QUANTUM PLUS 13 SEER

HEAT PUMP WITH

PURON™ REFRIGERANT

650A (60 Hz)

Sizes 024 thru 060

The Quantum Plus line of split-system outdoor units has been expanded to include the Model 650A 13 SEER heat pump

(with efficiencies up to 14.5 SEER). Homeowners will appreciate the Quantum Plus with Puron Refrigerant because of its efficiency, environmental soundness and its availability for years to come.

Another benefit of the Quantum Plus is the durability of the scroll compressor. Model 650A has received certifications from UL, c-UL, ARI, CEC, and CSA-EEV. The 650A is also approved by Energy Star SM for energy efficiency and by Green

Seal for efficiency and environmental soundness.

FEATURES

REFRIGERANT —The environmentally sound refrigerant used in the 650A is Puron. This advanced refrigerant contains no chlorine which can contribute to ozone depletion in the atmosphere, so it’s a smart choice for homeowners who are concerned with protecting our environment, now and for future generations. And it’s a smart choice for anyone interested in high-efficiency cooling.

RELIABLE BUILT-IN COMPONENTS —All units include a suction line accumulator that minimizes the amount of liquid refrigerant that reaches the compressor; a high-pressure switch for high-pressure protection; a low-pressure switch for loss of charge protection; and a liquid-line filter drier to remove any moisture or foreign matter from the system. A crankcase heater is standard on the 048 and 060 sizes.

COMPRESSOR PROTECTION —Each scroll compressor motor is protected with internal temperature and currentsensitive overloads. For improved serviceability each compressor is equipped with a compressor terminal plug.

UNIT DESIGN —Copper tube, enhanced aluminum fin coil is designed for strong heat transfer. Vertical air discharge carries sound and hot condenser air up and away from adjacent patio areas and foliage. Heat pump style base pan is popular for its easy removal of water, dirt, and leaves.

The AeroQuiet System (AQS) consists of 4 design features to achieve ultra-low sound ratings.

Aerocoustic Design featuring the Aeromax opening and wire dome top results in quieter and more efficient operation.

Energy-Efficient Fan and Fan Motor provide a slower fan operation, thus reducing noise and improving efficiency.

Sound Hood muffles noise from operation.

Discharge Muffler minimizes low frequency sound and pressure pulsation generated by compressor discharge gas.

WEATHER-PROTECTIVE CABINET —Steel is galvanized and coated with a layer of zinc phosphate. A layer of modified polyester powder is then applied and baked on, providing each unit with a durable finish that will last for many years.

All screws on cabinet exterior are coated for a long-lasting, rust-resistant, quality appearance.

COIL PROTECTION —The DuraGuard coil protector, made of a 12 gage coated steel wire grid with vertical 3/8-in. spacing, is designed to help protect the coil from inclement weather, vandalism, and incidental damage. It provides protection while not restricting airflow and maintaining ease of coil inspection and cleaning.

EASY SERVICEABILITY —One access panel provides access to electrical controls and compressor. Removal of wire dome gives access to fan motor and removal of the top gives access to the coil.

WIDE RANGE OF SIZES —Available in 6 nominal sizes from

024 through 060 to meet the needs of residential and light commercial applications.

LIMITED WARRANTY —Standard 1-year limited warranty on parts, with an additional 9-year limited warranty on compressor.

TOTALLY ENCLOSED FAN MOTOR —Means greater reliability under adverse weather conditions and dependable performance for many years. Permanent split-capacitor-type motors provide more economical operation.

DEFROST CONTROL BOARD —Incorporates a built-in

5-minute compressor time-delay relay, defrost relay, defrost timer, and low-voltage terminal board. The defrost control is a time/temperature initiation/termination control, which includes

3 field-selectable time periods of 30, 50, and 90 minutes.

APPLICATION VERSATILITY —Due to PressureGuard™ the 650A can be combined with a wide variety of evaporator coils and blower packages to provide quiet, dependable comfort. The 650A can be installed on a roof or at ground level on a slab.

EXTERNAL SERVICE VALVES —Both service valves are brass, back seating type with sweat connections. Valves are externally located so refrigerant tube connections can be made quickly and easily. Each valve has a service port for ease of checking operating refrigerant pressures.

THERMOSTATIC EXPANSION VALVE (TXV) —This unit must be installed with a Puron™ approved TXV on the indoor coil. The FX4 and FV4 fan coils come factory equipped with Puron TXVs. When installed with these fan coils, no further change is required. For any other coil combination, the approved field accessory Puron TXV must be installed. For applications with fan coils such as the

FC4 and FK4 which have R-22 TXVs, the R-22 TXV must be replaced with the approved field accessory Puron TXV.

ELECTRICAL RANGE —All units are offered in 208/230v single phase only.

Form No. PDS 650A.24.2

DIMENSIONS

C L

—2—

RECOMMENDED TUBE DIAMETERS

UNIT

SIZE

024

030

036

042, 048

060

LIQUID TUBE DIAMETER (IN.)

0 to 50 Ft

Tube Length

3/8

3/8

3/8

3/8

3/8

Alternate

3/8

3/8

3/8

3/8

3/8

0 to 50 Ft

Tube Length

5/8

3/4

3/4

7/8

1-1/8

VAPOR TUBE DIAMETER (IN.)

Alternate

3/4 ACR

7/8

7/8

7/8

7/8

RST*

(Not Permitted)

3/4

1-1/8

1-1/8

3/4 and 1-1/8

3/4

* RST—Refrigeration Service Tubing, standard refrigerant grade tubing.

NOTES:

1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult the Application Guideline and Service Manual for Residential Split-

System Air Conditioners and Heat Pumps using Puron Refrigerant.

2. Refrigerant tubes and indoor coils must be evacuated to 500 microns to minimize contamination and moisture in the system.

METERING DEVICE

UNIT SIZE

024

030

036

042

048

060

SERIES

A,C

A,C

A,C

A,C

A,C

B,C

OUTDOOR PISTON

46

52

57

59

61

73

INDOOR TXV*

KSATX0201HSZ

KSATX0201HSZ

KSATX0301HSZ

KSATX0301HSZ

KSATX0401HSZ

KSATX0501HSZ

REQUIRED SUBCOOLING

(°F)

11

9

9

11

10

12

* TXV must be installed when indoor coil is not equipped with a Puron approved TXV. TXV listed is for any approved coil combination. All TXVs are Puron specific bi-flow hard shutoff.

UNIT SIZE–SERIES

024-A,C

030-A,C

036-A,C

042-A,C

048-A,C

060-B,C

SOUND RATING (dBA)

SOUND RATING

72

74

76

76

78

78

As an ENERGY STAR

SM partner, Bryant Heating &

Cooling Systems has determined that this product meets the ENERGY

STAR guidelines for energy efficiency.

Meets GREEN SEAL Environmental Criteria for high energy efficiency, low noise, and recycled packaging. Does not use an ozone depleting substance during manufacturing, or as a refrigerant.

A

C

T

U

R

E

R

CE

RT

IFIED

U

N

IT

A

R

Y

TO ARI

AS

C

O

AIR

CO

N

D

IT

IO

M

P

L

Y

IN

A

RI

EQUIPMENT

STANDARD 21

0

CERTIFICATION APPLIES ONLY

WHEN THE COMPLETE SYSTEM

IS LISTED WITH ARI.

—3—

REGISTERED QUALITY SYSTEM

UNIT SIZE-SERIES

Operating Weight (Lb)

ELECTRICAL

Unit Volts—Hertz—Phase

Operating Voltage Range*

Compressor Rated Load Amps

Compressor Locked Rotor Amps

Condenser Fan Motor—Full Load Amps

Minimum Unit Ampacity for Wire Sizing

Minimum Wire Size (60°C Copper) (AWG)†

Minimum Wire Size (75°C Copper) (AWG)†

Maximum Wire Length (60°C) (Ft)‡

Maximum Wire Length (75°C) (Ft)‡

Maximum Branch Circuit Fuse Size**

COMPRESSOR & REFRIGERANT

Compressor Manufacturer

Compressor Type

Refrigerant Type

Refrigerant Amount (Lb)††

OUTDOOR COIL & FAN

Coil Face Area (Sq Ft)

Fins per In.—Rows—Circuits

Fan Motor—HP & RPM

Rated Airflow (CFM)

OPTIONAL EQUIPMENT

Support Feet—4 In. (4)

Snow Stand—18 In.

Time Delay Relay

Interface Control (Energy Minder)‡‡

Service Alarm***

Outdoor Thermostat

Secondary Outdoor Thermostat

Crankcase Heater

Start Assist—Capacitor/Relay Type

Start Assist—PTC Type

Bi-Flow TXV (Hard Shutoff)

Filter Drier (Suction Line)

Evaporator Freeze Thermostat†††

Isolation Relay†††

Liquid-Line Solenoid Valve (LSV)

Low-Ambient Pressure Switch

See notes on page 5.

SPECIFICATIONS

024-A,C

214

15.1

61.0

0.8

19.7

14

14

39

37

30

7.18

18.18

25—1—2

1/8 and 825

2400

030-A,C

205

208/230—60—1

187—253

14.7

72.5

1.1

19.5

14

14

39

37

30

Copeland

Scroll

Puron

6.63

15.15

25—1—3

1/5 and 825

2800

KSASF0101AAA

KHASS0206MPK

KAATD0101TDR

KHAIC0101AAA

KHASA0101AAA

KHAOT0301FST

KHAOT0201SEC

KAACH1201AAA

KSAHS1501AAA

Standard

KSATX0201HSZ

KH45LG140 (RCD)

KAAFT0101AAA

KHAIR0101AAA

KHALS0401LLS

KSALA0301410

036-A,C

217

15.4

83.0

1.1

20.4

12

12

60

57

30

8.87

12.12

20—2—3

1/5 and 825

2800

KSATX0301HSZ

—4—

SPECIFICATIONS Continued

UNIT SIZE-SERIES

Operating Weight (Lb)

ELECTRICAL

Unit Volts—Hertz—Phase

Operating Voltage Range*

Compressor Rated Load Amps

Compressor Locked Rotor Amps

Condenser Fan Motor—Full Load Amps

Minimum Unit Ampacity for Wire Sizing

Minimum Wire Size (60°C Copper) (AWG)†

Minimum Wire Size (75°C Copper) (AWG)†

Maximum Wire Length (60°C) (Ft)‡

Maximum Wire Length (75°C) (Ft)‡

Maximum Branch Circuit Fuse Size**

COMPRESSOR & REFRIGERANT

Compressor Manufacturer

Compressor Type

Refrigerant Type

Refrigerant Amount (Lb)††

OUTDOOR COIL & FAN

Coil Face Area (Sq Ft)

Fins per In.—Rows—Circuits

Fan Motor—HP & RPM

Rated Airflow (CFM)

OPTIONAL EQUIPMENT

Support Feet—4 In. (4)

Snow Stand—18 In.

Time Delay Relay

Interface Control (Energy Minder)‡‡

Service Alarm***

Outdoor Thermostat

Secondary Outdoor Thermostat

Crankcase Heater

Start Assist—Capacitor/Relay Type

Start Assist—PTC Type

Bi-Flow TXV (Hard Shutoff)

Filter Drier (Suction Line)

Evaporator Freeze Thermostat†††

Isolation Relay†††

Liquid-Line Solenoid Valve (LSV)

Low-Ambient Pressure Switch

042-A.C

218

21.1

104.0

1.1

27.5

10

10

71

68

40

8.63

12.12

20—2—3

1/5 and 825

2800

048-A,C

266

208/230—60—1

187—253

20.5

109.0

1.4

27.0

10

10

74

70

40

Copeland

Scroll

Puron

13.25

18.18

20—2—4

1/4 and 1100

3300

060-B,C

295

27.6

158.0

1.4

35.9

8

8

86

82

60

13.25

18.18

20—2—5

1/4 and 1100

3300

KAACH1201AAA

KSAHS1501AAA

KSATX0301HSZ

KSASF0101AAA

KHASS0206MPK

KAATD0101TDR

KHAIC0101AAA

KHASA0101AAA

KHAOT0301FST

KHAOT0201SEC

Standard

Standard

KSAHS1601AAA

KSATX0401HSZ

KH45LG141 (RCD)

KAACS0201PTC

KSATX0501HSZ

KAAFT0101AAA

KHAIR0101AAA

KHALS0401LLS

KSALA0301410

* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.

† If other than uncoated (non-plated), 60°C or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than

10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable

(NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26.

‡ Length shown is as measured 1 way along the wire path between the unit and the service panel for a voltage drop not to exceed 2 percent.

** Time-delay fuse or circuit breaker.

†† The factory refrigerant charge is for 15 ft of interconnecting tubing. For tubing lengths other than 15 ft, refer to the Residential Split-Systems Long-Line

Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using Puron (R-410A).

‡‡ Outdoor thermostat required.

*** For indicator function, thermostat specified must be used and wired according to service alarm Installation Instructions.

††† Use with low-ambient pressure switch.

NOTE: Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

—5—

THERMOSTATS AND ACCESSORIES

Thermostat—Auto Changeover, Non-Programmable, °F/°C, 2-Stage Heat, 1-Stage Cool

Thermostat—Auto Changeover, 7-Day Programmable, °F/°C, 2-Stage Heat, 1-Stage Cool

Thermostat—Auto Changeover, 7-Day Programmable, °F/°C, Dual Fuel, Includes Outdoor

Sensor (TSTATXXSEN01)

Thermidistat™ Control—Non-Programmable/Programmable Thermostat with Humidity

Control (For use in Dual Fuel, AC, HP, and 2S applications. Includes Outdoor Air

Temperature Sensor.)

Builder’s Thermostat—Manual Changeover, Non-Programmable, °F/°C, 2-Stage Heat,

1-Stage Cool, Heat Pump

Outdoor Air Temperature Sensor

Backplate for Non-Programmable Thermostat

Backplate for Programmable Thermostat and Thermidistat™ Control

Backplate for Builder’s Thermostat

Thermostat Conversion Kit (4 to 5 Wire)—10 Pack

TSTATBBNHP01-B

TSTATBBPHP01-B

TSTATBBPDF01-B*

TSTATBBPRH01-B*

TSTATBBBHP01*

TSTATXXSEN01

TSTATXXNBP01†

TSTATXXPBP01†

TSTATXXBBP01†

TSTATXXCNV10‡

* Do not use in zoning heat pump applications.

† This plate is designed to cover surrounding wall area located behind thermostat.

‡ Thermostat conversion kit is a 24-vac accessory that can turn a 4-wire thermostat application into a 5-wire application. This kit can also be used to replace a broken thermostat wire, or add an extra wire when needed.

** Outdoor air temperature sensor is an accessory for all Bryant electronic thermostats, except the non-programmable air conditioner version and builder’s thermostats. It allows the temperature at a remote location (outdoors) to be displayed on the thermostat.

The outdoor air temperature sensor must be used with the dual fuel thermostat.

The outdoor air temperature sensor is included with the Thermidistat Control and dual fuel thermostat.

ACCESSORY

Crankcase Heater

Evaporator Freeze Thermostat

Compressor Start Assist—Capacitor and Relay

Puron Low-Ambient Pressure Switch

Wind Baffle

Support Feet

Puron Hard Shutoff TXV

ACCESSORY USAGE GUIDELINE

REQUIRED FOR LOW-AMBIENT

APPLICATIONS

(Below 55°F)

Yes

Yes

Yes

Yes

See Low-Ambient

Pressure Switch Instructions

Recommended

Yes†

REQUIRED FOR LONG-LINE

APPLICATIONS*

(Over 50 Ft)

Yes

No

Yes

No

No

Puron Liquid-Line Solenoid Valve for Heating No

No

Yes†

See Long-Line

Application Guideline

* For tubing line sets between 50 and 175 ft and/or 20 ft elevation difference between indoor and outdoor units, refer to the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using Puron Refrigerant.

† Required for all applications.

—6—

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

1.

Compressor Start Assist—Capacitor and Relay

Start capacitor and start relay which gives a “hard” boost to compressor motor at each start-up.

SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C).

Units installed with Low Ambient Pressure Switch. Units installed with Liquid-Line Solenoid Valve.

2.

Compressor Start Assist—PTC Type

Solid-state electrical device which gives a “soft” boost to the compressor at each start-up.

SUGGESTED USE: Installations with marginal power supply.

3.

Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.

SUGGESTED USE: When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with Low-Ambient Pressure Switch.)

All commercial installations.

4.

Evaporator Freeze Thermostat

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.

SUGGESTED USE: All units to which Low-Ambient Pressure Switch has been added.

5.

Filter Drier—Suction Line

A device for removing contaminants from refrigerant circulating in a heat pump system; 2-direction flow for heat pumps.

SUGGESTED USE: Split-system heat pumps.

6.

Interface Control (Energy Minder)

An electric control for controlling a heat pump and gas or oil furnace system for maximum energy savings. It allows heat pump to operate down to a predetermined economic balance point temperature, then switches to allow furnace operation only below that temperature. Requires outdoor thermostat

(Item 11) to be adjusted for economic balance point temperature.

SUGGESTED USE: For heat pump and gas- or oil-fired furnace combination systems unless Duel Fuel Thermostat or Thermidistat™ Control is used.

7.

Isolation Relay

An SPDT relay which switches the Low-Ambient Controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.

SUGGESTED USE: All heat pumps where Low-Ambient Pressure Switch has been added.

8.

Liquid-Line Solenoid Valve (LSV)

An electrically operated shutoff valve to be installed at the outdoor unit which stops and starts refrigerant liquid flow in response to compressor operation.

Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.

SUGGESTED USE: In long-line applications. (Refer to the Residential Split-System Long-Line Application Guideline and Service Manual.)

9.

Low-Ambient Pressure Switch

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig). The control will maintain working head pressure at low-ambient temperatures down to

0°F (–17.8°C) when properly installed.

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).

10.

Outdoor Air Temperature Sensor

A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.

SUGGESTED USE: All Bryant programmable thermostats.

11.

Outdoor Thermostat

An SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point.

SUGGESTED USE: Heat pump installations with multiple-stage supplemental heaters.

12.

Secondary Outdoor Thermostat

An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the second-stage set point.

SUGGESTED USE: Heat pump installations where 3-stage operation of supplemental heaters is desired.

13.

Service Alarm

A current-sensing lockout relay which provides immediate notification that compressor is not operating during a call for heating or cooling. Used with proper room thermostat, a thermostat signal is turned on signifying service is required. This can minimize electrical cost increase due to operation of supplemental heaters only.

SUGGESTED USE: As a feature to notify owner immediately when the system is not operating most efficiently.

14.

Snow Stand

Coated wire rack which supports unit 18 in. above mounting pad to allow for drainage from unit base.

SUGGESTED USE: Heat pump installations in heavy snowfall areas.

Heat pump installations in snowdrift locations.

Heat pump installations in areas of prolonged subfreezing temperatures.

All commercial installations.

15.

Support Feet

Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base; minimizes corrosion.

SUGGESTED USE: Coastal installations.

Windy areas or where debris is normally circulating.

Rooftop installations.

16.

Thermostatic Expansion Valve (TXV)—Bi-Flow

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube.

SUGGESTED USE: Required for all installations.

17.

Time-Delay Relay

An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.

SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.)

Required for use on all zoning systems.

—7—

COMBINATION RATINGS*

UNIT

SIZE-

SERIES

024-A,C

030-A,C

036-A,C

042-A,C

048-A,C

ARI STANDARD RATINGS*

Cooling

INDOOR

UNIT CFM†† TC

Seasonal Efficiency SEER

Factory-

Supplied

Enhancement

Standard

Rating

FX4ANF030†

F(A,B)4AN(F,C)030

FC4BNF030

FK4CNF001

FK4CNF002

FK4CNF003

FV4ANF002

FV4ANF003

CC5A/CD5AA036

CD5AW036

CE3AA036

CJ5A/CK5A/CK5BA036

CJ5A/CK5A/CK5BW036

CJ5A/CK5A/CK5BN036

CK3BA036

900

900

800

800

800

800

800

800

800

800

700

700

700

700

700

25,000 TDR&TXV 13.00

23,600 TDR —

24,000

24,400

TDR

TDR

25,200

25,200

TDR

TDR

25,200 TDR&TXV 14.20

25,200 TDR&TXV 14.50

24,000

24,000

23,800

24,200

24,200

24,200

24,200

NONE

NONE

NONE

NONE

NONE

NONE

NONE

FX4ANF030†

F(A,B)4AN(F,C)036

FC4BNF036

FK4CNF001

FK4CNF002

1050 29,000 TDR&TXV 13.00

1050 28,400

1050 28,400

875

875

28,600

28,800

TDR

TDR

TDR

TDR

FK4CNF003

FV4ANF002

FV4ANF003

FX4ANF036

CC5A/CD5AA036

CD5AW036

CE3AA036

CJ5A/CK5A/CK5BN036

875

875

875

29,000 TDR —

29,200 TDR&TXV 14.00

29,400 TDR&TXV 14.50

1050 29,000 TDR&TXV 12.30

1080

1080

1050

1000

28,800

28,800

28,600

28,800

CJ5A/CK5A/CK5BW036 1050 28,800

CK3BA036 1050 28,800

NONE

NONE

NONE

NONE

NONE

NONE

FX4ANF042†

F(A,B)4AN(F,B,C)042

FC4BN(F,B)042

FK4CNF003

FK4CNF005

FV4ANF003

FV4ANF005

CC5A/CD5AA042

CC5A/CD5AW042

CC5A/CD5AC048

CC5A/CD5AW048

CD5AA048

CE3AA042

CE3AA048

CJ5A/CK5A/CK5BA042

1125

1125

1125 33,600

1050 34,000

1050 35,400

1050 34,400 TDR&TXV 13.70

1050

35,000

33,600

35,600

1125 34,000

1260 33,600

1260 33,600

1275 34,000

1275 34,000

1125 34,000

1125 34,200

1125 33,800

CJ5A/CK5A/CK5BN042

CJ5A/CK5A/CK5BA048

1125 33,800

1125 34,200

CJ5A/CK5A/CK5BN048 1125 34,200

CJ5A/CK5A/CK5BW048 1125 34,200

CK3BA042

CK3BA048

1125 33,800

1125 34,200

TDR&TXV

TDR

TDR

TDR

TDR

TDR&TXV

NONE

NONE

NONE

NONE

NONE

NONE

NONE

NONE

NONE

NONE

NONE

NONE

NONE

NONE

13.00

14.00

FV4ANF003†

F(A,B)4AN(F,B,C)048

FC4BN(F,B)048

FK4CNF003

FK4CNF005

FV4ANF005

1225 40,500 TDR&TXV 13.00

1400 40,000 TDR —

1400 40,500

1225 40,500

TDR

TDR

1225 41,000 TDR —

1225 41,000 TDR&TXV 14.00

FX4ANF042

CE3AA048

CJ5A/CK5A/CK5BA048

CJ5A/CK5A/CK5BN048

1400

1400

1400

1400

40,500

40,500

40,000

40,000

CJ5A/CK5A/CK5BW048 1400 40,000

CK3BA048 1400 4,0000

TDR&TXV

NONE

NONE

NONE

NONE

NONE

12.00

FV4ANF005†

F(A,B)4AN(F,B,C)060

FB4ANB070

FC4BN(F,B)060

FC4BNB070

FK4CNF005

FK4CNB006

FV4ANB006

FX4ANF048

FX4ANB060

CE3AA060

1400 45,500 TDR&TXV 13.50

1400 44,500

1400 46,000

1400 44,500

1400 46,000

1400 45,500

TDR

TDR

TDR

TDR

TDR

1400 46,500 TDR —

1400 46,500 TDR&TXV 14.10

1400 45,000 TDR&TXV 12.50

1400 45,500 TDR&TXV 12.60

1400 45,500 NONE —

Field-Supplied

Accessory‡

Puron

TXV

Puron TXV

& TDR**

12.20

12.20

13.70

13.70

14.20

12.50

12.50

13.80

14.00

14.20

12.30

12.30

13.70

14.00

11.70

12.50

11.70

12.50

13.20

14.00

12.00

12.00

13.00

13.50

EER

High-Temp

TC

11.10

25,000

10.95

24,400

10.95

24,400

12.00

23,800

12.35

25,000

12.60

25,200

12.05

25,200

12.35

25,000

13.00

11.10

24,800

13.00

11.10

24,800

12.60

11.05

24,600

13.00

11.20

24,800

13.00

11.20

24,800

13.00

11.20

24,800

13.00

11.20

24,800

11.15

30,000

10.75

29,800

10.75

29,800

12.10

28,600

12.15

29,000

12.55

28,600

12.15

29,000

12.55

28,600

10.85

30,000

13.00

11.25

29,400

13.00

11.25

29,400

12.70

11.15

29,200

12.70

11.25

29,400

13.00

11.30

29,400

13.00

11.30

29,400

10.80

35,000

10.65

34,200

10.65

34,200

11.80

33,600

12.30

33,800

11.80

33,600

12.30

34,000

12.50

10.65

34,000

12.20

10.50

34,000

12.20

10.50

33,600

12.50

10.60

34,200

12.50

10.65

34,200

12.50

10.65

34,200

12.50

10.70

34,200

12.50

10.60

34,200

12.50

10.60

34,200

12.50

10.70

34,400

12.50

10.70

34,400

12.50

10.70

34,400

12.50

10.60

34,200

12.50

10.70

34,400

11.00

40,500

10.25

41,500

10.25

41,500

11.10

40,000

11.55

40,000

11.55

40,000

— 10.25

41,500

12.00

10.35

41,500

12.00

10.30

41,500

12.00

10.30

41,500

12.00

10.30

41,500

12.00

10.30

41,500

11.60

47,500

10.20

48,500

10.90

48,000

10.20

48,000

10.90

48,000

11.60

48,000

12.05

12.05

10.75

10.90

48,000

48,000

48,000

48,000

12.50

10.80

48,000

COP

3.56

3.42

3.42

3.54

3.68

3.68

3.68

3.70

3.52

3.52

3.52

3.44

3.54

3.56

3.56

3.28

3.28

3.20

3.34

3.34

3.34

3.34

3.30

3.18

3.18

3.30

3.58

3.54

3.44

3.44

3.20

3.16

3.10

3.24

3.26

3.26

3.30

3.26

3.40

3.26

3.26

3.40

3.70

3.44

3.70

3.26

3.32

3.32

3.32

3.26

3.32

3.58

3.32

3.54

3.32

3.54

3.58

3.76

3.76

3.42

3.54

3.40

3.36

3.34

3.38

3.32

3.56

3.56

3.40

3.32

3.34

3.34

3.34

3.34

See notes on page 9.

Heating

Low-Temp

TC

18,500

18,700

18,700

17,800

17,900

17,700

17,900

17,700

18,800

18,500

18,500

18,500

18,500

18,500

18,500

16,600

16,500

16,500

16,000

16,100

16,000

16,100

15,900

16,600

16,600

16,600

16,600

16,600

16,600

16,600

21,600

21,400

21,400

20,600

20,800

20,600

20,800

21,400

21,400

21,400

21,400

21,400

21,600

21,600

21,600

21,600

21,600

21,600

21,600

21,600

21,600

27,600

29,000

28,600

29,000

28,600

27,800

27,600

27,600

28,400

28,600

28,400

25,400

26,600

26,600

25,400

25,200

25,200

26,600

26,400

26,400

26,400

26,400

26,400

COP

2.38

2.32

2.32

2.44

2.48

2.50

2.48

2.52

2.36

2.38

2.38

2.36

2.38

2.40

2.40

2.36

2.36

2.34

2.38

2.38

2.38

2.38

2.38

2.32

2.32

2.42

2.54

2.54

2.48

2.48

2.26

2.24

2.22

2.28

2.28

2.28

2.30

2.28

2.34

2.28

2.28

2.40

2.52

2.40

2.52

2.28

2.30

2.30

2.30

2.28

2.30

2.46

2.26

2.38

2.26

2.38

2.46

2.54

2.54

2.34

2.38

2.34

2.46

2.42

2.42

2.44

2.56

2.56

2.42

2.40

2.40

2.40

2.40

2.40

HSPF

8.00

7.40

7.40

7.80

8.00

8.00

8.10

8.10

8.00

7.65

7.65

7.45

7.65

7.70

7.70

7.50

7.50

7.40

7.50

7.50

7.50

7.50

8.00

7.50

7.50

7.75

8.00

8.00

8.00

8.00

7.30

7.30

7.30

7.30

7.30

7.40

7.45

7.40

7.70

7.40

7.40

7.70

8.00

7.80

8.10

7.40

7.50

7.50

7.50

7.40

7.50

8.50

7.80

8.00

7.70

8.00

8.20

8.50

8.60

8.00

8.10

8.00

7.70

7.50

7.55

7.40

8.00

8.10

7.55

7.40

7.50

7.50

7.50

7.50

—8—

COMBINATION RATINGS Continued

UNIT

SIZE-

SERIES

048-A,C

060-B,C

INDOOR

UNIT

CJ5A/CK5A/CK5BA060

CJ5A/CK5A/CK5BN060

CJ5A/CK5A/CK5BX060

CK3BA060

FV4ANB006†

FB4ANB070

FC4BNB070

FK4CNB006

FX4ANB060

CC5A/CD5AW060

CJ5A/CK5A/CK5BX060

CFM†† TC

Factory-

Supplied

Enhancement

Cooling

Standard

Rating

1400 45,000

1400 45,500

1400 45,500

1400 45,000

NONE

NONE

NONE

NONE

1750 58,000 TDR&TXV 13.00

1750 57,000 TDR —

1750 57,000

1750 58,000

TDR

TDR

1750 57,000 TDR&TXV 12.00

1750 56,000 NONE —

1750 56,500 NONE —

TXV

12.00

12.00

12.80

ARI STANDARD RATINGS*

Seasonal Efficiency SEER

Field-Supplied

Accessory‡

Puron Puron TXV

& TDR**

12.50

13.00

13.00

12.50

EER

10.75

10.90

10.90

10.75

High-Temp

TC

48,000

48,500

48,500

48,000

10.75

60,000

10.20

60,000

10.20

60,000

10.75

59,500

— 10.20

60,000

12.50

10.45

58,500

12.50

10.55

59,000

COP

3.50

3.52

3.52

3.50

3.56

3.44

3.44

3.56

3.44

3.26

3.44

Heating

Low-Temp

TC

28,600

28,600

28,600

28,600

37,000

37,800

37,800

37,000

37,800

36,800

37,000

COP

2.38

2.38

2.38

2.38

2.54

2.46

2.46

2.54

2.46

2.42

2.50

* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:

Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit.

High-Temp Heating Standard: 70°F (21°C) db indoor entering air temperature and 47°F (8°C) db 43°F (6°C) wb air entering outdoor unit.

Low-Temp Heating Standard: 70°F (21°C) db indoor entering air temperature and 17°F (–9°C) db 15°F (–10°C) wb air entering outdoor unit.

† Outdoor section/indoor section combination tested in accordance with DOE test procedure for heat pumps.

‡ Based on computer simulation. TXV must be Puron compatible and hard shutoff type.

** In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance.

Use either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. All Bryant furnaces are equipped with TDR except for the

394HAD.

†† Indoor Airflow

COP

EER

— Coefficient of Performance

— Energy Efficiency Ratio

HSPF

SEER

TC

TDR

TXV

— Heating Seasonal Performance Factor

— Seasonal Energy Efficiency Ratio

— Total Capacity (Btuh)

— Time-Delay Relay

— Thermostatic Expansion Valve

HSPF

8.20

8.25

8.25

8.20

8.00

7.80

7.80

8.00

7.80

7.50

7.70

—9—

BUILDING HEAT LOSS, 1000 BTU/HR

UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR

—10—

KW

DETAILED COOLING CAPACITIES*

EVAP

AIR

CFM EWB

75

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

85

Capacity

MBtuh†

Total Sens‡

CONDENSER ENTERING AIR TEMPERATURES °F

Total

Sys

Kw**

95

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

105

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

115

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

125

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

700

800

900

72

67

29.7

14.5

1.85

28.4

14.0

2.07

26.9

13.5

2.31

25.4

12.9

2.57

23.8

12.3

2.85

22.0

11.7

3.14

27.2

18.2

1.85

25.9

17.6

2.06

24.6

17.1

2.30

23.2

16.5

2.55

21.7

15.9

2.83

20.1

15.3

3.12

63†† 25.3

17.7

1.85

24.1

17.2

2.06

22.9

16.6

2.29

21.6

16.1

2.54

20.2

15.5

2.82

18.7

14.8

3.11

62 24.8

21.7

1.84

23.7

21.2

2.06

22.5

20.6

2.29

21.3

20.0

2.54

20.0

19.4

2.81

18.6

18.5

3.11

57 23.7

23.7

1.84

22.8

22.8

2.06

21.9

21.9

2.29

20.9

20.9

2.54

19.8

19.8

2.81

18.6

18.6

3.11

72

67

30.3

27.7

15.2

19.3

1.88

1.88

28.9

26.4

14.6

18.7

2.11

2.10

27.3

25.0

14.1

18.2

2.35

2.34

25.8

23.6

13.6

17.6

2.61

2.59

24.1

22.0

13.0

17.0

2.88

2.87

22.2

20.4

12.3

16.4

3.18

3.16

63†† 25.8

18.8

1.88

24.6

18.2

2.10

23.3

17.7

2.33

21.9

17.1

2.58

20.5

16.5

2.85

19.0

15.8

3.15

62

57

25.4

23.3

1.88

24.2

22.7

2.10

23.0

22.1

2.33

21.8

21.4

2.58

20.5

20.5

2.85

19.2

19.2

3.15

24.7

24.7

1.88

23.7

23.7

2.10

22.7

22.7

2.33

21.6

21.6

2.58

20.5

20.5

2.85

19.2

19.2

3.15

72

67

30.8

15.8

1.92

29.3

15.3

2.14

27.7

14.7

2.38

26.1

14.2

2.64

24.3

13.6

2.92

22.4

12.9

3.22

28.2

20.4

1.92

26.8

19.8

2.14

25.3

19.3

2.37

23.9

18.7

2.63

22.3

18.1

2.90

20.5

17.4

3.20

63†† 26.2

19.8

1.92

24.9

19.2

2.13

23.6

18.6

2.37

22.2

18.1

2.62

20.8

17.4

2.89

19.1

16.7

3.19

62 25.9

24.7

1.92

24.7

24.1

2.13

23.5

23.3

2.37

22.3

22.3

2.62

21.1

21.1

2.89

19.7

19.7

3.19

57 25.5

25.5

1.91

24.5

24.5

2.13

23.4

23.4

2.37

22.3

22.3

2.62

21.1

21.1

2.89

19.7

19.7

3.19

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FX4ANF

Size

030

Capacity

1.00

Power

1.00

Indoor

Section

CE3AA

Size

030

Capacity

0.94

Power

1.00

F(A,B)4AN(F,C)

FC4BNF

FK4CNF

030

030

001

0.94

0.96

0.98

1.00

1.00

0.93

CJ5A/CK5A/CK5BA

036

030

036

0.95

0.94

0.97

1.00

1.00

1.00

FV4ANF

002

003

002

003

1.01

1.01

1.01

1.01

0.93

0.91

0.93

0.91

CJ5A/CK5A/CK5BN

CJ5A/CK5A/CK5BW

CK3BA

036

030

036

030

036

0.97

0.94

0.97

0.94

0.97

1.00

1.00

1.00

1.00

1.00

See notes on page 14.

—11—

DETAILED COOLING CAPACITIES* Continued

EVAP

AIR

CFM EWB

1 825

1050

1250

75

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

85

Capacity

MBtuh†

Total Sens‡

CONDENSER ENTERING AIR TEMPERATURES °F

Total

Sys

Kw**

95

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

105

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

115

Capacity

MBtuh†

Total Sens‡

650AN030-A,C Outdoor Section With FX4ANF030 Indoor Section

Total

Sys

Kw**

125

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

72

67

34.3

17.2

2.07

32.6

16.6

2.31

30.9

15.9

2.58

29.0

15.3

2.87

27.0

14.6

3.20

24.8

13.8

3.56

31.4

21.7

2.06

29.9

21.1

2.29

28.3

20.5

2.56

26.6

19.8

2.86

24.8

19.1

3.18

22.7

18.3

3.54

63†† 29.2

21.1

2.04

27.8

20.5

2.28

26.4

19.9

2.55

24.8

19.2

2.84

23.1

18.5

3.17

21.2

17.7

3.53

62 28.8

26.2

2.04

27.4

25.5

2.28

26.0

24.8

2.55

24.5

24.0

2.84

23.0

23.0

3.17

21.4

21.4

3.53

57 27.8

27.8

2.04

26.7

26.7

2.27

25.6

25.6

2.54

24.3

24.3

2.84

23.0

23.0

3.17

21.4

21.4

3.53

72

67

35.2

32.4

18.7

24.3

2.14

2.13

33.5

30.7

18.1

23.7

2.38

2.36

31.6

29.0

17.4

23.0

2.65

2.63

29.7

27.2

16.8

22.3

2.94

2.93

27.6

25.3

16.1

21.6

3.27

3.25

25.2

23.2

15.3

20.7

3.62

3.61

63†† 30.2

23.6

2.11

28.6

22.9

2.35

27.0

22.3

2.62

25.4

21.5

2.91

23.6

20.8

3.24

21.6

19.9

3.59

62

57

29.9

29.4

2.11

28.6

28.5

2.35

27.2

27.2

2.62

25.8

25.8

2.91

24.3

24.3

3.24

22.5

22.5

3.60

29.8

29.8

2.11

28.5

28.5

2.35

27.2

27.2

2.62

25.8

25.8

2.91

24.3

24.3

3.24

22.6

22.6

3.60

72

67

35.8

20.0

2.20

34.0

19.4

2.44

32.1

18.7

2.71

30.0

18.1

3.00

27.8

17.3

3.33

25.4

16.5

3.68

32.9

26.5

2.19

31.2

25.8

2.42

29.4

25.1

2.69

27.6

24.4

2.98

25.6

23.6

3.31

23.4

22.6

3.67

63†† 30.7

25.6

2.17

29.1

24.9

2.41

27.5

24.2

2.67

25.7

23.4

2.97

23.9

22.6

3.30

21.9

21.5

3.65

62 31.0

31.0

2.17

29.7

29.7

2.41

28.3

28.3

2.68

26.8

26.8

2.98

25.1

25.1

3.31

23.2

23.2

3.67

57 31.0

31.0

2.17

29.7

29.7

2.41

28.3

28.3

2.68

26.8

26.8

2.98

25.1

25.1

3.31

23.2

23.2

3.67

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FX4ANF

F(A,B)4AN(F,C)

FC4BNF

FK4CNF

Size

030

030

036

030

036

001

Capacity

1.00

0.97

0.98

0.97

0.98

0.99

Power

1.00

1.00

1.03

1.00

1.03

0.92

Indoor

Section

FV4ANF

FX4ANF

CE3AA

CJ5A/CK5A/CK5BN

CJ5A/CK5A/CK5BW

Size

002

003

036

036

036

036

Capacity

1.01

1.01

1.00

0.99

0.99

0.99

Power

0.93

0.90

1.03

1.00

1.00

1.00

002

003

0.99

1.00

0.93

0.90

CK3BA 036

650AN036-A,C Outdoor Section With FX4ANF042 Indoor Section

0.99

1.00

1125

1250

1375

72

67

42.3

21.3

2.64

40.3

20.6

2.93

38.3

19.8

3.26

36.0

19.1

3.61

33.7

18.3

4.00

31.0

17.4

4.40

38.7

27.3

2.63

36.9

26.5

2.93

35.0

25.8

3.25

33.0

25.0

3.60

30.8

24.1

3.98

28.3

23.2

4.38

63†† 36.1

26.5

2.63

34.4

25.7

2.92

32.6

25.0

3.24

30.6

24.1

3.59

28.6

23.3

3.96

26.3

22.3

4.36

62 35.5

33.0

2.63

33.9

32.2

2.92

32.2

31.4

3.24

30.4

30.3

3.59

28.7

28.7

3.96

26.8

26.8

4.37

57 34.7

34.7

2.63

33.3

33.3

2.92

31.9

31.9

3.24

30.4

30.4

3.59

28.7

28.7

3.96

26.8

26.8

4.37

72

67

42.7

39.2

22.1

28.6

2.69

2.68

40.7

37.3

21.4

27.9

2.98

2.98

38.6

35.4

20.6

27.1

3.31

3.30

36.3

33.2

19.9

26.3

3.66

3.65

33.9

31.0

19.0

25.4

4.05

4.03

31.2

28.5

18.1

24.5

4.46

4.43

63†† 36.6

27.8

2.68

34.8

27.0

2.97

32.9

26.2

3.29

31.0

25.4

3.64

28.8

24.5

4.01

26.5

23.5

4.41

62

57

36.1

34.8

2.68

34.5

33.9

2.97

32.8

32.8

3.29

31.2

31.2

3.64

29.4

29.4

4.02

27.4

27.4

4.42

35.7

35.7

2.68

34.3

34.3

2.97

32.8

32.8

3.29

31.2

31.2

3.64

29.4

29.4

4.02

27.4

27.4

4.42

72

67

43.1

22.8

2.74

41.1

22.1

3.03

38.9

21.4

3.36

36.6

20.6

3.71

34.1

19.8

4.10

31.3

18.9

4.51

39.6

30.0

2.73

37.7

29.2

3.03

35.6

28.4

3.35

33.5

27.6

3.70

31.3

26.7

4.08

28.7

25.7

4.48

63†† 36.9

29.0

2.73

35.1

28.2

3.02

33.2

27.4

3.34

31.2

26.6

3.69

29.0

25.7

4.06

26.7

24.6

4.46

62 36.7

36.4

2.73

35.1

35.1

3.02

33.5

33.5

3.34

31.8

31.8

3.69

30.0

30.0

4.07

28.0

28.0

4.48

57 36.6

36.6

2.73

35.1

35.1

3.02

33.5

33.5

3.34

31.8

31.8

3.69

30.0

30.0

4.07

27.9

27.9

4.48

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FX4ANF

Size

042

Capacity

1.00

Power

1.00

Indoor

Section

CE3AA

Size

042

Capacity

0.97

Power

1.00

F(A,B)4AN(F,B,C)

FC4BN(F,B)

042

042

0.96

0.96

1.00

1.00

CJ5A/CK5A/CK5BA

048

042

0.98

0.97

1.00

1.00

FK4CNF

FV4ANF

CC5A/CD5AA

003

005

003

005

042

0.97

1.01

0.98

1.02

0.99

0.91

0.91

0.91

0.91

1.00

CJ5A/CK5A/CK5BN

CJ5A/CK5A/CK5BW

CK3BA

048

042

048

048

042

048

0.98

0.97

0.98

0.98

0.97

0.98

1.00

1.00

1.00

1.00

1.00

1.00

See notes on page 14.

—12—

DETAILED COOLING CAPACITIES* Continued

EVAP

AIR

CFM EWB

1225

1400

1575

75

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

85

Capacity

MBtuh†

Total Sens‡

CONDENSER ENTERING AIR TEMPERATURES °F

Total

Sys

Kw**

95

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

105

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

115

Capacity

MBtuh†

Total Sens‡

650AN042-A,C Outdoor Section With FV4ANF003 Indoor Section

Total

Sys

Kw**

125

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

72

67

48.5

24.4

2.95

46.4

23.6

3.32

44.1

22.8

3.72

41.7

21.9

4.17

39.0

21.0

4.65

36.1

20.0

5.17

44.6

30.9

2.91

42.6

30.1

3.28

40.5

29.2

3.68

38.3

28.3

4.12

35.8

27.4

4.61

33.2

26.3

5.12

63†† 41.7

30.1

2.89

39.8

29.3

3.25

37.8

28.4

3.65

35.7

27.5

4.09

33.4

26.5

4.57

31.0

25.5

5.09

62 41.0

37.2

2.88

39.2

36.3

3.24

37.3

35.3

3.65

35.3

34.3

4.09

33.2

33.0

4.57

31.1

31.1

5.09

57 39.7

39.7

2.87

38.2

38.2

3.24

36.7

36.7

3.64

35.0

35.0

4.08

33.1

33.1

4.57

31.1

31.1

5.09

72

67

49.4

45.4

25.6

32.9

2.99

2.96

47.1

43.3

24.8

32.0

3.36

3.32

44.8

41.2

23.9

31.2

3.77

3.73

42.2

38.8

23.1

30.2

4.22

4.17

39.5

36.3

22.1

29.3

4.70

4.65

36.5

33.6

21.1

28.2

5.22

5.17

63†† 42.5

32.0

2.93

40.5

31.1

3.30

38.4

30.2

3.70

36.2

29.3

4.14

33.9

28.3

4.62

31.3

27.2

5.14

62

57

41.9

39.7

2.93

40.0

38.7

3.29

38.2

37.6

3.70

36.2

36.2

4.14

34.2

34.2

4.62

32.0

32.0

5.15

41.2

41.2

2.92

39.6

39.6

3.29

37.9

37.9

3.69

36.1

36.1

4.14

34.2

34.2

4.62

32.0

32.0

5.15

72

67

50.0

26.7

3.04

47.7

25.9

3.41

45.3

25.1

3.81

42.7

24.2

4.26

39.9

23.2

4.74

36.8

22.2

5.26

46.0

34.7

3.00

43.9

33.9

3.37

41.6

33.0

3.77

39.3

32.1

4.22

36.7

31.1

4.70

33.9

29.9

5.22

63†† 43.1

33.7

2.98

41.0

32.8

3.34

38.9

31.9

3.74

36.7

31.0

4.19

34.3

29.9

4.66

31.6

28.8

5.18

62 42.7

41.9

2.97

40.9

40.7

3.34

39.0

39.0

3.74

37.1

37.1

4.19

35.1

35.1

4.68

32.8

32.8

5.20

57 42.4

42.4

2.97

40.8

40.8

3.34

39.0

39.0

3.74

37.1

37.1

4.19

35.1

35.1

4.68

32.8

32.8

5.20

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FV4ANF

F(A,B)4AN(F,B,C)

FC4BN(F,B)

FK4CNF

Size

003

048

048

003

Capacity

1.00

0.99

1.00

1.00

Power

1.00

1.07

1.09

1.00

Indoor

Section

CE3AA

CJ5A/CK5A/CK5BA

CJ5A/CK5A/CK5BN

CJ5A/CK5A/CK5BW

Size

048

048

048

048

Capacity

1.00

0.99

0.99

0.99

Power

1.08

1.08

1.08

1.08

FV4ANF

FX4ANF

005

005

042

1.01

1.01

1.00

0.98

0.98

1.09

CK3BA 048

0.99

1.08

650AN048-A,C Outdoor Section With FV4ANF005 Indoor Section

1400

1600

1800

72 54.7

27.7

3.20

52.2

26.8

3.56

49.6

25.9

3.96

46.9

24.9

4.41

43.9

23.9

4.90

40.7

22.8

5.43

67 50.2

35.2

3.16

47.9

34.3

3.52

45.5

33.3

3.92

43.0

32.3

4.36

40.3

31.3

4.85

37.4

30.1

5.39

63†† 46.8

34.3

3.13

44.7

33.3

3.49

42.4

32.4

3.89

40.1

31.3

4.33

37.6

30.3

4.82

34.9

29.1

5.36

62

57

46.1

44.9

42.5

44.9

3.12

3.11

44.0

43.2

41.5

43.2

3.48

3.47

42.0

41.4

40.5

41.4

3.88

3.88

39.7

39.6

39.3

39.6

4.33

4.33

37.5

37.5

37.5

37.5

4.82

4.82

35.2

35.2

35.2

35.2

5.37

5.37

72

67

55.6

29.1

3.26

53.0

28.1

3.62

50.3

27.2

4.02

47.4

26.2

4.47

44.4

25.2

4.96

41.1

24.1

5.49

51.1

37.5

3.22

48.7

36.6

3.58

46.2

35.6

3.98

43.6

34.6

4.42

40.8

33.5

4.91

37.8

32.3

5.45

63†† 47.7

36.5

3.19

45.4

35.5

3.55

43.1

34.5

3.95

40.7

33.5

4.39

38.1

32.4

4.88

35.3

31.2

5.42

62 47.1

45.5

3.18

45.1

44.4

3.54

42.9

42.9

3.95

41.0

41.0

4.39

38.8

38.8

4.89

36.3

36.3

5.43

57 46.7

46.7

3.18

44.8

44.8

3.54

42.9

42.9

3.94

40.9

40.9

4.39

38.8

38.8

4.89

36.4

36.4

5.43

72

67

56.3

51.7

30.4

39.7

3.32

3.28

53.6

49.3

29.4

38.8

3.68

3.64

50.8

46.7

28.5

37.8

4.08

4.04

47.9

44.1

27.5

36.8

4.53

4.48

44.8

41.2

26.5

35.7

5.01

4.97

41.4

38.2

25.4

34.4

5.55

5.51

63†† 48.3

38.5

3.24

46.0

37.5

3.60

43.6

36.5

4.00

41.1

35.5

4.45

38.5

34.4

4.94

35.7

33.1

5.48

62

57

48.2

48.1

3.24

46.2

46.2

3.61

44.2

44.2

4.01

42.1

42.1

4.46

39.8

39.8

4.95

37.3

37.3

5.50

48.1

48.1

3.24

46.2

46.2

3.60

44.2

44.2

4.01

42.1

42.1

4.46

39.8

39.8

4.95

37.3

37.3

5.50

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FV4ANF

Size

005

Capacity

1.00

Power

1.00

Indoor

Section

FX4ANF

Size

048

Capacity

0.99

Power

1.06

F(A,B)4AN(F,B,C)

FB4ANB

FC4BN(F,B)

FC4BNB

FK4CNB

FK4CNF

FV4ANB

060

070

060

070

006

005

006

0.98

1.01

0.98

1.01

1.02

1.00

1.02

1.10

1.06

1.10

1.06

0.98

1.00

0.98

FX4ANB

CE3AA

CJ5A/CK5A/CK5BA

CJ5A/CK5A/CK5BN

CJ5A/CK5A/CK5BX

CK3BA

060

060

060

060

060

060

1.00

1.00

0.99

1.00

1.00

0.99

1.06

1.06

1.06

1.06

1.06

1.06

See notes on page 14.

—13—

DETAILED COOLING CAPACITIES* Continued

EVAP

AIR

CFM EWB

1750

2000

2250

75

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

85

Capacity

MBtuh†

Total Sens‡

CONDENSER ENTERING AIR TEMPERATURES °F

Total

Sys

Kw**

95

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

105

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

115

Capacity

MBtuh†

Total Sens‡

650AN060-B,C Outdoor Section With FV4ANB006 Indoor Section

Total

Sys

Kw**

125

Capacity

MBtuh†

Total Sens‡

Total

Sys

Kw**

72

67

70.1

35.6

4.43

66.6

34.4

4.92

63.1

33.1

5.47

59.2

31.7

6.07

55.0

30.3

6.73

50.2

28.7

7.42

64.4

45.5

4.35

61.3

44.2

4.85

58.0

42.9

5.40

54.5

41.5

6.00

50.6

40.0

6.65

46.4

38.4

7.35

63†† 60.2

44.3

4.30

57.2

43.0

4.79

54.2

41.7

5.34

50.9

40.3

5.94

47.3

38.8

6.60

43.4

37.1

7.30

62 59.2

55.1

4.29

56.4

53.7

4.78

53.5

52.3

5.33

50.5

50.4

5.93

47.5

47.5

6.60

44.2

44.2

7.32

57 57.8

57.8

4.27

55.6

55.6

4.77

53.1

53.1

5.32

50.5

50.5

5.93

47.5

47.5

6.60

44.2

44.2

7.32

72

67

71.1

65.5

37.4

48.5

4.52

4.44

67.6

62.2

36.1

47.2

5.02

4.94

63.9

58.8

34.8

45.9

5.57

5.49

59.8

55.1

33.4

44.4

6.16

6.09

55.5

51.1

32.0

42.9

6.81

6.74

50.6

46.8

30.4

41.2

7.51

7.44

63†† 61.2

47.1

4.39

58.1

45.8

4.88

54.9

44.4

5.43

51.6

43.0

6.03

47.9

41.5

6.68

43.8

39.7

7.39

62

57

60.5

59.0

4.38

57.7

57.4

4.88

54.9

54.9

5.43

52.1

52.1

6.04

48.9

48.9

6.70

45.3

45.3

7.42

60.1

60.1

4.38

57.6

57.6

4.88

54.9

54.9

5.43

52.1

52.1

6.04

49.0

49.0

6.70

45.4

45.4

7.42

72

67

72.0

39.1

4.61

68.3

37.8

5.10

64.4

36.5

5.65

60.4

35.1

6.25

55.9

33.7

6.90

50.8

32.0

7.59

66.2

51.4

4.53

62.9

50.1

5.03

59.4

48.7

5.57

55.6

47.3

6.17

51.7

45.7

6.83

47.1

43.9

7.53

63†† 61.9

49.8

4.48

58.8

48.5

4.97

55.6

47.1

5.52

52.1

45.6

6.12

48.3

44.0

6.77

44.1

42.1

7.48

62 61.8

61.8

4.48

59.2

59.2

4.98

56.5

56.5

5.53

53.5

53.5

6.14

50.2

50.2

6.80

46.4

46.4

7.51

57 61.8

61.8

4.48

59.2

59.2

4.98

56.4

56.4

5.53

53.4

53.4

6.14

50.2

50.2

6.80

46.4

46.4

7.51

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FV4ANB

FB4ANB

FC4BNB

FK4CNB

Size

006

070

070

006

Capacity

1.00

0.98

0.98

1.00

Power

1.00

1.04

1.04

1.00

Indoor

Section

FX4ANB

CC5A/CD5AW

CJ5A/CK5A/CK5BX

Size

060

060

060

Capacity

0.98

0.97

0.97

Power

1.04

0.99

1.00

* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.

‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh

(245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air per degree above 80°F (27°C).

** System kw is total of indoor and outdoor unit kilowatts.

†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.

EWB—Entering Wet Bulb

—14—

HEAT PUMP HEATING PERFORMANCE

INDOOR

AIR

EDB CFM

OUTDOOR COIL ENTERING AIR TEMPERATURES °F

–3

Capacity

MBtuh†

Total

Pwr

7

Capacity

MBtuh†

Total

Pwr

17

Capacity

MBtuh†

Total

Pwr

27

Capacity

MBtuh†

Total

Pwr

37

Capacity

MBtuh†

Total

Pwr

47

Capacity

MBtuh†

Total

Pwr

57

Capacity

MBtuh†

Total

Pwr

67

Capacity

MBtuh†

Total

Pwr

Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†

650AN024-A,C Outdoor Section With FX4ANF030 Indoor Section

65

70

75

700 12.0 11.1 1.79 14.3 13.1 1.87 16.6 15.1 1.95 19.0 16.9 2.04 21.9 19.9 2.16 25.0 25.0 2.30 28.5 28.5 2.48 32.6 32.6 2.74

800 12.2 11.2 1.80 14.5 13.3 1.87 16.8 15.3 1.95 19.2 17.1 2.03 22.1 20.1 2.13 25.4 25.4 2.27 28.9 28.9 2.44 33.1 33.1 2.69

900 12.4 11.4 1.82 14.6 13.4 1.88 17.0 15.5 1.95 19.4 17.3 2.03 22.4 20.4 2.13 25.6 25.6 2.25 29.3 29.3 2.43 33.4 33.4 2.67

700 11.8 10.8 1.87 14.1 13.0 1.96 16.4 15.0 2.05 18.8 16.7 2.14 21.6 19.6 2.26 24.7 24.7 2.41 28.1 28.1 2.60 32.0 32.0 2.87

800 12.0 11.0 1.88 14.3 13.1 1.96 16.6 15.1 2.04 19.0 16.9 2.13 21.8 19.9 2.24 25.0 25.0 2.38 28.5 28.5 2.56 32.5 32.5 2.81

900 12.1 11.2 1.90 14.4 13.3 1.97 16.8 15.3 2.05 19.2 17.0 2.13 22.1 20.1 2.23 25.3 25.3 2.36 28.8 28.8 2.54 32.9 32.9 2.79

700 11.5 10.6 1.96 13.9 12.8 2.05 16.2 14.8 2.15 18.5 16.5 2.25 21.3 19.4 2.38 24.3 24.3 2.53 27.7 27.7 2.73 31.5 31.5 3.00

800 11.7 10.7 1.97 14.1 13.0 2.06 16.4 15.0 2.14 18.8 16.7 2.23 21.5 19.6 2.35 24.6 24.6 2.50 28.1 28.1 2.68 32.0 32.0 2.94

900 11.8 10.9 1.98 14.3 13.1 2.07 16.6 15.1 2.15 19.0 16.8 2.23 21.8 19.8 2.34 24.9 24.9 2.48 28.4 28.4 2.66 32.4 32.4 2.91

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FX4ANF

Size

030

Capacity

1.00

Power

1.00

Indoor

Section

CE3AA

Size

030

Capacity

0.98

Power

1.01

F(A,B)4AN(F,C)

FC4BNF

FK4CNF

030

030

001

0.98

0.98

0.95

1.01

1.01

0.95

CJ5A/CK5A/CK5BA

036

030

036

0.98

0.98

0.99

1.01

1.01

0.98

FV4ANF

002

003

002

003

1.00

1.01

1.01

1.00

0.92

0.94

0.97

0.96

CJ5A/CK5A/CK5BN

CJ5A/CK5A/CK5BW

CK3BA

036

030

036

030

0.99

0.98

0.99

0.98

0.98

1.01

0.98

1.01

65

70

75

— — — 036

650AN030-A,C Outdoor Section With FX4ANF030 Indoor Section

0.99

0.98

825 12.6 11.6 2.07 15.4 14.1 2.12 18.3 16.7 2.16 21.6 19.2 2.22 25.4 23.1 2.29 29.7 29.7 2.39 34.6 34.6 2.69 32.7 32.7 2.55

1050 12.9 11.9 2.11 15.7 14.4 2.14 18.7 17.0 2.17 22.0 19.6 2.21 25.9 23.6 2.27 30.4 30.4 2.35 35.4 35.4 2.63 33.5 33.5 2.49

1250 13.2 12.2 2.15 16.0 14.7 2.17 19.0 17.3 2.19 22.4 19.9 2.23 26.3 23.9 2.28 30.8 30.8 2.36 36.0 36.0 2.64 33.9 33.9 2.49

825 12.3 11.3 2.18 15.2 14.0 2.23 18.1 16.5 2.28 21.4 19.0 2.33 25.1 22.8 2.41 29.4 29.4 2.52 34.1 34.1 2.82 32.2 32.2 2.67

1050 12.7 11.7 2.21 15.6 14.3 2.25 18.5 16.9 2.28 21.8 19.4 2.32 25.6 23.3 2.38 30.0 30.0 2.47 34.9 34.9 2.76 33.0 33.0 2.60

1250 13.0 11.9 2.25 15.8 14.5 2.28 18.8 17.1 2.30 22.1 19.6 2.34 26.0 23.6 2.39 30.4 30.4 2.47 35.4 35.4 2.76 33.4 33.4 2.60

825 12.0 11.1 2.29 15.0 13.7 2.34 18.0 16.4 2.40 21.1 18.8 2.46 24.8 22.6 2.54 29.0 29.0 2.65 33.7 33.7 2.96 31.7 31.7 2.80

1050 12.4 11.4 2.32 15.3 14.1 2.35 18.3 16.7 2.40 21.6 19.1 2.44 25.3 23.0 2.50 29.6 29.6 2.59 34.4 34.4 2.89 32.5 32.5 2.72

1250 12.7 11.7 2.36 15.6 14.4 2.39 18.6 17.0 2.42 21.9 19.4 2.45 25.7 23.4 2.51 30.0 30.0 2.59 34.9 34.9 2.89 33.0 33.0 2.71

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FX4ANF

Size

030

Capacity

1.00

Power

1.00

Indoor

Section

FV4ANF

Size

002

Capacity

0.97

Power

0.94

F(A,B)4AN(F,C)

FC4BNF

FK4CNF

030

036

030

036

001

002

003

0.98

0.99

0.98

0.99

0.95

0.97

0.95

1.02

1.03

1.02

1.03

0.96

0.94

0.92

FX4ANF

CE3AA

CJ5A/CK5A/CK5BN

CJ5A/CK5A/CK5BW

CK3BA

003

036

036

036

036

036

0.95

1.00

0.97

0.98

0.98

0.98

0.92

1.01

1.01

0.99

0.98

0.98

See notes on page 17.

—15—

HEAT PUMP HEATING PERFORMANCE Continued

INDOOR

AIR

EDB CFM

OUTDOOR COIL ENTERING AIR TEMPERATURES °F

–3

Capacity

MBtuh†

Total

Pwr

7

Capacity

MBtuh†

Total

Pwr

17

Capacity

MBtuh†

Total

Pwr

27

Capacity

MBtuh†

Total

Pwr

37

Capacity

MBtuh†

Total

Pwr

47

Capacity

MBtuh†

Total

Pwr

57

Capacity

MBtuh†

Total

Pwr

67

Capacity

MBtuh†

Total

Pwr

Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†

650AN036-A,C Outdoor Section With FX4ANF042 Indoor Section

65

70

75

1125 14.7 13.5 2.42 18.3 16.8 2.51 21.9 20.0 2.59 25.8 22.9 2.66 30.4 27.6 2.76 35.6 35.6 2.88 41.7 41.7 3.04 48.8 48.8 3.27

1250 14.9 13.7 2.45 18.5 17.0 2.53 22.9 20.9 2.61 26.1 23.2 2.67 30.7 27.9 2.76 35.9 35.9 2.87 42.1 42.1 3.03 49.3 49.3 3.25

1375 15.1 13.9 2.49 18.7 17.2 2.56 22.4 20.4 2.62 26.3 23.4 2.68 31.0 28.2 2.76 36.3 36.3 2.87 42.5 42.5 3.03 49.7 49.7 3.25

1125 14.1 13.0 2.51 17.9 16.4 2.61 21.6 19.7 2.70 25.4 22.6 2.79 29.9 27.2 2.89 35.0 35.0 3.02 41.5 41.5 3.19 48.0 48.0 3.42

1250 14.4 13.2 2.54 18.1 16.7 2.63 21.9 19.9 2.72 25.7 22.8 2.79 30.2 27.5 2.89 35.4 35.4 3.00 41.5 41.5 3.17 48.5 48.5 3.40

1375 14.6 13.4 2.58 18.4 16.9 2.66 22.1 20.1 2.74 26.0 23.1 2.81 30.5 27.8 2.89 35.7 35.7 3.00 41.8 41.8 3.16 48.9 48.9 3.39

1125 13.5 12.4 2.60 17.4 16.0 2.71 21.2 19.4 2.82 25.0 22.2 2.92 29.5 26.8 3.03 34.5 34.5 3.16 40.3 40.3 3.34 47.1 47.1 3.58

1250 13.8 12.7 2.63 17.7 16.2 2.74 21.5 19.6 2.84 25.3 22.5 2.92 29.8 27.1 3.02 34.8 34.8 3.15 40.8 40.8 3.31 47.7 47.7 3.55

1375 14.0 12.9 2.67 17.9 16.4 2.76 21.7 19.8 2.86 25.6 22.7 2.93 30.1 27.4 3.03 35.2 35.2 3.15 41.2 41.2 3.31 48.1 48.1 3.54

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FX4ANF

Size

042

Capacity

1.00

Power

1.00

Indoor

Section

CJ5A/CK5A/CK5BA

Size

042

Capacity

0.98

Power

1.02

F(A,B)4AN(F,B,C)

FC4BN(F,B)

FK4CNF

042

042

003

0.98

0.98

0.96

1.02

1.02

0.96

CJ5A/CK5A/CK5BN

048

042

048

0.98

0.98

0.98

1.01

1.02

1.01

FV4ANF

CE3AA

005

003

005

042

0.97

0.96

0.97

0.98

0.89

0.95

0.89

1.02

CJ5A/CK5A/CK5BW

CK3BA

048

042

048

0.98

0.98

0.98

1.01

1.02

1.01

65

70

75

048 0.98

1.01

650AN042-A,C Outdoor Section With FV4ANF003 Indoor Section

1225 17.3 15.9 2.61 21.5 19.8 2.74 25.7 23.4 2.86 30.0 26.6 2.99 35.1 32.0 3.14 41.1 41.1 3.34 40.4 40.4 3.30 39.5 39.5 3.21

1400 17.6 16.2 2.61 22.5 20.7 2.74 25.9 23.6 2.84 30.2 26.9 2.95 35.5 32.3 3.09 41.5 41.5 3.28 40.8 40.8 3.22 40.0 40.0 3.14

1575 17.8 16.4 2.62 21.9 20.2 2.73 26.1 23.8 2.83 30.5 27.1 2.93 35.8 32.6 3.06 41.9 41.9 3.24 41.2 41.2 3.18 40.4 40.4 3.09

1225 16.8 15.5 2.74 21.1 19.4 2.88 25.4 23.2 3.03 29.6 26.3 3.16 34.7 31.6 3.32 40.5 40.5 3.53 39.8 39.8 3.48 38.9 38.9 3.38

1400 17.1 15.7 2.75 21.4 19.6 2.87 25.6 23.4 3.00 29.9 26.6 3.12 35.0 31.9 3.27 41.0 41.0 3.46 40.2 40.2 3.40 39.4 39.4 3.30

1575 17.3 15.9 2.76 21.6 19.8 2.87 25.8 23.6 2.99 30.1 26.8 3.10 35.3 32.2 3.24 41.3 41.3 3.42 40.6 40.6 3.35 39.8 39.8 3.25

1225 16.3 15.0 2.88 20.6 19.0 3.02 25.1 22.9 3.19 29.3 26.0 3.34 34.3 31.2 3.51 40.0 40.0 3.73 39.2 39.2 3.66 38.3 38.3 3.56

1400 16.6 15.2 2.89 20.9 19.2 3.01 25.3 23.1 3.17 29.6 26.3 3.30 34.6 31.5 3.46 40.4 40.4 3.66 39.6 39.6 3.58 38.8 38.8 3.47

1575 16.8 15.4 2.90 21.2 19.4 3.01 25.5 23.3 3.16 29.8 26.5 3.28 34.9 31.8 3.42 40.8 40.8 3.61 40.0 40.0 3.53 39.1 39.1 3.41

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FV4ANF

Size

003

Capacity

1.00

Power

1.00

Indoor

Section

FX4ANF

Size

042

Capacity

1.02

Power

1.01

F(A,B)4AN(F,B,C)

FC4BN(F,B)

FK4CNF

FV4ANF

See notes on page 17.

048

048

003

005

005

1.02

1.02

0.99

0.99

0.99

1.03

1.02

1.00

0.93

0.93

CE3AA

CJ5A/CK5A/CK5BA

CJ5A/CK5A/CK5BN

CJ5A/CK5A/CK5BW

CK3BA

048

048

048

048

048

1.02

1.02

1.02

1.02

1.02

1.04

1.03

1.03

1.03

1.03

—16—

HEAT PUMP HEATING PERFORMANCE Continued

INDOOR

AIR

EDB CFM

OUTDOOR COIL ENTERING AIR TEMPERATURES °F

–3

Capacity

MBtuh†

Total

Pwr

7

Capacity

MBtuh†

Total

Pwr

17

Capacity

MBtuh†

Total

Pwr

27

Capacity

MBtuh†

Total

Pwr

37

Capacity

MBtuh†

Total

Pwr

47

Capacity

MBtuh†

Total

Pwr

57

Capacity

MBtuh†

Total

Pwr

67

Capacity

MBtuh†

Total

Pwr

Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†

650AN048-A,C Outdoor Section With FV4ANF005 Indoor Section

65

70

75

1400 18.5 17.0 2.86 22.9 21.1 2.99 27.9 25.4 3.11 33.5 29.8 3.26 40.2 36.6 3.45 48.2 48.2 3.69 53.8 53.8 4.34 53.1 53.1 4.20

1600 18.7 17.2 2.87 23.2 21.3 2.98 28.1 25.6 3.10 33.8 30.1 3.23 40.7 37.0 3.41 48.7 48.7 3.64 54.4 54.4 4.28 53.7 53.7 4.14

1800 18.9 17.4 2.89 23.4 21.5 2.99 28.4 25.9 3.10 34.1 30.3 3.23 41.0 37.3 3.40 49.1 49.1 3.63 54.9 54.9 4.26 54.1 54.1 4.12

1400 18.1 16.7 3.03 22.7 20.9 3.16 27.6 25.2 3.29 33.2 29.4 3.44 39.8 36.2 3.64 47.5 47.5 3.89 54.3 54.3 4.57 52.3 52.3 4.40

1600 18.4 16.9 3.03 23.0 21.1 3.15 27.8 25.4 3.27 33.5 29.7 3.41 40.2 36.5 3.60 48.0 48.0 3.83 53.6 53.6 4.50 52.9 52.9 4.33

1800 18.6 17.1 3.05 23.2 21.3 3.16 28.1 25.6 3.27 33.8 30.0 3.41 40.5 36.9 3.58 48.4 48.4 3.81 54.1 54.1 4.47 53.3 53.3 4.31

1400 17.7 16.3 3.19 22.4 20.6 3.33 27.4 24.9 3.48 32.8 29.2 3.64 39.3 35.7 3.84 46.8 46.8 4.09 52.2 52.2 4.80 51.4 51.4 4.62

1600 18.0 16.6 3.20 22.7 20.9 3.33 27.6 25.2 3.46 33.1 29.4 3.60 39.7 36.1 3.79 47.4 47.4 4.04 52.8 52.8 4.72 52.0 52.0 4.54

1800 18.2 16.8 3.22 22.9 21.1 3.33 27.8 25.4 3.45 33.4 29.7 3.59 40.0 36.4 3.77 47.8 47.8 4.01 53.3 53.3 4.69 52.5 52.5 4.51

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FV4ANF

Size

005

Capacity

1.00

Power

1.00

Indoor

Section

FX4ANB

Size

060

Capacity

1.01

Power

1.02

F(A,B)4AN(F,B,C)

FB4ANB

FC4BN(F,B)

060

070

060

1.02

1.01

1.01

1.10

1.02

1.09

FX4ANF

CE3AA

CJ5A/CK5A/CK5BA

048

060

060

1.01

1.01

1.01

1.06

1.06

1.03

FC4BNB

FK4CNB

FK4CNF

FV4ANB

070

006

005

006

1.01

1.01

1.01

1.01

1.02

0.96

1.01

0.96

CJ5A/CK5A/CK5BN

CJ5A/CK5A/CK5BX

CK3BA

060

060

060

650AN060-B,C Outdoor Section With FV4ANB006 Indoor Section

1.02

1.02

1.01

1.04

1.04

1.03

65

70

75

1750 24.4 22.4 3.73 30.9 28.4 3.88 37.9 34.6 4.05 45.0 40.0 4.24 52.6 47.9 4.45 60.8 60.8 4.68 58.2 58.2 4.52 56.3 56.3 4.47

2000 24.9 22.9 3.76 31.5 28.9 3.90 38.5 35.1 4.05 45.7 40.6 4.22 53.2 48.4 4.41 61.6 61.6 4.61 59.0 59.0 4.44 57.1 57.1 4.37

2250 25.3 23.3 3.80 31.9 29.3 3.93 39.0 35.5 4.06 46.2 41.0 4.23 53.7 48.9 4.39 62.2 62.2 4.58 59.6 59.6 4.39 57.8 57.8 4.31

1750 23.4 21.5 3.92 30.0 27.6 4.09 37.0 33.7 4.27 44.2 39.2 4.46 52.0 47.3 4.70 60.0 60.0 4.94 57.4 57.4 4.76 55.4 55.4 4.71

2000 23.8 21.9 3.95 30.5 28.0 4.10 37.6 34.3 4.26 44.8 39.8 4.44 52.5 47.8 4.65 60.7 60.7 4.87 58.1 58.1 4.67 56.2 56.2 4.60

2250 24.3 22.3 4.00 31.0 28.5 4.13 38.1 34.7 4.28 45.4 40.3 4.45 53.1 48.3 4.63 61.4 61.4 4.83 58.8 58.8 4.62 56.9 56.9 4.53

1750 22.2 20.5 4.12 28.9 26.6 4.30 36.0 32.9 4.49 43.2 38.4 4.70 51.3 46.7 4.96 59.2 59.2 5.21 56.5 56.5 5.02 54.5 54.5 4.95

2000 22.7 20.9 4.15 29.5 27.1 4.31 36.7 33.4 4.49 43.9 39.0 4.67 51.9 47.2 4.90 59.9 59.9 5.13 57.3 57.3 4.92 55.3 55.3 4.83

2250 23.2 21.3 4.20 30.0 27.5 4.34 37.2 33.9 4.50 44.5 39.5 4.67 52.4 47.7 4.88 60.6 60.6 5.09 57.9 57.9 4.86 56.0 56.0 4.76

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Cooling

Indoor

Section

FV4ANB

FB4ANB

Size

006

070

Capacity

1.00

1.00

Power

1.00

1.03

Indoor

Section

FX4ANB

CC5A/CD5AW

Size

060

060

Capacity

1.00

0.98

Power

1.03

1.06

FC4BNB

FK4CNB

070

006

1.00

0.99

1.03

0.99

CJ5A/CK5A/CK5BX 060

0.98

1.02

* The Btuh heating capacity values shown are net “integrated” values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.

† The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to obtain total system kilowatts.

EDB—Entering Dry Bulb

NOTE: The performance shown includes the PressureGuard™ cycling the outdoor fan. The ambient temperature that the outdoor fan cycles depends on the outdoor/indoor combination, indoor airflow, installation practices, and system maintenance, all of which affect system performance.

—17—

System Design

1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.

2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).

3. Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C).

4. Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C).

5. Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C).

6. For reliable operation, unit should be level in all horizontal planes.

7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below = 150 ft. (See items 8 and

9 following).

8. For interconnecting refrigerant tube lengths greater than 50 ft and/or elevation differences between indoor and outdoor units greater than 20 ft, consult Residential Split-System Application Guideline and Service Manual for Air Conditioners and Heat Pumps using Puron Refrigerant.

9. If ANY refrigerant tubing is buried, provide a minimum 6-in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36-in.

may be buried without further considerations. Buried refrigerant tubing lengths greater than 36 in. are not recommended.

10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

11. Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity (unless so specified) may result in inadequate indoor comfort.

12. Do not apply capillary tube indoor coils to these units.

13. Factory-supplied filter drier must be installed.

MATCHED SYSTEM

HEAT PUMP

HUMIDIFIER

VENTILATOR PLUS

ZONE PERFECT PLUS ™

EQUIPMENT CONTROLLER

FAN COIL

AIR CLEANER

A98536

—18—

—19—

SERVICE TRAINING

Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:

• Unit Familiarization • Maintenance

• Installation Overview • Operating Sequence

A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.

Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.

CALL FOR FREE CATALOG 1-800-962-9212

[ ] Packaged Service Training [ ] Classroom Service Training

A94328

© 1998 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indianapolis, IN 46231

—20—

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE

WITH INSTALLATION INSTRUCTIONS

Cancels: PDS 650A.24.1

PRINTED IN U.S.A. Catalog No. 5265-002 1-99

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Uses environmentally friendly Puron Refrigerant.
  • Durable scroll compressor with internal temperature and current-sensitive overloads.
  • AeroQuiet System (AQS) design for ultra-low sound ratings.

Related manuals

Frequently Answers and Questions

What refrigerant does the Bryant 650A use?
The Bryant 650A uses Puron Refrigerant, which is environmentally friendly and does not contribute to ozone depletion.
What is the SEER rating of the Bryant 650A?
The Bryant 650A has a SEER rating of up to 14.5, making it a highly efficient heat pump.