YASKAWA
VS-606V7 Series
INSTRUCTION MANUAL
COMPACT GENERAL-PURPOSE INVERTER
(VOLTAGE VECTOR CONTROL)
Upon receipt of the product and prior to initial operation, read these instructions thoroughly and retain them for future reference.
YASKAWA
MANUAL NO. TOE-S606-11.2H
PREFACE
Yaskawa’s VS-606V7 is a small and simple Inverter; as easy to use as a contactor. This instruction manual describes installation, maintenance, inspection, troubleshooting, and specifications of the VS-606V7. Read this instruction manual thoroughly before operation.
YASKAWA ELECTRIC CORPORATION
General Precautions
• Some drawings in this manual are shown with protective covers or shields removed in order to show detail with more clarity. Make sure all covers and shields are replaced before operating the product.
• This manual may be modified when necessary because of improvements to the product, modifications, or changes in specifications.
Such modifications are indicated by revising the manual number.
• To order a copy of this manual, or if your copy has been damaged or lost, contact your Yaskawa representative.
• Yaskawa is not responsible for any modification of the product made by the user, since that will void the guarantee.
1
2
NOTATION FOR SAFETY PRECAUTIONS
Read this instruction manual thoroughly before installation, operation, maintenance, or inspection of the VS-606V7. In this manual, safety precautions are classified as either warnings or cautions and are indicated as shown below.
WARNING
Indicates a potentially hazardous situation which, if not avoided, may result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or damage to equipment.
It may also be used to alert against unsafe practices.
Even items classified as cautions may result in serious accidents in some situations. Always follow these important precautions.
NOTE
: Indicates information to insure proper operation.
PRECAUTIONS FOR UL/cUL MARKING
• Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON.
• The Inverter internal capacitor is still charged even after the power supply is turned OFF. To prevent electric shock, disconnect all power before servicing the Inverter, and then wait at least one minute after the power supply is disconnected. Confirm that all indicators are OFF before proceeding.
• Do not perform a withstand voltage test on any part of the Inverter. The
Inverter is an electronic device that uses semiconductors, and is thus vulnerable to high voltage.
• Do not remove the Digital Operator or the blank cover unless the power supply is turned OFF. Never touch the printed circuit board (PCB) while the power supply is turned ON.
• This Inverter is not suitable for use on a circuit capable of delivering more than 18,000 RMS symmetrical amperes, 250 V maximum (200 V Class
Inverters) or 18,000 RMS symmetrical amperes, 480 V maximum (400 V
Class Inverters).
CAUTION
• Use 75 °C copper wire or equivalent.
PRECAUTIONS FOR CE MARKINGS
• Only basic insulation to meet the requirements of protection class 1 and overvoltage category II is provided with control circuit terminals.
Additional insulation may be necessary in the end product to conform to
CE requirements.
• For 400 V Class Inverters, make sure to ground the supply neutral to conform to CE requirements.
• For conformance to EMC directives, refer to the relevant manuals for the requirements.
Document No. EZZ008389 for Japanese version,
Document No. EZZ008390 for English version
3
4
RECEIVING THE PRODUCT
CAUTION
• Do not install or operate any Inverter that is damaged or has missing parts.
Failure to observe this caution may result in injury or equipment damage.
MOUNTING
CAUTION
(Ref. page)
20
• Lift the Inverter by the heatsinks. When moving the Inverter, never lift it by the plastic case or the terminal cover.
Otherwise, the main unit may fall and be damaged.
• Mount the Inverter on nonflammable material
(i.e., metal).
Failure to observe this caution may result in a fire.
• When mounting Inverters in an enclosure, install a fan or other cooling device to keep the intake air temperature below 50 °C for IP20 (open chassis type), or below 40 °C for NEMA 1 (TYPE
1).
Overheating may cause a fire or damage the Inverter.
• The VS-606V7 generates heat. For effective cooling, mount it vertically.
Refer to the figure in Mounting Dimensions on page 26 .
(Ref. page)
26
25
25
26
WIRING
WARNING
• Only begin wiring after verifying that the power supply is turned OFF.
Failure to observe this warning may result in an electric shock or a fire.
• Wiring should be performed only by qualified personnel.
Failure to observe this warning may result in an electric shock or a fire.
• When wiring the emergency stop circuit, check the wiring thoroughly before operation.
Failure to observe this warning may result in injury.
• Always ground the ground terminal according to the local grounding code.
Failure to observe this warning may result in an electric shock or a fire.
• For 400 V class, make sure to ground the supply neutral.
Failure to observe this warning may result in an electric shock or a fire.
• If the power supply is turned ON during the
FWD (or REV) RUN command is given, the motor will start automatically.
Turn the power supply ON after verifying that the RUN signal is OFF.
Failure to observe this warning may result in injury.
• When the 3-wire sequence is set, do not make the wiring for the control circuit unless the multifunction input terminal parameter is set.
Failure to observe this warning may result in injury.
(Ref. page)
30
30
30
36
30
39
90
5
6
CAUTION
• Verify that the Inverter rated voltage coincides with the AC power supply voltage.
Failure to observe this caution may result in personal injury or a fire.
• Do not perform a withstand voltage test on the
Inverter.
Performing withstand voltage tests may damage semiconductor elements.
• To connect a Braking Resistor, Braking Resistor
Unit, or Braking Unit, follow the procedure described in this manual.
Improper connection may cause a fire.
• Always tighten terminal screws of the main circuit and the control circuits.
Failure to observe this caution may result in a malfunction, damage, or a fire.
• Never connect the AC main circuit power supply to output terminals U/T1, V/T2, W/T3, B1, B2, -,
+1, or +2.
The Inverter will be damaged and the guarantee will be voided.
• Do not connect or disconnect wires or connectors while power is applied to the circuits.
Failure to observe this caution may result in injury.
• Do not perform signal checks during operation.
The machine or the Inverter may be damaged.
• To store the constant with an ENTER command by communications, be sure to take measures for an emergency stop by using the external terminals.
Delayed response may cause injury or damage the machine.
(Ref. page)
30
30
37
30
30
30
30
119
OPERATION
WARNING
• Only turn ON the input power supply after confirming that the Digital Operator or blank cover
(optional) are in place. Do not remove the
Digital Operator or the covers while current is flowing.
Failure to observe this warning may result in an electric shock.
• Never operate the Digital Operator or DIP switches with wet hands.
Failure to observe this warning may result in an electric shock.
• Never touch the terminals while current is flowing, even if the Inverter is stopping.
Failure to observe this warning may result in an electric shock.
• When the fault retry function is selected, stand clear of the Inverter or the load. The Inverter may restart suddenly after stopping.
(Construct the system to ensure safety, even if the
Inverter should restart.) Failure to observe this warning may result in injury.
• When continuous operation after power recovery is selected, stand clear of the Inverter or the load. The Inverter may restart suddenly after stopping.
(Construct the system to ensure safety, even if the
Inverter should restart.) Failure to observe this warning may result in injury.
• The Digital Operator stop button can be disabled by a setting in the Inverter. Install a separate emergency stop switch.
Failure to observe this warning may result in injury.
(Ref. page)
40
40
40
75
70
84
7
8
WARNING
• If an alarm is reset with the operation signal ON, the Inverter will restart automatically. Reset an alarm only after verifying that the operation signal is OFF.
Failure to observe this warning may result in injury.
• When the 3-wire sequence is set, do not make the wiring for the control circuit unless the multifunction input terminal parameter is set.
Failure to observe this warning may result in injury.
CAUTION
(Ref. page)
39
90
• Never touch the heatsinks, which can be extremely hot.
Failure to observe this caution may result in harmful burns to the body.
• It is easy to change operation speed from low to high. Verify the safe working range of the motor and machine before operation.
Failure to observe this caution may result in injury and machine damage.
• Install a holding brake separately if necessary.
Failure to observe this caution may result in injury.
• If using an Inverter with an elevator, take safety measures on the elevator to prevent the elevator from dropping.
Failure to observe this caution may result in injury.
• Do not perform signal checks during operation.
The machine or the Inverter may be damaged.
(Ref. page)
40
40
40
153
40
CAUTION
• All the constants set in the Inverter have been preset at the factory. Do not change the settings unnecessarily.
The Inverter may be damaged.
(Ref. page)
40
9
MAINTENANCE AND INSPECTION
WARNING
(Ref. page)
157 • Never touch high-voltage terminals on the
Inverter.
Failure to observe this warning may result in an electrical shock.
• Disconnect all power before performing maintenance or inspection, and then wait at least one minute after the power supply is disconnected.
Confirm that all indicators are OFF before proceeding.
If the indicators are not OFF, the capacitors are still charged and can be dangerous.
• Do not perform withstand voltage test on any part of the VS-606V7.
The Inverter is an electronic device that uses semiconductors, and is thus vulnerable to high voltage.
• Only authorized personnel should be permitted to perform maintenance, inspection, or parts replacement.
(Remove all metal objects (watches, bracelets, etc.) before starting work.)
(Use tools which are insulated against electrical shock.)
Failure to observe these warnings may result in an electric shock.
157
157
157
10
CAUTION
• The control PCB employs CMOS ICs.
Do not touch the CMOS elements.
They are easily damaged by static electricity.
• Do not connect or disconnect wires, connectors, or the cooling fan while power is applied to the circuit.
Failure to observe this caution may result in injury.
OTHERS
(Ref. page)
157
157
WARNING
• Never modify the product.
Failure to observe this warning may result in an electrical shock or injury and will void the guarantee.
CAUTION
• Do not subject the Inverter to halogen gases, such as fiuorine, chlovine, bromine, and iodine, at any time even during transportation or installation.
Otherwise, the Inverter can be damaged or interior parts burnt.
11
WARNING LABEL
A warning label is provided on the front cover of the Inverter, as shown below.
Follow the warnings when handling the Inverter.
Plastic Case Top Cover (in case of 5.5/7.5 kW)
Status
Indicators
Nameplate
Warning Label Location
Warning Labels
12
Example of 5.5 kW for 400 V
WARRANTY INFORMATION
Free Warranty Period and Scope
Warranty Period
This product is warranted for twelve months after being delivered to
Yaskawa’s customer or if applicable eighteen months from the date of shipment from Yaskawa’s factory, whichever comes first.
Scope of Warranty
Inspections
Periodic inspections must be conducted by the customer. However, upon request, Yaskawa or one of Yaskawa’s Service Centers can inspect the product for a fee. In this case, if after conferring with the customer, a
Yaskawa product is found to be defective due to Yaskawa workmanship or materials and the defect occurs during the warranty period, then this fee will be waived and the problem remedied free of charge.
Repairs
If a Yaskawa product is found to be defective due to Yaskawa workmanship or materials and the defect occurs during the warranty period,
Yaskawa will provide a replacement, repair the defective product, and provide shipping to and from the site free of charge.
However, if the Yaskawa Authorized Service Center determines that the problem with a Yaskawa product is not due to defects in Yaskawa’s workmanship or materials, then the customer will be responsible for the cost of any necessary repairs. Some problems that are outside the scope of this warranty are:
• Problems due to improper maintenance or handling, carelessness, or other reasons where the customer is determined to be responsible.
• Problems due to additions or modifications made to a Yaskawa product without Yaskawa’s understanding.
• Problems due to the use of a Yaskawa product under conditions that do not meet the recommended specifications.
• Problems caused by natural disaster or fire.
• Or other problems not due to defects in Yaskawa workmanship or materials.
Warranty service is only applicable within Japan.
However, after-sales service is available for customers outside of Japan for a reasonable fee. Contact your local Yaskawa representative for more information.
13
Exceptions
Any inconvenience to the customer or damage to non-Yaskawa products due to Yaskawa's defective products whether within or outside the warranty period are NOT covered by this warranty.
RESTRICTIONS
• The VS-606V7 was not designed or manufactured or made for use in devices or systems that may directly affect or threaten human lives or health.
• Customers who intend to use the product described in this manual for devices or systems relating to transportation, health care, space aviation, atomic or electric power, or underwater use must contact your Yaskawa representatives or the nearest Yaskawa sales office beforehand.
• This product has been manufactured or made under strict quality-control guidelines. However, if this product is to be installed in any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a facility where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of any accident.
14
CONTENTS
NOTATION FOR SAFETY PRECAUTIONS - - - - - - 2
1. Receiving the Product - - - - - - - - - - - - - - - - - - - 20
Checking the Nameplate - - - - - - - - - - - - - - - - - - - - - - - - - - - 21
2. Identifying the Parts- - - - - - - - - - - - - - - - - - - - - 22
3. Mounting - - - - - - - - - - - - - - - - - - - - - - - - - - - - 25
Choosing a Location to Mount the Inverter - - - - - - - - - - - - - - 25
Mounting Dimensions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 26
Mounting/Removing Components- - - - - - - - - - - - - - - - - - - - - 27
Removing the Front Cover - - - - - - - - - - - - - - - - - - - - - - - - - - 27
Mounting the Front Cover - - - - - - - - - - - - - - - - - - - - - - - - - - 27
Removing the Terminal Cover - - - - - - - - - - - - - - - - - - - - - - - 27
Mounting the Terminal Cover - - - - - - - - - - - - - - - - - - - - - - - - 28
Removing the Digital Operator - - - - - - - - - - - - - - - - - - - - - - - 28
Mounting the Digital Operator- - - - - - - - - - - - - - - - - - - - - - - - 28
Removing the Bottom Cover - - - - - - - - - - - - - - - - - - - - - - - - 29
Mounting the Bottom Cover - - - - - - - - - - - - - - - - - - - - - - - - - 29
4. Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 30
Wire and Terminal Screw Sizes - - - - - - - - - - - - - - - - - - - - - - 32
Wiring the Main Circuits- - - - - - - - - - - - - - - - - - - - - - - - - - - - 36
Wiring the Control Circuits - - - - - - - - - - - - - - - - - - - - - - - - - - 38
Wiring Inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 39
5. Operating the Inverter - - - - - - - - - - - - - - - - - - - 40
Test Run - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 41
Selecting Rotation Direction - - - - - - - - - - - - - - - - - - - - - - - - - 43
Operation Check Points- - - - - - - - - - - - - - - - - - - - - - - - - - - - 43
Operating the Digital Operator - - - - - - - - - - - - - - - - - - - - - - - 44
Description of Status Indicators - - - - - - - - - - - - - - - - - - - - - - 45
Function Indicator Description - - - - - - - - - - - - - - - - - - - - - - - 46
MNTR Multi-function Monitoring - - - - - - - - - - - - - - - - - - - - - - 47
15
Input/Output Terminal Status - - - - - - - - - - - - - - - - - - - - - - - - - 49
Data Reception Error Display - - - - - - - - - - - - - - - - - - - - - - - - 49
Simple Data Setting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 51
6. Programming Features - - - - - - - - - - - - - - - - - - 53
Constant Setup and Initialization - - - - - - - - - - - - - - - - - - - - - - 53
Constant Selection/Initialization (n001) - - - - - - - - - - - - - - - - - 53
Using V/f Control Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - 55
Adjusting Torque According to Application - - - - - - - - - - - - - - - 55
Using Vector Control Mode - - - - - - - - - - - - - - - - - - - - - - - - - - 58
Precautions for Voltage Vector Control Application - - - - - - - - - 58
Motor Constant Calculation- - - - - - - - - - - - - - - - - - - - - - - - - - 59
V/f Pattern during Vector Control - - - - - - - - - - - - - - - - - - - - - - 60
Switching LOCAL/REMOTE Mode - - - - - - - - - - - - - - - - - - - - 61
How to Select LOCAL/REMOTE Mode - - - - - - - - - - - - - - - - - 62
Selecting RUN/STOP Commands - - - - - - - - - - - - - - - - - - - - - 62
LOCAL Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 62
REMOTE Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 63
Operating (RUN/STOP Commands) by Communications- - - - - 63
Selecting Frequency Reference - - - - - - - - - - - - - - - - - - - - - - 63
LOCAL Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 64
REMOTE Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 64
Setting Operation Conditions - - - - - - - - - - - - - - - - - - - - - - - - 65
Reverse Run Prohibit (n006)- - - - - - - - - - - - - - - - - - - - - - - - - 65
Multi-step Speed Selection - - - - - - - - - - - - - - - - - - - - - - - - - - 65
Operating at Low Speed - - - - - - - - - - - - - - - - - - - - - - - - - - - - 66
Adjusting Speed Setting Signal - - - - - - - - - - - - - - - - - - - - - - - 67
Adjusting Frequency Upper and Lower Limits - - - - - - - - - - - - - 68
Using Four Acceleration/Deceleration Times - - - - - - - - - - - - - 68
Momentary Power Loss Ridethrough Method (n081) - - - - - - - - 70
S-curve Selection (n023) - - - - - - - - - - - - - - - - - - - - - - - - - - - 71
Torque Detection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 72
Frequency Detection Level (n095) - - - - - - - - - - - - - - - - - - - - - 73
Jump Frequencies (n083 to n086) - - - - - - - - - - - - - - - - - - - - - 74
Continuing Operation Using Automatic Retry Attempts (n082) - 75
Operating a Coasting Motor without Tripping - - - - - - - - - - - - - 75
Holding Acceleration/Deceleration Temporarily - - - - - - - - - - - - 76
16
Using Frequency Meter or Ammeter (n066) - - - - - - - - - - - - - - 77
Calibrating Frequency Meter or Ammerter (n067)- - - - - - - - - - 78
Using Analog Output (AM-AC) as a Pulse Train Signal Output
(n065) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 78
Reducing Motor Noise or Leakage Current Using Carrier
Frequency Selection (n080) - - - - - - - - - - - - - - - - - - - - - - - - - 81
Operator Stop Key Selection (n007) - - - - - - - - - - - - - - - - - - - 84
Selecting the Stopping Method- - - - - - - - - - - - - - - - - - - - - - - 85
Stopping Method Selection (n005) - - - - - - - - - - - - - - - - - - - - 85
Applying DC Injection Braking - - - - - - - - - - - - - - - - - - - - - - - 86
Building Interface Circuits with External Devices - - - - - - - - - - 88
Using Input Signals - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 88
Using the Multi-function Analog Inputs (n077, n078, n079) - - - 92
Using Output Signals (n057, n058, n059) - - - - - - - - - - - - - - - 95
Setting Frequency by Current Reference Input - - - - - - - - - - - 97
Frequency Reference by Pulse Train Input - - - - - - - - - - - - - - 99
Preventing the Motor from Stalling (Current Limit) - - - - - - - - 100
Stall Prevention during Operation - - - - - - - - - - - - - - - - - - - - 102
Decreasing Motor Speed Fluctuation - - - - - - - - - - - - - - - - - 104
Slip Compensation (n002 = 0) - - - - - - - - - - - - - - - - - - - - - - 104
Motor Protection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 105
Motor Overload Detection - - - - - - - - - - - - - - - - - - - - - - - - - 105
Selecting Cooling Fan Operation - - - - - - - - - - - - - - - - - - - - 107
Using MEMOBUS (MODBUS) Communications - - - - - - - - - 107
MEMOBUS (MODBUS) Communications - - - - - - - - - - - - - - 107
Communications specified - - - - - - - - - - - - - - - - - - - - - - - - - 108
Communications Connection Terminal - - - - - - - - - - - - - - - - 108
Setting Constants Necessary for Communication- - - - - - - - - 109
Message Format- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 110
Storing Constants [ENTER Command] (can be written only.)- 119
Performing Self-test - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 122
Using Energy-saving Control Mode - - - - - - - - - - - - - - - - - - 123
Energy-saving Control Selection (n139) - - - - - - - - - - - - - - - 123
Energy-saving Search Operation - - - - - - - - - - - - - - - - - - - - 124
Motor Code - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 127
Using PID Control Mode - - - - - - - - - - - - - - - - - - - - - - - - - - 128
PID Control Selection (n128) - - - - - - - - - - - - - - - - - - - - - - - 129
17
Using Constant Copy Function - - - - - - - - - - - - - - - - - - - - - - 136
Constant Copy Function - - - - - - - - - - - - - - - - - - - - - - - - - - - 136
READ Function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 138
COPY Function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 139
VERIFY Function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 141
Inverter Capacity Display - - - - - - - - - - - - - - - - - - - - - - - - - - 143
Software No. Display - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 145
Display List - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 145
Unit Selection for Frequency Reference Setting/Display - - - - 147
Selecting Processing for Frequency Reference Loss (n064) - 149
Input/Output Open-phase Detection - - - - - - - - - - - - - - - - - - 150
Undertorque Detection - - - - - - - - - - - - - - - - - - - - - - - - - - - - 151
Using Inverter for Elevating Machines - - - - - - - - - - - - - - - - - 153
Brake ON/OFF Sequence- - - - - - - - - - - - - - - - - - - - - - - - - - 153
Stall Prevention During Deceleration - - - - - - - - - - - - - - - - - - 155
Settings for V/f Pattern and Motor Constants - - - - - - - - - - - - 155
Momentary Power Loss Restart and Fault Restart- - - - - - - - - 155
I/O Open-phase Protection and Overtorque Detection - - - - - - 155
Carrier Frequency - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 155
External Baseblock Signal - - - - - - - - - - - - - - - - - - - - - - - - - 156
Acceleration/Deceleration Time - - - - - - - - - - - - - - - - - - - - - - 156
Contactor on the Inverter’s Output-side - - - - - - - - - - - - - - - - 156
7. Maintenance and Inspection - - - - - - - - - - - - - 157
Periodic Inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 158
Part Replacement - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 159
Replacement of Cooling Fan- - - - - - - - - - - - - - - - - - - - - - - - 160
8. Fault Diagnosis - - - - - - - - - - - - - - - - - - - - - - - 162
Protective and Diagnostic Functions - - - - - - - - - - - - - - - - - - 162
Corrective Actions of Models with Blank Cover - - - - - - - - - - - 162
Corrective Actions of Models with Digital Operator - - - - - - - - 163
Troubleshooting- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 175
9. Specifications - - - - - - - - - - - - - - - - - - - - - - - - 177
Standard Specifications (200 V Class) - - - - - - - - - - - - - - - - - 177
18
Standard Specifications (400 V Class) - - - - - - - - - - - - - - - - 181
Standard Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 184
Sequence Input Connection with NPN/PNP Transistor - - - - - 188
Dimensions/Heat Loss - - - - - - - - - - - - - - - - - - - - - - - - - - - 190
Recommended Peripheral Devices- - - - - - - - - - - - - - - - - - - 193
Constants List - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 196
10 Conformance to CE Markings - - - - - - - - - - - - 209
CE Markings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 209
Requirements for Conformance to CE Markings - - - - - - - - - 209
Low Voltage Directive - - - - - - - - - - - - - - - - - - - - - - - - - - - - 209
EMC Directive - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 210
Revision History
19
1. Receiving the Product
CAUTION
Do not install or operate any Inverter that is damaged or has missing parts.
Failure to observe this caution may result in injury or equipment damage.
After unpacking the VS-606V7, check the following.
• Verify that the model number matches your purchase order or packing slip.
• Check the Inverter for physical damage that may have occurred during shipping.
If any part of VS-606V7 is missing or damaged, call for service immediately.
20
1. Receiving the Product
Checking the Nameplate
Example for 3-phase, 200-VAC, 0.1-kW Inverter for Asian standards
Inverter Model
Input Spec.
Output Spec.
Lot No.
Serial No.
CIMR-V7AT20P1 20P10
Mass
Software Number
Model
Inverter
VS-606V7 Series
Note: If the inverter meets Japanese domestic standards, V7 indicates the VS mini V7
Series.
No.
Type
A
B
C
With Digital Operator (with potentiometer)
Without Digital Operator (with blank cover)
With Digital Operator (without potentiometer)
Note: Contact your Yaskawa representatives
for models without heatsinks.
A T
Specifications
No.
B
2
4
No.
T
A
0P1
0P2
0P4
0P7
1P5
2P2
3P0
3P7
5P5
7P5
Max. applicable motor output
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
3.7 kW
5.5 kW
7.5 kW
Voltage Class
Single-phase 200 VAC
Three-phase 200 VAC
Three-phase 400 VAC
Specifications
Asian standards
Japan domestic standards
B
2
4
Single-phase 200 VAC
Three-phase 200 VAC
Three-phase 400 VAC
1P5
2P2
3P0
3P7
0P1
0P2
0P4
0P7
5P5
7P5
Max. applicable motor output
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
3.7 kW
5.5 kW
7.5 kW
No.
Protective structure
0
Open chassis
(IP20, IP00)* 1
1
Enclosed wall-mounted
(NEMA1)* 2
*1: Inverters with outputs 0P1 to 3P7
are rated IP20. Be sure to remove
the top and bottom covers if using
open-chassis mounted Inverters
with a 5P5 or 7P5 output.
*2: A NEMA 1 rating is optional for
Inverters with outputs 0P1 to 3P7
but standard for 5P5 or 7P5.
21
2. Identifying the Parts
Terminal Cover
Digital Operator
Wiring Holes for Control Circuit
Wiring Holes for Main Circuit
Ground Terminal
Cooling Fan
Fan Cover
Front Cover
Nameplate
Heatsink
Bottom Cover
Digital operator
(with potentiometer)
JVOP-140
Used for setting or changing constants.
Frequency can be set using potentiometer.
Digital operator
(without potentiometer)
JVOP-147
Used for setting or changing constants.
Blank cover
In models without a
Digital Operator, the blank cover is mounted in place of the Digital
Operator.
22
2. Identifying the Parts
VS-606V7 Inverters with the Covers Removed
Input Polarity
Switch
Short-circuit
Bar
Frequency Setting Potentiometer
Inverter Operation Status Indicators
Terminal Resistor Switch for
Communication Circuit
Voltage/Current Change Switch for
Analog Frequency Reference Input
Control Circuit Terminal Block
Main Circuit Terminal Block
Ground Terminals
Example for 3-phase (200 V Class, 1.5 kW) Inverter
Frequency Setting Potentiometer
Inverter Operation Status Indicators
Input Polarity
Switch
Terminal Resistor Switch for
Communication Circuit
Voltage/Current Change Switch for
Analog Frequency Reference Input
Control Circuit Terminal Block
Main Circuit Terminal Block
Short-circuit
Bar
Ground Terminals
Example for 3-phase (200 V Class, 0.1 kW) Inverter
23
Main Circuit Terminal Arrangement
The terminal arrangement of the main circuit terminals depends on the
Inverter model.
CIMR-V7
∗T20P1 to 20P7, B0P1 to B0P4
CIMR-V7 ∗T21P5, 22P2, B0P7, B1P5, 40P2 to 42P2
24
CIMR-V7 ∗T23P7, B2P2, 43P0, 43P7
CIMR-V7 ∗TB3P7
CIMR–V7 ∗ T25P5, 27P5, 45P5, 47P5
R/L1 S/L2 T/L3 +1 +2 B1 B2 U/T1 V/T2 W/T3
3. Mounting
3. Mounting
Choosing a Location to Mount the Inverter
Be sure the Inverter is protected from the following conditions.
• Extreme cold and heat. Use only within the specified ambient temperature range:
−10 to 50°C for IP20 (open chassis type),
−10 to 40°C for NEMA 1 (TYPE 1)
• Rain and moisture
• Oil sprays and splashes
• Salt spray
• Direct sunlight (Avoid using outdoors.)
• Corrosive gases (e.g., sulfurized gas) or liquids
• Dust or metallic particles in the air
• Physical shock or vibration
• Magnetic noise (Examples: Welding machines, power devices, etc.)
• High humidity
• Radioactive substances
• Combustibles, such as thinner or solvents
25
Mounting Dimensions
To mount the VS-606V7, the dimensions shown below are required.
a a Air
100 mm or more
26
100 mm or more
Air
Voltage Class
(V)
200 V 3-phase
400 V 3-phase
Max. Applicable
Motor Capacity
(kW)
5.5 kW
7.5 kW
Length a
200 V Single-phase
3-phase
400 V 3-phase
3.7 kW or less 30 mm min.
50 mm min.
CAUTION
• Lift the Inverter by the heatsinks. When moving the
Inverter, never lift it by the plastic case or the terminal cover.
Otherwise, the main unit may fall and be damaged.
• The VS-606V7 generates heat. For effective cooling, mount it vertically.
3. Mounting
NOTE
• The same space is required horizontally and vertically and right and left for both Open Chassis (IP00, IP20) and
Enclosed Wall-mounted (NEMA 1) Inverters.
• Always remove the top and bottom covers before installing a 200 or 400 V Class Inverter with an output of 5.5/7.5 kW in a panel.
Mounting/Removing Components
Removing and Mounting the Digital Operator and Covers
Removing the Front Cover
Use a screwdriver to loosen the screw on the front cover and then remove it in direction 1. Then press the right and left sides in direction 2 and lift the front cover in direction 3.
Mounting the Front Cover
Mount the front cover by reversing the order of the above procedure for removal.
Removing the Terminal Cover
• Inverters with Width of 108 mm,
140 mm or 170 mm
After removing the front cover, press the right and left sides of the terminal cover in direction 1 and lift the terminal cover in direction
2.
27
28
• Inverters with Width of 180 mm
Use a screwdriver to loosen the screw on the terminal cover surface to direction 1. Then press the right and left sides in direction 2 and lift the terminal cover in direction 3.
Mounting the Terminal Cover
Mount the terminal cover by reversing the order of the above procedure for removal.
2
Removing the Digital
Operator
After removing the front cover, lift the upper and lower sides (section
A) of the right side of the Digital
Operator in direction 1.
Mounting the Digital Operator
Mount the Digital Operator by reversing the order of the above procedure for removal.
1
3
2
A
A
Removing the Bottom Cover
• Inverters with Width of 108 mm, 140 mm or 170 mm
After removing the front cover and the terminal cover, tilt the bottom cover in direction 1 with section A as a supporting point.
A
A
3. Mounting
• Inverters with Width of 180 mm
After removing the terminal cover, use a screwdriver to loosen the mounting screw in direction 1.
1
1
Mounting the Bottom Cover
Mount the bottom cover by reversing the order of the above procedure for removal.
29
4. Wiring
WARNING
• Only begin wiring after verifying that the power supply is turned OFF.
Failure to observe this warning may result in an electric shock or a fire.
• Wiring should be performed only by qualified personnel.
Failure to observe this warning may result in an electric shock or a fire.
• When wiring the emergency stop circuit, check the wiring thoroughly before operation.
Failure to observe this warning may result in injury.
• For 400 V class, make sure to ground the supply neutral.
Failure to observe this warning may result in an electric shock or a fire.
CAUTION
• Verify that the Inverter rated voltage coincides with the AC power supply voltage.
Failure to observe this caution may result in personal injury or a fire.
• Do not perform a withstand voltage test on the
Inverter.
Performing withstand voltage tests may damage semiconductor elements.
• Always tighten terminal screws of the main circuit and the control circuits.
Failure to observe this caution may result in a malfunction, damage, or a fire.
• Never connect the AC main circuit power supply to output terminals U/T1, V/T2, W/T3, B1, B2, −, +1, or +2.
The Inverter will be damaged and the guarantee will be voided.
• Do not connect or disconnect wires or connectors while power is applied to the circuits.
Failure to observe this caution may result in injury.
• Do not perform signal checks during operation.
The machine or the Inverter may be damaged.
• To store the constant with an ENTER command by communications, be sure to take measures for an
30
4. Wiring emergency stop by using the external terminals.
Delayed response may cause injury or damage the machine.
NOTE
Wiring Instructions
1. Always connect the power supply for the main circuit inputs to the power input terminals R/L1, S/L2, and T/L3
(R/L1, S/L2 for single-phase power) via a molded-case circuit breaker (MCCB) or a fuse. Never connect the power supply to terminals U/T1, V/T2, W/T3, B1, B2, −,
+1, or +2. The Inverter may be damaged.
For single-phase Inverters, always use terminals R/L1 and
S/L2. Never connect terminal T/L3. Fuses must be of ULclass RK5 fuse or an equivalent.
Refer to page 193 for recommended peripheral devices.
Inverter Power Supply Connection Terminals
200-V 3-phase Input
Power Supply Specification Inverters
CIMR-V72
Connect to R/L1,
S/L2, and T/L3.
200-V Single Input
Power Supply Specification Inverters
CIMR-V7B
Connect to R/L1 and
S/L2.
400-V 3-phase Input
Power Supply Specification Inverters
CIMR-V74
Connect to R/L1,
S/L2, and T/L3.
2. If the wiring distance between Inverter and motor is long, reduce the Inverter carrier frequency. For details, refer to
Reducing Motor Noise or Leakage Current Using Carrier
Frequency Selection (n080) on page 81.
3. Control wiring must be less than 50 m in length and must be separated from power wiring. Use shielded twisted-pair cable when inputting the frequency signal externally.
4. Only basic insulation to meet the requirements of protection class 1 and overvoltage category II is provided with control circuit terminals. Additional insulation may be necessary in the end product to conform to CE requirements.
5. Closed-loop connectors should be used when wiring to the main circuit terminals.
6. Voltage drop should be considered when determining the
31
wire size.
Voltage drop can be calculated using the following equation:
Phase-to-phase voltage drop (V)
× current
(A)
3 × wire resistance (Ω/km) × wiring distance (m)
× 10 -3
Select a wire size so that voltage drop will be less than 2% of the normal rated voltage.
7. If the Inverter is connected to a power transformer exceeding 600 kVA, excessive peak current may flow into the input power supply circuit, and break the converter section. In this case, attach an AC reactor (optional) to the
Inverter input side, or a DC reactor (optional) to the DC reactor connection terminal.
Wire and Terminal Screw Sizes
1. Control Circuits
Model Terminal
Symbols
Same for all models
MA, MB, MC
S1 to S7, P1,
P2, SC, PC,
R+, R-, S+, S-,
FS, FR, FC,
AM, AC, RP
Screws Tightening
Torque
N •m
M3
M2
Applicable Size
0.5 to 0.6
mm
2
Twisted wires: 0.5 to 1.25,
Single: 0.5 to 1.25
0.22 to 0.25 Twisted wires: 0.5 to 0.75,
Single: 0.5 to 1.25
Wires
AWG
20 to 16,
20 to 16
20 to 18,
20 to 16
Recommended Size mm
2 AWG
0.75
18
Type
Shielded or equivalent
0.75
18
32
4. Wiring
Model
2. Main Circuits
200 V Class 3-phase Input Inverters
Terminal Symbols Screws
CIMR-
V7 ∗T
20P1
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M3.5
Tightening
Torque
N •m
0.8 to 1.0
Applicable Size mm 2
0.75 to 2
AWG
18 to 14
Wires
Recommended
Size mm 2 AWG
2 14
Type
600 V vinylsheathed or equivalent
CIMR-
V7 ∗T
20P2
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M3.5
0.8 to 1.0
0.75 to 2 18 to 14 2 14
CIMR-
V7 ∗T
20P4
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M3.5
0.8 to 1.0
0.75 to 2 18 to 14 2 14
CIMR-
V7 ∗T
20P7
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M3.5
0.8 to 1.0
0.75 to 2 18 to 14 2 14
CIMR-
V7 ∗T
21P5
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4
CIMR-
V7 ∗T
22P2
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4
1.2 to 1.5
2 to 5.5
14 to 10 2
1.2 to 1.5
2 to 5.5
14 to 10
3.5
3.5
14
12
12
CIMR-
V7 ∗T
23P7
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4 1.2 to 1.5
2 to 5.5
14 to 10 5.5
10
CIMR-
V7 ∗T
25P5
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M5 2.5
5.5 to 8 10 to 8 8 8
CIMR-
V7 ∗T
27P5
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M5 2.5
5.5 to 8 10 to 8 8
Note: The wire size is given for copper wire at 75 °C.
8
33
Model
200 V Class Single-phase Input Inverters
Terminal Symbols Screws
CIMR-
V7 ∗T
B0P1
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M3.5
Tightening
Torque
N •m
0.8 to 1.0
Applicable Size mm
2
0.75 to 2
AWG
18 to 14
Wires
Recommended
Size mm
2 AWG
2 14
Type
600 V vinylsheathed or equivalent
CIMR-
V7 ∗T
B0P2
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M3.5
0.8 to 1.0
0.75 to 2 18 to 14 2 14
CIMR-
V7 ∗T
B0P4
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M3.5
0.8 to 1.0
0.75 to 2 18 to 14 2 14
CIMR-
V7 ∗T
B0P7
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4 1.2 to 1.5
2 to 5.5
14 to 10 3.5
12
CIMR-
V7 ∗T
B1P5
R/L1, S/L2, -, +1,
+2, B1, B2, U/T1,
V/T2, W/T3
M4 1.2 to 1.5
2 to 5.5
14 to 10 5.5
10
CIMR-
V7 ∗T
B2P2
R/L1, S/L2, -, +1,
+2, B1, B2, U/T1,
V/T2, W/T3
M4 1.2 to 1.5
2 to 5.5
14 to 10 5.5
10
CIMR-
V7 ∗T
B3P7
R/L1, S/L2, -, +1,
+2, B1, B2, U/T1,
V/T2, W/T3
M5 3.0
3.5 to 8 12 to 8 8 8
M4 1.2 to 1.5
2 to 8 14 to 8
Note: 1. The wire size is given for copper wire at 75 °C.
2. Do not use terminal T/L3 on Inverters with single-phase input.
34
4. Wiring
Model
CIMR-
V7 ∗T
40P2
400 V Class 3-phase Input Inverters
Terminal Symbols Screws
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4
Tightening
Torque
N •m
1.2 to 1.5
Applicable Size mm
2
2 to 5.5
AWG
14 to 10
Wires
Recommended
Size mm
2 AWG
2 14
Type
600 V vinylsheathed or equivalent
CIMR-
V7 ∗T
40P4
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4 1.2 to 1.5
2 to 5.5
14 to 10 2 14
CIMR-
V7 ∗T
40P7
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4 1.2 to 1.5
2 to 5.5
14 to 10 2 14
CIMR-
V7 ∗T
41P5
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4 1.2 to 1.5
2 to 5.5
14 to 10 2 14
CIMR-
V7 ∗T
42P2
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4 1.2 to 1.5
2 to 5.5
14 to 10 2 14
CIMR-
V7 ∗T
43P0
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4
CIMR-
V7 ∗T
43P7
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4
CIMR-
V7 ∗T
45P5
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M4
1.2 to 1.5
1.2 to 1.5
1.4
2 to 5.5
14 to 10 2
2 to 5.5
14 to 10
3.5
2
3.5 to
5.5
12 to 10
3.5
5.5
14
12
14
12
10
CIMR-
V7 ∗T
47P5
R/L1, S/L2, T/L3,
-, +1, +2, B1, B2,
U/T1, V/T2, W/T3
M5 2.5
5.5 to 8 10 to 8 5.5
10
Note: The wire size is given for copper wire at 75 °C.
35
Wiring the Main Circuits
[Example of 3-phase,
400 V class, 0.2 kW Inverters]
MCCB or
Leakage
Breaker
Grounding
• Main Circuit Input Power Supply
Always connect the power supply line to input terminals R/L1, S/L2, and T/L3 (R/L1, S/
L2 for single-phase Inverters). Never connect them to terminals U/T1, V/T2, W/T3, B1,
B2, −, +1, or +2. The Inverter may be damaged if the wrong terminals are connected.
NOTE
For single-phase Inverters, always use terminals R/L1 and S/L2. Never connect terminal T/L3.
• Grounding (Use ground terminal .)
WARNING Always ground the ground terminal according to local grounding codes.
Failure to observe this warning may result in an electric shock or a fire.
Never ground the VS-606V7 to the same ground as welding machines, motors, or other electrical equipment.
When several VS-606V7 Inverters are used side by side, ground each as shown in examples. Do not loop the ground wires.
Good Good Poor
36
4. Wiring
• Braking Resistor Connection (Optional)
WARNING
To connect the braking resistor, cut the protector on terminals
B1 and B2.
To protect the braking resistor from overheating, install a thermal overload relay between the braking resistor and the
Inverter. This provides a sequence that turns OFF the power supply with thermal relay trip contacts.
Failure to observe this warning may result in a fire.
Use this same procedure when connecting a Braking Resistor Unit.
Refer to page 185.
• Inverter Output
Connect the motor terminals to U/T1, V/T2, and W/T3.
• Wiring the Main Circuit Terminals
Pass the cables through wiring hole to connect them. Always mount the cover in its original position.
Connect with a Phillips screwdriver.
37
Wiring the Control Circuits
Only basic insulation is provided for the control circuit terminals.
Additional insulation may be necessary in the end product.
• Control Circuit Terminals
Pass the cable through wiring hole to connect it. Always mount the cover in its original position.
Contact Output
38
SW1 can be changed according to sequence input signal (S1 to S7) polarity.
0 V common: NPN side (Factory setting)
+24 V common: PNP side
Refer to pages 188 and 189 for SW1.
Refer to pages 97 and 108 for SW2.
Wiring the Control Circuit Terminals Screwdriver Blade Width
0.4 mm max.
2.5 mm max.
Insert the wire into the lower part of the terminal block and connect it tightly with a screwdriver.
5.5 mm
The wire sheath strip length must be 5.5 mm.
4. Wiring
Open the front cover and verify that the strip length is 5.5 mm.
5.5mm
Scale
SW1
CONTACT OUTPUT
SW2
Wiring Inspection
After completing wiring, check the following.
• Wiring is proper.
• Wire clippings or screws are not left in the Inverter.
• Screws are securely tightened.
• Bare wires in the terminals do not contact other terminals.
WARNING
If the power supply is turned ON during the FWD (or
REV) RUN command is given, the motor will start automatically.
Turn the power supply ON after verifying that the
RUN signal is OFF.
Failure to observe this warning may result in injury.
NOTE
1. If the FWD (or REV) RUN command is given when the
RUN command from the control circuit terminal is selected (n003 = 1), the motor will start automatically after the main circuit input power supply is turned ON.
2. To set the 3-wire sequence, set terminal S3 (n052) to 0.
39
5. Operating the Inverter
The Control Mode Selection (n002) is initially set to V/f control mode.
WARNING
• Only turn ON the input power supply after confirming that the Digital Operator or blank cover
(optional) are in place. Do not remove the Digital
Operator or the covers while current is flowing.
Failure to observe this warning may result in an electric shock.
• Never operate the Digital Operator or DIP switches with wet hands.
Failure to observe this warning may result in an electric shock.
• Never touch the terminals while current is flowing, even if the Inverter is stopping.
Failure to observe this warning may result in an electric shock.
CAUTION
• Never touch the heatsinks, which can be extremely hot.
Failure to observe this caution may result in harmful burns to the body.
• It is easy to change operation speed from low to high. Verify the safe working range of the motor and machine before operation.
Failure to observe this caution may result in injury and machine damage.
• Install a holding brake separately if necessary.
Failure to observe this caution may result in injury.
• Do not perform signal checks during operation.
The machine or the Inverter may be damaged.
• All the constants set in the Inverter have been preset at the factory. Do not change the settings unnecessarily.
The Inverter may be damaged.
40
5. Operating the Inverter
Test Run
The Inverter operates when a frequency (speed) is set.
There are four operating modes for the VS-606V7:
1. RUN command from the Digital Operator (potentiometer/digital setting)
2. RUN command from the control circuit terminals
3. RUN command from MEMOBUS communications
4. RUN command from comunication card (optional)
Prior to shipping, the Inverter is set up to receive the RUN command and frequency reference from the Operator. Below are instructions for running the VS-606V7 using the JVOP-140 Digital Operator (with potentiometer). For instructions on operation, refer to page 51.
Operation reference or frequency reference constants can be selected separately as shown below.
Name
RUN
Command
Selection
Frequency
Reference
Selection
Constant n003 = 0 --- Enables run, stop, and reset from Digital Operator.
= 1 --- Enables run and stop from control circuit terminals.
= 2 --- Enables MEMOBUS communications.
= 3 --- Enables communication card (optional).
n004 = 0 --- Enables the Digital Operator’s potentiometer setting.
= 1 --- Enables Frequency Reference 1 (constant n024).
= 2 --- Enables a voltage reference (0 to 10 V) at the control circuit terminal.
= 3 --- Enables a current reference (4 to 20 mA) at the control circuit terminal.
= 4 --- Enables a current reference (0 to 20 mA) at the control circuit terminal.
= 5 --- Enables a pulse train reference at the control circuit terminal.
= 6 --- Enables MEMOBUS communications.
= 7 --- Enables a voltage reference (0 to 10 V) at the Digital Operator’s circuit terminal.
= 8 --- Enables a current reference (4 to 20 mA) at the Digital Operator’s circuit terminal.
= 9 --- Enables communication card (optional).
41
Operation Steps
1. Turn the potentiometer fully counterclockwise, and then turn the power ON.
Operator
Display
0.00
Function
Indicators
FREF
Status
Indicators
RUN
ALARM
2. F/R will lit.
Select FOR or REV RUN using the keys.
NOTE
Never select REV when reverse run is prohibited.
3. Press DSPL to make FREF lit. Then press RUN.
(Forward) or
(Reverse)
0.00
F/R
FREF
RUN
ALARM
RUN
ALARM
4. Operate the motor by turning the potentiometer clockwise. (A frequency reference corresponding to the potentiometer position will be displayed.)
If the potentiometer is switched
NOTE rapidly, the motor also accelerates or decelerates rapidly in proportion to the potentiometer movement. Pay attension to load status and switch the potentiometer at the speed that will not adversely affect motor movement.
0.00 to
60.00
Minimum output frequency is
1.50 Hz
Status indicators : ON : Flashing : OFF
FREF RUN
ALARM
42
5. Operating the Inverter
Selecting Rotation Direction
It is possible to select the direction in which the motor rotates when the
FORWARD RUN command is executed.
The motor rotates in the opposite direction when the REVERSE RUN command is executed.
n040
Setting
0
1
Description
The motor rotates in the counterclockwise direction as viewed from the load when the FORWARD RUN command is executed.
The motor rotates in the clockwise direction as viewed from the load when the FORWARD RUN command is executed.
Operation Check Points
• Motor rotates smoothly.
• Motor rotates in the correct direction.
• Motor does not have abnormal vibration or noise.
• Acceleration and deceleration are smooth.
• Current matching the load flows.
• Status indicators and Digital Operator display are correct.
43
Operating the Digital Operator
All functions of the VS-606V7 are set using the Digital Operator. Below are descriptions of the display and keypad sections.
Data Display Section
JVOP-140 Digital Operator
Indicator/Display Section
Function Indicators
Indicators switch to another function each time is pressed.
The displayed data can be changed.
Press to switch between functions.
Frequency setting potentiometer
Used to change frequency setting.
44
Press to enter the constant data.
(Displays the constant data when selecting a constant No.
for indicator.)
Press to increase constant No./data value.
Status indicator
(same function as
RUN indicator) constant No./data value.
(Rear side of the Operator)
Press to run the motor.
Press to stop the motor.
(Press to reset faults.)
CN2-3: GND for Operator circuit terminal
CN2-1: Operator circuit terminal
(voltage reference)
CN2-2: Operator circuit terminal
(current reference)
* For details, refer to Operator Analog Speed Reference Block Diagram on page 135.
Details of Indicators (Color in parenthesis indicates the color of indicator.)
FREF
Frequency reference setting/monitoring
(GREEN)
FOUT
Output frequency monitoring
(GREEN)
IOUT
Output current monitoring
(GREEN)
MNTR
Multi-function monitoring
(GREEN)
F/R
Operator RUN command FWD/REV selection
(GREEN)
LO/RE
LOCAL/REMOTE
Selection
(RED)
PRGM
Constant No./data
(RED)
5. Operating the Inverter
Description of Status Indicators
There are two Inverter operation status indicators on the middle right section of the face of the VS-606V7. The combinations of these indicators indicate the status of the Inverter (ON, flashing, and OFF). RUN indicator and status indicator on the tion.
button have the same func-
:ON :Flashing (long flashing) :Flashing :OFF
RUN
ALARM
(Green)
(Red)
Operation ready
(During stop)
Ramp to stop
Normal operation
For details on how the status indicators function for Inverter faults, refer to Chapter 8. Fault Diagnosis. If a fault occurs, the ALARM indicator will lit.
NOTE
The fault can be reset by turning ON the FAULT RESET signal (or by pressing the key on the Digital Operator) with the operation signal OFF, or by turning OFF the power supply. If the operation signal is ON, the fault cannot be reset using the FAULT RESET signal.
45
46
Function Indicator Description
By pressing on the Digital Operator, each of the function indicators can be selected.
The following flowchart describes each function indicator.
Power ON
Frequency reference setting/monitoring
(Hz)
Sets VS-606V7 operating speed.
Output frequency monitoring (Hz)
Displays frequency that VS-606V7 is currently outputting.
Setting disabled.
Output current monitoring (A)
Displays current that VS-606V7 is currently outputting.
Setting disabled.
Multi-function monitoring
Description of the selected monitor is displayed.
(Refer to page 47 for details.)
If the VS-606V7 loses power while in one of these modes, it will return to the same mode once power is restored.
FWD/REV run selection
Sets the motor rotation direction when the RUN command is given from the Digital Operator.
Setting can be changed using the or key.
(forward run) (reverse run)
Monitor No.
U-01: Frequency reference (FREF)
U-02: Output frequency (FOUT)
U-03: Output current (IOUT)
U-04: Output voltage reference (Unit: 1V)
U-05: DC voltage (Unit: 1V)
U-06: Input terminal status
U-07: Output terminal status
U-08: Torque monitor
U-09: Fault history (Last 4 faults)
U-10: Software number
U-11: Output power
U-13: Cumulative operation time
(5.5/7.5 kW only)
U-15: Data reception error
U-16: PID feedback
U-17: PID input
U-18: PID output
U-19: Frequency reference bias
monitor (%) (for software No.
VSP010028 or later)
5. Operating the Inverter
LOCAL/REMOTE Selection
This function switches the operation; operation using the Digital Operator including frequency setting with potentiometer, operation using the input terminals, or operation through communications.
Setting can be changed using the or key.
(Local) (Remote)
Constant No./data
Sets and changes data for a constant No.
(Refer to page 50 for details.)
Return to
MNTR Multi-function Monitoring
Selecting the Monitor
Press the key. When is ON, data can be displayed by selecting the monitor number.
Example: Monitoring the Output Voltage Reference
Select U-04 by pressing the
or key.
Output voltage reference is displayed.
or
47
48
Monitoring
The following items can be monitored using U constants.
Constant
No.
U-01
Name Unit Description
U-02
Frequency Reference
(FREF)* 1
Output Frequency
(FOUT)* 1
Output Current (IOUT)*
1
Hz
Hz
Frequency reference can be monitored.
(Same as FREF)
Output frequency can be monitored.
(Same as FOUT)
U-03
U-04
U-05
U-06
U-07
U-08
Output Voltage
DC Voltage
Input Terminal Status* 2
Output Terminal Status* 2
Torque Monitor
A
V
V
-
-
%
Output current can be monitored.
(Same as IOUT)
Output voltage can be monitored.
Main circuit DC voltage can be monitored.
Input terminal status of control circuit terminals can be monitored.
Output terminal status of control circuit terminals can be monitored.
The amount of output torque per rated torque of the motor can be monitored. When V/f control mode is selected, “---” is displayed.
The last four fault history records are displayed.
U-09
U-10
U-11
U-13
Fault History
(Last 4 Faults)
Software No.
Output Power* 3
Cumulative operation time * 4
Data Reception Error*
5
-
kW
Software number can be checked.
Output power can be monitored.
×10 H Cumulative operation time can be monitored in units of 10 hours.
U-15 Contents of MEMOBUS communication data reception error can be checked.
(Contents of transmission register No. 003DH are the same.)
Input 100(%)/Max. output frequency or equivalent U-16
U-17
U-18
PID Feedback*
6
PID Input*
6
PID Output* 6
%
%
%
±100(%)/± Max. output frequency
±100(%)/± Max. output frequency
U-19 Frequency reference bias monitor *
7
% Bias can be monitored when UP/DOWN command 2 is used.
* 1. The status indicator is not turned ON.
* 2. Refer to the next page for input/output terminal status.
* 3. The display range is from −99.9 to 99.99 kW.
When regenerating, the output power will be displayed in units of
0.01 kW when − 9.99 kW or less and in units of 0.1 kW when more than − 9.99 kW.
5. Operating the Inverter
In vector control mode, “---” will be displayed.
* 4. Applicable only for Inverters of 5.5 kW and 7.5 kW (200-V and 400-V
Classes).
* 5. Refer to the next page for data reception error.
* 6. Displayed in units of 0.1% when less than 100% and in units of 1% when
100% or more. The display range is from −999% to 999%.
* 7. Applicable for Inverters with software version No. VSP010028 or later.
Input/Output Terminal Status
Input terminal status
Output terminal status
1: Terminal S1 is closed.
1: Terminal S2 is closed.
1: Terminal S3 is closed.
1: Terminal S4 is closed.
1: Terminal S5 is closed.
1: Terminal S6 is closed.
1: Terminal S7 is closed.
Not used
1: Terminal MA-MC is closed.
1: Terminal P1-PC is closed.
1: Terminal P2-PC is closed.
Not used
Data Reception Error Display
1: CRC error
1: Data length fault
Not used
1: Parity error
1: Over run error
1: Framing error
1: Timeover
Not used
49
50
Fault History Display Method
When U-09 is selected, a four-digit box is displayed. The three digits from the right show the fault description, and the digit on the left shows the order of fault (from one to four). Number 1 represents the most recent fault, and numbers 2, 3, 4 represent the other faults, in ascending order of fault occurrence.
Example:
yyyyyy 4-digit number
: Order of fault (1 to 4)
: Fault description
"---" is displayed if there is no fault.
(Refer to Chapter 8. Fault Diagnosis for details.)
Switching Fault History Records
The fault that is displayed can be changed using the or key.
Clearing the Fault History
Set constant n001 to 6 to clear the fault history. The display will return to n001 after 6 is set.
Note: Initializing the constants (n001=8, 9) also clears the fault history.
Setting and Referencing Constants
The following diagram shows how to select and change constants.
REMOTE/LOCAL selection
• Setting n003 (RUN command selection)
Constant
No./ data n003
Operation reference selection
Factory setting: 0
Operator reference
Set to 1
Control circuit terminal reference
(flashing at changing)
Return to constant No.
display after
1 second
Data set
5. Operating the Inverter
Simple Data Setting
Digital setting (refer to 5. Operating the Inverter) and potentiometer setting are both possible for simple acceleration/deceleration operation of the VS-606V7.
Digital setting is set at the factory (n004=0). For the model with JVOP-
147 Digital Operator (without potentiometer), factory setting is set by frequency setting potentiometer (n004=1).
Following is an example in which the function indicators are used to set frequency reference, acceleration time, deceleration time, and motor direction.
51
Data setting by frequency setting potentiometer
Operation Steps
1. Turn ON the power supply.
Operator
Display
0.00
Function
Indicators
FREF
Status
Indicators
RUN
ALARM
2. Press DSPL to make set constant n004 to 1.
PRGM lit, then
1
PRGM
RUN
ALARM
3. Set the following constants.
n019: 15.0 (acceleration time) n020: 5.0 (deceleration time)
15.0
5.0
PRGM RUN
ALARM
4. Press DSPL to make F/R lit, then select forward or reverse run by press-
NOTE
Examine the application. (Never select REV when reverse run is prohibited.)
(Forward) or
(Reverse)
F/R RUN
ALARM
5. Press DSPL to make
FREF
lit, then set the reference by pressing or
key.
60.00
6. Press DSPL press .
to make FOUT lit, then
0.00
→60.00
FREF
FOUT
60.00
→0.00
FOUT
RUN
ALARM
RUN
ALARM
RUN
Status indicators : ON : Flashing (Long flashing)
ALARM
: Flashing : OFF
52
6. Programming Features
6. Programming Features
Factory settings of the constants are shaded in the tables.
Constant Setup and Initialization
Constant Selection/Initialization (n001)
The following table lists the data that can be set or read when n001 is set. By setting this constant, the fault history can be cleared and the constants initialized. Unused constants between n001 and n179 are not displayed.
7
8
9
5
6 n001 Setting
0
1
2
3
4
Constant that can be Set Constant that can be Referenced n001 n001 to n179 n001 to n049 n001 to n079
*1
*1 n001 to n119
*1 n001 to n049
*1 n001 to n079
*1 n001 to n119
*1 n001 to n179
*1 n001 to n179
*1
Not used
Fault history cleared
Not used
Initialize
Initialize (3-wire sequence)
*2
* 1. Excluding setting-disabled constants.
* 2. Refer to page 90.
53
54
NOTE
appears on the display for one second and the set data returns to its initial values in the following cases.
1. If the set values of Multi-function Input Selections 1 to 7
(n050 to n056) are the same
2. If the following conditions are not satisfied in the V/f pattern setting:
Max. Output Frequency (n011) ≥ Max. Voltage Output
Frequency (n013)
> Mid. Output Frequency
(n014)
≥ Min. Output Frequency
(n016)
For details, refer to Adjusting Torque According to Appli-
cation (V/f Pattern Setting) on page 55.
3. If the following conditions are not satisfied in the jump frequency settings:
Jump Frequency 3 (n085) ≤ Jump Frequency 2 (n084)
≤ Jump Frequency 1 (n083)
4. If the Frequency Reference Lower Limit (n034) ≤ Frequency Reference Upper Limit (n033)
5. If the Motor Rated Current (n036) ≤ 150% of Inverter rated current
6. If constant n018 is set to 1 (Acceleration/Deceleration
Time Unit is 0.01 s) when n018 is set to 0 (Acceleration/
Deceleration Time Unit is 0.1 s) and a value exceeding
600.0 s is set for an Acceleration/Deceleration Time (n019 to n022)
6. Programming Features
Using V/f Control Mode
V/f control mode is preset at the factory.
Control Mode Selection (n002) = 0: V/f control mode (factory setting)
1: Vector control mode
Adjusting Torque According to Application
Adjust motor torque by using the V/f pattern and full-range automatic torque boost settings.
V/f Pattern Setting
Set the V/f pattern in n011 to n017 as described below. Set each pattern when using a special motor (e.g., high-speed motor) or when requiring special torque adjustment of the machine.
V: (Voltage) f
(Frequency)
Be sure to satisfy the following conditions for the settings of n011 to n017.
n016 ≤ n014 < n013 ≤ n011
If n016 = n014, the setting of n015 will be disabled.
Constant
No.
n011 n012 n013 n014 n015 n016 n017
Max. Output Frequency
Max. Voltage
Name
Max. Voltage Output Frequency
(Base Frequency)
Unit
0.1 Hz
Setting Range
0.2 to 400.0 Hz
Factory
Setting
0.1 Hz 50.0 to 400.0 Hz 60.0 Hz
0.1 V 0.1 to 255.0 V *
(0.1 to 510.0 V)
200.0 V *
(400.0 V)
60.0 Hz
Mid. Output Frequency
Mid. Output Frequency Voltage
Min. Output Frequency
Min. Output Frequency Voltage
0.1 Hz
0.1 V
0.1 to 399.9 Hz
0.1 V 0.1 to 255.0 V *
(0.1 to 510.0 V)
0.1 Hz 0.1 to 10.0 Hz
0.1 to 50.0 V *
(0.1 to 100.0 V)
1.5 Hz
12.0 V *
(24.0 V)
1.5 Hz
12.0 V *
(24.0 V)
Note: The values in the parentheses are for the 400-V class of Inverters.
* 10.0 V (20.0 V) for Inverters of 5.5 kW and 7.5 kW (200-V and 400-V
Classes).
55
Typical Setting of the V/f Pattern
Set the V/f pattern according to the application as described below. For
400-V Class Inverters, the voltage values (n012, n015, and n017) should be doubled. When running at a frequency exceeding 50/60 Hz, change the Maximum Output Frequency (n011).
Note: Always set the maximum output frequency according to the motor characteristics.
1. For General-purpose Applications
Motor Specification: 60 Hz
(Factory setting)
Motor Specification: 50 Hz
56
2. For Fans/Pumps
V
200
Motor Specification: 60 Hz Motor Specification: 50 Hz
V
200
50
10
1.5 30 60 f
50
10
1.3 25 50 f
3. For Applications Requiring High Starting Torque
V
200
Motor Specification: 60 Hz Motor Specification: 50 Hz
V
200
24
18
1.5 3
24
18
1.3 2.5
60 f 50 f
Increasing the voltage of the V/f pattern increases motor torque, but an excessive increase may cause motor overexcitation, motor overheating, or vibration.
6. Programming Features
Full-range Automatic Torque Boost (when V/f Mode is
Selected: n002=0)
The motor torque requirement changes according to load conditions.
The full-range automatic torque boost adjusts the voltage of the V/f pattern according to requirements. The VS-606V7 automatically adjusts the voltage during constant-speed operation, as well as during acceleration.
The required torque is calculated by the Inverter.
This ensures tripless operation and energy-saving effects.
Output voltage Torque compensation gain (n103) Required torque
Operation
V
(Voltage)
Required torque Increase voltage f (Frequency)
Normally, no adjustment is necessary for the Torque Compensation
Gain (n103 factory setting: 1.0). When the wiring distance between the
Inverter and the motor is long, or when the motor generates vibration, change the automatic torque boost gain. In these cases, set the V/f pattern (n011 to n017).
Adjustment of the Torque Compensation Time Constant (n104) and the
Torque Compensation Iron Loss (n105) are normally not required.
Adjust the torque compensation time constant under the following conditions:
• Increase the setting if the motor generates vibration.
• Reduce the setting if response is slow.
57
58
Using Vector Control Mode
Set the Control Mode Selection (n002) to use vector control mode.
n002 = 0: V/f control mode (factory setting)
1: Vector control mode
Precautions for Voltage Vector Control Application
Vector control requires motor constants. The Yaskawa standard motor constants have been set at the factory prior to shipment. Therefore, when a motor designed for an Inverter is used or when a motor from any other manufacturer is driven, the required torque characteristics or speed control characteristics may not be maintained because the constants are not suitable. Set the following constants so that they match the required motor constants.
Constant
No.
Name n106 Motor Rated Slip
Unit Setting
Range
Factory
Setting n107 Motor Line-to-neutral
Resistance
0.1 Hz
0.001 Ω
(less than 10 Ω)
0.01 Ω
(10 Ω or more)
0.1 A
0.0 to
20.0 Hz
0.000 to
65.50 Ω
*
* n036 Motor Rated Current n110 Motor No-load Current 1%
0% to 150% of Inverter rated current
0% to 99%
(100% = motor rated current)
*
*
* Setting depends on Inverter capacity. (Refer to pages 207 and 208.)
Adjustment of the Torque Compensation Gain (n103) and the Torque
Compensation Time Constant (n104) is normally not required.
Adjust the torque compensation time constant under the following conditions:
• Increase the setting if the motor generates vibration.
• Reduce the setting if response is slow.
Adjust the Slip Compensation Gain (n111) while driving the load so that the target speed is reached. Increase or decrease the setting in increments of 0.1.
6. Programming Features
• If the speed is less than the target value, increase the slip compensation gain.
• If the speed is more than the target value, reduce the slip compensation gain.
Adjustment of the Slip Compensation Time Constant (n112) is normally not required. Adjust it under the following conditions:
• Reduce the setting if response is slow.
• Increase the setting if speed is unstable.
Select slip compensation status during regeneration as follows: n113 Setting Slip Correction during Regenerative Operation
0 Disabled
1 Enabled
Motor Constant Calculation
An example of motor constant calculation is shown below.
1. Motor Rated Slip (n106)
120 × motor rated frequency (Hz)* 1
Number of motor poles
Motor rated speed (min
120/Number of motor poles
-1 )* 2
2. Motor Line-to-neutral Resistance (n107)
Calculations are based on the line-to-line resistance and insulation grade of the motor test report.
E type insulation: Test report of line-to-line resistance at 75 °C (Ω) × 0.92 ×
B type insulation: Test report of line-to-line resistance at 75 °C (Ω) × 0.92 ×
F type insulation: Test report of line-to-line resistance at 115 °C (Ω) × 0.87 ×
3. Motor Rated Current (n036)
= Rated current at motor rated frequency (Hz) *1 (A)
4. Motor No-load Current (n110)
No-load current (A) at motor rated frequency (Hz)* 1
Rated current (A) at motor rated frequency (Hz)* 1
100 (%)
* 1. Base frequency (Hz) during constant output control
* 2. Rated speed (min
-1
) at base frequency during constant output control
59
60
Set n106 (Motor Rated Slip), n036 (Motor Rated Current), n107 (Motor
Line-to-neutral Resistance), and n110 (Motor No-load Current) according to the motor test report.
To connect a reactor between the Inverter and the motor, set n108 to the sum of the initial value of n108 (Motor Leakage Inductance) and the externally mounted reactor inductance. Unless a reactor is connected, n108 (Motor Leakage Inductance) does not have to be set according to the motor.
V/f Pattern during Vector Control
Set the V/f pattern as follows during vector control:
The following examples are for 200 V Class motors. When using 400 V
Class motors, double the voltage settings (n012, n015, and n017).
Standard V/f
(V)
[Motor Specification: 60 Hz]
(V)
[Motor Specification: 50 Hz]
High Starting Torque V/f
(V)
[Motor Specification: 60 Hz]
(Hz)
(V)
[Motor Specification: 50 Hz]
(Hz)
(Hz) (Hz)
6. Programming Features
When operating with frequency larger than 60/50 Hz, change only the
Max. Output Frequency (n011).
Constant torque
Constant output or variable output n012
=200 V
Base point n013
=60 or 50 Hz n011
=90 Hz
Switching LOCAL/REMOTE Mode
The following functions can be selected by switching LOCAL or
REMOTE mode. To select the RUN/STOP command or frequency reference, change the mode in advance depending on the following applications.
• LOCAL mode: Enables the Digital Operator for RUN/STOP commands and FWD/REV RUN commands. The frequency reference can be set using the potentiometer or .
• REMOTE mode: Enables RUN Command Selection (n003).
The frequency reference can be set using the Frequency Reference Selection (n004).
61
How to Select LOCAL/REMOTE Mode
When LOCAL/REMOTE switching function is not set for multi-function input selection
(When 17 is not set for any of constants n050 to n056)
When LOCAL/REMOTE switching function is set for multi-function input selection
(When 17 is set for any of constants n050 to n056)
Select Lo for operator
LO/RE selection.
Select rE for operator
LO/RE selection.
Turn ON multifunction input terminal.
Turn OFF multifunction input terminal.
62
LOCAL mode REMOTE mode
Selecting RUN/STOP Commands
Refer to Switching LOCAL/REMOTE Mode (page 61) to select either the LOCAL mode or REMOTE mode.
The operation method (RUN/STOP commands, FWD/REV RUN commands) can be selected using the following method.
LOCAL Mode
When Lo (local mode) is selected for Digital Operator ON mode, or when the LOCAL/REMOTE switching function is set and the input terminals are turned ON, run operation is enabled by the STOP
on the Digital Operator, and FWD/REV is enabled by the
ON mode (using or key).
or
6. Programming Features
REMOTE Mode
1. Select remote mode.
There are following two methods to select remote mode.
• Select rE (remote mode) for the selection.
• When the local/remote switching function is selected for the multi-function input selection, turn OFF the input terminal to select remote mode.
2. Select the operation method by setting constant n003.
n003=0: Enables the Digital Operator (same with local mode).
=1: Enables the multi-function input terminal (see fig. below).
=2: Enables communications (refer to page 107).
=3: Enables communication card (optional).
• Example when using the multi-function input terminal as operation reference (two-wire sequence)
FWD RUN/STOP
REV RUN/STOP n003: 1 (Factory setting: 0) n050: 1 (Factory setting) n051: 2 (Factory setting)
• For an example of three-wire sequence, refer to page 90.
• For more information on how to select the sequence polarity, refer to page 188.
Note: When the Inverter is operated without the Digital Operator, always set constant n010 to 0.
n010 = 0: Detects fault contact of the Digital Operator (Factory setting)
= 1: Not detect fault contact of the Digital Operator
Operating (RUN/STOP Commands) by Communications
Setting constant n003 to 2 in REMOTE mode enables using RUN/
STOP commands via MEMOBUS communications. For commands using communications, refer to page 107.
Selecting Frequency Reference
Select REMOTE or LOCAL mode in advance. For the method for selecting the mode, refer to page 61.
63
64
LOCAL Mode
Select command method using constant n008.
n008=0: Enables using the potentiometer on the Digital Operator
(factory setting).
The factory setting for models with the Digital Operator
without a potentiometer (JVOP-147) is n008=1.
=1: Enables digital setting on the Digital Operator.
[Setting can be stored in Frequency Reference 1 (n024)].
• Digital Setting Using the Digital Operator
Input the frequency while FREF is lit (press ENTER after setting the numeric value).
Frequency reference setting is effective when 1 (factory setting: 0) is set for constant n009 instead of pressing ENTER.
n009 =0: Enables frequency reference setting using the ENTER key.
=1: Disables frequency reference setting using the ENTER key.
REMOTE Mode
Select the command method in constant n004.
n004 =0: Enables frequency reference setting using the potentiometer on the Digital Operator (factory setting).
Factory setting of models with the Digital Operator without a potentiometer (JVOP-147) is n004=1.
=1: Enables using frequency reference 1 (n024)
=2: Enables a voltage reference (0 to 10 V) (refer to the figure on page 64).
=3: Enables a current reference (4 to 20 mA) (refer to page 97).
=4: Enables a current reference (0 to 20 mA) (refer to page 97).
=5: Enables a pulse train reference (refer to page 99).
=6: Enables communication (refer to page 107).
=7: Enables a voltage reference on Digital Operator circuit terminal (0 to 10 V)
=8: Enables a current reference on Digital Operator circuit terminal (4 to 20 mA)
=9: Enables communication card (optional).
Example of frequency reference by voltage signal
Master
Frequency
Reference
2 k
Ω
IM n004=2
(Factory setting: 0)
(Frequency Setting Power
(0 to +10 V)
FS
+12 V 20 mA
FR (Master Frequency Reference)
FC (0 V)
6. Programming Features
Setting Operation Conditions
Reverse Run Prohibit (n006)
The Reverse Run Prohibit setting disables accepting a reverse RUN command from the control circuit terminal or Digital Operator. This setting is used for applications where a reverse RUN command can cause problems.
Setting
0
1
Description
Reverse run enabled.
Reverse run disabled.
Multi-step Speed Selection
Up to 16 speed steps can be set using the following combinations of frequency reference and input terminal selections.
8-step speed change n003=1 (Operation mode selection) n004=1 (Frequency reference selection) n024=25.0 Hz (Frequency reference 1) n025=30.0 Hz (Frequency reference 2) n026=35.0 Hz (Frequency reference 3) n027=40.0 Hz (Frequency reference 4) n028=45.0 Hz (Frequency reference 5) n029=50.0 Hz (Frequency reference 6) n030=55.0 Hz (Frequency reference 7) n031=60.0 Hz (Frequency reference 8)
* For more information on how to select the sequence voltage and the current input, refer to page 188.
NOTE
When all multi-function reference inputs are OFF, the frequency reference selected by constant n004 (Frequency
Reference Selection) becomes effective.
n054=6 (Multi-function contact input terminal S5) n055=7 (Multi-function contact input terminal S6) n056=8 (Multi-function contact input terminal S7) n053=1
FWD
RUN/STOP
REV RUN/STOP
MULTI-STEP
SPEED REF 1
MULTI-STEP
SPEED REF 2
MULTI-STEP
SPEED REF 3
EXTERNAL FAULT
FAULT RESET
S1
S2
S5
S6
S7
S3
S4
SC
65
66
Frequency reference
(n031) 60.0 Hz
(n030) 55.0 Hz
(n029) 50.0 Hz
(n028) 45.0 Hz
(n027) 40.0 Hz
(n026) 35.0 Hz
(n025) 30.0 Hz
(n024) 25.0 Hz
Time
FWD (REV) RUN/STOP
Multi-step speed ref. 1
(terminal S5)
Multi-step speed ref. 2
(terminal S6)
Multi-step speed ref. 3
(terminal S7) n050 = 1 (Input terminal S1) (Factory Setting) n051 = 2 (Input terminal S2) (Factory Setting) n052 = 3 (Input terminal S3) (Factory Setting) n053 = 5 (Input terminal S4) (Factory Setting) n054 = 6 (Input terminal S5) (Factory Setting) n055 = 7 (Input terminal S6) (Factory Setting) n056 = 8 (Input terminal S7) (Change the setting to 8.)
16-step speed operation
Set frequency references 9-16 for n120 to n127.
Set the input terminal for a multi-step speed reference using the multifunction input selection.
Operating at Low Speed
By inputting a JOG command and then a FORWARD (REVERSE)
RUN command, operation is enabled at the jog frequency set in n032.
When multi-step speed references 1, 2, 3 or 4 are input simultaneously with the JOG command, the JOG command has priority.
Constant No.
n032
Name
Jog Frequency
Setting
Factory setting: 6.00 Hz n050 to n056 Jog References Set to 10 for any constant.
6. Programming Features
Adjusting Speed Setting Signal
The relationship between the analog inputs and the frequency reference can be set to provide the frequency reference as analog inputs to control circuit terminal FR or FC.
Frequency Reference
(4 mA)
(0 mA)
(20 mA)
(20 mA)
( ) indicates the value when a current reference input is selected.
1. Analog Frequency Reference Gain (n060)
The frequency reference provided when the analog input is 10 V (or
20 mA) can be set in units of 1%. (Max. Output Frequency n011=100%)
* Factory setting: 100%
2. Analog Frequency Reference Bias (n061)
The frequency reference provided when the analog input is 0 V
(4 mA or 0 mA) can be set in units of 1%. (Max. Output Frequency n011=100%)
* Factory setting: 0%
Typical Settings
• To operate the Inverter with a frequency reference of 0% to 100% at an input voltage of 0 to 5 V
Max. frequency (100%)
Gain n060 = 200
Bias n061 = 0
67
• To operate the Inverter with a frequency reference of 50% to
100% at an input voltage of 0 to 10 V
Max. frequency (100%)
0 V 10 V
Gain n060 = 100
Bias n061 = 50
Adjusting Frequency Upper and Lower Limits
Internal frequency reference
Frequency
Upper Limit
(n033)
Frequency
Lower Limit
(n034)
Set frequency reference
• Frequency Reference Upper Limit (n033)
Sets the upper limit of the frequency reference in units of 1%.
(n011: Max. Output Frequency = 100%)
Factory setting: 100%
• Frequency Reference Lower Limit (n034)
Sets the lower limit of the frequency reference in units of 1%.
(n011: Max. Output Frequency = 100%)
When operating at a frequency reference of 0, operation is continued at the frequency reference lower limit.
However, if the frequency reference lower limit is set to less than the
Minimum Output Frequency (n016), operation is not performed.
Factory setting: 0%
Using Four Acceleration/Deceleration Times
Output
Frequency
Accel
Time 2
(n021)
Accel
Time 1
(n019)
Decel
Time 2
(n022)
Decel
Time 1
(n020)
Accel
Time 3
(n041)
Accel
Time 4
(n043)
Decel
Time 4*
(n044)
Decel
Time 3*
(n042)
Time
FORWARD (REVERSE)
RUN Command
Multi-Step
Speed Reference
Accel/Decel
Time Selection 1
Accel/Decel
Time Selection 2
ON
ON
ON
ON
* When deceleration to a stop is selected (n005 = 0).
ON
68
6. Programming Features
By setting a multi-function input selection (either of n050 to n056) to 11
(acceleration/deceleration time selection 1) or 27 (acceleration/deceleration time selection 2), the acceleration/deceleration time is selected by
ON/OFF combinations of acceleration/deceleration time selection 1 and acceleration/deceleration time selection 2 (terminals S1 to S7).
The combinations of acceleration/deceleration time selection settings are shown below.
Accleration/
Deceleration
Time Selection 1
Accleration/
Deceleration
Time Selection 2
OFF OFF
ON
OFF
ON
OFF
ON
ON
Acceleration Time Deceleration Time
Acceleration time 1
(n019)
Deceleration time 1
(n020)
Acceleration time 2
(n021)
Deceleration time 2
(n022)
Acceleration time 3
(n041)
Deceleration time 3
(n042)
Acceleration time 4
(n043)
Deceleration time 4
(n044)
No.
n022 n042 n044
Name
Deceleration Time 4
Unit n019 Acceleration Time 1 Depends on n018 setting.
n020 Deceleration Time 1
(See the next n021 Acceleration Time 2 table.)
Deceleration Time 2 n041 Acceleration Time 3
Deceleration Time 3 n043 Acceleration Time 4
Setting Range Factory
Setting
Depends on n018 setting.
(See the next table.)
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
69
70 n018 Settings
No.
n018 0
Unit Setting Range
0.1 s 0.0 to 999.9 s (999.9 s or less)
1 s 1000 to 6000 s (1000 s or more)
1 0.01 s 0.00 to 99.99 s (99.99 s or less)
0.1 s 100.0 to 600.0 s (100 s or more)
Note: Constant n018 can be set while stopped.
If a value exceeding 600.0 s is set for the acceleration/deceleration time when n018=0 (in units of 0.1 s), 1 cannot be set for n018.
• Acceleration time
Set the time needed for the output frequency to reach 100% from 0%.
• Deceleration time
Set the time needed for the output frequency to reach 0% from 100%.
(Max. Output Frequency n011 = 100%)
Momentary Power Loss Ridethrough Method (n081)
WARNING
When continuous operation after power recovery is selected, stand clear of the Inverter or the load. The
Inverter may restart suddenly after stopping.
(Construct the system to ensure safety, even if the
Inverter should restart.) Failure to observe this warning may result in injury.
When constant n081 is set to 1 or 2, operation automatically restarts even if a momentary power loss occurs.
Setting
0
2
1
*1
*1, *2
Description
Continuous operation after momentary power loss not enabled.
Continuous operation after power recovery within momentary power loss ridethrough time
0.5 s
Continuous operation after power recovery
(Fault output not produced.)
6. Programming Features
* 1. Hold the operation signal to continue operation after recovery from a momentary power loss.
* 2. When 2 is selected, the Inverter restarts if power supply voltage recovers while the control power supply is held.
No fault signal is output.
S-curve Selection (n023)
To prevent shock when starting and stopping the machine, acceleration/ deceleration can be performed using an S-curve pattern.
Setting
0
1
2
3
S-curve Selection
S-curve characteristic not provided.
0.2 s
0.5 s
1.0 s
Note: The S-curve characteristic time is the time from acceleration/deceleration rate 0 to the normal acceleration/deceleration rate determined by the set acceleration/deceleration time.
Frequency
Reference
Output
Frequency
Output
Frequency
Time
S-curve Characteristic Time (Ts)
The following time chart shows switching between FWD/REV run when decelerating to a stop.
FORWARD RUN Command
REVERSE RUN Command
Acceleration
Output Frequency
Deceleration
Min. Output Frequency n016
Min. Output
Frequency n016
Acceleration
DC Injection Braking
Time at Stop n090
Deceleration
S-curve Characteristics in
71
Torque Detection
If an excessive load is applied to the machine, an increase in the output current can be detected to output an alarm signal to multi-function output terminal MA, MB, P1, or P2.
To output an overtorque detection signal, set one of the output terminal function selections n057 to n059 for overtorque detection (Setting: 6
(NO contact) or 7 (NC contact)).
Motor Current
72
Time
Multi-function Output Signal
(Overtorque Detection Signal)
Terminal MA, MB, P1, or P2
* The overtorque detection release width (hysteresis) is set at approx. 5% of the Inverter rated current.
Overtorque Detection Function Selection 1 (n096)
Setting
0
1
2
Description
Overtorque detection not provided.
Detected during constant-speed running. Operation continues after detection.
Detected during constant-speed running. Operation stops during detection.
3
4
Detected during running. Operation continues after detection.
Detected during running. Operation stops during detection.
1. To detect overtorque during acceleration/deceleration, set n096 to 3 or 4.
2. To continue operation after overtorque detection, set n096 to 1 or 3.
During detection, the Digital Operator will display an alarm
(flashing).
6. Programming Features
3. To stop the Inverter and generate a fault at overtorque detection, set n096 to 2 or 4. At detection, the Digital Operator will display an fault
(ON).
Overtorque Detection Level (n098)
Set the overtorque detection current level in units of 1%. (Inverter rated current = 100%) When detection by torque is selected, the motor rated torque becomes 100%.
Factory setting: 160%
Overtorque Detection Time (n099)
If the time that the motor current exceeds the Overtorque Detection
Level (n098) is longer than Overtorque Detection Time (n099), the overtorque detection function will operate.
Factory setting: 0.1 s
Overtorque/Undertorque Detection Function Selection 2
(n097)
When vector control mode is selected, overtorque/undertorque detection can be performed either by detecting the output current or the output torque.
When V/f control mode is selected, the setting of n097 is invalid, and overtorque/undertorque is detected by the output current.
Setting
0
1
Description
Detected by output torque
Detected by output current
Frequency Detection Level (n095)
Effective when one or more of the Multi-function Output Selections n057, n058 and n059 are set for frequency detection (setting: 4 or 5).
Frequency detection turns ON when the output frequency is higher or lower than the setting for the Frequency Detection Level (n095).
73
74
Frequency Detection 1
Output frequency ≥ Frequency Detection Level n095
(Set n057, n058 or n059 to 4.)
Frequency Detection
Level [Hz] (n095)
Release
Width
−2Hz
Output
Frequency
Frequency
Detection
Signal
Frequency Detection 2
Output frequency ≤ Frequency Detection Level n095
(Set n057, n058 or n059 to 5.)
Output
Frequency
Release
Width
+2Hz
Frequency
Detection
Level (Hz)
(n095)
Frequency
Detection
Signal
Jump Frequencies (n083 to n086)
This function allows the prohibition or “jumping” of critical frequencies so that the motor can operate without resonance caused by the machine system. This function is also used for dead band control. Setting the values to 0.00 Hz disables this function.
Set prohibited frequencies 1, 2, and 3 as follows:
Output Frequency n083 ≥ n084 ≥ n085
If this condition is not satisfied, the Inverter will display for one second and restore the data to initial settings.
Frequency Reference
Operation is prohibited within the jump frequency ranges.
However, the motor will operate without jumping during acceleration/ deceleration.
6. Programming Features
Continuing Operation Using Automatic Retry Attempts (n082)
WARNING
When the fault retry function is selected, stand clear of the Inverter or the load. The Inverter may restart suddenly after stopping.
(Construct the system to ensure safety, even if the
Inverter should restart.) Failure to observe this warning may result in injury.
The Inverter can be set to restart and reset fault detection after a fault occurs. The number of self-diagnosis and retry attempts can be set to up to 10 in n082. The Inverter will automatically restart after the following faults occur:
OC (overcurrent)
OV (overvoltage)
The number of retry attempts is cleared to 0 in the following cases:
1. If no other fault occurs within 10 minutes after retry
2. When the FAULT RESET signal is ON after the fault is detected
3. When the power supply is turned OFF
Operating a Coasting Motor without Tripping
To operate a coasting motor without tripping, use the SPEED SEARCH command or DC Injection Braking at Startup.
SPEED SEARCH Command
Restarts a coasting motor without stopping it. This function enables smooth switching between motor commercial power supply operation and Inverter operation.
Set a Multi-function Input Selection (n050 to n056) to 14 (SEARCH command from maximum output frequency) or 15 (SEARCH command from set frequency).
Build a sequence so that a FWD (REV) RUN command is input at the same time as the SEARCH command or after the SEARCH command.
If the RUN command is input before the SEARCH command, the
SEARCH command will be disabled.
75
76
Timechart at SEARCH Command Input
FWD (REV) RUN Command
SEARCH Command
Max. Output Frequency or
Frequency Reference at
Run Command Input
0.5 s Min.
Speed Agreement
Detection
Output Frequency
Min. Baseblock
Time (0.5 s)
Speed
Search
Operation
The deceleration time for speed search operation can be set in n101.
If the setting is 0, however, an initial value of 2.0 s will be used.
The speed search starts when the Inverter’s output current is greater than or equal to the speed search operation level (n102).
DC Injection Braking at Startup (n089, n091)
Restarts a coasting motor after stopping it. Set the DC injection braking time at startup in n091 in units of 0.1 s. Set the DC Injection Braking
Current in n089 in units of 1% (Inverter rated current =100%). When the setting of n091 is 0, DC injection braking is not performed and acceleration starts from the minimum output frequency.
When n089 is set to 0, acceleration starts from the minimum output frequency after baseblocking for the time set in n091.
Min. Output
Frequency n016 n091
DC Injection Braking
Time at Startup
Holding Acceleration/Deceleration Temporarily
To hold acceleration or deceleration, input an ACCELERATION/
DECELERATION HOLD command. The output frequency is maintained when an ACCELERATION/DECELERATION HOLD command is input during acceleration or deceleration.
When the STOP command is input while an ACCELERATION/
DECELERATION HOLD command is being input, the acceleration/ deceleration hold is released and operation ramps to a stop.
Set a Multi-function Input Selection (n050 to n056) to 16 (acceleration/ deceleration hold).
6. Programming Features
Timechart for ACCELERATION/DECELERATION HOLD
Command Input
FWD (REV)
RUN Command
ACCELERATION/
DECELERATION
HOLD Command
Frequency
Reference
Output
Frequency
FREQUENCY
AGREE
Signal
Note: If a FWD (REV) RUN command is input at the same time as an
ACCELERATION/DECELERATION HOLD command, the motor will not operate. However, if the Frequency Reference Lower Limit (n034) is set to a value greater than or equal to the Min. Output Frequency (n016), the motor will operate at the Frequency Reference Lower Limit (n034).
Using Frequency Meter or Ammeter (n066)
Selects to output either output frequency or output current to analog output terminals AM-AC for monitoring.
5
6
3
4
Setting
0
1
2
Description
Output frequency
Output current
Main circuit DC voltage
Torque monitor
Output power
Output voltage reference
Frequency reference monitor
77
78
In factory setting, analog voltage of approx. 10 V is output when output frequency (output current) is 100 %.
Output Frequency
(Output Current)
AM
Frequency
Meter
FM
100 %
Analog monitor gain can be set by n067.
AC
0
10 V
Analog Output
Calibrating Frequency Meter or Ammerter (n067)
Used to adjust analog output gain.
Frequency Meter/Ammeter
(3 V 1 mA Full-scale)
Output Frequency
(Output Current)
100 % n067 = 0.30
n067 = 1.00
Factory Setting n067
AM
FM
AC
0
3 V 10 V
Analog Output
Set the analog output voltage at 100 % of output frequency (output current). Frequency meter displays 0 to 60 Hz at 0 to 3 V.
10 V × n067 setting
0.30
= 3 V
Output frequency becomes
100 % at this value.
Using Analog Output (AM-AC) as a Pulse Train Signal
Output (n065)
Analog output AM-AC can be used as a pulse train output (output frequency monitor, frequency reference monitor).
Set n065 to 1 when using pulse train output.
Constant No.
n065
Name
Monitor output type
Unit Setting range
Factory setting
0, 1 0
6. Programming Features n065 Setting n065 Setting
0
1
Description
Analog monitor output
Pulse monitor output
(Output frequency monitor)
Pulse train signal can be selected by setting in n150.
n150 Setting
0
1
6
12
24
36
40
41
42
43
44
45
Output frequency monitor
Frequency reference monitor
Description
1440 Hz/Max. frequency (n011)
1F: Output frequency × 1
6F: Output frequency × 6
12F: Output frequency × 12
24F: Output frequency × 24
36F: Output frequency × 36
1440 Hz/Max. frequency (n011)
1F: Output frequency × 1
6F: Output frequency × 6
12F: Output frequency × 12
24F: Output frequency × 24
36F: Output frequency × 36
At the factory setting, the pulse of 1440 Hz can be output when output frequency is 100 %.
Output Frequency
100 %
AM
AC (0 V)
Pulse
1440 Hz
Pulse Monitor Output
79
NOTE
Peripheral devices must be connected according to the following load conditions when using pulse monitor output.
The machine might damage when the conditions are not satisfied.
Used as a Sourcing Output
Output Voltage
VRL (V)
+5 V
+8 V
+10 V
Load Impedance
(k Ω)
1.5 k Ω or more
3.5 k Ω or more
10 k Ω or more
AM
AC (0 V)
VRL
Load
Impedance
External Power
Supply (V)
Sinking Current
(mA)
Used as a Sinking Input
+12 VDC ±5 % or less
16 mA or less
AM
External Power Supply
Sink Current
Load
Impedance
AC (0 V)
(0 V)
80
6. Programming Features
Reducing Motor Noise or Leakage Current Using Carrier Frequency Selection (n080)
Set the Inverter output transistor switching frequency (carrier frequency).
Setting Carrier Frequency (kHz) Metallic
Noise from
Motor
Noise and
Current
Leakage
2
3
4
9
1
7
8
12 fout (Hz)
24 fout (Hz)
36 fout (Hz)
2.5 (kHz)
5.0 (kHz)
7.5 (kHz)
10.0 (kHz)
Higher
Not audible
Smaller
Larger
81
If the set value is 7, 8, or 9, the carrier frequency will be multiplied by the same factor as the output frequency.
n080=7 fc=Carrier Frequency
2.5 kHz fc=12 fout
1.0 kHz fout=Output Frequency
83.3 Hz 208.3 Hz n080=8 fc=Carrier Frequency
2.5 kHz fc=24 fout
1.0 kHz fout=Output Frequency
41.6 Hz 104.1 Hz n080=9 fc=Carrier Frequency
2.5 kHz fc=36 fout
1.0 kHz
69.4 Hz fout=Output Frequency
27.7 Hz
The factory setting depends on the Inverter capacity (kVA).
82
Voltage
Class (V)
200 V
Singlephase or
3-phase
Capacity
(kW)
Factory Setting
Setting Carrier Frequency
(kHz)
Maximum
Continuous
Output Current
(A)
0.1
0.25
0.4
0.75
1.5
2.2
3.7
4
4
4
4
3
3
3
10
10
10
10
7.5
7.5
7.5
0.8
1.6
3.0
5.0
8.0
11.0
17.5
Reduced
Current
(A)
-
7.0
10.0
16.5
6. Programming Features
Voltage
Class (V)
200 V
Singlephase or
3-phase
400 V
3-phase
Capacity
(kW)
5.5
7.5
Factory Setting
Setting Carrier Frequency
(kHz)
Maximum
Continuous
Output Current
(A)
3
3
7.5
7.5
25
33
2.2
3.0
3.7
5.5
0.2
0.4
0.75
1.5
3
3
3
3
3
3
3
3
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
5.5
7.2
8.6
14.8
1.2
1.8
3.4
4.8
Reduced
Current
(A)
23
30
7.5
3 7.5
18 17
* Reduction of the current is not necessary.
NOTE
1. Reduce the continuous output current when changing the carrier frequency to 4 (10 kHz) for 200 V Class (1.5 kW or more) and 400 V Class Inverters. Refer to the table above for the reduced current.
Operation Condition
• Input power supply voltage:
3-phase 200 to 230 V (200 V Class)
Single-phase 200 to 240 V (200 V Class)
3-phase 380 to 460 V (400 V Class)
• Ambient temperature:
−10 to 50°C
(Protection structure: open chassis type IP20,
IP00)
−10 to 40°C
(Protection structure: enclosed wall-mounted type
NEMA 1 (TYPE 1))
4.8
6.3
8.1
*
1.0
1.6
3.0
4.0
83
84
2. If the wiring distance is long, reduce the Inverter carrier frequency as described below.
Wiring Distance between Inverter and Motor
Carrier Frequency (n080 setting)
Up to 50 m Up to 100 m More than 100 m
10 kHz or less
(n080=1, 2, 3, 4,
7, 8, 9)
5 kHz or less
(n080=1, 2, 7, 8, 9)
2.5 kHz or less
(n080=1, 7, 8, 9)
3. Set the Carrier Frequency Selection (n080) to 1, 2, 3, or 4 when using vector control mode. Do not set it to 7, 8, or 9.
4. If the Inverter repeats stops and starts with a load exceeding 120% of the Inverter rated current within a cycle time of 10 minutes or less, reduce carrier frequency at a low speed. (Set constant n175 to 1.)
5. The carrier frequency is automatically reduced to 2.5 kHz when the Reducing Carrier Frequency Selection at Low
Speed (n175) is set to 1 and the following conditions are satisfied:
Output frequency ≤ 5 Hz
Output current ≥ 110%
Factory setting: 0 (Disabled)
Operator Stop Key Selection (n007)
WARNING
The Digital Operator stop button can be disabled by a setting in the Inverter. Install a separate emergency stop switch.
Failure to observe this warning may result in injury.
6. Programming Features
Set the processing when the STOP key is pressed during operation either from a multi-function input terminal or communications.
Setting
0
1
Description
The STOP key is effective either from a multifunction input terminal or communications. When the STOP key is pressed, the Inverter stops according to the setting of constant n005. At this time, the Digital Operator displays a alarm
(flashing). This STOP command is held in the
Inverter until both forward and reverse RUN commands are open, or until the RUN command from communications goes to zero.
The STOP key is ineffective either from multifunction input terminals or communications.
Selecting the Stopping Method
Stopping Method Selection (n005)
Select the stopping method suitable for the application.
Setting
0
1
Description
Deceleration to a stop
Coast to a stop
Deceleration to a Stop
Example when Acceleration/Deceleration Time 1 is selected
Output
Frequency
Acceleration
Time 1
(n019)
Deceleration
Time 1 Deceleration
(n020) Time 1 (n020)
Min. Output Frequency
(Frequency at
DC Injection Braking
Startup) n016
(Factory Setting: 1.5 Hz)
FWD (REV)
RUN
Command
Time
DC Injection Braking
Time at Stop (n090)
(Factory Setting: 0.5 s)
* Changing the frequency reference while running
Upon termination of a FWD (REV) RUN command, the motor decelerates at the deceleration rate determined by the time set in Deceleration
Time 1 (n020) and DC injection braking is applied immediately before stopping. DC injection braking is also applied when the motor deceler-
85
86 ates because the frequency reference is set lower than the Min. Output
Frequency (n016) when the FWD (REV) RUN command is ON. If the deceleration time is short or the load inertia is large, an overvoltage
(OV) fault may occur at deceleration. In this case, increase the deceleration time or install an optional Braking Resistor.
Braking torque: Without braking resistor: Approx. 20% of motor rating
With braking resistor: Approx. 150% of motor rating
Coast to a Stop
Example when Acceleration/Deceleration Time 1 is selected
Output
Frequency
Acceleration
Time 1
(n019)
Deceleration
Time 1
(n020) Coast to a stop
Time
FWD (REV)
RUN Command
* Changing the frequency reference while running
Upon termination of the FWD (REV) RUN command, the motor starts coasting.
Applying DC Injection Braking
DC Injection Braking Current (n089)
Sets the DC injection braking current in units of 1%. (Inverter rated current=100%)
DC Injection Braking Time at Stop (n090)
Sets the DC injection braking time at stopping in units of 0.1 s.
When the setting of n090 is 0, DC injection braking is not performed, but the Inverter output is turned OFF when DC injection braking is started.
6. Programming Features n016 Min.
Output
Frequency n090
DC Injection Braking
Time at Stop
When coasting to a stop is specified in the Stopping Method Selection
(n005), DC injection braking is not applied when stopping.
87
Building Interface Circuits with External Devices
Using Input Signals
The functions of multi-function input terminals S1 to S7 can be changed as necessary by setting constants n050 to n056. The same value cannot be set for more than one of these constants.
88
6
7
8
9
10
11
Setting
0
1
2
3
4
5
Name
FWD/REV RUN command
(3-wire sequence selection)* 1
FORWARD RUN command
(2-wire sequence selection)* 1
REVERSE RUN command
(2-wire sequence selection)* 1
External fault
(NO contact input)
External fault
(NC contact input)
Fault reset
12
13
14
15
Description
Setting enabled only for n052
(terminal S3)
Inverter stops for an external fault signal input. Digital
Operator displays EF.* 2
Resets a fault. Fault reset not effective when the RUN signal is ON.
Multi-step speed reference 1
Multi-step speed reference 2
Multi-step speed reference 3
Multi-step speed reference 4
JOG command
Acceleration/deceleration time selection 1
External baseblock,
NO contact input
External baseblock,
NC contact input
SEARCH command from maximum frequency
SEARCH command from set frequency
Motor coasts to a stop for this signal input. Digital Operator displays .
SPEED SEARCH command signal
Ref.
90
63
63
-
-
-
-
-
75
75
65
65
65
65
66
68
6. Programming Features
Setting
16
17
18
19
20
21
22
23
24
25
26
Name
ACCELERATION/
DECELERATION HOLD command
LOCAL/REMOTE selection
Communications/control circuit terminal selection
Emergency stop fault,
NO contact input
Emergency stop alarm,
NO contact input
Emergency stop fault,
NC contact input
Emergency stop alarm,
NC contact input
PID control cancel
PID integral reset
PID integral hold
Inverter overheat alert
(OH3 alarm)
Description
Inverter stops for an emergency stop signal input according to the Stopping Method Selection (n005). When frequency coasting to a stop (n005 is set to 0) is selected, the Inverter coasts to a stop according to
Deceleration Time Setting 2
(n022).
Digital Operator displays
.
Ref.
76
62
92
-
-
-
-
134
134
134
When the Inverter overheat signal turns ON, (flashing) is displayed at the Digital
Operator.
27 Acceleration/deceleration time selection 2
UP/DOWN commands
-
34
35
36
Self-test
UP/DOWN command 2
Setting enabled only for n056
(terminal S7)
Setting enabled only for n056
(terminal S7)
Setting enabled only for n056
(terminal S7)
91
122
-
* 1. For more information on how to select the sequence polarity, refer to page
188.
* 2. Numbers 1 to 7 are displayed for to indicate the terminal numbers S1 to
S7.
89
90
Factory Settings
No.
n050 n051 n052 n053 n054 n055 n056
Terminal Factory Setting
S1 1
S2
S3
S4
S5
S6
S7
2
6
7
3
5
10
Function
FORWARD RUN command
(2-wire sequence)
REVERSE RUN command
(2-wire sequence)
External fault (NO contact input)
Fault reset
Multi-step speed reference 1
Multi-step speed reference 2
JOG command
Terminal Functions for 3-wire Sequence Selection
When 0 is set for terminal S3 (n052), terminal S1 is the RUN command, terminal S2 is the STOP command, and terminal S3 is the FWD/REV
RUN command.
STOP SW
(NC Contact)
RUN SW
(NO Contact)
VS-606V7
RUN Command
(Run when Closed)
STOP Command
(Stop when Open)
FWD/REV Run Selection
FWD Run When Open
REV Run When Closed
WARNING
To select the 3-wire sequence, set terminal S3 (n052) to 0.
Failure to observe this warning may result in injury.
LOCAL/REMOTE Selection (Setting: 17)
Select the operation reference from either the Digital Operator or from the settings of the RUN Command Selection (n003) and Frequency Reference Selection (n004). The LOCAL/REMOTE Selection can be used only when stopped.
Open: Run according to the setting of RUN Command Selection
(n003) or Frequency Reference Selection (n004).
Closed: Run according to the frequency reference and RUN command from the Digital Operator.
6. Programming Features
Example: Set n003=1, n004=2, n008=0.
Open: Run according to the frequency reference from multi-function input terminal FR and RUN command from multi-function input terminals S1 to S7.
Closed: Run according to the potentiometer frequency reference and
RUN command from the Digital Operator.
UP/DOWN Commands (Setting: n056 = 34)
When the FWD (REV) RUN command is ON, acceleration/deceleration is enabled by inputting the UP or DOWN signal from multi-function input terminals S6 and S7 without changing the frequency reference.
Operation can thus be performed at the desired speed. When UP/
DOWN commands are specified in n056, any function set in n055 is disabled, terminal S6 is the input terminal for the UP command, and terminal S7 is the input terminal for the DOWN command.
Multi-function Input Terminal S6 (UP command)
Multi-function Input Terminal S7 (DOWN command)
Operation Status
Closed Open Open Closed
Open Closed Open Closed
Acceleration
Deceleration
Hold
Timechart for UP/DOWN Command Input
Hold
FWD RUN
UP Command S6
DOWN Command S7
Upper Limit Speed
Lower Limit Speed
Output Frequency
Frequency Agree
Signal
U = UP (accelerating) status
D = DOWN (decelerating) status
H = HOLD (constant speed) status
U1 = UP status, clamping at upper limit speed
D1 = DOWN status, clamping at lower limit speed
91
92
Note: 1. When UP/DOWN commands are selected, the upper limit speed is set regardless of frequency reference.
Upper limit speed = Maximum Output Frequency (n011)
× Frequency Reference Upper Limit (n033)/100
2. Lower limit value is either the Minimum Output Frequency (n016) or the Frequency Reference Lower Limit (n034) (whichever is larger.).
3. When the FWD (REV) RUN command is input, operation starts at the lower limit speed without using the UP/DOWN commands.
4. If the JOG command is input while running for an UP/DOWN command, the JOG command has priority.
5. Multi-step speed references 1 to 4 are not effective when an UP/
DOWN command is selected.
6. When 1 is set for the HOLD Output Frequency Memory Selection
(n100), the output frequency can be recorded during HOLD.
Setting
0 Output frequency is not recorded during
HOLD.
Description
1 When HOLD status is continued for 5 seconds or longer, the output frequency during HOLD is recorded and the Inverter restarts at the recorded frequency.
Communications/Control Circuit Terminal Selection
(Setting: 18)
Operation can be changed from communications commands, or from control circuit terminal or Digital Operator commands.
RUN commands from communications and the frequency reference are effective when the multi-function input terminal for this setting is closed (register No. 0001H, 0002H).
RUN commands in LOCAL/REMOTE mode and the frequency reference are effective when the terminal is open.
Using the Multi-function Analog Inputs (n077, n078, n079)
The input analog signal (0 to 10 V or 4 to 20 mA) for the CN2 terminal of the JVOP-140 Digital Operator can be used as an auxiliary function for the master frequency reference input to the control circuit terminals
(FR or RP). Refer to the block diagram on page 135 for details on the input signal.
NOTE
When using the signal for the CN2 terminal of the JVOP-140
Digital Operator as a multi-function analog input, never use it for the target value or the feedback value of PID control.
6. Programming Features
No.
Multi-function Input Selection (n077)
Name Unit n077 Multi-function Input Selection -
Setting
Range
0 to 4
Factory
Setting
0 n077 Settings
Setting
0
1
2
3
4
Function
Disabled
Auxiliary frequency reference (FREF2)
Frequency reference gain (FGAIN)
Frequency reference bias (FBIAS)
Output voltage bias
(VBIAS)
Description
The multi-function input is disabled.
When frequency reference 2 is selected using the multi-step speed references, the input analog signal for the CN2 terminal will be the frequency reference. The n025 setting will be invalid.
Note:Set the Frequency Reference Gain in n068 or n071, and the Frequency Reference Bias in n069 or n072.
Set the FGAIN to constant n060 or n074 and the FBIAS to constant n061 or n075 for the master frequency reference. Then, multiply the resulting frequency reference by the FGAIN.
Set the FGAIN to constant n060 or n074 and the FBIAS to constant n061 or n075 for the master frequency reference.
Then, add the FBIAS to the resulting frequency reference.
Then amount of the FBIAS to be added is set to n079.
Add the VBIAS to the output voltage after V/f conversion.
93
Analog Input Level
1. Auxiliary Frequency Reference
(n077=1)
FREF2
100%
2. Frequency Reference Gain
(n077=2)
FGAIN
2.00
1.00
0%
0 V
(4 mA)
10 V
(20 mA)
100%=Max. Output Frequency (n011)
0
0 V
(4 mA)
5 V 10 V
(20 mA)
3. Frequency Reference Bias (n077=3) 4. Output Voltage Bias (n077=4)
FBIAS VBIAS n079
100 V
94
0 %
0 V
(4 mA)
5 V 10 V
(20 mA)
-n079
0 V
0 V
(4 mA)
10 V
(20 mA)
The VBIAS value to be added is doubled for 400 V class Inverters.
Multi-function Analog Input Signal Selection (n078)
Constant
No.
n078
Name
Multi-function
Analog Input Signal
Selection
Unit
-
Setting Range
0=Digital Operator terminal
(voltage: 0 to 10 V)
1=Digital Operator terminal
(current 4 to 20 mA)
Frequency Reference Bias Setting (n079)
Constant
No.
n079
Name
Frequency
Reference
Bias Setting
Unit
1%
Setting Range
0 to 50
100 %/Max. Output Frequency
(n011)
Factory
Setting
0
Factory
Setting
10
6. Programming Features
Using Output Signals (n057, n058, n059)
The functions of multi-function output terminals MA, MB, P1 and P2 can be changed as necessary by setting constants n057, n058, and n059.
• Terminal MA and MB functions: Set in n057
• Terminal P1 function: Set in n058
• Terminal P2 function: Set in n059
Setting
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Fault
Name
Operating
Description
Closed when Inverter fault occurs.
Closed when either FWD/REV command is input or voltage is output from the Inverter.
Frequency agree
Zero speed
Frequency detection 1 Output frequency ≥ Frequency Detection Level (n095)
Frequency detection 2 Output frequency ≤ Frequency Detection Level (n095)
Overtorque detection,
NO contact output
Overtorque detection,
NC contact output
-
Undertorque detected,
NO contact output
Undertorque detected,
NC contact output
Minor fault
Closed when the set frequency agrees with Inverter output frequency.
Closed when Inverter output frequency is less than minimum output frequency.
-
-
Base blocked
Operating mode
Inverter operation ready
Fault retry
UV
Closed when an alarm has been detected.
Closed when the Inverter output is
OFF.
Closed when LOCAL is selected for the
LOCAL/REMOTE selection.
Closed when an Inverter fault is not detected, and operation is ready.
Closed during fault retries.
Closed when undervoltage is detected.
Ref.
-
-
96
-
-
-
-
-
-
-
73
73
72
72
151
151
95
Setting
16
17
18
19
20
21
Name
Reverse run
Speed search
Data output from communications
Description
Closed during reverse run.
Closed when Inverter conducts a speed search.
Operates multi-function output terminal independently from Inverter operation
(by MEMOBUS communication)
Ref.
-
-
107
PID feedback loss
Frequency reference loss
Closed during PID feedback loss
Inverter overheat alert Closed during Inverter overheat alert
133
Closed during frequency reference loss 149
89
No.
n057 n058 n059
Factory Settings
Terminal
MA, MB
P1
P2
Factory Setting
0 (fault)
1 (operating)
2 (frequency agree)
• FREQUENCY AGREE Signal (setting=2)
Release Width
±4 Hz
Detection Width
±2 Hz
Output Frequency
FREQUENCY AGREE Signal
96
6. Programming Features
Setting Frequency by Current Reference Input
When setting frequency by inputting current reference (4-20 mA or
0-20 mA) from the control circuit terminal FR, switch the DIP switch SW2 on the control circuit board to “I” side.
SW2
SW2
V I
NOTE
Never input voltage reference to control circuit terminal FR when DIP switch SW2 is switched to “I” side. The Inverter might be damaged.
97
98
Current Reference Selection
After changing DIP switch (V-I switch of SW2) to the “I” side, press
PRGM
on the Digital Operator, then set the following constants.
Current reference (4 to 20 mA)....constant n004 = 3
Current reference (0 to 20 mA)....constant n004 = 4
• Setting: n003 = 0
IM
Press the Digital Operator keys to run or stop the Inverter. Switch FWD and
REV run by setting F/R LED.
Current
Reference
4-20 mA or
0-20 mA
(n004 = 3 or 4
FS
FR
FC
Set frequency by the analog current signal [0-100 % (max. frequency)/4-
20 mA or 0 to 20 mA] connected to the control circuit terminals.
• Setting: n003 = 1
FWD RUN/STOP
REV RUN/STOP
S1
S2
SC
FS
FR
FC
IM
Switch run/stop and FWD/REV run with switching device connected to the control circuit terminal.
Multi-function input terminals S1 and
S2 are set to Forward run/stop
(n050=1) and Reverse run/stop
(n051=2) respectively.
Current
Reference
4-20 mA or
0-20 mA
(n004 = 3 or 4
Set frequency by the analog current signal [0-100 % (max. frequency)/4-
20 mA or 0 to 20 mA] connected to the control circuit terminal.
Frequency reference gain (n060)/bias (n061) can be set even when current reference input is selected. For details, refer to Adjusting Speed
Setting Signal on page 67.
6. Programming Features
Frequency Reference by Pulse Train Input
Frequency reference can be set by pulse train input from the control circuit terminals.
• Input pulse specifications
• Low-level voltage: 0.8 V or less
• High-level voltage: 3.5 to 13.2 V
• H duty: 30 to 70 %
• Pulse frequency: 0 to 33 kHz
• Frequency reference method
Frequency reference is a value obtained by multiplying the ratio of the maximum input pulse frequency and actual input pulse frequency by the maximum output frequency.
Reference frequency
=
Input pulse frequency
Maximum pulse train frequency (n149) × 10
×
Maximum output frequency (n011)
FWD RUN/STOP
REV RUN/STOP
Pulse
Reference
Device
S1
S2
SC
RP
FC
IM
Run/stop and FWD/REV can be selected by a switch connected to the multi-function input.
[Set S1 and S2 to FWD run/stop
(n050 = 1) or REV run/stop (n051 = 2).]
Set the frequency by a pulse-train input signal [0% to 100%
(maximum frequency)/0 kHz to 33 kHz] from the control circuit terminal.
Constant
No.
n003 n004 n149
Name Unit Setting
Range
RUN Command Selection
Frequency Reference
Selection
-
-
0 to 3
0 to 9
Pulse Train Input Scaling 1 = 10
Hz
100 to 3300
(33 kHz)
Factory
Setting
0
0
2500
(25 kHz)
99
Preventing the Motor from Stalling (Current
Limit)
This function automatically adjusts the output frequency and output current according to the load to continue operation without stalling the motor.
Stall Prevention (Current Limit) Level during Acceleration
(n093)
Sets the stall prevention (current limit) level during acceleration in units of 1%. (Inverter rated current = 100%)
Factory setting: 170%
A setting of 200% disables the stall prevention (current limit) during acceleration. If the output current exceeds the value set for n093 during acceleration, acceleration stops and the frequency is maintained. When the output current goes to the value set for n093, acceleration starts.
Motor Current n093
Output
Frequency
*2
Time
* 1 :
* 2 :
Stops the acceleration to prevent the motor from stalling.
Release width (hysteresis) of stall prevention during accel is approx. 5% of inverter rated current
Time
*1
100
Stall Prevention Level during Acceleration
6. Programming Features
In the constant output area (output frequency > Max. Voltage Output
Frequency (n013)), the stall prevention (current limit) level during acceleration is automatically decreased using the following equation.
Stall prevention (current limit) level during acceleration in constant output area
Stall prevention (current limit) level during acceleration (n093)
Max. voltage output frequency (n013)
Output frequency
Stall Prevention Level during
Acceleration (n093)
Stall Prevention Limit during
Acceleration (40% of n093)
Output Frequency
Maximum Voltage
Output Frequency n013
Stall Prevention (Current Limit) Level while Running (n094)
Sets the stall prevention (current limit) level while running in units of
1%. (Inverter rated current = 100%)
Factory setting: 160%
A setting of 200% disables stall prevention (current limit) while running.
If the stall prevention action current at speed agreement exceeds the value set for n094 for longer than 100 ms, deceleration starts.
If the output current exceeds the value set for n094, deceleration continues. If the output current goes to the value set for n094, acceleration to the set frequency starts.
Stall prevention acceleration/deceleration settings during operation are set either for the currently selected Acceleration Time, i.e., for Acceleration Time 1 (n019) and Deceleration Time 1 (n020), or for Acceleration Time 2 (n021) and Deceleration Time 2 (n022).
101
102
Motor Current n094
Output
Frequency
* 2
Time
* 1 :
* 2 :
Decreases frequency to prevent the motor from stalling.
At start of acceleration, the output current hysterisis is approx. 5% of Inverter rated current.
100 ms
Time
*1
Stall Prevention during Operation
Stall Prevention Above Base Speed During Run (n115)
The stall prevention level can be decreased automatically in the constant output range.
Constant
No.
n115
Name
Stall Prevention Above
Base Speed During Run
Unit
-
Setting
Range
0=Disabled
1=Enabled
Factory
Setting
0 n115 Settings
Setting
0
1
Function
The stall prevention level is the level set for constant n094 in all frequency areas.
The following figure shows how the stall prevention level is automatically decreased in the constant output range
(Max. frequency > Max. voltage output frequency (n013)).
The lower limit is 40% of the set value of n094.
Constant Output Area
Operation Level n094
Operation Level n094
Max. Voltage Output Frequency n013
Output Frequency
40% of n094 n013
Lower Limit
Output Frequency
6. Programming Features
Acceleration/Deceleration Time Selection during Stall Prevention (n116)
With this function, Acceleration Time 2 (n021) and Deceleration Time 2
(n022) can be fixed as the acceleration/deceleration time when moving to prevent stalling during operation.
Constant
No.
n116
Name
Acceleration/Deceleration
Time Selection during
Stall Prevention
Unit
-
Setting
Range
0=Disabled
1=Enabled
Factory
Setting
0 n116 Settings
Setting
0
1
Function
Acceleration/deceleration time is set to Acceleration/
Deceleration Time 1 or 2.
Acceleration/deceleration time is fixed at Acceleration/
Deceleration Time 2 (n021, n022)
• Stall Prevention during Deceleration (n092)
To prevent overvoltage during deceleration, the Inverter automatically extends the deceleration time according to the value of main circuit DC voltage. When using an optional braking resistor, set n092 to 1.
Controls the deceleration time to prevent overvoltage.
Setting
0
1
Stall Prevention during
Deceleration
Provided
Not provided (with braking resistor mounted)
Set
Decel
Time
Time
103
104
Decreasing Motor Speed Fluctuation
Slip Compensation (n002 = 0)
As the load becomes larger, the motor speed is reduced and the motor slip value is increased. The slip compensating function controls the motor speed at a constant value even if the load varies.
When the Inverter output current is equal to the Motor Rated Current
(n036), the compensation frequency is added to the output frequency.
Compensation frequency = Motor rated slip (n106)
Output current − Motor no-load current (n110)
Motor rated current
(n036)
Motor no-load current (n110)
Slip compensation gain (n111)
Related Constants
Constant
No.
n036
Name
Motor Rated Current n111 n110 n112 n106
Unit Setting Range
0.1 A 0% to 150% of Inverter rated current
0.1
0.0 to 2.5
Slip Compensation Gain
Motor No-load Current
Slip Compensation Time
Constant
Motor Rated Slip
1% 0% to 99%
(100%=Motor Rated
Current n036)
0.1 s 0.0 to 25.5 s
When 0.0 s is set, delay time is 2.0 s.
0.1 Hz 0.0 to 20 Hz
Factory
Setting
*
0.0
*
2.0 s
*
* Depends on Inverter capacity. (Refer to pages 207 and 208.)
Note: 1. Slip compensation is not performed under the following condition:
Output frequency < Minimum Output Frequency (n016)
2. Slip compensation is not performed during regeneration.
3. Slip compensation is not performed when the Motor Rated Current
(n036) is set to 0.0 A.
6. Programming Features
Motor Protection
Motor Overload Detection
The VS-606V7 protects against motor overload with a built-in electonic thermal overload relay.
Motor Rated Current (Electronic Thermal Reference Current, n036)
Set the rated current value shown on the motor nameplate.
Note: Setting n036 to 0.0 A disables the motor overload protective function.
Motor Overload Protection Selection (n037, n038) n037
Setting
0
1
2
Electronic Thermal Characteristics
For general-purpose motor
For Inverter motor
Electronic thermal overload protection not provided.
Constant
No.
Name Unit Setting Range Factory
Setting n038 Electronic Thermal
Motor Protection
Time Constant Setting
1 min 1 to 60 min 8 min
The electronic thermal overload function monitors the motor temperature based on Inverter output current and time to protect the motor from overheating. When the electronic thermal overload relay is enabled, an
error occurs, and the Inverter output is turned OFF to prevent excessive overheating in the motor. When operating with one Inverter connected to one motor, an external thermal relay is not needed. When operating more than one motor with one Inverter, install a thermal relay on each motor.
General-purpose Motors and Inverter Motors
Induction motors are classified as general-purpose motors or Inverter motors based on their cooling capabilities. The motor overload function operates differently for these two motor types.
105
106
Cooling Effect
Example for 200 V-Class Motors
Torque Characteristics
Effective when operated at
50/60 Hz from commercial power supply
Torque
(%)
60 s
Short-term
Continuous rating
Electronic
Thermal Overload error (motor overload protection) occurs when continuously operated at 50/
60 Hz or less at
100% load.
Operation Frequency (Hz)
Base Frequency 60 Hz
(V/f for 60-Hz, 220-V Input Voltage)
For low-speed operation, torque must be limited in order to stop motor temperature rise.
Effective even when operated at low speed
(approx. 6 Hz)
Torque
(%)
60 s
Short-term
Continuous rating
Electronic thermal overload protection is not activated even for continous operation at 50/60 Hz or less at a 100% load.
Operation Frequency (Hz)
Base Frequency 60 Hz
(V/f for 60-Hz, 220-V Input Voltage)
Use an Inverter motor for continuous operation at low speed.
6. Programming Features
Selecting Cooling Fan Operation
In order to increase the life of the cooling fan, the fan can be set to operate only when Inverter is running n039 = 0 (Factory setting): Operates only when Inverter is running
(Continues operation for 1 minute after
=1:
Inverter is stopped.)
Operates with power ON
Using MEMOBUS (MODBUS) Communications
Serial communication is available with VS-606V7 using programmable controller (MEMOCON series) and MEMOBUS (MODBUS). Refer to
MEMOBUS Instruction Manual (Manual No.: TOEZ-C736-70.1) for details of communications.
MEMOBUS (MODBUS) Communications
MEMOBUS system is composed of a single master (PLC) and slaves (1 to 31 VS-606V7 units).
Communication between master and slave (serial communication) is controlled according to the master program with the master initiating communication and the slave responding.
The master sends a signal to one slave at a time. Each slave has a preregistered address No., and the master specifies the number and conduct signal communications. The slave receives the communications to carry out designated functions and reply to the master.
MEMOCON Series
VS-606V7 VS-606V7 VS-606V7
Example of RS-485 communication
107
Communications specified
Interface
Synchronization
Communication
Parameters
RS-422, RS-485
Asynchronous (Start-stop synchronization)
Baud rate: Selected from 2400/4800/9600/19200 bps
Data length: 8 bits fixed
Parity: Selected from even/odd/none
Stop bits: 1 bit fixed
MEMOBUS (MODBUS) (RTU mode only) Communication
Protocol
Max. Number of
Inverters that Can be
Connected
31 units (When using RS-485)
Communications Connection Terminal
Use the following S+, S-, R+ and R- terminals for MEMOBUS communications. Change the termination resistor as shown below.
At RS-422, RS-485 communications: Turn ON SW2 ON/OFF switch of only the Inverter at the termination viewed from the PLC.
S+
S-
RS-422A or RS-485
R+
R-
Terminal Resistor (1/2W, 120 Ω)
SW2
SW2 ON/OFF Switch
SW1
SW2
PNP
NPN
OFF
V
ON
I
S5 S6 S7 P1 P2 R+ R- FS FR FC
S1 S2 S3 S4 SC PC S+ S- AM AC RP
108
Note: 1. Separate the wiring for communication from the main circuit wiring or other power lines.
2. Use shielded cables for communication wiring; connect the shielded sheath to the ground terminal and terminate the other end to prevent it from being connected (to prevent noise malfunction).
P2
PC
R+
S+
R-
S-
3. When communication is performed through RS-
485, connect S+ and R+, S- and R- terminals outside the Inverter as shown right side.
6. Programming Features
Procedure for Communications with PLC
The following shows the procedure for communications with PLC.
1. Connect the communication cable between the PLC and the VS-
606V7 with the power supply turned OFF.
2. Turn the power ON.
3. Set the constants (n151 to n157) required for communication by using the Digital Operator.
4. Turn the power OFF once to verify that the Digital Operator displays have been completely erased.
5. Turn the power ON again.
6. Communications with the PLC starts.
Setting Constants Necessary for Communication
Communication related constants must be set for PLC communication.
Constants n151 to n157 cannot be set by communication. Always set them before performing communication.
Constant n003 n004 n151 n152
Name Description
Run Command
Selection
Frequency Reference Selection
MEMOBUS
Timeover Detection Monitors
Transmission
Time between the
Receiving the
Correct Data from the PLC.
(Timeover: 2 s)
MEMOBUS
Frequency
Reference and
Frequency
Monitor Unit
0: Digital Operator
1: Control circuit terminals
2: MEMOBUS communications
3: Communications card (optional)
0: Potentiometer (Digital Operator)
1: Frequency reference 1 (n024)
2: Control circuit terminals (voltage 0 to 10 V)
3: Control circuit terminals (current 4 to 20 mA)
4: Control circuit terminals (current 0 to 20 mA)
5: Pulse train
6: MEMOBUS communication (register No. 0002H)
7: Operator circuit terminals (voltage 0 to 10 V)
8: Operator circuit terminals (current 4 to 20 mA)
9: Communication card (optional)
0: Timeover detection (coast to a stop)
1: Timeover detection (decelerates to a stop with speed deceleration time 1)
2: Timeover detection (decelerates to a stop with speed deceleration time 2)
3: Timeover detection (continuous operation, warning display)
4: Timeover detection not provided
0: 0.1 Hz
1: 0.01 Hz
2: 30000/100 % (30000=max.output frequency)
3: 0.1 %
Factory
Setting
0
0
0
0
109
Constant Name Description Factory
Setting
0 n153 n154 n155 n156 n157
MEMOBUS Slave
Address
Setting range: 0 to 32*
MEMOBUS BPS
Selection
0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
MEMOBUS Parity
Selection
0: Even parity
1: Odd parity
2: No parity
Transmission
Wating Time
RTS Control
Setting range: 10 ms to 65 ms
Setting unit: 1 ms
0: RTS control
1: No RTS control (RS-422A 1 to 1 communication)
2
2
10 ms
0
* The slave does not respond to the command from the master when set to 0.
Monitoring run status from the PLC, setting/referencing of constants, fault reset and multi-function input reference can be done regardless of run command or frequency reference selection.
Multi-function input reference from PLC becomes OR with input commands from S1 to S7 multi-function input terminals.
Message Format
For communications, the master (PLC) sends a command to the slave (VS-606V7) and the slave responds to it. The configuration for sending and receiving is as shown to the right. The length of the data varies according to the contents of commands (functions).
The interval between messages must be maintained at the following amount.
Slave address
Function code
Data
Error check
PLC - VS-606V7
Reference Message
VS-606V7 - PLC
Response Message
PLC - VS-606V7
Reference Message t (s)
24 bits n156 setting 24 bits 10 ms or more
• Slave address: Inverter address (0 to 32)
Setting to 0 indicates simultaneous broadcasting. The
Inverter does not respond to the command from the master.
110
6. Programming Features
• Function code: Command codes (See below.)
Function
Code
Hexadecimal
03H
Function Reference Message Response Message
Minimum
(Byte)
Maximum
(Byte)
Minimum
(Byte)
Maximum
(Byte)
08H
Reading holding register contents
Loop back test
8
8
8
8
7
8
37
8
10H Write in several holding registers
11 41 8 8
• Data: Composes a series of data by combining holding register numbers
(test codes for loop-back numbers) and their data. Data length depends on the contents of the command.
• Error check: CRC-16 (Calculate the value by the following method.)
1. The default value at calculation of CRC-16 is normally 0. In the
MEMOBUS system, change the default to 1 (all to 16-bit).
2. Calculate CRC-16 assuming that the loop address LSB is MSB and the last data MSB is LSB.
3. Also calculate CRC-16 for a response message from the slave and refer it to CRC-16 in the response message.
• Read Out Holding Register Contents (03H)
Reads out the contents of the holding registers with the continuous numbers for the specified quantity. The contents of holding register is dividing into the upper 8 bits and the lower 8 bits. They become the data items in response message in the order of numbers.
111
Quantity
(Example)
Reads out status signal, fault contents, data link status and frequency reference from the VS-606V7 (slave 2).
Reference Message
Slave address
Function code
Start number
Upper
Lower
Upper
Lower
02H
03H
00H
20H
00H
04H
Upper 45H
CRC-16
Lower F0H
(For error code 03H, refer to page 121.)
Response Message
(at normal operation)
Slave address
Function code
02H
03H
Number of data* 08H
First holding register
Upper 00H
Lower 65H
Upper 00H Next holding register
Next holding register
Lower
Upper
Lower
00H
00H
00H
Next holding register
Upper 01H
Lower F4H
Response Message
(at fault occurrence)
Slave address
Function code
02H
83H
Error code
Upper
CRC-16
Lower
03H
F1H
31H
CRC-16
Upper AFH
Lower 82H
* Twice as much as the number of reference message.
• Example of Loop-back Test (08H)
Reference message is returned as a response message without being changed. This function is used to check communication between the master and the slave. Any arbitrary values can be used for test codes or data.
(Example) Loop-back test of VS-606V7 (slave 1)
Reference Message
Slave address
Function code
Test code
Upper
Lower
Data
CRC-16
01H
08H
00H
00H
Upper
Lower
A5H
37H
Upper DAH
Lower 8DH
Response Message
(at normal operation)
Slave address
Function code
01H
08H
Test code
Data
CRC-16
Upper 00H
Lower 00H
Upper A5H
Lower 37H
Upper DAH
Lower 8DH
Response Message
(at fault occurrence)
Slave address
Function code
01H
89H
Error code
Upper
CRC-16
Lower
01H
86H
50H
112
6. Programming Features
• Writing to Several Holding Registers (10H)
Specified data are written into the several specified holding registers from the specified number, respectively. Written data must be arranged in a reference message in the order of the holding register numbers: from upper eight bits to lower eight bits.
(Example)
Set forward run at frequency reference 60.0 Hz to slave 1 VS-606V7 from the PLC.
Reference Message
Slave address
Function code
Start number
01H
10H
Upper 00H
Lower 01H
Quantity
Upper 00H
Lower 02H
Number of data*
First data
Upper 00H
Lower
04H
01H
Response Message
(at normal operation)
Slave address
Function code
01H
10H
Start number
Quantity
CRC-16
Upper 00H
Lower 01H
Upper 00H
Lower 02H
Upper 10H
Lower 08H
Response Message
(at fault occurrence)
Slave address
Function code
01H
90H
Error code 02H
Upper CDH
CRC-16
Lower C1H
Next data
Upper 02H
Lower 58H
CRC-16
Upper 63H
Lower 39H
* Sets twice as large as the actual number.
113
Data
• Reference Data (available to read out/write in)
Register
No.
Bit
0000H Reserved
0001H
0
1
2
3
RUN command
Reverse run
External fault
Fault reset
Description
1: Run 0: Stop
1: Reverse run 0: Forward run
1: Fault (EFO)
1: Reset command
4 Multi-function input reference 1 (Function selected by n050)
5 Multi-function input reference 2 (Function selected by n051)
6 Multi-function input reference 3 (Function selected by n052)
7 Multi-function input reference 4 (Function selected by n053)
0002H
0003H
0004H-
0008H
8 Multi-function input reference 5 (Function selected by n054)
9 Multi-function input reference 6 (Function selected by n055)
A Multi-function input reference 7 (Function selected by n056)
B-F (Not used)
Frequency reference (unit: n152)
V/f gain (1000/100 %) Setting range: 2.0 to 200.0 %
Reserved
0009H
0
1
2
Multi-function output reference 1
(Effective when n057=18)
Multi-function output reference 2
(Effective when n058=18)
Multi-function output reference 3
(Effective when n059=18)
3-F (Not used)
(1: MA ON 0: MA OFF)
(1: P1 ON 0: P1 OFF)
(1: P2 ON 0: P2 OFF)
000AH-
001FH
Reserved
Note: Write in “0” for unused bit. Never write in data for the reserved register.
114
6. Programming Features
• Simultaneous Broadcasting Data (available only for write in)
Register
No.
Bit Description
0001H
0002H
2
3
0
1
4
5
RUN command
Reverse run
(Not used)
(Not used)
External fault
Fault reset
1: Run 0: Stop
1: Reverse run 0: Forward run
1: Fault (EFO)
1: Fault reset command
6-F (Not used)
Frequency reference 30000/100 % fixed unit
(Data is converted into 0.01 Hz inside the Inverter, and fractions are rounded off.)
Bit signals not defined as the broadcast operation signals are used as the local station data signals.
Register
No.
• Monitor Data (available only for read out)
Bit Description
0020H
0
1
2
RUN command
Reverse run
Inverter operation ready
1: Run
1: Reverse run 0: Forward run
1: Ready
5
6
3
4
Fault
Data setting error
1: Fault
1: Error
Multi-function output 1 (1: MA ON
Multi-function output 2 (1: P1 ON
7 Multi-function output 3 (1: P2 ON
8-F (Not used)
0: Stop
0: Not ready
0: MA OFF)
0: P1 OFF)
0: P2 OFF)
115
Register
No.
0021H
0022H
0023H
0024H
0025H-
0026H
0027H
0028H
Bit Description
6
7
4
5
2
3
0
1
Overcurrent (OC)
Overvoltage (OV)
Inverter overload (OL2)
Inverter overheat (OH)
(Not used)
(Not used)
PID feedback loss (FbL)
External fault (EF, EFO), Emergency stop (STP)
8
9
Hardware fault (FXX)
Motor overload (OL1)
A Overtorque detection (OL3)
B Undertorque detection (UL3)
C Power loss (UV1)
D Control power fault (UV2)
E MEMOBUS communications timeover (CE)
F Operator connection fault (OPR)
2
3
0
1
Data wirte in
(Not used)
(Not used)
Upper/lower limit fault
4 Consistency fauft
5-F (Not used)
Frequency reference (unit: n152)
Output frequency (unit: n152)
(Not used)
Output current (10/1 A)
Output voltage reference (1/1 V)
116
Register
No.
0029H
002AH
002BH
6. Programming Features
Bit Description
2
3
0
1
(Not used)
(Not used)
Input open phase (PF)
Output open phase (LF)
4-F (Not used)
0 Operation function stop (STP)
1
2
Sequence error (SER)
Simultaneous FWD/REV run commands (EF)
5
6
3
4
External baseblock (BB)
Overtorque detection (OL3)
Cooling fan overheat (OH)
Main circuit overvoltage (OV)
7
8
Main circuit undervoltage (UV)
Cooling fan fault (FAN)
9 Communications fault (CE)
A Option card communications error (BUS)
B Undertorque (UL3)
C Inverter overheat alert (OH3)
D PID feedback loss (FBL)
E Emergency stop (STP)
1
2
F Communications waiting (CAL)
0 Terminal S1 1: Closed
Terminal S2
Terminal S3
1: Closed
1: Closed
5
6
3
4
Terminal S4
Terminal S5
Terminal S6
Terminal S7
7-F (Not used)
1: Closed
1: Closed
1: Closed
1: Closed
0: Open
0: Open
0: Open
0: Open
0: Open
0: Open
0: Open
117
Register
No.
002CH
002DH
002EH
Bit Description
2
3
0
1
Run
Zero-speed
1: Run
1: Zero-speed
6
7
4
5
8
Frequency agreed 1: Agreed
Minor fault (Alarm is indicated)
Frequency detection 1
Frequency detection 2
Inverter operation ready
Undervoltage detection
1: Output frequency ≤ (n095)
1: Output frequency ≥ (n095)
1: Ready
1: Undervoltage detection
9
A
B
C
Baseblock 1: Inverter output baseblock
Frequency referecne mode 1: Other than communications
0: Communications
RUN command mode
Overtorque detection
Undertorque detection
1: Other than communications
0: Communications
1: Detection or overtorque fault
1: Detection or undertorque fault
D Fault retry
E
Fault (Including MEMOBUS communications timeover)
1: Fault
1
2
F MEMOBUS communications timeover 1: Timeover
0 MA 1: ON 0: OFF
P1
P2
1: ON
1: ON
0: OFF
0: OFF
3-F (Not used)
0 Frequency reference loss 1: Frequency reference loss
1-F (Not used)
002FH-
0030H
0031H
0032H
0033H-
0036H
0037H
Reserved
Main circuit DC voltage (1/1 V)
Torque monitor (1/1 % ; 100 %/Motor rated torque ; with sign)
(Not used)
Output Power (1/1 W: with sign)
118
6. Programming Features
Register
No.
Bit Description
0038H
PID feedback value (100 % /Input equivalent to max. output frequency ;
10/1 % ; without sign)
0039H PID input value ( ±100 %/±Max. output frequency ; 10/1 % ; with sign)
003AH PID output value ( ±100 %/±Max. output frequency ; 10/1 % ; with sign)
003BH-
003CH
Reserved
003DH
6
7
4
5
2
3
0
1
CRC error
Data length fault
(Not used)
Parity error
Overrun error
Framing error
Timeover
(Not used)
003EH-
00FFH
Reserved
* Communications error contents are saved until fault reset is input.
(Reset is enabled during run.)
Storing Constants [ENTER Command] (can be written only.)
Register
No.
Name
0900H ENTER command
Contents
Write in constant data to nonvolatile memory (EEPROM)
Setting
Range
0000H to
FFFFH
Factory
Setting
-
When a constant is written from the PLC by communications, the constant is written to the constant data area on the RAM in the VS-606V7.
ENTER command is a command to write the constant data on the RAM to the non-volatile memory in the VS-606V7. This ENTER command is executed when data, regardlesss of the value, is written to register number 0900H. With the factory setting, an ENTER command is accepted only while the Inverter is stopped. By changing constant n170, an ENTER command can be accepted even while the Inverter is running.
119
120
CAUTION
While the constant is being stored after an ENTER command was issued, response to the commands or data input with the keys on the Digital Operator
(JVOP-140) becomes poor. Be sure to take some measures for an emergency stop by using the external terminals (setting the external terminal to run command priority, or setting the multi-function input terminal to external fault, external baseblock or emergency stop).
NOTE
Maximum number of writing times of the non-volatile memory used for VS-606V7 is 100,000; do not execute the
ENTER command excessively.
When a constant is changed from the Digital Operator, the constant data on the RAM is written to the non-volatile memory without ENTER command.
Constant
No.
n170
Name
ENTER command operation selection (MEMOBUS communications)
Unit Setting
Range
0, 1
Factory
Setting
0 n170
Setting
0
Description
Accepts the ENTER command (constant saving) while the
Inverter is stopped.
1 Always accepts the ENTER command (constant storing).
The new constant becomes valid even if the ENTER command is not input. If the ENTER command is not used, however, the value returns to the stored value when the power supply is turned ON again.
Register number 0900H is used only for write-in. If this register is readout, register number error (error code: 02H) occurs.
6. Programming Features
Error code
Error
Code
Contents
01H
02H
03H
21H
22H
Function code error
• Function code from PLC is other than 03H, 08H, or 10H.
Improper register number
• No register numbers to be accessed have been registered.
• ENTER command “0900H” that is an exclusive-use register for write-in was read out.
Improper quantity
• The number of data items to be read or wirte-in is not in the range between 1 and 16.
• The number of data items in a message is not the value obtained by multiplying the quantity by two in the write-in mode.
Data setting error
• A simple upper/lower limit error occurred with control data or constant wirte-in.
• A constant setting error occurred when a constant was written.
Write-in mode error
• Attempt to write-in a constant from PLC was made during running.*
• Attempt to write-in an ENTER command from PLC was made during running.
• Attempt to write-in a constant from PLC was made during UV occurrence.
• Attempt to write-in an ENTER command from PLC was made during UV occurrence.
• Attempt to write-in a constant other than n001=8, 9 (constant initialization) from PLC was made during “F04” occurrence.
• Attempt to write-in a constant from PLC was made while data were being stored.
• Attempt to write-in data exclusive for read-out from PLC was made.
* Refer to the constants list for constants that can be changed during operation.
121
122
Performing Self-test
VS-606V7 is provided with a function to perform self-diagnosis for operation check of the serial communication I/F circuit. This function is called self-test. In the self-test, connect the sending terminal with the receiving terminal in the communication section. It assures if the data received by VS-606V7 is not being changed. It also checks if the data can be received normally.
Carry out the self-test in the following procedure.
1. Turn ON the VS-606V7 power supply. Set constant n056 to 35
(self-test).
2. Turn OFF the VS-606V7 power supply.
3. Make the following wiring with the power supply turned OFF.
4. Turn the power ON.
S7 P1 P2 R+ R-
S4 SC PC S+ S-
(Note: Select NPN side for SW1.)
Normal operation: Operator displays frequency reference value.
Faulty operation: Operator displays , fault signal is turned ON and
Inverter ready signal is turned OFF.
6. Programming Features
Using Energy-saving Control Mode
Verify that the constant n002 is set to 0 (V/f control mode) when performing energy-saving control. Set n139 to 1 to enable the energy-saving control function.
Energy-saving Control Selection (n139)
Constant
No.
Name Unit Setting Range Factory
Setting n139 Energy-saving Control
Selection
0: Disabled
1: Enabled
0
Normally it is not necessary to change this setting. However, if the motor characteristics are different from a Yaskawa standard motor, refer to the description below and change the constant setting accordingly.
Energy-saving Control Mode (n140, n158)
The voltage for the best motor efficiency is calculated when operating in energy-saving control mode. The calculated voltage is used as the output voltage reference. The factory setting is set to the max. applicable motor capacity for a Yaskawa standard motor.
The greater the enegy-saving coefficient is, the greater the output voltage becomes.
When using a motor other than a Yaskawa standard motor, set the motor code corresponding to the voltage and capacity in n158. Then, change the setting of the energy-saving coefficient K2 (n140) by 5% to minimize the output power.
When the motor code is set in n158, the energy-saving coefficient K2, which corresponds to the motor code, must be set in n140.
Constant
No.
n140
Name Unit Setting Range Factory
Setting
0.0 to 6550 * n158
Energy-saving Control
Coefficient K2
Motor Code
-
0 to 70 *
* Depends on Inverter capacity. (Refer to page 196 and following pages.)
123
Energy-saving Voltage Lower/Upper Limits (n141, n142, n159, n160)
Set the upper and lower limits of the output voltage. When the value calculated in the energy-saving control mode is larger than the upper limit (or smaller than the lower limit), the limit value is output as the voltage reference. The upper limit is set to prevent over-excitation, and the lower limit is set to prevent stalls when the load is light. The voltage limit is set for machines using 6 or 60 Hz. For any value other than 6 or
60 Hz, set th e voltage limit using linear interpolation. The constants are set in % for 200-V/400-V Inverters.
Setting
Range
0 to 120
Factory
Setting
50
Constant
No.
n141 n142 n159 n160
Name
Lower Voltage Limit Energysaving Control at 60 Hz
Lower Voltage Limit Energysaving Control at 6 Hz
Upper Voltage Limit for Energysaving Control at 60 Hz
Upper Voltage Limit for Energysaving Control at 6 Hz
Unit
1%
1%
1%
1%
0 to 25
0 to 120
0 to 25
12
120
16
Voltage Limit
250 V*
Upper Limit
Lower Limit
6 Hz 60 Hz
* Doubled for the 400 V Class Inverters.
Output Frequency
124
Energy-saving Search Operation
In energy-saving control mode, the maximum applicable voltage is calculated using the output power. However, a temperature change or the use of another manufacturer’s motor will change the fixed constants, and the maximum applicable voltage may not be emitted. In the search operation, change the voltage slightly so that the maximum applicable voltage can be obtained.
6. Programming Features
Search Operation Voltage Limit (n144)
Limits the range where the voltage is controlled. The constant is set in
% for 200-V/400-V Inverters. The search operation is not performed when n144 is set to 0.
Constant
No.
n144
Name
Search Operation Voltage
Limit
Unit
1%
Setting
Range
0 to 100
Factory
Setting
0
Search Operation Voltage Steps (n145, n146)
Constants n145 and n146 set the change in voltage for one cycle of the search operation. For 200 V Class Inverters, set the values as percentages of 200 V. For 400 V Class Inverters, set the values as percentages of 400 V. Increase the value and the changes in the rotation speed will also increase.
For 200 V Class Inverters, the range of the change in voltage is determined from the 100% and 5% settings for 200 V. For 400 V Class
Inverters, the range of the change in voltage is determined from the
100% and 5% settings for 400 V. The values calculated by linear interpolation are used for voltages other than these.
Constant
No.
n145 n146 n143
Name
Search Operation Voltage
Step at 100%
Search Operation Voltage
Step at 5%
Power Average Time
Unit
0.1%
0.1%
1 = 24 ms
Setting
Range
0.1 to 10.0
0.1 to 10.0
1 to 200
Factory
Setting
0.5
0.2
1 (24 ms)
Voltage Fluctuation
Output Voltage
125
126
Search Operation Power Detection Hold Width (n161)
When the power fluctuation is less than this value, the output voltage is held for 3 seconds, and then, the search operating mode is started. Set the hold width as a percentage of the power that is currently held.
Constant
No.
n161
Name Unit Setting
Range
0 to 100 Search Operation
Power Detection Hold
Width
1%
Time Constant of Power Detection Filter (n162)
Response at load changes is improved when this value is small.
At low frequency, however, unstable rotation will result.
Factory
Setting
10
Constant
No.
n162
Name Unit
Time Constant of Power
Detection Filter
1 = 4 ms
Setting
Range
0 to 255
Factory
Setting
5
(20 ms)
6. Programming Features
Motor Code
The Energy-saving Coefficient K2 (n140) is set to a value that corresponds to the Motor Code (n158).
Motor Type
Yaskawa
Generalpurpose
Motor
Voltage
Class
200 V
400 V
5.5 kW
7.5 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.7 kW
3.7 kW
5.5 kW
7.5 kW
23
24
25
26
9
10
21
22
27
29
30
5
7
3
4
0
1
2
Capacity Motor Code: n158
Energy-saving
Coefficient K2: n140
481.7
356.9
288.2
223.7
169.4
156.8
122.9
94.8
72.7
713.8
576.4
447.4
338.8
313.6
245.8
245.8
189.5
145.4
127
128
Motor Type
Yaskawa
Inverter
Motor
Voltage
Class
200 V
400 V
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.7 kW
5.5 kW
7.5 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
3.7 kW
5.5 kW
7.5 kW
61
62
63
64
45
47
49
50
40
41
42
43
44
65
66
67
69
70
Capacity Motor Code: n158
Energy-saving
Coefficient K2: n140
481.7
356.9
300.9
224.7
160.4
138.9
106.9
84.1
71.7
713.8
601.8
449.4
320.8
277.8
213.8
213.8
168.3
143.3
Using PID Control Mode
For details on the PID control settings, refer to the block diagram of the
Inverter’s internal PID control or the block diagram of the Operator analog speed reference.
6. Programming Features
PID Control Selection (n128)
Constant
No.
n128
Name
PID Control Selection
Unit
-
Setting
Range
0 to 8
Factory
Setting
0
Setting
0
1
2
3
Disabled.
Function
Enabled: Deviation is subject to derivative control.
Enabled: Feedback signal is subject to derivative control.
Enabled: Frequency reference + PID output, and deviation are subject to derivative control.
PID Output
Characteristics
-
Forward
4
5
6
7
8
Enabled: Frequency reference + PID output, and feedback signal are subject to derivative control.
Enabled: Deviation is subject to derivative control.
Enabled: Feedback signal is subject to derivative control.
Enabled: Frequency reference + PID output, and deviation are subject to derivative control.
Reverse
(Reverse the
PID output.)
Enabled: Frequency reference + PID output, and feedback signal are subject to derivative control.
Set one of the above values when using PID control.
The following table shows how to determine the target value and the feedback value to be input when PID control is enabled.
Target
Value
Input
The currently selected frequency reference
Feedback
Value
The frequency reference that is set in the PID
Feedback Value Selection (n164)
Condition
Determined by the Frequency Reference
Selection (n004).
When local mode is selected, the target value is determined by the Frequency Reference Selection in Local Mode (n008).
When multi-step speed references are selected, the currently selected frequency reference will be the target value.
-
129
130 n164 Setting
0
1
2
3
4
Description
Control circuit terminal FR (Voltage 0 to 10 V)
Control circuit terminal FR (Current 4 to 20 mA)
Control circuit terminal FR (Current 0 to 20 mA)
Operator terminal: Voltage 0 to 10 V
Operator terminal: Current 4 to 20 mA
5 Pulse train
Note: 1. When selecting frequency reference from the control circuit terminal
FR as the target or feedback value, the V-I switch of SW2 on the control circuit board must be selected depending on the input method
(current or voltage input).
2. Never use the frequency reference from the control circuit terminal
FR for both the target and feedback values. The frequency reference for both the target value and the feedback value becomes the same.
(Example)
When the frequency reference from the control cirucit terminal FR, with a voltage of 0 to 10 V, is selected as the target value and n004=2, and when at the same time the frequency reference from the control circuit terminal FR, with a current of 4 to 20 mA, is selected as the feedback value and n164=1, the feedback value will be set as the frequency reference from the control circuit terminal FR with a voltage of 0 to 10 V.
3. When using an analog signal (0 to 10 V/4 to 20 mA) input to the CN2 terminal of the JVOP-140 Digital Operator as the target or feedback value of PID control, do not use it as a multi-function analog input.
Constant n077 (Multi-function Analog Input Function) must be set to
0 (disabled in this case).
6. Programming Features
Proportional Gain (P), Integral Time (I), Derivative Time (D)
(n130, n131, n132)
Adjust the response of the PID control with the proportional gain (P), integral time (I), and derivative time (D).
Constant
No.
n130 n131
Name
Proportional Gain (P)
Integral Time (I)
Unit
0.1
0.1 s
Setting
Range
0.0 to 25.0
0.0 to 360.0
Factory
Setting
1.0
1.0
n132 Derivative Time (D) 0.01 s 0.00 to 2.50
0.00
Optimize the responsiveness by adjusting the constants while operating an actual load (mechanical system). Any control (P, I, or D) that is set to zero will not operate.
Upper Limit of Integral (I) Values (n134)
Constant
No.
Name Unit Setting
Range
Factory
Setting n134 Upper Limit of Integral
Values
1% 0 to 100 100
Constant n134 prevents the calculated value of integral control from exceeding a specific amount. There is normally no need to change the setting.
Reduce the setting if there is a risk of load damage, or of the motor going out of step by the Inverter’s response when the load suddenly changes. If the setting is reduced too much, the target value and the feedback value will not match.
Set this constant as a percentage of the maximum output frequency with the maximum frequency as 100%.
PID Offset Adjustment (n133)
Constant
No.
Name Unit Setting
Range
Factory
Setting n133 PID Offset Adjustment 1% -100 to 100 0
Constant n133 adjusts the PID control offset.
If both the target value and the feedback values are zero, adjust n133 so that the Inverter output frequency is zero.
131
Primary Delay Time Constant for PID Output (n135)
Constant
No.
Name Unit Setting
Range
Factory
Setting n135 Primary Delay Time
Constant for PID Output
0.1 s 0.0 to 10.0
0.0
Constant n135 is the low-pass filter setting for PID control outputs.
There is normally no need to change the setting.
If the viscous friction of the mechanical system is high or if the rigidity is low causing the mechanical system to resonate, increase the setting so that it is higher than the resonance frequency period.
PID Output Gain (n163)
Factory
Setting
1.0
Constant
No.
Name Unit Setting
Range n163 PID Output Gain 0.1
0.0 to 25.0
Constant n163 adjusts the PID control output gain.
PID Feedback Gain (n129)
Constant
No.
Name Unit Setting
Range n129 PID Feedback Gain 0.01
0.00 to 10.00
Constant n129 is the gain that adjusts the feedback value.
Factory
Setting
1.00
132
6. Programming Features
PID Feedback Loss Detection (n136, n137, n138)
Constant
No.
n136
Name
Selection for PID
Feedback Loss Detection
Unit Setting Range Factory
Setting
0 n137 PID Feedback Loss
Detection Level
0: No detection of
PID feedback loss
1: Detection of PID feedback loss, operation continued: FbL alarm
2: Detection of PID feedback loss, output turned
OFF: Fault
1% 0 to 100
100%/Max. output frequency
0 n138 PID Feedback Loss
Detection Time
0.1 s 0.0 to 25.5
1.0
PID Upper Limit
Sets the upper limit after PID control as a percentage of the maximum output frequency.
Prohibition of PID Output
Zero limit occurs when the PID output is negative.
133
PID output v MNTR (U-18) 100%/FMAX
134
11
Adjustment gain
6. Programming Features
A/D conversion
A/D conversion
GND Pin 3
135
136
Using Constant Copy Function
Constant Copy Function
The VS-606V7 standard JVOP-140 Digital Operator can store constants for one Inverter. A backup power supply is not necessary because
EEPROM is used.
The constant copy function is possible only for the Inverters with the same product series, power supply specifications, and control mode (V/ f control or vector control). However, some constants may not be copied. It is also impossible to copy constants between VS-606V7 and VS mini J7 Inverters.
Prohibiting reading constants from the Inverter can be set in n177. The constant data cannot be changed when this constant is set.
If an alarm occurs when copying constants, PRGM will flash and copying will continue.
NOTE
To remove the Digital Operator from the Inverter, turn OFF the input power supply of the Inverter and confirm that the display on the Digital Operator has turned OFF. If the Digital
Operator is removed during the power ON, the Inverter may be broken.
Constant Copy Function Selection (n176)
Depending on the setting of n176 (Constant Copy Function Selection), the following functions can be used.
1. Reading all the constants from the Inverter (READ) and storing them in EEPROM in the Digital Operator
2. Copying the constants stored in the Digital Operator to the Inverter
(COPY)
3. Verifying that the constants in the Digital Operator and the constants in the Inverter are the same (VERIFY)
4. Displaying the maximum applicable motor capacity and the voltage class of the Inverter for which constants are stored in the Digital
Operator
5. Displaying the software number of the Inverter for which constants are stored in the Digital Operator
6. Programming Features
Constant
No.
Name Unit Setting Range Factory
Setting n176 Constant
Copy Function Selection
rdy: READY rEd: READ
CPy: COPY vFy: VERIFY vA: Inverter capacity display
Sno: Software No. display rdy
Prohibiting Constant Read Selection (n177)
Select this function to prevent accidentally overwriting the constants stored in EEPROM in the Digital Operator. Reading is not possible when this constant is set to 0.
The constant data stored in the Digital Operator are safe from accidental overwriting.
If reading is attempted while this constant is set to 0, PrE will flash.
Press
DSPL
or
ENTER
and return to the constant No. display.
Constant
No.
n177
Name
Constant Read
Selection Prohibit
Unit
-
Setting Range
0: READ prohibited
1: READ allowed
Factory
Setting
0
137
READ Function
Reads out the constants in batch from the Inverter and stores them in
EEPROM inside the Digital Operator. When the read-out is executed, the previously stored constants data in the EEPROM are cleared and replaced with the newly entered constants.
Example: Storing Constants from Inverter in EEPROM in Operator
• Enable the setting of constants n001 to n179.
Explanation
• Press
PRGM
DSPL
.
to lit
• Press to display the set value.
• Change the set value to
4 by pressing the or key.
ENTER
• Press ENTER .
Operator Display
(May be a different constant No.)
(Lit)
(May be a different set value.)
(Flashes)
(Lit for one second.)
↓
(The constant No. is displayed.)
• Set Contant
Read Prohibited
Selection (n177) to read-enabled.
*1
• Change the constant No. to n177 by pressing the
or key.
• Press ENTER to display the set value.
• Change the set value to
1 by pressing the or key.
• Press ENTER .
(Lit)
(Flashes)
(Lit for one second.)
↓
(The constant No. is displayed.)
138
6. Programming Features
Explanation read-out
(READ) using the
Constant Copy
Function Selection (n176).
• Change the constant No. by pressing the or key.
• Press ENTER play the set value.
• Change the set value to rEd by pressing the or
key.
• Press ENTER .
• Press
ENTER
DSPL
.
or
Operator Display
(Lit)
(Lit)
(Flashes while executing the read)
↓
(End is displayed after the read has been completed.)
(The constant No. is displayed.)
• Set Constant
Read Prohibited
Selection (n177) to read-disabled.
*2
• Change the constant No. to n177 by pressing the
or key.
• Press ENTER play the set value.
• Change the set value to
0 by pressing the or key.
• Press ENTER .
(Lit)
(Flashes)
(Lit for one second.)
↓
(The constant No. is displayed.)
* 1. When reading is enabled (n177=1), this setting is not necessary.
* 2. This setting is not necessary unless read-prohibition is selected.
COPY Function
This function writes the constants stored inside the Digital Operator in batch to the Inverter. Write-in is possible only for Inverters with the same product series, power supply specifications, and control mode (V/ f control or vector control).
Therefore, writing from 200 V Class to 400 V Class Inverters (or vice versa), from V/f control mode to vector control mode Inverters (or vice versa), or from VS-606V7 to VS mini J7 Inverters is not possible.
The Constant Copy Function Selection (n176), Constant Read Selection
Prohibit (n177), Fault History (n178), Software Version No. (n179), and hold output frequency are not written. vAE will appear (flashing) if the capacities of the Inverters differ.
Press ENTER to continue writing (the COPY function).
139
Press STOP/RESET to stop the COPY function.
The following constants are not written if the Inverter capacities differ.
Constant No.
n011 to n017 V/f Settings
Name n036 Motor Rated Current n080 n105
Carrier Frequency Selection
Torque Compensation Iron
Loss
Motor Rated Slip
Constant No.
n108 n109 n110 n140
Name
Motor Leakage Inductance
Torque Compensation Voltage Limiter
Motor No-load Current
Energy-saving Coefficient
K2
Motor Code n106 n158 n107 Motor Line-to-neutral Resistance
Constants added with software version upgrades will not be written between VS-606V7 Inverters without the additional constants and VS-
606V7 Inverters with the additional constans.
For this reason, the settings for the additional constants will not be changed by the copy operation.
Example: Writing Constants from EEPROM in Operator to Inverter
Explanation Operator Display
• Enable the settings for constants n001 to n179.
• Press
PRGM
DSPL
.
to lit
• Press ENTER to display the set value.
• Change the set value to 4 by pressing the or key.
• Press ENTER .
(May be a different constant No.)
(Lit)
(May be a different set value.)
(Flashes)
(Lit for one second.)
↓
(The constant No. is displayed.)
140
6. Programming Features
Explanation
• Execute write-in
(COPY) using the Constant
Copy Function
Selection (n176).
• Change the constant No. to n176 by pressing the
or key.
• Press ENTER to display the set value.
• Change the set value to
CPy by pressing the or
key.
• Press ENTER .
• Press
ENTER
DSPL
.
or
Operator Display
(Lit)
(Lit)
(Flashes while executing the copy.)
↓
(End is displayed after the copy has been completed.)
(The constant No. is displayed.)
A setting range check and matching check for the written constants are executed after the constants are written from the Digital Operator to the
Inverter. If a constant error is found, the written constants are discarded and the constants stored before writing are restored.
When a setting range error is found, the constant No. where an error occurs is indicated by flashing.
When an inconsistency in the settings is found, is indicated by flashing.
(: a number)
VERIFY Function
This function compares the constants stored in the Digital Operator with the constant in the Inverter. Verification is possible only for the Inverters with same product series, power supply specifications, and control mode (V/f control or vector control).
When the constants stored in the Digital Operator are the same as those in the Inverter, vFy will flash, and then End will be displayed.
When the constants are not the same, the unmatched constant No. will be displayed.
141
Constants added with software version upgrades will be displayed when
VERIFY is performed for VS-606V7 Inverters without the additional constants and VS-606V7 Inverters with the additional constants.
The constants added with each software version upgrade are shown in the following table.
Software No.
Additional Constants
VSP010015 or later
VSP010020 or later
VSP010024 or later n175 n077, n078, n079, n115, n116 n040, n041, n042, n043, n044, n064, n101, n102, n117, n118, n119, n166, n167, n168, n169, n173, n174
VSP010028 or later n045, n046, n047, n048, n049, n170, n171, n172
Refer to page 196 (Constants List) for deitals.
Example: Comparing Constants Stored in EEPROM in Operator with
Constants in Inverter
• Enable the settings for constants n001 to n179.
Explanation Operator Display
• Press
PRGM
DSPL
.
• Press ENTER to display the set value.
• Change the set value to 4 by pressing the or key.
• Press ENTER .
(May be a different constant No.)
(Lit)
(May be a different set value.)
(Flashes)
(Lit for one second.)
↓
(The constant No. is displayed.)
142
6. Programming Features
Explanation
VERIFY by Constant
Copy Function
Selection (n176).
• Change the constant No. to n176 by pressing the
• Press ENTER the set value.
• Change the set value to vFy by pressing the or
key.
• Press ENTER .
• Display the unmatched constant No.
• Display the constant value in the Inverter.
• Display the constant value in the
Digital Operator.
the execution of
VERIFY.
• Press
• Press
• Press the key.
• Press
ENTER
ENTER
DSPL
ENTER .
.
.
or
Operator Display
(Lit)
(Lit)
(Flashes while executing the verification)
(Flashes)
(When n011 is different.)
(Flashes)
(Flashes)
(Flashes while executing the verification)
↓
(End is displayed when the verification has been completed.) played.)
(The constant No. is dis-
While a constant No. that is not the same is displayed or a constant value is displayed, press STOP/RESET to interrupt the execution of the verification. End will be displayed. Press to the constant No. display.
DSPL
or ENTER to return
Inverter Capacity Display
The voltage class and maximum applicable motor capacity for which constants are stored in the Digital Operator are displayed.
Example: Displaying Voltage Class and Maximum Applicable Motor
Capacity for Inverter whose Constants are in EEPROM in
Operator
143
Explanation Operator Display
• Enable the setting for constants n001 to n179.
• Press
PRGM
DSPL
.
to lit
• Press ENTER to display the set value.
• Change the set value to 4 by pressing the or key.
• Press ENTER .
(May be a different constant No.)
(Lit)
(May be a different set value.)
(Flashes)
(Lit for one second.)
↓
(The constant No. is displayed.)
Inverter
Capacity Display
(vA) using the
Constant Copy
Function Selection (n176).
• Change the constant No. to n176 by pressing the or
key.
• Press ENTER the set value.
to display
• Change the set value to vA by pressing the or key.
(Lit)
(Lit)
(Lit) (For 20P7)*
• Press ENTER .
• Press DSPL
ENTER
.
or
(The constant No. is displayed.)
* The following figure shows the Inverter Capacity Display.
.
B
2
4
Voltage Class
Single-phase 200 V
Three-phase 200 V
Three-phase 400 V
0.1
0.2
0.4
0.7
1.5
2.2
3.0
3.7
5.5
7.5
Max. Applicable Motor Capacity
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
3.7 kW
5.5 kW
7.5 kW
144
Operator
Display
6. Programming Features
Software No. Display
The software number of the Inverter for which constants are stored in the Digital Operator is displayed.
Example: Displaying Software No. of Inverter for which Constants are
Stored in EEPROM in Digital Operator
Explanation Operator Display
• Enable the setting for constants n001 to n179.
• Execute Software No. Display
(Sno)* using the
Constant Copy
Function Selection (n176).
• Press DSPL
PRGM
.
• Press
ENTER the set value.
• Change the set value to 4 by pressing the or key.
• Press
ENTER
.
(May be a different constant No.)
(Lit)
(May be a different set value.)
(Flashes)
(Lit for one second.)
↓
(The constant No. is displayed.)
• Change the constant No. to n176 by pressing the or
key.
• Press
ENTER the set value.
• Change the set value to Sno by pressing the or key.
• Press
ENTER
.
(Lit)
(Lit)
(Lit)
(Software version: VSP010013)
DSPL ENTER
(The constant No. is displayed.)
* Displays the lower 4 digits of the software version.
Display List
Description Corrective Action
Lit: Constant copy function selection enabled.
-
Lit: READ selected.
Flashes: READ under execution.
Lit: Writing (COPY) selected.
Flashes: Writing (COPY) under execution.
Lit: VERIFY selected.
Flashes: VERIFY under execution.
-
-
-
145
Operator
Display
Description
Lit: Inverter capacity display selected.
Lit: Software No. display selected.
Corrective Action
-
-
Lit: READ, COPY (writing), VERIFY completed.
Flashes: Attempt made to execute READ while Constant Read Selection Prohibit (n177) is set to 0.
Flashes: The constant could not be read properly for READ operation. Or, a main circuit low voltage is detected during
READ operation.
Flashes: A checksum error occurred in the constant data stored in the Digital
Operator.
-
Confirm the necessity to execute READ, then set Constant Read Selection Prohibit (n177) to
1 to execute READ.
Confirm that the main circuit power supply voltage is correct, then re-execute READ.
The constants stored in the Digital Operator cannot be used.
Re-execute READ to store the constans in the
Digital Operator.
Check if the Inverters are the same product series.
Flashes: The password for the connected Inverter and that for the constant data stored in the Digital Operator disagree.
Example: Writing (COPY) from VS-606V7 to
VS mini J7
Flashes: No constant data stored in the Digital
Operator.
Execute READ.
Flashes: Attempt made to execute writing
(COPY) or VERIFY between different voltage classes or different control modes.
Check each voltage class and control mode.
Flashes: A main circuit low voltage was detected during writing (COPY) operation.
Lit: A checksum error occurred in the constant data stored in the Inverter.
Confirm that the main circuit power supply voltage is correct, then re-execute writing
(COPY).
Initialize the constants. If an error occurs again, replace the Inverter due to a failure of constant memory element (EEPROM) in the
Inverter.
Flashes: Attempt made to execute COPY or
VERIFY between different Inverters or different capacities.
Press
ENTER
to continue the execution of
COPY or VERIFY. Press
STOP
to interrupt the execution of COPY or VERIFY.
Flashes: A communications error occurred between the Inverter and the Digital Operator.
Check the connection between the Inverter and Digital Operator.
If a communications error occurs during the
READ operation or writing (COPY) operation, always re-execute the READ or COPY.
Note: While rEd, CPy, or vFy is flashing, key input on the Digital Operator is disabled. While rEd, CPy and vFy are not flashing, pressing DSPL or
ENTER
redisplays the constant No.
146
6. Programming Features
Unit Selection for Frequency Reference Setting/
Display
Constants and Monitor Displays for Which Selection of Unit
Function is Valid
Item Contents
Frequency reference constants
Frequency References 1 to 8 (Constants n024 to n031)
Jog Frequency Reference (Constant n032)
Frequency References 9 to 16 (Constants n120 to n127)
Monitor display Frequency Reference Display (FREF)
Output Frequency Display (FOUT)
Frequency Reference Display (U-01)
Output Frequency Display (U-02)
Setting/Displaying Unit Selection for Frequency Reference
(n035)
The frequency reference, output frequency, and the numeric data of frequency reference constants can be displayed in %, min -1 , or m/min according to the set value of constant n035.
Constant
No.
n035
Constant Name
Setting/Displaying Unit Selection for
Frequency Reference
Description
0: Units of 0.01 Hz (less than
100 Hz) 0.1 Hz (100 Hz and more)
1: Units of 0.1 %
2 to 39: Units of min
40 to 3999: Any unit
-1 (set the number of motor poles)
Factory
Setting
0
147
Setting
0
1
2 to 39
40 to
3999 n035 Settings
Description
• Setting unit: 0.01 Hz (less than 100 Hz), 0.1 Hz (100 Hz and more)
• Setting range
Min {Fmax (n011) × Frequency Reference Lower Limit (n034) to Fmax (n011) × Frequency Reference Upper Limit (n033),
400 Hz}
• Setting in units of 0.1%: 100.0%/Fmax (n011)
• Setting range
Min. {Frequency Reference Lower Limit (n034) to Frequency
Reference Upper Limit (n033), (400 Hz ÷ Fmax. (n011)) 100%}
Max. Upper Limit Value: Fmax. (n011) × Set value (%) ≤ 400 Hz
• Setting in units of 1 min -1
: min
-1
=120 × Frequency reference
(Hz) ÷ n035 (Set the number of motor poles in n035)
• Setting range
Min. {120 × (Fmax (n011) Frequency Reference Lower Limit
(n034) ÷ n035 to 120 × (Fmax (n011) × Frequency Reference
Upper Limit (n033)) ÷ n035, 400 Hz × 120 ÷ P, 9999 min -1
• Max. Upper Limit Value: N × P ÷ 120 ≤ 400 Hz
• Set the display value at 100% of frequency reference (set value of Fmax (n011)) at 1st to 4th digits of n035.
In the 4th digit of n035, set the position of decimal point.
In the 1st to 3rd digits of n035, set a 3-digit figure excluding the decimal point.
4th digit Position of decimal point
2
3
0
1
.
.
0.
Example: To display 20.0 at 100% of frequency reference, set n035 to 1200.
• Setting range
Min. {(Lower 3-digits of n035) × Frequency Reference Lower
Limit (n034) to (Lower 3-digits of n035) × Frequency Reference
Upper Limit (n033), 400 Hz × (Lower 3-digits of n035) ÷ Fmax
(n011), 999}
Max. Upper Limit Value: (Set value ÷ (Lower 3 digits of n035)) ×
Fmax(011) ≤ 400 Hz
148
6. Programming Features
Note: 1. The frequency reference constants and monitor display data for which this selection of the unit is valid are stored in the Inverter in units of Hz.
The units are converted as shown below:
Setting/Display Constant n035
Frequency reference constants
Data for monitor display
Each unit system
Display
Setting
Units of Hz
2. The upper limit for each unit is the value with decimal places below the significant digits truncated.
Example: Where the upper limit for the unit Hz is as follows for
60.00 Hz and n035 = 39:
120 × 60.00 Hz ÷ 39 = 184.6, thus 184 min -1 is displayed as the upper limit.
For displays other than for the upper limit, the decimal places below the significant digits are rounded off.
3. When verifying constants for the copy function, frequency reference constants (units of Hz) are used.
Selecting Processing for Frequency Reference
Loss (n064)
Use this setting to select the processing performed if the level of the frequency reference signal from the control circuit terminals suddenly drops.
n064
Setting
0
1*
Description
Processing for frequency reference loss disabled.
Processing for frequency reference loss enabled.
* Detected in REMOTE mode (drive mode) when analog reference (except potentiometer on Digital Operator) or pulse train reference is selected in the
Frequency Reference Selection (n004).
Processing Method When 1 is Selected
If the level of the frequency reference signal drops by 90 % within 400 ms, operation continues at 80 % of the signal level before the level drop.
149
Input/Output Open-phase Detection
Constant
No.
n166
Name
Input
Open-phase
Detection Level
Unit
1 %
Setting Range
0 to 100 % *1
400.0 V/100 %
(200 V Class)
800.0 V/100 %
(400 V Class)
0 to 255 s *2
Factory
Setting
0 % n167 n168
Input
Open-phase
Detection Time
Output
Open-phase
Detection Level
1 s
1 %
0 to 100 % *1
Inveter’s rated output current/100 %
0.0 to 2.0 s *2
0 s
0 % n169 Output
Open-phase
Detection Time
0.1 s 0.0 s
* 1. Not detected when set to 0 %.
* 2. Not detected when set to 0.0 s.
The recommended settings for input open-phase detection are n166=7 % and n167=10 s.
(Open-phase cannot be detected correctly depending on the load status.)
The recommended settings for output open-phase detection are n168=5 % and n169=0.2 s.
150
6. Programming Features
Undertorque Detection
An alarm signal can be output to a multi-function output terminal (MA,
MB, P1 or P2) when the load on the machine side suddenly becomes lighter (i.e., when an undertorque occurs).
To output an undertorque detection signal, set the output terminal funciton selection in n057, n058, or n059 to 8 (undertorque detected, NO contact) or 9 (undertorque detected, NC contact).
Motor Current n118
Multi-function Output
Terminal (Undertorque
Detection Signal)
MA, MB, P1, P2
ON ON
Time n119 n119
* Undertorque detection release width (hysteresis) is set at approx. 5 % of the
Inverter’s rated current.
Undertorque Detection Function Selection (n177)
Setting
0
1
2
Description
Undertorque detection not provided.
Detected during constant-speed running. Operation continues after detection.
Detected during constant-speed running. Operation stops.
3
4
Detected during running. Operation continues after detection.
Detected during running. Operation stops.
1. To detect undertorques during acceleration, set to 3 or 4.
2. To continue operation after undertorque detection, set to 1 or 3. During detection, the operation displays the “UL3” alarm (flashing).
3. To halt the Inverter by a fault at undertorque detection, set to 2 or 4.
At detection, the Operation displays the “UL3” fault (continuously lit).
151
152
Undertorque Detection Level (n118)
Sets the undertorque detection current level in units of 1 %. (Inverter rated current=100 %) When detected by torque is selected, motor rated torque becomes 100 %.
Factory setting=10 %
Undertorque Detection Time (n119)
If the time for which the motor current is less than the undertorque detection level (n118) is longer than the undertorque detection time
(n119), the undertorque detection function operates.
Factory setting=0.1 s
Overtorque/Undertorque Detection Function Selection 2
(n097)
When vector control mode is selected, it is possible to select whether overtorque/undertorque detection is performed by output current or output torque.
When V/f control mode is selected, the n097 setting becomes invalid, and overtorque/undertorque is detected by output current.
Setting
0
1
Description
Overtorque/undertorque detected by output torque.
Overtorque/undertorque detected by output current.
6. Programming Features
Using Inverter for Elevating Machines
CAUTION
If using an Inverter with an elevator, take safety measures on the elevator to prevent the elevator from dropping.
Failure to observe this caution may result in injury.
When using the VS-606V7 for elevating machines such as elevators and cranes, make sure that the brake holds and observe the following precautions for safe operation.
Brake ON/OFF Sequence
• For the holding brake’s ON/OFF sequence, use the following Inverter output signals according to the set control mode.
NOTE
Do not use “Running (Set value: 1)” for the holding brake’s
ON/OFF interlock signal.
Control
Mode
V/f
Control *1
(n002=0)
Brake ON/OFF Signals
Signal Name
Frequency detection 1
Constant *2
n058=4
Brake ON/OFF Level
Adjustment
Signal Name Constant
Frequency detection level n095=2.50 Hz to 4.00 Hz *3
* 1. For Vector control (n002=1), use the same brake ON/OFF sequence with the same signals as for V/f control.
* 2. Shows the setting when a multi-function photocoupler output terminal
(P1-PC) is used.
* 3. Usually, make the following settings for the frequency detection (n095):
For V/f control: Motor rated slip frequency +1 Hz
For Vector control: 2.5 Hz to 3.0 Hz
If the set value is too low, the motor torque is insufficient and the load may shift when the brake is applied. Be sure to set n095 to a value larger than that of the Minimum Output Frequency (n016) and larger than that of the braker releasing width shown in the following figure. If the set value is too large, the motor may not run smoothly when it starts running.
153
Output
Frequency n095
Releasing Width -2 Hz
Time
Frequency
Detection
Level 1
ON
OFF
• Sequence Circuit Configuration and Timing Chart Examples
Inverter VS-606V7
Fault Contacts MA
UP
DOWN
HIGH/LOW
S1
(Forward Run)
S2
(Reverse Run)
MB
MC
(Multi-step Speed Reference 2)
SC
Frequency
Detection1
P1
PC
Holding Brake
Auxiliary Relay Coil
+24V
Sequence
Circuit
BR
Energizes the brake when ON.
(30 VDC 1 A or less.)
For the AC sequence circuit, connect the signal between P1 and PC to the sequence circuit with a relay.
Design the sequence so that the holding brake contact is open when the sequence operation conditions are satisfied and the contact between P1 and PC is closed (ON).
Make sure that the holding brake contact is closed when the emergency stop signal or Inverter fault contact output signal is
ON.
• For V/f Control and Vector Control
S1-SC UP
OFF ON
Input
Output
S6-SC High Speed/
Low Speed
OFF ON
Output Frequency
0 n095
P1-PC
Frequency
Detection 1
(n058=4)
Holding Brake
Operation
CLOSE
ON
OPEN n026 n024 (Enabled when n004=1) n095
Time
DC Injection Brake
OFF
CLOSE
154
6. Programming Features
• For a variable speed operation by an analog signal, set the Frequency
Reference Selection (n004) to a value from 2 to 4.
Stall Prevention During Deceleration
If connecting a braking resistor to discharge regenerative energy, be sure to set the stall prevention during deceleration (n092) to 1.
NOTE
If the stall prevention during deceleration (n092) is set to the factory setting 0 (Enabled), the motor may not stop within the specified decelerating time.
The stall prevention during acceleration (n093) and the stall prevention level during running (n094) should be set to their factory settings to enable these functions.
Settings for V/f Pattern and Motor Constants
To set the control mode and the V/f pattern, refer to the instruction manual and the document “Motor Constant Settings for VS-606V7 Vector
Control (Document No. F-07-V7-01)”. If the Vector control method is used, also set the motor constants.
Momentary Power Loss Restart and Fault Restart
Do not use the momentary power loss restart and fault restart functions in applications for elevating machines. Make sure that n081=0 and n082=0. If these functions are used, the motor coasts to a stop with the brake contact open when a momentary power loss or fault occurs during operation, possibly resulting in serious accidents.
I/O Open-phase Protection and Overtorque Detection
The I/O open-phase protection is only available for 5.5 kW and 7.5 kW models.
To prevent the machine from falling when the motor is open-phase or similar situation, enable the I/O open-phase protection (n166 to n169) and the overtorque detection (n096 to n099). At the factory, these constants are set so that these functions are disabled.
Also, take safety measures such as protection against falls on the machine.
Carrier Frequency
Set the carrier frequency selection (n080) to 5 Hz or more (n080: 2 to 4) to secure the motor torque even if an overcurrent occurs (the current is limited).
155
156
External Baseblock Signal
If the external baseblock command (settings 12 and 13 of n050 to n056) is input while the motor is running, the motor will immediately coast to a stop. Do not input the external baseblock command while the motor is running unless necessary.
If using the external baseblock command for an emergency stop or to run start an interlock, make sure that the holding brake operates.
If the external beseblock command is input and immediately reset, the
Inverter does not output voltage during the minimum baseblock time, which is 0.5 to 0.7 seconds depending on the Inverter capacity. Do not use the external baseblock command in an application where the motor is frequency started and stopped.
Acceleration/Deceleration Time
If the delay time for the holding brake’s mechanical operation is not taken into consideration and the acceleration/deceleration time on the
Inverter side is set to a time that is too short, an overcurrent or wear on the brakes may occur at starting or the load will shift at stopping because the holding brake does not operate on time. If so, use the Scurve characteristic function or lengthen the acceleration/deceleration time to tune the timing for the holding brake.
Contactor on the Inverter’s Output-side
Do not install a contactor between the Inverter and the motor.
If a contactor must be installed because of local electrical codes or regulations or to operate motors with an Inverter, excluding emergencies, open or close the contactor only where the holding brake is fully closed and the Inverter is in baseblock status with the baseblock signal ON.
If the contactor is opened or closed while the Inverter is controlling the motor or DC injection braking, surge voltage or a current from the motor by full-voltage starting may cause an Inverter fault.
When a contactor is installed between the Inverter and the motor, enable the I/O open-phase protection (n166 to n169).
For more information on using Inverters exclusively for elevators or cranes, contact your Yaskawa representatives or the nearest Yaskawa sales office.
7. Maintenance and Inspection
7. Maintenance and Inspection
WARNING
• Never touch high-voltage terminals on the Inverter.
Failure to observe this warning may result in an electrical shock.
• Disconnect all power before performing maintenance or inspection, and then wait at least one minute after the power supply is disconnected. Confirm that all indicators are OFF before proceeding.
If the indicators are not OFF, the capacitors are still charged and can be dangerous.
• Do not perform withstand voltage test on any part of the VS-606V7.
The Inverter is an electronic device that uses semiconductors, and is thus vulnerable to high voltage.
• Only authorized personnel should be permitted to perform maintenance, inspection, or parts replacement.
(Remove all metal objects (watches, bracelets, etc.) before starting work.)
(Use tools which are insulated against electrical shock.)
Failure to observe these warnings may result in an electric shock.
CAUTION
• The control PCB employs CMOS ICs.
Do not touch the CMOS elements.
They are easily damaged by static electricity.
• Do not connect or disconnect wires, connectors, or the cooling fan while power is applied to the circuit.
Failure to observe this caution may result in injury.
157
Periodic Inspection
Periodically inspect the Inverter as described in the following table to prevent accidents and to ensure high performance with high reliability.
Location to
Check
Terminals, Inverter mounting screws, etc.
Heatsinks
Printed circuit boards
Check for Solution
Improper seating or loose connections in hardware.
Buildup of dust, dirt, and debris
Accumulation of conductive material or oil mist
Properly seat and tighten hardware.
Blow with dry compressed air at a pressure of 39.2
58.8 × 10 4
Blow with dry compressed air at a pressure of 39.2 × 10 4
58.8 × 10 4 Pa (4 to 6 kg/cm
to
2
If dust or oil cannot be removed, replace the Inverter.
).
Replace the Inverter.
× 10 4
Pa (4 to 6 kg/cm
to
2 ).
Power elements and smoothing capacitor
Cooling fan
Abnormal odor or discoloration
Abnormal noise or vibration
Cumulative operation time exceeding 20,000 hours
Replace the cooling fan.
158
7. Maintenance and Inspection
Part Replacement
Inverter’s maintenance periods are given below. Keep them as guidelines.
Part Replacement Guidelines
Part
Cooling fan
Smoothing capacitor
Breaker relays
Fuses
Aluminum capacitors on PCBs
Standard
Replacement
Period
2 to 3 years
5 years
-
10 years
5 years
Replacement Method
Replace with new part.
Replace with new part. (Determine need by inspection.)
Determine need by inspection.
Replace with new part.
Replace board. (Determine need by inspection.)
Note: Usage conditions are as follows:
• Ambient temperature: Yearly average of 30 °C
• Load factor: 80% max.
• Operating rate: 12 hours max. per day
159
160
Replacement of Cooling Fan
Inverters with Width of 68 mm, 140 mm, 170 mm, or 180 mm
1. Removal
1. Press the right and left catches on the fan cover in direction 1, and then pull them in direction
2 to remove the fan cover from the Inverter.
2. Pull the wiring in direction 3 from the fan cover rear face, and remove the protective tube and connector.
3. Open the left and right sides of the fan cover to remove the cooling fan from the cover.
2. Mounting
1. Mount the cooling fan on the fan cover. The arrow mark to indicate the airflow direction of the cooling fan must be on the opposite side to the cover.
2. Connect the connector and mount the protective tube firmly. Mount the connector joint section on the fan cover rear face.
3. Mount the fan cover on the
Inverter. Always mount the right and left catches on the fan cover on the heatsinks.
3
Airflow Direction
7. Maintenance and Inspection
Inverters with Width of 108 mm
1. Removal
1. Remove the front cover and terminal cover, and then remove the cooling fan connector (CN10).
2. Press the right and left catches on the fan cover in direction 1, and pull the fan cover in direction 2 to remove it from the
Inverter. Pull out the wiring from the cable lead-in hole at the bottom of the plastic case.
3. Open the right and left sides of the fan cover to remove the cover from the cooling fan.
2. Mounting
1. Mount the cooling fan on the fan cover. The arrow mark to indicate the airflow direction must be opposite to the cover.
2. Mount the fan cover on the
Inverter. Always mount the right and left catches on the fan cover on the heatsinks.
Thread in the wiring from the cable lead-in hole at the bottom of the plastic case to the inside of the Inverter.
3. Connect the wiring to the cooling fan connector (CN10) and mount the front cover and the terminal cover.
Cooling
Fan Wire
1
2
1
Airflow Direction
161
8. Fault Diagnosis
Protective and Diagnostic Functions
This section describes the alarm and fault displays, the fault conditions, and the corrective actions to be taken if the VS-606V7 malfunctions.
Inverter alarms are classified into alarm display and fault display.
Alarm display:When a minor fault occurs in the Inverter, the Digital
Operator flashes the display. In this case, the operation is continued, and restored automatically as soon as the cause is removed. Multi-function output can output the minor fault status to external devices.
Fault display: When a major fault occurs in the Inverter, the protective function operates, and the Digital Operator lights the display and shuts off the output to stop the Inverter. The fault can be output as a fault output to the external devices by multi-function output.
To reset the fault, turn ON the reset signal with the run command OFF or cycle the power after taking the corrective action.
* Selecting "always ON" mode at fan operation selection, the power must be cycled to release the alarm display.
Corrective Actions of Models with Blank Cover
1. Input fault reset or cycle the power supply OFF and ON.
2. When a fault cannot be corrected:
(1) Turn the power supply OFF and check the wiring and external circuit
(sequence).
(2) Turn the power supply OFF and replacce the blank cover with the
Digital Operator to display faults. The faults are displayes after turning the power ON.
162
Alarm Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
8. Fault Diagnosis
Corrective Actions of Models with Digital Operator
: ON : Flashing : OFF
Alarm Display
Alarm Displays and Meaning
Description Causes and
Corrective Actions
Flashing
Flashing
Flashing
Flashing
Detected as an alarm only. Fault contact output is not activated.
UV (Main circuit low voltage)
Main circuit DC voltage dropped below the low-voltage detection level while the
Inverter output is OFF.
200 V: Main circuit DC voltage drops below approx. 200 V (160 V for single-phase).
400 V: Main circuit DC voltage dropped below approx. 400 V.
(Control supply fault) Control power supply fault is detected while the Inverter output is
OFF.
Check the following:
• Power voltage
• Main circuit power supply connection.
• Terminal
• Monitor value
Confirm voltage (DC voltage) between terminals
"+1" and "-".
⇓
If there is no problem, the Inverter may be faulty.
OV (Main circuit overvoltage)
Main circuit DC voltage exceeded the overvoltage detection level while the Inverter output is OFF.
Detection level:
200 V: approx 410 V or more
400 V: approx 820 V or more
Check the following:
• Power
• Monitor
Confirm voltage (DC voltage) between terminals
"+1" and "-".
⇓
If there is no problem, the Inverter may be faulty.
OH (Heatsink overheat)
Intake air temperature increased while the Inverter output is OFF.
Check the following:
• Intake air temperature.
• There is no thermal source around the
Inverter or that oil adhering to the fan has deteriorated the cooling capability.
• Fan is not clogged.
• Any foreign matters such as water has entered in the Inverter and adhered.
CAL (MEMOBUS communications waiting)
Correct data has not been received from the PLC when the constants n003 (Run
Command Selection) is 2 or n004 (Frequency Reference
Selection) is 6, and power is turned ON.
Check the following:
• Communications and transmission signals.
• PLC is not faulty.
• Transmission cable is connected properly.
• Wiring is made properly.
• Any loose terminal screws do not result in improper contact.
163
Alarm Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
(Flashing)
Flashing
Flashing
Description Causes and
Corrective Actions
Detected as an alarm only. Fault contact output is not activated.
OP (Constant setting error when constants are set through MEMO-
BUS communications)
OP1: Two or more values are set for multi-function input selection.
(constants n050 to n056)
OP2: Relationship among V/f constants is not correct. (constants n011, n013, n014, n016)
OP3: Setting value of motor rated current exceeds
150% of Inverter Rated
Current. (constant n036)
OP4: Upper/lower limit of frequency reference is reversed. (constants n033, n034)
OP5: Relationship among jump frequency 1, 2 and 3 is not correct.
(constants n083 to n085)
OP9: The setting of the Inverter capacity does not coincide with the
Inverter. (Contact your
Yaskawa representative.)
Check the setting values.
OL3 (Overtorque detection)
Motor current exceeded the preset value in constant n098.
Overtorque detection level was exceeded because of increased leak current due to excessively long wiring.
• Reduce the load, and increase the acceleration/ deceleration time.
• Refer to the paragraph of
Reducing Motor Noise or Leakage Current Using
Carrier Frequency Selec-
tion (n080) on page 81.
• Check the wiring
(increase of current caused by rare shortcircuit, etc.).
SER (Sequence error)
Inverter received LOCAL/RE-
MOTE command or communications/control circuit terminal changing signals from the multi-function terminal while the Inverter output is ON.
Check the following:
• NO/NC contact selection
(constant).
• Wiring the PLC.
made
• Signal is not input from
164
8. Fault Diagnosis
Alarm Display
Digital
Operator
RUN (Green)
ALARM (Red)
Flashing
Flashing
Flashing
Flashing
Flashing or
Inverter
Status
Description Causes and
Corrective Actions
Detected as an alarm only. Fault contact output is not activated.
UL3 (Undertorque detection)
When V/f mode is selected:
The Inverter’s output current was less than the undertorque detection level (n118).
When vector mode is selected: The output current or output torque was less than the detection level (n097 or n118).
Operation when undertorque is detected will be determined by the setting in n117.
• Check the setting in n118.
• Check the operating conditions, and remove the cause.
BB (External baseblock)
BASEBLOCK command at multi-function terminal is ON and the Inverter output is
OFF (motor coasting). Condition is cleared when input command is removed.
Check the following:
• NO/NC contact selection
(constant).
• Wiring is made properly.
• Signal is not input from the PLC.
EF (Simultaneous FWD/
REV RUN commands)
When FWD and REV RUN commands are simultaneously input for over 500 ms, the
Inverter stops according to constant n005.
Check the following:
• NO/NC contact selection
(constant).
• Wiring is made properly.
• Signal is not input from the PLC.
STP (Operator function stop)
was pressed during running via a control circuit terminal FWD/REV command, or by a RUN command from communications. The Inverter stops according to constant n005.
STP (Emergency stop)
Inverter received emergency stop alarm signal. Inverter stops according to constant n005.
FAN (Cooling fan fault)
Cooling fan is locked.
OFF command of control circuit terminals.
Check the following:
• NO/NC contact selection
(constant).
• Wiring is made properly.
• Signal is not input from the PLC.
Check the following:
• Cooling
• Cooling fan connection
• Adhesion of foreign matters does not interrupt the rotation.
• Fan is mounted correctly.
• Relay connector is connected properly after replacement of the fan.
165
Alarm Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Flashing
Flashing
Flashing
Flashing or
Description Causes and
Corrective Actions
Detected as an alarm only. Fault contact output is not activated.
CE (MEMOBUS) communications fault
Check the following:
• Communicaiton or communication signals.
• PLC is not faulty.
• Transmission cable is connected properly.
• Any loose terminal screws do not result in improper contact.
• Wiring
Check the mechanical system and correct the cause, or increase the value of n137.
FBL (PID feedback loss detection)
PID feedback value dropped below the detection level
(n137). When PID feedback loss is detected, the Inverter operates according to the n136 setting.
Option card communications fault.
fault occurred the mode where the communications option card was used and a run command or frequency reference was input from the PLC.
• Communication has occured in a mode that
RUN command and frequency reference are set from the communication option card.
Check the following:
• Communications or communications signals.
• PLC is not faulty.
• Transmission cable is connected properly.
• Any loose terminal screws do not result in improper contact.
• Wiring made
• Communication card is inserted correctly.
OH3 (Inverter overheat alarm)
The Inverter overheat alarm
(OH3) was input from a multifunction input terminal (S1 and S7).
the input terminal’s Inverter overheat alert input.
• Check that the wiring is made properly.
• Check that a signal is not input from the PLC.
166
8. Fault Diagnosis
Fault Display
Fault Displays and Meanings
Fault Display Inverter
Status
Description Causes and Corrective
Actions
Digital
Operator
RUN (Green)
ALARM (Red)
Protective
Operation
Output is turned OFF and motor coasts to a stop.
OC (Overcurrent)
Inverter output current momentarily exceeded approx.
250% of rated current.
Operation is restored, if no fault is found, after confirming the following:
• Short circuit or grounding at Inverter output side
• Excessive load GD 2 rapid
Acceleration/Deceleration
Time (constants n019 to n022)
• Special motor used
• Starting motor during coasting
• Motor of a capacity greater than the Inverter rating has been started.
contactor opened/closed at the
Inverter output side
• Leak current increased because of excessive long wiring
GF (Grounding) *
Grounding current exceeded approx. 50% of Inverter rated output current at the Inverter output side.
SC (Load shortcircuit) *
Inverter output or load shortcircuited.
Inverter output grounded.
⇓
Check the cause, and restore the operation.
Inverter output shortcircuited or grounded.
⇓
Check the cause, and restore the operation.
OV (Main circuit overvoltage)
Main circuit DC voltage level exceeded the overvoltage detection level while the Inverter was running.
Detection level (DC voltage:
Voltage between terminals
"+1" and "-")
200 V: Approx. 410 V or more
400 V: Approx. 820 V or more
1. Regenerative energy is large.
• The setting of deceleration time is too short.
• Negative load (e.g., elevator) is excessive at lowering.
• Confirm that the load does not have any problem.
2. Input voltage is erroneous.
Confirm that DC voltage exceeding the left value is not input.
* Indicates that an Inverter of 5.5 kW and 7.5 kW (200-V and 400-V classes) is attached.
167
Fault Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Description Causes and Corrective
Actions
Protective
Operation
Output is turned OFF and motor coasts to a stop.
UV1 (Main circuit low voltage)
Main circuit DC voltage dropped below the low-voltage detection level while the
Inverter output is ON.
200 V: Stops at main circuit
DC voltage below approx. 200 V (160 V for single-phase)
400 V: Stops at main circuit
DC voltage below approx. 400 V.
Check the following:
• Power voltage
• Main circuit power supply connections
• Terminal screws: Loose?
value
Confirm voltage (DC voltage) between terminals
"+1" and "-".
⇓
If there is no problem, the Inverter may be faulty.
UV2 (Control power supply fault)
Inverter detected voltage fault of control power supply during running.
Replace the Inverter.
OH (Heatsink overheat)
Temperature increased because of Inverter overload operation or intake air temperature rise.
load
• Improper V/f pattern setting
• Insufficient acceleration time if the fault occurs during acceleration
• Intake temperature exceeding 50 °C fan
• Cooling deteriorates its cooling capability or stops.
• Fin clogged.
• There is a thermal source around the Inverter
⇓
Check the following: size
• V/f pattern setting (constants n011 to n017)
• Intake temperature.
• Cooling fan is turning while the Inverter is running.
foreign adhere to the fan and that they do not interrupt the rotation.
• Fan is mounted properly.
• There is not a thermal source around the
Inverter.
RH (Externally-mounting-type braking resistor overheat) *
Protection of externallymounting type braking resistor operated.
• Insufficient time motor ative energy
• Increase
⇓ deceleration time
• Reduce
168
8. Fault Diagnosis
Fault Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Description Causes and Corrective
Actions
Protective
Operation
Output is turned OFF and motor coasts to a stop.
RR (Built-in braking transistor fault) *
Built-in braking transistor malfunctioned.
Replace the Inverter.
OL1 (Motor overload)
Motor overload protection operated by built-in electronic thermal overload relay.
• Check the load size or V/f pattern setting (constants n011 to n017).
• Set the motor rated current shown on the nameplate in constant n036.
• Check that the settings of motor protection (whether motor cooling method is self-cooled or fan-cooled) and motor protection time constant are made correctly.
• Check the load size, V/f set value, operation pattern, etc. to confirm that the load is not excessive under actual operation.
• Recheck the item of motor protection and set the constants again if necessary.
to
Motor Noise or Leakage
Current Using Carrier
Frequency Selection
(n080) on page 81.
• Check wiring
(increase of current caused by rare shortcircuit, etc.).
* Indicates that an Inverter of 5.5 kW and 7.5 kW (200-V and 400-V classes) is attached.
169
Fault Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Description Causes and Corrective
Actions
Protective
Operation
Output is turned OFF and motor coasts to a stop.
OL2 (Inverter overload)
Inverter overload protection operated by built-in electronic thermal overload relay.
OL3 (Overtorque detection)
V/f mode: Inverter output current exceeded the preset value in constant n098.
Vector mode: Motor output current or torque exceeded the preset value in constants n097 and n098.
When overtorque is detected, Inverter performs operation according to the preset setting of constant n096.
• Check the load size or V/f pattern setting (constants n011 to n017).
• Check the Inverter capacity.
• Check the load size, V/f set value, operation pattern, etc. to confirm that the load is not excessive under actual operation.
to
Motor Noise or Leakage
Current Using Carrier
Frequency Selection
(n080) on page 81.
• Check wiring
(increase of current caused by rare shortcircuit, etc.).
the machine and correct the cause of the fault, or increase the value of constant n098 up to the highest value allowed for the machine.
• Check the load size, V/f set value, operation pattern, etc. to confirm that the load is not excessive under actual operation.
to
Motor Noise or Leakage
Current Using Carrier
Frequency Selection
(n080) on page 81.
• Check wiring
(increase of current caused by rare shortcircuit, etc.).
170
8. Fault Diagnosis
Fault Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Description Causes and Corrective
Actions
Protective
Operation
Output is turned OFF and motor coasts to a stop.
PF (Main circuit voltage fault)
The main circuit’s DC voltage oscillated in an irregular way when not in regenerative operation.
• Open phase of input supply
• Momentary
• Excessive power input supply voltage
• Unbalanced line voltage
⇓
Check the following:
• Main circuit power supply connections
Loose?
supply screws:
LF (Output open phase)
An open phase occurred in
Inverter output.
• Disconnection in output cable
• Disconnection in motor windings
• Loose output terminal screws
⇓
Check the following:
• Disconnection in output wirings impedance screws:
Loose?
UL3 (Undertorque detection)
When V/f mode is selected:
The Inverter’s output current was less than the Undertorque Detection Level
(n118).
When vector mode is selected:
The output current or output torque was less than the detection level (n097 to n118).
Operation when undertorque is detected will be determined by the setting in n117.
• Check the setting in n118.
• Check the operating conditions, and remove the cause.
171
Fault Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Description Causes and Corrective
Actions
Protective
Operation
Output is turned OFF and motor coasts to a stop.
EF (External fault)
Inverter receives an external fault input from control circuit terminal.
EF0: External fault reference through MEMOBUS communications
EF1: External fault input command from control circuit terminal S1
EF2: External fault input command from control circuit terminal S2
EF3: External fault input command from control circuit terminal S3
EF4: External fault input command from control circuit terminal S4
EF5: External fault input command from control circuit terminal S5 *
EF6: External fault input command from control circuit terminal S6 *
EF7: External fault input command from control circuit terminal S7
Check the following:
• NO/NC contact selection
(constant).
• Wiring is made properly.
• Signal is not input from the PLC.
CPF-00
Inverter cannot communicate with the Digital Operator for 5 s or more when power is turned ON.
Cycle power after confirming that the Digital Operator is securely mounted. If the fault remains, replace the Digital
Operator or Inverter.
CPF-01
Transmission fault occurred for 5 s or more when transmission starts with the Digital
Operator.
CPF-04
EEPROM fault of Inverter control circuit was detected.
Cycle power after confirming that the Digital Operator is securely mounted. If the fault remains, replace the Digital
Operator or Inverter.
all and initialize the constants. (Refer to page 50.)
• Cycle power. If the fault remains, replace the
Inverter.
CPF-05
AD converter fault was detected.
Cycle power.
If the fault remains, replace the Inverter.
172
8. Fault Diagnosis
Fault Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Description Causes and Corrective
Actions
Protective
Operation
Output is turned OFF and motor coasts to a stop.
CPF-06
• Option fault non-corresponding option card is connected.
CPF-07
Operator control circuit (EE-
PROM or AD converter) fault
CPF-11
Combination error
Communication option card self diagnostic error
Communication option card model code error
• Cycle power to the
Inverter after checking the connection of the
Communication option card.
• Verify Software Version
No. (n179).
• Check the applicable
Inverter software number that is described in the instruction manual of the communications option card.
Cycle power after checking the Digital Operator is securely mounted. If the fault remains, replace the Digital
Operator or Inverter.
Control circuit is not combined with correct software.
(Contact your Yaskawa representative.) card
• Replace the option card.
• Confirm that any foreign matters adhere to the communication option card.
Communication option card DPRAM error
OPR (Operator connecting fault)
Cycle power. If the fault remains, replace the Inverter.
CE (MEMOBUS communications fault)
Check the following:
• Communications devices or communications signals.
• PLC is not faulty.
• Transmission cable is connected properly.
• Any loose terminal screws do not result in improper contact.
• Wiring is made properly.
173
Fault Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Description Causes and Corrective
Actions
(OFF) or
Stops according to constant.
Protective
Operation
Output is turned OFF and motor coasts to a stop.
STP (Emergency stop)
The Inverter stopped according to constant n005 after receiving the emergency stop fault signal.
Check the following:
• NO/NC tion (constant).
• Wiring is made properly.
• Signal is not input from the PLC.
FBL (PID feedback loss detection)
PID feedback value dropped below the detection level.
When PID feedback loss is detected, the Inverter operates according to the n136 setting.
Option card communications fault
A communication error occurred in the mode where the communication option card was used and a run command or frequency reference was input from the PLC.
Check the mechanical system and correct the cause, or increase the value of n137.
Check the following:
• Communications devices or communications signals.
• PLC is not faulty.
• Transmission cable is connected properly.
• Wiring is made properly.
• Any loose terminal screws do not result in improper contact.
• Communication rectly.
option card is not inserted corpower supply voltage
• Control power supply fault
Check the following:
• Power voltage
• Main circuit power supply connections
• Terminal sequence.
• Replace
* To display or clear the fault history, refer to page 50.
174
8. Fault Diagnosis
Troubleshooting
Trouble
The motor does not operate when an external operation signal is input.
The motor stops. The torque is not output.
Cause
The operation method selection is wrong.
The RUN command (n003) is not set to Control Circuit Terminal.
A 3-wire sequence is in effect.
The Multi-function Input Selection
(n052) is set to 3-wire sequence, and the S2 control terminal is not closed.
The frequency reference is too low.
The input frequency reference is lower than the setting for the Min.Output
Frequency (n016).
Local mode is in effect.
Corrective Actions
Set the RUN command (n003) to
Control Circuit Terminal.
To use a 3-wire sequence, make the wiring so that the S2 control terminal is closed. To use a 2-wire sequence, set the Multi-function Input (n052) to a value other than 3-wire sequence.
Input a frequency reference greater than the Min. Output Frequency
(n016).
Set the LO/RE selection of the Digital
Operator to RE.
For analog input, make sure that the
Frequency Reference (n004) and SW2 settings are correct.
The V-I SW (SW2) setting is wrong.
Example: The reference 4-20 mA is input, but the SW2 is set to “V.”
The setting of NPN/PNP switch
(SW1) is not correct.
The stall prevention level during acceleration is too low.
Because the Stall Prevention Level during Acceleration (n093) is set too low, the output current reaches the set level, the output frequency is stopped, and the acceleration time is lengthened.
The stall prevention level during running is too low.
Because the Stall Prevention Level during Running (n094) is set too low, the output current reaches the set level, and the speed drops.
The load is too heavy.
If the load is too heavy, stall prevention is activated, the output frequency is stopped, and the acceleration time is lengthened.
When the maximum frequency was changed, the maximum voltage frequency was also changed.
Set SW1 correctly.
Check if the Stall Prevention Level during Acceleration (n093) is set to an appropriate value.
Check if the Stall Prevention Level during Running (n094) is set to an appropriate value.
• Lengthen the set acceleration time
(n019).
To increase the speed of a generalpurpose motor, only change the maximum frequency.
The V/f set value is too low.
Set the V/f (n011 to n017) according to the load characteristics.
175
Trouble
The motor speed is unstable. The motor speed fluctuates when operating with a light load.
The LED of the Digital
Operator is unlit.
Cause
The stall prevention level during running is too low.
Because the Stall Prevention Level during Running (n094) is too low, the output current reaches the set level and the speed drops.
The load is too heavy.
If the load is too heavy, stall prevention is activated, the output frequency is stopped, and the acceleration time is lengthened.
The carrier frequency is too high.
If operating the motor with a light load, a high carrier frequency may cause the motor speed to fluctuate.
The V/f set value is too high for a low speed operation.
Because the set value for the V/f is too high, over-excitation occurs at low speeds.
The maximum frequency and base frequency were incorrectly adjusted.
Example: To operate a 60 Hz motor at
40 Hz or less, the maximum frequency and base frequency are set to 40 Hz.
The Inverter is used for an operation at 1.5 Hz or less.
Corrective Actions
Check if the Stall Prevention Level during Running (n094) is set to an appropriate value.
Reduce the load.
Decrease the carrier frequency (n080).
Set the V/f (n011 to n017) according to the load characteristics.
Set the maximum frequency and the base frequency according to the motor specifications.
The analog reference input is unstable and has noise interference.
The power is not being supplied.
The breaker or other component on the power input side is not turned ON, and the power is not being supplied.
Because the Digital Operator is not correctly mounted, the display does not appear.
Short-circuit bar for terminals +1 and +2 is not connected.
POWER charge indicator lamp lights but the Digital Operator does not give any display after the power supply is turned ON.
Do not use the V7 Inverter for an operation that runs at 1.5 Hz or less.
For an operation at 1.5 Hz or less, use a different Inverter model.
Increase the set value for the filter time constant.
Check if the power is being supplied.
Mount the Digiral Operator correctly.
Confirm that the short-circuit bar is connected properly.
Since main circuit fuse is blown, replace the Inverter.
176
9. Specifications
9. Specifications
Standard Specifications (200 V Class)
Voltage Class 200 V single-/3-phase
Model
CIMR-
V7 ∗T
3-phase
Single-phase
20P1
B0P1
20P2
B0P2
20P4
B0P4
20P7
B0P7
21P5
B1P5
22P2
B2P2
23P7
B3P7
25P5
-
Max. Applicable Motor Output kW
*1
Inverter Capacity (kVA)
0.1
0.2
0.4
0.75
1.5
2.2
3.7
Rated Output Current
(A)
0.3
0.8
0.6
1.6
1.1
3
1.9
5
3.0
8
4.2
11
6.7
17.5
Max. Output Voltage (V) 3-phase, 200 to 230 V (proportional to input voltage)
Single-phase, 200 to 240 V (proportional to input voltage)
Max. Output Frequency
(Hz)
400 Hz (Programmable)
5.5
9.5
25
27P5
-
7.5
13
33
Rated Input Voltage and
Frequency
Allowable Voltage
Fluctuation
Allowable Frequency
Fluctuation
3-phase, 200 to 230 V, 50/60 Hz
Single-phase, 200 to 240 V, 50/60 Hz
−15 to +10%
±5%
177
Model
CIMR-
V7 ∗T
Voltage Class
3-phase
Single-phase
Control Method
Frequency Control
Range
Frequency Accuracy
(Temperature Change)
Frequency Setting
Resolution
200 V single-/3-phase
20P1 20P2 20P4 20P7 21P5 22P2 23P7 25P5 27P5
B0P1 B0P2 B0P4 B0P7 B1P5 B2P2 B3P7 -
Sine wave PWM (V/f control/vector control selectable)
0.1 to 400 Hz
Digital reference:
Analog reference:
Digital reference:
Analog reference: 1/1000 of max. output frequency
0.01 Hz
±0.01% (−10 to 50°C)
±0.5% (25 ±10°C)
0.01 Hz (less than 100 Hz)/0.1 Hz (100 Hz or more)
Output Frequency
Resolution
Overload Capacity
Frequency Reference
Signal
Acceleration/
Deceleration Time
Braking Torque
V/f Characteristics
150% rated output current for one minute
0 to 10 VDC (20 k Ω), 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω) pulse train input, frequency setting potentiometer (Selectable)
0.00 to 6000 s
(Acceleration/deceleration time are independently programmed.)
Short-term average deceleration torque *2
0.1, 0.25 kW: 150% or more
0.4, 0.75 kW: 100% or more
1.5 kW: 50% or more
2.2 kW or more: 20% or more
Continuous regenerative torque: Approx. 20% (150% with optional braking resistor, braking transistor built-in)
Possible to program any V/f pattern
178
9. Specifications
Model
CIMR-
V7 ∗T
Voltage Class
3-phase
Single-phase
Motor Overload
Protection
20P1
B0P1
20P2
B0P2
20P4
B0P4
200 V single-/3-phase
20P7
B0P7
Electronic thermal overload relay
21P5
B1P5
22P2
B2P2
23P7
B3P7
25P5
-
27P5
-
Instantaneous
Overcurrent
Overload
Motor coasts to a stop at approx. 250% or more of Inverter rated current
Motor coasts to a stop after 1 minute at 150% of Inverter rated output current
Motor coasts to a stop if DC bus voltage exceed 410 V Overvoltage
Undervoltage Stops when DC bus voltage is approx. 200 V or less (approx. 160 V or less for single-phase series).
Momentary Power Loss Following items are selectable: Not provided (stops if power loss is 15 ms or longer), continuous operation if power loss is approx. 0.5 s or shorter, continuous operation.
Heatsink Overheat
Stall Prevention Level
Cooling Fan Fault
Protected by electronic circuit.
Can be set individual level during acceleration/constant-speed operation, provided/not provided available during deceleration.
Protected by electronic circuit (fan lock detection).
Ground Fault
*4
Power Charge
Indication
Multi-function
Input
Multi-function
Output *5
Protected by electronic circuit (overcurrent level).
*3
ON until the DC bus voltage becomes 50 V or less. RUN indicator stays
ON or Digital Operator indicator stays ON.
Seven of the following input signals are selectable: Forward run command, reverse run command, forward/reverse run (3-wire sequence), fault reset, external fault, multi-step speed operation, JOG command, acceleration/deceleration time select, external baseblock, SPEED
SEARCH command, ACCELERATION/DECELERATION HOLD command, LOCAL/REMOTE selection, communication/control circuit terminal selection, emergency stop fault, emergency stop alarm, UP/DOWN command, self-test, PID control cancel, PID integral reset/hold, Inverter overheat alarm
Following output signals are selectable (1 NO/NC contact output, 2 photocoupler outputs):
Fault, running, zero speed, frequency agree, frequency detection, overtorque detection, undervoltage detection, minor error, baseblock, operating mode, Inverter run ready, fault retry, UV, speed search, data output through communications, PID feedback loss detection, frequency reference loss, Inverter overheat alarm
Standard Functions Voltage vector control, full-range automatic torque boost, slip compensation, DC injection braking current/time at startup/stop, frequency reference bias/gain, MEMOBUS communications (RS-485/422, max. 19.2 k bps), PID control, energy-saving control, constant copy, frequency reference with built-in potentiometer, unit selection for frequency reference setting/display, multi-function analog input
179
Model
CIMR-
V7 ∗T
Voltage Class
3-phase
Single-phase
Status
Indicators
Digital Operator
(JVOP-140)
200 V single-/3-phase
20P1 20P2 20P4 20P7 21P5 22P2 23P7 25P5 27P5
B0P1 B0P2 B0P4 B0P7 B1P5 B2P2 B3P7 -
RUN and ALARM provided as standard indicators
Provided for monitor frequency reference, output frequency, output current
Terminals Main circuit: screw terminals
Control circuit: plug-in screw terminal
100 m or less Wiring Distance between Inverter and
Motor
Enclosure
Cooling Method
Ambient Temperature
Humidity
Storage Temperature
*8
Location
Open chassis (IP20, IP00)
*6
or enclosed wall-mounted NEMA 1 (TYPE
1)
*7
Cooling fan is provided for the following models:
200 V, 0.75 kW or larger Inverters (3-phase)
200 V, 1.5 kW or larger Inverters (single-phase)
Other models are self-cooling.
Open chassis (IP20, IP00): −10 to 50°C
Enclosed wall-mounted NEMA 1 (TYPE 1): −10 to 40°C (not frozen)
95% or less (non-condensing)
−20 to 60°C
Indoor (free from corrosive gases or dust)
Elevation 1,000 m or less
Vibration
Up to 9.8 m/s
2
(1G) at 10 to less than 20 Hz, up to 2 m/s 2 (0.2G) at 20 to 50 Hz
* 1. Based on a standard 4-pole motor for max. applicable motor output.
* 2. Shows deceleration torque for uncoupled motor decelerating from 60 Hz with the shortest possible deceleration time.
* 3. The operation level becomes approx. 50% of Inverter rated output current in case of Inverters of 5.5 kW or 7.5 kW.
* 4. Since grounding in the motor winding is assumed, low-resistance grounding in the motor cable or terminal block cannot be protected.
* 5. Minimum permissible load: 5 VDC, 10 mA (as reference value)
* 6. 0P1 to 3P7 are of IP20. Be sure to remove the top and bottom covers when Inverter 5P5 or 7P5 of open chassis mounting type is used.
* 7. NEMA 1 of 0P1 to 3P7 is optional, while NEMA 1 of 5P5 and 7P5 is provided as standard.
* 8. Temperature during shipping (for short period).
180
9. Specifications
Standard Specifications (400 V Class)
Voltage Class 400 V 3-phase
Model
CIMR-
V7 ∗T
3-phase
Single-phase
40P2
-
40P4
-
40P7
-
41P5
-
42P2
-
43P0
-
43P7
-
Max. Applicable Motor Output kW
*1
Inverter Capacity (kVA)
0.2
0.4
0.75
1.5
2.2
3.0
3.7
Rated Output Current
(A)
0.9
1.2
1.4
1.8
2.6
3.4
3.7
4.8
4.2
5.5
5.5
7.2
Max. Output Voltage (V) 3-phase, 380 to 460 V (proportional to input voltage)
Max. Output Frequency
(Hz)
400 Hz (Programmable)
6.6
8.6
45P5
-
5.5
11
14.8
47P5
-
7.5
14
18
Rated Input Voltage and
Frequency
Allowable Voltage Fluctuation
Allowable Frequency
Fluctuation
Control Method
Frequency Control
Range
Frequency Accuracy
(Temperature Change)
Frequency Setting Resolution
Output Frequency Resolution
Overload Capacity
Frequency Reference
Signal
Acceleration/Deceleration Time
Braking Torque
V/f Characteristics
3-phase, 380 to 460 V, 50/60 Hz
−15 to +10%
±5%
Sine wave PWM (V/f control/vector control selectable)
0.1 to 400 Hz
Digital reference: ±0.01%, −10 to 50°C
Analog reference: ±0.5%, 25±10°C
Digital reference:
0.01 Hz (less than 100 Hz)/0.1 Hz (100 Hz or more)
Analog reference: 1/1000 of max. output frequency
0.01 Hz
150% rated output current for one minute
0 to 10 VDC (20 k Ω), 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω) pulse train input, frequency setting potentiometer (Selectable)
0.00 to 6000 s
(Acceleration/deceleration time are independently programmed.)
Short-term average deceleration torque
0.1, 0.2 kW: 150% or more
0.4, 0.75 kW: 100% or more
1.5 kW: 50% or more
*2
2.2 kW or more: 20% or more
Continuous regenerative torque: Approx. 20% (150% with optional braking resistor, braking transistor built-in)
Possible to program any V/f pattern
181
Model
CIMR-
V7 ∗T
Voltage Class
3-phase
Single-phase
Motor Overload Protection
Instantaneous
Overcurrent
Overload
400 V 3-phase
40P2 40P4 40P7 41P5 42P2 43P0 43P7 45P5 47P5
-
Electronic thermal overload relay
Motor coasts to a stop at approx. 250% or more of Inverter rated current
Overvoltage
Undervoltage
Momentary Power Loss
Heatsink Overheat
Stall Prevention Level
Cooling Fan Fault
Ground Fault
*4
Power Charge Indication
Multi-function
Input
Multi-function
Output
*5
Motor coasts to a stop after 1 minute at 150% of Inverter rated output current
Motor coasts to a stop if DC bus voltage exceed 820 V
Stops when DC bus voltage is approx. 400 V or less
Following items are selectable: Not provided (stops if power loss is 15 ms or longer), continuous operation if power loss is approx. 0.5 s or shorter, continuous operation.
Protected by electronic circuit.
Can be set to individual levels during acceleration/constant-speed operation, provided/not provided available during deceleration.
Protected by electronic circuit (fan lock detection).
Protected by electronic circuit (overcurrent level).
*3
ON until the DC bus voltage becomes 50 V or less. Charge LED is provided.
Seven of the following input signals are selectable: Forward run command, reverse run command, forward/reverse run (3-wire sequence), fault reset, external fault, multi-step speed operation, JOG command, acceleration/deceleration time select, external baseblock, SPEED
SEARCH command, ACCELERATION/DECELERATION HOLD command, LOCAL/REMOTE selection, communication/control circuit terminal selection, emergency stop fault, emergency stop alarm, UP/DOWN command, self-test, PID control cancel, PID integral reset/hold, Inverter overheat alarm
Following output signals are selectable (1 NO/NC contact output, 2 photocoupler outputs):
Fault, running, zero speed, frequency agree, frequency detection, overtorque detection, undertorque detection, minor error, baseblock, operating mode, Inverter run ready, fault retry, UV, speed search, data output through communications, PID feedback loss detection, frequency reference loss, Inverter overheat alarm
Standard Functions Voltage vector control, full-range automatic torque boost, slip compensation, DC injection braking current/time at startup/stop, frequency reference bias/gain, MEMOBUS communications (RS-485/422, max. 19.2 kbps), PID control, energy-saving control, constant copy, frequency reference with built-in potentiometer, unit selection for frequency reference setting/display, multi-function analog input
182
9. Specifications
Model
CIMR-
V7 ∗T
Voltage Class
3-phase
Single-phase
Status Indicators
40P2
-
40P4
-
40P7
-
41P5
-
400 V 3-phase
42P2
-
43P0
-
RUN and ALARM provided as standard indicators
43P7
-
45P5
-
47P5
-
Digital Operator
(JVOP-140)
Provided for monitor frequency reference, output frequency, output current
Terminals Main circuit: screw terminals
Control circuit: plug-in screw terminal
100 m or less Wiring Distance between Inverter and
Motor
Enclosure
Cooling Method
Ambient Temperature
Humidity
Open chassis (IP20, IP00)
*6
, or enclosed wall-mounted NEMA 1 (TYPE
1)
*7
Cooling fan is provided for the following models:
400 V, 1.5 kW or larger Inverters (3-phase)
Other models are self-cooling.
Open chassis (IP20, IP00): −10 to 50°C
Enclosed wall-mounted NEMA 1 (TYPE 1): −10 to 40°C
(not frozen)
95% or less (non-condensing)
−20 to 60°C
Storage Temperature
*8
Location
Elevation
Indoor (free from corrosive gases or dust)
1,000 m or less
Vibration
Up to 9.8 m/s 2 up to 2 m/s
2
(1G) at 10 to less than 20 Hz,
(0.2G) at 20 to 50 Hz
* 1. Based on a standard 4-pole motor for max. applicable motor output.
* 2. Shows deceleration torque for uncoupled motor decelerating from 60 Hz with the shortest possible deceleration time.
* 3. The operation level becomes approx. 50% of Inverter rated output current in case of Inverters of 5.5 kW or 7.5 kW
* 4. Since grounding in the motor winding is assumed, low-resistance grounding in the motor cable or terminal block cannot be protected.
* 5. Minimum permissible load: 5 VDC, 10 mA (as reference value)
* 6. 0P1 to 3P7 are of IP20. Be sure to remove the top and bottom covers when Inverter 5P5 or 7P5 of open chassis mounting type is used.
* 7. NEMA 1 of 0P1 to 3P7 is optional, while NEMA 1 of 5P5 and 7P5 is provided as standard.
* 8. Temperature during shipping (for short period).
183
Standard Wiring
DC Reactor
(Optional)
Thermal Overload
Relay
Braking Resistor
(Optional)
Short-circuit bar*1
MCCB
Power Supply
(
For Single-phase.
Use R/L1 and S/L2.
)
Multifunction input
FORWARD
RUN/STOP
REVERSE
RUN/STOP
EXTERNAL FAULT
(NO CONTACT)
FAULT RESET
MULTI-STEP
SPEED REF. 1
MULTI-STEP
SPEED REF. 2
JOG
COMMAND
FAULT
Grounding
Multi-function
Contact Output
250 VAC 1 A or less
30 VDC 1 A or less
*2
Pulse Train Input
Shield connection terminal
Reference Pulse Train
(Max. 33 kHz)
Frequency Setting
Power Supply
(+12 V 20 mA)
Frequency Reference
0 to +10 V (20 k
Ω)
4 to 20 mA/0 to 20 mA (250 Ω)
Digital Operator
Frequency
Setting
Potentiometer
Multi-function
Photocoupler Output
+48 VDC 50 mA or less
MEMOBUS
Communications
RS-485/422
Max. 19.2 kbps
Terminal Resistance
(1/2 W, 120 Ω)
Analog Monitor
Output
0 to +10 VDC (2 mA)
Output Frequency
Analog Monitor/Pulse
Monitor Selectable
Shielded
P
Shielded twisted-pair cable
184
: Only basic insulation (protective class 1, overvoltage category II) is provided for the
control circuit terminals. Additional insulation may be necessary in the end product to
conform to CE requirements.
*1. Short-circuit bar should be removed when connecting a DC reactor.
*2. Minimum permissible load: 5 VDC, 10 mA (as reference value)
9. Specifications
Connection Example of Braking Resistor
Overload Relay
Trip Contact
Braking
Resistor *
3-phase
Power
Supply
Motor
Fault Contact
* Disable stall prevention during deceleration by setting n092 to 1 when using a Braking Resistor Unit. The motor may not stop within the deceleration time if this setting is not changed.
Terminal Descriptions
Type Terminal
R/L1, S/L2,
T/L3
U/T1, V/T2,
W/T3
B1, B2
Name Function (Signal Level)
AC power supply input Use main circuit power input. (Use terminals R/L1 and S/
L2 for single-phase Inverters. Never use terminal T/L3.)
Inverter output Inverter output
+2, +1
+1, -
Braking resistor connection
Braking resistor connection
DC reactor connection When connecting optional DC reactor, remove the main circuit short-circuit bar between +2 and +1.
DC power supply input
Grounding
DC power supply input (+1: positive −: negative) *1
For grounding (according to the local grounding codes)
185
Type Terminal
S1
AM
AC
S2
S3
S4
S5
S6
S7
SC
RP
FS
FR
FC
MA
MB
MC
P1
P2
PC
Name
Multi-function input selection 1
Multi-function input selection 2
Multi-function input selection 3
Multi-function input selection 4
Multi-function input selection 5
Multi-function input selection 6
Function (Signal Level)
Factory setting closed:FWD run open: Stop
Factory setting closed:REV run open: Stop
Factory setting: External fault
(NO contact)
Factory setting: Fault reset
Photocoupler insulation, 24
VDC, 8 mA
Multi-function input selection 7
Multi-function input selection common
Master reference pulse train input
Power for frequency setting
Master frequency reference
Frequency reference common
NO contact output
NC contact output
Contact output common
Photocoupler output 1
Photocoupler output 2
Photocoupler output common
Factory setting: Multi-step speed reference 1
Factory setting: Multi-step speed reference 2
Factory Setting: JOG command
For control signal
33 kHz max.
+12 V (permissible current 20 mA max.)
0 to +10 VDC (20 k mA (250
0 V
Factory setting: Run
Factory setting: Frequency agree
0 V
Ω) or 4 to 20 mA (250 kΩ) or 0 to 20
Ω) (1/1000 resolution)
Factory setting: fault
Analog monitor output
*2
Analog monitor common
Factory setting:
Output frequency
0 to +10 V
0 V
Contact capacity
250 VAC 1 A or less,
30 VDC 1 A or less
*3
Photocoupler output +48 VDC,
50 mA or less
0 to +10 VDC, 2 mA or less,
8-bit resolution
186
Type Terminal
R+
R-
S+
S-
Name
Communications input (+)
Communications input (-)
Communications output (+)
Communications output (-)
9. Specifications
MEMOBUS communications
Function (Signal Level)
RS-485/422 MEMOBUS protocol 19.2 kbps max.
Run through RS-485 or RS-422.
* 1. DC power supply input terminal is not applied to CE/UL standard.
* 2. Can be switched to pulse monitor output.
* 3. Minimum permissible load: 5 VDC, 10 mA (as reference value)
187
Sequence Input Connection with NPN/PNP
Transistor
When connecting sequence inputs (S1 to S7) with transistor, turn the rotary switch SW1 depending on the polarity (0 V common: NPN side,
+24 V common: PNP side).
Factory setting: NPN side
Sequence Connection with NPN Transistor (0 V Common)
VS-606V7
Multifunction input
Forward run/stop
Reverse run/stop
External fault (NO)
Fault reset
Multi-step speed reference 1
Multi-step speed reference 2
JOG command
S1
S5
S6
S7
S2
S3
S4
SW1 NPN
+24 V
SC
PNP
188
9. Specifications
Sequence Connection with PNP Transistor (+24 V Common)
External power supply
+24V
Multifunction input
Forward run/stop
Reverse run/stop
External fault (NO)
Fault reset
Multi-step speed reference 1
Multi-step speed reference 2
JOG command
VS-606V7
S1
S2
S3
S4
S5
S6
S7
SC
SW1 NPN
+24 V
PNP
189
Dimensions/Heat Loss
2-d
W1
W
4-d
8.5
Fig. 1
D
190
W1
W 8.5
Fig. 2
D
4-d
9. Specifications
W1
W
8.5
D
Fig. 3
Dimensions in mm/Mass in kg/Heat Loss (W)
Voltage class
Capacity (kW)
W H D W1
200 V
3-phase
0.1
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
68
68
68
68
108
108
140
180
180
128
128
128
128
128
128
128
260
260
56
56
56
56
96
96
128
164
164
76
76
108
128
131
140
143
170
170
H1
118
118
118
118
118
118
118
244
244
5
5
5
5
5
5
5
8
8
H2 d
M4
M4
M4
M4
M4
M4
M4
M5
M5
Mass Heat Loss (W)
Heatsink
Unit Total
Fig.
0.6
0.6
3.7
7.7
9.3
13.0
10.3
18.0
1
1
0.9
1.1
1.4
1.5
2.1
4.6
4.8
15.8
12.3
28.1
28.4
16.7
45.1
53.7
19.1
72.8
60.4
34.4
94.8
96.7
170.4
219.2
52.4
79.4
98.9
149.1
249.8
318.1
1
1
2
2
2
3
3
191
Voltage class
Capacity (kW)
W
200 V singlephase
0.1
0.2
0.4
0.75
1.5
2.2
3.7
400 V
3-phase
0.2
0.4
0.75
1.5
2.2
3.0
3.7
5.5
140
140
180
108
108
108
108
108
108
108
140
170
68
68
68
H
128
128
260
128
128
128
128
128
128
128
128
128
128
128
128
D
143
143
170
92
110
140
156
156
140
156
163
180
76
76
131
W1 H1 H2
5
5
8
5
5
5
5
5
5
5
5
5
5
5
5
118
118
244
118
118
118
118
118
118
118
118
118
118
118
118
128
128
164
96
96
96
96
96
96
96
128
158
56
56
56 d
M4
M4
M5
M4
M4
M4
M4
M4
M4
M4
M4
M4
M4
M4
M4
2.1
2.1
4.8
1.0
1.1
1.5
1.5
1.5
Mass Heat Loss (W)
Heatsink
Unit Total
Fig.
1.5
1.5
2.2
2.9
0.6
0.7
1.0
3.7
7.7
10.4
12.3
14.1
20.0
15.8
16.1
31.9
28.4
23.0
51.4
53.7
29.1
82.8
64.5
49.1
113.6
98.2
78.2
176.4
2
2
2
2
1
1
1
9.4
13.7
23.1
15.1
15.0
30.1
30.3
24.6
54.9
45.8
29.9
75.7
50.5
32.5
83.0
58.2
37.6
95.8
73.4
44.5
117.9
168.8
87.7
256.5
2
2
3
2
2
2
2
2
7.5
180 260 170 164 244 8 M5 4.8
209.6
99.3
308.9
3
Note: Remove the top and bottom covers so that Inverters of 5.5/7.5 kW (200/
400-V Classes) can be used as IP00.
192
9. Specifications
Recommended Peripheral Devices
It is recommended that the following peripheral devices be mounted between the AC main circuit power supply and VS-606V7 input terminals R/L1, S/L2, and T/L3.
• MCCB (Molded-case Circuit Breaker)/Fuse:
Always connect for wiring protection.
• Magnetic Contactor:
Mount a surge suppressor on the coil. (Refer to the table shown below.) When using a magnetic contactor to start and stop the
Inverter, do not exceed one start per hour.
Recommended MCCB Magnetic Contactors and Fuses
• 200 V 3-phase
VS-606V7 Model V7**
20P1
0.3
V7**
20P2
0.6
V7**
20P4
1.1
V7**
20P7
1.9
V7**
21P5
3.0
V7**
22P2
4.2
V7**
23P7
6.7
V7**
25P5
9.5
V7**
27P5
13.0
Capacity (kVA)
Rated Output Current (A)
MCCB type NF30
(MITSUBISHI)
Magnetic contactor
(Fuji Electric FA
Components &
Systems)
0.8
5 A
1.6
5 A
3
5 A
5
10 A
8
20 A
11
20 A
17.5
30 A
Without reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N1
(26A)
SC-N2
(35A)
25.0
50 A
SC-
N2S
(50A)
33.0
60A
SC-N3
(65A)
Fuse (UL Class RK5)
With reactor
SC-03
(11A)
SC-03
(11A)
5 A 5 A
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N1
(26A)
SC-N2
(35A)
SC-
N2S
(50A)
5 A 10 A 20 A 20 A 30 A 50 A 60 A
• 200 V Single-phase
VS-606V7 Model
Capacity (kVA)
Rated Output Current (A)
MCCB type NF30, NF50
(MITSUBISHI)
Magnetic contactor
(Fuji Electric FA
Components &
Systems)
Without reactor
With reactor
V7**
B0P1
0.3
0.8
5 A
SC-03
(11A)
SC-03
(11A)
V7**
B0P2
0.6
1.6
5 A
SC-03
(11A)
SC-03
(11A)
V7**
B0P4
1.1
3
10 A
V7**
B0P7
1.9
5
20 A
V7**
B1P5
3.0
8
20 A
V7**
B2P2
4.2
11
40 A
V7**
B3P7
6.7
17.5
50 A
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N2
(35A)
SC-4-0
(18A)
SC-N1
(26A)
SC-N2
(35A)
SC-N2S
(50A)
SC-N2
(35A)
SC-N2S
(50A)
193
VS-606V7 Model
Fuse (UL Class RK5)
• 400 V 3-phase
V7**
B0P1
5 A
V7**
B0P2
5 A
V7**
B0P4
10 A
V7**
B0P7
20 A
V7**
B1P5
20 A
V7**
B2P2
40 A
V7**
B3P7
50 A
VS-606V7 Model
Capacity (kVA)
Rated Output Current (A)
MCCB type NF30, NF50 (MIT-
SUBISHI)
V7**
40P2
0.9
1.2
5 A
V7**
40P4
1.4
1.8
5 A
V7**
40P7
2.6
V7**
41P5
3.7
V7**
42P2
4.2
V7**
43P0
5.5
V7**
43P7
6.6
V7**
45P5
V7**
47P5
11.0
14.0
3.4
4.8
5.5
7.2
8.6
14.8
18.0
5 A 10 A 10 A 20 A 20 A 30 A 30 A
Magnetic contactor
(Fuji Electric FA
Components &
Systems)
Fuse (UL Class RK5)
Without reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-4-0
(18A)
SC-N1
(26A)
SC-N2
(35A)
SC-N2
(35A)
With reactor
SC-03
(11A)
SC-03
(11A)
5 A 5 A
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N1
(26A)
SC-N2
(35A)
5 A 10 A 10 A 20 A 20 A 30 A 30 A
Surge Suppressors
Surge Suppressors
Coils and Relays
Model
DCR2-
Specifications Code No.
200 V to
230 V
Large size magnetic contactors
Control relays
MY-2, -3 (OMRON)
HH-22, -23 (FUJI)
MM-2, -4 (OMRON)
50A22E
10A25C
250 VAC
0.5
µF 200 Ω
250 VAC
0.1
µF 100 Ω
C002417
C002482
• Ground Fault Interrupter:
Select a ground fault interrupter not affected by high frequencies. To prevent malfunctions, the current should be 200 mA or higher and the operating time 0.1 s or longer.
Example:
• NV series by Mitsubishi Electric Co., Ltd. (manufactured in 1988 and after)
• EGSG series by Fuji Electric Co., Ltd. (manufactured in 1984 and after)
194
9. Specifications
• AC and DC Reactor:
Install an AC reactor to connect to a power supply transformer of large capacity (600 kVA or more) or to improve power factor on the power supply side.
• Noise Filter:
Use a noise filter exclusively for Inverter if radio noise generated from the Inverter causes other control devices to malfunction.
NOTE
1. Never connect a general LC/RC noise filter to the Inverter output circuit.
2. Do not connect a phase-advancing capacitor to the I/O sides and/or a surge suppressor to the output side.
3. When a magnetic contactor is installed between the
Inverter and the motor, do not turn it ON/OFF during operation.
For the details of the peripheral devices, refer to the catalog.
195
Constants List
• Addition of Constants Accompained by the Upgraded Software
Version
The constants marked with #1, #2, and #3 are applicable for the following upgraded software version Nos.:
#1: Applicable for software version No. VSP010015 or later
#2: Applicable for software version No. VSP010020 or later
#3: Applicable for software version No. VSP010024 or later
#4: Applicable for software version No.VSP010028 or later.
First Functions (Constants n001 to n049)
No. Register
No. for
Transmission
003 0103 RUN Command Selection
004 0104 Frequency Reference Selection
Name Setting Range Setting Unit Factory
Setting
Change during
Operation
User
Setting
Ref.
Page
001 0101H Password
002 0102 Control Mode Selection (Note
6)
0 to 4, 6, 8, 9
0, 1
0 to 3
0 to 9
-
-
-
-
1
0
(Note 1)
0
0
(Note 5)
No
No
No
No
53
58
63
64
005 0105 Stopping Method Selection
006 0106 Reverse Run Prohibit
0, 1
0, 1 -
0
0
No
No
85
65
-
-
0
0
(Note 5)
0
No
No
No
84
64
64
007 0107 Stop Key Selection
008 0108 Frequency Reference Selection in Local Mode
0, 1
0, 1
009 0109 Frequency Reference Setting
Method From Digital Operator
010 010A Detecting Fault Contact of
Digital Operator
011 010B Max. Output Frequency
012 010C Max. Voltage
0, 1
0, 1
50.0 to 400.0
Hz
0.1 to 255.0 V
(Note 2)
0.2 to 400.0 Hz 013 010D Max. Voltage Output
Frequency
014 010E Mid. Output Frequency 0.1 to 399.9 Hz
015 010F Mid. Output Frequency Voltage
0.1 to 255.0 V
(Note 2)
-
0.1 Hz
0.1 V
0.1 Hz
0.1 Hz
0.1 V
0
60.0 Hz
200.0 V
(Note 2)
60.0 Hz
1.5 Hz
(Note 6)
12.0 V
(Note 2,
6)
No
No
No
No
No
No
63
55
55
55
55
55
196
9. Specifications
No. Register
No. for
Transmission
Name
016 0110 Min. Output Frequency
017 0111 Min. Output Frequency Voltage
Setting Range Setting Unit Factory
Setting
Change during
Operation
User
Setting
Ref.
Page
0.1 to 10.0 Hz 0.1 Hz No 55
0.1 to 50.0 V
(Note 2)
0, 1
0.1 V
-
1.5 Hz
(Note 6)
12.0 V
(Note 2,
6)
0
No
No
55
70 018 0112 Selecting Setting Unit for Acceleration/deceleration Time
019 0113 Acceleration Time 1
020
021
022
026
027
0114
0115
0116
011A
011B
Deceleration Time 1
Acceleration Time 2
Deceleration Time 2
Frequency Reference 3
Frequency Reference 4
0.00 to 6000 s Depend on n018 setting
0.00 to 6000 s Depend on n018 setting
0.00 to 6000 s Depend on n018 setting
0.00 to 6000 s Depend on n018 setting
0 to 3 -
10.0 s
10.0 s
10.0 s
10.0 s
023 0117 S-curve Selection 0
024 0118 Frequency Reference 1 (Master Frequency Reference)
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/
0.1 Hz (100
Hz or more)
6.00 Hz
025 0119 Frequency Reference 2 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/
0.1 Hz (100
Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/
0.1 Hz (100
Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/
0.1 Hz (100
Hz or more)
0.00 Hz
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
69
69
69
69
71
65
65
65
65
028 011C Frequency Reference 5
029 011D Frequency Reference 6
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/
0.1 Hz (100
Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/
0.1 Hz (100
Hz or more)
0.00 Hz
Yes
Yes
65
65
197
No. Register
No. for
Transmission
Name
030 011E Frequency Reference 7
031
032
011F
0120
Frequency Reference 8
Jog Frequency
033 0121 Frequency Reference Upper
Limit
034 0122 Frequency Reference Lower
Limit
035 0123 Setting/displaying Unit Selection for Frequency Reference
Setting Range Setting Unit Factory
Setting
Change during
Operation
User
Setting
Ref.
Page
Yes 65 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/
0.1 Hz (100
Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/
0.1 Hz (100
Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/
0.1 Hz (100
Hz or more)
6.00 Hz
0% to 110% 1% 100%
Yes
Yes
No
65
66
68
0% to 110%
0 to 3999
1%
-
0%
0
No
No
68
148
043
#3
044
#3
045
#4
036 0124 Motor Rated Current
037 0125 Electronic Thermal Motor Protection Selection
038 0126 Electronic Thermal Motor Protection Time Constant Setting
0% to 150% of
Inverter rated current
0 to 2
1 to 60 min
0, 1
041
#3
042
#3
039 0127 Selecting Cooling Fan Operation
040
#3
0128 Motor Rotation Direction
0129 Acceleration Time 3
012A Deceleration Time 3
012B
012C
012D
Acceleration Time 4
Deceleration Time 4
Frequency reference bias step amount (UP/DOWN command 2)
0, 1
0.00 to
6000 s
0.00 to
6000 s
0.00 to
6000 s
0.00 to
6000 s
0.00 Hz to
99.99 Hz
0.1 A
-
-
-
1 min
Depend on n018 setting
Depend on n018 setting
Depend on n018 setting
Depend on n018 setting
0.01 Hz
(Note 3)
0
8 min
0
0
10.0 s
10.0 s
10.0 s
10.0 s
0.00
Hz
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
105
105
105
107
43
69
69
69
69
-
198
9. Specifications
No. Register
No. for
Transmission
046
#4
047
#4
048
#4
049
#4
012E
012F
0130
0131
Name
Frequency reference bias accel/decel rate (UP/DOWN command 2)
Frequency reference bias operation mode selection
(UP/DOWN command 2)
Frequency reference bias value (UP/DOWN command
2)
Analog frequency reference fluctuation limit level (UP/
DOWN command 2)
Setting Range Setting Unit Factory
Setting
Change during
Operation
User
Setting
Ref.
Page
0, 1 0 Yes -
0, 1
-99.9% to
100.0%
(n011/
100%)
0.1% to
100.0%
(n011/100%)
-
0.1%
0.1%
0
0.0%
1.0%
Yes
No
Yes -
-
-
Second Functions (Constants n050 to n079)
No. Register
No. for
Transmission
Name
050 0132 Multi-function Input Selection
1 (Terminal S1)
Setting Range Setting Unit Factory
Setting
Change during
Operation
User
Setting
Ref.
Page
1 to 25, 26#3,
27#3
1 No 90
2 No 90 051 0133 Multi-function Input Selection
2 (Terminal S2)
1 to 25, 26#3,
27#3
052 0134 Multi-function Input Selection
3 (Terminal S3)
1 to 25, 26#3,
27#3
053 0135 Multi-function Input Selection
4 (Terminal S4)
1 to 25, 26#3,
27#3
054 0136 Multi-function Input Selection
5 (Terminal S5)
1 to 25, 26#3,
27#3
-
-
3
5
6
No
No
No
90
90
90
055 0137 Multi-function Input Selection
6 (Terminal S6)
1 to 25, 26#3,
27#3
056 0138 Multi-function Input Selection
7 (Terminal S7)
1 to 25, 26#3,
27#3, 34, 35,
36#4
057 0139 Multi-function Output Selection 1
058 013A Multi-function Output Selection 2
0 to 7, 8#3,
9#3, 10 to 19,
20#3, 21#3
0 to 7, 8#3,
9#3, 10 to 19,
20#3, 21#3
059 013B Multi-function Output Selection 3
0 to 7, 8#3,
9#3, 10 to 19,
20#3, 21#3
-
-
-
-
7
10
0
1
2
No
No
No
No
No
90
90
95
95
95
199
No. Register
No. for
Transmission
Name Setting Range Setting Unit Factory
Setting
Change during
Operation
User
Setting
Ref.
Page
1 % 100 % Yes 67 060 013C Analog Frequency Reference
Gain
0 % to 255 %
061 013D Analog Frequency Reference
Bias
-100 % to 100
%
062 013E Filter Time Constant for Analog Frequency Reference
0.00 to 2.00 s
1 %
0.01 s
0 %
0.10 s
Yes
Yes
67
-
0 No 149 064
#3
0140 Frequency Reference Loss
Detection
Selection
065 0141 Monitor Output Type
066 0142 Monitor Item Selection
0, 1
0, 1
0 to 5, 6#3
067 0143 Monitor Gain
068 0144 Analog Frequency Reference
Gain (Voltage input from Operator)
0.00 to 2.00
−255% to
255%
069 0145 Analog Frequency Reference
Bias (Voltage input from Operator)
−100% to
100%
070 0146 Analog Frequency Reference
Filter Time Constant (Voltage input from Operator)
0.00 to 2.00 s
−255% to
255%
071 0147 Analog Frequency Reference
Gain
(Voltage input from Operator)
072 0148 Analog Frequency Reference
Bias
(Current input from Operator)
073 0149 Analog Frequency Reference
Filter Time Constant (Current input from Operator)
0.00 to 2.00 s
074 014A Pulse Train Frequency Reference Gain
0 % to 255 %
078
#2
079
#2
075 014B Pulse Train Frequency Reference Bias
-100 % to 100
%
0.00 to 2.00 s 076 014C Pulse Train Frequency Filter
Time Constant
077
#2
014D Multi-function Analog Input
Function
0 to 4
014E Multi-function Analog Input
Signal Selection
014F Frequency Reference Bias
(FBIAS) Value
0, 1
0 % to 50 %
-
-
0.01
1%
1%
0.01 s
1%
1%
0.01 s
1 %
1 %
0.01 s
-
-
1 %
0
0
1.00
100%
0%
0.10 s
100%
0%
0.10 s
100 %
0 %
0.10 s
0
0
10 %
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
-
-
-
-
-
-
-
-
93
92
92
78
77
78
-
200
9. Specifications
Third Functions (Constants n080 to n119)
No. Register
No. for
Transmission
Name
080 0150 Carrier Frequency Selection
081 0151 Momentary Power Loss
Ridethrough Method
082 0152 Automatic Retry Attempts
083 0153 Jump Frequency 1
Setting Range Setting Unit Factory
Setting
Change during
Operation
1 to 4, 7 to 9
0 to 2 -
(Note 4)
0
084
085
086
0154
0155
0156
Jump Frequency 2
Jump Frequency 3
Jump Frequency Range
0 to 10 times 0
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz
0.01 Hz 0.00 to
25.50 Hz
0, 1 -
0.00
Hz
0 087
088
0157
0158
Cumulative operation time function selection
*9
Cumulative operation time
*9
0 to 6550 1 = 10H 0H
089 0159 DC Injection Braking Current
090 015A DC Injection Braking Time at
Stop
091 015B DC Injection Braking Time at
Startup
092 015C Stall Prevention During Deceleration
0 to 100%
0.0 to 25.5 s
0.0 to 25.5 s
0, 1
1%
0.1 s
0.1 s
-
50%
0.5 s
0.0 s
0
093 015D Stall Prevention Level During
Acceleration
30% to 200% 1% 170%
094 015E Stall Prevention Level During
Running
30% to 200%
095 015F Frequency Detection Level
1% 160%
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
User
Setting
Ref.
Page
81
70
75
74
74
74
74
-
-
76
86
76
103
100
103
73
201
No. Register
No. for
Transmission
Name
096 0160 Overtorque Detection Function Selection 1
097 0161 Overtorque/Undertorque Detection Function Selection 2
098 0162 Overtorque Detection Level
099 0163 Overtorque Detection Time
100 0164 Hold Output Frequency Saving
Selection
101
#3
0165 Speed Search Deceleration
Time
Setting Range Setting Unit Factory
0 to 4
0, 1
30% to 200%
0.1 to 10.0 s
0, 1
0.1 to 10.0 s
-
-
1%
0.1 s
-
0.1 s
Setting
0
0
160%
0.1 s
0
2.0 s
102
#3
103 0167 Torque Compensation Gain
104
0166
0168
Speed Search Operation Level
Torque Compensation Time
Constant
0 % to 200 %
0.0 to 2.5
0.0 to 25.5 s
105 0169 Torque Compensation Iron
Loss
106 016A Motor Rated Slip
1 %
0.1
0.1 s
150 %
1.0
(Note 6)
0.0 to 6550 0.01 W (less than 1000
W)/1 W
(1000 W or more)
(Note 3)
0.0 to 20.0 Hz 0.1 Hz (Note 3)
107
108
016B
016C
Motor Line-to-neutral Resistance
Motor Leakage Inductance
0.000 to 65.50
Ω
0.001 W
(less than 10
W)/0.01 W
(10 W or more)
(Note 3)
0.00 to
655.0 mH
0% to 250%
0.01 mH
(less than
100 mH)/0.1 mH (100 mH or more)
(Note 3)
1% 150% 109 016D Torque Compensation Voltage Limiter
110
111
016E
016F
Motor No-load Current
Slip Compensation Gain
0% to 99%
0.0 to 2.5
112 0170 Slip Compensation Time Constant
113 0171 Slip Compensation During Regenerative Operation
0.0 to 25.5 s
0, 1
115
#2
0173 Stall Prevention Above Base
Speed During Run
0, 1
1%
0.1
0.1 s
-
-
(Note 3)
(Note 6)
(Note 6)
0
0
Change during
Operation
User
Setting
Ref.
Page
No
No
No
No
No
No
No
Yes
No
No
Yes
No
No
No
No
Yes
No
No
No
72
73
73
73
92
76
76
57
57
57
59
59
60
58
104
104
-
-
102
202
9. Specifications
116
#2
117
#3
118
#3
No. Register
No. for
Transmission
Name
0174 Acceleration/deceleration
Time during Stall Prevention
0175 Undertorque Detection Function Selection 1
0176 Undertorque Detection Level
Setting Range Setting Unit Factory
Setting
Change during
Operation
User
Setting
Ref.
Page
0, 1 0 No 103
0 to 4
0% to 200%
-
1%
0
10%
No
No
152
152
119
#3
0177 Undertorque Detection Time 0.1 to 10.0 s 0.1 s 0.1 s No 152
Fourth Functions (Constants n120 to n179)
No. Register
No. for
Transmission
Name
120 0178 Frequency Reference 9
121 0179 Frequency Reference 10
122 017A Frequency Reference 11
123 017B Frequency Reference 12
124 017C Frequency Reference 13
125 017D Frequency Reference 14
126 017E Frequency Reference 15
Setting Range Setting Unit Factory
Setting
Change during
Operation
User
Setting
Ref.
Page
Yes 65 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz Yes 65
Yes 65 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz
Yes
Yes
Yes
65
65
65
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz Yes 65
203
No. Register
No. for
Transmission
Name
127 017F Frequency Reference 16
Setting Range Setting Unit Factory
Setting
Change during
Operation
User
Setting
Ref.
Page
Yes 65 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz or more)
0.00 Hz
No
Yes
129
132
128
129
0180
0181
PID Control Selection
PID Feedback Gain
130 0182 Proportional Gain (P)
131 0183 Integral Time (I)
132 0184 Derivative Time (D)
0 to 8
0.00 to 10.00
Hz
0.0 to 25.0
0.0 to 360.0 s
133 0185 PID Offset Adjustment
0.00 to 2.50 s
−100% to
100%
134 0186 Upper Limit of Integral Values 0% to 100%
135 0187 Primary Delay Time Constant for PID Output
0.0 to 10.0 s
136 0188 Selection of PID Feedback
Loss Detection
0 to 2
137 0189 PID Feedback Loss Detection
Level
0% to 100%
138 018A PID Feedback Loss Detection
Time
0.0 to 25.5 s
0, 1 139 018B Energy-saving Control Selection (V/f Control Mode)
140 018C Energy-saving Coefficient K2 0.0 to 6550
141 018D Energy-saving Control Voltage
Lower Limit at 60 Hz
0% to 120%
142 018E Energy-saving Control Voltage
Lower Limit at 6 Hz
143 018F Power Average Time
144 0190 Search Operation Voltage
Limit
0% to 25%
1 to 200
0% to 100%
0.1% to 10.0% 145 0191 Search Operation Voltage
Step at 100%
146 0192 Search Operation Voltage
Step at 5%
0.1% to 10.0%
149 0195 Pulse Train Input Scaling 100 to 3300
-
0.01
0.1
0.1 s
0.01 s
1%
1%
0.1 s
-
1%
0.1 s
-
0.1
1%
1%
0
1.00
1.0
1.0 s
0.00
0%
100%
0.0 s
0
0%
1.0 s
0
(Note 7)
50%
1 = 24 ms 1 (24 ms)
1% 0%
0.1%
0.1%
1 = 10 Hz
12%
0.5%
0.2%
2500
(25 kHz)
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
131
132
133
133
133
123
123
124
124
125
125
125
125
99
131
131
131
131
204
9. Specifications
No. Register
No. for
Transmission
Name Setting Range Setting Unit Factory
Setting
Change during
Operation
User
Setting
Ref.
Page
0 No 79 150 0196 Pulse Monitor Output Frequency Selection
151 0197 MEMOBUS Timeover Detection
0, 1, 6, 12, 24,
36, 40 to 45#3
0 to 4
152 0198 MEMOBUS Frequency Reference and Frequency Monitor
Unit
153 0199 MEMOBUS Slave Address
0 to 3
0 to 32 -
-
0
0
0
No
No
No
109
109
110
154
155
156
157
019A
019B
019C
019D
MEMOBUS BPS Selection
MEMOBUS Parity Selection
Transmission Waiting Time
RTS Control
158 019E Motor Code (Energy-saving
Control)
159 019F Upper Voltage Limit for Energy-saving Control at 60 Hz
160 01A0 Upper Voltage Limit for Energy-saving Control at 6 Hz
161 01A1 Search Operation Power Detection Hold Width
0 to 3
0 to 2
10 to 65 ms
0, 1
0 to 70
0% to 120%
0% to 25%
0% to 100%
-
-
1 ms
-
-
1%
1%
1%
2
0
10 ms
0
(Note 7)
120%
16%
10%
No
No
No
No
No
No
No
No
110
110
110
110
123
124
124
126
1 = 4 ms 5 (20 ms) No 126 162 01A2 Time Constant of Power Detection
Filter
163 01A3 PID Output Gain
164 01A4 PID Feedback Value Selection
165 01A5 Externally-mounting type braking resistor overheat protection selection *8
0 to 255
0.0 to 25.0
0 to 5
0, 1
0.1
-
-
1.0
0
0
No
No
No
132
130
-
166
#3
167
#3
168
#3
169
#3
170
#4
01A6 Input Open-phase Detection
Level
01A7 Input Open-phase Detection
Time
0% to 100%
0 to 255 s
01A8 Output Open-phase Detection
Level
0% to 100%
01A9 Output Open-phase Detection
Time
0.0 to 2.0 s
01AA ENTER command operation selection (MEMOBUS communications)
0, 1
1%
1 s
1%
0.1 s
-
0%
0 s
0%
0.0 s
0
No
No
No
No
No
150
150
150
150
119
205
172
#4
173
#3
174
#3
No. Register
No. for
Transmission
171
#4
Name Setting Range Setting Unit
01AB Frequency reference bias upper limit (UP/DOWN command 2)
0.0 to 100.0%
(n011/100%)
01AC Frequency reference bias lower limit (UP/DOWN command
2)
-99.9 to 0.0%
(n011/100%)
1 to 999 01AD DC Injection Braking Proportional Gain
01AE DC Injection Braking Integral
Time Constant
1 to 250
0.1%
0.1%
1 = 0.001
1 = 4 ms
Factory
Setting
0.0%
0.0%
83
(0.083)
25 (100 ms)
Change during
Operation
User
Setting
Ref.
Page
Yes
Yes
No
No -
-
-
-
175
#1
176
01AF Reducing Carrier Frequency
Selection at Low Speed
01B0 Constant Copy Function Selection
177 01B1 Constant Read Selection Prohibit
0, 1 rdy, rEd, Cpy, vFy, vA, Sno
0, 1
178 01B2 Fault History Stores, displays most recent 4 alarms
-
-
-
Setting disabled
0
*9 rdy
0
-
No
No
No
No
84
136
137
50
179 01B3 Software Version No.
Displays lower-place 4 digits of software No.
Setting disabled
No -
Note: 1. Not initialized by constant initialization.
2. Upper limit of setting range and factory setting are doubled for 400 V
Class.
3. Depends on Inverter capacity. Refer to the next page.
4. Depends on Inverter capacity. Refer to page 82.
5. Factory setting of the model with JVOP-147 Digital Operator (without potentiometer) is 1. Setting can be set to 0 by constant initialization.
6. When control mode selection (n002) is changed, factory setting corresponds to the control mode. Refer to the next page.
7. Depends on Inverter capacity. Refer to page 123.
8. Constant that is provided for 5.5 kW and 7.5 kW Inverters of 200-V and 400-V classes
9. 1 (Enabled) for 5.5 kW and 7.5 kW Inverters of 200-V and 400-V classes
206
9. Specifications
No.
Name n014 Mid. Output Frequency n015 Mid. Output Frequency Voltage n016 Min. Output Frequency n017 Min. Output Frequency Voltage
V/f Control
Mode
(n002 = 0)
1.5 Hz
12.0 V *1 *2
1.5 Hz
12.0 V *1 *2
0.3 s
0.0
Vector Control Mode
(n002 = 1)
3.0 Hz
11.0 V *1
1.0 Hz
4.3 V *1
0.2 s
1.0
n104 Torque Compensation Time Constant n111 Slip Compensation Gain n112 Slip Compensation Gain Time Constant 2.0 s 0.2 s
* 1. Values are doubled for 400 V Class.
* 2. 10.0 V for 5.5 kW and 7.5 kW Inverters of 200-V Class and 20.0 V of
400-V Class.
Factory Settings That Change with the Inverter Capacity
• 200 V Class 3-phase
No.
-
Name
Inverter Capacity n036 Motor Rated Current n105 Torque Compensation
Iron Loss n106 Motor Rated Slip n107 Motor Line-to-neutral
Resistance* n108 Motor Leakage
Inductance
Unit kW 0.1 kW
A
W
0.6
1.7
Hz 2.5
0.2 kW
0.4 kW
1.1
1.9
3.4
4.2
2.6
2.9
Factory Setting
0.75 kW
1.5 kW
2.2 kW
3.7 kW
5.5 kW
7.5 kW
3.3
6.2
8.5
14.1 19.6 26.6
6.5
11.1
11.8
19 28.8 43.9
2.5
2.6
2.9
3.3
1.5
1.3
Ω 17.99 10.28 4.573 2.575 1.233 0.8 0.385 0.199 0.111
mH 110.4 56.08 42.21 19.07 13.4 9.81 6.34 4.22 2.65
35 32 26 30 n110 Motor No-load
Current
% 72 73 62 55 45
* Sets the value of the motor resistance for one phase.
207
• 200 V Class Single-phase
No.
-
Name
Inverter Capacity n036 Motor Rated Current n105 Torque Compensation
Iron Loss n106 Motor Rated Slip
Unit Factory Setting kW 0.1 kW 0.2 kW 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW
A
W
0.6
1.7
1.1
3.4
1.9
4.2
3.3
6.5
6.2
11.1
8.5
11.8
14.1
19
Hz
Ω
2.5
17.99
2.6
10.28
2.9
4.573
2.5
2.575
2.6
1.233
2.9
0.8
3.3
0.385
n107 Motor Line-to-neutral
Resistance* n108 Motor Leakage
Inductance mH 110.4
56.08
42.21
19.07
13.4
9.81
6.34
45 35 32 n110 Motor No-load Current % 72 73 62 55
* Sets the value of the motor resistance for one phase.
• 400 V Class 3-phase
No.
-
Name
Inverter Capacity
Unit kW 0.2 kW 0.4 kW 0.75 kW
Factory Setting
1.5 kW
2.2 kW
3.0 kW
3.7 kW
5.5 kW
7.5 kW n036 Motor Rated Current n106 Motor Rated Slip n107 Motor Line-to-neutral
Resistance*
A n105 Torque Compensation Iron
Loss
W
0.6
3.4
1.0
4.0
1.6
6.1
3.1
4.2
7.0
7.0
9.8
13.3
11.0 11.7 19.3 19.3 28.8 43.9
Hz 2.5
2.7
2.6
2.5
3.0
3.2
3.2
1.5
1.3
Ω 41.97 19.08 11.22 5.044 3.244 1.514 1.514 0.797 0.443
n108 Motor Leakage Inductance mH 224.3 168.8 80.76 53.25 40.03 24.84 24.84 16.87 10.59
n110 Motor No-load Current % 73 63 52 45 35
* Sets the value of the motor resistance for one phase.
33 33 26 30
208
10 Conformance to CE Markings
10 Conformance to CE Markings
Points regarding conformance to CE markings are given below.
CE Markings
CE markings indicate conformance to safety and environmental standards that apply to business transactions (including production, imports, and sales) in Europe. There are unified European standards for mechanical products (Machine Directive), electrical products (Low Voltage
Directive), and electrical noise (EMC Directive). CE markings are required for business transactions in Europe (including production, imports, and sales).
The VS-606V7 Series Inverters bear CE markings indicating conformance to the Low Voltage Directive and the EMC Directive.
• Low Voltage Directive: 73/23/EEC
93/68/EEC
• EMC Directive: 89/336/EEC
92/31/EEC
93/68/EEC
Machinery and installations that incorporate the Inverter are also subject to CE markings. It is ultimately the responsibility of customers making products incorporating the Inverter to attach CE markings to the finished products. The customer must confirm that the finished products
(machines or installations) conform to the European Standards.
Requirements for Conformance to CE Markings
Low Voltage Directive
VS-606V7 Series Inverters satisfy testing for conformance to the Low
Voltage Directive under the conditions described in European Standard
EN50178.
Requirements for Conformance to the Low Voltage Directive
VS-606V7 Series Inverters must satisfy the following conditions in order to conform to the Low Voltage Directive.
• Only basic insulation to meet the requirements of protection class 1 and overvoltage category II is provided with control circuit terminals.
Additional insulation may be necessary in the end product to conform to CE requirements.
209
210
• For 400 V Class Inverters, always ground the supply neutral to conform to CE requirements.
EMC Directive
VS-606V7 Series Inverters satisfy testing for conformance to the EMC
Directive under the conditions described in European Standard
EN61800-3.
Installation Method
In order to ensure that the machinery or installation incorporating the
Inverter conforms to the EMC Directive, perform installation according to the method below.
• Install a noise filter that conforms to European Standards on the input side. (Refer to EMC Noise Filter on page 213.)
• Use a shielded line or metal piping for wiring between the Inverter and Motor. Make the wiring as short as possible.
• For details of installation method, refer to Installation Manual (document No. EZZ008390.)
10 Conformance to CE Markings
Installation and Wiring of Inverter and Noise Filter
(Model: CIMR-V720P1 to 27P5),
(Model: CIMR-V740P1 to 45P5)
L1 L2 L3 PE
Control Panel
3-phase Noise Filter
L1 L2 L3
E
Metal Mounting
Plate
Grounding
Face
Grounding
Face
RS T
Inverter
U V W
E
Shielded
Cable
IM
Motor cable: 20 m max.
211
Installation and Wiring of Inverter and Noise Filter
(Model: CIMR-V7B0P1 to B4P0)
L N PE
Control Panel
Single-phase Noise Filter
Metal Mounting
Plate
Grounding
Face
L N
212
Grounding
Face
Inverter
R S U V W
E
Shielded
Cable
IM
Motor cable: 20 m max.
10 Conformance to CE Markings
EMC Noise Filter
Voltage
Class
Inverter
Model
CIMR-
V7*
Model No.
200 V RS1010-V7
Number of
Phases
Noise Filter (Manufacturer: RASMI)
Rated
Current
(A)
Mass
(kg)
Dimensions
W ×L×H
1 10 0.6
71 × 169 × 45
400 V
27P5
40P2
40P4
40P7
41P5
42P2
21P5
22P2
23P7
24P0
25P5
43P0
43P7
44P0
45P5
47P5
B3P7
B4P0
20P1
20P2
20P4
20P7
B0P1
B0P2
B0P4
B0P7
B1P5
B2P2
RS1020-V7
RS1030-V7
RS1040-V7
RS2010-V7
RS2020-V7
RS2030-V7
RS2050-V7
RS3005-V7
RS3010-V7
RS3020-V7
RS3030-V7
1
1
1
3
3
3
3
3
3
3
3
20
30
40
10
16
26
50
5
10
15
30
1.0
1.1
1.2
0.8
1.0
1.1
2.3
1.0
1.0
1.1
2.3
111 × 169 × 50
144 × 174 × 50
174 × 174 ×50
120 × 161 5.0
150 × 161 5.0
82 × 194 × 50
111 × 169 × 50
111 × 169 × 45
111 × 169 × 45
Y ×X φd
51 × 156 5.0
91 × 156 5.0
62 × 181 5.0
91 × 156 5.0
144 × 174 × 50 120 × 161 5.0
184 × 304 × 56 150 × 264 6.0
91 × 156 5.0
91 × 156 5.0
144 × 174 × 50 120 × 161 5.0
184 × 304 × 56 150 × 264 6.0
213
214
The EMC-compliant V7 Series noise filter is footprint type.
φd
C I M R - V 7
X L
A to Z : Specifications
A to Z : Type
H Y
W
Revision History
The revision dates and numbers of the revised manuals are given on the bottom of the back cover.
MANUAL NO. TOE-S606-11.2H
C Printed in Japan July 2004 99-06 11
Date of printing
Revision number
Date of original publication
Date of
Printing
June 1999
October 1999
Rev.
No.
−
1
December
1999
April 2000
April 2001
2
3
4
Section
Chapter 6
Notes for Safe
Operation
Revised Content
First edition
Partly revised
Revision: Layout
Partly revised
Revision: Warning/Caution mark
September
2001
May 2002
July 2002
September
2002
5
6
7
8
Chapter 1
Chapter 8
Front cover
Notes for Safe
Operation
Revision: Changed “enclosed wallmounted type NEMA 1” to “enclosed wall-mounted type NEMA 1 (TYPE
1)”
Addition: Description of Inverters for
Japan demestic standards
Addition: Troubleshooting
Partly deleted
Deletion: CE and UL marks
Addition: Warnings for CE Markings
Date of
Printing
June 2003
Rev.
No.
9
Section
Chapter 6
Janualy 2004
August 2004
10
Endsheet on back cover
11
Revised Content
Addition: Description of overtorque/ undertorque detection function selection 2
Addition: Description of undertorque detection
Addition: Revision history
Addition: Details of 5.5/7.5 kW Inverters
英文 No.4-4 (A4) メカトロ製品用 TOE
VS-606V7 Series
INSTRUCTION MANUAL
IRUMA BUSINESS CENTER
480, Kamifujisawa, Iruma, Saitama 358-8555, Japan
Phone 81-4-2962-5696 Fax 81-4-2962-6138
YASKAWA ELECTRIC AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone 1-847-887-7000 Fax 1-847-887-7370
MOTOMAN INC. HEADQUARTERS
805 Liberty Lane West Carrollton, OH 45449, U.S.A.
Phone 1-937-847-6200 Fax 1-937-847-6277
YASKAWA ELETRICO DO BRASIL COMERCIO LTD.A.
Avenida Fagundes Filho, 620 Bairro Saude-Sao Paulo-SP, Brazil CEP: 04304-000
Phone 55-11-5071-2552 Fax 55-11-5581-8795
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany
Phone 49-6196-569-300 Fax 49-6196-569-312
Motoman Robotics Europe AB
Box 504 S38525 Torsas, Sweden
Phone 46-486-48800 Fax 46-486-41410
Motoman Robotec GmbH
Kammerfeldstra βe 1, 85391 Allershausen, Germany
Phone 49-8166-90-100 Fax 49-8166-90-103
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods Cumbernauld, G68 9LF, United Kingdom
Phone 44-1236-735000 Fax 44-1236-458182
YASKAWA ELECTRIC KOREA CORPORATION
Kfpa Bldg #1201, 35-4 Youido-dong, Yeongdungpo-Ku, Seoul 150-010, Korea
Phone 82-2-784-7844 Fax 82-2-784-8495
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
151 Lorong Chuan, #04-01, New Tech Park Singapore 556741, Singapore
Phone 65-6282-3003 Fax 65-6289-3003
YASKAWA ELECTRIC (SHANGHAI) CO., LTD.
No.18 Xizang Zhong Road. Room 1805, Harbour Ring Plaza Shanghai 20000, China
Phone 86-21-5385-2200 Fax 86-21-5385-3299
YATEC ENGINEERING CORPORATION
4F., No.49 Wu Kong 6 Rd, Wu-Ku Industrial Park, Taipei, Taiwan
Phone 886-2-2298-3676 Fax 886-2-2298-3677
YASKAWA ELECTRIC (HK) COMPANY LIMITED
Rm. 2909-10, Hong Kong Plaza, 186-191 Connaught Road West, Hong Kong
Phone 852-2803-2385 Fax 852-2547-5773
BEIJING OFFICE
Room No. 301 Office Building of Beijing International Club, 21
Jianguomenwai Avenue, Beijing 100020, China
Phone 86-10-6532-1850 Fax 86-10-6532-1851
TAIPEI OFFICE
9F, 16, Nanking E. Rd., Sec. 3, Taipei, Taiwan
Phone 886-2-2502-5003 Fax 886-2-2505-1280
SHANGHAI YASKAWA-TONGJI M & E CO., LTD.
27 Hui He Road Shanghai China 200437
Phone 86-21-6553-6060 Fax 86-21-5588-1190
BEIJING YASKAWA BEIKE AUTOMATION ENGINEERING CO., LTD.
30 Xue Yuan Road, Haidian, Beijing P.R. China Post Code: 100083
Phone 86-10-6233-2782 Fax 86-10-6232-1536
SHOUGANG MOTOMAN ROBOT CO., LTD.
7, Yongchang-North Street, Beijing Economic Technological Investment & Development Area,
Beijing 100076, P.R. China
Phone 86-10-6788-0551 Fax 86-10-6788-2878
YASKAWA ELECTRIC CORPORATION
YASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade
Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 1999-2004 YASKAWA ELECTRIC CORPORATION. All rights reserved.
MANUAL NO. TOE-S606-11.2H
04-1 ⑤
11