Digital Programmable Controller
PCD-300 Series
Economical Program Controller
...at the lowest prices anywhere!
Standard Features Program Pattern
Model PCD
1/4 DIN (96mm x 96mm)
• Structure
Unit available in standard DIN size (1/4 DIN).
NEMA 4X protective construction.
Black enclosure.
• Programmable Features
Unit features nine patterns with up to nine steps per pattern. Steps can be programmed from 99 hours and
59 minutes each.
• True Multi-Input
Unit features true multi-input capabilities:
10 thermocouple types, 2 RTD type, 2 current inputs, and 4 voltage inputs.
• Auto/Manual Control
Manual overide allows you to take control of your process at anytime.
• Large LED Display
All units feature dual display. PV red 4 digits,
SV green 4 digits.
• PID Autotune
All units feature as standard full function third generation PID Autotune. This feature minimizes process overshoot under the most demanding applications.
• Modbus Protocol With RS485
(Option)
Units offer communications capabilities. The PCD-300 can be used in conjunction withe the JC Series or the
DCL DIN Rail Controller to set up master/slave control systems.
• Approvals
UL, cUL and CE Safety Approvals.
• Warranty
All units manufactured to strict ISO standards and offer full 3 year manufacturers warranty.
Input Range Table
Input Type Scale
Thermocouple
K
J
R
S
B
E
T
N
PL-II
C (W/Re5-26)
-200 to 1370ºC
-199.9 to 400.0ºC
-200 to 1000ºC
0 to 1760ºC
0 to 1760ºC
0 to 1820ºC
-200 to 800ºC
-199.9 to 400.0ºC
-200 to 1300ºC
0 to 1390ºC
0 to 2315ºC
-320 to 2500ºF
-199.9 to 750.0ºF
-320 to 1800ºF
0 to 3200ºF
0 to 3200ºF
0 to 3300ºF
-320 to 1500ºF
-199.9 to 750.0ºF
-320 to 2300ºF
0 to 2500ºF
0 to 4200ºF
RTD Pt100 -199.9 to 850.0ºC
-200 to 850ºC
-199.9 to 999.9ºF
-300 to 1500ºF
DC
4 to 20mA DC
0 to 20mA DC
0 to 1V DC
0 to 10V DC
1 to 5V DC
0 to 5V DC
-1999.9 to 9999, -199.9 to 999.9
-19.99 to 99.99, -1.999 to 9.999
• For DC current input a shunt resistor (50 Ω) is provided as standard.
Terminal Wiring
All units feature a full 3 year warranty and lifetime technical support!
General Specifications
Display
Input
Accuracy
(Setting • Indicating)
PV.........Red
4-digit Character Size: 18.0 x 8.0 mm (H x W)
SV........Green 4-digit Character Size: 12.6 x 6.0 mm (H x W)
PTN......Green 1-digit Character Size: 12.6 x 6.0 mm (H x W)
STEP.....Green 1-digit Character Size: 12.6 x 6.0 mm (H x W)
Thermocouple ----- K, J, R, S, B, E, T, N, PL-II C (W/Re5-26) External resistance: 100 Ω or less
(However, for B input: 40 Ω or less)
RTD ------------------ Pt100, 3-wire system
(Allowable input wire resistance per wire: 10 Ω or less)
DC current ---------- 0 to 20mA DC, 4 to 20mA DC Input impedance: 50 Ω
(Connect shunt resistor 50 Ω between input terminals.)
Allowable input current: 50mA or less
(When shunt resistor 50 Ω is used.)
DC voltage ---------- 0 to 1V DC Input impedance: 1M Ω or greater
Allowable input voltage: 5V or less
Allowable signal source resistance: 2k Ω or less
0 to 5V DC, 1 to 5V DC, 0 to 10V DC Input impedance: 100k Ω or greater
Allowable input voltage: 15V or less
Allowable signal source resistance: 100 Ω or less
Scale..................Refer to “Rated Scale”
Resolution • Thermocouple, RTD (without decimal point----1ºC (1ºF)
• Thermocouple, RTD (with decimal point)-------0.1ºC (0.1ºF)
• DC current, DC voltage---------------------------1
Thermocouple -------------------- Within ±0.2% of each input span ±1 digit or ±2ºC (4ºF) whichever is greater
However, R or S input 0 to 200ºC (0 to 400ºF): Within ±6ºC (12ºF)
B input 0 to 300ºC (0 to 600ºF): Accuracy is not guaranteed.
K, J, E and N input less than 0ºC (32ºF): Within ±0.4% of input span ±1 digit
RTD --------------------------------- Within ±0.1% of each input span ±1 digit or ±1ºC (2ºF) whichever is greater
DC current and DC voltage ---- Within ±0.2% of each input span ± 1 digit
Time Indication
Accuracy
Within ±0.5% of setting time
Input Sampling
Period
0.25 seconds
Control Output
(OUT)
Must be designated
• Relay contact---1a1b 3A 250V AC (resistive load), 1A 250V AC (inductive load cos ∅=0.4), Electric life: 100,000 times
• Non-contact voltage--12V DC Max. 40mA DC (Short-circuit protected)
• DC current -------------4 to 20mA DC Load resistance: Max 550 Ω
Control Action Actions mentioned below can be selected by key operation. (Factory default set as PID)
PID (with auto-tuning function), PI, PD (with manual Reset function), P (with manual reset function), ON/OFF
Proportional band (P) --- Thermocouple: 0 to 1000ºC (0 to 2000ºF) (ON/OFF action when set to 0)
RTD: 0.0 to 999.9ºC (0 to 999.9ºF) (ON/OFF action when set to 0.0)
DC current and DC voltage: 0.0 to 100.0% (ON/OFF action when set to 0.0)
Integral time (I) -------------------- 0 to 1000 seconds (OFF when set to 0)
Derivative time (D) ---------------- 0 to 300 seconds (OFF when set to 0)
Proportional cycle ----------------- 1 to 120 seconds (DC current output type is not available.)
ARW -------------------------------- 0 to 100%
Hysteresis ------------------------- Thermocouple and RTD: 0.1 to 100.0ºC (F)
DC current and DC voltage: 1 to 1000 (Decimal point place follows the selection)
Output high limit, low limit ------------------- 0 to 100% (For DC current output, -5 to 100%)
Alarm 1 (A1)
Alarm 2 (A2)
Event Output
(EVT)
Alarm action and Energized/De-energized can be selected by key operation.
• Setting accuracy
• Action
• Hysteresis
• Output
The same as the indicating accuracy.
ON/OFF action
Thermocouple and RTD: 0.1 to 100.0ºC (ºF)
DC current and DC voltage: 1 to 1000
(The placement of the decimal point follows the selection)
Relay contact 3A 250V AC (Resistive load), Electric life: 100,000 times
One output can be selected from 3 outputs (Time signal output, Patten end output and RUN output) by front keypad operation.
Time signal output : If time signal OFF time and time signal ON time are set, time signal output is outputted within the total time
taken for 1 pattern during program control.
Pattern end output : Outputs the set time after the program ends
RUN output : Outputs during program control
Output : Relay contact, 1a 3A 250V AC (resistive load), 1A 250V AC (inductive load ∅=0.4), Electric life: 100,000 times
Model Number Configuration
PCD-33A-
___
/M
___ ___
CONTROL OUTPUT CODE
Relay Contact R
SSR Driver S
4-20mA A
INPUT CODE
True Multi-Input M
T/C, RTD. Voltage, Current
SUPPLY VOLTAGE CODE
24V AC/DC 1
100 - 240V AC -
OPTIONS CODE
RS-485 C5
Setting Value Digital Transmission SVTC
Transmission Power Supply 24 V DC P24
When (option C5) or (option SVTC) is added, the external operation function is not available.
(Option C5) and (Option SVTC) cannot be added together.
When (Option P24) is added, Alarm 2 (A2) is not available.
Distributed By:
High Performance
Temperature & Recording
Instrumentation
...at the lowest prices anywhere!
Shinko is an
ISO 9001 facility
PCD-SNA-08-2003 A
Options
Serial
Communication
(C5)
Each setting change, setting value reading and setting, etc. of PCD-33A can be operated from the external computer. (If option C% is added, external operation function is not available. The option SVTC and external operation cannot be applied together.
Communication interface Based on EIA, RS-485
Data transfer rate
Communication protocol
(2400/4800/9600/19200bps) Selectable by key operation
Based on Shinko standard protocol or Modbus (Selectable by key operation)
(When Modbus is selected, RTU mode or ASCII mode can be selected)
Number of connection units A maximum of 31 units per host computer
Data format
Communication protocol Modbus ASCII Mode Modbus RTU mode
Star bit
Data bit
Parity
Stop bit
1
7
Selectable (Even)
Selectable (1)
1
8
Selectable (Even)
Selectable (1)
Data bit is automatically switched by the selection of communication protocol. ( ): Basic setting value
Setting value digital transmission (master)
If Setting value digital transmission (master) is selected during Communication protocol selection, PCD-33A can be transmitted digitally to the controllers such as JC -33A series (slave) with communication function (option C5).
Wiring example of Setting value digital transmission (A maximum of 31 controller units with communication function
(option C5) can be connected.
Setting Value
Digital
Transmission
(SVTC)
Setting value with digital reception (slave)
If Setting value digital reception (slave) is selected during Communication protocol selection, the setting value can be received from the PC-935/PCD-13A/PCD-33A (master) with Setting value digital transmission (option SVTC). (If the option SVTC is added, external operation function is not availabale, and option C5 and external operation funciton cannot be applied together.)
Transmitter
Power Supply
(P24)
Outputs 24V DC. This is used for the power of 2-wire tranmsitter such as pressure converter. (If the option P24 is applied, Alarm 2 (A2) is not available.)
Output voltage 24V±3V DC (load current 30mA)
Ripple voltage
Max. load current
Within 200mV DC (load current 30mA)
30mA DC
Application Example
Temperature control of tunnel kiln - This is an application that controls tunnel kiln temperatures showing master/slave control that JCD-33A-S/M receives the setting value from PCD-33A with SVTC function.
General Specifications
Mounting Method
Setting Method
Material • Color
Screw type mounting brackets
Sheet key input.
Material: Flame resistant resin. Color: Black
Supply Voltage 100 to 240V AC 50/60Hz, 24V AC/DC 50/60Hz
Allowable voltage fluctuation: 85 to 264V AC, 20 to 28 AC/DC, Power consumption approximately 8VA
Environment
Ambient temperature: -10 to 50ºC Ambient humidity: 35 to 85%RH (No condensation)
ExternaDimension
& Weight
96 x 96 x 98.5mm (W x H x D) Approx. 370g
Attached Function Power failure countermeasures, Self diagnosis, automatic cold junction temperture compensation
(only for thermocouple), Sensor burnout alarms, Input burnout
Program
Number of Patterns
Number of Steps
External Operation
Function
WAIT Function
HOLD Function
ADVANCE Function
Other Functions
Program Time
Range
9 patterns
9 steps/pattern
Program control can be performed/stopped by opening/closing the external contact or open collector. Program control is being performed when the contact is switching from Open to Closed, and stops when the contact is switching from
Closed to Open.
During program run, the program does not proceed to the next step until deviation between PV and SV when step ends enters the WAIT setting value.
Setting Range: ---- Thermocouple, RTD (without decimal point): ±(0 to 100ºC)(ºF)
---- Thermocouple, RTD (without decimal point): ±(0.0 to 100.0ºC)(ºF)
---- DC input: 0 to 1000 (The placement of the decimal point follows the selection)
Program control RUN time is held temporarily.
The step during program control RUN can be stopped and advanced to the next step.
Step time until selection (Hour:Minute or Minute:Second), Program control start type selection (PV start or SV start)
0 to 99 hours and 59 minutes/stpe, or 0 to 99 minutes 59 seconds/step
Time Setting
Accuracy
Within ±0.5% of setting time
Setting Resolution Temperature: 1ºC (1ºF) or 0.1ºC (0.1ºF) Time: 1 minute or 1 second
Status After Power
Failure is Restored
Program starts to perform from the status before power failure.
(Progressing time error after power failure is restored: Max. 1 minute or 1 second
Panel Cutout Wiring Example
All units feature a full
3 year warranty
and lifetime technical support!