INSTALLATION

INSTRUCTIONS

STANDARD SERIES

36" Wood Burning Fireplaces

P/N 700,040M REV. A 02/2008

MODELS

BR-36

BRI-36

BR-36-2

BC-36

BCI-36

BC-36-2

This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system. Please read and understand these instructions before beginning your installation.

Do not alter or modify the fireplace or its components under any circumstances. Any modification or alteration of the fireplace system, including but not limited to the fireplace, chimney components and accessories, may void the warranty, listings and approvals of this system and could result in an unsafe and potentially dangerous installation.

IMPORTANT! TO ASSURE PROPER ALIGNMENT OF GLASS DOORS:

INSTALL THIS FIREPLACE IN A SQUARE AND PLUMB CONDITION,

USING SHIMS AS NECESSARY AT SIDES AND/OR BOTTOM.

RETAIN THESE INSTRUCTIONS

FOR FUTURE REFERENCE

OTL Report No. 116-F-43-2

US

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

1

2

TABLE OF CONTENTS

Safety Rules .................................... page 2

Tools and Building Supplies ............ page 2

Precautions ..................................... page 3

Introduction ..................................... page 3

Clearances/Height Requirements ..... page 3

Chimney System ............................. page 3

Assembly Outline ............................. page 4

Location of Fireplace ....................... page 4

Assembly Steps ............................... page 5

Preinstallation Notes ........................ page 5

Clearances ....................................... page 5

Installing the Fireplace ..................... page 5

Fireplace Specifications .................. page 6

Framing Specifications .................... page 7

Installing the Chimney System ........ page 8

30

°

Offset through Floor/Ceiling ...... page 9

Ten Foot Rule Summary .................. page 11

Multiple Terminations ...................... page 11

Chimney Component Calculations ... page 11

Special Offset Instructions ............... page 11

Vertical Elevation Chart ................... page 12

Offset Calculations ........................... page 12

Offset Elevation Chart ..................... page 13

Installing Offsets .............................. page 14

Optional Equipment Considerations . page 14

Forced Air Kits ................................. page 14

Combustion Air Kits ........................ page 15

Gas Line Connection ........................ page 15

Vent Free Appliances ....................... page 15

Glass Doors ..................................... page 16

Cold Climate Insulation .................... page 16

Fireplace Finishes ............................ page 16

Mantels and Trim ............................. page 16

Hearth Extensions/Wall Shields ....... page 16

Finish Requirements ........................ page 18

Installation Components .................. page 19

This manual is part of a set of two supporting this product. Refer to manual 725,041M for

Care and Operation instructions.

IMPORTANT: PLEASE READ AND

UNDERSTAND THESE RULES TO

FOLLOW FOR SAFETY.

1. Before starting your fireplace installation, read these installation instructions carefully to be sure you understand them completely and in entirety. Failure to follow them could cause a fireplace malfunction resulting in serious injury and/or property damage.

2. Always check your local building codes. The installation must comply with all local, regional, state and national codes and regulations.

3. These fireplaces must be installed with

Security Chimneys FTF8 (8" inside diameter) chimney System only. These systems are intended for use in any application where a traditional masonry type fireplace would apply. The chimney system must always vent to the outside of the building.

4. To ensure a safe fireplace system and to prevent the build-up of soot and creosote, inspect and clean the fireplace and chimney prior to use and periodically during the heating season.

5. Use solid fuel only. DO NOT use artificial wax based logs, chemical chimney cleaners or flame colorants in your fireplace.

6. DO NOT use charcoal or coal under any circumstances.

7. NEVER use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liquids to start or “freshen up” a fire in this fireplace. Keep any flammable liquids a safe distance from the fireplace.

8. NEVER leave children unattended when there is a fire burning in the fireplace.

9. Always keep flue damper open when heat is present in the fireplace.

10. Before servicing, allow the fireplace to cool. Always shut off any electricity or gas to the fireplace while working on it. This will prevent any possible electrical shock or burns.

11. This fireplace is not intended to heat an entire home or be used as a primary heat source. It is designed to ensure homeowner comfort by providing supplemental heat to the room.

12. Always ensure an that adequate supply of replacement combustion air from the outside of the house is accessible to the fire to support normal combustion. Fireplaces consume large volumes of air during the normal combustion process. In the event the home is tightly sealed with modern energy efficient features, the optional combustion air kit may not provide all the air required to support combustion.

The manufacturer is not responsible for any smoking or related problems that may result from the lack of adequate combustion air. It is the responsibility of the builder/contractor to ensure that adequate combustion air has been provided for the fireplace.

13. DO NOT use a fireplace insert or any other products not specified herein by the manufacturer for use with this fireplace. All gas log sets must be operated with the damper clamped open, including unlisted “vent free” log sets.

Listed “vent-free” log sets may be operated with the damper closed.

14. "Smoke free” operation is not warranteed nor are we responsible for inadequate system draft caused by mechanical systems, general construction conditions, inadequate chimney heights, adverse wind conditions and/or unusual environmental factors or conditions beyond our control.

15. Never, under any circumstances, install a fireplace, chimney component or any accessories, that has visible or suspected physical damage as a result of handling or transportation. These items should be inspected by your distributor or qualified factory representative to ensure safe condition. When in doubt, consult your distributor.

16. For additional safety considerations and complete operating instructions, refer to the

Care and Operation Manual provided with the fireplace.

TOOLS AND BUILDING SUPPLIES

NORMALLY REQUIRED

Tools should Include:

Phillips screwdriver

Hammer

Saw and/or sabersaw

Level

Measuring tape

Plumb line

Electric drill and bits

Pliers

Square

Building supplies:

Framing materials

Wall finishing materials

Caulking materials (noncombustible)

Fireplace surround and hearth extension materials (noncombustible)

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

PRECAUTIONS

Note: These fireplace systems are not difficult to install. However, in the interest of safety, it is recommended that the installer be a qualified or certified “tradesman” familiar with commonly accepted fireplace installation and safety techniques as well as prevailing local codes.

The most important areas of concern dealing with the installation of factory-built fireplaces are clearances to combustible materials, proper assembly of component parts, height of the chimney system, the proper use of accessories supplied by the manufacturer and the techniques employed in using finishing materials applied to the wall surrounding the fireplace, hearth extensions and wall shields. Each of these topics will be covered in thorough detail throughout this manual. Please give each your special attention as you progress with your installation.

INTRODUCTION

General Information

These fireplaces are conventional radiant heat fireplaces with standard bar grates, optional outside combustion air kits and optional decorative glass doors.

TYPICAL INSTALLATION

Chimney and

Termination

Outside

Combustion

Air Kit

(Optional)

The "C" models are designed as heat circulating fireplaces and may be fitted with accessory fans.

The BRI and BCI models are fully insulated for installation in colder climates.

WARNING: MODELS THAT HAVE THE

"-2" SUFFIX HAVE NOT BEEN TESTED

WITH AN UNVENTED GAS LOG SET. TO

REDUCE RISK OF FIRE OR INJURY, DO

NOT INSTALL AN UNVENTED GAS LOG

SET INTO THIS FIREPLACE.

Note: Illustrations shown reflect “typical” installations with nominal dimensions and are for design and framing reference only.

Actual installations may vary due to individual design preferences. However, always maintain minimum clearances to combustible materials and do not violate any specific installation requirements.

These fireplaces have been tested and listed by

Omni Test Laboratories (Report No. 116-F-43-

2) to U.L. standard 127. These units are intended for installation in residential homes and other buildings of conventional construction including commercial, not in mobile homes.

These fireplaces have been tested for installation in Canada to ULC-S610. For installations

in Canada, the chimney clearance to combustibles must be 2 inches and the Cold

Climat Kit must be installed.

These fireplace systems are designed for installation in accordance with the National Fire

Protection Standard for chimneys, fireplaces and solid fuel burning appliances; NFPA 211 and in accordance with codes such as the

BOCA Basic/National Codes, the Standard Mechanical Code and the Uniform Building Codes.

WARNING: FAILURE TO USE MANUFAC-

TURE PROVIDED PARTS, VARIATIONS

IN TECHNIQUES AND CONSTRUCTION

MATERIALS OR PRACTICES OTHER THAN

THOSE DESCRIBED IN THIS MANUAL

MAY CREATE A FIRE HAZARD AND VOID

THE LIMITED WARRANTY.

When complete these fireplace systems consists of four basic “sub-systems”:

1. The Fireplace

2. The Chimney and Termination

3. The Optional Glass Doors

4. The Optional Combustion Air Kits

CLEARANCES AND HEIGHT

REQUIREMENTS

The fireplace may be placed on or near normal construction materials*. The combustion air kit, firestop spacer and roof flashing (not chase flashings) may be placed directly on or against normal construction materials.* The chimney

and fireplace outer wrapper require a minimum

1"** air space to combustibles. A combustible mantle may be installed 12" above the opening of the fireplace as per NFPA 211, Section 7-2.3.3

(1992). In Canada, the minimum is 18" above the fireplace opening.

The minimum installed height of the completed fireplace system is 15' 0". The maximum height is 60' 0".

The fireplace and chimney system must be enclosed when installed in or passing through a living area where combustibles or people may come in contact with it. This is important to prevent possible personal injury or fire hazard.

For questions, please call your distributor or the manufacturer. Special restrictions apply to the front and facing of the fireplace and nearby walls (See pages 16, 17 and 18 ).

CHIMNEY SYSTEM

These fireplaces are designed and code listed for use with Security Chimneys FTF8 chimney

System only. Always use Security Chimneys

FTF8 chimney components with these fireplaces. Do not modify or alter these components as this may cause a potential serious hazard and void the Warranty.

*Construction Materials:

• framing materials • paneling

• particle board • flooring

• dry wall

• plywood

• etc.

**Note: 2" clearance to combustibles around chimney components required in Canada.

Radiant Model Shown

Figure 1

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

3

4

Insulate Joists

Same As Ceiling

Draft Stops

Firestop

CTDT

Termination

Chimney Height

The total height of your completed fireplace system from the surface the fireplace rests on to the chimney top must not exceed 60' and must also meet minimum height requirements.

Refer to the minimum system height chart.

Minimum System Height

Security's FTF8 Pipe

Vertical Installation

15' 0"

One Offsets

Two Offsets

15' 0"

25' 0"

LOCATION OF FIREPLACE

Carefully select the proper location for heat circulation, aesthetics, chimney obstructions and clearance to side wall(s). With proper preplanning, a slight adjustment of a few inches can save considerable time and expense later during construction and assembly.

Hearth

Note: Non-

Combustible

Chase

Flashing

Must Be

Used To

Cover

Chase

Opening

Optional

Insulation

In Outside

Walls Of

Chase

8'

Level

Solid

Continuous

Surface

Outside

Base

Insulation

(Thermal Barrier)

Figure 2

WARNING: IF INSULATION IS USED, THE

FIREPLACE MUST NOT BE PLACED DI-

RECTLY AGAINST IT. INSULATION OR

VAPOR BARRIERS, IF USED, MUST FIRST

BE COVERED WITH GYPSUM BOARD,

PLYWOOD, PARTICLE BOARD OR OTHER

MATERIAL TO ASSURE INSULATION AND

VAPOR BARRIERS REMAIN IN PLACE.

WARNING: DO NOT PACK OR FILL RE-

QUIRED AIR SPACES WITH INSULATION

OR OTHER MATERIAL. NO MATERIAL IS

ALLOWED IN THESE AREAS.

Note: Do not insulate the chase cavity with blown or fill type insulation materials.

Note: Local codes may not require firestopping at the ceiling levels for outside chase installations. However, it is recommended for safety and the reduction of heat loss.

Chase Enclosure

A chase is a vertical box-like structure constructed to surround the fireplace and chimney.

Refer to Figure 2 for a typical chase configuration. As with all chimney installations, avoid overhead obstructions such as trees, power lines, etc. A chase should be constructed and insulated just like any outside wall. In a cold climate, we recommend the base of the chase should also be insulated between the solid continuous floor beneath the fireplace and the chase bottom. Chase insulation in a cold climate installation is not required for safety.

ASSEMBLY OUTLINE

Before You Start

Check your inventory list to be sure you have all the necessary parts supplied in good usable condition. Check also for any concealed damage.

Check the operation of the damper. The damper is controlled through the use of a control lever located within the firebox opening at the top center in front of the firebox lintel ( Figure 3 ).

The control lever snaps into place at either extreme of its range of motion. When locked in position all the way to the right, the damper is open. When locked in position all the way to the left, the damper is closed.

Damper

Closed

Lintel

Damper

Open

Combustion

Air Actuator

Hearth

Optional

Outside Chase

Figure 4

Carefully consider the position of the fireplace opening with respect to the location of adjacent or nearby stairwells, bath or kitchen exhaust fans and/or return air registers for forced air furnaces/air conditioners that could cause a smoking fireplace condition if the house is tightly insulated.

When locating the fireplace, consideration must be given to combustibles and final finishing.

See

Figure 5 and confine the final location of combustible finish materials to the "Safe Zone".

DO NOT permanently place furniture or other items such as decorative pillows within 60" of the fireplace front face.

Black Portion Of Frame

Not To Be Covered With

Combustible Materials

Wall

Covering

12”

45

°

1”

Door

Opening

12”

Safe

Zone

Figure 5

Figure 3

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

ASSEMBLY STEPS

Note: The following steps represent the normal sequence of installation. Each installation is unique, however, and might require a different sequence.

1. Position firebox prior to framing or into prepared framing.

2. Install the chimney system.

3. Connect house wiring to the fireplace for later attachment of optional blower.

4. Install optional outside combustion air kit.

5. Plumb gas line if a decorative gas appliance will be used. (Gas connections should only be performed by an experienced, licensed/certified tradesman.)

6. Complete the installation, finish wall material, surround and hearth extension to your individual taste.

7. Assemble and attach optional glass door assembly.

Study the three dimensional illustration ( Figure 1 ) to get a general idea of each element of your fireplace system.

PRE-INSTALLATION NOTES

The fireplace may be installed directly on a combustible floor or raised on a platform of an appropriate height. Do not place fireplace on carpeting, vinyl or other soft floor coverings. It may, however, be placed on flat wood, plywood, particle board or other hard surfaces.

Be sure fireplace rests on a solid continuous floor or platform with appropriate framing for support and so that no cold air can enter the room from under the fireplace.

The fireplace may be positioned and then the framing built around it, or the framing may be constructed and the fireplace positioned into the opening.

Usually, no special floor support is needed for the fireplace, however, to be certain:

1. Estimate the total weight of the fireplace system including chimney and surround materials such as brick, stone, etc., to be installed. Shipping weights for the fireplace may be found on page 18.

2. Measure the square footage of the floor space to be occupied by the system, surrounds and hearth extensions.

3. Note the floor construction, i.e. 2 x 6’s, 2 x 8’s or 2 x 10’s, single or double joists, type and thickness of floor boards.

4. Use this information and consult your local building code to determine if you need additional support.

CAUTION: DO NOT BLOCK THE HEAT-CIRCU-

LATING AIR INLET AND OUTLET PORTS ON

CIRCULATING MODELS. DOING SO MAY RE-

SULT IN A POTENTIAL FIRE HAZARD.

If you plan to raise the fireplace and hearth extension, build the platform assembly then position fireplace and hearth extension on top.

Secure the platform to the floor to prevent possible shifting.

CLEARANCES

Minimum clearance to combustibles for the appliance is as follows: sides and back -

1" (25 mm), floor - 0" (0 mm), adjacent wall - 12" (305 mm), ceiling - 37-1/2" (953 mm).

INSTALLING THE FIREPLACE

Step 1. Slide the fireplace into prepared framing or position fireplace in its final position and frame later.

The fireplace may not be recessed into a combustible floor. Maintain the floor to hearth clearance established by the fireplace lower front face.

Step 2. Insert the provided metal safety strips, beneath the fireplace as illustrated ( Figures 6, 7 and 8 ). The safety strips should overlap 1/2" for continual coverage of the floor.

Note: Safety strips are not required when fireplace rests on a noncombustible surface.

Top Spacer

Maintain

1" (25 mm)

Air Space

At Back

And Sides

Front

Hearth

Extension

1" (25 mm) Space

Metal Safety Strip Floor

Note: Hearth extensions must not interfere with

circulating grillwork

Figure 6

1" (25 mm) Space

Maintain

1" (25 mm)

Air Space

At Back

And Sides

Front

Hearth

Extension

Metal Safety Strip Platform Floor

Note: Hearth extensions must not interfere with

circulating grillwork

Figure 7

Note: Install the hearth extension only as illustrated.

The safety strips should extend from front of the fireplace at least 1-1/2" and should extend to be at least flush with the sides. In the event a wooden support is used to elevate the fireplace above the floor, a “Z” type safety strip should be fabricated and used to protect the front surface of the wood support as well as the floor beneath the hearth extension ( Figures 8 and 9 ). The safety strips should be tacked down to prevent possible movement.

Note: The “Z” type safety strip is not supplied.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

5

FIREPLACE SPECIFICATIONS

7-1/2"

(191 mm)

1-1/2"

(38 mm)

9-5/8"

(244 mm)

36"

(914 mm)

37"

(940 mm)

1-1/2"

Metal Safety Strips

20-3/16"

(513 mm)

27-7/8"

(708 mm)

2"

(51 mm)

Figure 8

7-3/16"

(183 mm)

Blocking

43"

(1092 mm)

40"

(1016 mm)

Front (BC Model Shown)

Appliance Top Spacer

Metal Safety Strips

6

Figure 9

Step 3. Refer to fireplace drawings and specifications on pages 6 and 7 for framing dimensions and details. Frame appliance enclosure as illustrated in Figures 11 through 14 on page 8.

IMPORTANT: UNDER NO CIRCUMSTANCES

CAN THE FIREPLACE TOP SPACERS ( FIGURE

10 ) BE REMOVED OR MODIFIED, NOR MAY

YOU NOTCH THE HEADER TO FIT AROUND OR

BE INSTALLED LOWER THAN THE SPACERS.

THE HEADER MAY BE IN DIRECT CONTACT

WITH THE TOP SPACERS BUT MAY NOT BE

SUPPORTED BY THEM.

Note: The framed depth, 20-5/8" (524 mm) from a framed wall, must always be measured from a finished surface. If a wall covering such as drywall is to be attached to the rear wall, then the 20-5/8" (524 mm) must be measured from the drywall surface. It is important that this dimension be exact.

If the appliance is to be elevated above floor level, a solid continuous platform must be constructed.

The header may rest on the top metal spacers, but must not be notched to fit around them.

Consult all local codes.

Gas Line

Access

20-1/4"

(514 mm)

Left Side

7-13/16"

(198 mm)

37"

(940 mm)

Combustion

Air Inlet

17-3/8"

(441 mm)

9-7/8"

(251 mm)

Gas Line

Access

32"

(813 mm)

9-3/16"

(233 mm)

12-7/8"

(327 mm)

9-1/16"

(230 mm)

27-1/4"

(692 mm)

Appliance

Top Spacer

1-1/2"

(38 mm)

12-1/2"

(318 mm)

43"

(1092 mm)

40"

(1016 mm)

Top View

Figure 10

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Junction

Box

Right Side

20-1/4"

(514 mm)

FRAMING SPECIFICATIONS

*B

2

B

1

(See Note)

Header

Framing Dimensions

H

J

K

F

G

D

E

A

42-1/4" 1073 mm

B

1

37-1/2" 953 mm

B

2

54-1/2" 1384 mm

C

28-3/4" 730 mm

15-3/8"

70"

35"

391 mm

1778 mm

889 mm

20-5/8" 524 mm

19-5/8" 498 mm

49-1/2" 1257 mm

8" 203 mm

Note: All framing dimensions calculated for 1/2" dry wall at the fireplace face. If sheathing the chase or finishing with other thickness materials, calculations will need to be made.

A

Fireplace Framing

*Note: When Framing With 6” Studs Header Must

Be 17” (432mm) Higher. Use Security Chimney’s

OR15 Offset/Return Elbow To Recess The Chimney

Back 2 1/2” (64mm). Flat Frame Down To A False

Header At (B

1

). Maintain Required Clearance To

Chimney At All Times.

Figure 11

Back Wall of Chase/Enclosure

Including Finising Materials if any

Figure 12

A

Inside Chase

FOAK Combustion

Air Kit

G

Rough

Framing Face

(Unfinished Shown)

Framing Dimensions for Ceiling

Flue Type

FTF8 Vertical

A B

14-1/2" 14-1/2"

(368 mm) (368 mm)

FTF8 Vertical at 2"

16-1/2" 16-1/2"

(419 mm) (419 mm)

FTF8 Offset 30

°

14-1/2" 25"

(368 mm) (635 mm)

FTF8 Offset 30

°

16-1/2"

at 2"

(419 mm)

27"

(686 mm)

Back Wall of

Chase/Enclosure

Including Finising

Materials if any

J

Figure 15

D

Figure 16

B

C

D

C

FOAK Combustion

Air Kit - Optional

A

E

Rough

Framing Face

(Unfinished Shown)

Corner Installation

Figure 14

A

Ceiling Framing

Roof Framing

F

Back Wall of Chase/Enclosure

Including Finising Materials if any

FOAK

Combustion

Air Kit - Optional

H

A

Rough

Framing Face

(Unfinished Shown)

Outside Chase

Figure 13

G

Framing Dimensions for Roof

FTF8 at 1" FTF8 at 2"

Pitch

0/12

C D* C D*

14-1/2" 14-1/2" 16-1/2" 16-1/2"

(368 mm) (368 mm) (419 mm) (419 mm)

6/12

14-1/2" 17" 16-1/2" 19"

(368 mm) (442 mm) (419 mm) (483 mm)

12/12

14-1/2" 21-1/2" 16-1/2" 23-1/2"

(368 mm) (546 mm) (419 mm) (579 mm)

* Perpendicular to roof ridge

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

7

8

Step 4. Fireplace should be fastened to side framing members using the nailing tabs at the top and bottom of the fireplace front face. Use

8d nails or equivalent ( Figure 17 ).

8d Nail Or

Equivalent

Fastener

Figure 17

For Canadian Installations Proceed with Steps 5 through 8

Step 5. Attach the cold climate kit, Model

FTF8-CCK1-LD, around the chimney collar with the screws provided ( see Figure 18 ).

Note: CCK1-LD model requires a 6" diameter

Class 0 metallic air duct, acquired locally by installer.

Figure 18

Step 6. Connect the 6" (152 mm) Class 0 metallic air duct to the collar on the chimney collar enclosure with the screws provided in the hardware kit.

Step 7. Route the Class 0 metallic air duct out the back wall or side wall, up through the ceiling or floor joists to an outside wall. The air duct’s inlet should be located above any anticipated snow level.

Note: If the fireplace is installed against an inside wall, the Class 0 metallic air duct may be extended into a ventilated attic space at least 18"

(457 mm) above the attic floor. Secure the duct hood to a vertical post with the inlet positioned downward. Ensure that nothing blocks the hood opening. This air duct must never terminate higher than the fireplace chimney.

Step 8. Cut or frame a hole through the outside wall for the installation of the duct inlet hood. A

6-1/2" (165 mm) diameter hole is required.

Feed the loose end of the flexible duct through the hole cut for the inlet hood and attach to the collar on inlet hood using two (2) screws. Insert the hood into the opening. Secure in place with nails driven through the holes in hood flange.

Seal with noncombustible waterproof silicon type caulking. If additional air duct is needed, use Class 0 metallic duct.

INSTALLING THE CHIMNEY SYSTEM

Step 1. Before continuing, check the operation of the damper, as described on page 4, ( refer to Figure 3 ).

Step 2. Using standard construction framing techniques, construct opening for chimney route up through the ceiling(s) and roof or through an outside chase.

Framing must maintain adequate minimum air space clearance at all times.

CAUTION: ALLOW MINIMUM 1"* CHIMNEY

AIR SPACE TO COMBUSTIBLE FRAMING MEM-

BERS THROUGHOUT VERTICAL OR OFFSET

CHIMNEY INSTALLATION.

A minimum 1"* air space must be reserved for all combustible materials extending for any continuous length surrounding the chimney.

*Note: 2" clearance to combustibles required

in Canada.

Reference Figures 15 and 16 and charts Framing Dimensions for Ceiling and Roof, which specify minimum ceiling and roof dimensions.

In new construction, to determine chimney center line, use plumb line from roof or ceiling above fireplace to center of flue collar on fireplace.

For remodeling, plumb to center of flue collar from ceiling above, drive nail through ceiling from below to mark position, then mark and cut to passage from above ceiling (around nail) ( see Figure 19 ). Then plumb from ceiling or roof level directly above hole which has just been completed.

Figure 19

Step 3. Position appropriate firestop spacer at ceiling and nail temporarily with two (2) 8d nails. Use flat firestop spacer, Model F8FS-2, if chimney penetrates ceiling vertically. If chimney penetrates ceiling at 30

°

angle (offset chimney), use 30

°

firestop spacer, Model F8FS30.

Use one nail on opposite sides to hold firestop spacer in position. Nail permanently, using at least two (2) more 8d nails, after chimney sections have been assembled through the firestop spacer and after any necessary adjustments have been made. Firestop spacer must be secured by at least four (4) 8d nails when completely installed.

Note: If there is a room above ceiling level, firestop spacer must be installed on the bottom side of the ceiling. If an attic is above ceiling level, firestop spacer must be installed on top side of ceiling joist (Figures 20 and 21 ).

Room Above

Figure 20

Figure 21

Attic Above

Firestop Spacer

Firestop Spacer

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

CHIMNEY 30

°

OFFSET THROUGH FLOOR

OR CEILING

It may be necessary to assemble the chimney at

30

°

when passing through the floor or ceiling area. Use the F8FS30 firestop spacer as shown in Figures 22 and 23. Support the chimney at floor or ceiling penetration with a FTF8 stabilizer if distance of chimney below ceiling is 10' or more. Maintain 1"* minimum air space to combustibles from chimney sections.

Attic Space

F8FS30-2

Firestop Spacer

2" Min.

Air Space

2" Min.

Air Space

FTF8-S4 Stabilizer

10'

Max.

Figure 22

F8FS30-2

Firestop Spacer

Room Above

30

°

Firestop

And Attic Above

2" Min.

Air Space

2" Min.

Air Space

FTF8-S4 Stabilizer

Figure 23

For Canada Only

10'

Max.

30

°

Firestop

And Room Above

When installing the chimney system through an open attic space, the attic shield assemblyfirestop spacer must be used ( Figure 24 ). This installation is required only for use in Canada.

Open Attic Space

Step 4.

Note: Chimney sections are constructed with a unique locking tab design, which ensures an immediate, tight assembly between sections. Plan your chimney requirements carefully before assembly as chimney is difficult to disassemble after installation. If disassembled, the tabs might become damaged. Be certain tabs are properly formed to ensure locking tabs engage properly.

The Security Chimney's FTF8 chimney system is a two piece chimney, which snap together from the fireplace up. Start with the inner flue section with the lanced end up, snap lock it in to the matching collar on top of the fireplace. At all subsequent joints, the upper flue section fits into the preceding flue section. Each piece snaps together by means of locking tabs (9 locking tabs per joint). Check each piece by pulling up slightly from the top to ensure proper engagement before installing the next section.

If the flue has been installed correctly, it will not separate when you test it. Also, the inner flue joint where each section is joined should be tight and flat without gaps (

Figure 25 ).

Note: Assemble one component of chimney at a time (inner section first, then outer section last) before proceeding with the next complete section.

Continue to assemble the chimney up through framed opening. Assemble just enough to penetrate the roof flashing openings ( Figure 27 ).

Always maintain 1"* minimum air space to combustible materials and always check each chimney joint (inner and outer) to ensure proper engagement. Check vertical alignment of chimney so that it projects from the roof in true vertical position.

Figure 25

Outer pipe section installs in just the opposite way; the lanced end goes down and each new section goes OVER the outside of the previous section installed ( Figure 26 ).

Locking

Tabs

(Lances)

1"* Min. Air Space

To Combustibles

Figure 27

Security's chimney sections do not need to be screwed together. Additional reinforcement is not necessary except in certain offset conditions (refer to page 14,

Figure 38 ).

Step 5. The height of vertical chimney pipe supported only by the fireplace must not exceed 30'. Chimney heights above 30' must be supported by a Model FTF8-S4 stabilizer installed at 30' intervals.

Note: The Model FTF8-S4 adds 3" net effective height to the total chimney system.

Install the Model FTF8-S4 stabilizer by fitting inner section down into respective section of proceeding flue pipe and locking outer stabilizer section into place over the outer chimney pipe. Position for proper clearance through framed opening and nail straps securely (under tension in “shear”) into place on framing. Use

8d nails. Attach successive lengths of chimney pipe directly to stabilizer using same techniques as described in Step 4 ( see Figure 28 ).

*Note: 2" clearance to combustibles required in Canada.

Figure 24

Note: For Canadian installations, all chimney installed outside the building must be constructed with galvalume (outer sections only) effective

January 1, 1992. The appropriate model designations are located in the back of this manual.

Figure 26

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

9

Roof Ridge

10

FTF8-S4 Stabilizer

Figure 28

Note: Do not apply excessive pressure to any subsequent chimney sections following the stabilizer when installing. Ensure each subsequent chimney section is securely attached by testing as noted in Step 4.

Step 6. Select the proper Security Chimneys roof flashing based on pitch of roof. Use chart below for selection:

Roof Pitch

Flat to 6/12

6/12 to 12/12

Model

F8F6

F8F12

Figure 30

Step 8. Slide the FTF8 storm collar (ordered separately) over outer chimney, rest on flashing spacers and align with top surface of flashing. Insert tab in slot, pull tight and bend tab back over slot. Seal storm collar to outer chimney with roof caulking or mastic around entire circumference of pipe. Also add extra roof caulking to the tab/slot area to seal completely against water penetration ( Figure 31 ).

Check all joints very carefully to ensure no water intrusion can take place.

120

°

Figure 32

Step 10. Using a FTF8-CTD Round Termination:

1. Hold the FTF8-CTD over top of last chimney section ( Figure 33 ).

2. Center inner slip section in inner flue pipeslip down.

Next, slide roof flashing over extended chimney section that previously has been installed above the roof opening in Step 4. FTF8 flashings require flashing spacers. Slide flashing all the way down until the flashing base rests flat on the roof (

Figure 29 ). Again, check the vertical position of the chimney and the 1"* minimum air space to combustibles.

FTF8 Chimney

Flashing Spacers

FTF8 Flashing

Do Not Seal

Figure 29

Note: Do not caulk or seal the ventilating openings.

Step 7. Secure flashing by nailing along the perimeter into roof using 8d nails. If shingled roof, slide upper end and sides of roof flashing under shingles (trim if necessary), seal the top and both sides of the flashing to the roof with roof caulking. Cover nail heads with roof caulking ( Figure 30 ).

*Note: 2" clearance to combustibles required in Canada.

Locking Band

CTD

Termination

Chimney

Waterproof

Caulk

Figure 31

Step 9. Security Chimneys locking bands,

Model FLB, may be required if the chimney extends too high above the roof flashing. As a general rule, if the chimney extends more than

6' above the roof flashing, the use of locking bands is advisable to strengthen the chimney assembly. Align the locking band at the chimney joint. Locking bands wrap around pipe joints equally covering the joints of both pipe sections. Use the nut provided and TIGHTEN snugly. Do not overtighten as this might damage the chimney section ( refer to Figure 31 ).

Note: If chimney extends more than 8' above roof surface, guy wires are also recommended.

Use three (3) guy wires, attach to locking band assembly, extend and secure to roof in a triangular pattern (see Figure 32 ). Guy wires are not supplied by the manufacturer.

Figure 33

3. Center outer locking section over outer flue pipe. Push down until locking tabs are firmly engaged.

4. Pull up slightly on CTD to ensure locking joint has firmly engaged.

Using a FTF8-CTDT Chase Termination:

Refer to specific installation instructions included with the FTF8-CTDT chase termination for clearance and installation details.

Using a FTF8-CT1 Chase Termination:

Refer to specific installation instructions included with FTF8-CT1 chase terminations for clearance and installation details.

Using a FTF8-CT2 Chase Termination:

Refer to specific installation instructions included with FTF8-CT2 chase terminations for clearance and installation details.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Less Than 10'

3'

Min

Figure 34

Note: It is recommended that all exterior exposed metal fireplace components; such as terminations, flashings, storm collars and/or flue be painted with a premium quality, high temperature, rust preventative paint designed for metal. This is especially important when installations are made in abnormally adverse or corrosive environments; such as near lakes, oceans or in areas with consistently high humidity conditions. Consult the paint manufacturers instructions for proper preparation and application.

TEN FOOT RULE SUMMARY

The minimum chimney height above the roof and/or to adjacent walls and buildings is specified by all major building codes.

If the horizontal distance from the peak of the roof is less then 10', the top of the chimney must be at least 2' above the peak of the roof.

If the horizontal distance from the chimney edge to the peak of the roof is more than 10' a chimney height reference point is established on the roof surface 10' horizontally from the chimney edge. The top of the chimney must be at least 2' above this reference point. In all cases, the chimney cannot be less then 3' above the roof at the edge of the chimney.

The 2' in 10' rule is necessary in the interest of safety but does not ensure smoke-free operation. Trees, buildings, adjoining roof lines, adverse wind conditions, etc., may require a taller chimney should the fireplace not draft properly

( refer to Figure 34 ).

2' Min.

10'

3'

Min

MULTIPLE TERMINATIONS

If more than one termination is located in the same chase or within the same general proximity, we suggest they should be separated in distance at least 24" horizontally from flue center to flue center and stacked or staggered vertically at least 18" apart, from the termination of one smoke exit to the termination of another smoke exit ( Figure 35 ).

CTD

18"

18"

CTDT

24"

24"

CTDT

Figure 35

This suggestion is provided in the interest of better operation. If the terminations are located too close to each other, smoke may migrate from one flue into the other.

FTF8 CHIMNEY COMPONENT

CALCULATIONS

The minimum installed height of the completed fireplace system is 15' 0". The maximum height is 60' 0".

To determine the number of chimney sections and chimney components required, follow these steps:

1. Determine total vertical height of the fireplace installation. This dimension is the distance from the surface the fireplace sets on to the point where smoke exits from the termination.

2. Determine the number of chimney components required, except chimney sections. This would include firestop spacers, stabilizers, roof flashing, etc.

3. The effective heights of the components are:

The Fireplace

FTF8-12

FTF8-18

FTF8-36

= 36-1/4"

= 10-1/4"

= 16-1/4"

= 34-1/4"

FTF8-48 = 46-1/4"

FTF8-CTD Termination = 4"

FTF8-CT1 Termination = 12" to 18"

FTF8-CT2 Termination = 15" to 23"

FTF8-CTDT Termination = 12" to 18"

FTF8-S4 Stabilizer * = 3"*

* Required for every 30' of vertical chimney and/or 10' of offset chimney.

4. Determine amount of chimney height required by subtracting total combined height of all pre-selected components (fireplace and chimney components from total desired height.)

Reference Vertical Elevation Chart and determine the number of chimney sections (quantity and length) required.

SPECIAL OFFSET INSTRUCTIONS

To clear any overhead obstructions, you may offset your chimney system using Security

Chimneys 30

°

offset and return elbows. Use two elbows - an offset elbow to initiate the offset and a return elbow to terminate it. A 30

° offset elbow, angling in any direction, may be the first component used off the top of the fireplace flue collar.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

11

12

The offset and return elbows may be attached together, or a section or sections of chimney may be used between, but do not exceed 20' in total length between elbows. If sections of pipe exceed 10' between elbows, a chimney stabilizer must be used at the midpoint ( Figure 36 ).

The stabilizer support straps must be attached under tension (in shear) to structural framing members above. When two sets of elbows are used, the maximum combined length of chimney used between elbows cannot exceed 20'

( Figure 37 ). Example: If C

1 exceed 10'.

= 10' then C

2

cannot

If an offset exceeds 6' in length, each chimney joint beyond the first 6' of offset to the return elbow, must be secured by a No. 8 x 1/2" sheet metal screw located at the underside of the joint

( Figure 38 ).

A 1/8" diameter hole must be drilled in the chimney joint using a 1/8" diameter drill. Hole should be drilled in center of joint overlap

( Figure 39 ). Be sure to drill only through the outer chimney casting. Do not puncture the inner flue.

Maximum offset of chimney system is 30

°

. Two offsets must not be assembled to form a 60

° offset. However, two sets of offset and return elbows may be used on a single flue system, provided the total height of the system exceeds

25'.

Return elbow support straps must be securely attached under tension (in shear) to structural framing members above. Do not substitute a

FTF8-30 offset elbow in place of a FTF8-E30 return elbow.

OFFSET CALCULATIONS

Step 1. Use Offset Chart to determine amount of horizontal offset (A) and height (B) for various chimney section assemblies.

Step 2. Use “Height of Chimney Only” column in The Vertical Elevation Chart to determine combinations of chimney used above return elbow to achieve desired heights. Reference

Components Effective Height Chart in vertical elevation chart section.

Step 3. Use Elevation Chart as job estimator only. Add necessary firestop spacers and stabilizers as required. Firestop spacers must be used as shown in Figures 22 and 23 and stabilizers as shown in Figure 28.

FTF8 VERTICAL ELEVATION CHART

Height Of

Chimney Only

Number Of FTF8

Chimney Lengths

Inches Feet/Inches 12" 18" 36" 48"

11

17

21

¹⁄₄

27

¹⁄₄

35

143

¹⁄₂

149

¹⁄₂

155

¹⁄₂

159

³⁄₄

165

³⁄₄

173

¹⁄₂

183

³⁄₄

185

¹⁄₂

189

³⁄₄

195

³⁄₄

201

³⁄₄

97

¹⁄₄

102

¹⁄₂

109

¹⁄₄

113

¹⁄₂

119

¹⁄₂

127

¹⁄₄

137

¹⁄₂

139

¹⁄₄

47

51

¹⁄₄

57

¹⁄₄

63

¹⁄₄

67

¹⁄₄

73

¹⁄₄

81

¹⁄₄

93

¹⁄₄

206

212

219

³⁄₄

230

231

³⁄₄

236

242

248

252

258

266

276

278

282

288

294

³⁄₄

298

¹⁄₄

304

¹⁄₄

312

322

¹⁄₄

324

328

¹⁄₄

334

¹⁄₄

340

¹⁄₄

344

¹⁄₂

350

¹⁄₂

358

¹⁄₄

368

¹⁄₂

370

¹⁄₄

374

¹⁄₂

380

¹⁄₂

0 11

1 5

1 9

¹⁄₄

2 3

¹⁄₄

2 11

3 11

4 3

¹⁄₄

4 9

¹⁄₄

5 3

¹⁄₄

5 7

¹⁄₄

6 1

¹⁄₄

6 9

¹⁄₄

7 9

¹⁄₄

8 1

¹⁄₄

8 6

¹⁄₂

9 1

¹⁄₄

9 5

¹⁄₂

9 11

¹⁄₂

10 7

¹⁄₄

11 5

¹⁄₂

11 7

¹⁄₄

11 11

¹⁄₂

12 5

¹⁄₂

12 11

¹⁄₂

13 3

³⁄₄

13 9

³⁄₄

14 5

¹⁄₂

15 3

³⁄₄

15 5

¹⁄₂

15 9

³⁄₄

16 3

³⁄₄

16 9

³⁄₄

17 2

17 8

18 3

³⁄₄

19 2

19 3

³⁄₄

19 8

20 2

20 8

21 0

21 6

22 2

23 0

23 2

23 6

24 0

24 6

³⁄₄

24 10

¹⁄₄

25 4

¹⁄₄

26 0

26 10

¹⁄₄

27 0

27 4

¹⁄₄

27 10

¹⁄₄

28 4

¹⁄₄

28 8

¹⁄₂

29 2

¹⁄₂

29 10

¹⁄₄

30 8

¹⁄₂

30 10

¹⁄₄

31 2

¹⁄₂

31 8

¹⁄₂

1

0

0

1

0

0

2

1

0

1

0

0

1

1

0

2

0

0

0

1

0

2

1

0

1

1

0

0

1

0

2

1

1

0

0

1

2

1

0

1

0

0

0

1

0

1

0

2

0

1

2

1

1

0

0

0

0

0

0

2

1

1

0

0

0

1

1

0

1

0

0

0

1

0

1

0

0

1

0

0

1

0

0

1

0

1

1

0

0

0

0

0

0

0

1

0

1

1

0

0

1

0

0

1

0

1

1

0

0

1

0

1

0

0

1

0

1

0

0

0

0

1

0

1

0

1

1

0

1

0

1

0

0

1

0

0

1

1

0

0

0

0

0

1

1

1

0

0

0

1

0

1

0

1

1

0

0

0

0

0

1

0

0

0

1

0

0

0

1

0

1

1

0

0

1

0

0

0

0

0

1

0

1

0

1

0

0

0

0

6

7

6

6

6

6

6

5

6

5

5

5

6

5

5

5

5

4

4

4

4

4

4

3

4

3

4

7

7

8

7

7

7

7

7

8

3

3

3

3

3

3

2

2

2

2

2

2

1

2

1

1

1

1

1

2

0

1

0

0

0

0

0

Height Of

Chimney Only

Number Of FTF8

Chimney Lengths

Inches Feet/Inches 12" 18" 36" 48"

43 9

44 1

¹⁄₄

44 7

¹⁄₄

45 3

46 1

¹⁄₄

53 11

¹⁄₂

54 3

¹⁄₂

54 9

¹⁄₂

55 3

¹⁄₂

55 7

³⁄₄

56 1

³⁄₄

56 9

¹⁄₂

57 7

³⁄₄

57 9

¹⁄₂

58 1

³⁄₄

58 7

³⁄₄

59 1

³⁄₄

46 3

46 7

¹⁄₄

47 1

¹⁄₄

47 5

¹⁄₄

47 11

¹⁄₂

48 5

¹⁄₂

49 1

¹⁄₄

49 11

¹⁄₂

50 1

¹⁄₄

50 5

¹⁄₂

51 11

¹⁄₂

51 5

¹⁄₂

51 9

¹⁄₂

52 3

¹⁄₂

52 11

¹⁄₂

53 9

¹⁄₂

59 6

60 0

60 7

³⁄₄

61 6

61 7

³⁄₄

62 0

32 2

¹⁄₂

32 6

³⁄₄

33 0

³⁄₄

33 8

¹⁄₂

34 6

³⁄₄

34 8

¹⁄₂

35 0

³⁄₄

35 6

³⁄₄

36 0

³⁄₄

36 5

36 11

37 6

³⁄₄

38 5

38 6

³⁄₄

38 10

³⁄₄

³⁄₄ 39 4³⁄₄

39 10

³⁄₄

40 3

40 9

41 4

³⁄₄

42 3

42 4

³⁄₄

42 9

43 3

443

450

³⁄₄

461

462

³⁄₄

466

³⁄₄

472

478

³⁄₄

483

489

496

³⁄₄

507

508

³⁄₄

386

¹⁄₂

390

³⁄₄

396

³⁄₄

404

¹⁄₂

414

³⁄₄

416

¹⁄₂

420

³⁄₄

426

³⁄₄

432

³⁄₄

437

513

519

525

529

¹⁄₄

535

¹⁄₄

543

553

¹⁄₄

647

¹⁄₂

651

¹⁄₂

657

¹⁄₂

663

¹⁄₂

667

³⁄₄

673

³⁄₄

681

¹⁄₂

691

³⁄₄

693

¹⁄₂

697

³⁄₄

703

³⁄₄

709

³⁄₄

555

559

¹⁄₄

565

¹⁄₄

571

¹⁄₄

575

¹⁄₂

581

¹⁄₂

589

¹⁄₄

599

¹⁄₂

601

¹⁄₄

605

¹⁄₂

611

¹⁄₂

617

¹⁄₂

621

¹⁄₂

627

¹⁄₂

635

¹⁄₂

645

¹⁄₂

714

720

727

³⁄₄

738

739

³⁄₄

744

0

1

0

1

0

1

0

0

1

1

0

0

2

2

1

0

1

0

0

0

1

0

1

0

2

0

1

1

0

0

2

1

0

0

0

1

0

1

2

1

0

1

0

0

2

1

0

0

0

1

0

1

2

1

0

1

0

1

0

1

0

0

2

1

0

1

0

0

1

0

1

0

0

0

1

0

0

1

0

0

1

0

1

1

0

0

1

0

1

0

1

0

1

0

0

0

0

1

0

0

0

0

1

1

1

0

1

0

0

0

0

1

0

0

0

0

1

1

0

1

0

0

1

0

1

0

1

0

0

1

0

0

1

1

0

1

0

0

0

0

0

1

0

0

0

1

0

1

1

0

0

1

0

0

1

0

0

1

0

0

1

0

1

1

0

0

1

0

1

0

0

1

0

0

1

0

1

1

0

0

1

0

0

1

0

0

1

0

0

13

14

14

13

13

13

14

12

13

12

13

13

13

12

12

12

12

11

12

12

11

11

11

10

11

11

11

15

15

15

15

15

16

15

14

15

14

14

14

14

15

10

10

10

10

10

11

10

9

10

9

9

9

9

8

9

9

8

9

8

8

8

8

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

B

1

A

1

20'

Max.

10' Max.

Offset

Elbow

Stabilizer

Return

Elbow

Figure 36

A

2

C

2

A

1

B

2

B

1

C

1

C

2

A

2

A

1

B

2

B

1

C

1

OFFSET ELEVATION CHART

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

A B FTF8-ES30

Offset Height Offset/Return FTF8-S4

(Inches) (Inches) Elbow

Number of FTF8 Chimney Sections

Stabilizer 12" 18" 38" 48"

4

9

12

15

³⁄₄

24

¹⁄₂

29

³⁄₄

33

¹⁄₂

14

¹⁄₄

17

20

21

¹⁄₄

¹⁄₄

38

¹⁄₂

43

³⁄₄

45

¹⁄₄

47 ¹⁄₂

22

¹⁄₄

25

26

27

¹⁄₄

¹⁄₄

52 ¹⁄₂

54

¹⁄₄

55

³⁄₄

57 ³⁄₄

28

¹⁄₄

29

31

¹⁄₄

¹⁄₄

32

¹⁄₄

34

¹⁄₄

35

37

¹⁄₄

¹⁄₄

59

¹⁄₄

63

64

¹⁄₂

68 ¹⁄₄

69

³⁄₄

73

¹⁄₄

38

¹⁄₄ 75

39 ¹⁄₄ 77

41

¹⁄₂

43

¹⁄₄

44

¹⁄₄

45

¹⁄₄

80

¹⁄₂

83 ³⁄₄

85

¹⁄₄

87 ¹⁄₂

46 ¹⁄₄ 89

48 ¹⁄₄ 91 ¹⁄₂

49

¹⁄₄

50

¹⁄₄

94

95

¹⁄₄

³⁄₄

51

¹⁄₄ 97 ³⁄₄

54

¹⁄₄

103

55

¹⁄₄

104

¹⁄₂

56

¹⁄₂ 106 ¹⁄₂

58

¹⁄₄

109

³⁄₄

61

³⁄₄

116

64

³⁄₄

121

¹⁄₄

67 124

³⁄₄

68

³⁄₄ 128

70 130

73 135 ¹⁄₄

74

³⁄₄

138

¹⁄₄

79

80

145

¹⁄₂

147 ¹⁄₄

82 150 ³⁄₄

82 ¹⁄₄ 152

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

1

1

1

1

1

1

1

1

0

0

0

1

0

0

0

0

0

0

0

2

0

1

0

0

0

0

2

1

1

1

2

1

1

0

2

0

1

0

0

0

0

1

1

1

2

0

1

0

1

0

2

1

0

0

0

0

0

2

1

1

1

2

0

1

0

1

2

0

3

1

0

0

4

0

0

0

1

1

0

0

1

2

0

1

1

0

0

0

1

1

0

0

0

1

0

1

2

0

3

1

0

1

2

0

0

1

2

1

0

2

2

1

1

2

2

1

0

2

1

0

1

3

3

1

3

3

0

4

0

4

0

0

2

0

3

0

0

0

0

0

0

0

0

1

1

0

0

1

1

0

0

0

2

0

0

1

0

0

0

1

0

0

0

1

0

0

0

2

0

0

3

0

3

0

3

2

0

2

0

0

0

0

0

0

0

1

0

0

0

0

0

0

Figure 37

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

13

14

Chimney

Section

Figure 38

Underside Of Chimney

Figure 39

6'

4' y Joint Past 6'

Screws Required At

No. 8 x 1/2" SMS

A

Joints

FTF8-E30 Return Elbow*

Chimney Section (S)

FTF8-30 Offset Elbow*

B

*Part of Offset/Return Package Model FTF8-ES30

Figure 40

INSTALLING OFFSETS

First, review the Offset Elevation Chart and

Figure 40 for reference.

Step 1. Determine the offset distance where chimney is to pass through the first ceilingdimension “A.” To find this point on your ceiling, first determine the center point for a vertical chimney following the instructions for vertical installation.

Measure height to the ceiling from the top of fireplace-dimension “B.” Use the appropriate

Offset Elevation Chart to find dimension “A.”

Mark point where you will drive your nail to show the center point for your offset ceiling cut.

Step 2. Proceed by using the Straight Up Installation Instructions for cutting and framing ceiling and roof openings.

Note: See Framing and Dimension Chart for the sizes of the ceiling and roof openings. The size of the roof opening varies with the degree of pitch of the roof.

Offset Elbow Assembly

Offset elbows install the same as chimney sections. First, snap the inner section INTO the preceding inner section of flue. Check connection by pulling up slightly to ensure a tight fit.

Next, the outer sections snap lock OVER the preceding outer section of chimney. Again, check outer section by pulling up slightly to ensure proper connection is made.

Return Elbow Assembly

Return elbows install the same way as round terminations and stabilizers:

Step 1. Hold return elbow over top of last chimney section.

Step 2. Center inner slip section into inner flue pipe-slip down.

Step 3. Center outer-locking section over outer chimney pipe. Push down until locking joint has firmly engaged.

Step 4. Pull up slightly on return elbow to ensure locking joint has firmly engaged.

Step 5. Secure support straps to framing members by nailing under tension in sheer

( Figure 41 ).

Note: The return elbow assembly performs the same function as a stabilizer. Consider this when determining the need for a stabilizer.

Return

Elbow

Figure 41

Note: The return elbow assembly performs the same function as a stabilizer. Consider this when determining the need for a stabilizer.

Note: Do not apply excessive pressure to any subsequent chimney section following return elbow assembly when installing. Ensure that each subsequent chimney section is securely attached by testing as noted above.

OPTIONAL EQUIPMENT

CONSIDERATIONS

Blower Kits (Circulating Models Only)

Blower Kits model FBK-100/200 are available for use with circulating models. The Blower

Kit can be installed prior to or after installation of the fireplace.

When installing the FBK-100 Blower Kit, a

Blower Switch Kit (Model FUBSK) is required.

This switch kit allows for a unit mounted blower switch to be used. The FUBSK is not included and must be purchased separately.

The FBK-200 Blower Kit comes standard with a wall mounted variable speed control switch.

Note: The fireplace must have provisions for a wall mounted On/Off switch in order to install the FBK-200.

THE FIREPLACE MUST BE WIRED TO THE

HOUSE ELECTRICAL SYSTEM AT THE TIME

OF INSTALLATION IN ORDER FOR THE OP-

TIONAL FANS TO OPERATE, (SEE FIGURES

42 AND 43 ).

Note: The utilization of fans will increase the air flow around the firebox. However, only a minimal increase in heat output should be anticipated.

THIS FIREPLACE IS NOT INTENDED TO BE

USED AS A SUBSTITUTE FOR A FURNACE TO

HEAT AN ENTIRE HOME. USE FOR SUPPLE-

MENTARY HEATING ONLY.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

POWER TO THE FIREPLACE

The Optional Blower Kit

Operates on 115 volt 60 Hz

150 watts AC

HOUSE

WIRING

House Wiring Must Be Secured

With The Appropriate Electrical

Connector To The Fireplace

Convenience Outlet Wiring

GROUND

WIRE

COVER PLATE

Replace Cover Plate

After Electrical

Hook-Up

Figure 42

BLOWER THREE

PRONGED PLUG TO

GROUNDED OUTLET

Figure 43

The FBK-100/200 Blower Kits are design certified by Warnock Hersey for use with these appliances.

Always check local building codes. Installation of the FBK Blower Kits must comply with local regulations as well as the National Electric Code.

Combustion Air Kits

These appliances are equipped with an outside

(make-up) air door and integral actuator arm. If the appliance is to be installed with an outside air vent system, use only FireCraft Models

FAOK or FAOK-LD Combustion Air Kits. These kits come complete with detailed installation instructions and all components necessary in completing a combustion air vent system.

After completing the installation of the optional combustion air vent system the actuator arm must be put in service and tested to ensure proper operation before completing any enclosure around the firebox. Failure to do so may result in extensive and costly rework.

Locate the actuator arm along the right side of the appliance firebox opening and refer to

Figure 44. After completing the installation of the Outside Combustion Air Kit remove and discard the actuator arm locking screw.

WARNING: DO NOT REMOVE THE AC-

TUATOR ARM LOCKING SCREW UNLESS

THE COMPLETE OUTSIDE AIR VENT SYS-

TEM HAS BEEN INSTALLED IN ACCOR-

DANCE WITH THE DETAILED INSTRUC-

TIONS PROVIDED WITH THE KIT.

Combustion

Air Actuator

Pull Forward to Open,

Push Back to Close

Figure 44

To operate, push the end of the actuator to the left as shown in Figure 44, until it "pops" free of its "locked" position. Pull the actuator forward to open the combustion air door, and push it back to close. To "lock" the combustion air door closed, ensure the actuator is pushed all the way back then push the end of the actuators to the right until the step in the actuator moves behind the appliance front face within the slotted opening.

Operate the actuator through several cycles including the "lock position. Ensuring proper operation and freedom of movement. Return the actuator arm to the locked position.

Gas Line Connection

Install a 1/2" gas supply line through fireplace wall for connection to a decorative gas appliance inside the firebox. Outside, the gas supply line connects to a gas shut-off valve recessed flush into the wall or floor. The valve should be controlled by a removable valve key for safety.

Always plumb gas line installation per local codes. Check all connections with soap suds; leaks will bubble. Never test any gas line connection with a match or open flame.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

This provision is intended for connection to a decorative gas appliance incorporating an automatic shut-off device and complying with the

Standard for Decorative Gas Appliances for installation in vented fireplaces, ANSI Z21.60

(1991) or American Gas Association draft requirements for Gas-Fired Log Lighters for Wood

Burning Fireplaces, Draft No. 4 dated August,

1993. Install in accordance with the National

Fuel Gas Code, ANSI Z223.1. This complies with the revised U.L. 127 standard.

Vent Free Appliances

This unit has been tested and approved to

ANSI/IAS/AGA Z21.11.2 for use with unvented gas appliances and complies with the standard for Factory-Built fireplaces, UL 127, when installed with unvented gas log sets. Special instructions with regards to mantle installations must be taken into consideration when installing such appliances.

The unit has been tested for use with any unvented log sets having a maximum rating of

26,000 BTU. The minimum mantle configuration for these log sets are outlined in

Figure 46.

Log sets with 40,000 BTU may be installed provided that no combustible mantle projections are placed lower than 18 inches from the fireplace opening.

These fireplaces have been marked with a maximum rating of 26,000 BTU to assure that homeowners do not exceed the allowable limits for all allowed installations of mantles. That limit may be increased to 40,000 BTU, provided that the mantle installed complies with the 18-inch limitation and a copy of these instructions are available.

NEVER INSTALL AN UNVENTED GAS LOG

SET WITH A BTU GREATER THAN 26,000 IF

COMBUSTIBLE MANTLE PROJECTIONS ARE

LOWER THAN 18 INCHES ABOVE THE FIRE-

PLACE OPENING.

WARNING: MODELS THAT HAVE THE

"-2" SUFFIX HAVE NOT BEEN TESTED

WITH AN UNVENTED GAS LOG SET. TO

REDUCE RISK OF FIRE OR INJURY, DO

NOT INSTALL AN UNVENTED GAS LOG

SET INTO THIS FIREPLACE.

CAUTION: WHEN USING THE DECORATIVE

GAS APPLIANCE, THE FIREPLACE DAMPER

MUST BE SET IN THE FULLY OPEN POSITION.

CAUTION: PLUMBING CONNECTIONS SHOULD

ONLY BE PERFORMED BY A QUALIFIED, LI-

CENSED PLUMBER. MAIN GAS SUPPLY MUST

BE OFF WHEN PLUMBING GAS LINE TO FIRE-

PLACE OR PERFORMING SERVICE.

15

16

If you’re installing a gas line, connect it before the fireplace is framed and enclosed in the finished wall. The gas knockout is determined by the indentation located at the bottom and slightly off center in the side refractories. THE

KNOCKOUT IS ALWAYS REMOVED FROM IN-

SIDE THE FIREPLACE. DO NOT REMOVE THE

KNOCKOUT UNLESS YOU ARE INSTALLING A

GAS LINE. If removal is attempted from the outer wrapper, side refractory damage may occur. With a medium-sized hammer, lightly tap the surface of the indentation. The refractory material is very thin in this area and is easily removed. Once a small hole has been made, continue tapping until you have reached sufficient diameter for the gas line to fit through. The entire knockout does not have to be removed.

Remove insulation in the gas line channel.

IMPORTANT: REPACK INSULATION MATERIAL

IN SQUARE HOLE AROUND GAS LINE, INTE-

RIOR AND EXTERIOR OF FIREPLACE, TO SEAL.

Glass Doors

If glass doors are to be installed on these fireplaces, refer to specific installation instructions packed with the glass doors. Use only the doors that are listed for use with these fireplaces. Use of other non-listed glass door on these fireplaces may constitute a potential fire hazard and is not recommended.

CAUTION: CERTAIN GLASS DOORS OVERLAP

THE BLACK METAL FACING OF THE FIRE-

PLACE. IF THE FIREPLACE HAS BEEN FACED

WITH NONCOMBUSTIBLE MATERIALS, THERE

MIGHT NOT BE SUFFICIENT CLEARANCE TO

INSTALL THE GLASS DOORS OF YOUR

CHOICE. ENSURE ADEQUATE CLEARANCE IS

MAINTAINED AT ALL TIMES SO AS NOT TO

INTERFERE WITH THE INSTALLATION AND

OPERATION OF GLASS DOORS.

COLD CLIMATE INSULATION

If you live in a cold climate, it is especially important to seal all cracks around the fireplace opening with noncombustible material and wherever cold air could enter the room. Surrounding materials must be caulked where it meets the black metal facing of the fireplace to avoid cold air intrusion.

Use noncombustible caulking material only on fireplace facing to seal. Also, the outside air inlet duct should be wrapped with noncombustible insulation to minimize the formation of condensation. Do not place insulation materials on top of fireplace or against chimney sections.

Note: A 1"* air space must be preserved for all combustible materials extending for any continuous length adjacent to the chimney.

It is especially important to insulate between the studs of an outside chase cavity and under the floor if the floor is above ground level. Do not place insulation directly against the fireplace or chimney system.

FIREPLACE FINISHES

Mantels and Trim

It is sometimes best to frame your fireplace after it is positioned and the chimney is installed. Frame enclosure for chimney and fireplace with 2 x 4’s (or heavier) lumber.

Note: The header may rest on the two (2) metal top spacers on top of the unit but the header must not be notched to fit around the spacers.

These fireplaces may sit directly on a combustible surface. A 1"* air space is required between combustible framing and the chimney.

A 1" air space is required between combustible framing and fireplace outer wrapper. In

Canada, the minimum height for a combustible mantel is 18" (457 mm) above the fireplace opening. Figure 45 shows typical Canadian installations. Combustible mantels and trim may be installed 12" above the fireplace opening as per NFPA 211, Section 7-2.3.3. and

Figure 46. If a mantel is of a noncombustible material, it is exempt from these requirements as long as it does not interfere with the installation or operation of glass doors.

*Note: 2" clearance to combustibles required in Canada.

Figure 45

8" Max.

(203mm)

Combustible

Mantel

18" Min.

(457mm)

Fireplace

Opening

Canadian Installation

Finished

Wall

Header

Spacer

12"

Max.

Combustible

Mantel and Trim

12"*

Min.

8"*

Finished

Wall

1 1/2"

Header

Spacer

Fireplace

Opening

*Both Of These Dimensions Must Be At Least 18”

When An Unvented Gas Log Set Rated At 26,000

BTU Or Higher Is Used. (Maximum 40,000 BTU)

Typical Installation

Figure 46

Hearth Extensions and Wall Shields

A hearth extension must be installed with all fireplaces. It is to protect the combustible floor in front of the fireplace from both radiant heat and sparks. The hearth extension must extend 8" beyond both sides of the fireplace opening and 16" beyond the front ( see Figure

47 ). Use a hearth extension constructed of a durable noncombustible material having an equal or better (lower k value) insulating value of k = .84 BTU IN/FT 2 HR

°

F or a thermal resistance that equals or exceeds r = 1.19 HR

°

F FT 2 /BTU IN. With these values, determine the minimum thickness/material required using the formula and Page 17.

Note: Any noncombustible material whose k value is less than .84 or whose r value is more than 1.19 is acceptable.

If the fireplace is installed on a combustible floor, use the metal safety strips (provided) on the floor extending half under the fireplace and half under the hearth extension

(refer to Figures 6 & 7).

A wall shield is required where a continuous perpendicular side wall is within 12" of the fireplace opening (

Figure 48 ). Use a 36" W x

36" H wall shield constructed of a durable, noncombustible material having an equal or better (lower k value) insulating value than k =

.54 BTU IN/FT 2 HR

°

F. At no time may a perpendicular side wall be located closer than

9" from the fireplace opening.

If fireplace is installed diagonally across a 90

° corner; no wall shields are required.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Hearth Extension Dimensions

A

B

C

D

16"

35"

8"

51"

Note: To convert inches to millimeters divide by 0.03937

Figure 47

C

B

D

C

A

Methods of Determini

ng Hearth Extension and Wall Shield

Equivalents - To determine the thickness required for the alternate material when either the “k” value or “r” value is known, use either the

k formula or r formula.

Example: If Micore 160 is to be used for the hearth extension fireplace, how thick must this material be?

k

M r

M

T

M

T

S

= k value per inch of alternate material

= r value per inch of alternate material

= minimum thickness required for alternate material

= standard thickness of the

alternate material

k

L r

L

T

L

= k value per inch of listed material

= r value per inch of listed material

= minimum thickness of listed material

Note: An asterix “*” indicates, it is a value taken from Table 1.

Using the k formula:

Minimum k-value (per Inch) of thickness of = alternate material (k

M

) x alternate k-value (per inch) material (T

M

) of listed material (k

M

)

Specified min.

thickness of listed material (T

L

)

T

M

(inches) =

k

M

*.84

x T

L

Answer - The minimum required thickness of the Micore 160 is .417”, therefore round up to nearest standard thickness available which is 1/2”.

T

M

(inches) = *.35

*.84

.416 (inches) = .416

T

M

(inches) =

r

L

r

M

T

M

(inches) = *1.19

*2.86

.416 (inches)= .416

x x

1"

1"

Answer - The minimum required thickness of the Micore 160 is .417”, therefore round up to nearest standard thickness available which is 1/2”.

Using the r formula:

Minimum r-value (per Inch) thickness of = of listed material alternate material r-value (per inch) of alternate material x

Specified min.

thickness of listed material x x x

T

L

1"

1"

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Listed Material k (per inch) r (per inch) Listed Min.Thickness

Listed Material .84

K

L

1.19

r

L

1

"

T

L

** Approved Alternate Materials for Floor/Hearth Protection

AlternativeMaterials Thermal Values MinimumThickness

(rounded to nearest 1/8 inch)

Kaowool M Board

Micore 160™

U.S. Gypsum

Micore 300™

U.S. Gypsum k (per inch)

K

M

.47

.35

.46

r (per inch)

r

M

2.13

2.86

2.17

Min. Thickness

T

M

.56" (1/2")

.42" (3/8")

.55" (1/2")

Durock™ Cement Board

U.S. Gypsum

Hardibacker™

Hardibacker 500™

Cultered Stone Hearthstone™

Wonderboard

Super Firetemp M

Johns-Manville

Super Firetemp L

Johns-Manville

Face brick

Common brick

Cement mortar

Ceramic tile

Marble

Table 1

1.92

1.95

2.30

2.82

3.23

.61

.54

9.00

5.00

5.00

12.5

~11

.52

.513

.435

.355

.31

1.64

1.85

.111

.20

.20

.08

~.09

2.29" (2-1/4")

2.32" (2-3/8")

2.74" (2-3/4")

3.36" (3-3/8")

3.85" (3-7/8")

.73" (3/4")

.64" (5/8")

10.71" (10-3/4")

5.95" (6")

5.95" (6")

14.88" (14-7/8")

13.10" (13-1/8")

** If the hearth extension material(s) that is intended to be used is NOT listed on Table 1, the material can still be used if the material(s) is noncombustible.

However, the manufacturer of the material must provide either the listed kvalue per inch or r-value per inch with listed thickness so that the minimum thickness required for the hearth can be calculated (per instructions on this

Page and/or as specified in the NFI Certification manuals).

Note: Also see NFI (National Fireplace Institute) Certification Manuals showing other acceptable calculation methods and acceptable alternate materials which can be used.

17

18

30"

24"

Wall Shield Required

Where Less Than 12"

C

D

B

C

A

Figure 48

Calculating Minimum Thickness if Multiple

Materials are Used

At times it is important to know what combination of materials are acceptable for use as floor protection. The “R values” are used to determine acceptable combinations of materials because “R values” are additive where r and k values are not.

“R value” = 1/k = “r” x thickness of material used

Example: Given that the required “R value” for a suitable floor protector used must be equal to or greater than:

“R” = r

L

x T

L

= 1.19 x 1” = 1.19.”

If it is desired to elevate a marble hearth extension to a level of 5” or more above the floor surface. What combination of noncombustible materials can be used to accomplish this?

If common brick is used so that the 3 1/2” dimension is the height, “R” for the common brick becomes:

brick

“R”

M

= r

M

x T

S

= 0.20 x 3 1/2" = .70

Using 1/2” of mortar to set the brick, “R” for the mortar is calculated as follows:

mortar

“R”

M

= r

M

x T

S

= 0.20 x 1/2" = .10

Next, a 3/4" marble slab set in 1/2" mortar covers the brick, “R” for the marble and mortar becomes:

marble

“R”

M

= r

M

x T

S

= 0.05 x 3/4" = .038

mortar

“R”

M

= r

M

x T

S

= 0.20 x 1/2" = .10

The sum of all “R values” is: .70 + .10 +. 038

+ .10 = .938

This would NOT be an acceptable combination of material for the hearth extension since the total calculated “R value” of the materials used is under the required “R value” of 1.19. An additional layer of insulating materials must be used.

Note: Also see NFI Certification Manuals for expanded explanation on calculating “R values” when multiple materials are used.

WARNING: THE CRACK BETWEEN THE

FIREPLACE AND THE HEARTH EXTEN-

SION MUST BE SEALED WITH A NON-

COMBUSTIBLE MATERIAL.

WARNING: WHEN INSTALLING HEARTH

EXTENSION IN FRONT OF A NON-CIRCU-

LATING FIREPLACE MODEL, THE FIRE-

PLACE MUST BE RAISED IF HEIGHT OF

HEARTH EXTENSION EXCEEDS 7" ABOVE

THE BOTTOM OF FIREPLACE (

7 1/2"

FIGURE 49 ).

Max. Thickness Of Hearth Extension When

Non-Circulating Models Are On The Floor

Figure 49

WARNING: WHEN INSTALLING THE

HEARTH EXTENSION BE CAREFUL NOT

TO BLOCK THE HEAT-CIRCULATING AIR

INLET GRILL ON CIRCULATING MODELS.

WARNING: WHEN INSTALLING HEARTH

EXTENSION IN FRONT OF A CIRCULAT-

ING FIREPLACE MODEL, THE FIREPLACE

MUST BE RAISED IF HEIGHT OF HEARTH

EXTENSION EXCEEDS 2" ABOVE BOTTOM

OF FIREPLACE (

FIGURE 50 ).

5 1/2"

2"

Max. Thickness Of Hearth Extension When

Circulating Models Are On The Floor

Figure 50

Secure the hearth extension to the floor to prevent possible shifting.

FINISH TO YOUR TASTE

There are a wide variety of “finished looks” for these fireplaces, from formal wall decor with elaborate mantels to rustic wood paneling or warm brick facings.

Only noncombustible materials like stone, tile, brick, etc., may overlap the black front facing.

Do not extend these materials beyond the black facing and into the firebox area. Be sure not to interfere with the installation and operation of glass doors or block the upper or lower grilles.

Seal all joints between the black facing and wall surrounds to prevent air intrusion. Use noncombustible caulking material only to seal the black metal facing to the surround material on the finished wall.

Combustible materials may project beyond the sides of the fireplace opening as long as they are kept within the shaded areas illustrated in

Figure 51.

Combustible

Materials

Allowed In

Shaded Area

“Safe Zone”

12"

Fireplace

7"

45

°

1"

12"

7"

Min. Distance To

Protected Side Wall

Min. Distance To

Unprotected Side Wall

Figure 51

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

INSTALLATION COMPONENTS

The following items are available for use in the installation of this appliance.

(FBK-200 Models Only)

Firestop Spacer (30

°

)

Firestop Spacer (30

°

)

63L30

63L32

Chimney Section

F8FS30

F8FS30-2**

Canadian

Chimney Section

63L10

63L13

63L14

63L15

62L92

62L93

FTF8-12

FTF8-18

FTF8-36

FTF8-48

FTF8-18C

FTF8-36C

Forced Air Blower Kits

-Single Speed

-Variable Speed

80L84

80L85

FBK-100

FBK-200

Offset/ Return

Package (30

°

) 63L22 FTF8-ES30

Flashing

63L38

63L39

F8F6

F8F12

Outside Combustion Air Kits

(with duct)

(without duct)

FOAK

FOAK-LD

Stabilizer 63L25 FTF8-S4

Round Termination 63L42 FTF8-CTD

Firestop Spacer (Flat)

Firestop Spacer (Flat)

63L29

63L31

F8FS

F8FS-2**

Storm Collar 63L59 FSC

Unit Mounted

Blower Switch Kit

Shipping Weight

91L48 FUBSK

175 lbs.

Combination

Offset/Return Elbow 63L28 FTF8-OR15

Cold Climate Kits 63L61 FTF8-CCK1-LD**

**Note: 2" clearance required for Canadian

Installation - as applicable.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

19

INSTALLATION COMPONENTS

Chase Termination

(Square) 63L51 FTF8-CT2

Chase Termination

(Square) 63L48 FTF8-CT1

Attic Shield Assembly 63L67 FTF8-FSAS**

Chase Termination

(Round) 63L45 FTF8-CTDT

Locking Band 63L60 FLB

**Note: 2" clearance required for Canadian

Installation - as applicable.

20

The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products.

Consult your local distributor for fireplace code information.

Printed in U.S.A. © 2007 by LENNOX HEARTH PRODUCTS

P/N 700,040M REV. A 02/2008

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

LHP

1110 West Taft Avenue

Orange, CA 92865

advertisement

Key Features

  • EPA-certified, meeting strict emissions standards
  • Optional glass doors for added safety and efficiency
  • Heavy-duty steel construction for long-lasting durability
  • Fully assembled and ready to install

Related manuals

Frequently Answers and Questions

What are the dimensions of the Superior BC-36-2?
The Superior BC-36-2 has an overall size of 36" wide x 28" high x 23" deep.
What type of fuel does the Superior BC-36-2 use?
The Superior BC-36-2 uses solid fuel only, such as firewood or manufactured logs.
How much heat output does the Superior BC-36-2 produce?
The Superior BC-36-2 produces up to 30,000 BTUs of heat, providing ample warmth for most rooms.
Does the Superior BC-36-2 come with a warranty?
Yes, the Superior BC-36-2 comes with a limited lifetime warranty.
Can I install the Superior BC-36-2 myself?
Yes, the Superior BC-36-2 is designed to be easy to install. However, it is recommended that you consult with a qualified professional if you are not comfortable installing it yourself.