I N T E G R A T E D C O M F O R T S O L U T I O N S

9515

DIGITAL

NON-PROGRAMMABLE

THERMOSTAT

G

GAS

E

ELECTRIC

2 Heat / 2 Cool

User’s Manual

Quick Start

Installation

110-752

W

A R R A N T Y

IMPORTANT SAFETY INFORMATION

WARNING:

• Always turn off power at the main power source by unscrewing fuse or switching circuit breaker to the off position before installing, removing, cleaning or servicing thermostat.

• Read all of the information in this manual before installing or programming this thermostat.

• This is a 24V AC low-voltage thermostat. Do not install on voltages higher than 30V AC.

• All wiring must conform to local and national building and electrical codes and ordinances.

• Do not short (jumper) across terminals on the gas valve or at the system control to test installation. This will damage the thermostat and void the warranty.

1

Features

• Multi stage heating and cooling control

• Zone system compatible as a master thermostat

• Auxiliary heat

• Fahrenheit/Celsius display option

• Adjustable from 45°F (7°C) to 90°F (32°C)

• Accuracy within ± 1 degree

• Adjustable 1st stage temperature differential: 1°-3°,

2nd stage temperature differential: 2°-6° F

• Automatic heating shutdown if temperature exceeds 90°F (32°C)

• Battery free memory storage

Replacing Existing Thermostat

1. Turn off power to heating and cooling system.

2. Remove cover of old thermostat to expose wires.

Do not disconnect wires (Figure 1).

3. Label wires per Table 1.

Table 1

Old Label

R, V-VR or VR-R

Y, Y1 or M

O or R

B

F or G

Y2

W2 or W-U

C, X or B

W1 or W

New Label

R

Y1

O

B

G

Y2

W2

C

W1

Description

24 VAC, Return

1st Stage Cooling

Circuit

Reversing Valve,

(Cooling Mode)

Reversing Valve

(Heating Mode)

Fan Control Relay

2nd Stage Cooling

Circuit

2nd Stage Heating

Control

24 VAC, Transformer

Common Side

1st Stage Heating

Circuit

*NOTE: T

HIS THERMOSTAT REQUIRES A

24V

COMMON WIRE FOR PROPER OPERATION

.

2

4. After labeling wires, remove wires from terminals.

5. Remove existing thermostat base from wall.

6. Refer to the following section for instructions on how to install thermostat.

Figure 1

Installing Model 9515 Thermostat

NOTE: F

OR NEW INSTALLATIONS

,

MOUNT THERMOSTAT ON INSIDE WALL

, 5

FEET ABOVE THE FLOOR

. D

O

NOT INSTALL BEHIND A DOOR

,

IN A CORNER

,

NEAR AIR VENTS

,

IN DIRECT SUNLIGHT

,

OR NEAR ANY HEAT OR

STEAM GENERATING FIXTURES

. I

NSTALLATION AT THESE PLACES WILL AFFECT THERMOSTAT OPERATION

.

1. Turn power off to the heating and cooling systems.

2. Place COOL-OFF-HEAT in OFF position.

COOL-OFF-HEAT

COOL-OFF-HEAT AUTO - ON AUX

AUTO - ON into AUTO position.

4. Remove the cover using a coin or screwdriver (Figure 2).

3

Figure 2

5. Place thermostat against the wall at desired location. Make sure wires will feed through opening on base of thermostat.

6. Mark placement of mounting holes (Figure 3).

Set base aside.

Mounting Holes

Batteries NOT Required.

Figure 3

7. Drill the marked holes using a 3/16" drill bit. NOTE: Enclosed plastic anchors do not require a drilled hole for drywall.

8. Tap plastic anchors into the wall.

9. Align base with plastic anchors and feed wires through opening.

10. Secure base to wall with supplied screws.

4

11. Connect wires to terminal strip (refer to wiring diagrams).

Make sure wire connections are secure.

12. Set the °F/°C switch to either °F for Fahrenheit display or °C for Celsius display readout (Figure 4).

°

F/

°

C Switch

Batteries NOT Required.

Figure 4

13. Set the GAS/ELEC switch to either GAS for a gas/oil heating system or ELEC for an electric heating system.

14. Replace cover onto thermostat by snapping into place.

15. Turn on power to system. Test thermostat as described in the following section.

5

Operation

Setting or Changing the Setpoint Temperature

1. Press either the or button.

The display will show the current temperature setpoint.

C

COOL-OFF-HEAT AUTO - ON AUX

2. Press either the or button to adjust the temperature setting either up or down.

The display will return to the room temperature display five seconds after the last input and the new setpoint will be saved.

Changing Temperature Differential

IMPORTANT: The temperature differential is factory set at 1 (1°). This means that whenever the room temperature changes by one degree

Fahrenheit from the temperature setting, the system will turn on. If the system turns on too often, increase the temperature differential.

at the same time and hold for one second.

COOL-OFF-HEAT AUTO - ON AUX

2. Press either the or button to adjust the 1st stage temperature differential up or down.

3. After 5 seconds DIFF will begin to flash on the display indicating 2nd stage differential value.

4. Press either the or button to adjust the 2nd stage temperature differential up or down.

The display will return to the room temperature five seconds after the last input.

6

To Test Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR

SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND

VOID YOUR WARRANTY.

CAUTION: D

O NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE IS BELOW

50°F (10°C).

T

HIS CAN DAMAGE THE AIR CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY

.

1. Place the COOL-OFF-HEAT switch into the COOL position.

2. Press the button until the temperature setting is at least

3 degrees below the room temperature. The air conditioning system should turn on within a few seconds.

COOL-OFF-HEAT

NOTE: When in the COOL mode once the thermostat turns off, a built in 5minute delay prevents the system from turning on again. This protects the compressor. No additional time delay relay is required. To override the 5minute delay for installation, press the RESET button.

COOL-OFF-HEAT

3. Put the COOL-OFF-HEAT switch into the OFF position. The air conditioning system should turn off.

4. Put the COOL-OFF-HEAT switch into the HEAT position.

5. Press the button until the temperature setting is at least

3 degrees above room temperature.

The heating system should turn on.

The fan may not turn on immediately, depending upon the fan delay built into the furnace.

6. Put the COOL-OFF-HEAT switch into the OFF position. The heating system should turn off. The fan may continue to run for a short period of time.

7. Put the AUTO-ON switch to the

ON position. The blower fan should turn on.

8. Put the AUTO-ON switch to the AUTO position. The blower fan should turn off.

COOL-OFF-HEAT

COOL-OFF-HEAT

AUTO - ON

AUTO - ON

7

Changing Fahrenheit (F) to Celsius (C)

The thermostat is preset to display the temperature in degrees Fahrenheit.

You may change the display readout to Celsius if desired.

1. Move the manual switch marked F (Fahrenheit) and C (Celsius) located at the center of the circuit board to the desired setting (page 5).

2. Press RESET button located to the right of the LCD display to register the change.

The display will change to show the temperature in your desired temperature scale. To return the thermostat to its original setting, repeat steps 1 and 2 above.

Note: Pressing the RESET button resets the 1st and 2nd stage differential to factory preset conditions.

LED Indicator

The LED indicator illuminates during a call for second stage heating or cooling. The auxiliary stages are used to maintain comfort during extremes in weather conditions. If the LED is illuminated too frequently during periods of moderate temperature, check the differential settings

(page 6).

Troubleshooting

Symptom Remedy

Thermostat does not turn on system.

Check wiring.

(See INSTALLATION)

Check fuse. Replace with 2 amp fuse if fuse has opened.

Thermostat turns on and off too frequently.

System fan does not operate properly.

Thermostat does not display proper room temperature.

Increase temperature differential.

(See DIFFERENTIAL)

Move fan option switch to either gas or electric, to match system.

(See INSTALLATION)

Check F Fahrenheit/C Celsius switch located at top center of circuit board for proper position. If a new selection is made, press

RESET button located directly below LCD display.

8

If problems with thermostat cannot be solved, call:

Technical Support: (800) 445-8299

Monday-Friday 7:30-5:30 CST

For warranty returns, send thermostat, shipping prepaid to:

Uni-Line North America

Warranty Claims Department

515 S. Promenade

Corona, CA 91719

9

Wiring Diagrams

The following is just a sample of the most common types of HVAC systems. Refer to your system’s installation manual for wiring information.

Robertshaw 9515 Multi-Stage Thermostat

C R Y2 Y1 W1 G W2 O B

C R Y/Y1 W1 G W2

2 Stage Heat / 1 Stage Cool

Robertshaw 9515 Multi-Stage Thermostat

C R Y2 Y1 W1 G W2 O B

C R Y2 Y1 W1 G W2

2 Stage Heat / 2 Stage Cool

10

Five Year Limited Warranty

Maple Chase Company

warrants to the original contractor installer, or to the original consumer user, each new Maple Chase thermostat to be free from defects in materials and workmanship under normal use and service for a period of five (5) years from date of purchase. This warranty and our liability does not apply to batteries or merchandise that has been damaged, caused by misuse, neglect, mishandling, alterations, improper installation, or use in a way other than in accordance with Maple Chase

Company recommendations and instructions.

Maple Chase Company

agrees to repair or replace at its option any thermostat under warranty provided it is returned within the warranty period, postage prepaid, with proof of the date of purchase. Cost of thermostat removal or reinstallation is not the responsibility of Maple Chase

Company.

Repair or replacement as provided under this warranty is the exclusive remedy of the consumer.

Maple Chase Company

shall not be liable for any incidental or consequential damages for breach of any express or implied warranty on this product, or under any other theory of liability.

Except to the extent prohibited by applicable law, any implied warranty of merchantability or fitness for a particular purpose on this product is limited to the duration of this warranty.

Some states do not allow the exclusion or limitation of incidental or consequential damages, or allow limitations on how long an implied warranty lasts, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

Maple Chase Company

2820 Thatcher Road

Downers Grove, Illinois 60515

United States of America

©2000 Maple Chase Company

11

1/00

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement