Installation Instructions 50VR---A Performance System with Puron


Add to my manuals
36 Pages

advertisement

Installation Instructions 50VR---A Performance System with Puron | Manualzz

50VR---A

Performancet 15 SEER 2---Stage Packaged Heat Pump

System with Puron(R---410A) Refrigerant

Single and Three Phase

2---5 Nominal Tons (Sizes 24---60)

Installation Instructions

NOTE: Read the entire instruction manual before starting the installation.

NOTE: Installer: Make sure the Owner’s Manual and Service

Instructions are left with the unit after installation.

TABLE OF CONTENTS

SAFETY CONSIDERATIONS

INTRODUCTION

RECEIVING AND INSTALLATION

Check Equipment

Identify Unit

Inspect Shipment

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Unit Support

. . . . . . . . . . . . . . . . .

PAGE

. . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2--10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Roof Curb

Slab Mount

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Field Fabricate Ductwork

Rig and Place Unit

Inspection

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rigging/Lifting of Unit

Connect Condensate Drain

Install Duct Connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Configuring Units for Downflow (Vertical) Discharge

1

2

Install Electrical Connections

High--Voltage Connections

. . . .

. . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . .

Special Procedures for 208v Operation

Control Voltage Connections

Standard Connection

. . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Transformer Protection . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

10

9

9

11

11--13

9

9

7

8

7

7

6

7

6

6

2

2

2

2

2

2

PRE--START--UP

START--UP

Check Cooling and Heating Control Operation

Check for Refrigerant Leaks

Start--Up Adjustments

. . . . . . . . . . . . . . . . . . . . . . . . .

Checking and Adjusting Refrigerant Charge

Indoor Airflow and Airflow Adjustments

Low Stage Cooling

Models)

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . .

. . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Continuous Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . .

13

13

13

11

11

12

12

12

13

High Stage Cooling 13

High Stage Enhanced Dehumidification Cooling (208/230 Vac

Defrost Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13

Quiet Shift

Defrost

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MAINTENANCE

Air Filter

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Blower and Motor

Refrigerant Circuit

. . . . . . . . . . . . . . . . . . . . . . . . .

Outdoor Coil, Indoor Coil, and Condensate Drain Pan

Outdoor Fan

. . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Controls and Wiring . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13

13

29--32

29

29

30

30

30

31

1

A09033

Fig. 1 -- Unit 50VR--A

Evaporator Airflow

Metering Device

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

31

31

System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

32

Loss of Charge Switch

TROUBLESHOOTING

START--UP CHECKLIST

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check Defrost Thermostat . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Improper installation adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations.

Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes, the current editions of the National Electrical Code (NEC) NFPA 70.

In Canada refer to the current editions of the Canadian electrical

Code CSA C22.1.

32

32

32

32

Recognize safety information. This is the safety--alert symbol .

When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which

will result in enhanced installation, reliability, or operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable.

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD

Failure to relieve system pressure could result in personal injury and/or death.

1. Relieve pressure and recover all refrigerant before servicing existing equipment, and before final unit disposal.

Use all service ports and open all flow--control devices, including solenoid valves.

2. Federal regulations require that you do not vent refrigerant into the atmosphere. Recover during system repair or final unit disposal.

!

CAUTION

CUT HAZARD

Failure to follow this caution may result in personal injury.

When removing access panels (see Fig. 17) or performing maintenance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care is taken to reduce sharp edges to a minimum, be extremely careful and wear appropriate protective clothing, safety glasses and gloves when handling parts or reaching into the unit.

INTRODUCTION

The 50VR--A packaged heat pump is fully self--contained and designed for outdoor installation (See Fig.1 ). See Fig. 2 and 3 for unit dimensions. All unit sizes have discharge openings for both horizontal and downflow configurations, and are factory shipped with all downflow duct openings covered. The unit may be installed either on a rooftop or on a ground--level cement slab. (See

Fig. 4 for roof curb dimensions.)

RECEIVING AND INSTALLATION

Step 1 — Check Equipment

IDENTIFY UNIT

The unit model number and serial number are printed on the unit informative plate. Check this information against shipping papers.

INSPECT SHIPMENT

Inspect for shipping damage before removing packaging materials.

If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal.

Forward claim papers directly to transportation company.

Manufacturer is not responsible for any damage incurred in transit.

Check all items against shipping list. Immediately notify the nearest equipment distribution office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.

If the unit is to be mounted on a curb in a downflow application, review Step 7 to determine which method is to be used to remove the downflow panels before rigging and lifting into place. The panel removal process may require the unit to be on the ground.

Step 2 — Provide Unit Support

IMPORTANT: The unit must be secured to the curb by installing screws through the bottom of the curb flange and into the unit base rails. When installing large base units onto the common curb, the screws must be installed before allowing the full weight of the unit to rest on the curb. A minimum of six screws are required for large base units. Failure to secure unit properly could result in an unstable unit. See Warning near Rigging/Lifting information and accessory curb instructions for more details.

For hurricane tie downs, contact distributor for details and PE

(Professional Engineering) Certificate if required.

ROOF CURB

Install accessory roof curb in accordance with instructions shipped with curb (See Fig. 4). Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb.

IMPORTANT: The gasketing of the unit to the roof curb is critical for a water tight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing also can result in air leaks and poor unit performance.

Curb should be level to within 1/4 in. (6.35 mm) (See Fig 6). This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.

Installation on older “G” series roof curbs.

Two accessory kits are available to aid in installing a new “G” series unit on an old “G” roof curb.

1. Accessory kit number CPADCURB001A00, (small chassis) and accessory kit number CPADCURB002A00, (large chassis) includes roof curb adapter and gaskets for the perimeter seal and duct openings. No additional modifications to the curb are required when using this kit.

2. An alternative to the adapter curb is to modify the existing curb by removing the outer horizontal flange and use accessory kit number CPGSKTKIT001A00 which includes spacer blocks (for easy alignment to existing curb) and gaskets for the perimeter seal and duct openings. This kit is used when existing curb is modified by removing outer horizontal flange.

!

CAUTION

UNIT/STRUCTURAL DAMAGE HAZARD

Failure to follow this caution may result in property damage.

Ensure there is sufficient clearance for saw blade when cutting the outer horizontal flange of the roof curb so there is no damage to the roof or flashing.

SLAB MOUNT

Place the unit on a solid, level pad that is at least 2 in. (51 mm) above grade. The pad should extend approximately 2 in. (51 mm) beyond the casing on all 4 sides of the unit (See Fig. 7). Do not secure the unit to the pad except when required by local codes.

2

Fig. 2 -- 50VR--A24--30 Unit Dimensions

3

A13172

Fig. 3 -- 50VR--A36--60 Unit Dimensions

4

A13173

G C

HVAC unit base rails

Anchor screw

Flashing field supplied

Roofing material field supplied

Cant strip field supplied

HVAC unit basepan

Sealing

Gasket

Roofcurb

Wood nailer*

Roofcurb*

Insulation

(field supplied)

G

*Provided with roofcurb

ROOF CURB DETAIL

B

A09090

C

A

F

SUPPLY

AIR

H

D

SMALL/COMMON CURB

B

Dashed lines show cross support location for large basepan units.

SMALL

BASE

UNIT

E

A09413

F A

H

RETURN

AIR

LARGE

BASE

UNIT

E

D

LARGE CURB

A09415

UNIT PLACEMENT ON

COMMON CURB

SMALL OR LARGE BASE UNIT

A09094

A09414

UNIT

SIZE

CATALOG

NUMBER

A

IN.

(mm)

B

(small/common base)

IN. (mm)*

B

(large base)

IN. (mm)*

C

IN.

(mm)

D

IN.

(mm)

E

IN.

(mm)

F

IN.

(mm)

G

IN. (mm)

H

IN. (mm)

Small or

Large

Large

CPRFCURB010A00

CPRFCURB011A00

CPRFCURB012A00

CPRFCURB013A00

11

(279)

14

(356)

11

(279)

14

(356)

10 (254)

14 (356)

14 (356)

16

(406)

47.8

(1214)

32.4

(822)

43.9

(1116)

2.7

(69)

30.6 (778)

42.2 (1072)

46.1 (1170)

* Part Numbers CPRCURB010A00 and CPRCURB011A00 can be used on both small and large basepan units. The cross supports must be located based on whether the unit is a small basepan or a large basepan.

NOTES:

1. Roof curb must be set up for unit being installed.

2. Seal strip must be applied, as required, to unit being installed.

3. Roof curb is made of 16--gauge steel.

4. Attach ductwork to curb (flanges of duct rest on curb).

5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.

Fig. 4 -- Roof Curb Dimensions

5

CAUTION - NOTICE TO RIGGERS

PRUDENCE - AVIS AUX MANIPULATEUR

ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.

PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.

Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition

DUCTS

MINIMUM HEIGHT: 36" (914.4 mm)

HAUTEUR MINIMUM

UNIT HEIGHT

HAUTEUR D'UNITÉ

SEAL STRIP MUST BE IN

PLACE BEFORE PLACING

UNIT ON ROOF CURB

BANDE SCELLANT DOIT ÊTRE

EN PLACE AVANT DE PLACER

L'UNITÉ SUR LA BASE DE TOIT

DETAIL A

VOIR DÉTAIL A

SEE DETAIL A

VOIR DÉTAIL A

50CY502286 2.0

A09051

Unit*

SMALL CABINET

24 lb kg lb

30 kg

Rigging

Weight

356 162 364 165

NOTE: See dimensional drawing for corner weighs.

Standard Copper Tube Aluminum Fin

Unit*

Rigging

Weight

lb

420

36 kg

191

LARGE CABINET

42 lb kg

466 212

lb

462

48 kg

210

lb

511

60 kg

232

Optional Copper Tube Copper Fin

Unit*

SMALL CABINET

24 lb kg lb

30 kg

Rigging

Weight

414 188 426 193

NOTE: See dimensional drawing for corner weighs.

Unit*

Rigging

Weight

lb

482

36 kg

219

LARGE CABINET

42 lb kg

550 250

lb

540

48 kg

245

lb

616

60 kg

280

Step 3 — Provide Clearances

The required minimum service clearances are shown in Fig. 2 and

3. Adequate ventilation and outdoor air must be provided. The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. (1219 mm) above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in. (1219 mm)

IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor--air inlet or the fan discharge may be detrimental to compressor life.

Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab--mounted units should be at least 2 in. (51 mm) above the highest expected water and runoff levels. Do not use unit if it has been under water.

Step 4 — Field--Fabricate Ductwork

Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, unit is provided with flanges on the horizontal openings. All ductwork should be secured to the flanges. Insulate

Fig. 5 -- 50VR--A Unit Suggested Rigging

and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes. See unit rating plate for any required clearances around ductwork. Cabinet return--air static shall not exceed --.25 IN. W.C.

Step 5 — Rig and Place Unit

Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.).

Only trained, qualified crane operators and ground support staff should handle and install this equipment.

When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply.

Training for operators of the lifting equipment should include, but not be limited to, the following:

1. Application of the lifter to the load, and adjustment of the lifts to adapt to various sizes or kinds of loads.

2. Instruction in any special operation or precaution.

6

3. Condition of the load as it relates to operation of the lifting kit, such as balance, temperature, etc.

Follow all applicable safety codes. Wear safety shoes and work gloves.

OPTIONAL

RETURN

AIR

OPENING

OPTIONAL

SUPPLY

AIR

OPENING

A

C

B

A-B

MAXIMUM ALLOWABLE

DIFFERENCE in. (mm)

B-C

A-C

1/4

(6.35)

1/4

(6.35)

1/4

(6.35)

A07925

Fig. 6 -- Unit Leveling Tolerances

INSPECTION

Prior to initial use, and at monthly intervals, all rigging shackles, clevis pins, and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Materials showing any kind of wear in these areas must not be used and should be discarded.

!

WARNING

UNIT FALLING HAZARD

Failure to follow this warning could result in personal injury or death.

Never stand beneath rigged units or lift over people.

1. Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damaging the unit. If the skid is not available, use a spreader bar of sufficient length to protect the unit from damage.

!

WARNING

PROPERTY DAMAGE HAZARD

Failure to follow this warning could result in personal injury.

When straps are taut, the clevis should be a minimum of 36 in. (914 mm) above the unit top cover.

Rigging/Lifting of Unit (See Fig. 5)

!

WARNING

UNIT FALLING HAZARD

Failure to follow this warning could result in personal injury or death.

Large base units must be secured to common curb before allowing full weight of unit to rest on curb. Install screws through curb into unit base rails while rigging crane is still supporting unit.

Lifting holes are provided in base rails as shown.

1. Attach shackles, clevis pins, and straps to the base rails of the unit. Be sure materials are rated to hold the weight of the unit (See Fig. 5).

2. Attach a clevis of sufficient strength in the middle of the straps. Adjust the clevis location to ensure unit is lifted level with the ground.

After the unit is placed on the roof curb or mounting pad, remove the top skid.

(50.8mm)

EVAP. COIL COND. COIL

A07926

Fig. 7 -- Slab Mounting Detail

Step 6 — Connect Condensate Drain

NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.

Model 50VR--A disposes of condensate water through a 3/4 in.

NPT fitting which exits through the base on the evaporator coil access side. See Fig. 2 and 3 for location.

Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field--supplied 2--in. (51 mm) condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. (25 mm) lower than the drain pan condensate connection to prevent the pan from overflowing (See Fig. 8). When using a gravel apron, make sure it slopes away from the unit.

Connect a drain tube using a minimum of 3/4 --in. PVC or 3/4 --in.

copper pipe (all field--supplied) at the outlet end of the 2--in. (51 mm) trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1--in. (25 mm) for every 10 ft (3.1

m) of horizontal run. Be sure to check the drain tube for leaks.

Prime trap at the beginning of the cooling season start--up.

TRAP

OUTLET

1-in. (25 mm) min.

2-in. (51 mm) min.

A09052

Fig. 8 -- Condensate Trap

Step 7 — Install Duct Connections

The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of non--residence type air conditioning and ventilating systems,

NFPA 90A or residence type, NFPA 90B and/or local codes and ordinances.

Select and size ductwork, supply--air registers, and return air grilles according to ASHRAE (American Society of Heating,

Refrigeration, and Air Conditioning Engineers) recommendations.

The unit has duct flanges on the supply-- and return--air openings on the side of the unit.

When designing and installing ductwork, consider the following:

1. All units should have field--supplied filters or accessory filter rack installed in the return--air side of the unit.

Recommended sizes for filters are shown in Table 1.

2. Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.

IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to

7

ensure weather--tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24--in.

(610 mm) from electric heater element.

3. Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in

Table 2. Heater limit switches may trip at air quantities below those recommended.

4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and

Air Conditioning Contractors National Association

(SMACNA) and Air Conditioning Contractors Association

(ACCA) minimum installation standards for residential heating and air conditioning systems.

5. Secure all ducts to building structure. Flash, weatherproof, and vibration--isolate duct openings in wall or roof according to good construction practices.

CONFIGURING UNITS FOR DOWNFLOW

(VERTICAL) DISCHARGE

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before performing service or maintenance operations on the system, turn off main power to unit and install lockout tag.

There may be more than one disconnect switch.

1. Open all electrical disconnects and install lockout tag before starting any service work.

2. Remove horizontal (metal) ductcovers to access vertical

(downflow) discharge duct knockouts in unit basepan. (See

Fig. 9.)

To remove downflow return and supply knockout covers, break front and right side connecting tabs with a screwdriver and hammer. Push cover down to break rear and left side tabs.

NOTE: These panels are held in place with tabs similar to an electrical knockout. Reinstall horizontal duct covers (Fig. 9) shipped on unit from factory. Insure openings are air and watertight.

NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence--type air conditioning and ventilating systems, NFPA

90A or residence--type, NFPA 90B; and/or local codes and ordinances.

Adhere to the following criteria when selecting, sizing, and installing the duct system:

1. Units are shipped for side shot installation.

2. Select and size ductwork, supply--air registers, and return--air grilles according to American Society of Heating,

Refrigeration and Air Conditioning Engineers (ASHRAE) recommendations.

3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure weather--tight and airtight seal.

4. All units must have field--supplied filters or accessory filter rack installed in the return--air side of the unit.

Recommended sizes for filters are shown in Table 1.

5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt

Basepan

Downflow

(Vertical)

Supply

Knockout duct size increases or decreases or performance may be affected.

6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National

Association (SMACNA) and Air Conditioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.

7. Flash, weatherproof, and vibration--isolate all openings in building structure in accordance with local codes and good building practices.

Horizontal Duct Covers

A09076

Basepan

Downflow

(Vertical)

Return

Knockout

Fig. 9 -- Supply and Return Duct Opening

A09093

8

Step 8 — Install Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NFPA

70 (NEC) (latest edition) (in Canada, Canadian Electrical

Code CSA C22.1) and local electrical codes.

!

CAUTION

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to the unit being installed.

1. Make all electrical connections in accordance with

NFPA 70 (NEC) (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard

C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.

2. Use only copper conductor for connections between field--supplied electrical disconnect switch and unit. DO

NOT USE ALUMINUM WIRE.

3. Be sure that high--voltage power to unit is within operating voltage range indicated on unit rating plate. On

3--phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.

4. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.

HIGH--VOLTAGE CONNECTIONS

The unit must have a separate electrical service with a field--supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.

The field--supplied disconnect may be mounted on the unit over the high--voltage inlet hole when the standard power and low--voltage entry points are used. See Fig. 2 and 3 for acceptable location.

See unit wiring label (Fig. 15, 16 and 17) and Fig. 10 for reference when making high voltage connections. Proceed as follows to complete the high--voltage connections to the unit.

Single phase units:

1. Run the high--voltage (L1, L2) and ground lead into the control box.

2. Connect ground lead to chassis ground connection.

3. Locate the black and yellow wires connected to the line side of the contactor.

4. Connect field L1 to black wire from connection 11 of the compressor contactor.

HIGH VOLTAGE

POWER LEADS

(SEE UNIT WIRING

LABEL)

3-PHASE SHOWN

1-PHASE USES

TWO POWER

LEADS

EQUIP GR

CONTROL BOX

LOW-VOLTAGE

POWER LEADS

(SEE UNIT

WIRING LABEL)

POWER

SUPPLY

FIELD-SUPPLIED

FUSED DISCONNECT

WHT(W2)

VIO (W3)

YEL(Y1)

GRN(G)

RED(R)

BRN(C)

ORN(O)

BLU (DH)

PINK (Y2)

C

O

DH

W2

W3

Y1

G

R

Y2

THERMOSTAT

(TYPICAL)

DH WIRE IS ON

208/230 VAC MODELS

ONLY.

SPLICE BOX

Fig. 10 -- High-- and Control--Voltage Connections

A13176

5. Connect field wire L2 to yellow wire from connection 23 of the compressor contactor.

Three--phase units:

1. Run the high--voltage (L1, L2, L3) and ground lead into the control box.

2. Connect ground lead to chassis ground connection.

3. Locate the black and yellow wires connected to the line side of the contactor.

4. Connect field L1 to black wire from connection 11 of the compressor contactor.

5. Connect field wire L3 to yellow wire from connection 13 of the compressor contactor.

6. Connect field wire L2 to blue wire from compressor.

SPECIAL PROCEDURES FOR 208--V OPERATION

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing or servicing system, always turn off main power to system and install lockout tag. With disconnect switch open, move black wire from transformer (3/16 in.)(4.8 mm) terminal marked 230 to terminal marked 208.

This retaps transformer to primary voltage of 208 vac.

CONTROL VOLTAGE CONNECTIONS

NOTE: Do not use any type of power--stealing thermostat. Unit control problems may result.

Use no. 18 American Wire Gage (AWG) color--coded, insulated

(35C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft (30.5 m) from the unit (as measured along the control voltage wires), use no. 16 AWG color--coded, insulated

(35 C minimum) wires.

STANDARD CONNECTION

Locate the nine low voltage thermostat leads (eight for 460 VAC models) in 24 volt splice box. See Fig. 10 for connection diagram.

Run the low--voltage leads from the thermostat, through the control wiring inlet hole grommet (Fig. 2 and 3), and into the low--voltage splice box. Provide a drip loop before running wires through panel.

Secure and strain relief all wires so that they do not interfere with operation of unit.

9

If an accessory electric heater is installed, low voltage leads from heater must be connected to factory supplied control leads from

Indoor Fan Board P4 connector.

NOTE: If the unit 24V wires do not have a matching receptacle, cut the 24V wires from the electric heater plug, strip the ends, and wire nut together to match the schematic connections. If the electric heater 24V wires do not have a matching plug, cut the 24V wires from the unit receptacle, strip the ends, and wire nut together to match the schematic connections.

Factory wires are provided for electric heat staging W1 and W2

(W2 and W3 on IFB). If room thermostat has only one stage of supplemental heat, connect white and violet wires shown in Fig. 10 to second stage heat field wire.

Some electric heaters have four control wires (plus common wire).

Consult unit wiring diagram and electric heater wiring diagram for additional details.

TRANSFORMER PROTECTION

The transformer is of the energy--limiting type, however a direct short will likely blow a secondary fuse. If an overload or short is present, correct overload condition and check for blower fuse on

Indoor Fan Board. Replace fuse as required with correct size and rating.

UNIT SIZE

NOMINAL CAPACITY (ton)

SHIPPING WEIGHT lb.

SHIPPING WEIGHT (kg)

COMPRESSORS

Quantity

REFRIGERANT (R---410A)

Quantity lb

Quantity (kg)

REFRIGERANT METERING DEVICE

ORIFICE

ID (in.)

ID (mm)

OUTDOOR COIL

Rows...Fins/in.

Face Area (sq ft)

OUTDOOR FAN

Nominal Cfm

Diameter in.

Diameter (mm)

Motor Hp (Rpm)

INDOOR COIL

Rows...Fins/in.

Face Area (sq ft)

INDOOR BLOWER

Nominal Low Stage Cooling Airflow (Cfm)

Nominal High Stage Cooling Airflow (Cfm)

Size in.

Size (mm.)

Motor HP (RPM)

HIGH---PRESSURE SWITCH

(psig) Cut---out Reset (Auto)

LOW---PRESSURE SWITCH

(psig) cut---out Reset (auto)

RETURN---AIR FILTERS†}

Throwaway Size in.

Throwaway Size (mm)

24

2

356

162

9.0

4.1

.032 (2)

0.81 (2)

2...21

13.6

2100

24

609.6

Table 1 – Physical Data--Unit 50VR--A

30

2---1/2

364

165

36

3

420

191

Scroll

1

1/12 (800)

3...17

3.7

650

850

10x10

254x254

1/2 (1050)

10.0

4.5

.040 (2)

1.02 (2)

2...21

15.3

2500

24

609.6

1/8 (810)

3...17

3.7

750

1000

10x10

254x254

1/2 (1050)

11.0

5.0

14.6

6.6

TXV, Indoor TXV

.042 (2)

1.07 (2)

2...21

13.6

3000

26

660.4

1/5 (810)

3...17

4.7

900

1200

11x10

279.4x254

3/4 (1000)

3---1/2

.042 (2)

1.07 (2)

2...21

11x10

279.4x254

3/4 (1075)

20 +/--- 5

45 +/--- 5

42

466

212

19.4

3000

26

660.4

1/5 (810)

3...17

1050

1400

650 +/--- 15

420 +/--- 25

4.7

48

4

462

210

12.0

5.4

.042 (2)

1.07 (2)

2...21

17.5

3300

26

660.4

1/5 (810)

3...17

5.7

1200

1600

11x10

279.4x254

1.0 (1075)

60

5

511

232

14.8

6.7

.052 (2)

1.32 (2)

2...21

23.3

3600

26

660.4

1/5 (810)

4...17

5.7

1400

1750

11x10

279.4x254

1.0 (1075)

20x20x1

508x508x25

20x24x1

508x610x25

24x30x1

610x762x25

24x36x1

610x914x25

{

Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08

in. W.C.

}

If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.

SIZE

Cfm

24

850

Table 2 – Minimum Airflow for Safe Electric Heater Operation (CFM)

30

1000

36

1200

42

1400

48

1600

60

1750

10

!

PRE--START--UP

WARNING

ENVIRONMENTAL, FIRE,

ELECTRICAL SHOCK HAZARD

EXPLOSION,

Failure to follow this warning could result in personal injury or death and/or property damage.

1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.

2. Relieve and recover all refrigerant from system before touching or disturbing compressor plug if refrigerant leak is suspected around compressor terminals.

3. Never attempt to repair soldered connection while refrigerant system is under pressure.

4. Do not use torch to remove any component. System contains oil and refrigerant under pressure.

5. To remove a component, wear protective goggles and proceed as follows: a. Shut off electrical power to unit and install lockout tag.

b. Relieve and reclaim all refrigerant from system using both high-- and low--pressure ports.

c. Cut component connecting tubing with tubing cutter and remove component from unit.

d. Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame.

Use the Start--Up Checklist supplied at the end of this book and proceed as follows to inspect and prepare the unit for initial start--up:

1. Remove all access panels (see Fig. 20).

2. Read and follow instructions on all DANGER, WARNING,

CAUTION, and INFORMATION labels attached to, or shipped with unit.

3. Make the following inspections: a. Inspect for shipping and handling damages, such as broken lines, loose parts, disconnected wires, etc.

b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. Leak test all refrigerant tubing connections using electronic leak detector, or liquid--soap solution. If a refrigerant leak is detected, see following Check for Refrigerant Leaks section.

c. Inspect all field-- and factory--wiring connections. Be sure that connections are completed and tight. Ensure wires do not touch refrigerant tubing or sharp sheet metal edges.

d. Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb.

4. Verify the following conditions: a. Make sure that outdoor--fan blade is correctly positioned in fan orifice.

b. Make sure that air filter(s) is in place.

c. Make sure that condensate drain pan and trap are filled with water to ensure proper drainage.

d. Make sure that all tools and miscellaneous loose parts have been removed

5. Each unit system has two (2) Schrader--type ports, one low-side Schrader fitting located on the suction line, and one high--side Schrader fitting located on the compressor discharge line. Be sure that caps on the ports are tight.

START--UP

Step 1 — Check Cooling and Heating Control

Operation

Start and check the unit for proper control operation as follows:

1. Place room thermostat SYSTEM switch or MODE control in OFF position. Observe that blower motor starts when

FAN mode is placed in FAN ON position and shuts down when FAN MODE switch is placed in AUTO position.

2. Thermostat:

On a typical two stage thermostat, when the room temperature rises 1 or 2 degrees above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R and terminals Y1, and G.

These completed circuits through the thermostat connect the contactor coil (C) (through unit wire Y1) and indoor fan board (through unit wire G) across the 24--v. secondary of transformer (TRAN).

On a typical two stage thermostat, when the room temperature is several degrees above the cooling control setting of the thermostat, the thermostat completes the circuit between terminal R and terminals Y1, Y2 , and G.

3. If your unit contains accessory electric heat, place system switch or MODE control in HEAT position. Set control above room temperature. Observe that the indoor blower is operating and warm air is flowing through the supply air vents inside your home. Observe that the heating cycle shuts down when the control setting is satisfied.

If your unit does not contain accessory electric heat and you would like to obtain it, please contact your local dealer for more information.

4. When using an automatic changeover room thermostat place both SYSTEM or MODE control and FAN mode stitches in AUTO positions. Observe that unit operates in

Cooling mode when temperature control is set to “call for

Cooling” (below room temperature).

NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed.

Step 2 — Check for Refrigerant Leaks

!

WARNING

EXPLOSION HAZARD

Failure to follow this warning could result in death, serious personal injury, and/or property damage.

Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.

Proceed as follows to locate and repair a refrigerant leak and to charge the unit:

1. Locate leak and make sure that refrigerant system pressure has been relieved and reclaimed from both high--and low-pressure ports.

2. Repair leak following Refrigerant Service procedures.

NOTE: Install a filter drier whenever the system has been opened for repair.

3. Add a small charge of R--410A refrigerant vapor to system and leak--test unit.

4. Recover refrigerant from refrigerant system and evacuate to

500 microns if no additional leaks are found.

5. Charge unit with R--410A refrigerant, using an electronic scale. Refer to unit rating plate for required charge.

11

Step 3 — Start--Up Adjustments

Complete the required procedures given in the Pre--Start--Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the unit in cooling mode when the outdoor temperature is below 40_F (4_C) (unless accessory low--ambient kit is installed).

IMPORTANT: Three--phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor

3--phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3--phase power leads to the unit must be reversed to correct rotation. When turning backwards, the difference between compressor suction and discharge pressures may be near zero.

Checking and Adjusting Refrigerant Charge

!

WARNING

EXPLOSION HAZARD

Failure to follow this warning could result in death, serious personal injury, and/or property damage.

Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.

The refrigerant system is fully charged with R--410A refrigerant and is tested and factory sealed.

NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper R--410A charge.

A subcooling charging chart is attached to the inside of the compressor access panel. The chart includes the required liquid line temperature at given discharge line pressures and outdoor ambient temperatures.

An accurate thermocouple-- or thermistor--type thermometer, and a gauge manifold are required when using the subcooling charging method for evaluating the unit charge. Do not use mercury or small dial--type thermometers because they are not adequate for this type of measurement.

NOTE: Allow system to operate on high stage cooling for a minimum of 15 minutes before checking or adjusting refrigerant charge.

IMPORTANT: When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.

1. Remove caps from low-- and high--pressure service fittings.

2. Using hoses with valve core depressors, attach low-- and high--pressure gauge hoses to low-- and high--pressure service fittings, respectively.

3. Start unit and let run until system pressures stabilize.

4. Measure and record the following: a.

Outdoor ambient--air temperature (F [C] db).

Liquid line temperature (F [C]) at TXV.

b.

c.

d.

Discharge (high--side) pressure (psig).

Suction (low--side) pressure (psig) (for reference only).

5. Using Cooling Charging Charts (See Fig. 18) compare outdoor--air temperature (F [C] db) with the discharge line pressure (psig) to determine desired system operating liquid line temperature (See Fig. 18).

6. Compare actual liquid line temperature with desired liquid line temperature. Using a tolerance of 2F (1.1C), add refrigerant if actual temperature is more than 2F (1.1C) higher than proper liquid line temperature, or remove refrigerant if actual temperature is more than 2F (1.1C) lower than required liquid line temperature.

NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks section.

Indoor Airflow and Airflow Adjustments

!

CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit damage.

For cooling operation, the recommended airflow is 350 to

450 cfm for each 12,000 Btuh of rated cooling capacity. For heating operation, the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate.

NOTE: Be sure that all supply--air and return--air grilles are open, free from obstructions, and adjusted properly.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect electrical power to the unit and install lockout tag before changing blower speed.

This unit has independent fan speeds for low stage cooling and high stage cooling. In addition, 208/230 VAC models have the field--selectable capability to run an enhanced dehumidification

(’DEHUM’) speed on high stage cooling (as low as 320 CFM per ton). Coupled with the improved dehumidification associated with low stage cooling, the DHUM speed allows for a complete dehumidification solution independent of cooling stage. Table 3 shows the operation modes and the associated fan speeds with each mode:

Table 3 – Operation Modes and Fan Speeds

208/230 VAC Models

Operation Mode

Low Stage Cooling/Heat Pump

High Stage Cooling/Heat Pump

High Stage Enhanced

Dehumidification Cooling

Continuous Fan

Fan Speed Tap

Connection

LOW

HIGH

DH

LOW

460 VAC Models

Operation Mode

Low Stage Cooling/Heat Pump

High Stage Cooling/Heat Pump

Continuous Fan

Fan Speed Tap

Connection

LOW

HIGH

LOW

12

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect electrical power to the unit and install lockout tag before changing blower speed.

The evaporator fan motor is factory set to provide 5 different fan speeds to choose from for the various operation modes (see Table

4). All models are factory--shipped for nominal high stage and low stage cooling airflow operation at minimum external static pressure. See Table 2.

Table 4 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med--High Speed

Red = Med Speed

Pink = Med--Low Speed

Blue = Low Speed

Selection of Proper Fan Speeds for Operation Modes:

Low Stage Cooling/Heat Pump (All Models): Using Tables 7 , 8, and 9, find the external static pressure drops for wet coil, economizer, and filter, and add them to dry coil measured on the system. Using this total static pressure, look up Table 5 to find the airflows available at the total static pressure. For 208/230 VAC models, connect the chosen fan speed wire to “LO COOL” connection on the IFB Board (see Fig. 11). For 460 VAC models, connect the chosen fan speed wire to “LOW” connection on the

IFB (see Fig. 11).

High Stage Cooling/Heat Pump (All Models):Using Table 7 , 8, and 9, find the external static pressure drops for wet coil, economizer, and filter, and add them to dry coil measured on the system. Using this total static pressure, look up Table 5 to find the airflows available at the total static pressure. The speed chosen must provide airflow of between 350 to 450 CFM per ton of cooling. For 208/230 VAC models, connect the chosen fan speed wire to “HI COOL” connection on the IFB Board (See Fig. 11).

For 460 VAC models, connect the chosen fan speed wire to

“HIGH” connection on the IFB (see Fig. 11).

High Stage Enhanced Dehumidification Cooling (208/230 VAC

Models): Using the total static pressure for selecting the high stage cooling speed, look up Table 5 to find lower speed/airflows available at that total static pressure. All airflows highlighted in

Table 5 are acceptable for the Dehum speed. The speed chosen must provide airflow of between 320 to 400 CFM per ton of cooling. To activate the high stage enhanced dehumidification cooling mode, the shunt jumper must be moved from the “No DH” to the “DH” selection. (See Fig. 11, close up.) For 208/230 VAC models, connect the chosen fan speed wire to “DHUM” connection on the IFB Board (see Fig. 11).

Continuous Fan (All Models): Continuous fan speed is the same speed as Low Stage Cooling.

To activate the high stage enhanced dehumidification cooling mode, the shunt jumper in Fig. 11 must be moved from the No DH to DH selection (See Fig. 11, close up).

Using the Same Fan Speed for More than One Mode: Some fan speeds are ideal for more than one mode of operation. It is permissible to use a field--supplied jumper wire to connect one speed tap wire to two or more speed connections on the Interface

Fan Board (IFB). Jumper wires must use 18 AWG wire with at least 2/64” insulation.

SEQUENCE OF OPERATION

a. Continuous Fan

(1.) Thermostat closes circuit R to G energizing the blower motor for continuous fan. The indoor fan is energized on low speed.

b. Cooling Mode

(1.) Low Stage: Thermostat closes R to G, R to Y1, and R to O. The compressor and indoor fan are energized on low speed. The outdoor fan is also energized

(2.) High Stage: Thermostat closes R to G, R to Y1, R to Y2, and R to O. The compressor and indoor fan are energized on high speed. The outdoor fan is also energized.

c. Electric Heating Mode

(1.) Thermostat closes circuit R to W2 or W3, and R to

G. There are no on or off delays.

d. Heat Pump Heating

(1.) Low Stage: Thermostat closes R to G, R to Y1.

The compressor and indoor fan are energized on low speed. The outdoor fan is also energized

(2.) High Stage: Thermostat closes R to G, R to Y1, R to Y2. The compressor and indoor fan are energized on high speed. The outdoor fan is also energized.

e. Heat Pump Heating with Auxiliary Heat

(1.) Thermostat closes circuits R to G, R to Y and R to

W/W1 or W2. The compressor, indoor and outdoor fans are energized, as well as the electric heat relays.

f. Defrost Mode

The defrost mode is automatically energized by the defrost board during heating mode. The defrost board energizes “O” (reversing valve) and “W2” (electric heat). It also de--energizes the outdoor fan. When defrost is complete, unit will return to heating mode. If room thermostat is satisfied during defrost, unit will shut down and restart in defrost on next call for heat.

Step 4 — Defrost Control

Quiet Shift

Quiet Shift is a field--selectable defrost mode, which will eliminate occasional noise that could be heard at the start of defrost cycle and restarting of heating cycle. It is selected by placing DIP switch 3

(on defrost board) in ON position.

When Quiet Shift switch is placed in ON position, and a defrost is initiated, the following sequence of operation will occur. Reversing valve will energize, outdoor fan will turn off, compressor will turn off for 30 sec and then turn back on to complete defrost. At the start of heating after conclusion of defrost reversing valve will de--energize, compressor will turn off for another 30 sec, and the outdoor fan will stay off for 40 sec, before starting in the Heating mode.

Defrost

The defrost control is a time/temperature control which includes a field--selectable time period (DIP switch 1 and 2 on the board) between defrost cycles of 30, 60, 90, or 120 minutes (factory set at

60 minutes). To initiate a forced defrost, two options are available depending on the status of the defrost thermostat.

13

HIGH

QC5

DH

QC6

LOW COM

QC4

C

QC9 QC3

H S C I

US

2 4 V M OTO R TA P S

K2 K4

K3

674 674 674 674

K1

D2

R12

Q1

R13

R10

C5

QC2

QC1

C9 C4

R7 R9

C8 R15

C1

R1 D1

C2

D11 D6 D4 Z2

C7

D4

R11

674

R8

Z1

C6

R4

F1

R14

D5 D3 e

1

QC8

Y

JW2

R2 R5 R3 R6

P2

C3

R

674

W2

Y

C

1

674

W3 W3 W2 W2 C

P4

1

J2

DH DH

P1

6 7 4

DH W3 W2 Y2 G Y1 C R

H K 6 1 E A 0 2 3

1

DH

DH

Shunt in dehumidification position

DH DH

Shunt in no dehumidification position

208/230 VAC Models

HIGH

QC5

LOW

QC4

COM

QC3

A12571

KZ KL

DCR QCR

07 09 0L0 08

ALO

R13 C8 R11 Q1

Q3

D2

C

QC1

AL2

C9

C4

G1

RL

01

QIL

D5 D3

Z2 06 04

JW5

R2

QCB

C7

G2

A7 R9 AB A15

U1

C3

Z1

JWZ

R3 R5 R6

P2

JW3

R4

C0 F1

RL4

P4

Y

R W2 Y C W3 W3 W2 W2 C

JW4

SSTZ-8

P1

W3 W2

Y2

DH

G

Y1

Y

C R

460 VAC Models

Fig. 11 -- Interface Fan Board (IFB)

A09059

14

Fig. 12 -- Defrost Control Board

A13151

OUTDOOR COIL

TXV in Bypass

Position

LCS

HP S

Metering

Position

LEGEND

HPS – High Pressure Switch

LCS – Loss of Charge Switch

Accurater ® Metering De vice

Fig. 13 -- Typical Heat Pump Operation, Heating Mode

INDOOR COIL

OUTDOOR COIL

TXV in Metering

Position

LCS

HP S

LEGEND

HPS – High Pressure Switch

LCS – Loss of Charge Switch

Accurater Metering De vice

Bypass

Position

Fig. 14 -- Typical Heat Pump Operation, Cooling Mode

INDOOR COIL

C03012

C03011

15

16

17

18

19

20

21

Fig. 15 -- Connection Wiring Diagram 208/230--1--60

A13144

22

Fig. 12 Cont. -- Ladder Wiring Diagram 208/230--1--60

23

A13145

Fig. 16 -- Connection Wiring Diagram 208/230--3--60

24

A13146

Fig. 13 Cont. -- Ladder Wiring Diagram 208/230--3--60

25

A13147

Fig. 17 -- Connection Wiring Diagram 460--3--60

26

A13148

Fig. 14 Cont. -- Ladder Wiring Diagram 460--3--60

27

A13149

Fig. 18 -- Cooling Charging Chart

A13171

28

MAINTENANCE

To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This cooling unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table 11, Troubleshooting Chart.

NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.

!

WARNING

PERSONAL INJURY AND UNIT DAMAGE

HAZARD

Failure to follow this warning could result in personal injury or death and possible unit component damage.

The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment, other than those procedures recommended in the Owner’s

Manual.

!

WARNING

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow these warnings could result in personal injury or death:

1. Turn off electrical power to the unit and install lockout tag before performing any maintenance or service on this unit.

2. Use extreme caution when removing panels and parts.

3. Never place anything combustible either on or in contact with the unit.

!

CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnecting when servicing.

The minimum maintenance requirements for this equipment are as follows:

1. Inspect air filter(s) each month. Clean or replace when necessary.

2. Inspect indoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.

3. Inspect blower motor and wheel for cleanliness each cooling season. Clean when necessary.

4. Check electrical connections for tightness and controls for proper operation each cooling season. Service when necessary.

5. Ensure electric wires are not in contact with refrigerant tubing or sharp metal edges.

Air Filter

IMPORTANT: Never operate the unit without a suitable air filter in the return--air duct system. Always replace the filter with the same dimensional size and type as originally installed. See Table 1 for recommended filter sizes.

Inspect air filter(s) at least once each month and replace

(throwaway--type) or clean (cleanable--type) at least twice during each cooling season and twice during the heating season, or whenever the filter becomes clogged with dust and lint.

Indoor Blower and Motor

NOTE: All motors are pre--lubricated. Do not attempt to lubricate these motors.

For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect and tag electrical power to the unit before cleaning the blower motor and wheel.

To clean the blower motor and wheel:

1. Remove and disassemble blower assembly as follows: a. Remove blower access panel (see Fig. 20).

b. Disconnect 5 pin plug and 4 pin plug from indoor blower motor. Remove capacitor if required.

c. On all units remove blower assembly from unit.

Remove screws securing blower to blower partition and slide assembly out. Be careful not to tear insulation in blower compartment.

d. Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly.

e. Loosen setscrew(s) that secures wheel to motor shaft, remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing.

2. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel orientation.

b. Lift wheel from housing. When handling and/or cleaning blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.

c. Remove caked--on dirt from wheel and housing with a brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent.

d. Reassemble wheel into housing.

e. Reassemble motor into housing. Be sure setscrews are tightened on motor shaft flats and not on round part of shaft. Reinstall blower into unit.

f. Connect 5 pin plug and 4 pin plug to indoor blower motor. Reinstall capacitor if required.

g. Reinstall blower access panel (see Fig. 20).

3. Restore electrical power to unit. Start unit and check for proper blower rotation and motor speeds during cooling cycles.

29

FAN GRILLE

MOTOR

A

MOTOR SHAFT

42

48

60

24

30

36

MAX DISTANCE BETWEEN TOP OF FAN GRILLE AND BOTTOM OF FAN BLADE

SIZE

“A”

IN.

6.3

6.3

7.6

7.6

7.6

7.6

MM

160

160

193

193

193

193

Fig. 19 -- Fan Blade Position

Control

Blower

Access

Panel

Access

Panel

Compressor

Access Panel

A09214

Fig. 20 -- Unit Access Panels

Outdoor Coil, Indoor Coil, and Condensate Drain Pan

Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year.

The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.

Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent and water solution.

Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.

A08505

Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain trough is restricted, clear it with a

“plumbers snake” or similar probe device.

OUTDOOR FAN

!

CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in damage to unit components.

Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit.

1. Remove 6 screws holding condenser grille and motor to top cover.

2. Turn motor/grille assembly upside down on top cover to expose the fan blade.

3. Inspect the fan blades for cracks or bends.

4. If fan needs to be removed, loosen the setscrew and slide the fan off the motor shaft.

5. When replacing fan blade, position blade as shown in Fig.

19.

6. Ensure that setscrew engages the flat area on the motor shaft when tightening

7. Replace grille.

Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit.

Remove access panels (see Fig. 20) to locate all the electrical controls and wiring. Check all electrical connections for tightness.

Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.

30

After inspecting the electrical controls and wiring, replace the access panels (see Fig. 20). Start the unit, and observe at least one complete heating cycle and one complete cooling cycle to ensure proper operation. If discrepancies are observed in either or both operating cycles, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.

NOTE: Refer to the heating and/or cooling sequence of operation in this publication as an aid in determining proper control operation

Refrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrigerant leak.

!

WARNING

EXPLOSION, SAFETY AND ENVIRONMENTAL

HAZARD

Failure to follow this warning could result in personal injury, death or equipment damage.

This system uses Puron (R--410A) refrigerant which has higher operating pressures than R--22 and other refrigerants.

No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle

Puron. If you are unsure, consult the equipment manufacturer.

If oil is detected or if low cooling performance is suspected, leak--test all refrigerant tubing using an electronic leak--detector, halide torch, or liquid--soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section.

If no refrigerant leaks are found and low cooling performance is suspected, refer to Checking and Adjusting Refrigerant Charge section.

Evaporator Airflow

The heating and/or cooling air--flow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply-- and return--air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to

Indoor Airflow and Airflow Adjustments section to check the system airflow.

Metering Device

This unit uses 2 types of metering devices. The outdoor metering device is a fixed orifice and is contained in the brass hex--body in each liquid line feeding the outdoor coils. The indoor metering device is a TXV type device.

Pressure Switches

Pressure switches are protective devices wired into the control circuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically designed to operate with Puron

(R--410A) systems. R--22 pressure switches must not be used as replacements for the Puron (R--410A) air conditioner.

Loss of Charge Switch

This switch is located on the liquid line and protects against low suction pressures caused by such events as loss of charge, low airflow across indoor coil, dirty filters, etc. It opens on a pressure drop at about 20 psig. If system pressure is above this, switch should be closed. To check switch:

NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psi (0 Pa). Never open system without breaking vacuum with dry nitrogen.

High--Pressure Switch

The high--pressure switch is located in the discharge line and protects against excessive condenser coil pressure. It opens at 650 psig (31.1 kPa). High pressure may be caused by a dirty condenser coil, failed fan motor, or condenser air recirculation.

To check switch:

1. Turn off all power to unit.

2. Disconnect leads on switch.

3. Apply ohmmeter leads across switch. You should have continuity on a good switch.

Copeland Scroll Compressor (Puron Refrigerant)

The compressor used in this product is specifically designed to operate with Puron (R--410A) refrigerant and cannot be interchanged.

The compressor is an electrical (as well as mechanical) device.

Exercise extreme caution when working near compressors. Power should be shut off, if possible, for most troubleshooting techniques.

Refrigerants present additional safety hazards.

!

WARNING

FIRE/EXPLOSION HAZARD

Failure to follow this warning could result in personal injury or death and/or property damage.

Wear safety glasses and gloves when handling refrigerants.

Keep torches and other ignition sources away from refrigerants and oils.

The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll. The scroll compressor has no dynamic suction or discharge valves, and it is more tolerant of stresses caused by debris, liquid slugging, and flooded starts. The compressor is equipped with a noise reducing shutdown device and an internal pressure relief port. The pressure relief port is a safety device, designed to protect against extreme high pressure. The relief port has an operating range between 550

(26.3 kPa) and 625 (29.9 kPa) psig differential pressure.

Refrigerant

!

WARNING

EXPLOSION, ENVIRONMENTAL HAZARD

Failure to follow this warning could result in personal injury, death or equipment damage.

This system uses Puron (R--410A) refrigerant which has higher operating pressures than R--22 and other refrigerants.

No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle

Puron. If you are unsure, consult the equipment manufacturer.

This system uses Puron (R--410A) refrigerant which has higher operating pressures than R--22 and other refrigerants. No other refrigerant may be used in this system. Gage set, hoses, and recovery system must be designed to handle Puron. If you are unsure, consult the equipment manufacturer. Failure to use Puron compatible servicing equipment or replacement components may result in property damage or injury.

Compressor Oil

The Copeland scroll compressor uses 3MAF POE oil. If additional oil is needed, use Uniqema RL32--3MAF. If this oil is not available, use Copeland Ultra 32 CC or Mobil Arctic EAL22 CC.

31

This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere.

Servicing Systems on Roofs with Synthetic Materials

POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials. Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, replacing refrigerant components such as filter drier, pressure switch, metering device, coil, accumulator, or reversing valve.

Synthetic Roof Precautionary Procedure

1. Cover extended roof working area with an impermeable polyethylene (plastic) drip cloth or tarp. Cover an approximate 10 x 10 ft (3 x 3 m) area.

2. Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills, prevent run--offs, and protect drop cloth from tears caused by tools or components.

3. Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run--offs through the louvered openings in the unit base.

4. Perform required service.

5. Remove and dispose of any oil contaminated material per local codes.

Liquid Line Filter Drier

The filter drier is specifically designed to operate with Puron. Use only factory--authorized components. Filter drier must be replaced whenever the refrigerant system is opened. When removing a filter drier, use a tubing cutter to cut the drier from the system. Do not unsweat a filter drier from the system. Heat from unsweating will release moisture and contaminants from drier into system.

Puron (R--410A) Refrigerant Charging

Refer to unit information plate and charging chart. Some R--410A refrigerant cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder in upright position. For cylinders equipped with a dip tube, charge Puron units with cylinder in upright position and a commercial metering device in manifold hose.

Charge refrigerant into suction--line.

Step 5 — System Information

Loss of Charge Switch

The loss of charge switch is a protective device wired into control circuit (low voltage). It shuts off the compressor if abnormally low pressures are present in the refrigeration circuit.

NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psig. Never open system without breaking vacuum with dry nitrogen.

Check Defrost Thermostat

The defrost thermostat is usually located on the lowest liquid leaving circuit of the left condenser coil (see Fig. 21). The thermostat closes at 32_F (0_C) and opens at 65_F (18_C).

The defrost thermostat signals heat pump that conditions are right for defrost or that conditions have changed to terminate defrost. It is a thermally actuated switch clamped to outdoor coil to sense its temperature. Normal temperature range is closed at 32_  3_F (0

 1.7_C) and open at 65_  5_F (18  2.8_C).

NOTE: The defrost thermostat must be located on the liquid side of the outdoor coil on the bottom circuit and as close to the coil as possible.

FEEDER TUBE

STUB TUBE

DEFROST

THERMOSTAT

C99029

Fig. 21 -- Defrost Thermostat

TROUBLESHOOTING

Refer to the Troubleshooting Chart (Table 11) for troubleshooting information.

START--UP CHECKLIST

Use the Start--Up Checklist at the back of this manual.

32

SYMPTOM

Compressor and outdoor fan will not start

Compressor will not start but condenser fan runs

Three--phase scroll compressor (size 30--60 unit) has a low pressure differential

Compressor cycles (other than normally satisfying thermostat)

Compressor operates continuously

Excessive head pressure

Head pressure too low

Excessive suction pressure

Suction pressure too low

Table 11 – Troubleshooting Chart

CAUSE

Power failure

Fuse blown or circuit breaker tripped

Defective contactor, transformer or high--pressure, loss--of--charge or low--pressure switch

Insufficient line voltage

Incorrect or faulty wiring

Thermostat setting too high

Faulty wiring or loose connections in compressor circuit

Compressor motor burned out, seized, or internal overload open

Defective run/start capacitor, overload, start relay

Scroll compressor is rotating in the wrong direction

Refrigerant overcharge or undercharge

Defective compressor

Insufficient line voltage

Blocked condenser

Defective run/start capacitor, overload or start relay

Defective thermostat

Faulty condenser--fan motor or capacitor

Restriction in refrigerant system

Dirty air filter

Unit undersized for load

Thermostat set too low

Low refrigerant charge

Mechanical damage in compressor

Air in system

Condenser coil dirty or restricted

Dirty air filter

Dirty indoor or outdoor coil

Refrigerant overcharged

Air in system

Low refrigerant charge

Compressor IPR leaking

Restriction in liquid tube

High heat load

Compressor IPR leaking

Refrigerant overcharged

Dirty air filter

Low refrigerant charge

Metering device or low side restricted

Insufficient evaporator airflow

Temperature too low in conditioned area

Outdoor ambient below 55F (12.7C)

Filter drier restricted

REMEDY

Call power company

Replace fuse or reset circuit breaker

Replace component

Determine cause and correct

Check wiring diagram and rewire correctly

Lower thermostat setting below room temperature

Check wiring and repair or replace

Determine cause

Replace compressor

Determine cause and replace

Correct the direction of rotation by reversing the

3--phase power leads to the unit

Recover refrigerant, evacuate system, and recharge to capacities shown on rating plate

Replace and determine cause

Determine cause and correct

Determine cause and correct

Determine cause and replace

Replace thermostat

Replace

Locate restriction and remove

Replace filter

Decrease load or increase unit size

Reset thermostat

Locate leak, repair, and recharge

Replace compressor

Recover refrigerant, evacuate system, and recharge

Clean coil or remove restriction

Replace filter

Clean coil

Recover excess refrigerant

Recover refrigerant, evacuate system, and recharge

Check for leaks, repair and recharge

Replace compressor

Remove restriction

Check for source and eliminate

Replace compressor

Recover excess refrigerant

Replace filter

Check for leaks, repair and recharge

Remove source of restriction

Increase air quantity

Check filter–replace if necessary

Reset thermostat

Install low--ambient kit

Replace filter

33

PURON (R--410A) QUICK REFERENCE GUIDE

Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are designed to operate with Puron. Puron refrigerant cylinders are rose colored.

S

Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright position.

Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow.

S

Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.

S

Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.

S

Manifold sets should be minimum 700 psig high--side and 180 psig low--side with 550 psig low--side retard.

S

Use hoses with minimum 700 psig service pressure rating.

S

Leak detectors should be designed to detect HFC refrigerant.

S

Puron, as with other HFCs, is only compatible with POE oils.

S

Vacuum pumps will not remove moisture from oil.

S

Only use factory specified liquid--line filter driers with rated working pressures no less than 600 psig.

S

Do not install a suction--line filter drier in liquid line.

S

POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

S

POE oils may cause damage to certain plastics and roofing materials.

S

Wrap all filter driers and service valves with wet cloth when brazing.

S

A Puron liquid--line filter drier is required on every unit.

S

Do not use an R--22 TXV.

S

Never open system to atmosphere while it is under a vacuum.

S

When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.

S

Always replace filter drier after opening system for service.

S

Do not vent Puron into the atmosphere.

S

Observe all warnings, cautions, and bold text.

S

Do not leave Puron suction line driers in place for more than 72 hrs.

34

START--UP CHECKLIST

(Remove and Store in Job Files)

I. PRELIMINARY INFORMATION

MODEL NO.:

SERIAL NO.:

DATE:

TECHNICIAN:

II. PRESTART--UP (Insert check mark in box as each item is completed)

( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT

( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS

( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS

( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE

( ) VERIFY THAT UNIT INSTALLATION IS LEVEL

( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS

III. START--UP

ELECTRICAL

SUPPLY VOLTAGE

COMPRESSOR AMPS

INDOOR (EVAPORATOR) FAN AMPS

TEMPERATURES

OUTDOOR (CONDENSER) AIR TEMPERATURE

RETURN--AIR TEMPERATURE

COOLING SUPPLY AIR DB

DB

DB

WB

WB

HEAT PUMP SUPPLY AIR

ELECTRIC HEAT SUPPLY AIR

PRESSURES

REFRIGERANT SUCTION

REFRIGERANT DISCHARGE

PSIG, SUCTION LINE TEMP*

PSIG, LIQUID TEMP{

( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS

* Measured at suction inlet to compressor

{

Measured at liquid line leaving condenser.

35

Copyright 2013 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 05/13

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

36

Catalog No:50VR---01SI

Replaces: New

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement