Mitsubishi Electronics 2033C Power Supply Technical Manual


Add to my manuals
48 Pages

advertisement

Mitsubishi Electronics 2033C Power Supply Technical Manual | Manualzz

MITSUBISHI ELECTRIC AUTOMATION, INC.

UNINTERRUPTIBLE POWER SUPPLY SYSTEM

2033C SERIES

OWNERS / TECHNICAL MANUAL

Revision 2.1: November 11, 2003

ALN-H0626

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Preface

Page Number: i

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number: ii

TABLE OF CONTENTS

LIST OF TABLES ............................................................................................... iii

LIST OF FIGURES ............................................................................................. iv

HOW TO USE THIS MANUAL ............................................................................ v

1.0 INTRODUCTION ......................................................................................... 1-1

1.1 GENERAL..................................................................................................... 1-3

1.2 DEFINITIONS .............................................................................................. 1-4

1.3 OVERVIEW ................................................................................................. 1-5

1.4 SPECIFICATIONS ....................................................................................... 1-14

2.0 OPERATION CONTROLS AND INDICATORS .......................................... 2-1

2.1 LCD TOUCH PANEL MONITOR DISPLAY AND KEYPAD ......................... 2-1

2.2 EXTERNAL SIGNAL TERMINAL BLOCK .................................................... 2-5

2.3 EXTERNAL COMMUNICATION CONNECTOR ......................................... 2-8

3.0 INSTALLATION AND OPERATION ........................................................... 3-1

3.1 TRANSPORTATION AND INSTALLATION ............................................... 3-1

3.2 HANDLING ................................................................................................. 3-1

3.3 INSTALLATION PROCEDURE ................................................................... 3-2

3.4 PROCEDURE FOR CABLE CONNECTIONS ............................................. 3-3

3.5 OPERATING PROCEDURES .................................................................... 3-9

3.6 MAINTENANCE BYPASS SET-UP PROCEDURES .................................. 3-10

4.0 RESPONSE TO UPS FAILURE .................................................................. 4-1

5.0 PARTS REPLACEMENT ............................................................................ 5-1

6.0 FAULT CODES ........................................................................................... 6-1

7.0 WARRANTY & OUT OF WARRANTY SERVICE ....................................... 7-1

MITSUBISHI ELECTRIC 2033C SERIES UPS

Table 1.1

Table 1.2

Table 1.3

Table 1.4

Table 3.1

Table 3.2

Table 3.3

Table 3.4

Table 3.5

MITSUBISHI 2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

List of Tables

Page Number: iii

Power Specifications ................................................................... 1-14

UPS Module Information.............................................................. 1-14

Detail of Specifications ................................................................ 1-15

Rating of Conductor and Fuses ................................................... 1-16

How to Transport and Install the System ..................................... 3-1

List of UPS Weights (lb.).............................................................. 3-2

Type and Number of Internal Battery .......................................... 3-2

Recommended Cable Size and Torque Requirements .............. 3-4

Crimp Type Compression Lug ..................................................... 3-4

MITSUBISHI ELECTRIC 2033C SERIES UPS

Figure 2.2

Figure 2.3

Figure 2.4

Figure 2.5

Figure 2.6

Figure 2.7

Figure 2.8

Figure 2.9

Figure 3.1

Figure 3.2

Figure 3.3

Figure 3.4

Figure 3.5

Figure 3.6

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

List of Figures

Page Number: iv

Figure 1.1

Figure 1.2

Figure 1.3

Figure 1.4

Single Line Diagram-Normal Operation ....................................... 1-5

Single Line Diagram-Bypass Operation....................................... 1-6

Single Line Diagram-Battery Operation ....................................... 1-7

Single Line Diagram - UPS on Maintenance Bypass Operation. . 1-7

Figure 1.5a UPS Parts Location (7.5-20kVA) ................................................. 1-9

Figure 1.5b UPS Parts Location (30kVA) ....................................................... 1-10

Figure 1.5c UPS Parts Location (40,50kVA) .................................................. 1-11

Figure 1.6 Display PCB DPAU-72 ............................................................... 1-11

Figure 1.7

Figure 1.8

Figure 2.1

External I/F PCB RYDR-X .......................................................... 1-11

Main Control PCB UPFR-K.......................................................... 1-12

Operation/Display Panel ............................................................. 2-1

MAIN MENU Screen ................................................................... 2-2

MEASURMENT Screens ............................................................ 2-2

DATE&CLOCK SETUP Screen .................................................. 2-4

External Signal Terminal Block ................................................... 2-5

External Signal Terminal Block ................................................... 2-5

Control Wiring for External Contacts ........................................... 2-6

Remote "Start" Contact Connections........................................... 2-7

External communication connector.............................................. 2-8

Handling ..................................................................................... 3-1

UPS Terminal Designation .......................................................... 3-5

Input / Output Power Terminals (7.5-20kVA) -............................. 3-6

Input / Output Power Terminals (30kVA) ................................... 3-7

Input / Output Power Terminals (40,50kVA) ............................... 3-8

EPO Button ................................................................................. 3-9

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

How to use this Manual

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number: v

This manual is designed for ease of use, giving the user easy and quick reference to information.

This manual uses notice icons to draw attention to the user important information regarding the safe operation and installation of the UPS. The notice icons used in this manual are explained below, and should be taken into account and adhered to whenever they appear in the text of this manual.

Warning: A warning notice icon conveys information provided to protect the user and service personnel against hazards and/or possible equipment

damage.

Caution: A caution notice icon conveys information provided to protect the user and service personnel against possible equipment damage.

Note: A Note notice icon indicates when the user should make a reference of information regarding the UPS operation, load status and display status.

Such information is essential if Mitsubishi field service group assistance and correspondence is required.

Safety Recommendations: If any problems are encountered while following this manual,

Mitsubishi field service group assistance and correspondence is recommended.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-1

1.0 INTRODUCTION

The Mitsubishi Uninterruptible Power Supply (UPS) is designed to provide many years of reliable power supply and protection from power failure, brown-outs, line noise and voltage transients. To ensure optimum performance of the equipment, follow the manufacturer's instructions accordingly.

This manual contains descriptions for the installation and operation procedures of the UPS. Please read this manual carefully and retain it for future reference.

IMPORTANT SAFETY INSTRUCTIONS

RETAIN THESE INSTRUCTIONS

This manual contains important instructions for the 2033C Series Uninterruptible Power Supply

Systems that should be adhered to during installation, operation and maintenance of the UPS and batteries.

WARNING 1

Lethal voltages exist within the equipment during operation.

Observe all warning and cautions in this manual.

Failure to comply may result in serious injury or death.

Obtain a qualified service for this equipment as per instructions.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-2

WARNING 2

This UPS does not include an AC input circuit breaker (MCCB) to protect the bypass and main input circuit. The AC input circuit breaker (MCCB) is to be field supplied and installed. Circuit breaker (MCCB) specifications are as follows:

Capacity

(kVA)

AC input

Voltage (Vac)

AC input

Rating (Aac)

Recommended

Breaker (A)

7.5 208 23 30

10 208 30 35

15 208 45 60

20 208 61 75

30 208 91 125

40 208 121 150

50 208 151 200

AC output and DC input overcurrent protection and disconnection devices shall be field supplied and installed.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-3

1.1 GENERAL

The Mitsubishi 2033C Series UPS is designed to provide continuous and clean electrical power to a critical load. In the event of an input power failure, the UPS will supply power to the critical load for the specified battery time.

If the input power is not restored promptly, backup power from the UPS battery permits the orderly shutdown of equipment supported by the UPS. The UPS is simple to start up, operate and maintain.

The 2033C Series UPS is available in seven (7) kVA sizes: 7.5, 10, 15, 20, 30, 40 and 50kVA.

Specifications for each kVA model appear in Section 1.4. Models up to 30kVA have batteries included in the UPS module cabinet. 40kVA and 50kVA models have external batteries. The principles of operation described herein are applicable to all models.

This manual provides an overview of the 2033C Series components and their functions. The appearance and purpose of operator controls and indicators is described with procedures for operation, start-up, shutdowjn and basic maintenance included.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-4

1.2 Definitions

UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) - All components within the UPS

Module Cabinet and associated batteries which function as a system to provide continuous, conditioned AC power to a load. This is sometimes referred to as the "System".

UPS MODULE CABINET - The metal enclosure which contains the Converter / Charger,

Inverter, Static Transfer Switch, Internal Bypass line, operator controls, batteries (up to 30kVA models only) and internal control systems required to provide specified AC power to a load.

UPS MODULE - The Converter / Charger and Inverter assemblies which, under the direction of the internal control system and operator controls, provide specified AC power to a load.

CONVERTER / CHARGER - The UPS components which contain the equipment and controls necessary to convert input AC power to regulated DC power required for battery charging and for supplying power to the Inverter.

INVERTER - The UPS components which contain the equipment and controls necessary to convert DC power from the Converter / Charger, or the battery, to AC power required by the critical load.

STATIC TRANSFER SWITCH - The device which connects the critical load to the bypass line when the Inverter cannot supply continuous power.

BYPASS LINE - The line which conducts electricity directly from the input power source to the critical load during Maintenance or whenever the UPS is not completely operational.

AC INPUT POWER - Power provided by the electrical utility company, or auxiliary generator, which is connected to the UPS for supplying the critical load and recharging the battery.

BATTERY - The rechargeable battery strings which supply DC power to the inverter to maintain continuous AC power to the load during AC input power failure conditions.

MITSUBISHI ELECTRIC 2033C SERIES UPS

AC input

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-5

1.3 Overview

The UPS provides two power paths between the utility source and the critical load. Figure 1.1 shows the path for normal operation, with the load powered from the inverter. Figure 1.2 shows the path for bypass operation, with the load supplied through the static bypass line.

FIGURE 1.1 Single Line Diagram - Normal Operation. Load powered by inverter.

CB

User supplied

CB1

FI

BATTERY

CB3

CONVERTER INVERTER

FB

CB2

Static Transfer

Switch

FO

40kVA, 50kVA:

External Battery

Maintenance

Bypass

Switch

Output

52C

52CS(7.5-20kVA)

52MB&52L(30-50kVA)

Power Flow

Not in Use

UPS Module

During normal operation, the path through the inverter is used to power the load.

Referring to Figure 1.1: Input AC power is converted to DC by the Converter. DC power is utilized to charge the UPS battery and to provide power to the Inverter. The Inverter converts the DC power to clean AC power to supply the critical load.

The conversion - inversion process eliminates any voltage transients or fluctuations existing in the input power before it reaches the critical load.

* The Input circuit breaker(MCCB) for protection of the UPS and cables are field supplied and field installed. (See WARNING 2 in section 1.0).

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-6

FIGURE 1.2 Single Line Diagram - Bypass Operation. Load fed through static bypass line.

AC input

CB

CB3

Static Transfer

Switch

CONVERTER INVERTER

Maintenance

Bypass

Switch

User supplied

CB1

FI

FB

FO

Output

52C

52CS(7.5-20kVA)

52MB&52L(30-50kVA)

CB2

Power Flow

Not in Use

BATTERY

40kVA, 50kVA:

External Battery

UPS Module

Referring to Figure 1.2, the Internal Static Bypass line is a Hard wired line through CB3 which supplies the critical load with unconditioned input power. The purpose of this line is to route power to the critical load while the UPS module is de-energized (converter and inverter), and during

Start-up before the system is fully operational.

The internal control system determines the operation of the two paths, with the load powered from the inverter being the normal operation.

Referring to Figure 1.3, if the input power is interrupted, the battery will immediately supply the DC power required by the Inverter to maintain continuous AC power to the load. A fully charged battery will provide power for the specified time at the rated load, or longer at reduced load.

When power is restored after a low battery shutdown, the Converter automatically restarts operation, recharges the batteries and the Inverter is automatically restarted without operator intervention. The load is assumed by the inverter automatically without operator intervention.

In the event of a power failure, the Converter will de-energize and the batteries will discharge into the Inverter and maintain power to the critical load until a) the battery capacity expires and the inverter turns off, or b) input power is restored after which the converter will power the inverter and simultaneously recharge the batteries. Figure 1.3 illustrates the flow diagram during battery operation.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

FIGURE 1.3 Single Line Diagram - Battery Operation

CB3

Static Transfer

Switch

Page Number:

1-7

Maintenance

Bypass

Switch

CB

CONVERTER INVERTER

AC input

Output

User supplied

CB1

FI

FO

52C

FB

52CS(7.5-20kVA)

52MB&52L(30-50kVA)

CB2

Power Flow

Not in Use

BATTERY

40kVA, 50kVA:

External Battery

UPS Module

The UPS is equipped with an internal rotary type Maintenance Bypass Switch (MBS) that can be used to divert utility power to the load during maintenance sessions. Figure 1.4 illustrates the power path when the MBS is in the BYPASS mode.

FIGURE 1.4 Single Line Diagram - UPS on Maintenance Bypass Operation.

Static Transfer

Switch

Maintenance

Bypass

Switch

CB3

CB

CONVERTER INVERTER

AC input

Output

User supplied

CB1

FI

FO

52C

FB

52CS(7.5-20kVA)

52MB&52L(30-50kVA)

CB2

Power Flow

Not in Use

BATTERY

40kVA, 50kVA:

External Battery

UPS Module

(7.5/10/15/20kVA)

The rotary maintenance bypass switch is shown as 52CS in Figure 1.4. 52CS is a two position three point make-before-break transfer switch.

(30/40/50kVA)

Two contactors (52MB, 52L) are used instead of the 52CS. A rotary switch(SWM) is used for control of the two contactors.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-8

The two positions are identified as NORMAL and BYPASS. In the NORMAL position the load is fed by the UPS - either through the inverter or through the static bypass line. In the BYPASS position the load is powered by an external source such as the utility or a generator. This transfer operation must be made while the UPS is in the static bypass mode.

The transfer procedure to place the UPS in maintenance bypass mode, or from bypass mode to normal operation mode is outlined below:

A) Transfer of load from inverter to maintenance bypass

1. On the front panel, press the "STOP" button. The “BYP.OP.” LED illuminates within 3 seconds.

2. After confirming that the “BYP.OP.” LED is illuminated, Rotate MBS(52CS/SWM) clockwise to the “TRANSFER” position (Do not rotate 52CS/SWM if the “BYP.OP.” LED is NOT illuminated).

3. After 3 seconds, rotate 52CS/SWM clockwise to the “BYPASS” position.

4. Transfer complete. Load is now powered from the external source. UPS can be shutdown.

B) Transfer of load from maintenance bypass to inverter

1. Rotate 52CS/SWM counterclockwise from the “BYPASS” position to the “TRANSFER” position, wait 5 seconds.

2. On the UPS, confirm the “BYP.OP.” LED is illuminated. If not, press the “STOP” button.

3. Rotate 52CS/SWM counterclockwise to the “NORMAL” position.

4. On the UPS, press the “START” button. The “INV.OP.” LED should illuminate.

5. Transfer complete. Load now powered by the inverter.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

FIGURE 1.5a UPS Parts Location(7.5-20kVA)

UPS module

FRONT VIEW

4.Main PCB

UPFR-K

3.Relay PCB

RYDR-X

5.AC input, AC output terminal

Page Number:

1-9

Converter &

Inverter Unit

1.LCD touch panel

monitor display

Cooling fan

2.Display PCB

DPAU-72

Battery

7.Maintenance bypass transfer switch

52CS

6.Grounding bar

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

FIGURE 1.5b UPS Parts Location(30kVA)

UPS module

FRONT VIEW

4.Main PCB

UPFR-K

Cooling fan

7.Maintenance bypass transfer switch

SWM

3.Relay PCB

RYDR-X

5.AC input, AC output terminal

Converter &

Inverter Unit

6.Grounding bar

Page Number:

1-10

1.LCD touch panel

monitor display

2.Display PCB

DPAU-72

Battery

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

FIGURE 1.5c UPS Parts Location(40,50kVA)

Page Number:

1-11

4.Main PCB

UPFR-K

Cooling fan

3.Relay PCB

RYDR-X

5.AC input, AC output terminal

Converter &

Inverter Unit

1.LCD touch pane monitor display

2.Display PCB

DPAU-72

7.Maintenance bypass transfer switch SWM

UPS module

FRONT VIEW

6.Grounding bar

FIGURE 1.6 Display PCB DPAU-72

FIGURE 1.7 External I/F PCB RYDR-X

9.External contact

signal terminal block

8.SW5

TEST switch

DPAU-57

DPAU-72

RYDR-X

10.CN62 RS232C

D-sub Connector

11.CN64 RS232C

D-sub Connector

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-12

FIGURE 1.8 Main control PCB UPFR-K

8.SW11

TEST switch

12.SW13

BOOT switch

13.SW14

RESET switch

UPFR-K

Description of UPS parts, referred to in Figure 1.5:

1. LCD Touch Panel Monitor Display

The Liquid Crystal Display (LCD) Touch Panel Monitor Display indicates power flow, measured values and fault and error messages via user selectable display screens.

2. Display PCB DPAU-72

Switches on DPAU-72 board : FOR SERVICE PERSONNEL ONLY (Figure 1.6):

- (8) SW5 (TEST switch)

3. Relay PCB RYDR-X board

Signal I/F on RYDR-X board : (Figure 1.7):

- (9) External contact signal terminal block

- (10) CN62 (RS232C communication connector)

- (11) CN64 (RS232C communication connector)

4. Main PCB UPFR-K

Switches on UPFR-K board : FOR SERVICE PERSONNEL ONLY (Figure 1.8):

- (8) SW11 (TEST switch)

- (12) SW13 (BOOT switch).

- (13) SW14 (RESET switch)

5. AC input, AC output terminal

Refer to Figure 3.3 for details

6. Grounding bar (E)

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-13

7. Maintenance Bypass Switch (52CS/SWM) (FOR SERVICE PERSONNEL ONLY) This switch is used to transfer the load from inverter power to external power for maintenance purposes.

Do not operate it under normal operation.

8. "Test mode" switch (FOR SERVICE PERSONNEL ONLY)

This switch changes system operation to the test-mode. This switch is mounted on Display

PCB and Main PCB. (This switch should not be operated by personnel other than an

Authorized Service Engineer).

9. External contact signal terminal block

Terminal block to connect contact signal input/output lines to and from external dry contacts.

Refer to FIGURE 2.3 for details.

10. RS232C connector (CN62)

Refer to Figure 2.6 for detail.

11. RS232C connector (CN64)

12. "BOOT" switch (FOR SERVICE PERSONNEL ONLY)

This switch boots the processor on the main control circuit board following alarm conditions.

(Do not operate this switch while inverter and converter are in operation).

13. "Reset" switch (FOR SERVICE PERSONNEL ONLY)

This switch resets errors resulting from alarm conditions. (Do not operate this switch while inverter and converter are in operation).

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-14

1.4 Specifications

The UPS name plate displays the rated kVA as well as nominal voltages and currents. The name plate is located on the interior side of the UPS front door.

TABLE 1.1 Power Specifications

Rated output

Power

7.5kVA/6kW

10kVA/8kW

15kVA/12kW

20kVA/16kW

30kVA/24kW

40kVA/32kW

50kVA/40kW

TABLE 1.2 UPS Module Information

Input voltage

3 phase / 4 wire

208

208

208

208

208

208

208

Output voltage

3 phase / 3 or 4 wire

208

208

208

208

208

208

208

UPS

(kVA)

CABLE

ENTRY

WIDTH

(in/mm)

DEPTH

(in/mm)

HEIGHT

(in/mm)

WEIGHT

(lb./kg)

HEAT LOSS

@ 208V

(kBTU/h)

7.5 BOTTOM 17.7 / 450 31.5 / 800 43.3 / 1100 562 / 255* 3.2

10

15

20

30

BOTTOM

BOTTOM

BOTTOM

BOTTOM

17.7 / 450

17.7 / 450

17.7 / 450

23.6 / 600

31.5 / 800

31.5 / 800

31.5 / 800

31.5 / 800

43.3 / 1100

43.3 / 1100

43.3 / 1100

59.0 / 1500

562 / 255* 3.9

816 / 370* 5.1

816 / 370* 6.5

1235 / 560* 8.8

40 BOTTOM 27.6 / 700 31.5 / 800 59.0 / 1500 1082 / 490

50 BOTTOM 27.6 / 700 31.5 / 800 59.0 / 1500 1082 / 490

*:7.5-30kVA Including batteries

11.9

14.6

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

TABLE 1.3 Detail of Specifications

Rated Output kVA 7.5 10 15 20

Rated Output kW

Configuration

Voltage

6 8 12 16

AC INPUT CHARACTERISTICS

3 phase, 4 wire

120/208 V +15% ~ -25%

30

24

Page Number:

1-15

40

32

50

40

Reflected Current THD 4% typ. at 100% load; 7% typ. at 50% load

BATTERY

Type VRLA

8min. 5min. 11min. 7min. 5min. Ride Through

(at 100% load)

Nominal Voltage 360 Vdc

Minimum Voltage

Number of Cells

Configuration

300 Vdc

180

AC OUTPUT

3 phase, 3 or 4 wire

Voltage Stability

+/-

1%

Frequency Stability

Power Factor

Power Factor range

Voltage THD

Transient Response

+/-

0.01% in free running mode

0.8 nominal

0.8 ~ 1.0 lagging (within output kW rating)

2% typical THD at 100% Linear Load

4% typical THD at 100% non-linear load

+/-

3% typical at 100% load step

+/1% typical at loss/return of AC power

+/-

3% typical at load transfer to/from static bypass

Transient Recovery

Voltage Unbalance

Phase Displacement

16.7 ms

2% typical at 100% unbalanced load

1deg. typical at 100% load

Inverter Overload

System Overload

150% for 1 minute

150% for 1 minute, 1000% for 1 cycle (with bypass available)

Bypass Overload 150% for 1 minute, 1000% for 1 cycle

Crest Factor Capabilities 3:1

ENVIRONMENTAL

Operating Temperature 32゚F ~ 104゚F (0゚C ~ 40゚C).

Recommended 59゚F ~ 77゚F (15゚C ~ 25゚C)

Relative Humidity 5% ~ 95% Non Condensing

Altitude

Location

0 ~ 5000 feet No De-rating

Temperature-controlled, indoor area free of conductive contaminants

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-16

TABLE 1.4 Rating of Contactors and Fuses

Component Description Component Rating @ 208V,3 phase, 60 Hz

CB1

CB2

CB3

UPS Rating (kVA)

AC Input Contactor

DC Input Contactor

Static Bypass Input

Contactor

7.5

10

60A

60A

15 20 30

100A

100A

40

150A

150A

50

150A

150A

150A

150A

52C AC Output Contactor

FIU-W AC Input Fuse

FBP,FBN Battery Input Fuse

FOU-W AC Output Fuse

(OPTION)

FSU-W

Static Bypass Input

Fuse

F1,F2,F3 UPER-Y/UPFR-K

F1 CABR-JA

140A/660V 180A/600V 280A/660V 280A/660V

140A/660V 180A/600V 280A/660V 280A/660V

140A/660V 180A/600V 280A/660V

200A/660V 280A/660V 280A/660V

6.3A/250V 6.3A/250V 6.3A/250V 6.3A/250V

12A/600V

MITSUBISHI ELECTRIC 2033C SERIES UPS

4

2

3

5

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

2.0 OPERATOR CONTROLS AND INDICATORS

The 2033C Series operator controls and indicators are located as follows:

Maintenance bypass switch and contactors : Inside the module

UPS status indicators : Door exterior

Page Number:

2-1

FIGURE 2.1 Operation/Display Panel (Front panel)

MITSUBISHI

INV OP.

BAT OP.

BYP OP.

FAILURE

START STOP SILENCE CLEAR

2033C SERIES UPS

6

7

2.1 LCD Touch Panel Monitor Display and Keypad

8 9

EPO

10

MBP

1) LCD Touch Panel Monitor Display

The Liquid Crystal Display (LCD) Touch panel Monitor Display indicates power flow, measured values and fault and error messages via user selectable display screens.

MAIN MENU SCREEN

The MAIN MENU Screen is shown in Figure 2.2. The MAIN MENU screen displays the system Mimic diagram, and includes four MEASUREMENT Screen Touch icons: AC Input,

Bypass Input, Battery, AC Output and one FAULT DISPLAY Screen Touch Icon: Fault/Alarm

History. Date and Time are displayed at the bottom of the display.

1

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-2

FIGURE 2.2 MAIN MENU Screen

MEASUREMENT SCREENS

Pressing the MEASUREMENT Screen Touch icons on the MAIN MENU Screen will display each specific MEASUREMENT Screen. Each MEASUREMENT Screen displays specific system measurement data as shown in Figure 2.3.

FIGURE 2.3 MEASUREMENT Screens

AC Input Measurement Screen

Input line to neutral rms voltage (A-N, B-N, C-N)

Input Current

Input Real KW Power

Input Frequency

AC Output Measurement Screen

Output line to neutral rms voltage (A-N, B-N, C-N)

Output rms current of each phase

Output Real KW Power

Output Frequency

MAIN MENU Screen

Battery Measurement Screen

DC Bus Voltage

Battery Charge/Discharge Current

Each MEASUREMENT Screen includes a MAIN Menu Screen Touch Icon. On pressing this

MAIN Touch icon, the display returns to the MAIN MENU Screen.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-3

FAULT DISPLAY SCREEN

Pressing the FAULT DISPLAY Screen Touch icon on the MAIN MENU Screen will display the

Fault display screen. Fault/Alarm data including fault codes and occurrence/restore dates as well as fault/alarm History can be displayed as shown in Figure 2.4. The FAULT DISPLAY

Touch icon will flash on the MAIN MENU Screen if there are Fault/Alarms that have not been restored. Pressing the DETAIL DISPLAY Touch icon will display faults in more detail. Pressing the Rest. Item Delete Touch icon will delete all fault/alarms that are selected by the Cursor

Touch icons and have been restored. On Pressing the Main Touch Icon, the display returns to the MAIN MENU Screen.

FIGURE 2.4 FAULT DISPLAY Screen

MAIN MENU Screen

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-4

DATE & CLOCK SETUP SCREEN

Pressing the lower right of the MAIN MENU Screen will display the date & clock setup screen.

On Pressing the END Touch Icon, the display returns to the MAIN MENU Screen.

FIGURE 2.5 DATE & CLOCK SETUP Screens

SET CLOCK】

Pressing the each point can set the date or clock.

5 6 7 8 9 ▲ CLR

0 1 2 3 4 ▼ ENT

NOTE: The display measurement values shown for LCD Monitor Displays are samples only.

2) Load on inverter [INV OP.] (green)

Illuminated when power is supplied from inverter to the critical load.

3) Battery operation [BAT OP.] (yellow)

Illuminated when the battery is operating following an AC power failure.

4) Load on bypass [BYP OP.] (yellow)

Illuminated when power is supplied to load devices by static bypass.

5) UPS failure [FAILURE] (red)

Illuminated when UPS is in fault mode.

6) Inverter start [START] (green)

Inverter start button.

When pressed, the load will transfer from the static bypass line to the inverter.

7) Inverter stop [STOP] (gray)

Inverter stop button. When pressed, the inverter can be stopped.

The load will transfer from the inverter to the static bypass line.

8) Alarm Silence [SILENCE] (gray)

Audible alarm is silenced when this button is pressed.

9) Clear [CLEAR] (gray)

Clears errors in UPS system.

10)Emergency Power Off [EPO] (red)

Shuts down UPS when pressed. Load is dropped.

11)Load on maintenance bypass [MBP] (red)

Illuminated when power is supplied to load devices by maintenance bypass.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

2.2 External Signal Terminal Block

Page Number:

2-5

The UPS is equipped with a series of input/output terminals for the external annunciation of alarms and the remote access of certain UPS functions. Layout of terminals is shown in Figure

2.6, with a functional description of the input/output port presented:

FIGURE 2.6 External Signal Terminal Block (NEC Class2)

TB

11

12

13

14

7

8

9

10

15

16

17

18

1

2

3

4

5

6

LOAD ON INVERTER

LOAD ON BYPASS

BATTERY OPERATION

CONVERTER OPERATION

BATTERY LOW VOLTAGE

OVERLOAD

EMERGENCY STOP (Optional)

(User supplied dry contact)

BATTERY TEMP. HIGH (Optional)

- For external battery cabinet.

SUMMARY ALARM

(User supplied sensor

and dry contact)

UPS

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-6

A) Output Contacts (for external alarm annunciation)

Output contacts consist of form “A” dry type contacts. The rated capacity of all output contacts is 120Vac/0.5Aac or 30Vdc/1Adc. All dry contacts must be operated at their rated values or lower. Figure 2.7 illustrates a typical installation. The external relay can also be a lamp, LED, or computer, etc.

FIGURE 2.7 Control Wiring for External Contacts

UPS Cabinet

Terminal

Relay

Contact

Details of output alarm contacts :

Terminal

External to UPS

Cabinet

Relay

Coil

Power

Source

User supplied

Terminals 5 to 6 “Summary Alarm” contact

Activated when a fault alarm occurs.

Terminals 7 to 8 “Load on Inverter” contact

Activated when the power is supplied by the inverter.

Terminals 9 to 10 “Load on Bypass” contact

Activated when the power is supplied by the static bypass input.

Terminals 11 to 12 “Battery Operation” contact

Activated when the battery is operating following an AC power failure.

Terminals 13 to 14 “Converter Operation” contact

Activated when the converter is operating.

Terminals 15 to 16 “Battery Low Voltage” contact

Activated when battery voltage drops below discharge end voltage level during inverter operation (i.e. During AC failure conditions).

Terminals 17 to 18 “Overload” contact

Activated when a system overload occurs.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

B) Input Contacts (for remote access of UPS)

Page Number:

2-7

External contacts are provided by the user of the UPS system. The terminal voltage at the

UPS is 24Vdc. External dry contacts are to be provided accordingly.

NOTE: Do not apply voltages to remote access input terminals. Damage to UPS may result.

Refer to Figure 2.8 for a typical wiring configuration. Although this figure shows the emergency stop configuration, the same wiring arrangement is used for battery temperature high. See below for terminal connection details.

FIGURE 2.8 Remote "Stop" Contact Connections

UPS Cabinet External to UPS

Cabinet

Relay

Coil

24 VDC

Relay Coil current : 8.3mA

2

Details of input contacts for remote access :

User supplied

Terminals 1 to 2 “Emergency Stop” contact input

Used to perform a remote UPS emergency power off (EPO).

The load will be dropped.

Terminals 3 to 4 “Battery Temp. High” contact input

Emergency

Use Momentary Switches

Stop

Input fed by a thermocouple that monitors battery temperature. The converter float voltage level is reduced for battery over-temperature conditions. The external thermocouple will be user supplied

NOTE : In all cases, a switch having a protective cover is recommended in order to reduce

possibility of accidental operation.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

2.3 External communication connector

Page Number:

2-8

This is an RS232C port for “DiamondLink”* monitoring software. The layout of the connector is shown in Figure 2.9.

FIGURE 2.9 External communication connector (NEC Class2)

CN62

D-SUB 9Pin (male)

Pin 1. : Not used

Pin 2. RXD : Receive data

1

2

3

4

5

8

9

6

7

Pin 3. TXD : Transmit data

Pin 4. DTR : Always high level

Pin 5. GND

Pin 6.

: Signal ground

: Not used

Pin 7. RTS : Always high level

Pin 8. : Not used

Pin 9. : Not used

RYDR-O/ RYDR-X

* Consult MITSUBISHI ELECTRIC AUTOMATION, INC. for detail on “Diamond Link” monitoring software and its capabilities.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-1

3.0 INSTALLATION AND OPERATION

3.1 Transportation and Installation

TABLE 3.1 How to transport and install the system

Transportation

Transport unit with forklift.

Installation

Pull out the UPS cabinet as shown in Figure 3.1

Fix the UPS unit in place using the four (4) leveling feet.

Note : Do not transport in a horizontal position. Cabinets should be maintained upright within +/-

15° of the vertical during handling.

3.2 Handling

The UPS is shipped in export packaging. Remove the UPS from the package only when it is ready for installation.

FIGURE 3.1 Handling

Leveling feet

1

RAMP

Roof of the package during shipping

2

3

4

5

Note : The figure 3.1 export packaging is for 7.5kVA through 20kVA UPS only.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

3.3 Installation Procedure

A) Note the load tolerance of the floor

Refer to Table 3.2 for list of UPS weights:

TABLE 3.2 List of UPS weights

UPS Capacity (kVA) 7.5 10 15 20

Weight (lb.) 562 562 816 816

30

1235

Page Number:

3-2

40 50

1082 1082

Note: 40kVA and 50kVA UPS have batteries external to module cabinet

Please refer to the remote battery supply installation manual.

B) Minimum clearance required for ventilation

Right side

Left side

Back side

1.0" (25 mm) (not required when sidecars are used)

1.0" (25 mm) (not required when sidecars are used)

7.8" (200 mm)

Top side 39.4" (1000 mm)

C) Space requirement for routine maintenance

Allow for the following space at the time of installation.

Front

Sides

39.4" (1000 mm)

1.0" (25 mm)

Rear

D) Battery

7.8" (200 mm)

Please refer to the following when installing and maintaining batteries:

1. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.

2. When installing or replacing batteries, install or replace with the same number and type per Table 3.3

TABLE 3.3 Type and number of battery

Type Manufacturer Number

7.5kVA,10kVA PM12-7.2 Power Battery Inc.

NP7-12 Yuasa Corp.

15kVA,20kVA PM12-18 Power Battery Inc.

NP18-12B Yuasa Corp.

30

30

30

NP18-12B

NP18-12BFR

40kVA,50kVA

Yuasa Corp.

Yuasa Corp.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-3

Please refer to the remote battery supply installation manual.

3. CAUTION - Do not dispose of battery or batteries in a fire. The battery may explode.

4. CAUTION - Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.

5. CAUTION - A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:

- Remove watches, rings, or other metal objects.

-

Use tools with insulated handles.

- Wear rubber gloves and boots.

-

Do not lay tools or metal parts on top of batteries.

- Disconnect charging source prior to connecting or disconnecting battery terminals.

3.4 Procedure for Cable Connections (Refer to Table 3.4 for cable sizes.)

I. Confirm the capacity of the UPS being installed. Identify the input/output power terminal blocks as shown in the appropriate Figure 3.2 or Figure 3.3-Figure 3.5.

II. Connect the grounding conductor from the input service entrance to the UPS ground bar.

III. Confirm that an external input circuit breaker sized to protect both the converter input and the bypass lines is installed. Consult equipment nameplate for current ratings. Connect the AC power source cables from the input service entrance to the UPS’ INPUT power terminals identified as A, B, C and N in Figure 3.3-Figure 3.5. Input cables must be sized for an ampere rating larger than the maximum current capacity of the UPS.

IV. Refer to Table 3.4 for recommended cable sizes. Referring to Figure 3.3-Figure 3.5, connect UPS’ OUTPUT load terminals A, B, C and N to load distribution panel.

V. Connect external signal terminal block as needed. Refer to section 2.2 and Figure 2.3 for functional description. 12 AWG, or less, shielded conductor is recommended.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-4

NOTES:

1. Confirm that all UPS internal contactors (breakers) "CB1", "CB2", and

"CB3" are open before energizing UPS.

2. UPS power terminals are supplied with stud type fittings. It is

recommended that compression lugs be used to fasten all input/output power cables. Refer to Table 3.5 for recommended compression lugs and

appropriate crimping tool

Table 3.4 Recommended Cable Size and Torque Requirements

UPS

Capacity (kVA)

Input Side * 1

Cable *

2

Torque

Size (in. lbs)

Output Side * 1

Cable *

2

Torque

Size (in. lbs)

7.5kVA (208V) 8 AWG or larger 180 in. lbs 8 AWG or larger 180 in. lbs

10kVA (208V) 8 AWG or larger 180 in. lbs 8 AWG or larger 180 in. lbs

15kVA (208V) 8 AWG or larger 180 in. lbs 8 AWG or larger 180 in. lbs

20kVA (208V) 6 AWG or larger 180 in. lbs 6 AWG or larger 180 in. lbs

30kVA (208V) 2 AWG or larger 180 in. lbs 2 AWG or larger 180 in. lbs

40kVA (208V) 2/0 AWG or larger 180 in. lbs 2/0 AWG or larger 180 in. lbs

50kVA (208V) 2/0 AWG or larger 180 in. lbs 2/0 AWG or larger 180 in. lbs

*1 - Voltage drop across power cables not to exceed 3% of nominal source voltage.

*2 - Allowable ampere ratings based on 90゚C insulation at an ambient temperature of 30゚C.

No more than 3 conductors in a raceway without de-rating. Copper conductors assumed.

TABLE 3.5 Crimp Type Compression Lug

WIRE

SIZE

WIRE

STRAND

RECOMMENDATION CRIMP TOOL REQUIRED

BURNDY TYPE Y35 OR Y46

(CODE) CLASS VENDOR CAT. NO. COLOR KEY DIE INDEX

6

4

B

B

BURNDY

BURNDY

YA6C-L3

YA4C-L3

BLUE

GRAY

7 / 374

8 / 346

NOTE: When using crimp type lugs, the lugs should be crimped to the

specifications given in the manufacturer's instructions for both crimp tool

and lug.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Fig.3.2 UPS Terminal Designation

AC input

Terminals:

INPUT

A,B,C,N

CB1

FO

BATTERY

CB3

CONVERTER

CB2

FB

Static Transfer

Switch

INVERTER

FI

40kVA, 50kVA:

External Battery

52C

Page Number:

3-5

52CS

52CS(7.5-20kVA)

52MB&52L(30-50kVA)

UPS Module

Output

Terminals:

OUTPUT

A,B,C,N

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

FIGURE 3.3 Input/Output Power Terminals (7.5kvA - 20kVA)

Battery

Battery

RYDR-X

Control printed circuit boards

Inverter and Converter

A B C N A B C N

(INPUT) (OUTPUT)

Battery

Battery

NORMAL

Fan

TRANSFER

52CS

BYPASS

Page Number:

3-6

Input/Output Power Terminal Designation

ALL POWER TERMINALS USE 1/4” (6 MM) DIAMETER BOLTS

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

FIGURE 3.4 Input/Output Power Terminals (30kVA)

Page Number:

3-7

Cooling fan

Control printed circuit boards

Converter & Inverter Unit

.

NORMAL

TRANSFER

BYPASS

MBS

RYDR-X

N P

(DC INPUT)

A B C N A B C N

(INPUT) (OUTPUT)

Grounding bar

Battery

Battery

Battery

DC Input Power Terminal

HOLE DIAMETER: 0.28” (7 MM)

Battery

AC Input/Output Power Terminal Designation

HOLE DIAMETER: 0.36” (9 MM)

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

FIGURE 3.5 Input/Output Power Terminals (40kvA - 50kVA)

Cooling fan

RYDR-X

Control printed circuit boards

Converter & Inverter Unit

TRANSFER

NORMAL

MBS

BYPASS

A B C N A B C N N P

(AC INPUT) (AC OUTPUT) (DC INPUT)

Grounding bar

Page Number:

3-8

Input/Output Power Terminal Designation

HOLE DIAMETER: 0.47” (12 MM)

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-9

3.5 Operating Procedures

A) UPS Start-up Procedure

1. Close External Input Circuit Breaker (User supplied. Refer to warning 2).

2. The “BYP.OP.” illuminates and power is supplied to the critical load from the static bypass line automatically.

3. Within ten (10) seconds, the “INV.OP.” LED flashes and the Inverter starts. The UPS will automatically transfer the load from the static bypass line to the inverter and the “INV.OP.” light illuminates.

NOTE : If code “81” is indicated on the FAULT DISPLAY Screen, please check the

position of EPO button. If EPO button is in the ON position, press the button to clear EPO as shown in figure 3.6. Press the “CLEAR” button. If code “99” is indicated on the FAULT DISPLAY Screen, press “CLEAR” button again.

FIGURE 3.6 EPO button

EPO “On” position Normal position

B) UPS Shutdown Procedure

1. If a total UPS module (inverter and converter) shutdown is required, press the "STOP" button on the front panel. Within 3 seconds the “BYP.OP.” LED will illuminate and the

UPS will transfer the load to the static bypass line.

WARNING : Verify the load is OFF if the next step is to be performed .

NOTE : Power to the critical load is supplied through the static bypass line.

Power to the critical load will be lost after execution of the next step. The load will drop.

2. If turning off all power to the critical load is desired, open the AC Input Circuit Breaker

(User supplied.).

CAUTION : In bypass mode, all UPS power terminals are still live. Lethal voltages

are present. De-energize all external sources of AC and DC power

before handling UPS.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-10

C) EPO (Emergency Power Off) Procedure

If an all power supply shutdown is required in an emergency situation, press the "EPO" button on the front panel. The UPS will be shutdown and no power is supplied to the load.

WARNING : With EPO operation, although all output power from the UPS is

shutdown, it is necessary to manually open the input circuit breaker

(user supplied), to remove the input power to the UPS.

3.6 Maintenance bypass set-up procedures

A) Transfer of load from inverter to maintenance bypass

1. On the front panel, press the "STOP" button. The “BYP.OP.” LED illuminates within 3 seconds.

2. After confirming that the “BYP.OP.” LED is illuminated, Rotate the MBS(52CS/SWM) clockwise to the “TRANSFER” position (Do not rotate 52CS/SWM if the “BYP.OP.” LED is

NOT illuminated).

3. After 3 seconds, rotate 52CS/SWM clockwise to the “BYPASS” position.

4. Transfer complete. Load is now powered from the external source. UPS can be shutdown.

B) Transfer of load from maintenance bypass to inverter

1. Rotate 52CS/SWM counterclockwise from the “BYPASS” position to the “TRANSFER” position, wait 5 seconds.

2. On the UPS, confirm the “BYP.OP.” LED is illuminated. If not, press the “STOP” button.

3. Rotate 52CS/SWM counterclockwise to the “NORMAL” position.

4. On the UPS, press the “START” button. The “INV.OP.” LED should illuminate.

5. Transfer complete. Load now powered by the inverter.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

4.0 RESPONSE TO UPS FAILURE

UPS FAULT

Annunciator Silence

Recording of Fault

Primary Action

Information to Service Center

Page Number:

4-1

Depress “SILENCE” button on the front panel.

Refer to the list of fault codes for a description of the error. See section 6. For fault codes

Take necessary action per the list of fault codes in section 6 of this manual.

When faults occur, contact the Authorized Mitsubishi

Service Representative or call Mitsubishi at

1-800-887-7830.

Note :

The error code indicated on the FAULT DISPLAY Screen of the LCD Display at the time of UPS alarm condition is very important. In order to minimize repair time, please include this information along with the operation status and load status, on all

correspondence with Mitsubishi’s field service group.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

5-1

5.0 PARTS REPLACEMENT

Contact Mitsubishi or its Authorized Service Center on all issues regarding the replacement of parts.

A) Battery

Battery lifetime may vary according to the frequency of use and the average ambient operating temperature. Battery end of life is defined as the state of charge resulting in an ampere-hour capacity less than, or equal to, 80% of nominal capacity. Replace battery if capacity is within this percentage.

B) UPS Component Parts

Contact Mitsubishi or its Authorized Service Center for a complete parts replacement schedule. Recommended replacement time interval varies with operating environment.

Contact Mitsubishi or its Authorized Service Center for specific application recommendations.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

6-1

6.0 FAULT CODES

This section covers the fault codes, their description and required action.

At time of error :

A) Verify and record the occurrence of the alarm. Note fault code on the FAULT DISPLAY

Screen of the LCD Display .

Contact Mitsubishi Electric Automation, Inc. at 1-800-887-7830.

B) If the External AC Input Circuit Breaker (MCCB) is in the trip state, depress the toggle to reset the breaker before re-closing.

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

20033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Failure Code List

21

22

23

24

25

16

17

18

19

12

13

14

15

00

01

10

11

32

33

34

35

26

27

28

31

36

37

41

LCD Failure Code Status

Test mode (Pulse check)

Maintenance mode

Battery circuit abnormal

Battery test

Battery circuit abnormal

Battery depleted warning

Battery depleted

Battery temperature abnormal

Battery temperature abnormal

Battery charge voltage abnormal

DC voltage abnormal

Battery depleted (Converter overload)

AC input voltage out of range

AC input phase rotation error

Converter overload

Converter over current

Converter abnormal (DCOV)

Converter abnormal (DCUV)

Converter abnormal

Converter abnormal at pre-charge

Inverter voltage abnormal

Inverter abnormal (VLOV)

Inverter abnormal (VLUV)

Inverter abnormal (OC)

Inverter abnormal

52C abnormal

52C abnormal

Bypass voltage out of range

Guidance

-

-

Call service engineer

-

Call service engineer

-

-

Check battery

Check battery

Call service engineer

Call service engineer

Check AC input voltage

Check AC input voltage

Check AC input voltage

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Check bypass input

Page Number:

6-2

Note 3

Failure LED

Flicker

Flicker

Flicker

Lit up

-

Flicker

Flicker

Flicker

Lit up

-

-

Flicker

-

Flicker

Flicker

Lit up

Flicker

Lit up

Lit up

Lit up

Flicker

Lit up

Lit up

Lit up

Lit up

Flicker

Flicker

Flicker

[2]

[2]

[2]

[2]

[2]

[2]

[2]

[1]

[1]

[1]

-

[1]

[2]

[1]

[1]

[1]

[1]

[2]

[2]

[1]

[1]

[1]

[1]

-

[1]

[1]

Note 1

Buzzer

[1]

Note 2

External sendout contact

-

[1] -

Minor

-

Minor

Alarm

Alarm

Alarm

Minor

Alarm

Minor

Major

Alarm

Minor

Alarm

Minor

Major

Major

Major

Major

Minor

Major

Major

Major

Major

Minor

Minor

Alarm

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

LCD Failure Code

81

82

96

97

72

73

74

76

98

99

57

58

59

71

53

54

55

56

Status

Transfer circuit abnormal

Control circuit error

Control circuit error

Control circuit error

Control circuit error

Control circuit error

Control circuit error

Overload kW overload

Instantaneous overload

Load abnormal

Overload

Emergency stop activated

Fin temperature abnormal

Control circuit error

Restart after battery depleted

Control circuit error

Start up

20033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Guidance

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Call service engineer

Reduce load

Reduce load

Reduce load

Check load

Reduce load

-

Call service engineer

Call service engineer

-

Call service engineer

Press Clear button

Page Number:

6-3

[1]

[2]

[2]

-

[1]

[1]

[1]

[1]

[2]

-

[2]

[2]

[1]

[2]

[1]

Note 1

Buzzer

[1]

Note 2

External sendout contact

Minor

[2]

[2]

Major

Major

Major

Major

Minor

Major

Alarm

Alarm

Alarm

Alarm

Alarm

Alarm

Major

Major

Alarm

Major

Alarm

Note 3

Failure LED

Flicker

Flicker

Flicker

Flicker

Flicker

Lit up

Lit up

-

Lit up

-

Flicker

Lit up

Lit up

Lit up

Lit up

Flicker

Lit up

Flicker

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

6-4

(Note 1)

(Note 2)

Audible annunciator: [1] intermittent sound, [2] continuous sound.

- "Major" is defined as a major failure. Load transferred from inverter to the static bypass line;

- "Minor" is defined as a minor failure. UPS continues to operate normally, but cause of alarm must be identified;

-

“Over" is defined as an overload condition. Load will transfer from inverter to the static bypass line and may or may not return to the inverter. Return to inverter will occur only if overload corrects itself and output load is within rating of UPS. (Note: Inverter may need to be restarted manually subsequent to an output bolted fault.)

(Note 3)

Indicates one of two possible LED illumination patterns - continuously on (lit) or intermittent (flicker).

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

7-1

7.0 Warranty & Out of warranty Service

The Mitsubishi Electric UPS Systems Group Service Department has many Authorized Service Centers place strategically throughout the US, Canada and Latin America. For both in warranty and out of warranty service, please contact Mitsubishi Electric Automation, Inc. at (847) 478-2500. To register your UPS for warranty purposes, please complete the warranty registration form and fax it to the Mitsubishi Electric UPS Systems

Group, Service Department fax line shown on the registration form. (Next page)

For warranty purposes, it is essential that any and all service work that may be required on your Mitsubishi brand UPS equipment is performed by a Mitsubishi Electric Authorized Service Center. The use of nonauthorized service providers may void your warranty.

Mitsubishi Electric Automation Inc,

UPS Systems Group Service Department

500 Corporate Woods Parkway,

Vernon Hills, Illinois 60061, USA

Phone: (847) 478-2500

Fax: (847) 478-2290

MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI

ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

7-2

Mitsubishi Electric Automation, Inc.

UNINTERRUPTIBLE POWER SUPPLIES

500 Corporate Woods Parkway, Vernon Hills, IL 60061 Phone: (847) 478-2643, Fax: (847) 478-2290

UPS Warranty Registration

__ Register UPS for Warranty __ Address Change

To validate the Warranty on your UPS this form must be filled out completely by

Customer and returned.

Your Name:

CUSTOMER INFORMATION

Job Title:

Company Name:

Division / Department:

Address:

City:

Country: Province:

Ext: Business Phone:

E-Mail:

@

UPS Model #: Capacity (kVA):

Fax:

Internet Address:

UPS Serial #:

Start-Up Date:

/ /

Authorized Mitsubishi Service Company (if known):

Signature:

Which ONE of These Best Describes Your Organization’s

Date:

/ /

Number of Employees at This Location is:

{Energy Producer}

__ Utility

__ Alternate Energy

{Manufacturing Co.}

__ Education/Univ. Service

{Service}

__ Consulting

__ Engineering

__ 1 – 19

__ 20 – 49

__ 50 – 99

__ 100 - 249

__ 250 - 499

__ 500 - 999

__Yes __ No

__1000 or more

__ OEM

__ Process

__ Outsourcing Overall how was Start-Up performed:

__ Financial/Legal/Insurance __Unsatisfactory __ Satisfactory __ Exceeded

{Expectations}

__ Consumer Goods

__ Electronics

{Government}

__ Military

__ Power Quality Equipment __ Municipals

Would you like to receive future product updates and

news?

__ Commercial Business __ Federal/State/Local

Communications

Distributors/Reps

__ Internet __ Other __________________

After Start-Up has been done Fax completed Form to:

(847) 478-2290

MITSUBISHI ELECTRIC 2033C SERIES UPS

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement