Application Note #627

Revision B

March 2017

LG VRF – Lutron Palladiom Thermostat Integration

Overview

Lutron Electronics and LG, a leading supplier of Variable Refrigerant Flow (VRF) technology, have integrated a sleek, intuitive design of the Palladiom Thermostat for control of LG Systems. This integration is achieved by using a Palladiom

Thermostat, a Lutron Fan Coil Unit (FCU) Controller (myRoom) or Palladiom HVAC Controller (HomeWorks QS), and the

LG Dry Contact Closure interface. This integration is available for Lutron projects in the United States. 1

System Topology

The System includes a Palladiom Thermostat with the FCU Controller (Model SMC550050407) or Palladiom HVAC

Controller (SMC55-RESI) connected to the LG Dry Contact interface (Model PDRYCB300).

Thermostat Link

To LG Indoor Unit

QS Link to Lutron System Contact Closures

1 LG offers multiple other dry contact closure interfaces in International regions. The Lutron Palladiom Thermostat has not been tested to work with these interfaces. Please contact LG for further information regarding compatibility.

1 Customer Assistance — 1.844.LUTRON1

Wiring Diagrams

3-Speed Fan

Heat and Cool

Application Note #627

Power Supply

Common

Power Supply

12-24 V~ / 24 V-

Supply

Supply

5V

12V

AO2

DO6

AO1

GND

DI6

GND

DI5

AI5

DI4

AI4

DI3

AI3

DI2

AI2

DI1

AI1

5

AO

3 G 4

Fan Coil Unit Controller

SMC5500050407 or

Palladiom HVAC Controller

SMC55-RESI

LAN

DO6 DO1 DO2 DO3 N DO4

G + –

RS485

12 11 10 9 8 7 6 5

Slide to “VOLT”

Note: Do not input voltage signal in “NON

VOLT” setting mode, otherwise it will cause serious damage.

RESET_SW

CN_TherOper CN_MODE

CHANGEOVER_SW

CN_WIND

SETTING_SW

DISPLAY_LED

TEMP_SW

CN_OUT

Rotate to “1”

Rotate to “F”

2 www.lutron.com/help

Application Note #627

Wiring Diagrams (continued)

3-Speed Fan

Heat Only

Power Supply

Common

Power Supply

12-24 V~ / 24 V-

Supply

Supply

5V

12V AO2

DO6

AO1

GND GND

DI6 DI5

AI5

DI4

AI4

DI3

AI3

DI2

AI2

DI1

AI1

5

AO

3 G 4

Fan Coil Unit Controller

SMC5500050407 or

Palladiom HVAC Controller

SMC55-RESI

LAN

DO6 DO1 DO2 DO3 N

12 11 10 9 8 7 6 5

DO4

G + –

RS485

Slide to “VOLT”

Note: Do not input voltage signal in “NON

VOLT” setting mode, otherwise it will cause serious damage.

RESET_SW

CN_TherOper CN_MODE

CHANGEOVER_SW

CN_WIND

SETTING_SW

DISPLAY_LED

TEMP_SW

CN_OUT

Rotate to “1”

Rotate to “F”

3 Customer Assistance — 1.844.LUTRON1

Application Note #627

Wiring Diagrams (continued)

3-Speed Fan

Cool Only

Power Supply

Common

Power Supply

12-24 V~ / 24 V-

Supply

Supply

5V

12V

AO2

DO6

AO1

GND

DI6

GND

DI5

AI5

DI4

AI4

DI3

AI3

DI2

AI2

DI1

AI1

5

AO

3 G 4

Fan Coil Unit Controller

SMC5500050407 or

Palladiom HVAC Controller

SMC55-RESI

LAN

DO6 DO1 DO2 DO3 N DO4

G + –

RS485

12 11 10 9 8 7 6 5

Slide to “VOLT”

CN_TherOper CN_MODE

CN_WIND

CHANGEOVER_SW

Rotate to “1”

RESET_SW

SETTING_SW

DISPLAY_LED

Rotate to “F”

Note: Do not input voltage signal in “NON

VOLT” setting mode, otherwise it will cause serious damage.

TEMP_SW

CN_OUT

Design Considerations

• In heat only or cool only applications, the FCU controller and Palladiom HVAC controller must be configured for heating only or cooling only.

• The Palladiom HVAC controller must be configured to control FCUs.

• The PDRYCB300 interface should be supplied by your local LG distributor.

• The FCU controller must be part number SMC5500050407 from Lutron.

• The Palladiom HVAC controller must be part number SMC55-RESI from Lutron.

• Use one PDRYCB300 interface per indoor unit controlled by the Palladiom Thermostat.

• Power supply is required and field supplied by others.

• Use 18 AWG (1.0 mm 2 ) wire between PDRYCB300 and Lutron controller, maximum 500 ft (152 m).

• Lutron myRoom systems and Palladiom Thermostat must be programmed by a trained Lutron service engineer or an authorized distributor.

• Lutron HomeWorks QS systems and Palladiom Thermostat must be programmed by a qualified system programmer.

• A trained LG HVAC professional may change the PDRYCB300 configurations based on user preference.

4 www.lutron.com/help

Application Note #627

Lutron, HomeWorks, and Palladiom are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries.

myRoom is a trademark of Lutron Electronics Co., Inc.

LG is a registered trademark of LG Electronics Inc.

Lutron Contact Numbers

WORLD HEADQUARTERS

USA

Lutron Electronics Co., Inc.

7200 Suter Road

Coopersburg, PA 18036-1299

TEL: +1.610.282.3800

FAX: +1.610.282.1243

[email protected]

www.lutron.com/help

EUROPEAN HEADQUARTERS

United Kingdom

Lutron EA Ltd.

6 Sovereign Close

London, E1W 3JF United Kingdom

TEL: +44.(0)20.7702.0657

FAX: +44.(0)20.7480.6899

FREEPHONE (UK): 0800.282.107

Technical Support: +44.(0)20.7680.4481

[email protected]

ASIAN HEADQUARTERS

Singapore

Lutron GL Ltd.

390 Havelock Road

#07-04 King’s Centre

Singapore 169662

TEL: +65.6220.4666

FAX: +65.6220.4333

Technical Support: 800.120.4491

[email protected]

North & South America

Customer Assistance

USA, Canada, Caribbean:

1.844.LUTRON1 (1.844.588.7661)

Mexico:

+1.888.235.2910

Central/South America:

+1.610.282.6701

Asia Technical Hotlines

Northern China: 10.800.712.1536

Southern China: 10.800.120.1536

Hong Kong: 800.901.849

Indonesia: 001.803.011.3994

Japan: +81.3.5575.8411

Macau: 0800.401

Taiwan: 00.801.137.737

Thailand: 001.800.120.665853

Other Countries: +65.6220.4666

5

Lutron Electronics Co., Inc.

7200 Suter Road

Coopersburg, PA 18036-1299 U.S.A.

P/N 048627 Rev. B 03/2017