Lopi 400 PI Owner's Manual

Add to My manuals
42 Pages

advertisement

Lopi 400 PI Owner's Manual | Manualzz
LOPI
400 PS-PELLET STOVE
400 PI- PELLET INSERT
PREPARATION, INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
KEEP THIS MANUAL
September, 1991
Manufactured By:
- > Travis Industries, Inc.
10850 117th Place N.E. Kirkland, WA 98033
O Copyright 1991 T.I.
SAFETY PRECAUTIONS
VIEWING DOOR AND ASHPAN MUST BE CLOSED
AND LATCHED DURING OPERATION.
THIS UNIT MUST BE PROPERLY INSTALLED IN
ORDER TO PREVENT THE POSSIBILITY OF A HOUSE
FIRE. FOR YOUR SAFETY THE INSTALLATION
INSTRUCTIONS MUST BE STRICTLY ADHERED TO.
DO NOT USE MAKESHIFT METHODS OR COM-
PROMISE INSTALLATION.
CONTACT YOUR LOCAL BUILDING OFFICIALS TO
OBTAIN A PERMIT AND INFORMATION ON ANY IN-
STALLATION RESTRICTIONS OR INSPECTION RE-
QUIREMENTS IN YOUR AREA. ALSO, NOTIFY
YOUR INSURANCE COMPANY THAT YOU ARE
INSTALLING A PELLET BURNING APPLIANCE.
THIS UNIT'S EXHAUST SYSTEM WORKS WITH A
NEGATIVE COMBUSTION CHAMBER PRESSURE
AND A LOW POSITIVE CHIMNEY PRESSURE. IT IS
VERY IMPORTANT THAT THE EXHAUST SYSTEM
BE COMPLETELY AIRTIGHT AND PROPERLY
INSTALLED. THE CHIMNEY JOINTS SHOULD BE
SEALED WITH RTV 500 DEGREES FAHRENHEIT
(500° F) (260° C) SILICONE SEALANT. IMPROPERLY
INSTALLED STOVES ARE THE MAJOR CAUSE OF
HOME FIRES.
NEVER BLOCK FREE AIRFLOW THROUGH THE
OPEN VENTS OF THE UNIT.
NEVER TRY TO REPAIR OR REPLACE ANY PART
OF THE APPLIANCE UNLESS INSTRUCTIONS ARE
GIVEN IN THIS MANUAL. ALL OTHER WORK
SHOULD BE DONE BY A TRAINED TECHNICIAN.
WAIT UNTIL THE APPLIANCE HAS COOLED
BEFORE CARRYING OUT MAINTENANCE PRO-
CEDURES.
TRAVIS INDUSTRIES, INC. GRANTS NO
WARRANTY, IMPLIED OR STATED, FOR THE
INSTALLATION OR MAINTENANCE OF YOUR
STOVE, AND ASSUMES NO RESPONSIBILITY FOR
ANY CONSEQUENTIAL DAMAGE(S).
DO NOT INSTALL IN A BEDROOM.
KEEP FOREIGN OBJECTS OUT OF THE HOPPER.
ALWAYS FOLLOW THE INSTRUCTIONS IN THE
OWNER'S MANUAL.
KEEP THIS MANUAL FOR LATER USE.
PAGE 2
THE LOPI 400 APPLIANCE IS DESIGNED AND
APPROVED FOR THE BURNING OF PELLETIZED
WOOD FUEL ONLY. THE BURNING OF ANY TYPE
OF FUEL OTHER THAN THAT LISTED WILL VOID
ALL WARRANTIES AND THE SAFETY LISTING OF
THE UNIT. DO NOT ATTEMPT TO BURN ANY
OTHER FUEL THAN SPECIFIED IN THIS MANUAL
THE EXHAUST SYSTEM SHOULD BE CHECKED
TWICE A YEAR MINIMUM FOR ANY BUILD-UP OF
SOOT OR CREOSOTE.
GASOLINE OR OTHER FLAMMABLE LIQUIDS MUST
NEVER BE USED TO START THE FIRE OR
"FRESHEN UP" THE FIRE. DO NOT STORE OR
USE GASOLINE OR OTHER FLAMMABLE LIQUIDS
IN THE VICINITY OF THIS APPLIANCE.
ASHES MUST BE DISPOSED OF IN A METAL
CONTAINER WITH A TIGHT FITTING LID, AND
PLACED ON A NON-COMBUSTIBLE SURFACE
BEFORE FINAL DISPOSAL.
THIS UNIT MUST BE CONNECTED TO A
GROUNDED, STANDARD 110 VOLT, 60 HZ
ELECTRICAL OUTLET. NEVER ROUTE THE
POWER CORD UNDER OR IN FRONT OF THE
UNIT.
DO NOT, UNDER ANY CIRCUMSTANCES, CUT OR
REMOVE THE GROUNDING PRONG FROM THE
POWER CORD.
DO NOT USE AN ADAPTOR PLUG.
BEFORE REMOVING PANELS, DISCONNECT THE
POWER CORD FROM THE ELECTRICAL OUTLET.
NOTE: TURNING THE CONTROL SWITCH OFF
DOES NOT DISCONNECT THE POWER TO ALL
ELECTRICAL COMPONENTS.
WHEN INSTALLED IN A MOBILE HOME, THE UNIT
MUST BE GROUNDED TO THE STEEL CHASSIS OF
THE MOBILE HOME AND BOLTED TO THE FLOOR
IN COMPLIANCE WITH AND ACCORDING TO
H.U.D. REQUIREMENTS.
THE APPLIANCE WILL NOT OPERATE USING
NATURAL DRAFT OR WITHOUT A POWER
SOURCE FOR THE BLOWERS AND FUEL-FEEDING
SYSTEMS.
TABLE OF CONTENTS Page
Introduction and Important Information
Safety Precautions
Features and Specifications - Stove & Insert
STOVE INSTALLATION:
Preparation for Installation
Freestanding Installation Specifications
Horizontal Corner Installation
Vertical Exterior Flue Installation
inside Vertical Installation with Roof Termination
Hearth Stove Installation into existing Masonry Fireplace or Zero Clearance (Metal) Fireplace —-----—
Vertical Installation into existing Factory-Built Chimney
Horizontal Installation
Freestanding Mobile Home Installation
Freestanding Residential Alcove Installation
INSERT INSTALLATION:
Preperation For Installation
Insert Installation Specifications
Insert Installation into Existing Masonry Fireplaces
Insert installation into Existing Metal (Z.C.) Fireplaces
USE AND CARE: Pellet Stove and Pellet Insert
Location and Use of Controls
Operating your Pellet Appliance
Normal Operating Sounds
Care and Maintenance
, .
Maintenance Schedule - Weekly
Maintenance Schedule - 1000 lbs (1/2 ton) of Fuel Used
Maintenance Schedule - 6000 lbs (3 tons) of Fuel Used
Before Calling for Service
Replacement Parts List
Limited Warranty
Product Listing Information
PAGE 3
1
2
10
11
12
13
14
15
16
17
19
22
24
25
26
28
29
30
31
32
36
39
41
Pda,
FEATURES AND SPECIFICATIONS
w * FREESTANDING CONVENIENT
LONG BURN TIME
* ALCOVE VERSATILE
CLOSE CLEARANCES
* MOBILE HOME
* MASONRY FIREPLACE INSERT POWERFUL EFFICIENT FANS
* FACTORY-BUILT (Z.C.) HUGE HOPPER
FIREPLACE INSERT |
STAINLESS STEEL FIREPOT
QUIET OPERATION
Stove Insert
Heating Capacity SQ/FT .................ece.e.o 1200 to 1900 Maximum ..... reese 1200 TO 1900 Maximum
Burn Rate Ibs/hr...................eerercacecenoes 1.8eto5 ee, 1.2105
wr Overall EfficienCY ass re 80% (Estimated) @ = ................. 80% (Estimated)
Emissions Grams/per hour ..................... N/A (EPA Exempt) =... N/A (EPA Exempt)
Maximum Buming Time (Hours) ............. Upto50 QU —.................. Up to 41
Flue Opening Diameter ......................e.. 3.0°(76mm) een, 3.0" (76 mm)
Height from floor to top of stove on:
Pedestal ....................e.oerccvos 34 1/4" (870 mm) Depth Into Fireplace ............... 12 1/4" (311mm)
Legs, Brass ................eococon. 30 1/8" (765 mm) — Extension on to Hearth........ .. 12 7/8" (327mm)
Legs, Cast... 30 1/8" (765 mm) Width into fireplace -See page 19
Legs, Black... 28 3/4" (730 mm) Overall Height.......19" (483mm) (Add 1" for flue)
Overall Width ...................eeneceroezccon mee. 24" (610 тт) eee. 37 7/8" (962mm)
Overall Depth....................onecocmran e. 25 1/4" (641 mn) — Lenrvensenenneees 25 3/16 * (640mm)
Hopper Capacity (Ibs) ......................-..... 60 (27 KG) (Estimated) .................. 50 (23 KG) (Estimated)
Unit Weight (Ibs) ...........................e.mosznes 260 (118 К) А р|@.................. 240 (109 КС)
Electrical Rating ............................ pueeocono 115 Volts, 3 Amps, 60 HZ .................. 115 Volts, 3 Amps, 60 HZ
Watts... caconeeee 180 (Approx) eevee 180 (Approx.)
Standard Bay insert covers a fireplace opening
of 28”(711mm) Height x 37" (940mm) Wide
FUEL: The unit is designed to operate using 1/4 inch diameter pellets that comply with A.P.F.I.* standards. If the fuel
does not comply to this standard, the unit may not operate as designed. If the pellets are larger that 1/4 inch diameter
the unit may need adjustments; consuit with your dealer.
NOTE: * Store pellets in a clean dry place.
* Emissions information and efficiency information based on tests conducted by E.E.M.C. Laboratory.
BTU. output will vary depending on pellet size, moisture content and pellet type. Heating capacity is
~ subject to variations due to pellet type, relative moisture content, floor plan, degree of home
insulation, and temperature zone.
* A.F.P.1. - Association of Pellet Fuel industries.
PAGE 4
PREPARATION FOR INSTALLATION — PELLET STOVE
READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW APPLIANCE. FAILURE TO
FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJU RY, OR EVEN DEATH.
PREPARATION:
1. Remove all tape and packaging.
2. Remove the wood shipping frame from around and under the appliance.
3. Check that no parts have become loose and the appliance has not been damaged during shipping.
4. Remove the hardware pack from the appliance.
>. READ THE OWNER'S MANUAL BEFORE PROCEEDING.
* Appliance should be located such that no doors, drapes, furniture or other combustibles can be placed close or
swing closer than the minimum stated clearances.
* The appliance must be installed in a level, secure position.
* Required Floor Protection: .
Minimum size 24"W x 33"D (610mm W x 838 mmD) Side un (152 mm)
of non-combustible material with a minimum thickness Back - 0" 0 mm)
of 26 gauge (.018", .5mm) floor protection must extend mm)
under the appliance.
Chimney Lengths Maximum Minimum
Vertical 33' (10.06 т) Subject to installation. See Fig. 9
Horizontal 10' (3.05 m) Subject to installation. See Fig. 449
{
* Do not obtain combustion air from attic, garage, unventilated crawl space or any other enclosed space. Do not ~~
locate combustion air inlet at an elevation higher than exhaust termination.
* Outside air (combustion air intake) is recommended, but not required, for all residential installations, but is
required for mobile home installations. If an outside air intake (combustion air intake) is used, it must be
connected to a 1-3/4", or larger, metal or aluminium duct with a rodent screen fixed to the termination.
Do not use P.V.C.duct.
NOTE: TRAVIS INDUSTRIES, INC., recommends that an outside air (combustion air) intake be used in all
installations. If one is not used, there is a possibility of combustion gases (smoke) being released into your home,
if there is a power outage while the unit is in operation.
* The LOPI 400 peliet stove exhaust vent accepts 3" diameter pellet vent pipe. Some of the brands
available for use with the LOPI 400 are:
1. Duravent Model PL-Vent 2. James A. Ryder MFG Model PL-Vent — 3, MetalFab Model Pellet Vent
Simpson Dura-Vent + Ryder Mfg, Inc. P.O. Box 1138
Р.О. Вох 1510 241 Arvin Avenue Wichita, KS 67201
Vacaville, CA 95688 Stoney Creek, Ontario Canada (316) 943-2351
(707) 446-1786 or (416) 662-1701
1-800-227-8846
NOTE: 4" diameter may be substituted when a 3" to 4" adapter is used.
See manufacturer's installation instructions for precautions required for passing vent through a combustible wall a
or ceiling. Do not connect this appliance to a vent serving another appliance. ad
All sections of pellet vent must be fastened to each other with sheet metal screws and silicone sealed with type
500 degrees Fahrenheit (260°C) RTV (high heat) silicone sealer, to ensure that the joints are airtight.
PAGE 5
PREPARATION FOR INSTALLATION —
PELLET STOVE (cont)
Your Pellet Stove appliance comes completely assembled. Options are available for the different types of
installations. The options are listed below and are boxed separately from the appliance. They require assembly.
1. Pedestal.
2. Leg Kit, Black.
3 Leg Kit, Brass.
4. Leg Kit, Cast Black
When lifting the appliance, you may choose to remove the interior components to make it lighter. Refer to figures
14, 15 and 16 for the proper sequence of removal and replacement of internal components.
1. Pedestal Assembly;
Open the box marked Pedestal and remove the pedestal and the two attachment bolts and washers (3/8" diameter
- 16 x 3/4" hex. head bolt).
Lift the stove onto the pedestal. Line up the threaded bolt holes in the bottom of the stove with the two holes in the
mounting angle of the pedestal. Using a 9/16" open-end or socket wrench, fasten the pedestal to the stove with the
supplied bolts and washers. NOTE: The two front leg bolts must remain in place when installed on a pedestal.
a. Leg Kit, Black Assembly:
Open the box marked Leg Kit, Black and remove the four 6-1/2" high black steel legs, complete with leveling
bolts, the four attachment bolts (3/8" diameter - 16 x 3/4" hex. head bolts} and the washers.
Raise the stove on some pieces of lumber to a height of about 7". Line up the hole in the leg with the threaded bolt
hole in each corner of the stove bottom. Using a 9/16" open end or socket wrench, fasten the leg to the stove with
the supplied bolts and washers, making sure the legs are flush with the corners of the stove.
Stand the stove on its legs and place it in the desired position. Using a 3/8" open end wrench, adjust the leveling
bolts in the base of each leg until the stove is level and does not rock.
3, Leg Kit. Brass or Cast Black Assembly:
Open the box marked Leg Kit, Brass (or Cast) and remove the four 7-7/8" high legs, complete with leveling bolts,
the four attachment bolts (3/8" diameter - 16 x 3/4" hex. head bolts) and the washers.
Raise the stove on some pieces of lumber to a height of about 8-1/2". Line up the hole in the leg with the threaded
bolt hole in each corner of the stove bottom. Using a 9/16" open end or socket wrench, fasten the leg to the stove
with the supplied bolts and washers, making sure the legs are flush with the comers of the stove.
Stand the stove on its legs and place it in the desired position. Using a 1/4" open end wrench, adjust the leveling
bolts in the base of each leg until the stove is level and does not rock.
PAGE 6
FREESTANDING
INSTALLATION - SPECIFICATIONS
-
LOCATION OF EXHAUST VENT AND OUTSIDE COMBUSTION AIR INTAKE
3" DIA
„ 24 MIN. [610mm]
|
=
EXHAUST BTN EA 3 1/16"
(76mm)
"A"
Eme
Y
|
COMBUSTION
arm TT AIR INTAKE
13/4" O.D.
(44mm)
| 22 3/4” MIN. [578mm]
A’
PEDESTAL 13 7/8" (352mm)
LEGS, BRASS 9 3/4" (248mm)
LEGS, CAST 9 3/4" (248mm)
LEGS, BLACK 8 3/8" (213mm)
FIGURE 1
PAGE 7
|
|
A
14 1/2
10 7/8
10 7/8
9 1/2
"Ви ~~
“B”
* (368mm)
" (276mm)
" (276mm)
" (241mm)
FREESTANDING INSTALLATION SPECIFICATIONS
FLOOR PROTECTION (Fig. 2 &3)
G - Front - 6“ - (152 mm) NOTE: Front floor protection is measured from the door opening.
H - Sides - 0" - ( O mm)
H - Back -0"-( Omrm)
NOTE: Floor protector should extend to areas below andi-2" (50 mm) to each side of a "tee" when used. (See Fig. 6.)
CLEARANCE TO COMBUSTIBLES:
INTERIOR VERTICAL FLUE INSTALLATION:
Figures 2 & 3
A Sidewall to unit 9" - (229 mm)
B Backwall to unit 11" - (279 mm)
C Comer wall to unit 2“ - ( 51 mm)
D Flue vent/chimney 3" - ( 76 mm)
NOTE: Dimension "C", corner wall to unit, will vary depending on type and brand of pellet vent used. Check your
pellet vent installation instructions for information on its size and clearance required to a combustible.
HORIZONTAL THROUGH THE WALL INSTALLATION OR VERTICAL
EXTERIOR INSTALLATION
Figures 2 & 3
A Sidewall to unit 9" - (229 mm)
B Backwall to unit 3" - ( 76 mm)
C Corner wall to unit 2" - ( 51 mm)
D Flue vent/chimney 3" - ( 76 mm) |
BACKWALL CORNER WALL
SIDEWALL
CORNER WALL
= eat,
CLA LT te ea Te
LTE ae wine
re AR SE aa
pre ete certe
as E анна сотен
rr E OA Eee
Co UI Tae
e E поели е
Ta
FIGURES 243
PAGE 8
HORIZONTAL CORNER INSTALLATION
3" MIN. [76mm]
SN
AS
Les
TION í
OPTIONAL DIRECTIO ZZ Er 2° MIN. [Stmm]
WALL THIMBLE = . N
12° MIN. [304mm] ~ COMBUSTION AIR INTAKE
| — PELLET VENT
i
TT CHIMNEY CAP
FIGURE 4
The exhaust vent termination on either vertical or horizontal installations shall be located as follows:
>
* A minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door
or window that opens, or any opening into a building.
° A minimum of 2 feet (610 mm) from any adjacent building.
* A minimum of 7 feet (2134 mm) above grade, when located adjacent to public walkways.
* A minimum of 2 feet (610 mm) above grass, plants or other combustible surfaces.
PAGE 9
VERTICAL EXTERIOR FLUE SYSTEM
~~ NOTE: FOR STANDARD OR CORNER INSTALLATION, STANDARD INSTALLATION SHOWN.
WIND / RAIN CAP Z En
FLASHING
24” MIN. [610mm]
SUPPORT BRACKET
EVERY 5 FEET
IF
PELLET VENT
3° MIN. [76mm] я
u 3" MIN. [76mm]
WALL THIMBLE
TEE WITH
CLEAN OUT COVER
NON—COMBUSTIBLE
HEARTH PAD
- —— | — COMBUSTION AIR
SMN | | INTAKE WITH 90°
(152mm) / NIN ELBOW OR HOOD
FIGURE 5
|
The exhaust vent termination on either vertical or horizontal installations shall be located as follows:
A minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door
or window that opens, or any opening into a building.
— * A minimum of 2 feet (610 mm) from any adjacent building.
A minimum of 7 feet (2134 mm) above grade, when located adjacent to public walkways.
A minimum of 2 feet (610 mm) above grass, plants or other combustible surfaces.
PAGE 10
INSIDE VERTICAL INSTALLATION
WITH ROOF TERMINATION
NOTE: FOR STANDARD OR CORNER INSTALLATION, STANDARD INSTALLATION SHOWN.
WIND / RAIN CAP —Z \ _
FLASHING
24" MIN. [610mm]
OPTION 1. WALL OR <
CEILING THIMBLE
OPTION 2. FIRESTOP WITH
3" [76mm] CLEARANCE
br
3° MIN. [76mm] ——+
=
5 MIN. [76mm] PELLET VENT
TEE WITH
у CLEAN OUT COVER
N COMBUSTION AIR
mi o MIN — ELBOW OR HOOD
mp ua 6" MIN NON-COMBUSTIBLE
A MATERIAL TO
LL LL TT TTT EXTEND UNDER TEE
FIGURE 6
The exhaust vent termination on either vertical or horizontal installations shall be located as follows:
* A minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door
or window that opens, or any opening into a building.
A minimum of 2 feet (610 mm) from any adjacent building.
* A minimum of 7 feet (2134 mm) above grade, when located adjacent to public walkways.
* A minimum of 2 feet (610 mm) above grass, plants or other combustible surfaces.
PAGE 11
al
HEARTH STOVE INSTALLATION INTO EXISTING
MASONRY & ZERO CLEARANCE (METAL) FIREPLACE
WIND / RAIN CAP = SEAL COVER PLATE TO
6” MIN. [152mm] CHIMNEY WITH SILICONE
4" MIN. 102 f7 SEALER
y mm] U POSITIVE
CONNECTION
¡> ? STAINLESS STEEL SINGLE (COMPLETE RELINE).
WALL PIPE OR FLEXIBLE ы Du
LINER CAN BE USED = 1
(SEE NOTE BELOW). |; («9 BLOCK-OFF PLATE OR
— NON-COMBUSTIBLE
— I MATERIAL MAY BE USED
- 4 AT THE FIREPLACE
a |. DAMPER LOCATION. THIS
© / 1 SEAL MUST BE AIRTIGHT.
SINGLE WALL TEE a / 1 (SEE BELOW)
CAN BE USED AS AN OPTION / 7 3
— ‘ 12" TERMINATION OF
À | ( he DIRECT CONNECTION
не АЕ
N | || a
\
. OPTIONAL
— == OUTSIDE COMBUSTION
e" MIN. AIR INTAKE
(152mm)
| HEARTH PAD | AIR INTAKE OPTIONS
ULLI rt TT 1 1 1] |
y
FIGURE 7
NOTE: Masonry fireplace installations require a direct connection or positive (complete reline) connection to the
chimney flue. With a direct connection a block-off plate made of metal or other non-combustible material (i.e.
Kaowool or high temperature fiberglass insulation) must be used at the damper location and sealed airtight.
The singlewall pipe or flexible liner must extend past the block-off plate or insulation by one (1) foot (305 mm)
or to the first flue tile if the chimney has a tile lining.
With a positive connection, the block-off plate at the damper location is optional, but a sealed cover plate is
required at the top of the chimney. A positive connection (complete reline) is recommended for ease of
cleaning. Zero clearance (metal) fireplace installations require a complete re-line to topof chimney.
PAGE 12
VERTICAL INSTALLATION INTO EXISTING
FACTORY BUILT CHIMNEY
NOTE: FOR STANDARD OR CORNER INSTALLATION, STANDARD INSTALLATION SHOWN.
Flashing
OPTION 1. Wali Or
Ceiling Thimble
OPTION 2. Firestop With
3" (76mm) Clearance
de ca o vo
Зе;
Zas
ma
24" Min. (610mm)
Eo
! :
\
} $
‘ $
ta ме чо .
У Keep Clearance Specified
3 Fg By Factory Built Chimney
a Manufacturer
T™~
3" Min. (76mm)
—
6" Min. DD с
(152mm)
|
A
x
$
N Pellet Vent
N y» With
NN € Clean Out Cover
N
Ё
t Optional
: Combustion Air
Intake With 90°
; Elbow Or Hood
Non-Combustible
__ Material To Extend
FIGURE 8
Under The Tee
The exhaust vent termination on either vertical or horizontai installations shall be located as follows:
À minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door
Or window that opens, or an
A
A
A
Y opening into a building.
minimum of 2 feet (610 mm) from any adjacent building.
minimum of 7 feet (2134 mm)
minimum of 2 feet (610 mm) a
above grade, when located adjacent to
bove grass, plants or other combustible
PAGE 13
public walkways.
surfaces.
{ ча”
HORIZONTAL INSTALLATION
7
WIND / RAIN CAP —Z >s
FLASHING
|
|
| 24" MIN. [610mm]
|
\
|
U —
24" (610mm)
—
+ MIN. [76mm] À REFER NOTE
LY”
3” MIN. {76mm —
H 427 MÍN
305mm CHIMNEY CAP
/ и WALL
THIMBLE
== COMBUSTION AIR
6" MIN. INTAKE WITH 90
(152mm) ‹ 1 AN ELBOW OR HOOD
HEARTH PAD 12” MIN
NON-COMBUSTIBLE MATERIAL
FIGURE 9
NOTE: A 6 ft (1829mm) vertical rise is recommended to maintain a better draft. However, a shorter rise may
be used. Vertical installation as in Figure 5 is preferred. if a shorter rise is used and the termination is under
an eave or overhang, the termination must be at least 24" (610mm) from the combustible material, and the
chimney must be vented at least 12" (305mm) from the dwelling.
The exhaust vent termination on either vertical or horizontal installations shall be located as follows:
« A minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door
or window that opens, or any opening into a building.
« A minimum of 2 feet (610 mm) from any adjacent building.
. A minimum of 7 feet (2134 mm) above grade, when located adjacent to public walkways.
‚ A minimum of 2 feet (610 mm) above grass, plants or other combustible surfaces.
PAGE 14
|
É
A
4 3 MIN. [76mm]
OPTIONAL DIRECTION <a
12 MIN. [304mm]
—
~~
COMBUSTION AIR INTAKE
L 2 MIN. (Simm]
pr
MOBILE HOME INSTALLATION |
| WIND / RAN CIP —ZN |,
3
ww
[610mm]
=
3 MIN. [78mm]
3 MIN. [76mm] A
SUPPORT BRACKET
EVERY 5 FEET
PELLET VENT
: WALL THIMBLE
CLEAN OUT COVER
— PELLET VENT LH HEART ES TIBLE
minados Ш ==: me
(e | ve | EL30W OR HOOD
FIGURE 4 FIGURE 5
HORIZONTAL CORNER INSTALLATION VERTICAL EXTERIOR FLUE SYSTEM
| == WIND / RAIN Cap ZM
К 24” Min. (610mm) FLASHING à —]
o! !
A, : : | | 24° М, [610mm]
SN) |
о N SRE io
UNS N EEN | № a
| N :
N O Padet Vent To Fi h ~ | 24° (610mm)
Y Min (78mm) N - Dian Acacror Fequres 3 MIN. [76mm]-— E REFER NOTE
5 № $ MIN. [76mm]r 1
N KO T
\ : в Реж Vere CHIMNEY CAP
NF ms
N | Common
NL iT un a A
N (152mm) EL30W OR HODD
— 305mm
\ unas = Exeno NON-COMBUSTIBLE MATERIAL
FIGURE 8 FIGURE 9
INSIDE VERTICAL INSTALLATION WITH
ROOF TERMINATION HORIZONTAL INSTALLATION
CAUTION: "The structural integrity of the mobile home floor, wall, ceiling and roof must be maintained.
In addition to the FREESTANDING RESIDENTIAL INSTALLATION requirements, the following requirements
are mandatory for installation into a mobile home:
1. The stove must be permanently bolted to the floor of the mobile home.
(Some states do not require this; check with your local building department.)
ed
2. The stove must have Permanent outside air (combustion air) intake.
3. The stove must be
(Some states do n
PAGE 15
grounded to the steel chassis of the mobile home.
ot require this; check with your local building department.)
RESIDENTIAL ALCOVE INSTALLATION
9" MIN. y "MIN. y
(229mm) (229mm) |
— —
[] Г
E
5
5
E
‘ = "
3
® :
\ —
“e J
(ÑÁ——— 42" MIN. (1067mm) |
MINIMUM ALCOVE HEIGHT 60" - (1524mm)
MAXIMUM ALCOVE DEPTH 48" - (1219mm)
PAGE 16
PREPARATION FOR INSTALLATION — PELLET INSERT |
READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW APPLIANCE. FAILURE TO
FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH.
PREPARATION:
1. Remove all tape and packaging.
2. Remove the wood shipping frame from around and under the appliance. В
3. Check that no parts have become loose and the appliance has not been damaged during shipping.
4. Remove the hardware pack from the appliance.
5. READ THE OWNER'S MANUAL BEFORE PROCEEDING.
* Appliance should be located so that no doors, drapes, furniture or other combustibles can be placed close or
swing closer than the minimum 36" clearances.
* The appliance must be installed in a level, secure position.
FLOOR PROTECTION: (Fig. 10)
NOTE: Minimum hearth extension 24" W (61 Omm) x 16" D (406mm) (From fireplace opening).
Chimney Lengths Maximum Minimum
Vertical 33' (10.06 т) Subject to installation.
Horizontal 10° (3.05 m) Subject to installation.
* Do not obtain combustion air from attic, garage, unventilated crawl space or any other enclosed space. Do not
locate combustion air inlet at an elevation higher than exhaust termination.
* Outside air (combustion air intake) is recommended, but not required, for residential installations, but outside air
is required for mobile home installations. If an outside air intake (combustion air) is used, it must be
connected to a 1-3/4", or larger, metal or aluminium duct with a rodent screen fixed to the termination.
Do not use P.V.C. duct.
NOTE: TRAVIS INDUSTRIES, INC., recommends that an outside air (combustion air) intake be used in all
installations. If one is not used, there is a possibility of combustion gases (smoke) being released into your home,
if there is a power outage while the unit is in operation.
* The LOPI 400 pellet insert exhaust vent accepts 3" diameter pellet vent pipe or 3* diameter singlewall
stainless steel liner. Some of the brands available for use with the LOPI 400 are:
1. Duravent Model PL-Vent 2. James A. Ryder MFG Model PL-Vent 3. MetalFab Model Pellet Vent
Simpson Dura-Vent Ryder Mfg., Inc. P.O. Box 1138
Р.О. Вох 1510 241 Arvin Avenue Wichita, KS 67201
Vacaville, CA 95688 Stoney Creek, Ontario Canada (316) 943-2351
(707) 446-1786 or (416) 662-1701
1-800-227-8846
NOTE: 4" diameter may be substituted when a 3" to 4" adapter is used.
See manufacturer's installation instructions for precautions required for passing vent through a combustible wall
or ceiling. Do not connect this appliance to a vent serving another appliance.
All sections of pellet vent must be fastened to each other with sheet metal screws and silicone sealed with type
500 degrees Fahrenheit (260% C) RTV (high heat) silicone sealer, to ensure that the joints are airtight.
PAGE 17
PREPARATION FOR INSTALLATION —
PELLET INSERT (cont.)
NOTE: The fireplace cavity must be thoroughly cleaned prior to installation. It should be cleaned with a wire brush or
scraper and then painted with a latex paint to eliminate the possibility of odors from the fireplace being circulated into
the house by the room air fan of the pellet insert.
For your safety, examine the fireplace and chimney prior to installation of the pellet insert to determine that they are
free from cracks, loose mortar, creosote deposits, blockages, or other signs of deterioration. If evidence of
deterioration is noted, the pellet insert should not be installed until after repairs have been made. Any opening
between the masonry of the fireplace and the facing masonry must be permanently sealed.
Your pellet insert is listed for installation into masonry fireplaces, and is approved to be installed with or without
positive or direct chimney connection.
Your pellet insert is also approved for installation into metal or zero-clearance (Z.C.) fireplaces. Metal or Z.C.
installation requires a full reline with a 3" stainless steel single-wall pipe or a fiexible liner.
Your LOPI 400 Pellet insert appliance comes completely assembled, with the exception of the Switch Box, top panel
and panel trim. Options available for the different types of installations are:
1. Adjustable Front Insert Support.
2. Ceramic Log
The above items come boxed separately and require assembly.
VENT CONFIGURATION:
The 400 Pellet Insert is equipped with a dual vent configuration. It can be vented vertically or horizontally. Before
installing, you must determine which configuration will best suit your installation.
The unit comes set up for a vertical installation (Fig. 12-A). To change it to a horizontal venting configuration, remove
the 1/4" hex head bolt and clamp holding the vertical vent to the base of the unit, next release the spring clip on the
side of the lower vent duct (Fig. 12-b), and remove the vent assembly then release the spring clip holding the round
portion of the vent to the rectangular portion (Fig. 12-C). To complete the change over, clip the round portion into the
lower vent duct bracket (Figs. D &E).
NOTE: Make sure that the gaskets are not damaged and are in the proper position before latching the spring clip.
Figure 12-A Figure 12-C
Figure 12-B
16 PLACE PAGE 18
INSERT INSTALLATION SPECIFICATIONS
LOCATION OF EXHAUST VENT AND OUTSIDE COMBUSTION AIR INTAKE, DIMENSIONS
REQUIRED FOR INSTALLATION INTO FIREPLACE AND PANEL SIZING. “=”
37 7/8" (962mm)
—
27° (688mm) Overall Width at front of unit.
. 21° 333mm)
LOPI 400 PANEL SIZING: И eb
и N
The LOPI 400 pellet stove
comes with only one size panel.
The outside dimensions of the
\ FROM SIDE OF `
” rm
panels are ENT BEMIND_ |
37 7/8" (962mm) x 29" (737mm). =} Ш
This panel is designed to инет о
cover a fireplace opening STVENTÁ—— - La” 1 ©
of 28" (711mm) x 37" (940mm) ACCEPTS 3 FLEXBLE зле" (теч FIGURE 22
STEEL EXHAUST VENT
A
10 1/2* (287mm)
A I
À BACK VIEW €
Ceriter 3 db
> |= Line Px;
; 3 of Ynit 3
= |® 3
У
У y 4 (mm) К © J 3 3/4" У
| o —Ú————” (Umm)
ACCESO MUSTVENT Pra DN N FIGURE 23
OR RIGID STAINLESS | 3 3/10" (Himen)
LOPI 400 FIREPLACE SIZING: STEEL EXHAUST VENT | ——
NOTE: DUE TO THE POSITION OF THE BLOWER — .
MOTOR, THE REQUIRED FIREPLACE OPENING MUST
EXCEED THE ACTUAL WIDTH OF THE UNIT, RRR DTD.
MEASURE AND CENTER THE UNIT INTO THE
FIREPLACE BASED ON THE > ER
PROVIDED MEASUREMENTS. E D и
A - MINIMUM HEIGHT (FRONT) 20" (505MM) A — CO B 2
B - MINIMUM HEIGHT (BACK) 20" (505MM) ® >
C - MINIMUM WIDTH (FRONT) 27" (686MM) у
D - MINIMUM WIDTH (BACK) 21° (534MM) % o
E - DEPTH INTO FIREPLACE 12 1/4" (311MM) / 1 O \
F - EXTENSION ONTO HEARTH 12 7/8" (327MM)
PAGE 19
INSERT INSTALLATION SPECIFICATIONS (Cont.
u .
FLOOR PROTECTION: (Fig.10 )
E. Front 0" (Omm)
F. Sides О" (Отит)
NOTE: Although a non-combustible hearth extension is pot required, to extend past the front and sides of
the insert, the insert must be installed on a non-combustible hearth that extends to the front and side
edges of the insert.
CLEARANCE TO COMBUSTIBLES: (Fig. 10)
A. Adjacent Sidewall 9" (229mm)
B. Side Facing | 8" (203mm)
C. Top Facing 12" (305mm)
D. Mantle 13" (330mm)
NOTE: For clearances, use this clearance diagram (fig. 10) or the clearance diagram on the
safety label attached to the back of the appliance.
u”
y
Figure 10
uu
PAGE 20
INSERT INSTALLATION SPECIFICATIONS - (cont.)
DIRECT CONNECTION: ,
1.
2.
Make sure the fireplace and chimney are thoroughly cleaned, inspected and repaired where necessary to
make it safe. Paint with a latex paint, as explained on Page 18.
Wire open or remove the firebox damper.
Measure the area of the firebox below the damper opening and above the lintel. Transfer these
measurements to a piece of galvanized sheet metal (min. 24 gauge) and add 2" to each side. Mark the
position of several holes on each side, to suit your specific installation, and drill 1/4” diameter holes. Next
bend the 2" extended side to a 45° angle. The 2" lip with the 1/4" diameter holes will allow you to screw
the plate to the firebox walls.
A hole must be cut in the plate to allow the chimney connector to pass through from the appliance into the
chimney. Mark the hole position on the plate so that the center of the hole is in line with the center line of the
appliance flue. A flexible stainless steel connector works best if an offset is required.
Position the plate in the firebox where the measurements were taken. Secure the plate with screws through
. the holes in the lip, and seal around the outside edges of the plate with fiberglass insulation, furnace cement,
or both.
Insert the chimney connector (flexible or rigid single-wall stainless steel, 3" diameter and at least 24" long) up
through the hole in the plate and damper opening into the chimney. Seal where vent passes through block-
off plate. This should be done on completion of connection.
NOTE: Masonry fireplace installations require a direct connection or positive (complete reline) connection to
the chimney flue. With a direct connection a block-off plate made of metal or other non-combustible material
(.e. Kaowool or high temperature fiberglass insulation) must be used at the damper location and sealed
airtight. The singlewall pipe or flexible liner must extend past the biock-off plate or insulation by one (1) foot
(305 mm) or to the first flue tile if the chimney has a tile lining.
With a positive connection, the block-off plate at the damper location is optional, but a sealed cover plate is
required at the top of the chimney. A positive connection (complete reline) is recommended for ease of :
cleaning. da
PANEL INSTALLATION:
10.
11.
12.
13.
14.
NOTE: The 400 PI comes assembled with the two side Bay panels already installed. You will need to
remove them prior to installation.
Lay a protective covering such as a towel or blanket on the floor to protect the floor and the panel finish.
Remove, from the box marked Panels, one top panel. Make sure that the panel is large enough to cover the
fireplace opening. NOTE: Route the power cord out of the fireplace so that it exits through the lower outside
front corner of the fireplace opening. DO NOT ROUTE THE POWER CORD UNDER THE UNIT.
Align the side Bay panels with the sides of the unit. The panels are notched and clip onto the side of the unit.
Unwrap the Switch Box, (shipped inside the firebox of the appliance), and clip it into the panel, the Power
Switch should be at the top and the Blower Control at the bottom. Then connect the multiplug from the switch
box to the corresponding receptical on the control box. This must be done prior to the installation of the top
panel.
Position the top panel over the unit. Align the clips and slide the top panel over the side panel flanges and
the top pf the unit. Press down firmly to make a secure fit.
Place the trim face down on the floor, as it would appear on the unit Place the corner brackets in the
appropriate slots, insert the set screws and tighten firmly.
Slide the completed trim assembly over the top panel. You may wish to use two-sided tape at the ends of the
trim to hold it firmly against the bottom of the side panels.
Push the assembled insert, panels and trim into the fireplace until the spacers make contact with the face of
the fireplace. Be careful not to scratch the hearth. NOTE: Maintain at least a 3/8" air gap around the outside ,
edge of the panels. This allows air to flow around the unit. If this gap is not maintained the unit could e
overheat.
Make sure that the insert is square in the fireplace opening.
PAGE 21
dE
3/8 GAP PROVIDED
BY PANEL STANDOFF
...e ed ed e BN nea
: a. 715 2 4 2. = а
...w. Gl тов =
я т т т | В un =
vas e.
1 a e.
an 4 +.
+ в Ша ет
+. Sl eo
sw Ble sw
+ ® 4 =n.
sve vw
+. #5 =a»
x un e = à
…. rr.
= a eva
LC соо
ay ее
=» rro
«= + a
+. e.
» я Ва ©
= в «Я er:
» + 43 a 4 =
wn Bhs a»
LE. a.
= = à
en dR ww
. e ero
* +.
«= UE = =
LACIE 4 a
= + ln =»
+» Sl ..
= = Ма в +
[Га = 4 v0
E =
+. Sl та
CA + =
a нь
EM = a
+. Jl w=.
= Mu ==
ar - ===
- .
+ alll ==
DC BEE
= fu + =
- aw
«ne a.
aw le.
Lu ==
on Ш «сн
- ME 2 2
oe as
E == e
vu di +".
». pee
а я
- ..
EC т
= - a
a alia sp
«a ma
a ole sn
- .
LA Вот он
… du # =
» а Ве с +
= = Я ча =
« « Вэ =
+ + nao
LALA + um
ar ero
я = Ва в +
ax dl =.
LCE e...
LACIE +2 =
= в чо
.„. x
MES TE EE TE ECC 4 + à + 1 5 + = + 4 = а Ве = <
DEE ICICI CCE SE IC EEE вот оф оба в оф т т № ево
|", a +
..aZa e. a du dt ESE fill san
+= 4 0 5 0 4 55 5 = а не 2 =
a. .…
"war: = т
a a a a CE NE NE MN OO WN BLE EN)
ss olla am
an dll aw
+ = Ме со
LIE =.
as alle vu
ws a.
on a Ben
PENN + a Wl a wv
+s as as sve ta suns panasagasaaayp e rr a
ERIE. ad.
Fa... e +
ET 0 MAA A
+ a e =
DE dll wo
“on als a»
asa Sl s+ =
+ + В в ©
=. en.
a wile a a
+. Sl ve
++ Be + =
+ = rn.
»_. = +
an iF = a
u u
LLE EE
+ a «e. ..
ano ne:
CA CO
are nn Sl aaa
ua mow AAA AAA haa
E» a Al
NOTICE TO INSTALLER
Q 2 A 06 ot A
bi UC 00 30 MX OC 50 мб
A а д а E a д в д а д
A.
By design there are standoffs on the back of the panels. These standoffs
maintain a 3/8" gap between the face of the fireplace and the back of the
panels to allow for air movement through the back of the appliance. If an
optional panel flashing is used, the panel flashing is to be seated against the
fireplace front and the 3/8" gap maintained between the front of the flashing
and the back of the panels.
INSERT INSTALLATION INTO EXISTING
MASONRY FIREPLACE
TT OUTSIDE COMBUSTION
WIND / RAIN CAP AIR INTAKE
6" MIN. (152mm) 1
4" MIN. (102mm)
SN Na
TY
| LL SEE NOTE
«@r- 3" STAINLESS STEEL A BELOW
SINGLE =
WALL PIPE OR a
FLEXIBLE -
LINER IS REQUIRED; 4
REFER X
NOTE BELOW.
12"
i DIRECT
die mn CONNECTION
3 TERMINATION
= AT SINGLE WALL TEE
1 AL CAN BE USED AS AN
€ OPTION
: | PP
> A AIR INTAKE OPTIONS
0" MIN, A
(omm) .. ,
FROM Es M ih == A OPTIONAL
FRONT pon {| OUTSIDE
OF INSERT es | | [--- AIR INTAKE
CT 1.0 1 1 COL
NON-COMBUSTIBLE ~~
MATERIAL
NOTE: Masonry fireplace installations require a direct connection or positive (complete reline) connection to the chimney flue.
With a direct connection a block-off plate made of metal or other non-combustible material (i.e. Kaowool or high
temperature fiberglass insulation) must be used atthe damper location and sealed airtight. The singlewall pipe or flexible
liner must extend past the block-off plate or insulation by one (1) foot (305 mm) or to the first flue tile if the chimney has
a tile lining.
With a positive connection, the block-off plate at the damper location is optional, but a sealed cover plate is
required at the top of the chimney. A positive connection (complete reline) is recommended for ease of cleaning.
PAGE 22
INSERT INSTALLATION INTO EXISTING
MASONRY FIREPLACE (cont.)
SEE NOTE
BELOW
3" STAINLESS STEEL
SINGLE
WALL PIPE OR A
FLEXIBLE 12"
LINER IS REQUIRED; DIRECT -
CONNECTION
TERMINATION
v.
SINGLE WALL TEE
CAN BE USED AS AN
OPTION
0" MIN.
(Omm)
FROM N % AIR INTAKE OPTIONS
FRONT N
OUT UNIT :
OPTIONAL OUTSIDE
COMBUSTION AIR INTAKE
Li
| — IT T 1-1 1 1 A
| в
NON-COMBUSTIBLE
MATERIAL
NOTE: Masonry fireplace installations require a direct connection or positive (complete reline) connection to the chimney flue.
With a direct connection a block-off plate made of metal or other non-combustible material (i.e. Kaowool or high
temperature fiberglass insulation) must be used atthe damper location and sealed airtight. The singlewall pipe or flexible
liner must extend past the block-off plate or insulation by one (1) foot (305 mm) or to the first flue tile if the chimney has |,
a tile lining. |
Ji
— UU
With a positive connection, the block-off plate at the damper location is optional, but a sealed cover plate is required at
the top of the chimney. A positive connection (complete reline) is recommended for ease of cleaning.
PAGE 23
INSERT INSTALLATION INTO METAL (Z.C.) FIREPLACE
SEE NOTE
— BELOW
NN
3" STAINLESS STEEL
SINGLE
WALL PIPE OR
FLEXIBLE
LINER IS REQUIRED; Г 7
REFER |
NOTE BELOW. /
and]
- ey
'
nN SS FFF JJ FAW A A SA AA AE SEA A
—
o o ,_—
я:
SINGLE WALL
TEE CAN BE
USED AS AN
OPTION
Ea AN E atan
a's a’
pas
pr
ALA
LED
LE
LT Ze
a.
: a
E и и Ze
A CES PAC ne ww my www
\
~
Fate” a oll
-
“oo yo
+
wis
rll
ъ
*
*
= x
A
я
и ня
e
On ee fe
SR AAA 5
PLATO AAA e 3
У réa Fe rentes A et
i" vs e Ke y de DN CRC PA 2
0" MIN a EAN ee
. met: AA СООО Ср,
(Omm)
NON-COMBUSTIBLE
MATERIAL
NOTE: À 3" stainless steel single wall pipe or a fiexible liner is required to extend to the top of the existing chimney
for metal (Z.C.) fireplaces.
PAGE 24
LOCATION AND USE OF CONTROLS
Tums power ON and OFF
| to system components.
Indicates unit is in
operation.
> Initiates Start-up cycle.
EE)
y ENT PRY
AL MA
2 ; ES” peliet feed rate.
Controls convection air fan
speed.
AAA
dur
Turns power ON and OFF nn
to system components.
Indicates unit is in _—
operation.
Initiates Start-up cycle. —
pellet feed rate.
A0 ‘' Low
; , BLOWER
Controls convection air fan
speed.
AIR
CONTROL
KNOB
e
PAGE 25
=
OPERATING YOUR PELLET APPLIANCE
STEP 1. RECOMMENDED FUEL TYPES & SIZES:
The unit is designed to operate using 1/4" pellets that comply with A.P.F.I. * standards. If the fuel does not
comply to this standard, the unit may not operate as designed. If the pellets are larger than 1/4" diameter, the
unit may need adjustments. Consult with your dealer. NOTE: Store pellets in a clean, dry place.
* A P.F.l. = Association of Pellet Fuel Industries.
STEP 2. PRIMING THE AUGER:
Priming the auger is only required when the unit is new or when the hopper has compietely run out of pellets.
A. Load the hopper with pellets.
В. Set the burn rate control knob to "HIGH RANGE".
C. Switch the power switch to "ON".
D. Press the start switch and release when indicating light comes on.
This will start the auger and begin the priming process. Once pellets are feeding into the firepot, turn the power
switch "OFF." You are now ready to start a fire.
STEP 3. STARTING YOUR APPLIANCE:
A. Open the door and place a wax-impregnated wood fire starter or add gelled firestarter on a few
pellets in the center of the firepot and light. When the fire starter is buming, close the door.
B. Push the black "AIR CONTROL KNOB" to the closed position. (Located on the lower left side of
the unit). Press the power switch "ON." Adjust the bum rate control to the "EXTENDED BURN"
position and press the start switch. (The amber indicator light will come on.) Pellets will begin to
feed into the firepot.
C. Once the pellets are burning and you have established a fire, set the burn rate at the "HIGH
RANGE" position. Then pull the black "AIR CONTROL KNOB" out to the open position.
D. Before turning the unit to a lower bum setting, it is necessary to run the unit on "HIGH RANGE"
for at least 15-20 minutes after a fire has been established. This allows the unit to reach proper operating
temperature. Failure to do this could result in an inadequate operating temperature and the unit will tum
itself off. If this happens, you will have to repeat the entire start-up procedure.
E. The convection blower will be OFF for approximately 15 minutes after start-up of the appliance.
This is to allow the appliance to reach operating temperature before the convection fan comes on.
The fan will also continue to run after the stove has been shut off until the unit has cooled down.
NOTE: The unit will emit an odor for the first few hours of operation while the paint and oils on the metal
cure.
STEP 4. RUNNING YOUR APPLIANCE:
A. Bum ráte control and air control settings for normal operation when the bum rate setting is set on:
"HIGH RANGE", Air Control knob is pulied completely out for fully "Open" position.
"MEDIUM RANGE", Air Control knob is between fully "Closed" and "Open."
"EXTENDED BURN", Air Control knob is pushed completely in for fully "Closed" position.
NOTE: The Air Control knob settings for your unit could vary due to type and quality of fuel used.
Therefore, it is suggested that you establish the settings that best suit your particular fuel needs.
This is done by adjusting the air control knob "OPEN" or "CLOSED" to allow more or less
combustion air to increase or decrease the rate of burn.
PAGE 26
OPERATING YOUR PELLET APPLIANCE (cont.)
STEP 5. TURNING THE UNIT OFF:
A. Tum the power switch to the "OFF" position. The unit will automatically turn the convection and
combustion fans off when the temperatures have reached the shut down range.
AUTOMATIC SAFETY FEATURES:
1. POWER OUTAGES
During a power outage the unit will shut itself down safely. It will not restart unless there is a
sufficient firepot temperature to sustain combustion.
2. OVERHEATING
This unit is equipped with an overheat sensor. If the unit becomes overheated, it will shut itself
down safely. The appliance will not restart until it has cooled to a safe level. It may be necessary
to restart the unit if this occurs. [f this happens frequently, turn the unit off and consult with your
dealer to determine the problem.
3. BLOCKED FLUE OR DOWN DRAFT PROTECTION
This unit is equipped with a draft flow switch. If a draft restriction or back draft occurs, the unit
Will automatically shut itself off. if the restriction or back draft is momentary, it will automatically
resume operation. If not, you will need to locate the restriction and correct it before restarting
your unit.
PAGE 27
*
®
a 4
NORMAL OPERATING SOUNDS
Heat Exchange Thermostatic
Tubes Control
; : This part can
You will hear air icki
being forced through produce d clicking
the heat exchange automatically turns
convection fan the convection fan
« N W or в "
w
Convection Fan
The modern high Firepot Auger Motor Mu aust Fan
ear an ey When the auger || The fo of us:
pulsating sound As pellet are fed to feeds pellets you air-cooled induction
iculariv on the high the firepot, a light may hear the tor creat
a O e TOA || clicking sound may || intermittent buzz of motor creates a
+ be heard. this motor runnin steady low-pitched
may change as the 9. hum.
speed is varied.
y
PAGE 28
CARE AND MAINTENANCE
Weekly Maintenance: (Details on Page 30)
There are several areas and parts of the unit that must be inspected and cleaned at least once a week during
operation. However, depending on fuel quality and burning habits, this maintenance may have to be performed
more frequently. These are:
A. Heat exchanger tubes.
Ceramic log set. (Optional.)
B
C. Brick refractory.
D Firepot and holder.
E
Ashpan.
1000 Pounds (1/2 ton) of Fuel Used Maintenance: (Details on Page 31)
There are several areas and parts of the unit that should be inspected and cleaned after every 1000 pounds (1/2 ton)
of fuel used. These are:
A. Repeat Weekly maintenance schedule.
В. Flyash trap behind the exhaust ducts.
C. Hopper and auger tube area.
6000 Pounds (3 tons) of Fuel Used Maintenance: (Details on Page 32)
The following areas should be inspected, cleaned and serviced after every 6000 pounds (3 tons) of fuel used.
A. Repeat Weekly maintenance schedule.
B Flyash trap behind the exhaust ducts.
C. Hopper and auger tube area.
D
Exhaust fan, including exhaust duct system.
E. Convection fan.
F. Auger motor.
G. Chimney system.
H. Door gaskets.
I. Ashpan gaskets.
PAGE 29
Maintenance Schedule - Weekly
Prior to carrying out routine maintenance, ensure the appliance is unplugged and has cooled down sufficiently to
handle the parts with safety.
и | ToosRequred |
Built - in Scraper
(See Figure 13)
Keep the door closed while cleaning to contain ash in
appliance. After cleaning the tubes with the built - in
scraper, open the door and brush all the fiyash into the
ashpan.
Ceramic Log
Set
Stiff Brush (supplied)
Using a stiff brush, brush the flyash off of the log set
into the ash pan. Remove the log set from the firebox.
(See Figure 14.)
Brick
Refractory
Stiff Brush (supplied)
Using a stiff brush, brush the flyash off of the brick
refractory into the ashpan.
Firepot
Stiff Brush
To inspect and clean firepot, remove the entire assembly
as shown in figure 15. Using a stiff brush, clean all the
deposits from the firepot grate. Make sure the holes are
not blocked. When this is completed, clean the firepot of
all flyash.
NOTE: Regularity of firepot cleaning is subject to the
quality of fuel being used.
Ashpan
Remove the Ashpan (located under the ashlip) and
dispose of the flyash in a safe manner. (See Figure
18.)
PAGE 30
Maintenance Schedule - 1000 Ibs (1/2 ton) of Fuel Used
Prior to carrying out routine maintenance, ensure the appliance is unplugged and has cooled down sufficiently to
handle the parts with safety.
PREPARATION FOR 1000 LB (1/2 TON) MAINTENANCE:
1. Remove all the pellets from your unit. (It will be easer if you let the unit run out.)
2. Repeat the weekly maintenance schedule.
If the glass should break, wait until the stove and glass is cool before removing. Do not leave
the fire unattended during this cool down period as sparks could escape through the broken
glass. Do not operate appliance with broken glass.
To replace the glass, simply remove the door and unscrew the glass clips. Replace the broken
glass with only LOPI glass, available at all authorized LOPI Dealers. The replacement glass is
high temperature, high shock glass of Technical Neoceram (R) 5 mm thick. Under normal
operating conditions the glass will not break.
Metal Scraper Clean the visible flyash from the bottom of the firebox.
A. Trap Stiff Brush Clean the flyash trap area using a metal scraper, brush
Exhaust Duct | Heavy duty Vacuum or heavy-duty vacuum. (See Figures 16 and 17.)
Refer Figure 16:
To remove vertical combustion air ducts, start with either the left or right side, lift the side
duct up 1/4%, pull it towards the front of the stove, move the bottom towards the opposite
side, and pull it through the door opening.
To remove the horizontal combustion air duct, pull it towards the face of the unit and lift it up
and out.
Hopper 4 Heavy-duty Vacuum Vacuum the inside of the hopper area.
Auger
Areas
Glass Non-abrasive Glass Should soot or creosote deposits occur on the glass during
Maintenance Cleaner operation, clean when the stove is cold with a non-abrasive
glass cleaner.
NOTE: Inspect the gaskets on the door, glass and ashpan. If they show signs of deterioration,
replace them. See your dealer for the proper type and size of gaskets.
PAGE 31
UU
Maintenance Schedule - 6000 Ibs (3 tons) of Fuel Used
Make sure the appliance has cooled down sufficiently to handle the parts with safety.
NOTE: We recommend that this service be done by an authorized pellet stove technician.
PREPARATION FOR 6000 LB MAINTENANCE:
1. Unplug the unit and disconnect the exhaust and inlet connections at the rear of the appliance.
2. Remove all of the pellets from the hopper. (It will be easier if you let your unit run out.) Using
a heavy-duty vacuum, clean the hopper and auger tube opening of all sawdust and fines.
3. Repeat the weekly maintenance schedule.
4. Repeat the 1000 lbs maintenance schedule.
If you hav
Brick -
Refractory Remove the brick refractory. (See Figure 17.)
Remove 5/16" Wrench or Remove the sheet metal screws at the back of the unit
Side Panels Nut Driver with a 5/16" wrench or nut driver. (See Figure 19.)
(Pellet
Stoves) (For Pellet Inserts see panel installation section on page 21)
, Disconnect the exhaust fan electrical leads. Using the 5/16"
Remove 5/16 & 9/16" Nut Driver nut driver, remove the three fan mounting boits and the 1/4"
Exhaust Fan | Vacuum Cleaner hex head bolt holding the exhaust vent. Remove the fan,
Brush complete with the exhaust tube and insulator, from the
appliance. (See figure 20.) When the fan has been
removed, inspect the impeller blades, gasket, flow nipple
and housing. Clean all the fiyash from these areas using a
brush and vacuum cleaner. Prior to replacing the fan
assembly, check that the silicone seal at the fan and
exhaust tubes. If fractured, use Type RTV 500 degree F
silicone sealant to reseal the joint. Lubricate the exhaust
and convection fans with a few drops only of light machine
oil. (See figures 20 & 21.)
Combustion | Vacuum Cleaner Clean the combustion air duct
Air Duct -
Chimney Check the chimney system for soot and creosote build-up, and have it cleaned by a
System certified chimney sweep, if necessary.
Replace the “
Exhaust Fan 5/16 & 9/16" Nut Driver Reverse removal procedure.
Replace Side
Panels 1/4" Wrench Reverse removal procedure.
(PelletStove)
PAGE 32
Figure 15 & 16
Figure 17
PAGE 33
E
!
!
$
E A A A DE ADA
Cr 6 o
Le e
as
VET
Figure 13
PAGE 34
oe
274 E
и
и
ea
Figure 19
ee
ия
ae
eRe
, ab E
Figure 21
PAGE 35
BEFORE CALLING FOR SERVICE
SAVE TIME AND MONEY - CHECK THIS LIST BEFORE YOU CALL FOR SERVICE.
To eliminate unnecessary service calls, first read all the instructions in this manual carefully. The following checklist
provides possible solutions to common occurrences that are not the result of defective workmanship or materials in
this appliance. Always make sure unit is plugged in and that the circuit breaker has not tripped.
If you do have a problem that you cannot fix yourself, cali the dealer where you purchased your appliance. When
calling, have this manual handy with the model, serial number and purchase date of your appliance.
Problem Possible Cause Don't Call for Service
Until You Check
Firepot overfills on start-up. Starting appliance on Burn rate control is on low burn and air
"HIGH BURN" range. control is closed.
ent Up fire extinguishes Combustion air inlet blocked. Inlet tube is not blocked outside house.
itself.
Door ajar. “ | Dooris latched securely.
Ashpan open. Ashpan is latched and sealed.
Firepot not in correct position. Firepot is in correct position.
Lack of ignition. Ensure firestarter is ignited.
y
Lazy orange flame, Restriction in combustion intake tube. Combustion tube intake is not blocked.
smoking exhaust or firepot
overfills with pellets. Air leak in firebox. Door and ashpan are latched.
Firepot plugged. Firepot needs cleaning.
PAGE 36
BEFORE CALLING FOR SERVICE
db
Problem Possible Cause Don't Call for Service
Until You Check
Lazy orange flame, Incorrect air control setting. Air control is set to suit burn rates.
smoking exhaust or firepot (Open control until fire brightens up).
overfills with pellets. (cont.)
Combustion air duct restricted. Flyash buildup behind combustion air
| ducts.
Fuel.
Poor quality or wet fuel.
Power outage. Restart unit.
Restricted exhaust. Clean vent pipe.
Fire smolders. Firepot overfilled. Refer to previous check items.
Pellets are wet. Pellets in hopper are dry and all 4
stored pellets are dry. =”
Pellets not feeding. Auger not primed. Prime auger.
Hopper empty. Fill hopper.
Power switch not pressed. Power switch is pressed and amber
indicating light is on.
Start switch not pressed. Start switch is “on”.
- Appliance not plugged into power Appliance is plugged into outlet.
) outlet or no power available at Circuit breaker or fuse has not
outlet. tripped.
4
PAGE 37
| BEFORE CALLING FOR SERVICE
Problem
Possible Cause
Don't Call for Service
Until You Check
Smoke smell in house
and unit has gone off.
Intermittent power failure has shut
unit off.
Automatic safety feature has shut
unit off.
Unit was unplugged while under full
operation.
Power is on.
Wait 1/2 hour and relight. If unit
won't light, consult your dealer.
Refer to "Operating Your Pellet
Stove", page 27, "Automatic Safety
Features".
Unit has shut off and
hopper is full of pellets.
Automatic safety feature has shut
unit off.
Refer to "Operating Your Pellet
Stove", page 27, "Automatic Safety
Features”.
Fire goes out on low
bum
Air control setting is too high, blowing
flame out.
Pellets dropping into burn pot will
cause the flame to be knocked down
but will come back; this is normal.
Fire pot may not be in proper
position.
PAGE 38
Check air control.
Make adjustment to match
feed amount; low feed, low air
high feed, high air.
To adjust it properly, look in
the bum pot; there should be
a slight movement of pellets.
REPLACEMENT PARTS LIST
All parts listed may be ordered from your LOPI 400 dealer. When ordering
following information:
PN —
PART NUMBER
0191
0291
0391
0491
— 0591
0691
0791
0891
0991
1091
1191
1291
1391
1491
1591
1691
1791
Part Number
Part Description
Serial Number
Date of Purchase
PARTS DESCRIPTION
Auger Motor
Auger Assembly
Exhaust Fan
Convection Fan
Control Panel with Switches
Power Control Box
Draft Flow Switch
170° Degrees F N.C. Snap Disc
120° Degrees F N.O. Snap Disc
Power Cord
Draft Flow Switch Tube
Firepot
Ashpan & Door Gasket Set
Door Glass
Ceramic Log
Brick Refractory
200° Degrees F. N. C., Snap Disc
PAGE 39
replacement parts, always give the
A
w
LIMITED WARRANTY
TRAVIS INDUSTRIES, INC. warrants the LOP! 400-PS or Pl pellet appliance to be defect-free in material and workmanship for five (5) years
from the date of purchase, with the exception of the electrical components, fans, gaskets, refractory, auger assembly, firepot and moving parts.
This does not include service call cost or any other additional charges. Check with your dealer for all costs if arranging a warranty call. The
exceptions listed are warranted for one (1) year from the date of purchase to be defect-fres in material and workmanship.
Exclusions to this limited warranty include: Injury malfunction to the product, loss, damage, defect, failure to function due to accident, negligence,
misuse, improper installation, alteration or adjustment of the manufacturers settings of components, lack of proper and regular maintenance,
damage incurred while the unit is in transit, alteration, or act of God.
This limited warranty excludes damage caused by normal wear and tear, such as paint discoloration or chipping, worn or torn gasketing, eroded or
cracked refractory, etc. Also excluded is damage to the unit caused by abuse, improper installation, the use of fuel or fuel loads other than
specified by the manufacturer or use not set forth in the Owner's Manual. An overfired condition will cause warped metal parts and discolored or
burned-off paint.
TRAVIS INDUSTRIES, INC. is free of liability for any damages caused by the unit, as well as inconvenience expenses, material and labor charges
incurred by the removal or reinstallation of any LOPI 400-PS or Pl unit. Incidental or consequential damages are not covered by this
warranty. In some states, the exclusion of incidental or consequential damage may not apply.
This warranty does not cover any loss or damage incurred by the use or removal of any component or apparatus to or from the LOPI 400-PS
or Pl unit without the express written permission of TRAVIS INDUSTRIES, INC. and bearing a TRAVIS INDUSTRIES, INC. label of approval.
Any statement or representation of LOP| 400-PS or PI products and their performance contained in LOPi 400-PS or PI advertising,
packaging literature, or printed material is not part of this Emited warranty.
This warranty is automatically voided if the unit's serial number has been removed or altered in any way.
Only the original purchaser of an LOPI 400-PS or PI appliance is covered by this warranty. If the unit is used for commercial purposes, it is
excluded from this warranty.
No dealer, distributor, or similar person has the authority to represent or warrant LOPI 400-PS or Pl products beyond the terms contained
within this warranty. TRAVIS INDUSTRIES, INC. assumes no liability for such warranties or representations.
THIS LIMITED WARRANTY IS THE ONLY WARRANTY SUPPLIED BY TRAVIS INDUSTRIES, INC., THE MANUFACTURER OF THE UNITS.
ALL OTHER WARRANTIES, WHETHER EXPRESS OR IMPLIED, ARE HEREBY EXPRESSLY DISCLAIMED AND PURCHASER'S RECOURSE
IS EXPRESSLY LIMITED TO THE WARRANTIES SET FORTH HEREIN.
This warranty is limited to the time frame set forth above. In some states, ime limitations on warranties do not apply.
HOW TO USE YOUR LOPI 400-PS or Pl! FIVE-YEAR WARRANTY: If you find your unit to be defective in workmanship or material within a
5-year period from the date of purchase contact your local authorized LOPI 400-PS or Pl dealer. If your dealer is unable to repair your units
defect, he may process a warranty claim through TRAVIS INDUSTRIES, INC., including the name of the dealership where you purchased the unit,
a copy of your receipt showing the dete of the unit's purchase, and the serial number on your unit. At that time, you will be asked to ship your unit,
freight charges prepaid, to TRAVIS INDUSTRIES, INC. TRAVIS INDUSTRIES, INC., at #5 option, will repair or replace, free of charge, your LOPI
400-PS or Pl unit if it is found to be defective in material or workmanship within the time frame stated within this limited warranty. TRAVIS
INDUSTRIES, INC. will ship your unit, freight charges prepaid by TRAVIS INDUSTRIES, INC., to your regional distributor, or dealership.
To register your TRAVIS INDUSTRIES, INC. Five-Year Warranty, complete the enclosed warranty card and mail it within ten (10) days of the unit
purchase date to: TRAVIS INDUSTRIES, INC., 10850 117th Place N.E., Kirkland, Washington 98033.
OTHER RIGHTS:
This warranty provides you with certain legal rights. You may have additional rights, which vary from state to state, in regards to this warranty.
UNIT SSRIAL NUMBER
DATE OF PURCHASE Complete and
DEALER NAME AND ADDRESS : save for your
records
Travis Industries, Inc. reserves the right to change, without notice, product features or specifications described.
Г Is Industries, In
AN Travis stries, INC.
m 10850 117TH PLACE N.E. KIRKLAND, WA 98033
PAGE 40
PRODUCT LISTING INFORMATION
WARNING —DO NOT REMOVE OR COVER THIS LABEL
Listed Pelletizod Solid Fuel Burning Applianco
For use In masonryitactory built (ZC) fireplaces
Combustible floor beyond hearth extension py IT]
] 5 St bo protected b
«+ non-combustible material, oxtending 0 in/0 mm ASE tho fro
and Gini0 mm (F) to sidas of door opening. ww
omponents Required far Masonry Fireplac ion: Di
ria ds Y place Installation: Direct
Components Required for Factory Buill Fire 1
| place Installa м
Listad 3in/75 mmor 4 in/100 mm diameter flue liner. on
SIDE MAIL
WM
N NN
NON
FACIA OR TRI
`
For use with 1/4 in/6 mm to 5/16 in/7 mm diam A
wood fuels only. lamatar polletized
В Replace glass oniy with 5 mm ceramic glass.
TO Do not route power cord beneath heater. The space boncath the
Model: 400.P1 Electrical Rating: 115.60 Hz 3 Ame hoater must not be obstructed. Do not obstruct combustion air
Report No: 6254 (JULY 1991) Tested to: UL 1482/ASTIIULC S62 atau ELUATE
: ; 8 Е | y LI g door and ash removal tra
Maximum Input Rating: 5.0 1bs/hr-2.27 kgihr E e A tightly closed. Keep all furnishings well away from heater. y
stall and use only In accordance with the installation and
operating Instructions. Contact tocal building or lire officials Adj j !
als acent Sidewall i
ebout restrictions and installation inspection in your arca. Do PRT | NEE mun Lc,
not remove bricks or mortar from masonry flreplace or alter Top Facing inf305 mm ICES0 117th PL WE OLA
factory built tireptace. Side Facing 1n/205 mM
—————O——]ln028=222=——————2= 2 ————r——c—————— aaa,
Manutactured by Travis +
WARNING —DO NOT REMOVE OR COVER THIS LABEL
Warnock Hersey Listed Pelietized |
Solid Fuel Burning Appliance Serial No:
он Also tor Use in Mobile Homes
Г © Model: 400-PS 1.C.B.0. No. NER-QA 219
Report No: 5820 (MAY 1991) Tested to: UL1482/ULC S627/C5A B366.2/ASTM E-91 Dratt
Maximum Input Rating: 5.0 Ibs/hr.2.27 kgthr Electrica! Rating: 115 V, 60 Hz, 3 Amp
This pellet lired appliance has been tested and listed for use in manutactured homes in accordance with
Oregon Administrative Rufes 814-23-900 through 814-23-909.
Install and use only in accordance with the installation and operating instructions. Contact local building
or fire officlals about restrictions and Installation inspection in your area. Use only listed 3 in./75 mm or
4 In./100 mm diameter listed type “L” Vent complete with components. See manutacturer's installation
instructions for precautions required for passing a vent through a combustible wall or ceiling. Do not
connect this appliance to a vent serving another appliance.
Minimum Clearance to Combustible Materials (Measured to Stove 10D) e————————
li ADJACENT WALL í
interior Vertical Horizontal Through a : “wr
Fue Installation the Wall installation
CCIE 9 in/225 mm in‘225 mm
Right Sidewali 3 yns225 mm in/225 mm
Hathwall 11 tn°289 mm in“ 75 mm
Co:ner 2 1п/ $0 тт ins Simm
Flue Vent Ole in/ 75mm FLOOR PROTECTOR
Maximum alcove depth 48 in/1220 mm, min ceiling height 60 in/1525 mm.
Combustible floor must be protected by a non-combustible material, extending lo the frant (G)
6 Inf150 mm and to the sides {H} 0 in/C mm.
о
RIGHT SIDEMALL
—
nal
чт
=
ad
és
uw
Bal
prt
ADIACENT WAIL
La
For use with 1/4 in/6 mm to 5/16 in/7 mm diameter pelletized wood fuels only.
Replace glass only with 5mm ceramic glass.
Do not route power cord beneath heater. The space beneath the heater must not be obstructed. Qutside
combustion alr is mandatory tor mobile home installation. Do not obstruct combustion air openings.
Operate only with viewing door and ash removal tray tightly closed. Keep all furnishings well away from
heater.
Mtg. by TRAVIS INDUSTRIES. INC.
10850 117th PINE.
Kirkland. WA 98033
PAGE 41

advertisement

Related manuals

advertisement