GST200-2 Panel Overview

1

1/2-Loop Fire Panel

GST200-2/1 GST200-2

1/2 Loop Addressable Fire Alarm Control

Panel

 1 loop or 2 loops,235 devices for 1 st loop,242 device for 2 nd loop

 30 zones fire and fault/disable indication

 PAS and Acknowledge Function

 Dirty detector reporting

 Walk test feature

 Build in RS485 repeater output, (maximum10 repeaters)

 Standard: EN54-2/EN 54-4

 Mains supply: 220/230VAC 50/60Hz

 Backup battery: 24VDC/22AH

Optional Language version: Portuguese & Hungary

(Keypad, Fascia, LCD text display)

2

Addressable Fire Panel

Optional Components for GST200-2

P-9901A

Micro Thermal Printer

Specification:

 Power: 5v (from GST200-2 internal PSU

 Communication: Ribbon cable connect to

GST200-2 main board printer port

 Support all ASCII character

3

Addressable Fire Panel

Optional Components for GST200-2

LC200

Loop card (2

nd

Loop)

Specification:

 Power: 24v (from GST200-2 internal PSU)

 Communication: Ribbon cable connect to

GST200-2 main board XS2

 Expand one more loop for GST200-2/1 panel

 Loop capacity :242 points

4

Addressable Fire Panel

Optional Components for GST200-2

P-9930

GST200-2 Communication Card

Specification:

 Powered by GST200-2 main board

 RS232 or USB communication Interface between computer and GST200-2 panel

 Communication: 20 pin Ribbon cable connect to GST200-2 main board XS2

5

Addressable Fire Panel

Optional Components for GST200-2

P-9940A

RS485 class A network card

Specification:

 Powered by GST200-2 main board

 Communication: 20 pin Ribbon cable connect to GST200-2 main board XS2 port

 Networking interface with all GST intelligent FACP RS485 Class A network

6

Addressable Fire Panel

Optional Components for GST200-2

P-9960

Class B CAN network card

Specification:

 Powered by GST200-2 main board

 Communication: 20 pin Ribbon cable connect to GST200-2 main board XS2 port

 Networking interface with all GST intelligent FACP CAN network

7

Addressable Fire Panel

Optional Components for GST200-2

P-9960A

Class A CAN network card

Specification:

 Powered by GST200-2 main board

 Communication: 20 pin Ribbon cable connect to GST200-2 main board XS2 port

 Networking interface with all GST intelligent FACP CAN network

8

Panel Overview GST-200-2 Structure

Structures

9

Panel Overview GST-200-2 Fascia

Fascia

LCD Display 8x18 Control Buttons LED indicator

Buttons & 32 Zone Indication & Manual

Intervention

Panel Keypad

10

Panel Overview GST-200-2 Internal Parts Overview

Panel PSU

AC Power Filter

Terminal Board

(Loop 1 interface Board)

230V to27V AC Transformer

11

Panel Overview GST-200-2 Internal Parts Overview

Manual Intervention and

Zone Indication Board

Main Board

LED and keypad board

LCD Screen

12

Panel Overview GST-200-2 Internal Wiring Diagram

System

Diagram

RS 232 CARD

(Optional)

Serial port

USB port

XS2

XS3

H L1 H L2

+ +

D1

Network CARD

B2

A2

OTHER FACP

B1

A1

P-9940A

1.2Km bet two panels

B1

A1

B2

A2

XS1

F7.820.913

D1

+ + +

H L3 H L2 H L1

XS1

F7.820.1007

F7.820.1125

H L2

XS2

Loop 2 CARD

(GS200/2/1-Optional)

Loop 2 CARD

(GS200/2/2-Supplied)

XT2 + 2 4 V G N D

H L1 H L3

F7.820.828V1

Loop 1 Board

Terminal Board

(Supplied)

_

X4

HL5

F1

X5

X6

F2

X7

F3

X1

HL2

HL3

X2

HL4

X3

X8

EARTH

A C Input

AC Filter

L G N

+ 5 V G N D G N D + 5 V G N D + 2 4 V + 2 4 V G N D

Power Supply Unit

CHARGER

FAULT

H L1

_ BAT +

OFF

0 I

ON

FUSE

F7.820.829bV1

OFF

0 I

ON

AC 16-30V

XS13

A

B

XS13

24V+

24V-

B AT Fault

AC Fault

5V

GND

Main Control Board

SPEAKE R

E XTE NDE D P ORT

XS7

D17

XS12

SK1

D 4

D 8 D 9

LED P ORT

XS6

P RINTE R PORT

XS11

BACK

LIGHT

+

SPEAKE R

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

H L

H L

+ +

32 Manual Intervention zone and indicator board Printer

G N D + 5 V

Step-down Transformer

24V Batteries

-

12V

+ -

12V

+

13

Panel Overview GST-200-2 External Wiring Diagram

F7.820.828V1

Output to Repeater or Mimic Panel

Monitored

Terminal

Board

No connec tion

Refers to Optional

Network B oard

Loop Out (Out to First Device)

LOOP 1

Loop In (In From Last Device)

OR

4.7Kohm s

EOL

O/P

Output Device with fitted diode

4.7Kohm s

EOL

FPE

Sounder with built-in diode

FPE with fitted diode

FPE

4.7Kohm s

EOL

Sounder with fitted diode

Output Setting refers to Table List on the Manual

Sounder with built-in diode

Terminal/Output Board

X4

HL5

F1

X5

X6

F2

X7

F3

X1

HL2

HL3

X2

HL4

X3

X8

E AR T H

14

Panel Overview GST-200-2 System Diagram

Stand-alone Architecture

GST200-2/1 – Capacities

•235 devices

•1.0 km max loop length

•1.5mm

2

UTP fire cable

15

Panel Overview GST-200-2 System Diagram

Stand-alone Architecture

GST200-2 – Capacities

•Loop 1 -235 devices

•Loop 2 – 242 devices

•1.0 km max loop length

•1.5mm

2

UTP fire cable

16

Panel Overview GST-200-2 Repeater and GMC connection

Stand-alone Architecture

•Built-in Repeater/Mimic Output

• Up to 10 points

• RS485 – 1000meters

• GSTGMC-up to 8 users

• Required P-9930

•RS232- 15 meters

17

Panels Networking

18

Panels Networking

Network

 Fire resistance cable, Min. 1.0mm

2

 1.5sqmm UTP cable is recommended.

 1200 meters total distance for RS485 network Class B connection

 1200 meters distance between two panels for RS485 network Class A connection

 3500 meters distance for each branch of CAN network.

19

Panels Networking

RS485 Class A Network

Maximum 99 FACP

Recommend 32 FACP

RS 232 Card

Network Card RS 485

(P-9945A)

Length between panels1.2 Km (max)

Network Card RS 485

(P-9940A)

Network Card RS 485

(P-9940A)

Built-in Network Card RS 485

(P-9940A)

20

Panels Networking

CAN Class A Network

Maximum 99 FACP

Recommend 32 FACP

RS 232 Card

CAN Network Card

(P-9965A)

CAN Network Card

(P-9960A)

Length between panels 3.5Km (max)

CAN Network Card

(P-9960A)

CAN Network Card

(P-9965A)

CAN Network Card

(P-9960A)

21

Panels Networking

CAN Class B Network

Maximum 240 FACP in whole network.

Maximum 112 FACP in each branch

P-9960

P-9965

CAN HUB

CAN100H-4/8/12/16

P-9960

P-9965

Total Cable Length 3.5 Km (max)

P-9960

P-9965

P-9965

P-9960

22

Panels Networking

Fiber Optic Network

Maximum 99 FACP

Recommend 32 FACP

RS485 Class B Fiber Optic Network

Fibre Optic

+

P-9940A

(For Single-Mode-25KM)

Interface FIB485S01

+

P-9945A

(For Multi Mode -4.5km)

Interface FIB485M01

+

P-9940A

+

P-9940A

23

Panels Networking

Fiber Optic Network

Maximum 99 FACP

Recommend 32 FACP

RS485 Class A Fiber Optic Network

Fibre Optic

+

P-9940A

(For Single-Mode-25KM)

Interface FIB485S01

+

P-9945A

(For Multi Mode -4.5km)

Interface FIB485M01

Fibre Optic

+

P-9940A

+

P-9940A

24

Panels Networking

TCP/IP Network

+

P-9935 TCPIP + NPort5230

+

P-9935 TCPIP + NPort5230

+

NPort5230 + P-9930TCP/IP

TCP/IP

+

NPort5230 + P-9930TCP/IP

25

Product Overview

26

Initiating Device

Digital Intelligent Sensor

DI-9101E

Intelligent Combination Heat

Photoelectric Smoke Detector

 Advance digital communication

 Drift compensation, reject false alarm from environment changing, dust accumulation and component aging.

 Electrically addressed by handheld programmer

 Built-in remote indicator output

 Special LED blink under certain degree of dirty; fire alarm when 100% dirty

 A2R Heat alarming

 Magnetic test

 LED blink could be optionally disabled

 Detector store most recent 5 fire alarms and fault alarms, as well as total number of alarms.

DB-01

Standard Base

C-9314P

Remote Indicator

27

Initiating Device

Digital Intelligent Sensor

DI-9102E

Intelligent Photoelectric

Smoke Detector

 Advance digital communication

 Drift compensation, reject false alarm from environment changing, dust accumulation and component aging.

 Electrically addressed by handheld programmer

 Built-in remote indicator output

 Special LED blink under certain degree of dirty; fire alarm when 100% dirty

 LED blink could be optionally disabled

 Magnetic test

 Detector store most recent 5 fire alarms, and fault alarms, as well as total number of alarms.

DB-01

Standard Base

C-9314P

Remote Indicator

28

Initiating Device

Digital Intelligent Sensor

 Advance digital communication

 A1R/A1S/BS Selectable(LPCB)

 Electrically addressed by handheld programmer

 Built-in remote indicator output

 LED blink could be optionally disabled

 Magnetic test

 Detector store most recent 5 fire alarms, and fault alarms, as well as total number of alarms.

DI-9103E

Intelligent Rate of Rise and

Fixed Temperature Heat

Detector

DB-01

Standard Base

C-9314P

Remote Indicator

29

Initiating Device

Beam Detector

 Infrared beam detector

 Detection range 8 to 100 meters

 Path width 7 meters each side

 1 to 4 reflectors for different path length

 Standard EN54-12

 Electronically addressed by programmer

 Additional Fire and Fault dry contact relay output

 24VDC supply required

I-9105R

Reflective Beam Detector

30

Initiating Device

Manual Call Points

 Semi-flush or Surface mounted

 Standard EN54-11

 Re-settable (non-breaking glass)

 LED indicator

 Electronically addressed by handheld programmer

 Friendly installation and test

 Optional flipping plastic cover (

D-92FC )

 Optional weatherproof box(

D-92WPB )

 Optional back box for surface mount

DI-9204E

Digital manual Call Point

D-92FC D-92WPB

31

Notification Device

I-9403

Sounder Strobe

 16 selectable tone

 High sound level

 Low/high power consumption modes

 Loop powered or external 24VDC

 Max. 30 pieces per loop when powered by loop

 High intensity LED cluster

 Programmable evacuate only or alert/evacuate mode

 Standard EN54-3

 Electronically addressed by handheld programmer

 Easy installation and connection

C-94DB

Optional deep base for I-9403

32

Notification Device

I-9404

Intelligent Sounder

 16 selectable tone

 High sound level

 Low/high power consumption modes

 Loop powered or external 24VDC

 Max. 30 pieces per loop when powered by loop

 Programmable evacuate only or alert/evacuate mode

 Standard EN54-3

 Electronically addressed by handheld programmer

 Easy installation and connection

C-94DB

Optional deep base for I-9404

33

Notification Device

DI-9405

Addressable

Sounder Base

 “sandwich” structure

 Termination suitable for

“DI” range detectors

 Loop powered

 Maximum 30 pieces per loop

 Three working modes settable (Mode I, II, III, and the latter two available with pre-alarm state).

 16 tones of sound.

 Electronically addressed. The address and tones can be modified in field.

 Tone 14 and 16 are certified by EN54-3.

34

Notification Device

DI-9406

Addressable

Sounder Beacon Base

 “sandwich” structure

 Termination suitable for

“DI” range detectors

 16 selectable tone

 Loop powered

 Maximum 30 pieces per loop

 Three working modes settable (Mode I, II, III, and the latter two available with pre-alarm state).

 16 tones of sound and bright flashing light.

 Electronically addressed. The address and tones can be modified in field.

 Tone 14 and 16 are certified by EN54-3.

35

Interface

Input Interface

I-9300 Input Module

 Intelligent single input module

 Monitors switch contacts of remote equipment

 Loop Powered

 Cable monitored

 Standard EN54-18

 Electronically addressed by handheld programmer

 LED status indicator

36

Interface

Input Interface

I-9319 Zone Interface Module

 Intelligent zone monitor module

 Interface with conventional fire devices

 24VDC required

 Cable monitored

 Standard EN54-18

 Electronically addressed by handheld programmer

 LED status indicator

37

Interface

Output Interface

I-9301 Single Output Module

 Intelligent single output module

 24VDC/3A, 110VAC/3A dry contact output – Loop

Powered

 Interface with conventional polarized sounders –

24VDC required

 LED status indicator

 Standard EN54-18

 Electronically addressed by handheld programmer

 LED status indicator

38

Isolator

Loop Isolator

C-9503 Short Circuit Isolator

 Isolates faulty part of the loop in case short circuit

 Auto resume when trouble removed

 LED status indicator

 Standard EN54-17

 Not occupy loop address

39

Isolator

Loop Isolator Base

C-9504 E

Base Mount Short Circuit

Isolator

 Termination suitable for “I” range detectors

 Isolates faulty part of the loop in case short circuit

 Auto resume when trouble removed

 LED status indicator

 Not occupy loop address

40

Isolator

Loop Isolator Base

 Termination suitable for “DI” range detectors

 Isolates faulty part of the loop in case short circuit

 Auto resume when trouble removed

 LED status indicator

 Not occupy loop address

DC-9504 E

Base Mount Short Circuit

Isolator

41

Programmer

Handheld Programmer

 Set address to loop devices

 Change parameter setting of loop device

 Program graphic repeater panel LEDs

P-9910B Programmer

42

Repeater Panel

GST-852RP

Passive Repeater Panel

 Compatible with all GST intelligent fire alarm control panel

 Fire Event Display

 Local Sounder mute and Scroll alarm buttons

 Connect to RS485 repeater loop

43

Repeater Panel

GST-NRP01

Network Repeater Panel

 Display network message (Fire, Plant and Fault)

 Achieve remote control of systems

 Password protected

 Connect in GST panel network

 A class A network card already pre-installed

44

Repeater Panel

GST-8903

–A1/A2/A3

Graphic Repeater Panel

 Up to 100 LED per module

 Custom graphical layout

 Display individual points and zone wise fire and fault signal

 Display individual points action signal.

 Connect to RS485 repeater loop (can be mixed with GST852RP)

45

Graphic Station

GST-GMC

Graphic Monitor Center

 Display message (Fire, Fault, Action, Disable)

 Remote full control and monitor of systems

 Multi-level Password protected

 Historic data of all the system events

 Clock synchronization with panels

 Up to 8 users plus the server in a Network

 Connect with panel through RS232 cable

46

Configuration, Operation and

Programming

2014 V1.2

System Configuration

To configure a system

1. Decide panel type and quantity. If more than one panel is configured, add network card to each panel.

2. Decide loop quantity. Remember leave at least 20% of loop quantity for future expansion.

3. Calculate power consumption and configure PSU as required.

4. Consider of loop power consumption devices (like sounder base and loop powered sounder). Add more loop cards if needed.

5. Isolators will be required to protect the loop.

6. At least one handhold programmer and one RS232 communication card is required for each commissioning company.

7. Add any necessary accessories as requirement.

48

Addressable Fire Panel

GST200-2 and GST-IFP8Common Character

Large Graphical LCD display

3 alarm outputs, sounder/F.P.E/Alarm Routing

PAS (Positive Alarm Sequence) and Acknowledge function Advanced user friendly programming software including

“fuzzy logic”

Networkable with all GST Intelligent Fire Alarm panels

Enable and Disable function

Dirty detector report function

Walk test function

Optional RS 232 Color Graphics Software

Optional RS485 Network Card

Optional CAN network card

49

System Configuration

Points for system configuration

1. Max. 32 panels in RS485 network

2. Max. 112 panels in one branch of CAN network. Totally Max. 240 panels.

3. Max. 32 devices between two isolators

4. Max. 30 sounder bases and loop powered sounders (in total) in one loop.

5. Each device occupies one single address, except below devices.

Device Address QTY

C-9503 Loop Isolator

C-9314P Remote Indicator

DI-9309 Multi Input Output Interface

I-9406 Sounder Flasher Base

I-9403 Addressable Sounder Flasher

0

0

3 to 18

1 or 2

1 or 2

50

System Loop Parameter

Loop

Fire resistance UTP cable, Min. 1.0mm

2

1.5mm

2 UTP cable is recommended.

1000 meters loop length

51

System Loop Parameter

Loop cable parameter

Cable resistance should be less than 50

Ω

52

System Loop Parameter

Loop cable parameter

Before fix devices on loop, the resistance between 2core should be more than

2M

Ω, ideally 20MΩ

After fix devices on loop, the resistance between 2 core should be more than 1k

Ω

53

System Loop Parameter

Loop cable parameter

Insulation between cable to

Earth should be more than

20M

Ω, ideally 200MΩ

54

GST200-2 Panel Operation

55

Panel Operation GST200-2

Factory default password

Registration : 24220011

User Operator: 11111111

Manager / System: 11111111

56

Panel Operation GST200-2

Browse Menu

1Loop Devices

2 Zone Devices

3 Group Devices

4In Test Mode Zones

5 Com Devices

6 Access

7 Browsing C&E

Loop Devices: View the number of devices per loop and detailed provided with each device

Zone Devices: View the number of Input devices per zone

Group Device: View number of Output devices per zone

Browse

Zone: 001 GND FLR

No: 003 MCP

Sensitivity: Nominal

Left W ing Corridor

In Test Mode Zones: View which zones are in test mode

COM Devices: View the number of Control Panel and Repeater panel connected in the system

Browse

Sum: 003

Repeater01

Net Unit 01

Net Unit 02

Access: Control switch and zone indicator detailed.

Browsing C&E: View the configured sequence of operation

Browse

Equation 001

S0100103+S0100102

=S01***1312 G011433120

Browse

02 Zone (008)

Zone: 01 (001) 003

Zone : 02 (002) 001

Browse

Sum: 032

N01: Zone 01 (001)

N02: Zone 02 (002)

N03: No Define

57

Panel Operation GST200-2

Mode Menu

1 LCD Contrast

2 Display Mode

3 Print Mode

4 PAS Setup

5 Start Devices

6 Stop Devices

LCD Contrast : (0-100) (factory set

– 50)

Display Mode

1 Zone Mode : by zone detail

2 Loop Mode : by point device detail ( default setting)

Print Mode

1 Disable - ( default setting)

2 Only Fire : Automatic print on fire event

3 All History: Pressing Enter when viewing history records can print out the

messages being viewed

PAS Setup * (Positive Alarm Sequence)

1 Disable- ( default setting)

2 Enable

Start Devices (manually start)

Stop Devices (manually stop)

Start UP

Z001C***T13 Sounder

Stop EQ

Z001C125T03 Optical

58

Panel Operation GST200-2

Mode Menu - PAS

System Requirement (NFPA 72:6.8.1.3)

PAS MODE

Fire signal from detector shall be acknowledged at the panel within 15 sec in order to initiate the alarm investigation phase. Trained personnel shall have up to180 sec to investigate.

•Fire signal not acknowledged w/in 15 sec – Outputs (Equation) immediately activated

•Panel not reset during the 180 sec – Outputs (Equation) immediately activated

•Second fire signal during the 180 sec – Outputs (Equation) immediately activated

Notes:

•Press Evac override PAS

•MCP is exempted (BS5839 P1:2.19)

59

Panel Operation GST200-2

Test Menu

TEST [Operator Password required]

1 Display Test - check the LED and LCD

2 Each Zone In Test

1Display Test

2Each Zone In Test

3 Stop a Zone Test 4

Stop All Zone Test

Start a Zone in Test

Zone: 001

3 Stop a Zone Test

4 Stop All Zones Test

TEST MODE LED will on

Corresponded Zone Yellow LED will lit

60

Panel Operation GST200-2

Disable/Enable Menu

1 Disable Devices

1 Each Zone Fully

2 Individual Point 3

All Loop Sounder

4 Use Device Code

2 Enable Devices

1 Each Zone Fully

2 Individual Point

3 All Loop Sounder

4 Use Device Code

1Disable Devices

2 Enable Devices

3 Dis/En-able Output

4Dis/En-able Delays

5 Delete Net Disable

3 Dis/En-able Output

1 Sounder Circuit

2 F.P.E Output

Disabling a Point

Loop: 1 Point : 001

Enable

Z001C125T03 Optical

4 Dis/En-able Delays:

1 Disable - ( default setting)

By address Using device code

2 Enable- Delay in C&E equations will be effective

5 Delete Net Disable to delete not existing disable messages from network

61

Panel Operation GST200-2

System Menu

1 Time/Date

2 Password Change

1 Operator Password (0-8 digit)

2 Manager Password (0-8 digit)

3 Network Setup

1 Net Local Address (panel network address: 1-240)

2 Net Event Display

1Time/Date

2 Password Change

3 Network Setup

4Zone Start Number

5 Customize

6.Initialize System

7.Devices Debug

1 Disable - (default setting)

2 Enable (To show messages coming from network)

4 Zone Start Number

5 Customize

1 Output Set-up

1 Default Output: ( default setting)

Device type 13 Sounder activate at zone wise alarm .

2 C&E Output: The system output will be based on configured C&E equation

2 PAS Delay (000-180 second)* (factory set is 60 seconds)

3 Re-Sound Configurations

1 Another Zone - ( default setting)

2 Self Zone

6 Initialize System* (Not for common operation)

7 Devices debug * (For factory engineer use)

62

Panel Operation GST200-2 Register

GST200-2

1. Press

“System (9)”

2.

Enter the password

24220011”

(Factory set Commission Password) then Press

“Enter”

(Note:

“-” sign means the panel is set to commissioning mode)

3. Press

“SK1 button” behind the door.

SYSTEM

1Time/Date

2 Password Change

3 Network Setup

4 Zone Start Number

5 Customize

6Initialize System

7 Device Debug

63

GST200-2 Basic software

Configuration

64

GST Definition software installation

GST Definition software installation Flow Chart

1.GST Def.EXE

2.Windows XP. Double click

“GST Def.exe”, default following steps. Till installation finish

3.install USB driver

Software

Installation

Finish

2.Windows Vista or Windows 7, right click

“GST Def. exe” select

“Run as administrator” , default following steps. Till installation finish.

3.Install USB driver

4.Check computer

OS bits (32 bits or

64 bits), install patch file.

5.Right Click patch file. Select

“Run as administrator

” till installation finish

Right click

“My Computer” select

“property”, pop out window general information showing OS bits

65

GST200-2 Panel addressing

GST200-2 Panel addressing Flow Chart

1. GST200-2 panel, in power off condition

2.Connect RS232 communication card to GST200-2 panel

3.Power on

GST200-2 panel

4.Press panel

“System” button

8.Press

“System” button, input password

“24220011 “ Enter

9.Net work setup

7.Panel restart , during starting progress show

“Color Crt OK”

6.Press SK1 button at back of the main board

5.Input password

10.Net local address

11.Set up panel address . Enter to confirm

Note : Address on panel must be same as the panel address on

GST definition program

24220011

66

Basic Software Configuration GST200-2

GST200-2 Definition Flow Chart

1. Power On

GST200-2

2.Connect download card USB cable to computer USB port

3.Run GST

Definition Software

4.Select Com Port

10.Define

Repeater

(Option)

Save and

Download

9. Define

Zone indication and control switch

Save and

Download

8.Define

Cause &

Effect

7. Define devices

(zone , device type and Location)

Save and

Download

Save and

Download

6.Add zone, define zone

Save and

Download

5.Add panel, select panel type and panel address

Fire Alarm Control Panel GST200-2

67

Basic Software Configuration GST200-2

Points should be known before programming GST 200-2

Each devices code include 3 parts:

Device Zone number (3 digit, range 001-060 for GST200-2

Device address (3 digit, range 001-242)

Device type (2 digit) .

For example: 001001 03 means smoke detector (type 03) address 001 in zone 001

The device code is the device unique ID on standalone FACP or whole FACP network. So before addressing and programming devices, below points should be noted:

1. In same zone, in case the devices from different loop or different panel, the device address + device type can not be same as other device

’s. for example: in zone No.1 already has smoke detector address No.1 from loop1, and in this zone has another smoke detector from other loop or other panel, the device address can not be No.1 again. Or if use address No.1, can not given to smoke detector.

2. Device information transferred on network include :

“Device zone number + Device address + Device type (number only, no text)+ device location description.

So the zone information must be downloaded to each network panel, if has the user defined device type text, the description also need download to each panel.

68

Basic Software Configuration GST200-2

Points should be known before programming GST200-2

1. The maximum zone number for GST200-2 is 60, if the panel in network, and whole network zone numbers more than 60. for example 4 GST200-2 panels in network, each panel include

20 zones. Total 80 zones. The commissioning engineer can set the devices in panel No.1 to zone 1 to 20, devices in panel No.2 to zone 21 to 40, devices in panel No.3 in zone 41 to 60. and devices in panel No.4 in zone 1 to 20, then set the start zone number on panel No.4 is 61. then the zone 1 on panel 4 will be displayed as zone 61 on local and network panel.

2.

On GST200-2 panel, the network fire signal cannot use as local panel Cause & Effect condition.

3.

Local panel can send activation command to network. Such as above example if in case fire on panel 1 want to active module on panel No.4, must save cause & Effect on panel No.1, the activation device code must be the displayed number, for example 061001 13. not the local programmed code.

69

Basic Software Configuration GST200-2

Basic Software Configuration

1. Control Panel Detailed

2. Number of Loop

3. Zone Configuration

4. Device Detailed per Loop /Device Type

5. Equation (Cause & Effect)

6. Control Switch & Zone LED

7. Naming Repeater Panel

8. Saving Data

9. Download / Upload

70

Basic Software Configuration GST200-2

1. Control Panel Detailed

•Adding Control Panel

•Click the “FACP Net” icon

•Right-click “FACP” and select

“Add FACP”

•FACP Type: Select the panel part number

•FACPAddress: Address of the panel

•FACP Name: File name reference

•Net: Click if the panels are network

71

Basic Software Configuration GST200-2

2. Number of Loop

Note:

“Once the GST200-2 is selected, the software is automatically show the two loop, no loop configuration is required

.”

72

Basic Software Configuration GST200-2

3. Zone Configuration

Adding a zone

1.Click the

“FACP Zone” icon

2.Right-click

“Panel that will add zone” and select “Add Zone”

3.Or Click the

“New” icon

Note: Max number of zone is 60

Zone ID : Zone number

ForeColor: Font Color

BackColor: Text Highlight Color

Description: Zone name (note: 8 Max character)

Example: Zone example

4.To save click the

“Save” icon

73

Basic Software Configuration GST200-2

4. Device Detailed

Device Configuration per Loop

1.Click the

“FACP Net” icon

2.Click

“Panel to be programmed”

3.Click the

“Loop 1”

Address: 1-242

Loop Number: Loop Assignment

Zone: Zone assignment

Device Type: Selection of device type.

Properties: For output- 0-on/off ;

1-continoues

Location: Device location information

Note: GST200-2 character 32 max: 21 first line; 11 second line

Registered: Once the data is uploaded from the panel, it will indicate TRUE if the particular device is being found or registered in the panel ,otherwise it will indicate False.

4. Click Save icon to save

74

Basic Software Configuration GST200-2

To configure the Device Type

1.Click the

“Panel that will configure

2.Click the

“Device Type –icons

3.The

Device Type window will pop-up

4.Select the number to change and type new Device Type name.

Basic Software Configuration GST200-2

5. Equation ( Cause and Effect )

Configuring the Equation

1. Click the

“FACP Net” icon

2. Click

“Panel to be programmed”

3. Click the

“Equation”

4. Click

“NEW” to create a new equation.

5. To save as a new equation click

“Save New”

1. To overwrite original equation click

“Save

Modify

2. To save the entire equation click

“Save”

Condition: INPUT DEVICES- 8 digits

Effect: OUTPUT DEVICES

– 8 digits + 2 digits delay time

Logic: AND Logic (x), OR Logic (+)

Fuzzy Logic: Asterisk (* value 1-9)

Delay Time Ratio: 1:10 seconds

76

Basic Software Configuration GST200-2

5. Equation ( Cause and Effect ) cont.

G/S60

242 99 =

G/S60

242 99 99

Zone *Address

(Fuzzy/Amt)

Device Type Zone Address Device Type Delay Time

Condition

G01 020 03

S02 001 11

(By Zone) meaning Address 20 Optical smoke in Zone 1 (By Point)

(Fuzzy Logic)meaning At least 1 (Amount) MCP regardless of address in Zone 2

S** 002 02

(Global)

(Fuzzy Logic) meaning 2(Amount) Heat det. should alarm at same time in the entire area

Effect:

S**001 31 12 meaning latch all lift module after 2 minutes

–regardless of quantity.

Sample Equation:

S01 001 11 + S01 00103 + S0100102 = S0100113 00 S**00113 06

77

Basic Software Configuration GST200-2

6. Control Switch and LED Zones

Programming control switch

1.Click the

“FACP Net” icon

2.Click

“Panel to be programmed”

3.Click the

“Control Switch”

Keys: 1-30

Address of Device to Start: Select the address of a devices/s that wish to control

Zone to Display: Select the zone number that wish to display

Function: The control switch function-auto change

78

Basic Software Configuration GST200-2

7. Naming Repeater or Mimic Panel

1. Click the

“FACP Net” icon

2. Click the

“Repeater” icon

Based on the address of the repeater type the

Description

3. Click

“Save”

Note: Description- up to 8 characters

79

Basic Software Configuration GST200-2

8. Saving and Restoring the Data

Click the

“Database” icon

The Database Operation window will pop out

Click

“Backup Database” to save the data.

Save the data to the required location

Click

“Restore Database” to retrieve the data.

Locate the saved data

80

Basic Software Configuration GST200-2

9. Upload and Download Data

Terminology:

Download: Data transferring from the PC to the Control Panel

Upload : Data transferring from the Control Panel to the PC

3 important things:

1. Registration of RS232 download card (Hardware)

GST200 Series

Press

“System” Enter the password 24220011 Press “Enter”

Press

“SK1 button” behind the door.

(Note: procedure should be done within 25 seconds and HL1 red LED will blink indicates that the card is registered)

2. Set Serial Port number (USB Connection-My computer-Properties-Hardware-Device Manger-Port)

3. Matched the address of the control panel

“Local Address from the GSTDef software “FACP Address”.

To view the control panels address:

Press

“System”

3 Network Set-up

1 Net Local Address

81

Basic Software Configuration GST200-2

Basic PC Connection Procedures

• Panel must be OFF condition while connecting to the 20p ribbon

1.Turn on the panel and perform an auto learn/registration as follows:

2.Press

“System” Enter the password

24220011” (Commissioning password) then

Press

“Enter”

3.Press

“SK1 button” behind the door.

(Note: procedure should be done within 25 seconds otherwise the control panel will initialize the normal panel reset)

•After the registration HL1 will be flashing continuously