Lennox Merit ML193UH Installation Instructions Manual

Add to My manuals
52 Pages

advertisement

Lennox Merit ML193UH Installation Instructions Manual | Manualzz
INSTALLATION
INSTRUCTIONS
ML193UH
E 2012 Lennox Industries Inc.
Dallas, Texas, USA
MERIT® SERIES GAS FURNACE
UPFLOW / HORIZONTAL AIR DISCHARGE
507010−01
08/2012
Supersedes 06/2012
Litho U.S.A.
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This is a safety alert symbol and should never be ignored.
When you see this symbol on labels or in manuals, be alert
to the potential for personal injury or death.
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
AIR FLOW
UPFLOW
HORIZONTAL LEFT
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
AIR FLOW
AIR FLOW
WARNING
HORIZONTAL RIGHT
Table of Contents
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ML193UH Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . . . 3
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Use of Furnace as a Construction Heater . . . . . . . . . . . 4
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Combustion, Dilution, Ventilation Air . . . . . . . . . . . . . . . . 5
Setting Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Pipe and Fittings Specifications . . . . . . . . . . . . . . . . . . . 13
Joint Cementing Procedure . . . . . . . . . . . . . . . . . . . . . . 15
08/12
*2P0812*
Venting Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vent Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Measurement . . . . . . . . . . . . . . . . . . . . .
Proper Combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Other Unit Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . .
Twinning the ML193UH . . . . . . . . . . . . . . . . . . . . . . . . . .
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start Up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
507010−01
Page 1
16
17
36
39
41
42
43
44
44
46
47
48
49
50
*P507010-01*
ML193UH Unit Dimensions − inches (mm)
1NOTE
− 60C and 60D size units that require air
volumes 1800 cfm or over (850 L/s) must have
one of the following
1. Single side return air with transition, to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air
filter. Required to maintain proper air velocity.
2. Single side return air with optional Return Air Base
3. Bottom return air.
4. Return air from both sides.
5. Bottom and one side return air.
See Blower Performancetables for additional information.
EXHAUST AIR
OUTLET
3−3/8
(86)
2 (51)
D
SUPPLY AIR
OPENING
2−7/8
(73)
COMBUSTION
AIR INTAKE
2
Optional External Side Return Air Filter Kit is not for use
with the optional Return Air Base.
2 OPTIONAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
23−3/4
(603)
25
(635)
TOP VIEW
A
B
27−3/4
(705)
1 (25)
Front Panel
9/16 (14)
2 OPTIONAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
6−9/16 (167)
Left
9 (229)
Right
12−5/8 (321)
(Either Side)
19−7/16
(494)
9/16
(14)
2 (51)
(Either Side)
GAS PIPING INLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
6−1/2 (165)
(Either Side)
33
(838)
ELECTRICAL
INLET
(Either Side)
23
(584)
14−3/4
(375)
1−1/2
(38)
14
(356)
1 Side
Return
Air Opening
(Either Side)
16
(406)
AIR FLOW
1−15/16 (49)
3/4
(19)
C
1
Bottom Return
Air Opening
3/4
(19)
5/8
(16)
3−1/4
(83)
23−1/2
(597)
1 Bottom Return
Air Opening
FRONT VIEW
ML193UH
Model No.
045XP24B
045XP36B
070XP24B
070XP36B
090XP36C
090XP48C
110XP48C
110XP60C
135XP60D
SIDE VIEW
in.
A
B
mm
in.
17−1/2
446
16−3/8
416
16
406
7−5/8
194
21
533
19−7/8
505
19−1/2
495
9−3/8
238
24−1/2
622
23−3/8
594
23
584
11−1/8
283
Page 2
mm
D
mm
mm
in.
C
in.
ML193UH Gas Furnace
Shipping and Packing List
The ML193UH Category IV gas furnace is shipped ready
for installation in the upflow or horizontal position. The furnace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed in
horizontal or upflow applications with bottom return air.
The ML193UH can be installed as either a Direct Vent or
a Non−Direct Vent gas central furnace.
The furnace is equipped for installation in natural gas applications. A conversion kit (ordered separately) is required for use in propane/LP gas applications.
NOTE − In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged outdoors. In
Non−Direct Vent installations, combustion air is taken from
indoors or ventilated attic or crawlspace and flue gases are
discharged outdoors. See figures 1 and 2 for applications involving roof termination.
DIRECT VENT INSTALLATION
NON−DIRECT VENT
INSTALLATION
EXHAUST OUTLET
COMBUSTION
AIR INTAKE OUTSIDE
OF HOUSE
EXHAUST
OUTLET
Package 1 of 1 contains
1 − Assembled ML193UH unit
1 − Bag assembly containing the following:
1 − Snap bushing
1 − Snap plug
1 − Wire tie
1 − Condensate trap
1 − Condensate trap cap
1 − Condensate trap clamp
1 − 2" diameter debris screen
1 − 1/2" Threaded street elbow
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
The following items may also be ordered separately:
1 − Thermostat
1 − Propane/LP changeover kit
1 − Return air base kit
1 − Horizontal suspension kit
Safety Information
WARNING
COMBUSTION
AIR INTAKE
INSIDE
OF HOUSE
Improper installation, adjustment, alteration, service
or maintenance can cause property damage,
personal injury or loss of life. Installation and service
must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
FIGURE 1
NON−DIRECT VENT
INSTALLATION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
NON−DIRECT VENT
INSTALLATION
EXHAUST
OUTLET
EXHAUST
OUTLET
DANGER
Danger of explosion.
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
ATTIC SPACE
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
CRAWL SPACE
FIGURE 2
Page 3
There are circumstances in which odorant used with
LP/propane gas can lose its scent. In case of a leak,
LP/propane gas will settle close to the floor and may
be difficult to smell. An LP/propane leak detector
should be installed in all LP applications.
Use only the type of gas approved for use with this furnace.
Refer to unit nameplate.
ML193UH units are CSA International certified to ANSI
Z21.47 and CSA 2.3 standards.
Building Codes
In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must
be installed according to the current National Fuel Gas Code
(ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is
available from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current National
Standard of Canada CSA-B149 Natural Gas and Propane
Installation Codes, local plumbing or waste water codes
and other applicable local codes.
In order to ensure proper unit operation in non−direct vent
applications, combustion and ventilation air supply must be
provided according to the current National Fuel Gas Code
or CSA-B149 standard.
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of the
Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
Heating Unit Installed Parallell to Air Handler Unit
Dampers
(open during heating operation only)
Gas Unit
AIR FLOW
Air Handler Unit
Installation Locations
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
nameplate and in the table in figure 12. Accessibility and service clearances must take precedence over fire protection
clearances.
NOTE − For installation on combustible floors, the furnace
shall not be installed directly on carpeting, tile, or other
combustible material other than wood flooring.
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
floor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.
NOTE − Furnace must be adjusted to obtain a temperature
rise within the range specified on the unit nameplate. Failure
to do so may cause erratic limit operation and premature heat
exchanger failure.
This ML193UH furnace must be installed so that its electrical components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling coils (figure 3), it shall
be installed in parallel with, or on the upstream side of, cooling coils to avoid condensation in the heating compartment.
With a parallel flow arrangement, a damper (or other means
to control the flow of air) must adequately prevent chilled air
from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the
heating or the cooling unit, unless it is in the full HEAT or
COOL setting.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric
Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
AIR FLOW
Dampers
(open during cooling operation only)
Heating Unit Installed Upstream of Cooling Coil
AIR FLOW
Gas Unit
AIR FLOW
Cooling Coil
FIGURE 3
NOTE − This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
The ML193UH furnace may be installed in alcoves, closets, attics, basements, garages, crawl spaces and utility
rooms in the upflow or horizontal position.
This furnace design has not been CSA certified for installation in mobile homes, recreational vehicles, or outdoors.
Use of Furnace as Construction Heater
Lennox does not recommend the use of ML193UH units as
a construction heater during any phase of construction.
Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
ML193UH units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not
allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
Page 4
D
Air filters must be replaced upon construction completion.
D
The input rate and temperature rise must be set per the
furnace rating plate.
D
One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the
furnace. Do not connect duct directly to the furnace.
Size the temporary duct following these instructions in
section for Combustion, Dilution and Ventilation Air in a
confined space with air from outside.
D
The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction clean−up.
D
All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be verified
according to these installation instructions.
• The A" coil drain pan is high quality engineering polymer with a maximum service temperature of 500° F.
However, adequate space must be provided between
the drain pan and the furnace heat exchanger. At least
2" space is required for sectionalized heat exchanger
and and 4" for drum−type or oil−fired furnace exchanger.
Closer spacing may damage the drain pan and cause
leaking.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered
when installing a ML193UH furnace:
• Place the furnace as close to the center of the air distribution system as possible. The furnace should also be
located close to the vent termination point.
• When the furnace is installed in non−direct vent applications, do not install the furnace where drafts might blow
directly into it. This could cause improper combustion
and unsafe operation.
• When the furnace is installed in non−direct vent applications, do not block the furnace combustion air opening
with clothing, boxes, doors, etc. Air is needed for proper
combustion and safe unit operation.
• When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace.
• When the furnace is installed in an unconditioned
space, consider provisions required to prevent freezing
of condensate drain system.
CAUTION
ML193UH unit should not be installed in areas normally subject to freezing temperatures.
Page 5
WARNING
The State of California has determined that this product may contain or produce a chemical or chemicals,
in very low doses, which may cause serious illness
or death. It may also cause cancer, birth defects or reproductive harm.
WARNING
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De−icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
Combustion, Dilution & Ventilation Air
If the ML193UH is installed as a Non−Direct Vent Furnace, follow the guidelines in this section.
NOTE − In Non−Direct Vent installations, combustion air
is taken from indoors or ventilated attic or crawlspace
and flue gases are discharged out−doors.
In the past, there was no problem in bringing in sufficient
outdoor air for combustion. Infiltration provided all the air
that was needed. In today’s homes, tight construction
practices make it necessary to bring in air from outside
for combustion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional
air that could be used for combustion out of the house.
Unless outside air is brought into the house for combustion, negative pressure (outside pressure is greater than
inside pressure) will build to the point that a downdraft
can occur in the furnace vent pipe or chimney. As a result,
combustion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combus−
tion and ventilation, use the guidelines and procedures in
this section to install ML193UH furnaces to ensure efficient and safe operation. You must consider combustion
air needs and requirements for exhaust vents and gas
piping. A portion of this information has been reprinted
with permission from the National Fuel Gas Code (ANSI−
Z223.1/NFPA 54). This reprinted material is not the complete and official position of the ANSI on the referenced
subject, which is represented only by the standard in its
entirety.
Confined Space
In Canada, refer to the CSA B149 installation codes.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a
confined space such as a closet or small equipment room.
Even a small leak around the base of the unit at the platform
or at the return air duct connection can cause a potentially
dangerous negative pressure condition. Air for combustion
and ventilation can be brought into the confined space either from inside the building or from outside.
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliance will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all
fuel−burning appliances and appliances such as exhaust
fans which force air out of the house. When fireplaces, exhaust fans, or clothes dryers are used at the same time as
the furnace, much more air is required to ensure proper
combustion and to prevent a downdraft. Insufficient air
causes incomplete combustion which can result in carbon
monoxide.
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace components.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in
an unconfined or a confined space.
A confined space is an area with a volume less than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com−
bined input rating of all appliances installed in that space. This
definition includes furnace closets or small equipment rooms.
Air from Inside
If the confined space that houses the furnace adjoins a
space categorized as unconfined, air can be brought in by
providing two permanent openings between the two
spaces. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas−fired equipment in the confined
space. Each opening must be at least 100 square inches
(64516 mm2). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See figure 4.
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE
ROOF TERMINATED
EXHAUST PIPE
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the Air
from Outside section.
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
ML193UH
OPENINGS
(To Adjacent
Unconfined
Space)
NOTE − Each opening shall have a free area of at least one square inch
per 1,000 Btu (645mm2 per .29kW) per hour of the total input rating of
all equipment in the enclosure, but not less than 100 square inches
(64516mm. 2).
FIGURE 4
Page 6
Air from Outside
If air from outside is brought in for combustion and ventilation, the confined space shall be provided with two permanent openings. One opening shall be within 12" (305mm)
of the top of the enclosure and one within 12" (305mm) of
the bottom. These openings must communicate directly
or by ducts with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors or indirectly
through vertical ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645mm2
per 1.17kW) per hour of total input rating of all equipment
in the enclosure. When communicating with the outdoors
through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu (645mm2
per .59kW) per total input rating of all equipment in the enclosure (See figure 5). It is also permissible to bring in air
for combustion from a ventilated attic (figure 6) or ventilated crawl space (figure 7).
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Ventilation
Louvers
(Crawl space)
Furnace
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ouside)
VENTILATION LOUVERS
(Each end of attic)
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
*Intake Debris Screen Provided)
* See table 6 for maximum vent lengths
ROOF TERMINATED
EXHAUST PIPE
NOTE−The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 7
OUTLET
AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
INLET
AIR
VENTILATION
LOUVERS
(For unheated
crawl space)
NOTE−The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 5
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
Roof Terminated
Exhaust Pipe
If air from outside is brought in for combustion and ventilation, the confined space must have two permanent openings. One opening shall be within 12 inches (305 mm) of
the top of the enclosure and one opening within 12 inches
(305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl
or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a
minimum free area of 1 square inch (645 mm2) per 4,000
Btu (1.17 kW) per hour of total input rating of all equipment
in the enclosure. See figures 5 and 8. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645
mm2) per 2,000 Btu (.56 kW) per total input rating of all
equipment in the enclosure. See figure 9.
When ducts are used, they shall be of the same cross−sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens
must be considered. If the design and free area of protective covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have
20 to 25 percent free area and metal louvers and grilles
will have 60 to 75 percent free area. Louvers and grilles
must be fixed in the open position or interlocked with the
equipment so that they are opened automatically during
equipment operation.
*Intake Debris
Screen
(Provided)
Furnace
* See table 6 for maximum vent lengths
NOTE−The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 6
Page 7
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
ROOF TERMINATED
EXHAUST PIPE
leg). See figure 10. The bolt and washer must be removed before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg
will not touch the blower housing.
VENTILATION LOUVERS
(Each end of attic)
ML193UH090P48C
and ML193UH110P48C
with 1/2 HP Blower Motor
OUTLET
AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
RIGID LEG
(Remove shipping bolt
and washer)
INLET AIR
(Ends 12" above
bottom)
FURNACE
NOTE−The inlet and outlet air openings shall each have a free area of
at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per hour
of the total input rating of all equipment in the enclosure.
FIGURE 10
Installation − Setting Equipment
FIGURE 8
WARNING
EQUIPMENT IN CONFINED SPACE −
ALL AIR FROM OUTSIDE
Do not connect the return air duct to the back of the
furnace. Doing so will adversely affect the operation
of the safety control devices, which could result in
personal injury or death.
ROOF TERMINATED
EXHAUST PIPE
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
INLET AIR
NOTE−Each air duct opening shall have a free area of at least one
square inch per 2,000 Btu (645mm2 per .59kW) per hour of the total
input rating of all equipment in the enclosure. If the equipment room
is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area
of at least 1 square inch per 4,000 Btu (645mm 2 per 1.17kW) per
hour of the total input rating of all other equipment in the enclosure.
FIGURE 9
Shipping Bolt Removal
Units with 1/2 hp blower motor are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a
shipping bolt and a flat white plastic washer (rather than the
rubber mounting grommet used with a flexible mounting
WARNING
Blower access panel must be securely in place when
blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into
living space resulting in personal injury or death.
Upflow Applications
The ML193UH gas furnace can be installed as shipped
in the upflow position. Refer to figure 12 for clearances.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
condensate trap and drain connections, and installation
and service clearances [24 inches (610 mm) at unit
front]. The unit must be level from side to side. Unit may
be positioned from level to 1/2" toward the front to aid in
draining. See figure 11.
Allow for clearances to combustible materials as indicated
on the unit nameplate.
Page 8
SETTING EQUIPMENT
UPFLOW APPLICATION
UNIT
FRONT
UNIT
FRONT
AIR FLOW
AIR FLOW
FRONT VIEW
SIDE VIEW
1/2"
max.
SIDE VIEW
HORIZONTAL APPLICATION
UNIT
FRONT
AIR FLOW
1/2"
max.
END VIEW
FRONT VIEW
Unit must be level side−to−side. Unit may be positioned from level to 1/2" toward the front to aid in draining.
FIGURE 11
Page 9
Return Air Guidelines
WARNING
Improper installation of the furnace can result in personal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or air in the living space. Use sheet metal screws and
joint tape to seal return air system to furnace.
In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.
For no reason should return and supply air duct systems ever be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury
and/or property damage could result.
Installation Clearances
Top
Left Side
Return air can be brought in through the bottom or either
side of the furnace installed in an upflow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet
for installations that require side return air. Cut the furnace
cabinet at the maximum dimensions shown on page 2.
Refer to Engineering Handbook for additional information.
ML193UH applications which include side return air
and a condensate trap installed on the same side of the
cabinet (trap can be installed remotely within 5 ft.) require either a return air base or field−fabricated transition to accommodate an optional IAQ accessory taller
than 14.5". See figure 13.
Side Return Air
(with transition and filter)
Right Side
Bottom (Floor)
20” X 25” X 1”
(508mmX635mmX 25mm)
Air Filter
1−1/2”
Top/Plenum
1 in. (25 mm)
*Front
0
Back
0
Sides
0†
Vent
0
Floor
0‡
Return
Air
Plenum
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
†Allow proper clearances to accommodate condensate trap.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
Transition
FIGURE 13
FIGURE 12
Page 10
Optional Return Air Base
(Upflow Applications Only)
CONDENSATE
TRAP
FURNACE
FRONT
IF BASE
IS USED
WITHOUT
IAQ CABINET,
INDOOR AIR
A SINGLE
QUALITY
RETURN AIR
PLENUM
CABINET
MUST
(PCO, Filter
Cabinet, etc.) COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
AIR FLOW
17−1/2 (446) B Width (50W98)
21 (533) C Width (50W99)
24−1/2 (622) D Width (51W00)
3−1/4
(83)
7−1/4
(184)
1 23
(584)
Overall
(Maximum)
1
Minimum
11 (279)
2 Maximum
1 Unit side return air
14 (356)
Opening
5−5/8
(143)
22−7/16
(570)
Overall
(Maximum)
SIDE RETURN
AIR OPENINGS
(Either Side)
23
(584)
26−7/8
(683)
OPTIONAL
RETURN
AIR BASE
1
3/4
(19)
SIDE VIEW
FRONT VIEW
NOTE− Optional side return air filter kits are not for use with return air base.
1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm of air and over (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air
opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2 To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
FIGURE 14
Removing the Bottom Panel
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
the bottom cap. See figure 15.
Horizontal Applications
WARNING
Do not install the furnace on its front or back.
See figure 16.
Screw
Bottom Cap
Bottom Panel
Front
FIGURE 15
Back
FIGURE 16
Page 11
The ML193UH furnace can be installed in horizontal applications with either right− or left−hand air discharge.
Refer to figure 17 for clearances in horizontal applications.
Horizontal Application
Installation Clearances
Right−Hand Discharge
Left End
NOTE − Heavy−gauge sheet metal straps may be used to
suspend the unit from roof rafters or ceiling joists. When
straps are used to suspend the unit in this way, support
must be provided for both the ends. The straps must not
interfere with the plenum or exhaust piping installation.
Cooling coils and supply and return air plenums must
be supported separately.
HORIZONTAL SUSPENSION KIT
Right End
Air
Flow
Internal Brace
(provided with kit)
Metal Strap
(typical)
Air
Flow
Bottom (Floor)**
Bracket
(typical)
Left−Hand Discharge
Top
Left End
Air
Flow
Right End
Air
Flow
Air
Flow
Bottom (Floor)**
Top
0
Front*
0
Back
0
Ends
0
Vent
0
Floor
0‡
FIGURE 18
NOTE − When the furnace is installed on a platform or with
the horizontal suspension kit in a crawlspace, it must be
elevated enough to avoid water damage, accommodate
drain trap and to allow the evaporator coil to drain.
Platform Installation of Horizontal Unit
1 − Select location for unit keeping in mind service and
other necessary clearances. See figure 17.
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
**An 8" service clearance must be maintained below the unit to
provide for servicing of the condensate trap.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
FIGURE 17
Suspended Installation of Horizontal Unit
This furnace may be installed in either an attic or a crawlspace. Either suspend the furnace from roof rafters or
floor joists, as shown in figure 18, or install the furnace on a
platform, as shown in figure 19. A horizontal suspension
kit (51W10) may be ordered from Lennox or use equivalent.
2 − Construct a raised wooden frame and cover frame
with a plywood sheet. If unit is installed above finished
space, fabricate an auxiliary drain pan to be installed
under unit. Set unit in drain pan as shown in figure 19.
Leave 8 inches for service clearance below unit for
condensate trap.
3 − Provide a service platform in front of unit. When installing the unit in a crawl space, a proper support platform
may be created using cement blocks.
4 − Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.
Page 12
5 − If necessary, run the condensate line into a condensate pump to meet drain line slope requirements. The
pump must be rated for use with condensing furnaces.
Protect the condensate discharge line from the pump
to the outside to avoid freezing.
6 − Continue with exhaust, condensate and intake piping
installation according to instructions.
INTAKE PIPE
If the furnace is installed without a cooling coil, a removable
access panel should be installed in the supply air duct. The
access panel should be large enough to permit inspection
of the heat exchanger. The furnace access panel must always be in place when the furnace is operating and it must
not allow leaks.
Return Air Plenum
NOTE − Return air must not be drawn from a room
where this furnace, or any other gas−fueled appliance
(i.e., water heater), or carbon monoxide−producing device (i.e., wood fireplace) is installed.
*GAS CONNECTION
EXHAUST PIPE
RAISED
PLATFORM
SERVICE PLATFORM
Supply Air Plenum
FIGURE 19
Return Air −− Horizontal Applications
Return air may be brought in only through the end of a furnace installed in the horizontal position. The furnace is
equipped with a removable bottom panel to facilitate
installation. See figure 15.
Filters
This unit is not equipped with a filter or rack. A field−provided high velocity rated filter is required for the unit to operate properly. Table 1 lists recommended filter sizes.
A filter must be in place whenever the unit is operating.
TABLE 1
Filter Size
Furnace
Cabinet Width
Side Return
Bottom Return
17−1/2"
16 X 25 X 1 (1)
16 X 25 X 1 (1)
21"
16 X 25 X 1 (1)
20 X 25 X 1 (1)
24−1/2"
16 X 25 X 1 (2)
24 X 25 X 1 (1)
Duct System
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating
in a room with negative pressure, the flue products can
be pulled back down the vent pipe and into the room. This
reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This
raw gas or toxic fumes might then be distributed throughout the house by the furnace duct system.
Return air can be brought in through the bottom or either
side of the furnace (return air brought into either side furnace allowed in upflow applications only). If a furnace with
bottom return air is installed on a platform, make an airtight
seal between the bottom of the furnace and the platform to
ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equivalent sealing method
between the plenum and the furnace cabinet to ensure a
tight seal. If a filter is installed, size the return air duct to fit
the filter frame.
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform
with American National Standard Institute and the American Society for Testing and Materials (ANSI/ASTM) standards. The solvent shall be free flowing and contain no
lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of
the cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring. Refer to the table 2 below for approved piping and fitting materials.
Use industry-approved standards to size and install the
supply and return air duct system. Refer to ACCA Manual
D. This will result in a quiet and low-static system that has
uniform air distribution.
NOTE − This furnace is not certified for operation in heating
mode (indoor blower operating at selected heating speed)
with an external static pressure which exceeds 0.5 inches
w.c. Operation at these conditions may result in improper
limit operation.
Page 13
CAUTION
Solvent cements for plastic pipe are flammable liquids and should be kept away from all sources of
ignition. Do not use excessive amounts of solvent
cement when making joints. Good ventilation should
be maintained to reduce fire hazard and to minimize
breathing of solvent vapors. Avoid contact of cement
with skin and eyes.
TABLE 2
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe)
Schedule 40 PVC (Cellular Core Pipe)
D1785
F891
Schedule 40 PVC (Fittings)
D2466
Schedule 40 CPVC (Pipe)
F441
Schedule 40 CPVC (Fittings)
SDR−21 PVC or SDR−26 PVC (Pipe)
F438
D2241
SDR−21 CPVC or SDR−26 CPVC (Pipe)
F442
Schedule 40 ABS Cellular Core DWV (Pipe)
F628
Schedule 40 ABS (Pipe)
D1527
Schedule 40 ABS (Fittings)
D2468
ABS−DWV (Drain Waste & Vent)
(Pipe & Fittings)
D2661
PVC−DWV (Drain Waste & Vent)
Pipe & Fittings)
D2665
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer
PVC Solvent Cement
CPVC Solvent Cement
ABS Solvent Cement
ASTM
SPECIFICATION
F656
D2564
F493
D2235
PVC/CPVC/ABS All Purpose Cement For
Fittings & Pipe of the same material
D2564, D2235, F493
ABS to PVC or CPVC Transition Solvent
Cement
D3138
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
MARKING
IMPORTANT
ML193UH exhaust and intake connections are made
of PVC. Use PVC primer and solvent cement when
using PVC vent pipe. When using ABS vent pipe, use
transitional solvent cement to make connections to
the PVC fittings in the unit.
Use PVC primer and solvent cement or ABS solvent cement
meeting ASTM specifications, refer to Table 2. As an alternate, use all purpose cement, to bond ABS, PVC, or CPVC
pipe when using fittings and pipe made of the same materials. Use transition solvent cement when bonding ABS to either PVC or CPVC.
Low temperature solvent cement is recommended during
cooler weather. Metal or plastic strapping may be used for
vent pipe hangers. Uniformly apply a liberal coat of PVC
primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth
of fitting socket.
Canadian Applications Only − Pipe, fittings, primer
and solvent cement used to vent (exhaust) this appliance must be certified to ULC S636 and supplied by a
single manufacturer as part of an approved vent (exhaust) system. In addition, the first three feet of vent
pipe from the furnace flue collar must be accessible for
inspection.
ULCS636
ABS to PVC or CPVC Transition Cement
Page 14
TABLE 3
OUTDOOR TERMINATION USAGE
STANDARD
Input Size
045
070
090
110
135
Vent
Pipe
Dia. in.
FlushMount
Kit
Wall Kit
CONCENTRIC
Wall Ring Kit
2 inch
1−1/2 inch
2 inch
71M80
(US)
444W92
(CA)
69M29
(US)
444W92
(CA)
3 inch
2 inch
3 inch
51W11
22G44 (US)
430G28 (CA)
44J40
(US)
481J20 (CA)
15F74
2
3YES
YES
1YES
1YES
5YES
2YES
2−1/2
3YES
YES
1YES
1YES
5YES
2YES
3
3YES
YES
1YES
1YES
5YES
2YES
2
3YES
YES
1YES
1YES
5YES
2YES
2−1/2
3YES
YES
1YES
1YES
5YES
2YES
3
3YES
YES
1YES
1YES
5YES
2YES
2
3YES
YES
YES
5YES
YES
YES
2−1/2
3YES
YES
YES
5YES
YES
YES
3
3YES
YES
YES
5YES
YES
YES
2
YES
YES
YES
5YES
YES
YES
2−1/2
YES
YES
5YES
YES
YES
3
YES
YES
5YES
YES
YES
3
YES
YES
5YES
Field
Fabricated
60L46 (US)
(CA)
444W93
YES
NOTE − Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length
calculations. See vent length tables.
1Requires field−provided outdoor 1−1/2" exhaust accelerator.
2Concentric kits 71M80 and 44W92 include 1−1/2" outdoor accelerator, when uses with 045 and 070 input models.
3 Flush mount kit 51W11 includes 1−1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.
4 Termination kits 30G28, 44W92, 4493 and 81J20 are certified to ULC S636 for use in Canada only.
5 See table 8 for vent accelerator requirements.
Joint Cementing Procedure
All cementing of joints should be done according to the
specifications outlined in ASTM D 2855.
NOTE − A sheet metal screw may be used to secure the
intake pipe to the connector, if desired. Use a drill or self
tapping screw to make a pilot hole.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system
check. Allow fumes to dissipate for at least 5 minutes
before placing unit into operation.
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe
may remove cement from fitting socket and result in a
leaking joint.
3 − Clean and dry surfaces to be joined.
Page 15
4 − Test fit joint and mark depth of fitting on outside of pipe.
5 − Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket
surface of fitting and male end of pipe to depth of fitting
socket.
NOTE − Time is critical at this stage. Do not allow primer to dry before applying cement.
6 − Promptly apply solvent cement to end of pipe and inside socket surface of fitting. Cement should be applied lightly but uniformly to inside of socket. Take
care to keep excess cement out of socket. Apply second coat to end of pipe.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe
are wet with cement, forcefully insert end of pipe into
socket until it bottoms out. Turn PVC pipe 1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. DO NOT turn ABS or cellular
core pipe.
NOTE − Assembly should be completed within 20 seconds after last application of cement. Hammer blows
should not be used when inserting pipe.
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a
bead around its entire perimeter. Any gaps may indicate an improper assembly due to insufficient solvent.
9 − Handle joints carefully until completely set.
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced
by ML193)
Venting Practices
REPLACING FURNACE THAT
WAS PART OF A COMMON
VENT SYSTEM
WATER
HEATER
OPENINGS
(To Adjacent
Room)
Piping Suspension Guidelines
SCHEDULE 40
PVC − 5’
all other pipe* − 3’
If an ML193UH furnace replaces a furnace which
was commonly vented with another gas appliance,
the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the
original furnace flue products, the existing vent pipe
is probably oversized for the single water heater or
other appliance. The vent should be checked for
proper draw with the remaining appliance.
* See table 2 for allowable pipe.
NOTE − Isolate piping at the point where it exits the outside wall or
roof in order to prevent transmission of vibration to the structure.
Wall Thickness Guidelines
24" maximum
3/4" minimum
FIGURE 21
Exhaust Piping (Figures 24 and 25)
inside
Wall
outside
Route piping to outside of structure. Continue with installation following instructions given in piping termination section.
CAUTION
insulation
(if required)
FIGURE 20
1 − In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on
all sides of pipe through center of hole using a hanger.
2 − When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a
vacation home, make provisions for draining condensate collection trap and lines.
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end
is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pressure and must be completely sealed to prevent leakage of combustion products into the living space.
Page 16
Use the following steps to correctly size vent pipe diameter.
Vent Piping Guidelines
The ML193UH can be installed as either a Non−Direct
Vent or a Direct Vent gas central furnace.
NOTE − In Non-Direct Vent installations, combustion air is
taken from indoors and flue gases are discharged outdoors.
In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing −− Size pipe according to
tables 4 and 5. Count all elbows inside and outside the
home. Table 4 lists the minimum vent pipe lengths permitted. Table 5 lists the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as
it exits the termination. Refer to table 8.
In some applications which permit the use of several different sizes of vent pipe, a combination vent pipe may be
used. Contact Lennox’ Application Department for assistance in sizing vent pipe in these applications.
NOTE − The exhaust collar on all models is sized to accommodate 2" Schedule 40 vent pipe. In horizontal applications, any transition to exhaust pipe larger than 2"
must be made in vertical runs of the pipe. Therefore a 2"
elbow must be added before the pipe is transitioned to
any size larger than 2". This elbow must be added to the
elbow count used to determine acceptable vent lengths.
Contact the Application Department for more information
concerning sizing of vent systems which include multiple
pipe sizes.
Piping Size Process
1
2
3
What is the
furnace capacity?
045, 070, 090,
110 or 135?
Which style termination
being used?
Standard or concentric?
See table 3.
Which needs
most elbows?
Intake or
exhaust?
How many elbows?
4 Count all elbows inside
and outside house.
5
Desired pipe size?
2", 2−1/2", 3"
Exhaust Pipe
Exhaust Pipe
Horizontal
Gas Furnace
6
What is the altitude of
the furnace installation?
7
Use table 5 or 6 to find
max intake or exhaust pipe
length. Includes all vent
pipe and elbows inside
and outside the house.
12” Min .
12” ma x
of straight pip e
NOTE − All horizontal runs of exhaust pipe must slope back toward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm)
of horizontal run is mandatory for drainage.
NOTE − Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE − Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
FIGURE 23
FIGURE 22
TABLE 4
MINIMUM VENT PIPE LENGTHS
ML193UH
MODEL
MIN. VENT LENGTH*
IMPORTANT
15 ft. or
5 ft plus 2 elbows or
10 ft plus 1 elbow
135
*Any approved termination may be added to the minimum length listed.
045, 070, 090, 110
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze−ups
and may block the terminations.
Page 17
TABLE 5
Maximum Allowable Intake or Exhaust Vent Length in Feet
NOTE − Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe
size.
NOTE − Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Number Of
90° Elbows
Used
1
2
3
4
5
6
7
8
9
10
Number Of
90° Elbows
Usedl
1
2
3
4
5
6
7
8
9
10
045
81
76
71
66
61
56
51
46
41
36
045
73
68
63
58
53
48
43
38
33
28
070
66
61
56
51
46
41
36
31
26
21
070
58
53
48
43
38
33
28
23
18
13
2" Pipe
Model
090
44
39
34
29
24
19
14
110
24
19
14
n/a
n/a
2" Pipe
Model
090
42
37
32
27
22
17
12
n/a
110
22
17
12
n/a
Standard Termination at Elevation 0 − 10,000
2−1/2" Pipe
Model
135
045
070
090
110
135
115
100
68
43
110
95
63
38
105
90
58
33
100
85
53
28
95
80
48
23
n/a
n/a
90
75
43
18
85
70
38
13
80
65
33
75
60
28
n/a
70
55
23
Concentric Termination Elevation 0 − 10,000
2−1/2" Pipe
Model
135
045
070
090
110
135
105
90
64
39
100
85
59
34
95
80
54
29
90
75
49
24
85
70
44
19
n/a
n/a
80
65
39
14
75
60
34
70
55
29
n/a
65
50
24
60
45
19
045
137
132
127
122
117
112
107
102
97
92
045
121
116
111
106
101
96
91
86
81
76
070
137
132
127
122
117
112
107
102
97
92
3" Pipe
Model
090
118
113
108
103
98
93
88
83
78
73
110
118
113
108
103
98
93
88
83
78
73
135
114
109
104
99
94
89
84
79
74
69
070
121
116
111
106
101
96
91
86
81
76
3" Pipe
Model
090
114
109
104
99
94
89
84
79
74
69
110
114
109
104
99
94
89
84
79
74
69
135
105
100
95
90
85
80
75
70
65
60
TABLE 6
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated
Attic or Crawl Space For Intake Air in Feet
NOTE − Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Number Of
90° Elbows
Used
1
2
3
4
5
6
7
8
9
045
71
66
61
56
51
46
41
36
31
070
56
51
46
41
36
31
26
21
16
2" Pipe
Model
090
34
29
24
19
14
9
4
n/a
Standard Termination at Elevation 0 − 10,000
2−1/2" Pipe
Model
110
135
045
070
090
110
135
14
100
95
53
28
9
95
80
48
23
4
90
75
43
18
85
70
38
13
80
65
33
8
n/a
n/a
75
60
28
3
n/a
70
55
23
65
60
18
n/a
60
45
13
Page 18
045
117
112
107
102
97
92
87
82
77
070
117
112
107
102
97
92
87
82
77
3" Pipe
Model
090
98
93
88
83
78
73
68
63
58
110
98
93
88
83
78
73
68
63
58
135
94
89
84
79
74
69
64
59
54
TYPICAL EXHAUST PIPE CONNECTIONS IN UPFLOW DIRECT OR
NON−DIRECT VENT APPLICATIONS
Pipe size determined in table 5
2”
2”
2”
or
3”
2”
2”
or
TRANSITION
*2”
EXHAUST
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE − Exhaust pipe and intake pipe must be the same diameter.
FIGURE 24
TYPICAL EXHAUST PIPE CONNECTIONS IN HORIZONTAL DIRECT OR
NON−DIRECT VENT APPLICATIONS
(RIGHT HAND DISCHARGE SHOWN)
12" max.
45°
MAX
3”
2”
2”
TRANSITION
2”
or
2”
45°
MAX
*2”
2”
*2”
SIDE VIEW
EXHAUST
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE − Exhaust pipe and intake pipe must be the same diameter.
FIGURE 25
Page 19
TYPICAL AIR INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT VENT APPLICATIONS
2”
or
Pipe size determined in table 5
3”
TRANSITION
AIR INTAKE
*2”
2”
2”
2”
or
2”
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE − Intake and exhaust pipe must be the same diameter.
FIGURE 26
TYPICAL AIR INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT VENT APPLICATIONS
(RIGHT HAND DISCHARGE SHOWN)
3”
2”
2”
or
2”
TRANSITION
*2"
2”
2”
*2"
AIR INTAKE
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE − Intake and exhaust pipe must be the same diameter.
FIGURE 27
Page 20
Intake Piping
TYPICAL AIR INTAKE PIPE CONNECTIONS
The ML193UH furnace may be installed in either direct
vent or non−direct vent applications. In non−direct vent
applications, when intake air will be drawn into the furnace
from the surrounding space, the indoor air quality must be
considered and guidelines listed in Combustion, Dilution
and Ventilation Air section must be followed.
HORIZONTAL NON−DIRECT VENT APPLICATIONS
(Horizontal Right−Hand Air Discharge Application Shown)
PVC pipe
Follow the next two steps when installing the unit in Direct
Vent applications, where combustion air is taken from
outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct
vent applications (outdoors).
coupling
OR
1 − Use transition solvent cement or a sheet metal screw
to secure the intake pipe to the inlet air connector.
INTAKE
DEBRIS
SCREEN
(Provided)
2 − Route piping to outside of structure. Continue with
installation following instructions given in general
guide lines for piping terminations and intake and exhaust piping terminations for direct vent sections. Refer to table 5 for pipe sizes.
NOTE − Debris screen may be positioned straight out
(preferred) or with an elbow rotated to face down.
TYPICAL AIR INTAKE PIPE CONNECTIONS
FIGURE 29
UPFLOW NON−DIRECT
VENT APPLICATIONS
Follow the next two steps when installing the unit in NonDirect Vent applications where combustion air is taken
from indoors and flue gases are discharged outdoors.
INTAKE
DEBRIS
SCREEN
(Provided)
1 − Use field−provided materials and the factory−provided
air intake screen to route the intake piping as shown in
figure 28 or 29. Maintain a minimum clearance of 3"
(76mm) around the air intake opening. The air intake
opening (with the protective screen) should always be
directed forward or to either side in the upflow position,
and either straight out or downward in the horizontal
position.
The air intake piping must not terminate too close
to the flooring or a platform. Ensure that the intake
air inlet will not be obstructed by loose insulation
or other items that may clog the debris screen.
NOTE − Debris screen and elbow may be rotated, so that
screen may be positioned to face forward or to either side.
2 − If intake air is drawn from a ventilated attic (figure 30)
or ventilated crawlspace (figure 31) the exhaust vent
length must not exceed those listed in table 7. If 3" diameter pipe is used, reduce to 2" diameter pipe at the
termination point to accommodate the debris
screen.Use a sheet metal screw to secure the intake
pipe to the connector, if desired.
FIGURE 28
3 − Use a sheet metal screw to secure the intake pipe to
the connector, if desired.
Page 21
CAUTION
If this unit is being installed in an application with
combustion air coming in from a space serviced by
an exhaust fan, power exhaust fan, or other device
which may create a negative pressure in the space,
take care when sizing the inlet air opening. The inlet air opening must be sized to accommodate the
maximum volume of exhausted air as well as the
maximum volume of combustion air required for
all gas appliances serviced by this space.
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
Roof Terminated
Exhaust Pipe
*Intake Debris
Screen
(Provided)
Furnace
* See table 6 for maximum vent lengths
NOTE−The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 30
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Ventilation
Louvers
(Crawl space)
Furnace
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken
from indoors and the flue gases are discharged to the outdoors. The ML193UH is then classified as a non-direct
vent, Category IV gas furnace.
In Direct Vent applications, combustion air is taken from
outdoors and the flue gases are discharged to the outdoors. The ML193UH is then classified as a direct vent,
Category IV gas furnace.
In both Non-Direct Vent and Direct Vent applications, the
vent termination is limited by local building codes. In the
absence of local codes, refer to the current National Fuel
Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and current
CSA−B149 Natural Gas and Propane Installation Codes in
Canada for details.
Position termination according to location given in figure 32
or 33. In addition, position termination so it is free from any
obstructions and 12" above the average snow accumulation.
At vent termination, care must be taken to maintain
protective coatings over building materials (prolonged
exposure to exhaust condensate can destroy protective
coatings). It is recommended that the exhaust outlet not be
located within 6 feet (1.8m) of a condensing unit because
the condensate can damage the painted coating.
NOTE − See table 7 for maximum allowed exhaust pipe
length without insulation in unconditioned space during
winter design temperatures below 32°F (0°C). If required
exhaust pipe should be insulated with 1/2" (13mm) Armaflex or equivalent. In extreme cold climate areas, 3/4"
(19mm) Armaflex or equivalent may be necessary. Insulation on outside runs of exhaust pipe must be painted or
wrapped to protect insulation from deterioration. Exhaust
pipe insulation may not be necessary in some specific applications.
IMPORTANT
Do not use screens or perforated metal in exhaust
terminations. Doing so will cause freeze−ups and
may block the terminations.
*Intake Debris Screen Provided)
* See table 6 for maximum vent lengths
NOTE−The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 31
IMPORTANT
For Canadian Installations Only:
In accordance to CSA International B149 installation
codes, the minimum allowed distance between the
combustion air intake inlet and the exhaust outlet of
other appliances shall not be less than 12 inches
(305mm).
Page 22
TABLE 7
Maximum Allowable Exhaust Vent Pipe Length Without Insulation In Unconditioned Space For
Winter Design Temperatures Single − Stage High Efficiency Furnace
Winter Design
Temperatures1 °F (°C)
32 to 21
(0 to −6)
20 to 1
(−7 to −17)
0 to −20
(−18 to −29)
Unit Input Size
Vent Pipe
Diameter
045
070
090
110
135
2 in.
26
44
44
24
N/A
2−1/2 in.
18
32
50
58
N/A
3 in.
14
26
38
55
60
2 in
16
28
40
24
N/A
2−1/2 in.
12
20
30
44
N/A
3 in.
9
16
26
32
40
2 in.
10
20
30
24
N/A
2−1/2 in.
8
14
20
32
N/A
3 in.
4
10
16
26
30
1Refer
to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
NOTE − Maximum unisulated vent lengths listed cannot exceed the maximum allowable intake or exhaust vent length listed in table 5.
Page 23
VENT TERMINATION CLEARANCES
FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
H
A
D
E
B
L
Fixed
Closed
Operable
F
B
B
C
Fixed
Closed
Operable
I
M
B
K
J
A
B
AREA WHERE TERMINAL
IS NOT PERMITTED
AIR SUPPLY INLET
VENT TERMINAL
US Installations1
A=
Clearance above grade, veranda,
porch, deck or balcony
B=
Clearance to window or
door that may be opened
C=
Clearance to permanently
closed window
D=
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610 mm)
from the center line of the terminal
E=
Clearance to unventilated soffit
F=
Clearance to outside corner
G=
Clearance to inside corner
H=
Clearance to each side of center line extended above meter / regulator assembly
I=
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the combustion air inlet to any other appliance
J=
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
4 feet (1.2 m) below or to side of opening;
1 foot (30cm) above opening
Canadian Installations2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12"
* 12"
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* No minimum to outside corner
**
* Equal to or greater than soffit depth.
* No minimum to outside corner
**
* 3 feet (.9m) within a height 15 feet (4.5m) 3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
above the meter / regulator assembly
3 feet (.9m)
* 3 feet (.9m)
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
K=
Clearance to mechanical air supply inlet
L=
Clearance above paved sidewalk or
paved driveway located on public property
M = Clearance under veranda, porch, deck or balcony
3 feet (.9m) above if within 10 feet
(3m) horizontally
7 feet (2.1m)
7 feet (2.1m)
*12 inches (305mm)
1 In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2 In accordance with the current CSA B149.1, Natural Gas and Propane Installation
Code
A vent shall not terminate directly above a sidewalk or paved driveway that is
located between two single family dwellings and serves both dwellings.
Permitted only if veranda, porch, deck or balcony is fully open
on a minimum of two sides beneath the floor. Lennox recommends
avoiding this location if possible.
12 inches (305mm)
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these installation instructions."
FIGURE 32
Page 24
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
H
A
D
E
B
L
Fixed
Closed
Operable
F
B
B
C
I
Fixed
Closed
Operable
M
B
A
K
J
B
AREA WHERE TERMINAL
IS NOT PERMITTED
AIR SUPPLY INLET
VENT TERMINAL
US Installations1
A=
Clearance above grade, veranda,
porch, deck or balcony
B=
Clearance to window or
door that may be opened
C=
Clearance to permanently
closed window
D=
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610mm)
from the center line of the terminal
E=
Clearance to unventilated soffit
F=
Clearance to outside corner
G=
Clearance to inside corner
H=
Clearance to each side of center line extended above meter / regulator assembly
I=
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the combustion air inlet to any other appliance
J=
K=
Clearance to mechanical air supply inlet
L=
Clearance above paved sidewalk or
paved driveway located on public property
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
1 In
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for apBtuh (3kw), 12 inches (305mm) for
pliances > 10,000 Btuh (3kw) and <50,000
appliances > 10,000 Btuh (3kw) and
Btuh (15 kw), 12 inches (305mm) for ap<100,000 Btuh (30kw), 36 inches (.9m)
pliances > 50,000 Btuh (15kw)
for appliances > 100,000 Btuh (30kw)
* 12"
* 12"
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
* No minimum to outside corner
*
* 3 feet (.9m)
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for apBtuh (3kw), 12 inches (305mm) for
pliances > 10,000 Btuh (3kw) and <50,000
appliances > 10,000 Btuh (3kw) and
Btuh (15 kw), 12 inches (305mm) for ap<100,000 Btuh (30kw), 36 inches (.9m)
pliances > 50,000 Btuh (15kw)
for appliances > 100,000 Btuh (30kw)
3 feet (.9m) above if within 10 feet
6 feet (1.8m)
(3m) horizontally
7 feet (2.1m)
* 7 feet (2.1m)
M = Clearance under veranda, porch, deck or balcony
2 In
Canadian Installations2
*12 inches (305mm)
accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
A vent shall not terminate directly above a sidewalk or paved driveway that is located
between two single family dwellings and serves both dwellings.
Permitted only if veranda, porch, deck or balcony is fully open on a minimum of
two sides beneath the floor. Lennox recommends avoiding this location if possible.
FIGURE 33
Page 25
12 inches (305mm)
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these
installation instructions."
Details of Intake and Exhaust Piping Terminations for
Direct Vent Installations
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.
NOTE − Flue gas may be slightly acidic and may adversely
affect some building materials. If any vent termination is
used and the flue gasses may impinge on the building material, a corrosion−resistant shield (minimum 24 inches
square) should be used to protect the wall surface. If the
optional tee is used, the protective shield is recommended.
The shield should be constructed using wood, plastic,
sheet metal or other suitable material. All seams, joints,
cracks, etc. in the affected area should be sealed using an
appropriate sealant. See figure 39.
Intake and exhaust pipes may be routed either horizontally
through an outside wall or vertically through the roof. In attic
or closet installations, vertical termination through the roof
is preferred. Figures 34 through 48 show typical terminations.
1 − Intake and exhaust terminations are not required to be
in the same pressure zone. You may exit the intake on
one side of the structure and the exhaust on another
side (figure 35). You may exit the exhaust out the roof
and the intake out the side of the structure (figure 36).
2 − Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to illustrations). Maximum separation is 3" (76mm) on roof
terminations and 6" (152mm) on side wall terminations.
3 − On roof terminations, the intake piping should terminate straight down using two 90° elbows (See figure
34).
4 − Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust piping at the point where it exits the structure to improve
the velocity of exhaust away from the intake piping.
See table 8.
NOTE − Care must be taken to avoid recirculation of exhaust back into intake pipe.
5 − On field supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches
(305mm) for 2" PVC and 20 inches (508mm) for 3"
(76mm) PVC beyond the outside wall. Intake piping
should be as short as possible. See figures 37 and 38.
6 − On field supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of
the intake pipe without a termination elbow is 8" and a
minimum distance of 6" with a termination elbow. See
figures 37 and 38.
TABLE 8
FIGURE 35
Inches(mm)
3"(76mm) MAX.
SIZE TERMINATION
PIPE PER TABLE 8.
UNCONDITIONED
ATTIC SPACE
8" (203mm) MIN
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
12" (305mm) ABOVE
AVERAGE SNOW
ACCUMULATION
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 34
Exiting Exhaust and Intake Vent
(no common pressure zone)
Exhaust
Pipe
Furnace
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
Exiting Exhaust and Intake Vent
(no common pressure zone)
Roof Terminated
Exhaust Pipe
EXHAUST PIPE TERMINATION SIZE REDUCTION
ML193UH
MODEL
*045 and 070
*090
110
135
Termination
Pipe Size
1−1/2" (38mm)
2" (51mm)
2" (51mm)
2" (51mm)
Furnace
*ML193UH−045, −070 and −090 units with the flush mount
termination must use the 1−1/2"accelerator supplied with the
kit unless a tee is used for termination as shown figure 39.
Page 26
FIGURE 36
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
FIELD FABRICATED WALLL TERMINATION
OR (15F74) WALL RING TERMINATION KIT
With INTAKE ELBOW
FIELD FABRICATED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
NOTE − FIELD PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
NOTE − FIELD PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
1/2" (13mm) ARMAFLEX
INSULATION IN UNCONDITIONED SPACE
1/2" (13mm) ARMAFLEX
INSULATION IN UNCONDITIONED SPACE
SIZE TERMINATION
PER TABLE 8
SIZE TERMINATION
PER TABLE 8
D
D
B
C
B
STRAIGHT
APPPLICATION
A
C
A
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
D
E
* WALL
SUPPORT
D
E
* WALL
SUPPORT
B
B
A
A
C
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
EXTENDED
APPLICATION
C
EXTENDED
APPLICATION
See venting table 5 for maximum venting lengths with this
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
A−Minimum clearance
above grade or average
snow accumulation
See venting table 5 for maximum venting lengths with this
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
12" (305MM)
12" (305MM)
6" (152MM)
6" (152MM)
8" (203MM)
8" (203MM)
12" (305MM)
20" (508MM)
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
6" (152MM)
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
6" (152MM)
STRAIGHT
APPPLICATION
A−Minimum clearance
above grade or average
snow accumulation
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
12" (305MM)
12" (305MM)
6" (152MM)
6" (152MM)
6" (152MM)
6" (152MM)
12" (305MM)
20" (508MM)
6" (152MM)
6" (152MM)
FIGURE 38
FIGURE 37
Page 27
7 − If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other obstructions, piping must be supported every 24"
(610mm) as shown in figures 37 and 38. In addition,
close coupled wall termination kits must be extended
for use in this application. See figures 46 and 47.
When exhaust and intake piping must be run up an
outside wall, the exhaust piping must be terminated
with pipe sized per table 8.The intake piping may be
equipped with a 90° elbow turndown. Using turndown
will add 5 feet (1.5m) to the equivalent length of the
pipe.
8 − A multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
shown in figure 42.
B
B
D
D
C
Intake
C
3
1
Front View of
Intake and Exhaust
A
Exhaust
A
2
Intake
Exhaust
D
TABLE 9
1
E
2" (51mm)
Vent Pipe
B
A− Clearance above
grade or average snow
accumulation
12"
C
2
A
B−Horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Exhaust pipe length
E−Wall support distance
from top of each pipe
(intake/exhaust)
1 The
12" (305MM) Min.
3" (76mm)
Vent Pipe
12" (305MM) Min.
6" (152MM) Min.
6" (152MM) Min.
24" (610 MM) Max 24" (610 MM) Max
9" (227MM) Min.
9" (227MM) Min.
12" (305MM) Min. 12" (305MM) Min.
16" (405 MM) Max. 20" (508MM) Max.
6" (152MM) Max.
6" (152MM) Max.
exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2 As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches
square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints,
cracks, etc. in affected area, should be sealed using an appropriate sealant.
3Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away
from adjacent property. The exhaust must never be directed toward the combustion air inlet.
FIGURE 39
Page 28
1 1/2" (38mm) accelerator
provided on 71M80 & 44W92
kits for ML193UH045P24B,
070P24B & 070P36B
EXHAUST
VENT
12” (305mm)
Minimum
Above Average
Snow
Accumulation
Top View
1/2" (13mm) Foam Insulation
in Unconditioned Space
SHEET METAL STRAP
(Clamp and sheet metal strap
must be field installed to support
the weight of the termination kit.)
CLAMP
FIELD−
PROVIDED
REDUCER MAY
BE REQUIRED
TO ADAPT
LARGER VENT
PIPE SIZE TO
TERMINATION
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
INTAKE
AIR
EXHAUST
VENT
EXHAUST VENT
Front View
SIZE
TERMINATION
PIPE PER
TABLE 8.
INTAKE
AIR
EXHAUST
VENT
Top View
1/2" (13MM) Foam Insulation
in Unconditioned Space
INTAKE 12" (305mm) Min.
above grade or
AIR
CLAMP
(Not Furnished)
6 (152mm) MIN.
FIGURE 43
1−1/2" (38mm) accelerator
provided on 71M80 & 44W92
kits for ML193UH045P24B,
070P24B & 070P36B
OUTSIDE
WALL
INTAKE AIR
DIRECT VENT WALL TERMINATION KIT
(30G28 or 81J20)
FIGURE 40
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
EXHAUST VENT
OUTSIDE WALL
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
INTAKE
AIR
SIZE
TERMINATION
PIPE PER
TABLE 8.
INTAKE
AIR
FLASHING
(Not Furnished)
INTAKE
AIR
EXHAUST VENT
Front View
average snow
accumulation.
GRADE
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
FIELD−
PROVIDED
REDUCER MAY
BE REQUIRED
TO ADAPT
LARGER VENT
PIPE SIZE TO
TERMINATION
EXHAUST VENT
INTAKE AIR
8" (206MM) MIN.
OUTSIDE WALL
DIRECT VENT WALL TERMINATION KIT
(22G44 or 44J40)
FIGURE 41
FIGURE 44
EXHAUST
VENT
12"
(305mm)
5−1/2"
(140mm)
5"
(127mm)
2" EXTENSION FOR 2" PVC
PIPE1" EXTENSION FOR 3"
PVC PIPE
INTAKE
AIR
18" MAX.
(457mm)
FURNACE
EXHAUST
PIPE
4’’
Front View
EXHAUST VENT
Inches (mm)
12" (305mm) Min.
above grade or
average snow
INTAKE accumulation.
AIR
optional intake elbow
FURNACE
INTAKE
PIPE
GLUE EXHAUST
END FLUSH INTO
TERMINATION
FLAT
SIDE
Side View
1−1/2" ACCELERATOR
(all −45, −070 and −090 units)
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
(22G44, 44J40, 30G28 or 81J20)
FLUSH−MOUNT SIDE WALL TERMINATION
51W11
FIGURE 42
FIGURE 45
Page 29
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 22G44 (US)
3 inch (76 mm) 44J40 (US)
If intake and exhaust pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions, field−
fabricated piping must be installed.
WALL SUPPORT*
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
8” (203 mm) Min. for 2” (51 mm) & 3” (76 mm) DIA. pipe
between the end of the exhaust pipe and intake pipe
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12”
(305 mm)
EXHAUST
AIR
6” (152 mm)
Maximum
1/2” (13 mm)
FOAM INSULATION
(Field−Furnished)
INTAKE
AIR
INTAKE
AIR
EXHAUST
AIR
5” (127 mm)
8” (203 mm) Min.
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
ÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉ
GRADE
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
ÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉ
5−1/2”
(140 mm)
GRADE
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIGURE 46
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 30G28 (WTK Canada)
3 inch (76 mm) 81J20 (WTK Canada)
See Installation Instructions for additional information.
If intake and exhaust pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions, field−
fabricated piping must be installed.
WALL SUPPORT*
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12”
(305 mm)
EXHAUST
AIR
6” (152 mm)
Maximum
1/2” (13 mm)
FOAM INSULATION
(Field−Furnished)
INTAKE
AIR
6” (152 mm)
Minimum
INTAKE
AIR
EXHAUST
AIR
5” (127 mm)
6” (152 mm)
Minimum
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
ÉÉÉÉÉÉÉÉÉÉÉÉ
GRADE
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
ÉÉÉÉÉÉÉÉÉÉÉ
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIGURE 47
Page 30
5−1/2”
(140 mm)
GRADE
ML193UH DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
3"−8"
(76mm−203mm)
8" − 12"
(203mm − 305mm)
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE *
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
PVC REDUCER
12" MIN.
(305mm)
Above Grade or
average snow
accumulation
ALTERNATE
INTAKE PIPE
3" − 8"
(76mm−
203mm)
INSULATE
TO FORM
SEAL
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL TERMINATION KIT
EXTERIOR
PORTION OF
CHIMNEY
*SIZE TERMINATION
PIPE PER TABLE 8.
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 48
Details of Exhaust Piping Terminations for Non-Direct
Vent Applications
Exhaust pipes may be routed either horizontally through an
outside wall or vertically through the roof. In attic or closet
installations, vertical termination through the roof is preferred. Figures 49 through 52 show typical terminations.
1 − Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in
table 8.The specified pipe size ensures proper velocity required to move the exhaust gases away from the
building.
2 − On field supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches
(305mm) for 2" PVC and 20 inches (508mm) for 3"
(76mm) PVC beyond the outside wall. See figure 50.
12" (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
1/2" (13mm)
ARMAFLEX
INSULATION
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
SIZE TERMINATION
PIPE PER TABLE 8.
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
INTAKE PIPE
INSULATION (optional)
1/2" (13mm) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE
FIGURE 50
3 − If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions, piping must be supported every 24 inches (610mm) as
shown in figure 51. When exhaust piping must be run
up an outside wall, any reduction in exhaust pipe size
must be done after the final elbow.
12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)
UNCONDITIONED
SPACE
6" (152mm)
Max
*WALL SUPPORT
OUTSIDE WALL
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE TO
TERMINATION
12" (305mm)
ABOVE GRADE OR
AVERAGE SNOW
ACCUMULATION
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
1/2" (13mm) FOAM
INSULATION
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION
EXTENDED OR (15F74) WALL TERMINATION VENT PIPE
EXTENDED
*Use wall support every 24" (610). Use two supports if extension is
greater than 24" but less than 48".
SIZE TERMINATION
PIPE PER TABLE 8.
FIGURE 51
1/2" (13mm) FOAM
INSULATION
3" (76mm) OR
2" (51mm) PVC
SIZE TERMINATION
PIPE PER
TABLE 8.
UNCONDITIONED
ATTIC SPACE
PROVIDE SUPPORT
FOR EXHAUST LINES
NON−DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 49
Page 31
CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
ML193UH NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
SIZE TERMINATION
PIPE PER TABLE 8.
Trap
(same on
right side)
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE
1−1/2 in.
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
Plug
(same on left side)
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
EXTERIOR
PORTION OF
CHIMNEY
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 52
Condensate Piping
This unit is designed for either right- or left-side exit of condensate piping in upflow applications. In horizontal applications, the condensate trap must extend below the unit. An
8" service clearance is required for the condensate trap.
Refer to figures 53 and 54 for condensate trap locations.
Figure 60 shows trap assembly using 1/2" PVC or 3/4"
PVC.
NOTE − If necessary the condensate trap may be installed
up to 5´ away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4" per ft. toward trap.
1 − Determine which side condensate piping will exit the
unit, location of trap, field−provided fittings and length of
PVC pipe required to reach available drain.
2 − Use a 3/8 allen wrench and remove plug (figure 53)
from the cold end header box at the appropriate location on the side of the unit. Install field−provided 1/2
NPT male fitting into cold end header box. Use Teflon
tape or appropriate pipe dope.
NOTE − In upflow applications where side return
air filter is installed on same side as the condensate trap, filter rack must be installed beyond
condensate trap or trap must be re−located to
avoid interference.
FIGURE 53
5 − Figures 55 and 56 show the furnace and evaporator
coil using a separate drain. If necessary the condensate line from the furnace and evaporator coil can
drain together. See figures 57, 58 and 59.
Upflow furnace (figure 58) − In upflow furnace applications the field provided vent must be a minimum 1" to a
maximum 2" length above the condensate drain outlet
connection. Any length above 2" may result in a
flooded heat exchanger if the combined primary drain
line were to become restricted.
Horizontal furnace (figure 59) − In horizontal furnace
applications the field provided vent must be a minimum 4" to a maximum 5" length above the condensate
drain outlet connection. Any length above 5" may result in a flooded heat exchanger if the combined primary drain line were to become restricted.
NOTE − In horizontal applications it is recommended to
install a secondary drain pan underneath the unit and
trap assembly.
NOTE − Vinyl tubing may be used for condensate drain.
Tubing must be 1−1/4" OD X 1" ID and should be
attached to the drain on the trap using a hose clamp.
3 − Install the cap over the clean out opening at the base of
the trap. Secure with clamp. See figure 60.
4 − Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in figure 60. Route the condensate line to an open drain.
Condensate line must maintain a 1/4" downward slope
from the furnace to the drain.
CAUTION
Do not use copper tubing or existing copper condensate lines for drain line.
6 − If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit
Start−Up section.
Page 32
Condensate line must slope downward away from the
trap to drain. If drain level is above condensate trap,
condensate pump must be used. Condensate drain
line should be routed within the conditioned space to
avoid freezing of condensate and blockage of drain
line. If this is not possible, a heat cable kit may be used
on the condensate trap and line. Heating cable kit is
available from Lennox in various lengths; 6 ft. (1.8m) −
kit no. 26K68; 24 ft. (7.3m) − kit no. 26K69; and 50 ft.
(15.2m) − kit no. 26K70.
ML193UH With Evaporator
Coil Using A Separate Drain
Condensate trap
and evaporator coil
drain separately as
shown.
Field−Provided Vent
(1" min. to 2" Max. above
condensate drain connection)
Condensate
Drain Connection
CONDENSATE TRAP LOCATIONS
(Unit shown in upflow position with remote trap)
Field Provided Vent
Min. 1" Above Condensate
Drain Connection
Drain
1" Min.
2" Max.
*5’ max.
PVC Pipe Only
FIGURE 55
Trap Can Be Installed a
Maximum 5’ From Furnace
To Drain
*Piping from furnace must slope down a minimum
of 1/4" per ft. toward trap.
FIGURE 54
ML193UH with Evaporatoir Coil Using a Separate Drain
(Unit shown in horizontal left−hand discharge position)
Field−Provided Vent
(4" min. to 5" Max. above
condensate drain connection)
Evaporator
Coil
4”min
5”max
5’ max.
PVC Pipe Only
Drain Pan
Condensate Drain
Connection
*Piping from furnace and evaporator coil must slope down a minimum of 1/4" per ft. toward trap.
FIGURE 56
Page 33
ML193UH with Evaporator
Coil Using a Common Drain Evaporator
IMPORTANT
Drain Line
Vent Required
When combining the furnace and evaporator
coil drains together, the A/C condensate drain
outlet must be vented to relieve pressure in order for the furnace pressure switch to operate
properly.
Field−Provided Vent
(1" min. to 2" Max. above
condensate drain connection)
Condensate Trap With Optional Overflow Switch
From Evaporator Coil
Condensate
Drain Connection
Field−Provided Vent
(Upflow/Furnace 1" Min. to 2" Max.
Horizontal Furnace 4" Min. to 5" Max. above
condensate drain connection)
Furnace Condensate
Drain Connection
Optional
Overflow Switch
FIGURE 58
To Drain
FIGURE 57
ML193UH with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Field−Provided Vent
(4" min. to 5" Max. above
condensate drain connection)
Evaporator
Coil
4”min
5”max
5’ max.
PVC Pipe Only
Condensate Drain
Connection
Drain Pan
*Piping from furnace and evaporator coil must slope down a minimum of 1/4" per ft. toward trap.
FIGURE 59
Page 34
TRAP / DRAIN ASSEMBLY USING 1/2" PVC OR 3/4" PVC
Optional Condensate Drain Connection
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished)
90° Street Elbow
1/2 inch PVC
(Not Furnished)
1 (25 mm) Min.
2 (50 mm) Max.
Above Top Of
Condensate Drain
Connection In Unit
Condensate Drain
Connection In Unit
90° Street Elbow
1/2 inch PVC
(Furnished)
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished) Condensate Drain
Connection In Unit
Vent
5 Feet
Maximum
90° Elbow 1/2 inch PVC
(Not Furnished)
To
Trap
Optional Drain Piping From Trap
1/2 inch PVC Pipe
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Coupling 1/2 inch slip X slip
(Not Furnished)
Drain Assembly for 1/2 inch Drain Pipe
1/2 inch PVC Pipe
(Not Furnished)
Drain Trap
Assembly
(Furnished)
90° Elbow
1/2 inch PVC
(Not Furnished)
To
Drain
Drain Assembly for 3/4 inch Drain Pipe
Drain Trap
Clean Out
90° Elbow
3/4 inch PVC
(Not Furnished)
To
Drain
90° Elbow
3/4 inch PVC
(Not Furnished)
Drain Trap Assembly with 3/4 inch Piping
To Coupling 3/4 inch slip X slip
Drain
(Not Furnished)
Drain Trap Assembly with 1/2 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. Above Top
Of Condensate Drain Connection In Unit
Drain Trap Assembly
(Furnished)
7
(178)
Vent
Drain Trap Assembly with 3/4 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. Above Top
Of Condensate Drain Connection In Unit
Vent
3/4 inch
1/2 inch
Condensate Drain
Connection In Unit
Condensate Drain
Connection In Unit
To
Drain
To
Drain
FIGURE 60
Page 35
4 − Piping should be sloped 1/4 inch per 15 feet (6mm per
5.6m) upward toward the gas meter from the furnace.
The piping must be supported at proper intervals, every 8 to 10 feet (2.44 to 3.05m), using suitable hangers
or straps. Install a drip leg in vertical pipe runs to serve as
a trap for sediment or condensate.
5 − A 1/8" N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See figure 67.
6 − In some localities, codes may require installation of a
manual main shut-off valve and union (furnished by installer) external to the unit. Union must be of the
ground joint type.
Gas Piping
CAUTION
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet. The flexible connector can then
be added between the black iron pipe and the gas
supply line.
WARNING
IMPORTANT
Do not exceed 600 in−lbs (50 ft−lbs) torque when attaching the gas piping to the gas valve.
1 − Gas piping may be routed into the unit through either
the left- or right-hand side. Supply piping enters into
the gas valve from the side of the valve as shown in
figure 63. Move Bellows grommet to side which gas
line enters. Ensure opposite gas line hole is plugged
with supplied plug.
IMPORTANT
When converting the ML193 unit from natural gas to
LP/propane install the field provided low pressure
switch. See figure 61.
Compounds used on threaded joints of gas piping
must be resistant to the actions of liquified petroleum gases.
Leak Check
After gas piping is completed, carefully check all piping
connections (factory− and field−installed) for gas leaks. Use
a leak detecting solution or other preferred means.
Never use an open flame to test for gas leaks. Check all
connections using a commercially available soap solution
made specifically for leak detection.
The furnace must be isolated from the gas supply system
by closing its individual manual shut-off valve during any
pressure testing of the gas supply system at pressures less
than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
LOW INLET PRESSURE SWITCH
(S145) LOCATION
MANUAL MAIN SHUT−OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
Orange
White
1/8" N.P.T.
PLUGGED TAP
Orange
FURNACE
ISOLATE
GAS VALVE
CAP
FIGURE 62
Gas Valve Shown In Off Position
IMPORTANT
Yellow
FIGURE 61
2 − When connecting gas supply, factors such as length of
run, number of fittings and furnace rating must be considered to avoid excessive pressure drop. Table 10
lists recommended pipe sizes for typical applications.
NOTE − Use two wrenches when connecting gas piping to avoid transferring torque to the manifold.
3 − Gas piping must not run in or through air ducts, clothes
chutes, chimneys or gas vents, dumb waiters or elevator shafts. Center gas line through piping hole. Gas
line should not touch side of unit. See figures 63 and
64.
When testing pressure of gas lines, gas valve must
be disconnected and isolated. See figure 62. Gas
valves can be damaged if subjected to pressures
greater than 1/2 psig (3.48 kPa).
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could
result in serious injury, death, or property damage.
Never use an open flame to test for gas leaks. Check
all connections using a commercially available soap
solution made specifically for leak detection. Some
soaps used for leak detection are corrosive to certain
metals. Carefully rinse piping thoroughly after leak
test has been completed.
Page 36
Left Side Piping
(Standard)
Right Side Piping
(Alternate)
AUTOMATIC
GAS VALVE
(with manual
shut−off valve)
MANUAL
MAIN SHUT−OFF
VALVE
Bellows Grommet
Plug
MANUAL
MAIN SHUT−OFF
VALVE
Plug
GROUND
JOINT
UNION
GROUND
JOINT
UNION
Gas Valve
Gas Valve
DRIP LEG
Bellows Grommet
DRIP LEG
FIELD
PROVIDED
AND INSTALLED
NOTE − BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
FIGURE 63
Horizontal Applications
Possible Gas Piping Configurations
MANUAL
MAIN SHUT−OFF
VALVE
MANUAL
MAIN SHUT−OFF
VALVE
Horizontal Application
Left−Side Air Discharge
GROUND
JOINT
UNION
Bellows Grommet
GROUND
JOINT
UNION
DRIP LEG
Bellows Grommet
DRIP LEG
Gas Valve
Horizontal Application
Right−Side Air Discharge
MANUAL
MAIN SHUT−OFF
VALVE
Gas Valve
FIELD
PROVIDED
AND INSTALLED
Plug
Bellows Grommet
NOTE − BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
FIGURE 64
Page 37
GROUND
JOINT
UNION
DRIP LEG
TABLE 10
GAS PIPE CAPACITY − FT3/HR (kL/HR)
Length of Pipe−Feet(m)
50
60
70
(15.240) (18.288) (21.336)
Nominal
Iron Pipe Size
−Inches(mm)
Internal
Diameter
−Inches(mm)
10
(3.048)
20
(6.096)
30
(9.144)
40
(12.192)
1/2
(12.7)
.622
(17.799)
175
(4.96)
120
(3.40)
97
(2.75)
82
(2.32)
73
(2.07)
66
(1.87)
3/4
(19.05)
.824
(20.930)
360
(10.19)
250
(7.08)
200
(5.66)
170
(4.81)
151
(4.28)
1
(25.4)
1.049
(26.645)
680
(19.25)
465
(13.17)
375
(10.62)
320
(9.06)
1−1/4
(31.75)
1.380
(35.052)
1400
(39.64)
950
(26.90)
770
(21.80)
1−1/2
(38.1)
1.610
(40.894)
2100
(59.46)
460
(41.34)
2
(50.8)
2.067
(52.502)
3950
(111.85)
2−1/2
(63.5)
2.469
(67.713)
3
(76.2)
4
(101.6)
80
(24.384)
90
(27.432)
100
(30.480)
61
(1.73)
57
(1.61)
53
(1.50)
50
(1.42)
138
(3.91)
125
(3.54)
118
(3.34)
110
(3.11)
103
(2.92)
285
(8.07)
260
(7.36)
240
(6.80)
220
(6.23)
205
(5.80)
195
(5.52)
660
(18.69)
580
(16.42)
530
(15.01)
490
(13.87)
460
(13.03)
430
(12.18)
400
(11.33)
1180
(33.41)
990
(28.03)
900
(25.48)
810
(22.94)
750
(21.24)
690
(19.54)
650
(18.41)
620
(17.56)
2750
(77.87)
2200
(62.30)
1900
(53.80)
1680
(47.57)
1520
(43.04)
1400
(39.64)
1300
(36.81)
1220
(34.55)
1150
(32.56)
6300
(178.39)
4350
(123.17)
3520
(99.67)
3000
(84.95)
2650
(75.04)
2400
(67.96)
2250
(63.71)
2050
(58.05)
1950
(55.22)
1850
(52.38)
3.068
(77.927)
11000
(311.48)
7700
(218.03)
6250
(176.98)
5300
(150.07)
4750
(134.50)
4300
(121.76)
3900
(110.43)
3700
(104.77)
3450
(97.69)
3250
(92.03)
4.026
(102.260)
23000
(651.27)
15800
(447.39)
12800
(362.44)
10900
(308.64)
9700
(274.67)
8800
(249.18)
8100
(229.36)
7500
(212.37)
7200
(203.88)
6700
(189.72)
NOTE − Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas appliances, the venting system is likely to be too large to
properly vent the remaining attached appliances.
Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting requirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being
placed into operation, while all other appliances
connected to the venting system are not in
operation:
3 − Close all building doors and windows and all doors between the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4 − Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 − After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle.
6 − After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, widows, exhaust fans, fireplace dampers, and any other gas−burning appliances to their previous mode of operation.
7 − If a venting problem is found during any of the preceding tests, the common venting system must be modified to correct the problem.
1 − Seal any unused openings in the common venting system.
2 − Inspect the venting system for proper size and horizontal
pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.
Page 38
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current standards of the National Fuel Gas Code ANSI Z223.1.
Complete the wiring connections to the equipment. Use the
provided unit wiring diagram and the field wiring shown in
figure 66. Use 18−gauge wire or larger that is suitable for
Class II rating for thermostat connections.
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions to
neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
INTERIOR MAKE−UP BOX INSTALLATION
remove and relocate
plug to unused
opening on left side
Electrically ground the unit according to local codes or, in
the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70) for the USA and
current Canadian Electric Code part 1 (CSA standard
C22.1) for Canada. A green ground wire is provided in the
field make−up box.
NOTE − The ML193UH furnace contains electronic components that are polarity sensitive. Make sure that the furnace
is wired correctly and is properly grounded.
Accessory Terminals
One line voltage EAC" 1/4" spade terminal is provided on
the furnace integrated control. See figure 1 for integrated
control configuration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one
amp can be connected to this terminal with the neutral leg
of the circuit being connected to one of the provided neutral
terminals. If an accessory rated at greater than one amp is
connected to this terminal, it is necessary to use an external relay.
MAKE−UP
BOX
Right Side
FIGURE 65
The unit is equipped with a field make−up box. The make−
up box may be moved to the right side of the furnace to facilitate installation. Seal unused openings on left side with
plugs removed from right side. Secure the excess wire to
the existing harness to protect it from damage.
Refer to figure 66 for schematic wiring diagram and troubleshooting.
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
NOTE − Unit nameplate states maximum current draw.
Maximum Over−Current Protection allowed is 15 AMP.
Holes are on both sides of the furnace cabinet to facilitate
wiring.
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing.
Before connecting the thermostat check to make sure the
wires will be long enough for servicing at a later date. Make
sure that thermostat wire is long enough to facilitate future
removal of blower for service.
One line voltage HUM" 1/4" spade terminal is provided on
the furnace integrated control. See figure 1 for integrated
control configuration. This terminal is energized in the
heating mode when the combustion air inducer is operating. Any humidifier rated up to one amp can be connected
to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If a humidifier rated at greater than one amp is connected to this terminal, it is necessary to use an external relay relay.
Thermostat
Install the room thermostat according to the instructions
provided with the thermostat. See figure 66 for thermostat
designations. If the furnace is being matched with a heat
pump, refer to the FM21 installation instruction or appropriate dual fuel thermostat instructions.
Indoor Blower Speeds
Page 39
1 − When the thermostat is set to FAN ON," the indoor
blower will run continuously on the heating speed
when there is no cooling or heating demand.
2 − When the ML193UH is running in the heating mode,
the indoor blower will run on the heating speed.
3 − When there is a cooling demand, the indoor blower will
run on the cooling speed.
Generator Use − Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
D The furnace requires 120 volts + 10% (Range: 108
volts to 132 volts)
D The furnace operates at 60 Hz + 5% (Range: 57 Hz to
63 Hz)
D The furnace integrated control requires both polarity
and proper ground. Both polarity and proper grounding
should be checked before attempting to operate the
furnace on either permanent or temporary power
D Generator should have a wave form distortion of less
than 5% THD (total harmonic distortion).
TYPICAL ML193UH WIRING DIAGRAM
FIGURE 66
Page 40
Integrated Control
INTEGRATED CONTROL
(Automatic Hot Surface Ignition System)
HUM
LINE
XFMR
EAC
COOL
HEAT
PARK
CONT
NEUTRALS
TWIN
TERMINAL DESIGNATIONS
Humidifier (120VAC)
Input (120VAC)
Transformer (120VAC)
Indoor Air Qality Accessory Air Cleaner (120VAC)
Blower − Cooling Speed (120VAC)
Blower − Heating Speed (120VAC)
Dead terminals to park alternate spd taps
Continuous blower
Neutral terminals (120VAC)
Twinning Terminal (24VAC)
LED
PUSH BUTTON
TWIN
BLOWER OFF
DELAY JUMPER
FIGURE 1
Integrated Control Diagnostic Codes
DIAGNOSTIC CODES
LED Status
DESCRIPTION
LED Off
No power to control or control harware
fault detected.
LED On
Normal operation.
1 Flash
Flame present with gas vavle
de−energized.
2 Flashes
Pressure switch closed with combustion
air inducer de−energized.
3 Flashes
Pressure switch open with combustion air inducer energized.
4 Flashes
Primary limit switch open.
5 Flashes
Rollout switch open.
6 Flashes
Pressure switch cycle lockout.
7 Flashes
Lockout, burners fail to light.
8 Flashes
Lockout, buners lost flame too many
times.
9 Flashes
Line voltage polarity incorrect.
Note − This control is equipped with a push button switch for
diagnostic code recall. The control stores the last 5 fault
codes in non−volatile memory. The most recent fault code is
flashed first, the oldest fault code is flashed last. There is a
2 second pause between codes. When the push button
switch is pressed for less than 5 seconds, the control will
flash the stored fault codes when the switch is released.
The fault code history may be cleared by pressing the push
button switch for more than 5 seconds.
Page 41
5 − Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again allow the burners to fire for approximately 3 minutes.
6 − Adjust the thermostat to deactivate the heating demand and wait for the combustion air inducer to stop.
At this point, the trap should be primed with sufficient
water to ensure proper condensate drain operation.
Unit Start−Up
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been underwater. A flood−damaged furnace is extremely dangerous. Attempts to use the furnace can result in
fire or explosion. Immediately call a qualified service technician to inspect the furnace and to replace
all gas controls, control system parts, and electrical
parts that have been wet or to replace the furnace,
if deemed necessary.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation (Figure 67)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
3 − Turn off all electrical power to the unit.
4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5 − Remove the upper access panel.
6 − Move gas valve switch to OFF. See figure 67.
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step.
8 − Move gas valve switch to ON. See figure 67.
WARNING
Danger of explosion. Can cause injury
or product or property damage. Should
the gas supply fail to shut off or if
overheating occurs, shut off the gas
valve to the furnace before shutting off
the electrical supply.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
BEFORE LIGHTING the unit, smell all around the furnace area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the
floor.
The gas valve on the ML193UH is equipped with a gas
control switch (lever). Use only your hand to move
switch. Never use tools. If the the switch will not move by
hand, do not try to repair it. Force or attempted repair may
result in a fire or explosion.
Placing the furnace into operation:
ML193UH units are equipped with an automatic hot surface ignition system. Do not attempt to manually light
burners on this furnace. Each time the thermostat calls
for heat, the burners will automatically light. The ignitor
does not get hot when there is no call for heat on these
units.
Priming Condensate Trap
The condensate trap should be primed with water prior to
start−up to ensure proper condensate drainage. Either
pour 10 fl. oz. (300 ml) of water into the trap, or follow
these steps to prime the trap:
1 − Follow the lighting instructions to place the unit into operation.
2 − Set the thermostat to initiate a heating demand.
3 − Allow the burners to fire for approximately 3 minutes.
4 − Adjust the thermostat to deactivate the heating demand.
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
INLET
PRESSURE
PORT
GAS VALVE SHOWN IN ON POSITION
FIGURE 67
9 − Replace the upper access panel.
10− Turn on all electrical power to to the unit.
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call your service technician or gas supplier.
Turning Off Gas to Unit
1 − Set the thermostat to the lowest setting.
2 − Turn off all electrical power to the unit if service is to be
performed.
3 − Remove the upper access panel.
Page 42
4 − Move gas valve switch to OFF.
5 − Replace the upper access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 − Is the thermostat calling for heat?
2 − Are access panels securely in place?
3 − Is the main disconnect switch closed?
4 − Is there a blown fuse or tripped breaker?
5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 − Is gas turned on at the meter?
7 − Is the manual main shut-off valve open?
8 − Is the internal manual shut-off valve open?
9 − Is the unit ignition system in lockout? If the unit locks out
again, inspect the unit for blockages.
Heating Sequence Of Operation
1 − When thermostat calls for heat, combustion air inducer
starts.
2 − Combustion air pressure switch proves blower operation. Switch is factory set and requires no adjustment.
3 − After a 15−second prepurge, the hot surface ignitor energizes.
4 − After a 20−second ignitor warm−up period, the gas
valve solenoid opens. A 4−second Trial for Ignition period begins."
5 − Gas is ignited, flame sensor proves the flame, and the
combustion process continues.
6 − If flame is not detected after first ignition trial, the ignition control will repeat steps 3 and 4 four more times
before locking out the gas valve (WATCHGUARD"
flame failure mode). The ignition control will then automatically repeat steps 1 through 6 after 60 minutes.
To interrupt the 60−minute WATCHGUARD" period,
move thermostat from Heat" to OFF" then back to
Heat". Heating sequence then restarts at step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 11
GAS METER CLOCKING CHART
Seconds for One Revolution
Natural
LP
ML193
Unit
1 cu ft
2 cu ft
1 cu ft
2 cu ft
Dial
Dial
Dial
DIAL
−045
80
160
200
400
−070
55
110
136
272
−090
41
82
102
204
−110
33
66
82
164
−135
27
54
68
136
Natural−1000 btu/cu ft
LP−2500 btu/cu ft
Furnace should operate at least 5 minutes before checking gas flow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures a
more accurate time.) Divide by two and compare to time
in table 11 below. If manifold pressure matches table 12
and rate is incorrect, check gas orifices for proper size and
restriction. Remove temporary gas meter if installed.
NOTE − To obtain accurate reading, shut off all other gas
appliances connected to meter.
Supply Pressure Measurement
When testing supply gas pressure, use the 1/8" N.P.T.
plugged tap or pressure post located on the gas valve to
facilitate test gauge connection. See figure 67. Check gas
line pressure with unit firing at maximum rate. Low pressure may result in erratic operation or underfire. High pressure can result in permanent damage to gas valve or overfire.
On multiple unit installations, each unit should be checked
separately, with and without units operating. Supply pressure must fall within range listed in table 12.
Manifold Pressure Measurement
1 − Remove the threaded plug from the outlet side of the
gas valve and install a field−provided barbed fitting.
Connect to a manometer to measure manifold pressure.
2 − Start unit and allow 5 minutes for unit to reach steady
state.
3 − While waiting for the unit to stabilize, observe the
flame. Flame should be stable and should not lift from
burner. Natural gas should burn blue.
4 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
12.
NOTE − Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to remove
barbed fitting and replace threaded plug.
TABLE 12
Supply Line and Manifold Pressure (inches w.c.)
Unit
Fuel
Manifold
Pressure
Line Pressure
All
Nat. Gas
3.5
4.5 − 10.5
All
L.P. Gas
10.0
11.0 − 13.0
NOTE − A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit
installation instruction for the conversion procedure.
Page 43
Proper Combustion
High Altitude Information
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking combustion. Take combustion sample beyond the flue outlet
and compare to the tables below.
TABLE 13
ML193
CO2% For Nat CO2% For L.P.
Unit
−045
−070
−090
7.2 − 7.9
8.6 − 9.3
−110
−135
The maximum carbon monoxide reading should not exceed 50 ppm.
NOTE − In Canada, certification for installations at elevations over 4500 feet (1372 m) is the jurisdiction of local authorities.
ML193UH units require no manifold pressure adjustments
for operation at altitudes up to 10,000 feet (3048 m) above
sea level. Units installed at altitude of 4501 − 10,000 feet
(1373 to 3048m) require a pressure switch change which
can be ordered separately. Table 14 lists conversion kit and
pressure switch requirements at varying altitudes.
The combustion air pressure switch is factory−set and requires no adjustment.
NOTE − A natural to LP/propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit
installation instruction for the conversion procedure.
TABLE 14
Conversion Kit and Pressure Switch Requirements at Varying Altitudes
ML193
Unit
Natural to
LP/Propane
High Altitude
Natural Burner
Orifice Kit
LP/Propane
to
Natural
High Altitude
LP/Propane
Burner Orifice Kit
0 − 7500 ft
(0 − 2286m)
7501 − 10,000 ft
(2286 − 3038m)
0 − 7500 ft
(0 − 2286m)
7501 − 10,000 ft
(2286 − 3038m)
4501 − 7500 ft
(1373 − 2286m)
7501 −10,000 ft
(2286 − 3048m)
*69W73
73W37
*73W81
*68W68
93W87
93W88
High Altitude Pressure Switch
−045
−070
−090
−110
−135
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory−installed pressure switch from 0−4500 feet (0−1370 m).
Page 44
Testing for Proper Venting and Sufficient Combustion Air for Non−Direct Vent Applications
WARNING
CARBON MONOXIDE POISONING HAZARD!
3−
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being
placed into operation, while all other appliances connected to the venting system are not in operation.
4−
5−
After the ML193UH gas furnace has been started, the following test should be conducted to ensure proper venting
and sufficient combustion air has been provided to the
ML193UH as well as to other gas-fired appliances which
are separately vented.
If a ML193UH furnace replaces a Category I furnace which
was commonly vented with another gas appliance, the size
of the existing vent pipe for that gas appliance must be
checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the
single water heater or other appliance. The vent should be
checked for proper draw with the remaining appliance.
The test should be conducted while all appliances (both in
operation and those not in operation) are connected to the
venting system being tested. If the venting system has
been installed improperly, or if provisions have not been
made for sufficient amounts of combustion air, corrections
must be made as outlined in the previous section.
1 − Seal any unused openings in the venting system.
2 − Visually inspect the venting system for proper size and
Page 45
6−
7−
8−
9−
horizontal pitch. Determine there is no blockage or restriction, leakage, corrosion, or other deficiencies
which could cause an unsafe condition.
To the extent that it is practical, close all building doors
and windows and all doors between the space in which
the appliances connected to the venting system are located and other spaces of the building.
Close fireplace dampers.
Turn on clothes dryers and any appliances not connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan.
Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so
appliance will operate continuously.
Use the flame of match or candle to test for spillage of
flue gases at the draft hood relief opening after 5 minutes of main burner operation.
If improper venting is observed during any of the
above tests, the venting system must be corrected or
sufficient combustion/make-up air must be provided.
The venting system should be re-sized to approach
the minimum size as determined by using the appropriate tables in appendix G in the current standards
of the National Fuel Gas Code ANSI−Z223.1/NPFA 54
in the U.S.A., and the appropriate Natural Gas and
Propane appliances venting sizing tables in the current standard of the CSA−B149 Natural Gas and Propane Installation Codes in Canada.
After determining that each appliance remaining
connected to the common venting system properly
vents when tested as indicated in step 3, return
doors, windows, exhaust fans, fireplace dampers
and any other gas-burning appliance to their previous
condition of use.
Other Unit Adjustments
HEAT FAN-OFF TIME IN SECONDS
Primary Limit.
The primary limit is located on the heating compartment
vestibule panel. This limit is factory set and requires no adjustment.
NO JUMPER
Flame Rollout Switches (Two)
Fan Control
The fan on time of 30 seconds is not adjustable. The fan off
delay (amount of time that the blower operates after the
heat demand has been satisfied) may be adjusted by
changing the jumper position across the five pins on the
integrated control. The unit is shipped with a factory fan off
setting of 120 seconds. The fan off delay affects comfort
and is adjustable to satisfy individual applications. Adjust
the fan off delay to achieve a supply air temperature between 90° and 110°F at the moment that the blower is
de−energized. Longer off delay settings provide lower return air temperatures; shorter settings provide higher return air temperatures. See figure 68.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC + 10%
3 − Check amp−draw on the blower motor with blower access panel in place.
Motor Nameplate__________Actual__________
Blower Speeds
Follow the steps below to change the blower speeds.
1 − Turn off electrical power to furnace.
2 − Remove blower access panel.
3 − Disconnect existing speed tap at integrated control
speed terminal.
To adjust fan−off timing, reposition jumper across pins to
achieve desired setting.
180 Second
off Time
60
90
120
180
120 Second
off Time
60
90
120
180
90 Second
off Time
60
90
120
180
60 Second
off Time
60
90
120
180
These manually reset switches are located on the front of
the burner box.
Pressure Switch
The pressure switch is located in the heating compartment
on the cold end header box. This switch checks for proper
combustion air inducer operation before allowing ignition
trial. The switch is factory−set and must not be adjusted.
Temperature Rise
After the furnace has been started and supply and return air
temperatures have been allowed to stabilize, check the
temperature rise. If necessary, adjust the blower speed to
maintain the temperature rise within the range shown on
the unit nameplate. Increase the blower speed to decrease
the temperature. Decrease the blower speed to increase
the temperature rise. Failure to adjust the temperature rise
may cause erratic limit operation.
FIGURE 68
NOTE − Termination of any unused motor leads must be
insulated.
4 − Place unused blower speed tap on integrated control
PARK" terminal or insulate.
5 − Refer to blower speed selection chart on unit wiring diagram for desired heating or cooling speed. See Product
Specifications bulletin for blower performance tables.
6 − Connect selected speed tap at integrated control
speed terminal.
7 − Resecure blower access panel.
8 − Turn on electrical power to furnace.
9 − Recheck temperature rise.
Electronic Ignition
The integrated control has an added feature of an internal
Watchguard control. The feature serves as an automatic reset device for integrated control lockout caused by ignition
failure. This type of lockout is usually due to low gas line
pressure. After one hour of continuous thermostat demand
for heat, the Watchguard will break and remake thermostat
demand to the furnace and automatically reset the integrated control to begin the ignition sequence.
Exhaust and Air Intake Pipe
1 − Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
2 − Is pressure switch closed? Obstructed exhaust pipe
will cause unit to shut off at pressure switch. Check termination for blockages.
3 − Obstructed pipe or termination may cause rollout
switches to open. Reset manual flame rollout switches
on burner box assembly if necessary.
Page 46
Twinning the ML193UH
The control board in this furnace is equipped with a provision to "twin" (interconnect) two(2) adjacent furnaces with a
common plenum such that they operate as one (1) large
unit.
When twinned, the circulating blower speeds are synchronized between the furnaces. If either furnace has a need to
run the blower, both furnaces will run the blower on the
same speed. The cooling speed has highest priority, followed by heating speed and fan speed.
Field installation of twinning consists of connecting wires
between the "C" and "Twin" terminals of the two controls.
The 24 VAC secondary of the two systems must be in
phase. All thermostat connections are made to one control
only. Figure 2 show wiring for two−stage and single stage
thermostats.
The twinned furnace without thermostat connections is to
have the call for heat supplied by an external 24VAC isolation relay to prevent its rollout switch from being bypassed
by the other twinned furnace. The coil of the isolation relay
connects from the thermostat "W" to 24 VAC common. The
contacts of the relay connect "R" to "W" on the non−thermostat twin.
FIELD WIRING FOR TWINNING
TWO−STAGE THERMOSTAT
TWIN
R
Call For Cool
Call For Fan
Call For 1st
Stage Heat
Call For 2nd
StageHeat
SINGLE STAGE THERMOSTAT
R
R
Y
Y
Y
TWIN 1
G
W1
Call For Heat
W
W2
Y
G
TWIN 1
G
W
W
C
C
TWIN
TWIN
ISOLATION
RELAY
R
Call For Cool
Call For Fan
G
TWIN
ISOLATION
RELAY
R
Y
TWIN 2
R
Y
G
G
W
W
C
C
FIGURE 2
Page 47
TWIN 2
Electrical
Service
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating).
WARNING
3 − Check amp−draw on the blower motor.
Motor Nameplate__________Actual__________
Winterizing and Condensate Trap Care
1 − Turn off power to the furnace.
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result
in dangerous operation, serious injury, death or
property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
2 − Have a shallow pan ready to empty condensate water.
3 − Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the
clean out cap.
At the beginning of each heating season, system should be
checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal injury or death.
Filters
All air filters are installed external to the unit. Filters should
be inspected monthly. Clean or replace the filters when
necessary to ensure proper furnace operation. Table 1
lists recommended filter sizes.
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections
for tightness and to make sure there is no blockage.
NOTE − After any heavy snow, ice or frozen fog event the
furnace vent pipes may become restricted. Always check
the vent system and remove any snow or ice that may be
obstructing the plastic intake or exhaust pipes.
Cleaning the Burner Assembly
1 − Turn off gas and electrical power to the furnace. Remove heating compartment access panel.
2 − Disconnect the gas supply line from the gas valve.
3 − Disconnect and label wires from gas valve.
4 − Disconnect ignitor wiring at 2 circuit plug.
5 − Disconnect and label wires from rollout switch.
6 − Disconnect and label flame sensor wire.
7 − Disconnect and label ground wire from burner/manifold assembly.
8 − Remove four screws that secures burner/manifold assembly to vestibule. Remove the assembly and make
note not to allow ignitor plate to dislodge from the assembly.
9 − Gently clean the face of the burners using the soft
brush attachment on a vacuum cleaner. Visually inspect the inside of the burners and crossovers for any
blockage caused by foreign matter. Remove any
blockage
10 − Reinstall the burner/manifold assembly using the existing four screws. Burners are self aligning to center of clam shells.
11 − Reconnect ground wire.
12 − Reconnect flame sensor wire.
13 − Reconnect rollout switch wires.
14 − Reconnect ignitor wires.
15 − Reconnect gas valve wires.
16 − Reconnect gas supply line to gas valve.
17 − Refer to instructions on verifying gas and electrical
connections when re−establishing supplies.
18 − Follow instructions to place furnace in operation. Run
furnace 5 minutes to ensure burners are clean and operating correctly.
19 − Replace heating compartment access panel.
Page 48
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model
number listed on the CSA nameplate −− Example: ML193UH045XP36B−01. All service must be performed by a licensed
professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Upper access panel
Blower access panel
Top Cap
Control Panel Parts
Transformer
Integrated control board
Door interlock switch
Blower Parts
Blower wheel
Motor
Motor mounting frame
Motor capacitor
Blower housing cutoff plate
Heating Parts
Flame Sensor
Heat exchanger assembly
Gas manifold
Combustion air inducer
Gas valve
Main burner cluster
Main burner orifices
Pressure switch
Ignitor
Primary limit control
Flame rollout switches
Page 49
Start−Up & Performance Check List
UNIT SET UP
Furnace:
Model Number_______________
Serial Number_________________
Line Voltage
SUPPLY
AIR
2
4
1
GAS SUPPLY
Natural Gas
LP Propane Gas
3
Piping Connections Tight
2
Leak Tested
Flter
Supply Line Pressure W.C.________
RETURN AIR
1
Gas Supply Pressure
3
1
DUCT SYSTEM
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
2
RETURN DUCT
INTAKE / EXHAUST PIPE
Sealed
All Joints Primed and Glued
Filter Installed and Clean
Terminations Installed Properly
Grilles Unobstructed
Horizontal Pipes Sloped (if applicable)
4
Condensate Trap Primed / Line Sloped
VOLTAGE CHECK
Supply Voltage _____
Electrical Connections Tight
Pipes Supported
Heat Cable Installed and Operable (if applicable)
Page 50
UNIT OPERATION
HEATING MODE
1
2
COOLING MODE
GAS MANIFOLD PRESSURE W.C._____
COMBUSTION SAMPLE CO2%______CO PPM_______
3
INDOOR BLOWER AMPS______
4
TEMPERATURE RISE
3
INDOOR BLOWER AMPS______
4
TEMPERATURE DROP
Return Duct Temperature _________
Supply Duct Temperature _ _______
Temperature Drop = _________
5
Supply Duct Temperature ________
Return Duct Temperature _ _____
Temperature Rise = ________
5
6
TOTAL EXTERNAL STATIC
Supply External Static _______
Return External Static + ______
Total External Static = _______
8
DRAIN LINE
Leak Free
9
CONDENSATE LINE
THERMOSTAT
Adjusted and Programmed
Leak Free
7
TOTAL EXTERNAL STATIC (dry coil)
Supply External Static _______
Return External Static + ______
Total External Static = _______
Explained Operation to Owner
VENT PIPE
Leak Free
Combustion CO2
2
7
SUPPLY
AIR
Thermostat
Temperatures
8
Gas Manifold Pressure
9
4
1
Blower Motor Amps
3
6
Duct Static
5
RETURN AIR
Contractor’s: Name_________________________Telephone_____________Checklist Completed____________________
Job Address_____−________________________________Technician’s Name___________________________________
Page 51
Requirements for Commonwealth of Massachusetts
Modifications to NFPA−54, Chapter 10
Revise NFPA−54 section 10.8.3 to add the following requirements:
For all side wall, horizontally vented, gas−fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above the finished grade in the area of the venting, including but not limited to decks and porches, the following
requirements shall be satisfied:
1 − INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall, horizontally vented, gas−fueled equipment, the installing
plumber or gasfitter shall observe that a hard−wired
carbon monoxide detector with an alarm and battery
backup is installed on the floor level where the gas
equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery−operated or hard−wired carbon monoxide detector with an
alarm is installed on each additional level of the dwelling, building or structure served by the side wall, horizontally vented, gas−fueled equipment. It shall be the
responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard−wired carbon monoxide detectors.
a − In the event that the side wall, horizontally vented,
gas−fueled equipment is installed in a crawl space
or an attic, the hard−wired carbon monoxide detector with alarm and battery back−up may be installed
on the next adjacent floor level.
b − In the event that the requirements of this subdivision cannot be met at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30) day
period, a battery−operated carbon monoxide detector with an alarm shall be installed.
2 − APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accordance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3 − SIGNAGE. A metal or plastic identification plate shall
be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented, gas−fueled heating appliance or
equipment. The sign shall read, in print size no less
than one−half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS."
4 − INSPECTION. The state or local gas inspector of the
side wall, horizontally vented, gas−fueled equipment
shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt
from 24 CMR 5.08(2)(a) 1 through 4:
1 − The equipment listed in Chapter 10 entitled Equipment Not Required to Be Vented" in the most current
edition of NFPA 54 as adopted by the Board; and
2 − Product Approved side wall, horizontally vented, gas−
fueled equipment installed in a room or structure separate from the dwelling, building or structure used in
whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS −
GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas−fueled equipment provides a venting system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
1 − Detailed instructions for the installation of the venting
system design or the venting system components:
and
2 − A complete parts list for the venting system design or
venting system.
MANUFACTURER REQUIREMENTS −
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas−fueled equipment does not provide the parts for venting the flue gases, but identifies special venting systems," the following requirements shall be
satisfied by the manufacturer:
1 − The referenced special venting system" instructions
shall be included with the appliance or equipment
installation instructions; and
2
The special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas−fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at
the completion of the installation.
Page 52

advertisement

Related manuals

Download PDF

advertisement