Schlage CT500 Universal Access Controller Access Control System Installation & Programming Manual
Below you will find brief information for Access Control System CT500 Universal Access Controller. The CT500 Universal access controller can be interfaced to any Schlage access control devices such as iButton readers or Keypads. The CT500 can also be used with mag-stripe emulation output HID Prox Card readers as well as magnetic stripe card readers. The unit may have been ordered with the PS option (505 power supply in the same enclosure). If it does not have a supply, one will be required. Make sure that the supply chosen will meet the electrical requirements of all components in the system. Note that electrical power gets dissipated over long wire runs so it is important that the equipment be located close to the opening it is controlling.
Advertisement
Advertisement
Offline Hardwired Access
Control Systems
CT500
UNIVERSAL ACCESS CONTROLLER
77080-G 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Table of Contents / Contact Information
CT500 INSTALLATION & PROGRAMMING MANUAL
Table of Contents / Contact Information
PLEASE READ ALL INSTRUCTIONS PRIOR TO INSTALLING THE SYSTEM.
HANDLE ALL EQUIPMENT CAREFULLY.
IMPORTANT: This manual is intended to be kept for programming, maintenance, and trouble shooting purposes. Do not dispose of after installation. Please present this manual to facility manager upon completion of installation.
Table of Contents:
Contact Information: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Compatible Readers: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Specifications: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Getting Started: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Typical System Installation: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Overview on Installation: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Set Dipswitches: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wire Colors: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Programming: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Definition of Access Functions and Factory Defaults: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Creating a Master iButton/Card: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Keypad/100CAB Initialization: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Programmer Initialization TEP1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
System 7 Programming: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Erasing Memory: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Setting Time Delays: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Configuring the System: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Manual Programming - Keypad - Codes Only: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Manual Programming - Codes, Cards and iButtons: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3-Digit Function Codes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Sample Wiring Diagrams: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Error Codes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Troubleshooting: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
NOTES: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Contact Information:
Schlage Lock Company
575 Birch Street
Forestville, CT 06010 technical support: 866-322-1237 fax: 860-584-2136 http://www.irsupport.net
77080-G Page 2 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Compatible Readers
Compatible Readers
Compatible Readers:
77080-G Page 3 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Specifications / Getting Started
Specifications / Getting Started
Specifications:
Electrical:
Input Voltage: 12 to 24 VAC/VDC
Current Draw: 200mA max.
DC Output Voltage (with AC input):1 amp max. (Matches input voltage)
Control Relays:
Main -DPDT contacts, 5 amp max @ 30VDC
Aux -SPDT contacts, 5 amp max @ 30VDC
Alarm -SPDT contacts, 5 amp max @ 30VDC
Programmable Users:
500 User Codes/iButtons, mag-stripe or prox cards.
4 Internal “Timers”:
All Adjustable 0-255 Seconds.
Getting Started:
The CT500 universal access controller can be interfaced to any Schlage access control devices such as iButton readers or Keypads. The CT500 can also be used with mag-stripe emulation output HID Prox Card readers as well as magnetic stripe card readers. The unit may have been ordered with the PS option (505 power supply in the same enclosure). If it does not have a supply, one will be required.
Make sure that the supply chosen will meet the electrical requirements of all components in the system. Note that electrical power gets dissipated over long wire runs so it is important that the equipment be located close to the opening it is controlling.
Consult national electric code handbook for information regarding wire run lengths and minimum required wire gauge and type for the voltage and current in the system.
77080-G Page 4 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Typical System Installation
Typical System Installation
Typical System Installation:
A typical installation consists of a a locking device (magnetic lock (a), electric strike, etc.), a power supply (b), a controller (c), an adapter cable (d) (in some cases), an access control (keypad (e), card reader, etc.), an exit control (exit device
(f), pushbutton, etc.), and door cord (g) or electric hinge. Any installation involving modification or specification of an opening which is considered to be a means of egress (emergency exit) or a fire rated opening must conform to all local and national life safety and building codes. The specific gage and number of wires will vary with the kind of equipment used, the intended function, and local and national building codes. In most cases it is required that magnetic locks open in the event of a fire alarm condition. (Consult local authority having jurisdiction.)
110VAC Supply
Fire Panel Input
b c a d f g e
77080-G Page 5 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Overview on Installation / Set Dipswitches
Overview on Installation / Set Dipswitches
Overview on Installation:
1) 1. INSTALL COMPONENTS
A. Determine where each component will be located. Mount Controller and
Power Supply to Wall. Run conduit as required by local and national codes.
B. Follow instructions included with Access Control device to mount it and run
wires to controller.
C. Mount Lock.
2) 2. MAKE WIRING CONNECTIONS
A. Set Dipswitches correctly for your system.
B. Make wiring connections as required.
C. Connect Power.
3) 3. CONFIGURE AND PROGRAM SYSTEM
A. Initialize Master iButton/Card and programmer as required.
B. Configure and Program System.
C. Test System.
1) Set Dipswitches:
The Universal Access Control Board can accommodate virtually all types of Schlage access control. Set the dipswitches (SW1) according to your system requirements for “Normal Operation”. Consult the table below for the desired setting. Note that different positions are required depending on the function desired.
Keypad only access control is also available. Note: if the board is replacing an older board, CT500 Universal controller can be used with almost any type of keypad or iButton reader offered by Schlage in the past; simply connect all wires which were previously connected as shown in the board layout in this document.
77080-G Page 6 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Wiring
Wiring
2) Wiring:
Note that the main relay is a double pole, double throw relay. TB4 will put out DC unregulated voltage up to one Amp. Note that it is not necessary to use this terminal if your system already uses DC voltage from a power supply.
For wire colors, see next page.
For dipswitch settings, see previous page.
Door Prop: Triggers Alarm Relay when door is held open for 30sec. (Requires door position switch.)
Anti-Tailgate: Allows relocking of door immediately upon reclosing. (Requires door position switch.)
Forced Door: Triggers Alarm Relay when door is forced open without a legal release. (Requires door
position switch.)
Day/Night Timer: Input from an external timer allows codes to work only during certain times of day.
77080-G Page 7 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Wire Colors
Wire Colors
•
Wire Colors:
Make connections to the access control device or adapter cable as required. Be sure that all wiring is correct before power is applied. If more than one card reader or prox card reader must be wired, a CR2 adapter board will be required. Refer to the instructions included with the adapter board for special wiring instructions.
NOTES:
*1. 100CAB must be initialized to function with a keypad.
2. Only one 100CAB adapter cable can be wired. Two keypads can be connected to a single
100CAB.
3. Two TR80 or TR81 touch readers can be wired in parallel.
NOTES:
*1. New 770CAB adapter cables are shipped with the brown wire clipped. It is not necessary to connect it.
2. Consult factory when connecting older keypads that do not use the
770CAB cable to new controller
NOTES:
1. All 15 wires shown must be connected on the
CR90 models.
2. On CR91 models, connect the 9 wires which are <bracketed> to the terminals shown.
NOTES:
1. The PX95 requires the use of a iButton capable device for programming.
Use connection information for appropriate device as shown in addition to information above
(usually, a 770CAB with a keypad or iButton reader). There will therefore be two wires on some terminals. This is normal.
77080-G Page 8 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Programming
Programming
3) Programming:
GENERAL INFORMATION:
Programming the CT500 can be done either by computer programming or manually, using the keypad, or
TEP1 programmer. The standard unit can have up to 500 codes, cards, or iButtons. Their functions can be chosen using software or by manually adding the code/card/iButton and function (see “Definition of
tons which are issued to them along with their functions and PIN numbers (for cards or iButtons). This will enable the ability to manage the access system properly. Time delays can be set either manually or using computer programming.
is reset (memory erased), it will return to factory default codes. A keypad (using the 100CAB) or TEP1 and Master Card/iButton will need to be initialized again. Initializing a Master Card/iButton, TEP1, or changing the Master Code, or computer programming, will erase the factory default codes and “System
7” cards and iButtons.
When programming with a computer, it is possible to enable or disable manual programming. If manual programming is enabled, and a code, card, or iButton is entered manually, the Audit Trail Report will be corrupted. Using the “System 7” programming method, up to 7 iButtons and/or cards can be entered into
WHEN SWIPING MAG-STRIPE CARDS THE
STRIPE MUST BE TO THE RIGHT AS SHOWN.
INSERT THE CARD AT THE TOP OF THE READER
AND SWIPE SMOOTHLY DOWNWARD.
WHEN SWIPING PROX CARDS OR FOBS, SIMPLY
PRESENT THE CARD OR FOB WITHIN A FEW
INCHES OF THE READER.
77080-G Page 9 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Definition of Access Functions and Factory Defaults
Definition of Access Functions and Factory Defaults
•
Definition of Access Functions and Factory Defaults:
MASTER
NORMAL ACCESS
TOGGLE
LOCKOUT
Allows access to programming functions. Will not activate relays.
Activates main relay for relock time delay. Will reset alarm condition.
Activates main relay until same or another Toggle code/ card/iButton is entered.
“Freezes” the lock in its present condition, either locked or unlocked, until the same or another Lockout code/ card/iButton is entered.
ONE-TIME ACCESS: No factory default. This type of code/card/iButton will allow access only once.It will then become deleted from memory.
SUPERVISED ACCESS: No factory default. This type of code/card/iButton allows access only when used with another Supervised Access code/card/iButton. The second code/card/iButton must be entered within five seconds of the first one. The order that they are entered does not matter. The second supervised access credential entered will be reported on the ATR.
DAY/NIGHT/24 HOUR: Closed dry contact from an external timer on TB2 terminals 5 and 6 sets the lock into “night” mode. Open or no contacts set the lock into “day” mode. Code/card/iButtons can be entered into memory by computer or manually. For manual entry use “Add User Code/card/iButton and
Function” programming sequences on page 15 (for codes only) or page 16 (for codes/cards/iButtons)
77080-G Page 10 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Creating a Master iButton & Card / Keypad & 100CAB Init. / TEP1
Creating a Master iButton & Card / Keypad & 100CAB Init. / TEP1 Init.
4) Creating a Master iButton/Card:
(for computer programming)
1) Open the cover of the controller and set dipswitch SW1 for Master iButton/card initialization
according to the type of system you are using (see page 6).
2) Press SW2 once.
3) Touch Master iButton to reader (or swipe the Master Card). The
LED(s) will flash to indicate acceptance.
4) When you are finished, return the dipswitches to “normal” operation.
NOTES:
1. Refer to instructions included with the programmer/software that you will use to program for more
information regarding programming.
2. The Master iButton is used for initiating programming. It will not unlock the door.
3. If audit trail is required, be sure that the lock controllers being used have the ATR chip installed.
IMPORTANT: This version of the CT500 is not compatible with the DOS-based LockTrak software.
Schlage software which supports magstripe/prox cards is required. Consult your distributor for product offering and availability.
5) Keypad/100CAB Initialization:
(required to enable keypad)
It is necessary to initialize the keypad/100CAB any time that the memory is erased.
A. Set SW1 dipswitch for iButton Programmer Initialization (see page 6).
B. Press SW2 one time. The relay on the board should “click”.
C. Touch the iButton which will be used as the master iButton to the reader. When The LEDs stop flashing, press the 1-2 key. When the lights stop flashing press the 3-4 key, and so on until you press the (*) key.
D. Return SW1 dipswitch to its original position.
E. Follow programming instructions on page 15 and page 16.
6) Programmer Initialization TEP1:
TEP1 programmers are intended to simulate a keypad and are required to manually program iButtons or Cards using an iButton-only device. It is necessary to initialize the
TEP1 and Master iButton or Card any time that the memory is erased.
1. Open controller cover and set dipswitches for TEP1 initialization. Press SW2 once.
2. Touch Master iButton to reader (or swipe Master Card).
3. Take the TEP1 programmer and touch reader with each disc in the following order:
•
Wait for LEDs to stop flashing before touching next key or pushing next button.
TEP1
•
Waiting longer than 30 seconds will terminate initialization.
4. After the last key/button is entered, the LEDs will flash, indicating that programming has ended.
5. Return dipswitch to its original position.
77080-G Page 11 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
System 7 Programming / Erasing Memory
System 7 Programming / Erasing Memory
7) System 7 Programming:
Follow this procedure to create 7 iButtons (or cards) without the use of a separate programmer. Note that
7 iButtons or 7 cards can be entered and up to 7 more, provided that the first 7 were all cards or all iButtons. (If the first 7 were cards then the second 7 must be iButtons and visa versa). The function will be determined by the order they are entered, as shown below. Each time system 7 programming is done, previously “System 7” programmed cards/iButtons will be erased. Computer programming, initializing a master iButton/card, or erasing memory will also delete iButtons/cards programmed by this method.
1. Label the 7 iButtons/Cards as follows:
#1 User iButton/Card
#2 Toggle iButton/Card
#3 Lockout iButton/Card
#4 User iButton/Card
#5 User iButton/Card
#6 User iButton/Card
#7 User iButton/Card
2. Open cover of controller and set dipswitches for “System Seven” according to the system you have
3. Momentarily depress SW2 microswitch once. The red LED (or both LED’s w/ 100CAB) will turn on.
4. Touch iButton #1 to the reader (or swipe card). The LED will flash indicating acceptance.
5. Wait for the LED(s) to stop flashing before entering the next iButton (or swiping the next card).
Repeat Step 4 using iButton/card #2 thru iButton/card #7.
6. If fewer than 7 iButtons (or cards) were programmed, press SW2 microswitch once to end
programming. The LED will turn off.
8) Erasing Memory:
(return to factory defaults)
IMPORTANT: Resetting will delete all Keypad codes, iButtons/Cards, Master iButton/Card, and TEP programmers from the lock memory. All time delays and default codes will be restored to default values.
1. Open cover of controller and set dipswitches according to chart on page 6.
2. Depress SW2 microswitch three times. Relay clicking may be heard.
77080-G Page 12 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Setting Time Delays
Setting Time Delays
9) Setting Time Delays:
In most cases, the default time delays are sufficient. If advanced functions are required, follow the steps below to change any or all of the four timers shown below. Note that timers A, B, and C can be assigned to codes, cards or iButtons with different functions. It may be necessary to configure the system (see
page 14) for your system to function as desired.
“A” timer is the default timer for normal access codes. timers A, B, and C can be assigned to codes using
three digit function codes (see page 17).
The door propped delay is the time (starts counting after relock delay ends) before the alarm relay will close. The alarm will clear once the door closes again. The Door Propped Alarm must be enabled (see
77080-G Page 13 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Configuring the System
Configuring the System
10) Configuring the System:
In many cases it will not be necessary to configure the system. If, however, certain functions are desired it will be necessary. Follow the steps below. Note that many functions require that the system be outfitted with additional equipment.
NOTES:
1. The doorbell function and the lamp function require that something be connected to the auxiliary
relay.
2. The door forced open or door propped open alarm require that there be a door position switch
(normally open) which closes when the door opens, connected to TB2 terminals 3 and 4, as well as an
alarm of some kind connected to the alarm relay output.
3. The duress alarm requires that there be an alarm (silent or audible) connected to the alarm relay output.
4. The REX input is for a remote or local control other than a keypad. For example, an exit pushbutton,
electrified exit device, keyswitch, or remote console button. It must be connected to TB2 terminals 1
and 2, normally open.
77080-G Page 14 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Manual Programming - Keypad - Codes Only
Manual Programming - Keypad - Codes Only
11) Manual Programming - Keypad - Codes Only:
(Using Master Code)
When manually programming the CT500, using a keypad, the keypad must first be initialized. It is a recommended that the factory default Master Code be changed. Doing so will delete all factory default codes and ensure the security of the system. After entering the Master code the LEDs on the keypad will flash.
They will also flash each time that * is entered. Wait for the LED to stop flashing before entering the next sequence.
TO CHANGE MASTER CODE:
Master Code *...7 *...New Master Code (5-8 digits)*...New Master Code *
TO ADD NORMAL ACCESS CODES: - Will unlock door for relock time delay period. Will also reset lock in alarm.
Master Code *...3 *... New Code (3-8 digits) *...* (to end)
Up to 150 new codes can be added by returning here.
Note: If an external timer is used, the code will be a “Day
Only” code and will not function if the lock is set to “Night”
mode. See terminal layout information on page 14.
TO ADD CODES WITH SPECIAL FUNCTION: (See page 12 for “3-DIGIT FUNCTION CODES”)
Master Code *...33 *...(3-DIGIT FUNCTION CODE) *...New Code (3-8 digits) *...* (to end)
Up to 150 new codes w/functions can be added by returning here.
TO CHANGE CODES:
Master Code *...1 *...Old Code*...New Code (3-8 digits) *...* (to end)
More codes can be changed by returning here.
TO CHANGE FUNCTION AND/OR PIN:
Master Code *...11*...Old Code*... (New/Same 3-digit function code) *...New/Same Code (3-8 digits)
*...* (to end)
TO DELETE CODES:
Master Code *...5 *...Old Code *...* (to end)
More codes can be deleted by returning here.
TO DELETE CODES WITH ALARM/ATR NOTICE: Codes will be not be allowed to function but will remain in memory. When the code is used, the alarm relay will close. The door will not unlock. If the ATR option is present and the unit was programmed by computer, an access attempt will show in the audit trail.
Master Code *...55 *...Old Code *...* (to end)
More codes can be deleted by returning here.
77080-G Page 15 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Manual Programming - Codes, Cards and iButtons
Manual Programming - Codes, Cards and iButtons
12) Manual Programming - Codes, Cards and iButtons:
(Using Master Card or iButton)
A Master Card or iButton must be used to enter the programming mode in order to program cards or iButtons. If the system does not have a keypad, a TEP1 must be used to manually program cards or iButtons.
It must first be initialized. See steps below. After entering the Master Card/iButton the red and green
LEDs flash. They will also flash each time that * is entered. Wait for the LED(s) to stop flashing before entering the next sequence.
TO ADD NORMAL ACCESS (DAY) CARDS/iBUTTONS/CODES: Will unlock door for relock time delay period. Will also reset lock after an alarm condition.
Master Card/iButton...3*...New PIN(3-8 digits)*...New Access card/iButton...* (to complete)
Up to 500 new codes, cards and iButtons can be added by returning here.
* may be substituted if a code is desired instead of an iButton or card.
TO ADD FUNCTION CARDS/iBUTTONS/CODES: (Note that a three digit function code sets the
Master Card/iButton...33*...(3-digit FUNCTION CODE)*...PIN(3-8 digits)*...card/iButton...* (to end)
Up to 500 new codes, cards and iButtons can be added by returning here.
* may be substituted if a code is desired instead of an iButton or card.
TO CHANGE CODE/PIN:
Master iButton/card...1*...Old PIN*...New/Same PIN (3-8 digits) *...* (to end)
More cards, codes and iButtons can be changed by returning here.
TO CHANGE FUNCTION AND/OR CODE/PIN:
Master iButton/card...11*...Old PIN*... (New/Same 3-digit function code) *...New/Same PIN (3-8 digits) *...* (to end)
More cards, codes and iButtons can be changed by returning here.
TO DELETE CARDS/iBUTTONS/CODES:
Master Card/iButton...5 *...Old Code/PIN*...* (to end)
More iButtons can be deleted by returning here.
TO DELETE CARDS/iBUTTONS/CODES (with alarm/ATR notice): Codes will be not be allowed to function but will remain in memory. When the code is used, the alarm relay will close. The door will not unlock. If the ATR option is present and the unit was programmed by computer, an access attempt will show in the audit trail.
Master Card/iButton...55 *...Old PIN*...* (to complete)
More iButtons can be deleted by returning here.
77080-G Page 16 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
3-Digit Function Codes
3-Digit Function Codes
13) 3-Digit Function Codes:
The following 3-digit function codes can be used to attribute certain special functions to codes, cards, or iButtons. Only one function can be manually assigned to a code/card/iButton. Note that different timers
can be assigned. The time delay may be changed manually (see page 13).
NOTE:
Cards/iButtons/codes generated using 3-digit function codes in this column will change the state of the
MAIN RELAY ONLY.
NOTE:
Cards/iButtons/codes generated using 3-digit function codes below
will change the state of the
AUXILIARY RELAY ONLY.
111...Day Access Code: timer A
151...Day Access Code: timer B
171...Day Access Code: timer C
113...Day One-Time Access Code: timer A
153...Day One-Time Access Code: timer B
173...Day One-Time Access Code: timer C
117...Day Supervised Access Code: timer A
157...Day Supervised Access Code: timer B
177...Day Supervised Access Code: timer C
191...Day Toggle Code
193...Day One-Time Toggle Code
197...Day Supervised Toggle Code
115...Day Lockout Code
711...24Hr. Access Code: timer A
751...24Hr. Access Code: timer B
771...24Hr. Access Code: timer C
713...24Hr. One-Time Access Code: timer A
753...24Hr. One-Time Access Code: timer B
773...24Hr. One-Time Access Code: timer C
717...24Hr. Supervised Access Code: timer A
757...24Hr. Supervised Access Code: timer B
777...24Hr. Supervised Access Code: timer C
791...24Hr. Toggle Code
793...24Hr. One-Time Toggle Code
797...24Hr. Supervised Toggle Code
715...24Hr. Lockout Code
FOR USE WITH EXTERNAL TIMER ONLY:
311...Night Access Code: timer A
351...Night Access Code: timer B
371...Night Access Code: timer C
313...Night One-Time Access Code: timer A
353...Night One-Time Access Code: timer B
373...Night One-Time Access Code: timer C
317...Night Supervised Access Code: timer A
357...Night Supervised Access Code: timer B
377...Night Supervised Access Code: timer C
391...Night Toggle Code
393...Night One-Time Toggle Code
397...Night Supervised Toggle Code
315...Night Lockout Code
511...24Hr. Access Code: timer A
551...24Hr. Access Code: timer B
571...24Hr. Access Code: timer C
513...24Hr. One-Time Access Code: timer A
553...24Hr. One-Time Access Code: timer B
573...24Hr. One-Time Access Code: timer C
517...24Hr. Supervised Access Code: timer A
557...24Hr. Supervised Access Code: timer B
577...24Hr. Supervised Access Code: timer C
591...24Hr. Toggle Code
593...24Hr. One-Time Toggle Code
597...24Hr. Supervised Toggle Code
515...24Hr. Lockout Code
NOTE:
Cards/iButtons/codes generated using 3-digit function codes below
will change the state of the
MAIN AND AUXILIARY RELAYS
911...24Hr. Access Code: timer A
951...24Hr. Access Code: timer B
971...24Hr. Access Code: timer C
913...24Hr. One-Time Access Code: timer A
953...24Hr. One-Time Access Code: timer B
973...24Hr. One-Time Access Code: timer C
917...24Hr. Supervised Access Code: timer A
957...24Hr. Supervised Access Code: timer B
977...24Hr. Supervised Access Code: timer C
991...24Hr. Toggle Code
993...24Hr. One-Time Toggle Code
997...24Hr. Supervised Toggle Code
915...24Hr. Lockout Code
77080-G Page 17 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Sample Wiring Diagrams
Sample Wiring Diagrams
•
Sample Wiring Diagrams:
Below are two sample wiring diagrams showing only the power supply connections, connections to fail safe or fail secure lock, request to exit (REX), door status switch, and external timer. Note that the door status switch and timer are completely optional, depending on the design of your system.
CT500 w/MODEL 505 POWER SUPPLY (OR PS OPTION):
CT500 w/AC TRANSFORMER:
77080-G Page 18 07-27-2007
CT500 INSTALLATION & PROGRAMMING MANUAL
Error Codes / Troubleshooting
Error Codes / Troubleshooting
•
Error Codes:
If an error is made while manually programming a lock, an error code indication will be indicated at the iButton Key reader or keypad. The LED(s) will flash several times. Count the number of flashes and refer to the chart below for diagnosis.
ERROR CODES
Number of
Flashes
6
7
8
9
10
2
3
4
5
Error
Code entered too long. Code length cannot exceed 8 digits.
Memory full - too many codes/iButtons entered.
Master Code cannot be deleted, only changed.
Second entry of Master Code does not match first. Master Code unchanged.
Invalid commend.
Code does not exist. (For “Delete WIth Alarm/ATR” only.)
Code too short. Minimum Master Code=5-digits. Minimum User Code=3-digits.
Not a unique code/iButton.
Manual Programming disabled.
•
Troubleshooting:
Some common problems associated with the installation of the CT500 series can be easily recognized and corrected:
Problem: Possible Solution:
System has power but lock won’t lock.
No lights on.
System has power, but lock won’t lock.
Light/Lights always flashing.
Check wiring. Possibly the relay is wired wrong or power is not applied to lock.
REX (request to exit) input device wired closed instead of open.
Keypads lights work, but programming steps don’t seem to function.
Initialized Keypad (100CAB only)
Wrong master code, iButton, or Card.
When programming, unit will not accept iButtons or Must use master iButton or Card to program
Cards.
iButtons or Cards.
Door Position switch not installed or wired properly.
Door Forced/Propped Alarm configured, but not
Active.
Door Position installed and wired properly.
Door Forced/Propped Alarm not working.
System not configured properly.
Alarm not wired properly.
77080-G Page 19 07-27-2007
Notes
CT500 INSTALLATION & PROGRAMMING MANUAL
Notes
•
NOTES:
77080-G Page 20 07-27-2007
Download
Advertisement
Key features
Connects to iButton readers, Keypads, mag-stripe and Prox Card Readers
Supports up to 500 Codes, Cards or iButtons
Can be programmed manually or via computer
Supports day/night and 24-hour access modes
Includes several configurable timer options
Offers a variety of programming and security features
Supports door forced/propped alarms
Provides Master iButton/Card initialization
Allows for keypad/100CAB initialization
Supports System 7 programming
Frequently asked questions
The CT500 can hold up to 500 user codes, cards, or iButtons.
The CT500 is compatible with iButton readers, Keypads, mag-stripe readers, and Prox Card readers.
You can program the CT500 manually via a keypad or using computer software. The manual provides detailed instructions for both methods.
The CT500 supports day, night, and 24-hour access modes. You can program cards/iButtons/codes to function during specific times using an external timer.
The CT500 has four adjustable timers: A, B, C, and the Door Propped Delay. You can assign different timers to different user codes, cards, or iButtons.
Follow the instructions in the manual for initializing a Master iButton/Card. This step is crucial for initiating programming and ensuring system security.
You need to install a door position switch and configure the system accordingly. Refer to the manual's instructions for details on wiring and configuration.
Yes, the manual provides steps for erasing the memory and restoring the unit to its factory default settings.
The manual provides a table with error codes and their corresponding meanings. Use this table to diagnose and resolve any programming issues.