Before starting use
Heating performance
The heating performance values (kW) described in catalog are the values obtained by operating at an outdoor temperature of 7 C and indoor temperature of 20 C as set forth in the ISO Standards. As the heating performance decreases as the outdoor temperature drops, if the outdoor temperature is too low and the heating performance is insufficient, use other heating appliances as well.
Indication of sound values
The sound values are the values (A scale) measured in a chamber such as an anechoic chamber following the ISO Standards. In the actual installation state, the value is normally larger than the values given in the catalog due to the effect of surrounding noise and echo. Take this into consideration when installing.
Use in oil atmosphere
Avoid installing this unit in as atmosphere where oil scatters or builds up, such as in a kitchen or machine factory.
If the oil adheres to the heat exchanger, the heat exchanging performance will drop, mist may be generated, and the synthetic resin parts may deform and break.
Use in acidic or alkaline atmosphere
If this unit is used in acidic atmosphere such as hot spring areas having high level of sulfuric gases or in alkaline atmosphere including ammonia or calcium chloride, places where the exhaust of the heat exchanger is sucked in, or at coastal areas where the unit is subject to salt breezes, the outer plate or heat exchanger, etc., will corrode. Please ask a dealer or specialist when you use an air conditioner in places differing from a general atmosphere.
Use in places with high ceilings
If the ceiling is high, install a circulator to improve the heat and air flow distribution when heating.
Refrigerant leakage
The refrigerant (R410A) used for Air conditioner is non-toxic and inflammable in its original state.
However, in consideration of a state where the refrigerant leaks into the room, measures against refrigerant leaks must be taken in small rooms where the tolerable level could be exceeded. Take measures by installing ventilation devices, etc.
Use in snowy areas
Take the following measures when installing the outdoor unit in snowy areas.
·Snow prevention
Install a snow-prevention hood so that the snow does not obstruct the air intake port or enter and freeze in the outdoor unit.
·Snow piling
In areas with heavy snow fall, the piled snow could block the air intake port. In this case, a frame that is 50cm or higher than the estimated snow fall must be installed underneath the outdoor unit.
Automatic defrosting device
If the temperature is low, and the humidity is high, frost will stick to the heat exchanger of the outdoor unit. If use is continued, the heating performance will drop.
The "Automatic defrosting device" will function to remove this frost.
After heating for approx, three to ten minutes, it will stop, and the frost will be removed. After defrosting, hot air will be blown again.
Servicing the air-conditioner
After the air-conditioner is used for several seasons, dirt will build up in the air-conditioner causing the performance to drop. In addition to regular servicing, we recommend the maintenance contract (charged for) by a specialist.
Safety Precautions
Air-conditioner usage target
The air-conditioner described in this catalog is a dedicated cooling/heating device for human use.
Do not use it for special applications such as the storage of foodstuffs, animals or plants, precision devices or valuable art, etc.
This could cause the quality of the items to drop, etc.
Do not use this for cooling vehicles or ships. Water leakage or current leaks could occur.
Before use
Always read the "User,s Manual" thoroughly before starting use.
Installation
Always commission the installation to a dealer or specialist. Improper installation will lead to water leakage, electric shocks and fires.
Make sure that the outdoor unit is stable in installation. Fix the unit to stable base.
Usage place
Do not install in places where combustible gas could leak or where there are sparks.
Installation in a place where combustible gas could be generated, flow or accumulate, or places containing carbon fibers could lead to fires.
Our factories are ISO9001 and ISO14001 certified.
Certified ISO 9001 Certified ISO 14001
BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd.
Air-conditioning & Refrigeration Systems Headquarters
Certificate number : JQA-0709
MITSUBISHI HEAVY INDUSTRIES-
MAHAJAK AIR CONDITIONERS CO., LTD.
Certificate Number : 04100 1998 0813
Mitsubishi Heavy
Industries-Haier (Quingdao)
Air-conditioners Co.,Ltd.
Certificate Number : 5170-1996-AQ-RCG-RvA
Certificate 04104 1998 0813 E5
BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd.
Air-conditioning & Refrigeration Systems Headquarters
Certificate number : JQA-EM0256
MITSUBISHI HEAVY INDUSTRIES-
MAHAJAK AIR CONDITIONERS CO.,LTD.
Certificate Number : 04104 1998 0813 E5
Mitsubishi Heavy
Industries-Haier (Quingdao)
Air-conditioners Co.,Ltd.
Certificate number : 01-1998-083
Japan Head Office:
Mitsubishi Heavy Industries Ltd
16-5 2-Chome Kounan Minato-ku Tokyo
108-8215, Japan www.mhi.co.jp
HB91-10P01E-A-0 February 2010(3B)R
Because of our policy of continuous improvement, we reserve right to make changes in all specifications without notice.
Printed in Japan
High Performance Air-Conditioning
FD
series
Inverter Packaged Air-Conditioners
50/60Hz
10P01E-A-0
Our new advanced technology has realized high efficiency, strong heating and long piping.
This contributes to the environmental protection through energy saving and permits installation of the units (4~6HP) considering a heating operation under temperature conditions down to -20˚C and design flexibility has been improved by extension of piping length to 100m.
NEW
1.5~2.5HP
3HP 4~6HP
Line up
Hyper Inverter
HP
1.5 2 2.5 3 4 5 6 8 10
2
The industry,s highest COP levels are achieved by our latest technologies, such as new high efficient twin rotary compressors and the combination with new Hyper inverter outdoor units.
High efficiency
EER in cooling COP in heating
4.09
3.62
3.71
3.50
3.09
2.81
Micro Hyper
4HP
Micro Hyper Micro
5HP
Hyper
6HP
Micro Hyper
4HP
(comparison of FDT series)
Micro Hyper Micro
5HP
Hyper
6HP
Piping length
50
100m
Long piping
(in case of 4~6HP)
Height difference
(Outdoor higher
than Indoor)
30m
Strong heating
(in case of 4~6HP)
-20 °C
-15 °C
: Heating operation down to -20 °C
: Nominal heating capacity maintained at -15 °C
-20 °C
Heating
+20 °C
-15 °C
Cooling
+43 °C
-30 -20 -10 0 10 20 30 40 50
Max.heating capacity (kW)
Hyper Inverter
FDC100VSX(4HP, 3phase 380V)
FDC125VSX(5HP, 3phase 380V)
FDC140VSX(6HP, 3phase 380V)
Micro Inverter
12.5
16.0
16.5
Leading powerful heating capacity in the industry
Thanks to optimization of refrigeration control with use of electric expansion valve and development of new twin rotary compressors, max heating capacity has been increased.
Hyper Inverter series can reach the set temperature very quickly, keeping nominal heating capacity when outdoor temperature is -15 °C.
It is effective to be used even in cold area.
Temperature of supply air can reach 40 °C in 4 minutes after start up under low temperature operation conditions (at both indoor and outdoor temperature of 2 °C) and can reach 50 °C in 8 minutes after that.
(kW)
18.0
14.5
14.0
8.8
0
Heating capacity (in case of 5HP)
Keeping nominal heating capacity at -15 °C
-15 °C
Hyper Inverter
Micro Inverter nominal heating capacity
14.0kW
2 °C 7 °C model name
FDT100VSX(4HP, 3phase 380V)
FDT125VSX(5HP, 3phase 380V)
FDT140VSX(6HP, 3phase 380V) nominal heating capacity
(kW at outdoor temperature of 7 °C)
11.2kW
14.0kW
16.0kW
heating capacity at outdoor temperature of -15 °C
11.2kW
14.0kW
16.0kW
Please refer to our technical manual for installation conditions, operation range and heating/cooling capacities.
Heating capacity
50 °C
40 °C
30 °C
20 °C
10 °C
0 °C
Hyper Inverter
Micro Inverter
4minutes 8minutes
3
Our new advanced technology has realized high efficiency, strong heating and long piping.
This contributes to the environmental protection through energy saving and permits installation of the units (4~6HP) considering a heating operation under temperature conditions down to -20˚C and design flexibility has been improved by extension of piping length to 100m.
NEW
1.5~2.5HP
3HP 4~6HP
Line up
Hyper Inverter
HP
1.5 2 2.5 3 4 5 6 8 10
2
The industry,s highest COP levels are achieved by our latest technologies, such as new high efficient twin rotary compressors and the combination with new Hyper inverter outdoor units.
High efficiency
EER in cooling COP in heating
4.09
3.62
3.71
3.50
3.09
2.81
Micro Hyper
4HP
Micro Hyper Micro
5HP
Hyper
6HP
Micro Hyper
4HP
(comparison of FDT series)
Micro Hyper Micro
5HP
Hyper
6HP
Piping length
50
100m
Long piping
(in case of 4~6HP)
Height difference
(Outdoor higher
than Indoor)
30m
Strong heating
(in case of 4~6HP)
-20 °C
-15 °C
: Heating operation down to -20 °C
: Nominal heating capacity maintained at -15 °C
-20 °C
Heating
+20 °C
-15 °C
Cooling
+43 °C
-30 -20 -10 0 10 20 30 40 50
Max.heating capacity (kW)
Hyper Inverter
FDC100VSX(4HP, 3phase 380V)
FDC125VSX(5HP, 3phase 380V)
FDC140VSX(6HP, 3phase 380V)
Micro Inverter
12.5
16.0
16.5
Leading powerful heating capacity in the industry
Thanks to optimization of refrigeration control with use of electric expansion valve and development of new twin rotary compressors, max heating capacity has been increased.
Hyper Inverter series can reach the set temperature very quickly, keeping nominal heating capacity when outdoor temperature is -15 °C.
It is effective to be used even in cold area.
Temperature of supply air can reach 40 °C in 4 minutes after start up under low temperature operation conditions (at both indoor and outdoor temperature of 2 °C) and can reach 50 °C in 8 minutes after that.
(kW)
18.0
14.5
14.0
8.8
0
Heating capacity (in case of 5HP)
Keeping nominal heating capacity at -15 °C
-15 °C
Hyper Inverter
Micro Inverter nominal heating capacity
14.0kW
2 °C 7 °C model name
FDT100VSX(4HP, 3phase 380V)
FDT125VSX(5HP, 3phase 380V)
FDT140VSX(6HP, 3phase 380V) nominal heating capacity
(kW at outdoor temperature of 7 °C)
11.2kW
14.0kW
16.0kW
heating capacity at outdoor temperature of -15 °C
11.2kW
14.0kW
16.0kW
Please refer to our technical manual for installation conditions, operation range and heating/cooling capacities.
Heating capacity
50 °C
40 °C
30 °C
20 °C
10 °C
0 °C
Hyper Inverter
Micro Inverter
4minutes 8minutes
3
Compact Design of outdoor units
Line up
Micro Inverter
HP
1.5 2 2.5 3 4 5 6 8 10
Height
390 mm
Height
455 mm
Height
185 mm
4
FDC100VN/VS
(4.0HP)
FDC125VN/VS
(5.0HP)
FDC140VN/VS
(6.0HP)
Easy installation
Size reduction and high efficiency performance on the
DC twin rotary compressors
(Micro Inverter 4-6HP)
Employment of DC twin rotary compressor has enabled to utilize a high-speed range of up to 120 rps at the maximum to secure the required capacity.
Optimum compressor control has been realized by employing the vector control* and the starting current has been improved significantly compared with former models.
Moreover, vibration has been reduced.
Outside diameter of shell
ø185mm
Reduction in height by 22.3%
Reduction in volume by 44.1%
ø133mm
Width
380 mm
4.0
HP
5.0
HP
6.0
HP
8.0
HP
10.0
HP
82
118
125
225
225
74
74
74
122
140
-8
-44
-51
-103
-85
* Comparison with former models
Depth
350 mm
FDC200VS
(8.0HP)
Fits into elevators
Former compressor
New model
DC rotary compressor
* Vector control means a. technique to realize an optimum control by converting the current wave to a smooth sinusoidal waveform
Width
380 mm
Depth
350 mm
FDC250VS
(10.0HP)
4.0
HP
5.0
HP
6.0
HP
8.0
HP
10.0
HP
328
467
467
1643
1643
303
303
303
467
540
8%
35%
35%
72%
67%
* Comparison with former models
Improved efficiency of heat exchanger
Redesigning the fins to a straight shape has reduced the pressure loss of the airflow in the heat exchanger. Surface treatment on the fin has enhanced the frost resistance capacity compared with former models.
Owing to the reduction in the size of heat exchanger, the appropriate number of circuits for each HP has been applied. Employment of a high-speed motor has increased the airflow and enabled to keep the cooling capacity under a condition of higher outdoor air temperatures*.
* Limitation of use is around
43
:
at the maximum.
Former model New model
Controllability
Reliability in the protection of compressor has been improved by optimizing the controls of oil return, electronic expansion valve, etc.
1
2
3
4
5
FDC200VS
(8.0HP)
970mm
370mm
Employment of the scroll inverter compressors
(8/10HP)
A control over wide range of capacity and a high efficiency has been realized by inverter-driven scroll compressors.
In addition, the starting current significantly is improved.
The size has also been reduced by 3.2% in height and 31.8% in volume.
Employment of DC fan motor
Employment of DC fan motor has enabled to realize an excellent efficiency of approx. 60% higher than former models.
Wide range of operation
Our new advanced technology has expanded the heating and cooling operation range.
This permits installation of the units under a low outdoor temperature conditions down to -20 °C In heating operation and
-15 °C in cooling operation.
(FDC 100/125/140)
-20 °C
-30
-15 °C
-20 -10
Heating
0
Cooling
10 20
+20 °C
30 40
+43 °C
50
High technology
POINT
1
DC fan motor uses less energy
POINT
2
Optimization of heat exchanger path.
More efficient heating and cooling
POINT
3
Super heat control with low pressure sensor, works better in tough conditions
POINT
4
High efficiency refrigeration circuit
POINT
5
Newly developed High efficiency DC scroll compressor
Energy labeling “Class A”
MHI models have cleared the class A standard, the highest energy saving level, with their high
COP (coefficient of performance).
A
CLASS
A
D
E
F
G
B
C
Energy
Manufacturer
Outside unit
Inside unit
More efficient
A
Air-conditioner
Less efficient
Annual energy consumption, kWh in cooling mode
(Actual consumption will depend on how the appliance is used and climate)
Cooling output nergy fficiency atio
Full load (the higher the better) kW
Type Cooling only
Cooling + Heating
Air cooled
Water cooled
Heat output
Heating performance
A: higher G: lower
Noise
(dB(A) re 1 pW) kW
Further information is contained in product brochures
Air-conditioner
Energy Label Directive 2002/31/EC
5
Compact Design of outdoor units
Line up
Micro Inverter
HP
1.5 2 2.5 3 4 5 6 8 10
Height
390 mm
Height
455 mm
Height
185 mm
4
FDC100VN/VS
(4.0HP)
FDC125VN/VS
(5.0HP)
FDC140VN/VS
(6.0HP)
Easy installation
Size reduction and high efficiency performance on the
DC twin rotary compressors
(Micro Inverter 4-6HP)
Employment of DC twin rotary compressor has enabled to utilize a high-speed range of up to 120 rps at the maximum to secure the required capacity.
Optimum compressor control has been realized by employing the vector control* and the starting current has been improved significantly compared with former models.
Moreover, vibration has been reduced.
Outside diameter of shell
ø185mm
Reduction in height by 22.3%
Reduction in volume by 44.1%
ø133mm
Width
380 mm
4.0
HP
5.0
HP
6.0
HP
8.0
HP
10.0
HP
82
118
125
225
225
74
74
74
122
140
-8
-44
-51
-103
-85
* Comparison with former models
Depth
350 mm
FDC200VS
(8.0HP)
Fits into elevators
Former compressor
New model
DC rotary compressor
* Vector control means a. technique to realize an optimum control by converting the current wave to a smooth sinusoidal waveform
Width
380 mm
Depth
350 mm
FDC250VS
(10.0HP)
4.0
HP
5.0
HP
6.0
HP
8.0
HP
10.0
HP
328
467
467
1643
1643
303
303
303
467
540
8%
35%
35%
72%
67%
* Comparison with former models
Improved efficiency of heat exchanger
Redesigning the fins to a straight shape has reduced the pressure loss of the airflow in the heat exchanger. Surface treatment on the fin has enhanced the frost resistance capacity compared with former models.
Owing to the reduction in the size of heat exchanger, the appropriate number of circuits for each HP has been applied. Employment of a high-speed motor has increased the airflow and enabled to keep the cooling capacity under a condition of higher outdoor air temperatures*.
* Limitation of use is around
43
:
at the maximum.
Former model New model
Controllability
Reliability in the protection of compressor has been improved by optimizing the controls of oil return, electronic expansion valve, etc.
1
2
3
4
5
FDC200VS
(8.0HP)
970mm
370mm
Employment of the scroll inverter compressors
(8/10HP)
A control over wide range of capacity and a high efficiency has been realized by inverter-driven scroll compressors.
In addition, the starting current significantly is improved.
The size has also been reduced by 3.2% in height and 31.8% in volume.
Employment of DC fan motor
Employment of DC fan motor has enabled to realize an excellent efficiency of approx. 60% higher than former models.
Wide range of operation
Our new advanced technology has expanded the heating and cooling operation range.
This permits installation of the units under a low outdoor temperature conditions down to -20 °C In heating operation and
-15 °C in cooling operation.
(FDC 100/125/140)
-20 °C
-30
-15 °C
-20 -10
Heating
0
Cooling
10 20
+20 °C
30 40
+43 °C
50
High technology
POINT
1
DC fan motor uses less energy
POINT
2
Optimization of heat exchanger path.
More efficient heating and cooling
POINT
3
Super heat control with low pressure sensor, works better in tough conditions
POINT
4
High efficiency refrigeration circuit
POINT
5
Newly developed High efficiency DC scroll compressor
Energy labeling “Class A”
MHI models have cleared the class A standard, the highest energy saving level, with their high
COP (coefficient of performance).
A
CLASS
A
D
E
F
G
B
C
Energy
Manufacturer
Outside unit
Inside unit
More efficient
A
Air-conditioner
Less efficient
Annual energy consumption, kWh in cooling mode
(Actual consumption will depend on how the appliance is used and climate)
Cooling output nergy fficiency atio
Full load (the higher the better) kW
Type Cooling only
Cooling + Heating
Air cooled
Water cooled
Heat output
Heating performance
A: higher G: lower
Noise
(dB(A) re 1 pW) kW
Further information is contained in product brochures
Air-conditioner
Energy Label Directive 2002/31/EC
5
Ceiling Cassette -4way- Indoor units
FDT.FDTC
Individual flap control system
According to room temperature conditions, four directions of air flow can be controlled by individual flap as preferred.
As individual flap control is available even after installation, installation area became wider than before.
Due to optimization of outlet design of air flow with our new advanced technology, sufficient air flow is secured and long reach of air flow is realized.(FDT)
6
Previous
Flap control system
Selection of louver position is possible.
Louvers can be set at different angles.
* RCH-E3 is not applicable to the Individual flap control system and the Flap control system.
Upper position
Movable range
Lower position
The thinnest design
Thanks to new design of heat exchanger changed from 2 parts to 1 part, the height of indoor unit is reduced drastically.
Furthermore applying DC fan motors, the highest energy efficiency level, reduction of weight and significant compact design are realized.
FDT125~140
365mm
298 mm
18% reduction!!
FDT40~71
Shape of heat exchanger
Previous New
270mm
246 mm
9% reduction!!
New
For person who is far from the indoor unit
For both persons who are feeling hot or cold
Can cool both the kitchen and the guests
High efficiency
• Reduction of air flow pressure loss
Expansion of outlet air flow area realizes reduction of pressure loss caused by air flow in the indoor unit. Load of fan motor is decreased and efficiency is increased.
• Increase of heat transfer efficiency
Applying high efficient piping in heat exchanger and optimization of heat exchanger (2parts 1part) increases heat transfer efficiency.
Achieved COP 5.67
based on 50% capacity of FDT100V in heating operation
Air-conditioners are generally selected with the operation under the most severe ambient temperature conditions.
The inverter constantly adjusts compressor output to meet the exact demand of the indoor units.
i.e. In case that selecting the capacity of an inverter air-conditioner based on heating operation at -5 °C, its capacity drops by
50% at 7 °C(ISO-TI measurement condition) and operation period at 50% capacity is normally longer than that at 100% of nominal heating capacity.
Considering annual electrical power consumption of inverter air-conditioners, it is quite important to give the first priority to 50% actual capacity and selecting inverter air-conditioners is the best solution for saving energy and protecting the environment.
Signal output
A dry contact is equipped on an indoor unit to meet a possible need for signal output on the site.
Convenience
XR1
XR2
XR3
XR4
XR5
XR1
~
5 : approx. DC12v
XR5
XR1
XR2
XR3
XR4 common output1 (run) output2 (heat) output3 (comp on) output4 (alarm) in put
Monitoring Function
Equipped with RS232C for connection directly to your PC monitoring and service tasks made simple with our service software (“Mente PC”).
New remote control
Applying nonpolar 2-core in new remote control line for all indoor units, it is very convenient for installation including renewal case.
Previous
-core
New
Consideration on the Environment
Employment of lead-free solder
Adapt to RoHS
In order to comply with RoHS standard, the new inverter series products use lead-free solder. It was considered to be too difficult to use lead-free solder because it requires higher soldering temperatures at assembling, which could jeopardize the reliability of assembly, etc. PbF soldering method developed by us, however, has enabled a higher reliability for lead-free printed circuit boards.
*"RoHS" is the abbreviation of the new European standard, which means
Restriction of Hazardous Substances.
Employment of the new refrigerant
All models of the New inverter series use a new refrigerant R410A characterized by the ozone depletion coefficient being 0.
Energy Conservation
A High Performance and Excellent Energy Conservation are achieved at the same time by an increased capacity of heat exchanger and employment of high efficiency DC motor etc.
7
Ceiling Cassette -4way- Indoor units
FDT.FDTC
Individual flap control system
According to room temperature conditions, four directions of air flow can be controlled by individual flap as preferred.
As individual flap control is available even after installation, installation area became wider than before.
Due to optimization of outlet design of air flow with our new advanced technology, sufficient air flow is secured and long reach of air flow is realized.(FDT)
6
Previous
Flap control system
Selection of louver position is possible.
Louvers can be set at different angles.
* RCH-E3 is not applicable to the Individual flap control system and the Flap control system.
Upper position
Movable range
Lower position
The thinnest design
Thanks to new design of heat exchanger changed from 2 parts to 1 part, the height of indoor unit is reduced drastically.
Furthermore applying DC fan motors, the highest energy efficiency level, reduction of weight and significant compact design are realized.
FDT125~140
365mm
298 mm
18% reduction!!
FDT40~71
Shape of heat exchanger
Previous New
270mm
246 mm
9% reduction!!
New
For person who is far from the indoor unit
For both persons who are feeling hot or cold
Can cool both the kitchen and the guests
High efficiency
• Reduction of air flow pressure loss
Expansion of outlet air flow area realizes reduction of pressure loss caused by air flow in the indoor unit. Load of fan motor is decreased and efficiency is increased.
• Increase of heat transfer efficiency
Applying high efficient piping in heat exchanger and optimization of heat exchanger (2parts 1part) increases heat transfer efficiency.
Achieved COP 5.67
based on 50% capacity of FDT100V in heating operation
Air-conditioners are generally selected with the operation under the most severe ambient temperature conditions.
The inverter constantly adjusts compressor output to meet the exact demand of the indoor units.
i.e. In case that selecting the capacity of an inverter air-conditioner based on heating operation at -5 °C, its capacity drops by
50% at 7 °C(ISO-TI measurement condition) and operation period at 50% capacity is normally longer than that at 100% of nominal heating capacity.
Considering annual electrical power consumption of inverter air-conditioners, it is quite important to give the first priority to 50% actual capacity and selecting inverter air-conditioners is the best solution for saving energy and protecting the environment.
Signal output
A dry contact is equipped on an indoor unit to meet a possible need for signal output on the site.
Convenience
XR1
XR2
XR3
XR4
XR5
XR1
~
5 : approx. DC12v
XR5
XR1
XR2
XR3
XR4 common output1 (run) output2 (heat) output3 (comp on) output4 (alarm) in put
Monitoring Function
Equipped with RS232C for connection directly to your PC monitoring and service tasks made simple with our service software (“Mente PC”).
New remote control
Applying nonpolar 2-core in new remote control line for all indoor units, it is very convenient for installation including renewal case.
Previous
-core
New
Consideration on the Environment
Employment of lead-free solder
Adapt to RoHS
In order to comply with RoHS standard, the new inverter series products use lead-free solder. It was considered to be too difficult to use lead-free solder because it requires higher soldering temperatures at assembling, which could jeopardize the reliability of assembly, etc. PbF soldering method developed by us, however, has enabled a higher reliability for lead-free printed circuit boards.
*"RoHS" is the abbreviation of the new European standard, which means
Restriction of Hazardous Substances.
Employment of the new refrigerant
All models of the New inverter series use a new refrigerant R410A characterized by the ozone depletion coefficient being 0.
Energy Conservation
A High Performance and Excellent Energy Conservation are achieved at the same time by an increased capacity of heat exchanger and employment of high efficiency DC motor etc.
7
8
SINGLE [OUTDOOR UNIT : INDOOR UNIT = 1 : 1]
HP kW
Btu/h kcal/h
Indoor unit
1.5
4.0
13,700
3,440
FDT40VD
Outdoor unit
Set
1phase
3phase
1phase
3phase
Indoor unit
SRC40ZIX-S
FDTC40VD
Outdoor unit
Set
1phase
1phase
Indoor unit
SRC40ZIX-S
Outdoor unit
Set
1phase
3phase
1phase
3phase
Indoor unit
Outdoor unit
Set
1phase
3phase
1phase
3phase
Indoor unit
FDEN40VD
Outdoor unit
Set
1phase
3phase
1phase
3phase
SRC40ZIX-S
2.0
5.0
17,100
4,300
FDT50VD
FDEN50VD
2.5
6.0
19,100
4,816
FDT60VD
SRC50ZIX-S SRC60ZIX-S
FDTC50VD FDTC60VD
SRC50ZIX-S SRC60ZIX-S
FDUM50VD FDUM60VD
SRC50ZIX-S SRC60ZIX-S
FDEN60VD
SRC50ZIX-S SRC60ZIX-S
3.0
7.1
23,900
6,020
FDT71VD
FDC71VNX
FDU71VD
*
FDC71VNX
FDUM71VD
FDC71VNX
FDEN71VD
FDC71VNX
4.0
10.0
34,100
8,600
FDT100VD
FDC100VNX
FDC100VSX
FDU100VD
FDC100VNX
FDC100VSX
FDUM100VD
FDC100VNX
FDC100VSX
FDEN100VD
FDC100VNX
FDC100VSX
5.0
12.5
42,700
10,750
6.0
14.0
47,800
12,040
4.0
10.0
34,100
8,600
5.0
12.5
42,700
10,750
Micro Inverter
6.0
14.0
47,800
12,040
8.0
20.0
68,300
17,200
FDT125VD
NEW
FDC125VNX
FDC125VSX
FDT140VD
FDC140VNX
FDC140VSX
FDT100VD
FDC100VN
FDC100VS
FDT125VD FDT140VD
FDC125VN
FDC125VS
FDC140VN
FDC140VS
FDUM125VD
NEW
FDC125VNX
FDC125VSX
FDUM140VD
FDC140VNX
FDC140VSX
FDUM100VD FDUM125VD FDUM140VD
FDC100VN
FDC100VS
FDC125VN
FDC125VS
FDC140VN
FDC140VS
FDEN125VD
NEW
FDC125VNX
FDC125VSX
FDEN140VD
FDC140VNX
FDC140VSX
FDEN100VD FDEN125VD
FDC100VN
FDC100VS
FDC125VN
FDC125VS
FDEN140VD
FDC140VN
FDC140VS
10.0
25.0
85,400
21,500
FDU125VD
NEW
FDC125VNX
FDC125VSX
FDU140VD
FDC140VNX
FDC140VSX
FDU100VD
FDC100VN
FDC100VS
FDU125VD FDU140VD
FDC125VN
FDC125VS
FDC140VN
FDC140VS
FDU200VD
FDC200VS
FDU250VD
FDC250VS
* Not available in 60Hz
9
8
SINGLE [OUTDOOR UNIT : INDOOR UNIT = 1 : 1]
HP kW
Btu/h kcal/h
Indoor unit
1.5
4.0
13,700
3,440
FDT40VD
Outdoor unit
Set
1phase
3phase
1phase
3phase
Indoor unit
SRC40ZIX-S
FDTC40VD
Outdoor unit
Set
1phase
1phase
Indoor unit
SRC40ZIX-S
Outdoor unit
Set
1phase
3phase
1phase
3phase
Indoor unit
Outdoor unit
Set
1phase
3phase
1phase
3phase
Indoor unit
FDEN40VD
Outdoor unit
Set
1phase
3phase
1phase
3phase
SRC40ZIX-S
2.0
5.0
17,100
4,300
FDT50VD
FDEN50VD
2.5
6.0
19,100
4,816
FDT60VD
SRC50ZIX-S SRC60ZIX-S
FDTC50VD FDTC60VD
SRC50ZIX-S SRC60ZIX-S
FDUM50VD FDUM60VD
SRC50ZIX-S SRC60ZIX-S
FDEN60VD
SRC50ZIX-S SRC60ZIX-S
3.0
7.1
23,900
6,020
FDT71VD
FDC71VNX
FDU71VD
*
FDC71VNX
FDC71VNX
FDEN71VD
FDC71VNX
4.0
10.0
34,100
8,600
FDT100VD
FDC100VNX
FDC100VSX
FDU100VD
FDC100VNX
FDC100VSX
FDUM71VD FDUM100VD
FDC100VNX
FDC100VSX
FDEN100VD
FDC100VNX
FDC100VSX
5.0
12.5
42,700
10,750
6.0
14.0
47,800
12,040
4.0
10.0
34,100
8,600
5.0
12.5
42,700
10,750
Micro Inverter
6.0
14.0
47,800
12,040
8.0
20.0
68,300
17,200
FDT125VD
NEW
FDC125VNX
FDC125VSX
FDT140VD
FDC140VNX
FDC140VSX
FDT100VD
FDC100VN
FDC100VS
FDT125VD FDT140VD
FDC125VN
FDC125VS
FDC140VN
FDC140VS
FDUM125VD
NEW
FDC125VNX
FDC125VSX
FDUM140VD
FDC140VNX
FDC140VSX
FDUM100VD FDUM125VD FDUM140VD
FDC100VN
FDC100VS
FDC125VN
FDC125VS
FDC140VN
FDC140VS
FDEN125VD
NEW
FDC125VNX
FDC125VSX
FDEN140VD
FDC140VNX
FDC140VSX
FDEN100VD FDEN125VD
FDC100VN
FDC100VS
FDC125VN
FDC125VS
FDEN140VD
FDC140VN
FDC140VS
10.0
25.0
85,400
21,500
FDU125VD
NEW
FDC125VNX
FDC125VSX
FDU140VD
FDC140VNX
FDC140VSX
FDU100VD
FDC100VN
FDC100VS
FDU125VD FDU140VD
FDC125VN
FDC125VS
FDC140VN
FDC140VS
FDU200VD
FDC200VS
FDU250VD
FDC250VS
* Not available in 60Hz
9
10
[ INDOOR UNIT ]
CEILING CASSETTE -4way-
FDT
A
CLASS
Wired remote control Wireless remote control
FDT 40/50/60/71/
100/125/140VD
Point
1
Arrangement of installation balance of indoor unit
Checking from access ports with detachable covers at each corner, arrangement of installation balance of indoor unit can be available without removing a panel. Workability is improved and time of installation is reduced.
Point
3
Easy checking of drain pan
Easy checking of drain pan condition is available by removing corner lid only.
Due to new design changing fan motor is available without removing a panel. Temporally setting of drain pan is also available.
Outline drawing (Unit:mm)
Model FDT40,50,60,71VD Model 100,125,140VD
RC-E4
(Option)
RCH-E3
(Option)
RCN-T-36W-E
(Option)
Point
2
Installation Workability
For wireless control simply insert the infrared receiver kit on a corner of the panel wireless remote control
RCN-T-36W-E
Point
4
700mm Drain Pump
Drain can be discharged upwards by 700mm from the ceiling surface. It allows a piping layout with a high degree of freedom
Depending on the installation location and 260mm flexible hose as a standard equipment supports easy workability.
Flexible hose less than
700mm
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor
Outdoor
Height x Width x Depth
Unit+Panel
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size Liquid/Gas
Range of usage
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDT40ZIXVD
FDT40VD
SRC40ZIX-S
FDT50ZIXVD
FDT50VD
SRC50ZIX-S
FDT60ZIXVD
FDT60VD
SRC60ZIX-S
FDT71VNXVD
FDT71VD
FDC71VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDT100VNXVD
FDT100VD
FDC100VNX
4.0
(1.8~4.7)
4.5
(2.0~5.4)
5.0
(2.2~5.6)
5.4
(2.5~6.3)
5.6
(2.8~6.3)
6.7
(3.1~7.1)
7.1
(3.2~8.0)
8.0
(3.6~9.0)
10.0
(4.0~11.2)
11.2
(4.0~12.5)
0.93/1.15
4.30/3.91
A/A
5(12)
1.29/1.29
3.88/4.19
A/A
Hi:33 Me:31 Lo:30
5(14)
1.57/1.85
3.57/3.62
A/A
1.90/2.07
3.74/3.86
A/A
5(17)
Hi:35 Me:33 Lo:31
47
Hi:18 Me:16 Lo:14
40
48
Hi:18 Me:16 Lo:14
Cooling:51 Heating:48
Hi:21 Me:19 Lo:17
Cooling:60 Heating:50
Unit:246x840x840 Panel:35x950x950
27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5)
T-PSA-3AW-E
2.50/2.58
4.00/4.34
A/A
5(24)
Hi:40 Me:37 Lo:35
Cooling:48 Heating:50
Hi:27 Me:24 Lo:20
100
Unit:298x840x840 Panel:35x950x950
32.5(Unit:27 Panel:5.5)
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
640x800(+71)x290
43
Scroll
1.4(15)
6.35/12.7
30
20
20
750x880(+88)x340
60
2.95(30)
50
30
15
Rotary
9.52/15.88
1,300x970x370
105
4.5(30)
100
30
15
-15~43 * 2
-15~20 -20~20
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
FDT125VNXVD
FDT125VD
FDC125VNX
FDT140VNXVD
FDT140VD
FDC140VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDT100VSXVD
FDT100VD
FDC100VSX
FDT125VSXVD
FDT125VD
FDC125VSX
FDT140VSXVD
FDT140VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
Air flow
1
Exterior dimensions
Net weight
Panel
Air filter, Q'ty
Indoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
Unit+Panel
Range of usage
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
12.5
(5.0~14.0)
14.0
(5.0~16.0)
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(4.0~17.0)
16.0
(4.0~18.0)
11.2
(4.0~16.0)
14.0
(4.0~18.0)
16.0
(4.0~20.0)
3.28/3.43
3.81/4.08
A/A
5(26)
4.19/4.20
3.34/3.81
A/A
2.50/2.58
4.00/4.34
A/A
3.28/3.43
3.81/4.08
A/A
5(15)
Hi:42 Me:40 Lo:37 Hi:42 Me:40 Lo:37
Cooling:48 Heating:50
Hi:43 Me:41 Lo:38
Cooling:49 Heating:52
Hi:30 Me:27 Lo:23
Hi:40 Me:37 Lo:35
Cooling:48 Heating:50
Hi:27 Me:24 Lo:20
100
Unit:298x840x840 Panel:35x950x950
4.19/4.20
3.34/3.81
A/A
Hi:43 Me:41 Lo:38
Cooling:49 Heating:52
Hi:30 Me:27 Lo:23
32.5(Unit:27 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43 * 2
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 40/50ZIXVD 39dB, 60ZIXVD 46dB, 71VNXVD 46dB, 100/125/140VNXVD 51dB, 100/125/140VSXVD 51dB
Air flow: 40/50ZIXVD 20CMM, 60ZIXVD 28CMM, 71VNXVD 28CMM, 100/125/140VNXVD 37CMM, 100/125/140VSXVD 37CMM
11
10
[ INDOOR UNIT ]
CEILING CASSETTE -4way-
FDT
Wired remote control
A
CLASS
Wireless remote control
FDT 40/50/60/71/
100/125/140VD
Point
1
Arrangement of installation balance of indoor unit
Checking from access ports with detachable covers at each corner, arrangement of installation balance of indoor unit can be available without removing a panel. Workability is improved and time of installation is reduced.
Point
3
Easy checking of drain pan
Easy checking of drain pan condition is available by removing corner lid only.
Due to new design changing fan motor is available without removing a panel. Temporally setting of drain pan is also available.
Outline drawing (Unit:mm)
Model FDT40,50,60,71VD Model 100,125,140VD
RC-E4
(Option)
RCH-E3
(Option)
RCN-T-36W-E
(Option)
Point
2
Installation Workability
For wireless control simply insert the infrared receiver kit on a corner of the panel wireless remote control
RCN-T-36W-E
Point
4
700mm Drain Pump
Drain can be discharged upwards by 700mm from the ceiling surface. It allows a piping layout with a high degree of freedom
Depending on the installation location and 260mm flexible hose as a standard equipment supports easy workability.
Flexible hose less than
700mm
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor
Outdoor
Height x Width x Depth
Unit+Panel
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size Liquid/Gas
Range of usage
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDT40ZIXVD
FDT40VD
SRC40ZIX-S
FDT50ZIXVD
FDT50VD
SRC50ZIX-S
FDT60ZIXVD
FDT60VD
SRC60ZIX-S
FDT71VNXVD
FDT71VD
FDC71VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDT100VNXVD
FDT100VD
FDC100VNX
4.0
(1.8~4.7)
4.5
(2.0~5.4)
5.0
(2.2~5.6)
5.4
(2.5~6.3)
5.6
(2.8~6.3)
6.7
(3.1~7.1)
7.1
(3.2~8.0)
8.0
(3.6~9.0)
10.0
(4.0~11.2)
11.2
(4.0~12.5)
0.93/1.15
4.30/3.91
A/A
5(12)
1.29/1.29
3.88/4.19
A/A
Hi:33 Me:31 Lo:30
5(14)
1.57/1.85
3.57/3.62
A/A
1.90/2.07
3.74/3.86
A/A
5(17)
Hi:35 Me:33 Lo:31
47
Hi:18 Me:16 Lo:14
40
48
Hi:18 Me:16 Lo:14
Cooling:51 Heating:48
Hi:21 Me:19 Lo:17
Cooling:60 Heating:50
Unit:246x840x840 Panel:35x950x950
27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5)
T-PSA-3AW-E
2.50/2.58
4.00/4.34
A/A
5(24)
Hi:40 Me:37 Lo:35
Cooling:48 Heating:50
Hi:27 Me:24 Lo:20
100
Unit:298x840x840 Panel:35x950x950
32.5(Unit:27 Panel:5.5)
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
640x800(+71)x290
43
Scroll
1.4(15)
6.35/12.7
30
20
20
750x880(+88)x340
60
2.95(30)
50
30
15
Rotary
9.52/15.88
1,300x970x370
105
4.5(30)
100
30
15
-15~43 * 2
-15~20 -20~20
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
FDT125VNXVD
FDT125VD
FDC125VNX
FDT140VNXVD
FDT140VD
FDC140VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDT100VSXVD
FDT100VD
FDC100VSX
FDT125VSXVD
FDT125VD
FDC125VSX
FDT140VSXVD
FDT140VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
Air flow
1
Exterior dimensions
Net weight
Panel
Air filter, Q'ty
Indoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
Unit+Panel
Range of usage
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
12.5
(5.0~14.0)
14.0
(5.0~16.0)
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(4.0~17.0)
16.0
(4.0~18.0)
11.2
(4.0~16.0)
14.0
(4.0~18.0)
16.0
(4.0~20.0)
3.28/3.43
3.81/4.08
A/A
5(26)
4.19/4.20
3.34/3.81
A/A
2.50/2.58
4.00/4.34
A/A
3.28/3.43
3.81/4.08
A/A
5(15)
Hi:42 Me:40 Lo:37 Hi:42 Me:40 Lo:37
Cooling:48 Heating:50
Hi:43 Me:41 Lo:38
Cooling:49 Heating:52
Hi:30 Me:27 Lo:23
Hi:40 Me:37 Lo:35
Cooling:48 Heating:50
Hi:27 Me:24 Lo:20
100
Unit:298x840x840 Panel:35x950x950
4.19/4.20
3.34/3.81
A/A
Hi:43 Me:41 Lo:38
Cooling:49 Heating:52
Hi:30 Me:27 Lo:23
32.5(Unit:27 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43 * 2
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 40/50ZIXVD 39dB, 60ZIXVD 46dB, 71VNXVD 46dB, 100/125/140VNXVD 51dB, 100/125/140VSXVD 51dB
Air flow: 40/50ZIXVD 20CMM, 60ZIXVD 28CMM, 71VNXVD 28CMM, 100/125/140VNXVD 37CMM, 100/125/140VSXVD 37CMM
11
[ INDOOR UNIT ]
CEILING CASSETTE -4way Compact (600 X 600mm)-
FDTC
A
CLASS
Fits into standard
600 x 600 ceiling
Outline drawing (Unit:mm)
FDTC 40/50/60VD
Wired remote control Wireless remote control
12
Point
1
Quiet operation
(Sound level in the Lo mode)
(dB)
36
35
34
33
32
31
30
29
28
27
26
25
35dB
5dB
Down
Previous
(Cooling/Heating)
30dB
3dB
Down
32dB
New
(Cooling)
New
(Heating)
FDTC40/50/60VD
Point
4
Compact Concept
The industry's lowest level 248mm height.
Panel size (700x700) is suitable for 600x600 ceiling panel. All indoor unit size is (WxD: 570x570). It brings easy installation for 600x600 ceiling panel.
Point
2
RC-E4
(Option)
RCH-E3
(Option)
RCN-TC-24W-ER
(Option)
“CLEARER”Air Flow
New shape & angled louver redirects the air current away from the ceiling, to reduce ceiling stains
Point
3
Installation Workability
For wireless control simply insert the infrared receiver kit on a corner of the panel wireless remote control
RCN-TC-24W-ER
Point
5
Comfortable and Convenient
• All units are 18.5kg, light weight unit.
• 600mm Drain Pump is mounted.
Drain can be discharged upward by 600 mm from the ceiling surface close to the indoor unit.
It allows a piping layout with a high degree of freedom depending on the installation location.
• Thanks to width and depth of exterior dimensions of a indoor unit are 570mm each, the installation work can be conducted smoothly with a beautiful finishing in
2x2 ceiling size.
Flexible hose
600mm
Ultra slim design at just 248mm above the ceiling
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
FDTC40ZIXVD
FDTC40VD
SRC40ZIX-S
FDTC50ZIXVD
FDTC50VD
SRC50ZIX-S
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDTC60ZIXVD
FDTC60VD
SRC60ZIX-S
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor
Outdoor kW kW kW
A dB(A) kg(m)
ø m m m
O/U
O/U
4.0
(1.8~4.7)
4.5
(2.0~5.4)
1.04/1.10
3.85/4.09
A/A
5(12)
5.0
(2.2~5.6)
5.4
(2.5~6.3)
1.56/1.45
3.21/3.72
A/A
5(14)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
47
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
40
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
640x800(+71)x290
43
Scroll
1.4(15)
6.35/12.7
30
20
20
-15~43* 2
-15~20
5.6
(2.8~6.3)
6.7
(3.1~6.7)
1.99/2.08
2.81/3.22
C/C
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
48
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8 Air flow
Indoor
Outdoor
Exterior dimensions
Net weight
Panel
Height x Width x Depth
Unit+Panel
Air filter, Q'ty
Remote control(option)
Height x Width x Depth Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Range of usage
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating
CMM mm kg mm kg
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 40/50/60ZIXVD 47dB Air flow: 40/50/60ZIXVD 13.5CMM
13
[ INDOOR UNIT ]
CEILING CASSETTE -4way Compact (600 X 600mm)-
FDTC
A
CLASS
Fits into standard
600 x 600 ceiling
Outline drawing (Unit:mm)
FDTC 40/50/60VD
Wired remote control Wireless remote control
12
Point
1
Quiet operation
(Sound level in the Lo mode)
(dB)
36
35
34
33
32
31
30
29
28
27
26
25
35dB
5dB
Down
Previous
(Cooling/Heating)
30dB
3dB
Down
32dB
New
(Cooling)
New
(Heating)
FDTC40/50/60VD
Point
4
Compact Concept
The industry's lowest level 248mm height.
Panel size (700x700) is suitable for 600x600 ceiling panel. All indoor unit size is (WxD: 570x570). It brings easy installation for 600x600 ceiling panel.
Point
2
RC-E4
(Option)
RCH-E3
(Option)
RCN-TC-24W-ER
(Option)
“CLEARER”Air Flow
New shape & angled louver redirects the air current away from the ceiling, to reduce ceiling stains
Point
3
Installation Workability
For wireless control simply insert the infrared receiver kit on a corner of the panel wireless remote control
RCN-TC-24W-ER
Point
5
Comfortable and Convenient
• All units are 18.5kg, light weight unit.
• 600mm Drain Pump is mounted.
Drain can be discharged upward by 600 mm from the ceiling surface close to the indoor unit.
It allows a piping layout with a high degree of freedom depending on the installation location.
• Thanks to width and depth of exterior dimensions of a indoor unit are 570mm each, the installation work can be conducted smoothly with a beautiful finishing in
2x2 ceiling size.
Flexible hose
600mm
Ultra slim design at just 248mm above the ceiling
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
FDTC40ZIXVD
FDTC40VD
SRC40ZIX-S
FDTC50ZIXVD
FDTC50VD
SRC50ZIX-S
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDTC60ZIXVD
FDTC60VD
SRC60ZIX-S
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor
Outdoor kW kW kW
A dB(A) kg(m)
ø m m m
O/U
O/U
4.0
(1.8~4.7)
4.5
(2.0~5.4)
1.04/1.10
3.85/4.09
A/A
5(12)
5.0
(2.2~5.6)
5.4
(2.5~6.3)
1.56/1.45
3.21/3.72
A/A
5(14)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
47
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
40
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
640x800(+71)x290
43
Scroll
1.4(15)
6.35/12.7
30
20
20
-15~43* 2
-15~20
5.6
(2.8~6.3)
6.7
(3.1~6.7)
1.99/2.08
2.81/3.22
C/C
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
48
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8 Air flow
Indoor
Outdoor
Exterior dimensions
Net weight
Panel
Height x Width x Depth
Unit+Panel
Air filter, Q'ty
Remote control(option)
Height x Width x Depth Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Range of usage
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating
CMM mm kg mm kg
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 40/50/60ZIXVD 47dB Air flow: 40/50/60ZIXVD 13.5CMM
13
14
[ INDOOR UNIT ]
DUCT CONNECTED -High Static pressure-
FDU
Wired remote control
Wireless remote control
A
CLASS
R410A
Fan control kit
(100~200Pa)
RC-E4
(Option)
RCH-E3
(Option)
FDU 71/100/125/140VD
RCN-KIT3-E
(Option)
Point
1
Enhanced installation workability
Quiet, Lightweight and Compact
With the FDU71, the noise level is only 37dB (low), weight is only 40kg and height is only 297mm.
In addition 600mm Drain Pump is mounted in FDU71/100/125/140VD.
The indoor unit is completely hidden in the ceiling, so this is suitable for spaces with classy interior decoration.
Height
297mm
600mm
FDU 200/250VD U-FCRA
[For 200/250VD]
(option)
Point
2
Adaptability to higher static pressures
High static pressure of 200 Pa (FDU200/250VD) extends the degree of freedom in the designing of air conditioners.
This is a real and earnest model for duct air-conditioning.
A unit external static pressure of up to 200 Pa
(FDU200/250VD) is possible.
Precise air flow designing is possible.
Control box
Slide type fan system
Fan motor
Thin type duct connection opening
High static pressure silent fan
Outline drawing (Unit:mm)
FDU71VD
FDU100,125,140VD
FDU200,250VD
Installation workability
(FDU200,250VD)
Using piping attachment that has flared connection and brazed connection ends, there is no need conduct brazing work inside the outdoor unit.
Flared connection
ø19.05mm
232mm
Brazed connection
ø22.2mm
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1 Indoor
Outdoor
Air flow
Indoor
Outdoor
External static pressure
Exterior dimensions Height x Width x Depth
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Liquid/Gas
Range of usage
Ref.piping size
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
* FDU71VNXVD
FDU71VD
FDC71VNX
7.1
(3.2~8.0)
8.0
(3.6~9.0)
2.15/2.15
3.30/3.72
A/A
5(17)
Hi:41 Lo:37
Cooling:51 Heating:48
Hi:20 Lo:17
Cooling:60 Heating:50
297x850x650
40
750x880(+88)x340
60
2.95(30)
50
* Not available in 60Hz
* FDU100VNXVD
FDU100VD
FDC100VNX
* FDU125VNXVD
FDU125VD
FDC125VNX
1Phase 220-240V 50Hz
* FDU140VNXVD
FDU140VD
FDC140VNX
10.0
(4.0~11.2)
11.2
(4.0~12.5)
12.5
(5.0~14.0)
14.0
(4.0~17.0)
2.78/2.90
3.60/3.86
A/A
5(25)
Hi:42 Lo:37
Cooling:48 Heating:50
3.44/3.67
3.63/3.81
A/A
5(29)
Hi:34 Lo:27
100
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43* 2
-20~20
14.0
(5.0~16.0)
16.0
(4.0~18.0)
4.20/4.30
3.33/3.72
A/A
5(30)
Hi:43 Lo:38
Cooling:49 Heating:52
Hi:42 Lo:33.5
SPECIFICATIONS * Not available in 60Hz
Set model name
Indoor name
Outdoor name
Power source
* FDU100VSXVD
FDU100VD
FDC100VSX
* FDU125VSXVD
FDU125VD
FDC125VSX
* FDU140VSXVD
FDU140VD
FDC140VSX
3Phase 380-415V 50Hz
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1 Indoor
Outdoor
Air flow
Indoor
Outdoor
External static pressure
Exterior dimensions Height x Width x Depth
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Liquid/Gas
Range of usage
Ref.piping size
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
10.0
(4.0~11.2)
11.2
(4.0~16.0)
2.78/2.90
3.60/3.86
A/A
5(16)
Hi:42 Lo:37
Cooling:48 Heating:50
Hi:34 Lo:27
12.5
(5.0~14.0)
14.0
(4.0~18.0)
3.44/3.67
3.63/3.81
A/A
5(18)
Hi:43 Lo:38
Cooling:48 Heating:50
Hi:42 Lo:33.5
100
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43* 2
-20~20
14.0
(5.0~16.0)
16.0
(4.0~20.0)
4.20/4.30
3.33/3.72
A/A
5(19)
Cooling:49 Heating:52
*
*
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure of FDU71/100/125/140 is 60Pa and that of FDU200/250 is 100Pa.
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : External static pressure is changeable to be set by the remote control. Standard external static pressure is factory setting. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa.
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
15
14
[ INDOOR UNIT ]
DUCT CONNECTED -High Static pressure-
FDU
Wired remote control
Wireless remote control
A
CLASS
R410A
Fan control kit
(100~200Pa)
RC-E4
(Option)
RCH-E3
(Option)
FDU 71/100/125/140VD
RCN-KIT3-E
(Option)
Point
1
Enhanced installation workability
Quiet, Lightweight and Compact
With the FDU71, the noise level is only 37dB (low), weight is only 40kg and height is only 297mm.
In addition 600mm Drain Pump is mounted in FDU71/100/125/140VD.
The indoor unit is completely hidden in the ceiling, so this is suitable for spaces with classy interior decoration.
Height
297mm
600mm
FDU 200/250VD U-FCRA
[For 200/250VD]
(option)
Point
2
Adaptability to higher static pressures
High static pressure of 200 Pa (FDU200/250VD) extends the degree of freedom in the designing of air conditioners.
This is a real and earnest model for duct air-conditioning.
A unit external static pressure of up to 200 Pa
(FDU200/250VD) is possible.
Precise air flow designing is possible.
Control box
Slide type fan system
Fan motor
Thin type duct connection opening
High static pressure silent fan
Outline drawing (Unit:mm)
FDU71VD
FDU100,125,140VD
FDU200,250VD
Installation workability
(FDU200,250VD)
Using piping attachment that has flared connection and brazed connection ends, there is no need conduct brazing work inside the outdoor unit.
Flared connection
ø19.05mm
232mm
Brazed connection
ø22.2mm
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1 Indoor
Outdoor
Air flow
Indoor
Outdoor
External static pressure
Exterior dimensions Height x Width x Depth
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Liquid/Gas
Range of usage
Ref.piping size
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
* FDU71VNXVD
FDU71VD
FDC71VNX
7.1
(3.2~8.0)
8.0
(3.6~9.0)
2.15/2.15
3.30/3.72
A/A
5(17)
Hi:41 Lo:37
Cooling:51 Heating:48
Hi:20 Lo:17
Cooling:60 Heating:50
297x850x650
40
750x880(+88)x340
60
2.95(30)
50
* Not available in 60Hz
* FDU100VNXVD
FDU100VD
FDC100VNX
* FDU125VNXVD
FDU125VD
FDC125VNX
1Phase 220-240V 50Hz
* FDU140VNXVD
FDU140VD
FDC140VNX
10.0
(4.0~11.2)
11.2
(4.0~12.5)
12.5
(5.0~14.0)
14.0
(4.0~17.0)
2.78/2.90
3.60/3.86
A/A
5(25)
Hi:42 Lo:37
Cooling:48 Heating:50
3.44/3.67
3.63/3.81
A/A
5(29)
Hi:34 Lo:27
100
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43* 2
-20~20
14.0
(5.0~16.0)
16.0
(4.0~18.0)
4.20/4.30
3.33/3.72
A/A
5(30)
Hi:43 Lo:38
Cooling:49 Heating:52
Hi:42 Lo:33.5
SPECIFICATIONS * Not available in 60Hz
Set model name
Indoor name
Outdoor name
Power source
* FDU100VSXVD
FDU100VD
FDC100VSX
* FDU125VSXVD
FDU125VD
FDC125VSX
* FDU140VSXVD
FDU140VD
FDC140VSX
3Phase 380-415V 50Hz
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1 Indoor
Outdoor
Air flow
Indoor
Outdoor
External static pressure
Exterior dimensions Height x Width x Depth
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Liquid/Gas
Range of usage
Ref.piping size
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
10.0
(4.0~11.2)
11.2
(4.0~16.0)
2.78/2.90
3.60/3.86
A/A
5(16)
Hi:42 Lo:37
Cooling:48 Heating:50
Hi:34 Lo:27
12.5
(5.0~14.0)
14.0
(4.0~18.0)
3.44/3.67
3.63/3.81
A/A
5(18)
Hi:43 Lo:38
Cooling:48 Heating:50
Hi:42 Lo:33.5
100
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43* 2
-20~20
14.0
(5.0~16.0)
16.0
(4.0~20.0)
4.20/4.30
3.33/3.72
A/A
5(19)
Cooling:49 Heating:52
*
*
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure of FDU71/100/125/140 is 60Pa and that of FDU200/250 is 100Pa.
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : External static pressure is changeable to be set by the remote control. Standard external static pressure is factory setting. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa.
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
15
16
[ INDOOR UNIT ]
DUCT CONNECTED -Middle Static pressure-
FDUM
Wired remote control
Wireless remote control
Filter kit
UM-FL1E : for 50
UM-FL2E : for 60, 71
UM-FL3E : for 100, 125, 140
(option) external static pressure loss:5pa
RC-E4
(Option)
RCH-E3
(Option)
RCN-KIT3-E
(Option)
Point
1
Various Adaptability
Selectable static pressure and
Flexible duct design with selectable air suction (direct suction /duct suction) can meet wide pattern of installation.
Static pressure Pa model
50/60/71VD
100VD
125/140VD
Standard
50
60
60
(50Hz)
Max
85
90
85
Outline drawing(Unit:mm)
Model FDUM50VD
A
CLASS
FDUM 50/60/71/
100/125/140VD
Point
2
600mm Drain Pump
Drain can be discharged upwards by 600mm from the ceiling surface. It allows a piping layout with a high degree of freedom Depending on the installation location.
Flexible hose less than
600mm
Models FDUM60V,71VD Models FDUM100V,125V,140VD
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor
Outdoor
Air flow
Indoor
Static pressure
Outdoor
50Hz/60Hz
Height x Width x Depth Exterior dimensions
Net weight
Air filter, Q'ty
Range of usage
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDUM50ZIXVD
FDUM50VD
SRC50ZIX-S
FDUM60ZIXVD
FDUM60VD
SRC60ZIX-S
FDUM71VNVD
FDUM71VD
FDC71VNX
FDUM100VNXVD
FDUM100VD
FDC100VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
5.0
(2.2~5.6)
5.6
(2.8~6.3)
7.1
(3.2~8.0)
10.0
(4.0~11.2)
5.4
(2.5~6.3)
1.52/1.41
6.7
(3.1~7.1)
1.86/1.96
8.0
(3.6~9.0)
2.14/2.16
3.29/3.83
A/A
3.01/3.42
B/B
3.32/3.70
A/A
47
5(14)
Hi:34 Me:31 Lo:28
Hi:13 Me:12 Lo:11
Standard:50/40, Max:85/90
40
5(17)
Hi:35 Me:32 Lo:29
48
Hi:16 Me:15 Lo:14
Cooling:51 Heating:48
Hi:20 Me:18 Lo:15
Cooling:60 Heating:50
Standard:50/40, Max:85/100
299x750x635
34
299x950x635
40
Procure locally
640x800(+71)x290
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
750x880(+88)x340
60 43
Scroll
1.4(15)
6.35/12.7
2.95(30)
30
20
20
50
-15~43* 2
-15~20
Rotary
9.52/15.88
30
15
-20~20
11.2
(4.0~12.5)
2.72/2.95
3.68/3.80
A/A
5(24)
Hi:37 Me:35 Lo:32
Cooling:48 Heating:50
Hi:28 Me:25 Lo:22
100
Standard:60/60, Max:90/100
350x1,370x635
59
1,300x970x370
105
4.5(30)
100
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
FDUM125VNXVD
FDUM125VD
FDC125VNX
FDUM140VNXVD
FDUM140VD
FDC140VNX
FDUM100VSXVD
FDUM100VD
FDC100VSX
FDUM125VSXVD
FDUM125VD
FDC125VSX
FDUM140VSXVD
FDUM140VD
FDC140VSX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz 3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor
Outdoor
Air flow
Indoor
Outdoor
Static pressure
Exterior dimensions
Ref.amount precharged
Ref.piping size
Ref.piping length
50Hz/60Hz
Height x Width x Depth
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Type of compressor
Liquid/Gas
Range of usage
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
12.5
(5.0~14.0)
14.0
(5.0~16.0)
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(4.0~17.0)
3.62/3.77
16.0
(4.0~18.0)
4.34/4.69
11.2
(4.0~16.0)
2.72/2.95
14.0
(4.0~18.0)
3.62/3.77
16.0
(4.0~20.0)
4.34/4.69
3.45/3.71
A/A
Hi:38 Me:36 Lo:33
Cooling:48 Heating:50
5(26)
3.23/3.41
A/B
Cooling:49 Heating:52
Standard:60/55, Max:85/100
3.68/3.80
A/A
Hi:37 Me:35 Lo:32
Cooling:48 Heating:50
Hi:28 Me:25 Lo:22
100
3.45/3.71
A/A
5(15)
3.23/3.41
A/B
Hi:38 Me:36 Lo:33
Cooling:49 Heating:52
Standard:60/55, Max:85/100 Standard:60/60, Max:90/100
350x1,370x635
59
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43* 2
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure of indoor units is 60Pa.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 50ZIXVD 35dB, 60ZIXVD 38dB, 71VNXVD 38dB, 100/125/140VNXVD 41dB, 100/125/140VSXVD 41dB
Air flow: 50ZIXVD 14CMM, 60ZIXVD 18CMM, 71VNXVD 23CMM, 100/125/140VNXVD 34CMM, 100/125/140VSXVD 34CMM
17
16
[ INDOOR UNIT ]
DUCT CONNECTED -Middle Static pressure-
FDUM
Wired remote control
Wireless remote control
Filter kit
UM-FL1E : for 50
UM-FL2E : for 60, 71
UM-FL3E : for 100, 125, 140
(option) external static pressure loss:5pa
RC-E4
(Option)
RCH-E3
(Option)
RCN-KIT3-E
(Option)
Point
1
Various Adaptability
Selectable static pressure and
Flexible duct design with selectable air suction (direct suction /duct suction) can meet wide pattern of installation.
Static pressure Pa model
50/60/71VD
100VD
125/140VD
Standard
50
60
60
(50Hz)
Max
85
90
85
Outline drawing(Unit:mm)
Model FDUM50VD
A
CLASS
FDUM 50/60/71/
100/125/140VD
Point
2
600mm Drain Pump
Drain can be discharged upwards by 600mm from the ceiling surface. It allows a piping layout with a high degree of freedom Depending on the installation location.
Flexible hose less than
600mm
Models FDUM60V,71VD Models FDUM100V,125V,140VD
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor
Outdoor
Air flow
Indoor
Static pressure
Outdoor
50Hz/60Hz
Height x Width x Depth Exterior dimensions
Net weight
Air filter, Q'ty
Range of usage
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDUM50ZIXVD
FDUM50VD
SRC50ZIX-S
FDUM60ZIXVD
FDUM60VD
SRC60ZIX-S
FDUM71VNVD
FDUM71VD
FDC71VNX
FDUM100VNXVD
FDUM100VD
FDC100VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
5.0
(2.2~5.6)
5.6
(2.8~6.3)
7.1
(3.2~8.0)
10.0
(4.0~11.2)
5.4
(2.5~6.3)
1.52/1.41
6.7
(3.1~7.1)
1.86/1.96
8.0
(3.6~9.0)
2.14/2.16
3.29/3.83
A/A
3.01/3.42
B/B
3.32/3.70
A/A
47
5(14)
Hi:34 Me:31 Lo:28
Hi:13 Me:12 Lo:11
Standard:50/40, Max:85/90
40
5(17)
Hi:35 Me:32 Lo:29
48
Hi:16 Me:15 Lo:14
Cooling:51 Heating:48
Hi:20 Me:18 Lo:15
Cooling:60 Heating:50
Standard:50/40, Max:85/100
299x750x635
34
299x950x635
40
Procure locally
640x800(+71)x290
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
750x880(+88)x340
60 43
Scroll
1.4(15)
6.35/12.7
2.95(30)
30
20
20
50
-15~43* 2
-15~20
Rotary
9.52/15.88
30
15
-20~20
11.2
(4.0~12.5)
2.72/2.95
3.68/3.80
A/A
5(24)
Hi:37 Me:35 Lo:32
Cooling:48 Heating:50
Hi:28 Me:25 Lo:22
100
Standard:60/60, Max:90/100
350x1,370x635
59
1,300x970x370
105
4.5(30)
100
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
FDUM125VNXVD
FDUM125VD
FDC125VNX
FDUM140VNXVD
FDUM140VD
FDC140VNX
FDUM100VSXVD
FDUM100VD
FDC100VSX
FDUM125VSXVD
FDUM125VD
FDC125VSX
FDUM140VSXVD
FDUM140VD
FDC140VSX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz 3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor
Outdoor
Air flow
Indoor
Outdoor
Static pressure
Exterior dimensions
Ref.amount precharged
Ref.piping size
Ref.piping length
50Hz/60Hz
Height x Width x Depth
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Type of compressor
Liquid/Gas
Range of usage
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
12.5
(5.0~14.0)
14.0
(5.0~16.0)
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(4.0~17.0)
3.62/3.77
16.0
(4.0~18.0)
4.34/4.69
11.2
(4.0~16.0)
2.72/2.95
14.0
(4.0~18.0)
3.62/3.77
16.0
(4.0~20.0)
4.34/4.69
3.45/3.71
A/A
Hi:38 Me:36 Lo:33
Cooling:48 Heating:50
5(26)
3.23/3.41
A/B
Cooling:49 Heating:52
Standard:60/55, Max:85/100
3.68/3.80
A/A
Hi:37 Me:35 Lo:32
Cooling:48 Heating:50
Hi:28 Me:25 Lo:22
100
3.45/3.71
A/A
5(15)
3.23/3.41
A/B
Hi:38 Me:36 Lo:33
Cooling:49 Heating:52
Standard:60/55, Max:85/100 Standard:60/60, Max:90/100
350x1,370x635
59
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43* 2
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure of indoor units is 60Pa.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 50ZIXVD 35dB, 60ZIXVD 38dB, 71VNXVD 38dB, 100/125/140VNXVD 41dB, 100/125/140VSXVD 41dB
Air flow: 50ZIXVD 14CMM, 60ZIXVD 18CMM, 71VNXVD 23CMM, 100/125/140VNXVD 34CMM, 100/125/140VSXVD 34CMM
17
[ INDOOR UNIT ]
CEILING SUSPENDED
FDEN
A
CLASS
Wired remote control
FDEN 40/50/60/71/100/125/140VD
Wireless remote control
RC-E4
(Option)
RCH-E3
(Option)
RCN-E1R
(Option)
Point
1
Improved installation workability
Increased freedom of a piping layout
Up
Point
2
Compact and modern design
Height
210mm
Right
Rear
The refrigerant pipe from the unit can be arranged in three directions, rear, right and up. The drain pipe can be arranged in two directions, left and right. This will allow a free layout of piping for various installation conditions. The unit can only be serviced from the bottom.
All models fit compactly on ceiling. (Height-210mm or 250mm).
Plain, modern design featuring rounded edges gives room a comfortable atmosphere.
FDEN40VD, 50VD weights 30kg the lightest level in the industry.
Convenient and quick installation.
18
Outline drawing (Unit:mm)
24
40
Drain hole connection(1)
(VP20(I.D.20))
76 a (Suspension bolts pitch)
Air inlet grille b c
Gas piping
(VP20(I.D.20))
24
290(Suspension bolts pitch)
135
68
410
Holes for suspension bolts
(M8 to M10X 4pcs.Not included)
145
52
Liquid piping
Gas piping
40
Air outlet
Indication board
690
195
235
271
Note(1) The slope of drain piping
inside the unit is able
to take incline of 10mm.
(VP20 (I.D.20))
75
110
135
Liquid piping
Space for installation and service
100 or more or more 150 or more
Obstacles
5 or more
Dimension Table model
FDEN40,50
FDEN60,71
FDEN100~140 a
1022
1272
1572 b
990
1240
1540 c
1070
1320
1620 d
215
215
255 e
210
210
250
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Energy label
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
Air flow
1
Exterior dimensions
Net weight
Indoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
Range of usage
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDEN40ZIXVD
FDEN40VD
SRC40ZIX-S
FDEN50ZIXVD
FDEN50VD
SRC50ZIX-S
FDEN60ZIXVD
FDEN60VD
SRC60ZIX-S
FDEN71VNXVD
FDEN71VD
FDC71VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDEN100VNXVD
FDEN100VD
FDC100VNX
4.0
(1.8~4.7)
4.5
(2.0~5.4)
5.0
(2.2~5.6)
5.4
(2.5~6.3)
5.6
(2.8~6.3)
6.7
(3.1~7.1)
7.1
(3.2~8.0)
8.0
(3.6~9.0)
10.0
(4.0~11.2)
11.2
(4.0~12.5)
1.04/1.13
3.85/3.98
A/A
5(12)
1.59/1.58
3.14/3.42
B/B
1.95/2.12
2.87/3.16
C/D
2.11/2.11
3.36/3.79
A/A
2.80/2.88
3.57/3.89
A/A
Hi:39 Me:38 Lo:37
47
Hi:11 Me:9 Lo:7
210x1,070x690
28
40
5(14)
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
640x800(+71)x290
43
750x880(+88)x340
60
5(24)
48
Hi:41 Me:39 Lo:38 Hi:44 Me:41 Lo:39
Cooling:51 Heating:48 Cooling:48 Heating:50
Hi:18 Me:14 Lo:12 Hi:18 Me:14 Lo:12 Hi:26 Me:23 Lo:21
Cooling:60 Heating:50
210x1,320x690
37
5(17)
100
250x1,620x690
49
1,300x970x370
105
Scroll
1.4(15)
6.35/12.7
30
20
20
2.95(30)
Rotary
9.52/15.88
50
30
15
4.5(30)
-15~43* 2
-15~20 -20~20
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
FDEN125VNXVD
FDEN125VD
FDC125VNX
FDEN140VNXVD
FDEN140VD
FDC140VNX
FDEN100VSXVD
FDEN100VD
FDC100VSX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDEN125VSXVD
FDEN125VD
FDC125VSX
FDEN140VSXVD
FDEN140VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
(Min~Max)
ISO-T1(JIS)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor
Outdoor
Air flow
Exterior dimensions
Net weight
Air filter, Q'ty
Indoor
Outdoor
Height x Width x Depth
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Range of usage
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
12.5
(5.0~14.0)
14.0
(4.0~17.0)
14.0
(5.0~16.0)
16.0
(4.0~18.0)
10.0
(4.0~11.2)
11.2
(4.0~16.0)
12.5
(5.0~14.0)
14.0
(4.0~18.0)
14.0
(5.0~16.0)
16.0
(4.0~20.0)
3.86/3.77
3.24/3.71
A/A
5(26)
4.98/4.69
2.81/3.41
Hi:46 Me:44 Lo:43
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:29 Me:26 Lo:23
C/B
2.80/2.88
3.57/3.89
A/A
Hi:44 Me:41 Lo:39
Cooling:48 Heating:50
Hi:26 Me:23 Lo:21
100
250x1,620x690
49
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
1,300x970x370
105
3.86/3.77
3.24/3.71
4.98/4.69
2.81/3.41
A/A
5(15)
C/B
Hi:46 Me:44 Lo:43
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:29 Me:26 Lo:23
100
Rotary
4.5(30)
9.52/15.88
50
30
15
-15~43* 2
-20~20
100
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB.
Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 40/50ZIXVD 46dB, 60ZIXVD 50dB, 71VNXVD 50dB, 100VNXVD 46dB, 125/140VNXVD 50dB, 100VSXVD 46dB, 125/140VSXVD 50dB
Air flow: 40/50ZIXVD 13CMM, 60ZIXVD 22CMM, 71VNXVD 22CMM, 100VNXVD 28CMM, 125/140VNXVD 32CMM, 100VSXVD 28CMM, 125/140VSXVD 32CMM
19
[ INDOOR UNIT ]
CEILING SUSPENDED
FDEN
A
CLASS
Wired remote control
FDEN 40/50/60/71/100/125/140VD
Wireless remote control
RC-E4
(Option)
RCH-E3
(Option)
RCN-E1R
(Option)
Point
1
Improved installation workability
Increased freedom of a piping layout
Up
Point
2
Compact and modern design
Height
210mm
Right
Rear
The refrigerant pipe from the unit can be arranged in three directions, rear, right and up. The drain pipe can be arranged in two directions, left and right. This will allow a free layout of piping for various installation conditions. The unit can only be serviced from the bottom.
All models fit compactly on ceiling. (Height-210mm or 250mm).
Plain, modern design featuring rounded edges gives room a comfortable atmosphere.
FDEN40VD, 50VD weights 30kg the lightest level in the industry.
Convenient and quick installation.
18
Outline drawing (Unit:mm)
24 a (Suspension bolts pitch)
40
Drain hole connection(1)
(VP20(I.D.20))
76
Air inlet grille b c
Gas piping
(VP20(I.D.20))
24
290(Suspension bolts pitch)
135
68
410
Holes for suspension bolts
(M8 to M10X 4pcs.Not included)
145
52
Liquid piping
Gas piping
40
Air outlet
Indication board
690
195
235
271
Note(1) The slope of drain piping
inside the unit is able
to take incline of 10mm.
(VP20 (I.D.20))
75
110
135
Liquid piping
Space for installation and service
100 or more or more 150 or more
Obstacles
5 or more
Dimension Table model
FDEN40,50
FDEN60,71
FDEN100~140 a
1022
1272
1572 b
990
1240
1540 c
1070
1320
1620 d
215
215
255 e
210
210
250
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Energy label
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
Air flow
1
Exterior dimensions
Net weight
Indoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
Range of usage
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDEN40ZIXVD
FDEN40VD
SRC40ZIX-S
FDEN50ZIXVD
FDEN50VD
SRC50ZIX-S
FDEN60ZIXVD
FDEN60VD
SRC60ZIX-S
FDEN71VNXVD
FDEN71VD
FDC71VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDEN100VNXVD
FDEN100VD
FDC100VNX
4.0
(1.8~4.7)
4.5
(2.0~5.4)
5.0
(2.2~5.6)
5.4
(2.5~6.3)
5.6
(2.8~6.3)
6.7
(3.1~7.1)
7.1
(3.2~8.0)
8.0
(3.6~9.0)
10.0
(4.0~11.2)
11.2
(4.0~12.5)
1.04/1.13
3.85/3.98
A/A
5(12)
1.59/1.58
3.14/3.42
B/B
1.95/2.12
2.87/3.16
C/D
2.11/2.11
3.36/3.79
A/A
2.80/2.88
3.57/3.89
A/A
Hi:39 Me:38 Lo:37
47
Hi:11 Me:9 Lo:7
210x1,070x690
28
40
5(14)
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
640x800(+71)x290
43
750x880(+88)x340
60
5(24)
48
Hi:41 Me:39 Lo:38 Hi:44 Me:41 Lo:39
Cooling:51 Heating:48 Cooling:48 Heating:50
Hi:18 Me:14 Lo:12 Hi:18 Me:14 Lo:12 Hi:26 Me:23 Lo:21
Cooling:60 Heating:50
210x1,320x690
37
5(17)
100
250x1,620x690
49
1,300x970x370
105
Scroll
1.4(15)
6.35/12.7
30
20
20
2.95(30)
Rotary
9.52/15.88
50
30
15
4.5(30)
-15~43* 2
-15~20 -20~20
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
FDEN125VNXVD
FDEN125VD
FDC125VNX
FDEN140VNXVD
FDEN140VD
FDC140VNX
FDEN100VSXVD
FDEN100VD
FDC100VSX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDEN125VSXVD
FDEN125VD
FDC125VSX
FDEN140VSXVD
FDEN140VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
(Min~Max)
ISO-T1(JIS)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor
Outdoor
Air flow
Exterior dimensions
Net weight
Air filter, Q'ty
Indoor
Outdoor
Height x Width x Depth
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Range of usage
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
12.5
(5.0~14.0)
14.0
(4.0~17.0)
14.0
(5.0~16.0)
16.0
(4.0~18.0)
10.0
(4.0~11.2)
11.2
(4.0~16.0)
12.5
(5.0~14.0)
14.0
(4.0~18.0)
14.0
(5.0~16.0)
16.0
(4.0~20.0)
3.86/3.77
3.24/3.71
A/A
5(26)
4.98/4.69
2.81/3.41
Hi:46 Me:44 Lo:43
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:29 Me:26 Lo:23
C/B
2.80/2.88
3.57/3.89
A/A
Hi:44 Me:41 Lo:39
Cooling:48 Heating:50
Hi:26 Me:23 Lo:21
100
250x1,620x690
49
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
1,300x970x370
105
3.86/3.77
3.24/3.71
4.98/4.69
2.81/3.41
A/A
5(15)
C/B
Hi:46 Me:44 Lo:43
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:29 Me:26 Lo:23
100
Rotary
4.5(30)
9.52/15.88
50
30
15
-15~43* 2
-20~20
100
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB.
Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 40/50ZIXVD 46dB, 60ZIXVD 50dB, 71VNXVD 50dB, 100VNXVD 46dB, 125/140VNXVD 50dB, 100VSXVD 46dB, 125/140VSXVD 50dB
Air flow: 40/50ZIXVD 13CMM, 60ZIXVD 22CMM, 71VNXVD 22CMM, 100VNXVD 28CMM, 125/140VNXVD 32CMM, 100VSXVD 28CMM, 125/140VSXVD 32CMM
19
Micro Inverter
FDT
[ INDOOR UNIT ]
CEILING CASSETTE -4wayA
CLASS
Wired remote control
FDT 100/125/140VD
Wireless remote control
RC-E4
(Option)
RCH-E3
(Option)
RCN-T-36W-E
(Option)
20
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
FDT100VNVD
FDT100VD
FDC100VN
FDT125VNVD
FDT125VD
FDC125VN
FDT140VNVD
FDT140VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
Micro Inverter
FDT100VSVD
FDT100VD
FDC100VS
FDT125VSVD
FDT125VD
FDC125VS
FDT140VSVD
FDT140VD
FDC140VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel
*
1
Indoor
Outdoor kW kW kW
A dB(A) kg(m)
ø m m m
O/U
O/U
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.76/2.74
3.62/4.09
A/A
Hi:40
Me:37 Lo:35
49
Hi:27
Me:24 Lo:20
12.5
(5.0~14.0)
14.0
(4.0~16.0)
14.0
(5.0~14.5)
16.0
(4.0~16.5)
10.0
(4.0~11.2)
11.2
(4.0~12.5)
12.5
(5.0~14.0)
14.0
(4.0~16.0)
4.05/3.77
3.09/3.71
B/A
4.98/4.57
2.81/3.50
C/B
2.76/2.74
3.62/4.09
A/A
4.05/3.77
3.09/3.71
B/A
5(24)
Hi:42
Me:40 Lo:37
Cooling:50 Heating:51
Hi:30
Hi:43
Me:41 Lo:38
51
Hi:30
Hi:40
Me:37 Lo:35
49
Me:27 Lo:23
Cooling:75 Heating:73
Me:27 Lo:23
Hi:27
Me:24 Lo:20
Unit:298x840x840 Panel:35x950x950
32.5(Unit:27 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
845x970x370
5(15)
Hi:42
Me:40 Lo:37
Cooling:50 Heating:51
Hi:30
Me:27 Lo:23
Cooling:75 Heating:73
81 83
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43* 2
-20~20
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.98/4.57
2.81/3.50
C/B
Hi:43
Me:41 Lo:38
51
Hi:30
Me:27 Lo:23 Air flow
Indoor
Exterior dimensions
Net weight
Panel
Air filter, Q'ty
Outdoor
Height x Width x Depth
Unit+Panel
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Liquid/Gas
Range of usage difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating
CMM mm kg mm kg
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100/125/140VNVD 51dB, 100/125/140VSVD 51dB
Air flow: 100/125/140VNVD 37CMM, 100/125/140VSVD 37CMM
COP
DUCT CONNECTED -High Static pressure-
FDU
SPECIFICATIONS
Set model name
Indoor name
FDU 100/125/140VD
FDU 200/250VD
Fan control kit
(100~200Pa)
U-FCRA
[For 200/250VD]
(option)
Wired remote control
RC-E4
(Option)
RCH-E3
(Option)
Wireless remote control
RCN-KIT3-E
(Option)
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1 Indoor
Outdoor
Air flow
Indoor
Outdoor
External static pressure
Exterior dimensions Height x Width x Depth
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Range of usage
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height difference
Operating temperature range
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption Cooling/Heating
Cooling/Heating
Energy label
Inrush current (Max. running current)
Sound Ievel*
1
Cooling/Heating
Indoor
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor
Outdoor
External static pressure * 2
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Liquid/Gas
O/U is higher
Range of usage difference
Operating temperature range
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
* FDU140VNVD
FDU140VD
FDC140VN
1Phase
220-240V 50Hz
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.95/4.43
2.83/3.61
C/A
5(28)
Hi:43 Lo:38
51
Hi:42 Lo:33.5
81
* FDU100VSVD
FDU100VD
FDC100VS
Micro Inverter
* FDU125VSVD
FDU125VD
FDC125VS
3Phase 380-415V 50Hz kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
* FDU140VSVD
FDU140VD
FDC140VS
* Not available in 60Hz
Micro Inverter
* FDU100VNVD
FDU100VD
FDC100VN
* FDU125VNVD
FDU125VD
FDC125VN
1Phase 220-240V 50Hz
10.0
12.5
(4.0~11.2) (5.0~14.0)
11.2
(4.0~12.5)
14.0
(4.0~16.0)
2.88/2.99
3.47/3.75
A/A
5(25)
Hi:42 Lo:37
49
4.04/3.79
3.09/3.69
B/A
5(27)
Hi:43 Lo:38
Cooling:50 Heating:51
Hi:34 Lo:27 Hi:42 Lo:33.5
Cooling:75 Heating:73
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
81
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43* 3 -15~43* 2
-20~20
FDU200VSVD
FDU200VD
FDC200VS
A
CLASS
FDU250VSVD
FDU250VD
FDC250VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
20.0
(7.0~22.4)
25.0
(10.0~28.0)
11.2
(4.0~12.5)
14.0
(4.0~16.0)
16.0
(4.0~16.5)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
2.88/2.99
3.47/3.75
A/A
5(16)
Hi:42 Lo:37
49
4.04/3.79
3.09/3.69
350x1,370x650
B/A
5(18)
Hi:34 Lo:27
Cooling:75 Heating:73
Standard:50, Max:130
Hi:43 Lo:38
Cooling:50 Heating:51
4.95/4.43
2.83/3.61
Hi:42 Lo:33.5
C/A
5(19)
51
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
50Hz:6.59/6.08
60Hz:6.58/5.84
50Hz:3.03/3.68
60Hz:3.04/3.83
B/A
5(24)
51
57
50Hz: 9.91/8.50
60Hz:10.21/8.22
50Hz:2.52/3.29
60Hz:2.45/3.41
50Hz:E/C 60Hz:E/B
5(27)
52
Cooling:57 Heating:58
50Hz:51, 60Hz:60 50Hz:68, 60Hz:80
Cooling:150 Heating:145
Standard:100, Max:200
360x1,570x830
92
845x970x370 1,300x970x370
83 122 140
Rotary
3.8(30)
9.52/15.88
50
5.4(30)
9.52/25.4
Scroll
70
7.2(30)
12.7/25.4
30
15
-15~43 * 3
-20~20 -15~20
*
*
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure of FDU100/125/140 is 60Pa and that of FDU200/250 is 100Pa.
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : External static pressure is changeable to be set by the remote control. Standard external static pressure is factory setting. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa.
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
21
Micro Inverter
FDT
[ INDOOR UNIT ]
CEILING CASSETTE -4wayA
CLASS
Wired remote control
FDT 100/125/140VD
Wireless remote control
RC-E4
(Option)
RCH-E3
(Option)
RCN-T-36W-E
(Option)
20
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
FDT100VNVD
FDT100VD
FDC100VN
FDT125VNVD
FDT125VD
FDC125VN
FDT140VNVD
FDT140VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
Micro Inverter
FDT100VSVD
FDT100VD
FDC100VS
FDT125VSVD
FDT125VD
FDC125VS
FDT140VSVD
FDT140VD
FDC140VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel
*
1
Indoor
Outdoor kW kW kW
A dB(A) kg(m)
ø m m m
O/U
O/U
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.76/2.74
3.62/4.09
A/A
Hi:40
Me:37 Lo:35
49
Hi:27
Me:24 Lo:20
12.5
(5.0~14.0)
14.0
(4.0~16.0)
14.0
(5.0~14.5)
16.0
(4.0~16.5)
10.0
(4.0~11.2)
11.2
(4.0~12.5)
12.5
(5.0~14.0)
14.0
(4.0~16.0)
4.05/3.77
3.09/3.71
B/A
4.98/4.57
2.81/3.50
C/B
2.76/2.74
3.62/4.09
A/A
4.05/3.77
3.09/3.71
B/A
5(24)
Hi:42
Me:40 Lo:37
Cooling:50 Heating:51
Hi:30
Hi:43
Me:41 Lo:38
51
Hi:30
Hi:40
Me:37 Lo:35
49
Me:27 Lo:23
Cooling:75 Heating:73
Me:27 Lo:23
Hi:27
Me:24 Lo:20
Unit:298x840x840 Panel:35x950x950
32.5(Unit:27 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
845x970x370
5(15)
Hi:42
Me:40 Lo:37
Cooling:50 Heating:51
Hi:30
Me:27 Lo:23
Cooling:75 Heating:73
81 83
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43* 2
-20~20
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.98/4.57
2.81/3.50
C/B
Hi:43
Me:41 Lo:38
51
Hi:30
Me:27 Lo:23 Air flow
Indoor
Exterior dimensions
Net weight
Panel
Air filter, Q'ty
Outdoor
Height x Width x Depth
Unit+Panel
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Liquid/Gas
Range of usage difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating
CMM mm kg mm kg
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100/125/140VNVD 51dB, 100/125/140VSVD 51dB
Air flow: 100/125/140VNVD 37CMM, 100/125/140VSVD 37CMM
COP
DUCT CONNECTED -High Static pressure-
FDU
SPECIFICATIONS
Set model name
Indoor name
FDU 100/125/140VD
FDU 200/250VD
Fan control kit
(100~200Pa)
U-FCRA
[For 200/250VD]
(option)
Wired remote control
RC-E4
(Option)
RCH-E3
(Option)
Wireless remote control
RCN-KIT3-E
(Option)
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1 Indoor
Outdoor
Air flow
Indoor
Outdoor
External static pressure
Exterior dimensions Height x Width x Depth
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Range of usage
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height difference
Operating temperature range
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption Cooling/Heating
Cooling/Heating
Energy label
Inrush current (Max. running current)
Sound Ievel*
1
Cooling/Heating
Indoor
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor
Outdoor
External static pressure * 2
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Liquid/Gas
O/U is higher
Range of usage difference
Operating temperature range
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
* FDU140VNVD
FDU140VD
FDC140VN
1Phase
220-240V 50Hz
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.95/4.43
2.83/3.61
C/A
5(28)
Hi:43 Lo:38
51
Hi:42 Lo:33.5
81
* FDU100VSVD
FDU100VD
FDC100VS
Micro Inverter
* FDU125VSVD
FDU125VD
FDC125VS
3Phase 380-415V 50Hz kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
* FDU140VSVD
FDU140VD
FDC140VS
* Not available in 60Hz
Micro Inverter
* FDU100VNVD
FDU100VD
FDC100VN
* FDU125VNVD
FDU125VD
FDC125VN
1Phase 220-240V 50Hz
10.0
12.5
(4.0~11.2) (5.0~14.0)
11.2
(4.0~12.5)
14.0
(4.0~16.0)
2.88/2.99
3.47/3.75
A/A
5(25)
Hi:42 Lo:37
49
4.04/3.79
3.09/3.69
B/A
5(27)
Hi:43 Lo:38
Cooling:50 Heating:51
Hi:34 Lo:27 Hi:42 Lo:33.5
Cooling:75 Heating:73
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
81
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43* 3 -15~43* 2
-20~20
FDU200VSVD
FDU200VD
FDC200VS
A
CLASS
FDU250VSVD
FDU250VD
FDC250VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
20.0
(7.0~22.4)
25.0
(10.0~28.0)
11.2
(4.0~12.5)
14.0
(4.0~16.0)
16.0
(4.0~16.5)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
2.88/2.99
3.47/3.75
A/A
5(16)
Hi:42 Lo:37
49
4.04/3.79
3.09/3.69
350x1,370x650
B/A
5(18)
Hi:34 Lo:27
Cooling:75 Heating:73
Standard:50, Max:130
Hi:43 Lo:38
Cooling:50 Heating:51
4.95/4.43
2.83/3.61
Hi:42 Lo:33.5
C/A
5(19)
51
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
50Hz:6.59/6.08
60Hz:6.58/5.84
50Hz:3.03/3.68
60Hz:3.04/3.83
B/A
5(24)
51
57
50Hz: 9.91/8.50
60Hz:10.21/8.22
50Hz:2.52/3.29
60Hz:2.45/3.41
50Hz:E/C 60Hz:E/B
5(27)
52
Cooling:57 Heating:58
50Hz:51, 60Hz:60 50Hz:68, 60Hz:80
Cooling:150 Heating:145
Standard:100, Max:200
360x1,570x830
92
845x970x370 1,300x970x370
83 122 140
Rotary
3.8(30)
9.52/15.88
50
5.4(30)
9.52/25.4
Scroll
70
7.2(30)
12.7/25.4
30
15
-15~43 * 3
-20~20 -15~20
*
*
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure of FDU100/125/140 is 60Pa and that of FDU200/250 is 100Pa.
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : External static pressure is changeable to be set by the remote control. Standard external static pressure is factory setting. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa.
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
21
Micro Inverter [ INDOOR UNIT ]
DUCT CONNECTED -Low/Middle Static pressure-
FDUM
A
CLASS external static pressure loss:5pa
Wired remote control
FDUM 100/125/140VD
Filter kit
UM-FL3E : for 100, 125, 140
(option)
Wireless remote control
22
RC-E4
(Option)
RCH-E3
(Option)
RCN-KIT3-E
(Option)
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1 Indoor
Outdoor
Air flow
Indoor
Outdoor
Static pressure
Exterior dimensions
Net weight
Air filter, Q'ty
Height x Width x Depth
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Liquid/Gas
Range of usage difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
Micro Inverter
FDUM100VNVD
FDUM100VD
FDC100VN
FDUM125VNVD
FDUM125VD
FDC125VN
FDUM140VNVD
FDUM140VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
FDUM100VSVD
FDUM100VD
FDC100VS
FDUM125VSVD
FDUM125VD
FDC125VS
FDUM140VSVD
FDUM140VD
FDC140VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
11.2
(4.0~12.5)
50Hz:2.80/2.77
60Hz:2.80/2.80
50Hz:3.57/4.04
60Hz:3.57/4.00
A/A
Hi:37 Me:35 Lo:32
49
Standard:60, Max:90/100
14.0
(4.0~16.0)
50Hz:4.03/3.80
60Hz:4.03/3.85
50Hz:3.10/3.68
60Hz:3.10/3.64
16.0
(4.0~16.5)
50Hz:4.95/4.89
60Hz:4.95/4.91
50Hz:2.83/3.27
60Hz:2.83/3.26
C/C
11.2
(4.0~12.5)
50Hz:2.80/2.77
60Hz:2.80/2.80
50Hz:3.57/4.04
60Hz:3.57/4.00
A/A B/A
5(24)
Hi: 38 Me:36 Lo:33
Cooling:50 Heating:51 51
Hi: 37 Me:35 Lo:32
49
Hi:28 Me:25 Lo:22
Cooling:75 Heating:73
Standard:60/55, Max:85/100 Standard:60, Max:90/100
350x1,370x635
59
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
14.0
(4.0~16.0)
16.0
(4.0~16.5)
50Hz:4.03/3.80
60Hz:4.03/3.85
50Hz:3.10/3.68
60Hz:3.10/3.64
50Hz:4.95/4.89
60Hz:4.95/4.91
50Hz:2.83/3.27
60Hz:2.83/3.26
C/C B/A
5(15)
Hi: 38 Me:36 Lo:33
Cooling:50 Heating:51 51
Standard:60/55, Max:85/100
81 83
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43* 2
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure of indoor units is 60Pa.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100/125/140VNVD 41dB, 100/125/140VSVD 41dB
Air flow: 100/125/140VNVD 34CMM, 100/125/140VSVD 34CMM
CEILING SUSPENDED
FDEN
A
CLASS
Wired remote control
FDEN 100/125/140VD
Wireless remote control
RC-E4
(Option)
RCH-E3
(Option)
RCN-E1R
(Option)
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Energy label
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor
Outdoor
Air flow
Indoor
Exterior dimensions
Outdoor
Height x Width x Depth
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Type of compressor
Ref.amount precharged
Liquid/Gas
Range of usage
Ref.piping size
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
Micro Inverter
FDEN100VNVD
FDEN100VD
10.0
(4.0~11.2)
11.2
(4.0~12.5)
FDEN125VNVD
FDEN125VD
FDC100VN FDC125VN FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(4.0~16.0)
FDEN140VNVD
FDEN140VD
14.0
(5.0~14.5)
16.0
(4.0~16.5)
FDEN100VSVD
FDEN100VD
FDC100VS FDC125VS FDC140VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
11.2
(4.0~12.5)
FDEN125VSVD
FDEN125VD
12.5
(5.0~14.0)
14.0
(4.0~16.0)
FDEN140VSVD
FDEN140VD
14.0
(5.0~14.5)
16.0
(4.0~16.5)
2.85/2.97
3.51/3.77
A/A
Hi:44
Me:41 Lo:39
49
Hi:26
Me:23 Lo:21
4.45/4.08
2.80/3.43
C/B
5(24)
5.80/4.92
2.41/3.25
E/C
2.85/2.97
3.51/3.77
A/A
Hi:46 Me:44 Lo:43
Hi:44
Me:41 Lo:39
Cooling:50 Heating:51 51 49
Hi:26
Hi:29 Me:26 Lo:23
Me:23 Lo:21
Cooling:75 Heating:73
250x1,620x690
49
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
845x970x370
4.45/4.08
2.80/3.43
C/B
5(15)
Hi:46 Me:44 Lo:43
Cooling:50 Heating:51
5.80/4.92
2.41/3.25
Hi:29 Me:26 Lo:23
E/C
51
81 83
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43* 2
-20~20
*
*
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB.
Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VNVD 46dB, 125/140VNVD 50dB, 100VSVD 46dB, 125/140VSVD 50dB
Air flow: 100VNVD 28CMM, 125/140VNVD 32CMM, 100VSVD 28CMM, 125/140VSVD 32CMM
23
Micro Inverter [ INDOOR UNIT ]
DUCT CONNECTED -Low/Middle Static pressure-
FDUM
A
CLASS external static pressure loss:5pa
Wired remote control
FDUM 100/125/140VD
Filter kit
UM-FL3E : for 100, 125, 140
(option)
Wireless remote control
22
RC-E4
(Option)
RCH-E3
(Option)
RCN-KIT3-E
(Option)
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1 Indoor
Outdoor
Air flow
Indoor
Outdoor
Static pressure
Exterior dimensions
Net weight
Air filter, Q'ty
Height x Width x Depth
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Liquid/Gas
Range of usage difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM
Pa mm kg mm kg kg(m)
ø m m m
O/U
O/U
Micro Inverter
FDUM100VNVD
FDUM100VD
FDC100VN
FDUM125VNVD
FDUM125VD
FDC125VN
FDUM140VNVD
FDUM140VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
FDUM100VSVD
FDUM100VD
FDC100VS
FDUM125VSVD
FDUM125VD
FDC125VS
FDUM140VSVD
FDUM140VD
FDC140VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
11.2
(4.0~12.5)
50Hz:2.80/2.77
60Hz:2.80/2.80
50Hz:3.57/4.04
60Hz:3.57/4.00
A/A
Hi:37 Me:35 Lo:32
49
Standard:60, Max:90/100
14.0
(4.0~16.0)
50Hz:4.03/3.80
60Hz:4.03/3.85
50Hz:3.10/3.68
60Hz:3.10/3.64
16.0
(4.0~16.5)
50Hz:4.95/4.89
60Hz:4.95/4.91
50Hz:2.83/3.27
60Hz:2.83/3.26
C/C
11.2
(4.0~12.5)
50Hz:2.80/2.77
60Hz:2.80/2.80
50Hz:3.57/4.04
60Hz:3.57/4.00
A/A B/A
5(24)
Hi: 38 Me:36 Lo:33
Cooling:50 Heating:51 51
Hi: 37 Me:35 Lo:32
49
Hi:28 Me:25 Lo:22
Cooling:75 Heating:73
Standard:60/55, Max:85/100 Standard:60, Max:90/100
350x1,370x635
59
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
14.0
(4.0~16.0)
16.0
(4.0~16.5)
50Hz:4.03/3.80
60Hz:4.03/3.85
50Hz:3.10/3.68
60Hz:3.10/3.64
50Hz:4.95/4.89
60Hz:4.95/4.91
50Hz:2.83/3.27
60Hz:2.83/3.26
C/C B/A
5(15)
Hi: 38 Me:36 Lo:33
Cooling:50 Heating:51 51
Standard:60/55, Max:85/100
81 83
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43* 2
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure of indoor units is 60Pa.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100/125/140VNVD 41dB, 100/125/140VSVD 41dB
Air flow: 100/125/140VNVD 34CMM, 100/125/140VSVD 34CMM
CEILING SUSPENDED
FDEN
A
CLASS
Wired remote control
FDEN 100/125/140VD
Wireless remote control
RC-E4
(Option)
RCH-E3
(Option)
RCN-E1R
(Option)
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Energy label
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor
Outdoor
Air flow
Indoor
Exterior dimensions
Outdoor
Height x Width x Depth
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Type of compressor
Ref.amount precharged
Liquid/Gas
Range of usage
Ref.piping size
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
Micro Inverter
FDEN100VNVD
FDEN100VD
10.0
(4.0~11.2)
11.2
(4.0~12.5)
FDEN125VNVD
FDEN125VD
FDC100VN FDC125VN FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(4.0~16.0)
FDEN140VNVD
FDEN140VD
14.0
(5.0~14.5)
16.0
(4.0~16.5)
FDEN100VSVD
FDEN100VD
FDC100VS FDC125VS FDC140VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
11.2
(4.0~12.5)
FDEN125VSVD
FDEN125VD
12.5
(5.0~14.0)
14.0
(4.0~16.0)
FDEN140VSVD
FDEN140VD
14.0
(5.0~14.5)
16.0
(4.0~16.5)
2.85/2.97
3.51/3.77
A/A
Hi:44
Me:41 Lo:39
49
Hi:26
Me:23 Lo:21
4.45/4.08
2.80/3.43
C/B
5(24)
5.80/4.92
2.41/3.25
E/C
2.85/2.97
3.51/3.77
A/A
Hi:46 Me:44 Lo:43
Hi:44
Me:41 Lo:39
Cooling:50 Heating:51 51 49
Hi:26
Hi:29 Me:26 Lo:23
Me:23 Lo:21
Cooling:75 Heating:73
250x1,620x690
49
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
845x970x370
4.45/4.08
2.80/3.43
C/B
5(15)
Hi:46 Me:44 Lo:43
Cooling:50 Heating:51
5.80/4.92
2.41/3.25
Hi:29 Me:26 Lo:23
E/C
51
81 83
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43* 2
-20~20
*
*
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB.
Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VNVD 46dB, 125/140VNVD 50dB, 100VSVD 46dB, 125/140VSVD 50dB
Air flow: 100VNVD 28CMM, 125/140VNVD 32CMM, 100VSVD 28CMM, 125/140VSVD 32CMM
23
MULTI SYSTEM
Up to Four indoor units can be connected to a single outdoor unit and simultaneously operated with a single remote control.
Twin / Triple / Double Twin Multi System
By referring to the following table for applicable indoor units, select the same models and capacities.
Applicable indoor units
Capacity
Model
4way
4way compact
(600 x 600mm)
Low/Middle Static pressure
Ceiling Suspended
Wall Mounted
Only used with outdoor units of Multi System
Combination of indoor units
Micro Inverter
NEW
Combination
FDC71VNX
40 + 40
FDC100VNX
FDC100VSX
50 + 50
FDC125VNX
FDC125VSX
60 + 60
FDC140VNX
FDC140VSX
71 + 71
50 + 50 + 50
FDC100VNV
FDC100VSV
50 + 50
FDC125VNV
FDC125VSV
60 + 60
FDC140VNV
FDC140VSV FDC200VSV FDC250VSV
71 + 71
50 + 50 + 50
100 + 100
71 + 71 + 71
125 + 125
50+50+50+50 60+60+60+60
Decision of piping specification
Diagrams below show the application as samples. For further information, refer to TECHNICAL MANUAL.
24
Twin type
Models FDC71VNX, FDC100~140VNV/VSV
[Branch pipe set : DIS-WA1]
Indoor unit
Outdoor unit
Gas line
4
3
1 2
L
Liquid line
4
(Example)
Item
Model
FDC71
FDC100
FDC125
FDC140
Indoor unit combinations
40+40
50+50
60+60
71+71
Liquid pipe
Main pipe Branch pipe
ø9.52Xt0.8 ø9.52Xt0.8
Gas pipe
Main pipe
ø15.88Xt1.0
Branch pipe
ø12.7Xt0.8
ø15.88Xt1.0
Notes (1) When 40-60 models of indoor units are applied to this combination, the reducer 3 supplied with the branch piping set should be used in order to reduce the liquid piping size from ø9.52mm to ø6.35mm at indoor unit side
(2)
(flare connection). Accordingly be sure to select the liquid piping size
ø9.52mm from branch to indoor unit.
The reducer 4 is for FDC71 and 100 models only.
3
Gas pipe
ID15.88
Symbol Liquid pipe
ID9.52
Symbol Reducer
Chart of shapes of branch piping parts
(DIS-WA1)
ID15.88
11
1
8
ID9.52
2
ID9.52
8
24 ID15.88
210
ID9.52
Notes (1)
(2)
Symbol 1 to 4 in the drawing shows the symbols of branch piping parts in the chart respectively.
Branch piping should always be arranged to have level or perpendicular position.
105
50
ø6.35 flared nut
2 piece
Symbol
3
Reducer
OD15.88
80
ID12.7
10
2 piece
Symbol
4
The branch piping (both gas and liquid lines) should always be arranged to have a level or perpendicular position.
2-Way Branch
Mount sections level with the floor.
Floor
3-Way Branch
Floor
Floor
Mount sections perpendicular to the floor.
Floor
Floor
Floor
Ideal for the installation in large area and L-shaped rooms, the V
Multi System has an extensive degree of flexibility in the selection of indoor units. Specifically, the selection of indoor units with different capacities in different types can be made.
V Multi System
Different models and capacities can be selected.
Applicable indoor units
Capacity
Model
4way
Ceiling Suspended
Combination of indoor units
NEW
Micro Inverter
FDC71VNX
40 + 40
FDC100VNX
FDC100VSX
FDC100VNV
FDC100VSV
50 + 50
FDC125VNX
FDC125VSX
FDC125VNV
FDC125VSV
60 + 60
50 + 71
FDC140VNX
FDC140VSX
FDC140VNV
FDC140VSV
71 + 71
50 + 50 + 50
FDC200VSV FDC250VSV
100 + 100
71 + 125
71 + 71 + 71
125 + 125
60 + 60 + 125
71 + 71 + 100
50+50+50+50 60+60+60+60
Triple type
Model FDC140VNV/VSV
[Branch pipe set : DIS-TA1]
The indoor_outdoor piping length differences among indoor units are less than 3m.
Indoor unit
(Example)
Item
Model
Indoor unit combinations
Liquid pipe
Main pipe Branch pipe Main pipe
Gas pipe
Branch pipe
FDC140 50+50+50 ø9.52Xt0.8
ø9.52Xt0.8
ø15.88Xt1.0
ø12.7Xt0.8
3
Outdoor unit
Gas line
1
Notes (1) The reducer 3 supplied with the branch piping set should be used in order to reduce the liquid piping size from ø9.52mm to ø6.35mm at indoor unit side (flare connection). Accordingly be sure to select the liquid piping size ø9.52mm from branch to indoor unit.
L
Liquid line
2
3
3
Gas pipe
100 80 80
ID12.7x3
Symbol Liquid pipe
100
ID9.52x3
Symbol Reducer
Chart of shapes of branch piping parts
(DIS-TA1) ID15.88
1
ID9.52
14
2 ID9.52
8
10
300
8
237
8
Notes (1)
(2)
Symbol 1 to 3 in the drawing shows the symbols of branch piping parts in the chart respectively.
Branch piping should always be arranged to have level or perpendicular position.
105
50
ø6.35 flared nut
Symbol
3
25
MULTI SYSTEM
Up to Four indoor units can be connected to a single outdoor unit and simultaneously operated with a single remote control.
Twin / Triple / Double Twin Multi System
By referring to the following table for applicable indoor units, select the same models and capacities.
Applicable indoor units
Capacity
Model
4way
4way compact
(600 x 600mm)
Low/Middle Static pressure
Ceiling Suspended
Wall Mounted
Only used with outdoor units of Multi System
Combination of indoor units
Micro Inverter
NEW
Combination
Ideal for the installation in large area and L-shaped rooms, the V
Multi System has an extensive degree of flexibility in the selection of indoor units. Specifically, the selection of indoor units with different capacities in different types can be made.
V Multi System
Different models and capacities can be selected.
Applicable indoor units
Capacity
Model
4way
Ceiling Suspended
Combination of indoor units
NEW
FDC71VNX
40 + 40
FDC100VNX
FDC100VSX
50 + 50
FDC125VNX
FDC125VSX
60 + 60
FDC140VNX
FDC140VSX
71 + 71
50 + 50 + 50
FDC100VNV
FDC100VSV
50 + 50
FDC125VNV
FDC125VSV
60 + 60
FDC140VNV
FDC140VSV FDC200VSV FDC250VSV
71 + 71
50 + 50 + 50
100 + 100
71 + 71 + 71
125 + 125
50+50+50+50 60+60+60+60
Decision of piping specification
Diagrams below show the application as samples. For further information, refer to TECHNICAL MANUAL.
24
Twin type
Models FDC71VNX, FDC100~140VNV/VSV
[Branch pipe set : DIS-WA1]
Indoor unit
Outdoor unit
Gas line
4
3
1 2
L
Liquid line
4
(Example)
Item
Model
FDC71
FDC100
FDC125
FDC140
Indoor unit combinations
40+40
50+50
60+60
71+71
Liquid pipe
Main pipe Branch pipe
ø9.52Xt0.8 ø9.52Xt0.8
Gas pipe
Main pipe
ø15.88Xt1.0
Branch pipe
ø12.7Xt0.8
ø15.88Xt1.0
Notes (1) When 40-60 models of indoor units are applied to this combination, the reducer 3 supplied with the branch piping set should be used in order to reduce the liquid piping size from ø9.52mm to ø6.35mm at indoor unit side
(2)
(flare connection). Accordingly be sure to select the liquid piping size
ø9.52mm from branch to indoor unit.
The reducer 4 is for FDC71 and 100 models only.
3
Gas pipe
ID15.88
Symbol Liquid pipe
ID9.52
Symbol Reducer
Chart of shapes of branch piping parts
(DIS-WA1)
ID15.88
11
1
8
ID9.52
2
ID9.52
8
24 ID15.88
210
ID9.52
Notes (1)
(2)
Symbol 1 to 4 in the drawing shows the symbols of branch piping parts in the chart respectively.
Branch piping should always be arranged to have level or perpendicular position.
105
50
ø6.35 flared nut
2 piece
Symbol
3
Reducer
OD15.88
80
ID12.7
10
2 piece
Symbol
4
The branch piping (both gas and liquid lines) should always be arranged to have a level or perpendicular position.
2-Way Branch
Mount sections level with the floor.
Floor
3-Way Branch
Floor
Floor
Mount sections perpendicular to the floor.
Floor
Floor
Floor
Micro Inverter
FDC71VNX
40 + 40
FDC100VNX
FDC100VSX
FDC100VNV
FDC100VSV
50 + 50
FDC125VNX
FDC125VSX
FDC125VNV
FDC125VSV
60 + 60
50 + 71
FDC140VNX
FDC140VSX
FDC140VNV
FDC140VSV
71 + 71
50 + 50 + 50
FDC200VSV FDC250VSV
100 + 100
71 + 125
71 + 71 + 71
125 + 125
60 + 60 + 125
71 + 71 + 100
50+50+50+50 60+60+60+60
Triple type
Model FDC140VNV/VSV
[Branch pipe set : DIS-TA1]
The indoor_outdoor piping length differences among indoor units are less than 3m.
(Example)
Indoor unit Item
Model
Indoor unit combinations
Liquid pipe
Main pipe Branch pipe Main pipe
Gas pipe
Branch pipe
FDC140 50+50+50 ø9.52Xt0.8
ø9.52Xt0.8
ø15.88Xt1.0
ø12.7Xt0.8
3
Outdoor unit
Gas line
1
Notes (1) The reducer 3 supplied with the branch piping set should be used in order to reduce the liquid piping size from ø9.52mm to ø6.35mm at indoor unit side (flare connection). Accordingly be sure to select the liquid piping size ø9.52mm from branch to indoor unit.
Liquid line
L
2
3
3
Gas pipe
100 80 80
ID12.7x3
Symbol Liquid pipe
100
ID9.52x3
Symbol Reducer
Chart of shapes of branch piping parts
(DIS-TA1) ID15.88
1
ID9.52
14
2 ID9.52
8
10
300
8
237
8
Notes (1)
(2)
Symbol 1 to 3 in the drawing shows the symbols of branch piping parts in the chart respectively.
Branch piping should always be arranged to have level or perpendicular position.
105
50
ø6.35 flared nut
Symbol
3
25
MULTI [ INDOOR UNIT ]
CEILING CASSETTE -4way-
FDT
Wired remote control
RC-E4
(Option)
RCH-E3
(Option)
FDT 40/50/60/71/100/125VD
Wireless remote control
RCN-T-36W-E
(Option)
A
CLASS
The values are for simultaneous Multi operation.
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor* 2
Outdoor
Height x Width x Depth
Unit+Panel
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDT71VNXPVD FDT100VNXPVD
Twin
FDT40VD
FDC71VNX
FDT50VD
FDC100VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
7.1
(3.2~8.0)
10.0
(4.0~11.2)
8.0
(3.6~9.0)
11.2
(4.0~12.5)
1.85/1.99
3.84/4.02
2.56/2.66
3.91/4.21
A/A A/A
5(17) 5(24)
Hi:33 Me:31 Lo:30
Cooling:51 Heating:48 Cooling:48 Heating:50
Hi:18 Me:16 Lo:14
Cooling:60 Heating:50 100
Unit:246x840x840 Panel:35x950x950
27.5(Unit:22 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
750x880(+88)x340
60
2.95(30)
1,300x970x370
9.52/15.88
105
4.5(30)
50 100
30
15
-15~43* 3
-20~20
SPECIFICATIONS The values are for simultaneous Multi operation.
26
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor* 2
Outdoor
Height x Width x Depth
Unit+Panel
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDT125VNXPVD FDT140VNXPVD FDT140VNXTVD FDT100VSXPVD
FDT60VD
FDC125VNX
Twin
FDT71VD
FDC140VNX
Triple
FDT50VD
FDC140VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(5.0~16.0)
FDT50VD
FDC100VSX
FDT125VSXPVD
Twin
FDT60VD
FDC125VSX
FDT140VSXPVD
FDT71VD
FDC140VSX
FDT140VSXTVD
Triple
FDT50VD
FDC140VSX
10.0
(4.0~11.2)
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~14.5)
14.0
(5.0~14.5)
14.0
(4.0~17.0)
3.06/3.22
4.08/4.35
A/A
Hi:33 Me:31 Lo:30
Cooling:48 Heating:50
Hi:18 Me:16 Lo:14
16.0
(4.0~18.0)
3.88/3.70
3.61/4.32
A/A
29.5(Unit:24 Panel:5.5)
16.0
(4.0~18.0)
3.88/3.76
3.61/4.26
A/A
5(26)
Hi:35 Me:33 Lo:31 Hi:33 Me:31 Lo:30
Cooling:49 Heating:52
Hi:21 Me:19 Lo:17 Hi:18 Me:16 Lo:14
11.2
(4.0~16.0)
2.56/2.66
3.91/4.21
A/A
14.0
(4.0~18.0)
3.06/3.22
4.08/4.35
A/A
Hi:33 Me:31 Lo:30
Cooling:48 Heating:50
Hi:18 Me:16 Lo:14
100
5(15)
16.0
(4.0~20.0)
3.88/3.70
3.61/4.32
A/A
Hi:35 Me:33 Lo:31
Cooling:49 Heating:52
Hi:21 Me:19 Lo:17
Unit:246x840x840 Panel:35x950x950
27.5(Unit:22 Panel:5.5)
T-PSA-3AW-E
29.5(Unit:24 Panel:5.5)
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43* 3
-20~20
16.0
(4.0~20.0)
3.88/3.76
3.61/4.26
A/A
Hi:33 Me:31 Lo:30
Hi:18 Me:16 Lo:14
27.5(Unit:22 Panel:5.5)
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 71/100VNXPVD 39dB, 100VSXPVD 39dB, 125/140VNXPVD 46dB, 125/140VSXPVD 46dB, 140VNXTVD 39dB,
140VSXTVD 39dB
Air flow: 71/100VNXPVD 20CMM, 100VSXPVD 20CMM, 125/140VNXPVD 28CMM, 125/140VSXPVD 28CMM, 140VNXTVD 20CMM, 140VSXTVD 20CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor* 2
Outdoor
Air flow
Net weight
Ref.amount precharged
Ref.piping size
Range of usage
Ref.piping length
Vertical height difference
Operating temperature range
Indoor* 2
Outdoor
Exterior dimensions
Net weight
Panel
Air filter, Q'ty
Height x Width x Depth
Unit+Panel
Remote control(option)
Exterior dimensions
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg kg kg(m)
ø m m m
O/U
O/U
FDT100VNPVD
FDT50VD
FDC100VN
FDT125VNPVD
Twin
FDT60VD
FDC125VN
FDT140VNPVD
FDT71VD
FDC140VN
Micro Inverter
FDT140VNTVD
Triple
FDT50VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
14.0
(5.0~14.5)
FDT100VSPVD FDT125VSPVD
Twin
FDT140VSPVD
FDT50VD
FDC100VS
FDT60VD
FDC125VS
FDT71VD
FDC140VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
11.2
(4.0~12.5)
14.0
(4.0~16.0)
16.0
(4.0~16.5)
16.0
(4.0~16.5)
11.2
(4.0~12.5)
14.0
(4.0~16.0)
2.94/3.09
3.40/3.62
A/A
3.95/3.70
3.16/3.78
B/A
4.51/4.58
3.10/3.49
B/B
Hi:33
Me:31 Lo:30
49
Hi:33
Me:31 Lo:30
5(24)
Hi:35
Me:33 Lo:31
Cooling:50 Heating:51
Hi:18 Me:16 Lo:14
Hi:21
Me:19 Lo:17
4.65/4.63
3.01/3.46
B/B
2.94/3.09
3.40/3.62
A/A
3.95/3.70
3.16/3.78
B/A
5(15)
51
Hi:33
Me:31 Lo:30
Hi:18
Me:16 Lo:14
Cooling:75 Heating:73
Hi:33
Me:31 Lo:30
49
Hi:33
Me:31 Lo:30
Cooling:50 Heating:51
Hi:18 Me:16 Lo:14
27.5(Unit:22 Panel:5.5)
Unit:246x840x840 Panel:35x950x950
29.5(Unit:24 Panel:5.5) 27.5(Unit:22 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
845x970x370
81
3.8(30)
9.52/15.88
50
30
15
-15~43* 3
-20~20
16.0
(4.0~16.5)
4.51/4.58
3.10/3.49
B/B
Hi:35
Me:33 Lo:31
51
Hi:21
Me:19 Lo:17
29.5(Unit:24 Panel:5.5)
83
Powerful-Hi can be selected. Sound level: 100VNPVD 39dB, 125/140VNPVD 46dB, 140VNTVD 39dB, 100VSPVD 39dB, 125/140VSPVD 46dB
Air flow: 100VNPVD 20CMM, 125/140VNPVD 28CMM, 140VNTVD 20CMM, 100VSPVD 20CMM, 125/140VSPVD 28CMM
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Indoor* 2
Exterior dimensions
Net weight
Panel
Outdoor
Height x Width x Depth
Unit+Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Ref.amount precharged
Height x Width x Depth
Ref.piping size Liquid/Gas
Range of usage
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDT200VSPVD
Twin
FDT250VSPVD
FDT100VD
FDC200VS
FDT125VD
FDC250VS
20.0
(7.0~22.4)
25.0
(10.0~28.0)
Micro Inverter
FDT140VSTVD FDT200VSTVD
FDT50VD
FDC140VS
Triple
FDT71VD
FDC200VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
14.0
(5.0~14.5)
20.0
(7.0~22.4)
FDT200VSDVD
20.0
(7.0~22.4)
FDT250VSDVD
Double Twin
FDT50VD FDT60VD
FDC200VS FDC250VS
25.0
(10.0~28.0)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
16.0
(4.0~16.5)
22.4
(7.6~25.0)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
6.58/6.02
3.04/3.72
B/A
5(19)
Hi:40
Me:37 Lo:35
8.30/7.75
3.01/3.61
B/A
5(22)
Hi:42
Me:40 Lo:37
57
Hi:27
Cooling:57 Heating:58
Hi:30
Me:24 Lo:20 Me:27 Lo:23
Cooling:150 Heating:145
Unit:298x840x840 Panel:35x950x950
32.5(Unit:27 Panel:5.5)
4.65/4.63
3.01/3.46
B/B
5(15)
Hi:33
Me:31 Lo:30
51
Hi:18
Me:16 Lo:14
Cooling:75 Heating:73
6.49/6.12
3.08/3.66
B/A
5(19)
Hi:35
Me:33 Lo:31
57
Hi:21
Me:19 Lo:17
Cooling:150 Heating:145
6.58/6.15
3.04/3.64
B/A
5(19)
Hi:33
Me:31 Lo:30
57
8.28/7.70
3.02/3.64
B/A
5(22)
Hi:18
Me:16 Lo:14
Cooling:150 Heating:145
27.5(Unit:22 Panel:5.5)
Unit:246x840x840 Panel:35x950x950
29.5(Unit:24 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
27.5(Unit:22 Panel:5.5)
1,300x970x370
122
5.4(30)
9.52/22.22
70
140
7.2(30)
12.7/22.22
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
1,505x970x370 845x970x370
83
3.8(30)
9.52/15.88
50
1,300x970x370
122
5.4(30)
9.52/22.22
30
15
-15~43* 3
-15~20 -20~20
70
-15~20
Hi:33
Me:31 Lo:30
Cooling:57 Heating:58
29.5(Unit:24 Panel:5.5)
1,505x970x370
140
7.2(30)
12.7/22.22
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 200/250VSPVD 51dB, 140VSTVD 39dB, 200VSTVD 46dB, 200VSDVD 39dB, 250VSDVD 46dB
Air flow: 200/250VSPVD 37CMM, 140VSTVD 20CMM, 200VSTVD 28CMM, 200VSDVD 20CMM, 250VSDVD 28CMM
27
MULTI [ INDOOR UNIT ]
CEILING CASSETTE -4way-
FDT
Wired remote control
RC-E4
(Option)
RCH-E3
(Option)
FDT 40/50/60/71/100/125VD
Wireless remote control
RCN-T-36W-E
(Option)
A
CLASS
The values are for simultaneous Multi operation.
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor* 2
Outdoor
Height x Width x Depth
Unit+Panel
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDT71VNXPVD FDT100VNXPVD
Twin
FDT40VD
FDC71VNX
FDT50VD
FDC100VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
7.1
(3.2~8.0)
10.0
(4.0~11.2)
8.0
(3.6~9.0)
11.2
(4.0~12.5)
1.85/1.99
3.84/4.02
2.56/2.66
3.91/4.21
A/A A/A
5(17) 5(24)
Hi:33 Me:31 Lo:30
Cooling:51 Heating:48 Cooling:48 Heating:50
Hi:18 Me:16 Lo:14
Cooling:60 Heating:50 100
Unit:246x840x840 Panel:35x950x950
27.5(Unit:22 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
750x880(+88)x340
60
2.95(30)
1,300x970x370
9.52/15.88
105
4.5(30)
50 100
30
15
-15~43* 3
-20~20
SPECIFICATIONS The values are for simultaneous Multi operation.
26
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor* 2
Outdoor
Height x Width x Depth
Unit+Panel
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDT125VNXPVD FDT140VNXPVD FDT140VNXTVD FDT100VSXPVD
FDT60VD
FDC125VNX
Twin
FDT71VD
FDC140VNX
Triple
FDT50VD
FDC140VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(5.0~16.0)
FDT50VD
FDC100VSX
FDT125VSXPVD
Twin
FDT60VD
FDC125VSX
FDT140VSXPVD
FDT71VD
FDC140VSX
FDT140VSXTVD
Triple
FDT50VD
FDC140VSX
10.0
(4.0~11.2)
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~14.5)
14.0
(5.0~14.5)
14.0
(4.0~17.0)
3.06/3.22
4.08/4.35
A/A
Hi:33 Me:31 Lo:30
Cooling:48 Heating:50
Hi:18 Me:16 Lo:14
16.0
(4.0~18.0)
3.88/3.70
3.61/4.32
A/A
29.5(Unit:24 Panel:5.5)
16.0
(4.0~18.0)
3.88/3.76
3.61/4.26
A/A
5(26)
Hi:35 Me:33 Lo:31 Hi:33 Me:31 Lo:30
Cooling:49 Heating:52
Hi:21 Me:19 Lo:17 Hi:18 Me:16 Lo:14
11.2
(4.0~16.0)
2.56/2.66
3.91/4.21
A/A
14.0
(4.0~18.0)
3.06/3.22
4.08/4.35
A/A
Hi:33 Me:31 Lo:30
Cooling:48 Heating:50
Hi:18 Me:16 Lo:14
100
5(15)
16.0
(4.0~20.0)
3.88/3.70
3.61/4.32
A/A
Hi:35 Me:33 Lo:31
Cooling:49 Heating:52
Hi:21 Me:19 Lo:17
Unit:246x840x840 Panel:35x950x950
27.5(Unit:22 Panel:5.5)
T-PSA-3AW-E
29.5(Unit:24 Panel:5.5)
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43* 3
-20~20
16.0
(4.0~20.0)
3.88/3.76
3.61/4.26
A/A
Hi:33 Me:31 Lo:30
Hi:18 Me:16 Lo:14
27.5(Unit:22 Panel:5.5)
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 71/100VNXPVD 39dB, 100VSXPVD 39dB, 125/140VNXPVD 46dB, 125/140VSXPVD 46dB, 140VNXTVD 39dB,
140VSXTVD 39dB
Air flow: 71/100VNXPVD 20CMM, 100VSXPVD 20CMM, 125/140VNXPVD 28CMM, 125/140VSXPVD 28CMM, 140VNXTVD 20CMM, 140VSXTVD 20CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor* 2
Outdoor
Air flow
Net weight
Ref.amount precharged
Ref.piping size
Range of usage
Ref.piping length
Vertical height difference
Operating temperature range
Indoor* 2
Outdoor
Exterior dimensions
Net weight
Panel
Air filter, Q'ty
Height x Width x Depth
Unit+Panel
Remote control(option)
Exterior dimensions
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg kg kg(m)
ø m m m
O/U
O/U
FDT100VNPVD
FDT50VD
FDC100VN
FDT125VNPVD
Twin
FDT60VD
FDC125VN
FDT140VNPVD
FDT71VD
FDC140VN
Micro Inverter
FDT140VNTVD
Triple
FDT50VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
14.0
(5.0~14.5)
FDT100VSPVD FDT125VSPVD
Twin
FDT140VSPVD
FDT50VD
FDC100VS
FDT60VD
FDC125VS
FDT71VD
FDC140VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
11.2
(4.0~12.5)
14.0
(4.0~16.0)
16.0
(4.0~16.5)
16.0
(4.0~16.5)
11.2
(4.0~12.5)
14.0
(4.0~16.0)
2.94/3.09
3.40/3.62
3.95/3.70
3.16/3.78
4.51/4.58
3.10/3.49
4.65/4.63
3.01/3.46
2.94/3.09
3.40/3.62
3.95/3.70
3.16/3.78
A/A
Hi:33
Me:31 Lo:30
49
B/A
Hi:33
Me:31 Lo:30
Hi:18 Me:16 Lo:14
5(24)
Cooling:50 Heating:51
B/B
Hi:35
Me:33 Lo:31
51
B/B
Hi:33
Me:31 Lo:30
Hi:21 Hi:18
Me:19 Lo:17 Me:16 Lo:14
Cooling:75 Heating:73
A/A
Hi:33
Me:31 Lo:30
49
B/A
5(15)
Hi:33
Me:31 Lo:30
Cooling:50 Heating:51
Hi:18 Me:16 Lo:14
27.5(Unit:22 Panel:5.5)
Unit:246x840x840 Panel:35x950x950
29.5(Unit:24 Panel:5.5) 27.5(Unit:22 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
845x970x370
81
3.8(30)
9.52/15.88
50
30
15
-15~43* 3
-20~20
16.0
(4.0~16.5)
4.51/4.58
3.10/3.49
B/B
Hi:35
Me:33 Lo:31
51
Hi:21
Me:19 Lo:17
29.5(Unit:24 Panel:5.5)
83
Powerful-Hi can be selected. Sound level: 100VNPVD 39dB, 125/140VNPVD 46dB, 140VNTVD 39dB, 100VSPVD 39dB, 125/140VSPVD 46dB
Air flow: 100VNPVD 20CMM, 125/140VNPVD 28CMM, 140VNTVD 20CMM, 100VSPVD 20CMM, 125/140VSPVD 28CMM
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Indoor* 2
Exterior dimensions
Net weight
Panel
Outdoor
Height x Width x Depth
Unit+Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Ref.amount precharged
Height x Width x Depth
Ref.piping size Liquid/Gas
Range of usage
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDT200VSPVD
Twin
FDT250VSPVD
FDT100VD
FDC200VS
FDT125VD
FDC250VS
20.0
(7.0~22.4)
25.0
(10.0~28.0)
Micro Inverter
FDT140VSTVD FDT200VSTVD
FDT50VD
FDC140VS
Triple
FDT71VD
FDC200VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
14.0
(5.0~14.5)
20.0
(7.0~22.4)
FDT200VSDVD FDT250VSDVD
Double Twin
FDT50VD FDT60VD
FDC200VS FDC250VS
20.0
(7.0~22.4)
25.0
(10.0~28.0)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
16.0
(4.0~16.5)
22.4
(7.6~25.0)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
6.58/6.02
3.04/3.72
B/A
5(19)
Hi:40
Me:37 Lo:35
8.30/7.75
3.01/3.61
B/A
5(22)
Hi:42
Me:40 Lo:37
57
Hi:27
Cooling:57 Heating:58
Hi:30
Me:24 Lo:20 Me:27 Lo:23
Cooling:150 Heating:145
Unit:298x840x840 Panel:35x950x950
32.5(Unit:27 Panel:5.5)
4.65/4.63
3.01/3.46
B/B
5(15)
Hi:33
Me:31 Lo:30
51
Hi:18
Me:16 Lo:14
Cooling:75 Heating:73
6.49/6.12
3.08/3.66
B/A
5(19)
Hi:35
Me:33 Lo:31
57
Hi:21
Me:19 Lo:17
Cooling:150 Heating:145
6.58/6.15
3.04/3.64
B/A
5(19)
Hi:33
Me:31 Lo:30
57
8.28/7.70
3.02/3.64
B/A
5(22)
Hi:18
Me:16 Lo:14
Cooling:150 Heating:145
27.5(Unit:22 Panel:5.5)
Unit:246x840x840 Panel:35x950x950
29.5(Unit:24 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
27.5(Unit:22 Panel:5.5)
1,300x970x370
122
5.4(30)
9.52/22.22
70
140
7.2(30)
12.7/22.22
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
1,505x970x370 845x970x370
83
3.8(30)
9.52/15.88
50
1,300x970x370
122
5.4(30)
9.52/22.22
30
15
-15~43* 3
-15~20 -20~20
70
-15~20
Hi:33
Me:31 Lo:30
Cooling:57 Heating:58
29.5(Unit:24 Panel:5.5)
1,505x970x370
140
7.2(30)
12.7/22.22
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 200/250VSPVD 51dB, 140VSTVD 39dB, 200VSTVD 46dB, 200VSDVD 39dB, 250VSDVD 46dB
Air flow: 200/250VSPVD 37CMM, 140VSTVD 20CMM, 200VSTVD 28CMM, 200VSDVD 20CMM, 250VSDVD 28CMM
27
MULTI [ INDOOR UNIT ]
CEILING CASSETTE -4way Compact (600 X 600mm)-
FDTC
A
CLASS
Wired remote control
FDTC 40/50/60VD
Wireless remote control
RC-E4
(Option)
RCH-E3
(Option)
RCN-TC-24W-ER
(Option)
SPECIFICATIONS The values are for simultaneous Multi operation.
28
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor* 2
Outdoor
Air flow
Indoor*
O/U is higher
O/U is lower
Cooling
Heating
2
Exterior dimensions
Net weight
Panel
Outdoor
Height x Width x Depth
Unit+Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Liquid/Gas kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDTC71VNXPVD
FDTC40VD
FDC71VNX
FDTC100VNXPVD
Twin
FDTC50VD
FDC100VNX
FDTC125VNXPVD
FDTC60VD
FDC125VNX
FDTC140VNXTVD
Triple
FDTC50VD
FDC140VNX
7.1
(3.2~8.0)
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
FDTC100VSXPVD
11.2
(4.0~16.0)
FDTC125VSXPVD FDTC140VSXTVD
FDTC50VD
FDC100VSX
Twin
FDTC60VD
FDC125VSX
Triple
FDTC50VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(4.0~18.0)
16.0
(4.0~20.0)
8.0
(3.6~9.0)
11.2
(4.0~12.5)
14.0
(4.0~17.0)
16.0
(4.0~18.0)
1.99/2.18
3.57/3.67
A/A
5(17)
Heating : Hi:42 Me:36 Lo:32
Cooling:51 Heating:48
2.78/3.02
3.60/3.71
A/A
5(24)
Cooling : Hi:42 Me:36 Lo:30
4.10/4.10
3.05/3.41
B/B
5(26)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
Cooling:48 Heating:50
4.34/4.34
3.23/3.69
A/A
2.78/3.02
3.60/3.71
A/A
4.10/4.10
3.05/3.41
B/B
Cooling : Hi:42 Me:36 Lo:30
5(15)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:42 Me:36 Lo:32
Cooling:49 Heating:52
Heating : Hi:46 Me:39 Lo:32
Cooling:48 Heating:50
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Cooling:60 Heating:50
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
100
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
750x880(+88)x340
60
2.95(30)
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
1,300x970x370
105
4.5(30)
9.52/15.88
50 100
30
15
-15~43* 3
-20~20
4.34/4.34
3.23/3.69
A/A
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
Cooling:49 Heating:52
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 71/100/125VNXPVD 47dB, 100/125VSXPVD 47dB, 140VNXTVD 47dB, 140VSXTVD 47dB
Air flow: 71/100/125VNXPVD 13.5CMM, 100/125VSXPVD 13.5CMM, 140VNXTVD 13.5CMM, 140VSXTVD 13.5CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor* 2
Outdoor
Air flow
Indoor*
O/U is higher
O/U is lower
Cooling
Heating
2
Outdoor
Exterior dimensions
Net weight
Panel
Air filter, Q'ty
Height x Width x Depth
Unit+Panel
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size
Range of usage
Ref.piping length
Vertical height difference
Operating temperature range
Liquid/Gas kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDTC100VNPVD
FDTC50VD
FDC100VN
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.84/3.08
3.52/3.64
A/A
5(24)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
49
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Micro Inverter
FDTC125VNPVD
Twin
FDTC60VD
FDC125VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(4.0~16.0)
5.35/4.62
2.34/3.03
F/D
5(27)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
Cooling:50 Heating:51
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
Cooling:75 Heating:73
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
845x970x370
81
3.8(30)
9.52/15.88
50
30
15
-15~43* 3
-20~20
Powerful-Hi can be selected. Sound level: 100/125VNPVD 47dB, 140VNTVD 47dB
Air flow: 100/125VNPVD 13.5CMM, 140VNTVD 13.5CMM
FDTC140VNTVD
Triple
FDTC50VD
FDC140VN
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.64/4.52
3.02/3.54
B/B
5(24)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
51
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor* 2
Outdoor
Air flow
Indoor* 2
Exterior dimensions
Net weight
Panel
Outdoor
Height x Width x Depth
Unit+Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Ref.amount precharged
Height x Width x Depth
Liquid/Gas Ref.piping size
Range of usage
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDTC100VSPVD
FDTC50VD
FDC100VS
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.84/3.08
3.52/3.64
A/A
5(15)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
49
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Twin
FDTC125VSPVD
FDTC60VD
FDC125VS
Triple
FDTC50VD
FDC140VS
FDTC50VD
FDC200VS
12.5
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
(5.0~14.0)
14.0
(5.0~14.5)
20.0
(7.0~22.4)
14.0
(4.0~16.0)
Micro Inverter
FDTC140VSTVD
16.0
(4.0~16.5)
FDTC200VSDVD
22.4
(7.6~25.0)
FDTC250VSDVD
Double Twin
FDTC60VD
FDC250VS
25.0
(10.0~28.0)
28.0
(9.5~31.5)
5.35/4.62
2.34/3.03
F/D
5(15)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
Cooling:50 Heating:51
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
Cooling:75 Heating:73
4.64/4.52
3.02/3.54
7.33/6.98
2.73/3.21
11.28/10.19
2.22/2.75
B/B
5(15)
D/C
5(19)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
51 57
F/E
5(22)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
Cooling:57 Heating:58
Cooling : PHi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
Cooling:150 Heating:145
3.8(30)
9.52/15.88
50
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
845x970x370
83
1,300x970x370
122
5.4(30)
9.52/22.22
30
15
-15~43* 3
-20~20
70
-15~20
1,505x970x370
140
7.2(30)
12.7/22.22
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100/125VSPVD 47dB, 140VSTVD 47dB, 200/250VSDVD 47dB
Air flow: 100/125VSPVD 13.5CMM, 140VSTVD 13.5CMM, 200/250VSDVD 13.5CMM
29
MULTI [ INDOOR UNIT ]
CEILING CASSETTE -4way Compact (600 X 600mm)-
FDTC
A
CLASS
Wired remote control
FDTC 40/50/60VD
Wireless remote control
RC-E4
(Option)
RCH-E3
(Option)
RCN-TC-24W-ER
(Option)
SPECIFICATIONS The values are for simultaneous Multi operation.
28
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor* 2
Outdoor
Air flow
Indoor*
O/U is higher
O/U is lower
Cooling
Heating
2
Exterior dimensions
Net weight
Panel
Outdoor
Height x Width x Depth
Unit+Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Liquid/Gas kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDTC71VNXPVD
FDTC40VD
FDC71VNX
FDTC100VNXPVD
Twin
FDTC50VD
FDC100VNX
FDTC125VNXPVD
FDTC60VD
FDC125VNX
FDTC140VNXTVD
Triple
FDTC50VD
FDC140VNX
7.1
(3.2~8.0)
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
FDTC100VSXPVD
11.2
(4.0~16.0)
FDTC125VSXPVD FDTC140VSXTVD
FDTC50VD
FDC100VSX
Twin
FDTC60VD
FDC125VSX
Triple
FDTC50VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(4.0~18.0)
16.0
(4.0~20.0)
8.0
(3.6~9.0)
11.2
(4.0~12.5)
14.0
(4.0~17.0)
16.0
(4.0~18.0)
1.99/2.18
3.57/3.67
A/A
5(17)
Heating : Hi:42 Me:36 Lo:32
Cooling:51 Heating:48
2.78/3.02
3.60/3.71
A/A
5(24)
Cooling : Hi:42 Me:36 Lo:30
4.10/4.10
3.05/3.41
B/B
5(26)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
Cooling:48 Heating:50
4.34/4.34
3.23/3.69
A/A
2.78/3.02
3.60/3.71
A/A
4.10/4.10
3.05/3.41
B/B
Cooling : Hi:42 Me:36 Lo:30
5(15)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:42 Me:36 Lo:32
Cooling:49 Heating:52
Heating : Hi:46 Me:39 Lo:32
Cooling:48 Heating:50
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Cooling:60 Heating:50
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
100
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
750x880(+88)x340
60
2.95(30)
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
1,300x970x370
105
4.5(30)
9.52/15.88
50 100
30
15
-15~43* 3
-20~20
4.34/4.34
3.23/3.69
A/A
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
Cooling:49 Heating:52
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 71/100/125VNXPVD 47dB, 100/125VSXPVD 47dB, 140VNXTVD 47dB, 140VSXTVD 47dB
Air flow: 71/100/125VNXPVD 13.5CMM, 100/125VSXPVD 13.5CMM, 140VNXTVD 13.5CMM, 140VSXTVD 13.5CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor* 2
Outdoor
Air flow
Indoor*
O/U is higher
O/U is lower
Cooling
Heating
2
Outdoor
Exterior dimensions
Net weight
Panel
Air filter, Q'ty
Height x Width x Depth
Unit+Panel
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size
Range of usage
Ref.piping length
Vertical height difference
Operating temperature range
Liquid/Gas kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDTC100VNPVD
FDTC50VD
FDC100VN
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.84/3.08
3.52/3.64
A/A
5(24)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
49
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Micro Inverter
FDTC125VNPVD
Twin
FDTC60VD
FDC125VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(4.0~16.0)
5.35/4.62
2.34/3.03
F/D
5(27)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
Cooling:50 Heating:51
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
Cooling:75 Heating:73
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
845x970x370
81
3.8(30)
9.52/15.88
50
30
15
-15~43* 3
-20~20
Powerful-Hi can be selected. Sound level: 100/125VNPVD 47dB, 140VNTVD 47dB
Air flow: 100/125VNPVD 13.5CMM, 140VNTVD 13.5CMM
FDTC140VNTVD
Triple
FDTC50VD
FDC140VN
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.64/4.52
3.02/3.54
B/B
5(24)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
51
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor* 2
Outdoor
Air flow
Indoor* 2
Exterior dimensions
Net weight
Panel
Outdoor
Height x Width x Depth
Unit+Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Ref.amount precharged
Height x Width x Depth
Liquid/Gas Ref.piping size
Range of usage
Ref.piping length
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDTC100VSPVD
FDTC50VD
FDC100VS
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.84/3.08
3.52/3.64
A/A
5(15)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
49
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Twin
FDTC125VSPVD
FDTC60VD
FDC125VS
Triple
FDTC50VD
FDC140VS
FDTC50VD
FDC200VS
12.5
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
(5.0~14.0)
14.0
(5.0~14.5)
20.0
(7.0~22.4)
14.0
(4.0~16.0)
Micro Inverter
FDTC140VSTVD
16.0
(4.0~16.5)
FDTC200VSDVD
22.4
(7.6~25.0)
FDTC250VSDVD
Double Twin
FDTC60VD
FDC250VS
25.0
(10.0~28.0)
28.0
(9.5~31.5)
5.35/4.62
2.34/3.03
F/D
5(15)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
Cooling:50 Heating:51
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
Cooling:75 Heating:73
4.64/4.52
3.02/3.54
7.33/6.98
2.73/3.21
11.28/10.19
2.22/2.75
B/B
5(15)
D/C
5(19)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
51 57
F/E
5(22)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
Cooling:57 Heating:58
Cooling : PHi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
Cooling:150 Heating:145
3.8(30)
9.52/15.88
50
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
845x970x370
83
1,300x970x370
122
5.4(30)
9.52/22.22
30
15
-15~43* 3
-20~20
70
-15~20
1,505x970x370
140
7.2(30)
12.7/22.22
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100/125VSPVD 47dB, 140VSTVD 47dB, 200/250VSDVD 47dB
Air flow: 100/125VSPVD 13.5CMM, 140VSTVD 13.5CMM, 200/250VSDVD 13.5CMM
29
MULTI [ INDOOR UNIT ]
DUCT CONNECTED -Low/Middle Static pressure-
FDUM
SPECIFICATIONS external static pressure loss:5pa
Wired remote control
RC-E4
(Option)
RCH-E3
(Option)
FDUM 50/60/71/
100/125VD
Filter kit
UM-FL1E : for 50
UM-FL2E : for 60, 71
UM-FL3E : for 100, 125
(option)
Wireless remote control
RCN-KIT3-E
(Option)
A
CLASS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor* 2
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size Liquid/Gas
Ref.piping length
Range of usage
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDUM100VNXPVD FDUM125VNXPVD
Twin
FDUM50VD
FDC100VNX
FDUM60VD
FDC125VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
11.2
(4.0~12.5)
14.0
(4.0~17.0)
2.94/2.94
3.40/3.81
A/A
5(24)
3.86/4.10
3.24/3.41
A/B
5(26)
Hi:34 Me:31 Lo:28
Cooling:48 Heating:50
Hi:13 Me:12 Lo:11 Hi:16 Me:15 Lo:14
100
299x750x635
34
299x950x635
40
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43* 3
-20~20
SPECIFICATIONS The values are for simultaneous Multi operation.
30
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating kW kW kW
FDUM140VNXPVD
Twin
FDUM71VD
FDC140VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
14.0
(5.0~16.0)
14.0
(5.0~16.0)
16.0
(4.0~18.0)
FDUM140VNXTVD FDUM100VSXPVD
Triple
FDUM50VD
FDC140VNX
16.0
(4.0~18.0)
FDUM50VD
FDC100VSX
10.0
(4.0~11.2)
11.2
(4.0~16.0)
FDUM125VSXPVD FDUM140VSXPVD FDUM140VSXTVD
Twin
FDUM60VD
FDC125VSX
FDUM71VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(4.0~18.0)
16.0
(4.0~20.0)
Triple
FDUM50VD
FDC140VSX
14.0
(5.0~16.0)
16.0
(4.0~20.0)
4.60/4.69
4.60/4.69
2.94/2.94
3.86/4.10
4.60/4.69
4.60/4.69
COP Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Indoor* 2
Air flow
Exterior dimensions
Net weight
Air filter, Q'ty
Outdoor
Height x Width x Depth
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Ref.amount precharged
Ref.piping size Liquid/Gas
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
3.04/3.41
3.04/3.41
3.40/3.81
3.24/3.41
3.04/3.41
B/B B/B
5(26)
Hi:35 Me:32 Lo:29
Cooling:49 Heating:52 Cooling:49 Heating:52
Hi:20 Me:18 Lo:15
299x950x635
40
A/A
Hi:34 Me:31 Lo:28
A/B
Cooling:48 Heating:50
5(15)
B/B
Hi:35 Me:32 Lo:29
Cooling:49 Heating:52
Hi:13 Me:12 Lo:11 Hi:13 Me:12 Lo:11 Hi:16 Me:15 Lo:14
100
299x750x635
34
Procure locally
Hi:20 Me:18 Lo:15
299x950x635
40
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43* 3
-20~20
3.04/3.41
B/B
Hi:34 Me:31 Lo:28
Cooling:49 Heating:52
Hi:13 Me:12 Lo:11
299x750x635
34
*
*
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VNXPVD 35dB, 100VSXPVD 35dB, 125/140VNXPVD 38dB, 125/140VSXPVD 38dB, 140VNXTVD 35dB, 140VSXTVD 35dB
Air flow: 100VNXPVD 14CMM, 100VSXPVD 14CMM, 125/140VNXPVD 18CMM, 125/140VSXPVD 18CMM, 140VNXTVD 14CMM, 140VSXTVD 14CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating kW kW kW
FDUM100VNPVD
FDUM50VD
FDC100VN
10.0
(4.0~11.2)
11.2
(4.0~12.5)
3.12/3.27
3.21/3.43
FDUM125VNPVD
Twin
FDUM60VD
FDC125VN
12.5
(5.0~14.0)
14.0
(4.0~16.0)
Micro Inverter
FDUM140VNPVD
FDUM71VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDUM140VNTVD
Triple
FDUM50VD
FDC140VN
14.0
(5.0~14.5)
16.0
(4.0~16.5)
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Exterior dimensions
Net weight
Exterior dimensions
Net weight
Ref.amount precharged
Indoor* 2
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Height x Width x Depth
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
A/B
Hi:34 Me:31 Lo:28
49
Hi:13 Me:12 Lo:11
299x750x635
34
Powerful-Hi can be selected. Sound level: 100VNPVD 35dB, 125VNPVD 38dB, 140VNPVD 38dB, 140VNTVD 35dB, 100VSPVD 35dB
Air flow: 100VNPVD 14CMM, 125VNPVD 18CMM, 140VNPVD 23CMM, 140VNTVD 14CMM, 100VSPVD 14CMM
FDUM100VSPVD
Twin
FDUM50VD
FDC100VS
3Phase 380-415V 50Hz,
3Phase 380V 60Hz
10.0
(4.0~11.2)
14.0
(5.0~14.5)
16.0
(4.0~16.5)
11.2
(4.0~12.5)
4.47/4.51
2.80/3.10
50Hz:5.00/4.94
60Hz:5.00/4.80
50Hz:2.80/3.24
60Hz:2.80/3.33
C/D
Cooling:50 Heating:51
Hi:16 Me:15 Lo:14
C/C
Hi:34 Me:31 Lo:28
5(24)
Hi:35 Me:32 Lo:29
Hi:20 Me:18 Lo:15
Cooling:75 Heating:73
51
50Hz:5.09/5.03
60Hz:5.09/4.89
50Hz:2.75/3.18
60Hz:2.75/3.27
50Hz:D/D 60Hz:D/C
299x950x635
40
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
81
3.8(30)
9.52/15.88
50
30
15
-15~43* 3
-20~20
34
3.12/3.27
3.21/3.43
Hi:34 Me:31 Lo:28
Hi:13 Me:12 Lo:11
A/B
5(15)
49
299x750x635
83
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Indoor* 2
Air flow
Exterior dimensions
Net weight
Air filter, Q'ty
Exterior dimensions
Remote control(option)
Height x Width x Depth
Net weight
Ref.amount precharged
Outdoor
Height x Width x Depth
Liquid/Gas Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating mm kg kg(m)
ø m m m
O/U
O/U
The values are for simultaneous Multi operation.
kW kW kW
A dB(A)
CMM mm kg
Micro Inverter
FDUM125VSPVD FDUM140VSPVD FDUM200VSPVD
Twin
FDUM60VD
FDC125VS
12.5
(5.0~14.0)
FDUM71VD
FDC140VS
14.0
(5.0~14.5)
FDUM250VSPVD
FDUM100VD
FDC200VS
FDUM125VD
FDC250VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
20.0
(7.0~22.4)
25.0
(10.0~28.0)
FDUM140VSTVD
FDUM50VD
FDC140VS
14.0
(5.0~14.5)
FDUM200VSTVD
Triple
FDUM71VD
FDC200VS
20.0
(7.0~22.4)
22.4
(7.6~25.0)
14.0
(4.0~16.0)
16.0
(4.0~16.5)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
16.0
(4.0~16.5)
4.47/4.51
50Hz:5.00/4.94
60Hz:5.00/4.80
50Hz:2.80/3.24
2.80/3.10
C/D
5(15)
60Hz:2.80/3.33
C/C
Hi:34 Me:31 Lo:28
Cooling:50 Heating:51
Hi:35 Me:32 Lo:29
51
Hi:16 Me:15 Lo:14 Hi:20 Me:18 Lo:15
Cooling:75 Heating:73
299x950x635
40
845x970x370
83
3.8(30)
9.52/15.88
50
-20~20
6.86/6.72
2.92/3.33
9.31/8.35
2.69/3.35
C/C
5(19)
Hi:37 Me:35 Lo:32
57
D/C
5(22)
Hi:38 Me:36 Lo:33
Cooling:57 Heating:58
Hi:28 Me:25 Lo:22
Cooling:150 Heating:145
350x1,370x635
59
50Hz:5.09/5.03
60Hz:5.09/4.89
50Hz:2.75/3.18
60Hz:2.75/3.27
50Hz:D/D 60Hz:D/C
5(15)
Hi:34 Me:31 Lo:28
51
Hi:13 Me:12 Lo:11
Cooling:75 Heating:73
15
-15~43* 3
-15~20
299x750x635
34
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370 1,505x970x370
122
5.4(30)
9.52/22.22
70
30
140
7.2(30)
12.7/22.22
845x970x370
83
3.8(30)
9.52/15.88
50
-20~20
6.88/6.74
2.91/3.32
C/C
5(19)
Hi:35 Me:32 Lo:29
57
Hi:20 Me:18 Lo:15
Cooling:150 Heating:145
1,300x970x370
122
1,300x970x370
122
5.4(30)
9.52/22.22
70
-15~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure of indoor units is 60Pa.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 125/140VSPVD 38dB, 200/250VSPVD 41dB, 140VSTVD 35dB, 200VSTVD 38dB
Air flow: 125VSPVD 18CMM, 140VSPVD 23CMM, 200/250VSPVD 34CMM, 140VSTVD 14CMM, 200VSTVD 23CMM
31
MULTI [ INDOOR UNIT ]
DUCT CONNECTED -Low/Middle Static pressure-
FDUM
SPECIFICATIONS external static pressure loss:5pa
Wired remote control
RC-E4
(Option)
RCH-E3
(Option)
FDUM 50/60/71/
100/125VD
Filter kit
UM-FL1E : for 50
UM-FL2E : for 60, 71
UM-FL3E : for 100, 125
(option)
Wireless remote control
RCN-KIT3-E
(Option)
A
CLASS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor* 2
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size Liquid/Gas
Ref.piping length
Range of usage
Vertical height difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDUM100VNXPVD FDUM125VNXPVD
Twin
FDUM50VD
FDC100VNX
FDUM60VD
FDC125VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
11.2
(4.0~12.5)
14.0
(4.0~17.0)
2.94/2.94
3.40/3.81
A/A
5(24)
3.86/4.10
3.24/3.41
A/B
5(26)
Hi:34 Me:31 Lo:28
Cooling:48 Heating:50
Hi:13 Me:12 Lo:11 Hi:16 Me:15 Lo:14
100
299x750x635
34
299x950x635
40
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43* 3
-20~20
SPECIFICATIONS The values are for simultaneous Multi operation.
30
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating kW kW kW
FDUM140VNXPVD
Twin
FDUM71VD
FDC140VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
14.0
(5.0~16.0)
14.0
(5.0~16.0)
16.0
(4.0~18.0)
FDUM140VNXTVD FDUM100VSXPVD
Triple
FDUM50VD
FDC140VNX
16.0
(4.0~18.0)
FDUM50VD
FDC100VSX
10.0
(4.0~11.2)
11.2
(4.0~16.0)
FDUM125VSXPVD FDUM140VSXPVD FDUM140VSXTVD
Twin
FDUM60VD
FDC125VSX
FDUM71VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(4.0~18.0)
16.0
(4.0~20.0)
Triple
FDUM50VD
FDC140VSX
14.0
(5.0~16.0)
16.0
(4.0~20.0)
4.60/4.69
4.60/4.69
2.94/2.94
3.86/4.10
4.60/4.69
4.60/4.69
COP Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Indoor* 2
Air flow
Exterior dimensions
Net weight
Air filter, Q'ty
Outdoor
Height x Width x Depth
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Ref.amount precharged
Ref.piping size Liquid/Gas
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
3.04/3.41
3.04/3.41
3.40/3.81
3.24/3.41
3.04/3.41
B/B B/B
5(26)
Hi:35 Me:32 Lo:29
Cooling:49 Heating:52 Cooling:49 Heating:52
Hi:20 Me:18 Lo:15
299x950x635
40
A/A
Hi:34 Me:31 Lo:28
A/B
Cooling:48 Heating:50
5(15)
B/B
Hi:35 Me:32 Lo:29
Cooling:49 Heating:52
Hi:13 Me:12 Lo:11 Hi:13 Me:12 Lo:11 Hi:16 Me:15 Lo:14
100
299x750x635
34
Procure locally
Hi:20 Me:18 Lo:15
299x950x635
40
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43* 3
-20~20
3.04/3.41
B/B
Hi:34 Me:31 Lo:28
Cooling:49 Heating:52
Hi:13 Me:12 Lo:11
299x750x635
34
*
*
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VNXPVD 35dB, 100VSXPVD 35dB, 125/140VNXPVD 38dB, 125/140VSXPVD 38dB, 140VNXTVD 35dB, 140VSXTVD 35dB
Air flow: 100VNXPVD 14CMM, 100VSXPVD 14CMM, 125/140VNXPVD 18CMM, 125/140VSXPVD 18CMM, 140VNXTVD 14CMM, 140VSXTVD 14CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating kW kW kW
FDUM100VNPVD
FDUM50VD
FDC100VN
10.0
(4.0~11.2)
11.2
(4.0~12.5)
3.12/3.27
3.21/3.43
FDUM125VNPVD
Twin
FDUM60VD
FDC125VN
12.5
(5.0~14.0)
14.0
(4.0~16.0)
Micro Inverter
FDUM140VNPVD
FDUM71VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDUM140VNTVD
Triple
FDUM50VD
FDC140VN
14.0
(5.0~14.5)
16.0
(4.0~16.5)
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Exterior dimensions
Net weight
Exterior dimensions
Net weight
Ref.amount precharged
Indoor* 2
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Height x Width x Depth
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
A/B
Hi:34 Me:31 Lo:28
49
Hi:13 Me:12 Lo:11
299x750x635
34
Powerful-Hi can be selected. Sound level: 100VNPVD 35dB, 125VNPVD 38dB, 140VNPVD 38dB, 140VNTVD 35dB, 100VSPVD 35dB
Air flow: 100VNPVD 14CMM, 125VNPVD 18CMM, 140VNPVD 23CMM, 140VNTVD 14CMM, 100VSPVD 14CMM
FDUM100VSPVD
Twin
FDUM50VD
FDC100VS
3Phase 380-415V 50Hz,
3Phase 380V 60Hz
10.0
(4.0~11.2)
14.0
(5.0~14.5)
16.0
(4.0~16.5)
11.2
(4.0~12.5)
4.47/4.51
2.80/3.10
50Hz:5.00/4.94
60Hz:5.00/4.80
50Hz:2.80/3.24
60Hz:2.80/3.33
C/D
Hi:34 Me:31 Lo:28
Cooling:50 Heating:51
Hi:16 Me:15 Lo:14
C/C
5(24)
Hi:35 Me:32 Lo:29
Hi:20 Me:18 Lo:15
Cooling:75 Heating:73
51
50Hz:5.09/5.03
60Hz:5.09/4.89
50Hz:2.75/3.18
60Hz:2.75/3.27
50Hz:D/D 60Hz:D/C
299x950x635
40
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
81
3.8(30)
9.52/15.88
50
30
15
-15~43* 3
-20~20
34
3.12/3.27
3.21/3.43
Hi:34 Me:31 Lo:28
Hi:13 Me:12 Lo:11
A/B
5(15)
49
299x750x635
83
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Indoor* 2
Air flow
Exterior dimensions
Net weight
Air filter, Q'ty
Exterior dimensions
Remote control(option)
Height x Width x Depth
Net weight
Ref.amount precharged
Outdoor
Height x Width x Depth
Liquid/Gas Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating mm kg kg(m)
ø m m m
O/U
O/U
The values are for simultaneous Multi operation.
kW kW kW
A dB(A)
CMM mm kg
Micro Inverter
FDUM125VSPVD FDUM140VSPVD FDUM200VSPVD
Twin
FDUM60VD
FDC125VS
12.5
(5.0~14.0)
FDUM71VD
FDC140VS
14.0
(5.0~14.5)
FDUM250VSPVD
FDUM100VD
FDC200VS
FDUM125VD
FDC250VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
20.0
(7.0~22.4)
25.0
(10.0~28.0)
FDUM140VSTVD
FDUM50VD
FDC140VS
14.0
(5.0~14.5)
FDUM200VSTVD
Triple
FDUM71VD
FDC200VS
20.0
(7.0~22.4)
22.4
(7.6~25.0)
14.0
(4.0~16.0)
16.0
(4.0~16.5)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
16.0
(4.0~16.5)
4.47/4.51
50Hz:5.00/4.94
60Hz:5.00/4.80
50Hz:2.80/3.24
2.80/3.10
C/D
5(15)
60Hz:2.80/3.33
C/C
Hi:34 Me:31 Lo:28
Cooling:50 Heating:51
Hi:35 Me:32 Lo:29
51
Hi:16 Me:15 Lo:14 Hi:20 Me:18 Lo:15
Cooling:75 Heating:73
299x950x635
40
845x970x370
83
3.8(30)
9.52/15.88
50
-20~20
6.86/6.72
2.92/3.33
9.31/8.35
2.69/3.35
C/C
5(19)
Hi:37 Me:35 Lo:32
57
D/C
5(22)
Hi:38 Me:36 Lo:33
Cooling:57 Heating:58
Hi:28 Me:25 Lo:22
Cooling:150 Heating:145
350x1,370x635
59
50Hz:5.09/5.03
60Hz:5.09/4.89
50Hz:2.75/3.18
60Hz:2.75/3.27
50Hz:D/D 60Hz:D/C
5(15)
Hi:34 Me:31 Lo:28
51
Hi:13 Me:12 Lo:11
Cooling:75 Heating:73
15
-15~43* 3
-15~20
299x750x635
34
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370 1,505x970x370
122
5.4(30)
9.52/22.22
70
30
140
7.2(30)
12.7/22.22
845x970x370
83
3.8(30)
9.52/15.88
50
-20~20
6.88/6.74
2.91/3.32
C/C
5(19)
Hi:35 Me:32 Lo:29
57
Hi:20 Me:18 Lo:15
Cooling:150 Heating:145
1,300x970x370
122
1,300x970x370
122
5.4(30)
9.52/22.22
70
-15~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure of indoor units is 60Pa.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 125/140VSPVD 38dB, 200/250VSPVD 41dB, 140VSTVD 35dB, 200VSTVD 38dB
Air flow: 125VSPVD 18CMM, 140VSPVD 23CMM, 200/250VSPVD 34CMM, 140VSTVD 14CMM, 200VSTVD 23CMM
31
32
MULTI [ INDOOR UNIT ]
CEILING SUSPENDED
FDEN
Wired remote control
RC-E4
(Option)
FDEN 40/50/60/71/100/125VD
RCH-E3
(Option)
Wireless remote control
RCN-E1R
(Option)
A
CLASS
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
Air flow
1
Indoor* 2
Outdoor
Indoor* 2
Outdoor
Height x Width x Depth Exterior dimensions
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
ISO-T1(JIS)
ISO-T1(JIS)
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDEN71VNXPVD FDEN100VNXPVD
Twin
FDEN40VD
FDC71VNX
FDEN50VD
FDC100VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
7.1
(3.2~8.0)
10.0
(4.0~11.2)
8.0
(3.6~9.0)
11.2
(4.0~12.5)
1.98/2.40
3.59/3.33
A/C
5(17)
3.02/3.18
3.31/3.52
A/B
5(24)
Hi:39 Me:38 Lo:37
Cooling:51 Heating:48 Cooling:48 Heating:50
Hi:11 Me:9 Lo:7
Cooling:60 Heating:50 100
210x1,070x690
28
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
750X880(+88)X340
60
2.95(30)
1,300x970x370
105
4.5(30)
9.52/15.88
50 100
30
15
-15~43* 3
-20~20
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor* 2
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDEN125VNXPVD FDEN140VNXPVD
FDEN60VD
FDC125VNX
Twin
FDEN71VD
FDC140VNX
FDEN140VNXTVD
Triple
FDEN50VD
FDC140VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(5.0~16.0)
14.0
(4.0~17.0)
16.0
(4.0~18.0)
16.0
(4.0~18.0)
FDEN100VSXPVD FDEN125VSXPVD FDEN140VSXPVD FDEN140VSXTVD
FDEN50VD
FDC100VSX
Twin
FDEN60VD
FDC125VSX
Triple
FDEN50VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(5.0~16.0)
11.2
(4.0~16.0)
14.0
(4.0~18.0)
FDEN71VD
FDC140VSX
16.0
(4.0~20.0)
16.0
(4.0~20.0)
3.86/3.70
3.24/3.78
A/A
4.78/4.43
2.93/3.61
C/A
Hi:41 Me:39 Lo:38
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:18 Me:14 Lo:12
5(26)
Hi:39 Me:38 Lo:37
Cooling:49 Heating:52
Hi:11 Me:9 Lo:7
49
100
210x1,320x690
37
4.72/4.38
2.97/3.65
C/A
3.02/3.18
3.31/3.52
A/B
3.86/3.70
3.24/3.78
A/A
4.78/4.43
2.93/3.61
C/A
5(15)
Hi:41 Me:39 Lo:38
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:18 Me:14 Lo:12
210x1,070x690
28
210x1,320x690
37
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43* 3
-20~20
4.72/4.38
2.97/3.65
C/A
Hi:39 Me:38 Lo:37
Cooling:49 Heating:52
Hi:11 Me:9 Lo:7
210x1,070x690
28
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 71/100VNXPVD 46dB, 100VSXPVD 46dB, 125/140VNXPVD 50dB, 125/140VSXPVD 50dB, 140VNXTVD 46dB, 140VSXTVD 46dB
Air flow: 71/100VNXPVD 13CMM, 100VSXPVD 13CMM, 125/140VNXPVD 22CMM, 125/140VSXPVD 22CMM, 140VNXTVD 13CMM, 140VSXTVD 13CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Air flow
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Indoor* 2
Outdoor
Indoor*
Cooling
Heating
2
Exterior dimensions
Net weight
Exterior dimensions
Net weight
Ref.amount precharged
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Height x Width x Depth
Liquid/Gas
O/U is higher
O/U is lower kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDEN100VNPVD
FDEN50VD
FDC100VN
10.0
(4.0~11.2)
11.2
(4.0~12.5)
3.12/3.28
3.21/3.41
A/B
Hi:39 Me:38 Lo:37
49
Hi:11 Me:9 Lo:7
14.0
(4.0~16.0)
4.23/3.83
2.96/3.66
C/A
16.0
(4.0~16.5)
4.87/4.59
2.87/3.49
C/B
Hi:41 Me:39 Lo:38
Cooling:50 Heating:51
5(24)
Hi:18 Me:14 Lo:12
Micro Inverter
FDEN125VNPVD
Twin
FDEN60VD
FDC125VN
FDEN140VNPVD
FDEN71VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~14.5)
51
FDEN140VNTVD
Triple
FDEN50VD
FDC140VN
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.88/4.58
2.87/3.49
C/B
FDEN100VSPVD
Twin
FDEN125VSPVD
FDEN50VD
FDC100VS
FDEN60VD
FDC125VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
11.2
(4.0~12.5)
3.12/3.28
3.21/3.41
A/B
Hi:39 Me:38 Lo:37
Hi:11 Me:9 Lo:7
49
14.0
(4.0~16.0)
4.23/3.83
2.96/3.66
C/A
5(15)
Hi:41
Me:39 Lo:38
Cooling:50 Heating:51
Hi:18
Me:14 Lo:12
210x1,070x690
28
Cooling:75 Heating:73
210x1,320x690
37 28
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
845x970x370
210x1,070x690
81
3.8(30)
9.52/15.88
50
30
15
-15~43* 3
-20~20
Powerful-Hi can be selected. Sound level: 100VNPVD 46dB, 125/140VNPVD 50dB, 140VNTVD 46dB, 100VSPVD 46dB, 125VSPVD 50dB
Air flow: 100VNPVD 13CMM, 125/140VNPVD 22CMM, 140VNTVD 13CMM, 100VSPVD 13CMM, 125VSPVD 22CMM
83
210x1,320x690
37
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor* 2
Outdoor
Air flow
Indoor* 2
Exterior dimensions
Net weight
Air filter, Q'ty
Exterior dimensions
Remote control(option)
Height x Width x Depth
Net weight
Ref.amount precharged
Outdoor
Height x Width x Depth
Liquid/Gas Ref.piping size
Ref.piping length
Vertical height
difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDEN140VSPVD
FDEN71VD
FDC140VS
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.87/4.59
2.87/3.49
C/B
5(15)
Hi:41
Me:39 Lo:38
51
Hi:18
Me:14 Lo:12
Cooling:75 Heating:73
210x1,320x690
37
845x970x370
83
3.8(30)
9.52/15.88
50
-20~20
FDEN200VSPVD
Twin
FDEN100VD
FDC200VS
Micro Inverter
FDEN250VSPVD
FDEN125VD
FDC250VS
FDEN140VSTVD
FDEN50VD
FDC140VS
FDEN200VSTVD FDEN200VSDVD FDEN250VSDVD
Triple
FDEN71VD
FDC200VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
25.0
(10.0~28.0)
14.0
(5.0~14.5)
20.0
(7.0~22.4)
FDEN50VD
FDC200VS
20.0
Double Twin
(7.0~22.4)
FDEN60VD
FDC250VS
25.0
(10.0~28.0)
20.0
(7.0~22.4)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
16.0
(4.0~16.5)
22.4
(7.6~25.0)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
6.47/5.97
3.09/3.75
B/A
5(19)
Hi:44
9.01/8.05
2.77/3.48
D/B
5(22)
Hi:46
Me:41 Lo:39
57
Hi:26
Me:23 Lo:21
Me:44 Lo:43
Cooling:57 Heating:58
Cooling:150 Heating:145
250x1,620x690
49
Hi:29
Me:26 Lo:23
4.88/4.58
2.87/3.49
C/B
5(15)
Hi:39
Me:38 Lo:37
51
Hi:11
Me:9 Lo:7
Cooling:75 Heating:73
6.40/5.90
3.13/3.80
B/A
Hi:41
Me:39 Lo:38
Hi:18
5(19)
57
7.43/7.26
2.69/3.09
D/D
Hi:39
Me:38 Lo:37
Hi:11
Me:39 Lo:38
Cooling:57 Heating:58
Me:14 Lo:12 Me:9 Lo:7
Cooling:150 Heating:145
-15~20
210x1,070x690
28
15
-15~43* 3
-20~20
210x1,320x690
37
210x1,070x690
28
1,300x970x370
122
5.4(30)
9.52/22.22
70
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
1,505x970x370
140
7.2(30)
12.7/22.22
845x970x370
83
3.8(30)
9.52/15.88
1,300x970x370
122
5.4(30)
9.52/22.22
50
30
70
-15~20
9.50/8.69
2.63/3.22
D/C
5(22)
Hi:41
Hi:18
Me:14 Lo:12
210x1,320x690
37
1,505x970x370
140
7.2(30)
12.7/22.2
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 140VSPVD 50dB, 200VSPVD 46dB, 250VSPVD 50dB, 140VSTVD 46dB, 200VSTVD 50dB, 200VSDVD 46dB, 250VSDVD 50dB
Air flow: 140VSPVD 22CMM, 200VSPVD 28CMM, 250VSPVD 32CMM, 140VSTVD 13CMM, 200VSTVD 22CMM, 200VSDVD 13CMM, 250VSDVD 22CMM
33
32
MULTI [ INDOOR UNIT ]
CEILING SUSPENDED
FDEN
Wired remote control
RC-E4
(Option)
FDEN 40/50/60/71/100/125VD
RCH-E3
(Option)
Wireless remote control
RCN-E1R
(Option)
A
CLASS
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
Air flow
1
Indoor* 2
Outdoor
Indoor* 2
Outdoor
Height x Width x Depth Exterior dimensions
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Height x Width x Depth
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
ISO-T1(JIS)
ISO-T1(JIS)
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDEN71VNXPVD FDEN100VNXPVD
Twin
FDEN40VD
FDC71VNX
FDEN50VD
FDC100VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
7.1
(3.2~8.0)
10.0
(4.0~11.2)
8.0
(3.6~9.0)
11.2
(4.0~12.5)
1.98/2.40
3.59/3.33
A/C
5(17)
3.02/3.18
3.31/3.52
A/B
5(24)
Hi:39 Me:38 Lo:37
Cooling:51 Heating:48 Cooling:48 Heating:50
Hi:11 Me:9 Lo:7
Cooling:60 Heating:50 100
210x1,070x690
28
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
750X880(+88)X340
60
2.95(30)
1,300x970x370
105
4.5(30)
9.52/15.88
50 100
30
15
-15~43* 3
-20~20
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel* 1
Indoor* 2
Outdoor
Air flow
Exterior dimensions
Net weight
Indoor* 2
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Liquid/Gas
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDEN125VNXPVD FDEN140VNXPVD
FDEN60VD
FDC125VNX
Twin
FDEN71VD
FDC140VNX
FDEN140VNXTVD
Triple
FDEN50VD
FDC140VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(5.0~16.0)
14.0
(4.0~17.0)
16.0
(4.0~18.0)
16.0
(4.0~18.0)
FDEN100VSXPVD FDEN125VSXPVD FDEN140VSXPVD FDEN140VSXTVD
FDEN50VD
FDC100VSX
Twin
FDEN60VD
FDC125VSX
Triple
FDEN50VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(5.0~16.0)
11.2
(4.0~16.0)
14.0
(4.0~18.0)
FDEN71VD
FDC140VSX
16.0
(4.0~20.0)
16.0
(4.0~20.0)
3.86/3.70
3.24/3.78
A/A
4.78/4.43
2.93/3.61
C/A
Hi:41 Me:39 Lo:38
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:18 Me:14 Lo:12
5(26)
Hi:39 Me:38 Lo:37
Cooling:49 Heating:52
Hi:11 Me:9 Lo:7
49
100
210x1,320x690
37
4.72/4.38
2.97/3.65
C/A
3.02/3.18
3.31/3.52
A/B
3.86/3.70
3.24/3.78
A/A
4.78/4.43
2.93/3.61
C/A
5(15)
Hi:41 Me:39 Lo:38
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:18 Me:14 Lo:12
210x1,070x690
28
210x1,320x690
37
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43* 3
-20~20
4.72/4.38
2.97/3.65
C/A
Hi:39 Me:38 Lo:37
Cooling:49 Heating:52
Hi:11 Me:9 Lo:7
210x1,070x690
28
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 71/100VNXPVD 46dB, 100VSXPVD 46dB, 125/140VNXPVD 50dB, 125/140VSXPVD 50dB, 140VNXTVD 46dB, 140VSXTVD 46dB
Air flow: 71/100VNXPVD 13CMM, 100VSXPVD 13CMM, 125/140VNXPVD 22CMM, 125/140VSXPVD 22CMM, 140VNXTVD 13CMM, 140VSXTVD 13CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Cooling/Heating
Cooling/Heating
Energy label Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Air flow
Ref.piping size
Ref.piping length
Vertical height
Range of usage difference
Operating temperature range
Indoor* 2
Outdoor
Indoor*
Cooling
Heating
2
Exterior dimensions
Net weight
Exterior dimensions
Net weight
Ref.amount precharged
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Height x Width x Depth
Liquid/Gas
O/U is higher
O/U is lower kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDEN100VNPVD
FDEN50VD
FDC100VN
10.0
(4.0~11.2)
11.2
(4.0~12.5)
3.12/3.28
3.21/3.41
A/B
Hi:39 Me:38 Lo:37
49
Hi:11 Me:9 Lo:7
14.0
(4.0~16.0)
4.23/3.83
2.96/3.66
C/A
16.0
(4.0~16.5)
4.87/4.59
2.87/3.49
C/B
Hi:41 Me:39 Lo:38
Cooling:50 Heating:51
5(24)
Hi:18 Me:14 Lo:12
Micro Inverter
FDEN125VNPVD
Twin
FDEN60VD
FDC125VN
FDEN140VNPVD
FDEN71VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~14.5)
51
FDEN140VNTVD
Triple
FDEN50VD
FDC140VN
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.88/4.58
2.87/3.49
C/B
FDEN100VSPVD
Twin
FDEN125VSPVD
FDEN50VD
FDC100VS
FDEN60VD
FDC125VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
11.2
(4.0~12.5)
3.12/3.28
3.21/3.41
A/B
Hi:39 Me:38 Lo:37
Hi:11 Me:9 Lo:7
49
14.0
(4.0~16.0)
4.23/3.83
2.96/3.66
C/A
5(15)
Hi:41
Me:39 Lo:38
Cooling:50 Heating:51
Hi:18
Me:14 Lo:12
210x1,070x690
28
Cooling:75 Heating:73
210x1,320x690
37 28
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
845x970x370
210x1,070x690
81
3.8(30)
9.52/15.88
50
30
15
-15~43* 3
-20~20
Powerful-Hi can be selected. Sound level: 100VNPVD 46dB, 125/140VNPVD 50dB, 140VNTVD 46dB, 100VSPVD 46dB, 125VSPVD 50dB
Air flow: 100VNPVD 13CMM, 125/140VNPVD 22CMM, 140VNTVD 13CMM, 100VSPVD 13CMM, 125VSPVD 22CMM
83
210x1,320x690
37
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption
COP
Energy label
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel*
1
Indoor* 2
Outdoor
Air flow
Indoor* 2
Exterior dimensions
Net weight
Air filter, Q'ty
Exterior dimensions
Remote control(option)
Height x Width x Depth
Net weight
Ref.amount precharged
Outdoor
Height x Width x Depth
Liquid/Gas Ref.piping size
Ref.piping length
Vertical height
difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
FDEN140VSPVD
FDEN71VD
FDC140VS
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.87/4.59
2.87/3.49
C/B
5(15)
Hi:41
Me:39 Lo:38
51
Hi:18
Me:14 Lo:12
Cooling:75 Heating:73
210x1,320x690
37
845x970x370
83
3.8(30)
9.52/15.88
50
-20~20
FDEN200VSPVD
Twin
FDEN100VD
FDC200VS
Micro Inverter
FDEN250VSPVD
FDEN125VD
FDC250VS
FDEN140VSTVD
FDEN50VD
FDC140VS
FDEN200VSTVD FDEN200VSDVD FDEN250VSDVD
Triple
FDEN71VD
FDC200VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
25.0
(10.0~28.0)
14.0
(5.0~14.5)
20.0
(7.0~22.4)
FDEN50VD
FDC200VS
20.0
Double Twin
(7.0~22.4)
FDEN60VD
FDC250VS
25.0
(10.0~28.0)
20.0
(7.0~22.4)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
16.0
(4.0~16.5)
22.4
(7.6~25.0)
22.4
(7.6~25.0)
28.0
(9.5~31.5)
6.47/5.97
3.09/3.75
B/A
5(19)
Hi:44
9.01/8.05
2.77/3.48
D/B
5(22)
Hi:46
Me:41 Lo:39
57
Hi:26
Me:23 Lo:21
Me:44 Lo:43
Cooling:57 Heating:58
Cooling:150 Heating:145
250x1,620x690
49
Hi:29
Me:26 Lo:23
4.88/4.58
2.87/3.49
C/B
5(15)
Hi:39
Me:38 Lo:37
51
Hi:11
Me:9 Lo:7
Cooling:75 Heating:73
6.40/5.90
3.13/3.80
B/A
Hi:41
Me:39 Lo:38
Hi:18
5(19)
57
7.43/7.26
2.69/3.09
D/D
Hi:39
Me:38 Lo:37
Hi:11
Me:39 Lo:38
Cooling:57 Heating:58
Me:14 Lo:12 Me:9 Lo:7
Cooling:150 Heating:145
-15~20
210x1,070x690
28
15
-15~43* 3
-20~20
210x1,320x690
37
210x1,070x690
28
1,300x970x370
122
5.4(30)
9.52/22.22
70
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
1,505x970x370
140
7.2(30)
12.7/22.22
845x970x370
83
3.8(30)
9.52/15.88
1,300x970x370
122
5.4(30)
9.52/22.22
50
30
70
-15~20
9.50/8.69
2.63/3.22
D/C
5(22)
Hi:41
Hi:18
Me:14 Lo:12
210x1,320x690
37
1,505x970x370
140
7.2(30)
12.7/22.2
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
* 2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 140VSPVD 50dB, 200VSPVD 46dB, 250VSPVD 50dB, 140VSTVD 46dB, 200VSTVD 50dB, 200VSDVD 46dB, 250VSDVD 50dB
Air flow: 140VSPVD 22CMM, 200VSPVD 28CMM, 250VSPVD 32CMM, 140VSTVD 13CMM, 200VSTVD 22CMM, 200VSDVD 13CMM, 250VSDVD 22CMM
33
MULTI [ INDOOR UNIT ]
WALL MOUNTED
SRK
Only used with outdoor units of TWIN, TRIPLE, MULTI System.
A
CLASS
SRK 50/60ZJX-S
Wired remote control
RC-E4
(Option)
RCH-E3
(Option)
34
Point
1
Jet Air Scroll
We used the same aerodynamic analysis technology as used in developing jet engines.
CFD (computational fluid dynamics), used in blade shape design of jet engines, has been applied to the design of air channels in air conditioners to develop the ideal air channel system (air circulation). The airflow of the jets created in this system enable a large volume of air to be blown with minimum power consumption, yet the air flow is uniform, quiet and reaches points a long distance from the blower.
Fast Slow
Colors in the figure show the air speed.
Point
2
Long Reach Air Flow
Powerful airflow is realized by Jet technology.
Good for large living rooms and shops.
Increase your comfort.
SRK50/60ZJX-S
(in cooling operation)
SC-BIKN-E
RC-E4
Outline drawing (Unit:mm)
881.9
26 60 60 21
890
SC-BIKN-E
220 3
Piping hole right
Terminal block
122.1
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Energy label
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel * 1
Cooling/Heating
Indoor * 2
Cooling
Heating
Air flow
Exterior dimensions
Net weight
Outdoor
Indoor * 2
Cooling
Heating
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Vertical height
Range of usage difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
SRK100VNXPZJX SRK125VNXPZJX SRK140VNXTZJX
Twin Triple
SRK50ZJX-S
FDC100VNX
SRK60ZJX-S
FDC125VNX
SRK50ZJX-S
FDC140VNX
1Phase 220-240 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
11.2
(4.0~12.5)
14.0
(4.0~17.0)
16.0
(4.0~18.0)
SRK100VSXPZJX SRK125VSXPZJX
Twin
SRK140VSXTZJX
Triple
SRK50ZJX-S
FDC100VSX
SRK60ZJX-S
FDC125VSX
SRK50ZJX-S
FDC140VSX
3Phase 380-415 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
11.2
(4.0~16.0)
14.0
(4.0~18.0)
16.0
(4.0~20.0)
3.98/3.68
3.52/4.35
A/A
2.66/2.60
3.76/4.31
A/A
3.60/3.48
3.47/4.02
A/A
5 (24)
Hi:45 Me:38 Lo:26 Hi:47 Me:38 Lo:26
Hi:45 Me:38 Lo:32 Hi:45 Me:39 Lo:33
Cooling:48 Heating:50
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
Hi:14.5 Me:12.5 Lo:8.5
Hi:17 Me:15 Lo:11
3.98/3.68
3.52/4.35
A/A
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
Cooling:49 Heating:52
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
2.66/2.60
3.76/4.31
A/A
3.60/3.48
3.47/4.02
A/A
5 (15)
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
Hi:47 Me:38 Lo:26
Hi:45 Me:39 Lo:33
Cooling:48 Heating:50
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
100
309x890x220
15
Hi:14.5 Me:12.5 Lo:8.5
Hi:17 Me:15 Lo:11
Polypropylene net x2 (Washable)
Wired:RC-E4, RCH-E3 & Interface kit:SC-BIKN-E
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43 * 3
-20~20
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
Cooling:49 Heating:52
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Energy label
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel * 1
Indoor * 2
Cooling
Heating
Outdoor
Air flow
Indoor * 2
Cooling
Heating
Range of usage
Exterior dimensions
Net weight
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Liquid/Gas difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
SRK100VNPZJX
11.2
(4.0~12.5)
SRK125VNPZJX
14.0
(4.0~16.0)
SRK140VNTZJX
Twin Triple
SRK50ZJX-S
FDC100VN
SRK60ZJX-S
FDC125VN
SRK50ZJX-S
FDC140VN
1Phase 220-240 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
16.0
(4.0~16.5)
Micro Inverter
SRK100VSPZJX
11.2
(4.0~12.5)
SRK125VSPZJX
Twin Triple
SRK50ZJX-S
FDC100VS
SRK60ZJX-S
FDC125VS
SRK50ZJX-S
FDC140VS
3Phase 380-415 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
14.0
(4.0~16.0)
SRK140VSTZJX
16.0
(4.0~16.5)
2.72/2.86
3.62/3.92
A/A
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
49
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
4.25/4.29
2.94/3.26
C/C
5 (24)
Hi:47 Me:38 Lo:26
Hi:45 Me:39 Lo:33
Cooling:50,Heating:51
Hi:14.5 Me:12.5 Lo:8.5
Hi:17 Me:15 Lo:11
4.53/4.05
3.09/3.95
B/A
2.72/2.86
3.62/3.92
A/A
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
51
Hi:13.5 Me:11 Lo:8
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
49
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
Hi:16.5 Me:14.5 Lo:10.5
Cooling:75,Heating:73
309x890x220
15
Polypropylene net x2 (Washable)
Wired:RC-E4, RCH-E3 & Interface kit:SC-BIKN-E
845x970x370
4.25/4.29
2.94/3.26
C/C
5 (15)
Hi:47 Me:38 Lo:26
Hi:45 Me:39 Lo:33
Cooling:50,Heating:51
Hi:14.5 Me:12.5 Lo:8.5
Hi:17 Me:15 Lo:11
81 83
3.8(30)
9.52/15.88
50
30
15
-15~43 * 3
-20~20
4.53/4.05
3.09/3.95
B/A
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
51
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
The data are measured under the following conditions (ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB.
Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
35
MULTI [ INDOOR UNIT ]
WALL MOUNTED
SRK
Only used with outdoor units of TWIN, TRIPLE, MULTI System.
A
CLASS
SRK 50/60ZJX-S
Wired remote control
RC-E4
(Option)
RCH-E3
(Option)
34
Point
1
Jet Air Scroll
We used the same aerodynamic analysis technology as used in developing jet engines.
CFD (computational fluid dynamics), used in blade shape design of jet engines, has been applied to the design of air channels in air conditioners to develop the ideal air channel system (air circulation). The airflow of the jets created in this system enable a large volume of air to be blown with minimum power consumption, yet the air flow is uniform, quiet and reaches points a long distance from the blower.
Fast Slow
Colors in the figure show the air speed.
Point
2
Long Reach Air Flow
Powerful airflow is realized by Jet technology.
Good for large living rooms and shops.
Increase your comfort.
SRK50/60ZJX-S
(in cooling operation)
SC-BIKN-E
RC-E4
Outline drawing (Unit:mm)
881.9
26 60 60 21
890
SC-BIKN-E
220 3
Piping hole right
Terminal block
122.1
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Energy label
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel * 1
Cooling/Heating
Indoor * 2
Cooling
Heating
Air flow
Exterior dimensions
Net weight
Outdoor
Indoor * 2
Cooling
Heating
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Ref.amount precharged
Ref.piping size
Ref.piping length
Liquid/Gas
Vertical height
Range of usage difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
SRK100VNXPZJX SRK125VNXPZJX SRK140VNXTZJX
Twin Triple
SRK50ZJX-S
FDC100VNX
SRK60ZJX-S
FDC125VNX
SRK50ZJX-S
FDC140VNX
1Phase 220-240 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
11.2
(4.0~12.5)
14.0
(4.0~17.0)
16.0
(4.0~18.0)
SRK100VSXPZJX SRK125VSXPZJX
Twin
SRK140VSXTZJX
Triple
SRK50ZJX-S
FDC100VSX
SRK60ZJX-S
FDC125VSX
SRK50ZJX-S
FDC140VSX
3Phase 380-415 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
11.2
(4.0~16.0)
14.0
(4.0~18.0)
16.0
(4.0~20.0)
3.98/3.68
3.52/4.35
A/A
2.66/2.60
3.76/4.31
A/A
3.60/3.48
3.47/4.02
A/A
5 (24)
Hi:45 Me:38 Lo:26 Hi:47 Me:38 Lo:26
Hi:45 Me:38 Lo:32 Hi:45 Me:39 Lo:33
Cooling:48 Heating:50
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
Hi:14.5 Me:12.5 Lo:8.5
Hi:17 Me:15 Lo:11
3.98/3.68
3.52/4.35
A/A
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
Cooling:49 Heating:52
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
2.66/2.60
3.76/4.31
A/A
3.60/3.48
3.47/4.02
A/A
5 (15)
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
Hi:47 Me:38 Lo:26
Hi:45 Me:39 Lo:33
Cooling:48 Heating:50
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
100
309x890x220
15
Hi:14.5 Me:12.5 Lo:8.5
Hi:17 Me:15 Lo:11
Polypropylene net x2 (Washable)
Wired:RC-E4, RCH-E3 & Interface kit:SC-BIKN-E
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43
-20~20
* 3
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
Cooling:49 Heating:52
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
SPECIFICATIONS The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
ISO-T1(JIS)
ISO-T1(JIS)
Power Consumption
COP
Energy label
Cooling/Heating
Cooling/Heating
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel * 1
Indoor * 2
Cooling
Heating
Outdoor
Air flow
Indoor * 2
Cooling
Heating
Range of usage
Exterior dimensions
Net weight
Outdoor
Height x Width x Depth
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth
Net weight
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
Liquid/Gas difference
Operating temperature range
O/U is higher
O/U is lower
Cooling
Heating kW kW kW
A dB(A)
CMM mm kg mm kg kg(m)
ø m m m
O/U
O/U
SRK100VNPZJX
11.2
(4.0~12.5)
SRK125VNPZJX
14.0
(4.0~16.0)
SRK140VNTZJX
Twin Triple
SRK50ZJX-S
FDC100VN
SRK60ZJX-S
FDC125VN
SRK50ZJX-S
FDC140VN
1Phase 220-240 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
16.0
(4.0~16.5)
Micro Inverter
SRK100VSPZJX
11.2
(4.0~12.5)
SRK125VSPZJX
Twin Triple
SRK50ZJX-S
FDC100VS
SRK60ZJX-S
FDC125VS
SRK50ZJX-S
FDC140VS
3Phase 380-415 50Hz, 3Phase 380V 60Hz
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~14.5)
14.0
(4.0~16.0)
SRK140VSTZJX
16.0
(4.0~16.5)
2.72/2.86
3.62/3.92
A/A
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
49
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
4.25/4.29
2.94/3.26
C/C
5 (24)
Hi:47 Me:38 Lo:26
Hi:45 Me:39 Lo:33
Cooling:50,Heating:51
Hi:14.5 Me:12.5 Lo:8.5
Hi:17 Me:15 Lo:11
4.53/4.05
3.09/3.95
B/A
2.72/2.86
3.62/3.92
A/A
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
51
Hi:13.5 Me:11 Lo:8
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
49
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
Hi:16.5 Me:14.5 Lo:10.5
Cooling:75,Heating:73
309x890x220
15
Polypropylene net x2 (Washable)
Wired:RC-E4, RCH-E3 & Interface kit:SC-BIKN-E
845x970x370
4.25/4.29
2.94/3.26
C/C
5 (15)
Hi:47 Me:38 Lo:26
Hi:45 Me:39 Lo:33
Cooling:50,Heating:51
Hi:14.5 Me:12.5 Lo:8.5
Hi:17 Me:15 Lo:11
81 83
3.8(30)
9.52/15.88
50
30
15
-15~43 * 3
-20~20
4.53/4.05
3.09/3.95
B/A
Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32
51
Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5
The data are measured under the following conditions (ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB.
Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
* 1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
2 : The values are for one indoor unit operation.
* 3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
35
OUTDOOR UNIT (1.5-10.0HP)
SRC40ZIX-S
SRC50ZIX-S
SRC60ZIX-S
*
(1.5HP~2.5HP)
* SRC50/60ZIX-S is common for both of outdoor units of
SRK50/60ZJX-S (Residential Air-conditioners) and 1.5,
2, 2.5HP of Inverter Packaged Air-Conditioners.
Common components make for easy inventory control and the installation procedure will be the same.
NEW
FDC71VNX
(3.0HP)
FDC100VNX
FDC100VSX
(4.0HP)
FDC125VNX
FDC125VSX
(5.0HP)
FDC140VNX
FDC140VSX
(6.0HP)
Blue Fin (3~10HP)
Due to application of blue coated fins (KS101) for the heat exchanger of new outdoor unit, corrosion resistance has been improved compared to current models.
FDC100VN
FDC125VN
FDC100VS
FDC125VS
FDC140VN FDC140VS
(4.0HP~6.0HP)
FDC200VS
(8.0HP)
FDC250VS
(10.0HP)
Base heater kit (option)
This kit is recommended to be used in an area where the lowest temperature drops below 0˚C.
CW-H-E applied for
FDC100~250VN,VS
FDC100~140VNX,VSX
Installation workability
Enhanced installation workability thanks to the extended pipe length – longest level in the industry and pre-charged refrigerant.
Point
1
Piping length – 100m (Hyper Inverter 4~6HP)
Refer to our Technical Manual in detail
Micro Inverter
Height difference
(Outdoor higher than Indoor)
Height difference
(Outdoor higher than Indoor)
Piping length
Piping length
HP
1.5~2.5
Piping length
30m
3
4~6
50m
100m
Height difference
20m
30m
30m
HP
4~6
8.10
Piping length
50m
70m
Height difference
30m
30m
36
Point
2
Refrigerant precharged piping length extending to 30m
Refrigerant precharged piping length extends up to 30m. (1.5~2.5HP:15m)
This eliminates the need to add refrigerant on site, which sets it free from trouble of excessive or insufficient charging of refrigerant, and allows carrying out the installation smoothly.
Control Systems [Individual control]
Remote Control line up indoor unit wired all models remote control
RC-E4
RCH-E3 wireless indoor unit
FDT
FDTC
FDUM, FDU
FDEN remote control
RCN-T-36W-E
RCN-TC-24W-ER
RCN-KIT3-E
RCN-E1R
Wired remote control with weekly timer (option)
RC-E4
Run hour meters to facilitate maintenance checking
RC-E4 stores operation data when an anomaly occurs and indicates the error on the LCD. It also displays cumulative operation hours of the air conditioner and compressor since commissioning.
The RC-E4 controller enables extensive access to service and maintenance technical data combined with easy to use functions and a clear LCD display.
Room temperature controlled
by the remote control sensor
The temperature sensor is housed in the top section of the remote control unit. This arrangement has improved the sensitivity of the remote control unit’s sensor, which permits more finely controlled air conditioning.
Weekly timer function as standard
RC-E4 provides (as a standard feature) a weekly timer, which allows oneweek operation schedules to be registered. A user can specify up to four times a day to start/stop the air conditioner. (Temperature setting is also possible with the timer).
Timer operation
Changeable set temperature ranges
RC-E4 allows the upper and lower limits of a set temperature range to be specified separately.
By adjusting a set temperature range, you can ensure energy saving air conditioning by avoiding excessive cooling or heating.
Upper limit
Lower limit
Changeable range
20~30 °C(effective for heating operation)
18~26 °C(effective for non-heating operation)
Simple remote control (option)
RCH-E3 (wired)
Considering specialized usage in hotel rooms, control buttons are limited only to minimum required functions such as ON/OFF, mode, temperature setting and fan speed. It is really simple and easy to use.
RCH-E3 is not applicable to the Individual flap control system and the Flap control system.
When RCH-E3 is used, the fan has 3 speed settings (Hi-
Me-Lo) only.
Up to 16 units
It can control up to 16 units individually, with pressing the AIR CON No. button.
AUTO restart
This function allows starting the air conditioner automatically when power supply is restored after power failure or by turning on the power switch.
Wireless remote control (option)
For wireless control simply insert the infrared receiver kit on a corner of the panel.
RCN-T-36W-E,
RCN-TC-24W-ER
RCN-KIT3-E RCN-E1R
Thermistor (option)
SC-THB-E3
In case sensor in the indoor units or the remote control sensor can not sense the room temperature correctly, or individual remote control in each room is not required but only censor is required (as when center control system is in place), install SC-THB-E3 at proper place in the rooms.
When wireless remote control is used, the fan has 3 speed settings (Hi-Me-Lo) only.
37
OUTDOOR UNIT (1.5-10.0HP)
SRC40ZIX-S
SRC50ZIX-S
SRC60ZIX-S
*
(1.5HP~2.5HP)
* SRC50/60ZIX-S is common for both of outdoor units of
SRK50/60ZJX-S (Residential Air-conditioners) and 1.5,
2, 2.5HP of Inverter Packaged Air-Conditioners.
Common components make for easy inventory control and the installation procedure will be the same.
NEW
FDC71VNX
(3.0HP)
FDC100VNX
FDC100VSX
(4.0HP)
FDC125VNX
FDC125VSX
(5.0HP)
FDC140VNX
FDC140VSX
(6.0HP)
Blue Fin (3~10HP)
Due to application of blue coated fins (KS101) for the heat exchanger of new outdoor unit, corrosion resistance has been improved compared to current models.
FDC100VN
FDC125VN
FDC100VS
FDC125VS
FDC140VN FDC140VS
(4.0HP~6.0HP)
FDC200VS
(8.0HP)
FDC250VS
(10.0HP)
Base heater kit (option)
This kit is recommended to be used in an area where the lowest temperature drops below 0˚C.
CW-H-E applied for
FDC100~250VN,VS
FDC100~140VNX,VSX
Installation workability
Enhanced installation workability thanks to the extended pipe length – longest level in the industry and pre-charged refrigerant.
Point
1
Piping length – 100m (Hyper Inverter 4~6HP)
Refer to our Technical Manual in detail
Micro Inverter
Height difference
(Outdoor higher than Indoor)
Height difference
(Outdoor higher than Indoor)
Piping length
Piping length
HP
1.5~2.5
Piping length
30m
3
4~6
50m
100m
Height difference
20m
30m
30m
HP
4~6
8.10
Piping length
50m
70m
Height difference
30m
30m
36
Point
2
Refrigerant precharged piping length extending to 30m
Refrigerant precharged piping length extends up to 30m. (1.5~2.5HP:15m)
This eliminates the need to add refrigerant on site, which sets it free from trouble of excessive or insufficient charging of refrigerant, and allows carrying out the installation smoothly.
Control Systems [Individual control]
Remote Control line up indoor unit wired all models remote control
RC-E4
RCH-E3 wireless indoor unit
FDT
FDTC
FDUM, FDU
FDEN remote control
RCN-T-36W-E
RCN-TC-24W-ER
RCN-KIT3-E
RCN-E1R
Wired remote control with weekly timer (option)
RC-E4
Run hour meters to facilitate maintenance checking
RC-E4 stores operation data when an anomaly occurs and indicates the error on the LCD. It also displays cumulative operation hours of the air conditioner and compressor since commissioning.
The RC-E4 controller enables extensive access to service and maintenance technical data combined with easy to use functions and a clear LCD display.
Room temperature controlled
by the remote control sensor
The temperature sensor is housed in the top section of the remote control unit. This arrangement has improved the sensitivity of the remote control unit’s sensor, which permits more finely controlled air conditioning.
Weekly timer function as standard
RC-E4 provides (as a standard feature) a weekly timer, which allows oneweek operation schedules to be registered. A user can specify up to four times a day to start/stop the air conditioner. (Temperature setting is also possible with the timer).
Timer operation
Changeable set temperature ranges
RC-E4 allows the upper and lower limits of a set temperature range to be specified separately.
By adjusting a set temperature range, you can ensure energy saving air conditioning by avoiding excessive cooling or heating.
Upper limit
Lower limit
Changeable range
20~30 °C(effective for heating operation)
18~26 °C(effective for non-heating operation)
Simple remote control (option)
RCH-E3 (wired)
Considering specialized usage in hotel rooms, control buttons are limited only to minimum required functions such as ON/OFF, mode, temperature setting and fan speed. It is really simple and easy to use.
RCH-E3 is not applicable to the Individual flap control system and the Flap control system.
When RCH-E3 is used, the fan has 3 speed settings (Hi-
Me-Lo) only.
Up to 16 units
It can control up to 16 units individually, with pressing the AIR CON No. button.
AUTO restart
This function allows starting the air conditioner automatically when power supply is restored after power failure or by turning on the power switch.
Wireless remote control (option)
For wireless control simply insert the infrared receiver kit on a corner of the panel.
RCN-T-36W-E,
RCN-TC-24W-ER
RCN-KIT3-E RCN-E1R
Thermistor (option)
SC-THB-E3
In case sensor in the indoor units or the remote control sensor can not sense the room temperature correctly, or individual remote control in each room is not required but only censor is required (as when center control system is in place), install SC-THB-E3 at proper place in the rooms.
When wireless remote control is used, the fan has 3 speed settings (Hi-Me-Lo) only.
37
KX6 series
SC-SL1N-E
SC-SL2NA-E
SC-SL1N-E
RAC series
(SRK/SRF-ZJX-S)
SC-BIKN-E
SC-ADNA-E
SC-ADNA-E SC-ADNA-E
Central Control
SC-SL2NA-E SC-SL3N-AE/BE
Start/stop control of up to 16 indoor units is possible either individually or collectively. With simple operations, you can effect centralized control.
PC windows central control
SC-WGWNA-A/B
(SC-WGWNA-B is with electric power calculation function)
Centralized control of up to 64 indoor units. It can allow connection with a weekly timer without using any interface.
Easy operation realized with a large color LCD and touch panel. Up to 128 indoor units can be controlled, when three SUPERLINK-2 systems are connected.
BMS interface unit
SC-BGWN-A/B
(BACnet gateway)
(SC-WGWN-B is with electric power calculation function)
SC-LGWN-A
(LonWorks gateway)
38
Up to 96 cells (some cells can have two or more indoor units and total number of indoor units can be up to 128 units) are controlled from the Internet Explorer.
Additional engineering service cost etc. is required. Please consult your dealer when using this central control.
Up to 96 cells (some cells can have two or more indoor units and total number of indoor units can be up to 128 units) are controlled centrally from a BMS.
Additional engineering service cost etc. is required.
In case of SC-BGWN-B, communication test by qualified person regarding electric cost calculation function is required before commissioning. Please consult your dealer when using this gateway.
Up to 96 indoor units (48 indoor unit x 2) are linked as an open network! Centrally controlled through LonWorks!
Additional engineering service cost etc. is required. Please consult your dealer when using this gateway.
SUPERLINK E BOARD (SC-ADNA-E)
This board is used when conducting control of the single package (wired remote control unit) 1-type series using a network option (SC-SL1N-E, SC-SL2NA-E, etc).
(1) Functions
(a) Transmits the settings from the network option to the indoor units.
(b) Returns the priority indoor unit data in response to a data request from the network option.
(c) Inspects the error status of connected indoor units and transmits the inspection codes to the network option.
(d) A maximum of 16 units can be controlled (if in the same operation mode).
(2) Wiring connection diagram
SL E board
X
Y
A
B
ON
OFF SW3
SW1 SW2
Master/Sub address
Network address setting switches
[000]-(127)
Blue
Blue
Black
White
X
Y
A
B
Connected to the terminals for
Superlink signal lines
MVVS 0.75 - 1.25mm
2
Connected to the remote controller terminals (no polarity) (the length should be 600 m or shorter)
200 m or shorter
300 m or shorter
400 m or shorter
600 m or shorter
0.5 mm 2 x 2 cores
0.75 mm
1.25 mm
2.0 mm 2
2
2
x 2 cores
x 2 cores
x 2 cores
Basic Connections
Outdoor unit
Internal/external Crossing
Indoor unit
X Y
SL E Board
X Y
A B
Network options
A B
Remote control
X Y
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Outdoor unit
Internal/external Crossing
Inside Inside Inside Inside
SL E
Board
Network options
R R
• Transmit the information of plural “Master” units to the network.
• Transmit the abnormalities of the “Slave” units to the network.
Setting the plural “Master/Slave” units with the dip SW of the printed circuit board.
Setting the “Master/Slave” remote controls with the dip SW of the remote control board.
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units Without Remote Control Wireless Kit
Outdoor unit
Internal/external Crossing
Inside Inside Inside Inside
Outdoor unit
Internal/external Crossing
Inside Inside Inside
SL E
Board
Network options
R R SL E
Board
R R
Set up “000” to “127” using address switch on the SL E board.
Outdoor unit
Internal/external Crossing
Inside Inside
SL E
Board
Network options
Set the SL E board dip SW to “Master” SW3-1 ON.
The network option SLA-1-
E, SL1N-E is not allowed
(This will disturb switching of the operation mode)
Outdoor unit
Internal/external Crossing
Inside Inside
SL E
Board
Network options
Wireless Kit
Wireless remote control
(3) Metal box dimension
85
40 22.5
35
30
2-ø6
39
KX6 series
SC-SL1N-E
SC-SL2NA-E
SC-SL1N-E
RAC series
(SRK/SRF-ZJX-S)
SC-BIKN-E
SC-ADNA-E
SC-ADNA-E SC-ADNA-E
Central Control
SC-SL2NA-E SC-SL3N-AE/BE
Start/stop control of up to 16 indoor units is possible either individually or collectively. With simple operations, you can effect centralized control.
PC windows central control
SC-WGWNA-A/B
(SC-WGWNA-B is with electric power calculation function)
Centralized control of up to 64 indoor units. It can allow connection with a weekly timer without using any interface.
Easy operation realized with a large color LCD and touch panel. Up to 128 indoor units can be controlled, when three SUPERLINK-2 systems are connected.
BMS interface unit
SC-BGWN-A/B
(BACnet gateway)
(SC-WGWN-B is with electric power calculation function)
SC-LGWN-A
(LonWorks gateway)
38
Up to 96 cells (some cells can have two or more indoor units and total number of indoor units can be up to 128 units) are controlled from the Internet Explorer.
Additional engineering service cost etc. is required. Please consult your dealer when using this central control.
Up to 96 cells (some cells can have two or more indoor units and total number of indoor units can be up to 128 units) are controlled centrally from a BMS.
Additional engineering service cost etc. is required.
In case of SC-BGWN-B, communication test by qualified person regarding electric cost calculation function is required before commissioning. Please consult your dealer when using this gateway.
Up to 96 indoor units (48 indoor unit x 2) are linked as an open network! Centrally controlled through LonWorks!
Additional engineering service cost etc. is required. Please consult your dealer when using this gateway.
SUPERLINK E BOARD (SC-ADNA-E)
This board is used when conducting control of the single package (wired remote control unit) 1-type series using a network option (SC-SL1N-E, SC-SL2NA-E, etc).
(1) Functions
(a) Transmits the settings from the network option to the indoor units.
(b) Returns the priority indoor unit data in response to a data request from the network option.
(c) Inspects the error status of connected indoor units and transmits the inspection codes to the network option.
(d) A maximum of 16 units can be controlled (if in the same operation mode).
(2) Wiring connection diagram
SL E board A
B
X
Y
ON
OFF SW3
SW1 SW2
Master/Sub address
Network address setting switches
[000]-(127)
Blue
Blue
Black
White
X
Y
A
B
Connected to the terminals for
Superlink signal lines
MVVS 0.75 - 1.25mm
2
Connected to the remote controller terminals (no polarity) (the length should be 600 m or shorter)
200 m or shorter
300 m or shorter
400 m or shorter
600 m or shorter
0.5 mm 2 x 2 cores
0.75 mm
1.25 mm
2.0 mm 2
2
2
x 2 cores
x 2 cores
x 2 cores
Basic Connections
Outdoor unit
Internal/external Crossing
Indoor unit
X Y
SL E Board
X Y
A B
Network options
A B
Remote control
X Y
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Outdoor unit
Internal/external Crossing
Inside Inside Inside Inside
SL E
Board
Network options
R R
• Transmit the information of plural “Master” units to the network.
• Transmit the abnormalities of the “Slave” units to the network.
Setting the plural “Master/Slave” units with the dip SW of the printed circuit board.
Setting the “Master/Slave” remote controls with the dip SW of the remote control board.
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units Without Remote Control Wireless Kit
Outdoor unit
Internal/external Crossing
Inside Inside Inside Inside
Outdoor unit
Internal/external Crossing
Inside Inside Inside
SL E
Board
Network options
R R SL E
Board
R R
Set up “000” to “127” using address switch on the SL E board.
Outdoor unit
Internal/external Crossing
Inside Inside
SL E
Board
Network options
Set the SL E board dip SW to “Master” SW3-1 ON.
The network option SLA-1-
E, SL1N-E is not allowed
(This will disturb switching of the operation mode)
Outdoor unit
Internal/external Crossing
Inside Inside
SL E
Board
Network options
Wireless Kit
Wireless remote control
(3) Metal box dimension
85
40 22.5
35
30
2-ø6
39
40
OUTDOOR UNIT DIMENSIONS
FDC100VNX, 100VSX, 125VNX, 125VSX,
140VNX, 140VSX (unit:mm)
113
46
B
A
Terminal block
Mark
A
B
C
D
E
F
Item
Service valve connection of the attached connecting pipe(gas side)
Service valve connection(liquid side)
Pipe/cable draw-out hole
Drain discharge hole
Anchor bolt hole
Cable draw-out hole
ø15.88(5/8")(Flare)
ø9.52(3/8")(Flare)
ø20x3places
M10x4places
ø30x2places(front)
ø45(side)
ø50(back)
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than
15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The model name label is attached on the lower right corner of the front panel.
(7) Connect the Service valve with local pipe by using the pipe of the attachment. (Gas side only)
B
A
F F C
60
970
190
60
E
580
C
50
55
15
200
60 15
262 388
D
SRC40ZIX-S, 50ZIX-S, 60ZIX-S (unit:mm)
C
52
27 50
C
L2
L3
Intake
L4
Intake
L1
Service space
Outlet
Minimum installation space
15
50
50
F
Dimensions
L
1
L
2
L
3
L
4
Examples of
installation
1
Open
300
150
5
2
Open
5
300
5
3
500
Open
150
5
Terminal block
327.3
D
50.6
12
89
327.3
510
800
201
17.9
E
71.2
148.4
Check joint
33.5
40
°
40
°
B
A
Intake
L2 Intake
L3
L4
outlet
L1
Examples of
installation
Dimensions
L
1
L
2
L
3
L
4
1
Open
100
100
250
2
280
75
80
Open
3
280
Open
80
250
Mark
A
B
D
E
Drain discharge port
Anchor bolt hole
Item
Refrigerant gas side pipe connection tap
Refrigerant liquid side pipe connection tap
ø12.7(flare)
ø6.35(flare)
ø20.5x5places
M10x4places
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts.An anchor bolt must not protrude more than
15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
(4) Leave a 1m or larger space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The unit name plate is attached on the lower right corner of the front panel.
FDC71VNX (unit:mm)
2-R7.5
223 310
61
150
D
580
880
60
15
E
B
C
D
E
Mark
A
Item
Service valve connection
(gas side)
Service valve connection
(liquid side)
Pipe/cable draw-out hole
Drain discharge hole
Anchor bolt hole
ø15.88(5/8")
(Flare)
ø9.52(3/8")
(Flare)
ø20x3places
M10x4places
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more the 15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The model name label is attached on the lower right corner of the front.
150
88
27
32
Terminal block
Intake
L2
Intake outlet
Minimum installation space
L4
B
30
30
C
A
Examples of
installation
Dimensions
L
1
L
2
L
3
L
4
1 2
Open
300
100
250
Open
250
150
250
3
500
Open
100
250
165.5
25
FDC100VN, 125VN, 140VN
100VS, 125VS, 140VS (unit:mm)
40
100
B
Terminal block
B
A
A
B
E
F
C
D
Mark
A
Item
Refrigerant gas side pipe connection tap
Refrigerant liquid side pipe connection tap
Pipe/cable draw-out port
Drain discharge port
Anchor bolt hole
Cable draw-out port
ø15.88(flare)
ø9.52(flare)
ø20.3x3places
M10x4places
ø30.3x3places
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts.An anchor bolt must not protrude more than 15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
(4) Leave a 1m or larger space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The unit name plate is attached on the lower right corner of the front panel.
A
F
F
E
60
190
60
970
C
580
50
55
15
200
60 15
262 388
D
C
52
27 50
C
L2
Intake
L1
L3 Intake outlet
L4
Minimum installation space
C
15
40
50
VIEW A
Examples of
installation
Dimensions
L
1
L
2
L
3
L
4
1 2
Open
300
150
5
Open
5
300
5
3
500
Open
150
5
41
40
OUTDOOR UNIT DIMENSIONS
FDC100VNX, 100VSX, 125VNX, 125VSX,
140VNX, 140VSX (unit:mm)
113
46
B
A
Terminal block
Mark
A
B
C
D
E
F
Item
Service valve connection of the attached connecting pipe(gas side)
Service valve connection(liquid side)
Pipe/cable draw-out hole
Drain discharge hole
Anchor bolt hole
Cable draw-out hole
ø15.88(5/8")(Flare)
ø9.52(3/8")(Flare)
ø20x3places
M10x4places
ø30x2places(front)
ø45(side)
ø50(back)
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than
15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The model name label is attached on the lower right corner of the front panel.
(7) Connect the Service valve with local pipe by using the pipe of the attachment. (Gas side only)
B
A
F F C
60
970
190
60
E
580
C
50
55
15
200
60 15
262 388
D
SRC40ZIX-S, 50ZIX-S, 60ZIX-S (unit:mm)
C
52
27 50
C
L2
L3
Intake
L4
Intake
L1
Service space
Outlet
Minimum installation space
15
50
50
F
Examples of
installation
Dimensions
L
1
L
2
L
3
L
4
1
Open
300
150
5
2
Open
5
300
5
3
500
Open
150
5
Terminal block
327.3
D
50.6
12
89
327.3
510
800
201
17.9
E
71.2
148.4
Check joint
33.5
40
°
40
°
B
A
Intake
L2 Intake
L3
L4
outlet
L1
Examples of
installation
Dimensions
L
1
L
2
L
3
L
4
1
Open
100
100
250
2
280
75
80
Open
3
280
Open
80
250
Mark
A
B
D
E
Drain discharge port
Anchor bolt hole
Item
Refrigerant gas side pipe connection tap
Refrigerant liquid side pipe connection tap
ø12.7(flare)
ø6.35(flare)
ø20.5x5places
M10x4places
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts.An anchor bolt must not protrude more than
15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
(4) Leave a 1m or larger space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The unit name plate is attached on the lower right corner of the front panel.
FDC71VNX (unit:mm)
2-R7.5
223 310
61
150
D
580
880
60
15
E
B
C
D
E
Mark
A
Item
Service valve connection
(gas side)
Service valve connection
(liquid side)
Pipe/cable draw-out hole
Drain discharge hole
Anchor bolt hole
ø15.88(5/8")
(Flare)
ø9.52(3/8")
(Flare)
ø20x3places
M10x4places
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more the 15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The model name label is attached on the lower right corner of the front.
150
88
27
32
Terminal block
Intake
L2
Intake outlet
Minimum installation space
L4
B
30
30
C
A
Examples of
installation
Dimensions
L
1
L
2
L
3
L
4
1 2
Open
300
100
250
Open
250
150
250
3
500
Open
100
250
165.5
25
FDC100VN, 125VN, 140VN
100VS, 125VS, 140VS (unit:mm)
40
100
B
Terminal block
B
A
A
B
E
F
C
D
Mark
A
Item
Refrigerant gas side pipe connection tap
Refrigerant liquid side pipe connection tap
Pipe/cable draw-out port
Drain discharge port
Anchor bolt hole
Cable draw-out port
ø15.88(flare)
ø9.52(flare)
ø20.3x3places
M10x4places
ø30.3x3places
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts.An anchor bolt must not protrude more than 15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
(4) Leave a 1m or larger space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The unit name plate is attached on the lower right corner of the front panel.
A
F
F
E
60
190
60
970
C
580
50
55
15
200
60 15
262 388
D
C
52
27 50
C
L2
Intake
L1
L3 Intake outlet
L4
Minimum installation space
C
15
40
50
VIEW A
Examples of
installation
Dimensions
L
1
L
2
L
3
L
4
1 2
Open
300
150
5
Open
5
300
5
3
500
Open
150
5
41
OUTDOOR UNIT DIMENSIONS
FDC200VS (unit:mm)
42
FDC250VS (unit:mm)
MEMO
43
OUTDOOR UNIT DIMENSIONS
FDC200VS (unit:mm)
42
FDC250VS (unit:mm)
MEMO
43
Before starting use
Heating performance
The heating performance values (kW) described in catalog are the values obtained by operating at an outdoor temperature of 7 C and indoor temperature of 20 C as set forth in the ISO Standards. As the heating performance decreases as the outdoor temperature drops, if the outdoor temperature is too low and the heating performance is insufficient, use other heating appliances as well.
Indication of sound values
The sound values are the values (A scale) measured in a chamber such as an anechoic chamber following the ISO Standards. In the actual installation state, the value is normally larger than the values given in the catalog due to the effect of surrounding noise and echo. Take this into consideration when installing.
Use in oil atmosphere
Avoid installing this unit in as atmosphere where oil scatters or builds up, such as in a kitchen or machine factory.
If the oil adheres to the heat exchanger, the heat exchanging performance will drop, mist may be generated, and the synthetic resin parts may deform and break.
Use in acidic or alkaline atmosphere
If this unit is used in acidic atmosphere such as hot spring areas having high level of sulfuric gases or in alkaline atmosphere including ammonia or calcium chloride, places where the exhaust of the heat exchanger is sucked in, or at coastal areas where the unit is subject to salt breezes, the outer plate or heat exchanger, etc., will corrode. Please ask a dealer or specialist when you use an air conditioner in places differing from a general atmosphere.
Use in places with high ceilings
If the ceiling is high, install a circulator to improve the heat and air flow distribution when heating.
Refrigerant leakage
The refrigerant (R410A) used for Air conditioner is non-toxic and inflammable in its original state.
However, in consideration of a state where the refrigerant leaks into the room, measures against refrigerant leaks must be taken in small rooms where the tolerable level could be exceeded. Take measures by installing ventilation devices, etc.
Use in snowy areas
Take the following measures when installing the outdoor unit in snowy areas.
·Snow prevention
Install a snow-prevention hood so that the snow does not obstruct the air intake port or enter and freeze in the outdoor unit.
·Snow piling
In areas with heavy snow fall, the piled snow could block the air intake port. In this case, a frame that is 50cm or higher than the estimated snow fall must be installed underneath the outdoor unit.
Automatic defrosting device
If the temperature is low, and the humidity is high, frost will stick to the heat exchanger of the outdoor unit. If use is continued, the heating performance will drop.
The "Automatic defrosting device" will function to remove this frost.
After heating for approx, three to ten minutes, it will stop, and the frost will be removed. After defrosting, hot air will be blown again.
Servicing the air-conditioner
After the air-conditioner is used for several seasons, dirt will build up in the air-conditioner causing the performance to drop. In addition to regular servicing, we recommend the maintenance contract (charged for) by a specialist.
Safety Precautions
Air-conditioner usage target
The air-conditioner described in this catalog is a dedicated cooling/heating device for human use.
Do not use it for special applications such as the storage of foodstuffs, animals or plants, precision devices or valuable art, etc.
This could cause the quality of the items to drop, etc.
Do not use this for cooling vehicles or ships. Water leakage or current leaks could occur.
Before use
Always read the "User,s Manual" thoroughly before starting use.
Installation
Always commission the installation to a dealer or specialist. Improper installation will lead to water leakage, electric shocks and fires.
Make sure that the outdoor unit is stable in installation. Fix the unit to stable base.
Usage place
Do not install in places where combustible gas could leak or where there are sparks.
Installation in a place where combustible gas could be generated, flow or accumulate, or places containing carbon fibers could lead to fires.
Our factories are ISO9001 and ISO14001 certified.
Certified ISO 9001 Certified ISO 14001
BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd.
Air-conditioning & Refrigeration Systems Headquarters
Certificate number : JQA-0709
MITSUBISHI HEAVY INDUSTRIES-
MAHAJAK AIR CONDITIONERS CO., LTD.
Certificate Number : 04100 1998 0813
Mitsubishi Heavy
Industries-Haier (Quingdao)
Air-conditioners Co.,Ltd.
Certificate Number : 5170-1996-AQ-RCG-RvA
Certificate 04104 1998 0813 E5
BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd.
Air-conditioning & Refrigeration Systems Headquarters
Certificate number : JQA-EM0256
MITSUBISHI HEAVY INDUSTRIES-
MAHAJAK AIR CONDITIONERS CO.,LTD.
Certificate Number : 04104 1998 0813 E5
Mitsubishi Heavy
Industries-Haier (Quingdao)
Air-conditioners Co.,Ltd.
Certificate number : 01-1998-083
Japan Head Office:
Mitsubishi Heavy Industries Ltd
16-5 2-Chome Kounan Minato-ku Tokyo
108-8215, Japan www.mhi.co.jp
HB91-10P01E-A-0 February 2010(3B)R
Because of our policy of continuous improvement, we reserve right to make changes in all specifications without notice.
Printed in Japan
High Performance Air-Conditioning
FD
series
Inverter Packaged Air-Conditioners
50/60Hz
10P01E-A-0