Mhouse WG10S K & WG20S Swing Gate Openers User manual
Add to My manuals36 Pages
Mhouse WG10S K & WG20S are designed for automating residential swing gates. These kits include a control unit, gearmotors, release keys, photocells (optional), radio transmitters (optional), a flashing light, and metal hardware. Each gearmotor features a 24V DC motor, a worm reducer, and a manual locking system. The control unit integrates a radio receiver to accept commands from transmitters and can store up to 256 transmitters and 6 pairs of photocells.
advertisement
MhouseKit WG20 S
For power-operated swing gate
Installation instructions and warnings, and User Manual
IS0010A00EN_28-03-2011
CONTENTS
GENERAL SAFETY WARNINGS AND PRECAUTIONS
STEP 1
KNOWLEDGE OF THE PRODUCT AND PREPARATION FOR
INSTALLATION
STEP 2
2.1 - PRODUCT DESCRIPTION AND INTENDED USE
2.2 - COMPONENTS USED TO SET UP A COMPLETE SYSTEM
2
2
3
PRELIMINARY CHECKS FOR INSTALLATION
STEP 3
3.1 - CHECKING SUITABILITY OF GATE TO BE AUTOMATED AND
RELATIVE ENVIRONMENT
3.2 - PRODUCT APPLICATION LIMITS
3.3 - PRODUCT DURABILITY
PRODUCT DISPOSAL
3
FURTHER INFORMATION
STEP 10
10.1 - ADVANCED SETTINGS
10.2 - OPTIONAL ACCESSORIES
10.3 - ADDING OR REMOVING DEVICES
10.4 - MEMORIZING ALL RADIO TRANSMITTERS
10.5 - TROUBLESHOOTING
10.6 - DIAGNOSTICS AND SIGNALS
3
3
3
TECHNICAL SPECIFICATIONS OF PRODUCT
COMPONENTS
STEP 4
4.1 - PRELIMINARY CHECKS FOR INSTALLATION
4.2 - PREPARING ELECTRIC CABLES
4
4
4
APPENDIX 1 - EC declaration of conformity
INSTALLATION: ASSEMBLY AND CONNECTION
OF COMPONENTS
STEP 5
5.1 - INSTALLING THE GEARMOTOR WG10SK
STEP 6
6.1 - INSTALLING CL20S
6.2 - INSTALLING AND CONNECTING PHOTOCELLS PH100
6.3 - INSTALLING AND CONNECTING THE FLASHING LIGHT FL100
6.4 - ELECTRICAL CONNECTION TO CONTROL UNIT CL20S
6
6
7
7
6
6
7
USER’S GUIDE
STEP 11
11.1 - SAFETY INSTRUCTIONS
11.2 - GATE CONTROL
11.3 - MANUALLY RELEASING OR LOCKING THE GEARMOTOR
11.4 - MAINTENANCE OPERATIONS ADMISSIBLE TO THE USER
11.5 - REMOTE CONTROL BATTERY REPLACEMENT
11.6 - REMOTE CONTROL BATTERY REPLACEMENT
APPENDIX 2 - EC declaration of conformity
PROGRAMMING
STEP 7
7.1 - POWER SUPPLY CONNECTION
7.2 - INITIAL CHECKS
7.3 - LEARNING CONNECTED DEVICES
7.4 - LEARNING THE GATE LEAF OPENING AND CLOSING ANGLES
7.5 - CHECKING THE RADIO TRANSMITTERS
7.6 - SETTING
13
13
13
13
13
13
13
2
MAINTENANCE
STEP 9
TESTING AND COMMISSIONING
STEP 8
8.1 - TESTING
8.2 - COMMISSIONING
15
15
15
25
28
20
22
22
16
16
17
19
15
15
29
30
30
30
29
29
29
31
English – 1
GENERAL SAFETY WARNINGS AND PRECAUTIONS
––– STEP 1 –––
Safety warnings
• CAUTION! – This manual contains important instructions and
warnings for personal safety. Incorrect installation could cause serious physical injury. Carefully read all parts of this manual before starting any work. If in doubt, suspend installation immediately and contact the
Mhouse Technical Assistance.
• CAUTION! – Important instructions: keep this manual in a safe place to enable future product maintenance and disposal procedures.
• CAUTION! – According to the most recent European legislation, the production of a power-operated door or gate must comply with the standards envisaged in the Directive 2006/42/EC (Machinery
Directive) and in particular standards EN 12445; EN 12453; EN
12635 and EN 13241-1, which enable declaration of presumed conformity of the automation. In consideration of this, all mains connection, testing, commissioning and maintenance operations must be performed exclusively by a qualified and skilled technician.
All preliminary set-up, installation and programming operations may be performed by personnel with standard skills, provided that all instructions and the relative sequences in this manual are strictly observed, with particular reference to the warnings in this STEP
1.
Installation warnings
While reading this manual, take care to observe all instructions marked with the following symbol:
These symbols indicate subjects that may be the source of potential hazards and therefore the prescribed operations must be performed exclusively by qualified and skilled personnel, in observance of these instructions current safety standards.
• Before installation, ensure that this product is suitable for automation of your gate or door (see STEP 3 and chapter “Product Technical Specifications”). If not suitable, do NOT proceed with installation.
• On the system power mains install a device for disconnection (not supplied), to guarantee a gap between contacts and complete disconnection in the conditions of overvoltage category III.
• All installation and maintenance operations must be performed
with the automation disconnected from the power supply. If the power disconnect device is not visible from the location of the automation, before work a notice should be affixed on the disconnect device, with the text “CAUTION! MAINTENANCE IN PROGRESS”.
• CAUTION! - Never power up the motor before fully installed
on the column and leaf of the gate.
• During installation, handle the automation with care, avoiding the risk of impact, dropping or contact with any type of liquid. Never place the product near to sources of heat and never expose to naked flames. This may damage product components and cause malfunctions, fire or hazardous situations. If this occurs, suspend installation immediately and contact the MhouseTechnical Assistance.
• Never make modifications to any part of the product. Operations other than as specified can only cause malfunctions. The manufacturer declines all liability for damage caused by makeshift modifications to the product.
• If the power cable is damaged, it must be replaced exclusively by a qualified technician, to avoid potential risks.
• Connect the control unit to an electric power line equipped with an earthing system.
• This product is not designed to be used by persons (including children) whose physical, sensorial or mental capacities are reduced, or with lack of experience or skill, unless suitable instructions regarding use of the product have been provided by a person responsible for safety.
• The key-operated selector switch must be positioned in sight of the automation, but far from moving parts and at a height of at least 1.5 m from the ground, not accessible by the public. If this is used in “hold-torun” mode, ensure that there are no persons in the vicinity of the automation.
• In the vicinity of the automation children must be supervised to ensure that they do not play with it.
• Ensure that there are not points of entrapment or crushing with fixed parts when the gate leaf is in the maximum opening or closing position; protect parts if necessary.
• The product may not be considered an efficient system of protection against intrusion. If an efficient protection system is required, the automation must be integrated with other safety devices.
• The automation must not be used before performing the commissioning procedure as specified in the chapter “Testing and commissioning”.
• Check the automation frequently to ensure there is no imbalance, signs of wear or damage to electrical or mechanical parts. Do not use the automation if adjustments or repairs are necessary.
• In the event of long periods of disuse, to avoid the risk of leaks of harmful substances from the optional battery (PR1) disconnect it from the automation and store in a dry location.
• Do not allow children to play with fixed control devices. Keep remote control devices out of reach of children.
• The product’s packaging materials must be disposed of in full compliance with local regulations.
Operation warnings
• For cleaning the product surfaces, use a soft damp cloth. Use water only; never use detergents or solvents for cleaning.
KNOWLEDGE OF THE PRODUCT AND PREPARATION FOR INSTALLATION
NOTES TO MANUAL
• This manual describes how to set up a complete and optimal automation, such as that shown in fig. 6, using all Mhouse devices that are part of the automation system named “WG20S”. Some of these devices are optional and may not be present in the kit. For a complete overview of the devices, refer to the MHouse product catalogue.
• This manual has been drawn up as a step-by-step guide. Therefore, to ensure safe and facilitated assembly and programming procedures, perform all operations described in the same order as specified in this document.
––– STEP 2 –––
2.1 - PRODUCT DESCRIPTION AND INTENDED USE
The devices in this kit, plus other accessories (some optional and not included in the pack), form the automation system named “WG20S”, designed for the automation of a “residential” swing gate. Any other use
than as specified herein or in environmental conditions other than as stated in this manual is to be considered improper and is strictly prohibited!
The main part of the automation comprises one control unit and two electromechanical gearmotors, each equipped with a 24 V DC motor, a worm reducer and a mechanical locking system with key to enable manual opening and closing of the gate in the event of a power failure.
The control unit comprises a board and incorporated radio receiver which receives the commands sent by the user via a transmitter. It can memorise up to 256 GTX4 transmitters (if memorised in “Mode I”) and up to 6 pairs of PH100 photocells.
2 – English
Connection of the control unit with the various devices is by means of a single 2-wire cable (“ECSbus” system). The control unit can also be mains-powered (230 V) or alternatively by the Mhouse PF photovoltaic system.
If powered from the mains, it can house a buffer battery (model PR1, optional accessory), which ensures that the automation can perform a number of manoeuvres for several hours in the event of a power failure.
During the power failure, or at any other time, the gate leaf can be moved manually if required, by first releasing the gearmotor using the relative key
(see chapter 11.3 - User’s Guide).
2.2 - COMPONENTS USED TO SET UP A COMPLETE
SYSTEM
Fig. 1 illustrates all components used to set up a complete system, such as that shown in fig. 6.
Components shown in Fig. 1:
A - 2 electromechanical gearmotors WG10SK with fixing brackets
B - 3 release keys
C - 1 pair of PH100 photocells (one TX and one RX)
D - 2 GTX4 radio transmitters
E - 1 FL100 flashing light with integrated aerial
F - 1 control unit CL20S
G Metal hardware
Notes:
- Some devices and accessories specified in the manual are optional and may not be present in the kit. .For a complete description, refer to the
Mhouse product catalogue or visit the website
- The limit switch stops are not supplied in the pack and are not part of the
Mhouse product range.
––– STEP 3 –––
The shape of the gate and weather conditions (such as the presence of strong winds) may reduce these maximum values; in this case the user must measure the torque required to move the leafs in the worst conditions, and compare this value with the technical specifications.
2 - Check the overall dimensions of the gearmotor (fig. 2). Note – These
measurements also serve as a reference to calculate the space occupied by the foundation pit for routing the electrical cable ducting.
3 - Ensure that the estimated lifetime is compatible with the intended use
(see paragraph 3.3).
4 - Ensure that all limitations, conditions and warnings in this manual can be fully observed.
3.3 - PRODUCT DURABILITY
The lifetime is the average economic duration of the product. The value of lifetime is strongly influenced by the intensity of the manoeuvres, i.e. the sum of all factors that contribute to product wear, see Table 1. To estimate the durability of your automation, proceed as follows:
01. Add up all the values in the items of Table 1;
02. In Graph 1 from the value obtained above, trace vertical line until it intersects the curve; from this point trace a horizontal line until it intersects the line of the “manoeuvre cycles”. The value obtained is the estimated lifetime of your product.
The lifetime values specified in the graph are only obtainable if the maintenance schedule is strictly observed (see chapter 9 - Maintenance schedule). The estimation of lifetime is made on the basis of design calculations and the results of tests performed on prototypes. As it is only an estimation, it does not represent any form of guarantee on the effective lifetime of the product.
TABLE 1
Severity index
Leaf length
1 - 1,5 m
1,5 - 2 m
2 - 3 m
3 - 4 m
4 - 4,5 m
0%
0%
10%
20%
25%
3.1 - CHECKING SUITABILITY OF GATE TO BE
AUTOMATED AND RELATIVE ENVIRONMENT
• Ensure that the mechanical structure of the gate complies with current national standards and that it is suitable for automation. For this check, refer to the information specified on the gate dataplate. Important -
This product cannot be used to automate a gate that is not already efficient and safe; furthermore it cannot solve defects caused by incorrect gate installation or poor maintenance.
• Manually move the gate leafs in both directions (opening/closing) and ensure that friction is constant throughout travel (there must be no points of increased or decreased force).
• If the leaf is fitted in a pedestrian pass door or a door onto the leaf movement area, ensure that this door does not obstruct normal travel, and install a suitable interlock device if necessary.
• Manually move the gate to any position; leave it stationary and ensure that it does not move when left.
• Ensure that the space around the site of gearmotor installation enables safe and easy manual gate release.
• Ensure that the selected surfaces for installation of the various devices are solid and guarantee a stable fixture; as regards photocells, select a flat surface that guarantees correct alignment between photocells (Tx and Rx).
• Ensure that all devices to be installed are in a sheltered location and protected against the risk of accidental impact.
• Verify the overall limits with reference to fig. 2.
• Ensure that there is sufficient space also when the gate is open (fig. 3).
• On the basis of the leaf opening angle, check to ensure observance of the positions in fig. 4 and fig. 5 - Graph 2.
• The bracket can be fitted in various ways (fig. 10): position “C” can vary from 53 mm to 176 mm. It is normally approx. 150 mm.
• Position “D” is easily measured on the gate.
• Position “A” is the sum of “C” and “D”.
• On the basis of value “A”, and the leaf opening angle in the table, value
“B” can be calculated. For example: if “A” is 150 mm and the leaf opening angle is 100°, the value of “B” is approx. 150 mm.
It is recommended to select similar values for “A” and “B”. This guaran tees regular movement of the leaf and minimal stress on the gearmotor.
3.2 - PRODUCT APPLICATION LIMIT
Before proceeding with installation, perform the following checks in the specified sequence and ensure conformity both with the data in this paragraph and the technical data provided in the chapter “Technical Specifications”.
1 - Ensure that the dimensions and weight of the gate leafs are within the following limits of use:
WG20S - maximum length 4.5 m
- maximum weight 500 kg.
- opening up to 130°
Leaf weight
> 100 kg
> 200 kg
> 300 kg
Ambient temperature over 40°C or lower than 0°C or humidity greater than 80%
Solid leaf
Installation in windy zone
125.000
100.000
75.000
50.000
25.000
GRAPH 1
Severity index (%)
0%
10%
25%
20%
15%
15%
Example of durability calculation: \ automation of a gate with a leaf length of 1.5 m with weight of 220 kg, for example, in a location subject to strong winds. Table 1 states the “severity index” values for this type of installation: 10% (“Leaf length”), 25% (“Leaf weight”) e 15% (“Installation in windy areas”).
These values must be added up to obtain the overall severity index, which in this case is 50%.
With the value obtained (50%), check the horizontal axis of Graph 2
(“severity index”), for the corresponding value of “manoeuvre cycles” which our product can complete in its lifetime = approx. 55,000 cycles.
English – 3
––– STEP 4 –––
4.1 - PRELIMINARY CHECKS FOR INSTALLATION
4.1.1 - Establish the position of devices in the system
With reference to fig. 6 and 7, locate the approximate position for installation of each device envisaged in the system. Fig. 6 shows a system made using this product and other optional accessories in the Mhouse range.
These elements are positioned according to a typical standard layout. The components are:
[a] - 1 CL20S control unit.
[b] - 1 FL100 flashing light with integrated aerial
[c] - 1 pair of PH100 photocells (one TX and one RX)
[d] - 1 KS100 key-operated selector switch
[e] - 2 photocell posts
[f] - 2 limit switch stops
[g] - 2 electromechanical gearmotors WG10SK
WARNING! - Some of these devices are optional and may not be present in the kit (see Mhouse product catalogue).
WARNINGS:
The fixed control devices must be positioned:
- in sight of the automation;
- far from moving parts;
- at a height of at least 1.5 m from the ground,
- not accessible by the public.
4.1.2 - Establish the position of all connection cables
Refer to the instructions in paragraph 4.2 to establish the layout of the raceways for electric cable ducting.
4.1.3 - Ensure all equipment and materials for work are available
Before starting work, ensure that you have all equipment and materials required to complete the work. Ensure that all items are in good condition and comply with local safety standards.
4.1.4 - Completing the set-up work
Prepare the area for subsequent installation of the devices, completing all preliminary work, such as:
- digging of raceways for protection ducting of electric cables (external ducting may be used as an alternative);
- laying of protection ducting and embedding in concrete;
- sizing of all electric cables to required length (see paragraph 4.2) and routing in protection ducting. Caution! - In this phase, do not make
any electrical connections.
Warnings:
• The hoses and ducting serve to protect electrical cables and prevent accidental damage in the event of impact.
• When laying pipelines, take into account the risk of possible deposits of water in the branch wells, where condensate may form in the pipelines and the control unit with possible damage to the electronic circuits.
• Position the ends of the ducting at the points envisaged for fixture of the various components.
4.2 - PREPARING ELECTRIC CABLES
To prepare all connection cables, proceed as follows:
a) - Refer to fig. 7 to check the connections of the various devices to the control unit and terminals to be used for each connection. Important
- Only devices using “ECSbus” technology can be connected to the terminal “ECSbus”.
b) - Refer to fig. 6 to check positions of the electrical cables in the area.
Then draw a similar diagram on paper, adapting it to specific requirements of your system. Note - This diagram will be useful to establish
the route of the raceways for cable ducting, and to draw up a complete list of the cables required.
c) - Read Table 2 to determine the type of cables to be used; then refer to the diagram drawn above and on-site measurements to determine the length of each cable. Caution! - No cable must exceed the
specific maximum length stated in Table 2.
WARNING - “ECSbus” technology enables the interconnection of devices using a single “bus” cable, with 2 internal electrical wires. Connection of several devices can be in the configuration “cascade”, “star” or the latter two “combined”:
cascade star combined
TABLE 2 – Technical specifications of electric cables
Connection
A - Power line
B - FLASH flashing light output
C - Radio aerial
D - input/output ECSbus
E - STOP input
F - OPEN input
G - Motor output M1 and M2
Type of cable (minimum section values)
Max. admissible length
cable 3 x 1.5 mm cable 2 x 0.5 mm cable 2 x 0.5 mm cable 2 x 0.5 mm cable 3 x 1 mm 2
2
2
RG58 shielded cable type cable 2 x 0.5 mm 2
2
2
30 m (note 1)
20 m
20 m (less than 5 m recommended)
20 m (note 2)
20 m (note 2)
20 m (note 2)
10 m
Note 1 - If the power cable is longer than 30 m, a cable with a larger section is required (e.g. 3x2.5 mm 2 ) and safety earthing is necessary in the vicinity of the automation.
Note 2 - For cables of ECSbus and those of the STOP and OPEN inputs, a single cable with multiple internal wires may be used, to combine several connections: for example, the STOP and OPEN inputs can be connected to the KS100 selector switch with a cable of 4 x 0.5 mm 2 .
CAUTION! – The cables used must be suited to the installation environment.; for example a cable type H03VV-F is recommended for indoor environments, and a cable type H07RN-F for outdoor environments is recommended.
4 – English
2
4
1
A
E
B
F
C
3
G
D
5
GRAPH 2
maximum leaf length (m)
English – 5
6 a b c c d
7 e
A f g
B C D h
D g f
E F e
D G G
INSTALLATION: ASSEMBLY AND CONNECTION OF COMPONENTS
––– STEP 5 –––
IMPORTANT!
- The following assembly phases show installation of a gearmotor model WG10SK.
- To ensure correct system operation, mechanical stops must be mounted on the floor or wall at the maximum leaf opening and closing points. Note - These stops are not supplied in the pack and are not part of the Mhouse product range.
WARNINGS
• Incorrect installation may cause serious physical injury to those working on or using the system.
• Before starting automation assembly, make the preliminary checks
as described in STEP 3.
5.1 - INSTALLING THE GEARMOTOR WG10SK
To secure the gearmotor, proceed as follows:
01. Select the fixing position, observing the specifications in paragraph
3.1 “Preliminary checks”;
02. Ensure that the fixing surface is perfectly smooth, level and sufficiently compact. WG10SK is not supplied with fixing devices, which must be chosen also on the basis of the fixing surface material.
03. Lay the duct for routing the electric cable (fig. 8);
04. To construct the rear supports, assemble the two brackets and rear plate as shown in fig. 9;
05. the brackets and rear plate can be assembled in different ways: to obtain the various values of “C” see fig. 10;
06. To construct the front support, assemble the bracket and front plate as shown in fig. 11;
07. Remove the rear cover of the gearmotors pulling it out in the direction of the arrows (fig. 12);
08. Move the leafs to the closed position;
09. With reference to the previously calculated position “B” (fig. 4 and 5), place the rear support on the fixing surface, in the envisaged position;
Caution! - check the positions in fig. 15.
10. Trace the drilling points of the rear support using the support as a reference Using a drill make four holes on the surface for insertion of 4 plugs of at least 8 mm (not supplied). Fix the plate with suitable screws and washers (fig. 13);
11. Ensure that the plate is perfectly level (the slots on the bracket enable small corrections to alignment, as shown in fig. 14);
12. Place the front support as shown in fig. 15;
13. Provisionally secure the front support to the leaf with a clamp (fig.
16);
14. Lift the gearmotor and insert the fork in the hole of the front support;
15. Keeping the gearmotor raised, pull to open the leaf and align the hole on the rear plate with the hole on the gearmotor. Fix the gearmotor to the rear support [A] using screw [B], nut [C] and washer [D] (fig. 17);
16. Tighten the nut fully down then loosen by approx. half a turn to enable rotation of the gearmotor on its support;
17. Secure the gearmotor to the front support, tightening the screw [E] and washer [F], then tighten the screw fully down (fig. 18);
18. Unlock the gearmotor again using the release keys (see paragraph
11.3 - User’s Guide);
6 – English
19. Test a number of manoeuvres moving the gate by hand. Check that the fork slides smoothly on the worm gear of the gearmotor and that there are margins of at least 5 mm on the opening and closing limits, while avoiding a situation in which an excessive section of the worm gear is not used;
20. If necessary, adjust the limit switch of the gearmotor, loosening it by means of the hex wrench [G] and moving it to the required position
(fig. 19). The mechanical opening limiter [H] is only used if there are
no limit stops present. After adjusting the limiters tighten the screws fully down:
21. Fix the front support permanently using screws suited to the leaf material;
22. Unlock the gearmotor again using the release keys (see paragraph
11.3 - User’s Guide).
Make electrical connections. Refer to figure 24 and step 6.
––– STEP 6 –––
6.1 - INSTALLING CL20S CONTROL UNIT
01. Select the installation position in an area protected against potential impact and in the vicinity of the gate, to reduce the overall length of the cables;
02. Remove the cover, levering it off with a screwdriver from the opening on the base; slide it by a few centimetres then lift it off the base (fig.
20);
03. Lay the duct for routing the electric cables so that they can be inserted from the lower section of the control unit;
04. Drill the lower side of the control unit and use special connectors for securing the ducts for routing electric cables, as shown in fig. 21;
05. On the base, use a screwdriver to punch through the two holes; trace the drilling points using the base as a reference (fig. 22);
06. Use a percussion drill to drill the wall, with a 6 mm tip, and insert 6 mm plugs;
07. Fix the base, using the relative screws [A];
08. Before closing the control unit (fig. 23), make the electrical connection with reference to paragraph 6.6 and fig. 24.
09. To close the control unit, place the cover on the base by approx. 3 cm higher than the final position and push it downwards to engage it completely, as shown in fig. 23.
6.2 - INSTALLING AND CONNECTING PHOTOCELLS PH100
(fig. 29)
Warning: all installation operations must be performed with the system disconnected from the power supply; if fitted, the PR1 backup battery must also be disconnected.
Warnings: Take care not to damage the o-ring fitted (fig. 29-3) [A].
Select the position of the two elements making up the photocell (TX and
RX) observing the following:
• Place them at a height of 40-60 cm from the ground, to the sides of the zone to be protected, and as close as possible to the edge of the gate, i.e. no further than 15 cm.
• There must be a raceway tube at the point envisaged for routing cables.
• Point the transmitter TX at receiver RX with a maximum tolerance of 5°.
01. Remove the front glass panel (fig. 29-1).
02. Position the photocell at the point where the cable routing tube arrives.
03. Trace the drilling points using the base as a reference. Use a percussion drill to drill the wall, with a 5 mm tip, and insert 5 mm plugs.
04. Route the electric cables through the specific holes (pierce those required): see the two options in fig. 29-2.
05. Fix the base, using the relative screws [B] of fig. 29-3 ensuring that the hole on the base [C] of fig. 29-3 is aligned with the cable outlet.
2 self-tapping screws are also supplied for fixture on surfaces with a different density.
06. Connect the electrical cable in the relative terminals of both TX and
RX (fig. In electrical terms, TX and RX must be connected in parallel
(fig. 29-5) and to the blue terminal of the control board. There is no need to observe polarity.
07. Fix the covering shell [D] of fig. 29-6 with the two screws [E] of fig.
29-6 using a Phillips screwdriver. Lastly, insert the external cover [F] in fig. 29-6 pressing it slightly to secure in place.
6.3 - INSTALLING AND CONNECTING THE FLASHING
LIGHT FL100 (fig. 30)
Select the position of the flashing light so that it is in the vicinity of the gate in a visible location. It can be fixed on either a horizontal or vertical surface.
Fig. 30 shows the two options:
01. Remove the cover, unscrewing the screw if present.
02. Separate the base, unscrewing the screws present to route the electric cables.
03. Trace the drilling holes using the base as a reference and ensuring that the hole on the base is aligned with the cable outlet: vertical fixture (A) or horizontal fixture (B).
04. Use a percussion drill to drill the wall, with a 6 mm tip, and insert 6 mm plugs.
05. Fix the base, using the relative screws.
06. Connect the electric cables in the relative FLASH and “aerial” terminals as shown in the figure: To facilitate operations, remove terminals, make connections, then refit the terminals.
No polarity needs to be observed on the FLASH terminal, while in the case of the shielded cable connection of the aerial, the sheath must be connected.
07. Insert the lamp holder in the base, taking care to press it down so that it locks into place.
08. Secure the body of the flashing light to the fixing support and turn it left until it clicks into place, then secure by means of the screw.
6.4 - ELECTRICAL CONNECTION TO CONTROL UNIT CL20S
To make the electrical connection, at very low voltage, of the various devices, refer to fig. 24.
01. To connect the gearmotors: remove the gearmotor cover as shown in fig. 20.
02. Loosen the cable clamp located below the gearmotor, route through the electric cable, then tighten the cable clamp fully down (fig. 25).
03. Make the electrical connections observing the colour coding shown in fig. 26.
04. Close the cover of the gearmotor (fig. 27).
At this point, make the electrical connections of the various devices
(see the paragraphs of the various accessories).
• The terminals have the same colour as the terminals on the corresponding devices; for example the grey terminal (OPEN) of the KS100 keyoperated selector switch must be connected to the grey terminal (OPEN) of the control unit;
• No polarity is needed for virtually any of the connections; only in the case of the shielded cable of the aerial, the central core and sheath must be connected as shown in detail [A] of fig. 24.
Notes: - To facilitate connections, terminals can be removed as shown in
fig. 28 - [B]; after making the connections, refit the terminals in their seats.
- At the end of connections, use cable ties to secure the electric cables to
the relative fixtures (fig. 28 - [C]).
English – 7
13
15
8 – English
8
10
11
9
12
14
16
18
20
E
F
17
B
19
A
C
D
H
G
21
22
23
English – 9
24
FL100
TX
PH100
RX
KS100
25
WG10SK
M2
WG10SK
M1
Brown
Yellow/Green
Blue
A
Blue
Yellow/Green
Brown
26
Yellow/Green
Brown
Blue
B
27 28
C
B
10 – English
29
1 2
A
3
C
4
B
5
D
E
F
6
30
A B
1
3
A / B
4
A / B
2
A / B
B x4
Ø = 6 mm
B B
English – 11
30
4
5
A
Ø = 6 mm x4
A
A / B
6
A / B
7
A A
A / B
8
A / B
9
A / B
10
A / B
11
A / B
12
A / B
12 – English
PROGRAMMING
––– STEP 7 –––
7.1 - POWER SUPPLY CONNECTION
WARNINGS
– The power cable is in PVC and is designed for installation indoors. If installed outdoors, the entire cable must be covered with a protection ducting. Otherwise the cable can be replaced with a H07RN-F version.
– Final connection of the automation to the electrical mains or replacement of the cable supplied must be made exclusively by a qualified and skilled electrician, in observance of the current safety standards and the following instructions.
• For automation operation tests and programming, use the cable supplied, inserting the plug in an electrical socket. If the socket is far from the automation, an extension may be used in this phase.
• For the automation testing and commissioning phase the control unit must be permanently connected to the power mains, replacing the cable supplied with one of adequate length. To connect the cable to the gearmotor control unit, proceed as follows:
WARNING!
The power line must be fitted with a disconnect device that ensures complete shut-off of power to the automation. The disconnect device must have contacts with a sufficient gap to ensure complete disconnection, in compliance with the overvoltage category III, according to the installation instructions. If necessary, this device guarantees quick and safe disconnection from the mains power and therefore must be positioned in sight of the automation. If located in a concealed position, it must be equipped with a system that prevents inadvertent or unauthorised reconnection of power, to avoid potential hazards. The disconnect device is not supplied with the product.
01. To test, insert the CL20S plug in a power socket, using an extension if necessary.
7.2 - INITIAL CHECKS (fig. 31)
After powering up the control unit, perform the following checks:
01. Ensure that the led “ECSBus” [A] (fig. 31) flashes regularly with the frequency of 1 flash per second;
02. Ensure that the LED “SAFE” [B] (fig. 31) on the photocells is flashing
(both on TX and RX); the type of flash is not important, as this depends on other factors; it is important that it is not off or permanently lit.
03. Ensure that the night-time light on the KS100 key-operated selector switch is on.
04. If these events do not occur, disconnect the control unit from the power supply and check the cable connections again with care. For other useful information, refer also to chapters 10.5 “Troubleshooting” and 10.6 “Diagnostics and signals”.
7.3 – LEARNING CONNECTED DEVICES (fig. 32)
On completion of initial checks, the control unit must be able to recognise the devices connected on the terminals “ECSBus” and “STOP”.
01. On the control unit, press and hold P2 [C] (fig. 32) for at least 3 seconds, then release.
02. Wait a few seconds for the control unit to complete the device learning phase.
03. At the end of the learning phase the STOP led [B] (fig. 32) must remain lit, while the LED P2 [C] (fig. 32) should turn off. If the LED P2 flashes it means there is an error; see paragraph 10.5 “Troubleshooting”.
The phase for learning connected devices can be repeated at any time also after installation (for example if a photocell is added); simply repeat the procedure from point 01.
7.4 - LEARNING THE GATE LEAF OPENING AND CLOSING
ANGLES
After learning devices, the control unit must recognise the opening angles of the leafs. In this phase the system reads the leaf opening angle from the mechanical closing stop through to the mechanical opening stop. The presence of fixed and sufficiently strong mechanical stops is essential.
01. Release the motors by means of the special keys (see paragraph
11.3 - User’s Guide) and move the leafs to mid-travel so that they are free to move in the opening and closing directions; then lock the motors.
02. On the control unit, press and release the key P3 [B] (fig. 33); wait for the control unit to perform the learning phase. closure of motor M1 through to the mechanical stop, closure of motor M2 through to the mechanical stop, opening of motor M2 and motor M1 through to the mechanical stop; complete closure of M1 and M2.
- If the first manoeuvre of one or both the leafs is not closure, press
P3 to stop the learning phase, invert the polarity of the motor/s that opened the leaf, inverting the two brown and blue wires on the terminal.
- If the first motor to close is not M1, press P3 to stop the learning phase, and invert the motor connections on the terminals.
- During the learning phase, if any device trips (photocells, key-operated selector switch, P3 pressed etc.), the learning phase is stopped immediately. In this case the entire learning phase must be repeated.
03. If LED P3 [A] (fig. 33) flashes at the end of the learning phase, it means there is an error; see paragraph 10.5 “Troubleshooting”.
The phase for learning the opening angles can be repeated at any time also after installation (for example if one of the opening stops is moved); simply repeat the procedure from point 1.
7.5 - CHECKING THE RADIO TRANSMITTERS
To check transmitters, simply press one of its 4 keys, ensure that the LED flashes and that the automation performs the associated command.
The command associated with each key depends on the mode in which they were memorised (see paragraph 10.4 “Memorising radio transmitters”). The transmitters supplied are already memorised and the keys, when pressed, send the following commands (fig. 34):
Key T1 = “OPEN” command
Key T2 = “Pedestrian opening” command
Key T3 = “Only open” command
Key T4 = “Only close” command
7.6 - SETTINGS
7.6.1 - Selecting the leaf speed
Leaf opening and closing can be at two speeds: “low” or “high”.
To change from one speed to another, briefly press key P2 [B] (fig. 35); the corresponding led P2 [A] (fig. 35) will turn on or off; when the led is off, the speed setting is “low”, when the led is on the speed setting is “high”.
7.6.2 - Selecting the operating cycle
Gate opening and closing can be performed in two different operating modes:
• Single cycle (semi-automatic): with one command, the gate opens and remains open until the next command which activates closing.
• Complete cycle (automatic closure): with one command, the gate opens and closes again automatically after a short interval (for the time interval, see paragraph 10.1 “Parameter settings via radio transmitter”).
To change from one mode to another, briefly press key P3 [B] (fig. 34); the corresponding led [A] (fig. 34) will turn on or off; when the led is off, the cycle is “single”, when the led is on the cycle is “complete”.
English – 13
31
A
32
A
B
C
33
34
T1
T2
T4
35
T3
14 – English
B
A
B
A
B
TESTING AND COMMISSIONING
––– STEP 8 –––
These are the most important phases when setting up an automation, in order to guarantee maximum safety.
Testing can also be used as a periodic check of devices in the automation.
Testing of the entire system must be performed by skilled and qualified personnel, who are responsible for the tests required to verify the solutions adopted according to the risks present, and for ensuring observance of all legal provisions, standards and regulations, with particular reference to all requirements of the standard EN
12445 which establishes the test methods for testing automations for power-operated gates.
8.1 - TESTING
01. Ensure that all instructions and warnings in STEP 1 have been strictly observed.
02. Using the selector or radio transmitter, test a gate closing and opening cycle and ensure that the leaf movement corresponds to specifications. A number of tests should be performed to ensure that the gate moves smoothly and that there are no assembly defects, incorrect settings, or any points of friction.
03. Check operation of all system safety devices one at a time (photocells, sensitive edges, etc.). In particular, each time a device trips, the
“ECSBus” led on the control unit emits a longer flash to confirm control unit recognition of the event.
04. To test photocells and in particular that there is no interference with other devices, pass a cylinder (fig. 36) (diameter 5 cm, length 30 cm) through the optic axis, first close to the TX and then the RX and then mid-way between the two. Ensure that in all cases the device engages, changing from the active status to alarm status and vice versa; then ensure that the action envisaged is performed on the control unit: during closure inverts movement.
05. Measure the force as specified in the standard EN 12445. If the motor force control is used as an auxiliary function for reduction of impact force, test and identify the setting that obtains the best results.
8.2 - COMMISSIONING
Commissioning can only be performed after positive results of all test phases. Partial or “makeshift” commissioning is strictly prohibited.
01. Produce the technical documentation of the automation, which must include at least the following documents: overall layout drawing (e.g.
fig. 3), electrical wiring diagram (e.g. fig. 24), risk assessment and solutions adopted, manufacturer’s declaration of conformity for all devices used (use appendix 1).
02. Affix a dataplate on the door, specifying at least the following data: type of automation, name and address of manufacturer (responsible for commissioning), serial number, year of construction and CE mark.
03. Permanently attach to the gate the label supplied in the pack, regarding the procedure for manual locking/release of the gearmotor.
04. Compile and provide the automation owner with the declaration of conformity (use appendix 2)
05. Prepare and provide the automation owner with the User’s guide; for this purpose appendix 3 “User’s guide” may be used as an example
(chapter 11.3).
06. Prepare and provide the owner with the form “Maintenance schedule”, containing all maintenance instructions for all devices in the automation
07. Before commissioning the automation, ensure that the owner is adequately informed of all associated risks and hazards.
36
MAINTENANCE
––– STEP 9 –––
Maintenance must be performed in strict observance of the safety provisions in this manual and according to current legislation and standards.
The automation devices do not require special maintenance. However a check should be performed at least every six months to ensure complete efficiency of all devices.
For this purpose, the tests and checks envisaged in paragraph 8.1 “Testing” should all be performed, as well as all procedure in the paragraph
“Maintenance operations permitted for the user”.
If other devices are present, follow the instructions in the relative maintenance schedule.no manutenzione.
PRODUCT DISPOSAL
This product is an integral part of the automation and therefore must be disposed together with the latter.
As in installation, also at the end of product lifetime, the disassembly and scrapping operations must be performed by qualified personnel.
This product is made of various types of material, some of which can be recycled while others must be scrapped. Seek information on the recycling and disposal systems envisaged by the local regulations in your area for this product category.
Caution! – some parts of the product may contain pollutant or hazardous substances which, if disposed of into the environment, may cause serious damage to the environment or physical health.
As indicated by the symbol alongside, disposal of this product in domestic waste is strictly prohibited. Separate the waste into categories for disposal, according to the methods envisaged by current legislation in your area, or return the product to the retailer when purchasing a new version.
Caution! – Local legislation may envisage serious fines in the event of abusive disposal of this product.
English – 15
FURTHER INFORMATION
––– STEP 10 –––
10.1 - ADVANCED SETTINGS
10.1.1 - Parameter settings via radio transmitter
The radio transmitter can be used to set a number of control unit operating parameters: there are eight parameters.
1) Pause time: the time for which the leafs remain open (in the case of automatic closure).
2) Pedestrian opening: Pedestrian leaf opening mode.
3) Motor force: motor force over which the control unit recognises an obstacle and inverts movement.
4) “OPEN” function: sequence of movements associated with each
“OPEN” command.
Parameters NO.
Value
5) Level of discharge of motor 1 on closing sets the duration of the “brief inversion” of the motor after a closing manoeuvre, serving to reduce the final residual force.
6) Level of discharge of motor 1 on opening: sets the duration of the “brief inversion” of the motor after an opening manoeuvre, serving to reduce the final residual force.
7) Level of discharge of motor 2 on closing sets the duration of the “brief inversion” of the motor after a closing manoeuvre, serving to reduce the final residual force.
8) Level of discharge of motor 2 on opening: sets the duration of the “brief inversion” of the motor after an opening manoeuvre, serving to reduce the final residual force.
TABLE 3
Action: operation to be performed at point 3 of the settings phase
Pause Time
Pedestrian opening
Motor force
“OPEN” function
2
3
4
1
2
1
2
3
4
1
2
3
4
3
4
1
(*) Factory setting
10s
20s (*)
40s
80s
Opening of 1 leaf to mid-travel
Total opening of 1 leaf (*)
Partial opening of 2 leafs to 1/4 of travel
Partial opening of 2 leafs to mid-travel
Low
Medium low (*)
Medium high
High
“Open”, “Stop”, “Close”, “Stop”
“Open”, “Stop”, “Close”, “Open” (*)
“Open”, “Close”, “Open”, “Close”
Opening only
Press T1 once
Press T1 twice
Press T1 three times
Press T1 four times
Press T2 once
Press T2 twice
Press T2 three times
Press T2 four times
Press T3 once
Press T3 twice
Press T3 three times
Press T4 four times
Press T4 once
Press T4 twice
Press T4 three times
Press T4 four times
Parameters
Discharge on closing Motor 1
Discharge on opening Motor 1
Discharge on closing Motor 2
Discharge on opening Motor 2
NO.
Value
7
8
1
2
3
2
3
4
5
6
5
6
7
8
1
3
4
1
2
1
2
3
4
5
6
7
8
4
5
6
7
8
No discharge (*)
0.1 s (Minimum)
0.4 s (Medium)
0.7 s (Maximum)
No discharge (*)
0.1 s (Minimum)
0.4 s (Medium)
0.7 s (Maximum)
No discharge (*)
0.1 s (Minimum)
0.4 s (Medium)
0.7 s (Maximum)
No discharge (*)
0.1 s (Minimum)
0.4 s (Medium)
0.7 s (Maximum)
TABLE 4
Actions to be performed
Press T1 once
Press T2 twice
Press T1 three times
Press T1 four times
Press T1 five times
Press T1 six times
Press T1 seven times
Press T1 eight times
Press T2 once
Press T2 twice
Press T2 three times
Press T2 four times
Press T2 five times
Press T2 six times
Press T2 seven times
Press T2 eight times
Press T3 once
Press T3 twice
Press T3 three times
Press T3 four times
Press T3 five times
Press T3 six times
Press T3 seven times
Press T3 eight times
Press T4 once
Press T4 twice
Press T4 three times
Press T4 four times
Press T4 five times
Press T4 six times
Press T4 seven times
Press T4 eight times
(*) Factory setting
16 – English
The parameter setting operation can be performed using any radio transmitter, provided that it is memorised in mode 1, in the same way as that supplied (see paragraph 10.4 “Memorisation mode 1”).
If there is no transmitter memorised in mode 1 a single one may be memorised for this phase, after which it must be deleted immediately (see paragraph 10.4.4 “Deleting a radio transmitter”).
CAUTION! – When making settings via a transmitter, the control unit must be allowed sufficient time to recognise the command via radio; in practice the keys must always be pressed and released slowly, pressing for at least one second, releasing for one second and so on.
To program the parameters, see Table 3.
01. Press T1 and T2 simultaneously (fig. 37) on the radio transmitter for at least 5 s.
02. Release the two keys.
03. Within three seconds, complete the action as specified in Table 3 according to the parameter to be modified.
Example: to set the pause time at 40 s.
01 Press and hold the keys T1 and T2 simultaneously for at least 5 seconds.
02. Release T1 and T2
03. Press T1 three times
37
38
T1
T2
All parameters can be adjusted as required without any contraindications, only the “Motor force” setting may require special attention:
• Do not use force values to compensate for anomalous points of friction on the gate. Excessive force settings may impair safety system operation or cause damage to the gate.
• If the “Motor force control” is used in support of the system for impact force reduction, after each adjustment the force measurement procedure must be performed, as envisaged by standard EN 12445.
• Weather conditions can influence gate movement; new adjustments may be required periodically.
To program the parameters, see Table 4.
01. Press T1 and T3 simultaneously (fig. 38) on the radio transmitter for at least 5 s.
02. Release the two keys.
03. Within three seconds, complete the action as specified in Table 4 according to the parameter to be modified.
Example: to set discharge on closing of motor 2 on level 4.
01. Press and hold the keys T1 and T3 simultaneously for at least 5 s seconds.
02. Release T1 and T3
03. Press T3 four times
T1
T3
10.1.2 - Checking settings via a radio transmitter
With a radio transmitter memorised in Mode 1 the user can check settings at any time for each parameter, as follows:
To display the parameters, see Table 5.
01. Press T1 and T2 simultaneously on the radio transmitter for at least
5s.
02. Release the two keys.
03. Within three seconds, complete the action as specified in Table 5 according to the parameter to be modified.
04. Release the key when the flashing light starts to flash
05. Count the number of flashes and, according to the number, check the corresponding value on Table 3.
Example: After pressing T1 and T2 for 5 s followed by T1, if the flashing light flashes three times, the pause time is set at 40 s.
TABLE 5
Parameter
Pause Time
Pass door
Motor force
“OPEN” function
Action
Press and hold T1
Press and hold T2
Press and hold T3
Press and hold T4
To display the parameters, see Table 6.
01. Press T1 and T3 simultaneously on the radio transmitter for at least 5 s.
02. Release the two keys.
03. Within three seconds, complete the action as specified in Table 6 according to the parameter to be modified.
04. Release the key when the flashing light starts to flash
05. Count the number of flashes and, according to the number, check the corresponding value on Table 4.
TABLE 6
Parameter
Level of discharge of motor 1 on closing
Level of discharge of motor 1 on opening
Level of discharge of motor 2 on closing
Level of discharge of motor 2 on opening
Action
Press and hold T1
Press and hold T2
Press and hold T3
Press and hold T4
10.2 - OPTIONAL ACCESSORIES
As well as the devices in WG20S, there are a number of optional accessories which may be used to integrate the automation system.
PR1: 24 V buffer battery; in the event of a mains power failure, this guarantees at least 10 complete cycles.
PF: 24 V solar power system; useful in cases in which there is no electrical mains power.
PT50: Pair of columns (height 500 mm) with photocell
PT100: Pair of columns (height 1000 mm) with two photocells
For information on new accessories, consult the MHOUSE catalogue or visit the website www.mhouse.com.
10.2.1 - Installing the PR1 buffer battery (fig. 39)
CAUTION! - The electric connection of the battery to the control unit must only be made after completing all installation and programming phases, as the battery constitutes an emergency power supply.
To install and connect the buffer battery PR1 to the control unit, refer to
fig. 39 and the PR1 instruction manual.
When the automation is powered by the buffer battery, 60 seconds after a manoeuvre is completed, the control unit automatically switches off the output “ECSbus” (and all connected devices), output Flash and all leds, with the exception of the ECSbus led, which flashes at slower intervals; this indicates the “Standby” function. When the control unit receives a command, it restores normal operation (with a short delay). This function is used to reduce consumption; an important factor when the unit is powered by battery.
10.2.2 - Installing the PF solar power supply system (fig. 40)
CAUTION! - When the automation is powered exclusively by the solar power system “PF”, IT MUST NEVER BE POWERED at the same time by the mains.
To connect the PF solar power system to the control unit, refer to fig. 40
English – 17
and the PF instruction manual.
When the automation is powered by the solar panel, 60 seconds after a manoeuvre is completed, the control unit automatically switches off the output “ECSbus” (and all connected devices), output Flash and all leds, with the exception of the ECSbus led, which flashes at slower intervals; this indicates the “Standby” function. When the control unit receives a command, it restores normal operation (with a short delay). This function is used to reduce consumption; an important factor when the unit is powered by photovoltaic panels.
39
1 2 3
B
40
B
1 2
10.2.3 - Maximum possible number of cycles per day
This product is specifically designed to operate also with the PF solar power supply system. Special technical provisions have been envisaged to minimise energy consumption when the automation is stationary, by turning off all devices not essential to operation (for example photocells and the key-operated selector switch). In this way all energy available and stored in the battery is used to move the gate.
Caution! - When the automation is powered by the solar power system “PF”, IT MUST NEVER BE POWERED at the same time by the mains.
Application limits: maximum possible number of cycles per day within a set period of the year.
The PF solar power system enables complete power autonomy of the automation, until the energy produced by the photovoltaic panel and stored in the battery remains above the amount consumed during gate manoeuvres. A simple calculation enables an estimate of the maximum number of cycles per day performed by the automation in a certain period of the year, provided that a positive energy balance is maintained.
The first step in calculating the energy available, is dealt with in the PF instruction manual; the second step in calculating the energy con-
sumed and therefore the maximum number of cycles per day, is dealt with in this chapter.
Calculating the energy available
To calculate the energy available (refer also to the PF instruction manual) proceed as follows:
01. On the terrestrial map supplied in the PF kit instruction manual, locate the point of system installation; then read the value Ea and the degrees of latitude of this location (E.g. Ea = 14 and degrees = 45°N)
02. On the graphs (North or South) supplied in the PF kit instruction manual, locate the curve for the location’s latitude (e.g. 45°N)
03. Choose the period of the year on which to base the calculation, or select the lowest point of the curve to calculate the worst period of the year; then read the corresponding value Am (e.g. December, January: Am= 200)
04. Calculate the value of energy available Ed (produced by the panel) multiplying Ea x Am = Ed (e.g. Ea = 14; Am = 200 therefore Ed =
2800)
Calculating the energy consumed
To calculate the energy consumed by the automation, proceed as follows:
05. On the table below, select the box corresponding to the intersection between the line with the weight and the column with the opening
angle of the gate leaf. The box contains the value of the severity
index (K) for each manoeuvre (e.g. WG2S with a leaf of 180 Kg and opening of 95°; K = 105).
Leaf weight
< 100 Kg
100-150 Kg
150-200 Kg
200-250 Kg
Opening angle
≤90°
90÷105°
61 76
72 92
84
110
105
144
105÷120°
105
138
200
336
18 – English
4500
4000
3500
3000
2500
2000
1500
1000
Ed
9500
9000
8500
8000
7500
7000
6500
6000
5500
5000
06. On the table A below, select the box corresponding to the intersection between the line with the Ed value and the column with the K value. The box contains the maximum possible number of cycles per day (e.g. Ed = 2800 and K= 105; cycles per day
≈ 22).
If the number obtained is too low for the envisaged use or is located in the
“area not recommended for use”, the use of 2 or more photovoltaic panels may be considered, or the use of a photovoltaic panel with a higher power.
Contact the Mhouse technical assistance service for further information.
The method described enables the calculation of the maximum possible number of cycles per day that can be completed by the automation while running on solar power. The calculated value is considered an average value and the same for all days of the week. Considering the presence of the battery, which acts as an energy “storage depot”, and the fact that the battery enables automation autonomy also for long periods of bad weather
(when the photovoltaic panel produces very little energy) it may be possible to exceed the calculated maximum possible number of cycles per day, provided that the average of 10-15 days remains within the envisaged limits.
Table B below specifies the maximum possible number of cycles, according to the manoeuvre’s severity index (K), using exclusively the energy
stored by the battery. It is considered that initially the battery is completely charged (e.g. after a prolonged period of good weather or recharging via the optional PCB power supply unit) and that the manoeuvres are performed within a period of 30 days.
When the battery runs out of the stored energy, the led starts to indicate the battery low signal by flashing briefly every 5 seconds, accompanied by a “beep”.
K
≤75
123
116
109
103
96
89
83
76
69
63
56
49
43
36
29
23
16
9
K=100
92
87
82
77
72
67
62
57
52
47
42
37
32
27
22
17
12
7
34
30
26
22
18
14
10
6
TABLE A - Maximum possible number of cycles per day
K=125 K=150 K=175 K=200 K=225 K=250
74
70
66
62
58
61
58
55
51
48
53
50
47
44
41
46
44
41
39
36
41
39
36
34
32
37
35
33
31
29
54
50
46
42
38
45
41
38
35
31
38
35
33
30
27
34
31
29
26
24
30
28
25
23
21
27
25
23
21
19
28
25
21
18
15
11
8
24
21
18
15
13
10
7
21
19
16
14
11
9
6
19
16
14
12
10
8
5
17
15
13
11
9
7
K=275
33
32
30
28
26
24
23
21
19
17
15
13
12
10
8
6
K=300
31
29
27
26
24
22
21
19
17
16
14
12
11
9
7
6
Area of use not recommended
8
7
5
13
11
10
K
≥325
28
27
25
24
22
21
19
18
16
14
K
≤75
741
K=100
556
TABLE B - Maximum number of cycles using exclusively battery power
K=125
445
K=150
371
K=175
318
K=200
278
K=225
247
K=250
222
K=275
202
K=300
185
K
≥325
171
10.3 - ADDING OR REMOVING DEVICES
An automation using WG20S enables devices to be added or removed at any time.
Caution! – Do not add devices before ensuring that they are fully compatible with WG20S; for further details, contact the MHOUSE technical assistance.
10.3.1 - ECSBus
ECSBus is a system that enables connections of ECSBus devices using just two wires, which convey both electrical power and communication signals. All devices are connected in parallel on the same 2 wires of the
ECSBus; each device is recognised individually as it is assigned a unique address during installation.
Photocells and other devices using this system can be connected to
ECSBus, such as safety devices, control buttons, indicator lights etc. For information on ECSBus devices, refer to the MHOUSE catalogue or visit the website www.mhouse.com.
A special learning phase enables the control unit to recognise all connected devices individually, and enables precise diagnostics procedures. For this reason, each time a device connected to ECSBus is added or removed, the learning phase must be performed on the control unit; see paragraph 10.3.3 “Learning other devices”.
10.3.2 - STOP Input
STOP is the input that causes immediate shutdown of the movement (followed by a brief inversion of the manoeuvre). This input can be connected to devices with contact types Normally Open (NO, as in the case of the
KS100 selector switch), Normally Closed (NC) or devices with a constant resistance of 8.2 k
Ω, such as sensitive edges.
When set accordingly, more than one device can be connected to the
STOP input, also different from one another; see Table 7.
Note 1. The NO and NC combination can be obtained by placing the two contacts in parallel, and placing an 8.2k
Ω resistance in series with the NC
contact (it is, therefore, possible to combine 3 devices: NA, NC and
8,2k
Ω).
Note 2. Any number of NO devices can be connected to each other in parallel.
Note 3. Any number of NC devices can be connected to each other in series.
Note 4. Only two devices with an 8.2 k
Ω constant resistance output can
be connected in parallel; multiple devices must be connected “in cascade” with a single 8.2 k
Ω termination resistance.
TABLE 7
1 st device type:
NO
NC
NO NC
In parallel (note 2) (note 1)
(note 1)
8,2K
Ω
In parallel
8.2 K
Ω
In parallel
In series (note 3) In series
In series (note 4)
Caution! – If the STOP input is used to connect devices with safety functions, only the devices with 8.2 k
Ω constant resistance output
will guarantee the fail-safe category 3.
As with the ECSBus, the control unit recognises the type of device connected to the STOP input during the learning phase; subsequently the control unit gives a STOP command when it detects a variation with respect to the learned state.
10.3.3 - Recognition of other devices
The learning operation of the devices connected to the ECSBus and
STOP input is usually carried out during the installation phase; if devices are added or removed the learning operation can be carried out again as follows:
01. Press and hold key P2 [B] on the control unit for at least three seconds (fig. 41), then release the key.
02. Wait a few seconds for the control unit to complete the device learning phase.
03. At the end of the learning the LED P2 [A] (fig. 41) should switch off. If the LED P2 flashes it means there is an error; see paragraph 10.5
“Troubleshooting”.
04. After having added or removed a device the automation test must be carried out again as specified in paragraph 8.1 “Testing”.
English – 19
41
A
B
42
10.3.4 - Adding optional photocells
Additional photocells to those supplied with the WG2S can be installed at any time. On an automation for 2-leaf gates, these can be positioned as shown in fig. 42.
In order for the control unit to correctly recognise the photocells they must be assigned with addresses using special electric jumpers. The address assignment operation must be carried out on both TX and RX (placing the electric jumpers in the same way) and it is important to check that there are not any other pairs of photocells with the same address. The photocell address assignment operation is necessary for them to be correctly recognised among the other devices of the ECSBus and to assign them their function.
01. Open the housing of the photocell.
02. Identify the position in which they are installed according to Figure 70 and place the jumper according to Table 8.
Unused jumpers must be placed in the special compartment for future use (fig. 43).
03. Carry out the learning phase as described in paragraph 10.3.3
“Recognition of other devices”.
43
TABLE 8
Photocell Jumpers
A
Photocell h=50 cm; triggered on closure
Photocell
D
Photocell on right with activation on opening
B
Photocell h=100 cm; triggered on closure
E
Photocell on left with activation on opening
C
Photocell h=50 cm; triggered on opening and closure
F
Photocell h=100 cm; triggered on opening and closure
Jumpers
10.4 - MEMORIZING ALL RADIO TRANSMITTERS
The control unit contains a radio receiver for GTX4 transmitters; the transmitter included in the box is already memorised and ready to use.
There are two ways of memorising a new transmitter:
• Mode 1: in this “mode” the radio transmitter is used as a whole, i.e. all the keys carry out a preset command (the transmitter supplied with the
WG2S is memorised using Mode 1).Obviously a radio transmitter in mode
1 can only control one single automation; that is:
Key T1
Key T2
Key T3
Key T4
“OPEN” Command
“Pedestrian opening” command
“Only open” command
“Only close” command
• Mode 2: each key can be associated to one of the four commands available. If this mode is used appropriately 2 or more different automations can be controlled, for example:
Key T1
Key T2
Key T3
Key T4
“Only open” Automation N° 1 command
“Only close” Automation N° 1 command
“OPEN” Automation N° 2 command
“OPEN” Automation N° 3 command
Obviously each transmitter is treated separately and for one single control unit there can be some transmitters memorised in mode 1 and others in mode 2.
The overall maximum memory capacity is of 150 units; mode 1 memorisation occupies one unit per transmitter while mode 2 occupies one unit per key.
Caution! – As memorisation procedures have a time limit (10 s), it is important to read the instructions in the next paragraphs before starting.
20 – English
Press key P1 [B] (fig. 44) for at least 3 s. When the LED P1 [A] (fig. 44) switches on release the key.
02. Within 10 s press any one key on the transmitter for at least 3 s to memorise it. If the memorisation procedure is successful, the LED P1 will emit 3 flashes.
03. If there are other transmitters to be memorised repeat step 2 within the next 10 s otherwise the memorisation phase will end automatically.
10.4.2 - Memorisation mode 2
With Mode 2 transmitter memorisation each key can be associated with any one of the commands shown in table 9.
In Mode 2 each key requires its own memorisation phase.
01. If the transmitter to be memorised is already memorised (such as the transmitters supplied which are already memorised in mode 1) the transmitter must be deleted following the procedure described in:
“10.4.4 - Deleting a radio transmitter”.
02. Press key P1 [B] (fig. 44) on the control unit the number of times equal to the required command, according to Table 9 (e.g. 3 times
for the “Only open” command).
03. Check that LED P1 [A] (fig. 44) flashes quickly for a number of times equal to the command selected.
04. Within 10 s press the required key on the radio transmitter for at least
2 s to memorise it. If the memorisation procedure is successful, the
LED P1 will emit 3 slow flashes.
05. If there are other transmitters to be memorised for the same type of command, repeat step 03 within the next 10 s otherwise the memorisation phase will end automatically.
10.4.3 - Remote memorisation
A new radio transmitter can be memorised on the control unit without having to use the unit itself. It is sufficient to have an “OLD” working and memorised radio transmitter. The “NEW” radio transmitter will “inherit” the characteristics of the OLD one; in other words if the old one is memorised in Mode 1 then the NEW one will also be memorised in Mode 1; in this case during the memorisation phase press any one key on the two transmitters. If the OLD radio transmitter is memorised in Mode 2 press the key with the required command on the OLD transmitter and press the key on the NEW transmitter with which you wish to associate the new command.
Take the two transmitters and position yourself within the action range of the automation and follow the following steps:
01. Press the key on the NEW radio transmitter for at least 5 s then release it.
02. Press the key on the OLD radio transmitter slowly 3 times.
03. Press the key on the NEW radio transmitter slowly once.
At this point the NEW radio transmitter will be recognised by the control unit and will take on the characteristics of the OLD one.
Repeat these steps for each new transmitter to be memorised.
10.4.4 - Deleting a radio transmitter
It is necessary to have a radio transmitter to delete it.
If the transmitter is memorised in Mode 1 one single deletion phase is sufficient and at point 3 any key can be pressed. If the transmitter is memorised in Mode 2 a deletion phase must be carried out for each key.
01. Press and hold key P1 [B] (fig. 44) on the control unit.
02. Wait for the LED P1 [A] (fig. 44) to switch on and within three seconds
03. Press the key on the radio transmitter to be deleted for at least three seconds. If deletion is successful LED P1 will emit five quick flashes.
If LED P1 emits one slow flash it means that the deletion has not been completed because the transmitter is not memorised.
04. To delete other transmitters keep key P1 pressed and repeat step 3 within 10 seconds otherwise the deletion procedure will end automatically.
10.4.5 - Deleting all radio transmitters
This procedure deletes all memorised transmitters.
01. Press and hold key P1 [B] (fig. 44) on the control unit.
02. Wait for LED P1 [A] (fig. 44) to switch on, then off and then flash 3 times.
03. Release P1 key precisely when the LED flashes the third time.
04. Wait about 4s for deletion to be completed, during which the LED will emit quick flashes.
If the procedure is successful after a few moments the LED P1 will emit 5 slow flashes.
44
A
B
TABLE 9
Once
Twice
Three times
Four times
Five times
Six times
“OPEN” Command
“Pedestrian opening” command
“Only open” command
“Only close” command
“Stop” command
“Apartment block open” command
Seven times “High priority open” command
Eight times “Pedestrial opening 2” command
Nine times
Ten times
“Pedestrial opening 3” command
Activates the automation as described in Table 3 (Open function)
Activates partial opening of one or two leafs as described in Table 3
(Pedestrian opening)
Activates opening of the leafs (open - stop - open etc.)
Activates closing of the leafs (close - stop - close etc.)
Stops the manoeuvre
On opening the command has no effect, and on closing inverts movement, i.e. opening of the leafs l’inversione del movimento, cioè l’apertura delle ante
Gives command even when automation is blocked
Activates partial opening of the leaf M2, equal to approx. mid-travel
Activates partial opening of the two leafs, equal to approx. mid-travel
“Open+ block automation” command It causes an opening manoeuvre, after which the automation is blocked;
The control unit accepts no further commands with the exception of “Open high priority” and “Release” automation
Eleven times “Close + block automation” command It causes a closure manoeuvre, after which the automation is blocked;
The control unit accepts no further commands with the exception of “Open high priority” and “Release” automation
Twelve times “Block automation” command It causes the manoeuvre to stop and the automation to block;
The control unit accepts no further commands with the exception of “Open high priority” and “Release” automation
Thirteen times “Unblock automation” command It causes the automation to be released and normal operation to resume
English – 21
10.5 - TROUBLESHOOTING
Table 10 gives possible indications on how to deal with malfunctions that may be met during installation or due to a fault.
TABLE 10 (fig. 45)
Probable cause and possible solution
• Check whether the batteries are flat and if necessary replace them (see paragraph 11.5)
Symptoms
The radio transmitter does not emit any signal (the LED [A] does not light up)
The manoeuvre does not start and the LED
“ECSBus” [B] does not flash
The manoeuvre does not start and the flashing light is off
The manoeuvre does not start and the flashing light flashes
The manoeuvre starts but is immediately followed by an inversion
The manoeuvre is carried out but the flashing light is not working
• Check that the power supply cable is correctly inserted in the mains socket
• Check that the fuses [E] and [F] have not been activated; if this is the case check the cause of the fault and replace them with other fuses with the same characteristics
• Check that the command is actually received. If the command reaches the OPEN input the relevant LED
“OPEN” [D] should light up; if a radio transmitter is used the LED “ECSBus” should emit two long flashes
• Check that the STOP input is active, in other words that the LED “STOP” [C] is on. If this is not the case check the device connected to the STOP input
• The photocell test carried out at the beginning of each manoeuvre is negative; check the photocells and refer to Table 11
• The force selected is too low to move the gate. Check for obstructions and if necessary select a higher force as described in paragraph 10.1.1
• During the manoeuvre, ensure that there is voltage on the FLASH terminal of the flashing light (as this is intermittent, the voltage value is not significant
45
B C
D
A
E
F
10.6 - DIAGNOSTICS AND SIGNALS
Some devices directly provide particular signals to describe the state of operation or eventually a malfunction.
10.6.1 - Photocells
The photocells contain a LED “SAFE” [A] (fig. 46) that provides information at any moment on the state of operation; see Table 11.
46
A
LED “SAFE”
Off
3 quick flashes and 1 second pause
1 very slow flash
1 slow flash
1 quick flash
1 very quick flash
Always lit
22 – English
TABLE 11
STATUS
The photocell is not powered or it is faulty
Device not recognised by the control unit
The RX receives an excellent signal
The RX receives a good signal
The RX receives a poor signal
The RX receives a bad signal
The RX does not receive any signal
ACTION
Check that the voltage on the photocell terminals is of about 8-
12 Vdc; if the voltage is correct then the photocell is probably faulty
Repeat the learning procedure on the control unit. Check that all the photocell pairs on ECSBus have different addresses (see
Table 8)
Normal operation
Normal operation
Normal operation but check TX-RX alignment and correct cleaning of photocell lenses
At the limit of normal operation; check TX-RX alignment and correct cleaning of photocell lenses
Check for any obstruction between TX and RX. Check that the
LED on the TX flashes slowly. Check TX-RX alignment
10.6.2 - Flashing light
During a manoeuvre the flashing light flashes every second; in case of anomalies the light flashes at more frequent intervals (half a second); the flashes are repeated twice with an interval of one second; see Table 12.
Quick flashes
1 flash
1 second pause
1 flash
2 flashes
1 second pause
2 flashes
3 flashes
1 second pause
3 flashes
4 flashes
1 second pause
4 flashes
Status
ECSbus error
Photocell activated
TABLE 12
Action
“Gearmotor force” limiting device activated
At the beginning of the manoeuvre the devices present do not correspond with those recognised; check and eventually carry out the learning procedure (10.3.3 “Recognition of other devices”). One or more devices may be faulty; check and, if necessary, replace them.
At the start of the manoeuvre, one or more photocells do not enable movement; check to see if there are any obstructions. During the movement if there is an obstruction no action is required.
During the movement, the gate experienced excessive friction; identify the cause.
STOP input activated At the start of the manoeuvre or during the movement, the STOP input was activated; identify the cause.
10.6.3 - Control unit
The LEDs on the control unit provide particular signals to report on the normal operation and on possible faults; see Table 13.
47
A
B
C
D
E
F
LED ECSBus [A] Status
TABLE 13 (fig. 47)
Action
Off
On
One flash per second
2 long flashes
1 flash every 5 seconds
Series of flashes separated by a pause
Quick flash
Fault
Serious fault
Check that the unit is powered; check that the fuses have not been activated; if this is the case check the cause of the fault and replace them with other fuses with the same characteristics.
There is a serious fault; switch off the control unit for a few seconds; if the status persists there is a fault and the electronic board must be replaced.
Control unit works correctly
Everything OK
Input status variation
Robotics in "standby" mode
A variation to the status of the inputs: OPEN, STOP, activation of the photocells, or when the radio transmitter is used, is normal.
Everything OK; when the control unit receives a command normal operation is restored (with a short delay).
The same signal as for the flashing light, see Table 12.
ECSBus short circuit
LED STOP [B]
Off *
On
LED OPEN [C]
Status
STOP input activated
Everything OK
Status
An overload has been detected therefore the power to the ECS-
Bus switched off. Check by disconnecting the devices one at a time.
To restore power to the ECSBus simply send a command, for example with a radio transmitter.
Action
Check the devices connected to the STOP input
STOP input active
Action
Off
On
Everything OK
OPEN input activated
OPEN input not active
This is normal only if the device connected to the OPEN input is active.
English – 23
LED P1 [D]
Off *
On
Series of quick flashes, from 1 to 4
5 quick flashes
1 slow flash
3 slow flashes
5 slow flashes
LED P2 [E]
Off *
On
1 flash per second
2 flashes per second
LED P3 [F]
Off *
On
1 slow flash
2 slow flashes
* or it could be in “Standby” mode
Status
Everything OK
Memorisation mode 1
Memorisation mode 2
Deletion OK
Wrong command
Memorisation OK
Deletion OK
Status
Everything OK
Everything OK
The learning phase has not been carried out or there are errors in the memory data
Device learning procedure underway
Status
Everything OK
Everything OK
There is no memorised opening angle
Opening angle learning phase is underway
Action
No memorisation underway
This is normal during memorisation mode 1 which lasts maximum 10 s.
This is normal during memorisation mode 2 which lasts maximum 10 s.
Deletion of a transmitter successfully completed
Command received from a transmitter which is not memorised
Memorisation successfully completed
All radio transmitters successfully deleted
Action
“Low” speed selected
“High” speed selected
Some faulty devices may be present; check and if necessary repeat the device learning phase (see paragraph 10.3.3 “Learning other devices”).
It shows that the search for connected devices is underway (it lasts maximum a few seconds).
Action
Cycle operation
Complete cycle operation
Perform the learning phase (see chapter 3.5.2 - Learning the leaf opening and closing angles)
Opening angle learning phase is underway
24 – English
TECHNICAL SPECIFICATIONS OF PRODUCT COMPONENTS
The product WG20S is produced by Nice S.p.a. (TV) I, Mhouse S.r.l is a company part of the NICE S.p.a. group. In order to improve its products, NICE
S.p.a. reserves the right to modify the technical characteristics at any time without prior notice. In any case, the manufacturer guarantees their functionality and fitness for the intended purposes. Note: all technical specifications refer to a temperature of 20°C.
Model/type
Product type
Adopted technology
Maximum start-up torque
Nominal torque
No-load speed
Speed at nominal torque
Stroke
Maximum frequency of cycles
Maximum frequency of cycles
Application limits
Power supply
Max. absorbed rated power
Ambient operating temperature
Use in particularly acid, saline or potentially explosive atmospheres
Assembly
Protection rating
Dimensions / weight
Straight gearmotor for WG10SK swing gates
Electromechanical gearmotor for automations of automatic gates and doors
24Vdc motor, helical gear reducer; mechanical release
1800N
600N
0.016 mm/s
0.014m/s
480 mm
26 cycles/hour
15 minutes approx.
The structural design of this product makes it suitable for use on gates with a weight up to 250 kg or leaf width up to 4.5 m and opening angle up to 130°
24Vdc
1,1A,; on start-up, maximum current is 3.6 A for a maximum time interval of 2 s
-20 ÷50°C (gearmotor efficiency is reduced at low temperatures)
No
Horizontal with specific fixing plates
IP44
908 x 100 h 117/ 10kg
Photocells PH100
Product type
Adopted technology
Detection capacity
TX transmission angle
RX reception angle
Useful range
Power supply / output
Absorbed power
Max. cable length
Possibility of address assignment
Ambient operating temperature
Presence detector for automations of automatic gates and doors (type D according to standard
EN 12453) comprising a transmitter “TX” and receiver “RX
Optical, by direct interpolation of TX-RX with modulated infra-red rays
Opaque objects located on the optical axis between TX and RX, larger than 50 mm and moving slower than 1.6 m/s
20° approx.
20° approx.
10 m for maximum TX-RX misalignment ±5° (the device can signal an obstacle even in the event of particularly adverse weather conditions
The device can only be connected to the “ECSBus” networks from which it receives mains power, and sends the output signals
1 ECSBus unit
Up to 20 m (observe warnings regarding the minimum section and type of cables)
UP to 7 detectors with protection function and 2 with opening command function
Automatic synchronisation prevents interference between the various detectors
-20 ÷ 50°C
Use in particularly acid, saline or potentially explosive atmospheres
Assembly
Protection rating
Dimensions/weight
No
Vertical, wall-mounted
IP44
64 x 89,2 h 29 mm / 60 g
English – 25
Control unit CL2S
Product type
Adopted technology
Max. cycles frequency
Power supply
Absorbed rated power
Emergency power supply
Motor outputs
Flashing light output
ECSBus output
“OPEN” input
“STOP” input
Radio aerial input
Max. cable length
Control unit for 1 or 2 24Vdc motors for automation of automatic gates or doors, complete with radio receiver for “GTX4” transmitters
Electronic board governed by 8-bit microcontroller with flash technology
A transformer incorporated in the control unit, but separated from the board, reduces the mains voltage to the nominal 24 V voltage used in the whole automation system.
30 cycles/hour
230Vac (+10% -10%) 50/60Hz
120 W; on start-up power is 310 W for a maximum time interval of 2s
For “PR1” buffer batteries
2, for 24 Vdc motors with nominal current of 1.1A, on start-up, maximum current is 3.5 A for a maximum time interval of 2 s
For flashing lights with 12V (maximum 21 W) bulb
1 output with maximum load of 15 ECSBus units
For normally open contacts (closure of the contact prompts the “OPEN” command)
For normally open and/or 8,2kohm constant resistance type contacts, or normally closed contacts with self-learning of the "normal" status (a variation with respect to the memorised status generates a “STOP” command)
50 ohm for RG58 or similar type cable
Mains power-supply: 30 m; motor outputs: 10 m; other inputs/outputs: 20 m with antenna cable preferably less than 5 m (observe warnings regarding the minimum section and type of cables)
-20 ÷ 50°C
No
Ambient operating temperature
Use in particularly acid, saline or potentially explosive atmospheres
Assembly
Protection rating
Dimensions / weight
Possibility of remote control
Compatible GTX4 transmitters
GTX4 transmitter range
Programmable functions
Self-programmed functions
Vertical, wall-mounted
IP44
180 x 240 h 110mm / 2.8kg
With “GTX4” transmitters, the control unit is set to receive one or more of the following commands: “OPEN”, “Partial opening”, “Only Open” and “Only Close”
Up to 150 if memorised in mode 1
50-100 m This distance may vary in the presence of obstacles and electromagnetic disturbance present, and is influenced by the position of the receiving antenna built into the flashing light
"Single cycle" or “Complete cycle” (automatic closure) operating mode
Motor speed “low” or “high”
Pause time in “complete cycle” selectable from 10, 20, 40, and 80 seconds
Type of partial opening selectable from 4 modes
Obstacle detection system sensitivity selectable on 4 levels “Open command” operating mode selectable on 4 modes
Self-learning of devices connected to the ECSBus output
Self-learning of type of "STOP" device (NO, NC or 8.2 k
Ω resistance contact)
Self-learning of manoeuvre length for each motor
Self-learning og the automation with 1 or 2 motors
26 – English
Indicator light FL100
Product Type
Adopted technology
Lamp
Power supply
Flashing indicator light for automations of automatic gates and doors.
The device incorporates a receiver antenna for remote control
Indicator light with 12V 21W lamp controlled by the control units for MHOUSE automations
12V 21W fitting BA15 (vehicle type lamp)
The device can only be connected to the terminals “FLASH” and “AERIAL” of the MHOUSE automation control units
-20 ÷ 50°C
No
Ambient operating temperature
Use in particularly acid, saline or potentially explosive atmospheres
Assembly
Protection rating
Dimensions / weight
Horizontal on a flat surface or vertical wall-mounted
IP55
120 x 60 h 170mm / 285g
GTX4 Transmitters
Product Type
Adopted technology
Frequency
Encoding
Keys
Radiated power
Power supply
Battery life
Ambient operating temperature
Use in particularly acid, saline or potentially explosive atmospheres
Protection rating
Dimensions / weight
Radio transmitters for remote control of automations for automatic gates and doors.
Encoded AM OOK radio modulation
433.92 MHz
64 Bit rolling code (18 billion billion combinations)
4, each key can be used for different commands of the same control unit or to control different control units
0.001 W approx.
3V; +20% -40%; with 1 lithium battery type CR2032
3 years, estimated on the basis of 10 commands/day lasting 1s at 20°C (battery efficiency is reduced at low temperatures)
-20 ÷ 50°C
No
IP40 (use in the home or protected environments)
50 x 50 h 17mm / 16g
English – 27
CE Declaration of Conformity
Declaration in accordance with the Directives: 1999/5/EC (R&TTE), 2004/108/EC (EMC); 2006/42/EC (MD) Appendix II, part B
WG10SK, CL20S, GTX4, PH100 and FL100, and are produced by Nice S.p.a. (TV) I;
MHOUSE S.r.l . is a commercial trademark owned by the group Nice S.p.a.
Note - The contents of this declaration correspond to declarations in the last revision of the official document deposited at the
registered offices of Nice Spa available before this manual was printed. The text herein has been re-edited for editorial purposes. A copy of the original declaration can be requested from Nice S.p.a. (TV) I.
Number: 367/WG20S
Manufacturer’s Name:
Address:
Person authorised to compile the technical documentation:
Product type:
Model / Type:
Accessories:
Revision: 0
NICE S.p.A.
Language: EN
Via Pezza Alta 13, Z.I. Rustignè, 31046 Oderzo (TV) Italy
Sig. Oscar Marchetto.
Electromechanical gearmotor with accessories
WG10SK, CL20S, GTX4, PH100, FL100
The undersigned, Luigi Paro, in the role of Managing Director, declares under his sole responsibility, that the above mentioned product conforms to the requirements of the following directives:
• The products CL20S and GTX4 conform to the 1999/5/CE DIRECTIVE OF THE EUROPEAN PARLIAMENT AND COUNCIL of
9th March 1999 regarding radio equipment and telecommunications terminal equipment and the mutual recognition of their conformity, according to the following harmonised standards:
- Health protection (art. 3(1)(a)): EN 50371:2002
- Electric safety (art. 3(1)(a)): EN 60950-1:2006
- Electromagnetic compatibility (art. 3(1)(b)): EN 301 489-1 V1.8.1:2008, EN 301 489-3 V1.4.1:2002
- Radio spectrum (art. 3(3)): EN 300 220-2 V2.1.2:2007
In accordance with the directive 1999/5/EC (appendix V), the product is class 1 and marked:
0682
• Models WG10SK, CL20S, PH100 and FL100 conform to DIRECTIVE 2004/108/CE/108/EC OF THE EUROPEAN PARLIA-
MENT AND COUNCIL of 15th December 2004 regarding the approximation of member state legislation related to electromagnetic compatibility, repealing directive 89/336/EEC, according to the following harmonised standards:
EN 61000-6-2:2005, EN 61000-6-3:2007
In addition the product WG10SK and CL20S conform to the following directive according to the requirements for “partly completed machinery”:
2006/42/EC DIRECTIVE OF THE EUROPEAN PARLIAMENT AND COUNCIL of 17 May 2006 regarding machinery, repealing directive 95/16/EC
•
We hereby declare that the relevant technical documentation has been compiled in conformity with Annex VII B of directive 2006/42/EC and that the following essential requirements have been satisfied:
1.1- 1.1.2- 1.1.3- 1.2.1-1.2.6- 1.5.1-1.5.2- 1.5.5- 1.5.6- 1.5.7- 1.5.8- 1.5.10- 1.5.11
•
The manufacturer undertakes to transmit, in response to a reasoned request by the national authorities, relevant information on the “partly completed machinery”, without prejudice to intellectual property rights of the manufacturer.
•
Should the “partly completed machinery” be put into service in a European country with an official language different from the one of this declaration, the importer must attach the translation of this document to the declaration.
•
The “partly completed machinery” must not be put into service until the final machinery into which it is to be incorporated has been declared in conformity with the provisions of directive 2006/42/EC.
In addition the product WG10SK and CL20S conform to the following directives:
EN 60335-1:2002 + A1:2004 + A11:2004 + A12:2006 + A2:2006 + A13:2008
EN 60335-2-103:2003
The products WG10SK and CL20S also comply, within the constraints of applicable parts, with the following standards:
EN 13241-1:2003, EN 12445:2002, EN 12453:2002, EN 12978:2003
Oderzo, 11 th November 2010
Ing. Luigi Paro (Managing Director)
28 – English
USER’S GUIDE
––– STEP 11 –––
This guide must be stored safely and be accessible to all automation users.
11.1 – Safety instructions
• Keep at a safe distance from the moving door until it is completely open or closed; do not go through the door until it is completely open and has come to a standstill.
• Do not allow children to play near the door or with the controls.
• Keep the transmitters away from children.
• Suspend the use of the automation immediately as soon as you notice something abnormal in the operation (noises or jolting movements); failure to follow this warning may cause serious danger and accidents.
• Do not touch moving parts.
• Regular maintenance checks must be carried out by qualified personnel according to the maintenance plan.
• Maintenance or repairs must only be carried out by qualified technical personnel.
11.2 – Gate Control
• With radio transmitter
The radio transmitter supplied is ready for use and the four keys have the following functions (fig. 48):
• With selector (optional accessory)
The selector has two positions with automatic return to the centre
(fig. 49).
49
48
T1
T2
T4
T3
Function (*)
Key T1
Key T2
Key T3
Key T4
(*) This table must be compiled by the person who programmed the automation.
Action
Turned right: “OPEN”
Turned left: “STOP”
Function
(*)
Stops movement of the sectional or up-and-over door
(*) This item must be compiled by the person who programmed the automation.
• Control with safety devices out of service
In the event of safety devices malfunctioning or out of service, the door may still be moved.
01. Activates the gate command (with remote control or key-
operated selector switch). The door will open normally if there is the consent of the safety devices, otherwise the command must be activated and held within 3 seconds.
02. After about 2 s the door will move in “hold-to-run” mode, in
other words until the command is pressed the door will continue to move; the door will stop as soon as the command is released.
In the event of safety devices out of service arrange for repairs to the automation immediately.
11.3 – Manually releasing or locking the gearmo-
tor (fig. 50)
WG20S are equipped with a mechanical system that enables manual opening and closing of the gate (i.e. as if there is not a gearmotor).
The manual operation must be carried out in case of power failure or system malfunction. In case of power failure the buffer battery can be used (optional accessory PR1).
In case of fault of the gearmotor the motor release can be used to check whether the fault is in the release mechanism.
01. Turn the release cap cover anti-clockwise until it coincides
with the hole with the release pin.
02. Insert the key in the release pin.
03. Turn the key anti-clockwise by about 90° until the gate is
released.
04. Then move the gate manually.
English – 29
05. To reset the automation turn the key clockwise and at the
same time move the gate until you hear the carriage engage.
06. Remove the key and close the release cap cover by turning it
clockwise.
50
11.5 – Remote control battery replacement
(fig. 51)
When the battery charge is low, the transmitter range is reduced significantly. When a key is pressed, if led L1 illuminates and then immediately fades and turns off, this means that the battery is completely discharged and must be replaced immediately.
Otherwise if led L1 illuminates briefly, this means that the battery charge is low; in this case press and hold the key for at least half a second to enable the transmitter to attempt delivery of the command. In any event, if the battery charge is too low to complete a command (and wait for a response) led L1 fades and the transmitter turns off. In these cases, to restore normal operation of the transmitter, replace the old battery with a new version of the same type, taking care to observe the specified polarity.
51
11.4 – Maintenance operations admissible to the
user
The list of operations to be regularly carried out by the user is listed below.
• For cleaning the surfaces of the devices, use a slightly damp (not wet) cloth. Never use substances containing alcohol, benzene, diluents or other flammable substances. Use of these substances may damage the devices and cause fires or electric shocks.
• Disconnect the automation from the power supply before removing leaves or stones to stop anyone activating the door.
• Regularly check the system, in particular the cables, springs and supports and check for signs of unbalance, wear or damage. Do not use the automation if it needs to be repaired or adjusted as a fault or an incorrectly balanced door may cause injuries.
The batteries contain pollutant substances: do not dispose of them with normal waste material; follow the instructions foreseen by local regulations.
11.6 – Installing the remote control support
To install the remote control support, see fig. 52.
52
30 – English
APPENDIX 2
CE DECLARATION OF CONFORMITY
In conformity with Directive 2006/42/EC, APPENDIX II, part A (EC declaration of conformity for machinery)
––––––––––––––––––––
The undersigned/company (name or company name of the person responsible for commissioning of the power-ope-
rated gate):
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hereby declares under his/her sole responsibility that:
- the automation: power-operated swing gate
- Serial N°: . . . . . . . . . . . . . . . . . . .
- Year of manufacture: . . . . . . . . . . . . . . . . . . .
- Location (address): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Complies with the essential requirements of the following directives:
2006/42/EC “Machinery” Directive
2004/108/EEC Electromagnetic compatibility directive
2006/95/EEC “Low Voltage” Directive
1999/5/EC “R&TTE” Directive
and what is provided for by the following harmonised standards:
EN 12445 “Industrial, commercial and garage doors and gates. Safety in use of power operated doors - Test methods”
EN 12453 “Industrial, commercial and garage doors and gates. Safety in use of power operated doors -
Requirements”
Name: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Signature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Date: . . . . . . . . . . . . . . . . . . . . . .
Place: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
English – 31
Mhouse is a commercial trademark owned by Nice S.p.a.
Nice S.p.a.
Via Pezza Alta, 13 - Z.I. Rustignè
31046 Oderzo (TV), Italia
Tel. +39 0422 85 38 38
Fax +39 0422 85 35 85
advertisement
Key Features
- Residential swing gate automation
- Control unit with radio receiver
- 24V DC motor with worm reducer
- Manual locking system
- Up to 256 transmitters & 6 photocell pairs
- Optional accessories (photocells, transmitters)
- Flashing light with integrated aerial
Related manuals
Frequently Answers and Questions
What type of gate is this automation system designed for?
What are the main components of the Mhouse WG20S system?
What kind of motor is used in the gearmotors?
Can I manually open the gate if the power goes out?
How many transmitters can the control unit store?
What kind of photocells can be used with this system?
advertisement