be set for individual timers up to 72 hours. The LCD also shows when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.

Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.

16

Simple system provides a diverse assortment of control modes.

Control pattern Wired remote controller Wireless remote controller

Control by 1 remote controller

(Basic system)

Control by 2 remote controllers

For control from 2 locations such as in room and control room, exits, etc.

Non-polar, double-core

(max. wiring length 500 m)

Signal receiver unit installed on indoor unit

Control by 1 wireless remote controller and 1 wired remote controller (See note 2, 3)

Signal receiver unit installed on indoor unit

Connects 2 wired remote controllers (See note 1)

Group control

For simultaneous control of up to 16 indoor units.

Automatic address setting function Automatic address setting function

Signal receiver unit installed on 1 indoor unit

Control by external command

Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.

Optional wiring adaptor for electrical appendices is necessary

Central remote controller (option)

Optional wiring adaptor for electrical appendices is necessary

Central remote controller (option)

Centralised remote control

Centralised control of up to 64 indoor groups from remote location up to 1 kilometer away.

Optional SkyAir series interface adaptor required (See note 4)

Optional SkyAir series interface adaptor required (See note 4)

Heat Reclaim

Ventilator

Heat Reclaim

Ventilator

Link by remote controller group control.

Can be operated simultaneously or independently by remote controller

(set by ventilation mode)

Can be operated simultaneously by remote controller

(set by ventilation mode)

Interlock control with Heat Reclaim

Ventilator

Central remote controller (option) Central remote controller (option)

Zone link control by centralised control.

Heat Reclaim

Ventilator

Heat Reclaim

Ventilator

Heat Reclaim Ventilator for indoor units within a zone are operated by interlocking Can also be operated independently by remote controller.

Heat Reclaim Ventilator for indoor units within a zone are operated by interlocking

Note:1.BRC1E62 can connect to BRC1E62 only.

2.It is not possible to use two wireless remote controllers.

3.BRC1E62 cannot connect to wireless remote controller.

4.The ceiling mounted cassette type <Round Flow>, wall mounted type, and duct connection middle/high static pressure type come standard with an interface adaptor for SkyAir series.

Easily adaptable to large-scale, high-function, centralised remote control system.

Central remote controller Unified on/off controller Schedule timer

DCS601C51 (Option)

DCS302CA61 (Option) DCS301BA61 (Option) DST301BA61 (Option)

17

Centralised control, with setting as simple as it is with a standard remote controller, of up to 64 groups

(1,024 indoor units) is possible.

Centralised control of on/off by group or all at once for up to 256 indoor units.

Interface adaptor for SkyAir series

DTA112BA51 (Option)

Unified control of weekly schedule for up to 1,024 indoor units.

Schedule timer sets on/off time in 1 minute units to be executed twice a day for a week at a time.

Enables centralised control via connection to a high-speed, DIII-NET communication system, adopted for the Daikin VRV system.

Necessary for interface adaptor for SkyAir series with the central remote control units shown at above.

With its high functionality, the full colour “all-in-one” graphic controller facilitates management of SkyAir

System in a variety of ways.

The interface adaptor for the SkyAir series is optional except for the ceiling mounted cassette type <Round Flow>, wall mounted type, and the duct connection middle/high static pressure type.

Abundance of functions that provide comfortable air-conditioning in stores and offices.

Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.

Comfort

Auto-swing

Delivers comfortable air-conditioning to all areas, near to and far from the air-conditioner.

The air flow direction can be fixed at your desited angle by the remote controller.

High-ceiling application

Delivers air-conditioning comfort all the way down to the floor in air-conditioning zones with high ceilings.

Swing pattern selection

(standard, ceiling soiling prevention)

You can freely set 2 air discharge setting by remote controller.

(1) Air direction in standard setting

(2) Air direction in ceiling soiling prevention setting

Note:When units are installed on high ceilings, depending on the model, various restrictions concerning maximum height, air discharge direction, and choice of options may apply.

Switchable fan speed

High setting provides maximum reach while low setting minimises drafts.

Auto airflow rate

Airflow rate is automatically controlled in accordance with the difference between room temperature and set temperature.

Two selectable temperature-sensors

Temperature-sensors are included in the indoor unit and optional wired remote controller. Temperature sensing closer to target area is possible to further increase the comfort level.

Use the temperature-sensor in the indoor unit when controlling air conditioning from another room.

Note: Wireless remote controllers have no temperature-sensor.

Programme "Dry"

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature. Useful for reducing uncomfortable humidity without uncomfortable cooling of the room.

High fan speed mode

You can increase fan speed approximately 10% higher than the "high" setting.

Applicable for wall mounted type

Year-round cooling applicable

Efficient cooling even in winter when indoor temperatures are higher than those outside, such as in underground public spaces or offices with many computers.

The year-round cooling kit is required as option.

Remote Controller

Setpoint auto reset

Even if the set temperature is changed, it returns to the preset temperature after a preset period of time.

Setpoint range set

Saves energy by limiting the minimum and maximum set temperatures. Avoids excessive heating and cooling.

Weekly schedule timer

Up to five operation ON/OFF settings can be programmed per day for each day of the week. Not only can the time be set for the operation ON setting, but also the temperature.

Cleanliness

Anti-bacterial air filter

The Air filter has a anti-bacterial treatment to help prevent the growth of bacteria and mould on it.

Mould-proof air filter

Sanitary filter has mould-resistant treatment.

Off timer (programmed)

Sets and saves setting for an increment of time that automatically turns off air conditioner after a preset period of time for each time operation starts.

On/Off timer

Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.

Silver ion anti-bacterial drain pan

Mould-proof drain pan includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.

Mould-proof drain pan

Mould-proof drain pan prevents growth of mould in highly humid conditions.

18

19

Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.

Work and Servicing

Drain pump mechanism

Steeper gradient realises more efficient condensate drainage.

High-lift is especially useful for long lengths of drain piping.

Filter sign

The filter sign warns you when it is time to clean the filter.

*When using a wired remote controller the sign is displayed in the LCD.

When using a wireless remote controller the filter sign lamp illuminates on the signal receiver unit.

Pre charged for up to 30 metres

If refrigerant piping length does not exceed 30 m, there is no need for on-site gas charging.

Emergency operation

If there is a malfunction elsewhere in the system, the fan or compressor can still be operated.

Long-life filter

Maintenance is not required for one year (two years when a ceiling mounted cassette type is used).

Ceiling soiling prevention function

Daikin's innovative air discharge mechanism keeps airflow away from the ceiling. Ceiling cleaning is less frequently required.

Self diagnosis function

The operating parameters of indoor and outdoor units, and sensor data at critical locations throughout the system, are constantly monitored using a microcomputer. To facilitate quick response in the event of a malfunction, a message appears on the LCD of the remote controller and an LED on the unit illuminates.

Control features

Auto-restart

If there is a power outage while the equipment is operating, operations will restart in the same mode as before the power cut when electricity is restored.

Control by 2 remote controllers

Using 2 remote controllers you can operate the equipment locally or from a remote location.

Note: When a wireless remote controller is used, remote control by two remote controllers is not possible.

Group control by 1 remote controller

You can turn up to 16 indoor units on/off with a single remote controller. (When using connected indoor units, the settings must all be the same and on/off will be simultaneous.)

External command control

Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.

*Required for KRP58M51 (Option)

Central remote control

Optional central remote controller enables centralised control of up to 1024 indoor units (64 groups) from up to 1 kilometer away.

Interlock control

Enables interlocking control with external equipment such as

Heat Reclaim Ventilator.

DIII-NET communication standard

Standardly equipped interface enables connection to centralised control system without need of an adaptor.

Options

Ultra long-life filter

Requires no maintenance for about 4 years* (10,000h) in stores and offices.

*For dust concentration of 0.15 mg/m 3

High-efficiency filter unit

Two types are available: 65% and 90% colorimetry.

Fresh-air intake kit

You can provide air-conditioning with fresh air from outside.

Convenient for places where a ventilation fan cannot be installed.

Note: *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.

**Outside Air fan interlocked with air conditioning unit is necessary. Optional

PCB(KRP1C63)is required for interlocking.

***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating noise and may also influence temperature sending.

Others

Anti corrosion treated heat exchangers

To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated Anti corrosion treated heat exchangers (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.

In high corrosive areas, regular maintenance needs to be carried out.

SPECIFICATIONS

CEILING MOUNTED CASSETTE TYPE

Indoor unit

71

FCQ71LUV1

Model

Name

Outdoor unit

RR71MV1

Power supply

Cooling capacity 1

Power consumption

Indoor unit

Colour

Cooling 1

Unit

Decoration panel

Airflow rate (H/L)

Sound level (H/L) 2

Dimensions

(H X W X D)

Machine weight

Certified Operation range

Unit

Decoration panel

Unit

Decoration panel

Cooling

Outdoor unit

Piping connections

Colour

Compressor Type

Motor output

Refrigerant charge (R-410A)

Sound level 2 Cooling

Dimensions (H X W X D)

Machine weight

Certified Operation range Cooling

Liquid (Flare)

Gas (Flare)

Drain Indoor unit

Outdoor unit

Max. interunit piping length

Max. installation level difference

Heat insulation kW kW kW kg dB(A) mm kg

°CDB mm mm mm mm m m m 3 /min cfm dB(A) mm mm kg kg

°CWB

V1

Y1

RR71MY1

1 Phase, 220–230 V, 50 Hz

3 Phase, 380–415 V, 50 Hz

7.7

2.72(V1), 2.66(Y1)

21/13.5

741/477

35/28

256 X 840 X 840

21

2.2

2.7 (Charged for 30 m)

50

770

X

900

X

320

83(V1), 81(Y1)

100

FCQ100LUV1

RR100MY1

125

FCQ125LUV1

RR125MY1

3 Phase, 380–415 V, 50 Hz

10.5

3.60

12.8

4.66

----------

Fresh white

32/20

1,129/706

43/32 44/34

298 X 840 X 840

50 X 950 X 950

24

5.5

12 to 25

3.0

Ivory white

Hermetically sealed scroll type

3.75

3.7 (Charged for 30 m)

53

1,170

X

900

X

320

99

-15 to 46 o/9.5

o/15.9

VP25 (O.D o/32 X I.D o/25) o/26.0 (Hole)

70 (Equivalent length 90m)

30

Both liquid and gas piping

106

33/22.5

1,164/794

Note :

1 Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).

2 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

140

FCQ140LUV1

RR140MY1

14.2

5.02

44/36

14 to 25

2.84

4.3 (Charged for 30 m)

54

1,345

X

900

X

320

108

-5 to 46

CEILING SUSPENDED TYPE

Indoor unit

71

FHQ71BVV1B

100

FHQ100BVV1B

125

FHQ125BVV1B

Model

Name

RR71MV1

Outdoor unit RR100MY1 RR125MY1

RR71MY1

Power supply

Cooling capacity

Power consumption

Indoor unit

Outdoor unit

1

Colour

Airflow rate (H/L)

Sound level (H/L) 2

Dimensions (H X W X D)

Machine weight

Certified operation range

Colour

Compressor Type

Motor output

Refrigerant charge (R-410A)

Sound level 2

Dimensions (H X W X D)

Machine weight

Certified operation range

Piping connections

Liquid (Flare)

Gas (Flare)

Drain Indoor unit

Outdoor unit

Max. interunit piping length

Max. installation level difference

Heat insulation m kW kW

3 /min cfm dB(A) mm kg

°CWB kW kg dB(A) mm kg

°CDB mm mm mm mm m m

V1

Y1

1 Phase, 220–230 V, 50 Hz

3 Phase, 380–415 V, 50 Hz

195 X

770 X

7.1

2.75(V1), 2.70(Y1)

17/14

600/494

39/35

1,160

27

2.2

50

900

X

X

680

2.7 (Charged for 30 m)

320

83(V1), 81(Y1)

3 Phase, 380–415 V, 50 Hz

9.8

3.53

White

24/20

847/706

42/37

195 X 1,400 X 680

32

12 to 25

Ivory white

Hermetically sealed scroll type

3.0

3.7 (Charged for 30 m)

53

1,170 X 900 X 320

99

-15 to 46 o/9.5

o/15.9

VP20 (O.D o/26

X

I.D o/20) o/26.0 (Hole)

70 (Equivalent length 90m)

30

Both liquid and gas piping

12.2

4.51

30/25

1,059/883

44/39

195 X 1,590 X 680

35

3.75

106

Note :

1

2

Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).

Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

20

21

SPECIFICATIONS

WALL MOUNTED TYPE

Indoor unit

71

FAQ71BVV1B

100

FAQ100CVEA

Model

Name

RR71MV1

Outdoor unit RR100MY1

Power supply

Cooling capacity

Power consumption

Colour

Indoor unit

Outdoor unit

1

Cooling

Airflow rate (H/M/L)

Sound level (H/M/L)

Dimensions (H

X

W

X

D)

Machine weight

Max. installation level difference

Heat insulation

1

2

Certified Operation range

Colour

Compressor Type

Motor output

Refrigerant charge (R-410A)

Sound level 2 Cooling

Piping connections

Dimensions (H X W X D)

Machine weight

Certified Operation range

Liquid (Flare)

Gas (Flare)

Drain Indoor unit

Outdoor unit

Max. interunit piping length m kW kW

3 /min cfm dB(A) mm kg

°CWB kW kg dB(A) mm kg

°CDB mm mm mm mm m m

V1

Y1

RR71MY1

1 Phase, 220–230 V, 50 Hz

3 Phase, 380–415 V, 50 Hz

7.6

2.93

(V1), 2.87(Y1)

White

19/-/15

671/-/530

43/-/37

290 X 1,050 X 230

13

12 to 25

Ivory white

Hermetically sealed scroll type

2.2

2.7 (Charged for 30 m)

50

770

X

900

X

320

83(V1), 81(Y1)

-15 to 46 o/9.5

o/15.9

VP13 (O.D o/18 X I.D o/13) o/26.0 (Hole)

70 (Equivalent length 90m)

30

Both liquid and gas piping

3 Phase, 380–415 V, 50 Hz

10.0

3.72

Fresh white

26/23/19

918/812/671

49/45/41

340 X 1,200 X 240

17

3.0

3.7 (Charged for 30 m)

1,170

X

53

900

99

X

320

Note :

1 Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).

2

Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

71 100

Indoor unit FBQ71DV1 FBQ100DV1

125

FBQ125DV1

140

FBQ140DV1

Model

Name

RR71MV1

Outdoor unit RR100MY1 RR125MY1 RR140MY1

RR71MY1

Indoor unit 1 Phase, 220–240 V, 50 Hz

Power supply

Outdoor unit

Cooling capacity 1

Power consumption

Indoor unit

Cooling

Colour

Fan Airflow rate Cooling

(H/L)

External static pressure 2

Sound level 3 Cooling (H/L)

Outdoor unit

Dimensions (H X W X D)

Machine weight

Certified Operation range Cooling

Colour

Compressor Type

Motor output

Refrigerant charge (R-410A)

Sound level 3 Cooling

Piping connections

Dimensions (H X W X D)

Machine weight

Certified Operation range

Liquid (Flare)

Cooling

Gas (Flare)

Drain Indoor unit

Outdoor unit

Max. interunit piping length

Max. installation level difference

Heat insulation kW kW m 3 /min cfm

Pa dB(A) mm kg

°CWB kW kg dB(A) mm kg

°CDB mm mm mm mm m m

V1

Y1

1 Phase, 220–230 V, 50 Hz

3 Phase, 380–415 V, 50 Hz

7.1

2.85

(V1), 2.80(Y1)

18/15

635/530

37/32

300 X 1,000 X 700

36

2.2

2.7 (Charged for 30 m)

50

770 X 900 X 320

83(V1) 81(Y1)

10.0

3.70

32/23

1,130/812

----------

3 Phase, 380–415 V, 50 Hz

12.2

4.76

50-200

38/33

300 X 1,400 X 700

46

12 to 25

3.0

Ivory white

Hermetically sealed scroll type

3.75

3.7 (Charged for 30 m)

99

-15 to 46

53

1,170 X 900 X 320 o/9.5

o/15.9

VP25 (O.D o/32 X I.D o/25) o/26 (Hole)

70 (Equivalent length 90m)

30

Both liquid and gas piping

106

39/28

1,377/988

40/36

Note :

1

Rated cooling capacities are based on the following conditions: Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)

2

Initial setting is standard.

3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

14.1

5.07

14 to 25

3.0

4.3 (Charged for 30 m)

54

1,345 X 900 X 320

108

-5 to 46

OPTIONS

Indoor unit

CEILING MOUNTED CASSETTE TYPE

Name of option Remark

FCQ71LUV1

Decoration panel

Sealing material of air discharge outlet

Panel spacer

Fresh air intake kit 1

Chamber type

Direct installation type

Chamber connection kit 2

Insulation kit for high humidity

Without the T-joint pipe and fan

With the T-joint pipe, without fan

High-efficiency filter

Replacement high-efficiency filter

(Colorimetric method 65%)

(Colorimetric method 90%)

(Colorimetric method 65%)

(Colorimetric method 90%)

Filter chamber

Replacement long-life filter

Ultra long-life filter

Replacement ultra long-life filter

Branch duct chamber

Remote controller

Wired LCD remote controller with weekly schedule timer 3

Navigation Remote Controller Wired type 3

Central remote controller 4

Unified ON/OFF controller 4

Wired type 3

Wireless type

Schedule timer 4

Touch Controller 4

Adaptor for wiring 5

Wiring adaptor for electrical appendices 5

Installation box for adaptor PCB

Remote sensor (for indoor temperature)

Cooling only

KDTP55K80

KAFP556B80

KAFP557B80

KAFP552B80

KAFP553B80

KDJP55B80

Note: 1 Refer to page 6 for the details.

2 Required for installing high-efficiency filter or ultra long-life filter.

3 Wiring for wired remote controller to be procured locally.

4

The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.

5

Installation box for adaptor PCB (KRP1H98) is necessary.

FCQ100LUV1

Kit name

FCQ125LUV1

BYCP125K-W1

KDBH55K160F

KDBP55H160FA

KDDP55B160

KDDP55B160K

KDDP55X160

KKSJ55KA160

KDTP55K160

KAFP556B160

KAFP557B160

KAFP552B160

KAFP553B160

KDDFP55B160

KAFP551K160

KAFP55B160

KAFP55H160H

KDJP55B160

BRC1C61

BRC7F633F

BRC1D61

BRC1E62

DCS302CA61

DCS301BA61

DST301BA61

DCS601C51

KRP1C63

KRP4AA53

KRP1H98

KRCS01-4B

FCQ140LUV1

Round flow type: List of optional parts required to achieve different flow patterns

For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option

(shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect.

A circle ( o ) indicates compatibility, and a cross ( x

) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation.

All round flow 4-way flow

Optional accessory parts

Independently installable optional parts

Panel/grille related Panel spacer 1

Operation control related

Auxillary function related

Wireless remote controller

Fresh air intake kit (Chamber type) 1,2

Filter related

Fresh air intake kit (direct mount)

High-humidity operation kit

High-efficiency filter 2

Ultra-long-life filter 2

Panel spacer 1 o o o x o o

Wireless remote controller o

Fresh air intake kit

(Chamber type) 1,2 o o o o o o o x x o o

Fresh air intake kit

(direct mount) o o x o o o

High-humidity operation kit x o x o x x

High-efficiency

filter 2 o o o o x x

Ultra-long-life filter 2 o o o o x x

3-way flow 2-way flow

Optional accessory parts

Independently installable optional parts

Panel/grille related Panel spacer 1

Operation control related

Auxillary function related

Wireless remote controller

Fresh air intake kit (Chamber type) 1,2

Filter related

Fresh air intake kit (direct mount)

High-humidity operation kit

Ultra-long-life filter 2

Panel spacer 1

o

o

o x

o

3

3

3

3

Wireless remote controller

o

3

Fresh air intake kit

(Chamber type)

1,2

o

3 o o o o o x x o

Fresh air intake kit

(direct mount)

o

3 o x o o

High-humidity operation kit x o x o x

High-efficiency

filter

2 x x x x x x

Ultra-long-life filter

2

o

3 o o o x

Branch duct connection

Optional accessory parts

Independently installable optional parts

Branch duct 1

(Chamber type)

(Round duct type)

1-way branch / unit 3-way flow

2-way branch / unit 2-way flow

1-way branch / unit 2-way flow

Panel spacer 1 o x x

Wireless remote controller o o o

Fresh air intake kit

(Chamber type) 1,2

o

o

o

Fresh air intake kit

(direct mount) o

4 o

4 o

4

High-humidity operation kit x x x

High-efficiency

filter 2 x x x

Ultra-long-life filter 2 o o o

1

In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check whether or not joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable.

2

Use a chamber connection kit if two different types of optional chamber are used together. In this case, the fresh air intake kit must be installed in the upper position.

3

It is not possible to use panel spacers in a 2-way flow installation.

4

It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed.

22

OPTIONS

Indoor unit

CEILING SUSPENDED TYPE

Name of option Remark

Replacement long-life filter

Drain-up kit

L-type piping kit (for upward direction)

Remote controller

Resin net

Wired type 1

Wireless type

Wired LCD remote controller with weekly schedule timer 1

Navigation Remote Controller Wired type 1

Central remote controller 2

Unified ON/OFF controller 2

Schedule timer 2

Touch Controller 2

Adaptor for wiring

Wiring adaptor for electrical appendices 3

Interface adaptor for SkyAir series

Installation box for adaptor PCB

Remote sensor (for indoor temperature)

Electrical box with earth terminal (3 blocks)

Electrical box with earth terminal (2 blocks)

Note: 1

Wiring for wired remote controller to be procured locally.

2 This optional accessory requires DTA112BA51.

3 Installation box for adaptor PCB (KRP1CA93) is necessary.

Cooling only

FHQ71BVV1B

KAF501DA80

WALL MOUNTED TYPE

Name of option Remark

FAQ71BVV1B

Drain-up kit

Remote controller Wired type 1

Wireless type

Wired LCD remote controller with weekly schedule timer 1

Navigation Remote Controller

Remote sensor (for Indoor temperature)

Wired type 1

Central remote controller 2

Unified ON/OFF controller 2

Schedule timer 2

Touch Controller 2

Wiring adaptor for electrical appendices 3

Installation box for adaptor PCB

Cooling only

Electrical box with earth terminal (3 blocks)

Electrical box with earth terminal (2 blocks)

Noise filter ( For electromagnetic interface use only)

Note: 1 Wiring for wired remote controller to be procured locally.

2 The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.

3 Installation box for adaptor PCB (KRP4AA93) is necessary.

BRC7EA619

KRCS01-1B

Kit name

FHQ100BVV1B

KAF501DA112

KDU50N125VE

KHFP5MA160

BRC1C61

BRC7EA66

BRC1D61

BRC1E62

DCS302CA61

DCS301BA61

DST301BA61

DCS601C51

KRP1BA54

KRP4AA52

DTA112BA51

KRP1CA93

KRCS01-1B

KJB311AA

KJB212AA

Kit name

K-KDU572EVE

BRC1C61

BRC1D61

BRC1E62

DCS302CA61

DCS301BA61

DST301BA61

DCS601C51

KRP4AA51

KRP4AA93

KJB311AA

KJB212AA

KEK26-1A

FHQ125BVV1B

KAF501DA160

FAQ100CVEA

BRC7EB519

KRCS01-4B

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

Name of option

High-efficiency filter 1

Remark

(Colorimetric method 65%)

(Colorimetric method 90%)

FBQ71DV1

KAF372AA80

KAF373AA80

KDDF37AA80

FBQ100DV1

Kit name

FBQ125DV1

KAF372AA160

KAF373AA160

KDDF37AA160 Filter chamber

Replacement long-life filter

Replacement long-life filter chamber kit

Service panel

Air discharge adaptor

Remote controller Wired type 2

Wireless type

Wired LCD remote controller with weekly schedule timer 2

Navigation Remote Controller Wired type 2

Adaptor for wiring (interlock for fresh air intake fan)

Wiring adaptor for electrical appendices

Cooling only

KAF371AA80

KAF375AA80

KTB25KA80W

KTBJ25K80F

KTBJ25K80T

KDAJ25K71A

BRC1C61

BRC4C64

BRC1D61

BRC1E62

KRP1C64

KAF371AA160

KAF375AA160

KTB25KA160W

KTBJ25K160F

KTBJ25K160T

KDAJ25K140A

KRP4AA51

KRCS01-4B Remote sensor

Mounting plate for adaptor PCB.

3

Central remote controller 4

Unified ON/OFF controller 4

Schedule timer 4 DST301BA61

DCS601C51 Touch Controller 4

Note:

1

2

If installing a high efficiency filter on the unit, an assembly chamber for either bottom or rear suction is required.

Wiring for wired remote controller to be procured locally.

3 Mounting plate for adaptor PCB is necessary for each adaptor marked .

4 The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.

5

Up to 2 adaptors can be fixed for each mounting plate.

6

Only one mounting plate can be installed for each indoor unit.

KRP4A96 5,6

DCS302CA61

DCS301BA61

FBQ140DV1

23

Outdoor unit

Name of option

Central drain plug

RR71MV1/Y1

Kit name

RR100MY1

KKPJ5F180

RR125MY1 RR140MY1

DIMENSIONS

(Unit: mm)

CEILING MOUNTED CASSETTE TYPE

[FCQ71-140LUV1]

9

B

300 or less

860~910(Ceiling opening space) (Note 4)

710(Hanging bolt pitch)

420

55

[FCQ71-140LUV1]

950

81

[FCQ71LUV1]

2x100=200

124

C/L

85

Connection position of branch duct

(round shape type)

16-M4 Hole

8

Piping Connection

Side

Note 2

C

157

350

B arrow view

Connection position of branch duct

(square-shaped type)

6

420

[FCQ71LUV1]

840

340

80 2x100=200 80

124

16-M4 Prepared hole

55

Connection position of branch duct

(square-shaped type)

Drain Connection

Side

A arrow view

7

[FCQ71LUV1]

3

55

64

50

81

840

2x100=200

124

85

55

27-M4 Prepared hole

5

Connection position of branch duct

(square-shaped type)

20-M4

Prepared hole

[FCQ71LUV1]

160

124

109

95

C/L

Hanging bolt

4-M8~M10

Connection position of branch duct

(round shape type)

20

350

C/L

157

280

330

4 1 2

35 or less

(Note 4)

Connection position of branch duct

(round shape type)

256

157

350

A

35 or less

(Note 4)

Connection position of branch duct

(square-shaped type)

[FCQ100-140LUV1]

81 2x100=200 85

160

C/L

Connection position of branch duct

(round shape type)

16-M4 Hole

157

350

B arrow view

Connection position of branch duct

(square-shaped type)

20-M4

Connection position of branch duct

(square-shaped type)

[FCQ100-140LUV1]

160

167

93 67

95

29

Prepared hole

C/L

Connection position of branch duct

(round shape type)

Connection position of fresh air intake kit

(direct installation type)

90

183

C arrow view

ø100

(knock

hole)

Connection position of branch duct

(round shape type)

Connection position of fresh air intake kit

(direct installation type)

ø100

(knock

hole)

90

196

C arrow view

55

Hanging bolt

4-M8~M10

Connection position of branch duct

(round shape type)

[FCQ100-140LUV1]

340

80

840

2x100=200

160

20

350

C/L

157

80

280

330

16-M4 Prepared hole

55

Connection position of branch duct

(square-shaped type)

4 1 2

35 or less

(Note 4)

Connection position of branch duct

3

(round shape type)

55

[FCQ100-140LUV1]

64

50

81 2x100=200

160

256

840

157

350

A

85

55

27-M4 Prepared hole of branch duct

5

35 or less

(Note 4)

Connection position

(square-shaped type)

Notes:

1

Sticking location for manufacture's label

manufacture's label for indoor unit:

Suction grille inner side's electric components box's lid surface

manufacture's label for decoration panel :

Decoration panel's corner decoration cover inner surface

2 In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.

3 When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

4

Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less between the indoor unit and the ceiling opening so that

the panel overlap allowance can be ensured.

5

Please do not place the thing been damp and troubled under an indoor unit.

When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.

Required space

200mm or more

1500mm or more

1500mm

or more

1500mm

or more

200mm or more 1500mm or more

The necessary space is 500mm or more when the air-outlet is blocked with the accessory.

Moreover when the corner areas are blocked

(both right and left of the blocked air outlet), the necessary space is 200mm or more.

1

2

3

4

5

Liquid piping connection

Gas piping connection

Drain piping connection

Transmission wiring connection

8

9

6

7

Remote controller wiring connection

Air-outlet

Suction grille

Corner decoration cover

Drain hose (accessory)

24

DIMENSIONS

(Unit: mm)

CEILING SUSPENDED TYPE

FHQ71BVV1B

FHQ100BVV1B

FHQ125BVV1B

A

1120

1360

1550

B

1160

1400

1590

18 17 16

170

142

105

90

58

12 9

145 60

127

40 50

60 65

Position slit hole for taking out in piping back

(View from the front)

10

8

105

15

A

(Hanging position)

680

Hanging bolt

4-M8~M10

1

5 11 80

Position : Hole of wall for taking out in piping back

(View from the front)

13

55

6

Obstacle

Floor side

30 or more

(Service space)

Drain piping connection VP20

(For left piping)

B

The Front

80

3 2

Notes:

1

Location of unit's Name Plate: Bottom of fan housing inside the suction grille.

2

In case of using wireless remote controller, this position will be a signal receiver.

Refer to the drawing of wireless remote controller in detail.

3

(Applies to FHQ35-71BV only)

The remote control code is the standard <about 3 m outside the machine> attached.

(0.5 mm 2 2 wicks O.D. 5.4)

(It is not attached to VRV.)

7 5

80

105

170

30 or more

(Service space)

Brand name plate

(Note.2)

6

4

4 o/ 45

55 14

1

2

3

4

5

Air discharge grille

Air suction grille

Air filter

Gas piping connection

6

7

Liquid piping connection

Drain piping connection

Earth terminal (inside the electric components box) (M4) (Applies to FHQ35-71BV)

Earth terminal (inside the control box) (M4)

(Applies to FHQ100P/125P)

8

9

10

11

12

13

Suspension bracket

Backward piping and wiring connection opening lid

Upward piping and wiring connection opening lid

Right side piping connection

14

15

16

17

Left back drain piping connection

Left side drain piping connection

Right side drain piping connection

Hole of wall for taking out in piping back

Upward drain piping connection

Upward gas piping connection

18 Upward liquid piping connection

WALL MOUNTED TYPE

[FAQ71BVV1B]

Piping direction

Approx.400

232

230

7

25

Dimensions for full open front panel

9 2 1

50 or more

(Required space)

Piping direction

104

Outside line

1

Notes:

Location of unit's of name Plate:

Right side surface of casing

2

In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.

80 hole

60

6

5

4

Mounting location

3

Name plate Note)2

1050

894

Piping direction

52

50 or more

(Required space)

2500

For in or more installation high spaces

120 or less

Approx.345

Approx.390

Approx.475

98

80 hole

Piping

Wiring and intake

4

5

1

2

Front panel

3

Front grille

Air outlet

6

7

8

9

Gas piping

Liquid piping

Drain hose

Earth terminal

Right side piping connection hole

Left side piping connection hole

8

WALL MOUNTED TYPE

[FAQ100CVEA]

Piping direction

242

Approx.440

240

7

9

Dimensions for full open front panel

2

1

50 or more

(Requred space)

Piping direction

79.5

Outside line

φ80 hole

1200

3

Name plate Note)2 Piping direction

50 or more

(Requred space)

2500 or more

For installation in high spaces

1085 35.5

φ80 hole

Piping and

Wiring intake

120 or less

8

65

6

Approx.400

89

Mounting location

5

4

Approx.460

Approx.465

Notes:

1

Location of unit's of Name Plate:Right side surface of casing

2 In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote contorller in detail.

3

Please do not place the thing been damp and troubled under an indoor unit. when the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

[FBQ71DV1]

30- 4.7 Hole

(All around)

8

27 631

(Hanging bolt pitch)

10

30- 4.7 Hole

(All around)

CASE 1)

Control box

Air outlet Air inlet

9

Inspection hatch 450 or more

167

700 or more

(Service space)

2

6

Air outlet

3

1 5

Air inlet

(Note.2)

1

2

3

4

5

6

Front panel

Front grill

Air outlet

Gas piping

7

8

Liquid piping

Drain hose

Earth terminal

Right side piping connection hole

9 Left side piping connection hole

Inspection hatch 1

(450mmX450mm)

Control box

300 or less

12

435

16-8X12 oblong hole

(All around)

Inspection hatch Ceiling

Air outlet

Unit base

Fig.A

Air inlet

5X150=750

760

785

View

(From the Air outlet)

513

18-8X12 oblong hole

(All around)

49

CASE 2),3)

Control box

Inspection hatch 1

(450mmX450mm)

Control box

Inspection hatch 3

(SAME AS THE INDOOR

UNIT SIZE +300 OR MORE)

Control box

B

Inspection hatch Ceiling

Inspection hatch 2

(SAME AS THE INDOOR

UNIT SIZE OR MORE)

700 or more

View B-1

700 or more

View B-2

169

290

11

28

7 4 6X150=900

700

925

950

Ceiling

Notes:

1

Location of MANUFACTURE'S LABEL: Contro box surface

Floor surface

(From the Air inlet)

2 Mount the air filter at the suction side. (Select its colorimethod (gravity method) 50% or more.)

3 Do not locate things should not be wet under the indoor unit. Dews may drop when humidity reaches over 80%,or a drain gets stuck,or air filters are not clean.

4

Space for Service Works

According to any one of below 1)~3),secure a space for service works,such as,checking and maintenance of control box,etc.

1)One inspection hatch (450X450) on the control box side and a space of 300mm or more under the unit.(Fig.A)

2)One inspection hatch (450X450) on the control box side and 2 (two) inspection hatches under the unit.(Arrow View B-1)

3)3 (three) inspection hatches under the unit and the control box.(Arrow View B-2)

1

2

3

4

Liquid piping connection

Gas piping connection

Drain piping connection

Earth terminal

(Terminal in Control box)

5

6

7

Control box(Inside)

Remote control wiring connection

Power supply wiring and a

8

9

10 transmission wiring

Air discharge flange

Air suction flange

Hanger

11 Socket (for maintenance)

12 Drain hose(Accessory)

26

DIMENSIONS

(Unit: mm)

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

[FBQ100DV1, 125DV1, 140DV1]

40- 4.7 Hole

(All around)

27 631

(Hanging bolt pitch)

8

10

48- 4.7 Hole

(All around)

CASE 1)

Control box

Inspection hatch 1

(450mmX450mm)

Control box

Air outlet

Inspection hatch 450 or more

700 or more

(Service space)

Air outlet

167

3

1 2

6

5

Air inlet

9

Air inlet

(Note.2)

169

290

11

28

7 4 8X150=1200

700

1325

1350

Ceiling

Floor surface

Notes:

1

2

Location of MANUFACTURE'S LABEL: Control box surface

Mount the air filter at the suction side.(Select its colorimethod (gravity method) 50% or more.

(From the Air inlet)

3 Do not locate things should not be wet under the indoor unit.Dews may drop when humidity reaches over 80%,or a drain gets stuck,or air filters are not clean.

4 Space for Service Works

According to any one of below 1)~3),secure a space for service works,such as,checking and maintenance of control box,etc.

1)One inspection hatch (450X450) on the control box side and a space of 300mm or more under the unit.(Fig.A)

2)One inspection hatch (450X450) on the control box side and 2 (two) inspection hatches under the unit.(Arrow View B-1)

3)3 (three) inspection hatches under the unit and the control box.(Arrow View B-2)

Inspection hatch

Ceiling

Air outlet

Unit base

Fig.A

Air inlet

300 or less

12

635

(SAME AS THE INDOOR

UNIT SIZE OR MORE)

20-8X12 oblong hole

(All around)

7X150=1050

1160

1185

View

(From the Air outlet)

713

49

20-8X12 oblong hole

(All around)

CASE 2),3)

Control box

Inspection hatch 1

(450mmX450mm)

Control box

Inspection hatch 3

(SAME AS THE

INDOOR UNIT

SIZE +300 OR

MORE)

Control box

Inspection hatch

B

Ceiling

Inspection hatch 2

(SAME AS THE

INDOOR UNIT

SIZE OR MORE)

700 or more

View B-1

700 or more

View B-2

5

6

3

4

1

2

Liquid pip ing connection

Gas pip ing connection

Drain pip ing connection

Earth terminal

(Terminal in Control box)

7

Control box(Inside)

Remote control wiring connection

Power supply wiring and a

8

9 transmission wiring

Air discharge flange

Air suction flange

Hanger 10

11

12

Socket(For maintenance)

Drain hose(Accessory)

27

OUTDOOR UNIT // RR71MV1/Y1

Hole for anchor bolt 4-M12

30

140 620

900

89

140

36

3

4

2

1

7

6

5

8

89

142

71

19

16

5

45 376 191

19 80

145

6

7

5

52

13 67

1

2

Gas piping connection

Liquid piping connection

3

4

5

Service port (in the unit)

Earth terminal

Refrigerant piping intake

6

7

8

Power supply wiring intake

Transmission wiring intake

Drain piping connection

OUTDOOR UNIT // RR100MY1

Hole for anchor bolt 4-M12

30

140 620

900

89

140

36

2

1

7

3

4

6

5

5

45 376 191

8

89

142

19

71 16

5

19 80

145

7

6

7

6

5

52

13 67

1

2

Gas piping connection

Liquid piping connection

3

4

5

Service port (in the unit)

Earth terminal

Refrigerant piping intake

6

7

8

Power supply wiring intake

Transmission wiring intake

Drain piping connection

28

DIMENSIONS

(Unit: mm)

OUTDOOR UNIT // RR125MY1

Hole for anchor bolt 4-M12

30

140 620

900

89

140

36

3

4

2

1

7

6

5

5

45

OUTDOOR UNIT // RR140MY1

Hole for anchor bolt 4-M12

376 191

8

89

142

19

71 16

5

19 80

145

7

6

7

6

5

52

13 67

1

2

Gas piping connection

Liquid piping connection

5

6

3

4

Service port (in the unit)

Earth terminal

Refrigerant piping intake

Power supply wiring intake

7

8

Transmission wiring intake

Drain piping connection

30

140 620

(Pitch of foundation bolt holes)

900

140

38

91

1

7

6

5

4

2

3

5

7

6

7

6

5

8

71

89

142

19

16

5

45 376 191

19 80

145

52

13 67

4

5

6

1

2

3

Gas piping connection

Liquid piping connection

Service port

Earth terminal

Refrigerant piping intake

Power supply wiring intake

7

8

Transmission wiring intake

Drain piping connection

29

REMOTE CONTROLLER

Wireless type

• Remote controller dimensions

Transmitting part

CEILING MOUNTED CASSETTE TYPE <Round Flow>

• Receiver installation procedure

Receiver

Refrigerant piping side

CEILING SUSPENDED TYPE

• Receiver installation procedure

The Front Receiver

62 17.5

• Remote controller holder installation procedure

<installation to wall surface>

Liquid crystal remote controller

(wireless)

Remote controller holder

Drain piping side

• Receiver detail Decoration panel

• Receiver

detail

WALL MOUNTED TYPE

• Receiver installation procedure

FAQ71BVV1B

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

• Receiver detail

2-5 x 9 Slot

• Receiver

detail

Receiver

FAQ100CVEA Receiver

70 18

0.5

35

49

(Ceiling opening)

Switch box

(field Supplied parts)

Service space for ceiling installation

Note :

Do not install more than 3 receivers in the vicinity of one another.

With 4 or more units, there is always the possibility of malfunction

• Receiver

detail

Wired type

BRC1D61 / BRC1C61

• Remote controller dimensions

120 17

18

23 28

46

Cord outlet hole

• Installation method

A Exposed body, exposed cord

Staple

Remote controller

B Exposed body, embedded cord

17 Conduit

Remote controller

C Exposed body, embedded code

Remote controller

17

0~5

(Between remote

controller and

control box)

Control box

Specifications of cord

Type

Size

Total length

Shield wire (insulated thickness: 1 mm or more)

0.75~1.25 mm

500 m

2

17

Through hole

( 12- 16)

Note)

1. Remote controller cord and staple are not attached.

They are field supplied parts.

BRC1E62

Upper case Lower case

120

   

Operation lamp

(Green)

19

5 X 7 oblong hole

23

46

28

48.5

Code outlet hole

5 X 15 oblong hole

• Installation method

A Exposed cord

Top left outlet

Top center outlet

Staple

B Embedded cord

19

C Embedded cord

(use switch box)

Condit

19

Left outlet

19

Specifications of cord

48.5

Lower case portion

Note)2

Through hole

( 8- 10)

28

46

Switch box for one switch ex.) KJB111A

(optional accessory)

Switch box for two switch ex.) KJB211A

(optional accessory)

Lower case portion

0~5

(Between remote controller and control box)

Switch box

[field supplied part]

Note)

1. Remote controller cord and staple are not attached. They are field supplied parts.

2.If the hole size is too large or the location is not proper, the hole may come out from the remote controller.

Type

Size

Total length

Vinyl cord with sheath or cable (insulated thickness: 1mm or more)

0.75~1.25 mm 2

500 m

30