LISTING NUMBER
afp - 1083
Version: .... 5.... 29-Jul-2009
Valid until
†
: ........... 31-Jul-2010
PRODUCT LISTING DATA SHEET
(Active Fire Protection Equipment)
Product designation
VESDA®, aspirated smoke detector system
(Refer to the Technical Specification section of this document for further specific detail)
Supplier
Xtralis Pty Ltd
4 North Drive, Virginia Park, 236-262 East Boundary Road, BENTLEIGH EAST, VIC, AUSTRALIA, 3165
Manufacturer
Xtralis Pty Ltd
4 North Drive, Virginia Park, 236-262 East Boundary Road, BENTLEIGH EAST, VIC, AUSTRALIA, 3165
Supplier's description
The VESDA
®
Aspirated Smoke Detector System consists of the following components:
Model num. Description
VLP-002
VLP-012
VLP-100
VLP-400
VLP-401
VLS-100
VLS-204
VLS-214
VLS-304
VLS-314
VLS-500
VLS-600
VLS-601
VLS-700
VLS-701
VRT-200
VRT-400
LaserPLUS™ Aspirated Smoke Detector
LaserPLUS™ Aspirated Smoke Detector
LaserPLUS™ Aspirated Smoke Detector
LaserPLUS™ Aspirated Smoke Detector
LaserPLUS™ Aspirated Smoke Detector
LaserPLUS™ FD (Four Detector)
LaserPLUS™ FD (Four Detector)
LaserPLUS™ FD (Four Detector), Scanner Aspirated Smoke Detector
LaserPLUS™ FD (Four Detector)
LaserPLUS™ FD (Four Detector), Scanner Aspirated Smoke Detector
LaserPLUS™ FD (Four Detector)
LaserPLUS™ FD (Four Detector)
LaserPLUS™ FD (Four Detector)
LaserPLUS™ FD (Four Detector)
LaserPLUS™ FD (Four Detector)
Remote Display with Relays
Remote Scanner Display with Relays
VRT-300
VSR-0231
VLC-500
VLC-505
VSW-202
Remote VESDAnet Socket
19 inch Sub-rack
LaserCOMPACT™ Aspirating Smoke Detector - Relays only Version (RO)
LaserCOMPACT™ Aspirating Smoke Detector - VESDAnet Version (VN)
ASPIRE2™ System Design Tool, Version v 2.01.00 – 3835
afp1083.lds
This product listing data sheet should be read in conjunction with the general requirements of the terms and conditions of listing under the ActivFire Scheme.
© CSIRO Australia, 2009
Executive Officer
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
Model VLP-002
Model VLP-012, LaserPLUS™ Aspirated Smoke Detector
Model VLP-100
Model VLP-400
Model VLP-401
The VESDA
®
LaserPLUS™, Model VLP-012 Aspirated and smoke detector is modular designed, active smoke detection system that sample air from a fire zone for the presence of smoke. Air samples are drawn to the detector head from a sampling pipe network using an aspirator. The sampling pipe network consists of a series of PVC 25 mm OD pipes with sampling points and an end-cap.
A display module provides a visual representation of the smoke levels and alarms detected by the detector. The detector supports four levels of alarm, each of which is indicated by a high intensity red light and an audible sounder. These lights flash until acknowledged by a key-press, whereupon they become steady and the sounder is silenced. Detector faults and systems faults are indicated on the display by the flashing of appropriate amber lights and the sounding of an alarm.
A numerical display is provided to indicate the Fire 1 alarm threshold, smoke level (in %Obs/m), and the zone number of the detector. The default setting for the display is the Smoke Level. A twenty (20) segment bargraph indicates the current level of detected smoke. The scaling of the bargraph is dynamic in that Fire 1 threshold always corresponds to the top bargraph light. The Action and Alert levels are scaled proportionally.
Buttons are provided in the display module front panel to check but not configure the system functions. These buttons can be configured as lock-out to prevent unauthorised operation. The Mode/Test button either switches the numerical display reading or activates the test mode. The Silence button will silence any alarm or fault beeps sounding from the display and any flashing alarm or fault LEDs will change to a steady illuminated condition. The
Reset button will reset any alarm or fault conditions and return relays to their normal state. Any beepers or flashing lights will be turned off. The Isolate button isolates the zone from external devices. An Isolate indicator light will illuminate and a reminder beep will sound.
The LCD Programmer module allows the user to adjust the alarm thresholds, smoke confirmation delay times and relay configuration of the modules in the VESDA
®
LaserPLUS™ system. Access is PIN protected. A list of programmable functions is shown in the Supplementary Information. The VESDA
®
LaserPLUS™ aspirating smoke detector is powered from an external dc source that can vary between 18 Vdc and 30 Vdc. Guidance is provided by the manufacturer on the selection of wire size depending on source voltage and length of wire. The VESDA
®
LaserPLUS™ aspirating smoke detectors are not claimed to be waterproof.
Model VLS-100
Model VLS-204
Model VLS-214, FD (Four Detector),
LaserPLUS™
Scanner Aspirated Smoke Detector
Model VLS-304
Model VLS-314, FD (Four Detector),
LaserPLUS™
Scanner Aspirated Smoke Detector
Model VLS-500
Model VLS-600
Model VLS-601
Model VLS-700
The display module provides a visual representation of the smoke levels, scanning action, the first alarm sector
(FAS) and any alarms detected by the detector. Detector faults and systems faults are indicated on the display by the flashing of appropriate amber lights and the sounding of an alarm.
A numerical display is provided to indicate the Fire 1 alarm threshold, smoke level (in %Obs/m), the zone number, the scanning function (Sc), and either the first alarm sector (FAS) or highest alarm sector (HAS) of the detector. If an alarm has been detected the FAS is displayed. The numeric display will indicate the (HAS) if this sector is different from the FAS. The commencement of the rapid scanning function is displayed as Sc. A twenty (20) segment bargraph indicates the current level of detected smoke. The scaling of the bargraph is dynamic in that
Fire 1 threshold always corresponds to the top bargraph light. The Action and Alert levels are scaled proportionally. The default setting for the display is the Smoke Level.
Buttons are provided in the display module front panel to check but not configure the system functions. The
Mode/Test button either switches the numerical display reading or activates the test mode. The Silence button will silence any alarm or fault beeps sounding from the display and any flashing alarm or fault LEDs will change to a steady illuminated condition, or if held depressed for longer than 2 seconds will initiate a manual scan operation.
The Reset button will reset any alarm or fault conditions and return relays to their normal state. Any beepers or afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009 flashing lights will be turned off. The Isolate button isolates the zone from external devices. An Isolate indicator light will illuminate and a reminder beep will sound.
The LCD Programmer module allows the user to adjust the alarm thresholds, smoke confirmation delay times and relay configuration of the modules in the VESDA
®
LaserPLUS™ system. Access is PIN protected. A list of programmable functions is provided in Appendix C of the VESDA
®
System Design Manual. If a user is not logged on to the LCD Programmer, the display will automatically provide a textual scanner status screen when a scan cycle commences. A typical textual display is shown in Figure 1.
Zone 01 Basement
→
Alarm Level
P3 Fire 1
First Alarm Sector
1.154 %/m
P3
Scanner status screen
A detailed description of the LCD Programmer and its functions can be can be found in the VESDA
®
System
Design Manual.
A twelve (12) relay termination card, LPV-PCA-021 -OOA, is supported by the detector and display. The FD
Scanner software will support the original seven (7) relay termination card but only when configured for that type of relay termination card. The default configuration for the seven (7) and twelve (12) relay cards is shown in the following table.
Relay No. 7 Relay Termination Card
1 Isolate
2
3
4
5
Minor fault (normally energised)
Urgent fault (normally energised)
Alert (any sector)
Action (any sector)
6
7
8
9
10
11
Fire 1 (any sector)
Fire 2 (any sector)
-
-
-
-
12 -
Default relay configuration table
12 Relay Termination Card
Isolate
Minor fault (normally energised)
Urgent fault (normally energised)
Alert (any sector)
Action (any sector)
Fire 1 (any sector)
Fire 2 (any sector)
FAS Sector 1
FAS Sector 2
FAS Sector 3
FAS Sector 4
Scanning
The VESDA
®
LaserPLUS™ model VLS-314 FD Scanner is powered from an external dc source that can vary between 18 Vdc and 30 Vdc. Guidance is provided by the manufacturer on the selection of wire size depending on source voltage and length of wire.
The VESDA
®
LaserPLUS™ model VLS-314 FD Scanner is not claimed to be waterproof.
Comparison table:
Feature / Function
Aspirated Smoke Detection
Standard Laser Chamber Detector
Smoke Sensitivity
Area covered
Number of Pipe Inlets
Pipe ID
Can measure smoke level per pipe
Automatic Fortnightly Valve Test
Standard Aspirator
Standard Filter Module
Modelling Tool Used
VLP-012
Detector
VLS-214
VLS-314
FD (Four Detector)
Scanner
Yes
Yes
Yes
Yes
0.005 to 20% 0.005 to 20% obscuration/m obscuration/m
2000 m
2
2000
4
19 to 25mm
(preferred OD 25mm)
No
No
Yes
Yes
ASPIRE
4
1 9 to 25mm
(preferred OD 25mm)
Yes
Yes
Yes
Yes
ASPIRE afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
Feature / Function
Supply Voltage
Dimensions (W x H x D) mm
Weight
Operating Temperature
Sampled Air Temperature
Humidity
IP Rating
Relay Alarm Outputs
(factory default configuration)
(FIRE 1 and URGENT relay functions are fixed)
VLP-012
Detector
18 - 30 Vdc
350 x 225 x 125
4.0 kg
0 to 39 DegC
-20 to 60 DegC
10 to 95 % RH, non-condensing
IP30
7-relays
• Isolate
Fault
• Urgent
• Alert (any sector)
• Action
• sector)
• Fire 1 (any sector)
• Fire 2 (any sector)
VLS-214
VLS-314
FD (Four Detector)
Scanner
18 - 30 Vdc
350 x 225 x 125
4.0 kq
0 to 39 DegC
-20 to 60 DegC
10 to 95 % RH, non-condensing
IP30
12-relays (VLS-314)
• Isolate
Fault
• Urgent
• Alert (any sector)
• Action (any sector)
• Fire 1 (any sector)
• Fire 2 (any sector)
• FAS Sector 1
• FAS Sector 2
• FAS Sector 3
• FAS Sector 4
7-relays (VLS-214)
• Isolate
Fault
• Urgent
• Alert (any sector)
• Action (any sector)
• Fire 1 (any sector) Fire 2
(any sector)
VRT-200 Remote Display with Relays
VRT-400 Remote Scanner Display with Relays
The VESDA
®
LaserPLUS™ model VRT-200 remote and model VRT-400 remote scanner display with relays are a duplication of the display modules normally mounted in the VESDA
®
LaserPLUS™ aspirated and scanner aspirated detectors. The VESDA
®
LaserPLUS™ remote displays with relays are mounted in a metal case with a remote termination card that provides interconnection for supply power and VESDAnet.
The remote displays can be programmed to monitor a single detector using either the programmer or a PC. The model VRT-200 remote display will only monitor the detector in a non scanning model VESDA
®
LaserPLUS™ aspirating detector. A display can only monitor one (1) detector.
VRT-100 Remote Programmer
The VESDA
®
LaserPLUS™ model VRT-100 remote programmer is a duplication of the programmer module mounted in the VESDA
®
LaserPLUS™ detector. The VESDA
®
LaserPLUS™ remote programmer is mounted in a metal case with a remote termination card without relays that provides interconnection for supply power and
VESDAnet. The remote programmer can be used to monitor the status of all components connected in the
VESDAnet loop.
Note: In the VRT-100 remote programmer, the relays are not provided, and hence no relay outputs are supported in the remote programmer. afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
VRT-300 Remote VESDAnet Socket
The VESDA
®
LaserPLUS™ model VRT-300 remote VESDAnet socket has a fifteen (15) pin high density female
`D’ type connector mounted in a blank plate. This socket is a duplicate of the socket mounted on the head termination card, LPV-PCA-010-00, in the VLP-012 aspirating detector. A Hand held programmer or PC-Link HLI can be connected to the VESDAnet via the socket. The `D’ socket provides a nominal 24 Vdc power supply and
VESDAnet connections to the hand held programmer or PC-Link HLI.
VHH-100 Hand held programmer
The VESDA
®
LaserPLUS™ model VHH-100 hand held programmer is a portable device which provides the same functionality as that of the programmer module mounted in the VESDA
®
LaserPLUS™ detector. It physically consists of a programmer interface card, LPV-PCB-014-00, and a programmer processor card, LPV-PCB-009-00A.
Connection to the VESDAnet is made through a cable connecting the fifteen (15) pin high density male `D’ type connector to the fifteen (15) pin high density female 'D' type in the remote VESDAnet socket or the head termination card, LPV-PCA-010-00, in the VLP-012 aspirating detector. The female `D’ socket provides a nominal
24 Vdc power supply and VESDAnet connections to the hand held programmer.
VSR-0231 19” sub-rack
The VESDA
®
LaserPLUS™ model VSR-0231 19 inch sub-rack is a configured example of a mounting facility for a maximum combination of four (4) modules consisting of display(s), programmer, VESDAnet socket, and blank plate(s). The Rack unit consists of the 19 inch sub-rack, a rear shield, and a 19 inch rack mounting. The termination cards and front modules are mounted as required.
VHX-0100 PC-Link HLI
The VESDA
®
LaserPLUS™ VHX-0100 PC-Link HLI is an interface between the female ‘D’ socket of a VLP-012 aspirating detector, or remote VESDAnet socket and a PC. The VESDA
®
LaserPLUS™ VHX-0100 PC-Link HLI requires two cables to effect communication between the PC and the VESDA
®
LaserPLUS™ network. It enables communication with modules over the VESDAnet by using a variety of VESDA
®
LaserPLUS™ PC software.
VPS-101 Single Zone Intelligent Power Supply (with VESDAnet)
The Vision Systems VESDA
®
LaserPLUS
™
Model VPS-101 Single Zone Intelligent Power Supply (with
VESDAnet) is a single-zone 24 Vdc power supply referenced to mains earth potential and capable of providing power with battery backup and temperature compensated charging for a single LaserPLUS
™
detector head fitted with display and programmer. The VESDA
®
LaserPLUS
™
Model VPS-101 power supply has the added ability to supply low voltage power to other devices on the system and has built in diagnostic and fault reporting functions which include a fault indicator and fault relay output. The Vision Systems VESDA
®
LaserPLUS
™
Model VPS-101
Single Zone Intelligent Power Supply (with VESDAnet) is also provided with a VESDAnet communications interface which reports detectable fault conditions and status information to the intelligent devices powered by it.
VLC-505 (VN) LaserCOMPACT™ Detector
VLC-500 (RO) LaserCOMPACT™ Detector
The LaserCOMPACT™ is made up of two parts. The main enclosure houses all the key components of the detector. All non-serviceable items like the main processor board and detector chamber are mounted away from the general access area, protecting them during installation and service. The main enclosure includes:
• The Laser Detection Chamber,
• Main processing board with integrated flow sensor,
• Single-port entry with air flow monitoring,
• Termination card supporting three relays
Fire, Pre-Alarm, Alert / Fault (including service and isolate)
Power and connections and VESDAnet communication connection on VN version aspirator
• Dual stage filter cartridge
The front cover supports five LEDs, Fire, Pre-Alarm/Alert, Fault, Reset/Isolate. The Reset/Isolate push button operates as a press to reset and press and hold to isolate. afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
Conformance criteria and evaluation
The VESDA®, aspirated smoke detector system has been evaluated and verified as conforming with the relevant requirements of the following criteria.
1. Australian Standard AS 1603.8-1996, 'Automatic fire detection and alarm systems - Multi-point aspirated smoke detectors'.
Certification/listing is subject to ActivFire Scheme terms and conditions as applicable to the designated registrant and supplier.
Limitations/conditions of conformance
Limitations/conditions of conformance, where identified on this Product Listing Data Sheet, are derived from qualifications within the report of the testing agency and/or other related technical documentation. It is recommended that all details with respect to design, assembly and installation restrictions should be checked against the designated supplier's/manufacturer's current technical manual/data sheets and the requirements of the Authority having Jurisdiction.
Specified limitations/conditions, determined from the evaluation for conformity, include the following. i.
The components are to be installed in accordance with the manufacturer's instructions contained in the System
Design Manual and subsequent addendums and amendments. ii. iii.
The power source meets the requirements of the power supply specifications contained in the Installation Guide.
The Vision Systems VESDA
®
LaserPLUS
™
Model VPS-101 Single Zone Intelligent Power Supply (with
•
VESDAnet); can only be installed with a shielded VESDAnet cable Belden type 9841 (or equivalent ) as specified in the cabling chapter of the VESDA
®
LaserPLUS
™
System Design Manual V2.2.
• can only be installed adjacent to fault relay monitoring equipment and also adjacent to equipment being powered by 24 volts as the 24 volt power line and fault signal line were not tested in the frequency range 0.15-
100 MHz.
Technical specification
The following details are a representative extract of the technical specification for the VESDA®, aspirated smoke detector system and may be subject to change. Complete and current details should be determined from the designated supplier's/manufacturer's technical manual/data sheets.
Ambient temperature range:
Sampled temperature range:
Relative humidity:
Sensitivity of detector
Coverage of detector:
Signal outputs:
0°C to 39°C
-10°C to 60°C
10% to 95%, non-condensing
0.005% to 20 % obscuration/metre ±0.005% or ±10% of reading
(whichever is greater)
2000 square metres maximum
7 Relay outputs NC/NO
12 Relay outputs NC/NO. (except for Fire 1 and Urgent Faults that are NO/NC)
2 Adc @ 30 Vdc
Latched, Non-latched, or Pulsed
(Programmable)
Dimensions (W x H x D):
Detector:
Remote:
19 inch Sub rack:
Module weight:
Detector with display &
350 mm x 225 mm x 125 mm
140 mm x 150 mm x 90 mm
19 inch x 3U x 4 inch
Remote with display
Operating voltage range:
Current consumption:
1 kg
18 Vdc to 30 Vdc
Dependant upon supply voltage and modules operating within the system.
Model VLC-505 (VN) LaserCOMPACT™ Detector
Model VLC-500 (RO) LaserCOMPACT™ Detector afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
Sensitivity range:
Threshold setting range:
Alert:
Pre-alarm:
Fire:
Supply voltage:
Current consumption (quiescent):
Current consumption (alarm):
Power consumption:
Operating temperature:
Detector ambient:
Sampled air:
Humidity:
Sampling network:
Maximum area of coverage:
0.005 to 20% obscuration/metre
0.005% to 1.990% obscuration/metre
0.010% to 1.995% obscuration/metre
0.015% to 20% obscuration/metre
18 Vdc to 30 Vdc
170 mA @ 24 Vdc quiescent plus 20 mA (typical)
4.0 watts quiescent plus 0.5 watt in alarm
-10°C to 39°C
-20°C to 60°C
10 to 95% RH, non condensing
500 m
2
“T” pipe arrangement: 100 m (ie. 2 x 50 m) - maximum aggregate length
Model VPS-101 Single Zone Intelligent Power Supply (with VESDAnet)
Nominal output voltage:
24 Vdc
Current limit fuse rating:
Line regulation @ I
L
= 1 A
Load regulation @ 254 Vac supply:
Worst case ripple @ 216 Vac supply:
Battery Charger:
Battery charge voltage setting:
Circuit current limit:
Current limit device rating:
Line regulation @ I
L
= 0 A:
Maximum battery charger current (I bat
):
Power supply Standby consumption (I
S
):
Manufacturer's nominated
2 A
0.8 %
1.2 %
11 mV p-p
26.8 Vdc
3.4 A
10 A
3.7 %
0.75 A @ 21.8 Vdc
0.38-0.45 A @ 24 Vdc afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
Supplementary information
Manufacturer's system specifications:
The following information is extracted from Vision Systems Products Division marketing specification document: -
VESDA
®
LaserPLUS™ Product Numbering Specification MKT-SPC-003-00
BUNDLE NUMBERS
The bundle number represents the physical configuration of a LaserPLUS™ product. It does not include the software (VESDAnet) version information in this release.
1. General format
Field
1
Use Series
Digits values
V
2
Box type
LP
LaserPLUS
PS
PSL
3
LS
LaserScanner
S
W
Software Pkg
RT
Remote
HH
Hand Held
SR
19” sub-rack
HX
HLI
All non specified characters are reserved for
future use
Dash
-
Dependant on Box type
(See definitions below)
Dash
-
Variations
(See Variations
Table) afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
2. For Box type LP (VLP Detector)
Field
Use Series
Box type
Chars values
Dash
1 2 1
V LP -
Dependant on Box type
5
0..9
Dash
1
Variations
3
Field
Use values
5 6 7 8 9
Position 1 Position 2 Position 3 Mounting Standard/Custom
0 Blank plate, non- 0 Blank plate
EMC,
VESDA logo & 2 Display
7-relay HTC7 3 <not used>
1 <not used>
1 Programmer
4 Scanner Display
1 Programmer
2 Display
3 <not used>
4 Scanner Display
0 Normal
1 Inverted
0 Standard
1 [Custom]
2 used>
3 used>
4
EMC,
VESDA logo &
FOK LEDs &
7-relay
5 used>
6 used>
7 used>
Notes:
• HTC is Head Termination Card, FOK LEDs is Fire 1 Alarm & OK LEDs.
• Items marked in brackets eg. [Custom] are proposed and not yet available.
• Eg. VLP-01200-G00 is a LaserPLUS™ Detector with blank plate in left hand position, programmer in centre position, and display in right most position, set up for Generic with English language display.
• Position 1, 2, 3 (fields 5,6 & 7) refers to the left most, centre, and right most panel locations of the front cover of the LaserPLUS™ unit.
• The mounting options are normal mounted or inverted mounted. The recessed mounting kit is available as part
VSP-01100-G00.
• Eg. VLP-012 is a LaserPLUS™ Detector with blank plate in left hand position, programmer in centre position, and display in right most position, set up for Generic with English language display. (truncated format)
• Eg. VLP-410 is a LaserPLUS™ Detector with blank plate in left hand position with Fire 1 & OK LEDs, programmer in centre position, and blank plate in right most position, set up for Generic with English language display. (truncated format)
• Housing more than one display or programmer in a detector is NOT allowed, to prevent confusion with end users afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
3. For Box type LS (VLS Scanner)
Field
Use Series
Box type
Dash
Chars
1 2 1 values V LS -
Field
Use values
Position 1
0 Blank plate, non-EMC, with
Position 2
0 Blank plate
1 Programmer
FAS 7-relay HTC7
1 <reserved>
3 <not used>
4 Scanner
3 FD 12-relay HTC12 or
Display
7-relay
Blank plate, non-
EMC, with VESDA logo & FOK LEDs plus:
Dependant on Box type
5
0..9
Position 3
0 Blank plate
1 Programmer
2 Display
3 <not used>
4 Scanner
Display
7-relay
Dash
1
Variations
3
Mounting
0 Normal
1 Inverted
Standard/Custom
0 Standard
1 [Custom]
Notes:
• FAS is First Alarm Sector Scanner, FD is Four-in-one Detector Scanner
• HTC is Head Termination Card, FOK LEDs is Fire 1 Alarm & OK LEDs
• Items marked in brackets eg. [Custom] are proposed and not yet available.
• Eg. VLS-30401-G00 is a LaserPLUS™ FD Scanner with blank plate in left hand position with 12-relay HTC, blank plate in centre position, and scanner display in right most position, set up for Generic use with English language display, and incorporating some customised features specific to that customer order. Details of the customisation would be found in file notes associated with the customer order.
• Position 1, 2, 3 (fields 5,6 & 7) refers to the left most, centre, and right most panel locations of the front cover of the LaserPLUS™ unit.
• The mounting options are normal mounted or inverted mounted The recessed mounting kit is available as part
VSP-017.
• Eg. VLS-610 is a LaserPLUS™ FD Scanner with blank plate with Fire 1 & OK LEDs in left hand position with 7relay HTC, programmer in centre position, and blank plate in right most position, set up for Generic with English language display. (truncated format)
• Housing more than one display or programmer in a detector is NOT allowed, to prevent confusion with end users. afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
4. For Box Type PS (PSL Power Supply)
Field
Use Series
Box type
Chars
Dash
1 2 1 values
V PS -
Field
Use values
Dependant on Box type
5
0..9
Dash
1
Variations
3 m
0 <not used> 0 85-265 Vac Mains 0 No VESDAnet 0 Surface (Norm)
0
Standard
1 Single Zone 1
2 <not used>
<reserved> 1 VESDAnet 1
2
<not allowed>
<not allowed>
1 [Custom]
3 <not used>
4 <reserved>
3 <not allowed>
Notes:
• Eg. VPS-10100-G00 is a LaserPLUS™ Intelligent Power Supply, AC Mains input (85-265 Vac), with VESDAnet capability, capable of supporting a single zone (detector) of type Generic English.
• Eg. VPS-100 is a LaserPLUS™ Intelligent Power Supply, AC Mains input (85-265 Vac), without VESDAnet capability, capable of supporting a single zone (detector) of type Generic English. (truncated format)
5. For Box type HH (Hand-Held)
Field
Use Series
Box type
Chars
Dash
1 2 1 values V HH -
Dependant on Box type
5
0..9
Field
Use values
Dash
1
Variations
3
Remote Type Reserved
1
Reserved Reserved Standard/Custom used> always 0 always 0 Standard
Notes:
• Items marked in brackets eg. [Custom] are proposed and not yet available.
• Eg. VHH-10000-G00 is a Hand Held Programmer module, Generic English
• Eg. VHH-100 is a Hand Held Programmer module, Generic English (truncated format) afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
6. For Box type RT (Remote mounting)
Field
Use Series
Box type
Chars
Dash
1 2 1
values
V RT -
Dependant on Box type
3
0..9
Dash
Variations
1 3
Field
Use values
5 6 7 8 9
Remote Type Reserved
0 Normal 0 Standard
1 Programmer with
0 always
2 <not used>
4 Scanner Display with
RTC7
5 RTC7 & DRP only
(7-relays only)
6 Display with RTC0
(no relays)
7 Scanner Display with
RTC0 (no relays)
8 Scanner Display with
RTC12
9 RTC12 & DRP only
(12-relays only)
Notes:
• RTC is the Remote Termination Card
• DRP is the Display & Relay Processor Card
• Items marked in brackets eg. [Custom] are proposed and not yet available.
• Eg. VRT-40000-G00 is a Scanner Display with relays (7-relay RTC) configured for normal mounting, Generic
English.
• Eg. VRT-10000-G00 is a Programmer without relays configured for normal mounting, Generic English.
• Eg. VRT-10001-G00 is a Programmer without relays configured for normal mounting, Generic English, with some customer specific customised features.
• Eg. VRT-51000-G00 is a remote relay box (12-relay RTC) with relays
• Eg. VRT-000 is an empty remote box with cover, but no blank plate (truncated version)
• Although the remote mounting box can only be ordered in normal orientation ONLY, inverted orientation is available at the time of installation, since cover must be removed to install mounting box. The recess mounted kit is available as Part No. VSP-01200-G00.
• Eg. VRT-400 is a Scanner Display with relays (7-relay RTC) configured for normal mounting, Generic English.
(truncated format)
• Eg. VRT-210 is a Display with relays (12-relay RTC) configured for normal mounting, Generic English.
(truncated format) afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
7. For Box type SR (19” sub rack)
Field
Use Series
Box type
Chars
Dash
1 2 1 values
V SR -
Dependant on Box type
5
0..9
Dash
1
Variations
3
Field
Use Position 1 Position 2 Position 3 Position 4 Standard/ Custom values 0 EMC Blank plate 0 EMC Blank plate 0 EMC Blank plate 0 EMC Blank plate 0 19" Standard
1 Programmer
RTC0 (no relays) RTC0 (no relays) RTC0 (no relays) RTC0 (no relays)
1 [Custom]
2 Display with RTC7 2 Display with RTC7 2 Display with RTC7 2 Display with RTC7
3 Socket
4 Scanner with RTC7
5 RTC7 & DRP only with RTC7
5 RTC7 & DRP only with RTC7
5 RTC7 & DRP only with RTC7
5 RTC7 & DRP only
(7-relays only)
6 Display with RTC0
(no relays)
7 Scanner with RTC0 (no relays)
8 Scanner
(7-relays only)
6 Display with RTC0
(no relays)
7 Scanner Display with RTC0 (no relays)
(7-relays only)
6 Display with RTC0
(no relays)
7 Scanner Display with RTC0 (no relays)
(7-relays only)
6 Display with RTC0
(no relays)
7 Scanner Display with RTC0 (no relays) with RTC12]
9 RTC12 & DRP only with RTC12]
9 RTC12 & DRP only with RTC12]
9 RTC12 & DRP only with RTC12]
9 RTC12 & DRP only
(12-relays only) (12-relays only) (12-relays only) (12-relays only)
A Programmer with no A Programmer with no A Programmer with no A Programmer with no
RTC (Sharing) RTC (Sharing) RTC (Sharing) RTC (Sharing)
B Display with no RTC B Display with no RTC B Display with no RTC B Display with no RTC
(Sharing) (Sharing) (Sharing) (Sharing)
C Scanner Display, no C Scanner Display, no C Scanner Display, no C Scanner Display, no
RTC (Sharing) RTC (Sharing) RTC (Sharing) RTC (Sharing)
D <reserved> D <reserved>
E <reserved>
F <reserved>
E <reserved>
F <reserved>
E <reserved> E <reserved>
Notes:
• Definitions as follows:
• RTC
= Relay Termination Card
• RTC0 = Relay Termination Card with no relays fitted
• RTC7 = 7-Relay Relay Termination Card
• RTC12 = 12-Relay Relay Termination Card
• DRP
= Display & Relay Processor Card
• Sharing = Module in this position shares adjacent RTC by daisy-chain connection (if possible).
• Use of any kind of RTC (RTC0, RTC7 and RTC12) requires connection to DRP either by itself or part of Display or Scanner Display. The DRP provides the intelligence & VESDAnet addressing.
• Items marked in brackets eg. [Custom] are proposed and not yet available.
• The 19” sub-rack can be fitted with 4 modules. The left most is position 1, & the right most is position 4.
• Eg. VSR-01260-G00 is a 19” sub rack fitted with Blank plate in position 1, Programmer in position 2, Display with relays in position 3, and Display without relays in position 4, all with Generic English display coding.
• Eg. VSR-0126 is a 19” sub rack fitted with Blank plate in position 1, Programmer in position 2, Display with relays in position 3, and Display without relays in position 4, all with Generic English display coding. (truncated format) afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
8. For Box type HX (HLI)
Field
Use Series
Box type
Chars
Dash
1 2 1 values
V HX -
Dependant on Box type
5
0..9
Dash
1
Variations
3
Field 5 6 7
Use values
Access Port
Protocol Stack Custom ID
0 Standard / NP
8
Physical Interface
Access Port
9
Custom ID
0 Standard
Protocol Stack
00 No Protocol (Accessory item)
01 PCLink HLI Stop’n’Go
02 PCLink HLI Sliding Windows
03..99 Reserved for future
1 Even Parity
2 .. 9 [Custom ID]
Physical Interface
0 PCLink RS232
1..8 Reserved for future
9 Modem Cable
1..9 [Custom ID]
Notes:
Items marked in brackets eg. [Open Protocol] are proposed and not yet available.
Eg. VHX-01000-G00 is a HLI box loaded with PCLink HLI Stop’n’Go protocol with No Parity, and RS232
Asynchronous Serial interface on the Access port side, configured for Generic English.
Eg. VHX-02000 is a HLI box loaded with PCLink HLI Sliding Windows protocol with No Parity, and RS232
Asynchronous Serial interface on the Access port side, configured for Generic English.
Eg. VHX-00090 is a standard modem cable only.
9. For Box type LC (LaserCOMPACT™ Detector)
Field
Use Series Box type
Chars
Dash
1 2 1 values
V LC -
Field
Use values
Position 1
EMC
2
Position 2
200 <reserved for future use>
300 <reserved for future use>
400 <reserved for future use>
500 RO Relays Only 500 m
2
VESDAnet 500 m
2
600 <reserved for future use>
700 <reserved for future use>
800 Rx 200 m
2
805 Rx 500 m
2
900 E700R 2000 m
2
Dependant on Box type
5
0..9
Position 3
Dash
1
Variations
3
Mounting Standard/Custom
0 Standard
1 inverted 1 [Custom]
Notes:
Items marked in brackets eg. [Custom] are proposed an not yet available
Eg. VLC-100 is an EMC
2
OEM variant of the LaserCOMPACT™ Detector
Eg. VLC-50000-G00 is a LaserCOMPACT Detector, Relays only outputs, set up for Generic English.
The mounting options are normal mounted or inverted mounted.
The LaserCOMPACT™ recessed mounting kit is available as part VSP-010
Eg. VLC-505 is a LaserCOMPACT™ Detector, with VESDAnet interface, and set up for Generic English.
(truncated format)
Eg. VLC-90001-133 is an E700R variant of the LaserCOMPACT™ Detector, with customisation as specified in
Variations Specifications #133. afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.
afp - 1083
Version: ....5 ....29-Jul-2009
10. For Box type SW (Software Package)
Field
Use
Series
Box type
Dash
Chars 1
Dependant on Box type
Dash
Variations
3 values V
Field
Use Software Custom Unique ID values 001 ASPIRE - DOS 1.95 (superseded by VSW-002) 00
002 ASPIRE - WIN (Win-95 & 3.11 (superseded by VSW-202) [01..99] Custom Software
003 VConfig Basic (Win-3.1) {formerly free PC-configurator}
004 VConfig Basic (Win-95) {formerly free PC-configurator}
005 VConfig Pro (Win-95) {enhanced & licensed software}
006 <reserved>
007 VSM III (Win-95)
008 <reserved>
009 <reserved>
010 <reserved>
011 Demo Disk (AUS)
012 .. 999 Reserved for future use
Notes:
Items marked in brackets eg. [VesdaCAD] are proposed and not yet available.
Eg. VSW-00100-G00 is ASPIRE for DOS software, Generic English (latest version).
Eg. VSW-00732-G00 is a Special custom VSM III software package number 32, Generic English.
Eg. VSW-00500-G00 is a Downloader software package, Generic English.
Eg. VSW-00501-G00 is a VConfig Pro (Win-95) package number 01, Generic English.
Eg. VSW-002 is ASPIRE for Win-95/3.11 software, Generic English (latest version, truncated format).
Eg. VSW-00200-B is ASPIRE for Win-95/3.11 software (Beta version), Generic English (latest version).
Eg. VSW-00700-A is VSM III for Win-95 (Alpha version) software, Generic English (latest version).
11. Truncating
Where specialised or customised VLP components are not required the variation MAY be omitted. Fields which may be truncated MUST have their default value or zero and lie between Field 8 and Field 13. Specification of fields 1 through 7 is mandatory.
For example:
VLP-012 is translated as VLP-01200-G00
VLP-01200
VLP-0121
VLP-01201 is also translated as VLP-01200-G00 is translated at the generic version inverted is a standard unit with specific instructions FOR THIS ORDER ONLY
VLP-01200-B03 is a customised version with specific badging
VLP-01201-B03 is the same customised version with additional requirements
VPS-101
VRT-201 is a standard PSL i.e. VPS-10100-G00 is the standard remote display - VRT-20100-G00
VSP-011 is the LaserPLUS™ Recess Mounting Kit ie. VSP-01100-G00
12. Software version
The software version refers to the Version and update number for VESDAnet. This number consists of three parts, the major and minor numbers, and the patch level. In general two LaserPLUS™ units linked together with differing minor numbers will operate without error. Two LaserPLUS™ units linked together with differing major numbers will generate a system fault.
Software version is always represented as three groups of 2 digit numbers separated by dots:
<2 major number digits>.<2 minor number digits>.<2 patch level digits> afp1083.lds
† Listing may be subject to amendment, suspension or withdrawal at any time. Always verify current status.