Panduit CFAPPBL1A patch panel accessory Installation Instructions
Panduit FMT1A is a rack-mount angled fiber cassette enclosure designed to provide a compact and organized solution for fiber optic cable management and splicing. With its versatile design, it accommodates up to 4 fiber adapter panels (FAPs), allowing for easy integration of various fiber optic components and providing flexibility for future expansion. The FMT1A is well-suited for applications requiring a high-density fiber optic connection point, such as data centers, telecommunication facilities, and enterprise networks.
Advertisement
Advertisement
© Panduit Corp. 2009
O
PTICOM
Q
UICK
N
ET
Rack Mount Angled Fiber
Cassette Enclosures and Patch Panels
Part Numbers: FMT1A, FMT2A, CFAPPBL1A, CFAPPBL2A
INSTALLATION INSTRUCTIONS FS007A
FMT2A
FMT1A
CFAPPBL1A
(sold separately) CFAPPBL2A
(sold separately)
CONTENTS: (#) indicates FMT2A quantity
1 - ENCLOSURE
1 (2) - #10-32 x 5/16" SCREWS
4 (5) - #10-32 HEX NUTS
4 - #12-24 x 1/2" SCREWS
4 - M6 x 1 SCREWS
3 - #10 FLAT WASHERS
1 (2) - CABLE ENTRY GROMMET(S)
1 (2) - STRAIN RELIEF BRACKET(S)
2 - ADHESIVE BEVEL ENTRY CLIPS
2 - ADHESIVE BACKED MOUNTS
4 - T AK -T Y s (6" pcs.)
2 - SLACK SPOOLS (FMS1 or FMS2)
1 - CAUTION LABEL
1 - LASER WARNING LABEL
WARNING: UNMATED CONNECTORS MAY EMIT INVISIBLE LASER RADIATION. DO NOT LOOK DIRECTLY INTO THE END OF THE
CONNECTOR. DO NOT INSPECT WITH MAGNIFYING DEVICES. MAINTAIN CAP ON UNMATED CONNECTORS.
CAUTION:
Fiber optic cable is sensitive to excessive pulling, bending and crushing forces. Consult the manufacturer’s cable specification sheet for the specific cable in use.
Follow TIA/EIA-568A, 569, 606, and 607 installation guidelines where applicable.
Care should be taken when opening and closing fully loaded drawer in order to protect fiber components.
ASSEMBLY VIEW
showing Fiber Adapter Panels (FAPs) - sold separately
Cover (field removable)
Fiber Adapter Panels (FAPs):
Up to 4 for FMT1A
Up to 8 for FMT2A
(sold separately) Trunk or Interconnect
Cable Entry Grommet
PG16 Gland
(customer supplied)
Angled Patch Panel
(CFAPPBL1A shown)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 8
Strain Relief Bracket
Enclosure
© Panduit Corp. 2009
Preparation and Rack Mounting
INSTALLATION INSTRUCTIONS
Cover
#10-32 screw
FS007A
To remove the cover, unscrew the #10-32 screw, slide the cover back, lift up and off.
Figure 1
Attach the angled patch panel to the enclsoure with (2) #10 flat washers and (2) #10-32 hex nuts.
#10-32 hex nuts and
#10 flat washers
Figure 2
Determine where the cable will enter the enclosure. Carefully remove the knock-out so as not to damage the surrounding sheet metal.
DO NOT install the grommet at this stage.
Grommet will be installed after the enclosure is mounted to the rack.
Figure 3
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 8
© Panduit Corp. 2009
Mounting Brackets
(2) #12-24 x 1/2" screws
Repeat for other side.
Angled Patch
Panel
(CFAPPBL1A shown)
INSTALLATION INSTRUCTIONS FS007A
Place the mounting brackets at the desired position on the rack.
Figure 4A
Mount the enclosure to the rack using
(4) #12-24 x 1/2" screws.
Use (4) M6 x 1 screws if mounting to a metric rack.
Figure 4B
Figure 4C
Angled patch panels may be mounted directly to the rack without an enclosure. Place at the desired position on the rack and secure with
(4) #12-24 x 1/2" screws.
Use (4) M6 x 1 screws if mounting to a metric rack.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 8
© Panduit Corp. 2009
Grommet Cutting Diagram
INSTALLATION INSTRUCTIONS
Cut out the small circle for 1" dia. innerduct
Cut the straight lines for smaller bundle sizes
FS007A
After the enclosure is mounted to the rack, determine the size of the innerduct (if any) that will be used to bring the cable into the enclosure.
Prepare grommet according to the proper cutting diagram to the left.
Cut out the small circle for 1-1/4" dia. innerduct
Cut out the large circle for 1-1/2" dia. innerduct
Cut the straight lines when not using any innerduct
Figure 5A
#10-32 hex nut
#10 flat washer
Grommet
Install prepared grommet.
Install (1) #10 flat washer and (1) #10-32 hex nut over the stud on the enclosure as shown. This will be used to secure the strength member from the cable.
Figure 5B
#10-32 x 5/16" screw
Install the strain relief bracket near where the cable will enter the enclosure. Secure with
#10-32 x 5/16" screw and #10-32 hex nut.
#10-32 hex nut
Strain Relief
Bracket
Figure 6
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 8
© Panduit Corp. 2009
INSTALLATION INSTRUCTIONS
Q UICK N ET
Cassette Installation -
sold separately
Cassettes: Up to 3 for FMT1A
Up to 6 for FMT2A
FS007A
Insert Q UICK N ET Pre-Terminated Fiber Optic
Cassettes into the enclosure as shown. Once mounted, fully seat NyLatch fasteners to secure the cassettes.
A Fiber Access Blanking Panel (FAPB) may be installed in the open bay to close.
FAPB
(sold separately)
NyLatch fasteners
Adhesive Bevel
Entry Clips
(Note location and position of clips)
Figure 7A
Grommet
Fixed
T AK -T Y
Route fiber through the cable entry grommet to the fiber cassettes as shown.
Use T AK -T Y s to secure fiber cords at cable entry location and other points as shown.
Free Floating
T AK -T Y s
Figure 7B
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 8
© Panduit Corp. 2009
INSTALLATION INSTRUCTIONS
Field Termination or Pre-Terminated Trunk Installation
Slack Spools
FMS1 or FMS2
FS007A
Using adhesive backing, place slack spools in enclosure, note spool orientation. Approximate location is 5" off back wall with spools 9" apart centered in the enclosure.
Position FAPs into the angled patch panel as shown. Once mounted, fully seat NyLatch fasteners to secure FAPs.
Fiber Adapter Panels (FAPs):
Up to 4 for FMT1A
Up to 8 for FMT2A
Figure 8A
Individual fiber break out point
(See detail)
Strength Member
9"
[228mm]
5"
[127mm]
Adhesive Backed
Mount with T AK -T Y
Grommet
Route fiber through the cable entry grommet as shown. Use enough cable length to ensure one complete loop of individual fibers around slack spools. Attach the strength member of the cable around the #10-32 stud, securing with the
#10 flat washer and #10-32 hex nut previously installed.
Use T AK -T Y s to secure fiber cords at the cable entry location and other points as shown.
cable jacket individual fiber
Fixed T AK -T Y
1.0"
[2.54mm]
Fiber Break out Detail
Be sure adhesive backed mount is positioned to secure the jacketed trunk cable. DO NOT clip individual 900µm buffered fibers.
Figure 8B
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 8
© Panduit Corp. 2009
INSTALLATION INSTRUCTIONS
Fiber Optic Splice Module (FOSM) Installation -
sold separately
FOSM: Up to 4 for FMT1A, Up to 8 for FMT2A
Break off side latches on top module only
(See Note)
FS007A
Recommended position for FOSM is 3" max from enclosure back wall.
Place first FOSM into the enclosure using double stick tape (not included). Note orientation. Remaining FOSMs are stacked on top of each other and snap in place.
Note: If 4 FOSMs are to be installed in the
FMT1A, the side latches on the top module must be broken off to place the cover back on the enclosure.
Position FAPs into the angled patch panel as shown. Once mounted, fully seat NyLatch fasteners to secure FAPs.
Fiber Adapter Panels (FAPs):
Up to 4 for FMT1A, Up to 8 for FMT2A.
Individual Fiber
Break out Point
(See fiber break out detail on page 6)
Figure 9A
Adhesive Bevel
Entry Clip
(Note location and position of clips)
Grommet
3" MAX
76.2mm
Route fiber through cable entry grommet as shown. Use enough cable length to ensure one complete loop (approx. 45" [1.15m]) of individual fibers around FOSM slack spools.
Route 900µm buffered fiber from the trunk cable and splice to pigtail per instructions in
FS001*, “O PTICOM Fiber Optic Splice Module
Installation Instructions.”
Use T AK -T Y s to secure fiber cords at cable entry location and other points as shown.
Fixed
T AK -T Y
Figure 9B
* Denotes revision letter.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 8
© Panduit Corp. 2009
INSTALLATION INSTRUCTIONS
FST6 Fiber Splice Tray Installation -
sold separately
Fiber Splice Tray
3" MAX
[76.2mm]
FS007A
Position Splice Tray as shown. Reference
CM92*, installation instructions for Fiber
Splice Tray.
FSC24 Fiber Splice Holder Installation -
sold separately
Fiber Splice Holder
Figure 11
Reference Figure 8B for slack spool positioning.
See CM307*, installation instructions for fiber splice holder.
* Denotes revision letter.
For Instructions in Local Languages and Technical Support: www.panduit.com/resources/install_maintain.asp
Figure 12 www.panduit.com
Page 8 of 8
E-mail: [email protected]
Fax:
(708) 444-6448
Download
Advertisement