Installation Instructions: CompactLogix Isolated Analog Input Module


Add to my manuals
24 Pages

advertisement

Installation Instructions: CompactLogix Isolated Analog Input Module | Manualzz

Installation Instructions

CompactLogix Isolated Analog

Input Module

Catalog Number 1769-IF4I

Topic

Important User Information

North American Hazardous Location Approval

Module Description

Prevent Electrostatic Discharge

System Assembly

Mounting Expansion I/O

Replacing a Single Module within a System

Replacement Part

System Wiring Guidelines

I/O Memory Mapping

Specifications

Additional Resources

7

9

6

6

3

5

Page

2

10

10

14

18

23

2 CompactLogix Isolated Analog Input Module

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment.

Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication

SGI-1.1

available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ ) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell

Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 3

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations.

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous

Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

Informations sur l’utilisation de cet équipement en environnements dangereux.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2

Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

WARNING:

Explosion Hazard -

• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

• Substitution of components may impair suitability for Class I, Division 2.

• If this product contains batteries, they must only be changed in an area known to be nonhazardous.

AVERTISSEMENT:

Risque d’Explosion –

• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.

• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet

équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.

• S'assurer que l'environnement est classé non dangereux avant de changer les piles.

Publication 1769-IN074C-EN-P - March 2011

4 CompactLogix Isolated Analog Input Module

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is considered Group 1, Class A industrial equipment according to

IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.

This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

Besides this publication, see:

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

, for additional installation requirements, .

NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 5

Module Description

8a

1

2a

7a

7a

OK

Analog

3

OK

Analog

10a

10

10b

DANGER

Do Not Remove RTB Under Power

Unless Area is Non-Hazardous

Ch0+

N/C

Ch0_iRtn

N/C

Ch0-

Ch1+

N/C

Ch1_iRtn

Ch2+

Ch1-

Ch2_iRtn

N/C

Ch2-

Ch3+

N/C

Ch3_iRtn

N/C

Ch3-

Ensure Adjacent

Bus Lever is Unlatched/Latched

Before/After

Removing/Inserting Module

1769-IF4I

4

5a

9

6

2b 7b

7b

8b

Item Description

1

2a

Bus lever (with locking function)

Upper panel mounting tab

2b

3

Lower panel mounting tab

Module status indicator

4

5a

5b

6

Item Description

7a

7b

8a

8b

Upper tongue-and-groove slots

Lower tongue-and-groove slots

Upper DIN rail latch

Lower DIN rail latch

Module door with terminal identification label

9

Write-on label (user ID tag)

Movable bus connector with female pins

10

Removable terminal block (RTB) with finger-safe cover

Stationary bus connector with male pins

10a

RTB upper retaining screw

Nameplate label

10b

RTB lower retaining screw

5b

Publication 1769-IN074C-EN-P - March 2011

6 CompactLogix Isolated Analog Input Module

Prevent Electrostatic Discharge

ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

Touch a grounded object to discharge potential static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component boards.

Do not touch circuit components inside the equipment.

Use a static-safe workstation, if available.

Store the equipment in appropriate static-safe packaging when not in use.

Remove Power

WARNING: When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.

System Assembly

The module can be attached to the controller or an adjacent I/O module before or after

mounting. For mounting instructions, see Panel Mounting on page 8

, or DIN Rail Mounting on page 9 . To work with a system that is already mounted, see Replacing a Single Module within a

System on page 9

.

The following procedure shows you how to assemble the Compact I/O system.

4

3

2

1

6

5 30536-M

1

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 7

1.

Disconnect power.

2.

Check that the bus lever of the module to be installed is in the unlocked (fully right) position.

3.

Use the upper and lower tongue-and-groove slots (1) to secure the modules together (or to a controller).

4.

Move the module back along the tongue-and-groove slots until the bus connectors (2) line up with each other.

5.

Push the bus lever back slightly to clear the positioning tab (3).

Use your fingers or a small screwdriver.

6.

To allow communication between the controller and module, move the bus lever fully to the left (4) until it clicks.

Be sure it is locked firmly in place.

ATTENTION: When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical connection.

7.

Attach an end cap terminator (5) to the last module in the system by using the tongue-and-groove slots as before.

8.

Lock the end cap bus terminator (6).

IMPORTANT

A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the communication bus.

Mounting Expansion I/O

ATTENTION: During panel or DIN rail mounting of all devices, be sure that all debris (such as metal chips or wire strands) is kept from falling into the module.

Debris that falls into the module could cause damage on power up.

ATTENTION: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.

Publication 1769-IN074C-EN-P - March 2011

8 CompactLogix Isolated Analog Input Module

Grounding the Module

ATTENTION: This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the power supply's mounting tabs or DIN rail (if used) are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding

Guidelines, Rockwell Automation publication 1770-4.1

, for additional information.

Minimum Spacing

Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown.

Panel Mounting

Mount the module to a panel by using two screws per module. Use M4 or #8 panhead screws.

Mounting screws are required on every module.

Panel Mounting Using the Dimensional Template

Spacing for single-wide modules 35 mm (1.378 in.).

l Mounting

Refer to host controller documentation for this dimension.

NOTE: Overall hole spacing tolerance: ±0.4 mm (0.016 in.).

Locate holes every 17.5 mm (0.689 in.) to allow for a mix of single-wide and one-and-a-half-wide modules

(for example, the 1769-OA16 module).

Panel Mounting Procedure Using Modules as a Template

The following procedure allows you to use the assembled modules as a template for drilling holes in the panel. If you have sophisticated panel mounting equipment, you can use the dimensional template provided on page 8 . Due to module mounting hole tolerance, it is important to follow this procedure.

1.

On a clean work surface, assemble no more than three modules.

2.

Using the assembled modules as a template, carefully mark the center of all module-mounting holes on the panel.

3.

Return the assembled modules to the clean work surface, including any previously mounted modules.

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 9

4.

Drill and tap the mounting holes for the recommended M4 or #8 screw.

5.

Place the modules back on the panel and check for proper hole alignment.

6.

Attach the modules to the panel using the mounting screws.

TIP

If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group.

7.

Repeat steps 1 … 6 for any remaining modules.

DIN Rail Mounting

The module can be mounted using the following DIN rails:

35 x 7.5 mm (1.38 x 0.30 in.; EN 50 022 - 35 x 7.5)

35 x 15 mm (1.38 x 0.59 in.; EN 50 022 - 35 x 15)

Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place.

Replacing a Single Module within a System

The module can be replaced while the system is mounted to a panel (or DIN rail). Follow these steps.

1.

Remove power.

See important note on page 6 .

2.

On the module to be removed, remove the upper and lower mounting screws from the module (or open the DIN latches by using a flat-blade or phillips-style screwdriver).

3.

Move the bus lever to the right to disconnect (unlock) the bus.

4.

On the right-side adjacent module, move its bus lever to the right (unlock) to disconnect it from the module to be removed.

5.

Gently slide the disconnected module forward.

If you feel excessive resistance, check that the module has been disconnected from the bus and that both mounting screws have been removed (or DIN latches opened).

TIP

It may be necessary to rock the module slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.

6.

Before installing the replacement module, be sure that the bus lever on the module to be installed and on the right-side adjacent module are in the unlocked (fully right) position.

Publication 1769-IN074C-EN-P - March 2011

10 CompactLogix Isolated Analog Input Module

7.

Slide the replacement module into the open slot.

8.

Connect the modules together by locking (fully left) the bus levers on the replacement module and the right-side adjacent module.

9.

Replace the mounting screws (or snap the module onto the DIN rail).

Replacement Part

Terminal block, catalog number 1769-RTBN18 (one per kit).

System Wiring Guidelines

ATTENTION: Use supply wires suitable for 20 °C (68 °F) above surrounding ambient.

Consider the following when wiring your system:

Do not use the analog module’s NC terminals as connection points.

Channels are isolated from each other.

Use Belden 8761, or equivalent, shielded wire.

Under normal conditions, the drain wire and shield junction must be connected to earth ground via a panel or DIN rail mounting screw at the analog I/O module end. Keep the shield connection to ground as short as possible.

(1)

To ensure optimum accuracy, limit overall cable impedance by keeping your cable as short as possible. Locate the I/O system as close to your sensors or actuators as your application will permit.

If multiple power supplies are used with analog inputs, the power supply commons must be connected.

The 1769-IF4I module does not provide loop power for analog inputs. Use a power supply that matches the input transmitter specifications.

Differential analog inputs are more immune to noise than single-ended analog inputs.

(1) In environments where high-frequency noise may be present, it may be necessary to directly ground cable shields to earth at the module end and via a 0.1µF capacitor at the sensor end.

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 11

Voltages on Ch+, Ch-, and Ch_iRtn for a single, isolated channel of the 1769-IF4I module must not exceed the maximum overload levels detailed in the

Input Specifications on page 21 .

ATTENTION: To comply with UL restrictions, this equipment must be powered from a source compliant with Class 2 or Limited Voltage/Current.

Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up. Once wiring is complete, make sure that the module is free of all metal fragments.

Wiring Differential Inputs

Belden 8761 Cable

(or Equivalent)

Analog Source

IMPORTANT

1769-IF4I input channels connected to current sources must have a jumper wire placed between Ch#_iRtn and the Ch#- terminals for that channel.

Publication 1769-IN074C-EN-P - March 2011

12 CompactLogix Isolated Analog Input Module

Wiring Single-ended Sensor/Transmitter Types

Sensor/

Transmitter

Supply

+

-

Current

Transmitter

+

Signal

Voltage Transmitter

+

Ground

Signal

Voltage Transmitter

+

Ground

Signal

Wiring Mixed Transmitter Types

Sensor/

Transmitter

Supply

+

-

Current

Transmitter

+

Signal

Voltage Transmitter

+

Ground

Signal

+

Voltage Transmitter

Ground

Signal

1769-IF4I Terminal Block

Ch0+

N/C

Ch0_iRtn

N/C

Ch0-

Ch1+

N/C

Ch1_iRtn

N/C

Ch1-

Ch2+

N/C

Ch2_iRtn

N/C

Ch2-

Ch3+

N/C

Ch3_iRtn

N/C

Ch3-

Differential

Voltage

Transmitter

+

+

Signal

_

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 13

Labeling the Terminals

A removable, write-on label is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door.

Your markings (ID tag) will be visible when the module door is closed.

Upper Retaining Screw

Wiring the finger-safe terminal block

Lower Retaining Screw

Removing the Finger-safe Terminal Block

WARNING: When you connect or disconnect the removable terminal block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

When wiring field devices to the module, it is not necessary to remove the terminal block. If you remove the terminal block, use the write-on label on the side of the terminal block to identify the module slot location and type. RTB position can be indicated by circling either the ‘R’ for right side or ‘L’ for left side.

To remove the terminal block, loosen the upper and lower retaining screws. The terminal block will back away from the module as you remove the screws. When replacing the terminal block, torque the retaining screws to 0.46 N•m (4.1 lb•in).

Wiring the Finger-safe Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.

1.

Loosen the terminal screws to be wired.

2.

Route the wire under the terminal pressure plate.

Publication 1769-IN074C-EN-P - March 2011

14 CompactLogix Isolated Analog Input Module

You can use the bare wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.

TIP

The terminal screws are non-captive. Therefore, it is possible to use a ring lug

[maximum 1/4 inch o.d. with a 0.139 in. minimum i.d. (M3.5)] with the module.

3.

Tighten the terminal screw, making sure the pressure plate secures the wire.

Recommended torque when tightening terminal screws is 0.68 N•m (6 lb•in).

TIP

If you need to remove the finger-safe cover, insert a screwdriver into one of the square wiring holes and gently pry off the cover. If you wire the terminal block with the finger-safe cover removed, you will not be able to put the cover back on the terminal block because the wires will obstruct the cover.

Wire Size and Terminal Screw Torque

Each terminal accepts one or two wires with the following restrictions.

Solid

Stranded

Wire Type

Cu-90 °C (194°F)

Cu-90 °C (194°F)

Wire Size

#14…#22 AWG

#16…#22 AWG

Terminal Screw

Torque

0.68 N•m

(6 lb•in)

0.68 N•m

(6 lb•in)

Retaining Screw

Torque

0.46 N•m

(4.1 lb•in)

0.46 N•m

(4.1 lb•in)

I/O Memory Mapping

Input Data File

For each input module, slot x, words 0-3 in the input data file contain the analog values of the inputs.

0

Bit Position

15 14 13 12 11 10 9

SGN

8 7 6 5 4

Analog Input Data Channel 0

1 SGN

2 SGN

Analog Input Data Channel 1

Analog Input Data Channel 2

3 SGN

4 Nu

5 Nu

6 L3

Nu

H3

Nu

U3

Nu

O3

Nu

L2

Nu

H2

Analog Input Data Channel 3

Nu

U2

Time Stamp Value

Nu

O2

Nu

L1

Nu

H1

Nu

U1

Nu

O1

3

S3

L0

2

S2

H0

1

S1

U0

0

S0

O0

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 15

The bits are defined as follows:

SGN = Sign bit in two’s complement format

Nu = Not used. Bit set to 0

Sx = General status bit for input channels 0…3

Lx = Low alarm flag bits for input channels 0…3

Hx = High alarm flag bits for input channels 0…3

Ux = Under-range flag bits for channels 0…3

When set, the input signal is under normal range or an open circuit condition exists, in the case of the 4…20 mA range.

Ox = Over-range flag bits for channels 0…3

When set, the input signal is over normal range or an open circuit condition exists (open circuit detection applies to voltage input ranges only).

Output Data File

For each input module, slot x, word 0 in the output data file contains the analog values of the outputs.

Bit Position

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 Nu Nu Nu Nu Nu Nu Nu Nu UL3 UH3 UL2 UH2 UL1 UH1 UL0 UH0

The bits are defined as follows:

Nu = Not used. Bit set to 0

UHx = Cancel High Process Alarm Latch x

Allows each high process alarm latch to be individually cancelled. Cancel = 1.

ULx = Cancel Low Process Alarm Latch x

Allows each low process alarm latch to be individually cancelled. Cancel = 1.

Publication 1769-IN074C-EN-P - March 2011

16 CompactLogix Isolated Analog Input Module

Configuration Data File

The manipulation of the bits from this file is normally done with programming software (for example, RSLogix 5000 or RSNetWorx for DeviceNet software) during initial configuration of the system. In that case, graphical screens are provided by the programmer to simplify configuration. However, some systems, like the 1769-ADN DeviceNet adapter, also allow the bits to be altered as part of the control program, using communication rungs. In that case, it is necessary to understand the bit arrangement.

Configuration Data Array

Bit Position

15 14 13 12 11 10 9 8 7 6

0 Real Time Sample Value

1 ETS Reserved

2 EC

3 Reserved

4

5

S

S

Reserved EA AL EI Reserved

Inpt Dta Fm

Chl0

Reserved

Process Alarm High Data Value Channel 0

Process Alarm Low Data Value Channel 0

6 S

7 Reserved

Alarm Dead Band Value Channel 0

8 EC

9 Reserved

Reserved EA AL

Inpt Dta Fm

Chl1

EI Reserved

Reserved

10 S

11 S

Process Alarm High Data Value Channel 1

Process Alarm Low Data Value Channel 1

12 S

13 Reserved

Alarm Dead Band Value Channel 1

14 EC

15 Reserved

16

17

S

S

Reserved EA AL EI Reserved

Inpt Dta Fm

Chl2

Reserved

Process Alarm High Data Value Channel 2

Process Alarm Low Data Value Channel 2

18 S

19 Reserved

Alarm Dead Band Value Channel 2

20 EC

21 Reserved

Reserved EA AL

Inpt Dta Fm

Chl3

EI Reserved

Reserved

22 S

23 S

Process Alarm High Data Value Channel 3

Process Alarm Low Data Value Channel 3

5 4 3 2 1 0

Input Filter Sel Chl0

Inpt Tp/RngeSel Chl0

Inpt Filter Sel Chl1

Inpt Tp/RngeSel Chl1

Input Filter Sel Chl2

Inpt Tp/RngeSel Chl2

Input Filter Sel Chl3

Inpt Tp/RngeSel Chl3

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 17

Configuration Data Array (cont.)

Bit Position

15 14 13 12 11 10 9

24 S

25 Reserved

Alarm Dead Band Value Channel 3

8 7 6 5 4 3 2 1 0

The bits are defined as follows:

EC = Enable Channel

Inpt Dta Fm Chlx = Input Data Format Select

EA = Enable Alarm

AL = Alarm Latch

EI = Enable Interrupt

(1)

Inpt Tp/Rnge Sel Chlx = Input Type/Range Select

Inpt Filter Sel Chlx = Input Filter Select

Reserved = Allows for future expansion

ETS = Enable Time Stamp

Bit Definitions for Channel Configuration Words

Define To Select

Input Filter Selection 60 Hz

50 Hz

28.5 Hz

300 Hz

Enable Interrupt

Enable Process

AlarmLatch

360 Hz

Enable

Disable

Enable

Enable Process

Alarms

Enable Channel

Disable

Enable

Disable

Enable

Disable

1

0

Make these bit settings

15 14

…11 10 9

8 7

…4 3

2 1 0

0 0 0 0

0 0 0 1

0 0 1 0

0 0 1 1

0 1 0 0

1

0

1

0

1

0

(1) MicroLogix 1500 and CompactLogix L3x controllers do not support interrupts.

Publication 1769-IN074C-EN-P - March 2011

18 CompactLogix Isolated Analog Input Module

Bit Definitions for Input Range and Input Data Configuration

Define Indicate This

Input Range Select -10

…+10V DC

0

…5V DC

0

…10V DC

4

…20 mA

1

…5V DC

0

…20 mA

Input Data Select Raw/Proportional

Counts

These bit settings

15

…11

10 9 8 7

…4 3

2 1 0

0 0 0 0

0 0 0 1

0 0 0

0

0

0

0

0

0

1

1

1

1

0

0

0

1

0

1

Engineering Units

Scaled for PID

Percent Range

0

0

0

0

1

1

1

0

1

Specifications

Technical Specifications 1769-IF4I

Attribute

Enclosure type rating

Dimensions, HxWxD (approx.)

1769-IF4I

None (open-style)

118 mm x 35 mm x 87 mm

Height including mounting tabs is 138 mm

4.65 in. x 1.38 in. x 3.43 in.

Height including mounting tabs is 5.43 in.

300 g (0.66 lb) Approximate shipping weight

(with carton)

Enclosure type rating

Wire size…

Wiring category

(1)

North American temp code

None (open-style)

0.32…2.1 mm

2

(22…14 AWG) solid copper wire or 0.32…1.3 mm

2

(22…16 AWG) stranded copper wire rated at 90 °C (194 °F ) insulation max

2 - on signal ports

T4A

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial

Automation Wiring and Grounding Guidelines, publication 1770-4.1

.

Environmental Specifications 1769-IF4I

Attribute

Temperature, storage

1769-IF4I

-40…85 °C (-40…185 °F)

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 19

Environmental Specifications 1769-IF4I

Attribute

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry

Heat)

IEC 60068-2-14 (Test Nb, Operating

Thermal Shock)

Temperature, surrounding air, max

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged

Nonoperating Cold)

IEC 60068-2-2 (Test Bb, Unpackaged

Nonoperating Dry Heat)

IEC 60068-2-14 (Test Na, Unpackaged

Nonoperating Thermal Shock)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp

Heat)

Vibration

IEC 60068-2-6 (Test Fc, Operating)

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

Emissions

CISPR 11

ESD immunity

IEC 61000-4-2

Radiated RF immunity

IEC 61000-4-3

EFT/B immunity

IEC 61000-4-4

1769-IF4I

0…60 °C (32…140 °F)

60 °C (140 °F)

-40…85 °C (-40…185 °F)

5…95% noncondensing

5 g @ 10…500 Hz

20 g

30 g

Group 1, Class A

4 kV contact discharges

8 kV air discharges

10V/m with 1 kHz sine-wave 80% AM from

80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900

MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890

MHz

3V/m with 1 kHz sine-wave 80% AM from

2000…2700 MHz

±2 kV at 5 kHz on signal ports

Publication 1769-IN074C-EN-P - March 2011

20 CompactLogix Isolated Analog Input Module

Environmental Specifications 1769-IF4I

Attribute

Surge transient immunity

IEC 61000-4-5

Conducted RF immunity

IEC 61000-4-6

Supply power and current ratings

Isolation voltage

1769-IF4I

±1 kV line-earth(CM) on shielded ports

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Backplane:

5V DC, 140 mA

24V DC, 110 mA

Voltage Inputs:

±10V DC

0…10V DC

1…5V DC

0…5V DC (30V DC max)

Current Inputs:

0…20 mA

4…20 mA

30V (continuous), reinforced insulation type, channel to system and channel to channel

Type tested at 710V DC for 60 s

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 21

Input Specifications

Attribute

Analog normal operating ranges

(1)

Full scale analog ranges

(1)

Number of inputs

Bus current draw (max)

1769-IF4I

Voltage: ± 10V DC, 0…10V DC, 0…5V DC, 1…5V DC

Current: 0…20 mA, 4…20 mA

Voltage: ± 10.5V DC, 0…10.5V DC, 0…5.25V DC, 0.5…5.25V DC

Current: 0…21 mA, 3.2…21 mA

4 isolated differential

145 mA at 5V DC

125 mA at 24V DC

Heat dissipation 3.0 Total Watts (The Watts per point, plus the minimum Watts, with all points energized.)

Delta Sigma Converter type

Response speed per channel Input filter and configuration dependent. See your user manual.

Resolutions (max)

(2)

16 bits (unipolar)

15 bits plus sign (bipolar)

Rated working voltage

(3)

30V AC

30V DC

Common mode rejection Greater than 60 dB at 50 and 60 Hz with the 10 Hz filter selected, respectively.

Normal mode rejection ratio -50 dB at 50 and 60 Hz with the 10 Hz filter selected, respectively.

Input impedance Voltage Terminal: 1M

Ω (typical)

Current Terminal: 249

Ω

Overall accuracy

(4)

Voltage Terminal: ±0.2% full scale at 25 °C (77 °F)

Current Terminal: ±0.35% full scale at 25 °C (77 °F)

(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.

(2) Resolution is dependent upon your filter selection. The maximum resolution is achieved with the 10 Hz filter selected.

(3) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V DC input signal and 20V DC potential above ground).

(4) Includes offset, gain, non-linearity and repeatability error terms.

Publication 1769-IN074C-EN-P - March 2011

22 CompactLogix Isolated Analog Input Module

Input Specifications (cont.)

Attribute

Accuracy drift with temperature

Calibration

Non-linearity (in percent full scale)

Repeatability

(1)

Value

Voltage terminal: ±0.003% per °C

Current terminal: ±0.0045% per °C

The module performs only initial factory calibration.

±0.03%

±0.03%

Module error over full temperature range

(0…60 °C [+32…140 °F])

Voltage: ±0.3%

Current: ±0.5%

Input channel configuration Via configuration software screen or the user program (by writing a unique bit pattern into the module’s configuration file). Refer to your controller’s user manual to determine if user program configuration is supported.

Module OK status indicator On: module has power, has passed internal diagnostics, and is communicating over the bus.

Off: Any of the above is not true.

Channel diagnostics

Maximum overload at input terminals

(2)

Over- or under-range by bit reporting, process alarms

Voltage Terminal: ±24V DC continuous, 0.1 mA

Current Terminal: ±28 mA continuous, ±7.0V DC

System power supply distance rating

8 (The module may not be more than 8 modules away from the system power supply)

Recommended cable

Vendor I.D. code

Belden 8761 (shielded)

1

Product type code

Product code

10

44

(1) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.

(2) Damage may occur to the input circuit if this value is exceeded.

Publication 1769-IN074C-EN-P - March 2011

CompactLogix Isolated Analog Input Module 23

Certifications 1769-IF4I

Certifications

(1)

(when product is marked)

c-UL-us

1769-IF4I

CE

C-Tick

UL Listed for Class I, Division 2 Group A,B,C,D

Hazardous Locations, certified for U.S. and

Canada. See UL File E10314.

European Union 2004/108/EC EMC Directive, compliant with:

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers

(Clause 8, Zone A & B)

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

(1) See the Product Certification link at http://www.ab.com

for Declarations of Conformity, Certificates, and other certification details.

Additional Resources

These documents contain additional information concerning related Rockwell Automation products.

Resource

CompactLogix I/O Analog Modules

User Manual, publication 1769-UM002

MicroLogix 1500 Programmable

Controllers User Manual, publication

1764-UM001

1769-ADN DeviceNet Adapter User

Manual, publication 1769-UM001

Description

Provides detailed information on installing, programming, and troubleshooting CompactLogix analog I/O modules.

Provides a detailed description for installing and using

Compact I/O modules with a MicroLogix 1500 programmable controller.

Provides a detailed description of how to install and use

Compact I/O modules with the 1769-ADN DeviceNet adapter.

You can view or download publications at http://www.rockwellautomation.com/literature/ . To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.

Publication 1769-IN074C-EN-P - March 2011

Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/ , you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

For an additional level of technical phone support for installation, configuration and troubleshooting, we offer

TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/ .

Installation Assistance

If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.

United States or Canada 1.440.646.3434

Outside United States or Canada

Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html

, or contact your local Rockwell Automation representative.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

United States

Outside United States

Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback

Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002 , available at http://www.rockwellautomation.com/literature/ .

Allen-Bradley, CompactLogix, RSLogix, RSNetWorx, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell

Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Publication 1769-IN074C-EN-P - March 2011

Supersedes Publication 1769-IN074B-EN-P - May 2010

PN-101424

Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement