- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Rittal
- SK 3302.series
- Operating instructions
advertisement
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
Service - Tel.: (++49) - (0)2772 / 505-1855
Service - Fax: (++49) - (0)2772 / 505-1850
Installation / Operating Instructions
Recooling unit
3318.xxx
®
For exact type designation see type plate
Important:
It is mandatory to read these operating instructions prior to commissioning and to keep these for future use. The manufacturer cannot accept any liability for damage or operating problems resulting from nonobservance of these operating instructions. The right to make technical changes for further development is reserved.
FRIEDHELM L O H GROUP 1
Table of contents:
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
®
Intended use of the cooling system
The system is used for the cooling of water or of a water-glycol mixture.
When using other media (e.g. de-ionised water) please refer to the technical data contained in the appendix, or contact the manufacturer. The limit values given in the technical data must in no case be exceeded.
Warning:
The use of the system for cooling inflammable or explosive substances is prohibited:
Explosion hazard.
FRIEDHELM L O H GROUP 2
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
General notes
These operating instructions are containing basic notes which must be observed during commissioning, operation and maintenance. It is mandatory, therefore, for the fitter and the responsible operating staff/ operator to read these prior to commissioning. They must always be available at the location of the system. It is a must to observe not only the general safety notes given in this section, but also the special safety notes included in the other sections.
Qualification of personnel and training
The personnel for operation, maintenance, inspection, and installation must have the appropriate qualification for this work. The scope of responsibility, competence, and supervision of the personnel must be defined precisely by the operator.
Risks in case of nonobservance of safety notes
In case of nonobservance of the safety notes hazards may occur for personnel, as well as for the environment and the system proper. Nonobservance of safety notes will entail loss of any rights to claim damages.
Safety consciousness at work
The safety notes listed in these operating instructions, the existing national regulations for the prevention of accidents, and also any further internal work, operating, safety regulations must be observed.
Safety notes for the operating company / operator
Any existing contact hazard protection for moving parts must not be removed from plants being in operation.
Hazards due to electrical energy must be excluded. ( → For details on this see, for instance, the VDE regulations and those of the local utilities).
Safety notes for maintenance, inspection, and installation work
On principle, cleaning and maintenance work must be carried out only with the plant in standstill condition. It is mandatory to follow the procedures described in the operating instructions for shut-down of the plant.
Warning! Prior to maintenance work the recooling unit must be switched voltage-free at the input end.
Immediately after completion of this work the safety and protective system must be attached again or their function restored.
Unauthorised modification and production of spare parts
Any modification or change of the plant is allowed only as agreed with the manufacturer. Original spare parts and accessories approved by the manufacturer enhance safety. The use of other parts can make void the liability for the consequences arising from this.
Unallowable operating modes
The operational reliability of the system supplied is ensured only in case of intended use. The limit values given in the technical data must in no case be exceeded.
Health hazards originating from the refrigerant
There is only very little risk to the health originating from the refrigerant. Narcotic properties are met only in case of very high concentrations. Following direct effect of very high concentrations this is eliminated again very quickly via the lungs. The refrigerant can have a certain irritating effect on skin and mucous membranes. The effect of liquid refrigerant on the skin may cause frostbite. In the presence of open fire or hot surfaces refrigerants may decompose and form poisonous decomposition products (e.g. hydrogen chloride, phosgene).
The refrigerant volatises when escaping in gaseous form into the open. An intentional discharge is not allowed.
Refrigerating systems must be positioned in a way that they do not become damaged due to internal traffic and transport processes.
®
FRIEDHELM L O H GROUP 3
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
3. Transport and handling
ATTENTION:
Please note when using water refrigerant!
When the recooling unit is stored or transported at temperatures below freezing point the consumer circuit must be drained completely and if necessary flushed with a water-glycol mixture for preventing frost damage.
This also applies to the cooling circuit for water-cooled condensers.
Until first start-up the cooling system may be transported only in its original packaging material. In case of damage the manufacturer must be informed immediately. If the unit is being moved inside the works all connections must be disconnected from the unit. Moving of the unit must be done in a manner that no damage can occur. If damage should occur in spite of these notes, the unit must be inspected prior to renewed start-up by an expert and be repaired if necessary.
A possibly existing tank must be emptied prior to transportation.
When preventing the recooling system the weight specified on the type plate must be taken into consideration. A fork lift truck or transport device of the appropriate carrying capacity should be used.
For preventing damage on transport:
• The unit may be transported in upright position only.
• Suspend the recooling unit for transport only at the lifting rings provided for this purpose or on the pallet supplied with it.
• Strong shocks during transport must be prevented.
®
FRIEDHELM L O H GROUP 4
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
4. Installation
Conditions for Installation
• The site of the recooling unit should be, if possible, directly next to the consumers for avoiding long distances and line losses connected with this. Line losses are mainly caused by:
- Pressure loss in line system caused by piping resistance and separate resistance due to shut-off fittings and pipe bends.
- Heat transfer at non-insulated pipelines due to prevailing temperature differential along the piping system.
• The site for the recooling unit chosen should be such that – in case of service intervals or repair work - easy access is possible at any time. This facilitates maintenance and repair.
• It must be assured that the fans are not working in "air short-circuit". Air short-circuits may cause loss of performance of the recooling unit. If ventilation of the room in which the recooling unit is placed is insufficient room temperature may increase due to accumulated waste heat. This may cause a decrease of performance of the cooling unit.
IMPORTANT:
When installing the recooling unit attention should be paid to the following:
• With air-cooled recooling units the following minimum distances to wall and ceiling must be maintained:
Wall:
Minimum 1 x height of condenser
Ceiling:
Minimum 3 x height of condenser
• The connection of a duct for fresh and exhaust air is allowed only following prior release by the manufacturer →loss of performance (air-cooled recooling unit).
• Do not place the recooling unit in the vicinity of a heating device →loss of performance.
• The recooling unit may be positioned only on level firm surfaces . The maximum deviation from the vertical is 2° ensuring a safe stand.
• The consumer to be cooled is to be connected to the recooling unit by means of insulated piping or hose connections.
• If the consumer is positioned on a higher level than the recooling unit a non-return valve is to be installed in the feed line and a solenoid valve in the return line →to prevent the tank from flowing over.
• With recooling units to be sited in the open under a roof the minimum outside temperature should be taken from the technical data.
• With recooling units (for water) with a tank at below-zero temperatures a water-glycol mixture of the
specified ratio, Æ see technical data, is to be filled in.
• When it is possible to shut-off the consumer circuit an appropriate bypass must be provided to protect the pump.
• The circulation pump must never run dry Æ otherwise the pump will be damaged.
®
FRIEDHELM L O H GROUP 5
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
5. Electrical
It is mandatory to observe the following notes:
• The electrical connection, in accordance with the type plate , may be made only by authorised specialist personnel.
• Recooling units must always be integrated into the potential equalisation.
• The conductor cross sections of the power cables must be selected according the rated current (see nameplate).
• The max. voltage drop must not exceed 10%.
• With three-phase current systems the connection must be made with a clockwise rotating field.
• The cooling system must be connected to the mains by means of a disconnecting device ensuring a minimum contact gap of 3 mm in switched-off condition.
• With a transformer installed (option) one must check whether it is connected to the correct terminal (on primary side).
6. Start-up
•
When connecting the recooling unit to the fluid circuit to be cooled the latter should always be flushed. This procedure prevents any depositions existing in the fluid circuit to contaminate the recooling unit which may, under circumstances, cause damage to or failure of the internal pump.
• Unpack unit, place it on a level surface and align it using a spirit-level.
• With air-cooled recooling units the siting selected must be such that no “air short-circuiting”
(hot air exit Å Æ air intake condenser) can occur.
• Observe allowed ambient temperature and wall distance.
• Connect to mains.
• Make media connections.
• Make cooling water connections (water-cooled condenser).
• Nominal width of piping must correspond at least to the nominal width of media connections at unit.
• Fill medium into the unit.
• For closed systems: please prepare an admission pressure of 1.2-2 bar.
• Start up recooling unit.
• Check direction of rotation of motors.
• Vent piping, top up medium.
• Activate cooling water circuit (water-cooled condenser).
• Check connection lines and pipe connections during start-up phase for leak-tightness.
Prolonged standstill
If a prolonged standstill of the system is intended, drain the medium circuit completely. For renewed start-up of the system the same checks are be carried out as with initial start-up.
FRIEDHELM L O H GROUP 6
®
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
7. Hydrological data
In order to prevent problems in the water circuit (this also applies to water-cooled units) it is mandatory to comply with the VEB Cooling water guidelines (VGB-R 455 P).
Antifreeze component in cooling water: see technical data
Cooling water and/ or cold water must not cause sediments of water scale or lose precipitation. It should also be of low hardness, in particular of low carbonate hardness. Particularly with cooling by circulating operation carbonate hardness should not be too high. On the other hand, the water should not be soft to an extent that materials are attacked. When the cooling water is recooled the salt content should not increase due to evaporation to an extent that with increasing concentration of dissolved substances the electric conductivity increases, making the water more corrosive. Therefore, not only a corresponding amount of fresh water must always be added, but also a part of the enriched water must be taken out.
Note:
We have to point out again that without water treatment it is only seldom possibly to achieve satisfactory conditions. The water treatment by the client must ensure that even with extreme conditions depositions and corrosion are avoided.
IMPORTANT
Only fill in distilled or DI water in recooling units specified for this purpose (see data sheet).
Treatment and/ or maintenance of the water in recooling units
The cooling water must meet particular conditions, depending on the installation to be cooled. Depending on its contamination and size and design of the recooling unit a suitable process will then be employed for water treatment and/ or maintenance. The most frequent types of contamination and normal processes for dealing with these in industrial cooling are:
• Mech. contamination:
Filtering of the water using screen filters, gravel filters, cartridge filters, precoated filters
• Hardness too high:
Softening of the water by ion exchange
• Moderate content of mechanical contamination and hardness constituents:
Softening of the water by ion exchange
• Moderate content of chemical contamination:
Inoculation of the water with passivators and/ or inhibitors
• Biological contamination, slime bacteria, and algae:
Inoculation of the water with biocides
®
FRIEDHELM L O H GROUP 7
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
Check water quality regularly.
Evaporation processes at the system water surface have a thickening effect on the system water.
Remove thickened water from the system by water exchange, in order to keep water values within the required limits.
The properties of the water used should not deviate from the hydrological data listed below. pH value 7 - 8,5
Carbonate hardness
Free carbon dioxide
Associated carbon dioxide
Aggressive carbon dioxide
Sulphides
Oxygen
3 - 8° dH
8 - 15 mg/dm
3
8 - 15 mg/dm
3
0 mg/dm 3
Zero
< 10 mg/dm³
Chloride ions
Sulphate ion
Nitrates and nitrites
< 50 mg/dm³
< 250 mg/dm³
< 10 mg/dm³
CSB (chemical oxygen consumption) <7 mg/dm³
Ammonia
Iron
< 5 mg/dm³
Manganese
Conductivity
< 0.2 mg/dm³
< 0.2 mg/dm³
200 – 2200 µS/cm
Residue on evaporation
Potassium permanganate consumption
Suspended matter
< 500 mg/dm³
< 25 mg/dm³
< 3 mg/dm³
3 – 15 mg/dm³
> 15 mg/dm³
Split stream cleaning recommended
Continuous cleaning recommended
®
FRIEDHELM L O H GROUP 8
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
8. Maintenance
The cooling circuit which is a hermetically sealed system has been filled at works with the required volume of refrigerant, tested for leak tightness, and subjected to a functional trial run.
Attention!
Prior to maintenance work the recooling unit must be switched voltage-free at the input end.
Important!
• For ensuring proper function of the recooling unit it is a must to take care that the laminae of the air-cooled condenser are kept clean.
• Oil-containing ambient air in combination with dust will cause increased dirt deposition on the condenser laminae. Here, the following should be observed:
Simply sweeping the outside with the fan running will not afford thorough cleaning. It is absolutely necessary to use oil-solving agents, like cleaner's naphtha, or similar, for cleaning and we recommend using a spray gun for penetrating into the depth of the condenser. When doing this, functional components, mounted in the lower part, must be well covered in order to remove the flushed contamination and to prevent damage to surrounding components. Cleaning should be done at regular intervals with the frequency depending on the degree of contamination in the room where the system is put up.
With cooling of / with water or similar media please pay attention always to:
• Solid matter residues (clean used filters regularly, if applicable)
• Algae and depositions
• Corrosion may cause irreversible damage to the recooling unit. Such residues will always have the effect that the performance of the recooling unit can suffer. The manufacturer's guarantee and liability become void in cases of incorrect use and treatment of the recooling unit. In such cases we do not accept any liability for damage.
®
FRIEDHELM L O H GROUP 9
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
Summary of service activities recommended by us
Compressor
• No servicing is required with fully hermetic compressors.
Fan (air-cooled recooling unit)
• Check noise level
Æ ½ year
Condenser (air-cooled recooling unit)
• Clean laminae by compressed air or by sweeping
Æ 2 months
• Clean filter mat
Æ 4 weeks
Condenser (water-cooled recooling system)
Please note the special data in the appendix
Inspection glass cooling circuit (unit-specific)
• Check moisture indicator, green for dry = OK, yellow for moist, possible moisture in cooling circuit or condenser defect
Æ ½ year
Consumer medium
• Check medium circuit for contamination and possible solid matter (chips or similar)
Æ 4 weeks
Tank, components, and all connections (piping, valves and fittings, hoses) of consumer circuit
• Check for leaks
Æ 1 week
Filling level medium
• Check for sufficient filling level, top up if necessary
Æ 1 week
Electrical connections
• Check terminals and connections
Æ ½ year
9. Shutting down / disposing the cooling system
Shutting down / disposing the recooling unit may be carried out only by authorised expert personnel.
Because the refrigerant will volatise when escaping in gaseous form into the open intentional blowing off is not permitted. The refrigerant and the components of the cooling unit must be disposed of in accordance with the rules of the trade and local regulations. The same applies to the oil in the compressor and possibly present waste water.
FRIEDHELM L O H GROUP 10
®
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
10. General fault analysis
Insufficient cooling performance resp. low air outlet temperature from condenser at ambient temperature.
Refrigerant shortage
Increased condenser
pressure
When the allowed condenser pressure is exceeded the high-pressure limiter will trip and switch off the compressor.
An indicator light or a fault indicator (option) gives a fault message.
- Refrigerant shortage is announced by a marked drop of cooling performance. The cooling circuit is leaking in this case.
Remarks
- Eliminate leakage and top up cooling circuit again.
The cooling circuit may be repaired by a specialist firm only. In case of cooling circuit problems please contact the manufacturer.
- Too high ambient temperature (see technical data)
- Nonobservance of required distances
(see siting)
- A specialist is needed for manual resetting of the highpressure limiter
Evaporator pressure
If the required evaporator pressure is not reached the low-pressure limiter (option) trips and switches off the compressor.
An indicator light or a fault indicator (option) gives a fault message.
Compressor is continuously being switched on and off
- Too high feed medium temperature (see technical data)
- Water-flow controller defective (with watercooled units only)
- Contamination of cooling water inlet / outlet
(with water-cooled units only)
- Cooling water temperature outside limits
(with water-cooled units only, see technical data)
- Cooling water shortage (with water-cooled units only, see technical data)
- Too low ambient temperature (see technical data)
- Expansion valve or capillary tube defective
- Operation solenoid valve defective (if existing, see wiring plan)
- When using evaporating coils in tank: not enough medium in tank
- The evaporating coils must be covered completely by the medium.
- Cooling performance of recooling system too high
- Differential gap of controller too small - Check parameter setting
- Medium temperature too high - Check temperature of medium
®
FRIEDHELM L O H GROUP 11
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
Remarks
Unit does not work
- Contactor defective
Compressor, pump, and fan are working
- Condenser or air inlet filter heavily contaminated
Cooling performance low
Current input high
- Air short-circuit: hot air is taken in again because of obstacles at place of siting
- Check function and rating of current supply.
- Cleaning without using any aggressive agents
- Remove obstacles or re-direct air flow
Insufficient cooling effect and condensate formation at condenser
Compressor without function
An indicator light or a fault indicator (option) gives a fault message.
-
-
Volume flow through evaporator too low
Thermal stop of compressor (motor circuitbreaker)
- Check function of pump
- Check heat loss of hydraulic circuit
- Condenser pressure too high
(contaminated air filter or condenser)
Fan without function
An indicator light or a fault indicator (option) gives a fault message
Pump without function
An indicator light or a fault indicator (option) gives a fault message
No medium circulation
An indicator light or a fault indicator (option) gives a fault message
- Thermal stop of fans (motor circuit-breaker)
- Thermal stop of pumps (motor circuitbreaker)
- Valve shut possibly
- Ambient temperature too high
(>45° C)
- High pressure loss (Obstacles in area of air outlet).
- Compare pressure of pump with data on nameplate
- Cooling insufficient (air inlet contaminated)
- Open the valve in question
While in continuous operation, the recooling system is in stable operating condition. The recooling system keeps the medium feed temperature at the set desired value.
Possible causes for deviation from desired value could be:
- Cooling demand too high (see technical data)
- Too high ambient temperature (see technical data)
- Required distances are not held (see technical data) contaminated
- Refrigerant shortage (bubble formation in inspection glass)
- Medium level too low in tank (not with once-through cooler)
- Medium temperature set too low (see technical data) set incorrectly
®
FRIEDHELM L O H GROUP 12
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
11. Appendix
• Technical data
• P+ID Schematics
• Wiring plan
• Description of components
®
FRIEDHELM L O H GROUP 13
Technische Daten
Technical data
Caractéristiques techniques
Dati tecnici
R i t t a l GmbH & Co. KG
Auf dem Stützelberg
D – 3 5 7 4 5 H e r b o r n
Service - Tel.: (++49) - (0)2772 505-1855
Service - Fax: (++49) - (0)2772 505-1850
SK3335.069, WA Nr.: 6952001/001, Masch.-Nr. 06 06 19
Deutsch English Français Italiano
Netzfrequenz nominale
Mains frequency Fréquence du réseau
Tensione nominale
Frequenza di rete
400 V / 3~ / PE
50 Hz
12 A tension de contrôle nominale
Controlli la tensione
24VDC / 230 VAC
Anschlussleistung démarrage
Connected load Puissance connectée frigorifique
Corrente di spunto
Potenza allacciata
Potenza frigorifera
Kältemittel Refrigerant Agent réfrigérant Refrigerante
3 x I
Nenn
4200 W
6000 W
T
W1
= +18°C / T
U
= +32°C
R407 C
Kältemittelmenge Refrigerant quantity
Temperaturbereich Umgebung
Temperature range ambient
Tank air
Tank capacity
Quantité de réfrigérant
Zone de température de l'air ambiant
Capacité de réservoir
Quantità di refrigerante
Gamma di temperatura dell'aria ambiente
Volume utile vasca
3,5kg
+10°C bis +43C
150 ltr.
Geräuschpegel Noise level Niveau sonore Livello di rumorosità
70 dB(A)
Gewicht Weight Poids Peso
Dimensions Dimensions Dimensioni
280 kg
Tiefe Depth Profondeur Profondità
1200 mm
2000 mm
600 mm
Temperatur
Vorlauf
Temperature outlet
Température vidange
Temperatura scarico
Hysterese Hysteresis Hystérésis Isteresi
+18°C
+2 K
Nennförderleistung
Rohranschluss,
Vorlauf
Rohranschluss,
Rücklauf
Rated delivery power
Pipe connection, outlet
Pipe connection, inlet
Puissance nominale de débit
Connexion de tuyau, vidange
Connexion de tuyau, admission
Potenza nominale di flusso
Connessione tubo, scarico
Connessione tubo, immissione
21,5 ltr./min bei
0,5bar absolut
1 ¼“ IG
1 ¼“ IG
Frostschutzanteil Anti-frost agent content
Part de l'antigel
Wir empfehlen: We recommend: Fournisseur préconisé:
Percentuale antigelo
Nostra direttiva interna:
30 % max
Clariant
Typ Type Type Tipo Antifrogen N
®
FRIEDHELM L O H GROUP
0 1
Plant designation
Maschine number
Drawing number
Incoming supply
Control voltage max. power supply max. current supply
2 3 4 5
RITTAL GmbH & Co. KG
Auf dem Sttzelberg
D-35745 Herborn http://www.rittal.de
SK 3335.169
06 06 19
06 06 19
6
3 x 400V/PE
24VDC/ 230VAC
4,2kW
12A
Project leader :
Last change :
Last processor :
22.06.06
TRA
nderung Datum Name
Datum
Bearb.
TRA
Gepr.
Norm
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Cover
7 8 9
ESSE002D
Number of pages 12
Zeichnungsnummer: 06 06 19
2
=
+
Bl.
1
12
Bl.
0 1 2
Table of contents
6
7
8
4
5
9
10
11
12
2
3
Page
1
Name of the page
Cover
Table of contents
Main current
Control circuit
Thermostat
Pump control
Water level control
Fault signal
Flowdiagram
Clamp plan X1
Stckliste
Stckliste
3 4 5 6 7 addition of page Date
22.06.06
22.06.06
22.06.06
22.06.06
22.06.06
22.06.06
22.06.06
22.06.06
22.06.06
22.06.06
22.06.06
22.06.06
8
Processor
TRA
TRA
TRA
TRA
TRA
TRA
TRA
TRA
TRA
TRA
TRA
TRA
9
ESSJ010D
X
X
X
X
X
1
nderung Datum Name
Datum
Bearb.
TRA
Gepr.
Norm
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Table of contents
Zeichnungsnummer: 06 06 19
3
=
+
Bl.
2
12
Bl.
0
-Q0
1 3 5
L1 L2 L3
1 2 3
-Q1
4,5-6,3A
Set: 6A
1 3
2 4
5
13 21
14
5.7
8.1
22
6
4 5 6 7
-Q2
3,5-5A
Ieinst.: 4A
1
2
3
4
5
13 21
6.8
14 22
8.2
6
8 9
L1
/4.0
L3
/4.0
N
/4.0
-K1
5.7
1
2
3
4
5
6
X1 1 2 3 N
PE
PE
L1 L2 L3 N PE
Input
3x400V / PE /50 Hz
PE
X1 5 6 7 PE
-M1
R407C
U1 V1
3
M
~
W1
PE
Compressor
MTZ 28-4
U:400V 50Hz
I:5,5A
P:3,2KW
2
nderung Datum Name
Datum
Bearb.
TRA
Gepr.
Norm
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
PE
X1 8 9 10 PE
-M2
U1 V1
3
M
~
W1
PE
Fan
S 4 D 350
U:400V 50Hz
I:0,34A
P:0,16KW
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Main current
-K2
6.8
5,5KW
1
2
3
4
5
6
Sp1
/6.0
Sp2
/6.0
PE
X1 11 12 13 PE
-M3
U1 V1
3
M
~
W1
PE
CV/+
0V/-
X1 38 39
Pump
MHIE 205-2G
U:400V
I: 4A
P:1,5KW
0...10V Signal
Pump
Zeichnungsnummer: 06 06 19
4
=
+
Bl.
3
12
Bl.
0
3.9/
L1
3.9/
L3
3.9/
N
1 2 3 4 5 6 7 8
-F1
500mA
-F2
500mA
-T1
EKL 1,0 0V 400V
0V 24V
24VDC
2A
-
-
-F1
2A
2
+
+
1
-F3
2A
-F4
2A
-K3
6.4
1
2
3
4
-PE1
X1 42 43 for extern signals
3
nderung Datum Name
Datum
Bearb.
TRA
Gepr.
Norm
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
24VDC
/5.0
0VDC
/5.0
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Control circuit
X1
14
-M4
L1
1
M
~
15
N
PE
PE
PE
Vakuum pump
Zeichnungsnummer: 06 06 19
9
L02
/7.0
N
/7.0
5
=
+
Bl.
4
12
Bl.
0
4.3/
24VDC
1 2 3 4 5
-U1
8.0
MPRA-SMK...-F
A1 11 21 31
.
Stufe 1
A2 12
.
.
14
Stufe 2
.
22
.
.
24
Stufe 3
.
32
.
34
.
F F X1
20 21
-B1
KTY10-6
1
2
-Y1
X1 40
X1
41
X1 16
-P1
P78B
+ -
ND P
A
PE
PE
B
X1 18
- +
HD P
C
X1 17
PE
D
X1
19
PE
4.3/
0VDC
Thermostat
Pressostat
4
nderung Datum Name
Datum
Bearb.
TRA
Gepr.
Norm
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
Probe
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Thermostat
6 7 8 9
24VDC
/6.0
F3
/8.2
F4
/8.2
F5
/8.2
F6
/8.2
-K2
6.8
13
14
38
-Q1
3.3
13
14
-K1
A1
A2
-V1
1
3
5
2 3.3
4 3.3
6 3.3
Compressor
Zeichnungsnummer: 06 06 19
0VDC
/6.0
6
=
+
Bl.
5
12
Bl.
0
5.9/
24VDC
1 2 3 4 5 6 7 8 9
24VDC
/7.0
F2
/8.2
-U2
KS41-1
(L)
(N)
1
2
3
(OUT1)
(OUT2)
(OUT3)
7/-
8
(OUT3)
(OUT3)
9/+
4
5
6
(INP2)
(INP2)
(di1)
(INP1)
(INP1)
(INP1)
10
11
12
13
14
15
X1
22
X1
23
X1
26
-S1
PN 7009 1
X1
3
27 X1
2
28 X1
4
29
-K10T
.5
15
16
Verz
-S2
IFM
TYP: SI10xx
18
/7.8
X1
ELEKTRONISCHER
STROEMUNGSWAECHTER
( Oeffner )
HI-Teach
0 1 2 3 4 5 6 7 8 9
LO-Teach
0 1 2 3 4 5 6 7 8 9
Schaltpunkt
0 1 2 3 4 5 6 7 8 9
Fernabgleich
0 1 2 3 4 5 6 7 8 9
4 1 3 2
30 31 32
-K11T
.6
15
16
-K5
7.4
18
21
22
X1 24
-B2
1
4-20mA
3
25
0-30bar
-Q2
3.7
13
14
3.8/
Sp2
3.8/
Sp1
5.9/
0VDC
-K3
A1
A2
-V3 -K10T
A1
A2
-K11T
A1 B1
A2
-K2
A1
A2
-V2
Remote
Regulator for pump M3
5
nderung Datum Name
Datum
Bearb.
TRA
Gepr.
Norm
22.06.06
1
3
2 4.7
4 4.8
15
18 .6
16 .5
Pressure control
-B2
Pressure control
S1
Vakuum pump
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Pump control
Funktion: R/ 3s
1
3
5
13
2 3.6
4 3.7
6 3.7
14 5.7
Float switch
-S2
Pump
Zeichnungsnummer: 06 06 19
0VDC
/7.0
=
+
Bl.
7
6
12
Bl.
0
6.9/
24VDC
4.9/
L02
1 2 3 4 5 6 7
-K12T
.3
15
16 18
-K7
.7
11
14
6.5/
Verz
8
-K7
.7
21
24
9
24VDC
/8.0
-U3
RIA 452
L
N
41 51 44 54
.
Relais 1
42
.
.
43
.
Relais 2
52
.
.
53
.
Relais 3
45
.
.
46
.
Relais 4
55
.
56
.
PE
81
82
11
12
PE
X1 33 34
-B3
+
S1
1
2
-H1 weiá
-H2 gelb
-K12T
A1
A2
-H3 rot
-K5
A1
A2
4.9/
N
6.9/
0VDC
6
nderung Datum
Function: WU 1s
Water level indicator
Water level "full"
> 40%
15
Water level
"water level indicator"
< 10%
18 .7
16 .7
21
Water level
"dry run"
< 0%
Name
Datum
Bearb.
TRA
Gepr.
Norm
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
22 6.8
Water level sensor
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Water level control
-K7
A1
A2
11
21
14 .7
24 .8
Warning horn
RESET
Zeichnungsnummer:
H5
Warning horn dry run
06 06 19
0VDC
/8.0
8
=
+
Bl.
7
12
Bl.
0
7.9/
24VDC
1 2 3 4 5 6 7 8
-U1
5.2
MPRA-SMK...-F
7
7.9/
0VDC
-Q1
3.4
21
22
-Q2
3.7
21
22
5.9/
F6
5.9/
F5
5.9/
F4
5.9/
F3
6.9/
F2
F1 F2 F3
Fault signal modul
F4 F5 F6 F7 F8 F9 F10
41
42 44
F1: Motor circuit switch
F2: Float control
F3: Temperature low
F4: Temperature to high
F5: Low pressure
F6: High pressure
F7:-
F8:-
F9:-
F10:_
-K6
A1
A2
-H6
nderung Datum Name
Datum
Bearb.
TRA
Gepr.
Norm
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
X1 35
-K6
.5
11
12
36
14
37
Fault signal contact
11
14 .8
12 .8
Fault signal lamp
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Fault signal
Zeichnungsnummer: 06 06 19
9
9
=
+
Bl.
8
12
Bl.
0 1 2 3 4 5 6 7 8 9
1.1
-M1
-P1
HD ND
-M2
5.1
2.1
Vakuum pump
3.1
Y1
4.1
FC
1.1
PIS
IN
R 1 1/4"
LIS
R 1 1/2"
R 1"
Vakuum
PIS
R 1/2"
Vakuum meter
R 1"
21,5l/min.
Fill 1" IG
TC
-U1
-M3
-B1
In 1 1/4" IG
Out 1 1/4" IG
8
nderung Datum Name
Datum
Bearb.
TRA
Gepr.
Norm
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Flowdiagram
Zeichnungsnummer: 06 06 19
10
=
+
Bl.
9
12
Bl.
0
Clamp plan
1 2 3
Name of terminal block X1
Cable name
WX1/-B1
WX1/-B1 wire cable type
1
2
-P1
-K2
-U1
-U1
-B1
-B1
-U2
-B2
-B2
-S1
-U2
-K3
Target- name
L1
L2
L3
N
Connect
-M1
-M1
-M1
-M2
-M2
-M2
-M4
-M4
-K11T
-K11T
-B3
-B3
U1
V1
W1
U1
V1
W1
L1
N
A
13
F5
F6
1
2
2
A1
3
1
1
1
B1
A2
-
+
Cl.-
Nb.
23
24
25
26
19
20
21
22
PE
16
17
18
13
PE
14
15
10
PE
11
12
7
PE
8
9
N
PE
5
6
1
2
3
39
40
41
42
43
35
36
37
38
31
32
33
34
27
28
29
30
Brigde
4 5 6 7 8
-U3
-U3
-K6
-K6
-K6
-U2
-U2
-U1
-T1
-T1
-U2
-K10T
-S1
-S1
-S1
-S2
Target name
L1
L2
L3
N
-Q0
-Q0
-Q0
-K3
-K2
-K2
-K2
-K3
-K3
-U1
-P1
-P1
-P1
-U1
-U1
-U1
-K1
-K1
-K1
-K1
-K1
-K1
Connect
L1
L2
L3
3
Cable name
2
4
6
2
4
14
C
B
F
31
D
F
2
4
6
2
4
6
14
7/-
9/+
14
11
81
11
12
+
-
13
A1
3
2
4
1 wire
Cable type
Side/
Path Function text
5.3
5.5
5.5
6.1
6.1
6.2
6.2
6.3
3.7
3.7
4.7
4.8
4.8
5.2
5.2
5.3
3.3
3.3
3.4
3.4
3.4
3.5
3.6
3.7
3.0
3.0
3.1
3.1
3.1
3.3
3.3
8.7
8.8
8.8
3.8
3.8
5.1
5.1
4.2
4.2
6.3
6.4
6.4
6.6
6.6
6.7
7.6
7.6
for extern signals
=
=
=
Fan
=
=
=
Pump
=
Input
=
=
=
=
Compressor
=
=
=
Vakuum pump
=
=
=
=
Pressostat
=
Probe
=
Remote
=
Pressure control -B2
=
Pressure control S1
=
=
=
Float switch -S2
=
=
Water level sensor
=
Fault signal contact
=
=
0...10V Signal Pump
=
9
nderung Datum Name
Datum
Gepr.
Norm
22.06.06
Bearb.
TRA
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Clamp plan X1
Zeichnungsnummer: 06 06 19
9
ESSK016D
11
=
+
Bl.
10
12
Bl.
0 1 2 3
-K3
-K5
-K6
-K7
-H3
-H6
-K1
-K2
-F3
-F4
-H1
-H2
-B2
-B3
-F1
-F2
-M2
-M3
-M4
-P1
-Q0
-K10T
-K11T
-K12T
-M1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
List of parts
COMPONENT AMOUNT DESIGNATION
DRUCKTRANSMITTER 1/4"
Messwertaufnehmer
Feinsicherungshalter 5x20mm, 2,5qmm
Feinsicherungshalter 5x20mm, 2,5qmm
Feinsicherungshalter 5x20mm, 2,5qmm
Feinsicherungshalter 5x20mm, 2,5qmm
Leuchtmelder mit glatter Linse (ws)
Leuchtmelder mit glatter Linse (ge)
Leuchtmelder mit glatter Linse (rt)
Leuchtmelder mit glatter Linse (rt)
SCHšTZ, 230 V,50/60 Hz, 5,5 KW,1S,
SCHšTZ, 230 V,50/60 Hz, 5,5 KW,1S,
SCHšTZ 24VDC, 5,5kW, 1S
Relais RSS214-24VDC
Relais RSS214-24VDC
Relais RSS214-24VDC
Zeitrelais MRF 24VAC/DC-110-240VAC
Zeitrelais MRF 24VAC/DC-110-240VAC
Zeitrelais MRF 24VAC/DC-110-240VAC
Kompressor MTZ28-4
Lfter S4D-350-AP08-01
Pumpe MHIE 205/2G mit Frequenzumrichter
VAKUUM-PUMPE N026ANE
Duo-Druckw„chter P 78 B
Hauptschalter 9,5kW, 25A, Schwarz
10
nderung Datum Name
Datum
Gepr.
Norm
21.06.06
Bearb.
TRA
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
4
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
5
Stckliste
6
ORDER NUMBER
DRUCKTRANSMITTER 1/4"
942205-9000
ASK 1
ASK 1
ASK 1
ASK 1
3SB32 44-6AA60
3SB32 44-6AA30
3SB32 44-6AA20
3SB32 44-6AA20
3RT10 17-1AP01
3RT10 17-1AP01
3RT1017-1BB41
RSS214-24VDC
RSS214-24VDC
RSS214-24VDC
MRF
MRF
MRF
MTZ28-4
S4D-350-AP08-01
MHIE 205/2G
VAKUUM-PUMPE N026ANE
P 78 B
3LD2103-0TK51
IDENTIFICATION
DRUCKTRANSMITTER 1/4"
MULTICAP T DC11TEN
ASK 1
ASK 1
ASK 1
ASK 1
3SB32 44-6AA60
3SB32 44-6AA30
3SB32 44-6AA20
3SB32 44-6AA20
3RT1017-1AP01
3RT1017-1AP01
3RT1017-1BB41
RSS214-24VDC
RSS214-24VDC
RSS214-24VDC
MRF
MRF
MRF
MTZ28-4
S4D-350-AP08-01
MHIE 205/2G
VAKUUM-PUMPE N026ANE
P 78 B
3LD2103-0TK51
7
Zeichnungsnummer:
8 9
NIL_133E / 02.04.03
SUPPLIER
PAGE
PATH
Wilo 6.1
Endress&Hauser 7.5
Weidmueller 4.2
Weidmueller 4.2
Weidmueller 4.5
4.5
Weidmueller
Siemens 7.2
Siemens 7.2
7.4
Siemens
Siemens
Siemens
Siemens
Siemens
Tele
Tele
Tele
Conta-Clip
Conta-Clip
Conta-Clip
Maneurop
EBM
Wilo
KNF
PENN
Siemens
8.6
5.7
6.8
6.4
7.4
8.5
7.7
6.5
6.6
7.3
3.3
3.4
3.6
4.7
5.2
3.0
06 06 19
12
=
+
Bl.
11
12
Bl.
0 1 2 3 4 5 6
-U2
-U3
-V1
-V2
-V3
-Y1
-Y1
S1
-S2
-T1
-U1
-Q1
-Q2
-S1
S1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
List of parts
COMPONENT AMOUNT DESIGNATION ORDER NUMBER
IDENTIFICATION
Motorschutzschalter 3RV 1011-1GA10 /4,5-6,3
Motorschutzschalter 3RV 1011-1FA10 /3,5-5
Drucksensor PN7009
™ffnerelement 3SB34 00 -0C
3SB30 00-0AA71
Stroemungswaechter SI 1000
Netzteil EKL 1,0
Temperaturregler MPRA-SMK-A-3-KT-F / 24UCV
Temp. regler KS 41
PROZESSANZEIGER
RC Beschaltung 24VAC/DC, S00
RC Beschaltung 127...240VAC, S00
RC Beschaltung 24VAC/DC, S00
Magnetventilspule 24VDC
RC-GLIED 24VUC
3RV 1011-1GA10 /4,5-6,3
3RV 1011-1FA10 /3,5-5
PN7009
3SB34 00 -0C
3SB30 00-0AA71
SI 1000 STROEMUNGSWAECH.
EKL 1,0
MPRA-SMK-A-3-KT-F
KS41-113-000D-000
51008029
3 RT 1916-1CB00
3 RT 1916-1CD00
3 RT 1916-1CB00
SPULE 24VDC
RC-GLIED 24VUC
3RV 1011-1GA10 /4,5-6,3
3RV 1011-1FA10 /3,5-5
PN7009
3SB34 00 -0C
TASTER 3SB30 00-0AA71
SI 1000 STROEMUNGSWAECH.
EKL 1,0
MPRA-SMK-A-3-KT-F
KS41-113-000D-000
PROZESSANZEIGER RIA452
3 RT 1916-1CB00
3 RT 1916-1CD00
3 RT 1916-1CB00
SPULE 24VDC
RC-GLIED
7 8 9
NIL_133E / 02.04.03
SUPPLIER
PAGE
PATH
Siemens 3.3
Siemens 3.6
ifm electronic 6.3
Siemens 7.7
Siemens 7.7
ifm electronic 6.6
MARX 4.1
ers 5.2
PMA 6.0
Endress&Hauser 7.1
Siemens
Siemens
Siemens
CASTEL
5.7
6.9
6.4
5.1
Murrelektronik 5.1
11
nderung Datum Name
Datum
Gepr.
Norm
21.06.06
Bearb.
TRA
22.06.06
WA 6952001/001
SK 3335.169
Urspr.
Ers.f.
Rittal GmbH & Co. KG
Auf dem Sttzelberg
D - 35745 Herborn
Ers.d.
Stckliste
Zeichnungsnummer: 06 06 19
=
+
Bl.
12
12
Bl.
MPR-SMK-A-x-xx-x ENG
Parameter-List for temperature controller MPR-SMK-A-x-xx-x
Working level
Indication Description
Present value The present temperature of the medium as measured is permanently displayed.
Target value Press the SET button to see the target temperature set for output port relay K1.
Press the “RESET” button to reset a failure message
C – Parameter level
Switching to C-Parameter level:
Press the “UP” and “Down” arrow key simultaneously for 5 seconds until “C1”
appears on the display.
Back to working level : Press “UP” and “DOWN” arrow key for 5 seconds.
Indication Description
C1 Target temperature C1 Compressor
Zone
+18°C
C2
C3
C4
C20
C21
C22
C23
C91
C99
Target temperature C2 Temperature high
Target temperature C3 Temperature low
Target temperature C4 (depends on setting in parameter P5)
Hysteresis for target-temperature C1
Hysteresis for target-temperature C2 (if present)
Hysteresis for target-temperature C3 (if present)
Hysteresis for target-temperature C4 (depends on setting in parameter P5)
Actual value correction for sensor (offset value)
Button lock
0 = not locked
1 = locked
+30°C
+5°C
-
1,5K
1K
1K
-
0K
0
Seite 1 von 1
MPR-SMK-A-x-xx-x ENG
P – Parameter level
Switching to P-Parameter level: Jump first into C-Parameter level than press the “UP” arrow key
simultaneously till “C99” appears. Hold down the “UP” arrow key and press
additionally the “Down” arrow key till “P1” is seen on the display.
Back to working level: Press “UP” and “DOWN” arrow key for 5 seconds.
Parameter Description Zone
P1
P2
P3
P4
P5
P6
P7
P10
P11
P12
P13
P15
P16
P17
P18
P20
P21
P22
P23
P24
P25
P26
P27
Switching direction Relay K1
Switching direction Relay K2 (if present)
Switching direction Relay K3 (if present)
0 = Heating contact
1 = Cooling contract
0 = Heating contact
1 = Cooling contract
0 = Heating contact
1 = Cooling contract
0 = Heating contact
1 = Cooling contract
Switching direction Relay K4
(depends on setting in parameter P5)
General function for relay K4
Wire protection function for all fault inputs
0 = control contact
1 = alarm contact
2 = alarm contact for upper- or – lower
target value C4
0 = Fault recognition by “low” input signal
1 = Fault recognition by “high” input signal
0 = Relay K4 is off at alarm or fault signal
1 = Relay K4 is on at alarm or fault singal
Alarmfunction relay K4
(only active if P5 = 1 or 2)
Function K1 in event of sensor failure
Function K2 in event of sensor failure
(if present)
Function K3 in event of sensor failure
(if present)
Function K4 in event of sensor failure
0 = inactive in event of failure
1 = active in event of failure
0 = inactive in event of failure
1 = active in event of failure
0 = inactive in event of failure
1 = active in event of failure
0 = inactive in event of failure
1 = active in event of failure
Hysteresis mode target temperature C1
Hysteresis mode target temperature C2 (if present)
Hysteresis mode target temperature C3 (if present)
Hysteresis mode target temperature C4
(depends on settingin parameter P5)
0 = symmetrical
1 = only on one side
0 = symmetrical
1 = only on one side
0 = symmetrical
1 = only on one side
0 = symmetrical
1 = only on one side
Limit for target temperature C1 downwards -50°C .. +150°C
Limit for target temperature C1 upwards
Limit for target temperature C2 downwards
(if present)
-50°C .. +150°C
-50°C .. +150°C
Limit for target temperature C2 upwards
(if present)
-50°C .. +150°C
Limit for target temperature C3 downwards
(if present)
Limit for target temperature C3 upwards
(if present)
-50°C .. +150°C
-50°C .. +150°C
Limit for target temperature C4 downwards -50°C .. +150°C
Limit for target temperature C4 upwards -50°C .. +150°C
1
0
1
-
1
1
0
0
0
0
0
1
1
1
1
+10°C
+25°C
+30°C
+40°C
+0°C
+5°C
Seite 2 von 2
MPR-SMK-A-x-xx-x ENG
Parameter Description
P30
P31
P32
P33
P34
P35
P36
P37
P50
P51
P52
P53
P54
P55
P56
P57
Limit for hysteresis 1 downwards (parameter C20) 0,1K .. 99,9 K
Limit for hysteresis 1 upwards (parameter C20) 0,1K .. 99,9 K
Limit for hysteresis 2 downwards (parameter C21) 0,1K .. 99,9 K
Limit for hysteresis 2 upwards (parameter C21) 0,1K .. 99,9 K
Limit for hysteresis 3 downwards (parameter C22) 0,1K .. 99,9 K
Limit for hysteresis 3 upwards (parameter C22) 0,1K .. 99,9 K
Limit for hysteresis 4 downwards (parameter C23) 0,1K .. 99,9 K
Limit for hysteresis 4 upwards (parameter C23)
Minimum action time for relay K1
0,1K .. 99,9 K
0...999 Sec.
Minimum pause time for relay K1
Minimum action time for relay K2 (if present)
Minimum pause time for relay K2 (if present)
Minimum action time for relay K3 (if present)
Minimum pause time for relay K3 (if present)
Minimum action time for relay K4 (depends on setting in parameter P5)
Minimum pause time for relay K4 (depends on setting in parameter P5)
0...999 Sec.
0...999 Sec.
0...999 Sec.
0...999 Sec.
0...999 Sec.
0...999 Sec.
0...999 Sec.
P99 Temperature unit °C / °F
0 = °C
1 = °F
Fault And Error Codes
The display shows the relevant fault code in case of a fault. (display flashes)
Code Description
F1 Failure on input 1 Motor circuit breaker
F2 Failure on input 2 Float control
F3 Failure on input 3 Temperature low
F4 Failure on input 4 Temperature high
F5 Failure on input 5 Low pressure
F6 Failure on input 6 High pressure
F7 Failure on input 7 -
F8 Failure on input 8 -
F9 Failure on input 9 -
F10 Failure on input 10 -
E1 Short circuit sensor
E2
Damaged sensor
FFF Exceeded maximum measurement field of sensors
F13 Memory error
Seite 3 von 3
Zone
1K
3K
1K
3K
1K
3K
-
-
0 sec.
0 sec.
0 sec.
0 sec.
0 sec.
0 sec.
0 sec.
0 sec.
0
MPR-SMK-A-x-xx-x ENG
Device
10
Device
9
Device
8
Device
7
Device
6
Device
5
Device
4
Device
3
Device
2
Device
1
Error detection at “low” signal
Error detection at“high” signal
KS
A2 10 9 8 7 6 5 4 3 2 1 Faultinputs
A1
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
1 2
Sensor
3 4 5 6 7 8 9 10 11 12 13 14 15
K1 K2 K3
A1 = Positive operating Voltage / phase L1
A2 = Neutal wire (N)
K1..K3
KS
= Relay contacts
= Relay contact depents on configuration
- Control contact
- Fault contact
- Fault contact and temperature alarm
contact.
A1 A2
Supply
Connecting diagram (the right number of replays are shown of the device label)
Seite 4 von 4
MPR-SMK-A-x-xx-x ENG
Specification of the temperature controller MPR-SMK-x-xx-x
Connecting Diagram
44 41 42 NC
K4:= 230V
10A AC1
10 9 8 7 6 5 4 3 2 1
K1..K3:= 230V 10AC1
Sample – please refer the label of your device
Technical Data
Number of Sensors: 1
Type of Sensor:
Effective range :
KTY 81-210 (PT100)
-50°C bis +150°C
The effective range is only good if you use a right type of sensor and wiring.
Output
Number of outputs: Max. 3 + 1
Output 1 … 4 (K1 .. KS): Two way contact (voltage free)
Max. switching current 10A (1,5)A
Max. switching voltage 250V~
Number of inputs: 10
Note: Connect the inputs always with A1!!
Features
- Two-step regulator
- Free adjustable Hysteresis
- Heating/cooling interchangeable
- Temperature alarm
- Fault indicator with 10 digital inputs
Operation voltage
24V AC with ( 50 ... 60 ) Hz or 230V AC ( 50 … 60 ) Hz
(Use only the operation voltage as shown on the device label)
Connectors
- Screw terminals and plug connectors
- 2 x 15 polar, grid 5,00 mm for 2,5 mm² wire
Display
- 3 digits LED-Display red, 13,0 mm
- 4 LEDs for output status control
- Range of display from –99 to 999
Housing
The regulator is fit for board montage
Front-panel
Front-panel cut-out
Installation depth
( 48 x 96 ) mm
( 42 x 90 ) mm ca. 88 mm
Protection code IP64 (Front panel side)
Ambient temperature
Operating temperature:
Storage temperature:
Max. humidity:
0°C … +50°C
-20°C … +70°C
75 % (no condensation)
Seite 5 von 5
PMA Prozeß- und Maschinen-Automation GmbH
Industrial controller KS 40-1,
KS41-1 and KS42-1
KS40-1
KS41-1
KS42-1
KS40-1
KS41-1
KS42-1
Operating manual
English
9499-040-62711
Valid from: 8415
û
BlueControl
®
More efficiency in engineering, more overview in operating:
The projecting environment for the BluePort controllers
Updates
Mini
ATTENTION!
Version www or
PMA-CD on
Description of symbols:
g
General information
a
General warning
l
Attention: ESD sensitive devices
© PMA Prozeß- und Maschinen-Automation GmbH Printed in Germany
All rights reserved. No part of this document may bereproduced or published in any form or by any means without prior written permission from the copyright owner.
A publication of PMA Prozeß- und Maschinen Automation
P.O.Box 310229
D-34058 Kassel
Germany
Contents
1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Connecting diagram . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Terminal connection. . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1 Front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2 Behaviour after power-on . . . . . . . . . . . . . . . . . . . . . 11
3.3 Operating level . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4 Maintenance manager / Error list . . . . . . . . . . . . . . . . 12
3.5 Self-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.5.1 Preparation for self-tuning . . . . . . . . . . . . . . . . . . . . . . . 14
3.5.2 Self-tuning sequence . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.5.3 Self-tuning start . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.5.4 Self-tuning cancellation . . . . . . . . . . . . . . . . . . . . . . . . 15
3.5.5 Acknowledgement procedures in case of unsuccessful self-tuning . 16
3.5.6 Examples for self-tuning attempts . . . . . . . . . . . . . . . . . . 16
3.6 Manual tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.7 Alarm handling. . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.8 Operating structure. . . . . . . . . . . . . . . . . . . . . . . . . 20
4 Configuration level . . . . . . . . . . . . . . . . . . . . . . . . 21
4.1 Configuration survey . . . . . . . . . . . . . . . . . . . . . . 21
4.2 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.3 Set-point processing . . . . . . . . . . . . . . . . . . . . . . . . 29
4.4 Configuration examples . . . . . . . . . . . . . . . . . . . . . . 30
4.4.1 On-Off controller / Signaller (inverse) . . . . . . . . . . . . . . . . . 30
4.4.2 2-point controller (inverse) . . . . . . . . . . . . . . . . . . . . . . . 31
4.4.3 3-point controller (relay & relay) . . . . . . . . . . . . . . . . . . . . 32
4.4.4 3-point stepping controller (relay & relay) . . . . . . . . . . . . . . . 33
4.4.5 Continuous controller (inverse) . . . . . . . . . . . . . . . . . . . . . 34
4.4.6
- Y - Off controller / 2-point controller with pre-contact . . . . . . 35
4.4.7 KS4x-1 with measured value output . . . . . . . . . . . . . . . . . . 36
Operating KS4x-1 3
5 Parameter setting level . . . . . . . . . . . . . . . . . . . . . . 37
5.1 Parameter survey . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.4 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.5 Input scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.5.1 Input Inp.1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.5.2 Input InP.2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6 Calibration level . . . . . . . . . . . . . . . . . . . . . . . . . 41
7 Programmer . . . . . . . . . . . . . . . . . . . . . . . . . . 44
8 Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
8.1 Setting up the timer . . . . . . . . . . . . . . . . . . . . . . . . 46
8.1.1 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
8.1.2 Tolerance band. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
8.1.3 Timer start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
8.1.4 Signal end . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
8.2 Determining the timer run-time . . . . . . . . . . . . . . . . . . 48
8.3 Starting the timer . . . . . . . . . . . . . . . . . . . . . . . . 48
9 BlueControl . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
11
Technical data
. . . . . . . . . . . . . . . . . . . . . . . . . . 51
12 Safety hints . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
12.1 Resetting to factory setting. . . . . . . . . . . . . . . . . . . . . 56
4 Operating KS4x-1
Mounting
1
Mounting
10
(0.4")
(4.65")
118
SP.X
126
125 run
Ada
Err min.48
(1.89")
1..10
(0.04..0.4")
+0,6 45
(1.77" +0.02
)
KS 40-1 universal
48 (1.89")
Loc 10V i mA/Pt
Safety switch max.
60°C min.
0°C max.
95% rel.
%
Loc 10V mA/Pt
Front view KS41-1
SP.x
126
125 run
Ada
Err
KS 41-1 universal
96 (3.78")
Front view KS42-1
SP.x
run
Ada
Err
126
125
KS 42-1 universal
96 (3.78")
Ü or:
Ü
*
*
Safety switch:
For access to the safety switches, the controller must be withdrawn from the housing. Squeeze the top and bottom of the front bezel between thumb and forefinger and pull the controller firmly from the housing..
10V i mA/Pt right 1
Loc left open
Current signal / Pt100 / thermocouple at InP.1
Voltage signal at InP.1
Access to the levels is as adjusted by means of BlueControl
2 closed
1 all levels accessible wihout restriction
1
Factory setting
2
Default setting: display of all levels suppressed, password PASS = OFF a Safety switch 10V i mA/Pt always in position left or right. Leaving the safety switch open may lead to faulty functions!
l Caution! The unit contains ESD-sensitive components.
Operating KS4x-1 5
Electrical connections
2
Electrical connections
2.1 Connecting diagram
Modbus RTU
RGND
DATA B
RXD-B
GND
RXD-A
TXD-B
DATA A TXD-A
RS485 RS422 di2 di3
U
T
Option
9
10
11
7
8
12
13
14
15
(16)
17
3
4
5
6
1
(2) a
7
8
9
4
5
6
1
2
3
10
11
12
13
14
15
L
N
90...250V
24V AC/DC
e
Logic c d b
U
OUT1
OUT2
OUT3
HC mA mA INP2 di1
0..10 V*
INP1 a b c d
* Safety switch mA i V in position left g Dependent of order, the controller is fitted with : w flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to DIN 46 244 or screw terminals for 0,5 to 2,5mm²
2.2 Terminal connection
Power supply connection 1
See chapter 11 "Technical data"
Connection of input INP1 2
Input for variable x1 (process value)
a thermocouple
b resistance thermometer (Pt100/ Pt1000/ KTY/ ...)
c current (0/4...20mA)
d voltage (0/2...10V)
Connecting diagram 6 Operating KS4x-1
Electrical connections
Connection of input INP2 3
Heating current input (0...50mA AC) or input for ext. set-point (0/4...20mA)
Connection of input di1 4
Digital input, configurable as switch or push-button
Connection of outputs OUT1/2 5
Relay outputs 250V/2A normally open with common contact connection
Connection of output OUT3 6
a relay (250V/2A), potential-free changeover contact universal output
b current (0/4...20mA)
c voltage (0/2...10V)
d transmitter supply
e logic (0..20mA / 0..12V)
Connection of inputs di2/3 7 (option)
Digital inputs (24VDC external), galvanically isolated, configurable as switch or push-button
Connection of output U
Supply voltage connection for external energization
T
8 (option)
Connection of bus interface 9 (option)
RS422/485 interface with Modbus RTU protocol
3 INP2 current tansformer
7
8
9
4
5
6
1
2
3
10
11
12
13
14
15
Logic
7
8
9
4
5
6
1
2
3
10
11
12
13
14
15
+
SSR
_
+
5 OUT1/2 heating/cooling
N
L
N
L
Operating KS4x-1 7 Terminal connection
Electrical connections
7 8 di2/3, U
T
2-wire transmitter supply
+24VDC
3
0V
1
+
2
-
K
17,5V
22mA
5mA
5mA
+
-
Option
10
11
12
13
14
15
(16)
17
1
(2)
7
8
9
5
6
3
4
J x
4
5
6
1
2
3
7
8
9
10
11
12
13
14
15
+
-
OUT3
6 OUT3 transmitter supply
-
+
13V
22mA
+
-
3
2
1
K a If U
T and the universal output OUT3 is used there may be no external galvanic connection between measuring and output circuits!
6 OUT3 as logic output with solid-state relay (series and parallel connection)
Series connection
Logic
3
4
5
6
10
12V
4V
4V
4V
+
SSR
_
+
SSR
_
+
SSR
_
Parallel connection
12V
SSR
_
+
SSR
_
+
Terminal connection 8 Operating KS4x-1
Electrical connections
9 RS485 interface (with RS232-RS485 interface converter) *
R
T
RGND
DATA B
DATA A
12
13
14
15
(16)
17
10
11
12
13
14
15
RGND
DATA B
DATA A
12
13
14
15
(16)
17
10
11
12
13
14
15
RGND
DATA B
DATA A
12
13
14
15
(16)
17
R=100 Ohm
10
11
12
13
14
15
RGND connection optional max. 1000m
”Twisted Pair” R
T
J
PC converter
RS485-RS232
* Interface description Modbus RTU in seperate manual: see page 50.
KS4x-1 connecting example:
L1
L2
KS 40-1
1
2
3
Logic
7
8
9
4
5
6
10
11
12
13
14
15 fuse
SSR
_
+
+ fuse contactor heating
TB 40-1 1
Temperature limiter
1
2
3
7
8
9
4
5
6
10
11
12
13
14
15
+ reset fuse
N1
N2
1 TB 40-1 Temperature limiter
Standard version (3 relays):
TB40-100-0000D-000 r other versions on request a CAUTION: Using a temperature limiter is recommendable in systems where overtemperature implies a fire hazard or other risks.
Operating KS4x-1 9 Terminal connection
Operation
3
Operation
3.1 Front view
KS40-1
0
!
$
SP.x
1 2 3 OK
126.
125
KS 40-1 universal
SP.x
KS41-1
126
125 run
Ada
Err
KS 41-1 universal
SP.x
run
Ada
Err
KS 42-1 universal run
Ada
Err
1
2
3
5
6
7
8
4
"
KS42-1
126
125
1 Status of switching outputs
OuT.1... 3
2 Lit with limit value 1 ( PArA /
Lim ) not exceeded
3 Process value display
4 Set-point, controller output
5 Signals ConF and PArA level
6 Programmer or timer running
7 Self-tuning active
8 Entry in error list
9 Set-point SP.2 or SP.E is effective
0 Set-point gradient effective
! Manual/automatic switch-over:
Off: Automatic
On: Manual
(changing possible)
Blinks: Manual
(changing not possible
(r ConF/ Cntr/ MAn)
" Enter key: calls up extended operating level / error list
§ Up/down keys: changing the set-point or the controller output value
$ Manual mode /spec. function
( ConF / LOGI )
% PC connection for
BlueControl (engineering tool)
LED colours:
LED 1, 2, 3:
LED OK: other LEDs: yellow green red g In the upper display line, the process value is always displayed. At parameter, configuration, calibration as well as extended operating level, the bottom display line changes cyclically between parameter name and parameter value.
Front view 10 Operating KS4x-1
Operation
3.2 Behaviour after power-on
After supply voltage switch-on, the unit starts with the operating level.
The unit is in the condition which was active before power-off.
If KS4x-1 was in manual mode before power-off, the controller starts with correcting value Y2 after switching on again.
3.3 Operating level
The content of the extended operating level is determined by means of BlueControl (engineering tool). Parameters which are used frequently or the display of which is important can be copied to the extended operating level.
Automatic Manual time out
126
125
È
Ì
Ù i Ò i
Ò
126 y 21
È
Ì
Ù time out
126 y 21
Ù only display
126
125
È
Ì
Ù
Extended operating level
time out
Errorliste
(if error exists)
126
FbF.1
Err display switching
126
2
Err
Operating KS4x-1 11 Behaviour after power-on
Operation
3.4 Maintenance manager / Error list
With one or several errors, the extended operating level always starts with the error list. Signalling an actual entry in the error list (alarm, error) is done by the Err LED in the display. To reach the error list press Ù twice.
SP.x
126
125 run
Ada
Err
Err LED status
(Status 2) error
Signification
Alarm due to existing
Error removed,
Alarm not acknowledged
No error, all alarm entries deleted
Proceed as follows
- Determine the error type in the error list via the error number
- -Change to status 1 after error removal.
- Acknowledge the alarm in the error list pressing key È or Ì
- The alarm entry was deleted (Status 0) .
-Not visible except when acknowledging
Error list:
Name
E.1
E.2
E.4
FbF.1
Sht.1
POL.1
FbF.2
Sht.2
POL.2
HCA
SSr
Description
Internal error, cannot be removed reset
Hardware error
Cause
- E.g. defective EEPROM
- e.g. EMC trouble
- Codenumber and hardware are not identical
Sensor break INP1 - Sensor defective
- Faulty cabling
Short circuit INP1 - Sensor defective
- Faulty cabling
INP1polarity error - Faulty cabling
Sensor break INP2 - Sensor defective
- Faulty cabling
Short circuit INP2 - Sensor defective
INP2 polarity
(HCA)
- Faulty cabling
- Faulty cabling
- Heating current circuit interrupted, I< HC.A or I>
HC.A (dependent of configuration)
- Heater band defective
- Current flow in heating circuit with controller off
- SSR defective
Possible remedial action
- Contact PMA service
- Return unit to our factory
- Keep measurement and power supply cables in separate runs
- Ensure that interference suppression of contactors is provided
- Contact PMA service
- Elektronic-/Optioncard must be exchanged
- Replace INP1 sensor
- Check INP1 connection
- Replace INP1 sensor
- Check INP1 connection
- Reverse INP1 polarity
- Replace INP2 sensor
- Check INP2 connection
- Replace sensor INP2
- Check INP2 connection
- Reverse INP2 polarity
- Check heating current circuit
- If necessary, replace heater band
- Check heating current circuit
- If necessary, replace solid-state relay
Maintenance manager / Error list 12 Operating KS4x-1
Operation
Name
LooP
AdA.H
AdA.C
LiM.1
Lim.2
Lim.3
Inf.1
Inf.2
Description
(LOOP)
Cause
- Input signal defective or not connected correctly
- Output not connected correctly
- See Self-tuning heating error status alarm
(ADAH) alarm cooling
(ADAC)
- See Self-tuning cooling error status stored limit alarm 1 - adjusted limit value 1 exceeded stored limit alarm 2 - adjusted limit value 2 exceeded stored limit alarm 3 - adjusted limit value 3 exceeded duty cycle message
(digital ouputs)
- adjusted number of operating hours reached
- adjusted number of duty cycles reached
Possible remedial action
- Check heating or cooling circuit
- Check sensor and replace it, if necessary
- Check controller and switching device
- see Self-tuning heating error status
- see Self-tuning cooling error status
- check process
- check process
- check process
- application-specific
- application-specific g Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital input di1/2/3 or the Ò-key.
Configuration, see page 27: ConF / LOGI / Err.r
g If an alarm is still valid that means the cause of the alarm is not removed so far
(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.
Self-tuning heating ( ADA.H) and cooling ( ADA.C) error status:
Error status
0
3
4
5
6
7
8
Description
No error
Faulty control action
Low reversal point
Behaviour
Re-configure controller (inverse i direct)
The control loop is perhaps not closed: check sensor, connections and process
Increase ( ADA.H) max. output limiting Y.Hi or decrease ( ADA.C) min. output limiting Y.Lo
If necessary, increase (inverse) or reduce (direct) set-point
(dy > 5%) ( ADA.C) min. output limiting Y.Lo
Set-point reserve too small Increase set-point (invers), reduce set-point (direct) or increase set-point range
(r PArA / SEtp / SP.LO and SP.Hi )
Operating KS4x-1 13 Maintenance manager / Error list
Operation
3.5 Self-tuning
For determination of optimum process parameters, self-tuning is possible.
After starting by the operator, the controller makes an adaptation attempt, whereby the process characteristics are used to calculate the parameters for fast line-out to the set-point without overshoot.
The following parameters are optimized when self-tuning:
Parameter set 1:
Pb1 - Proportional band 1 (heating) in engineering units [e.g. °C] ti1 - Integral time 1 (heating) in [s] r only, unless set to OFF td1 - Derivative time 1 (heating) in [s] r only, unless set to OFF t1 - Minimum cycle time 1 (heating) in [s] r only, unless Adt0 was set to
“no self-tuning” during configuration by means of BlueControl ®.
Pb2 - Proportional band 2 (cooling) in engineering units [e.g. °C] ti2 - Integral time 2 (cooling) in [s] r only, unless set to OFF td2 - Derivative time 2 (cooling) in [s] r only, unless set to OFF t2 - Minimum cycle time 2 (cooling) in [s] r only, unless Adt0 was set to
“no self-tuning” during configuration by means of BlueControl ®
3.5.1 Preparation for self-tuning w Adjust the controller measuring range as control range limits. Set values rnG.L and rnG.H to the limits of subsequent control. (Configuration rControllerrlower and upper control range limits)
ConFrCntrr rnG.L and rnG.H
w Determine which parameter set shall be optimized (see tables above).
3.5.2 Self-tuning sequence
The controller outputs 0% correcting variable or Y.Lo and waits, until the process is at rest (see start-conditions on page 8).
Subsequently, a correcting variable step change to 100% is output.
The controller attempts to calculate the optimum control parameters from the process response. If this is done successfully, the optimized parameters are taken over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.
After completing the 1st step as described, a correcting variable of -100% (100% cooling energy) is output from the set-point.
After successfull determination of the “cooling parameters”, line-out to the set-point is using the optimized parameters.
Self-tuning 14 Operating KS4x-1
Operation
Start condition: w Rest condition
For process evaluation, a stable condition is required. Therefore, the controller waits until the process has reached a stable condition after self-tuning start.
The rest condition is considered being reached, when the process value oscillation is smaller than 0,5% of (rnG.H - rnG.L).
Set-point reserve
After having come to rest with 0% correcting variable or with Y.Lo, the controller requires a sufficient set-point reserve for its self-tuning attempt, in order to avoid overshoot.
Sufficient set-point reserve: inverse controller:(with process value<set-point-(10% of SP.Hi - SP.LO) direct controller:(with process value>set-point+ (10% of SP.Hi - SP.LO)
3.5.3 Self-tuning start g Self-tuning start can be locked via BlueControl
(engineering tool) ( P.Loc).
The operator can start self-tuning at any time.
For this, keys Ù and È must be pressed simultaneously. The AdA LED starts blinking. The controller outputs 0% or Y.Lo, waits until the process is at rest and starts self-tuning (AdA
LED lit permanently).
SP.x
126
125
After successful self-tuning, the AdA-LED is off and the controller continues operating with the new control parameters.
run
Ada
Err
3.5.4 Self-tuning cancellation
By the operator:
Self-tuning can always be cancelled by the operator. For this, press Ù and È key simultaneously. With manual-automatic switch-over configured via Ò key, self-tuning can also be canceled by actuating Ò key. The controller continues operating with the old parameters in automatic mode in the first case and in manual mode in the second case.
By the controller:
If the Err LED starts blinking whilst self-tuning is running, successful self-tuning is prevented due to the control conditions. In this case, self-tuning was cancelled by the controller.
Dependent of control type, the output status is: w 3-pnt. stepping controller: actuator is closed (0% output) w 2-pnt./ 3-pnt./ continuous controller:
If self-tuning was started from the automatic mode, the controller output is
0%. With self-tuning started from manual mode, the controller output is Y2.
Operating KS4x-1 15 Self-tuning
Operation
3.5.5 Acknowledgement procedures in case of unsuccessful self-tuning
1. Press keys Ù and È simultaneously:
The controller continues controlling using the old parameters in automatic mode. The Err LED continues blinking, until the self-tuning error was acknowledged in the error list.
2. Press key Ò (if configured):
The controller goes to manual mode. The Err LED continues blinking, until the self-tuning error was acknowleged in the error list.
3. Press key Ù :
Display of error list at extended operating level. After acknowledgement of the error message, the controller continues control in automatic mode using the old parameters.
Cancellation causes: r page 13: "Error status self-tuning heating ( ADA.H) and cooling ( ADA.C)"
3.5.6 Examples for self-tuning attempts
(controller inverse, heating or heating/cooling)
Start: heating power switched on
Heating power Y is switched off (1).
When the change of process value X was constant during one minute (2), the power is switched on (3).
At the reversal point, the self-tuning attempt is finished and the new parameter are used for controlling to set-point W.
Start: heating power switched off
The controller waits 1,5 minutes (1).
Heating power Y is switched on (2).
At the reversal point, the self-tuning attempt is finished and control to the set-point is using the new parameters.
X
W
100%
Y
0%
Start r 1
X
W blinks
100%
Y
0% start r 1 blinks
2
2
3 t reversal point t reversal point t t
Self-tuning 16 Operating KS4x-1
Operation
Start: at set-point
Heating power Y is switched off (1).
If the change of process value X was constant during one minute and the control deviation is > 10% of SP.Hi -
SP.LO (2), the power is switched on
(3). At the reversal point, the self-tuning attempt is finished, and control to set-point W is using the new parameters.
X
W
100%
Y
0% start r 1 blinks
2
3 t reversal point t
Three-point controller
The parameters for heating and cooling are determined in two attempts.
The heating power is switched on
(1). At reversal point 1, heating parameters Pb1, ti1, td1 and t1 are determined. The process value is lined out to the set-point (2). The
X
W
+100%
Y 0%
-100% start r 1 t reversal point 1
2 3 t t reversal point 2 cooling power is switched on (3). At reversal point 2, parameters Pb2, ti2, td2 and t2 are determined and the self-tuning attempt is finished. Control to set-point W is using the new parameters.
3.6 Manual tuning
The optimization aid should be used with units on which the control parameters shall be set without self-tuning.
For this, the response of process variable x after a step change of correcting variable y can be used. Frequently, plotting the complete response curve (0 to 100%) is not possible, because the process must be kept within defined limits. Values T and x max
(step change from 0 to 100 %) or t and x (partial step response) can be used to determine the maximum rate of increase v max
.
g y
100%
0%
Xmax
Yh x
Tg t y = correcting variable
Y h
= control range
Tu = delay time (s)
Tg = recovery time (s)
X max
= maximum process value
Tu
{t
{X t
V max
Tg { x t
= max. rate of increase of process value
Operating KS4x-1 17 Manual tuning
Operation
The control parameters can be determined from the values calculated for delay time T u
, maximum rate of increase v oscillates.
max
, control range X h and characteristic K according to the formulas given below. Increase Xp, if line-out to the set-point
Parameter adjustment effects
Parameter Control Line-out of disturbances
Pb1 higher increased damping slower line-out
Start-up behaviour slower reduction of duty cycle lower reduced damping faster line-out faster reduction of duty cycle td1 higher reduced damping faster response to disturbances faster reduction of duty cycle lower increased damping slower response to disturbances slower reduction of duty cycle ti1 higher increased damping slower line-out slower reduction of duty cycle lower reduced damping faster line-out faster reduction of duty cycle
K = Vmax * Tu
With 2-point and
3-point controllers, the cycle time must be adjusted to t1 / t2 £ 0,25 * Tu
Formulas
controller behavior Pb1 [phy. units]
PID 1,7 * K
PD
PI
P
3-point-stepping
0,5 * K
2,6 * K
K
1,7 * K td1 [s]
2 * Tu
Tu
OFF
OFF
Tu ti1 [s]
2 * Tu
OFF
6 * Tu
OFF
2 * Tu
3.7 Alarm handling
Max. three alarms can be configured and assigned to the individual outputs. Generally, outputs OuT.1... OuT.3 can be used each for alarm signalling. If more than one signal is linked to one output the signals are OR linked. Each of the 3 limit values Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which can be switched off individually (parameter = “OFF”). Switching difference
HYS.x of each limit value is adjustable.
Alarm handling 18 Operating KS4x-1
Operation
Ü Operaing principle absolut alarm
L.1 = OFF
InL.1
InH.1
H.1
* Operating principle relative alarm
L.1 = OFF
SP
InL.1
H.1
HYS.1
HYS.1
InH.1
LED
1 2
LED
1 2
H.1 = OFF
InL.1
L.1
2
LED
HYS.1
1
InH.1
InL.1
H.1 = OFF
HYS.1
L.1
SP
LED
2 1
InH.1
InL.1
H.1
L.1
LED
2
HYS.1
1
HYS.1
InH.1
InL.1
2
LED
2
LED
HYS.1
L.1
SP
1
InH.1
H.1
HYS.1
2
LED
1: normally closed ( ConF/ Out.x / O.Act=1 )
2: normally open ( ConF/ Out.x / O.Act= 0 ) g The variable to be monitored can be selected seperately for each alarm via configuration
The following variables can be monitored: w process value w control deviation xw (process value - set-point) w control deviation xw + suppression after start-up or set-point change w effective set-point Weff w correcting variable y (controller output)
Operating KS4x-1 19 Alarm handling
Operation g If measured value monitoring + alarm status storage is chosen ( ConF / Lim /
Fnc.x = 2), the alarm relay remains switched on until the alarm is resetted in the error list ( Lim 1..3 = 1).
3.8 Operating structure
After supply voltage switch-on, the controller starts with the operating levels.
The controller status is as before power off.
126
125
Ù
3 sec.
126
PArA
Ì
Ù
126
ConF
Ì
PASS
Ù
126
CAL
Ì
PASS
Ù
126
End
PASS
Ù g PArA - level: At PArA - level, the right decimal point of the upper display line is lit continuously.
g ConF - level: At ConF - level, the right decimal point of the upper
PASS display line blinks
.
When safety switch Loc is open, only the levels enabled by means of BlueControl (engineering tool) are visible and accessible by entry of the password adjusted by means of BlueControl (engineering tool). Individual parameters accessible without password must be copied to the extended operating level.
Factory setting: Safety switch Loc closed: all levels accessible without restriction, password PASS = OFF.
Loc closed open open open
OFF / password
OFF / password
OFF
Password disabled / enabled disabled enabled enabled enabled disabled enabled entry
Operating structure 20 Operating KS4x-1
Configuration level
4
Configuration level
4.1 Configuration survey
ConF Configuration level
È
Ì
Cntr Control
SP.Fn StYP I.Fnc Fnc.1
O.Act
b.ti S.Lin StYP Src.1
Y.1
C.Fnc Corr mAn
C.Act
FAIL rnG.L
rnG.H
Fnc.2
Src.2
Fnc.3
Src.3
HC.AL
LP.AL
Y.2
Lim.1
Lim.2
Lim.3
LP.AL
HC.AL
HC.SC
time
P.End
FAi.1
FAi.2
O.tYP
O.Act
Y.1
Y.2
Lim.1
Lim.2
Lim.3
LP.AL
HC.AL
HC.SC
time
P.End
FAi.1
FAi.2
OuT.0
Out.1
O.Src
L_r bAud
SP.2 Addr
SP.E PrtY
Y.2
dELY mAn Unit
C.oFF dP m.Loc C.dEl
Err.r
P.run
di.Fn
Adjustment: w The configuratiuons can be adjusted by means of keys ÈÌ .
w Transition to the next configuration is by pressing key Ù .
w After the last configuration of a group, donE is displayed and followed by automatic change to the next group g Return to the beginning of a group is by pressing the Ù key for 3 sec.
Operating KS4x-1 21 Configuration survey
Configuration level
4.2 Configuration
Cntr
Name
SP.Fn
b.ti
C.Fnc
mAn
C.Act
FAIL
Value range Description
Basic configuration of setpoint processing
0
1
2
3 set-point controller can be switched over to external set-point
( LOGI/SP.E) program controller timer, mode 1(bandwidth-controlled, switched off at the end)
4
5
0
1
6
7
0...9999
2 active at the end) timer, mode 3 (switched off at the end) timer, mode 4 (set-point remains active at the end) timer, mode 5 (switch-on delay) timer, mode 6 (set-point switch-over)
Timer tolerance band for timer mode 1, 2 and 6. The timer starts when process value = setpoint b.ti
Control behaviour (algorithm) on/off controller or signaller with one output
PID controller (2-point and continuous)
0
1
3
4
0
1
0
1
2 switch-over
2 x PID (3-point and continuous)
3-point stepping controller
Manual operation permitted no yes (see also LOGI/ mAn)
Method of controller operation inverse, e.g. heating direct, e.g. cooling
Behaviour at sensor break controller outputs switched off y = Y2
Default
0
5
1
0
0
1 rnG.L
-1999...9999
X0 (low limit range of control) 1 rnG.H
-1999...9999
X100 (high limit range of control) 1
Adt0
0
1
Optimization of T1, T2 (only visible with BlueControl!)
Automatic optimization
No optimization
1 rnG.L and rnG.H are indicating the range of control on which e.g. the self-tuning is refering
0
900
0
Configuration 22 Operating KS4x-1
Configuration level
InP.1
Name
S.tYP
S.Lin
Corr fAI1
Value range Description
Sensor type selection
0
1
2
3
4
5
20
21
22
23
30
40 thermocouple type L (-100...900°C) , Fe-CuNi DIN thermocouple type J (-100...1200°C) , Fe-CuNi thermocouple type K (-100...1350°C), NiCr-Ni thermocouple type N (-100...1300°C), Nicrosil-Nisil thermocouple type S (0...1760°C), PtRh-Pt10% thermocouple type R (0...1760°C), PtRh-Pt13%
Pt100 (-200.0 ... 100,0 °C)
Pt100 (-200.0 ... 850,0 °C)
Pt1000 (-200.0 ... 200.0 °C) special 0...4500 Ohm (pre-defined as KTY11-6)
0...20mA / 4...20mA 1
0...10V / 2...10V 1
0
1
30 (0..20mA) and 40 (0..10V) adjustable) none
0
1
2
3
0
1 characteristic for KTY 11-6 temperature sensors is preset.
Measured value correction / scaling
Without scaling
Offset correction (at CAL level)
2-point correction (at CAL level)
Scaling (at PArA level)
Forcing INP1 (only visible with BlueControl!)
No forcing
Forcing via serial interface
InP.2
Name
I.Fnc
S.tYP
fAI2
Value range Description
Function selection of INP2
0
1
2
30 no function (subsequent input data are skipped) heating current input external set-point (SP.E)
Sensor type selection
31
0
1
0...20mA / 4...20mA 1
0...50mA AC 1
Forcing INP2 (only visible with BlueControl!)
No forcing
Forcing via serial interface
Default
1
0
0
0
Default
1
31
0
Configuration 23 Operating KS4x-1
Configuration level
Lim
Name
Fnc.1
Fnc.2
Fnc.3
Src.1
Src.2
Src.3
HC.AL
LP.AL
Value range Description
Function of limit 1/2/3
0
1 switched off measured value monitoring
2
0
0
1
0
1
1
2
6
7
2 limit value can be reset via error list, Ò-key or a digital input ( LOGI/ Err.r).
Source of limit 1/2/3 process value control deviation xw (process value - set-point) control deviation xw (with suppression after start-up and set-point change) effective set-point Weff correcting variable y (controller output)
Alarm heat current function (INP2) switched off
Overload short circuit monitoring
Break and short circuit monitoring
Monitoring of control loop interruption for heating switched off / inactive active
If ti1=0 LOOP alarm is inactive!
Hour OFF..999999
Operating hours (only visible with BlueControl!)
Swit OFF..999999
Output switching cycles (only visible with BlueControl!)
Default
1
1
0
0
OFF
OFF
Out.1
Name
O.Act
Y.1
Y.2
Lim.1
Lim.2
HC.AL
Value range Description
Method of operation of output OUT1
0
1
0
1 direct / normally open inverse / normally closed
Controller output Y1/Y2 not active
0
1
0
1
0
1 active
Limit 1/2/3 signal not active active
Interruption alarm signal (LOOP) not active active
Heat current alarm signal not active active
Default
0
1
0
0
0 g
1 with current and voltage input signals, scaling is required (see chapter 5.3)
Resetting the controller configuration to factory setting (Default) r chapter 12.1 (page 56)
Configuration 24 Operating KS4x-1
Configuration level
Name
HC.SC
timE
P.End
FAi.1
FAi.2
fOut
Value range Description
Solid state relay (SSR) short circuit signal
0
1
0 not active active
Timer end signal not active
1
0
1
0
1
0
1 active
Programmer end signal not active active
INP1/ INP2 error signal not active active
Forcing OUT1 (only visible with BlueControl!)
No forcing
Forcing via serial interface
Default
0
0
0
0
0
Out.2
Configuration parameters Out.2 as Out.1 except for: Default Y.1 = 0 Y.2 = 1
Out.3
Name
O.tYP
Default
0
Value range Description
Signal type selection OUT3
0
1
2
3
4
5 relay / logic (only visible with current/logic voltage)
0 ... 20 mA continuous (only visible with current/logic/volt.)
4 ... 20 mA continuous (only visible with current/logic/volt.)
0...10 V continuous (only visible with current/logic/voltage)
2...10 V continuous (only visible with current/logic/voltage) transmitter supply (only visible without OPTION)
O.Act
1
Y.1
Y.2
Lim.1
Lim.2
Lim.3
HC.AL
0
1
0
1
0
1
0
1
0
1
O.TYP=0) direct / normally open inverse / normally closed
Controller output Y1/Y2 (only visible when O.TYP=0) not active active
Limit 1/2/3 signal (only visible when O.TYP=0) not active active
Interruption alarm signal (LOOP) (only visible when
O.TYP=0) not active active
Heat current alarm signal (only visible when O.TYP=0) not active active
0
1
0
0
Operating KS4x-1 25 Configuration
Configuration level
Name
HC.SC
timE
P.End
FAi.1
FAi.2
Value range Description
Solid state relay (SSR) short circuit signal (only visible
0 when O.TYP=0) not active
1
0
1
0
1
0
1 active
Timer end signal (only visible when O.TYP=0) not active active
Programmer end signal (only visible when O.TYP=0) not active active
INP1/ INP2 error (only visible when O.TYP=0) not active active
Out.0
-1999...9999
Scaling of the analog output for 0% (0/4mA or 0/2V, only
Out.1
O.Src
fOut
-1999...9999
0
1
2
3
4
5
0
1
Scaling of the analog output for 100% (20mA or 10V, only
Signal source of the analog output OUT3 (only visible when not used controller output y1 (continuous) controller output y2 (continuous) process value effective set-point Weff control deviation xw (process value - set-point)
Forcing OUT3 (only visible with BlueControl!)
No forcing
Forcing via serial interface
Default
0
0
0
1
0
100
1
0 g Method of operation and usage of output Out.1 to Out.3:
Is more than one signal chosen active as source, those signals are OR-linked.
LOGI
Name
L_r
SP.2
Value range Description
Local / Remote switching (Remote: adjusting of all values
0 by front keys is blocked) no function (switch-over via interface is possible)
1
2
2
3
3
4
0
4 active
DI1
DI2 (only visible with OPTION)
DI3 (only visible with OPTION)
Switching to second setpoint SP.2
no function (switch-over via interface is possible)
DI1
DI2 (only visible with OPTION)
DI3 (only visible with OPTION)
Default
0
0
Configuration 26 Operating KS4x-1
Name
SP.E
Y2 mAn
C.oFF
m.Loc
Err.r
P.run
di.Fn
fDI1
Value range Description
Switching to external setpoint SP.E
0
1
2
3
4 no function (switch-over via interface is possible) active
DI1
DI2 (only visible with OPTION)
0
1
2
3
4
4
6
2
3
3
4
2
3
4
6
0
1
2
6
0
4
6
0
2
3
4
0
2
3
0
2
0
0
1
DI3 (only visible with OPTION)
Y/Y2 switching no function (switch-over via interface is possible)
DI1
DI2 (only visible with OPTION)
DI3 (only visible with OPTION)
Ò key
Automatic/manual switching no function (switch-over via interface is possible) always activated (manual station)
DI1
DI2 (only visible with OPTION)
DI3 (only visible with OPTION)
Ò key
Switching off the controller no function (switch-over via interface is possible)
DI1
DI2 (only visible with OPTION)
DI3 (only visible with OPTION)
Ò key
Blockage of hand function no function (switch-over via interface is possible)
DI1
DI2 (only visible with OPTION)
DI3 (only visible with OPTION)
Reset of all error list entries no function (switch-over via interface is possible)
DI1
DI2 (only visible with OPTION)
DI3 (only visible with OPTION)
Ò key
Programmer Run/Stop (see page 44) no function (switch-over via interface is possible)
DI1
DI2 (only visible with OPTION)
DI3 (only visible with OPTION)
Function of digital inputs (valid for all inputs) direct inverse toggle key function
Forcing di1 (only visible with BlueControl!)
No forcing
Forcing via serial interface
Operating KS4x-1 27
Configuration level
Default
0
0
0
0
0
0
0
0
0
Configuration
Configuration level
Name fDI2 fDI3
Value range Description
Forcing di2 (only visible with BlueControl!)
0
1
0
1
No forcing
Forcing via serial interface
Forcing di3 (only visible with BlueControl!)
No forcing
Forcing via serial interface
Default
0
0
othr
Name bAud
Addr
PrtY dELY
Unit dP
C.dEl
FrEq
ICof
IAda
IExo
Pass
Value range Description
Baudrate of the interface (only visible with OPTION)
0
1
2
3
1...247
2400 Baud
4800 Baud
9600 Baud
19200 Baud
0
1
2
1
2
0...200
0
Address on the interace (only visible with OPTION)
Parity (only visible with OPTION) no parity (2 stop bits) even parity odd parity
Delay of response signal [ms] (only visible with OPTION)
Unit without unit
°C
°F
0
1
2
3
0..200
0
1
0
1
0
1
0
1
OFF...9999
point) no digit behind the decimal point
1 digit behind the decimal point
2 digits behind the decimal point
3 digits behind the decimal point
Modem delay [ms]
Switching 50 Hz / 60 Hz (only visible with BlueControl!)
50 Hz
60 Hz
Block controller off (only visible with BlueControl!)
Released
Blocked
Block auto tuning (only visible with BlueControl!)
Released
Blocked
Block extended operating level (only visible with
BlueControl!)
Released
Blocked
Password (only visible with BlueControl!)
Default
2
0
0
0
1
1
1
0
0
0
0
OFF
Configuration 28 Operating KS4x-1
Configuration level
Name
IPar
ICnf
ICal
Value range Description
Block parameter level (only visible with BlueControl!)
0
1
0
Released
Blocked
Block configuration level (only visible with BlueControl!)
Released
1
0
1
Block
Block calibration level (only visible with BlueControl!)
Released
Blocked
Default
1
1
1
+ BlueControl - the engineering tool for the BluePort controller series
3 engineering tools with different functionality facilitating KS4x-1 configuration and parameter setting are available (see chapter 10: Accessory equipment with
ordering information).
In addition to configuration and parameter setting, the engineering tools are used for data acquisition and offer long-term storage and print functions. The engineering tools are connected to KS4x-1 via the front-panel interface "BluePort " by means of PC (Windows 95 / 98 / NT) and a PC adaptor.
Description BlueControl: see chapter 9: BlueControl (page 49)
4.3 Set-point processing
The set-point processing structure is shown in the following picture:
SP.x
126
125 run
Ada
Err
Xeff internal setpoint
Ü
ù programmer timer
{ 1
5
7
*
0 external setpoint
INP2
2.setpoint
SP.E
0/4...20 mA
SP.2
Index:
Ü
*
Ö :
: int/ext-setpoint switching
: configuration SP.Fn
switching
SP.Hi
SP.Lo
limitation
Ö r.SP
actual setpoint ramp
- LED
The ramp starts at process value with the following switchings:
-
- int / ext-setpoint switching
SP SP.2
switching
- Manual-/ Automatic switching
- at power on
Operating KS4x-1 29 Set-point processing
Configuration level
4.4 Configuration examples
4.4.1 On-Off controller / Signaller (inverse)
InL.1
SP.LO
InP.1Ê
100%
Out.1Â
0%
SH
SP SP.Hi
InH.1
ConF / Cntr: SP.Fn = 0
C.Fnc = 0
C.Act = 0
ConF / Out.1: O.Act = 0
Y.1
PArA / Cntr: SH
= 1
= 0...9999
set-point controller signaller with one output inverse action
(e.g. heating applications) action Out.1 direct control output Y1 active switching difference (symmetrical to the trigger point)
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff g For direct signaller action, the controller action must be changed
(ConF / Cntr / C.Act = 1 ) process value
SH setpoint output
Configuration examples 30 Operating KS4x-1
Configuration level
4.4.2 2-point controller (inverse)
InL.1
SP.LO
InP.1Ê
100%
Out.1Â
0%
PB1
SP SP.Hi
InH.1
ConF / Cntr: SP.Fn = 0
C.Fnc = 1
C.Act = 0
ConF / Out.1: O.Act = 0
Y.1
= 1
PArA / Cntr: Pb1 = 0,1...9999
proportional band 1 (heating) ti1 = 1...9999
td1 = 1...9999
t1 set-point controller
2-point controller (PID) inverse action
(e.g. heating applications) action Out.1 direct control output Y1 active in units of phys. quantity (e.g. °C) integral time 1 (heating) in sec.
derivative time 1 (heating) in sec.
= 0,4...9999
min. cycle time 1 (heating)
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff g For direct action, the controller action must be changed
(ConF / Cntr / C.Act = 1 ).
output setpoint process value
Operating KS4x-1 31 Configuration examples
InL.1
SP.LO
InP.1Ê
100%
Out.1Â
0%
PB1
SP
PB2
SP.Hi
InH.1
100%
Out.2Â
0%
Configuration examples 32 Operating KS4x-1
Configuration level
4.4.4 3-point stepping controller (relay & relay)
InL.1
SP.LO
InP.1Ê
100%
Out.1Â
0%
PB1
SP
SH
SP.Hi
InH.1
100%
Out.2Â
0%
ConF / Cntr: SP.Fn = 0
C.Fnc = 4
C.Act = 0
ConF / Out.1: O.Act = 0
Y.1
Y.2
ConF / Out.2: O.Act = 0
Y.1
Y.2
= 1
= 0
= 0
= 1
PArA / Cntr: Pb1 = 0,1...9999 proportional band 1 (heating) in units of phys. quantity (e.g. °C) ti1 = 1...9999
td1 = 1...9999
t1
SH = 0...9999
set-point controller
3-point stepping controller inverse action
(e.g. heating applications) action Out.1 direct control output Y1 active control output Y2 not active action Out.2 direct control output Y1 not active control output Y2 active integral time 1 (heating) in sec.
derivative time 1 (heating) in sec.
= 0,4...9999 min. cycle time 1 (heating) tP tt neutral zone in units of phy. quantity
= 0,1...9999 min. pulse length in sec.
= 3...9999
actuator travel time in sec.
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff g For direct action of the 3-point stepping controller, the controller output action must be changed ( ConF / Cntr / C.Act = 1 ).
output 1 output 2
Operating KS4x-1 setpoint
33 process value
Configuration examples
Configuration level
4.4.5 Continuous controller (inverse)
InL.1
SP.LO
InP.1Ê
20 mA
Out.3Â
0/4 mA
PB1
SP SP.Hi
InH.1
ConF / Cntr: SP.Fn = 0
C.Fnc = 1
C.Act = 0 set-point controller continuous controller (PID) inverse action
(e.g. heating applications)
ConF / Out.3: O.tYP = 1 / 2 Out.3 type ( 0/4 … 20mA )
Out.0 = -1999...9999 scaling analog output 0/4mA
Out.1 = -1999...9999 scaling analog output 20mA
PArA / Cntr: Pb1 = 0,1...9999
proportional band 1 (heating) ti1 = 1...9999
td1 = 1...9999
t1 = 0,4...9999
in units of phys. quantity (e.g. °C) integral time 1 (heating) in sec.
derivative time 1 (heating) in sec.
min. cycle time 1 (heating)
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff g For direct action of the continuous controller, the controller action must be changed ( ConF / Cntr / C.Act = 1 ).
g To prevent control outputs Out.1 and Out.2 of the continuous controller from switching simultaneously, the control function of outputs Out.1 and Out.2 must be switched off ( ConF / Out.1 and Out.2 / Y.1 and Y.2 = 0 ).
Configuration examples 34 Operating KS4x-1
Configuration level
4.4.6 - Y - Off controller / 2-point controller with pre-contact
InL.1
InP.1Ê
100%
Out.1Â
0%
Out.2Â
SP.LO
SH
PB1 d.SP
SP SP.Hi
InH.1
ConF / Cntr: SP.Fn = 0
C.Fnc = 2
C.Act = 0
ConF / Out.1: O.Act = 0
Y.1
Y.2
ConF / Out.2: O.Act = 0
Y.1
Y.2
= 1
= 0
= 0
= 1
PArA / Cntr: Pb1 = 0,1...9999
proportional band 1 (heating) in units of phys. quantity (e.g. °C) ti1 = 1...9999
td1 = 1...9999
t1
SH
= 0,4...9999
= 0...9999
set-point controller
-Y-Off controller inverse action
(e.g. heating applications) action Out.1 direct control output Y1 active control output Y2 not active action Out.2 direct control output Y1 not active control output Y2 active integral time 1 (heating) in sec.
derivative time 1 (heating) in sec.
min. cycle time 1 (heating) switching difference d.SP
= -1999...9999 trigg. point separation suppl. cont.
/ Y / Off in units of phys. quantity
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff
Operating KS4x-1 35 Configuration examples
Configuration level
4.4.7 KS4x-1 with measured value output phys.
quantity
Out.1
phys. quantity
Out.0
0/4mA
0/2V
20mA
10V mA / V
U
7
8
9
4
5
6
1
2
3
10
11
12
13
14
15
L
N
}
90...250VAC
24VUC
OUT3
INP1
+
ConF / Out.3: O.tYP = 1
= 2
= 3
= 4
Out.0 = -1999...9999
Out.1 = -1999...9999
O.Src = 3
Out.3 0...20mA continuous
Out.3 4...20mA continuous
Out.3 0...10V continuous
Out.3 2...10V continuous scaling Out.3
for 0/4mA or 0/2V scaling Out.3
for 20mA or 10V signal source for Out.3 is the process value
Configuration examples 36 Operating KS4x-1
Parameter setting level
5
Parameter setting level
5.1 Parameter survey
PArA Parameter setting level
È
Ì t2
SH d.SP
tP tt
Y2
Y.Lo
Y.Hi
Y0
Ym.H
L.Ym
Pb1
Pb2 ti1 ti2 td1 td2 t1
SP.Lo SP.01 InL.1 Inl.2 L.1
SP.Hi Pt.01 OuL.1 OuL.2 H.1
SP.2 SP.02 InH.1 InH.2 HYS.1
r.SP Pt.02 OuH.1 OuH.2 L.2
t.SP SP.03 tF.1
H.2
Pt.03
SP.04
Pt.04
HYS.2
dEl.2
L.3
H.3
HYS.3
HC.A
Adjustment: w The parameters can be adjusted by means of keys ÈÌ w Transition to the next parameter is by pressing key Ù w After the last parameter of a group, donE is displayed, followed by automatic change to the next group.
g Return to the beginning of a group is by pressing the Ù key for 3 sec.
g If for 30 sec. no keypress is excecuted the controler returns to the process value and setpoint display ( Time Out = 30 sec. )
Parameter survey 37 Operating KS4x-1
Parameter setting level
5.2 Parameters
Cntr
Name Value range Description
Pb1 1...9999 1 Proportional band 1/2 (heating) in phys. dimensions (e.g. °C)
Pb2 1...9999 1 Proportional band 2 (cooling) in phys. dimensions (e.g. °C) ti1 1...9999
Integral action time 1 (heating) [s] ti2 1...9999
Integral action time 2 (cooling) [s] td1 1...9999
Derivative action time 1 (heating) [s] td2 1...9999
Derivative action time 2 (cooling) [s] t1 0,4...9999
Default
100
100
180
180
180
180
10
0...9999
d.SP
-1999...9999
Trigger point speration for series contact / Y / Off [phys.
tP 0,1...9999
Minimum impulse [s] tt 3...9999
Actuator response time for servo-motor [s]
Y2 -120...120
2. correcting variable
Y.Lo
-120...120
Lower output limit [%]
Y.Hi
-120...120
Upper output limit [%]
Y.0
-120...120
Working point for the correcting variable [%]
Ym.H
-120...120
Limitation of the mean value Ym [%]
L.Ym
0...9999
Max. deviation xw at the start of mean value calculation [phys.
2
100
1 Valid for ConF/ othr/ DP = 0. At DP = 1/ 2/ 3 also 0,1 / 0,01 / 0,001.
SEtP
Name Value range Description
SP.LO
-1999...9999
Set-point limit low for Weff
SP.Hi
-1999...9999
Set-point limit high for Weff
SP.2
-1999...9999
Set-point 2.
r.SP
t.SP
SP
0...9999
0...9999
-1999...9999
Set-point gradient [/min]
Timer time [min]
Set-point (only visible with BlueControl!)
Default
0
900
0
OFF
5
0
OFF
60
0
0
100
0
5
8
ProG
Name Value range Description
SP.01
-1999...9999
Segment end set-point 1
Pt.01
0...9999
Segment time 1 [min]
SP.02
-1999...9999
Segment end set-point 2
Pt.02
0...9999
Segment time 2 [min]
SP.03
-1999...9999
Segment end set-point 3
Pt.03
0...9999
Segment time 3 [min]
Default
100 1
10 2
100 1
10 2
200 1
10 2
Operating KS4x-1 38 Parameters
Parameter setting level
Name Value range Description
SP.04
-1999...9999
Segment end set-point 4
Pt.04
0...9999
Segment time 4 [min]
1 If SP.01 … SP.04 = OFF then following parameters are not shown
Default
200 1
10 2
2 If segment end set-point = OFF then the segment time is not visible
InP.1
Name Value range Description
InL.1
-1999...9999
Input value for the lower scaling point
OuL.1
-1999...9999
Displayed value for the lower scaling point
InH.1
-1999...9999
Input value for the upper scaling point
OuH.1
-1999...9999
Displayed value for the lower scaling point t.F1
-1999...9999
Filter time constant [s]
InP.2
Name Value range Description
InL.2
-1999...9999
Input value for the lower scaling point
OuL.2
-1999...9999
Displayed value for the lower scaling point
InH.2
-1999...9999
Input value for the upper scaling point
OuH.2
-1999...9999
Displayed value for the upper scaling point
Lim
Name
L.1
H.1
HYS.1
L.2
H.2
HYS.2
L.3
H.3
HYS.3
Value range Description
-1999...9999
-1999...9999
0...9999
Lower limit 1
Upper limit 1
-1999...9999
-1999...9999
0...9999
-1999...9999
-1999...9999
0...9999
Hysteresis limit 1
Lower limit 2
Upper limit 2
Hysteresis limit 2
Lower limit 3
Upper limit 3
Hysteresis limit 3
HC.A
-1999...9999
Heat current control limit [A]
Default
0
0
20
20
0,5
Default
0
0
50
50
Default
-10
10
1
OFF
OFF
1
OFF
OFF
1
50 g Resetting the controller configuration to factory setting (Default) r chapter 12.1 (page 56)
Operating KS4x-1 39 Parameters
Parameter setting level
5.3 Input scaling
When using current or voltage signals as input variables for InP.1 or InP.2, scaling of input and display values at parameter setting level is required. Specification of the input value for lower and higher scaling point is in the relevant electrical unit (mA / V).
phys.
quantity
OuH.x
mA / V phys. quantity
OuL.x
InL.x
InH.x
mA/V
5.3.1 Input Inp.1
g Parameters InL.1 , OuL.1, InH.1 and OuH.1 are only visible if
ConF / InP.1 / Corr = 3 is chosen.
S.tYP
30
(0...20mA)
40
(0...10V)
Input signal
0 … 20 mA
4 … 20 mA
0 … 10 V
2 … 10 V
InL.1
0
4
0
2
OuL.1
any any any any
InH.1
20
20
10
10
OuH.1
any any any any
In addition to these settings, InL.1 and InH.1 can be adjusted in the range
(0...20mA / 0...10V) determined by selection of S.tYP .
a For using the predetermined scaling with thermocouple and resistance thermometer (Pt100), the settings for InL.1 and OuL.1 and for InH.1 and
OuH.1 must have the same value.
g Input scaling changes at calibration level (r page 41) are displayed by input scaling at parameter setting level. After calibration reset (OFF), the scaling parameters are reset to default.
5.3.2 Input InP.2
S.tYP
30
31
Input signal
0 … 20 mA
0 … 50 mA
InL.2
0
0
OuL2 any any
InH.2
20
50
OuH.2
any any
In addition to these settings, InL.2 and InH.2 can be adjusted in the range
(0...20/ 50mA) determined by selection of S.tYP.
Input scaling 40 Operating KS4x-1
Calibration level
6
Calibration level
g Measured value correction ( or 2 is chosen.
CAL)
is only visible if ConF / InP.1 / Corr = 1
The measured value can be matched in the calibration menu ( CAL). Two methods are available:
Offset correction
( ConF/ InP.1 / Corr =1 ): display standard setting offset correction w possible on-line at the process
OuL.1
new
OuL.1
old
InL.1
2-point correction
( ConF/ InP.1 / Corr = 2 ): w is possible off-line with process value simulator display
OuH.1
old
OuH.1
new standard setting
2-point correction
OuL.1
new
OuL.1
old
InL.1
InH.1
X
X
Operating KS4x-1 41
Calibration level
Offset correction ( ConF/ InP.1 / Corr =1 ):
SP.X
126
125 run
Ada
Err r Ù
3 sec.
r
PArA
CAL r Ù r
InP.1
r Ù r r r
InL.1
OuL.1
End r Ù
È
Ì r Ù r Ù
InL.1: The input value of the scaling point is displayed.
The operator must wait, until the process is at rest.
Subsequently, the operator acknowledges the input value by pressing key Ù.
OuL.1: The display value of the scaling point is displayed.
Before calibration, OuL.1 is equal to InL.1.
The operator can correct the display value by pressing keys ÈÌ .
Subsequently, he confirms the display value by pressing key Ù.
42 Operating KS4x-1
Calibration level
2-point correction ( ConF/ InP.1 / Corr =1 ):
SP.X
126
125 run
Ada
Err r Ù
3 sec.
r PArA
Ì
:
CAL r Ù r
InP.1
r Ù r r
InL.1
OuL.1
r Ù
È
Ì r Ù r r
InH.1
OuH.1
r Ù
È
Ì r Ù r
End r Ù
InL.1: The input value of the lower scaling point is displayed.
The operator must adjust the lower input value by means of a process value simulator and confirm the input value by pressing key Ù.
OuL.1: The display value of the lower scaling point is displayed.
Before calibration, OuL.1 equals InL.1.
The operator can correct the lower display value by pressing the ÈÌ keys. Subsequently, he confirms the display value by pressing key Ù.
InH.1: The input value of the upper scaling point is displayed. .
The operator must adjust the upper input value by means of the process value simulator and confirm the input value by pressing key Ù.
OuH.1: The display value of the upper scaling point is displayed.
Before calibration OuH.1 equals InH.1.
The operator can correct the upper display value by pressing keys ÈÌ
Subsequently, he confirms the display value by pressing key Ù.
g The parameters (OuL.1, OuH.1) changed at CAL level can be reset by adjusting the parameters below the lowest adjustment value (OFF) by means of decrement key Ì .
Operating KS4x-1 43
Programmer
7
Programmer
W,X SP.01
W,X
Pt.01
Pt.02
SP.02
Pt.03
SP.03
Pt.04
SP.04
W t
Programmer set-up:
For using the controller as a programmer, select parameter SP.Fn = 1 in the
ConF menu (r page 21). The programmer is started via one of digital inputs di1..3. Which input shall be used for starting the programmer is determined by selecting parameter P.run = 2 / 3 / 4 in the ConF menu accordingly.
(r page 23).
For assigning the program end as a digital signal to one of the relay outputs, parameter P.End = 1 must be selected for the relevant output OUT.1...OUT.3 in the
ConF menu (r page 26, 27).
Programmer parameter setting:
A programmer with 4 segments is available to the user. Determine a segment duration Pt.01 .. Pt.04 (in minutes) and a segment target set-point SP.01 ..
SP.04 for each segment in the PArA menu (r page 38).
Starting/stopping the programmer:
Starting the programmer is done by a digital signal at input di1..3 selected by parameter P.run (r page 23).
The programmer calculates a gradient from segment end setpoint and segment time. This gradient is always valid. Normaly, the programmer starts the first segment at process value. Because of this the effective run-time of the first segment may differ from the at PArA level setted segment time (process value setpoint).
After program end, the controller continues controlling with the target set-point set last.
If the program is stopped during execution (signal at digital input di1..3 is taken away), the programmer returns to program start and waits for a new start signal.
44 Operating KS4x-1
Programmer
+ Program parameter changing while the program is running is possible.
Changing the segment time:
Changing the segment time leads to re-calculation of the required gradient. When the segment time has already elapsed, starting with the new segment is done directly, where the set-point changes with a step.
Changing the segment end setpoint:
Changing the set-point leads to re-calculation of the required gradient, in order to reach the new set-point during the segment rest time, whereby the required gradient polarity sign can change.
Operating KS4x-1 45
Timer
8
Timer
8.1 Setting up the timer
8.1.1 Operating modes
6 different timer modes are available to the user. The relevant timer mode can be set via parameter SP.Fn in the Conf menu (r page 21).
Mode 1 (—)
After timer start, control is to the adjusted set-point . The timer (t.SP) runs as soon as the process value enters or leaves the band around the set-point (x = SP _ b.ti). After timer elapse, the controller returns to Y2.
End and the set-point are displayed alternately in the lower display line.
Mode 2 (····)
Mode 2 corresponds to mode 1, except that control is continued with the relevant set-point after timer (t.SP) elapse.
Mode 3 (—)
After timer start, control is to the adjusted set-point. The timer (t.SP) starts immediately after switch-over. After timer elapsing the controller switches off. End and the set-point are displayed alternately in the bottom display line.
Mode 4 (····)
Mode 4 corresponds to mode 3, except that control is continued with the relevant set-point after timer (t.SP) elapse.
Mode 5 (delay)
The timer starts immediately. The controller output remains on Y2. After timer (t.SP) elapse, control starts with the adjusted set-point.
SP u u
SP
Start
Start
SP blinks run run run t.SP
run t.SP
run
1
2
ò blinks
End
3
4
ò blinks
End
ò blinks
End
Start t.SP
Setting up the timer 46 Operating KS4x-1
Timer
Mode 6
After set-point switch-over (SPr SP.2), control is to SP.2. The timer (t.SP) starts when the process value enters the adjusted band around the set-point (x = SP.2 _ b.ti).
After time elapse the controller returns to SP.
End and the set-point are displayed alternately in the lower display line.
SP.2
u u
SP blinks run
Start run
End
SP t.SP
8.1.2 Tolerance band
Timer modes 1,2 and 6 are provided with a freely adjustable tolerance band. The tolerance band around the set-point can be adjusted via parameter b.ti in the
Conf menu (x = SP.2 _ b.ti )
(r page 21).
8.1.3 Timer start
Various procedures for starting the timer are possible:
Start via
Pressing key Ò
Power On
LOGI
Y2
= di1 2
Mode
SP.2
=
1 2 3 4 5 6 x d d d d d di2 3 di3 4 di1 x di2 x di3 x
6
0 x x x d d d d d x d d d d d -
2 - - - - - d
3 - - - - - d
4 - - - - - d x d d d d d x d d d d d -
0 - - - - - d x d d d d d d
Serial interface (if provided)
1
LOGI) ( key function) x no effect x x d d d d d d
Operating KS4x-1 47 Setting up the timer
Timer
8.1.4 Signal end
If one of the relays shall switch after timer elapse, parameter TimE = 1 and inverse action O.Act = 1 must be selected for the relevant output OUT.1 …
OUT.3 in the ConF menu (r page 25, 26). If direct action is selected, the relevant output signals the active timer.
8.2 Determining the timer run-time
The timer run-time can be determined via parameter t.SP in the PArA menu.
The timer run-time must be specified in minutes with one digit behind the decimal point (0,1 minutes = 6 seconds).
Alternatively, the timer run-time can be determined directly at extended operating level (r chapter 8.3).
8.3 Starting the timer
Dependent of configuration, the timer start is as follows: w by a positive flank at one of digital inputs di1..3
w by pressing key Ò w by switching on the controller (power On) w by changing the timer run-time t.ti > 0
(extended operating level) w via the serial interface
Display:
Run LED blinks lit off
( End and setpoint are displayed alternately)
SP.x
126
125
Signification
- timer was started
- timer is not running yet
- timer was started
- timer is running
- timer is off
- timer has elapsed
- deletion of End display by pressing any key run
Ada
Err g With active timer, the time can be adjusted by changing parameter t.ti at extended operating level.
Determining the timer run-time 48 Operating KS4x-1
BlueControl
9
BlueControl
BlueControl is the projection environment for the BluePort controller series of
PMA. The following 3 versions with graded functionality are available:
The mini version is - free of charge - at your disposal as download at PMA homepage www.pma-online.de or on the PMA-CD (please ask for).
At the end of the installation the licence number has to be stated or
DEMO mode must be chosen.
At DEMO mode the licence number can be stated subsequently under Help r
Licence r
Change.
Operating KS4x-1 49
Versions
10
Versions
Accessories delivered with the unit
Operating manual (if selected by the ordering code) w 2 fixing clamps w operating note in 15 languages
Accessory equipment with ordering information
Description
Heating current transformer 50A AC
PC-adaptor for the front-panel interface
Standard rail adaptor
Operating manual
Operating manual
Operating manual
Interface description Modbus RTU
Interface description Modbus RTU
BlueControl (engineering tool)
BlueControl (engineering tool)
BlueControl (engineering tool)
German
English
French
German
English
Mini
Basic
Expert
Order no.
9404-407-50001
9407-998-00001
9407-998-00061
9499-040-62718
9499-040-62711
9499-040-62732
9499-040-63518
9499-040-63511
Download www.pma-online.de
9407-999-11001
9407-999-11011
50 Operating KS4x-1
Technical data
11
Technical data
INPUTS
PROCESS VALUE INPUT INP1
Resolution:
Decimal point:
> 14 bits
0 to 3 digits behind the decimal point
Dig. input filter: adjustable 0,000...9999 s
Scanning cycle: 100 ms
Measured value correction:
2-point or offset correction
Thermocouples r Table 1 (page 53 )
Input resistance:
Effect of source resistance:
³ 1 MW
1 mV/W
Cold-junction compensation
Maximal additional error: 0,5 K
Sensor break monitoring
Sensor current:
Configurable output action
£ 1 mA
Resistance thermometer r Table 2 (page 53 )
Connection:
Lead resistance:
2 or 3-wire max. 30 Ohm
Input circuit monitor: break and short circuit
Special measuring range
BlueControl (engineering tool) can be used to match the input to sensor KTY 11-6
(characteristic is stored in the controller).
Physical measuring range:
Linearization segments
0...4500 Ohm
16 r Table 3 (page 53 )
Span start, end of span:
Scaling:
Linearization: anywhere within measuring range selectable -1999...9999
16 segments, adaptable with
Decimal point:
BlueControl adjustable
Input circuit monitor: 12,5%belowspanstart(2mA,1V)
SUPPLEMENTARY INPUT INP2
Resolution: > 14 bits
Scanning cycle: 100 ms
Accuracy: < 0,5 %
Heating current measurement via current transformer ( Accessory equipment)
Measuring range: 0...50mA AC
Scaling: adjustable -1999...0,000...9999 A
Current measuring range
Technical data as for INP1
CONTROL INPUT DI1
Configurable as switch or push-button!
Connection of a potential-free contact suitable for switching “dry” circuits.
Switched voltage:
Current:
2,5 V
50 mA
CONTROL INPUTS DI2, DI3 (OPTION)
Configurable as switch or push-button!
Optocoupler input for active triggering
Nominal voltage
Current sink (IEC 1131 type 1)
Logic “0”
Logic “1”
Current requirement
24 V DC external
-3...5 V
15...30 V approx.. 5 mA
TRANSMITTER SUPPLY U
T
(OPTION)
Power: 22 mA / ³ 18 V
If the universal output OUT3 is used there may be no external galvanic connection between measuring and output circuits!
GALVANIC ISOLATION
Safety isolation
Function isolation
Process value input INP1
Supplementary input INP2
Digital input di1
Relay outputs OUT 1,2 RS422/485 interface
Relay output OUT3 Digital inputs di2, 3
Universal output OUT3
Transmitter supply U
T
OUTPUTS
RELAY OUTPUTS OUT1, OUT2
Contact type: 2 NO contacts with common connection
Max. contact rating: 500 VA, 250 V, 2A at 48...62Hz, resistive load
Min. contact rating: 6V, 1 mA DC
Operating KS4x-1 51
Technical data
Operating life
(electr.):
800.000 duty cycles with max.
rating
OUT3 USED AS RELAY OUTPUT
Contact type: potential-free changeover contact
Max.contact rating: 500 VA, 250 V, 2A at 48...62Hz, resistive load
Min. contact rating: 5V, 10 mA AC/DC
Operating life
(electr.):
600.000 duty cycles with max.
contact rating
Note:
If the relays OUT1...OUT3 operate external contactors, these must be fitted with RC snubber circuits to manufacturer specifications to prevent excessive switch-off voltage peaks.
OUT3 AS UNIVERSAL OUTPUT
Galvanically isolated from the inputs.
Freely scalable
Resolution: 11 bits
Current output
0/4...20 mA configurable.
Signal range:
Max. load:
Load effect:
Resolution:
Accuracy
0...approx.22mA
£ 500 W no effect
£ 22 mA (0,1%)
£ 40 mA (0,2%)
Voltage output
0/2...10V configurable
Signal range:
Min. load:
Load effect:
Resolution:
Accuracy
0...11 V
³ 2 kW no effect
£ 11 mV (0,1%)
£ 20 mV (0,2%)
OUT3 used as transmitter supply
Output power: 22 mA / ³ 13 V
OUT3 used as logic output
Load £ 500 W
Load > 500 W
0/£ 20 mA
0/> 13 V
POWER SUPPLY
Dependent of order:
AC SUPPLY
Voltage:
Frequency:
90...260 V AC
48...62 Hz
Power consumption approx. 7,0 VA
UNIVERSAL SUPPLY 24 V UC
AC voltage:
Frequency:
DC voltage:
Power consumption:
20,4...26,4 V AC
48...62 Hz
18...31 V DC approx.. 7,0 VA
BEHAVIOUR WITH POWER FAILURE
Configuration, parameters and adjusted set-points, control mode:
Non-volatile storage in EEPROM
BLUEPORT FRONT INTERFACE
Connection of PC via PC adapter (see
"Accessory equipment"). The BlueControl software is used to configure, set parameters and operate the KS4x-1.
BUS INTERFACE (OPTION)
Galvanically isolated
Physical:
Protocol:
RS 422/485
Modbus RTU
Transmission speed: 2400, 4800, 9600, 19.200 bits/sec
Address range: 1...247
Number of controllers per bus: 32
Repeaters must be used to connect a higher number of controllers.
ENVIRONMENTAL CONDITIONS
Protection modes
Front panel:
Housing:
Terminals:
IP 65 (NEMA 4X)
IP 20
IP 00
Permissible temperatures
For specified accuracy: 0...60°C
Warm-up time:
For operation:
For storage:
³ 15 minutes
-20...65°C
-40...70°C
Humidity
75% yearly average, no condensation
Shock and vibration
Vibration test Fc (DIN 68-2-6)
Frequency: 10...150 Hz
Unit in operation: 1g or 0,075 mm
Unit not in operation: 2g or 0,15 mm
Shock test Ea (DIN IEC 68-2-27)
Shock:
Duration:
15g
11ms
52 Operating KS4x-1
Technical data
Electromagnetic compatibility
Complies with EN 61 326-1
(for continuous, non-attended operation)
GENERAL
Housing
Material: Makrolon 9415 flame-retardant
Flammability class: UL 94 VO, self-extinguishing
Plug-in module, inserted from the front
Safety test
Complies with EN 61010-1 (VDE 0411-1):
Overvoltage category II
Contamination class 2
Working voltage range 300 V
Protection class II
Certifications
Type-tested to DIN 3440
For use in: w Heat generating plants with outflow temperatures up to 120°C to DIN 4751 w Hot water plants with outflow temperatures above 110°C to DIN 4752 w Thermal transfer plants with organic transfer media to DIN 4754 w Oil-heated plants to DIN 4755 cUL certification
(Type 4x, indoor use)
File: E 208286
For compliance with cUL certificate,the following information must be taken into account: w Use only 60 / 75 or 75°C copper (Cu) wire.
w Tighten the terminal- screws with a torque of 0,5 - 0,6 Nm
Mounting
Panel mounting with two fixing clamps at top/bottom or right/left,
High-density mounting possible
Mounting position: uncritical
Weight: 0,27kg
Accessories delivered with the unit
Operating manual
Fixing clamps
Table 1 Thermocouple measuring ranges
Thermocouple type
L Fe-CuNi (DIN)
J Fe-CuNi
K NiCr-Ni
N Nicrosil/Nisil
S PtRh-Pt 10%
R PtRh-Pt 13%
Range
-100...900°C
-100...1200°C
-100...1350°C
-100...1300°C
0...1760°C
0...1760°C
-148...1652°F
-148...2192°F
-148...2462°F
-148...2372°F
32...3200°F
32...3200°F
Table 2 Resistance transducer measuring ranges
Type
Pt100
Pt100
Pt1000
KTY 11-6
Sens. current Range
-200...100°C
0,2mA
-200...850°C
-200...850°C
-50...150°C
-140...212°F
-140...1562°F
-140...1562°F
-58...302°F
Table 3 Current and voltage measuring ranges
Range
0-10 Volt
0-20 mA
Input resistance
~ 110 kW
49 W (voltage requirement ß 2,5 V)
Accuracy
ß 2K
ß 2K
ß 2K
ß 2K
ß 2K
ß 2K
Accuracy
ß 1K
ß 1K
ß 2K
ß 2K
Accuracy
ß 0,1 %
ß 0,1 %
Operating KS4x-1 53
Resolution (Ô)
0,1 K
0,1 K
0,2 K
0,2 K
0,2 K
0,2 K
Resolution (Ô)
0,1K
0,1K
0,1K
0,05K
Resolution (Ô)
ß 0,6 mV
ß 1,5 mA
Safety hints
12
Safety hints
This unit was built and tested in compliance with VDE 0411-1 / EN 61010-1 and was delivered in safe condition.
The unit complies with European guideline 89/336/EWG (EMC) and is provided with CE marking.
The unit was tested before delivery and has passed the tests required by the test schedule. To maintain this condition and to ensure safe operation, the user must follow the hints and warnings given in this operating manual.
The unit is intended exclusively for use as a measurement and control instrument in technical installations.
a Warning
If the unit is damaged to an extent that safe operation seems impossible, the unit must not be taken into operation.
ELECTRICAL CONNECTIONS
The electrical wiring must conform to local standards (e.g. VDE 0100). The input measurement and control leads must be kept separate from signal and power supply leads.
In the installation of the controller a switch or a circuit-breaker must be used and signified. The switch or circuit-breaker must be installed near by the controller and the user must have easy access to the controller.
COMMISSIONING
Before instrument switch-on, check that the following information is taken into account: w Ensure that the supply voltage corresponds to the specifications on the type label.
w All covers required for contact protection must be fitted.
w If the controller is connected with other units in the same signal loop, check that the equipment in the output circuit is not affected before switch-on. If necessary, suitable protective measures must be taken.
w The unit may be operated only in installed condition.
w Before and during operation, the temperature restrictions specified for controller operation must be met.
SHUT-DOWN
For taking the unit out of operation, disconnect it from all voltage sources and protect it against accidental operation.
If the controller is connected with other equipment in the same signal loop, check that other equipment in the output circuit is not affected before switch-off. If necessary, suitable protective measures must be taken.
54 Operating KS4x-1
Safety hints a
MAINTENANCE, REPAIR AND MODIFICATION
The units do not need particular maintenance.
Warning
When opening the units, or when removing covers or components, live parts and terminals may be exposed.
Before starting this work, the unit must be disconnected completely.
After completing this work, re-shut the unit and re-fit all covers and components.
Check if specifications on the type label must be changed and correct them, if necessary.
l Caution
When opening the units, components which are sensitive to electrostatic discharge (ESD) can be exposed. The following work may be done only at workstations with suitable ESD protection.
Modification, maintenance and repair work may be done only by trained and authorized personnel. For this purpose, the PMA service should be contacted.
a The cleaning of the front of the controller should be done with a dry or a wetted
(spirit, water) kerchief.
Operating KS4x-1 55
Safety hints
12.1 Resetting to factory setting
In case of faultyconfiguration, KS4x-1 can be reset to the default condition.
4 1
ÌÈ
+ Power on
1.
SP.x
FAC
torY
Ada
Err run
2.
SP.x
FAC
no
run
Ada
Err
2
È
SP.x
FAC
YES
run
Ada
Err
3
Ù
SP.x
FAC
COPY
run
Ada
Err
SP.x
8.8.8.8.
8.8.8.8.
run
Ada
Err
1 For this, the operator must keep the keys increment and decrement pressed during power-on.
2 Then, press key increment to select YES.
3 Confirm factory resetting with Enter and the copy procedure is started
(display COPY).
4 Afterwards the device restarts.
In all other cases, no reset will occur (timeout abortion).
g If one of the operating levels was blocked and the safety lock is open, reset to factory setting is not possible.
g If a pass number was defined (via BlueControl ®
3. A wrong pass number aborts the reset action.
) and the safety lock is open, but no operating level was blocked, enter the correct pass number when prompted in g The copy procedure ( COPY) can take some seconds.
Now, the transmitter is in normal operation.
Resetting to factory setting 56 Operating KS4x-1
Index
0-9
2-point correction. . . . . . . . . . . . 41
A
Alarm handling . . . . . . . . . . 18 - 19
B
BlueControl. . . . . . . . . . . . . . . 49
Bus interface
Technical Data. . . . . . . . . . 52
C
Calibration level (CAL) . . . . . . 41 - 43
Certifications . . . . . . . . . . . . . . 53
Configuration examples
2-point controller . . . . . . . . 31
3-point controller . . . . . . . . 32
3-point stepping controller . . . 33
Continuous controller . . . . . . 34
D - Y -Off controller. . . . . . . 35
Measured value output . . . . . 36
Signaller . . . . . . . . . . . . . 30
Configuration level
Configuration parameters. . 22 - 28
Parameter survey . . . . . . . . 21
Connecting diagram . . . . . . . . . . . 6
Connecting examples di2/3, 2-wire transmitter supply . 8
INP2 current transformer . . . . . 7
OUT1/2 heating/cooling . . . . . 7
OUT3 as logic output . . . . . . . 8
OUT3 transmitter supply . . . . . 8
RS485 interface . . . . . . . . . . 9
Control inputs di1, di2, di3
Technical data . . . . . . . . . . 51
Current signal measuring range . . . . 51
D
Digital inputs di1, di2, di3
Configuration . . . . . . . . . . 26
Technical data . . . . . . . . . . 51
E
Environmental conditions . . . . . . . 53
Equipment . . . . . . . . . . . . . . . 50
Error list . . . . . . . . . . . . . . . . 12
F
Front view . . . . . . . . . . . . . . . 10
I
Input INP1
Configuration . . . . . . . . . . 23
Parameters . . . . . . . . . . . . 39
Technical data . . . . . . . . . . 51
Input INP2
Configuration . . . . . . . . . . 23
Parameters . . . . . . . . . . . . 39
Technical data . . . . . . . . . . 51
Input scaling . . . . . . . . . . . . . . 40
K
Kalibrierung (CAL) . . . . . . . . . . 41
L
LED
Ada - LED . . . . . . . . . . . . 10
Err - LED . . . . . . . . . . . . 10
ì - LED. . . . . . . . . . . . . 10
LED colours . . . . . . . . . . . 10
ò - LED. . . . . . . . . . . . . 10 run - LED . . . . . . . . . . . . 10
SP.x - LED. . . . . . . . . . . . 10
M
Maintenance manager . . . . . . . 12 - 13
Manual tuning . . . . . . . . . . . . . 17
Mounting. . . . . . . . . . . . . . . . . 5
O
Offset correction . . . . . . . . . . . . 41
Output OUT1
Configuration . . . . . . . . . . 24
Technical data . . . . . . . . . . 52
Output OUT2
Configuration . . . . . . . . . . 25
Technical data . . . . . . . . . . 52
Output OUT3
Configuration . . . . . . . . . . 25
Technical data . . . . . . . . . . 52
P
Parameter setting level
Parameter survey . . . . . . . . 37
Parameters . . . . . . . . . 38 - 39
Operating KS4x-1 57
Power supply . . . . . . . . . . . . . . 52
Programmer
Changing segment end setpoint . 45
Changing segment time . . . . . 45
Parameter setting . . . . . . . . 44
Set-up . . . . . . . . . . . . . . 44
Starting/Stopping . . . . . . . . 44
R
Resetting to factory setting . . . . . . . 56
S
Safety hints . . . . . . . . . . . . 55 - 56
Safety switch. . . . . . . . . . . . . . . 5
Safety test. . . . . . . . . . . . . . . . 53
Self-tuning
Cancelation . . . . . . . . . . . 15
Cancelation causes. . . . . . . . 16
Start . . . . . . . . . . . . . . . 15
Set-point processing . . . . . . . . . . 29
T
Thermocouple measuring range . . . . 51
Timer
Display run-LED . . . . . . . . 48
Operating modes. . . . . . . . . 46
Signal end . . . . . . . . . . . . 48
Timer start . . . . . . . . . . . . 47
Tolerance band . . . . . . . . . 47
V
Versions . . . . . . . . . . . . . . . . 50
Voltage signal measuring range . . . . 51
58 Operating KS4x-1
Operating KS4x-1 59
9499-040-62711
Subject to alterations without notice
Änderungen vorbehalten
Sours réserve de toutes modifications
© PMA Prozeß- und Maschinen-Automation GmbH
P.O.B. 310 229, D-34058 Kassel, Germany
Printed in Germany 9499-040-62711 (07/2004)
A6
! " # $ % #
"
!
#
%
0
!
& '
! ! !'
!
!
! 1
1!& !
2 !
" !
(
* !
*8
$ !
!
!
#
$
./
!
( )* + ,
!
( $*
' ) + ( +
./
! 1
!
!
3 4!
56/
56/
,7 7
7 7
%
$# # &
' (" #) #
*
)
* ) !
).>
3 >
3 C
) !
!
# 8
&
! !
!
# 8
!
!
1 !
!
!
!!
# ?
A 8' B
!
1 ' !
A 8' B
! = !
.
*
1).
!@
>
%
$#
1
# & . )
' (" #) #
. )
!'
D !
./
.
.
!@
1).
%
$# # & . )
' (" #) #
. )
1
1 !
./
!'
./
%
/#%
$#
C* )>
> )>
C
& !
# & /#%#
' (" #) #
/#%#
1 !
1 !
1 !
1 !
1 !
8 !
1
1
!
8 =
! ! & ! 8 =
!
!
!
!
!
!
*
*
7
7
7
7
*
7
7 ! !+ 9!
7 .$ !
!
: !
!
7 <
=
!
8 !
!
7 & ! 8 ! @
!!
!
;
7 !
!
!
7
7 8 !
7 )* :
! 7 +
D !
*
7
7 !
7 & ! 8
7
11
7 & ! 8
7 & ! 8
>""
11
11
11
11
!
!
!
!
);
)
+
+
+
+
*#(#,
-
9
9
9
9
9
9
9
*#(#,
-
9
9
9
*#(#,
-
9
9
*#(#,
-
9
9
9
9
9
9
%
$#
0
" ) !
@
>
)
)
1" !
1
# & 0 )
' (" #) #
0 )
!
!
1 !
! ! @
!
./ 1
./ 1
"6%
%
$#
0
" ) !
@
>
)
)
1" !
1
# & 0 )
' (" #) #
0 )
!
!
./ 1
./ 1
"6%
!
1 !
! ! @
0
" !@
" !
" !
"
1" !
%
$#
1
# & 0 )
' (" #) #
0 )
!' 1 "6%
E
E
"6%
@
)
*
>
F
F
%
$#
/01.
>
1$.
# & / #"
' (" #) #
/ #"
1
1
# ? 1 !
9!
! !
! !
!
!
!
! +
!
11
)+< ? ' # ?
!
!
!
1 !
& ! 8
*
7
7
7
7
7
7 !
*
7
7
7
7
7
7
!
*
7 ( !
7
7 !
! ! ' : ! ;
*
7 ! 1
7 ! 1
7 ! 1
7 ! 1
7 ! 1
7 ! 1
7 ! 1
7
7
7 ! 1
!
'
'
'
'
'
'
'
'
+
+
+
+
*#(#,
-
9
9
9
9
9
*#(#,
-
9
9
9
9
9
*#(#,
-
9
9
9
9
9
9
9
9
9
*#(#,
-
9
9
9
9
* F>
FG
* 1
)
F9
> !
2
%
$#
6 !
* 1
*
# & 0 2
' (" #) #
0 2
!
& ! 8
!
!
' A B
+ CD
! !
11
9!
!
! 8
&
!
1
# !
!
%
% &
' (" #) #
!
@
!
!
#
@ >
@ C
@
!
!
!
!
' !
!
#
!
#
A 8' B
A B
A B
A B
& ! !
! !
& ?
! AEB
AEB
AEB
%
%
)
>"
C
& ) #
' (" #) #
) #
&
! !
! !
! !
! !
! ! A 8' B
A 8' B
A 8' B
A+ B
%
%
1
&
' (" #) #
%%
%%
*
7
7 *
! # 8 !8
7
7
7
7
7
11
7 # ?
#
#
#
1 G
7 # ?
7 # ?
' CD
!
*
*
*
11
+
+
+
+
,
*#(#,
-
9
9
9
*#(#,
-
9
9
9
9
*#(#,
-
9
9
9
9
9
9
9
9
*#(#,
-
.
!
. >
" >
. C
" C
%
% & . )
' (" #) #
. )
&
&
1 !
!
!
! !
!
! !
A B
A 8' B
A 8' B
A 8' B
A 8' B
.
. >
" >
. C
" C
%
% & . )
' (" #) #
. )
&
&
!
! !
!
! !
A 8' B
A 8' B
A 8' B
A 8' B
%
/#%
%
>
C
C@
& /#%#
' (" #) #
/#%#
&
8' !
!
A 8' B
!
A 8' B
A 8' B
*
*
*
+
+
+
*#(#,
-
9
9
9
9
9
*#(#,
-
9
9
9
9
*#(#,
-
9
9
9
'#() 3
% ' (" #) #
45 5 )
%
# 6
' (" #) #
" # 5#
%# 7
)# 5 (" #) #
%
)
)
)
)
)
)
),
)
)
)
)
H
H
>
/
( )*+$*
( )*+$*
)
)
"6% /"
"6% * + "6% *
) "6% /"
)I "6% *
"6% -(
./ C*
./ C*
-
./ - )
= ./ )
' (" #) #
8 !
!
J
!
!
Brief adjustment instructions
1
• After installation ( → page 24) and electrical connection
( → page 26),
• apply the operating voltage.
After approx. 15 s the unit is ready.
• Allow the medium to flow through the system at the required maximmum flow rate.
2
M S
6-8 s
LO
LO
LO
HI
HI
HI
Press the Learn/Set button and keep it pressed.
The green LEDs on the right and on the left flash, after 5 s the LED bar (green) fills from left to right
(release the button now).
The indication goes off briefly.
The unit stores the current flow as maximum flow and passes into the operating mode.
After this procedure the unit is ready for normal operation.
• This setting is sufficient for the majority of waterbased applications. Optional: adjustment to minimum flow ( → page 27)
• If needed, set the switch point (for changing the reaction time and excess gain, → page 27).
Manual setting options
• Manual adjustment to maximum flow ( → page 27).
• Manual adjustment to maximum flow / monitoring and optical indication of excess flow ( → page 27).
• Manual adjustment to minimum flow / flow standstill
( → page 28).
• Activate / deactivate the function for remote adjustment
( → page 28).
20
Controls and visual indication
setting buttons
MODE /
ENTER
LO
FLOW RATE
LEARN /
SET
HI
function display
0 1 2 3 4 5 6 7 8 9
Function display (Run mode)
0 1 2 3 4 5 6 7 8 9 current flow within the display range
(LED bar green)
0 1 2 3 4 5 6 7 8 9 excess flow (LED 9 flashes) underflow (LED 0 flashes)
Indication of the switch point (SP):
LED orange: flow ≥ SP; LED red: flow < SP
Setting buttons
Mode / Enter: selection of the menu items and acknowledgement
Learn/Set: adjustment to maximum / minimum flow; setting of values (scrolling by holding pressed;incremental by pressing briefly)
SID 701657/02 21
LO
Menu structure
Run mode
HI
0 1 2 3 4 5 6 7 8 9
Adjustment to maximum flow
Manual settings
Adjustment to maximum flow
6-8s
Adjustment to minimum flow
11-15s
2x
>5s
1x
Monitoring excess flow
Setting the switch point
1x
>5s
1x
Activate / deactivate the function for remote adjustment
4x
> 5s
1x
2x
>5s
...
1x
Adjustment to minimum flow
3x
>5s
1x
22
LED = green LED = orange LED = red
701657/02 SID
Contents
Function and features . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 27
Installation and set-up / Operation / Maintenance . . . . . . . page 29
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29
Programming diagrams / Technical information . . . . . . . . . page 30
Function and features
The flow monitor
• detects the flow velocity in liquid and gaseous media
• switches the output according to the programming
(N.O./ or N.C./ , programmmable by wiring; → page 26)
• and indicates the relative flow value within the adjustable detection range by means of LEDs:
- LED 0 = lower limit of the detection range (maximum value / LO)
- LED 9 = upper limit of the detection range (minimum value / HI)
• It is also possible to indicate:
- Switching status (LED red: flow below the switch point,
LED orange: flow has reached the switch point).
- Excess flow: LED 9 flashes if the flow is considerably higher
(2 LEDs) than the display range.
- Underflow / flow standstill: LED 0 flashes if the flow is lower than the display range.
23
Installation
The unit is adaptable for various process fittings (adapters to be ordered separately as accessories).
• In the case of horizontal pipes mount the unit from the side, if possible (fig. 1).
When the unit is to be mounted at the bottom of the pipe, it should be free from deposits.
When the unit is to be mounted at the top of the pipe, it should be completely filled with the medium to be monitored.
• In the case of vertical pipes mount the unit in a place where the medium flows upwards (fig. 2).
1 2
To avoid malfunction a minimum distance between the flow monitor and bends, valves, changes in cross-section or such like must be observed:
• Min. 5 x pipe diameter upstream (A),
• min. 3 x pipe diameter downstream (B).
3
D min.
3 x D
B min.
5 x D
A
24
1 2 3 thread M18 x 1.5
1. Lubricate the nut (3) and all threads with grease to ensure the nut can be loosened and tightened several times.
Note: No grease must be applied to the sensor tip (A).
2. Screw the suitable adapter (2) onto the process fitting (1).
3. Insert the flow monitor into the adapter. While keeping the unit aligned tighten the nut (3); (max. tightening torque 50 Nm).
Insertion depth of the sensor: min. 12 mm in the pipe. When the
adapters are used which are available as accessories, the correct depth is ensured.
Note: The sensor tip must not touch the pipe wall.
mounting dimension with M12 adapter mounting dimension with G¼ adapter mounting dimension with G½ adapter
25
Electrical connection
The unit must only be connected by an electrician.
The national and international regulations for the installation of electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
The device shall be supplied from an isolating source and protected by an overcurrent device such that the limited voltage circuit requirements in accordance with UL 508 are met.
Disconnect power before connecting the unit.
Wiring ( = N.O. / = N.C.):
PNP units
1 BN
4 BK
3 BU
2 WH
L+
L-
P
3 BU
4 BK
1 BN
2 WH
L+
L-
P connector view (sensor)
1
2 4
3
NPN units
1
4
3
2
BN
BK
BU
WH
L+
L-
P
3 BU
4 BK
1 BN
2 WH
L+
L-
P connector view (sensor)
2
1
3
4
P = programming wire (for remote adjustment)
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black)
If the function for remote adjustment is active:
Use 4-wire connection cables without a link between pins 2 and 4.
With 3-wire sockets with a link between pin 2 and pin 4 switching of the output stage triggers the remote adjustment!
Failure indication: In the case of a short circuit the function indication and the red LED row are lit alternately.
26
Programming
■ Setting of the detection range (→ page 30)
• Allow the medium to flow through the system at the required maximum flow rate.
• Press the Learn/Set button for 6-8 s (= adjustment to maximum flow / upper limit of the detection range).
This setting is sufficient for the majority of waterbased applications.
Optional: adjustment to minimum flow.
• Allow the medium to flow through the system at the required minimum flow rate or bring flow to a standstill.
• Press the Learn/Set button for 11-15 s (= adjustment to minimum flow or flow standstill / lower limit of the detection range).
■ Remote adjustment via programming wire
Apply the operating voltage (+U
B
) to pin 2 for the respective time.
■ Setting of the switch point (→ page 32)
• Press the Mode/Enter button briefly.
• Press the Learn/Set button for 5 s,
• keep the Learn/Set button pressed or press the button several times until the requested switch point is set.
• Press the Mode/Enter button briefly.
■ Manual adjustment to maximum flow (HI-Teach) (→ page 33)
• Allow the medium to flow through the system at the required maximmum flow rate.
• Press the Mode/Enter button twice.
• Press the Learn/Set button for 5 s, release the button when LED bar fills from left to right.
• Press the Mode/Enter button briefly, when LED 9 is lit.
■ Manual adjustment to maximum flow (HI-Teach) / monitoring
excess flow (
→ page 34)
• Allow the medium to flow through the system at the required maximmum flow rate.
• Press the Mode/Enter button twice.
• Press the Learn/Set button for 5 s, release the button when LED bar fills from left to right.
• When LED 9 (= LED for the maximum display value) is lit: Press the
Learn/Set button several times to shift the LED.
• Press the Mode/Enter button briefly.
27
■ Manual adjustment to minimum flow (LO-Teach) (→ page 35)
• Allow the medium to flow through the system at the required minimum flow rate or bring flow to a standstill.
• Press the Mode/Enter button three times.
• Press the Learn/Set button for 5 s, release the button when LED bar fills from right to left.
• Press the Mode/Enter button briefly, when LED 0 is lit.
■ Activate / deactivate the function for remote adjustment
( → page 36)
• Press the Mode/Enter button four times.
• Press the Learn/Set button for 5 s,
• keep the Learn/Set button pressed or press the button several times until the requested function is set (function active, when 3 LEDs
on the right and 3 LEDs left are lit green; function not active,
when the 4 LEDs in the middle are lit in red).
• Press the Mode/Enter button briefly.
■ The following applies to all setting procedures:
• If no button is pressed for 20 s during the setting procedure, the unit returns to the operating mode with the parameter values unchanged.
• If adjustment has not been possible, all the red LEDs flash. The unit returns to the operating mode with the parameter values unchanged.
■ Locking / Unlocking
The unit can be electronically locked to prevent unwanted adjustment of the set parameters: Press both setting buttons for 10 s (the unit must be in Run mode). Indication goes out briefly (acknowledgement of locking / unlocking).
Units are delivered from the factory in the unlocked state.
If the unit is locked, it is possible to indicate
• the current switch point (press the Mode/Enter button once) and
• the setting of the function for remote adjustment (press the
Mode/Enter button two times).
28
Installation and set-up / Operation / Maintenance
After mounting, wiring and setting check whether the unit operates correctly.
At power on, all LEDs light and go off one after the other.* The unit is then ready for operation.
*During this time the output is switched according to the programming: ON with the NO function and OFF with the NC function.
Failure indication: In the case of a short circuit the function indicati-
on and the red LED row are lit alternately.
Recommended maintenance
Check the sensor tip for build-up from time to time. Clean it with a soft cloth. If necessary, build-up which adheres firmly (e.g. lime) can be removed with a common vinegar cleansing agent.
Technical data
Operating voltage [V] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 ... 36 DC 1)
Current rating [mA]. . . . . . . . . . . . . . . . . . . . . 400; short-circuit protection; reverse polarity protection / overload protection
Voltage drop [V] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 2.5
Current consumption [mA] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 80
Liquids
Medium temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80
Setting range [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ... 300
Greatest sensitivity [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ... 60
Max. temperature gradient of medium [K/min] . . . . . . . . . . . . . . . . . . . 300
Gases
Medium temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80
Setting range [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 ... 3000
Greatest sensitivity [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 ... 800
Response time [s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ... 10
Power-on delay time [s] . . . . . . . . . . . . . . . . . . . . . . . 15, optically indicated
Pressure rating [bar]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Operating temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 67 (IEC 60529) / UL50)
Housing material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PBT-GF 20
Material sensor surface (SI10xx) . . . . . . . . . . . . . . . stainless steel (316S12);
O-ring: FPM 8x1.5 gr 80° Shore A
Material sensor surface (SI11xx) titanium; O-ring: FPM 8x1.5 gr 80° Shore A
1) to EN50178, SELV, PELV; referring to UL: see page 26 (Electrical connection).
29
Programming diagrams / Technical information
■ Setting of the detection range
The detection range (window) is determined by:
• Adjustment to the required maximum flow (HI-Teach)
= upper limit of the window.
This setting is sufficient for the majority of waterbased applications.
• Adjustment to the required minimum flow / flow standstill
(LO-Teach) = lower limit of the window.
0
LO
LO HI
0 1 2 3 4 5 6 7 8 9
HI sensor signal
0 1 2 3 4 5 6 7 8 9
LO
0 1 2 3 4 5 6 7 8 9
HI
• Adjustment to maximum flow (HI-Teach)
The unit detects the current flow and sets this value as the maximum value for the LED display (LED 9).
1
Apply the operating voltage. After approx. 15 s the unit is ready.
Allow the medium to flow through the system at the required
maximum flow rate.
2
M S
6-8 s
LO
LO
HI
HI
Press the Learn/Set button and keep it pressed.
The green LEDs on the right and on the left flash, after 5 s the LED bar (green) fills from left to right
(release the button now).
LO HI
The indication goes off briefly.
The unit stores the current flow as maximum flow and passes into the operating mode.
30
• Adjustment to minimum flow / flow standstill (LO-Teach),
optional
The unit detects the current flow and sets this value as the minimum display value for the LED display. In normal operation the first green
LED (LED 0) flashes when the flow falls below this value (or when it comes to a standstill).
NOTE: The LO-Teach operation may only be carried out after the HI-
Teach operation.
1 Allow the medium to flow through the system at the required minimum flow rate or bring to a standstill.
M S
11-15 s
LO
LO
HI
HI
Press the Learn/Set button and keep it pressed.
The green LEDs on the right and on the left flash, after 5 s the LED bar (green) fills from left to right
2
LO HI after a further 5 s the LED bar
(gren) fills from right to left
(release the button now).
LO HI
The indication goes off briefly.
The unit stores the current flow as minimum flow and passes into the operating mode.
• Remote adjustment
You can also adjust the unit via the programming wire, if the function for remote adjustment is active. Apply the operating voltage (+U
B
) to pin 2 (P) for the respective time: min. 6 s / max. 8 s for HI-Teach; min.
11s / max. 15 s for HI-Teach.
If the operating voltage is applied to pin 2 for more than 15 s,
• the adjustment does not become effective; the unit passes into the operating mode with unchanged values,
• the unit is locked (the buttons are inactive as long as the operating voltage is applied).
31
■ Setting of the switch point
The switch point is preset at the factory (LED 7). The setting influences the reaction time of the unit.
• High switch point = fast reaction in the case of flow decrease.
• Low switch point = fast reaction in the case of flow increase.
1
2
3
M S
1 x
M S
>5 s
M S
LO
LO
LO
LO
HI
HI
HI
HI
Press the Mode/Enter button briefly. The current switch point is indicated:
LED lit: coarse setting, LED flashes: fine setting.
Press the Learn/Set button and keep it pressed.
After 5 s the switch point is increased* (incremental by pressing briefly or scrolling by holding pressed).
Indication:
The flashing LED moves from left to right. After LED 9 has been reached the cycle starts again at
LED 0. The LED which is constantly lit moves on by one position.**
Press the Mode/Enter button briefly (acknowledgement).
The indication goes off briefly.
The set switch point becomes effective; the unit passes into the operating mode.
*Decrease the switch point: Let the flashing and lit LEDs move to the maximum setting value. Then the cycle starts again at the minimum setting value.
**Overflow: If the flashing LED and the lit LED exceed the maximum setting value, the cycle starts again at the minimum setting value.
32
■ Manual adjustment to maximum flow (HI-Teach)
The unit detects the current flow and sets this value as the maximum value for the LED display (LED 9).
In normal operation all LEDs are lit in green when the max. flow is reached. They go out step by step as the flow decreases.
1
Apply the operating voltage. After approx. 15 s the unit is ready.
Allow the medium to flow through the system at the required
maximum flow rate.
M S
2
LO HI
Press the Mode/Enter button twice.
LED 9 flashes.
2 x
M S
3 >5 s
LO
LO
HI
HI
Press the Learn/Set button and keep it pressed.
after 5 s the LED bar (green) fills from left to right
(release the button now), after this LED 9 is lit.
4
M S
LO HI
Press the Mode/Enter button briefly (acknowledgement).
The indication goes off briefly.
The unit stores the current flow as maximum flow and passes into the operating mode.
33
■ Manual adjustment to maximum flow (HI-Teach) /
monitoring excess flow
The unit detects the current flow and sets this value as the maximum value for the LED display (LED 9).
In addition the position of the display window within the detection range can be defined: Shift the LED for the maximum display value to position 8, 7, 6 or 5. In the case of maximum flow all LEDs from 0 up to this LED are lit. The LEDs above the range signal excess flow. If the switch point is above this range, the unit switches in the case of excess flow.
1
Apply the operating voltage. After approx. 15 s the unit is ready.
Allow the medium to flow through the system at the required
maximum flow rate.
M S
2
LO HI
Press the Mode/Enter button twice.
LED 9 flashes.
2 x
M S
3 >5 s
LO
LO
HI
HI
Press the Learn/Set button and keep it pressed, after 5 s the LED bar (green) fills from left to right
(release the button now), after this LED 9 is lit.
4
5
M S
M S
LO
LO
HI
HI
Press the Learn/Set button several times until the requested
LED lights (LED 8, 7, 6 or 5).
Each time the button is pressed the LED moves back by one position.
When it is lower than LED 5 the cycle starts again at LED 9.
Press the Mode/Enter button briefly (acknowledgement).
The indication goes off briefly.
The unit stores the current flow as maximum flow and passes into the operating mode.
34
■ Manual adjustment to minimum flow (LO-Teach)
The unit detects the current flow and sets this value as the minimum display value for the LED display. In normal operation the first green
LED (LED 0) flashes when the flow falls below this value (or when it comes to a standstill).
NOTE: The LO-Teach operation may only be carried out after the HI-
Teach operation.
1 Allow the medium to flow through the system at the required
minimum flow rate or bring to a standstill.
2
M S
LO HI
Press the Mode/Enter button three times.
LED 0 flashes.
3 x
M S
3
4
>5 s
M S
LO
LO
LO
HI
HI
Press the Learn/Set button and keep it pressed.
after 5 s the LED bar (green) fills from right to left
(release the button now), after this LED 0 is lit.
HI
Press the Mode/Enter button briefly (acknowledgement).
The indication goes off briefly.
The unit stores the current flow as minimum flow and passes into the operating mode.
35
■ Activate / deactivate the function for remote adjustment
If the function is active, the unit can be adjusted by applying voltage to pin 2.
Unit supplied: function active.
Function active
LO HI The 3 LEDs on the right and left are lit in green.*
Function not active
LO HI
The 4 LEDs in the middle are lit in red.*
*The LEDs flash if voltage is applied to pin 2.
1
2
M S
4 x
M S
>5 s
LO
LO
LO
HI
Press the Mode/Enter button four times.
The current setting is indicated.
HI
Press the Learn/Set button and keep it pressed,
HI after 5 s the function changes.
(Each time the Learn/Set button is pressed the function changes again).
3
M S
LO HI
Press the Mode/Enter button briefly (= acknowledgement).
The indication goes off briefly, the unit then passes into the operating mode.
If the function for remote adjustment is active and the operating voltage is applied to pin 2 for more than 15 s, the unit is locked (the buttons are inactive as long as the operating voltage is applied).
Use 4-wire connection cables without a link between pins 2 and 4.
With 3-wire sockets with a link between pin 2 and pin 4 switching of the output stage triggers the remote adjustment!
36
Hysteresis function
flow maximum flow switch point (SP) hysteresis minimum flow
OUT
OUT
1
0
1
0 t
When the flow rises, the output switches when the switch point (SP) has been reached.
When the flow falls again, the output switches back when the value
"SP minus hysteresis" has been reached.
The hysteresis is considerably influenced by the choice of the operating range on the sensitivity curve of the sensor:
• In the case of adjustment to HI-Flow values in the range 0 ... 60cm/s the hysteresis is 2 - 4 cm/s (values apply to water).
• In the case of adjustment to HI-Flow values above 100 cm/s the hysteresis increases as the flow rises.
The typical response time of the unit is 3 ... 8s. It can be influenced by setting the LO-Teach and the switch point:
• The lower the LO-Teach or the switch point is set, the faster the unit switches on.
• The higher the LO-Teach or switch point is set, the faster the unit switches off.
37
Bedienungsanleitung
Operating instructions
Notice utilisateurs
R
Elektronischer
Drucksensor
Electronic pressure sensor
Capteur de pression
électronique
PN70XX
Safety instructions
Read the product description before installing the unit. Ensure that the product is suitable for your application without any restrictions.
Non-adherence to the operating instructions or technical data can lead to personal injury and/or damage to property.
In all applications check compliance of the product materials
(see Technical data) with the media to be measured.
For gaseous media the application is limited to max. 25 bar.
Controls and indicating elements
1 2
3
Mode/Enter Set
4
5
1
2
3
3 (4) x LED green
2 x LED yellow
4-digit alphanumerical display
Set button 4
5
16
Mode / Enter button
Lighting LED = set display unit.
Switching status; lights if the respective output has switched.
Display of the system pressure, display of parameters and parameter values.
Setting of the parameter values
(scrolling by holding pressed; incremental by pressing briefly).
Selection of the parameters and acknowledgement of the parameter values.
Function and features
• The pressure sensor detects the system pressure,
• shows the current system pressure on its display,
• and generates 2 output signals according to the set output configuration.
Switching function
(output 1 and output 2; function can be selected for each output separately)
Diagnostic function
(only output 2) hysteresis function / N.O. (Hno) hysteresis function / N.C. (Hnc) window function / N.O. (Fno) window function / N.C. (Fnc)
OU2 = dESI; in case of a fault output 2 becomes inactive.
Applications (Type of pressure: relative pressure)
Order no.
Measuring range
Permissible overl. pressure
Bursting pressure
PN7000
PN7001
PN7002
PN7003
PN7004
PN7006
PN7007
PN7009
PN7060 bar
0...400
0...250
0...100
0...25
-1...+10
0...2.5
0...1
-1...+1
0...600
PSI
0...5 800
0...3 625
0...1 450
0...363
-14.5...145
0...36.3
0...14.5
-14.5...+14.5
0...8 700 bar
600
400
300
150
75
20
10
20
800
PSI
8 700
5 800
4 350
2 175
1 087
290
145
290
11 600 bar
1 000
850
650
350
150
50
30
50
1 200
MPa = bar ÷ 10 / kPa = bar × 100
Avoid static and dynamic overpressure exceeding the given overload pressure.
For gaseous media the application is limited to max. 25bar.
Even if the bursting pressure is exceeded only for a short time the unit can be destroyed (danger of injuries)!
PSI
14 500
12 300
9 400
5 075
2 175
725
450
725
17 400
High-pressure units (400 bar, 600 bar) are supplied with an integrated damping device to comply with the regulations for UL approval and to avoid any risk of injury in case of bursting when bursting pressure is exceeded.
17
When the damping device is removed
• the unit can no longer be used under UL conditions,
• the damping device can become unusable.
If you have any questions, please contact ifm electronic's sales specialists.
Operating modes
Run mode
Normal operating mode
At power on the unit is in the Run mode. It carries out its measurement and evaluation functions and provides output signals according to the set parameters.
The display shows the current system pressure. The yellow LEDs indicate the switching state of the outputs.
Display mode
Indication of parameters and the set parameter values
When the "Mode/Enter" button is pressed briefly, the unit passes to the Display mode which allows parameter values to be read. The internal sensing, processing and output functions of the unit continue as if in Run mode.
• The parameter names are scrolled with each pressing of the
"Mode/Enter" button.
• When the "Set" button is pressed briefly, the corresponding parameter value is displayed for 15 s. After another 15 s the unit returns to the Run mode.
Programming mode
Setting of the parameter values
While viewing a parameter value pressing the "Set" button for more than 5 s causes the unit to enter the programming mode. You can alter the parameter value by pressing the "Set" button and confirm the new value by pressing the "Mode/Enter" button. The internal sensing, processing and output functions of the unit continue as if in
Run mode with the original parameter values unless a new value is confirmed.
The unit returns to the Run mode when no button has been pressed for 15 s.
18
Installation
Before mounting and removing the sensor, make sure that no pressure is applied to the system.
Mount the pressure sensor on a G¼ process connection.
Electrical connection
The unit must be connected by a suitably qualified electrician.
The national and international regulations for the installation of electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
The device shall be supplied from an isolating source and protected by an overcurrent device such that the limited voltage circuit requirements in accordance with UL 508 are met.
Disconnect power before connecting the unit as follows:
2: OUT2
4: OUT1
2 x p-switching
1 BN
2 WH
4 BK
3 BU
L+
L
2: OUT2
4: OUT1
2 x n-switching
1 BN
2 WH
4 BK
3 BU
L+
L
Connector view (sensor)
2
3 1
4
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white),
3 = BU (blue), 4 = BK (black).
Pin 4 (OUT1) = switching output
Pin 2 (OUT2) = switching output if
OU2 = Hno, Hnc, Fno, Fnc
Pin 2 (OUT2) = diagnostic output if
OU2 = dESI
19
Programming
1
Mode/Enter Set
Press the Mode/Enter button several times until the respective
parameter is displayed.
Mode/Enter Set
Press the Set button and keep it pressed. The current parameter
value flashes for 5 s,
2
then the value is increased*
(incremental by pressing briefly or scrolling by holding pressed).
3
4
Mode/Enter Set
Change more parameters:
Start again with step 1.
Press the Mode/Enter button
briefly (= acknowledgement).
The parameter is displayed again, the set parameter value
becomes effective.
Finish programming:
Wait for 15 s or press the
Mode/Enter button until the current measured value is indicated again.
*Decrease the value: Let the display of the parameter value move to the maximum setting value. Then the cycle starts again at the minimum setting value.
Select the display unit (Uni) before setting values for the parameters SPx and rPx. This avoids rounding errors generated internally during the conversion of the units and enables exact setting of the values.
Setting at the factory: bAr.
If no button is pressed for 15 s during the setting procedure, the unit returns to the Run mode with unchanged values.
The unit can be electronically locked to prevent unwanted adjustment of the set parameters: Press both pushbuttons until
To unlock: Press both pushbuttons until is displayed.
is displayed. Units are delivered from the factory in the unlocked state.
With the unit in the locked state is indicated briefly when you try to change parameter values.
20
Installation and set-up / operation
After mounting, wiring and setting check whether the unit operates correctly.
Fault indication
Overload (above measuring range of the sensor).
Underload (below measuring range of the sensor).
Flashing: short circuit in the switching output 1*.
Flashing: short circuit in the switching output 2*.
Flashing: short circuit in both switching outputs*.
Flashing: internal fault
*The output concerned is switched off as long as the short circuit continues.
The faults SC1, SC2, SC, Err are indicated even if the display is deactivated.
Diagnostic function
(according to DESINA specification)
Output 2 is used as a diagnostic output if OU2 = dESI.
• If there is no fault, the output is switched and carries UB+ (if P-n =
PnP) or UB- (if P-n = nPn).
• In case of malfunctions the output becomes inactive. The following malfunctions are detected:
Measuring cell defect; short circuit in output 1; exceeding / not reaching the limits of the measuring range, EEPROM fault, RAM fault, processor fault.
21
Technical informations / Functioning / Parameters
Adjustable parameters
Switch-on point 1 / 2:
Upper limit value at which the output changes its switching status.
Setting range → page 38 / 39.
SP2 is active only if OU2 = Hno, Hnc, Fno or Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching status.
rPx is always lower than SPx. The unit only accepts values which are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is automatically reduced (rPx is set to the minimum setting value).
Setting range → page 38 / 39.
rP2 is active only if OU2 = Hno, Hnc, Fno or Fnc.
Configuration of output 1
4 switching functions can be set:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
Configuration of output 2
4 switching functions and the diagnostic function can be set:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
- dESI = Output 2 is used as a diagnostic output
Enhanced functions
This menu item contains a submenu with additional parameters.
You can access these parameters by pressing the SET button briefly.
If the submenu is protected with an access code,"Cod1" flashes in the display.
- Press the "Set" button and hold it pressed until the valid code no. is shown.
- Then briefly press the "Mode/Enter" button.
Delivery by ifm electronic: no access restriction.
22
Display unit
The measured value and the values for SPx, rPx can be displayed in the following units: bar / mbar, PSI, MPa / kPa, for PN7007 and PN7009 in addition inHg.
Select the display unit before setting the values for the parameters SPx, rPx. This avoids rounding errors generated internally during the conversion of the units and enables exact setting of the values.
Setting at the factory: Uni = bAr.
Min-Max memory for system pressure
• HI: displays the highest measured pressure
• LO: displays the lowest measured pressure (only PN7004 and
PN7009).
Erase the memory:
- Press the "Mode/Enter" button until HI or LO is displayed.
- Press the "Set" button and keep it pressed until “- - - -” is displayed.
- Then press the "Mode/Enter" button briefly.
Delay time for the switching outputs
dSx = switch-on delay; drx = switch-off delay.
The output does not immediately change its switching status when the switching condition is met but when the delay time has elapsed. If the switching condition is no longer met when the delay time has elapsed, the switching state of the output does not change.
• Setting range: 0 (= delay time not active) - 0.2 ... 50 s,
• in steps of 0.2 s.
dS2 / dr2 are not active if OU2 = dESI.
Output polarity
2 options can be selected:
- PnP = positive switching / - nPn = negative switching
This setting applies to both switching outputs.
Damping for the switching outputs
Pressure peaks of short duration or high frequency can be filtered out.
dAP-value = response time between pressure change and change of the switching status in ms.
• The value for dAP defines the switching frequency (f) of the output: dAP f [Hz]
3
170
6
80
10
50
17
30
30
16
60
8
125
4
250
2
500
1
23
Setting of the display
7 options can be selected: d1 = update of the measured value every 50 ms.
d2 = update of the measured value every 200 ms.
d3 = update of the measured value every 600 ms.
The update interval only refers to the display. It has no effect on the output.
rd1, rd2, rd3, = display as d1, d2, d3; but rotated 180°.
OFF = In the Run mode the display of the measured value is deactivated. If one of the buttons is pressed, the current measured value is displayed for 15 s. Another press of the
Mode/Enter button opens the Display mode.
The LEDs remain active even if the display is deactivated.
24
1
0
1
0
Hysteresis function (fig. 1):
The hysteresis keeps the switching state of the output stable if the system pressure varies about the preset value. With the system pressure rising, the output switches when the switch-on point has been reached (SPx). With the system pressure falling the output does not switch back until the switch-off point (rPx) has been reached.
The hysteresis can be adjusted: First the switch-on point is set, then the switch-off point with the requested distance.
Window function (fig. 2):
The window function enables the monitoring of a defined acceptable range.
When the system pressure varies between the switch-on point (SPx) and the switch-off point (rPx), the output is switched (window function / NO) or not switched (window function / NC).
The width of the window can be set by means of the difference between SPx and rPx. SPx = upper value, rPx = lower value.
1 2
P
P acceptable range
SP rP hysteresis
SP rP t
Hno
Hnc 1
0
1
0 t
Fno
Fnc
Technical data
Operating voltage [V] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 ... 36 DC 1)
Current consumption [mA] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 50
Current rating [mA] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Reverse polarity and overload protected up to 40 V
Short-circuit protected; Watchdog
Voltage drop [V]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 2
Power-on delay time [s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.3
Switching frequency [Hz] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170 ... 1
Accuracy / deviations (in% of the span)
- Accuracy of switch point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ± 0.5
- Characteristics deviation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ± 0.5
- Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ± 0.25 (0.5 for PN7060)
- Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ± 0.1
- Long-time stability (in% of value of measuring range / 6 months). < ± 0.05
- Temperature coefficients (TEMPCO) in the compensated temperature range 0 ... +80°C (in% of the span/10K) greatest TEMPCO of the zero point / of the span . . . . . . . . . . . . . 0.2 / 0.2
Materials (wetted parts) . . . . stainless steel (303S22); ceramics; FPM (Viton)
Housing material stainless steel (304S15); stainless steel (316S12);
PC(Macrolon); Pocan; PEI; EPDM/X (Santoprene); FPM (Viton)
Protection / Housing
Protection / Housing
2)
3) in addition PTFE (PN7003 ... PN7009)
. . . . . . . . . . . . . . . . . . . . IP 67 (IEC 60529) / (UL50)
. . . . . . . . . . . . . . . . . . . . IP 65 (IEC 60529) / (UL50)
Protective class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . III (EN 50178)
Insulation resistance [M Ω] . . . . . . . . . . . . . . . . . . . . . . . . > 100 (500 V DC)
Shock resistance [g] . . . . . . . . . . . . . . . . . . . . 50 (DIN / IEC 68-2-27, 11ms)
Vibration resistance [g] . . . . . . . . . . . . . 20 (DIN / IEC 68-2-6, 10 - 2000 Hz)
Switching cycles min. . . . . . . . . . . . . . . 100 million (50 million for PN7060)
Operating temperature [°C] . . . . . . . . . . . . . . . . . -20 ... +80 (at UB < 32 V)
-20 ... +60 (at UB > 32 V)
Medium temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80
Storage temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40 ... +100
EMC EN 61000-4-2 ESD: . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 / 8 KV
EN 61000-4-3 HF radiated: . . . . . . . . . . . . . . . . . . . . . . . . . 10 V/m
EN 61000-4-4 Burst: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 KV
EN 61000-4-5 Surge: . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 / 1 KV
EN 61000-4-6 HF conducted: . . . . . . . . . . . . . . . . . . . . . . . . 10 V
1)
2)
3) to EN50178, SELV, PELV referring to UL; see also page 19 (Electrical connection) for PN7060, PN7000 ... PN7002 for PN7003 ... PN7009
25
Operating Instructions
RIA452
Process display
BA188R/09/a3/10.05
51009173
RIA452
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . 52
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
1.2 Installation, commissioning and operation . . . . . . . 52
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . 52
1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
1.5 Notes on safety conventions and icons . . . . . . . . . . 53
2 Identification . . . . . . . . . . . . . . . . . . . 54
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . 54
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . 54
2.3 Certificates and approvals . . . . . . . . . . . . . . . . . . . 54
3 Installation . . . . . . . . . . . . . . . . . . . . . 55
3.1 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 55
3.2 Installation instructions . . . . . . . . . . . . . . . . . . . . . 55
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 56
4.1 Quick wiring guide . . . . . . . . . . . . . . . . . . . . . . . . 56
4.2 Connecting the device . . . . . . . . . . . . . . . . . . . . . . 59
4.3 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 60
5 Operation . . . . . . . . . . . . . . . . . . . . . . 61
5.1 Quick operation guide . . . . . . . . . . . . . . . . . . . . . 61
5.2 Display and operating elements . . . . . . . . . . . . . . . 62
5.3 Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
6 Commissioning. . . . . . . . . . . . . . . . . . 65
6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.2 Switching on the measuring device . . . . . . . . . . . . 65
6.3 Device configuration . . . . . . . . . . . . . . . . . . . . . . . 65
7 Maintenance. . . . . . . . . . . . . . . . . . . . 78
8 Accessories. . . . . . . . . . . . . . . . . . . . . 78
9 Trouble-shooting . . . . . . . . . . . . . . . . 78
9.1 Trouble-shooting instructions . . . . . . . . . . . . . . . . 78
9.2 Process error messages . . . . . . . . . . . . . . . . . . . . . 79
9.3 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
9.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
9.5 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
10 Technical data . . . . . . . . . . . . . . . . . . 82
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Endress+Hauser
Table of contents
51
Safety instructions RIA452
1 Safety instructions
Safe operation of the process display unit is only guaranteed if these Operating Instructions have been read and the safety instructions have been observed.
1.1
Designated use
The RIA452 process display unit analyses analog process variables and depicts them on its multicoloured display. Processes can be monitored and controlled using analog and digital outputs and limit relays. RIA452 provides the user with a wide range of software functions for this purpose.
Power can be supplied to 2-wire sensors with the integrated transmitter power supply.
– The device is seen as accessory equipment and may not be installed in hazardous areas.
– The manufacturer does not accept liability for damage caused by improper or non-designated use.
The device may not be converted or modified in any way.
– The device is designed for installation in a panel and may only be operated in an installed state.
1.2
Installation, commissioning and operation
This device has been constructed to state-of-the-art technology and meets all applicable standards and EU directives. The device, however, can be a source of application-related danger if used improperly or other than intended.
Installation, wiring, commissioning and maintenance of the device must only be carried out by trained technical personnel. They must have read and understood these Operating Instructions and must follow the instructions they contain. The information in the electrical wiring diagrams (see
Section 4 'Wiring') must be observed closely.
1.3
Operational safety
Technical improvement
The manufacturer reserves the right to adapt technical details to the most up-to-date technical developments without any special announcement. Contact your local sales centre for information about the current state of and possible extensions to the Operating Instructions.
1.4
Return
For a return, e.g. in case of repair, the device must be sent in protective packaging. The original packaging offers the best protection. Repairs must only be carried out by your supplier's service orga-
!
nisation.
Note!
Please enclose a note describing the fault and the application when sending the unit in for repair.
52 Endress+Hauser
RIA452 Safety instructions
1.5
Notes on safety conventions and icons
The safety instructions in these Operating Instructions are labelled with the following safety icons
" and symbols:
Caution!
This symbol indicates an action or procedure which, if not performed correctly, can result in
# incorrect operation or destruction of the device.
Warning!
This symbol indicates an action or procedure which, if not performed correctly, can result in injury,
!
a safety hazard or the destruction of the device.
Note!
This symbol indicates an action or procedure which, if not performed correctly, can have an indirect effect on operation or trigger an unexpected response on the part of the device.
Endress+Hauser 53
Identification
2 Identification
2.1
Device designation
2.1.1
Nameplate
Compare the nameplate on the device with the following diagram:
RIA452
54
Fig. 2:
1
2
3
4
5
Nameplate of the process display unit (example)
Order code and serial number of the device
Power supply
Software version number
Ambient temperature
Performance
2.2
Scope of delivery
The scope of delivery of the process display unit comprises:
• Process display unit for panel mounting
• Operating Instructions
• CD-ROM with PC configuration software and interface cable RS232 (optional)
• Fixing clips
!
• Sealing ring
Note!
Please note the device accessories in Section 8 'Accessories'.
2.3
Certificates and approvals
CE mark, declaration of conformity
The process display unit is designed to meet state-of-the-art safety requirements, has been tested and left the factory in a condition in which it is safe to operate. The device meets the relevant standards and directives as per IEC 61 010-1 "Safety requirements for electrical equipment for measurement, control and laboratory use".
The device described in these Operating Instructions thus meets the legal requirements of the EU directives. The manufacturer confirms that the device has been tested successfully by affixing the
CE mark.
Endress+Hauser
RIA452 Installation
3 Installation
3.1
Installation conditions
The permitted ambient conditions (see Section 10 "Technical data") must be observed when installing and operating. The device must be protected against the effects of heat.
3.1.1
Dimensions
Observe the device face-to-face length of 150 mm (5.91"). Further dimensions are provided in
Section 10 "Technical data".
3.1.2
Mounting location
Installation in panel with 92x92 mm (3.62"x3.62") cutout (as per EN 60529). The mounting location must be free from vibrations.
3.1.3
Orientation
Horizontal +/- 45 in every direction.
3.2
Installation instructions
Endress+Hauser
Fig. 3: Panel cutout (data in mm, data in inches in brackets)
Provide a panel cutout of 92x92mm (3.62"x3.62"). The installation depth is 150mm (5.91").
1.
Push the device with the sealing ring through the panel cutout from the front.
2.
Keep the device horizontal and suspend the two fixing clips in the recesses provided.
3.
Tighten the screws of the fixing clips evenly with a screwdriver.
The dimensions of the process display unit are provided in Section 10 "Technical data".
55
Wiring
56
RIA452
4
4.1
Wiring
Quick wiring guide
Current input
81
82
11
12
20..36V DC
20...28V AC
50/60Hz
90...250V AC
50/60Hz
Relay 8
Relay 7
Relay 6
Relay 5
146
151
152
153
141
142
143
154
155
156
144
145
Relay output nc
53
41
42
43
46
51
52
54
55
56
44
45
J1
J2
Relay 4
Relay 3
Relay 2
Relay 1
Relay 1-8
250V AC /30V DC
3 A
Analog output
0..20mA, 0..10V DC
Transmitter power supply unit
24V, <= 250mA
Internal circuits represented by dashed lines.
RS232
1
2
3
4
Digital inputs acc. to DIN 19240
Voltage level: -3...5 V low,
12...30 V high
Input current typ. 3 mA
(with overload and reverse polarity protection)
Input voltage max. 34.5 V
Sampling frequency max. 10 Hz
Digital output, passive open collector max. 24V, 200mA
Fig. 4: Terminal assignment of process display unit (Universal input see Page 58)
Terminal assignment
J2
11
Terminal Terminal assignment
L/L+
N/L-
L for AC
L+ for DC
N for AC
L- for DC
NC
J1
Not connected
Type
Power supply
Jumper for locking device operation via hardware.
If the jumper is set to J1, the configuration cannot be modified.
!
Note!
The device can always be configured with
Readwin ® 2000 via RS232, even if the jumper is attached to J1.
Not connected
+ 0/4 to 20mA signal
Endress+Hauser
RIA452
152
153
144
145
146
154
155
156
54
55
56
141
142
143
151
53
44
45
46
43
51
52
Terminal Terminal assignment
12
81
82
41
42
Signal ground (current)
24 V, sensor power supply 1
Ground, sensor power supply 1
Normally closed (NC)
Common (COM)
Normally open (NO)
Normally closed (NC)
Common (COM)
Normally open (NO)
Normally closed (NC)
Common (COM)
Normally open (NO)
Normally closed (NC)
Common (COM)
Normally open (NO)
Normally closed (NC)
Common (COM)
Normally open (NO)
Normally closed (NC)
Common (COM)
Normally open (NO)
Normally closed (NC)
Common (COM)
Normally open (NO)
Normally closed (NC)
Common (COM)
Normally open (NO)
Relay 3
Relay 4
Relay 5 (optional)
Relay 6 (optional)
Relay 7 (optional)
Relay 8 (optional)
Wiring
Type
Transmitter power supply (optionally intrinsically safe)
Relay 1
Relay 2
Endress+Hauser 57
Wiring
34
91
92
Terminal
96
Terminal assignment
Ground for digital status inputs
97
197
297
397
31
32
33
+ digital status input 1
+ digital status input 2
+ digital status input 3
+ digital status input 4
+ analog output
Ground, analog output
+ digital output
Ground, digital output
24 V, sensor power supply 2
Ground, sensor power supply 2
Type
Digital inputs
Analog output (optional)
Digital output (optional)
Transmitter power supply
Universal input option
The device can be optionally equipped with a universal input instead of a current input.
RIA452
58
Fig. 5: Universal input terminal assignment
Endress+Hauser
RIA452 Wiring
Terminal assignment
Terminal Terminal assignment
13
15
17
19
11
12
+ 0/4 to 20 mA signal
Signal ground (current, voltage, temperature)
± 1 V, + thermocouples, - resistance thermometer signal (3-wire/4-wire)
+ resistance thermometer signal (4-wire)
± 30 V
+ resistance thermometer power supply (3-wire/4-wire)
4.2
Connecting the device
"
Caution!
Do not install or wire the device when it is connected to the power supply. Failure to comply with this precaution can result in irreparable damage to the electronics.
"
4.2.1
Caution!
Connecting the power supply
• Before wiring the device, ensure that the supply voltage corresponds to the specification on the nameplate.
• For the 90 to 250 V AC version (mains connection), a switch marked as a separator, as well as an overvoltage organ (rated current d 10 A), must be fitted in the supply line near the device (easy to reach).
Fig. 6: Connecting the power supply
!
4.2.2
Note!
Connecting external sensors
Active and passive sensors with analog, TC, resistance and RTD sensors can be attached to the device.
Depending on the type of signal of the sensor in question, the terminals can be freely selected which means the process display unit can be used with great flexibility.
Endress+Hauser 59
Wiring
Current input 0/4...20 mA active sensor passive sensor
81 81
82 82
Fig. 7:
Y
-
11
12
11
Y
-
Terminals 12 and 82 internally bridged
12
Connecting a 2-wire sensor to current input 0/4...20 mA
Universal input
RIA452
60
Fig. 8: Connecting a sensor to universal input
4.3
Post-connection check
Device condition and specifications
Is the device or cable damaged (visual inspection)?
Electrical connection
Does the supply voltage match the specifications on the nameplate?
-
Notes
Notes
90 to 250 V AC (50/60 Hz)
20 to 36 V DC
20 to 28 V AC (50/60 Hz)
Are all of the terminals firmly engaged in their correct slots? Is the coding on the individual terminals correct?
Are the mounted cables strain relieved?
Are the power supply and signal cables correctly connected?
-
-
Are all screw terminals firmly tightened?
-
See wiring diagram on the housing
Endress+Hauser
RIA452 Operation
5 Operation
5.1
Quick operation guide
M1
M2
M3
Analog input
INPUT
Display
DISPLAY
Analog output
ANALOG
OUT
M5
Digital input 1-4
DIGITAL INP.
Signal type
Signal type
0% value
0% value
Connection type*
Connection
00% value
100% value
Assign numerical display
Ref. num.
Assign bargraph
Ref. bargraph
Curve
Curve
Offset
Offset
Assignment
Ref. num.
Offset
Offset
Function, digital input 1-4
Function
Damping
Out damp
Output in the event of a fault
Fail mode
Active level
1-4
Level
Decimal point bargraph
Dec. point
Output range
Out range
Value in the event of a fault
Fail value
Pump monitoring sampling time
Sampl. time
-
M10
M17
Limit
1-4 (8)
LIMIT
M18
Integration
INTEGRATION
Assignment
Ref. num
Alternate function
1-4 (8)
Alternate
Function
1-4 (8)
Function
Recurrent operation
24 h
Signal source for integration
Ref. Integr.
Integration base
Integr. base
Decimal point
Dec. point
Runtime display 1-8
Runtime
Decimal point factor
Dec. factor
Signal damping
1st order low pass
Damp
Comparative temperature*
Comp. temp
Dimension
Dimension
Fixed comparative temperature *
Const. temp
Decimal point
Dec. point
Cable open circuit detection
Open circ.
* = Only available if the associated option is installed in the device
0% value
Bar 0%
100% value
Bar 100%
Orientation
Bar rise
Decimal point
Dec. point
Simulation mA
Simu mA
0% value
Out 0%
Simulation Volt
Simu V
Switch point A
Setpoint A
Switching freq. display 1-8
Count
Factor
Factor
Switch point B
Setpoint B
Reset switching freq. and runtime
Reset
Dimension totalizer
Dimension
M19
Pulse output
PULSE OUT
M20
Min/Max memory
MIN/MAX
Decimal point pulse value
Dec value
Signal source for
Min/Max
Ref. Min/Max
Pulse value
Unit Value
Decimal point
Dec. point
Pulse width
Pulse width
Display minimum value
Min. value
Pulse output simulation
Sim pulseout
Display maximum value
Max. value
Reset minimum value
Reset min
M21
Linearisation table
LIN-TABLE
-
M23
Mxx
Lin. support points
NO 01 NO 32
Number of support points
Counts
X-axis
X value
M55
Operating parameters
PARAMETERS
User code
User code
Failsafe mode at
4-20 mA input
Namur
M56
SERVICE
M57
M58
EXIT
SAVE
Dimension linearised value
Dimension
Y-axis
Y value
Program name
Progname
Error limit 1
Range 1
Decimal point
Y-axis
Dec. Y value
Program version
Version
Error limit 2
Range 2
Delete all support points
Del points
Pump rotation function
Func. alt.
Error limit 3
Range 3
Show all support points
Show points
Relay lock time
Lock time
Error limit 4
Range 4
- For service personnel only. The service code must be entered.
- Exit the menu. If parameters have been changed, a query is issued whether the changes are to be saved.
- Changes are saved and the menu is exited.
Fig. 9: Operating matrix
100% value
Out 100%
Hysteresis or switchback gradient
Hysteresis
Relay simulation
Simu Relay
Switching delay
1-4 (8) in seconds
Delay
Decimal point totalizer
Dec. total
Reset totalizer
Totalizer
Reset maximum value
Reset max
Relay failsafe mode
Rel. Mode
Display contrast
Contrast
Time for gradient evaluation
Grad. Time
Endress+Hauser 61
Operation
5.2
Display and operating elements
RIA452
62
Fig. 10: Display and operating elements
4)
5)
6)
7)
1)
2)
3)
8)
9)
Green operating indicator, lights up when supply voltage is applied
Red fault indicator, flashes in event of sensor or device error
Limit value display: If power is supplied to a relay, the symbol is displayed.
Digital input status: green indicates ready for operation, yellow indicates a signal is present
Bargraph yellow, 42-section with orange/red range overshoot and undershoot
7-digit 14-segment display in white for measured values
9x77 DOT matrix in white for text or units
Key or lock symbol indicates whether device operation is locked (see Section 5.3.3)
Jog/shuttle dial for local device operation
5.2.1
Display
Range
Input current is < lower error limit
Input current above lower error limit and below lower limitations of validity
Input current in valid range
Display "
Display
"
Display " "
Display scaled measured value
Input current below upper error limit and above upper limitations of validity
Input current above upper error limit
Display "
Display "
"
"
Relay
Fault condition
Analog output
Set failsafe mode
Integration
No integration
Normal limit value behaviour Normal behaviour with max.
10% overrange. No output
< 0 mA/0 V possible
Normal limit value behaviour Normal behaviour with max.
10% overrange. No output
< 0 mA/0 V possible
Normal limit value behaviour Normal behaviour with max.
10% overrange. No output
< 0 mA possible.
Fault condition Set failsafe mode
Normal behaviour (negative integration not possible)
Normal behaviour (negative integration not possible)
Normal behaviour (negative integration not possible)
No integration
Relay display
No power to relay: no display
Power to relay: (symbol displayed (yellow))
Digital input status display
Digital input configured: (green)
!
Signal at digital input:
Note!
(yellow)
Information on trouble-shooting can be found in Sections 9.1 and 9.2 of these Operating
Instructions.
Endress+Hauser
RIA452 Operation
5.3
Local operation
You can enter the menu by pressing the jog/shuttle dial for > 3 s.
5.3.1
Operation using the jog/shuttle dial
A) E+H 3-key functions
• Press = "Enter"
• Turning clockwise = "+"
• Turning counterclockwise = "-"
Fig. 11: Operation using jog/shuttle dial
B) List selection
Fig. 12: List selection with jog/shuttle dial
Æ Downward arrow:
Selection is at top of the list. Further entries are displayed when the jog/ shuttle dial is turned to the right.
Å
Æ
Both arrows visible:
User is in the middle of the selection list.
Å
Upward arrow:
End of selection list is reached. User moves towards top of the list by turning jog/shuttle dial to the left.
5.3.2
Entering text
Endress+Hauser
Fig. 13: Entering text with RIA452
63
Operation RIA452
3
4
1
2
Item
No.
5
Description
Start entering text by pushing the jog/shuttle dial for > 3 s. The first character starts flashing.
Turn the jog/shuttle dial to change the flashing (selected) character (see "Possible characters").
Press the jog/shuttle dial to select the next character (in our example, the second character is now flashing).
If the jog/shuttle dial is pressed briefly for the last character, the information entered is accepted.
If the jog/shuttle dial is pressed longer than 1 second (max. 2 seconds), the data input is rejected.
Possible characters
The following characters can be entered: space +ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwxyz0123456789/\% 23 +-
.,:*()
5.3.3
Disabling the programming mode
The entire configuration can be protected against unintentional access by means of a four-digit code.
This code is assigned in the submenu "Parameter/User Code". All the parameters remain visible. If the value of a parameter should be changed, you are first asked for the user code.
In addition, configuration can also be locked using a switch on the rear of RIA452 (see Section 4.1).
This is indicated with a corresponding symbol on the display.
The "key" symbol is displayed if configuration is locked using the user code.
The "lock" symbol is displayed if hardware locking is activated.
64 Endress+Hauser
RIA452 Commissioning
6 Commissioning
6.1
Function check
Make sure that all post-connection checks have been carried out before you commission your device:
• See Section 3.3 'Post-installation check'
• Checklist Section 4.3 'Post-connection check'
6.2
Switching on the measuring device
Once the operating voltage is applied, the green LED (= device operating) lights up if no fault is present.
• When the device is first commissioned, it is in the status when delivered and uses the default settings for all parameters.
• When commissioning a device already configured or preset, measuring is immediately started as per the settings. The limit values only switch once the first measured value has been determined.
Function (menu item)
Signal type
6.3
Device configuration
This section describes all the configurable device parameters with the associated value ranges and factory settings (default values).
6.3.1
Analog input - INPUT/M1
All the parameters available for the input can be found under the analog input menu item which is marked as INPUT in the device.
Parameter setting
Off
4 - 20 mA
0 - 20 mA
0 - 5 mA *
0 - 100 mV *
0 - 200 mV *
0 - 1 V *
0 - 10 V *
± 150 mV *
± 1 V *
± 10 V *
± 30 V *
Type B (IEC584) *
Type J (IEC584) *
Type K (IEC584) *
Type L (DIN43710) *
Type L (GOST) *
Type N (IEC584) *
Type R (IEC584) *
Type S (IEC584) *
Type T (IEC584) *
Type U (DIN43710) *
Type D (ASTME998) *
Type C (ASTME998)
*
Description
Selects the signal type of the connected sensor. Parameters marked * can only be selected with the universal input option.
Endress+Hauser 65
Commissioning RIA452
Function (menu item)
Connection
Curve
3 Wire
4 Wire
Linear
Quad.
°C
°F
Kelvin
0..99.9
Parameter setting
PT50 (GOST) *
PT100 (IEC751) *
PT100 (JIS1604) *
PT100 (GOST) *
PT500 (IEC751) *
PT500 (JIS1604) *
PT500 (GOST) *
PT1000 (IEC751) *
PT1000 (JIS1604) *
PT1000 (GOST) *
Cu50 (GOST) *
Cu100 (GOST) *
30 - 3000 Ohm *
Damp
Dimension
Dec. point
0% value
100% value
Offset
XXXXXXXXX
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
-99999..99999
-99999..99999
-99999..99999
Comp. temp
Const. temp
Open circ.
Intern const
9999.9
No
Yes
Description
Selects the signal type of the connected sensor. Parameters marked * can only be selected with the universal input option.
Configures the sensor connection in 3-wire or 4-wire technology. Can only be selected for "Signal type" 3000 :, PT50/100/1000, Cu50/100
Linear or square (quad.) curve of the sensor used; can be selected for analog signals. °C, °F, Kelvin physical measured variable, can be selected for temperature sensors.
Signal damping of measuring input with 1st order low pass. Time constant can be selected from 0 to 99.9 sec.
The technical unit or an arbitrary text for the measured value of the sensor can be configured here. Max. length 9 characters.
Number of places after the decimal point for displaying the measured value.
Start value of measured value, can be selected for analog signal types
End value of measured value, can be selected for analog signal types
Shifts the zero point of the response curve. This function is used to adjust the sensor.
Comparative temperature for thermocouple measurement. An internal cold junction (= Intern) or a constant value (= const) can be selected.
Fixed comparative temperature.
This can only be selected if const is set for "Cmp. Temp".
Cable open circuit detection
Adjusting the analog input
The input can be adjusted to the sensor with the aid of the following parameters.
For non-temperature sensors, a scaled value is calculated from the sensor signal:
For temperature outputs, the scaled value is calculated from linearisation tables. The temperature value can be converted to degrees Celsius, degrees Fahrenheit or Kelvin. In addition, the temperature value can be corrected by means of an offset.
66 Endress+Hauser
RIA452 Commissioning
Function (menu item)
Ref. num.
Ref. bargraf
Dec. point
Bar 0%
Bar 100%
Bar rise
6.3.2
Display - DISPLAY/M2
All the settings for the device display are grouped under this menu item.
Parameter setting
Input
Lintab
Total
Description
Selects which value is shown on the display.
• Input = measured value
• Lintab = linearised measured value
• Total = integrated value (can only be selected if the pulse output option is available)
Selects the signal source for the bargraph Input
Lintab
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
-99999..99999
-99999..99999
Right
Left
Number of places after the decimal point for bargraph scaling.
Start value for the bargraph
End value for the bargraph
Bargraph orientation.
• Right = 100% value (rising from left to right)
• Left = 100% value left (falling from left to right)
Function (menu item)
Ref. num.
Out damp
Out range
Dec. point
Out 0%
Out 100%
Offset
6.3.3
Analog output - ANALOG OUT/M3
All the parameters available for the output can be found under the analog output menu item which is marked as ANALOG OUT in the device.
Parameter setting
Input
Lintab
0..99.9
Description
Selects which value is output at the analog output.
• Input = measured value
• Lintab = linearised measured value
Signal damping of measuring input with 1st order low pass. Time constant can be selected from 0 to 99.9 sec.
Signal type of output
!
Note!
"Off" switches the output signal off completely.
Off
0 - 20 mA
4 - 20 mA
0 - 10 V
2 - 10 V
0-1 V
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
-99999..99999
-99999..99999
-999.99..999.99
Number of places after the decimal point for outputting the measured value. Can be selected for analog signal types
Start value of the output signal
End value of the output signal
Shifts the zero point of the output curve in mA or V.
Endress+Hauser 67
Commissioning RIA452
Function (menu item)
Fail mode
Fail value
Hold const
Min
Max
Parameter setting
0..999.99
Description
Output value if a sensor or device error occurs.
• Hold = last valid value
• Const = freely selectable value
• Min = output value is 3.5 mA for 4-20 mA, and 0 V or 0 mA otherwise
• Max = output value is 22.0 mA for 0/4-20 mA, and 1.1 V or 11 V otherwise
The freely selectable value for "Fail mode = Const" can be set here.
Current output: 0...22 mA
Voltage output: 0...11 V
Outputs the selected current at the output regardless of the input value.
Is automatically set to OFF when exited.
Simu mA
Simu V
OFF
0.0 mA
3.6 mA
4 mA
10 mA
12 mA
20 mA
21 mA
OFF
0.0 V
5.0 V
10.0 V
Outputs the selected voltage at the output, regardless of the input value.
Is automatically set to OFF when exited.
Function (menu item)
Function
Level
Sampl. time
6.3.4
Digital input - DIGITAL INP./M5
The settings for the digital status inputs, e.g. for monitoring pumps, starting/stopping the counter or resetting the min/max-value memory are grouped in this section.
Note: The digital status inputs are permanently assigned to the relays in the PUMP function. Relay 1 is monitored by digital input 1, relay 2 by digital input 2 etc.
Parameter setting
OFF
Pump
Res. Tot.
Start/Stop
Min/Max
Low
High
0..99
Description
Function of the selected digital input.
• OFF
• Pump = pump monitoring (see Pump monitoring function)
• Res. Tot. = reset the totalizer*
• Start/Stop = start or stop the totalizer*
• Min/Max = reset the min/max memory values
!
Note!
Parameters marked * are only available with the pulse output option.
Selects the side for evaluation.
• Low = descending side
• High = increasing side
Defines the time within which pump feedback at the digital input is to be expected. If there is no feedback within the defined time, an error message is generated and a second pump is activated if more than one pump is available.
68 Endress+Hauser
RIA452 Commissioning
Pump monitoring function
The digital inputs 1-4 are permanently assigned to each relay 1-4. If the function of the digital input is set to pump monitoring, the sampling time starts when the relay is switched on. When the sampling time expires, the digital input is sampled continuously. If the signal is not active, the relay is switched off immediately and a fault message is generated (see ). If the alternate function for this relay is activated, a relay with an alternate function is also searched for and switched on.
Level
Threshold
Max + hysteresis
Threshold max
Relay
Digital input
Sampling time t
Quiescent state
Fault state
Active
Inactive
Pump feedback
OK
Relay remains energised
Fig. 14: Pump monitoring, pump OK
Endress+Hauser
Fig. 15: Pump monitoring, pump fault
The following parameters must be configured:
Menu
DIGITAL INP./M5
Function (menu item)
Function
Level
Sampl. time
Setting value
Pump
Low or High
Sampling time in seconds
69
Commissioning RIA452
Function (menu item)
Ref. num.
Function
Dec. point
Setpoint A
Setpoint B
Hysteresis
Delay
Alternate
24h
Runtime
Count
Reset
Simu relay
6.3.5
Limit values - LIMIT 1...8/M10...17
Parameter setting
Input
Lintab
Min
Max
Grad
In band
Out band
Alarm
Description
Selects which value is used:
• Input: scaled value from analog input
• Lintab: value from linearisation table
Selects limit value and fault monitoring. The relays are currentless in the event of device errors or incorrect input values (see error limits range 1...4 in
Section 1.3.11).
• Min: minimum with hysteresis (see Fig. 16)
• Max: maximum with hysteresis (see Fig. 17)
• Grad: gradient (see Fig. 18)
• In band: validity range within two values
• Out band: validity range outside of two values
• Alarm: relay is used as an alarm relay
Number of digits after the decimal point for the limit value.
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
-99999...99999
-99999...99999
-99999...99999
0...99
No
Yes
0...60
Measured value at which a change in the switch status occurs (slope for gradient).
Default: 0.0
The second setpoint can be configured for the "In band" and "Out band" operating modes.
For entering the hysteresis for the threshold at minimum/maximum.
Sets the limit value event delay once the threshold is reached (in seconds)
(see Fig. 19).
Determines the switching function for this relay:
• No: none; switch point permanently assigned to relay
• Yes: alternate function (see Fig. 20)
Limit value is activated cyclically every 24 hours for 0...60 min.
Displays the run time of the connected device, e.g. pump, in hours [h].
Records the switching frequency of the limit value.
Resets the run time and switching frequency for this limit value.
No
Yes
Off
Low
High
Simulation of the selected limit value. Is automatically set to OFF when exited.
70 Endress+Hauser
RIA452 Commissioning
Min operating mode
Measured value
Threshold
+ hysteresis
Threshold
Min
Hysteresis t
Relay at quiescent state
Relay at fault state
Fig. 16: Min operating mode
The following parameters must be configured:
Menu
LIMIT 1...8/M10...17
Function (menu item)
Function
Setpoint A
Hysteresis
Max operating mode
Measured value
Threshold
Max
Threshold
- hysteresis
Setting value
Min
Value for threshold
Value for hysteresis
Hysteresis t
Relay at quiescent state
Relay at fault state
Fig. 17: Max operating mode
The following parameters must be configured:
Menu
LIMIT 1...8/M10...17
Function (menu item)
Function
Setpoint A
Hysteresis
Setting value
Max
Value for threshold
Value for hysteresis
Endress+Hauser 71
Commissioning RIA452
Grad operating mode
Measured value
M
0
M
0-m
T m
T
0
M
1-m
M
1
T m
T
1 evaluation t
Relay at quiescent state
Relay at fault state
Fig. 18: Grad operating mode
The "Grad" operating mode is used for monitoring the changes in the input signal over time. The time basis t m
of the monitoring system is configured in the "PARAMETER/M55 -> Grad. time" menu.
The difference between the lower range value M
0-m
and the upper range value M
0
of the interval is calculated. If the calculated value is greater that the value set under "Setpoint A", the relay is switched currentless.
The relay is switched on again once the difference between M
1-m
and M
1
drops below the value set in "Hysteresis". The sign determines the direction of signal change. A new value is calculated every
1.0 s (floating interval).
The following parameters must be configured:
Menu Function (menu item) Setting value
LIMIT 1...8/M10...17
Function
Setpoint A
Hysteresis
Grad
Gradient value for threshold
Value for hysteresis
Delay
Measured value
Threshold
Max
Threshold
- hysteresis
Delay
Hysteresis t
Relay at quiescent state
Relay at fault state
Fig. 19: Delay
72 Endress+Hauser
RIA452 Commissioning
The following parameters must be configured:
Menu Function (menu item)
LIMIT 1...8/M10...17
Setpoint A
Hysteresis
Delay
Setting value
Value for threshold
Value for hysteresis
Delay time in [s]
Alternate
Measured value
Setpoint A 3
Setpoint A 3
- Hysterese 3
Setpoint A 2
Setpoint A 2
- Hysterese 2
Setpoint A 1
Setpoint A 1
- Hysterese 1
Mode Max t
With alternating pump control
Switching status
Relay 3
Relay 2
Relay 1 t
Without alternating pump control
Switching status
Relay 3
Relay 2
Relay 1 t
Relay currentless
Fig. 20: Alternating pump control
Alternate switching is used to ensure that several pumps are utilised evenly in level control systems.
The main factor for switching on a certain pump is not a fixed assigned switch-on value but rather
!
the question as to which pump was out of operation the longest.
Note!
Relays not included in alternating pump control are available.
This function cannot be applied to individual relays. Relays not included are not assessed based on the switch-on and switch-off duration.
The following parameters must be configured for the example above:
Menu Function (menu item) Setting value
LIMIT 1...3/M10...12
Each: Setpoint A
Each: hysteresis
Each: alternate
Value for threshold
Value for hysteresis
Yes
Endress+Hauser 73
Commissioning RIA452
Function (menu item)
Ref. integr.
Integr. base
Dec. factor
Factor
Dimension
Dec. total
Totalizer
Reset Total
6.3.6
INTEGRATION/M18
This function can only be selected if the pulse output option is available in the device.
Parameter setting
Input
Lintab
Description
Selects which value should be integrated.
• Input = measured value
• Lintab = linearised measured value
Time basis for integration OFF sec
Min hour day
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
0 ..99999
XXXXXXXXX
Decimal point position of the conversion factor
Conversion factor
The technical unit or an arbitrary text for the measured value of the sensor can be configured here. Max. length 9 characters.
Decimal point of totalizer XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
9999999
No
Yes
Assign totalizer a default value.
Reset totalizer
!
Note!
Cannot be configured with ReadWin ® 2000.
Integration function
With this function, the computed value from the linearisation table or that of the analog input can be numerically integrated to create a totalizer for example.
The totalizer is calculated as follows:
Function (menu item)
Dec. value
The measuring interval is 0.1 s.
6.3.7
Pulse output - PULSE OUT/M19
All the possible settings for the pulse output can be found in this menu item. This menu item can only be selected if your device is fitted with this option.
Parameter setting
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
Description
Decimal point position of the pulse value.
74 Endress+Hauser
RIA452 Commissioning
Function (menu item)
Unit value
Pulse width
Parameter setting
0 ..99999
0.04 .. 2000ms
Description
Pulse value with which the pulses at the output should be output.
Sets the pulse width at the pulse output.
!
Note!
The maximum output frequency depends on the pulse width: f(max) = 1 / (2*pulse width)
Outputs the selected pulses at the pulse output regardless of the input value.
Is automatically set to OFF when exited.
Sim pulseout OFF
1 Hz
10 Hz
100 Hz
1000 Hz
10000 Hz
Function (menu item)
Ref. min/max
Dec. point
Min. value
Max. value
Reset min
Reset max
No
Yes
No
Yes
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
0..99999
0..99999
6.3.8
Min/Max memory - MIN MAX/M20
The RIA452 can save a minimum and a maximum measured value. The input signal or the signal processed using the linearisation table are available as the signal source. The memory is reset manually or using the digital input (see Section 6.3.4).
Parameter setting
Input
Lintab
Description
Signal source for the min/max value memory.
• Input = input signal
• Lintab = linearised input signal
Number of digits after the decimal point for the min/max value memory.
Displays the current minimum value in the memory.
Displays the current maximum value in the memory.
Resets the minimum value memory.
Resets the maximum value memory.
Endress+Hauser 75
Commissioning RIA452
Function (menu item)
Counts
Dimension
Dec. Y value
Del. points
Show points
6.3.9
Linearisation table - LIN. TABLE/M21
The RIA452 can store a table which can be used to linearise the input signal. This table can convert a level signal to the associated volume for example.
Parameter setting
2..32
XXXXXXXXX
Description
Number of support points needed. At least two points have to be entered.
The technical unit or an arbitrary text for the measured value of the sensor can be configured here. Max. length 9 characters.
Decimal point position for the Y-values in the linearisation table.
No
Yes
No
Yes
XXXXXXX
XXXXXX.X
XXXXX.XX
XXXX.XXX
XXX.XXXX
Delete all programmed support points.
Show all programmed support cells.
Function (menu item)
X value
Y value
6.3.10
Support points of linearisation table - LINPOINTS 1..X/
M23..MXX
Displays the set value pairs of the linearisation table. This menu item is only visible if a linearisation table was configured under Section 6.3.9 and "Yes" was selected in the "Show points" parameter in the "LIN. TABLE/M21" menu.
Parameter setting
-99999..99999
-99999..99999
Description
X-value of the linearisation table. Corresponds to the input value.
Y-value that belongs to the previous X-value. Corresponds to the converted measured value.
76 Endress+Hauser
RIA452 Commissioning
Function (menu item)
User code
Progname
Version
Func. alt.
Lock time
Rel. Mode
Grad. Time
Namur
Range 1
Range 2
Range 3
Range 4
Contrast
6.3.11
Operating parameter - PARAMETER/M55
This menu item contains configuration options such as the user code, failsafe mode of RIA452 to
NAMUR etc.
Parameter setting
0..99999
ILU00xA
V X.XX.XX
Time
Count
99.9
OFF
ON
1..100
No
Yes
3.6 (0.0...22.0)
3.8 (0.0...22.0)
20.5 (0.0...22.0)
21.0 (0.0...22.0)
0...99
Description
Freely selectable user code. Once this code has been entered, configuration can only be enabled again by reentering this code.
This is indicated on the display with the "key" figure once the code has been saved.
Displays the name of the device software currently installed in the display unit.
Version of the software currently installed in the device.
Setting for controlling pump rotation in alternating pump control.
• Time = switching time of the relay
• Count = switching frequency of the relay
Locking time of the relay, 0...99.9 s
Failsafe mode of the relays.
• OFF = relays de-energise in the event of an error or device malfunction
• ON = relays energise in the event of an error or device malfunction
Time setting for gradient evaluation, 1...100 s
Sensor evaluation to NAMUR (e.g. cable open circuit).
Only for 4...20 mA current signal.
Error limits for the input signal.
In the "NAMUR=Yes" operating mode, ranges 1...4 are assigned the limits specified by Namur NE 43 and cannot be changed.
In the "NAMUR=No" operating mode, the error limits can be freely selected.
Here, please note that the following applies: Range 1 < Range 2 < Range 3 <
Range 4.
Violation of these limits can be evaluated with a relay for example ("Alarm" operating mode).
Setting for the display contrast.
• 0 = low contrast
• 99 = high contrast
Endress+Hauser 77
Maintenance RIA452
7 Maintenance
No special maintenance work is required on the device.
8 Accessories
Name Order No.
ReadWin ® 2000 PC configuration software and serial cable with jack connector 3.5 mm for RS232 port.
ReadWin ® 2000 PC configuration software and serial cable for USB port with
TDL connecter.
RIA452A-VK
TXU10A-xx
IP65 Field housing.
51009957
9 Trouble-shooting
The following section provides you with an overview of possible causes of errors to provide you with an initial trouble-shooting aid.
9.1
Trouble-shooting instructions
#
Warning!
In the case of Ex devices, fault diagnosis cannot be carried out on the open device as this annuls the explosion protection.
Display
No measured value display
Cause
No power supply connected
Remedy
Check the power supply of the device.
Power supply applied, device defective The device must be replaced.
The red marking for overrange/underrange is flashing on the bargraph.
Analog output is > 10% above or below the scaled range.
Check the scaling of the analog output
(Out 100% or Out 0%).
!
Note!
Errors for which an error code is shown on the display are described in Section 9.2.
Further information on the display is also provided in Section 5.2.1.
78 Endress+Hauser
RIA452 Trouble-shooting
9.2
Process error messages
!
Note!
Faults have the highest priority. The associated error code is displayed. A fault is present if the memory module for writing and reading data is defective or if data could not be read correctly.
9.2.1
Device malfunction
Error code Cause
E 101 Bus error reading the config/ calibration data after power-up
E 102
E 103
Implausible operating data
(checksum)
Implausible calibration data
Effect
Faulty device functioning
Configuration lost
Faulty device functioning
E 104
E 105
E 106
E 210
E 221
E 222
E 290
Remedy
Instrument error, notify Service
Perform preset
Instrument error, notify Service
Reset min/max values Bus error reading the min/max data after power-up
Incorrect min/max values
Bus error reading the relay data after power-up
Incorrect relay data
Universal card bus error
Pulse output, pulse buffer overflow
Faulty universal input functioning
A maximum of 10 pulses are buffered
Reset relay data
Replace universal card, notify
Service
Set the parameters of the pulse output in such a way that the maximum frequency is not exceeded
Pump error, digital input 1
Pump error, digital input 2
Pump error, digital input 3
Relay goes to failsafe mode
Acknowledge error via operation or switching power on/off
Pump error, digital input 4
Number overshoot due to decimal point shift
Decimal point position cannot be altered
Check decimal point position and number range
9.2.2
Incorrect entries
Error code
E 290
Description Reaction at device
The number of digits after the decimal point cannot be increased due to number overflow of the dependent parameters.
Error code is shown on the display until a key is pressed.
Endress+Hauser 79
Trouble-shooting
9.3
Spare parts
RIA452
80
Fig. 21: RIA452 spare parts
8
9
10
11
12
13
14
15
No Item
No.
4
5
6
2
3
Item No.
Name
1 Housing front
Housing seal
Ex-cover (rear panel)
Rotary button with seal
Relay board
Mainboard 90...250 V, 50/60 Hz
Mainboard 20...36 V DC; 20...28 V AC, 50/60 Hz
7 Standard input card
Standard input card ATEX, FM, CSA approval
Multi-function input card
Complete display board
LC display (glass with background illumination)
Terminal (mains) 3-pin
Terminal (relay 1-8) 6-pin
Terminal (analog input) 4-pin
Terminal (analog output, Open Collector, transmitter power supply) 6-pin
Terminal (digital inputs) 5-pin
Jumper operating lock
Casing fixing clip RIA452 (1 piece)
51008588
51008587
50033350
50084623
Order No.
RIA452X-HA
50070730
51008272
RIA452X-HB
RIA452X-RA
RIA452X-MA
RIA452X-MB
RIA452X-IA
RIA452X-IB
RIA452X-IC
RIA452X-DA
RIA452X-DB
50078843
51005104
51009302
Endress+Hauser
RIA452 Trouble-shooting
9.4
Return
To reuse later or in case of repair, the device must be sent in protective packaging, preferably the original packaging. Repairs must only be carried out by your supplier's service organisation or specially trained personnel. Enclose a note describing the fault when sending the unit in for repair.
9.5
Disposal
The device contains electronic components and must, therefore, be disposed of as electronic waste in the event of disposal. Please observe in particular the local waste disposal regulations of your country.
Endress+Hauser 81
Technical data
Measured variable
Measuring ranges
Galvanic isolation
Output signal
Signal on alarm
Current/voltage output
RIA452
10 Technical data
10.0.1
Input
Current (standard)
Digital inputs (standard)
Current/voltage, resistance, resistance thermometer, thermocouples (universal input option)
Current input:
• 0/4...20 mA +10% overrange, 0...5 mA
• Short-circuit current: max. 150 mA
• Input impedance: d 5 :
• Reaction time: d 100 ms
Universal input:
Current:
• 0/4...20 mA +10% overrange, 0...5 mA
• Short-circuit current: max. 100 mA
• Input impedance: d 50 :
Voltage:
• ±150 mV, ±1 V, ±10 V, ±30 V, 0...100 mV, 0...200 mV, 0...1 V, 0...10 V
• Input impedance: t 100 k:
Resistance:
• 30...3,000 : in 3-wire/4-wire technology
Resistance thermometer:
• Pt100/Pt100/500/1000, Cu50/100, Pt50 in 3-wire/4-wire technology
• Measuring current for Pt100/500/1000 = 250 PA
Thermocouple types:
• J, K, T, N, B, S, R as per IEC584
• D, C as per ASTME998
• U, L as per DIN43710/GOST
• Reaction time: d 100 ms
Digital input:
• Voltage level -3...5 V low, 12...30 V high (as per DIN19240)
• Input voltage max. 34.5 V
• Input current typ. 3 mA with overload and reverse polarity protection
• Sampling frequency max. 10 Hz
Towards all other circuits
10.0.2
Output
Relay, transmitter power supply (standard)
Current, voltage, pulse, intrinsically safe transmitter power supply (option)
No measured value visible on the LC display, no background illumination, no sensor power supply, no output signals, relays behave in fail safe manner.
Span:
• 0/4...20 mA (active), 0...10 V (active)
Load:
• d 600 : (current output)
• Max. loop current 22 mA (voltage output)
82 Endress+Hauser
RIA452 Technical data
Pulse output
Signal characterisation:
• Signal freely scalable
Galvanic isolation towards all other circuits
• Frequency range up to 12.5 kHz
• I max
= 200 mA
• U max
= 28 V
• U low/max
= 2 V at 200 mA
• Pulse width = 0.04 up to 2000 ms
• Load min. 1 k :
Relay Signal characterisation:
• Binary, switches when the limit value is reached
Switch function: limit relay switches for the operating modes:
• Minimum/maximum safety
• Alternating pump control function
• Batch function
• Time control
• Window function
• Gradient
• Device malfunction
• Sensor malfunction
Switching threshold:
• Freely programmable
Hysteresis:
• 0 to 99%
Signal source:
• Analog input signal
• Integrated value
• Digital input
Number:
• 4 in basic unit (can be extended to 8 relays, option)
Electrical specifications:
• Relay type: changeover
• Relay switching capacity: 250 V AC / 30 V DC, 3 A
• Switch cycles: typically 10 5
• Switching frequency: max. 5 Hz
!
Galvanic isolation towards all other circuits
Note! Assignment
Mixed assignment of low and extra-low voltage circuits is not permitted for neighbouring relays.
Transmitter power supply Transmitter power supply 1, terminal 81/82 (optionally intrinsically safe):
Electrical specifications:
• Output voltage: 24 V ± 15%
• Output current: max. 22 mA (at U out
• Impedance: d 345 : t 16 V, sustained short-circuit proof)
Approvals:
• ATEX
• FM
• CSA
Transmitter power supply 2, terminal 91/92:
Electrical specifications:
• Output voltage: 24 V ± 15%
• Output current: max. 250 mA (sustained short-circuit proof)
Endress+Hauser 83
Technical data
Electrical connection
RIA452
Transmitter power supply 1 and 2
Galvanic isolation:
• Towards all other circuits
HART ® :
• No HART ® signal influence
10.0.3
Power supply
Current input
81
82
11
12
20..36V DC
20...28V AC
50/60Hz
90...250V AC
50/60Hz
Relay 8
Relay 7
Relay 6
Relay 5
151
152
153
141
142
143
154
155
156
144
145
146
Relay output nc
41
42
43
51
52
53
54
55
56
44
45
46
J1
J2
Relay 4
Relay 3
Relay 2
Relay 1
Relay 1-8
250V AC /30V DC
3 A
Analog output
0..20mA, 0..10V DC
Transmitter power supply unit
24V, <= 250mA
Internal circuits represented by dashed lines.
RS232
1
2
3
4
Digital inputs acc. to DIN 19240
Voltage level: -3...5 V low,
12...30 V high
Input current typ. 3 mA
(with overload and reverse polarity protection)
Input voltage max. 34.5 V
Sampling frequency max. 10 Hz
Digital output, passive open collector max. 24V, 200mA
Fig. 22: Terminal assignment of process display unit
Universal input option
The device can be optionally equipped with a universal input instead of a current input.
84 Endress+Hauser
RIA452 Technical data
Fig. 23: Universal input terminal assignment (option)
Supply voltage
Power consumption
Connection data interface
Power supply 90...250 V AC 50/60 Hz
Low voltage power supply 20...36 V DC, 20...28 V AC 50/60 Hz max. 24 VA
RS232
• Connection: jack socket 3.5 mm, rear of device
• Transmission protocol: ReadWin ® 2000
• Transmission rate: 38,400 Baud
Reference operating conditions
Maximum measured error
10.0.4
Performance characteristics
Power supply: 230 V AC ±10%, 50 Hz ±0.5 Hz
Warm-up period: 90 min
Ambient temperature range: 25 °C (77 °F)
Current input:
Accuracy
Resolution
Temperature drift
0.1% of full scale
13 bit d 0.4%/10K (d 0.22%/10 °F)
Universal input:
Accuracy
Input: Range:
Current 0...20 mA, 0...5 mA, 4...20 mA
Overrange: up to 22 mA
Maximum measured error of measuring range
(oMR):
± 0.10%
Endress+Hauser 85
Technical data
86
RIA452
Voltage > 1 V 0...10 V, ± 10 V, ± 30 V
Voltage d 1 V
Resistance thermometer
± 1 V, 0...1 V, 0...200 mV, 0...100 mV, ± 150 mV
Pt100, -200...600 °C (-328 °F...1112 °F)
(IEC751, JIS1604, GOST)
Pt500, -200...600 °C (-328 °F...1112 °F)
(IEC751, JIS1604)
Pt1000, -200...600 °C (-328 °F...1112 °F)
(IEC751, JIS1604)
Cu100, -200...200 °C (-328...392 °F) (GOST)
Cu50, -200...200 °C (-328...392 °F) (GOST)
Pt50, -200...600 °C (-328...1112 °F) (GOST)
30...3000
: Resistance measurement
Thermocouples Type J (Fe-CuNi), -210...999.9 °C (-346...1831 °F)
(IEC584)
Type K (NiCr-Ni), -200...1372 °C (-328...2501 °F)
(IEC584)
Type T (Cu-CuNi), -270...400 °C (-454...752 °F)
(IEC584)
Type N (NiCrSi-NiSi), -270...1300 °C (-
454...2372 °F)
(IEC584)
Type B (Pt30Rh-Pt6Rh), 0...1820 °C (32...3308 °F)
(IEC584)
Type D (W3Re/W25Re), 0...2315 °C (32...4199 °F)
(ASTME998)
Type C (W5Re/W26Re), 0...2315 °C (32...4199 °F)
(ASTME998)
Type L (Fe-CuNi), -200...900 °C (-328...1652 °F)
(DIN43710, GOST)
Type U (Cu-CuNi), -200...600 °C (-328...1112 °F)
(DIN43710)
Type S (Pt10Rh-Pt), 0...1768 °C (32...3214.4 °F)
(IEC584)
Type R (Pt13Rh-Pt), -50...1768 °C (-58...3214.4 °F)
(IEC584)
± 0.10%
± 0.10%
4-wire: ± (0.10% oMR + 0.3K (0.54 °F))
3-wire: ± (0.15% oMR + 0.8K (1.44 °F))
4-wire: ± (0.20% oMR + 0.3K (0.54 °F))
3-wire: ± (0.20% oMR + 0.8K (1.44 °F))
4-wire: ± (0.20% oMR + 0.3K (0.54 °F))
3-wire: ± (0.20% oMR + 0.8K (1.44 °F))
± (0.15% oMR +0.5K) from -100 °C
(± (0.15% oMR +0.9 °F) from -148 °F)
± (0.15% oMR +0.5K) from -130 °C
(± (0.15% oMR +0.9 °F) from -202 °F)
± (0.15% oMR +0.5K) from -200 °C
(± (0.15% oMR +0.9 °F) from -328 °F)
± (0.15% oMR +0.5K) from -100 °C
(± (0.15% oMR +0.9 °F) from -148 °F)
± (0.15% oMR +1.5K) from 600 °C
(± (0.15% oMR +2.7 °F) from 1112 °F)
± (0.15% oMR +1.5K) from 500 °C
(± (0.15% oMR +2.7 °F) from 932 °F)
± (0.15% oMR +1.5K) from 500 °C
(± (0.15% oMR +2.7 °F) from 932 °F)
± (0.15% oMR +0.5K) from -100 °C
(± (0.15% oMR +0.9 °F) from -148 °F)
± (0.15% oMR +0.5K) from -100 °C
(± (0.15% oMR +0.9 °F) from -148 °F)
± (0.15% oMR +3.5K) for 0...100 °C
(± (0.15% oMR +6.3 °F) for 32...212 °F)
± (0.15% oMR +1.5K) for 100...1768 °C
(± (0.15% oMR +2.7 °F) for 212...3214.4 °F)
± (0.15% oMR +3.5K) for 0...100 °C
(± (0.15% oMR +6.3 °F) for 32...212 °F)
± (0.15% oMR +1.5K) for 100...1768 °C
(± (0.15% oMR +2.7 °F) for 212...3214.4 °F)
Resolution 16 bit
Temperature drift
Temperature drift: d 0.1%/10K (0.056%/10 °F)
Current output:
Linearity
Resolution
Temperature drift
Output ripple
0.1% of full scale
13 bit d 0.1%/10K (0.056%/10 °F)
10 mV to 500 : for d 50 kHz
Voltage output
Linearity 0.1% of full scale
Endress+Hauser
RIA452
Installation instructions
Environment
Resolution
Temperature drift
13 bit d 0.1%/10K (0.056%/10 °F)
10.0.5
Installation
Mounting location
Panel, cutout 92x92 mm (3.62x3.62") (see 'Mechanical construction').
Orientation
Horizontal +/- 45 in every direction
Ambient temperature range
-20 to +60 °C (-4 to 140 °F)
Storage temperature
-30 to +70 °C (-22 to 158 °F)
Operating height
< 3000 m (9842 ft) above MSL
Climate class
As per IEC 60654-1, Class B2
Condensation
Front: permitted
Casing: not permitted
Degree of protection
Front IP 65 / NEMA 4
Casing IP 20
Shock and vibration resistance
2(+3/-0) Hz - 13.2 Hz: ±1.0 mm
13.2 Hz - 100 Hz: 0.7 g
Electromagnetic compatibility (EMC)
• Interference immunity:
To IEC 61326 industrial environments / NAMUR NE 21
• Interference emissions:
To IEC 61326 Class A
Technical data
Endress+Hauser 87
Technical data
Design, dimensions
10.0.6
Mechanical construction
Fig. 24: Data in mm (data in inches in brackets)
RIA452
Weight
Material
Terminals
Fig. 25: Panel cutout (data in mm, data in inches in brackets) approx. 500 g (1.1 lb)
• Housing front: ABS plastic, galvanised
• Housing casing: plastic PC10GF
Pluggable screw terminals, range 1.5 mm 2 ( i 14 AWG) solid, 1.0 mm 2 ( i 18 AWG) stranded with ferrule
88 Endress+Hauser
RIA452
Display elements
10.0.7
Human interface
Operating elements
Remote operation
Fig. 26: LC display of process display unit
Pos 1: Device status LEDs: green - device ready for operation; red - device or sensor malfunction
Pos. 2: Bargraph with overreach and underreach
Pos. 3: 7-digit 14-segment display
Pos. 4: Unit and text field 9x77 dot matrix
Pos. 5: Limit value flags 1...8
Pos. 6: Status display, digital inputs
Pos. 7: Symbol for 'device operation blocked'
• Display range
-99999 to +99999
• Signalling
– Relay activation
– Measuring range overrange/underrange
Jog/shuttle dial
Configuration
The device can be configured with the PC software ReadWin ® 2000.
Interface
TDL interface at device; connection to PC via USB box (see 'Accessories')
RS232 interface at device; connection with serial interface cable (see 'Accessories')
Technical data
Endress+Hauser 89
Technical data RIA452
CE mark
Ex approval
Other standards and guidelines
10.0.8
Certificates and approvals
The device meets the legal requirements of the EU directives. Endress+Hauser confirms that the device has been tested successfully by affixing the CE mark.
Information about currently available Ex versions (ATEX, FM, CSA, etc.) can be supplied by your
E+H Sales Centre on request. All explosion protection data are given in a separate documentation which is available upon request.
• IEC 60529:
Degrees of protection by housing (IP code)
• IEC 61010-1:
Protection measures for electrical equipment for measurement, control, regulation and laboratory procedures
• CSA 1010.1
Safety requirements for electrical equipment for measurement, control, and laboratory use -
General requirements
• FM 3610
Intrinsically safe apparatus and associated apparatus for use in class 1, 2 and 3, division 1 hazardous (classified) locations
• CSA C22.2.157
Intrinsically safe & non-incendive equipment for use in hazardous locations
• CSA E79-11
Electrical apparatus for explosive gas atmospheres - intrinsic safety "i"
• EN 50020
Electrical apparatus for hazardous areas - intrinsic safety "I"
10.0.9
Documentation
System components - display unit, top-hat rail devices, overvoltage protection and energy computer (FA016K/09/en)
Supplementary Ex documentation:
ATEX II(1)GD: XA 053R/09/a3
90 Endress+Hauser
RIA452 Index
Index
Numerics
0% value (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
100% value (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
24h (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
A
Adjusting the analog input . . . . . . . . . . . . . . . . . . . . . . . . . 66
Alternate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Alternate (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Alternating pump control. . . . . . . . . . . . . . . . . . . . . . . . . . 73
Analog input
Adjusting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Analog output
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
B
Bar 0% (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Bar 100% (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Bar rise (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
C
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . . . . . 90
Code
User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Comp. Temp (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Configuration
Operating parameter . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Connecting external sensors . . . . . . . . . . . . . . . . . . . . . . . 59
Current input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Universal input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Connecting the power supply . . . . . . . . . . . . . . . . . . . . . . 59
Connection (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Const. temp (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Contrast (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Count (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Counts (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Current input
Connecting external sensors. . . . . . . . . . . . . . . . . . . . . 60
Curve (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
D
Damp (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Dec. factor (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Dec. point (function) . . . . . . . . . . . . . . . . . . . . 66–67, 70, 75
Dec. total (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Dec. value (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Dec. Y value (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Del. points (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Delay (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Device malfunction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Digital input
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Dimension (function) . . . . . . . . . . . . . . . . . . . . . . 66, 74, 76
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Disable
Endress+Hauser
Programming mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Disabling the programming mode. . . . . . . . . . . . . . . . . . . . 64
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
E
Electrical connection
Post-connection check (checklist) . . . . . . . . . . . . . . . . . 60
Entering text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
F
Factor (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Fail mode (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Fail value (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Func. alt. (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68, 70
G
Grad. Time (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
H
Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Hysteresis (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
I
Incorrect entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Integr. base (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Integration
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Integration (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Integration function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
L
Level (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Limit values
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Linearisation table
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Lock time (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
M
Max. value (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Menu
Analog Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Digital Inp.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
LIN. Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
LINPOINTS 1..X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
MIN MAX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
91
RIA452 Index
Pulse out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Min. value (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Min/max memory
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Mounting location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
N
Nameplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Namur (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
O
Offset (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66–67
Open circ. (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Operating matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Operating mode
Grad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Max. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Min . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Operating parameter
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Out 0% (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Out 100% (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Out damp (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Output range (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
P
Panel cutout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Parameter
Analog input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Analog output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Digital input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Integration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Limit values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Linearisation table . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Min/max memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Pulse output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Support points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Performance characteristics . . . . . . . . . . . . . . . . . . . . . . . . 85
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59, 84
Progname (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Pulse output
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Pulse width (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Pump monitoring function. . . . . . . . . . . . . . . . . . . . . . . . . 69
R
Range 1 (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Range 2 (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Range 3 (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Range 4 (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Ref. bargraf (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Ref. integr. (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Ref. Min/Max (function) . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Ref. num. (function) . . . . . . . . . . . . . . . . . . . . . . . . . . 67, 70
Rel. Mode (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52, 81
Reset (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
92
Reset max (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Reset min (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Runtime (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
S
Sampl. time (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Scaling the analog input . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Sensors
Connecting external - . . . . . . . . . . . . . . . . . . . . . . . . . 59
Setpoint A (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Setpoint B (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Show points (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Signal type (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Sim pulseout (function). . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Simu mA (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Simu relay (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Simu V (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Support points
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
T
Technical data
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . . 90
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . . 88
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Performance characteristics . . . . . . . . . . . . . . . . . . . . . 85
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Terminal assignment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Universal input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Text entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Totalizer (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
U
Unit value (function). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Universal input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Connecting external sensors . . . . . . . . . . . . . . . . . . . . 60
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . 59
User code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
User code (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
V
Version (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
X
X value (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Y
Y value (function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Endress+Hauser
50
RIA452
Brief overview
For rapid and easy commissioning:
Safety instructions
Æ
Installation
Æ
Wiring
Æ
Display and operating elements
Æ
Commissioning
Device configuration - explanation and use of all the configurable device functions with the associated value ranges and settings.
Block diagram
Analog input:
1 x current (0/4...20 mA) or 1 x universal (I, U, R, TC, RTD) or 1 x intrinsically safe current input
Digital input:
4 x digital status input
Power supply:
90...250 V AC or 20...36 V DC /
20...28 V AC
Interfaces:
1 x RS 232
1 x CDI
Fig. 1: Block diagram RIA452 optional
Page 52
Page 55
Page 56
Page 62
Page 65
Relays:
4 x change-over contact
8 x change-over contact
Output:
Analog (I, U)
Pulse (with integration)
Transmitter power supply:
1 x 250 mA, 24 V DC
1 x 22 mA, 24 V DC, intrinsically safe
Endress+Hauser
BA 158F/00/en/06.03
016705-1000
multicap T
DC 12 TE
DC 11/16/21/26 TEN
DC 11/16/21/26 TES
Level Probes
Operating Instructions
Endress
+
Hauser
The Power of Know How
Measuring System
Left:
Limit detection with separate Nivotester switching unit
Right:
Level measurement with separate Silometer transmitter
Left:
Compact level switch with relay or transistor output
Right:
Compact loop-powered level measurement system with standard 4…20 mA current output.
The FEC 12 is a smart electronic insert which allows remote calibration over the
4…20 mA output
(HART protocol)
Probe Selection
Cover aluminium/plastic for
FEC 12
FEC 22 for
EC .. Z
Type: F6 aluminium
Type: F10 plastic
(formerly F7)
Cover aluminium for
FEC 12
FEC 22
Connection module:
- with RFI-filter for EC .. Z or FEC 12 (IS) (2-pole)
- for FEC 12 (XP) (2-pole)
- for FEC 22 (AC: 8-pole)
DC: 3-pole) for
EC .. Z
Type: T3 aluminium housing with separate connection compartment to
XP, IS version
Cover stainless steel
Type: F8 stainless steel housing
Electronic insert
EC 11 Z
EC 17 Z
EC 37 Z
EC 47 Z
EC 61 Z
EC 72 Z
Electronic insert FEC 12
4…20 mA
Smart
Electronic insert FEC 22
Compact limit switch
1)
2)
3)
4)
5)
6)
7) 8)
9)
1) DC 12 TE with reinforced rod, fully insulated
2) DC 12 TE with reinforced rod, partially insulated
3) DC 11 TEN with fully insulated rod
4) DC 16 TEN with partially insulated rod
5) DC 21 TEN with fully insulated rope
6) DC 26 TEN with partially insulated rope
7) DC 11, 16, 21, 26 TES with screening against condensation and material build-up at the process connection
8) DC 11, 16, 21, 26 TES with active compensation of conductive material build-up at the probe
9) DC 11, 16, 21, 26 TES with screening and active build-up compensation
Not shown: rod probes DC 11, 16 TEN and TES with ground tube; not for probes with active build-up compensation
2
Notes on Installation Approved Usage
Multicap T capacitance probes are designed for level measurement or limit detection in tanks containing liquids or small silos containing light bulk solids.
They have been designed to operate safely in accordance with current technical and safety standards, and must be installed by qualified personnel in accordance with the instructions which follow.
The manufacturer accepts no responsibility for any damage arising from incorrect use, installation or operation of the equipment. Changes or modifications not expressly approved in the following instructions or by the bodies responsible for compliance may make the user’s authority to operate the equipment null and void.
Personnel
The equipment may be installed, commissioned and maintained by authorised personnel only.
The instructions which follow must have been read and understood before the equipment is installed.
Explosion Hazardous Areas
When installing equipment in explosion hazardous areas the instructions included in the accompanying certification as well as any local standards must be observed.
Please note that where the quoted technical data differs from that in the certificate, the certificate applies.
Operating Conditions
Before installing the probe, check that it is suitable for the operating conditions to be encountered, in particular:
- the chemical resistance of all probe materials
- the permitted operating temperature and pressure
- the approvals for use in explosion hazardous areas.
Unpacking
To avoid damage to the probe, remove the packaging on-site just before mounting.
Compare the code on the nameplate of the probe with the product designation on Page 14...18 to ensure that the correct probe is mounted.
Check the probe length (for shortening see page 5).
Preparations for
Installation
When installing in explosion hazardous areas observe all national and local regulations as well as the specifications in the certificate.
When the electronic insert is not installed, connect the probe terminal in the housing to the ground terminal.
Possibilities for connection:
Insert plug or wire jumper in both sockets - to be found adjacent to the central thread.
Before the electronic insert is installed, remove the plug or jumper.
1
2
Grounding the probe rod or rope in the housing:
1) type F6 / F8 / F10
2) type T3
A Jumper, e.g. made from bare wire,
1.5 mm
2
B Plug: supplied with probes without electronic insert
B
919247-1000 or
A
15 max.
1.4
min.
1.1
e.g. 1.5 mm² or
AWG 16 / SWG 18
3
Mounting
Probe with parallel thread G ¾ A and with sealing ring:
Tighten at the hexagonal nut to max. 100 Nm
(G 1 A to max. 180 Nm)
Do not tighten by rotating the housing!
Mounting the probe
Protect the insulation
Ensure that the insulation of the probe is not damaged when inserting the probe through the process connection of the vessel.
41
Probe with Triclamp, sanitary thread or flange:
Use a sealing material suitable for the application.
If the flange is PTFE-cladded, then this is generally a suitable seal up to the permitted operating pressure.
Probe with thread
- G ¾ A or G 1 A (parallel):
Use the elastomer/fibre seal provided or any other chemically resistant seal which can withstand temperatures up to 300 °C.
- ¾ - 14 NPT or 1 - 11½ NPT (tapered):
Wrap suitable sealing material around the thread.
- When tightening, rotate the probe at the hexagonal nut only, not at the housing!
- For probes with a G ¾ A parallel thread and seal: a torque of 30 Nm is sufficient for a tight seal against pressures in the vessel up to 25 bar.
(G 1 A: sufficient torque = 50 Nm).
1.
Rotating the small housing
(type F6, F8, F10)
1. - 2. - 3.
Below right:
Protective cover for the small housing
(type F6, F10).
Always to be used when the probe is mounted outdoors
2.
1.
3...4 x
... 280°
2.
3.
3.
Rotating the Housing
The housing can be rotated to reposition the cable entry.
In order to provide optimal protection from the entry of moisture, particular when the probe is mounted outdoors, we strongly recommend:
- A probe mounted laterally in the tank with one cable entry, should have the cable entry pointing downwards
- A probe mounted laterally in the tank with two cable entries, should have both cable entries positioned horizontally
- When mounted with protective cover the cable entries should always be positioned horizontally
Small housing (type F6, F8, F10)
- Unscrew cover
- Loosen the Phillips screw in the base of the housing by 3 or 4 turns
- The housing can now be rotated through 280° from one stop to the other
- Retighten the Phillips screw in the base of the housing.
Large housing (type T3)
- Loosen the Phillips screw on the housing collar
- The housing can now be rotated through 280° from one stop to the other
- Retighten the Phillips screw at the housing collar.
Rotating the large housing (type T3)
1. - 2. - 3.
4
Sealing the Probe Housing
It is important that no moisture enters the probe housing when mounting the probe, connecting the electronic insert or when operating the probe.
The housing cover and the cable entries must, therefore, always be screwed tight.
The O-ring seal at the housing cover and the thread of the aluminium cover are both smeared with a lubricant when delivered.
If the lubricant has been removed, it must be replaced e.g. with silicone or graphite, so that the cover is an air-tight seal and the aluminium thread does not seize when screwed down.
Under no circumstances should an oil-based lubricant be used as this would destroy the O-ring.
Altering the Probe
Length
A fully insulated rod probe cannot be shortened or lengthened.
Shortening a rope probe
See instructions supplied with the rope shortening kit.
Shortening a partly insulated rod probe
• Clamp the probe by the bare rod, not by the insulation and not by the process connection so that the rod connection is not under strain and cannot be damaged.
Saw off the rod and deburr.
If the uninsulated rod is less than
100 mm, shorten the insulation accordingly.
• Change the length specification stated on the nameplate.
Lengthening a partially insulated rod probe
• Remove the electronic insert from the probe housing
• Weld on a section of rod or tube
(use 1.4435 stainless steel)
Note:
- Do not damage or overheat the insulation
- The weld must be as rugged and corrosion-resistant as the probe rod itself
- A longer or thicker probe rod is subjected to higher loads by the movement of material, the maximum lateral load will be reduced.
- Do not exceed the permitted probe length. See appropriate certificate
• Change the length specification stated on the nameplate
• Replace the electronic insert.
Connection
Refer to the appropriate Technical
Information for connecting the electronic insert EC or FEC in the probe housing.
For T3 housing, the connection designations in the separate connection compartment are the same as those on the built-in electronic insert.
Insulated mounting of the probe in a metal container: Connect the ground terminal of the probe to the container with the aid of a short cable.
Mounting in a plastic container: Connect the ground terminal of the probe to the counterelectrode with the aid of a short cable.
Ensure that the probe housing is tightly sealed.
Calibration
Refer to the operating manual for the transmitter connected or the electronic insert FEC 12 or FEC 22 which is installed.
Replacing components
Mounting without electronic insert
Exchange of electronic inserts
• After the defective electronic insert has been removed and the replacement properly installed, the instrument must be recalibrated and checked for correct function.
• If fully insulated multicap probes are mounted in explosion hazardous areas without the electronic insert, and there is a risk of dangerous electronic discharges, then the probe terminal in the housing must be short-circuited with the ground terminal.
5
Maintenance
Return of Goods
Disposal
Accessories
Supplementary
Documentation
Cleaning and inspecting the vessel:
- Check the probe insulation for damage
- Remove material build-up especially at the process connection
- Check the housing cover and the cable entry for tightness.
Caution!
The probe can be damaged if used as a grip or support when inspecting the container.
PLATZHALTER
If a probe is to be returned to
Endress+Hauser for repair or disposal, then all residue must be removed from it.
This is especially important if the product measured can impair health.
Please do not return goods if the last traces of dangerous products cannot be removed, e.g. product has penetrated into fissures or diffused into plastic parts.
Packaging
All sales and transportation packaging from Endress+Hauser is produced in conformance to the regulations governing packaging for reuse and recycling.
Instruments
For a small charge, Endress+Hauser will accept and recycle any instruments manufactured in its own E+H production program. These will then be disposed of according to the German regulations covering the disposal of electronics.
Delivery to Endress+Hauser,
Hauptstraße 1, 79689 Maulburg,
Germany.
q Protective cover for the small probe housing (type F6, F10) see Technical Information
“Probe accessories”
The protective cover shields the probe from excessive heat and prevents condensation from forming in the housing when temperatures vary over a wide range.
q Slip-on plate for partially insulated probe DC 12 TE for increasing the switching safety for limit detection q Rope shortening kit for fully insulated probes q Rope shortening kit for partially insulated probes
Technical Information q Probe accessories
Technical Information TI 229F/00/en q Electronic insert FEC 12
Technical Information TI 250F/00/en q Electronic insert FEC 22
Technical Information TI 251F/00/en q Electronic insert EC 17 Z
Technical Information TI 268F/00/en q Electronic insert EC 61
Technical Information TI 267F/00/en q Electronic insert EC 37 Z, EC 47 Z
Technical Information TI 271F/00/en q Electronic insert EC 11, EC 72
Technical Information TI 270F/00/en q Transmitters for limit detection and continuous level measurement on request
Certificates
See product structure on page 14/16.
6
Dimensions
(Dimensions in mm)
DC 12 TE
L1 = Length of active probe rod
L2 = Length of partial insulation minimum: 75 mm maximum: length L1 minus 50 mm
Thread options: G ¾ A, G 1 A
¾ - 14 NPT, 1 - 11½ NPT
NPT G
41 AF
NPT G
41 AF
DC 12 TE
Rod probe with reinforced rod for high lateral load
Left: fully insulated
Right: partially insulated
Dimensions
(Dimensions in mm)
DC 11/16/21/26 TEN
L1 = Length of active probe rod or probe rope
L2 = Length of partial insulation minimum: 75 mm maximum: length L1 minus 50 mm
Thread options: G ¾ A, G 1 A
¾ - 14 NPT, 1 -11½ NPT
Left:
DC 11 TEN
Fully insulated rod probe
Centre:
DC 16 TEN
Partially insulated rod probe
Right:
DC 11, 16 TEN with ground tube
(fully or partially insulated probe rod)
ø16 ø12
NPT G
41 AF
NPT G
41 AF
NPT
G
41 AF
ø10 ø8 ø21.3
41 AF
NPT G
41 AF
NPT G
ø2.5
ø4
Left:
DC 21 TEN
Fully insulated rope probe
Right:
DC 26 TEN
Partially insulated rope probe
Tensioning weight with anchor hole
ø22 ø18
7
Dimensions
(Dimensions in mm)
DC 11/16/21/26 TES
All probes on this page are shown with partial insulation. All versions are available with full insulation
L1 = Length of active probe rod or probe rope
L2 = Length of partial insulation see page 7
Thread options: G ¾ A, G 1 A
¾ - 14 NPT, 1 - 11½ NPT
Probes with screening
L3 against condensation and material build-up on the process connection
Left:
Rod probe DC 11 TES or DC 16 TES
Centre:
Rod probe DC 11 TES or DC 16 TES with ground tube
Right:
Rope probe DC 21 TES or DC 26 TES
NPT G
ø21.3
41 AF
NPT G
41 AF
ø21.3
NPT G
41 AF
ø21.3
NPT G
ø19.2
41 AF
NPT G
41 AF
ø19.2
Probes with active build-up compensation
(always 100 mm)
Left:
Rod probe DC 11 TES or DC 16 TES
Right:
Rope probe DC 21 TES or DC 26 TES
NPT G
ø21.3
41 AF
NPT G
41 AF
ø21.3
Probes with screening
L3 and with active build-up compensation
Left:
Rod probe DC 11 TES or DC 16 TES
Right:
Rope probe DC 21 TES or DC 26 TES
L3
The screening is available in three standard lengths:
L3 = 150 mm,
L3 = 250 mm,
L3 = 500 mm
Special lengths on demand
L3 min. 100 mm
L3 max. 1500 mm
8
Dimensions Continued /
Additional
Process Connections
Tapered threads
3 /
4
- 14 NPT and 1 - 11 1 /
2
NPT
Parallel threads
G
3
/
4
A and G 1 A
All probes shown with type F6/F10 housing
Dimensions for type T3 housing are also shown
Dimensions of temperature spacer
NPT G
Flange Triclamp Coupling 2"
Triclamp Coupling 1
1
/
2
“
Triclamp Coupling 1"
Sanitary thread DN 50 Options:
•
Corrosion-resistant steel tag
•
Temperature spacer
60
20
9
Housing Dimensions
Top row:
Housings in aluminium
(type F6) or plastic
(type F10, formerly F7)
Bottom row:
Housings in aluminium
(type T3) with separate connection compartment;
- with RFI filter for small electronic inserts
EC 17 Z, EC 61 Z
EC 37 Z, EC 47 Z,
EC 11 Z, EC 72 Z
- with RFI filter and terminal connection module for
FEC 12 (EEx ia)
- with RFI filter and safety barriers for
FEC 12 (EEx d)
- terminal connection module for FEC 22
Both housings:
- with low cover for small electronic inserts EC .. Z,
- with raised cover for electronic inserts
FEC 12, FEC 22; with two cable entries, one sealed with a blind plug
91
98
~66
Stainless steel housing (type F8) for electronic inserts
EC .. Z/FEC .. , with two cable entries, one sealed with a blind plug.
ø86 ~32 max. 81.5
ø104
ø 86
10
Technical Data
General Information
Operating data
Permitted operating pressures p e and operating temperatures T
B
Manufacturer
Instrument family
Instrument types
Function
Endress+Hauser GmbH+Co. D-79689 Maulburg, Germany
Multicap T
DC 12 TE, DC 11, 16, 21, 26 TEN / TES
Probes for capacitive level measurement and limit detection
Operating pressure
Operating temperature
Lateral load on probe rod
Max. tension on probe rope max. 25 bar depending on material - see below max. 200 °C depending on material - see below
DC 12 TE: 30 Nm at 20 °C, static
DC 11, 16: 15 Nm at 20 °C, static
200 N at 20 °C, static
40
30
20
10 p e bar
0
2 bar
1 bar
50 100 150 200
T
B
° C
80 60 40 20
30
20
10 p e bar
0 20 40
2 bar
1 bar
60
T
B
° C
Insulation PTFE, FEP or PFA
Insulation PE
Mounting of the electronic insert as a function of operating temperature T
B and ambient temperature T
U
:
A Basic probe
B Probe with temperature spacer
C Electronic insert in separate housing
D Probe with temperature spacer and electronic insert in separate housing
The graphs A and B apply to all electronic inserts
The graphs C and D apply to the small electronic inserts
EC 17 Z, EC 61 Z,
EC 37 Z, EC 47 Z
EC 11 Z, EC 72 Z
A T
U
° C
EC
FEC
80
40
0
– 80 – 40
– 40
0 40 80 120 160 200
T
B
° C
C Separate housing
EC
T
U
° C
120
80
40
0
– 80 – 40
– 40
0 40 80 120 160 200
T
B
° C
B
80
40
0
– 80 – 40
– 40
0 40 80 120 160 200
D
T
U
° C
Separate housing
EC
FEC
160
120
T
U
° C
EC
80
40
0
– 80 – 40
– 40
0 40 80 120 160 200
Probe Lengths
Total length of rod probe
Total length of rope probe min. 100 mm, max. 3000 mm, see dimensions min. 350 mm, max. 20000 mm, see dimensions
Capacitance values of the probe
Basic capacitance: approx. 30 pF
Temperature spacer: approx. 5 pF
Active build-up compensation: < 10 pF
T
B
° C
T
B
° C
11
Operating data
(continued)
Additional capacitances
Probe 250 mm from a conductive vessel wall
Probe rod: approx. 1.3 pF/100 mm in air
Probe rope: approx. 1.0 pF/100 mm in air
Insulated probe rod in water: approx. 38 pF/100 mm DC TE approx. 50 pF/100 mm DC 11 TEN/TES
Insulated probe rope in water: approx. 20 pF/100 mm
Rod probe with ground tube insulated probe rod uninsulated probe rod in air approx. 6,4 pF/100 mm in water approx. 50 pF/100 mm in air approx. 5,6 pF/100 mm
Probe Lengths for continuous measurement in conducting liquids
EC with
∆C max
= 2000 pF
(EC 47 Z, EC 72 Z, FEC 12)
Rope probe up to 8000 mm
(up to 20000 mm in non conducting liquids)
Rod probe up to 3000 mm
EC with
∆C max
= 4000 pF
(EC 37 Z, EC 11 Z)
Rope probe up to 20000 mm
Rod probe up to 3000 mm
Accuracy:
Length tolerances up to 1 m: +0 mm, - 5 mm rod probe/ -10 mm rope probe up to 3 m: +0 mm, - 10 mm rod probe/ -20 mm rope probe up to 6 m: +0 mm, - 30 mm up to 20 m: +0 mm, - 40 mm
The following specifications apply to fully insulated probes operating in conducting liquids
Linearity error < 1 % for 1 m **
Temperature dependence of the probe rod
Pressure dependence of the probe rod
< 0,1 % per K DC 12 TE **
< 0,12 % per K DC 11 TE **
0,12…0,34 % per bar **
Temperature dependence of the probe rope
Pressure dependence of the probe rope
< 0,1 % per K **
< 0,1 % per bar **
** Error in non-conducting materials insignificant
Process Connections
Parallel thread G ¾ A or G 1 A DIN ISO 228/I, with sealing ring 27x32 or 33x39 to DIN 7603
Tapered thread ¾ - 14 NPT or
1 - 11 ½ NPT
ANSI B 1.20.1
DIN flanges without raised face
DIN 2527, Form B
DIN flanges with tongue
DIN flanges with groove
ANSI flanges
Sanitary thread
Triclamp coupling
DIN 2512, Form F
DIN 2512, Form N
ANSI B 16.5
DIN 11851
ISO 2852
12
Operating data
(Continued)
Materials
Aluminium housing (F6, T3)
Plastic housing (F10)
Sainless steel housing (F8)
Seal for housing cover
GD-Al Si 10 Mg, DIN 1725, plastic coated (blue/grey) fibre-glass reinforced polyester (blue/grey) stainless steel 1.4301 (AISI 304), unvarnished type F6, T3 housings: O-ring in EPDM (elastomer) type F10 housing: O-ring in silicone rubber type F8 housing: profiled O-ring in silicone
Cable gland IP 66 for cable entry Pg 16
Sealing ring for process connection G 3 /
4
A or G 1 A
Temperature spacer
Probe rod, ground tube process connection, screening, build-up compensation, tensioning weight for rope probe
Polyamide with neoprene CR seal for cable diameter
7...12 mm; ambient temperature up to 80°C
Elastomer-fibre, asbestos-free, resistant to oils, solvents, steam, weak acids and alkalis; up to 300°C and 100 bar
Stainless steel SS 304 (1.4301) or similar
AISI 316L (1.4435)
Probe rope AISI 316 (1.4401)
Further material specifications see Product Structure on Page 14...18
13
Product Structure
DC 12 TE Multicap T DC 12 TE
Rod probe for standard applications
Certificate
A For non-hazardous areas
B ATEX II 1/2 G EEx ia IIC T6
D For non-hazardous areas
E ATEX II 2 G EEx d [ia] IIC T6
Overspill protection to WHG
F ATEX II 1/2 G EEx ia IIC T6
K FM XP
Overspill protection to WHG
Class I, Div. 1, Groups A-D
R CSA XP Class I, Div. 1, Groups B-D
Y Special version
1 ATEX II 2 G EEx d (ia) IIB T6
2 ATEX II 1/2 G EEx ia IIB T6
3 ATEX II 1/2 G EEx ia IIB T6
Overspill protection to WHG
4 ATEX II 2 G EEx d (ia) IIC T6*
5 ATEX II 1/2 G EEx ia IIC T6* Overspill protection to WHG
6 ATEX II 1/2 G EEx ia IIC T6*
*) With note: “Avoid electrostatic charge”
Type of insulation
1 Fully insulated probe
6 Partiall insulated probe
Length of insulation L2
A ......mm (75 mm...3000 mm)
B ......mm (75 mm...3000 mm)
C ......mm (75 mm...3000 mm)
Y Special version
1 Fully insulated probe partially insulated PTFE partially insulated PFA partially insulated PE
Active length L1, Material
A ......mm (100 mm...3000 mm) fully insulated PTFE
B ......mm (100 mm...3000 mm) fully insulated PFA
C ......mm (100 mm...3000 mm) fully insulated PE
Y Special version
1 ......mm (100 mm...3000 mm) partially insulated
Process connection, Material
A G ¾ A,
B G 1 A,
Thread ISO 228
Thread ISO 228
316L
316L
C
D
¾” NPT
1” NPT
E DN 50 PN 40
Hygienic connection
Thread ANSI
Thread ANSI
316L
316L
DIN 11851 316L
ISO 2852 316L F DN 40-51 (2”)
Tri-Clamp connection
G DN 38 (1½“)
Tri-Clamp connection
ISO 2852 316L
316L H DN 25 (1”)
Tri-Clamp connection
L DN 38 (1½”) removable,
Tri-Clamp connection
Y Special version
5 Flanged process connection
ISO 2852
ISO 2852 316L, A3
316L
Flange type, Material
1B without process flange connection
1C DN 25 PN 6 B DIN 2527
1D DN 25 PN 25/40 B
1E DN 32 PN 6 B
DIN 2527
DIN 2527
1F DN 32 PN 25/40 B
1G DN 40 PN 6 B
1H DN 40 PN 25/40 B
1K DN 50 PN 6 B
1L DN 50 PN 25/40 B
DIN 2527
DIN 2527
DIN 2527
DIN 2527
DIN 2527
2D DN 25 PN 25/40
2F DN 32 PN 25/40
2H DN 40 PN 25/40
2K DN 50 PN 6
2L DN 50 PN 25/40
3F DN 32 PN 40 F
3H DN 40 PN 40 F
3L DN 50 PN 40 F
4F DN 32 PN 40 N
4H DN 40 PN 40 N
4L DN 50 PN 40 N
DIN 2527
DIN 2527
DIN 2527
DIN 2527
DIN 2527
DIN 2512
DIN 2512
DIN 2512
DIN 2512
DIN 2512
DIN 2512
316L
316L
316L
316L
316L
316L
316L
316L
PTFE >316L
PTFE >316L
PTFE >316L
PTFE >316L
PTFE >316L
316L
316L
316L
316L
316L
316L
Basic weight 1,2 kg including
¾“ process connection and F10 housing
Additional weight
0,1 kg/m
0,1 kg/m
0,1 kg/m
1 kg/m
1 kg/m
1 kg/m
0,9 kg/m
0,1 kg
0,1 kg
0,5 kg
0,5 kg
1,2 kg
1,8 kg
2,2 kg
1,4 kg
3,0 kg
1,8 kg
2,2 kg
3,0 kg
1,8 kg
2,2 kg
3,0 kg
0,6 kg
1,2 kg
1,0 kg
1,8 kg
1,2 kg
2,2 kg
1,4 kg
3,0 kg
DC 12 TE -
Continued Page 15
Product designation (first part)
14
Product Structure
(Continued)
Flange type, Material (Continued)
5A
5B
5E
5F
5G
5H
6A
6B
6E
1"
1"
2"
2"
1"
1"
150 lbs,
300 lbs,
1½“ 150 lbs,
1½” 300 lbs,
150 lbs,
300 lbs,
150 lbs,
300 lbs,
1½“ 150 lbs,
9Y Special version
RF,
RF,
RF,
RF,
RF,
RF,
RF,
RF,
RF,
6F 1½” 300 lbs, RF,
6G 2" 150 lbs, RF,
6H 2" 300 lbs, RF,
ANSI B16.5
316L
ANSI B16.5
316L
ANSI B16.5
316L
ANSI B16.5
316L
ANSI B16.5
316L
ANSI B16.5
316L
ANSI B16.5
PTFE >316L
ANSI B16.5
PTFE >316L
ANSI B16.5
PTFE >316L
ANSI B16.5
PTFE >316L
ANSI B16.5
PTFE >316Ti
ANSI B16.5
PTFE >316L
Additional weight
Electronic insert
A prepared for ECxx electronic insert with low housing cover
B with EC 61 Z, 3-wire insert
C with EC 11 Z, 3-wire Tx, 33 kHz
D with EC 72 Z, 3-wire Tx, 1 Mhz
E with EC 17 Z, 2-wire PFM
G with EC 37 Z, 2-wire PFM, 33 kHz
H with EC 47 Z, 2-wire PFM, 1 MHz
K with FEC 12, 2-wire 4-20 mA HART
M with FEC 22, 90…253 V AC, DPDT relay
N with FEC 22, 10…55 V DC, 3-wire PNP
P with FEC 14, PROFIBUS PA
V with FEC 14, Local operation FHB 20 and PROFIBUS PA
Y Special version
2 prepared for FECxx electronic insert with raised housing cover 0,3 kg**
0,2 kg
0,2 kg
0,2 kg
0,2 kg
0,2 kg
0,2 kg
0,3 kg**+ 0,3 kg
0,3 kg**+ 0,3 kg
0,3 kg**+ 0,3 kg
**) Additional weight for raised cover
Housing
A Polyester F10 Housing gland Pg16
E Polyester
F Aluminium
F10 Housing HNA24x1,5
F6 Housing HNA24x1,5
G Aluminium T3 Housing HNA24x1,5
K Polyester F10 Housing gland M20x1,5
L Aluminium F6 Housing gland M20x1,5
M Aluminium T3 Housing gland M20x1,5
N Aluminium T3 Housing PA-plug M12
O 316L
P Polyester
F8 Housing PA-plug M12
F10 Housing Nema4X, NPT ½”
5
6
3
4
1
2
R Aluminium F6 Housing Nema4X, NPT ½”
S Aluminium T3 Housing Nema4X, NPT ¾”
T Aluminium T3 Housing entry G ½ A
Y Special version
316L
316L
F8 Housing gland Pg13,5
F8 Housing entry G ½”
316L
316L
Polyester
Aluminium
F8 Housing gland M20x1,5
F8 Housing entry NPT ½”
F10 Housing PA-plug M12
F6 Housing PA-plug M12
Option
1 Basic version
2 TAG number
3 Temperature spacer
4 Temperature spacer and TAG number
9 Special version
IP66
IP66
IP66
IP66
IP66
IP66
IP66 1,0 kg
IP66 1,0 kg
IP66 1,0 kg
IP66
IP66
IP66
IP66
IP66
IP66
IP66
0,2 kg
0,2 kg
0,7 kg
1,2 kg
1,3 kg
2,5 kg
2,2 kg
3,0 kg
0,7 kg
1,2 kg
1,3 kg
2,5 kg
2,2 kg
3,0 kg
Please don’t forget:
Length of
Partial insulation
Active probe length
L2
L1 mm mm
DC 12 TE -
15
Complete product designation for DC 12 TE
Product Structure
DC 11 TEN- MULTICAP T DC 11 TEN
Fully insulated rod probe for standard applications
DC 16 TEN- MULTICAP T DC 16 TEN
Partially insulated rod probe for standard applications
DC 21 TEN- MULTICAP T DC 21 TEN
Fully insulated rope probe for standard applications
DC 26 TEN- MULTICAP T DC 26 TEN
Partially insulated rope probe for standard applications
DC 11 TES- MULTICAP T DC 11 TES
Fully insulated rod probe with protection features
DC 16 TES- MULTICAP T DC 16 TES
Partially insulated rod probe with protection features
DC 21 TES- MULTICAP T DC 21 TES
Fully insulated rope probe with protection feature
DC 26 TES- MULTICAP T DC 26 TES
Partially insulated rope probe with protection features
Certificate
A For non-hazardous areas
B ATEX II 1/2 G EEx ia IIC T6
D For non-hazardous areas Overspill protection to WHG
E ATEX II 2 G
Y Special version
EEx d (ia) IIC T6
1 ATEX II 2 G EEx d (ia) IIB T6
3 ATEX II 1/2 G EEx ia IIB T6
4 ATEX II 2 G EEx d (ia) IIC T6*
6 ATEX II 1/2 G EEx ia IIC T6*
*) With note: “Avoid electrostatic charge”
Build-up protection
DC 11, 16, 21, 26 TEN
A Protection feature not selected
DC 11, 16, 21, 26 TES
B 100 mm active guard
C 150 mm L3 screening
D 250 mm L3 screening
E 500 mm L3 screening
F ......mm (100 mm...1500 mm) L3 screening
G 150 mm L3 screening and
100 mm active guard
H 250 mm L3 screening and
100 mm active guard
K 500 mm L3 screening and
100 mm active guard
L ......mm (100 mm...1500 mm) L3 screening and
100 mm active guard
Y Special version
Basic weight including
¾“ process connection and F10 housing, for rope probes with tensioning weight
1,2 kg
1,2 kg
1,4 kg
1,4 kg
1,2 kg
1,2 kg
1,4 kg
1,4 kg
Additional weight
0,2 kg
0,2 kg
0,3 kg
0,6 kg
1,2 kg/m
0,4 kg
0,5 kg
0,9 kg
1,7 kg/m + 0,2 kg
Probe insulation
DC 11 TEN/TES, DC 21 TEN/TES
1 Fully insulated probe
DC 16 TEN/TES
A ......mm (75 mm...3000 mm) partially insulated PTFE
DC 26 TEN/TES
D rope type; 2,5 mm
9 Special version
Active length L1, Material
DC 11 TEN/TES
1 ......mm (100 mm...3000 mm)
2 ......mm (100 mm...3000 mm) with ground tube
DC 16 TEN/TES
1 ......mm (100 mm...3000 mm)
2 ......mm (100 mm...3000 mm) with ground tube
DC 21 TEN/TES
1 ......mm (100 mm...20000 mm) tensioning weight with anchor hole
DC 26 TEN/TES
1 ......mm (100 mm...20000 mm)
9 Special version
316L+PTFE
316L+PTFE
Rod 316L
Rod 316L
316+FEP
316+FEP
0,06 kg/m
0,5 kg/m
1,2 kg/m
0,4 kg/m
1,1 kg/m
0,04 kg/m
0,03 kg/m
Continued Page 17
DC . . TE . Product designation (first part)
16
Product Structure
(Continued)
Process connection, Material
A G ¾ A
B G 1 A
Thread ISO 228
Thread ISO 228
C
D
¾” NPT
1” NPT
E DN 50 PN 40
Thread ANSI
Thread ANSI
DIN 11851
Hygienic connection
F DN 40-51 (2”)
Tri-Clamp connection
ISO 2852
Y Special version
5 Flanged process connection
316L
316L
316L
316L
316L
316L
316L
Flange type, Material
1B without process flange connection
1C DN 25 PN 6 B DIN 2527
1D DN 25 PN 25/40 B
1E DN 32 PN 6 B
DIN 2527
DIN 2527
1F DN 32 PN 25/40 B
1G DN 40 PN 6 B
1H DN 40 PN 25/40 B
1K DN 50 PN 6 B
DIN 2527
DIN 2527
DIN 2527
DIN 2527
1L DN 50 PN 25/40 B
2D DN 25 PN 25/40
2F DN 32 PN 25/40
2H DN 40 PN 25/40
2K DN 50 PN 6
2L DN 50 PN 25/40
3F DN 32 PN 40 F
DIN 2527
DIN 2527
DIN 2527
DIN 2527
DIN 2527
DIN 2527
DIN 2512
3H DN 40 PN 40 F
3L DN 50 PN 40 F
4F DN 32 PN 40 N
4H DN 40 PN 40 N
4L DN 50 PN 40 N
5A 1" 150 lbs, RF,
5B 1" 300 lbs, RF,
5E 1½“ 150 lbs, RF,
5F 1½” 300 lbs, RF,
5G 2" 150 lbs, RF,
5H 2" 300 lbs, RF,
6A 1" 150 lbs, RF,
6B 1" 300 lbs, RF,
6E 1½“ 150 lbs, RF,
6F 1½” 300 lbs, RF,
6G 2" 150 lbs, RF,
6H 2" 300 lbs, RF,
316L
316L
316L
316L
316L
316L
316L
316L
PTFE >316L
PTFE >316L
PTFE >316L
PTFE >316L
PTFE >316L
316L
DIN 2512
DIN 2512
DIN 2512
DIN 2512
316L
316L
316L
316L
DIN 2512 316L
ANSI B16.5
316L
ANSI B16.5
316L
ANSI B16.5
316L
ANSI B16.5
316L
ANSI B16.5
316L
ANSI B16.5
316L
ANSI B16.5
PTFE >316L
ANSI B16.5
PTFE >316L
ANSI B16.5
PTFE >316L
ANSI B16.5
PTFE >316L
ANSI B16.5
PTFE >316Ti
ANSI B16.5
PTFE >316L only DC 11, 16 TEN/TES and DC 21 TEN
7A 10 K 25 A RF, JIS B2210 316L
7B 10 K 40 A
7C 10 K 50 A
RF,
RF,
JIS B2210 316L
JIS B2210 316L
7D 10 K 80 A
7L 10 K 100 A
8A 10 K 25 A
8B 10 K 40 A
8C 10 K 50 A
8D 10 K 80 A
8L 10 K 100 A
RF,
RF,
RF,
RF,
RF,
RF,
RF,
JIS B2210
JIS B2210
JIS B2210
JIS B2210
JIS B2210
316L
316L
PTFE >316L
PTFE >316L
PTFE >316L
JIS B2210 PTFE >316L
JIS B2210 PTFE >316L
DC 21 TES
7C 10 K 50 A
8A 10 K 25 A
RF,
RF,
JIS B2210
JIS B2210
316L
PTFE >316L
DC 26 TEN/TES
7A 10 K 25 A
7C 10 K 50 A
8A 10 K 25 A
9Y Special version
RF,
RF,
RF,
JIS B2210
JIS B2210
JIS B2210
316L
316L
PTFE >316L
Additional weight
0,1 kg
0,1 kg
0,5 kg
0,5 kg
2,2 kg
3,0 kg
1,8 kg
2,2 kg
3,0 kg
0,7 kg
1,2 kg
1,3 kg
2,5 kg
2,2 kg
3,0 kg
0,7 kg
1,2 kg
1,3 kg
2,5 kg
2,2 kg
3,0 kg
0,6 kg
1,2 kg
1,0 kg
1,8 kg
1,2 kg
2,2 kg
1,4 kg
3,0 kg
1,2 kg
1,8 kg
2,2 kg
1,4 kg
3,0 kg
1,8 kg
DC . . TE . DC . . TE . -
Continued Page 18
Product designation (second part)
17
Electronic insert Additional weight
A prepared for ECxx electronic insert with low housing cover
B
C
D
E
G
H
K with EC 61 Z, 3-wire insert with EC 11 Z, 3-wire Tx, 33 kHz with EC 72 Z, 3-wire Tx, 1 Mhz with EC 17 Z, 2-wire PFM with EC 37 Z, 2-wire PFM, 33 kHz with EC 47 Z, 2-wire PFM, 1 MHz with FEC 12, 2-wire 4-20 mA HART
M with FEC 22, 90…253 V AC, DPDT relay
N with FEC 22, 10…55 V DC, 3-wire PNP
0,2 kg
0,2 kg
0,2 kg
0,2 kg
0,2 kg
0,2 kg
0,3 kg**+ 0,3 kg
0,3 kg**+ 0,3 kg
0,3 kg**+ 0,3 kg
P with FEC 14, PROFIBUS PA
V with FEC 14, Local operation FHB 20 and PROFIBUS PA
Y Special version
2 prepared for FECxx electronic insert with raised housing cover 0,3 kg**
**) Additional weight for raised cover
Housing
A Polyester
E Polyester
F10 Housing gland Pg16
F10 Housing HNA24x1,5
F Aluminium F6 Housing HNA24x1,5
G Aluminium T3 Housing HNA24x1,5
K Polyester F10 Housing gland M20x1,5
L Aluminium F6 Housing gland M20x1,5
M Aluminium T3 Housing gland M20x1,5
N Aluminium T3 Housing PA-plug M12
O 316L
P Polyester
F8 Housing PA-plug M12
F10 Housing Nema4X, NPT ½”
S Aluminium T3 Housing Nema4X, NPT ¾”
T Aluminium T3 Housing entry G ½ A
Y Special version
1 316L
2 316L
F8 Housing gland Pg13,5
F8 Housing entry G ½”
3 316L
4 316L
F8 Housing gland M20x1,5
F8 Housing entry NPT ½”
5 Polyester F10 Housing PA-plug M12
6 Aluminium F6 Housing PA-plug M12
Option
1 Basic version
2 TAG number
3 Temperature spacer
4 Temperature spacer and TAG number
9 Special version
IP66
IP66
IP66
IP66
IP66
IP66
IP66 1,0 kg
IP66 1,0 kg
IP66 1,0 kg
IP66
IP66
IP66
IP66
IP66
IP66
IP66
0,2 kg
0,2 kg
Please don’t forget:
Length of
Screening L3
Partial insulation L2
Active probe length L1 mm mm mm
DC . . TE . -
18
Complete product designation for DC . . TEN / TES
19
Europe
Austria
❑ Endress+Hauser Ges.m.b.H.
Wien
Tel. (02 22) 8 80 56-0, Fax (02 22) 8 80 56-35
Belarus
Belorgsintez
Minsk
Tel. (01 72) 26 31 66, Fax (01 72) 26 31 11
Belgium
❑ Endress+Hauser S.A./N.V.
Brussels
Tel. (02) 2 48 06 00, Fax (02) 2 48 05 53
Bulgaria
INTERTECH-AUTOMATION
Sofia
Tel. (02) 65 28 09, Fax (02) 65 28 09
Croatia
❑ Endress+Hauser GmbH+Co.
Zagreb
Tel. (01) 41 58 12, Fax (01) 44 78 59
Cyprus
I+G Electrical Services Co. Ltd.
Nicosia
Tel. (02) 48 47 88, Fax (02) 48 46 90
Czech Republic
❑ Endress+Hauser GmbH+Co.
Ostrava
Tel. (0 69) 6 61 19 48, Fax (0 69) 6 61 28 69
Denmark
❑ Endress+Hauser A/S
Søborg
Tel. (31) 67 31 22, Fax (31) 67 30 45
Estonia
Elvi-Aqua-Teh
Tartu
Tel. (7) 42 27 26, Fax (7) 42 27 26
Finland
❑ Endress+Hauser Oy
Espoo
Tel. (90) 8 59 61 55, Fax (90) 8 59 60 55
France
❑ Endress+Hauser
Huningue
Tel. 89 69 67 68, Fax 89 69 48 02
Germany
Endress+Hauser Meßtechnik GmbH+Co.
Weil am Rhein
Tel. (0 76 21) 9 75-01, Fax (0 76 21) 9 75-5 55
Great Britain
❑ Endress+Hauser Ltd.
Manchester
Tel. (01 61) 2 86 50 00, Fax (01 61) 9 98 18 41
Greece
I & G Building Services Automation S.A.
Athens
Tel. (01) 9 24 15 00, Fax (01) 9 22 17 14
Hungary
Mile Ipari-Elektro
Budapest
Tel. (01) 2 61 55 35, Fax (01) 2 61 55 35
Iceland
Vatnshreinsun HF
Reykjavik
Tel. (05) 88 96 16, Fax (05) 33 20 22
Ireland
Flomeaco Company Ltd.
Kildare
Tel. (0 45) 86 86 15, Fax (0 45) 86 81 82
Italy
❑ Endress+Hauser Italia S.p.A.
Cernusco s/N Milano
Tel. (02) 92 10 64 21, Fax (02) 92 10 71 53
Latvia
Raita Ltd.
Riga
Tel. (02) 25 47 95, Fax (02) 7 25 89 33
Lithuania
Agava Ltd.
Kaunas
Tel. (07) 20 24 10, Fax (07) 20 74 14 http://www.endress.com
Luxembourg
❑ Endress+Hauser S.A./N.V.
Brussels
Tel. (02) 2 48 06 00, Fax (02) 2 48 05 53
Netherlands
❑ Endress+Hauser B.V.
Naarden
Tel. (0 35) 6 95 86 11, Fax (0 35) 6 95 88 25
Norway
❑
Endress+Hauser A/S
Tranby
Tel. (0 32) 85 10 85, Fax (0 32) 85 11 12
Poland
Endress+Hauser Polska Sp. z o.o.
Warsaw
Tel. (0 22) 6 51 01 74, Fax (0 22) 6 51 01 78
Portugal
Tecnisis - Tecnica de Sistemas Industriais
Linda-a-Velha
Tel. (01) 4 17 26 37, Fax (01) 4 18 52 78
Romania
Romconseng SRL
Bucharest
Tel. (01) 4 10 16 34, Fax (01) 4 10 16 34
Russia
Avtomatika-Sever Ltd.
St. Petersburg
Tel. (08 12) 5 55 07 00, Fax (08 12) 5 56 13 21
Slovak Republic
Transcom technik s.r.o.
Bratislava
Tel. (7) 5 21 31 61, Fax (7) 5 21 31 81
Slovenia
Endress+Hauser D.O.O.
Ljubljana
Tel. (0 61) 1 59 22 17, Fax (0 61) 1 59 22 98
Spain
❑ Endress+Hauser S.A.
Barcelona
Tel. (93) 4 73 46 44, Fax (93) 4 73 38 39
Sweden
❑ Endress+Hauser AB
Sollentuna
Tel. (08) 6 26 16 00, Fax (08) 6 26 94 77
Switzerland
❑ Endress+Hauser AG
Reinach/BL 1
Tel. (0 61) 7 15 62 22, Fax (0 61) 7 11 16 50
Turkey
Intek Endüstriyel Ölcü ve Kontrol Sistemleri
Istanbul
Tel. (02 12) 2 75 13 55, Fax (02 12) 2 66 27 75
Ukraine
Industria Ukraïna
Kyiv
Tel. (44) 2 68 52 13, Fax (44) 2 68 52 13
America
Argentina
Servotron SACIFI
Buenos Aires
Tel. (01) 3 31 01 68, Fax (01) 3 34 01 04
Bolivia
Tritec S.R.L.
Cochabamba
Tel. (0 42) 5 09 81, Fax (0 42) 5 09 81
Brazil
Servotek
Sao Paulo
Tel. (0 11) 5 36 34 55, Fax (0 11) 5 36 34 57
Canada
❑ Endress+Hauser Ltd.
Burlington, Ontario
Tel. (9 05) 6 81 92 92, Fax (9 05) 6 81 94 44
Chile
DIN Instrumentos Ltda.
Santiago
Tel. (02) 2 05 01 00, Fax (02) 2 25 81 39
Colombia
Colsein Ltd.
Santafe de Bogota D.C.
Tel. (01) 2 36 76 59, Fax (01) 6 10 78 68
Costa Rica
EURO-TEC S.A.
San Jose
Tel. 2 96 15 42, Fax 2 96 15 42
Ecuador
Insetec Cia. Ltda.
Quito
Tel. (02) 46 18 33, Fax (02) 46 18 33
El Salvador
ACISA
San Salvador, C.A.
Tel. (02) 84 07 48
Guatemala
ACISA Automatiziacion Y Control
Ciudad de Guatemala, C.A.
Tel. (02) 32 74 32, Fax (02) 32 74 31
Mexico
Maquinaria y Accesorios S.A. de C.V.
Mexico D.F.
Tel. (5) 5 63 81 88, Fax (5) 3 93 29 37
Paraguay
Incoel S.R.L.
Asuncion
Tel. (0 21) 20 34 65, Fax (0 21) 2 65 83
Peru
Esim S.A.
Lima
Tel. (01) 4 71 46 61, Fax (01) 4 71 09 93
Uruguay
Circular S.A.
Montevideo
Tel. (02) 92 57 85, Fax (02) 92 91 51
USA
❑ Endress+Hauser Inc.
Greenwood, Indiana
Tel. (3 17) 5 35-71 38, Fax (3 17) 5 35-14 89
Venezuela
H. Z. Instrumentos C.A.
Caracas
Tel. (02) 9 79 88 13, Fax (02) 9 79 96 08
Africa
Egypt
IAB Office
Et Cairo
Tel. (02) 3 61 61 17, Fax (02) 3 60 96 76
Morocco
Oussama S.A.
Casablanca
Tel. (02) 24 13 38, Fax (02) 40 56 02
Nigeria
J F Technical Invest. Nig. Ltd.
Lagos
Tel. (1) 62 23 45 46, Fax (1) 62 23 45 48
South Africa
❑ Endress+Hauser Pty. Ltd.
Sandton
Tel. (0 11) 4 44 13 86, Fax (0 11) 4 44 19 77
Tunisia
Controle, Maintenance et Regulation
Tunis
Tel. (01) 79 30 77, Fax (01) 78 85 95
Asia
China
Endress+Hauser Beijing
Beijing
Tel. (0 10) 4 07 21 20, Fax (0 10) 4 03 45 36
Hong Kong
❑ Endress+Hauser (H.K.) Ltd.
Hong Kong
Tel. 25 28 31 20, Fax 28 65 41 71
India
❑ Endress+Hauser India Branch Office
Bombay
Tel. (022) 6 04 55 78, Fax (022) 6 04 02 11
Indonesia
PT Grama Bazita
Jakarta
Tel. (21) 7 97 50 83, Fax (21) 7 97 50 89
Japan
❑ Sakura Endress Co., Ltd.
Tokyo
Tel. (04 22) 54 06 11, Fax (04 22) 55 02 75
Malaysia
❑ Endress+Hauser (M) Sdn. Bhd.
Petaling Jaya, Selangor Darul Ehsan
Tel. (03) 7 33 48 48, Fax (03) 7 33 88 00
Philippines
Brenton Industries Inc.
Makati Metro Manila
Tel. (2) 8 43 06 61, Fax (2) 8 17 57 39
Singapore
❑ Endress+Hauser (S.E.A.) Pte., Ltd.
Singapore
Tel. 4 68 82 22, Fax 4 66 68 48
South Korea
Hitrol Co. Ltd.
Kyung Gi-Do
Tel. (032) 6 72 31 31, Fax (32) 6 72 00 90
Taiwan
Kingjarl Corporation
Taipei R.O.C.
Tel. (02) 7 18 39 38, Fax (02) 7 13 41 90
Thailand
❑ Endress+Hauser Ltd.
Bangkok
Tel. (2) 2 72 36 74, Fax (2) 2 72 36 73
Vietnam
Tan Viet Bao Co. Ltd.
Ho Chi Minh City
Tel. (08) 8 33 52 25, Fax (08) 8 33 52 27
Iran
Telephone Technical Services Co. Ltd.
Tehran
Tel. (0 21) 8 82 74 26, Fax(0 21) 8 82 73 36
Israel
Instrumetrics Industrial Control Ltd.
Tel-Aviv
Tel. (03) 6 48 02 05, Fax (03) 6 47 19 92
Jordan
A.P. Parpas Engineering S.A.
Amman
Tel. (06) 83 92 83, Fax (06) 83 92 05
Kingdom of Saudi Arabia
Intrah
Dammam
Tel. (03) 8 34 78 79, Fax (03) 8 34 48 32
Kuwait
Kuwait Maritime & Mercantile Co. K.S.C.
Safat
Tel. 2 43 47 52, Fax 2 44 14 86
Lebanon
Network Engineering Co.
Jbeil
Tel. (3) 25 40 52, Fax (9) 94 40 80
Sultanate of Oman
Mustafa & Jawad Sience & Industry Co.
L.L.C.
Ruwi
Tel. 60 20 09, Fax 60 70 66
United Arab Emirates
Descon Trading EST.
Dubai
Tel. (04) 35 95 22, Fax (04) 35 96 17
Yemen
Yemen Company for Ghee and Soap Industry
Taiz
Tel. (04) 23 06 65, Fax (04) 21 23 38
Australia + New Zealand
Australia
GEC Alsthom LTD.
Sydney
Tel. (02) 6 45 07 77, Fax (02) 7 43 70 35
New Zealand
EMC Industrial Instrumentation
Auckland
Tel. (09) 4 44 92 29, Fax (09) 4 44 11 45
All other countries
❑ Endress+Hauser GmbH+Co.
Instruments International
Weil am Rhein
Tel. (0 76 21) 9 75-02, Fax (0 76 21) 97 53 45
Endress
+
Hauser
The Power of Know How
❑ Members of the Endress+Hauser group 05.02/PT
BA 158F/00/en/06.03
016705-1000
CCS/CV8 016705- 1000
BA 148F/00/en/07.95 (b)
Software Version 1.x
Part No. 016700-1000
Electronic insert
FEC 12 with
HART Protocol
Level Measurement
Operating Instructions
Endress
+
Hauser
The Power of Know How
Abb. 1
Short instructions for calibrating the FEC 12 electronic insert using its own operating elements
Electronic insert FEC 12 (HART)
Short Instructions
The short instructions are intended for trained personnel who have read and understood the operating instructions in this manual. They allow a quick standard calibration of the electronic insert using the its own operating elements. A detailed description of calibration and operation is given in Sections 3 - 5.
lid with short instructions
FEC 12
Linearisation at FEC 12 linear: horiz. cylinder:
Reset to factory settings:
Empty calibration:
Full calibration:
Lock parameters:
Unlock parameters:
Linearisation at handheld terminal
5 s
.
.
.
✔
LED 2 s
✔ LED 2 s
Electronic insert FEC 12 (HART)
Table of Contents
Short Instructions
Notes on Safety . . . . . . . . . . 2
1 Introduction . . . . . . . . . . 3
1.1 Application
1.2 Measuring System
1.3 Operating Principle
3
3
3
2 Installation . . . . . . . . . . . 4
2.1 Electrical Connection
2.2 Technical Data
4
5
3 Operating Elements . . . . . . . 6
3.1 FEC 12 Electronic Insert
3.2 HART Communicator DXR 275
3.3 HART Menu Structure
6
7
7
4 Calibrating for Level Measurement 8
4.1 Basic Calibration at the FEC 12
Electronic Insert
4.2 Basic Settings using the HART
Communicator DXR 275
4.3 Extended Calibration using the
HART Communicator 275
8
11
12
5 Entries for the Measuring Point . 14
5.1 Locking/Unlocking Parameters
5.2 Tag Number
14
14
6 Diagnosis and Troubleshooting . 15
6.1 Alarms
6.2 Simulation
6.3 Description of Fault Responses,
15
15
Error Messages 17
6.4 Replacing the FEC 12 Electronic Insert 17
6.5 Transmitting Basic Settings
6.6 Transmitting All Settings
17
18
In addition to these operating instructions, the following documentation is also available on the use of the FEC 12 electronic insert:
•
Technical Information TI 242F/00/e: Multicap Probes DC ... E
•
Technical Information TI 243F/00/e: Multicap Probes DC ... A
•
Technical Information TI 240F/00/e: Multicap Probes DC ... T
•
Operating instructions for the HART handheld terminal DXR 275
Endress+Hauser
Supplementary documentation
1
2
Notes on Safety Electronic insert FEC 12 (HART)
Notes on Safety
Approved usage
Use in hazardous areas
Installation, commissioning and operation
The electronic insert FEC 12 may be used for level measurement in connection with capacitive Multicap probes only. It has been designed to operate safely in accordance with current technical and safety standards and must be installed by qualified personnel according to the instructions in this manual.
The manufacturer accepts no responsibility for any damage arising from incorrect use, installation or operation of the equipment. Changes or modifications to the equipment not expressly approved in the operating instructions or by the bodies responsible for compliance may make the user’s authority to use the equipment null and void. Damaged instruments which may be a safety hazard must not be operated and are to be marked as defective.
When used in explosion hazardous areas, the equipment must be installed in accordance with local regulations as well as with the technical and safety requirements on the measuring point as specified in the accompanying certificate.
Installation, electrical connection, commissioning, operation and maintenance may be carried out by trained and authorised personnel only. The operating instructions must have read and understand before the equipment is installed: instructions are to be followed exactly.
Safety Conventions
In order to highlight safety-relevant procedures in the manual, the following conventions have been used, each indicated by a corresponding icon in the margin.
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly affect operation or may lead to an instrument response which is not planned.
Note!
Caution!
Caution!
A caution indicates actions or procedures which, if not performed correctly, may lead to personal injury or incorrect function of the instrument.
Warning!
A warning indicates actions or procedures which, if not performed correctly, may lead to personal injury, a safety hazard or destruction of the instrument.
Warning!
Endress+Hauser
Electronic insert FEC 12 (HART) 1 Introduction
1 Introduction
1.1 Application
The FEC 12 electronic insert is a transmitter for capacitive level measurement. It converts changes in capacitance resulting from changes in level into a capacitance-proportional impressed current. In vessels with a uniform cross section, the level or quantity (volume) can be thus displayed as a percentage of full level or, if a handheld terminal is used, in technical units. A pre-stored linearisation program also allows volumes to be measured in horizontal cylinders.
The FEC 12 electronic insert is installed in the housing of the Multicap probe. It can be used for applications in explosion hazardous areas.
Versions with corresponding features
Two versions of the FEC 12 electronic insert are available:
•
With HART protocol to be used with the Universal HART Communicator (described in these operating instructions) and
•
With INTENSOR protocol to be used with the Commulog VU 260 Z (see operating instructions BA 149F/00/e).
The version with the INTENSOR protocol can also be used for communication with the Silometer FMX 770.
•
Analogue output signal: standard 4...20 mA current.
•
Easy on-site settings: Settings "empty calibration" (= 4 mA) and "full calibration"
(= 20 mA) using pushbuttons on the electronic insert.
•
Operates with a linear characteristic as well as with a stored linearisation curve for horizontal cylinders.
•
The adjustable integration time ensures stable measured values even with agitated materials.
Versions
Features
1.2 Measuring System
The measuring system consists of a capacitive Multicap level probe and an
FEC 12 electronic insert. A DC power supply is also required. The two-wire power cable is also used for signal transmission, and delivers a 4...20 mA signal with a superimposed bidirectional digital signal conforming to the HART protocol. The superimposed signal has no influence on the follow-up instrumentation.
4...20 mA with digital signal e.g. display e.g. plotter
Multicap probe
DC power supply or
PLC
1.3 Operating Principle
Capacitive measurement functions as follows: the probe and vessel wall form a capacitor. Depending on the level, the space between these "capacitor plates" is filled either with air (empty vessel) or an unspecified quantity of material. The initial capacitance for the empty vessel is low but increases proportionally to the amount of material covering the probe.
Fig. 2
Measuring system: the electronic insert is used in a
Multicap probe for capacitive measurement.
Endress+Hauser 3
4
2 Installation Electronic insert FEC 12 (HART)
Fig. 3
Connecting the
FEC 12 electronic insert to the power supply
2 Installation
This section describes the electrical connection of the electronic insert. See Section 6 for instructions on replacing the electronic insert.
2.1 Electrical Connection
FEC 12
✔
✔
1
1 2
3 4 5
- + transmitter power supply unit
Insert the power cable through the cable entry on the probe housing. Unscreened or general purpose multi-core cable can be used as the connecting cable. If strong electromagnetic interference occurs due to, e.g. machinery or radios, then screened cable, grounded at the probe end, should be used. Connect the screening to the ground terminal on the probe housing.
The power cable is connected to
Terminals 1 - and 2 + of the electronic insert. The electronic insert has built-in polarity protection. The black ground wire in the probe is always connected to
Terminal 3.
Warning!
Note!
Fig. 4
Connecting the handheld terminal to the load or power cable
Warning!
•
When using the probe in explosion-hazardous areas, ensure that the type and routing of the intrinsically safe power and signal line is in accordance with the certificate and local regulations.
•
See the certificate of conformity for maximum permissible values for capacitance and inductance.
Note!
After connection, ensure that the cover is screwed down securely and that the cable gland of the probe housing is screwed tight.
Field Control room min 230
Ω
FEC 12
✔
✔
1
1 2
3 4 5
4...20 mA
I
O
I
O
Not permitted with protection
Ex d
EX EX follow-up units or e.g.
communications resistor
I
O min
230
Ω
Endress+Hauser
Electronic insert FEC 12 (HART) 2 Installation
A load should be connected into the power cable when connecting a handheld terminal. The handheld terminal can now be connected at any point along the power cable for communication with the electronic insert. The size of the load is given in the following table.
Load for handheld terminal
FEC 12 electronic insert
Version HART
Without communication
Load resistance minimum
230
Ω
0
Ω
Maximum cable length: 1000 m.
Maximum capacitance for screened cabling: 100 nF.
Load resistance maximum (U
B
=30V)
720
Ω
720
Ω
2.2 Technical Data protective cover
49
Fig. 5
Construction and dimensions of the FEC 12 electronic insert
Weight : approx. 170 g
Housing: plastic, potted electronics,
Colour: light grey RAL 7035, protection to DIN 40050: IP 20
Interlock diode with jumper: 13.0 V ... 30 V,
With Interlock diode: 13.8 V ... 30 V for Ex d with Zener diode module: 13.8 V ... 30 V
Permissible superimposed AC voltage (50 Hz ... 400 Hz): 100 mV pp
Without communication: 3 % of power supply voltage,
No understepping of minimum voltage!
Integrated polarity protection
Current consumption 3.8 ... 22 mA
Load for HART: 230 ... 720
Ω,
Without communication: 0 ... 720
Ω
Initial capacitance (‘offset’) for empty vessel
(probe free): 0 pF ... 350 pF
Change in capacitance (‘span’) for full vessel
(probe covered): 10 pF ... 2000 pF
Total capacitance resulting from initial capacitance plus change in capacitance: maximum 2000 pF
Output signal: superimposed direct current for initial capacitance: 4 mA for total capacitance: 20 mA
Resolution: 14
µ
A
Alarm signal for error indication (can be switched off):
22 mA
±
0.1 mA, to NAMUR
Adjustable time constant: 0 ... 40 s
Factory set: 1 s
Output current from power supply voltage: smaller than 0.05 % / V of full scale value at 24 V
Output current from load: smaller than 0.1 % / 100
Ω
of full scale value at 24 V
Type of signal: quasi-sine curve superposed on measuring current without DC component
With Interlock diode: for ammeter
According to DIN 40040, HOE, condensation not permitted
Permitted ambient temperature:
Nominal operating range: 0 ... +70 °C
Limiting operating range: -20 ... +80 °C
Storage temperature: -40 ... +85 °C
Protection against electrostatic build-up: up to 15 kV
RFI immunity (depending on type of housing): up to 10 V/m
Electromagnetic Compatibility:
Interference Emission to EN 61326; Electrical Equipment Class B
Interference Immunity to EN 61326; Annex A (Industrial) and
NAMUR Recommendation EMC (NE 21)
Endress+Hauser
Construction
Power Supply
Load
Capacitance Ranges
Analogue Output
Output damping
Accuracy
Communication Interface
Additional Signal Output
Environmental Conditions
5
3 Operating Elements Electronic insert FEC 12 (HART)
Fig. 6
Operating elements on the
FEC 12 electronic insert
3 Operating Elements
This Section describes the operating elements of the electronic insert. It also describes the menu structure of the HART protocol used with the Universal HART
Communicator DXR 275.
3.1 FEC 12 Electronic Insert
The operating elements of the electronic insert are protected by a cover. This can be raised by inserting a small screwdriver into a slit at the edge. The inside of the cover has symbols printed on it that serve as a quick operating manual.
lid with short instructions switch for selecting local or remote linearisation pushbuttons, e.g. for empty calibration switch for the type of linearisation pushbuttons, e.g. for full calibration
Switches
Pushbuttons
6
FEC 12 green LED: indicates successful calibration
✔
✔
1 2
4...20 mA
3 4 5 connection for ammeter
The lefthand switch selects whether the linearisation is to be carried out remotely with the handheld terminal or locally with the FEC 12 operating elements. If linearisation at the FEC 12 is required, then one of two stored linearisation modes in the electronic insert is activated (vertical vessel with linear characteristics or horizontal cylinder) at the righthand switch.
Calibration, locking and reset to factory-set values are carried out at the FEC 12 by using the four pushbuttons (see Section 4).
Basic Operation:
The pushbuttons marked with (+) increase current and those marked (-) decrease current. Punching the pushbuttons produces a step-wise change. The smallest resolution possible is 0.014 mA. If the pushbutton is pressed continuously, then the current also changes continuously until the pushbutton is released. The change begins slowly and gradually increases in speed and so quickly passes through a wide range. Just before reaching the value required, the pushbutton should be released and the procedure completed by punching the pushbutton for fine resolution. If the value required is overrun, then correct for it by pressing the pushbutton for the other direction.
Endress+Hauser
Electronic insert FEC 12 (HART) 3 Operating Elements
3.2 HART Communicator DXR 275
When the lefthand switch is set to remote linearisation (arrow symbol), the FEC 12 electronic insert can be calibrated using the HART Communicator handheld terminal.
The terminal communicates with the electronic insert over the power/signal cable. The operating manual for the HART Communicator describes its operation. Some knowledge of operating the HART Communicator is assumed for the following section.
Note!
When calibrating the FEC 12 electronic insert, the following sections will assume the operating steps given below. They apply to all instructions and will, therefore, no longer be given in this manual:
•
First step: Move from the "MATRIX GROUP SEL." menu to the next higher menu with the
→ arrow key.
•
Last step: Return to the "Online" menu with F3 [HOME].
3.3 HART Menu Structure
All parameters of the FEC 12 can be addressed by the menu structure using the handheld terminal. The following diagram shows the menu structure of the HART protocol for the FEC 12 electronic insert. Each field in the menu structure can be selected using the arrow or numeric keys on the handheld terminal.
Note!
From "Online" menu«
Fig. 7
Menu structure for the HART
Communicator handheld terminal
1
CALIBRATION
1 MEASURED VALUE
2 EMPTY CALIBRATION
3 FULL CALIBRATION
4 MIN: CURRENT 4 mA
5 OUTPUT DAMPING
6 VALUE FOR 4 mA
7 VALUE FOR 20 mA
8 SAFETY ALARM
9 CAPACITANCE
CURRENT
HOME
2
EXTENDED CAL.
1 LINEARISATION
2 OFFSET
3 SENSITIVITY
4 TEMPERATURE UNIT
5 MEASURED TEMPERATURE
6 MIN. TEMPERATURE
7 MAX. TEMPERATURE
8 SECURITY LOCKING
HOME
MATRIX GROUP SEL.
1 CALIBRATION
2 EXTENDED CAL.
3 SERVICE/SIMULATION
4 USER INFORMATION
HOME
3
SERVICE/SIMULATION
1 DIAGNOSTIC CODE
2 LAST DIAGNOSTIC
3 SOFTWARE NO.
4 DEFAULT VALUES
5 SIMULATION
6 SIM. LEVEL
7 SIM. VOLUME
8 SIM. CURRENT
HOME
4
USER INFORMATION
1 SET TAG NUMBER
2 SERIAL NUMBER
3 MEASURING RANGE
4 C AT EMPTY CAL.
5 C AT FULL CAL.
6 SELECT UNIT
7 OFFSET OF DEVICE
8 SENSIT. OF DEVICE
HOME
Endress+Hauser 7
8
4 Calibrating Electronic insert FEC 12 (HART)
Note!
4 Calibrating
This section deals with the basic settings necessary for the electronic insert to convert capacitance values into correct data on level or volume, which can then be shown on a display unit (e.g. meter or handheld terminal).
The electronic insert can carry out basic settings in two ways:
•
On site at the electronic insert itself or
•
On the handheld terminal.
The initial basic settings can also be carried out locally at the electronic insert and then later with the handheld terminal for, e.g. setting the type of linearisation
(Note: the electronic insert must not be locked).
Note!
•
After completing calibration the matrix should then be locked (see Section 5.1).
After locking, all entries can be called up and displayed but no longer changed.
•
The values entered can be written in the table below so that the identical values can again be entered if the electronic insert is replaced. A complete recalibration is not then required (see also Section 6).
Note!
Reset (recall of factory settings)
4.1 Basic Calibration at the FEC 12 Electronic Insert
The following entries are required for basic calibration of the electronic insert:
•
Type of linearisation
•
Empty calibration
•
Full calibration
Note!
•
If an initial calibration is not to be carried out, but instead a recalibration of the system, then a reset the electronic insert first.
•
This also applies when it is not clear if the electronic insert is calibrated with factory settings (see following section). Unwanted settings may result and lead to incorrect measured values.
Press the pushbuttons for empty calibration (-) and for full calibration (-) simultaneously for approx. 5 s. This produces the following factory settings:
Significance
Empty calibration [%]
Full calibration [%]
Min. current 4 mA
Output damping [s]
Value for 4 mA [%]
Value for 20 mA [%]
Safety alarm
Linearisation
Offset [pF]
Sensitivity [pF/%]
Set tag number
Select unit
Factory settings Entered values
0.0
100.0
off
1
0.0
100.0
max (110 %) linear
349.90
16.49
’--------’
%
Endress+Hauser
Electronic insert FEC 12 (HART) 4 Calibrating
Two types of linearisation can be selected:
•
Vessel characteristics as linear
•
Vessel characteristics as a horizontal cylinder
Use the lefthand switch to select whether linearisation is to be carried out at the electronic insert or by the handheld terminal. If the switch is moved to the right, then linearisation is carried out at the electronic insert. The handheld terminal cannot now change the setting. If the switch is moved to the left, then linearisation must be carried out with the handheld terminal and the switch on the right remains inactive.
Select the type of linearisation for local calibration using the righthand switch. When it is moved to the left, then the level (output current) is proportional to volume, i.e. the cross-section of the vessel should be constant over its entire length. When it is moved to the right, then linearisation is set for a horizontal cylinder, and the measured value supplied corresponds directly to a percent of full volume.
Selecting linearisation
Empty calibration With the vessel empty (0 %) both pushbuttons on the left (-) and (+) are pressed simultaneously in order to set the signal current to the 4 mA lower value. The green
LED lights up to acknowledge that the setting has been accepted. Only when the green LED goes out is the correct current value of 4 mA shown on the ammeter.
With the vessel full (100 %) both pushbuttons on the right (-) and (+) are pressed simultaneously in order to set the signal current to the 20 mA upper value. The green
LED lights up to acknowledge that the setting has been accepted. Only when the green LED goes out is the correct value of 20 mA shown on the ammeter.
Full calibration
In this case, the level of product in the vessel must be known as accurately as possible and should not be too high. A level which is too high reduces the accuracy of the zero point (corresponding to an empty vessel). An ammeter must be connected to the electronic insert at Terminals 4 - 5.
Assuming that the level is at 15 %, the current value corresponding to a 15% level must now be determined. The lower current value can be varied by pressing the two pushbuttons on the left. The following calculation is used:
➀ The lower current value (= empty vessel, 0 %) is 4 mA.
➁ The upper current value (= full vessel, 100 %) is 20 mA.
➂ This gives a measuring range (‘span’) of 16 mA for a change from 0 to 100 % or a
0.16 mA increase in current for every 1 % rise in level.
➃ For a 15 % level, this is 15 % x 0.16 mA/% or 2.4 mA. This must be added to the
4 mA to give the current value required:
2.4 mA + 4 mA = 6.4 mA
➄ The value 6.4 mA (check with the ammeter) is set by pressing the two pushbuttons on the left. Pressing pushbutton (+) increases the current and pressing pushbutton
(-) decreases the current.
Note!
•
No indication is given on the green LED when using this procedure.
•
If the operating status is unclear due to an incorrect setting, then all settings should be reset to factory-set values and the basic calibration carried out again.
Alternative procedure: calibration with the vessel almost empty
Note!
Endress+Hauser 9
4 Calibrating Electronic insert FEC 12 (HART)
Alternative procedure: calibration with the vessel almost full
Note!
The level of the vessel must be known as accurately as possible and should be as high as possible. A level which is too low reduces the accuracy of the upper point
(corresponding to a full vessel). An ammeter must be connected to the electronic insert at Terminals 4 - 5.
Assuming that the level is at 90 %, the current value corresponding to a 90 % level must now be determined. The upper current value can be varied by pressing the two pushbuttons on the right. The following calculation is used:
➀ The lower current value (= empty vessel, 0 %) is 4 mA.
➁ The upper current value (= full vessel, 100 %) is 20 mA.
➂ This gives a measuring range (‘span’) of 16 mA for a change from 0 to 100 % or a 0.16 mA increase in current for every 1 % rise in level.
➃ For a 90 % level this is 90 % x 0.16 mA/% or 14.4 mA. This must be added to the
4 mA to give the current value required:
14.4 mA + 4 mA = 18.4 mA
(The upper current value can also be used and
10 % x 0.16 mA/% = 1.6 mA is to be subtracted from 20 mA)
➄ The value 18.4 mA (check with the ammeter) is set by pressing the two pushbuttons on the right. Pressing pushbutton (+) increases the current and pressing pushbutton (-) decreases the current.
Note!
•
No indication is given on the green LED when using this variation.
•
If the operating status is unclear due to an incorrect setting, then all settings should be reset to factory-set values and the basic calibration carried out again.
Locking the parameters
Unlocking the parameters
Press simultaneously the pushbutton for empty calibration (+) and the pushbutton for full calibration (-). The settings of the electronic insert can now be called up at any time using the handheld terminal but not changed. This condition is indicated in the handheld terminal by the appearence of the code 9999 in Menu Level 2 "EXTENDED
CALIBRATION" , Field 8 "SECURITY LOCKING" (see Section 5).
Press simultaneously the pushbutton for empty calibration (-) and the pushbutton for full calibration (+). All settings of the electronic insert can now be called up and changed using the handheld terminal. This condition is indicated in the handheld terminal by the appearence of the code 12 in Menu Level 2 "EXTENDED CALIBRATION" ,
Field 8 " SECURITY LOCKING " (see Section 5).
10 Endress+Hauser
Electronic insert FEC 12 (HART) 4 Calibrating
4.2 Basic Settings using the HART Communicator DXR 275
The FEC 12 allows calibration in % only. A remote calibration from the handheld allows, e.g. technical units to be displayed. If a recalibration is to be carried out, then a reset should be done first. The parameters of the electronic insert must not be locked, see above!
Note!
When calibrating the FEC 12 electronic insert, the following sections will assume the operating steps given below. They apply to all instructions and will, therefore, no longer be given in this manual:
•
First step: Move from the "MATRIX GROUP SEL." menu to the next higher menu with the
→
arrow key.
•
Last step: Return to the "Online" menu with F3 [HOME].
Step Entry
1 3
Cursor in display at
SERVICE/SIMULATION
2 4 DEFAULT VALUES
3 12 12
5 F2 [SEND]
Significance
Code number for reset
Confirms entry
Value to be transmitted
The factory settings given on reset are shown in the following table:
1; 7
1; 8
2; 1
2; 2
2; 3
4; 1
4; 6
Menu field
1; 2
1; 3
1; 4
1; 5
1; 6
Significance
EMPTY CALIBRATION [%]
FULL CALIBRATION [%]
MIN. CURRENT 4 mA
OUTPUT DAMPING [s]
VALUE FOR 4 mA [%]
VALUE FOR 20 mA [%]
SAFETY ALARM
LINEARISATION
OFFSET [pF]
SENSITIVITY[pF/%]
SET TAG NUMBER
SELECT UNIT
Factory setting
0.0
100.0
OFF
1
0.0
100.0
MAX (110 %)
LINEAR
349.90
16.49
’--------’
%
Values entered
Note!
Reset (factory settings)
Endress+Hauser 11
4 Calibrating Electronic insert FEC 12 (HART)
Selecting linearisation Two vessel characteristics are available: linear or horizontal cylinder
Note!
•
The switch on the left on the FEC 12 electronic insert must be moved to the left so that linearisation can be carried out remotely with the handheld terminal.
3
4
Step Entry
1 2
2 1
F4 [ENTER]
Cursor in display at
EXTENDED CALIBRATION
LINEARISATION e.g. LINEAR
HORIZ. CYL.
Significance
Extended calibration
Selecting linearisation
Level is proportional to volume, i.e. the cross-section of the vessel remains constant over the entire distance
Horizontal cylinder : the measured value directly corresponding to volume
Confirms entry, value to be transmitted
Empty and full calibration
4 mA threshold
Note!
Step Entry Cursor in display at
1 1 CALIBRATION
2 2 EMPTY CALIBRATION
3 0.0 0.0
4
5
F4 [ENTER]
3
6 100.0
FULL CALIBRATION
100.0
7 F4 [ENTER]
Significance
Basic calibration
Empty calibration
Vessel is empty, a 4 mA signal is output at the entered level or volume
Confirms entry, value to be transmitted
Full calibration
Vessel is full, a 20 mA signal is output at the entered level or volume
Confirms entry, value is transmitted
Note!
•
You can also calibrate in technical units, see also 4 mA/20 mA value, p 13. In this case, if a horizontal cylinder is selected, the entries must be made in volume units!
4.3 Extended Calibration using the HART Communicator 275
The factory settings allow a current range from 3.8 mA to 20 mA and larger. Since a current less than 4 mA could result in unwanted responses by process control systems, it is possible to set a threshold of 4 mA on the current output, below which it cannot fall.
Step Entry
1 1
2 4
3
Cursor in display at
CALIBRATION
MIN. CURRENT 4 mA
ON
OFF
Significance
Basic calibration
Current output at minimum 4 mA
Threshold is at 4.0 mA
Current range begins at 3.8 mA
Confirms entry, value is transmitted
Note!
•
At factory setting the 4 mA threshold is switched off
Note!
12 Endress+Hauser
Electronic insert FEC 12 (HART) 4 Calibrating
The output damping is set in the factory at 1 s and affects the speed at which the current output responds to a change in level. When there is a sudden jump from empty to full in the vessel, after 1 s the current display reaches 63% or 14.08 mA of the set point (1*output damping). After 5 s (5*output damping) it reaches 99 % or
19.84 mA. If a larger output damping is set, then these display times are correspondingly longer.
The output damping can be selected between the range 0 and 40 s. For liquids, the turbulence can cause the display to be unstable. Increasing the output damping with the handheld terminal cancels this effect.
Output damping
Step Entry Cursor in display at
1 1 CALIBRATION
2 5 OUTPUT DAMPING
1 s
2 3 e.g. 2
4 F4 [ENTER]
5 F2 [SEND]
Significance
Basic setting
Setting the output damping
(Factory setting 1 s)
Sets the output damping to 2 s
Confirms entry
Value is transmitted
If another value instead of 0 (= empty vessel) is to be displayed, then the value can be entered here. The units are changed from % in the " SELECT UNIT " menu.
Step Entry
1 1
2
3
6
Cursor in display at
CALIBRATION
VALUE FOR 4 mA e.g. 20.0 20.0
4 F4 [ENTER]
5 F2 [SEND]
Significance
Basic setting
Value for 4 mA
Value is displayed if the current value is 4 mA
Confirms entry
Value is transmitted
Value for 4 mA
If another value instead of 100 (= full vessel) is to be displayed, then the value can be entered here. The units are changed from % in the " SELECT UNIT" menu (see below).
Value for 20 mA
Step Entry
1 1
2
3
7
Cursor in Display at
CALIBRATION
VALUE FOR 20 mA e.g. 80.0 80.0
4 F4 [ENTER]
5 F2 [SEND]
Significance
Basic setting
Value for 20 mA
Value is displayed, if the current value is 20 mA
Confirms entry
Value is transmitted
Instead of giving the results in %, the following units may be selected:
Level:
Volume:
Weight: cm l ton dm hl kg m t cm3 inch dm3 lb.
ft m3 ft3 us_gal i_gal
Selecting units
Step Entry
1 4
2 6
3
Cursor in display at
USER INFORMATION
SELECT UNIT
%
e.g.10x
m3
5 F2 [SEND]
Significance
User information
Select units
Factory setting
Volume display in m3
Confirms entry
Value to be transmitted
Endress+Hauser 13
5 Entries for the Measuring Point
Locking
Unlocking
Electronic insert FEC 12 (HART)
5 Entries for the Measuring Point
5.1 Locking/Unlocking Parameters
The parameters can be locked from the handheld terminal by entering a code number between 1 and 11 or between 13 and 9998: all settings in the electronic insert are protected from being altered. If the code number 9999 is shown in the display, then locking has been activated at the electronic insert by pushbutton.
Step Entry Cursor in Display at
1 2 EXTENDED CALIBRATION
2 8 SECURITY LOCKING
3 e.g. 35
4 F4 [ENTER]
12
35
Significance
Extended calibration
Locking
No locking activated
Selected code number for locking
Confirms entry, valueis transmitted
With the exception of " SECURITY LOCKING" all fields can be viewed but not changed..
Locking can be again cancelled by entering the code number 12. This does not apply if the locking was activated at the electronic insert. This is indicated by the code number 9999 in the menu field.
Step Entry Cursor in Display at
1 2 EXTENDED CALIBRATION
2 8 e.g. 35
3 12
4 F4 [ENTER]
SECURITY LOCKING
35
12
Significance
Extended calibration
Locking
Selected code number for locking
Code number for unlocking
Confirms entry, value to be transmitted
5.2 Tag Number
A measuring point number ( "SET TAG NUMBER" ) can be assigned to the electronic insert by using the handheld terminal. This consists of 8 ASCII characters. This measuring point tag serves to identify different electronic inserts connected to the same power line as every electronic insert has to have its own unique tag number.
2
3
Step Entry Cursor in Display at
1 4 USER INFORMATION
1 SET TAG NUMBER e.g. LIC10 LIC10
4 F4 [ENTER]
Significance
User information
Locking
Enter up to 8 characters
Confirms entry, value is transmitted
14 Endress+Hauser
Electronic insert FEC 12 (HART) 6 Diagnosis and Troubleshooting
6 Diagnosis and Troubleshooting
6.1 Alarms
The following response is set in the factory:
If the FEC 12 detects a fault, then the current output is set to 22 mA (=110 %) to enable process control systems to, e.g. assume a response.
If no alarm indication is to be given on an alarm, then " CONTINUE" can be set. In this case the FEC 12 continues to measure although the measured value is possibly incorrect.
Step
2
Entry
1 1
8
3
4 F4
[ENTER]
5 F2
[SEND]
Cursor in Display to
CALIBRATION
SAFETY ALARM
MAX (110%)
CONTINUE
Significance
Basic setting
Output on alarm
Output jumps to 22 mA (=110 %), factory set
Continue measuring, no alarm indication
Confirms entry
Value to be transmitted
Output on alarm
Alarm indication
6.2 Simulation
Simulation enables the current value coming from the electronic insert to be simulated. It can be used for checking the correct processing of probe signals, e.g. in a process control system. Simulation may also be necessary for tracing faults. No change in level is required to produce a different current value. The various types of simulation
•
Level ( LEVEL)
•
Volume ( VOLUME)
•
Current ( CURRENT) are independent from one another and therefore none affects the others.
Note!
•
If simulation is activated, Warning E 613 is displayed to indicate this.
•
The full simulation range is only available with a free probe, only a limited range is possible with a covered probe.
•
On completion, switch off simulation again in order to continue normal measurement.
Activate simulation as follows:
Note!
Simulation
Step Entry Cursor in Display at
1 3 SERVICE/SIMULATION
2 5 SIMULATION
3
OFF
ON
Significance
Service/Simulation
Simulation
Simulation switched off
Simulation switched on
Confirms entry, value to be transmitted
Endress+Hauser 15
6 Diagnosis and Troubleshooting Electronic insert FEC 12 (HART)
Simulation for level
Simulation for volume
Enter the level value to be simulated. The appropriate current is given by the electronic insert.
Step Entry Cursor in Display at
1 3 SERVICE/SIMULATION
2 6 SIM. LEVEL
3
4 F4 [ENTER] e.g. 77.06
e.g. 35.00
35.00
Significance
Service/Simulation
Simulation for level
Actual measured value is displayed
Level to be simulated is entered
Confirms entry, value to be transmitted
Enter the volume value to be simulated. The appropriate current is given by the electronic insert.
Step Entry Cursor in Display to
1 3 SERVICE/SIMULATION
2 7 SIM. VOLUME
3
4 F4 [ENTER] e.g. 77.06
e.g. 5.00
5.00
Significance
Service/Simulation
Simulation of volume
Actual measured value is displayed
Volume to be simulated is entered
Confirms entry, value to be transmitted
Simulation for current Enter directly the current value to be simulated.
Step Entry Cursor in Display at
1 3 SERVICE/SIMULATION
2 7 SIM. CURRENT
3
4 F4 [ENTER] e.g. 17.02
e.g. 8.00
8.00
Significance
Service/Simulation
Simulation of current output
Actual measured value is displayed
Current to be simulated is entered
Confirms entry, value to be transmitted
Note!
Note!
The values entered during simulation are stored until simulation is again switched off.
16 Endress+Hauser
Electronic insert FEC 12 (HART) 6 Diagnosis and Troubleshooting
6.3 Description of Fault Responses, Error Messages
Error code
103
106
116
204
613
615
616
617
618
620
Significance
Initialisation activated
Check sum error
This appears during the download, and remians if the download is not completed correctly. A new and successful download or reset deletes the error message.
Error in download format
Measuring capacitance too large (larger than 2000 pF)
Simulation switched on
The actual calibration at 4 mA produces an initial capacitance larger than 350 pF. It cannot be altered further.
A reset deletes the error message.
The actual calibration at 20 mA produces a total capacitance larger than 2000 pF. It cannot be altered further.
A reset deletes the error message.
The actual calibration produces a difference in capacitance (’span’) of less than
10 pF between initial and total capacitance. It cannot be altered further.
A reset deletes the error message.
Process-specific sensitivity too large
The current lies outside the permitted range (4.0 ... 20 mA or
3.8 ... 20 mA). It has no relationship to the measured value.
6.4 Replacing the FEC 12 Electronic Insert
Note!
If you want to transmit the settings of the old electronic insert into a new electronic insert, then please note the following section.
•
Disconnect the power supply cable from the old electronic insert
•
Loosen the central mounting screw
•
Remove the electronic insert
•
Plug in the new electronic insert
•
Screw down the central mounting screw securely
•
Connect the power cable to the electronic insert
Note!
Removal
Insertion
6.5 Transmitting Basic Settings
The recalibration procedure can be dispensed when replacing an electronic insert.
Call up the setting for offset and sensitivity using the handheld terminal, replace the electronic insert, and then enter both settings in the new electronic insert.
The offset value indicates zero point calibration and is given as the capacitance value
(initial capacitance). The value for sensitivity is the difference between the initial and total capacitance (’span’) divided by 100.
Calling up offset and sensitivity
Endress+Hauser 17
6 Diagnosis and Troubleshooting Electronic insert FEC 12 (HART)
Calling up offset and sensitivity (cont.) Step Entry
1 2
2 2
3 F3 [ESC]
4 3
5 F3 [ESC]
Cursor in Display to
EXTENDED CALIBRATION
OFFSET e.g. 63.43
OFFSET
SENSITIVITY e.g. 2.02
SENSITIVITY
Significance
Extended calibration
Offset of electronic insert
Record value for offset
Sensitivity of electronic insert
Record value for sensitivity
Entering offset and sensitivity
5
6
Step Entry Cursor in Display to
1 2 EXTEND. CALIBRATION
2
3
4 3
2
63.43
OFFSET
63.43
F4 [ENTER] OFFSET
SENSITIVITY
2.02
2.02
F4 [ENTER] SENSITIVITY
F2 [SEND]
Significance
Extended calibration
Offset
Enter recorded value for offset
Confirms entry
Sensitivity
Enter recorded value for sensitivity
Confirms entry
Value to be transmitted
All settings can be transmitted from one electronic insert to another. Please see following section.
6.6 Transmitting All Settings
All settings stored in an electronic insert can be transmitted to another electronic insert using the HART Communicator handheld terminal. The procedure begins with an upload with the data from the old FEC 12 to the handheld terminal. Once the upload has been completed, a download is is made and all data are transmitted from the handheld terminal to the new FEC 12.
Upload
(loading data into the handheld terminal)
0 MATRIX GROUP SEL.
1 Online
2 3 Transfer
Device to Memory
3 1
Looking for a device
Save data from device to configuration memory
4 F3 [SAVE] Overwrite existing
5 F1 [YES] configuration memory
Device to Memory
Higher menu level
Data transfer
Upload: Loading data into the memory of the handheld terminal
Looking for an electronic insert
Ready for receiving data
Prompts confirmation
Data of the electronic insert now in memory of handheld terminal
Data loaded into the
HART Communicator
1 Set Tag Number
2 Select Unit
3 Output Damping
4 Safety Alarm
5 Min Current 4 mA
6 Value for 4 mA
7 Value for 20 mA
8 Linearisation
9 Offset
10 Sensitivity
11 Temperature Unit
12 Descriptor
13 Message
14 Date
15 Poll addr
18 Endress+Hauser
Electronic insert FEC 12 (HART) 6 Diagnosis and Troubleshooting
You must first move to the "Offline Configure" menu before carrying out a download.
1
2
3
4
Step
0
Entry
1
2
1
1
Display
MATRIX GROUP SEL.
Online
Offline
Offline Configure
New Device or
Last Device
Significance
The data you wish to be transmit to another electronic insert can be collected in this menu.
1 New Device
→
2 Last Device
→
This option enables a new electronic insert to be calibrated.
This option enables variables to be edited and changed after an upload.
There are four function keys within this menu:
HELP (F1) -
SEND (F2) -
EDIT (F3) -
SKIP (F4) -
Online help. Help describes the variable shown in the display
Marks the variable in the display for the download and then marks the next variable.
The variable can be edited and is marked for download once
RETURN (F4) is pressed.
The variable is skipped (not marked for download). The next variable is then marked.
The "Offline" menu is displayed after the last variable. The parameters are now stored in the HART Communicator and are ready for a download into an electronic insert.
After marking has been carried out, downloads can be carried out without first marking the variables again.
Download
Download
(loading data into the electronic insert) 0 MATRIX GROUP SEL.
1 Online
2 3 Transfer
3 2
Device to Memory
Memory to Device
Looking for a device
Download data from configuration memory to device
4 F3 [SEND] Sending data to device
Main menu level
Data transfer
Download:
Loading data into electronic insert
Looking for a device
Ready for data transmission
Data now stored in electronic insert
Endress+Hauser 19
Europe
Austria
❑ Endress+Hauser Ges.m.b.H.
Wien
Tel. (01) 8 80 56-0, Fax (01) 8 80 56-35
Belarus
Belorgsintez
Minsk
Tel. (01 72) 508473, Fax (01 72) 508583
Belgium / Luxemburg
❑ Endress+Hauser N.V.
Brussels
Tel. (02) 2 48 06 00, Fax (02) 2 48 05 53
Bulgaria
INTERTECH-AUTOMATION
Sofia
Tel. (02) 66 48 69, Fax (02) 9 63 13 89
Croatia
❑ Endress+Hauser GmbH+Co.
Zagreb
Tel. (01) 6 63 77 85, Fax (01) 6 63 78 23
Cyprus
I+G Electrical Services Co. Ltd.
Nicosia
Tel. (02) 48 47 88, Fax (02) 48 46 90
Czech Republic
❑ Endress+Hauser GmbH+Co.
Praha
Tel. (0 26) 6 78 42 00, Fax (0 26) 6 78 41 79
Denmark
❑ Endress+Hauser A/S
Søborg
Tel. (70) 13 11 32, Fax (70) 13 21 33
Estonia
ELVI-Aqua
Tartu
Tel. (7) 44 16 38, Fax (7) 44 15 82
Finland
❑ Endress+Hauser Oy
Espoo
Tel. (09) 8 67 67 40, Fax (09) 86 76 74 40
France
❑ Endress+Hauser S.A.
Huningue
Tel. (3 89) 69 67 68, Fax (3 89) 69 48 02
Germany
❑ Endress+Hauser Messtechnik GmbH+Co.
Weil am Rhein
Tel. (0 76 21) 9 75-01, Fax (0 76 21) 9 75-5 55
Great Britain
❑ Endress+Hauser Ltd.
Manchester
Tel. (01 61) 2 86 50 00, Fax (01 61) 9 98 18 41
Greece
I & G Building Services Automation S.A.
Athens
Tel. (01) 9 24 15 00, Fax (01) 9 22 17 14
Hungary
Mile Ipari-Elektro
Budapest
Tel. (01) 2 61 55 35, Fax (01) 2 61 55 35
Iceland
BIL ehf
Reykjavik
Tel. (05) 61 96 16, Fax (05) 61 96 17
Ireland
Flomeaco Company Ltd.
Kildare
Tel. (0 45) 86 86 15, Fax (0 45) 86 81 82
Italy
❑ Endress+Hauser S.p.A.
Cernusco s/N Milano
Tel. (02) 92192-1, Fax (02) 92192-362
Latvia
Rino TK
Riga
Tel. (07) 31 5087, Fax (07) 31 5084
Lithuania
UAB "Agava"
Kaunas
Tel. (07) 20 24 10, Fax (07) 20 74 14
Netherlands
❑ Endress+Hauser B.V.
Naarden
Tel. (0 35) 6 95 86 11, Fax (0 35) 6 95 88 25
Norway
❑ Endress+Hauser A/S
Tranby
Tel. (0 32) 85 98 50, Fax (0 32) 85 98 51
Poland
Endress+Hauser Polska Sp. z o.o.
Warszawy
Tel. (0 22) 7 20 10 90, Fax (0 22) 7 20 10 85
Portugal
Tecnisis - Tecnica de Sistemas Industriais
Linda-a-Velha
Tel. (21) 4267290, Fax (21) 4267299
Romania
Romconseng S.R.L.
Bucharest
Tel. (01) 4 10 16 34, Fax (01) 4 11 2 5 0 1
Russia
Endress+Hauser Moscow Office
Moscow
Tel. (0 95) 1 58 75 64, Fax (0 95) 1 58 98 71
Slovakia
Transcom Technik s.r.o.
Bratislava
Tel. (7) 44 88 86 84, Fax (7) 44 88 71 12
Slovenia
Endress+Hauser D.O.O.
Ljubljana
Tel. (01) 519 22 17, Fax (01) 519 22 98
Spain
❑ Endress+Hauser S.A.
Sant Just Desvern
Tel. (93) 4 80 33 66, Fax (93) 4 73 38 39
Sweden
❑ Endress+Hauser AB
Sollentuna
Tel. (08) 55 51 16 00, Fax (08) 55 51 16 55
Switzerland
❑ Endress+Hauser AG
Reinach/BL 1
Tel. (0 61) 7 15 75 75, Fax (0 61) 7 11 16 50
Turkey
Intek Endüstriyel Ölcü ve Kontrol Sistemleri
Istanbul
Tel. (02 12) 2 75 13 55, Fax (02 12) 2 66 27 75
Ukraine
Photonika GmbH
Kiev
Tel. (44) 2 68 81, Fax (44) 2 69 08
Yugoslavia Rep.
Meris d.o.o.
Beograd
Tel. (11) 4 44 19 66, Fax (11) 4 44 19 66
Africa
Egypt
Anasia
Heliopolis/Cairo
Tel. (02) 4 17 90 07, Fax (02) 4 17 90 08
Morocco
Oussama S.A.
Casablanca
Tel. (02) 24 13 38, Fax (02) 40 26 57
South Africa
❑ Endress+Hauser Pty. Ltd.
Sandton
Tel. (011) 2 62 80 00 Fax (011) 2 62 80 62
Tunisia
Controle, Maintenance et Regulation
Tunis
Tel. (01) 79 30 77, Fax (01) 78 85 95
America
Argentina
❑ Endress+Hauser Argentina S.A.
Buenos Aires
Tel. (01) 1 45 22 79 70, Fax (01) 1 45 22 79 09
Bolivia
Tritec S.R.L.
Cochabamba
Tel. (0 42) 5 69 93, Fax (0 42) 5 09 81
Brazil
❑ Samson Endress+Hauser Ltda.
Sao Paulo
Tel. (0 11) 50 31 34 55, Fax (0 11) 50 31 30 67
Canada
❑ Endress+Hauser Ltd.
Burlington, Ontario
Tel. (9 05) 6 81 92 92, Fax (9 05) 6 81 94 44
Chile
❑ Endress+Hauser Chile Ltd.
Santiago
Tel. (02) 321-3009, Fax (02) 321-3025
Colombia
Colsein Ltda.
Bogota D.C.
Tel. (01) 2 36 76 59, Fax (01) 6 10 41 86
Costa Rica
EURO-TEC S.A.
San Jose
Tel. (02) 96 15 42, Fax (02) 96 15 42
Ecuador
Insetec Cia. Ltda.
Quito
Tel. (02) 26 91 48, Fax (02) 46 18 33
Guatemala
ACISA Automatizacion Y Control Industrial S.A.
Ciudad de Guatemala, C.A.
Tel. (03) 34 59 85, Fax (03) 32 74 31
Mexico
❑ Endress+Hauser S.A. de C.V.
Mexico City
Tel. (5) 5 68 24 05, Fax (5) 5 68 74 59
Paraguay
Incoel S.R.L.
Asuncion
Tel. (0 21) 21 39 89, Fax (0 21) 22 65 83
Uruguay
Circular S.A.
Montevideo
Tel. (02) 92 57 85, Fax (02) 92 91 51
USA
❑ Endress+Hauser Inc.
Greenwood, Indiana
Tel. (3 17) 5 35-71 38, Fax (3 17) 5 35-84 98
Venezuela
Controval C.A.
Caracas
Tel. (02) 9 44 09 66, Fax (02) 9 44 45 54
Asia
China
❑ Endress+Hauser Shanghai
Instrumentation Co. Ltd.
Shanghai
Tel. (0 21) 54 90 23 00, Fax (0 21) 54 90 23 03
❑ Endress+Hauser Beijing Office
Beijing
Tel. (0 10) 68 34 40 58, Fax (0 10) 68 34 40 68
Hong Kong
❑ Endress+Hauser HK Ltd.
Hong Kong
Tel. 25 28 31 20, Fax 28 65 41 71
India
❑ Endress+Hauser (India) Pvt. Ltd.
Mumbai
Tel. (0 22) 8 52 14 58, Fax (0 22) 8 52 19 27
Indonesia
PT Grama Bazita
Jakarta
Tel. (21) 7 97 50 83, Fax (21) 7 97 50 89
Japan
❑ Sakura Endress Co. Ltd.
Tokyo
Tel. (04 22) 54 06 13, Fax (04 22) 55 02 75
Malaysia
❑ Endress+Hauser (M) Sdn. Bhd.
Petaling Jaya, Selangor Darul Ehsan
Tel. (03) 7 33 48 48, Fax (03) 7 33 88 00
Pakistan
Speedy Automation
Karachi
Tel. (0 21) 7 72 29 53, Fax (0 21) 7 73 68 84
Philippines
❑ Endress+Hauser Philippines Inc.
= Metro Manila
Tel. (2) 3 72 36 01-05, Fax (2) 4 12 19 44
Singapore
❑ Endress+Hauser (S.E.A.) Pte., Ltd.
Singapore
Tel. 5 66 82 22, Fax 5 66 68 48
South Korea
❑ Endress+Hauser (Korea) Co., Ltd.
Seoul
Tel. (02) 6 58 72 00, Fax (02) 6 59 28 38
Taiwan
Kingjarl Corporation
Taipei R.O.C.
Tel. (02) 27 18 39 38, Fax (02) 27 13 41 90
Thailand
❑ Endress+Hauser Ltd.
Bangkok
Tel. (2) 9 96 78 11-20, Fax (2) 9 96 78 10
Vietnam
Tan Viet Bao Co. Ltd.
Ho Chi Minh City
Tel. (08) 8 33 52 25, Fax (08) 8 33 52 27
Iran
PATSA Co.
Tehran
Tel. (0 21) 8 75 47 48, Fax(0 21) 8 74 77 61
Israel
Instrumetrics Industrial Control Ltd.
Netanya
Tel. (09) 8 35 70 90, Fax (09) 8 35 0619
Jordan
A.P. Parpas Engineering S.A.
Amman
Tel. (06) 4 64 32 46, Fax (06) 4 64 57 07
Kingdom of Saudi Arabia
Anasia Ind. Agencies
Jeddah
Tel. (02) 6 71 00 14, Fax (02) 6 72 59 29
Lebanon
Network Engineering
Jbeil
Tel. (3) 94 40 80, Fax (9) 54 80 38
Sultanate of Oman
Mustafa & Jawad Sience & Industry Co.
L.L.C.
Ruwi
Tel. 60 20 09, Fax 60 70 66
United Arab Emirates
Descon Trading EST.
Dubai
Tel. (04) 2 65 36 51, Fax (04) 2 65 32 64
Yemen
Yemen Company for Ghee and Soap Industry
Taiz
Tel. (04) 23 06 64, Fax (04) 21 23 38
Australia + New Zealand
Australia
ALSTOM Australia Limited
Milperra
Tel. (02) 97 74 74 44, Fax (02) 97 74 46 67
New Zealand
EMC Industrial Group Limited
Auckland
Tel. (09) 4 15 51 10, Fax (09) 4 15 51 15
All other countries
❑ Endress+Hauser GmbH+Co.
Instruments International
Weil am Rhein
Germany
Tel. (0 76 21) 9 75-02, Fax (0 76 21) 97 5-3 45 http://www.endress.com
Endress
+
Hauser
The Power of Know How
❑ Members of the Endress+Hauser group 12.97/MTM
BA 148F/00/en/07.95 (b)
016700-1000
CCS/CV4.2
016700- 1000
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 General description
- 3 Important safety measures
- 4 Transport and handling
- 5 Installation
- 6 Electrical connection
- 6 Start-up
- 7 Hydrological data
- 9 Maintenance
- 10 Shutting down / disposing the cooling system
- 11 General fault analysis
- 11 Evaporator pressure
- 11 Compressor is continuously being switched on and off
- 12 No medium circulation
- 13 Appendix
- 13 Technical data
- 13 P+ID Schematics
- 13 Wiring plan
- 13 Description controller
- 13 List of parameters
- 13 List of spare parts
- 33 Contents
- 37 1 Mounting 5
- 38 2 Electrical connections 6
- 38 2.1 Connecting diagram 6
- 38 2.2 Terminal connection 6
- 42 3 Operation 10
- 42 3.1 Front view 10
- 43 3.2 Behaviour after power-on 11
- 43 3.3 Operating level 11
- 44 3.4 Maintenance manager / Error list 12
- 46 3.5 Self-tuning 14
- 46 3.5.1 Preparation for self-tuning 14
- 46 3.5.2 Self-tuning sequence 14
- 47 3.5.3 Self-tuning start 15
- 47 3.5.4 Self-tuning cancellation 15
- 48 3.5.5 Acknowledgement procedures in case of unsuccessful self-tuning 16
- 48 3.5.6 Examples for self-tuning attempts 16
- 49 3.6 Manual tuning 17
- 50 3.7 Alarm handling 18
- 52 3.8 Operating structure 20
- 53 4 Configuration level 21
- 53 4.1 Configuration survey 21
- 54 4.2 Configuration 22
- 61 4.3 Set-point processing 29
- 62 4.4 Configuration examples 30
- 62 4.4.1 On-Off controller / Signaller (inverse) 30
- 63 4.4.2 2-point controller (inverse) 31
- 64 4.4.3 3-point controller (relay & relay) 32
- 65 4.4.4 3-point stepping controller (relay & relay) 33
- 66 4.4.5 Continuous controller (inverse) 34
- 67 4.4.6 D - Y - Off controller / 2-point controller with pre-contact 35
- 68 4.4.7 KS4x-1 with measured value output 36
- 69 5 Parameter setting level 37
- 69 5.1 Parameter survey 37
- 69 5.2 37
- 69 5.3 37
- 70 5.4 Parameters 38
- 72 5.5 Input scaling 40
- 72 5.5.1 Input Inp.1 40
- 72 5.5.2 Input InP.2 40
- 73 6 Calibration level 41
- 76 7 Programmer 44
- 78 8 Timer 46
- 78 8.1 Setting up the timer 46
- 78 8.1.1 Operating modes 46
- 79 8.1.2 Tolerance band 47
- 79 8.1.3 Timer start 47
- 80 8.1.4 Signal end 48
- 80 8.2 Determining the timer run-time 48
- 80 8.3 Starting the timer 48
- 81 9 BlueControl 49
- 82 10 Versions 50
- 83 11 Technical data 51
- 87 12 Safety hints 55
- 88 12.1 Resetting to factory setting 56
- 33 Index
- 33 0-9
- 73 2-point correction 41
- 33 A
- 50 Alarm handling 18 - 19
- 33 B
- 81 BlueControl 49
- 33 Bus interface
- 84 Technical Data 52
- 33 C
- 73 Calibration level (CAL) 41 - 43
- 85 Certifications 53
- 33 Configuration examples
- 63 2-point controller 31
- 64 3-point controller 32
- 65 3-point stepping controller 33
- 66 Continuous controller 34
- 67 D - Y -Off controller 35
- 68 Measured value output 36
- 62 Signaller 30
- 33 Configuration level
- 54 Configuration parameters 22 - 28
- 53 Parameter survey 21
- 38 Connecting diagram 6
- 33 Connecting examples
- 40 di2/3, 2-wire transmitter supply 8
- 39 INP2 current transformer 7
- 39 OUT1/2 heating/cooling 7
- 40 OUT3 as logic output 8
- 40 OUT3 transmitter supply 8
- 41 RS485 interface 9
- 33 Control inputs di1, di2, di3
- 83 Technical data 51
- 83 Current signal measuring range 51
- 33 D
- 33 Digital inputs di1, di2, di3
- 58 Configuration 26
- 83 Technical data 51
- 33 E
- 85 Environmental conditions 53
- 82 Equipment 50
- 44 Error list 12
- 33 F
- 42 Front view 10
- 33 I
- 33 Input INP1
- 55 Configuration 23
- 71 Parameters 39
- 83 Technical data 51
- 33 Input INP2
- 55 Configuration 23
- 71 Parameters 39
- 83 Technical data 51
- 72 Input scaling 40
- 33 K
- 73 Kalibrierung (CAL) 41
- 33 L
- 33 LED
- 42 Ada - LED 10
- 42 Err - LED 10
- 42 ì - LED 10
- 42 LED colours 10
- 42 ò - LED 10
- 42 run - LED 10
- 42 SP.x - LED 10
- 33 M
- 44 Maintenance manager 12 - 13
- 49 Manual tuning 17
- 37 Mounting 5
- 33 O
- 73 Offset correction 41
- 33 Output OUT1
- 56 Configuration 24
- 84 Technical data 52
- 33 Output OUT2
- 57 Configuration 25
- 84 Technical data 52
- 33 Output OUT3
- 57 Configuration 25
- 84 Technical data 52
- 33 P
- 33 Parameter setting level
- 69 Parameter survey 37
- 70 Parameters 38 - 39
- 84 Power supply 52
- 33 Programmer
- 77 Changing segment end setpoint 45
- 77 Changing segment time 45
- 76 Parameter setting 44
- 76 Set-up 44
- 76 Starting/Stopping 44
- 33 R
- 88 Resetting to factory setting 56
- 83 Resistance thermometer measuring range 51
- 33 S
- 87 Safety hints 55 - 56
- 37 Safety switch 5
- 85 Safety test 53
- 33 Self-tuning
- 47 Cancelation 15
- 48 Cancelation causes 16
- 47 Start 15
- 61 Set-point processing 29
- 33 T
- 83 Thermocouple measuring range 51
- 33 Timer
- 80 Display run-LED 48
- 78 Operating modes 46
- 80 Signal end 48
- 79 Timer start 47
- 79 Tolerance band 47
- 33 V
- 82 Versions 50
- 83 Voltage signal measuring range 51