Conventional
Fire Alarm Systems
2
Contents
Introduction
Premier SX Conventional
Fire Alarm Panel
Premier Elite Conventional
Fire Alarm Panel
Premier Conventional Repeater Panel
Premier M Plus 8-24 Zone
Conventional Fire Alarm Panel
Premier M Plus Repeater Panel
Premier 48 M Plus 24-48 Zone
Conventional Fire Alarm Panel
Premier 48 M Plus Repeater Panel
Premier MX Conventional
Fire Alarm Panel
Fyreye Extra Conventional
Optical Smoke Detector
Fyreye Extra Conventional Rate of
Rise and Fixed Heat Detectors
Fyreye Extra Conventional
Opto-Heat Detector
Fyreye Conventional
Ultra-Violet Flame Detector
Fyreye Conventional Detector Bases
Zeta Remote LED Indicator
Fyreye 50 & 100m Reflective Beam
Smoke Detector
Fyreye 50 & 100m Auto-aligning Beam
Smoke Detector Systems 50 & 100m
3-7
8
11
12
13
14
15
16
17
18
22-23
24-25
19
20
21
9
10
Zeta UV/IR Optical Flame Detectors
Zeta Conventional Manual Call Points
Zeta Conventional
Weatherproof Call Point
Zeta Conventional Explosion Proof
Manual Call Point
Miditone Conventional
Electronic Sounder
Miditone Conventional Combined
Electronic Sounder & Flasher
Securetone Conventional
Electronic Sounder
Secure Light Xenon Flasher
Maxitone Conventional Sounder and
Combined Sounder & Flasher
Zeta Conventional Fire Alarm Bells
Zeta Flame Proof Siren
Zeta Flame Proof Gong Bell
Zeta Magnetic Door Holders
Zeta Duct Unit
Premier Power Pack EN 54-4 Power
Supply with LCD Screen
Batteries
31
32
33
34
37
38
35
36
39
40
41
42
26-27
28
29
30
Introduction
Zeta Alarm Systems, a trading name of GLT Exports Ltd, was founded in 1985 and is a privately held UK manufacturer of
Fire Alarm
,
Gas
Detection
and
Emergency Systems
.
Our brand name is well known throughout the industry and is acclaimed in
over forty countries worldwide
. We are currently represented in the UK, Europe, Africa, the
Middle East, Southern Asia & South America and this list continues to grow.
Complete System Supplier
To meet the requirements of our ever-changing market, we pride ourselves on being a
complete system supplier
. This means our customers can rely on us for their
entire system requirements
.
One of the main advantages of using a complete system supplier, compared with a component supplier, is that system wide compatibility is assured and there is one point of contact.
Marketing our products as systems has played a vital role in our
worldwide success
.
The Future
Our continued inward investment and constant endeavour to offer the very best products is recognised by our increased turnover and profit margin year-onyear. Our mission is to support our existing & future customers by providing them with the
highest quality products, at the most competitive prices
.
Customer Support & Product Warranty
We value our customers greatly and to ensure they have the best experience we have a dedicated support team who are able to assist with sales, technical or logistical queries.
Our products carry a full
24 month manufacturers’ guarantee
from the date of purchase. Our network of authorised agents is fully trained on the use of our products and will provide a helpful & friendly service.
Research & Development
As with all electronic equipment there is an ever present drive to
manufacture products that are increasingly effective whilst becoming more cost sensitive
. To meet this objective we spend a significant percentage of our profits on the continued development of products, whether it be introducing new items, or improving existing ones. We have a team of engineers & designers all of whom have vast industry knowledge & experience.
As a manufacturer we always follow the market needs closely to evaluate how we should adapt our product range. This, combined with welcomed customer feedback, has proved to be a successful formula for meeting the current and future industry needs.
Statement Of Quality Policy
We maintain a Quality System, which conforms to BS EN
ISO9001:2008. We are committed, where applicable, to manufacture in compliance with all appropriate legislation & regulatory requirements.
3
4
Introduction to Fire
Alarm Systems
Fire Detection &
Alarm Systems BS5839
Fire alarm systems are used to detect a fire, and to signal a warning alarm to the appropriate source.
In general, there are 3 types of system;
1.
Manual Fire Alarm Systems
– which rely on manual call points to signal an alarm
2.
Life Protection Fire Alarm Systems
– these are designed to protect the occupants of a building
3.
Property Protection Fire Alarm Systems
– these are designed to protect buildings
Risk Assessment
The ‘Fire precautions (Workplace) Regulations’ require any business employing five or more persons to hold a written ‘Fire Risk Assessment’ and ‘Emergency Plan’.
This must be periodically reviewed.
The local fire brigade can enforce compliance, and close any building that does not meet this act.
In the event of a fire in a building without a written
‘Fire Risk Assessment’, those responsible may face fines and imprisonment, and/or private litigation.
The warning may be simply ringing fire alarm sirens, however if a building is likely to be unoccupied, it may be more appropriate to signal to a monitoring station, or at least send a message to the building owner via telephone.
What the law requires you to do:
Complete a fire risk assessment for your work place (considering all employees, the public, disabled people and people with special needs).
Identify and record any significant findings or persons at risk.
Provide and maintain fire precautions.
Provide information, instruction and training.
Nominate persons responsible to implement your emergency plan.
Consult employees about the above nominations and your proposals to improve fire precautions.
Inform other employees who may have work places in the building about any significant risks which may affect their safety and co-operate with them to reduce/control these risks.
If you are not an employer, but control premises which contain more than one workplace, you are responsible for complying with fire regulations.
You must establish a suitable means of contacting the emergency services.
Your employees must co-operate to ensure the workplace is safe from fire and its effects.
System Zoning
Information
In order to aid identification of the source of a possible fire, the protected building should be divided into
‘zones’. When deciding on a suitable zoning scheme for a building, consideration should be given to the size, any existing fire routines, escape routes, zone accessibility, and structural fire compartmentation.
The following guide lines should be observed:
If the total floor area of the building is less than 300m
2
then the building needs only one zone, regardless of the number of storeys.
Manual Call Points
A ‘Manual Call Point’ is a device which enables personnel to raise an alarm in the event of a fire incident by pressing a frangible element to activate the alarm system.
Manual Call Points should be installed at a height of
1.2m above floor level at easily accessible, conspicuous positions, on exit routes, at the entry floor landings of staircases and at all exits to the open air.
If the total floor area is greater than
300m
2
:
The maximum area for a zone is 2000m
2
If a stairwell (or similar) extends beyond one floor it should be a separate zone.
If a zone covers more than one fire compartment then the zone boundaries should follow the compartment boundaries.
The search distance within the zone in order to ascertain the position of the fire should not exceed
60m. Remember that the use of Remote Indicator lamps may help to reduce the distance travelled.
1.2m - 1.4m
Manual Call Points should be spaced so that one may always be found within a maximum distance of 45m apart or 25m for disabled person.
45m Max. or
25m Max. for disabled person
60m Max.
If a building is divided between occupiers, zones must not be shared between them.
5
6
Detector Information
Automatic Detectors
When deciding on the type of detector to be used in any area it is important to remember that the detector has to discriminate between a genuine fire and the normal conditions existing therein.
Smoke Detectors
In open spaces under flat horizontal ceilings, every point should lie within 7.5m of a smoke detector.
Heat Detectors General
In open spaces under flat horizontal ceilings, every point should lie within 5.3m of a heat detector.
10.6m
7.5m
112m²
(10.6m x
10.6m)
Room boundary
56.3m²
(7.5m x
7.5m)
Room boundary
7.5m
5.3m
5.3m
3.8m
Smoke detection should be generally avoided in the following areas to avoid unwanted alarms. They should be protected by means of other detectors such as heat detectors.
Contamination in dusty areas may cause unwanted alarms and reduce the life of the detector.
Damp or humid conditions such as showers, bathrooms and external areas should be avoided as the water vapour may cause unwanted alarms and reduce the life of the detector.
Detectors should not be mounted where gases, vapours or fumes are present.
Detectors should never be used at low temperature where ice or condensation can affect detector sensitivity.
Kitchens, garages, welding shops and boiler houses should generally be avoided.
Heat detectors are designed to either detect a rapid rise in temperature or to operate at a fixed temperature. Although they provide a slower response time than smoke detectors they do provide a method of protection for areas where smoke detectors cannot be used.
Heat detectors should not be used for the protection of life or where extensive property loss may be expected.
‘Rate of Rise’ Heat Detectors
‘Rate of Rise’ heat detectors respond to both rapid increases of temperature and to fixed top temperature.
‘Fixed Temperature’ Heat Detectors
Fixed temperature heat detectors are available with different temperature settings, and are normally installed in kitchens, boiler rooms, etc.
Detection In Apex Roofs
If the ceiling is pitched or sloping, smoke will tend to rise towards the highest point (apex) of the roof, therefore detection should be placed in the apex. As the slope tends to reduce the delay before smoke or heat reaches the detectors, it is permissible to use a greater spacing between the detectors mounted there.
Limits of Ceiling Height
Fire Alarm Sounders
Fire Alarm Sounders should be installed throughout the building with an even distribution, to generally provide a minimum sound level of 65dB(A) or 5dB(A) above any background noise which is likely to persist for more than 30 seconds.
65dB(A)
@ 500Hz - 1000Hz
+5dB(A)
@ 500Hz - 1000Hz
Background noise
Heat
Detector
Smoke
Detector
Heat
Detector
Smoke
Detector
Apex
<150mm
Apex
<600mm
Apex
>150mm
Apex
>600mm
Small Apex
= Standard Spacing
Large Apex
= Extended Spacing
Cabling
The operation of a Fire Alarm and Detection
System’ depends on the cabling and connections between the components. It is essential that connection between Manual Call Points and
Detectors function correctly when they are operated.
Cables within the system are required to function correctly for significant periods after being attacked by fire. These include the power supply cables to the control panel, the detection circuits and the fire alarm sounder circuits. Thus the cables chosen must be correctly rated to withstand these conditions.
Where the alarm may have to arouse sleeping persons e.g. Hotel bedrooms, nursing homes, etc, a minimum sound level of 75dB(A) is required, at the bed head with all the doors shut.
75dB(A)
All fire alarm sounders in a building should produce the same sound, distinct from any other audible warning devices in the building.
Where fire alarm sounders are required in extremely noisy areas e.g. Machine shops, it may be necessary to install additional ‘Visual Indication Beacons’.
7
Conventional Fire Alarm Systems /
Premier SX Conventional Fire Alarm Panel
(NPSX1, NPSX2, NPSX4, NPSX6, NPSX8)
8
The Premier SX control panel range is available in 1, 2, 4, 6 and 8 zones, housed in a light grey flame retardant ULV0 enclosure, designed to meet modern architectural surroundings, with a removable hinged door.
The Premier SX has been designed with ease of installation in mind, in addition to the robust electronic design expected from Zeta Alarm Systems.
73mm 100mm
Features
LPCB Approved to EN54 parts 2 & 4
One man test facility
Disablement facility for zones & sounders
Space for up to 7Ahr batteries
Sounder delay option (0 – 9 min)
Panel can be flush mounted
Flush Mount
Model
Part No.
Mains Voltage
System Voltage
Zone Voltage
Sounder Alarm Output
Fault Relay Output
Fire Relay Output
Zone Capacity
Remote Sounder Activation
Sounder Activation Delay
Zone End Of Line
Sounder End Of Line
Charger Voltage
Zone Short Circuit Protection
Charger Short Circuit Protection
Enclosure Size
Weight
Wall Mount
NPSX1
37-050
NPSX2
37-051
230V AC +10% / -15% @ 50/60Hz
NPSX4
37-052
24V DC (nominal)
21V DC (nominal)
2 x 400mA @ 24V DC (nominal)
1 x relay SELV @ 1A maximum
1 x relay SELV @ 1A maximum
32 devices per zone
Via N/O contact (class change)
0-9 minutes in 1 minute increments
IN4002 Diode (cathode stripe to +)
10K resistor
28.4V @ 20°C (with battery disconnected)
100mA
Battery voltage less than 20V
355 (l) x 275 (h) x 100 (d) mm
3.25kg (excluding batteries)
NPSX6
37-053
NPSX8
37-054
Conventional Fire Alarm Systems /
Premier Elite Conventional Fire Alarm Panel
(PE1, PE2, PE4, PE6, PE8)
The Premier Elite 1-8 zone fire alarm panels are ideal for small to medium sized installations. They meet all the requirements of EN54 parts 2 & 4, and come in an attractively styled enclosure.
The zonal output card gives a drive voltage to operate zonal alarm relays, or a hardwired repeater panel.
73mm
Flush Mount
Model
Part No.
Detection Zones
Mains Voltage
System Voltage
Zone Voltage
Sounder Alarm Output
Fault Relay Output
Fire Relay Output
Zone Capacity
Remote Sounder Activation
Sounder Activation Delay
Zone End Of Line
Sounder End Of Line
Charger Voltage
Zone Short Circuit Protection
Charger Short Circuit Protection
Operating Temperature
Enclosure Size
Weight
100mm
Features
Fault relay (4, 6 & 8 zone only)
Alarm relay
Current limited charger to prevent flat batteries drawing too much current (4, 6 & 8 zone only)
Built in diode base compatibility (4, 6 & 8 zone only)
Sounder delay facility (4, 6 & 8 zone only)
Connection to optional add on zonal output card
(4, 6 & 8 zone only)
Zone disablement facility (4, 6 & 8 zone only)
One man test facility (4, 6 & 8 zone only)
Wall Mount
PE1
37-040
PE2
37-041
1 2
230V AC +10%/-15% @ 50/60Hz
PE4
37-042
4
PE6
37-043
6
PE8
37-044
8
24V DC (nominal)
22V DC (nominal)
2 x 400mA @ 24V DC (nominal)
N/A
29V DC (nominal)
1 x relay SELV @ 1A maximum
1 x relay SELV @ 1A maximum
20 Devices
N/A
N/A
10K resistor
10K resistor
32 Devices
Via N/O Contacts
0-9 minutes in 1 minute increments
IN4002 Diode (cathode stripe to +)
10K resistor
27.6V DC (No Batt Connected) 28.4V @ 25°C (No Battery Connected)
N/A
N/A
0°C to 50°C
355 x 275 x 100mm
2.5kg (excluding batteries)
100mA
Batteries less than 21V
3.25kg (excluding batteries)
9
Conventional Fire Alarm Systems /
Premier Conventional Repeater Panel
(PRE-REP)
73mm 100mm
The Premier Repeater panel is a hard-wired repeater panel for use with the Premier SX (all sizes), and the Premier Elite (4-8 zone) panels.
It is display only (no controls) and indicates power, general fault, general fire & the zone in alarm. It also has an internal buzzer to indicate that it requires attention.
It comes supplied with an interface card to connect to the Premier SX and Premier Elite (4-8 zone) panels.
Features
Zonal indication for fire
Common fault indication
Surface or semi flush fixing
10
Model
Flush Mount
Part No.
Supply Voltage
Supply Voltage
Connections
Operating Temperature
Enclosure Size
Weight
Wall Mount
PRE-REP
37-045
20–35V DC
29V DC (nominal)
A+
0V
GA
CF-
TN-
Z1- to Z8-
-0°C to 50°C
355 x 275 x 100mm
1kg
Supply +VE
Supply –VE
General Alarm
Common Fault
Tone (Buzzer Active)
Zonal Alarm
Conventional Fire Alarm Systems /
Premier M Plus 8-24 Zone Conventional Fire
Alarm Panel
(PMP8, PMP16, PMP24)
Model
Part No.
Detection Zones
Mains Voltage
System Voltage
Zone Voltage
Sounder Alarm Output
Fault Relay Output
Fire Relay Output
Zone Capacity
Remote Sounder Activation
Sounder Activation Delay
Zone End Of Line
Sounder End Of Line
Charger Voltage
Zone Short Circuit Protection
Charger Short Circuit Protection
Charger Size
Operating Temperature
Enclosure Size
The Premier M Plus control panels are designed to fulfil the requirements of EN54 parts 2 & 4 as well as being easy to install, operate and maintain.
Being of modular construction, the basic M Plus panel has 8 zone capacity, expandable to 16, 20 and 24 zones.
The Premier M Plus is suitable for surface mounting or semi-flush fitting (with just the door protruding).
Features
4 Common sounder circuits (150mA each)
Optional add-on zonal sounder circuits (50mA
Max.)
Serial repeater output
Auxiliary supply (29 Volts, 250mA)
Zone & sounder disablement facility
Sounder delay facility
Zonal to common timer (when fitted with zonal sounder boards)
One man test mode
PMP8
37-020
PMP16
37-022
8 16
230V AC +10% / -15% @ 50/60 Hz
24V DC (nominal)
21V DC
4 x 150mA @ 24V DC
1 x relay SELV @ 1A maximum
1 x relay SELV @ 1A maximum
32 Devices
N/A
0 – 9 minutes in 1 minute increments
IN4002 Diode
10KΩ Resistor
28.4V DC (batteries disconnected)
100mA
Batteries less than 20V
3.0 Amp
0°C - 50°C
485 x 477.5 x 125mm
PMP24
37-024
24
11
Conventional Fire Alarm Systems /
Premier M Plus Repeater Panel
(PMP-REP, PMP-REP/M)
12
The Premier M Plus repeater is available in 2 versions – standard & multiple.
The standard repeater offers display & control functions, however it is limited to one per system.
The second version allows multiple repeaters on the same system however they do not have any control functions (i.e. they cannot be used to silence or reset the system).
A single repeater can be powered from the panels’ auxiliary 24V supply. If more than one repeater is to be used, a separate 24V is required.
Model
Part No.
Functions
Supply Voltage
Max. Quantity Per System
Connections
Operating Temperature
Enclosure Size
Weight
PMP-REP
37-026
Display & control
20-30V DC
1
Serial Repeater A
Serial Repeater B
+24V DC
0V
0°C to 50°C
375 x 335 x 125mm
TBC
PMP-REP/M
37-027
Control only
5
Conventional Fire Alarm Systems /
Premier 48 M Plus 24-48 Zone Conventional
Fire Alarm Panel
(PMP48/24, PMP48/32, PMP48/40, PMP48/48)
The Premier 48 M Plus control panels are designed to fulfil the requirements of EN54 parts 2 & 4 as well as being easy to install, operate & maintain.
Being of modular design, the basic panel has 24 zones built in and it can be expanded to 32, 40 & 48 zones.
The construction of the panel is epoxy painted steel enclosure, with top & rear cable entries.
Features
4 common sounder circuits (400mA each)
Optional add-on zonal sounder circuits (50mA
Max)
Serial repeater output
Auxiliary supply (29 Volts, 250mA)
Zone & sounder disablement facility
Sounder delay facility
Zonal to common timer (when fitted with zonal sounder boards)
One man test mode
Model
Part No.
Detection Zones
Supply Voltage
System Voltage
Zone Voltage
Sounder Alarm Output
Fault Relay Output
Fire Relay Output
Other Connections
Zone Capacity
Remote Sounder Activation
Sounder Activation Delay
Zone End Of Line
Sounder End Of Line
Charger Voltage
Zone Short Circuit Protection
Charger Short Circuit Protection
Charger Size
IP Rating
Operating Temperature
Enclosure Size
Weight
PMP48/24
37-030
PMP48/32
37-032
24 32
230V AC +10%/-15% @ 50/60 Hz
PMP48/40
37-034
40
PMP48/48
37-036
48
29V DC (nominal)
21V DC
4 X 400mA @ 24V DC
1 relay SELV @ 1A (normally energised)
1 relay SELV @ 1A maximum
Class Change Input (N/O Contact) / F.A.R.E. Output / Serial Repeater Output (4 Wire)
Up to 32 devices
N/A
0 to 9 minutes
100μF capacitor
10K resistor
28.4V DC (Batteries disconnected)
100mA
Batteries less than 20V
3 Amp
IP43
0°C to 50°C
675 x 480 x 135mm
13kg
13
Conventional Fire Alarm Systems /
Premier 48 M Plus Repeater Panel
(PMP48-REP, PMP48-REP/M)
14
The Premier 48 M Plus repeater is available in
2 versions – standard & multiple.
The standard repeater offers display & control functions, however is limited to one per system.
The second version allows multiple repeaters on the same system however they do not have any control functions (i.e. they cannot be used to silence or reset the system).
A single repeater can be powered from the panels’ auxiliary 24V supply. If more than one repeater is to be used, a separate 24V is required.
Model
Part No.
Functions
Supply Voltage
Maximum Quantity Per System
Connections
Operating Temperature
Enclosure Size
Weight
PMP48-REP
37-037
Display & control
20–30V DC
1
Serial Repeater A
Serial Repeater A
+24V DC
0V
0°C to 50°C
480 x 330 x 60mm
4.8kg
PMP48-REP/M
37-038
Control only
5
Conventional Fire Alarm Systems /
Premier MX Conventional Fire Alarm Panel
(MX-16 & MX-32)
The Premier MX ranges of panels are available in either 16 or 32 zone versions and have been approved by LPCB to EN54 parts 2 & 4.
The panels offer an extensive range of configuration options whilst remaining easy to install and configure.
Model
Part No.
MX-16
37-140
Detection Zones 16
Supply Voltage 230V AC +/- 10%
MX-32
37-142
32
System Voltage
Zone Voltage
24V DC (Nominal)
24V DC (Nominal) Relay, SELV @ 1A
Zone End of Line 22uF, 35V Axial Capacitor
Sounder Output 4 X 1.0A @ 24V DC
Sounder EOL
Aux DC Output
Repeater option
Panel Inputs
3K9 Resistor
24V DC (Nominal) 1A
Yes
Remote
Evacuation
Fire Protection Relay,
SELV @ 1A
Remote Silence
Alarms
Disablement Active
(Open Collector
Output)
Remote Reset
Class Change
Panel Outputs
Evacuation Active
(Open Collector
Output)
Fault Routing
Relay, SELV @ 1A
Buzzer Active (Open
Collector Output)
Fire Routing
Relay, SELV @ 1A
RS 485 Repeater
Connection
Operating
Temperature
Size
Weight
-5°C to 40°C
325 x 370 x 126mm 400 x 441 x 131mm
7.05kg 9.35kg
Features
LPCB Approved to EN54 parts 2 & 4
Zonal one-man test facility
Latching or non-latching zones
Delayed or non delayed zone operation
Standard or intrinsically safe zone mode
Short circuit to fire mode for compatibility with old detectors
Zonal or common alarm operation (requires output expansion PCBs)
Latching or non-latching fault modes
Fault routing, fire routing & fire protection relays can be programmed as 24V output
(monitored) or volt free
Fault routing, fire routing & fire protection relays can have delayed operation in any configuration
The panel is available as flush mount on request
Repeater panel option (up to 5 maximum per panel)
15
Conventional Fire Alarm Systems /
Fyreye Extra Conventional
Optical Smoke Detector
(FEOE2000)
100mm 37mm
The Fyreye Extra optical smoke detector uses a pulsing IR LED & photodiode to detect IR scatter caused by smoke entering the chamber.
The detector is particularly suitable for detecting optically dense smoke, involving materials such as soft furnishings, PVC, plastic, foam and all similar materials which produce small visible particles (0.5 to 10μm).
The detector will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition.
Features
Designed to meet EN54 requirements
Attractive design
Dual LEDs for 360° visibility
Lockable base to stop unauthorised removal
Compatible with all Fyreye bases
16
Model
Part No.
Detector Class
Design Standard
Approval
Operating Voltage
Quiescent Current
Alarm Current @ 24V DC
Operating Temperature
Minimum Continuous Temperature
Maximum Humidity
Alarm Condition
Coverage
IP Rating
Start-up Time
Size (with Base)
Weight (with Base)
FEOE2000
80-022
Optical Smoke
EN54 part 7
DIFT
9-33V DC
65μA
53mA MAX
-10°C to +50°C
0°C
95% RH non-condensing
2.4% obscuration per metre
100m
2
IP43
10 Seconds
100 x 37mm (101 x 53mm)
95g (153g)
Conventional Fire Alarm Systems /
Fyreye Extra Conventional Rate of Rise and
Fixed Heat Detectors
(FEHE2000 & FEFHE2000)
100mm 48mm
The Fyreye Rate of Rise heat detector
(FEHE2000) uses a thermistor arrangement to sense a quick rise in temperature and also a final threshold temperature of 57°C. The
Fyreye fixed heat detector (FEFHE2000) has a single thermistor arrangement that gives an alarm at a temperature of 90°C.
The detectors will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition.
Features
Designed to meet EN54 requirement
Lockable to base to stop unauthorised removal
Remote LED output
Dual LEDs for 360° visibility
Compatible with all Fyreye bases
Model
Part No.
Detector Class
Design Standard
Approval
Operating Voltage
Quiescent Current
Alarm Current @ 24V DC
Operating Temperature
Minimum Continuous Temperature
Maximum Humidity
Alarm Condition
Coverage
IP Rating
Start-up Time
Size (with Base)
Weight (with Base)
FEHE2000
80-038
Rate of Rise & Fixed Heat Detector
FEFHE2000
80-039
Fixed Heat Only
EN54 part 5
DIFT
9-33V DC
40μA
34mA
-10°C to +50°C
0°C
95% RH non-condensing
Rate of rise or fixed heat trigger @ 57°C Fixed heat trigger @90°C
50m²
IP43
10 Seconds
100 x 48 mm (101 x 64 mm)
75g (133g)
17
18
Conventional Fire Alarm Systems /
Fyreye Extra Conventional
Opto-Heat Detector
(FEOH2000)
100mm
Model
Part No.
Detector Class
Design Standard
Approval
Operating Voltage
Quiescent Current
Alarm Current @ 24V DC
Operating Temperature
Minimum Continuous Temperature
Maximum Humidity
Alarm Condition
Coverage
IP Rating
Start-up Time
Size (with Base)
Weight (with Base)
50mm
The Fyreye Extra opto-heat detector incorporates both an optical chamber and heat sensing element with advanced detection technology & discrimination algorithms. This multisensor is the perfect replacement for ionisation detectors.
The detector will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition.
Features
Advanced electronic technology used to minimise false alarms
Designed to meet EN54 requirement
Built-in 10 seconds alarm verification
Lockable to base to stop unauthorised removal
Remote LED output
Dual LEDs for 360° visibility
Compatible with all Fyreye bases
FEOH2000
80-025
Optical / Heat
EN54
DIFT
17-20V DC
100μA
70mA MAX
-20°C to +60°C
0°C
95% RH non-condensing
3% obscuration per metre
100m²
IP43
10 Seconds
100 x 50mm (100 x 66mm)
95g (153g)
Conventional Fire Alarm Systems /
Fyreye Conventional
Ultra-Violet Flame Detector
(FEUV2000)
0°
30° 30°
60° 60°
VERTICAL VIEWING
(top fig.)
90° 90°
UV EMISSION
POINT
ANODE
CATHODE
0°
30° 30°
90°
60° 60°
90°
ANODE
CATHODE
Horizontal & Vertical Detector Field Of View
HORIZONTAL
VIEWING
(bottom fig.)
The Fyreye ultra-violet flam detector is particularly suited to applications where flames can be expected to develop initially rather than smoke. This is typically due to the nature of the materials being protected for instance camera film, computer, audio & video tapes or disks.
The detector is for indoor use only and should not be exposed to spurious sources of UV, such as sparks, uncovered halogen lights, lightening, etc. as these may trigger a false alarm.
Due to the operational nature of flame detectors it is generally recommended to fit just one detector per zone.
Features
Low profile shape
The detector is solar blind and incorporates an electronic filter to eliminate unwanted alarms from naturally occurring phenomena
Fast response time
High immunity to electrical noise & RF interference
Model
Part No.
Detector Class
Operating Voltage
Quiescent Current
Alarm Current @ 24V DC
Operating Temperature
Minimum Continuous Temperature
Maximum Humidity
Alarm Condition
Detection Angle
UV Sensitivity
Size (with Base)
Weight (with Base)
FEUV2000
80-045
Ultra Violet Flame Detector
12-28V DC
320μA
45-50mA
0°C to 45°C
0°C
95% RH non-condensing
10 seconds for 30mm flame @ 4 metres
120°
185-260nm
98 x 36mm (98 x 52mm)
85g (143g)
19
Conventional Fire Alarm Systems /
Fyreye Conventional Detector Bases
(FE-CB, FE-DB, FE-RB)
FE-CB
FE-CB/S FE-CB/D FE-RB FE-DB
20
There are 3 types of base available for the Fyreye conventional range of detectors namely common base, diode base and relay base.
The Fyreye common base and diode base are available in standard, shallow or deep versions.
The diode base is used on systems that do need line integrity on head removal. This would include all conventional systems that mix detectors & call points on the same line (please note that the Premier M
Plus panels will need an active end of line to work with diode bases).
The common base is used on systems that do not need to keep line integrity on head removal and also on addressable systems.
The relay base is mainly used on 12V security systems to signal detector operation to the panel. They can also be used on 24V fire systems where the activation of a particular detector requires a signal to nearby equipment (for instance door holders).
Please note that a remote led indicator cannot be used with a relay base as the detector cannot sink enough current to operate both.
Model
Part No.
Type
Supply Voltage
FE-CB
9-33V DC
FE-CB/S
80-050
Common base
80-050S
FE-CB/D
80-050D
FE-DB
80-052
Diode base
FE-DB/S
80-052S
FE-DB/D
80-052D
FE-RB
80-054
Relay base
24V DC
Quiescent Current @ 24V
Alarm Current @ 24V
0μA
0mA
Relay Max Switching Power N/A
Relay Max Switching Power N/A
Relay Max Switching Current N/A
Relay Max Switching Voltage N/A
Relay Minimum Capability
Relay Dropout Voltage
Operating Temperature
N/A
N/A
-20°C to 90°C (non-condensing or icing)
Max. Wind Speed
Connections
Size
Weight
15mA
30W, 50VA
30W, 50VA
1A resistive
50V AC
10μA, 10mV
<6V
Not affected
L1in, L1out, L2, -R & Earth
100 x 15mm 100 x 8mm 100 x 25mm 100 x 15mm 100 x 8mm 100 x 25mm 100 x 15mm
48g 42g 61g 48.2g
42.2g
61.2g
171.4g
Conventional Fire Alarm Systems /
Zeta Remote LED Indicator
(ZT-RL)
Remote LEDs indicators are used in installations where a detector going to alarm is likely to occur out of sight (for instance behind a locked door or in a ceiling void). In these instances the indicator will then show the location of the alarm.
Features
Twin LED’s
Surface or flush mounting
Model
Part No.
Input Voltage
Quiescent Current
Alarm Current
Operating Temperature
Max Humidity
IP Rating
Size
Weight
ZT-RL
48-023
5 – 30vdc
0mA
12mA
0°C - 50°C
95% Relative Humidity Non-condensing
IP41
85 x 85 x 70mm
113g
21
Conventional Fire Alarm Systems /
Fyreye 50 & 100m Reflective Beam
Smoke Detector
(ZT-50RZ, ZT-100RZ, ZT-50RV & ZT-100RV)
The Fyreye reflective beam detectors comprise of a single unit incorporating an infrared transmitter & receiver. The signal is reflected by a prism and analysed for smoke presence.
Should a predetermined level be reached then the detector will signal an alarm.
The system is designed to be mounted so that the beam will project between 0.3 and 0.6 metres below the ceiling and parallel to it. Lateral detection may be up to
7.5 metres either side of the beam.
22
126mm 120mm
70mm
100mm
9.5mm
Features
50 or 100 metre reflective beam smoke detector
VdS approved
Complies fully to;
BS 5839 part 5
EN54 part 12
Single compact housing
Horizontal or vertical mounting
12-24V DC operation
Low current consumption
Latching or non latching alarm
Reflector targeting mode to ease set-up
Microprocessor controlled
Automatic contamination compensation
Selectable sensitivity
Robust construction
The Fyreye beam detectors are available with ranges of up to 50 or 100 metres and either 2 or 4 wire connections.
The
2 wire models
(ZT-50RZ & ZT-100RZ) are zone powered (please note these will only work on Premier SX & M Plus panels).
The
4 wire models
(ZT-50RV & ZT-100RV) require an external 24V power supply and have a fire & fault relay output for wide compatibility.
Typical Applications
Beam detectors are generally used for two purposes; either to cover a wide-open space and/or in places where several regular smoke detectors would be aesthetically unacceptable.
Such places include;
Shopping centres
Heritage sites
Churches or mosques
Museums
Leisure centres
Open Plan offices
Warehouses
Factories
Power stations
and more
Model
Part No.
Range
Number of Wires
Supply Voltage
Quiescent Current
Operating Temperature
Max Humidity
Max Wind Speed
Alarm Current
Fire Output
ZT-50RZ
47-050
5-50m
2
10.2V to 30V DC
<4mA
-30°C to 55°C
95% RH non-condensing
Not affected
35mA (typical)
ZT-100RZ
47-051
50-100m
Fault Output
Power Down Reset
Beam Misalignment Tolerance at 35%
Alarm Thresholds
Optical Wavelength
Construction
IP Rating
Size
Weight
Schottky diode introduced between –VE in &
-VE out
<2 seconds
Detector ± 0.8°
Prism ± 5.0°
2.50dB (25%), 3.74dB (35%), 6.02dB (50%)
880nm
Flame Retardant ABS (Grey /Black)
IP50
130 x 210 x 120mm
0.75kg
ZT-50RV
47-050A
5-50m
4
<15mA
ZT-100RV
47-051A
50-100m
Fault relay opening (relay contact is normally closed)
>5 seconds
0.7kg
23
24
Conventional Fire Alarm Systems /
Fyreye 50 & 100m Auto-aligning Beam Smoke
Detector Systems 50 & 100m
(ZT-5000R & ZT-5000R/100)
Based on the proven technology of the standard Fyreye reflective beam detectors, the
Fyreye auto-aligning beam detector has been designed to help improve ease of installation.
The system is ideally suited for the protection of large areas where the use of traditional detection technologies would prove to be too difficult and/or costly to install.
The system combines an infrared transmitter and receiver in the same discrete unit and operates by projecting a well-defined beam to a reflective prism, which returns the beam to the receiver for analysis.
Smoke in the beam path causes a drop in power, which, if below a pre-determined level, results in an alarm signal.
The system consists of 2 parts; the beam detector itself and a low level control unit.
The system can be fully customised, according to local conditions and installation guidelines; alarm thresholds
(sensitivity) and time to alarm/fault can be set from the low level system controller.
Each detector head is independently configurable from
8m through to 100m and has its own individual fire threshold. The system controller retains one set of fire and fault relays that is common to all detectors that are installed.
The system is supplied as either a 50 or 100 metre version with a single detector head. Additional heads and a long range kit (additional prisms to allow the detector head to reach 100m) are available separately.
Features
Worldwide approvals including EN54:12 and
UL268
Up to 4 detectors per system controller
Each detector configurable from 8m to 100m
Integral LASER
Auto-align fast automatic beam alignment
Auto-optimise building movement and contamination compensation
Low level system controller
20mm cable gland knockouts on system controller
2-wire interface from system controller to detector
Additional System Components
ZT-5000R/DH - 47-072 - Fyreye Auto-aligning Single
Beam Detector Head 50m
ZT-5000R/100/DH - 47-073 - Fyreye Auto-aligning
Single Beam Detector Head 100m
ZT-5000R/LRK - 47-074 - Fyreye Auto-aligning Beam
Detector Long Range Kit
135mm 135mm
202mm 81mm
Model
Part No.
Range
Number of Wires
Supply Voltage
Operating Current
Operating Temperature
Storage Temperature
Max Humidity
Max Wind Speed
Alarm Current
Fire Output
Fault Output
Beam Misalignment Tolerance @ 35%
Alarm Thresholds
Optical Wavelengths
Construction
IP Rating
Detector Size
Detector Weight
Controller Size
Controller Weight
ZT-5000R
47-070
50m
4
ZT-5000R/100
47-071
100m
14-28V DC
8-12mA (low current mode with 1 detector)
48-52mA (high current mode with 1-4 detectors)
-20°C to 55°C
-40°C to 85°C
85% RH non-condensing
Not affected
35mA (typical)
Volt free relay contact
Volt free relay contact
Detector ± 0.8°, Prism ± 5.0°
2.50dB (25%), 3.74dB (35%) & 6.02dB (50%)
850nm
Flame Retardant ABS (Grey / Black)
IP54
135 x 135 x 135mm
0.5kg
202 x 230 x 81mm
0.9kg
25
Conventional Fire Alarm Systems /
Zeta UV/IR Optical Flame Detectors
(VS-200P & VS-200EX)
VS-200P VS-200EX
The VS-200P & VS-200EX UV/IR flame detectors detect fuel & gas fires at long distances with the highest immunity to false alarms. The detectors can detect a 0.1m² gasoline pan fire at 30m in less than 5 seconds.
26
Typical
Applications
Non-hazardous (VS-200P)
Parking buildings
Warehouse
Waste disposal facilities
Culture centres
Hazardous (VS-200EX)
Offshore oil & gas installations
Onshore oil & gas installations and pipelines
Petrochemical plants
Chemical plants
Shipbuilding facility
Automotive industry
Storage tank farms
Power generation facility
Petrochemical plants
Painting industry
Warehouse
Waste disposal facility
Explosive & munitions
Features
UV/IR spectrum for medium distance detection and high false alarm immunity
Compact & lighter design
User selectable sensitivity & functions
Multiple output options (relays for alarm & fault,
0-20mA (stepped) and RS-485/RS-232 spectrum monitoring)
ATEX approved by DNV for explosion-proof (VS-
200EX UV/IR only)
CE certified
Model
Part No.
Spectrum Response
VS-200P
47-150
VS-200EX
47-151
Spectrum Response
(at highest sensitivity setting for 0.1m² pan fire)
UV /IR (Dual Bands)
Fuel n-Heptane
Gasoline
Diesel
LPG*
Distance
30m
30m
20m
20m
Fuel
Ethanol
IPA
Methanol
Distance
20m
25m
20m
Response Time
Adjustable Time Delay
Sensitivity Range
Field of View
Built-in-Test
Temperature Range
Humidity
Operating Voltage
Power Consumption
Cable Entry
Wiring
Relays
*0.5m high / 0.2m width plume fire
Typically 5 seconds
Up to 20 seconds
4 sensitivity ranges for 0.1m² n-Heptane pan fire from 15m to 65m
Horizontal 90°, Vertical 90°
Manual (optionally Automatic)
Operating/Storage: -40°C to 75°C
Up to 95% non-condensing
24VDC norminal (17-31VDC)
Standby: max. 35mA, Alarm: max. 75mA
1 x M20 (ISO)
AWG 16-26 (Str 1.5mm² to 0.13mm²)
Electromagnetic Compatibility EMI/RFI protected to EN61000 series
Electrical Interface The detector includes twelve(12) terminals with four(4) wiring options
Alarm, Fault. SPST volt-free contacts rated 5A at 30VDC or 250VAC
Non-isolated “Source” configuration
0-20mA (stepped)
Materials
Fault:
Normal:
Alarm:
0 +1mA
4mA±10%
20mA±10%
Polycarbonate Enclosure
Bit Fault:
Warning:
Resistance
Loop:
2mA±10%
16mA±10%
Max. 800Ω
Heavy duty copper free aluminium (less than 1%) with bright grey anodizing finish
Mounting (Tilt Mount) Stainless Steel
Enclosure options - Stainless Steel 316L with electro polish finish
Heavy duty copper free aluminium (less than 1%) with grey epoxy enamel finish
Options - Stainless Steel 316L with electro polish finish
Dimensions
Detector: 80 x 82 X 86 mm
Detector: 83(d) x 126(l) mm
Detector (aluminium): 1.1 kg (1.4 kg with Ex cable gland /
1m-length
Weight
Detector : 0.3kg (1.0kg with cable gland /
1m-length cable / Tilt
Mount)
Detector (St. SUS316L): 2.0 kg
Tilt mount (aluminium/ St.): 0.3kg / 0.7kg
Water and Dust IP66 per EN60529 IP66 and IP67 per EN60529
ATEX Ex II 2 G
EMI/RFI CE Marking
Performance
EN54-10 (designed to meet)
Exd IIC T6, -40°C to +75°C (DNV 09 ATEX 0000)
KFI (Korea)
EN54-10 (designed to meet)
27
Conventional Fire Alarm Systems /
Zeta Conventional Manual Call Points
(ZT-CP2, ZT-CP2/W, ZT-CP1 & ZT-CP1/W)
The Zeta conventional manual call point has a modern design and has been approved by
BSI to EN54 part 11. It is a resettable call point that signals an alarm with a yellow flag entering the window area and a red alarm LED.
There are two versions available; the ZT-CP2 call points comes complete with a protective Perspex cover as well as a “snaplatch” catch that needs to be broken off before the call point cover can be lifted (this acts as a deterrent to malicious activations and forms a Type B call point). Alternatively the ZT-CP1 is supplied without the Perspex cover & “snaplatch” and is single action or
Type A call point.
The recommended colour for these call points is red however white is also available to meet architectural requirements.
Features
BSI approved to EN54 part 11
Attractive design
28
Model
Part No.
Type
ZT-CP2
43-300
Type B
ZT-CP2/W
43-314
Element Type
Alarm Activation
Colour
Input Voltage
Quiescent Current
Alarm Current
Resettable
Break “snaplatch”, lift Perspex cover, press element
Red
9-33V DC
White
0mA
Typical 35mA (maximum 51mA)
Alarm Load 470 Ω resistor
Operating Temperature -20°C to 50°C
Max Humidity
IP Rating
Size
Weight
95% RH non-condensing
IP43
111 x 100 x 67mm
198g
ZT-CP1
43-301
Type A
Press element
Red
105 x 100 x 58mm
175g
ZT-CP1/W
43-317
White
Conventional Fire Alarm Systems /
Zeta Conventional Weatherproof Call Point
(ZT-CP2/WP)
The Zeta conventional weatherproof manual call point is an IP65 rated call point which complies with EN54 part 11. It is resettable and signals an alarm with a yellow flag entering the window area and a red alarm LED.
The call point comes complete with a protective Perspex cover as well as a “snaplatch” catch that needs to be broken off before the call point cover can be lifted (this acts as a deterrent to malicious activations and forms a
Type B call point).
Features
Complies with EN54 part 11
Attractive design
Resettable element
Protective cover
Model
Part No.
Type
Element Type
Alarm Activation
Colour
Input Voltage
Quiescent Current
Alarm Current
Alarm Load
Operating Temperature
Max Humidity
IP Rating
Size
Weight
ZT-CP2/WP
43-350
Type B
Resettable
Break “snaplatch”, lift Perspex cover, press element
Red
9-33V DC
0mA
Typical 35mA (maximum 51mA)
470 Ω resistor
-20°C to 50°C
95% RH non-condensing
IP65
87 x 87 x 70mm
198g
29
30
Conventional Fire Alarm Systems /
Zeta Conventional Explosion Proof
Manual Call Point
(ZT-BGU/WP/R & ZT-BGU/WP)
The Zeta conventional explosion proof manual call point is manufactured from aluminium with a built-in push button activator. The call point is finished with red anti-corrosive epoxy powder coating with 2 x 20mm cable entries.
This unit is equipped with a stainless steel hammer and chain.
Two models are available; the ZT-BGU/WP/R with 470Ω built-in resistor for connection to a standard fire alarm system or the ZTBGU/WP for mains connection.
4 Holes - ø7
185mm
IN
CASE OF
B
R
E A
F I R E
K G L A
S
S
105mm
Hammer
Chain
Model
Part No.
Contact Rating
Voltage Rating
Build-in Resistor
IP Rating
Earthling
Size
Weight
ZT-BGU/WP/R
43-300/WP
10 Amp
ZT-BGU/WP
43-305/WP
500V AV
470Ω N/A
IP65
2No M6 eternal & 1No M5 internal
TBC
1.5kg
2 Nos.0.75″ET
Conventional Fire Alarm Systems /
Miditone Conventional Electronic Sounder
(ZMDD/8R & ZMDD/8W)
Model
Part No.
Sound Output
Colour
Operating Voltage
Quiescent Current
Alarm Current @ 24V
Operating Temperature
Minimum Continuous Temperature
Maximum Humidity
IP Rating
Size (with Back Box)
Weight (with Back Box)
ZMDD/8R
42-040
See current consumption table
Red
9-30V DC
0mA
See current consumption table
-10°C to 50°C
0°C
95% RH Non Condensing
IP43
85 x 85 x 35mm (85 x 85 x 67mm)
100g (150g)
Off
On
Off
On
DIL Switch Settings (SW4 N/A)
1 2 3
Off
On
Off
On
Off
Off
On
On
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
Tone Description
Sweep Negative 1200- 500 Hz In 1 Second
Alternating 554 and 440Hz 0.5s Each
Continuous 660Hz
Alternating 554Hz @ 0.1s/440Hz @ 0.4s
Intermittent 970Hz @ 0.5s On/Off
Continuous 970Hz
Sweep Positive 800-970Hz
Alternating 800 and 970Hz @ 0.25s Each
The Miditone sounder is a small, high output conventional sounder which designed to meet the requirements of EN54 part 3 and is CE marked.
The sounder is a compact unit that fits a standard
European back box and can be either surface or flush mounted. It has a choice of 8 tone patterns, selectable by an internal dip switch and a sound output of 95dB @
1m with volume control.
It is available in red or white to meet architectural requirements.
Features
Complies to EN54 part 3
95dB @ 1m sound output
8 Tone patterns
Flush or surface fixing
ZMDD/8W
42-040A
White dB Level
97 (+/- 2dB)
95 (+/- 2dB)
96 (+/- 2dB)
94 (+/- 2dB)
93 (+/- 2dB)
95 (+/- 2dB)
99 (+/- 2dB)
100 (+/- 2dB)
Current (mA)
21
17
22
17
8-24
25.5
25
25
31
32
Conventional Fire Alarm Systems /
Miditone Conventional Combined Electronic
Sounder & Flasher
(ZMDF/8R, ZMDF/8A, ZMDF/8B, ZMDF/8C & ZMDF/8G)
The Miditone combined sounder & flasher is a small, high output conventional sounder & flasher which is designed to meet the requirements of EN54 part 3 and is CE marked.
The device is a compact unit that fits a standard
European back box and can be either surface or flush mounted. It has a choice of 8 tone patterns, selectable by an internal dip switch and a sound output of 95dB
@ 1m with volume control. This is an ideal solution to upgrade an existing sounder to a combined sounder & flasher.
It is available with either a red, amber, blue, clear or green lens to meet architectural requirements.
Features
Complies to EN54 part 3
95dB @ 1m sound output
8 tone patterns
Flush or surface fixing
Model
Part No.
Sound Output
Lens Colour
Operating Voltage
Quiescent Current
Alarm Current @ 24V
Operating Temperature
Minimum Continuous Temperature
Maximum Humidity
IP Rating
Size (with Back Box)
Weight (with Back Box)
ZMDF/8R ZMDF/8A
42-024 42-024A
See current consumption table
Red Amber
ZMDF/8B
42-024B
Blue
17-30V DC
0mA
See current consumption table
-10°C to 50°C
0°C
95% RH non condensing
IP43
85 x 85 x 35mm (85 x 85 x 67mm)
112g (162g)
Off
On
Off
On
DIL Switch Settings (SW4 N/A)
1 2 3
Off
On
Off
Off
Off
Off
Off
On
On
On
Off
Off
On
On
Off
Off
On
On
On
On
Tone Description
Sweep Negative 1200- 500 Hz In 1 Second
Alternating 554 and 440Hz 0.5s Each
Continuous 660Hz
Alternating 554Hz @ 0.1s/440Hz @ 0.4s
Intermittent 970Hz @ 0.5s On/Off
Continuous 970Hz
Sweep Positive 800-970Hz
Alternating 800 and 970Hz @ 0.25s Each
ZMDF/8C
42-02C
Clear dB LEVEL
102 (+/- 2dB)
100 (+/- 2dB)
100 (+/- 2dB)
98 (+/- 2dB)
93 (+/- 2dB)
103 (+/- 2dB)
103 (+/- 2dB)
103 (+/- 2dB)
ZMDF/8G
42-024G
Green
CURRENT (mA)
35
27
33
26
13 - 35
37
45
42
Conventional Fire Alarm Systems /
Securetone Conventional Electronic Sounder
(ZST/8R & ZST/8W)
85mm
The Securetone sounder is designed to be aesthetically pleasing and unobtrusive. It has an elegant round design and fits to its supplied mounting plate with a bayonet action to avoid unsightly screws.
It has 8 selectable tones with a volume adjust screw to set the required sound level.
This product is designed to meet the requirements of
EN54 part 3 and is CE marked.
Features
8 selectable tones
Volume control
Model
Part No.
Sound Output
Colour
Operating Voltage
Quiescent Current
Alarm Current @ 24V
Operating Temperature
Minimum Continuous Temperature
Maximum Humidity
IP Rating
Size (including Plate)
Weight (including Plate)
ZST/8R
42-004
100dBA @ 1 metre
Red
10-30V DC
0mA
35mA MAX
-0°C to 50°C
0°C
95% RH Non Condensing
IP43
100 x 100 x 75mm (100 x 100 x 85mm)
230g (260g)
ZST/8W
42-004A
White
33
Conventional Fire Alarm Systems /
Secure Light Xenon Flasher
(ZTSL6/R & ZTSL6/A)
The Secure Light Xenon Flasher range is designed to provide a visual warning at alarm condition.
Both red and amber versions are available with the lenses constructed of high-Impact and heat resistant
ACRYREX. The case is made of high-impact resistant ABS plastic.
97mm
Features
Available in Red & Amber
Fits onto a standard outlet box
34
Model
Part No.
Colour
Flash Energy
Flash Frequency
Operating Voltage
Quiescent Current
Alarm Current @ 24V
Operating Temperature
Minimum Continuous Temperature
Maximum Humidity
IP Rating
Size
Weight (including Plate)
ZST/8R
42-035
Red
3 Watt
60 times per minute
20-30V DC
0mA
100mA MAX
-30°C to 60°C
0°C
95% RH Non Condensing
IP54
97 x 100mm
231g
ZST/8W
42-038
Amber
Conventional Fire Alarm Systems /
Maxitone Conventional Sounder and
Combined Sounder & Flasher
(ZMT/8R, ZMT/8W & ZMTF/8R)
The Maxitone sounder is an ideal alternative to fire bells and for external use. It is housed in an attractive horn comprises of flame retardant ABS. Eight selectable tones and volume control are featured to meet most requirements.
The Maxitone is also available with transparent polycarbonate front which will provide both visual and audible alarm.
120mm
Features
High output
8 selectable tones
Volume control
126mm
107mm
Model
Part No.
Sound Output
Colour
ZMT/8R
42-001
ZMT/8W
42-001A
ZMTF/8R
42-032
See current consumption table
Red White Red
Operating Voltage 17-30V DC
Quiescent Current 0mA
Alarm Current @
24V
Operating
Temperature
See current consumption table
-20°C to 60°C
Minimum
Continuous
Temperature
0°C
Maximum Humidity 95% RH non condensing
IP Rating IP65
Size
Weight
124 x 130 x 100mm
357g
DIL SWITCH SETTINGS (SW4 N/A)
1 2 3 Tone Description
Off On Off Continuous 660Hz
On On Off Alternating 554Hz @
Off Off On
Intermittent 970Hz @
0.5s On/Off
On Off On Continuous 970Hz
Off On
On On
On
On
Sweep Positive 800-
970Hz
Alternating 800 and
970Hz @ 0.25s Each
101 (+/-
2dB)
98 (+/-
2dB)
101 (+/-
2dB)
98 (+/-
2dB)
98 (+/-
2dB)
103 (+/-
2dB)
103 (+/-
2dB)
102 (+/-
2dB)
27
20
27
19
20
29.3
38
35
35
Conventional Fire Alarm Systems /
Zeta Conventional Fire Alarm Bells
(ZTB6B, ZTB8B/230, ZTB8B & ZTB8B/WP)
ZTB6B
ZTB8B
36
152mm
203mm
55mm
55mm
The Zeta motorised fire alarm bells combine styling and functional efficiency. They incorporate a low power rotary centrifugal mechanism, which gives a high sound output with low current consumption at 24V dc.
The bells are available in 2 sizes; 6″ (152mm) and 8″
(203mm). These sizes suit a wide variety of installations.
There is a 230V ac version of the 6″ bell, and a 24V dc
Weatherproof version of the 8″ bell.
Features
Low current
Universally accepted fire evacuation signal
Model
Part No.
Supply Voltage
Diameter
Quiescent Current
Nominal Output @ 1M
Dimensions
Weight
ZTB6B
41-003
18-30V dc
6″ (152mm)
25mA
95dB(A)
152 x 152 x 55mm
860g
ZTB8B/230
41-004
200-250V AC
960g
ZTB8B
41-005
18-30V dc
8″ (203mm)
28mA
97dB(A)
203 x 203 x 55mm
1700g
ZTB8B/WP
41-006
1800g
Conventional Fire Alarm Systems /
Zeta Flame Proof Siren
(ZTSR/EXD24 & ZTSR/EXD230)
170mm 240mm
The Zeta flame proof siren is an explosion proof siren available in either 24V or 230V versions.
An intrinsically safe circuit is housed in the main chamber and it is duly wired up to terminal chamber through sealed bushes. The horn unit is placed on the main chamber cover and the output signals are taken through sealed coils. Neoprene ‘0’ rings are provided for the weather proof protection.
Model
Part No.
ZTSR/EXD24
42-100/24
Type Of Protection Flame proof – Exd T6 IP 65
Area Classification Zone 1 & 2
Group I, II A, II B, II C
ZTSR EXD230
42-105/230
Gas Groups
Apparatus
Standard
IS - 2148
CMRI Certificate
Approvals
Materials
Weight
CMRI / TC / S / H388
CCE, DGFAS
Cast Aluminium LM 6
5 Kg (approx.)
Size
IP Protection
Finish
Cable Entry
Gasket
Hardware
170 (w) x 390 (h) x 240 (d) mm
IP 65 to IS 13947 / 93
Anti corrosive Epoxy – Powder Coated
2 x ¾″ ET
Neoprene
Terminals
Voltage
Output Current
Power Rating
Sound Output
Earthing
Stainless Steel
4 x 2.5 sq. mm (standard) 6 x 2.5 sq. mm (for looping)
24 V DC 230 V AC – 50 Hz
600mA Peak. Galvanically Isolated
18 Watts
106 db 900 Hz On & Off alternatively at 1C/s
External: 2 Nos.
- M6
Internal: 1 No. -
M5
37
38
Conventional Fire Alarm Systems /
Zeta Flame Proof Gong Bell
(ZTB8B/EXD/24)
225mm 160mm
The Zeta flame proof gong bell is an explosion proof gong bell with a terminal chamber.
A highly reliable electric circuit is housed inside to control the frequency of the gong operating spindle.
The operating spindle and dish are made out of stainless steel thereby ensuring a long life.
The electric circuits are connected to terminals in the terminal chamber through nipple. The covers are provided with neoprene gaskets for weatherproof protection.
Model
Part No.
Type Of Protection
Area Classification
Apparatus Standard
Material
Weight
Size
IP Protection
Finish
Cable Entry
Gasket
Hardware
Voltage
Power Rating
Sound Output
Terminals
Earthing
ZTB8B/EXD
41-075
Flame proof – Exd T6 IP 65
Zone 1 & 2
IS - 2148
Cast Aluminium LM 6
3 Kg (approx.)
225(w) x 285(h) x 160(d) mm
IP 65 to IS 13947 / 93
Anti Corrosive Epoxy –
Powder coated
1 X 3/4″ ET
Neoprene
Stainless steel
24V DC or 110V / 230V AC –
50 Hz
12 Watt
112db
4 x 4 mm²
External: 2 Nos – M6 Internal:
1 No. - M5
Conventional Fire Alarm Systems /
Zeta Magnetic Door Holders
(ZT-DR24 & ZT-DR240)
ZT-BR
Model
Part No.
Rated Voltage
Rated Current
Switch Through Aux
Needs Back EMF Diode
Holding Force
Size (Main Unit)
Dimensions (Keeper Plate)
Weight (Main Unit)
Weight (Keeper Plate)
ZT-DR24
50-001
24V DC
65mA
Yes
Yes
400 N
110 x 85 x 38mm
55 x 55 x 50mm
404g
153g
The Zeta magnetic door holders are designed to retain a fire door open against the force of its own closing device. In the event of a fire, the door holder magnet can be turned off by the fire alarm, allowing the door to shut.
The manual release button is changeable from the base side to left or right. Cable entry is possible from rear side by means of enclosed exits from the base side, left or right.
An optional bracket is also available for floor or wall mounting (ZT-BR).
Features
Tested according to EN1155
ZT-DR240
50-002
230V AC
6mA
No
No
39
40
Conventional Fire Alarm Systems /
Zeta Duct Unit
(ZT-DU, ZT-DU/12 & ZT-DU/230)
Duct Wall
Direction of Airflow
Model
Part No.
Supply Voltage
Stand by current
Alarm current
Fault current
Indications
Outputs
Size
Weight
Test Point
ZT-DU
48-011A
N/A
N/A
N/A
N/A
N/A
N/A
190 x 227 x 70mm
728g
The Zeta duct unit allows air in a ventilation duct to be monitored for smoke via a smoke detector mounted externally in a sealed chamber. The unit comes supplied with 2 sampling probes (one in & one out) which are mounted through the duct in the centre of the air flow.
There are 3 versions of the unit available which are as follows;
ZT-DU
– enclosure supplied with a Fyreye common base
(FE-CB) allowing either a conventional or addressable
Fyreye detector to be connected and wired as part a system.
ZT-DU/12
– enclosure c/w Fyeye base and relay board with form C relay outputs for alarm and for fault which requires 12V power supply.
ZT-DU/230
- enclosure c/w Fyeye base and relay board with form C relay outputs for alarm and for fault which requires 230V power supply.
Please note for reliable smoke detection the air speed in the duct must be at least 2.5m/s.
Features
Fire and Fault relays
Option for latching or non-latching
Manual reset (latching option)
ZT-DU/12
48-011B
12V
46mA (From 12v supply)
86mA (From 12v supply)
26mA (From 12v supply)
Power, fault & alarm
1 x fault relay & 1 x alarm relay
ZT-DU/230
48-011C
230V
989g
Conventional Fire Alarm Systems /
Premier Power Pack EN 54-4 Power Supply with LCD Screen
(PP-2/12, PP-5/17)
Screen Information
System Normal Screen
Z E T A A L A R M S Y S T E M S
P R E M I E R P O W E R - P A C K
R A T I N G 3 0 V D C 2 . 0 A
S Y S T E M N O R M A L
Screen 1 - Main Information
M A I N S : O K B A T T S : O K
V ( A ) = 2 9 . 5 V ( B ) = 2 9 . 5
C U R R E N T 0 . 1 2 A M P S
Screen 2 - Battery Info
B A T T E R Y I M P : 0 . 0 0 3 7
C H A R G E R V O L T : 2 5 . 4 5 V
C H A R G E T Y P E : B O O S T
B A T T E R Y S T A T E : G O O D
Screen 3 - Misc.
E A R T H : 2 . 4 4 7 V G O O D
C H A R G E R C I R C U I T : O K
B A D B A T T E R Y L V L X . X R
Screen 4 - Software Information
S o f t w a r e P S U : 2 V 0 0
S o f t w a r e L C D : 2 V 0 0
The Premier Power Pack Power supply uses an innovative design that allows the engineer to view system status through the on board LCD screen. The screen can display several power supply parameters, including output voltage, and output current.
The power supply itself uses a 3 state charger which uses BOOST, FLOAT, and PULSE modes, depending on the state of the battery.
The PSU will disconnect the batteries under mains fail condition, when the batteries are fully discharged to prevent damage to the batteries.
The PSU will also monitor the battery for high internal resistance, and signal a fault if that condition is detected.
Model
Part No.
Input Voltage
Output Voltage
Power Rating
PP-2/12
46-300
PP-5/17
46-305
170-264V AC 47-63 Hz
28V DC Nominal
75W
79%
28V DC Nominal
150W
86% Efficiency
Total Power
Output
Power Supply
Outputs
Maximum Current
Per Output
2.0 Amp
2 Fused Outputs
0.625mA
5.0 Amp
2 Fused Outputs
2.0 Amps
Battery Charging
Current
Fault Relay Rating SELV 1A
IP Rating IP30
Size
750mA 920mA
SELV 1A
IP30
375 x 335 x 128mm 375 x 403 x 128mm
41
42
Conventional Fire Alarm Systems /
Batteries
(Z20201, Z20301, Z20651, Z21251 & Z21751)
As fire alarm systems are life safety systems, they must have a battery backup to ensure full functionality is maintained in the event of a mains failure. All parts of the system (including auxiliary power supplies) must have a battery backup.
All the batteries stocked are 12V meaning that 2 batteries are required for a 24V systems. The standard capacities available are 2.2Ah, 3.2Ah, 7Ah, 12Ah and
17Ah.
It is important to choose the correct battery size for the system load to give the required standby time (usually
24 or 48 hours).
Battery Calculation
To calculate the required battery backup, we use the equation:-
Battery Size (Standby time in Amp Hours) = 1.25 x [(T
ALM
x I
ALM
) + (T
SBY
x I
SBY
)]
Where:
T
ALM
= Maximum time in hours required for the alarm [½ hour is most common time]
I
ALM
= Total Alarm Current in amps for all alarm devices connected to the alarm circuits
T
SBY
hr]
= Standby time in hours for the system after mains failure [normally 24, 48 or 72
I
SBY
= Quiescent current in amps of control panel in fault condition [because of mains failure] PLUS all loop devices
Model
Part No.
Type
Voltage
Capacity
Size
Weight
Z20201
46-002
Sealed lead acid
12V DC
2.2 Ah
178 x 34 x 65mm
1.0kg
Z20301
46-100
3.2 Ah
132 x 59 x 65mm
1.25kg
Z20651
46-003
7.2 Ah
151 x 65 x 98mm
2.5kg
Z21251
46-105
Z21751
46-004
12 Ah 17 Ah
150 x 98 x 103mm 178 x 75 x 168mm
3.5kg
5.8kg
Available now from:
Tel: +44 (0) 1792 455 175
Fax: +44 (0) 1792 455 176
E-mail: [email protected]
Web: www.zetaalarmsystems.com
Detection House
72-78 Morfa Road
Swansea
SA1 2EN
United Kingdom