advertisement
![Trane Tracer CH530 User manual | Manualzz Trane Tracer CH530 User manual | Manualzz](http://s3.manualzz.com/store/data/022397080_1-4b8108a5e7111afcdeecaf70bcc0dc84-360x466.png)
User Guide
Tracer CH530™
Control System for Chillers
RTWD/RTUD 060-250
RLC-SVU05A-E4
General information
Foreword
These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane
CH530 chiller control system on chillers. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up.
Warnings and cautions
Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel.
WARNING!
: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION!
: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.
Safety recommendations
To avoid death, injury, equipment or property damage, the following recommendations should be observed during maintenance and service visits:
1. Disconnect the main power supply before any servicing on the unit.
2. Service work should be carried out only by qualified and experienced personnel.
Reception
On arrival, inspect the unit before signing the delivery note.
Reception in France only:
In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify
Trane Epinal Operations - Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery.
Reception in all countries except
France:
In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane
Epinal Operations - Claims team.
Note
: for deliveries in France, even concealed damage must be looked for at delivery and immediately treated as visible damage.
© 2009 Trane
RLC-SVU05A-E4
RLC-SVU05A-E4
General information
Warranty
Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer.
Maintenance contract
It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment.
Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.
Training
To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.
3
4
Contents
General Information
Overview
DynaView Interface
Display Screens
Diagnostics
TechView Interface
Software Download
6
8
28
54
55
2
5
RLC-SVU05A-E4
RLC-SVU05A-E4
Overview
The Trane CH530 control system that runs the chiller consists of several elements:
• The main processor collects data, status, and diagnostic information and communicates commands to the LLID (for Low
Level Intelligent Device)
bus. The main processor has an integral display (DynaView).
• LLID bus. The main processor communicates to each input and output device (e.g. temperature and pressure sensors, low voltage binary inputs, analog input/output) all connected to a four-wire bus, rather than the conventional control architecture of signal wires for each device.
• The communication interface to a building automation system
(BAS).
• A service tool to provide all service/maintenance capabilities.
Main processor and service tool
(TechView) software is downloadable from
www.Trane.com
. The process is discussed later in this section under TechView Interface.
DynaView provides bus management. It has the task of restarting the link, or filling in for what it sees as "missing" devices when normal communications has been degraded. Use of
TechView may be required.
The CH530 uses the IPC3 protocol based on RS485 signal technology and communicating at 19.2 Kbaud to allow 3 rounds of data per second on a 64-device network.
Most diagnostics are handled by the
DynaView. If a temperature or pressure is reported out of range by a LLID, the DynaView processes this information and calls out the diagnostic. The individual LLIDs are not responsible for any diagnostic functions.
Note
: It is imperative that the CH530
Service Tool (TechView) be used to facilitate the replacement of any
LLID or reconfigure any chiller
component.
Controls Interface
DynaView (picture on cover)
Each chiller is equipped with the
DynaView interface. DynaView has the capability to display additional information to the advanced operator including the ability to adjust settings. Multiple screens are available and text is presented in multiple languages as factoryordered or can be easily downloaded online.
TechView
TechView can be connected to the
DynaView module and provides further data, adjustment capabilities, diagnostics information, downloadable software, and downloadable languages.
5
6
DynaView Interface
Power Up
On power-up, Dynaview will progress through 3 screens.
The first screen (Figure 1) will display for 3-10 seconds. This screen will give the status of the
Application software, the Boot
Software P/N, selftest results and the application part number. The contrast is adjustable from this screen. The message "Selftest passed" may be replaced with "Err2:
RAM Error" or "Err3: CRC Failure"
Note that the Application and Boot software numbers will vary according to the unit type.
If no application is found, the screen
(Figure 2) will display instead of
Figure 1.
Figure 1
Figure 2
RLC-SVU05A-E4
RLC-SVU05A-E4
DynaView Interface
The second screen (Figure 3) will display for 15-25 seconds. If a valid configuration is present, "Tracer
CH530" will also be displayed. If the
MP configuration is found to be invalid, "MP: Invalid Configuration" is displayed indefinitely. Contact your local Trane service technician.
The third screen is the first screen of the application.
Figure 3
Figure 4
7
8
Figure 5 - Basic Screen Format
DynaView Interface
The display on DynaView is a
1/4 VGA display with a resistive touch screen and an LED backlight.
The display area is approximately
4 inches wide by 3 inches high
(102mm x 60mm).
CAUTION!
Equipment Damage! Putting excessive pressure on the touch screen could cause damage. It takes less than 7 kg of force to break the screen.
In this touch screen application, key functions are determined completely by software and change depending upon the subject matter currently being displayed. The basic touch screen functions are outlined below.
Radio Buttons
Radio buttons show 1 menu choice among 2 or more alternatives, all visible. The possible selections are each associated with a button. The selected button is darkened, presented in reverse video to indicate it is the selected choice.
The full range of possible choices as well as the current choice is always in view.
Spin Value Buttons
Spin values are used to allow a variable setpoint to be changed, such as leaving water setpoint. The value increases or decreases by touching the (+) or (-) arrows.
Action Buttons
Action buttons appear temporarily and provide the user with a choice such as Enter or Cancel.
File Folder Tabs
File folder tabs are used to select a screen of data. The tabs are in
1 row across the top of the display.
The user selects a screen of information by touching the appropriate tab.
Display Screens
The main body of the screen is used for description text, data, setpoints, or keys (touch sensitive areas). The
Chiller Mode is displayed here.
A double arrow pointing to the right indicates more information is available about the specific item on that same line. Pressing it will bring you to a sub-screen that will present the information or allow changes to settings.
9
RLC-SVU05A-E4
DynaView Interface
The bottom of the screen (7) is present in all screens and contains the following functions. The contrast (8,9) may require readjustment at ambient temperatures significantly different from those present at last adjustment. The other functions are critical to machine operation. The
AUTO and STOP keys are used to enable or disable the chiller. The key selected is in black (reverse video). The chiller will stop when the STOP key is touched and after completing the Run Unload mode.
Touching the AUTO key will enable the chiller if no diagnostic is present. (A separate action must be taken to clear active diagnostics.)
The AUTO and STOP keys take precedence over the Enter and
Cancel keys. (While a setting is being changed, AUTO and STOP keys are recognized even if Enter or
Cancel has not been pressed.) The
ALARMS button appears only when an alarm is present, and blinks (by alternating between normal and reverse video) to draw attention to a diagnostic condition. Pressing the
ALARMS button takes you to the corresponding tab for additional information.
Note: screens may differ according to unit type or configuration. They should be considered as examples.
Keypad/Display Lockout
Feature
Note
: The DynaView display and
Touch Screen Lock screen is shown above. This screen is used if the
Display and touch screen and lock feature is enabled. Thirty minutes after the last keystroke, this screen is displayed and the Display and
Touch Screen is locked out until the sequence "159 <ENTER>" is
pressed. Until the proper password is entered, there will be no access to the DynaView screens including all reports, setpoints, and
Auto/Stop/Alarms/Interlocks. The password "159" can not be changed from either DynaView or TechView.
For setting changes, use the password "314 <ENTER>".
Figure 6 - Keypad
1
System/Circuit Selection Buttons
On some report and setting screens, radio buttons on the top of the screen shall be presented to allow the user to select subscreens based on system-level data and per-circuit data.
For single-circuit units with system/circuit selection buttons, the buttons shall be labeled (in English)
“System” and “Ckt”. For two-circuit units with system/circuit selection buttons, the buttons shall be labeled “System”, “Ckt1”, and
“Ckt2”.
RLC-SVU05A-E4 9
10
DynaView Interface
Main Screens
The Main screen is a “dashboard” of the chiller. High level status information is presented so that a user can quickly understand the mode of operation of the chiller.
The Chiller Operating Mode will present a top level indication of the chiller mode (i.e. Auto, Running,
Inhibit, Run Inhibit, etc.) The
“additional info” icon will present a subscreen that lists in further detail the subsystem modes.
The Main screen shall be the default screen. After an idle time of
30 minutes the CH530 shall display the Main screen with the first data fields. The remaining items (listed in the following table) will be viewed by selecting the up/down arrow icons.
Figure 7 - Main screen
Chiller Mode:
Circuit 1 Mode:
Circuit 2 Mode:
Evap Ent / Lvg Water Temp:
Cond Ent / Lvg Water Temp:
Active Chilled Water Setpoint:
Running
Running - Limit
Auto
12 / 7 C
30 / 35 C
7 C
RLC-SVU05A-E4
DynaView Interface
Table 1 - Main Screen Data Fields Table
Description
1.
Chiller Mode (>> submodes)
2.
3.
4.
5.
Circuit 1 Mode (>> submodes)
Circuit 2 Mode (>> submodes)
Evap Ent/Lvg Water Temp
Cond Ent/Lvg Water Temp
6.
7.
8.
9.
10.
11.
12.
13.
14.
Active Chilled Water Setpoint (>>source) (>> front panel setpoint) from arbitration setpoint screen
Active Hot Water Setpoint (>>source) (>> front panel setpoint) - from arbitration setpoint screen
Average Line Current
Active Current Limit Setpoint (>> source) (>> front panel setpoint) - from arbitration setpoint screen
Active Ice Termination Setpoint
(>>front panel setpoint)
Outdoor Air Temperature
Software Type
Software Version
Units
enumeration enumeration enumeration
F / C
F / C
F / C
F / C
%RLA
% RLA
F / C
F / C enumeration
Resolution
0.1
0.1
0.1
0.1
1
1
0.1
0.1
RTWD / RTUD
X.XX
Dependencies
Water Cooled only (i.e. RTWD or
RTUD with ACFC=None)
Hot Water Option installed only
If Ice Building Option is installed
Only if OA sensor is installed
Chiller Mode
The machine-operating mode indicates the operational status of the chiller. A subscreen with additional mode summary information will be provided by selection of an additional information icon (>>). The operating mode line will remain stationary while the remaining status items scroll with the up/down arrow keys.
Active Chilled Water Setpoint and
Active Hot Water Setpoint
The active chilled water setpoint is the setpoint that is used in cool mode. The active hot water setpoint is the setpoint that is used in heat mode. Both setpoints result from the logical hierarchy of setpoint arbitration by the main processor.
The water setpoint will be displayed to 0.1 degrees Fahrenheit or
Celsius.
Touching the double arrow to the left of the Active Chilled Water
Setpoint or to the left of the Active
Hot Water Setpoint will take the user to the respective active water setpoint arbitration sub-screen.
Figure 8 - Active Chilled Water Subscreen
:
Active Water Setpoint Arbitration
Subscreen
The active water setpoint is that setpoint to which the unit is currently controlling. It is the result of arbitration between the front panel, BAS, and external setpoints.
The active chilled water water setpoint may also be subjected to a form of chilled water reset.
RLC-SVU05A-E4 11
DynaView Interface
Other Active Setpoints
The Active Current Limit Setpoint will behave the same way as the
Active Chilled Water Setpoint, with the exception that Active Current
Limit Setpoint does not have an external source.
12 RLC-SVU05A-E4
DynaView Interface
Chiller Level Mode
Top Level Mode
Stopped
Stopped Sub Modes
Local Stop
Immediate Stop
No Circuits Available
Diagnostic Shutdown - Manual Reset
Cond Pmp Strt Dly (Head Pres Ctrl) min:sec
Chiller Operating Mode
The machine-operating mode indicates the operational status of the chiller.
A subscreen with additional mode summary information will be provided by selection of an additional information icon (>>). The operating mode line will remain stationary while the remaining status items scroll with the up/down arrow keys.
Table 2 - Main screen menu, Chiller Operating Modes - Top Level
Description
The chiller is not running either circuit, and cannot run without intervention.
Description
Chiller is stopped by the DynaView Stop button command- cannot be remotely overridden.
Chiller is stopped by the DynaView Immediate Stop (by pressing the Stop then Immediate Stop buttons in succession) - previous shutdown was manually commanded to shutdown immediately.
The entire chiller is stopped by circuit diagnostics or lockouts that may automatically clear.
The chiller is stopped by a diagnostic that requires manual intervention to reset.
Only possible when Condenser Head Pressure Control option is enabled and the condenser pump is being manually commanded to run - this wait may be necessary due to the Head Pressure control device's stroke time.
Top Level Mode
Chiller Level Mode
Run Inhibit
Run Inhibit Sub Modes
No Circuits Available
Ice Building Is Complete
Ice to Normal Transition
Start(ing is)* Inhibited by BAS (Building
Automation System)*
Start(ing is)* Inhibited by External Source
Diagnostic Shutdown - Auto Reset
Waiting for BAS Communications (to Establish
Operating Status)*
Start(ing is)* Inhibited by Low Ambient
Temp(erature)*
Start(ing is)* Inhibited by Local Schedule
Description
The chiller is currently being inhibited from starting (and running), but may be allowed to start if the inhibiting or diagnostic condition is cleared.
Description
The entire chiller is stopped by circuit diagnostics or lockouts that may automatically clear.
The chiller is inhibited from running as the Ice Building process has been normally terminated on the evaporator entering temperature. The chiller will not start unless the ice building command (hardwired input or Building Automation System command) is removed or cycled.
The chiller is inhibited from running for a brief period of time if it is commanded from active ice building mode into normal cooling mode via the ice building hardwired input or Tracer. This allows time for the external system load to "switchover" from an ice bank to the chilled water loop, and provides for a controlled pull down of the loop's warmer temperature. This mode is not seen if the ice making is automatically terminated on return brine temperature per the mode below.
Chiller is stopped by Tracer or other BAS system.
The chiller is inhibited from starting or running by the "external stop" hardwired input.
The entire chiller is stopped by a diagnostic that may automatically clear.
The chiller is inhibited because of lack of communication with the BAS. This is only valid 15 minutes after power up.
The chiller is inhibited based on the outdoor air temperature.
The chiller is inhibited from starting based on the local time of day scheduling (option)
RLC-SVU05A-E4 13
14
DynaView Interface
Chiller Level Mode
Top Level Mode
Auto
Auto Sub Modes
Waiting For Evap(orator)* Water Flow
Waiting For A Need To Cool
Waiting For A Need To Heat
Power Up Delay Inhibit: min:sec
Chiller Level Mode
Top Level Mode
Waiting to Start
Waiting to Start
Sub Modes
Waiting For Condenser Water Flow
Cond Water Pump PreRun Time min:sec
Cond Pmp Strt Dly (Head Pres Ctrl) min:sec
Cprsr Strt Delay (Head Pres Ctrl) min:sec
Top Level Mode
Running
Chiller Level Mode
Running Sub Modes
Maximum Capacity
Capacity Control Softloading
Current Control Softloading
Top Level Mode
Chiller Level Mode
Running - Limit
Running - Limit
Sub Modes
<none applicable>
Description
The chiller is not currently running but can be expected to start at any moment given that the proper conditions and interlocks are satisfied.
Description
The unit will wait up to 20 minutes in this mode for water flow to be established per the flow switch hardwired input.
The chiller will wait indefinitely in this mode, for a leaving water temperature higher than the Chilled
Water Setpoint plus some control dead-band.
The chiller will wait indefinitely in this mode, for a leaving water temperature lower than the Hot Water
Setpoint plus some control dead-band.
On Power up, the chiller will wait for the Power Up Delay Timer to expire.
Description
The chiller is not currently running and there is a call for cooling but the lead circuit start is delayed by certain interlocks or proofs. Further information is provided by the sub-mode:
Description
The chiller will wait up to 4 minutes in this mode for condenser water flow to be established per the flow switch hardwired input.
The chiller will wait up to 30 minutes (user adjustable) in this mode for to allow the condenser water loop to equalize in temperature
Only possible when Condenser Head Pressure Control option is enabled, this wait may be necessary due to the Head Pressure control device's stroke time.
Only possible when Condenser Head Pressure Control option is enabled, this wait may be necessary due to the Head Pressure control device's stroke time
Description
At least one circuit on the chiller is currently running.
Description
The chiller is operating at its maximum capacity.
The control is limiting the chiller loading due to capacity based softloading setpoints.
The chiller is running, and loading of individual compressors may be limited by a gradual filter of the chiller's softloading current limit setpoint. The starting current limit and the settling time of this filter is user adjustable as part of the current control softload feature. The mode will be displayed as long as the Current Control Softloading limit is ramping or "settling".
Description
At least one circuit on the chiller is currently running, but the operation of any of the circuits on the chiller is being actively limited by a chiller level limit. Other sub modes that apply to the Chiller
Running top level modes may also be displayed here. Refer to the list of circuit limit modes for circuit limits that will cause display of this Chiller Level Running Limit mode.
Description
Design Note: Hot Start Limit is applied and annunciated at a circuit level, even though it is based on the chiller's leaving water temperature.
RLC-SVU05A-E4
DynaView Interface
Top Level Mode
Chiller Level Mode
Shutting Down
Shutting Down Sub Modes
Operational Pumpdown
Evaporator Water Pump Off Delay: MIN:SEC
Cond Water Pump Off Delay: MIN:SEC
Top Level Mode
Chiller Level Mode
Misc.
Misc. Sub Modes
Manual Evap(orator)* Water Pump Override
Diagnostic Evap Water Pump Override
Diagnostic Cond Water Pump Override
Local Schedule Active
Manual Condenser Water Pump Override
Manual Compressor Control Signal
Night Noise Setback
Hot Water Control
Chilled Water Control
Ice Building
Description
The chiller is still running but shutdown is imminent. The chiller is going through a compressor rununload or extended operational pumpdown of the lag circuit/compressor (or all circuits simultaneously).
Description
The lag circuit (or all circuits) is in the process shutting down by performing an operational pumpdown just prior to stopping the circuit's compressor. The EXV is commanded closed. Pumpdown will terminate when both the liquid level and the evap pressure are low (below specific criteria) or after a specific time has expired.
The Evaporator water pump is continuing to run past the shutdown of the compressors, executing the pump off delay timer.
The Condenser water pump is continuing to run past the shutdown of the compressors, executing the pump off delay timer.
Description
These sub modes may be displayed in most of the top level chiller modes
Description
The Evaporator water pump relay is on due to a manual command.
The Evaporator water pump relay is on due to a diagnostic.
The Condenser water pump relay is on due to a diagnostic.
The local time of day scheduler (option) is operational and could automatically change modes or setpoints as scheduled
The condenser water pump relay is on due to a manual command.
Chiller capacity control is being controlled by DynaView or TechView.
The Night Noise Setback feature has been activated. If the unit is running, fans will be running at low speed.
These modes are mutually exclusive and they indicate that the chiller is controlling to the active hot water setpoint, the active chilled water setpoint, or the active ice termination setpoint respectively.
RLC-SVU05A-E4 15
16
Circuit Level Mode
Top Level Mode
Stopped
Stopped Sub Modes
Diagnostic Shutdown - Manual Reset
Front Panel Circuit Lockout
External Circuit Lockout
Circuit Level Mode
Top Level Mode
Run Inhibit
Run Inhibit
Sub Modes
Diagnostic Shutdown - Auto Reset
Low Oil Flow Cool Down Time mn:sc
Restart Inhibit min:sec
Top Level Mode
Circuit Level Mode
Auto
Auto Sub Modes
Calibrating EXV
Top Level Mode
Circuit Level Mode
Waiting to Start
Waiting to Start
Sub Modes
Start Inhibited Waiting For Oil
Waiting For EXV Preposition
DynaView Interface
Table 2 - Circuit Level Operating Modes
Description
The circuit is not running, and cannot run without intervention.
Description
The circuit has been shutdown on a latching diagnostic.
The circuit is manually locked out by the circuit lockout setting - the nonvolatile lockout setting is accessible through either the DynaView or TechView.
The respective circuit is locked out by the external circuit lockout binary input.
Description
The given circuit is currently being inhibited from starting (and running), but may be allowed to start if the inhibiting or diagnostic condition is cleared.
Description
The circuit has been shutdown on a diagnostic that may clear automatically.
The cool-down period is necessary to allow the compressor rotors to cool after starts.
The compressor (and therefore, its circuit) is currently unable to start due to its restart inhibit timer. A given compressor is not allowed to start until 5 minutes (adj) has expired since its last start, once a number of "free starts" have been used up.
Description
The circuit is not currently running but can be expected to start at any moment given that the proper conditions are satisfied.
Description
This submode is displayed when the EXV is performing a calibration. A calibration is only performed when the chiller is not running and never more frequently than once every 24 hours
Description
The chiller is going through the necessary steps to allow the lead circuit to start.
Description
The compressor (and thus its circuit) will wait up to 2 minutes in this mode for oil level to appear in the oil tank.
The Chiller will wait for the time it takes the EXV to get to its commanded pre-position prior to starting the compressor. This is typically a relatively short delay and no countdown timer is necessary (less than 15 seconds)
RLC-SVU05A-E4
DynaView Interface
Circuit Level Mode
Top Level Mode
Running
Running
Sub Modes
Establishing Min(imum)* Cap(acity)* - Low
Diff(errential)* Pressure
Description
The compressor on the given circuit is currently running.
Description
Establishing Min Cap - High Disch Temp
The circuit is experiencing low system differential pressure and its compressor is being force loaded, irregardless Chilled Water Temperature Control, to develop pressure sooner.
The circuit is running with high discharge temperatures and its compressor is being forced loaded to its step load point, without regard to the leaving water temperature control, to prevent tripping on high compressor discharge temperature.
The following modes annunciations have not been implemented as a display but are actually operational in the EXV liquid level control algorithm. The modes included here as possible future annunciated modes
EXV Controlling Differential Pressure
EXV Controlling for Low Evaporator Pressure
Liquid level control of the Electronic Expansion Valve has temporarily been suspended. The EXV is being modulated to control for a minimum differential pressure. This control implies low liquid levels and higher approach temperatures, but only as is necessary to provide minimum oil flow for the compressor until the condenser water loop can warm up to approx 50F. (Future mode display - display of mode not implemented in Phase 1 or 2 although present in algorithms.)
Liquid level control of the Electronic Expansion Valve has temporarily been suspended. The EXV is being modulated to control for a minimum evaporator pressure that is based of the pressure of the
Low Refrigerant Temperature Cutout. This control will tend to increase the liquid level above the setpoint or to open the valve more quickly than liquid level control can, in order to avoid an LRTC trip.
It is most often invoked transiently to help open the EXV in the event of rapidly falling liquid level and rapidly declining evaporator pressures. (Future Mode display, - display of mode not implemented in
Phase 1 or 2 although present in algorithms.)
Circuit Level Mode
Top Level Mode Description
Running - Limit
The circuit, and compressor are currently running, but the operation of the chiller/compressor is being actively limited by the controls. Further information is provided by the sub-mode.* See the section below regarding criteria for annunciation of limit modes
Running - Limit
Sub Modes
Description
Current Limit
High Condenser Pressure Limit
The compressor is running and its capacity is being limited by high currents. The current limit setting is 120% RLA (to avoid overcurrent trips) or lower as set by the compressor's "share" of the active current limit (demand limit) setting for the entire chiller.*
The circuit is experiencing condenser pressures at or near the condenser limit setting. Compressors on the circuit will be unloaded to prevent exceeding the limits.*
Low Evaporator Rfgt Temperature Limit
Hot Start Limit
The circuit is experiencing saturated evaporator temperatures at or near the Low Refrigerant
Temperature Cutout setting. Compressors on the circuit will be unloaded to prevent tripping. *
This mode will occur if the leaving evaporator water temperature exceeds 75F (for SW version 6.30
and earlier) or 90 F (for software 7.01 and later) at the point at which the step load for the respective circuit would be desired. This is often the case in a high water temperature pulldown. While in this mode, no compressor on the circuit will be allowed to load past its minimum load capacity step, but it will not inhibit other compressors from staging on. This mode is necessary to prevent nuisance trips due to Compressor Overcurrent or High Pressure Cutout. Reasonable pulldown rates can still be expected despite this limit, since the compressor's capacity even at partial load is much greater at high suction temperatures.
RLC-SVU05A-E4 17
18
DynaView Interface
Top Level Mode
Circuit Level Mode
Shutting Down
Preparing Shutdown
Sub Modes
Description
The circuit is preparing to de-energize the compressor.
Description
Operational Pumpdown
The circuit is in the process shutting down by performing an operational pumpdown just prior to stopping the last running compressor. The EXV is commanded closed. Pumpdown will terminate when both the liquid level and the evap pressure are low (below specific criteria) or after a specific time has expired.
The compressor is in its run unload time. The number of seconds remaining in run unload is shown in the submode. The run unload time must expire before the compressor will shut down.
Compressor Unloading: MIN:SEC
Top Level Mode
Circuit Level Mode
Misc.
Description
These sub modes may be displayed in most of the top level circuit modes
Description Misc. Sub Modes
Service Pumpdown The circuit is currently performing a service pumpdown.
Restart Time Inhibit: MIN:SEC If there is accumulated Restart Inhibit Time, it must expire before a compressor is allowed to start.
* Mode text strings in parenthesis for TechView display only - available space for DynaView text strings is limited.
RLC-SVU05A-E4
DynaView Interface
Reports Screen
The Reports tab will allow a user to select from a list of possible reports headings (i.e. Custom, ASHRAE
Guideline 3, Refrigerant, etc.).
Each report will generate a list of status items as defined in the following tables.
Figure 9 - Reports screen
Main
Evaporator
Condenser
Compressor
ASHRAE Chiller Log
Historic Diagnostics
Reports Settings
Auto
Stop
Alarms
Table 3- Reports Screen
Report Menu
Description
1.
Evaporator
2. Condenser
3. Compressor
4. ASHRAE Chiller Log
5. Historic Diagnostics
Report name: System Evaporator
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description
1.
Evap Entering Water Temperature
2. Evap Leaving Water Temperature
3. Evap Water Flow Switch Status
Report name: Circuit Evaporator
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description
1.
Evap Entering Water Temperature
2. Evap Leaving Water Temperature
3. Evap Sat Rfgt Temp
4. Suction Pressure
5. Evap Approach Temp
6. Evap Water Flow Switch Status
7.
Expansion Valve Position
8. Expansion Valve Position Steps
9. Evaporator Liquid Level
Resolution
+ XXX.X
+ XXX.X
(Flow, No Flow)
Units
Temperature
Temperature
Enum
Dependencies
Resolution
+ XXX.X
+ XXX.X
+ XXX.X
XXX.X
+ XXX.X
(Flow, No Flow)
XXX.X
XXXX
XX.X
Units
Temperature
Temperature
Temperature
Pressure
Temperature
Enum
Percent
Steps
Height
Dependencies
RLC-SVU05A-E4 19
20
DynaView Interface
Report name: System Condenser
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description
1.
Cond Entering Water Temp
2. Cond Leaving Water Temp
3. Cond Water Flow Switch Status
4. Outdoor Air Temperature
5. Cond Head Pressure Ctrl Command
Report name: Circuit Condenser
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description
1.
Cond Entering Water Temp
2. Cond Leaving Water Temp
3. Condenser Air Flow
4. Cond Inverter Speed
5. Outdoor Air Temperature
6. Cond Water Flow Switch Status
7.
Cond Sat Rfgt Temp
8. Cond Rfgt Pressure
9. Differential Pressure
10. Cond Approach Temp
Report name: System Compressor
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description
1.
Average Line Current
2. Unit Volts
3. Unit Running Time
4. Power Demand
5. Power Demand Time Period
6. Energy Consump-Resettable
7.
Time of Last Reset
8. Energy Consump-NonReset
Resolution
+ XXX.X
+ XXX.X
(Flow, No Flow)
+ XXX.X
XXX
Units
Temperature
Temperature
Enum
Temperature
%
Dependencies
Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
Water Cooled only (i.e. RTWD or RTUD with ACFC=None))
Only if OA sensor is installed
Only if Cond Head pressure control option is installed
Resolution
+ XXX.X
+ XXX.X
XXX
XXX
+ XXX.X
(Flow, No Flow)
+ XXX.X
XXX.X
XXX.X
+ XXX.X
Units
Temperature
Temperature
%
%
Temperature
Enum
Temperature
Pressure
Pressure
Temperature
Dependencies
Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
Air Cooled (i.e RTUD with ACFC=INT)
Air Cooled with Low Ambient Var Spd fan (i.e RTUD with ACFC<>None and with LAFC = VARA or VARP)
Only if OA sensor is installed
Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
Resolution
XXX
XXX
XXXX:XX
Units
%RLA
Volts hr:min kW min kWh time-date
Kwh
Dependencies
Only if pwr meter option installed
Only if pwr meter option installed
Only if pwr meter option installed
Only if pwr meter option installed
Only if pwr meter option installed
RLC-SVU05A-E4
DynaView Interface
Report name: Circuit Compressor
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description
1.
Oil Pressure
2. Compressor Rfgt Dschg Temp
3. Cond Sat Rfgt Temp
4. Average Line Current
5. % RLA L1 L2 L3
6. Amps L1 L2 L3
7.
Phase Voltages
8. Power Consumption
9. Load Power Factor
10. Compressor Starts:
11. Compressor Running Time:
Report name: System ASHRAE Chiller Log
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description
1.
Current Time/Date
2. Chiller Mode
3. Active Chilled Water Setpoint
4. Active Hot Water Setpoint
5. Evap Entering Water Temperature
6. Evap Leaving Water Temperature
7.
Average Leaving Water Temp
8. Evap Water Flow Switch Status
9. Outdoor Air Temperature
Report name: Circuit ASHRAE Chiller Log
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description
1.
Circuit Mode
2. Evap Sat Rfgt Temp
3. Suction Pressure
4. Evap Approach Temp
5. Cond Sat Rfgt Temp
6. Cond Rfgt Pressure
7.
Cond Approach Temp
8. Compressor Starts
9. Compressor Running Time
Resolution Units
XX:XX mmm dd, yyyy Time / Date
Enum
XXX.X
XXX.X
Temperature
Temperature
XXX.X
XXX.X
XXX.X
XXX.X
Temperature
Temperature
Temperature
Enum
Temperature
Resolution
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXXX
XX:XX
Resolution
XXX.X
+ XXX.X
+ XXX.X
XXX
XXX.X
XXX.X
XXX
XXX
X.XXX
XXXX
XXXX:XX
Units
Pressure
Temperature
Temperature
%RLA
%RLA
Amps
Vac kW
Integer hr:min
Units
Enum
Temperature
Pressure
Temperature
Temperature
Pressure
Temperature
Integer
Hours:Minute
Items 1 - 9 will be unique for each circuit, ckt1, and ckt2.
Dependencies
Only if pwr meter option installed
Only if pwr meter option installed
Only if pwr meter option installed
Dependencies
Hot Water Option installed only
Only if OA sensor is installed
Dependencies
Water Cooled only (i.e. RTWD or RTUD with ACFC=None)
RLC-SVU05A-E4 21
22
DynaView Interface
Settings Screen
The Settings screen provides a user the ability to adjust settings justified to support daily tasks. The layout provides a list of sub-menus, organized by typical subsystem.
This organization allows each subscreen to be shorter in length which should improve the users navigation.
Figure 10 - Settings screen
Main Reports Settings
Unit
Feature Settings
Control Settings
Manual Control Settings
Display Settings
Stop
Settings Menu
Description
1.
Chiller
2. Feature Settings
3. Manual Control Settings
4. Display Settings
Auto Alarms
RLC-SVU05A-E4
RLC-SVU05A-E4
DynaView Interface
Chiller
Description
Resolution or (Enumerations),
Default
(Cool, Heat), Cool 1.
Front Panel Cool/Heat Command
2. Front Panel Chilled Water Setpt
3. Front Panel Hot Water Setpt
4. Front Panel Current Limit Setpt
5. Front Panel Ice Build Cmd
6. Front Panel Ice Termination Setpoint
7.
Setpoint Source
(2)
+ XXX.X
(2)
+ XXX.X
1
On/Auto
XXX.X
8. Leaving Water Temp Cutout
9. Low Refrigerant Temp Cutout
10. Staging Sequence
11. Condenser Pump Prestart Time
(BAS/Ext/FP, Ext/ Front Panel,
Front Panel), BAS/Ext/FP
XX.X
XX.X
(Bal Starts/Hrs, Fixed), Bal Starts/Hrs
XX , 0
Feature Settings
Note: Purple Box Designates Phase 2 Air Cooled RTUD items.
Description
1. Cooling Low Ambient Lockout
1a. Cooling Low Ambient Lockout
1b. Cooling Low Amb Lockout Setpt
2. Noise Setback Command
3. Ice Building
4. Ext Chilled/Hot Water Setpt
5. Ext Current Limit Setpoint
6 Chilled Water Reset
6a. Chilled Water Reset
6b. Return Reset Ratio
6c. Return Start Reset
6d. Return Maximum Reset
6e. Outdoor Reset Ratio
6f. Outdoor Start Reset
6g. Outdoor Maximum Reset
7. LCI-C Diag Language
8. LCI-C Diag Encoding
Resolution or (Enumerations),
Default
(Enable, Disable), Enable
(Enable, Disable), Enable
XXX.X
(Auto, On, Schedule), Auto
(Enable, Disable), Disable
(Enable, Disable), Disable
(Enable, Disable), Disable
(Const Return, Outdoor,
Return, Disable), Disable
(Const Return, Outdoor,
Return, Disable), Disable
XXX
XXX.X
XXX.X
XXX
XXX.X
XXX.X
(English, Selection 2,
Selection 3) English (0)
(Text, Code) Text
Units
Enum
Temperature
Temperature
%RLA
Enum
Temperature
Enum
Temperature
Temperature
Enum minutes
Units
Enum
Enum
Temperature
Enum
Enum
Enum
Enum
Enum
Percent
Temperature
Temperature
Percent
Temperature
Temperature
Enum
Enum
Items 1 and 6 are top level. If user presses this line another screen opens to allow user to change relevant setpoints.
Items 7 and 8 are present if comm5 LCI-C option is installed.
23
24
DynaView Interface
System Manual Control Settings
<| Back System Ckt1 Ckt2
<scroll up/down buttons>
Description
1. Evap Water Pump
1.a.Evap Water Pump
2. Cond Water Pump
2.a. Cond Water Pump
3. Head Pressure Control
3.a. Head Pressure Control
4. Staging/Stepping Control
4.a. Staging/Stepping Control
5. Capacity Modulation Control
5a. Capacity Modulation Control
6. Clear Energy Consumption
6.a. Clear Energy Consumption
Circuit Manual Control Settings
Description
1. Compressor Pumpdown
1.a. Compressor Pumpdown
2. Front Panel Ckt Lockout
2.a. Front Panel Ckt Lockout
3. Expansion Valve Control
3.a. Expansion Valve Control
Resolution or (Enumerations), Default
(Auto, On), Auto (6)
<Auto / On Buttons>
(Auto, On), Auto (6)
<Auto / On Buttons>
(Auto, Manual), Auto (7)
<Auto / Manual Buttons> (7)
(Auto, Manual), Auto (7)
<Auto / Manual Buttons> (7)
(Auto, Manual), Auto (7)
<Auto / Manual Buttons> (7)
1) Resettable Energy consumption totalization (kWh)
<Clear Button>
Resolution or (Enumerations), Default
(Continue, Not Available)
<Pumpdown / Abort Buttons> (8)
(Not Locked Out, Locked Out), Not Locked Out
<Not Locked Out / Locked Out Buttons>
(Auto, Manual)
<Auto / Manual Buttons> (7)
Units
Enum
Enum
Enum
Monitor Value
1) Water Flow status
2) Override Time Remaining
1) Water Flow status
2) Override Time Remaining
1) Override status -
Auto/Manual
Enum
Only if Cond Head pressure control option is installed
Enum
Only if Cond Head pressure control option is installed
Enum
1) Resettable Energy consumption totalization (kWh)
Only if Energy Meter option is installed
Units
Enum
Enum
Enum
Dependency
Water Cooled only (i.e.
RTWD or RTUD with
ACFC=None)
Only if Cond Head pressure control option is installed
Monitor Value
1) Override status:
NotAvailable / Continue / Starting / Pumpdown
2) Suction Pressure
RLC-SVU05A-E4
RLC-SVU05A-E4
DynaView Interface
1.1.1 Display Settings
Description
1.
Date Format
2. Date
3. Time Format
4. Time of Day
5. Keypad/Display Lockout
6. Display Units
7.
Pressure Units
8. Language (5)
Resolution or (Enumerations),
Default
("mmm dd, yyy", "dd-mmm-yyyy"),
"mmm dd, yyy"
(4)
(12-hour, 24-hour), 12-hour
(4)
(Enable, Disable), Disable (3)
(SI, English), SI
(Absolute, Gauge), Gauge
(English, Selection 2, Selection 3),
English (1)
Units
Enum
Enum
Enum
Enum
Enum
Enum
(1) Language choices are dependent on what the Service Tool has setup in the Main Processor. Get Radio Button names from Main Processor setups. Language selections will include English and qty 2 alternate as loaded by
TechView.
(2) Temperatures will be adjustable to 0.1 deg F or C. The Main Processor will provide the minimum and maximum allowable value.
(3) Enables a DynaView Lockout screen. All other screens timeout in 30 minutes to this screen. The DynaView
Lockout Screen will have 0-9 keypad to permit the user to re-enter the other DynaView screens with a fixed password. See below for further details.
(4) The Date and Time setup screen formats deviate slightly from the standard screens defined above. See the alternate screen layouts below.
(5) Language shall always be the last setting listed on the Control Settings menu (which will also always be the last item listed on the Settings menu list). This will allow a user to easily find language selection if looking at an unrecognizable language.
(6) The pump on mode terminates after 60 minutes.
(7) These items cannot be set to "Manual" from the DynaView - The manual buttons on the Manual Control submode screen are hidden unless the particular item has been set to manual from the Service Tool - The auto button shall be operational to change the mode back to auto. The subscreen shall also display a note:
"Manual not available from Front Panel - See Service Tool for Manual Mode"
(8) Buttons are displayed on this Manual Control submode screens depending on the pumpdown status:, when in
"pumpdown", the abort button is shown, when "not available", no buttons shown, when "continue", pumpdown button is shown.
25
26
DynaView Interface
Auto, Stop/Immediate
Stop
The AUTO and STOP keys are radio buttons within the persistent key display area. The selected key will be black.
The chiller will stop when the STOP key is touched, entering the Run
Unload mode. An informational screen will be displayed for
5 seconds indicating that a second depression of an "Immediate Stop" key during this time period will result in an immediate/panic stop.
Pressing the "Immediate Stop" key while the panic stop screen is displayed, will cause the unit to stop immediately, skipping operational pumpdown.
Touching the Auto key will arm the chiller for active cooling if no diagnostic is present. A separate action must be taken to clear active diagnostics.
The AUTO and STOP keys take precedence over the ENTER and
CANCEL keys. While a setting is being changed, AUTO and STOP keys are recognized even if ENTER or CANCEL has not been pressed.
When an active diagnostic is present, an ALARMS key will be added to the persistent display area.
This key is used to alert the operator that a diagnostic exists, or to provide navigation to a diagnostic display screen.
Figure 11
Auto
Stop
Alarms
RLC-SVU05A-E4
RLC-SVU05A-E4
DynaView Interface
Diagnostics Screen
The diagnostic screen is accessible by depressing the Alarms enunciator. A verbal description will be provided. A scrollable list of the last (up to 10) active diagnostics will be presented.
Performing a Reset All Active
Diagnostics will reset all active diagnostics regardless of type, machine or refrigerant circuit.
Compressor diagnostics, which hold off only one compressor, will be treated as circuit diagnostics, consistent with the circuit to which they belong.
The scrollable list will be sorted by time of occurrence. If a diagnostic of severity = warning is present, the
"Alarms" key will be present but not flashing. If a diagnostic of severity = shutdown (normal or immediate) is present, the "Alarm" key will display that is flashing. If no diagnostics exist, the "Alarm" key will not be present.
The "Operating Mode At Last
Diagnostic" text above the most recent diagnostic will display a subscreen listing the operating mode and submodes at the time of the last diagnostic.
Figure 12 - Diagnostics screen
Rfgt Setpoint Diagnostic
Reset Diags
Operating Mode At Last Diagnostic:
[01] 10:56 PM Nov 26, 2001
Low Chilled Water Temp: Unit Off
[02] 10:55 PM Nov 26, 2001
Low Evaporator Temp: Unit Off
Auto
Stop
Alarms
27
28
Diagnostics
The following diagnostic table contains all the diagnostics possible. Not all data is available unless tech view is connected.
Code:
Three digit hexadecimal code used on all past products to uniquely identify diagnostics.
Diagnostic Name:
Name of
Diagnostic and its source. Note that this is the exact text used in the
User Interface and/or Service Tool displays.
Severity:
Defines the severity of the above effect. Immediate means immediate shutdown of the effected portion, Normal means normal or friendly shutdown of the effected portion, Special Mode means a special mode of operation (limp along) is invoked, but without shutdown, and Info means an
Informational Note or Warning is generated.
Persistence:
Defines whether or not the diagnostic and its effects are to be manually reset (Latched), or can be either manually or automatically reset (Nonlatched).
Criteria:
Quantitatively defines the criteria used in generating the diagnostic and, if nonlatching, the criteria for auto reset. If more explanation is necessary a hot link to the Functional Specification is used.
Reset Level:
Defines the lowest level of manual diagnostic reset command which can clear the diagnostic. The manual diagnostic reset levels in order of priority are:
Local and Remote. A diagnostic that has a reset level of Local, can only be reset by a local diagnostic reset command, but not by the lower priority remote Reset command whereas a diagnostic listed as
Remote reset can be reset by either.
Affects Target itemized with an * asterisk: applied to many comm loss and starter module derived diagnostic targets, listed as circuit targeted diagnostics, but should be understood as "cprsr" targeted diagnostics.
RLC-SVU05A-E4
Diagnostics
Table 4 - Main Processor Diagnostics
Diagnostic Name and Source
Starter Did Not
Transition -
Compressor 1A
Starter Did Not
Transition -
Compressor 2A
Phase Reversal -
Compressor 1A
Phase Reversal -
Compressor 2A
Starter 1A Dry Run
Test
Starter 2A Dry Run
Test
Phase Loss -
Compressor 1A
Affects
Target
*Circuit
*Circuit
*Circuit
*Circuit
*Circuit
*Circuit
*Circuit
Severity
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Persistence
Latch
Latch
Latch
Latch
Active Modes
[Inactive Modes]
On the first check after transition.
On the first check after transition.
Criteria
The Starter Module did not receive a transition complete signal in the designated time from its command to transition. The must hold time from the Starter Module transition command is 1 second. The Must trip time from the transition command is 6 seconds. Actual design is 2.5 seconds. This diagnostic is active only for
Y-Delta, Auto-Transformer, Primary Reactor, and X-Line
Starters.
The Starter Module did not receive a transition complete signal in the designated time from its command to transition. The must hold time from the Starter Module transition command is 1 second. The Must trip time from the transition command is 6 seconds. Actual design is 2.5 seconds. This diagnostic is active only for
Y-Delta, Auto-Transformer, Primary Reactor, and X-Line
Starters.
Compressor energized to transition command
[All Other Times]
A phase reversal was detected on the incoming current.
On a compressor startup the phase reversal logic must detect and trip in a maximum of .3 second from compressor start.
Reset Level
Local
Local
Local
Compressor energized to transition command
[All Other Times]
A phase reversal was detected on the incoming current.
On a compressor startup the phase reversal logic must detect and trip in a maximum of .3 second from compressor start.
Local
Latch
Latch
Latch
Starter Dry Run Mode While in the Starter Dry Run Mode either 50 % Line
Voltage was sensed at the Potential Transformers or 10
% RLA Current was sensed at the Current Transformers.
Starter Dry Run Mode While in the Starter Dry Run Mode either 50 % Line
Voltage was sensed at the Potential Transformers or 10
% RLA Current was sensed at the Current Transformers.
Start Sequence and
Run modes a) No current was sensed on one or two of the current transformer inputs while running or starting (See
Nonlatching Power Loss Diagnostic for all three phases lost while running). Must hold = 20% RLA. Must trip =
5% RLA. Time to trip shall be longer than guaranteed reset on Starter Module at a minimum, 3 seconds maximum. Actual design trippoint is 10%. The actual design trip time is 2.64 seconds. b) If Phase reversal protection is enabled and current is not sensed on one or more current xformer inputs. Logic will detect and trip in a maximum of 0.3 seconds from compressor start.
Local
Local
Local
RLC-SVU05A-E4 29
30
Diagnostics
Diagnostic Name and Source
Phase Loss -
Compressor 2A
Power Loss -
Compressor 1A
Power Loss -
Compressor 2A
Severe Current
Imbalance -
Compressor 1A
Affects
Target
*Circuit
Severity
Immediate
Persistence
Active Modes
[Inactive Modes]
Start Sequence and
Run modes
*Circuit
*Circuit
*Circuit
Immediate
Immediate
Immediate
Latch
NonLatch
NonLatch
Latch
All compressor running modes
[all compressor starting and nonrunning modes]
All compressor running modes
[all compressor starting and nonrunning modes]
All Running Modes
Criteria
a) No current was sensed on one or two of the current transformer inputs while running or starting (See
Nonlatching Power Loss Diagnostic for all three phases lost while running). Must hold = 20% RLA. Must trip =
5% RLA. Time to trip shall be longer than guaranteed reset on Starter Module at a minimum, 3 seconds maximum. Actual design trippoint is 10%. The actual design trip time is 2.64 seconds. b) If Phase reversal protection is enabled and current is not sensed on one or more current xformer inputs. Logic will detect and trip in a maximum of 0.3 second from compressor start
The compressor had previously established currents while running and then all three phases of current were lost. Design: Less than 10% RLA, trip in 2.64 seconds.
This diagnostic will preclude the Phase Loss Diagnostic and the Transition Complete Input Opened Diagnostic from being called out. To prevent this diagnostic from occurring with the intended disconnect of main power, the minimum time to trip must be greater than the guaranteed reset time of the Starter module. Note: This diagnostic prevents nuisance latching diagnostics due to a momentary power loss - It does not protect motor/compressor from uncontrolled power reapplication. See Momentary Power Loss Diagnostic for this protection. This diagnostic is not active during the start mode before the transition complete input is proven. Thus a random power loss during a start would result in either a "Starter Fault Type 3" or a "Starter Did
Not Transition" latching diagnostic.
The compressor had previously established currents while running and then all three phases of current were lost. Design: Less than 10% RLA, trip in 2.64 seconds.
This diagnostic will preclude the Phase Loss Diagnostic and the Transition Complete Input Opened Diagnostic from being called out. To prevent this diagnostic from occurring with the intended disconnect of main power, the minimum time to trip must be greater than the guaranteed reset time of the Starter module.
A 30% Current Imbalance has been detected on one phase relative to the average of all 3 phases for 90 continuous seconds.
Reset Level
Local
Remote
Remote
Local
Severe Current
Imbalance -
Compressor 2A
Starter Fault Type I -
Compressor 1A
*Circuit
*Circuit
Immediate
Immediate
Latch
Latch
All Running Modes
Starting - Y Delta
Starters Only
A 30% Current Imbalance has been detected on one phase relative to the average of all 3 phases for 90 continuous seconds
This is a specific starter test where 1M(1K1) is closed first and a check is made to ensure that there are no currents detected by the CT's. If currents are detected when only 1M is closed first at start, then one of the other contactors is shorted.
Local
Local
RLC-SVU05A-E4
Diagnostics
Diagnostic Name and Source
Starter Fault Type I -
Compressor 2A
Affects
Target
*Circuit
Starter Fault Type II -
Compressor 1A
*Circuit
Starter Fault Type II -
Compressor 2A
*Circuit
Starter Fault Type III
- Compressor 1A
Starter Fault Type III
- Compressor 2A
Compressor Did Not
Accelerate:
Transition -
Compressor 1A
*Circuit
Compressor Did Not
Accelerate:
Transition -
Compressor 2A
*Circuit
Transition Complete
Input Shorted -
Compressor 1A
Transition Complete
Input Shorted -
Compressor 2A
*Circuit
*Circuit
*Circuit
*Circuit
Severity
Immediate
Immediate
Immediate
Immediate
Immediate
Info
Info
Immediate
Immediate
Persistence
Latch
Latch
Latch
Latch
Latch
Latch
Latch
Latch
Latch
Active Modes
[Inactive Modes]
Starting - Y Delta
Starters Only
Starting All types of starters
Starting - All types of starters
Starting
[Adaptive Frequency
Starter Type]
Starting
[Adaptive Frequency
Starter Type]
Start Mode
Start Mode
Pre-Start
Pre-Start
Criteria
This is a specific starter test where 1M(1K1) is closed first and a check is made to ensure that there are no currents detected by the CT's. If currents are detected when only 1M is closed first at start, then one of the other contactors is shorted.
a. This is a specific starter test where the Shorting
Contactor (1K3) is individually energized and a check is made to ensure that there are no currents detected by the CT's. If current is detected when only S is energized at Start, then 1M is shorted. b. This test in a.
above applies to all forms of starters (Note: It is understood that many starters do not connect to the
Shorting Contactor.).
a. This is a specific starter test where the Shorting
Contactor (1K3) is individually energized and a check is made to ensure that there are no currents detected by the CT's. If current is detected when only S is energized at Start, then 1M is shorted. b. This test in a.
above applies to all forms of starters (Note: It is understood that many starters do not connect to the
Shorting Contactor.).
As part of the normal start sequence to apply power to the compressor, the Shorting Contactor (1K3) and then the Main Contactor (1K1) were energized. 1.6 seconds later there were no currents detected by the CT's for the last 1.2 Seconds on all three phases. The test above applies to all forms of starters except Adaptive
Frequency Drives.
As part of the normal start sequence to apply power to the compressor, the Shorting Contactor (1K3) and then the Main Contactor (1K1) were energized. 1.6 seconds later there were no currents detected by the CT's for the last 1.2 seconds on all three phases. The test above applies to all forms of starters except Adaptive
Frequency Drives.
The compressor did not come up to speed (fall to
<85%RLA) in the allotted time defined by the Maximum
Acceleration Timer and a transition was forced (motor put across the line) at that time. This applies to all starter types.
The compressor did not come up to speed (fall to
<85%RLA) in the allotted time defined by the Maximum
Acceleration Timer and a transition was forced (motor put across the line) at that time. This applies to all starter types.
The Transition Complete input was found to be shorted before the compressor was started. This is active for all electromechanical starters.
The Transition Complete input was found to be shorted before the compressor was started. This is active for all electromechanical starters.
Reset Level
Local
Local
Local
Local
Local
Remote
Remote
Local
Local
RLC-SVU05A-E4 31
32
Diagnostics
Diagnostic Name and Source
Transition Complete
Input Opened -
Compressor 1A
Affects
Target
*Circuit
Transition Complete
Input Opened -
Compressor 2A
*Circuit
Motor Current
Overload -
Compressor 1A
Motor Current
Overload -
Compressor 2A
Starter Contactor
Interrupt Failure -
Compressor 1A
Starter Contactor
Interrupt Failure -
Compressor 2A
Over Voltage
Under Voltage
Circuit
Circuit
Chiller
Chiller
Chiller
Chiller
Severity
Immediate
Immediate
Immediate
Immediate
Special
Action
Special
Action
Normal
Normal
Persistence
Active Modes
[Inactive Modes]
All running modes
Latch
Latch
Latch
Latch
Latch
Latch
Criteria
All running modes
Cprsr Energized
Cprsr Energized
The Transition Complete input was found to be opened with the compressor motor running after a successful completion of transition. This is active only for Y-Delta,
Auto-Transformer, Primary Reactor, and X-Line Starters.
To prevent this diagnostic from occurring as the result of a power loss to the contactors, the minimum time to trip must be greater than the trip time for the power loss diagnostic.
The Transition Complete input was found to be opened with the compressor motor running after a successful completion of transition. This is active only for Y-Delta,
Auto-Transformer, Primary Reactor, and X-Line Starters.
To prevent this diagnostic from occurring as the result of a power loss to the contactors, the minimum time to trip must be greater than the trip time for the power loss diagnostic.
Compressor current exceeded overload time vs. trip characteristic. Must trip = 140% RLA, Must hold=125%, nominal trip 132.5% in 30 seconds
Compressor current exceeded overload time vs. trip characteristic. Must trip = 140% RLA, Must hold=125%, nominal trip 132.5% in 30 seconds
Starter Contactor not
Energized [Starter
Contactor Energized]
Detected compressor currents greater than 10% RLA on any or all phases when the compressor was commanded off. Detection time shall be 5 second minimum and 10 seconds maximum. On detection and until the controller is manually reset: generate diagnostic, energize the appropriate alarm relay, continue to energize the Evap Pump Output, continue to command the affected compressor off, fully unload the effected compressor and command a normal stop to all other compressors. For as long as current continues, perform liquid level, oil return, and fan control on the circuit effected.
Starter Contactor not
Energized [Starter
Contactor Energized]
Detected compressor currents greater than 10% RLA on any or all phases when the compressor was commanded off. Detection time shall be 5 second minimum and 10 seconds maximum. On detection and until the controller is manually reset: generate diagnostic, energize the appropriate alarm relay, continue to energize the Evap Pump Output, continue to command the affected compressor off, fully unload the effected compressor and command a normal stop to all other compressors. For as long as current continues, perform liquid level, oir return, and fan control on the circuit effected.
Reset Level
Local
Local
Local
Local
Local
Local
NonLatch
Pre-Start and Any
Ckt(s) Energzd
Nom. trip: 60 seconds at greater than 112.5%, + 2.5%,
Auto Reset at 110% or less for 10 cont secs.
Remote
NonLatch
Pre-Start and Any
Ckt(s) Energzd
Nom. trip: 60 seconds at less than 87.5%, + 2.8% at
200V 1.8% at 575V, Auto Reset at 90% or greater for
10 cont secs.
Remote
RLC-SVU05A-E4
Main Processor Diagnostics
Diagnostic Name
MP: Reset Has
Occurred
Unexpected Starter
Shutdown
Circuit
High Motor Winding
Temperature -
Compressor 1A
High Motor Winding
Temperature -
Compressor 2A
Low Evaporator
Refrigerant
Temperature -
Circuit 1
Circuit
Circuit
Circuit
Low Evaporator
Refrigerant
Temperature -
Circuit 2
Affects
Target
None
Circuit
Severity
Info
Normal
Immediate
Persistence
Active Modes
[Inactive Modes]
All
NonLatch
NonLatch
Latch
Criteria
The main processor has successfully come out of a reset and built its application. A reset may have been due to a power up, installing new software or configuration. This diagnostic is immediately and automatically cleared and thus can only be seen in the
Historic Diagnostic List in TechView
All Cprsr Running modes, Starting,
Running and Preparing to Shutdown
The Starter module status reported back that it is stopped when the MP thinks it should be running and no Starter diagnostic exist. This diagnostic will be logged in the active buffer and then automatically cleared. This diagnostic could be caused by intermittent communication problems from the Starter to the MP, or due to misbinding.
All The respective compressor's motor winding thermostat is detected to be open
Reset Level
Remote
NA
Local
Immediate
Latch
All The respective compressor's motor winding thermostat is detected to be open
Local
Immediate
Immediate
Latch
Latch
All Ckt Running
Modes
All Ckt Running
Modes
The inferred Saturated Evap Refrigerant Temperature
(calculated from suction pressure transducer dropped below the Low Refrigerant Temperature Cutout Setpoint for 1125°F-sec (25°F-sec max rate) while the circuit was running. The minimum LRTC setpoint is -5°F (18.7 Psia) the point at which oil separates from the refrigerant.
During the time that the trip integral is non zero, the unload solenoid(s) of the running compressors on the circuit, shall be energized continuously and the load solenoid shall be off. Normal load/unload operation will be resumed if the trip integral decays to zero by temps above the cutout setpoint. The integral is held nonvolatily though power down, is continuously calculated, and can decay during the circuit's off cycle as conditions warrant.
Remote
The inferred Saturated Evap Refrigerant Temperature
(calculated from suction pressure transducer dropped below the Low Refrigerant Temperature Cutout Setpoint for 1125°F-sec (25°F-sec max rate) while the circuit was running. The minimum LRTC setpoint is -5°F (18.7 Psia) the point at which oil separates from the refrigerant.
During the time that the trip integral is non zero, the unload solenoid(s) of the running compressors on the circuit, shall be energized continuously and the load solenoid shall be off. Normal load/unload operation will be resumed if the trip integral decays to zero by temps above the cutout setpoint. The integral is held nonvolatily though power down, is continuously calculated, and can decay during the circuit's off cycle as conditions warrant.
Remote
RLC-SVU05A-E4 33
34
Main Processor Diagnostics
Diagnostic Name
Low Oil Flow -
Compressor 1A
Low Oil Flow -
Compressor 2A
Loss of Oil -
Compressor 1A
(Running)
Loss of Oil -
Compressor 2A
(Running)
Loss of Oil -
Compressor 1A
(Stopped)
Loss of Oil -
Compressor 2A
(Stopped)
No Differential
Refrigerant
Pressure - Circuit 1
No Differential
Refrigerant
Pressure - Circuit 2
Low Differential
Refrigerant
Pressure - Circuit 1
Low Differential
Refrigerant
Pressure - Circuit 2
High Differential
Refrigerant
Pressure - Circuit 1
Affects
Target
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Severity
Immediate
Immediate
Immediate
Immediate
Immediate and Special
Action
Immediate and Special
Action
Immediate
Immediate
Immediate
Immediate
Normal
Persistence
Latch
Active Modes
[Inactive Modes]
Cprsr Energized and
Delta P above 15 Psid
Criteria
The intermediate oil pressure transducer for this compressor was out of the acceptable pressure range for 15 seconds, while the Delta Pressure was greater than 15 Psid (172.4 kPa).: Acceptable range is 0.50 >
(PC-PI) / (PC-PE) for the first 2.5 minutes of operation, and 0.28 > (PC-PI) / (PC-PE) thereafter.
Latch
Latch
Latch
Latch
Latch
Latch
Cprsr Energized and
Delta P above 15 Psid
The intermediate oil pressure transducer for this compressor was out of the acceptable pressure range for 15 seconds, while the Delta Pressure was greater than 15 Psid (172.4 kPa).: Acceptable range is 0.50 >
(PC-PI) / (PC-PE) for the first 2.5 minutes of operation, and 0.28 > (PC-PI) / (PC-PE) thereafter.
Starter Contactor
Energized
Starter Contactor
Energized
In running modes , Oil Loss Level Sensor detects lack of oil in the oil sump feeding the compressor
(distinguishing a liquid flow from a vapor flow)
In running modes , Oil Loss Level Sensor detects lack of oil in the oil sump feeding the compressor
(distinguishing a liquid flow from a vapor flow)
Compressor Pre-start
[all other modes]
Compressor Pre-start
[all other modes]
Compressor running on Circuit
Oil Loss Level Sensor detects a lack of oil in the oil sump feeding the compressor for 90 seconds just prior to attempted compressor start. Note: Compressor start is delayed while waiting for oil to be detected, and compressor start is not allowed.
Oil Loss Level Sensor detects a lack of oil in the oil sump feeding the compressor for 90 seconds just prior to attempted compressor start. Note: Compressor start is delayed while waiting for oil to be detected, and compressor start is not allowed.
The system differential pressure was below 7.7 Psid (53 kPa) for 6 seconds after the 11 seconds ignore time relative to cprsr/circuit startup had expired.
Reset Level
Local
Local
Local
Local
Local
Local
Remote
Latch
Latch
Latch
Latch
Compressor running on Circuit
Cprsr Energized
Cprsr Energized
Cprsr Energized
The system differential pressure was below 7.7 Psid (53 kPa) for 6 seconds after the 11 seconds ignore time relative to cprsr/circuit startup had expired.
The system differential pressure for the respective circuit was below 25 Psid (240.5 kPa) while its compressor was unstepped or pressure ratio was below
1.75 if stepped - for a varying period of time - refer to specification for trip time as a function of system DP below the requirement
The system differential pressure for the respective circuit was below 25 Psid (240.5 kPa) while its compressor was unstepped or pressure ratio was below
1.75 if stepped - for a varying period of time - refer to specification for trip time as a function of system DP below the requirement
High Vi Cprsr:
The differential pressure for the respective circuit was above 275 Psid (1890 kPa) for 2 consecutive samples or more than 10 seconds.
Low Vi Cprsr:
The system differential pressure was above 188 Psid (1296.4 kPa) - for 2 consecutive samples or more than 10 seconds.
Remote
Remote
Remote
Remote
RLC-SVU05A-E4
Main Processor Diagnostics
Diagnostic Name
High Differential
Refrigerant
Pressure - Circuit 2
High Refrigerant
Pressure Ratio -
Circuit 1
High Refrigerant
Pressure Ratio -
Circuit 2
High Discharge
Temperature -
Compressor 1A
High Discharge
Temperature -
Compressor 2A
Low Discharge
Superheat -
Circuit 1
Affects
Target
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Severity
Normal
Immediate
Immediate
Immediate
Immediate
Normal
Normal
Persistence
Active Modes
[Inactive Modes]
Cprsr Energized
Latch
Latch
Latch
Latch
Latch
Criteria
Service Pumpdown
Only
Service Pumpdown
Only
High Vi Cprsr: The differential pressure for the respective circuit was above 275 Psid (1890 kPa) for 2 consecutive samples or more than 10 seconds.
Low Vi Cprsr: The system differential pressure was above 188 Psid (1296.4 kPa) - for 2 consecutive samples or more than 10 seconds.
The pressure ratio for the respective circuit exceeded
5.61 for 1 contiguous minute while in service pumpdown. This pressure ratio is a fundamental limitation of the compressor. The pressure ratio is defined as Pcond (abs)/Pevap(abs).
The pressure ratio for the respective circuit exceeded
5.61 for 1 contiguous minute while in service pumpdown. This pressure ratio is a fundamental limitation of the compressor. The pressure ratio is defined as Pcond (abs)/Pevap(abs).
All
[compressor run unload or compressor not running]
All
[compressor run unload or compressor not running]
The compressor discharge temperature exceeded 200°F
(without oil cooler) or 230ºF (with oil cooler). This diagnostic will be suppressed during Run-Unload or after the compressor has stopped. Note: As part of the
Compressor High Temperature Limit Mode (aka
Minimum Capacity Limit), the compressor shall be forced loaded as the filtered discharge temperature reaches 190ºF(without oil coolers), or 220ºF (with oil coolers).
The compressor discharge temperature exceeded 200°F
(without oil cooler) or 230ºF (with oil cooler). This diagnostic will be suppressed during Run-Unload or after the compressor has stopped. Note: As part of the
Compressor High Temperature Limit Mode (aka
Minimum Capacity Limit), the compressor shall be forced loaded as the filtered discharge temperature reaches 190ºF(without oil coolers), or 220ºF (with oil coolers).
Reset Level
Remote
Remote
Remote
Remote
Remote
Latch
Latch
Any Running Mode
Any Running Mode
While Running Normally, the Discharge Superheat was less than 12 degrees F +- 1F for more than 6500 degree
F seconds.. At circuit startup the Discharge Superheat will be ignored for 5 minutes.
While Running Normally, the Discharge Superheat was less than 12 degrees F +- 1F for more than 6500 degree
F seconds.. At circuit startup the Discharge Superheat will be ignored for 5 minutes.
Remote
Remote
Low Discharge
Superheat -
Circuit 2
Discharge
Temperature
Sensor -
Compressor 1A
Discharge
Temperature
Sensor -
Compressor 2A
Evaporator Liquid
Level Sensor -
Circuit 1
Evaporator Liquid
Level Sensor -
Circuit 2
Circuit
Circuit
Circuit
Circuit
Immediate
Immediate
Normal
Normal
Latch
Latch
Latch
Latch
All
All
All
All
Bad Sensor or LLID
Bad Sensor or LLID
Bad Sensor or LLID
Bad Sensor or LLID
Remote
Remote
Remote
Remote
RLC-SVU05A-E4 35
36
Main Processor Diagnostics
Diagnostic Name
Fan Inverter Fault -
Circuit 1
Fan Inverter Fault -
Circuit 2
BAS Failed to
Establish
Communication
BAS
Communication
Lost
Low Evaporator
Liquid Level -
Circuit 1
Low Evaporator
Liquid Level -
Circuit 2
Affects
Target
Severity Persistence
Active Modes
[Inactive Modes]
Circuit (fan control)
Special Mode
(or in single fan deck:
Circuit
Immediate shutdown
NonLatch (or in single fan deck:Latch)
Prestart and Running w/ Low Ambient
Variable Spd Fan configured
Circuit (fan control)
Special Mode
(or in single fan deck:
Circuit
Immediate shutdown
NonLatch (or in single fan deck:Latch)
Prestart and Running w/ Low Ambient
Variable Spd Fan configured
None Special
Action
NonLatch
At power-up
Criteria
A fault signal has been detected from the respective condenser's Variable Speed Inverter Drive (fan).
Condenser Fan control will revert to constant speed operation without the use of the inverter's fan. If the inverter's fault clears, fan control will switch back to variable speed. For single fan deck configurations, this diagnostic causes a latching circuit shutdown
A fault signal has been detected from the respective condenser's Variable Speed Inverter Drive (fan).
Condenser Fan control will revert to constant speed operation without the use of the inverter's fan. If the inverter's fault clears, fan control will switch back to variable speed. For single fan deck configurations, this diagnostic causes a latching circuit shutdown
The BAS was setup as "installed" and the BAS did not communicate with the Lontalk LCIC within 15 minutes after chiller controls power-up. Refer to Section on
Setpoint Arbitration to determine how setpoints and operating modes may be effected. Note that this diagnostic is never operational for BacNet
Communication interface (BCIC) and only operational with a LonTalk Communication interface (LCIC) if so configured by the BAS or Tracer system.
None
None
None
Special
Action
Info
Info
NonLatch
NonLatch
NonLatch
All
Starter Contactor
Energized [all Stop modes]
Starter Contactor
Energized [all Stop modes]
The BAS was setup as "installed" at the MP and the
Lontalk LCIC lost communications with the BAS for 15 contiguous minutes after it had been established. Refer to Section on Setpoint Arbitration to determine how setpoints and operating modes may be effected by the comm loss. The chiller follows the value of the Tracer
Default Run Command which can be previously written by Tracer and stored nonvolatilely by the MP (either use local or shutdown). Note that this diagnostic is never operational for BacNet Communication interface (BCIC) and only operational with a LonTalk Communication interface (LCIC) if so configured by the BAS or Tracer system.
The liquid level sensor is seen to be at or near its low end of range for 80 contiguous minutes while the compressor is running and the EXV has not been in low differential pressure control during that time. Design: approx 20% or less of bit count corresponding to -40 mm or less liquid level for 80 minutes - the minute counter is reset if EXV is in Low DP control for 5 iterations (10 sec) implemented as an integral.
The liquid level sensor is seen to be at or near its low end of range for 80 contiguous minutes while the compressor is running and the EXV has not been in low differential pressure control during that time. Design: approx 20% or less of bit count corresponding to -40 mm or less liquid level for 80 minutes - the minute counter is reset if EXV is in Low DP control for5 iterations (10 sec) implemented as an integral .
Reset Level
Remote
Remote
Remote
Remote
RLC-SVU05A-E4
Main Processor Diagnostics
Diagnostic Name
High Evaporator
Liquid Level - Circuit
1 (early Phase 1
RTWD production only - eliminated in
2nd Phase 1 release in Sept 08)
High Evaporator
Liquid Level - Circuit
2 (early Phase 1
RTWD production only - eliminated in
2nd Phase 1 release in Sept 08)
External Chilled/Hot
Water Setpoint
Affects
Target
Circuit
Circuit
None
External Current
Limit Setpoint
Evaporator Water
Flow (Entering
Water Temp)
None
None
Evaporator
Entering Water
Temperature
Sensor
Evaporator
Leaving Water
Temperature
Sensor
Condenser
Entering Water
Temperature
Sensor
Condenser
Leaving Water
Temperature
Sensor
Condenser
Refrigerant
Pressure
Transducer -
Circuit 1
Condenser
Refrigerant
Pressure
Transducer -
Circuit 2
Suction
Refrigerant
Pressure
Transducer -
Circuit 1
RLC-SVU05A-E4
Chiller
Chiller
Chiller
Chiller
Info and
Special
Action
Info and
Special
Action
Circuit Immediate
Circuit Immediate
Circuit Immediate
Severity
Normal
Normal
Info
Info
Info
Normal
Normal
Persistence
Latch
Latch
Latch
Latch
Latch
Latch
Active Modes
[Inactive Modes]
Starter Contactor
Energized [all Stop modes]
Starter Contactor
Energized [all Stop modes]
Criteria
The liquid level sensor is seen to be at or near its high end of range for 80 contiguous minutes while the compressor is running. (The diagnostic timer will hold, but not clear when the circuit is off). Design: approx
80% or more of bit count corresponding to +30 mm or more liquid level for 80 minutes).
The liquid level sensor is seen to be at or near its high end of range for 80 contiguous minutes while the compressor is running. (The diagnostic timer will hold, but not clear when the circuit is off). Design: approx
80% or more of bit count corresponding to +30 mm or more liquid level for 80 minutes).
Reset Level
Remote
Remote
All
All
Any Ckt(s) Energzd
[No Ckt(s) Energzd]
All a. Function Not "Enabled": no diagnostics. b. "Enabled ":
Out-Of-Range Low or Hi or bad LLID, set diagnostic, default CWS to next level of priority (e.g. Front Panel
SetPoint). This Info diagnostic will automatically reset if the input returns to the normal range.
a. Not "Enabled": no diagnostics. b. "Enabled ": Out-Of-
Range Low or Hi or bad LLID, set diagnostic, default
CLS to next level of priority (e.g. Front Panel SetPoint.
This Info diagnostic will automatically reset if the input returns to the normal range.
The entering evaporator water temp fell below the leaving evaporator water temp by more than 2°F for
100°F-sec. For falling film evaporators, this diagnostic cannot reliably indicate loss of flow, but can warn of improper flow direction through the evaporator, misbound water temperature sensors, improper sensor installation, partially failed sensors, or other system problems. Note that either entering or leaving water temp sensor could be at fault.
Bad Sensor or LLID. Note: Entering Water Temp Sensor is used in EXV pressure control as well as ice making so it must cause a unit shutdown even if ice or CHW reset is not installed.
Remote
Remote
Remote
Remote
Latch All Bad Sensor or LLID Remote
Latch All
Latch All
Latch All
Latch All
Latch All
RTWD only: Bad Sensor or LLID. If chiller running, and condenser water regulating valve option installed, force valve to 100% flow.
RTWD only: Bad Sensor or LLID. If Chiller is running in the heat mode of operation - normal chiller shutdown, otherwise, informational warning only.
Discontinue Min Capacity Limit forced cprsr loading due to Low DP in subsequent startups.
Remote
Remote
Bad Sensor or LLID
Bad Sensor or LLID
Bad Sensor or LLID
Remote
Remote
Remote
37
38
Main Processor Diagnostics
Diagnostic Name
Suction Refrigerant
Pressure Transducer
- Circuit 2
Evaporator
Approach Error -
Circuit 1
Affects
Target
Circuit
Circuit
Evaporator
Approach Error -
Circuit 2
Oil Pressure
Transducer -
Compressor 1A
Oil Pressure
Transducer -
Compressor 2A
Oil Pressure
System Fault -
Circuit 1
Oil Pressure
System Fault -
Circuit 2
Low Evaporator
Refrigerant
Pressure - Circuit 1
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Severity
Immediate
Persistence
Active Modes
[Inactive Modes]
All
Latch
Immediate Respective circuit running
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Latch
Latch
Respective circuit running
All
Bad Sensor or LLID
Criteria Reset Level
Remote
The Evaporator approach temperature for the respective circuit (ELWT - Evap Sat Temp Ckt x) is negative by
10ºF or more, for 1 minute continuously while the circuit
/ compressor is operating. Either the Evap Leaving
Water Temp sensor, or Evap Suction Rfgt Pressure
Transducer Ckt 1 is in error.
The Evaporator approach temperature for the respective circuit (ELWT - Evap Sat Temp Ckt x) is negative by
10ºF or more, for 1 minute continuously while the circuit
/ compressor is operating. Either the Evap Leaving
Water Temp sensor, or Evap Suction Rfgt Pressure
Transducer Ckt 2 is in error
Bad Sensor or LLID
Remote
Remote
Remote
Latch
All Bad Sensor or LLID Remote
Latch
Latch
Latch
Latch
Starter Contactor
Energized [all Stop modes]
Starter Contactor
Energized [all Stop modes]
Cprsr Prestart and
Cprsr Energized
The Intermediate Oil Pressure Transducer for this cprsr is reading a pressure either above its respective circuit's Condenser Pressure by 15 Psia or more, or below its respective Suction Pressure 10 Psia or more for 30 seconds continuously.
The Intermediate Oil Pressure Transducer for this cprsr is reading a pressure either above its respective circuit's Condenser Pressure by 15 Psia or more, or below its respective Suction Pressure 10 Psia or more for 30 seconds continuously.
a. The Evap Refrig Pressure dropped below 10 Psia just prior to compressor start (after EXV preposition). b. For
RTUD A/C during early startup period: The Evap Refrig
Pressure fell below the Condenser Pressure ÷ 8, limited to between 2 and 10 psia. c. For RTWD (or
RTUD, ACFC=none) during early startup period: The
Evap Refrig Pressure fell below 10 Psia. d. For all chiller types, after early Startup Period expires: The Evap Refrig
Pressure fell below 16 Psia.
(Note: the Startup Period for RTWD is 3 min ; for RTUD it is between 1 and 5 min for as an inverse function of the Cond Temp measured at time of circuit startup).
Local
Local
Local
CG-SVU02C-E4
Main Processor Diagnostics
Diagnostic Name
Low Evaporator
Refrigerant Pressure
- Circuit 2
Very Low
Evaporator
Refrigerant Pressure
- Circuit 1
Very Low
Evaporator
Refrigerant Pressure
- Circuit 2
Affects
Target
Circuit
Chiller
Chiller
Low Evaporator
Leaving Water Temp:
Unit Off
Evap (and circ) Pump
Severity
Immediate
Immediate
Immediate
Special
Action
Persistence
Latch
Latch
Active Modes
[Inactive Modes]
Cprsr Prestart and
Cprsr Energized
Criteria
a. The Evap Refrig Pressure dropped below 10 Psia just prior to compressor start (after EXV preposition). b. For
RTUD A/C during early startup period: The Evap Refrig
Pressure fell below the Condenser Pressure ÷ 8, limited to between 2 and 10 psia. c. For RTWD (or
RTUD, ACFC=none) during early startup period: The
Evap Refrig Pressure fell below 10 Psia. d. For all chiller types, after early Startup Period expires: The Evap Refrig
Pressure fell below 16 Psia.
(Note: the Startup Period for RTWD is 3 min; for RTUD it is between 1 and 5 min for as an inverse function of the
Cond Temp measured at time of circuit startup).
All
[compressor or circuit in manual lockout]
The respective circuit's evaporator pressure dropped below 80% of the current Low Evap Refrig Press Cutout setting (see above) or 8 psia, whichever is less, regardless of the running state of the circuit's compressor. If a given compressor or circuit is locked out, the suction pressure transducer(s) associated with it, will be excluded from causing this diagnostic.
Reset Level
Local
Local
Latch
All
[compressor or circuit in manual lockout]
The respective circuit's evaporator pressure dropped below 80% of the current Low Evap Refrig Press Cutout setting (see above) or 8 psia, whichever is less, regardless of the running state of the circuit's compressor. If a given compressor or circuit is locked out, the suction pressure transducer(s) associated with it, will be excluded from causing this diagnostic.
Local
NonLatch
Unit in Stop Mode, or in Auto Mode and No
Ckt(s) Energzd [Any
Ckt Energzd]
The leaving Evaporator water temp. fell below the leaving water temp cutout setting for 30 degree F seconds while the Chiller is in the Stop mode, or in Auto mode with no compressors running. Energize small
Evap Circulating Pump (RTUD A/C) and Evap Water pump Relay (but only if "Evap Water Pump Diagnostic
Override" setting is enabled) until diagnostic auto resets, then de-energize the circ pump and return to normal evap pump control. Automatic reset occurs when the temp rises 2°F (1.1°C) above the cutout setting for 30 minutes. This diagnostic even while active, does not prevent operation of either circuit
Remote
CG-SVU02C-E4 39
40
Main Processor Diagnostics
Diagnostic Name
Low Evaporator
Temp - Ckt 1: Unit
Off
Low Evaporator
Temp - Ckt 2: Unit
Off
Low Evaporator
Water Temp: Unit On
Evaporator Water
Flow Overdue
Evaporator Water
Flow Lost
Affects
Target
Evap (and circ) Pump
Evap (and circ) Pump
Chiller
Chiller
Chiller
Severity
Special
Action
Special
Action
Immediate and Special
Action
Normal
Immediate
Persistence
Active Modes
[Inactive Modes]
Unit in Stop Mode, or in Auto Mode and No
Ckt's Energzd [Any
Ckt Energzd]
NonLatch
Criteria
The respective evap sat temp fell below the water temp cutout setting while the evap liquid level was greater than -36 mm for 150º-sec degree F seconds while
Chiller is in the Stop mode, or in Auto mode with no compressors running. Energize small Evap Circulating
Pump (RTUD A/C) and Evap Water pump Relay (but only if "Evap Water Pump Diagnostic Override" setting is enabled) until diagnostic auto resets, then de-energize the circ pump and return to normal evap pump control.
Automatic reset occurs when the derived evap sat temp rises 2°F (1.1°C) above the cutout setting for 1 minute or the liquid level is below -36.0 mm for 20 minutes, or any compressor restarts. OA temp is substituted for evap sat temp in case of invalidity. This diagnostic even while active, does not prevent operation of either circuit.
Reset Level
Remote
NonLatch
Unit in Stop Mode, or in Auto Mode and No
Ckt's Energzd [Any
Ckt Energzd]
The respective evap sat temp fell below the water temp cutout setting while the evap liquid level was greater than -36 mm for 150º-sec degree F seconds while
Chiller is in the Stop mode, or in Auto mode with no compressors running. Energize small Evap Circulating
Pump (RTUD A/C) and Evap Water pump Relay (but only if "Evap Water Pump Diagnostic Override" setting is enabled) until diagnostic auto resets, then de-energize the circ pump and return to normal evap pump control.
Automatic reset occurs when the derived evap sat temp rises 2°F (1.1°C) above the cutout setting for 1 minute or the liquid level is below -36.0 mm for 20 minutes, or any compressor restarts. OA temp is substituted for evap sat temp in case of invalidity. This diagnostic even while active, does not prevent operation of either circuit.
Remote
NonLatch
NonLatch
NonLatch
Any Ckt[s] Energzd
[No Ckt(s) Energzd]
The evaporator water temp. fell below the cutout setpoint for 30 degree F Seconds while the compressor was running. Automatic reset occurs when the temperature rises 2° F (1.1°C) above the cutout setting for 2 minutes. This diagnostic shall not de-energize the
Evaporator Water Pump Output.
Estab. Evap. Water
Flow on going from
STOP to AUTO or Evap
Pump Override.
Evaporator water flow was not proven within 20 minutes of the Evaporator water pump relay being energized in normal "Stop" to "Auto" transition. If the pump is overridden to "On" for certain diagnostics, the delay on diagnostic callout shall be only 255 seconds.
The pump command status will not be effected by this diagnostic in either case.
[All Stop modes] a. The Evaporator water flow switch input was open for more than 6 contiguous seconds (or 15 seconds for thermal dispersion type flow switch). b. This diagnostic does not de-energize the evap pump output c. 6 seconds of contiguous flow shall clear this diagnostic.
Remote
Remote
Remote
CG-SVU02C-E4
Main Processor Diagnostics
Diagnostic Name
High Evaporator
Refrigerant Pressure
Affects
Target
Chiller
High Evaporator
Water Temperature
Condenser Water
Flow Overdue
Condenser Water
Flow Lost
Chiller
Chiller
Chiller
Severity
Immediate
Info and
Special
Action
Normal
Persistence
Active Modes
[Inactive Modes]
All
NonLatch
NonLatch
Criteria
The evaporator refrigerant pressure of either circuit has risen above 190 psig. The evaporator water pump relay will be de-energized to stop the pump regardless of why the pump is running. The diagnostic will auto reset and the pump will return to normal control when all of the evaporator pressures fall below 185 psig. The primary purpose is to stop the evaporator water pump and its associated pump heat from causing refrigerant side pressures, close to the evaporator relief valve setting, when the chiller is not running, such as could occur with
Evap Water Flow Overdue or Evaporator Water Flow
Loss Diagnostics.
Only effective if either
1)Evap Wtr Flow
Overdue,
2)Evap Wtr Flow Loss, or 3)Low Evap Rfgt
Temp,-Unit Off, diagnostic is active.
The leaving water temperature exceeded the high evap water temp limit (TV service menu settable -default
105F) for 15 continuous seconds. The evaporator water pump relay will be de-energized to stop the pump but only if it is running due one of the diagnostics listed on the left . The diagnostic will auto reset and the pump will return to normal control when the temperature falls
5°F below the trip setting. The primary purpose is to stop the evaporator water pump and its associated pump heat from causing excessive waterside temperatures and waterside pressures when the chiller is not running but the evap pump is on due to either
Evap Water Flow Overdue, Evaporator Water Flow Loss
, or Low Evap Temp - Unit Off Diagnostics. This diagnostic will not auto clear solely due to the clearing of the enabling diagnostic.
Reset Level
Remote
Remote
NonLatch
Estab Cond Water
Flow
Condenser water flow was not proven within 20 minutes of the condenser pump relay being energized.
The Cond Pump shall be commanded off. Diagnostic is reset with return of flow (although only possible with external control of pump).
Remote
Immediate
NonLatch
Start and All Run
Modes
The condenser water flow proof input was open for more than 6 contiguous seconds (or 15 seconds for thermal dispersion type flow switch) after flow had been proven. This diagnostic is automatically cleared once the compressor is stopped by a fixed time out of 7 sec. In
Cooling Mode: The Cond Pump shall be commanded off but the Evap pump command will not be effected. once the diagnostic auto clears, if diff to start is met, the cond pump can be restarted. In Heating Mode: The
Cond Pump shall remain on, and the Evap pump shall shut off - once diagnostic auto clears, if diff to start is met, the chiller may restart normally and the evap pump can be restarted.
Remote
CG-SVU02C-E4 41
42
Main Processor Diagnostics
Diagnostic Name
High Pressure
Cutout -
Compressor 1A
High Pressure
Cutout -
Compressor 2A
Excessive
Condenser Pressure
- Circuit 1
Excessive
Condenser Pressure
- Circuit 2
Emergency Stop
Affects
Target
Circuit
Circuit
Circuit
Circuit
Chiller
Severity
Immediate
Immediate
Immediate
Immediate
Immediate
Persistence
Latch
Latch
Latch
Latch
Active Modes
[Inactive Modes]
All
Criteria
A high pressure cutout was detected on Compressor
1A; trip at 270 ± 5 PSIG. Note: Other diagnostics that may occur as an expected consequence of the HPC trip will be suppressed from annunciation. These include
Phase Loss, Power Loss, and Transition Complete Input
Open. For Air Cooled Condenser, check for dirty coils or any fouling or restrictions as well as proper operation and rotational direction of all fans..
Reset Level
Local
All A high pressure cutout was detected on Compressor
1A; trip at 270 ± 5 PSIG. Note: Other diagnostics that may occur as an expected consequence of the HPC trip will be suppressed from annunciation. These include
Phase Loss, Power Loss, and Transition Complete Input
Open. For Air Cooled Condenser, check for dirty coils or any fouling or restrictions as well as proper operation and rotational direction of all fans..
Local
All
All
The condenser pressure transducer of this circuit has detected a pressure in excess of the safe high side pressure as limited by the particular compressor type or the evaporator distributor present on this particular chiller. For Air Cooled Condenser, check for dirty coils or any fouling or restrictions as well as proper operation and rotational direction of all fans.
The condenser pressure transducer of this circuit has detected a pressure in excess of the safe high side pressure as limited by the particular compressor type or the evaporator distributor present on this particular chiller. For Air Cooled Condenser, check for dirty coils or any fouling or restrictions as well as proper operation and rotational direction of all fans.
Remote
Remote
Latch All a. EMERGENCY STOP input is open. An external interlock has tripped. Time to trip from input opening to unit stop shall be 0.1 to 1.0 seconds.
Local
Outdoor Air
Temperature
Sensor
Starter Panel High
Temperature Limit
- Compressor 1A
Starter Module
Memory Error Type
1Starter 1A
Chiller
RTUD with
ACFC#NONE-
Normal
Shutdown;
OATS=INST-
Special Action
Latch
Latch
Circuit
None
Immediate and Special
Action
Info
NonLatch
Latch
All
All
All
Bad Sensor or LLID. If the outdoor temperature is used for CHW reset, there shall be no CHW reset.
Apply slew rates per Chilled Water Reset spec. RTUD: if this diagnostic occurs, operational pumpdown will be performed regardless of the last valid temperature.
For RTWD, if installed for low ambient lockout, there shall be no LA lockout .
Remote
Starter Panel High Limit Thermostat (170°F) trip was detected. Compressor 1A is shutdown and inoperative until the thermostat resets. Note: Other diagnostics that may occur as an expected consequence of the
Panel High Temp Limit trip will be suppressed from annunciation. These include Momentary Power Loss,
Phase Loss, Power Loss, and Transition Complete
Input for Compressor 1A.
Checksum on RAM copy of the Starter LLID configuration failed. Configuration recalled from
EEPROM.
Local
Local
CG-SVU02C-E4
Main Processor Diagnostics
Diagnostic Name
Starter Module
Memory Error Type
1 - Starter 2A
Starter Module
Memory Error Type
2 - Starter 1A
Starter Module
Memory Error Type
2 - Starter 2A
Affects
Target
None
Circuit
Circuit
Severity
Info
Immediate
Immediate
Persistence
Active Modes
[Inactive Modes]
All
Latch
Latch
Latch
All
All
Pumpdown
Terminated -
Circuit 1
Pumpdown
Terminated -
Circuit 2
Pumpdown
Terminated by
Time - Circuit 1
Pumpdown
Terminated by
Time - Circuit 2
MP: Invalid
Configuration
MP Application
Memory CRC Error
MP: Non-Volatile
Memory Reformat
Check Clock
MP: Could not
Store Starts and
Hours
MP: Non-Volatile
Block Test Error
Starter Failed to
Arm/Start -
Cprsr 1A
Starter Failed to
Arm/Start -
Cprsr 2A
Oil Analysis
Recommended -
Ckt #1
Circuit
Circuit
Circuit
Circuit
None
Chiller
None
Chiller
None
None
Circuit
Circuit
Circuit
Info
Info
Info
Info
Immediate
Immediate
Info
Info
Info
Info
Normal
Normal
Info
NonLatch
NonLatch
NonLatch
NonLatch
Latch
Latch
Latch
Latch
Latch
Latch
Latch
Latch
Latch
All
All
Criteria
Checksum on RAM copy of the Starter LLID configuration failed. Configuration recalled from
EEPROM.
Checksum on EEPROM copy of the Starter LLID configuration failed. Factory default values used.
Reset Level
Local
Local
Service or
Operational
Pumpdown
Service or
Operational
Pumpdown
Service Pumpdown
Service Pumpdown
All
All Modes
All
All
All
All
Checksum on EEPROM copy of the Starter LLID configuration failed. Factory default values used.
Operational or Service Pumpdown cycle for this circuit was terminated abnormally due to excessive time (op pd only) or due to a specific set of diagnostic criteria but w/o associated latching diagnostics . (RTWD max
Operation Pumpdown = 2 min)
Operational or Service Pumpdown cycle for this circuit was terminated abnormally due to excessive time (op pd only) or due to a specific set of diagnostic criteria but w/o associated latching diagnostics . (RTWD max
Operation Pumpdown = 2 min)
Service Pumpdown cycle for this circuit was terminated abnormally due to excessive time (RTWD max Service Pumpdown = 4 min).
Service Pumpdown cycle for this circuit was terminated abnormally due to excessive time (RTWD max Service Pumpdown = 4 min).
MP has an invalid configuration based on the current software installed.
Memory error criteria TBD
MP has determined there was an error in a sector of the Non-Volatile memory and it was reformatted.
Check settings.
The real time clock had detected loss of its oscillator at some time in the past. Check / replace battery?
This diagnostic can be effectively cleared only by writing a new value to the chiller's time clock using the TechView or DynaView's "set chiller time" functions.
MP has determined there was an error with the previous power down store. Starts and Hours may have been lost for the last 24 hours.
MP has determined there was an error with a block in the Non-Volatile memory. Check settings.
Starter failed to arm or start within the allotted time
(15 seconds).
Starter failed to arm or start within the allotted time
(15 seconds).
Local
Local
Local
Local
Local
Remote
Remote
Remote
Remote
Remote
Remote
Local
Local
Remote "Service Messages" enabled
Diagnostic occurs when accumulated circuit operating hours since last initialized exceeds 2000 hours.
Diagnostic can be manually cleared but will reoccur every month (720 hours on real time clock) as long as accumulator is not re-initialized.
CG-SVU02C-E4 43
44
Main Processor Diagnostics
Diagnostic Name
Oil Analysis
Recommended -
Ckt #2
Oil Filter Change
Recommended -
Cprsr 1A
Oil Filter Change
Recommended -
Cprsr 2A
LCI-C Software
Mismatch: Use BAS
Tool
Software Error
1001: Call Trane
Service
Affects
Target
Circuit
Circuit
Circuit
Chiller
All functions
Severity
Info
Info
Info
Info
Persistence
Latch
Active Modes
[Inactive Modes]
Criteria
"Service
Messages" enabled
Diagnostic occurs when accumulated circuit operating hours since last initialized exceeds 2000 hours.
Diagnostic can be manually cleared but will reoccur every month (720 hours on real time clock) as long as accumulator is not re-initialized.
Latch
"Service
Messages" enabled
(After RTUD release in Fall of 09:) Diagnostic occurs only when "service messages" are enabled and when Oil
Filter Life remaining falls below 5 %. Diagnostic can be manually cleared but will reoccur every month real time
(720 hours on real time clock) as long as the oil filter life remaining does not rise above 20% (through normal calculations or reinitializing) (Prior to RTUD Release in
Fall of 09): Diagnostic occurs only when "service messages" are enabled and when average oil pressure drop exceeds 18%. Diagnostic can be manually cleared but will reoccur every month (720 hours on real time clock) as long as average pressure drop does not fall below 16%.
Reset Level
Remote
Remote
Latch
"Service
Messages" enabled
(After RTUD release in Fall of 09:) Diagnostic occurs only when "service messages" are enabled and when Oil
Filter Life remaining falls below 5 %. Diagnostic can be manually cleared but will reoccur every month real time
(720 hours on real time clock) as long as the oil filter life remaining does not rise above 20% (through normal calculations or reinitializing) (Prior to RTUD Release in
Fall of 09): Diagnostic occurs only when "service messages" are enabled and when average oil pressure drop exceeds 18%. Diagnostic can be manually cleared but will reoccur every month (720 hours on real time clock) as long as average pressure drop does not fall below 16%.
Remote
All
NonLatch
The neuron software in the LCI-C module does not match the chiller type. Download the proper software into the LCI-C neuron. To do this, use the Rover service tool, or a LonTalk® tool capable of downloading software to a Neuron 3150®.
Remote
Immediate Latch
All
A high level software watchdog has detected a condition in which there was a continuous 1 minute period of compressor operation, with neither
Evaporator water flow nor a" contactor interrupt failure" diagnostic active. The presence of this software error message suggests an internal software problem has been detected. The events that led up to this failure, if known, should be recorded and transmitted to Trane
Controls Engineering.
Local
CG-SVU02C-E4
Main Processor Diagnostics
Diagnostic Name
Software Error 1002:
Call Trane Service
Affects
Target
All functions
Severity
Immediate
Persistence
Active Modes
[Inactive Modes]
All
Latch
Software Error 1003:
Call Trane Service
All functions
Immediate
Latch
All
Criteria
Reported if state chart misalignment in stopped or inactive state occurred while a compressor was seen to be operating and this condition lasted for at least 1 minute (cmprsr operation due to Service Pumpdown or with Contactor Interrupt Failure diagnostic is excluded).
The presence of this software error message suggests an internal software problem has been detected. The events that led up to this failure, if known, should be recorded and transmitted to Trane Controls Engineering.
Reported if state chart misalignment occurred inferred from either the Capacity Control, Circuit, or Compressor
State Machines remaining in the Stopping state for more than 3 minutes. The presence of this software error message suggests an internal software problem has been detected. The events that led up to this failure, if known, should be recorded and transmitted to
Trane Controls Engineering.
Reset Level
Local
Local
CG-SVU02C-E4 45
46
Diagnostics
Table 5 - Communication Diagnostics
Notes:
1. The following communication loss diagnostics will not occur unless that input or output is required to be present by the particular configuration and installed options for the chiller.
2. Communication diagnostics
(with the exception of "Excessive
Loss of Comm" are named by the Functional Name of the input or output that is no longer being heard from by the Main
Processor.
Many LLIDs, such as the Quad Relay
LLID, have more than one functional output associated with it. A comm loss with such a multiple function board will generate multiple diagnostics. Refer to the Chiller's wiring diagrams to relate the occurrence of multiple communication diagnostics back to the physical llid boards that they have been assigned to (bound).
Diagnostic Name
Comm Loss: Male Port
Unload Compressor 1A
Comm Loss: Male Port Load
Compressor 1A
Comm Loss: Male Port
Unload Compressor 2A
Comm Loss: Male Port Load
Compressor 2A
Comm Loss: Female Step
Load Compressor 1A
Comm Loss: Female Step
Load Compressor 2A
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Comm Loss: Motor Winding
Thermostat Compressor 1A
Comm Loss: Motor
Winding Thermostat
Compressor 2A
Comm Loss: External
Auto/Stop
Comm Loss: Emergency
Stop
Circuit
Circuit
Chiller
Chiller
Comm Loss: External
Circuit Lockout, Circuit #1
Comm Loss: External
Circuit Lockout, Circuit #2
Comm Loss: External Ice
Building Command
Affects
Target
Circuit
Circuit
Ice
Making
Mode
Severity Persistence Active Modes
[Inactive
Modes]
Normal Latch All
Criteria
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Normal
Normal
Latch
Latch
All
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Normal Latch All
Normal
Normal
Latch
Latch
All
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Normal Latch All
Normal
Normal
Normal
Special
Action
Special
Action
Special
Action
Latch
Latch
Latch
Latch
Latch
Latch
All
All
All
All
All
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. MP will nonvolatily hold the lockout state (enabled or disabled) that was in effect at the time of comm loss.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. MP will nonvolatily hold the lockout state (enabled or disabled) that was in effect at the time of comm loss
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Chiller shall revert to normal (non-ice building) mode regardless of last state.
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
RLC-SVU05A-E4
Diagnostics
Diagnostic Name
Comm Loss: Heat/Cool
Switch
Comm Loss: Outdoor Air
Temperature
Comm Loss: Evaporator
Leaving Water Temperature
Comm Loss: Evaporator
Entering Water
Temperature
Comm Loss: Condenser
Leaving Water Temperature
Comm Loss: Condenser
Entering Water
Temperature
Comm Loss: Discharge
Temperature Circuit 1,
Cprsr 1A
Comm Loss: Discharge
Temperature, Circuit 2 ,
Cprsr 2A
Affects
Target
Heat
Mode
Chiller
Chiller
Chiller
Chiller
Chiller
Circuit
Circuit
Severity
Special Action
Persistence
Latch
Active
Modes
[Inactive
Modes]
All
Criteria
RTUD with
ACFC#NONE-
Normal
Shutdown;
OATS=INST-
Special Action
Normal
Normal
Info and Special
Action
Info and Special
Action
Normal
Normal
Latch
Latch
Latch
Latch
Latch
Latch
Latch
All
All
All
All
All
All
All
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Reset
Level
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. The external input shall revert to normal (cooling) request regardless of last state. Chiller mode shall follow "OR" arbitration for heating/cooling mode, i.e. If any of the remaining inputs (front panel of BAS) are requesting heat mode, then the chiller shall be in heat mode.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. If the outdoor temperature is used for CHW reset, there shall be no CHW reset. Apply slew rates per Chilled Water Reset spec. For RTUD if this diagnostic occurs, operational pumpdown will be performed regardless of the last valid temperature. For RTWD, if installed for low ambient lockout, there shall be no lockout
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Note:
Entering Water Temp Sensor is used in EXV pressure control as well as ice making & CHW reset, so it must cause a unit shutdown even if Ice or CHW reset is not installed.
RTWD Only: Continual loss of communication between the
MP and the Functional ID has occurred for a 30 second period. If Chiller is running in the heat mode of operation normal shutdown, otherwise, informational only.
Discontinue Min Capacity Limit forced cprsr loading due to
Low DP in subsequent startups.
Remote
Remote
Remote
Remote
Remote
RTWD Only: Continual loss of communication between the
MP and the Functional ID has occurred for a 30 second period. If chiller running, and condenser water regulating valve option installed, force valve to 100% flow.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Remote
Remote
RLC-SVU05A-E4 47
48
Diagnostics
Diagnostic Name
Comm Loss: External
Chilled/Hot Water
Setpoint
Comm Loss: External
Current Limit Setpoint
Comm Loss: High
Pressure Cutout Switch,
Cprsr 1A
Comm Loss: High
Pressure Cutout Switch,
Cprsr 2A
Comm Loss: Evaporator
Water Flow Switch
Affects
Target
External
Chilled
Water setpoint
External
Current
Limit setpoint
Circuit
Severity
Special Action
Special Action
Immediate
Persistence
Latch
Active
Modes
[Inactive
Modes]
All
Criteria
Latch
Latch
All
All
Reset
Level
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Chiller shall discontinue use of the External Chilled
Water Setpoint source and revert to the next higher priority for setpoint arbitration
Remote
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Chiller shall discontinue use of the External Current limit setpoint and revert to the next higher priority for
Current Limit setpoint arbitration
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Remote
Remote
Circuit Immediate Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Remote
Chiller Immediate Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Remote
Chiller Immediate
Comm Loss: Condenser
Water Flow Switch
Comm Loss: Suction
Rfgt Pressure, Circuit #1
Comm Loss: Suction
Rfgt Pressure, Circuit #2
Comm Loss: Cond Rfgt
Pressure, Circuit #1
Comm Loss: Cond Rfgt
Pressure, Circuit #2
Comm Loss: Oil
Pressure, Cprsr 1A
Comm Loss: Oil
Pressure, Cprsr 2A
Comm Loss: Oil Return
Gas Pump Fill -
Circuit #1
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Normal
Latch
Latch
Latch
Latch
Latch
Latch
Latch
Latch
All
All
[Ckt/Cprsr lock out]
All
[Ckt/Cprsr lock out]
All
RTWD only: Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Note: This diagnostic is replaced by diagnostic 5FB below with Rev 15.0
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Note: This diagnostic is replaced by diagnostic 5FD below with Rev 15.0
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
All
All
All
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
All
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
RLC-SVU05A-E4
Diagnostics
Diagnostic Name
Comm Loss: Oil Return
Gas Pump Fill -
Circuit #2
Comm Loss: Oil Return
Gas Pump Drain -
Circuit #1
Comm Loss: Oil Return
Gas Pump Drain -
Circuit #2
Comm Loss: Oil Loss
Level Sensor Input -
Circuit #1
Comm Loss: Oil Loss
Level Sensor Input -
Circuit #2
Comm Loss: Evaporator
Water Pump Relay
Comm Loss: Condenser
Water Pump Relay
Comm Loss: Ice-Making
Status
Comm Loss: Evaporator
Rfgt Liquid Level,
Circuit #1
Comm Loss: Evaporator
Rfgt Liquid Level,
Circuit #2
Comm Loss: Starter 1A
Comm Loss: Starter 2A
Comm Loss: Electronic
Expansion Valve,
Circuit #1
Comm Loss: Electronic
Expansion Valve,
Circuit #2
Starter 1A Comm
Loss: MP
Affects
Target
Circuit
Circuit
Circuit
Circuit
Circuit
Chiller
Chiller
Chiller
Circuit
Severity
Normal
Normal
Normal
Normal
Persistence
Latch
Active
Modes
[Inactive
Modes]
All
Criteria
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Reset
Level
Remote
Remote
Remote
Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Remote
Normal
Normal
Normal
Special Action
Normal
Latch
Latch
Latch
Latch
Latch
All
All
All
All
All
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Remote
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
RTWD only: Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Chiller shall revert to normal (non-ice building) mode regardless of last state.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Remote
Remote
Remote
Remote
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
Normal
Immediate
Immediate
Normal
Normal
Immediate
Latch
Latch
Latch
Latch
Latch
Latch
All
All
All
All
All
All
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Remote
Local
Local
Remote
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Starter has had a loss of communication with the MP for a 15 second period.
Remote
Local
RLC-SVU05A-E4 49
Diagnostics
Diagnostic Name
Starter 2A Comm
Loss: MP
Comm Loss: Local
BAS Interface
Affects
Target
Circuit
Chiller
Severity
Immediate
Info
Comm Loss: Op
Status Programmable
Relays
Comm Loss: Starter
Panel High
Temperature Limit ,
Compressor 1A
Comm Loss:
Condenser Rfgt
Pressure Output
Comm Loss: Cond
Head Press Cntrl
Output
Comm Loss: Chiller %
RLA Output
Comm Loss: Fan
Inverter Fault,
Circuit #1
None
None
Chiller
Chiller
Chiller
Circuit
(fan control)
Comm Loss: Fan
Inverter Fault,
Circuit #2
Circuit
(fan control)
Comm Loss: Fan
Inverter Speed
Command,
Circuit #1
Comm Loss: Fan
Inverter Speed
Command,
Circuit #2
Comm Loss: Fan
Control Relays,
Circuit #1
Comm Loss: Fan
Control Relays,
Circuit #2
Comm Loss: Ext Noise
Setback Command
Comm Loss: Noise
Setback Relay
Comm Loss:
Evaporator Off-cycle
Freeze Protection
Relay
Circuit
(fan control)
Circuit
(fan control)
Circuit
Circuit
None
None
None
Info
Info
Info
Immediate
Info Latch
Special Mode (or in single fan deck:
Circuit Immediate shutdown)
Latch (or in single fan deck:Latch)
Special Mode (or in single fan deck:
Circuit Immediate shutdown)
Latch (or in single fan deck:Latch)
Special Mode (or in single fan deck:
Circuit Immediate shutdown)
Latch (or in single fan deck:Latch)
Special Mode (or in single fan deck:
Circuit Immediate shutdown)
Latch (or in single fan deck:Latch)
Normal
Normal
Info
Info
Info
Latch
Latch
Latch
Latch
Latch
Latch
Latch
Latch
Persistence
Latch
NonLatch
Latch
Active
Modes
[Inactive
Modes]
All
Criteria
All
All
Starter has had a loss of communication with the MP for a 15 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Use last valid BAS setpoints.
Diagnostic is cleared when successful communication is established with the LonTalk LLID (LCIC) or BacNet
LLID (BCIC).
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
All
All
All
All
All
All
All
All
All
All
All
All
All
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Reset
Level
Local
Remote
Remote
Local
Remote
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Remote
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Operate the remaining fans as fixed speed fan deck. For single fan deck configurations, this diagnostic causes a latching circuit shutdown
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Operate the remaining fans as fixed speed fan deck. For single fan deck configurations, this diagnostic causes a latching circuit shutdown
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Operate the remaining fans as fixed speed fan deck. For single fan deck configurations, this diagnostic causes a latching circuit shutdown
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Operate the remaining fans as fixed speed fan deck. For single fan deck configurations, this diagnostic causes a latching circuit shutdown
Remote
Remote
Remote
Remote
Remote
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period.
Remote
Remote
Remote
Remote
Remote
50 CG-SVU02C-E4
Diagnostics
Table 6 - Main Processor - Boot Messages and Diagnostics
DynaView Display Message
Boot Software Part
Numbers:
LS Flash --> 6200-0318-04
MS Flash --> 6200-0319-04
Err2: RAM Pattern 1 Failure
Err2: RAM Pattern 2 Failure
Err2: RAM Addr Test #1
Failure
Err2: RAM Addr Test #2
Failure
No Application Present
Please Load Application...
App Present. Running
Selftest.…
Selftest Passed
App Present. Running
Selftest…
Err3: CRC Failure
A Valid Configuration is
Present
Err4: UnHandled Interrupt
Restart Timer:
[3 sec countdown timer]
Description
Troubleshooting
The "boot code" is the portion of the code that is resident in all MPs regardless of what application code (if any) is loaded. Its main function is to run power up tests and provide a means for downloading application code via the MP's serial connection. The Part numbers for the code are displayed in the lower left hand corner of the DynaView during the early portion of the power up sequence and during special programming and converter modes. See below. For the
EasyView, the extension of the boot code part number is displayed for approximately 3 immediately following power up.
// This is normal, but you should provide this information when contacting Technical Service about power up problems.
There were RAM errors detected in RAM Test Pattern #1.
// Recycle power, if the error persists, replace MP.
There were RAM errors detected in RAM Test Pattern #2.
//Recycle power, if the error persists, replace MP.
There were RAM errors detected in RAM Address Test #1.
// Recycle power, if error persists, replace MP.
There were RAM errors detected in RAM Address Test #2.
//Recycle power, if the error persists, replace MP.
No Main Processor Application is present - There are no RAM Test Errors.
// Connect a TechView Service Tool to the MP's serial port, provide chiller model number (configuration information) and download the configuration if prompted by TechView. Then proceed to download the most recent RTAC application or specific version as recommended by Technical Service.
An application has been detected in the Main Processor's nonvolatile memory and the boot code is proceeding to run a check on its entirety. 8 seconds later, the boot code had completed and passed the (CRC) test.
// Temporary display of this screen is part of the normal power up sequence.
An application has been detected in Main Processor's nonvolatile memory and the boot code is proceeding to run a check on its entirety. A few seconds later, the boot code had completed but failed the (CRC) test.
//Connect a TechView Service Tool to the MP's serial port, provide chiller model number (configuration information) and download the configuration if prompted by TechView. Then proceed to download the most recent RTAC application or specific version as recommended by Technical Service. Note that this error display may also occur durring the programming process, if the MP never had a valid application any time prior to the download. If the problem persists, replace the MP.
A valid configuration is present in the MP's nonvolatile memory. The configuration is a set of variables and settings that define the physical makeup of this particular chiller. These include: number/airflow,/and type of fans, number/and size of compressors, special features, characteristics, and control options.
// Temporary display of this screen is part of the normal power up sequence.
An unhandled interrupt has occurred while running the application code. This event will normally cause a safe shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and attempt to restart the application and allow a normal restart of chiller as appropriate.
// This condition might occur due to a severe electro-magnetic transient such as can be caused by a near lightening strike. Such events should be rare or isolated and if no damage results to the CH530 control system, the Chiller will experience a shutdown and restart. If this occurs more persistently it may be due to an MP hardware problem. Try replacing the MP. If replacement of the MP proves ineffective, the problem may be a result of extremely high radiated or conducted EMI. Contact Technical Service.
If this screen occurs immediately after a software download, attempt to reload both the configuration and the application. Failing this, contact Technical Service.
CG-SVU02C-E4 51
52
Diagnostics
Err5: Operating System
Error
Restart Timer:
[30 sec countdown timer]
Err6: Watch Dog Timer Error
Restart Timer:
[30 sec countdown timer]
Err7: Unknown Error
Restart Timer:
[30 sec countdown timer]
Err8: Held in Boot by User
Key Press
Converter Mode
Programming Mode
Software Error 1001: Call
Trane Service
Software Error 1002: Call
Trane Service
Software Error 1003: Call
Trane Service
An Operating System error has occurred while running the application code. This event will normally cause a safe shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and attempt to restart the application and allow a normal restart of chiller as appropriate.
// See Err 4 above
A Watch Dog Timer Error has occurred while running the application code. This event will normally cause a safe shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and attempt to restart the application allowing a normal restart of chiller as appropriate.
An unknown Error has occurred while running the application code. This event will normally cause a safe shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and attempt to restart the application allowing a normal restart of chiller as appropriate
The boot detected a key press in the center of the DynaView or both the + and - keys pressed on an EasyView while the
MP was in the boot code. Upon seeing this message the user can use Techview to connect to the MP to perform a software download or another service tool function.
A command was received from the Service Tool (Tech View) to stop the running application and run in the "converter mode". In this mode the MP acts as a simple gateway and allows the TechView service computer to talk to all the LLIDS on the IPC3 bus.
A command was received by the MP from the Tech View Service Tool and the MP is in the process of first erasing and then writing the program code to its internal Flash (nonvolatile) Memory. Note that if the MP never had a prior application already in memory, the error code "Err3"will be displayed instead of this, during the programming download process.
See item in Main Processor Diagnostics table above
See item in Main Processor Diagnostics table above
See item in Main Processor Diagnostics table above
Design Note: In general, all failures/comm loss due to CH530 components should have a latching diagnostic and effect. All customer inputs failures (out of range, etc) are generally nonlatching.
RLC-SVU05A-E4
Diagnostics
Programmable Relays
(Alarms and Status)
CH530 provides a flexible alarm or chiller status indication to a remote location through a hard wired interface to a dry contact closure.
Four relays are available for this function, and they are provided
(generally with a Quad Relay Output
LLID) as part of the Alarm Relay
Output Option.
The events/states that can be assigned to the programmable relays are listed in the following table and through a TechView configuration.
Alarm - Latching
This output is true whenever there is any active latching shutdown diagnostic that targets the Unit,
Circuit, or any of the Compressors on a circuit.
Alarm - NonLatching
This output is true whenever there is any active non-latching shutdown diagnostic that targets the Unit,
Circuit, or any of the Compressors on a circuit.
Alarm
This output is true whenever there is any active latching or nonlatching shutdown diagnostic that targets the Unit, Circuit, or any of the Compressors on a circuit.
Alarm Ckt 1
This output is true whenever there is any active latching or nonlatching shutdown diagnostic that targets Circuit 1, or any of the
Compressors on Circuit 1.
Alarm Ckt 2
This output is true whenever there is any active latching or nonlatching shutdown diagnostic that targets Circuit 2, or any of the
Compressors on Circuit 2.
Unit Limit Mode
This output is true whenever a circuit on the unit has been running in one of the limit modes continuously for the Limit Relay debounce time. A given limit or overlapping of different limits must be in effect continuously for the debounce time prior to the output becoming true. It will become false if no limits are present for the debounce time.
Compressor Running
The output is true whenever any compressor is running.
Circuit 1 Running
The output is true whenever any compressor of Circuit 1 is running.
Circuit 2 Running
The output is true whenever any compressor of Circuit 2 is running.
Maximum Capacity
The output is true whenever the unit has reached maximum capacity continuously for the Max Capacity
Relay debounce time. The output is false when the unit is not at maximum capacity continuously for the fitler debounce time.
Head Pressure Relief Request
This relay output is energized anytime the chiller or a single circuit on the chiller is running in one of the following modes; Ice
Making Mode, or Condenser
Pressure Limit continuously for the duration specified by the Chiller
Head Relief Relay Filter Time. The
Chiller Head Relief Relay Filter Time is a service setpoint. The relay output is de-energized anytime the chiller exits all above modes continuously for the duration specified by the same Chiller Head
Relief Relay Filter Time
None:
This selection is desireable to provide an easy way for a customer to defeat the effect of the relay, if it has already been wired. For instance, if the relay was normally programmed as an "alarm" relay, and was wired to a claxon, it may be desirable to temporarily defeat the feature without changing wiring.
Default Assignments
The four available relays the Alarm
Package Option shall be assigned with the following defaults as follows:
Operation of the Relays:
If any of the four programmable annunciation relays are assigned with the given event or state, that relay shall be energized when the event or state is true and deenergized when the event or state is false pursuant to debounce or filter timing that may be applied per the details of a given assignment.
Table 7 - Default settings
LLID Name
Operating Status
Programmable Relays
LLID Software
Relay Designation
Relay 0
Relay 1
Relay 2
Relay 3
Output Name
Status Relay 4, J2-1,2,3
Status Relay 3, J2-4,5,6
Status Relay 2, J2-7,8,9
Status Relay 1, J2-10,11,12
Default
Unit Limit Mode
Maximum Capacity
Compressor Running
Alarm
RLC-SVU05A-E4 53
54
TechView Interface
TechView is the PC (laptop) based tool used for servicing Tracer
CH530. Technicians that make any chiller control modification or service any diagnostic with Tracer
CH530 must use a laptop running the software application
"TechView." TechView is a Trane application developed to minimize chiller downtime and aid the technicians' understanding of chiller operation and service requirements.
CAUTION:
Performing any Tracer
CH530 service functions should be done only by a properly trained service technician. Please contact your local Trane service agency for assistance with any service
requirements. TechView software is available via Trane.com.
(http://www.trane.com/commercial/s oftware/tracerch530/) This download site provides a user the
TechView installation software and
CH530 main processor software that must be loaded onto your PC in order to service a CH530 main processor. The TechView service tool is used to load software into the Tracer CH530 main processor.
Minimum PC requirements to install and operate TechView are:
• Pentium II or higher processor
• 128Mb RAM
• 1024 x 768 resolution of display
• CD-ROM
• 56K modem
• 9-pin RS-232 serial connection
• Operating system - Windows XP
Pro or Vista Business
• USB 2.0 or higher
• Internet Explorer 6.0 or higher
Note
: TechView was designed for
the proceeding listed laptop configuration. Any variation will have unknown results. Therefore, support for TechView is limited to only those operating systems that meet the specific configuration listed here. KestrelView is designed and validated for this specific laptop configuration. Any variation from this configuration may have different results. Therefore, support for KestrelView is limited to only those laptops configured as described above. Trane will not support KestrelView on a laptop configured differently. There is no support for laptops running Intel
Celeron, AMD, Cyrix, or processors other than Pentium. Only laptops with a Pentium II class processor or better are supported.
TechView is also used to perform any CH530 service or maintenance function.
Servicing a CH530 main processor includes:
• Updating main processor software
• Monitoring chiller operation
• Viewing and resetting chiller diagnostics
• Low Level Intelligent Device
(LLID) replacement and binding
• Main processor replacement and configuration modifications
• Setpoint modifications
• Service overrides
RLC-SVU05A-E4
RLC-SVU05A-E4
TechView Interface
TechView installation has been simplified. All related software, including Main Processor software, is now packaged together with the
TechView application resulting in a single installation.
Note: You do not have to uninstall an earlier version of TechView.
The new TechView will update the existing files.
To install TechView on your computer
1. Create a new folder titled CH530
(C:\CH530) on your hard drive.
This \CH530 folder is the standard location for the installation file. Storing the installation file in this location helps you remember where it is stored and makes it easier for technical support personnel to assist you.
2. Click the Download link for the latest version on the TechView
Software Download page.
The File Download – Security
Warning dialog box appears.
3. Click Save to copy the installation file to your hard drive.
Specify the \CH530 folder you created in Step 1 on the Save dialog box.
4. Double-click the installation (.exe) file.
The License Agreement dialog box appears.
5. Click I Agree after reviewing the
License Agreement.
The Choose Components dialog box appears. All components are selected by default. (These are the actual MP versions for all units.)
Deselect any components you do not want included in the installation.
Note: Deselecting components reduces the size of the installed application.
6. Click Install.
The Installation dialog appears with a progress meter indicating the percentage of the installation that has occurred. An installation information file appears when the installation is complete.
7. Click Close to exit the installation routine.
55
www.trane.com
For more information, contact your local sales office or e-mail us at [email protected]
Literature Order Number
Date
RLC-SVU05A-E4
1109
New
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication.
Trane bvba
Lenneke Marelaan 6 -1932 Sint-Stevens-Woluwe, Belgium
ON 0888.048.262 - RPR BRUSSELS
advertisement